Beruflich Dokumente
Kultur Dokumente
Presentations for
Electrical Engineers
R. K. Sinha
www.power-publishers.com
1
Copyright: R. K. Sinha
Price: `300
Printed on recycled paper. No trees were cut for the production of this book.
All rights reserved. No part of this publication may be reproduced, stored in a
retrieval system, or transmitted in any form or by any means electronic,
mechanical, photocopying, recording or otherwise without the prior
permission of the publisher and author. The views expressed in this book are
those of the author. The publisher is not in any way responsible for the views
expressed in this book. All legal actions are subject to the jurisdictions of
courts of Kolkata, India.
2
Dedication
R K Sinha
3
Foreword
4
INDEX OF ARTICLES
Sl. No. Title
1 Area Classification & selection of
Electrical equipments 08
2 Circuit Breakers 17
3 Earthing 24
4 Earth Leakage Currents & ELCBs 33
5 Electric Shock 39
6 Electrical Engineering Softwares 52
7 Fault Levels 60
8 Fuses 66
9 Maintenance Management 73
10 Electrical Motors 79
11 Offshore Electrical System 90
12 Partial Discharge Analysis 96
13 Power Factor Improvement 100
14 Relay Coordination 106
15 Solar Photo - Voltaic 112
16 Static Electricity 117
17 Safety against Arc Flash 124
18 Safe Usage of Multimeters 130
19 Variable Frequency Drives 134
INDEX OF SLIDES
Sl. No. Title
1 Induction Motors 138
2 Area Classification 150
3 Cables 168
4 Concepts of Earthing 178
5 ELCB 184
6 Electric Shock 191
7 Generator Protections 204
8 Harmonics 212
9 Lighting 219
10 Motor Protections 233
11 Partial Discharge Analysis 248
12 Power Factor Improvement 250
13 Relay Coordination 258
14 Static Electricity 264
15 Arc Flash 280
5
6
PART 1
ARTICLES
7
AREA CLASSIFICATION AND SELECTION OF
ELECTRICAL EQUIPMENTS
SOME DEFINITIONS
We know that for a fire to take place three things are essential :
1. Presence of fuel such as flammable gas
2. Presence of oxygen
3. Presence of heat ie. sufficient ignition energy to ignite
the flammable mixture
8
• Ignition Temperature : The lowest temperature at which
ignition occurs in a mixture of explosive gas and air.
• Flash Point : The temperature at which the liquid gives
so much vapour,that this vapour,when mixed with
air,forms an ignitable mixture.
• Explosive Limits : The extreme values for the
concentration of a flammable gas or air under
atmospheric conditions,which can be ignited by an
electric arc or spark.
STANDARDS
Most countries have developed their own standards and codes
for Area Classification but internationally two main standards
are being followed.These are :
• The North American standards produced by the API
and NFPA.
• The International Electrotechnical Commission (IEC)
standards.
• API 500 is used in the United States whereas IEC 79 is
popular in Europe.
The North American API RP 500 defines the above two aspects
as Divisions and Gas Groups whereas in IEC 79 they are
termed as Zones and Gas Groups.
9
Metallic dust such as aluminium or magnesium have several
dsangerous properties.
(i) They are electrically conductive.
(ii) They can burn very violently even when not finely
distributed in air.
(iii) When finely distributed in air they can be violently
explosive.
CLASS 3 : Fibers or flyings that are easily ignitable but are not
apt to be suspended in air in such amounts to produce ignitable
mixtures.
Example : Rayon, Nylon, Cotton, Sawdust etc.
DIVISIONS
DIVISION 1A Hazardous concentrations exist continuously
or intermittently under normal operating
conditions.
DIVISION 1B Hazardous concentrations may exist
frequently due to leakage.
DIVISION 1C The breakage or faulty operations of
equipment or process which might release
hazardous concentrations of flammable gases
and might also cause simultaneous failure of
electrical equipments.
DIVISION 2A Hazardous volatile liquids,vapous or gases
are normally confined within enclosed
containers or closed systems from which they
can escape only in the case of accidental
rupture or breakdown.
DIVISION 2B Hazardous concentration are normally
prevented by positive ventilation but might
become hazardous through failure of the
ventilation system.
DIVISION 2C Hazardous concentrations of the gases or
vapours might occasionally be communicated
because of their proximity to Division 1 areas.
GAS GROUPS
GROUP A Atmospheres containing acetylene.
GROUP B Atmospheres containing hydrogen
GROUP C Atmospheres containing ethyl ether
vapours,ethylene or equivalent gases
GROUP D Atmospheres containing
gasoline,naptha,propane,acetone,natural gas or
equivalent
10
EUROPEAN METHOD
ZONES
ZONE 0 An area in which hazardous
atmosphere is continuously
present.In oil industry such a
condition exists in confined
spaces, such as the vapour
space of closed process
vessels,storage tanks etc.
ZONE 1 An area where explosive gas
and air mixture is continuously
present for a long period or is
likely to occur in normal
operation.
ZONE 2 An area in which explosive gas
and air mixture is likely to
occur only under abnormal
operating conditions. For
example : Gas Turbine
enclosures.
NON-HAZARDOUS AREA Areas not falling under Zone
0,1 or 2 are considered as safe
areas. Oil and gas pipelines
laid in the open outside
hazardous areas and that do
not have any flange
joints,which cannot become
loose, are considered safe
area.
GAS GROUPS
GROUP 1 Covers gases produced in coal
mines (mainly fire damp
methane).
GROUP 2A Atmospheres containing
acetone, ethane, hexane, ethyl
acetate, ammonia, benzene,
butane, diesel, propane etc.
GROUP 2B Atmospheres containing
ethylene, town gas, ethyl ether
etc.
GROUP 2C Atmospheres containing
hydrogen, acetylene, ethyl
nitrate, carbon disulphide.
11
In addition to the zones ( defining probability of occurrence of
flammable mixture) and Gas Groups ( defining type of
flammable gas) , the European Standard also has a
Temperature Classification .
• The external surfaces of explosion proof equipment
must not exceed the temperature whereby they may
be liable to become source of ignition for the
surrounding atmosphere.
• According to ignition temperature gases and vapours
are divided into six temperature classes as follows :
T1 450 deg C
T2 300 deg C
T3 200 deg C
T4 135 deg C
T5 100 deg C
T6 85 deg C
The ignition temperature of natural gas is approximately
480 deg Celsius.
12
the interconnecting
wiring,exposed to a potentially
explosive atmosphere, to a
level below that which can
cause ignition by either
sparking or heating
effects.Devices whose
electrical parameters do not
exceed any of the values 1.2
V,100mA,20 J or 25 mW.
Type ‘p’ (Pressurized) A method of protection using
the pressure of a protective
gas to prevent the ingress of
an external flammable
atmosphere to a space which
may contain a source of
ignition.
Type ‘n’ (Non-sparking) A type of protection applied to
an electrical apparatus such
that,in normal operation,it is
not capable of igniting a
surrounding explosive
atmosphere , and a fault
capable of causing ignition is
not likely to occur.
Type ‘o’ (Oil Immersed) A method of protection where
the enclosure is made safe by
oil-immersion in the sense that
flammable gases or vapours
above the oil or outside the
enclosure will not be ignited.
Type ‘q’ (Sand filled) A method of protection where
the enclosure of electrical
apparatus is filled with a
powdery material such that, if
an arc occurs, it will not be
able to ignite the external
flammable atmosphere.
Type ‘s’ (Special) Special methods of protection
which may be a combination of
above methods
13
SELECTION OF ELECTRICAL EQUIPMENTS
Zone 0 Only Type ‘ia’ (Intrinsically safe)
and some special type ‘s’
allowed.
Zone 1 Apparatus suitable for Zone 0
and Intrinsically Safe
‘ib’,Flameproof (‘d’),Oil Immersed
(‘o’),Pressurised (‘p’), Sand Filled
(‘q’).
Zone 2 Apparatus for Zone 0 & 1 plus
Increased Safety (‘e’),Non-
sparking (‘n’) allowed.
INGRESS PROTECTION
To complete the subject it is also worthwhile to touch upon the
topic of Ingress Protection for enclosures of electrical
equipments and switchgear. Ingress protection defines the level
of protection of the enclosure against the ingress of solids and
liquids. It is denoted as IP followed by two digits eg. IP 55. Here
the first digit specifies protection against ingress of solids
whereas the second digit specifies protection against ingress of
liquids.The following tables provides the details :
SOLIDS
0 No protection
1 Protected against solid objects
upto 50 mm (eg. Hands)
2 Protected against solid objects
upto 12.5 mm (eg. Fingers)
3 Protected against solid objects
upto 2.5 mm (eg. Tools)
4 Protected against solid objects
over 1 mm (eg. Wires)
5 Protected against dust (No
harmful deposits)
6 Totally protected against dust.
14
LIQUIDS
0 No protection
1 Protected against vertically
falling drops of water
2 Protected against water spray
upto 15 deg from the vertical
3 Protected against water spray
upto 60 deg from the vertical
4 Protected against water spray
from all directions
5 Protected against water jets
from all directions
6 Protected against strong water
jets from all directions
7 Protected against immersion
upto 1 Mtr depth.
8 Protected against lengthy
immersion under pressure.
15
RP 14 Electrical Systems for Offshore Petroleum Facilities.
F
IEC Classification of Hazardous Areas
79-10
IS Indian Standard for Classification of Hazardous Areas
5572
16
CIRCUIT BREAKERS
17
called the “Transient State’.The transient state lasts for a few
cycles.After the transient state,’Steady State’ is reached.During
the steady state the RMS value of the short-circuit current
remains almost constant.
THE CIRCUIT BREAKERS OPERATE DURING THE
TRANSIENT STATE.
18
CLASSIFICATION OF CIRCUIT-BREAKERS
Circuit-Breakers are generally classified as follows according to
the medium of arc extinction :
1. MCB/MCCB/Air-break circuit breakers.
2. Air blast circuit breakers.
3. Oil circuit breakers.
4. Minimum oil circuit breakers.
5. SF6 circuit breakers.
6. Vacuum circuit breakers.
19
blast.After the arc extinction the chamber is filled with high
pressure air which prevents the arc from restriking.
These circuit breakers were developed during
1930’s.Nowadays they are becoming obsolete and being
replaced by Vacuum and SF6 breakers.
DISADVANTAGES OF OIL
1. The decomposed products of dielectric oil are
inflammable and explosive.If the oil circuit breaker is
unable to break the fault current,the pressure in the
tank may rise above safe limit and explosion may
occur.This does not happen in other types of breakers.
2. The oil absorbs moisture easily.Its dielectric strength
reduces by carbonization which occurs during
arcing.The oil needs replacement after certain breaker
operations.It needs regular maintenance.
3. Oil is not a suitable medium for breakers which have to
operate frequently because the oil deteriorates.
20
increases with pressure and is more than that of dielectric oil at
a pressure of 3 Kg/cm2.SF6 circuit breakers .These breakers
were developed around 1970 and are available for rated
voltages from 3.6 KV to 760 KV.
AT 15Kg/cm2 SF6 gas starts liquefying at 10 deg
Celcius.Hence this gas is not suitable for pressures above 15
Kg/cm2.
Physical properties of SF6 Gas
• Colourless
• Odourless
• Non-toxic
• Non-inflammable
• State – Gas at normal temperature and pressure.
• Density – Heavy gas, density 5 times that of air at 20
deg C and atmospheric pressure.
22
HRC FUSES AND CIRCUIT BREAKERS : A COMPARISION
1. HRC fuses possess high rupturing capacity
compared to the circuit breakers in the medium
voltage range.Fuses with breaking capacity of
100 KA are available.Breakers with
corresponding capacity will be too bulky.
2. HRC fuses are cheaper than the circuit
breakers.
3. HRC fuses take less space and are simpler to
install and maintain.
4. In case of severe faults,HRC fuses open a
circuit in less than half cycle,ie. before the
current peak is reached.As against this,circuit
breakers take 2-3 cycles.
5. There is no deterioration in case of HRC fuses
while circuit breakers are prone to become
sluggish in operation with lapse of time.The
worn latches,contacts etc. can cause mal-
operation of circuit-breakers.
6. It takes some time to replace fuses whereas a
circuit breaker can be switched on quickly to
resume operations.
7. Fuses need replacement after every fault
clearing.
23
CONCEPTS OF EARTHING
INTRODUCTION
SOME FUNDAMENTALS
24
the absence of a well designed effective earthing system,earth
fault conditions may lead to tremendous loss of property and
lives.The main objectives of earthing are as follows :
• To ensure safety of life and property from hazards of
electric shock and electric fires.
• To ensure that system voltages on healthy lines remain
within reasonable limits under fault conditions thereby
prevending insulation breakdowns.
• To provide a low impedance path to facilitate the
satisfactory operation of protective devices under fault
conditions.
• To minimize arcing burn downs as in an earthed system
arcing fault would produce a current in ground path
thereby providing an easy means of detecting and
tripping against phase to earth arcing fault breakdowns.
• To provide an equipotential platform on which electronic
equipments can operate.
• To provide an alternative path for induced current and
minimize the electrical noise in cables.
EARTHING CATEGORIES
There are two types of earthing.
1. SYSTEM EARTHING : This is primarily
concerned with the protection pf electrical
equipmen by stabilizing voltages with respect to
ground.
2. EQUIPMENT EARTHING : This is primarily
concerned with the protection of personnel from
electric shock by maintaining the potential of
non-current carrying equipment at or near
ground potential.
SYSTEM EARTHING
This is basically achieved by earthing the neutral of the supply
system.Ungrounded neutral supply systems are not in use
mainly for the following disadvantages :
1. Under a single line to earth fault the voltage to earth of
the two healthy phases rises from phase value to line
value ie. Root 3 times.
2. The capacitive current in the two healthy phases
increases to root 3 times the normal value.
3. The capacitive current in the faulty phase is 3 times its
normal value.
25
4. The capacitive fault current gives rise to arcing ground
condition.Under such condition the phase voltage may
rise to 5 to 6 times its normal value causing insulation
breakdown.
5. It is difficult to detect and isolate a single phase to earth
fault.
26
4. Arc Suppresson Coil Grounding : Sometimes neutral
earthing is done with an arc suppression coil.It is
provided with tappings and the reactance of the coil can
be tuned depending upon the length of the transmission
line and the capacitance to be neutralized.
EQUIPMENT EARTHING
Under fault conditions the non-current carrying metal parts of an
electrical installation such as
frames,enclosures,supports,fencing etc. may attain high
potential with respect to ground so that any person or stray
animal touching these or approaching these will be subjected to
potential difference which may result in the flow of a current
through the body of the person or the animal of such a value as
may prove fatal.
Safe value of current in amp(rms) which a human body can
tolerate is
I = 0.165/root t for t < 3 secs
And I = 9 mA for t > 3 secs where ‘t’ is time duration in
seconds of the flow of current.
To avoid this the non-current carrying metal parts of the
electrical system are connected to the general mass of earth by
means of an earthing system comprising of earth conductors to
conduct the fault currents safely to the ground.The object of
earthing is to ensure safety by discharging the electrical energy
to the earth.The conductors may be in the form of a grid (also
called mat) or multiple electrodes in the form of
rods,plates,pipes etc.
Here,it is important to understand the concept of STEP and
TOUCH voltage.
27
Consider that damage to a terminal bushing on a transformer
(see fig.) has resulted in the faulting of the respective phase to
the transformer body which is earthed by a pipe electrode
driven into the earth.The earth fault current will flow from the
phase conductor to the transformer body and through the earth
electrode to earth.Around the electrode the current will flow
outward in all directions.
As the current flows through a constantly increasing volume of
earth ,its density drops as the distance from the electrode
increases.The highest potential is at the electrode which is the
same as that of the transformer tank.As the distance from the
electrode increases,the less is the difference in earth surface
potential between two points per unit length.
Now if a person happens to touch the transformer tank,the
potendial difference between his hands and feet will be
E(Touch) = V1-V2
Where E(Touch) is termed as the Touch Potential . It is the
voltage that exists between the hand and both feet of the
person.
28
On the left side of the figure a person is shown walking towards
the transformer tank.At any time,the earth surface potential
between his feet will amount to
E(Step) = V3-V4
Where E(Step) is termed as the Step Potential and is the
voltage between the two feet of a person.
It can be seen that
E(Step) = (Rk + 2Rf) Ik volts
And E(Touch) = (Rk + Rf/2) Ik volts
Where Rk is the resistance of the body,
Rf is the grounding resistance of one foot in ohms,taken
for all practical purposes to be equal to 3 times the resistivity of
the soil near the surface of ground in ohm-meter,
And Ik is the current in amps(rms) flowing through the body.
When a grounding system is installed,the objective is to obtain
as low values of E(Step) and E(Touch) as possible in order to
ensure full safety for human beings and stray animals.
29
conductors) of all transformers and any other apparatus
used for regulating or controlling energy and all medium
voltage energy consuming apparatus shall be earthed
by two separate and distinct connections with earth.
• Rule 61(4) states that all earthing systems shall –
a) consist of equipotential bonding conductors capable of
carrying the prospective earth fault current and a
group of pipe/rod/plate electrodes for dissipating the
current to the general mass of earth without exceeding
the allowable temperature limits in order to maintain
all non-current carrying metal works reasonably at
earth potential and to avoid dangerous contact
potentials being developed on such metal works.
b) Limit earth resistance sufficiently low to permit
adequate fault current for the operation of protective
devices in time and to reduce neutral shifting.
c) Be mechanically strong,withstand corrosion and retain
electrical continuity during the life of the installation.
30
NATIONAL ELECTRICAL CODE (INDIA)
• Clause 2.0.2 states that the object of an earthing
system is to provide, as nearly as possible, a surface
under and around a station which shall be at a uniform
potential and as nearly zero or absolute earth potential
as possible.The purpose of this is to ensure that all
parts of apparatus,other than live parts,shall be at earth
potential,as well as to ensure that operators shall be at
earth potential at all times.Also by providing such an
earth surface of uniform potential under and
surrounding the station,as nearly as possible,there can
exist no diffrence of potential big enough to shock or
injure an operator when fault conditions occur.
• Clause 2.0.3 states that earthing associated with
current-carrying conductor is normally essential to the
security of the system and is generally known as
system earthing,while earthing of non-current carrying
metal work is essential to the safety of life and property
and is generally known as equipment earthing.
• Clause 2.0.9 states that each earth system shall be so
devised that the testing of individual earth electrode is
possible.It is recommended that the value of any earth
system resistance shall not be more than 5
ohms,unless otherwise specified.
• Clause 2.0.10 states that a drawing shall be prepared
for each installation showing the main earth connection
and earth electrodes.
• Clause 2.0.11 states that no addition to the current-
carrying system shall be made which will increase the
maximum available earth fault current or its duration
until it has been ascertained that the existing
arrangement of earth electrodes,earth bus-bar etc. is
capable of carrying the new value of earth fault current.
• Clause 2.0.11 states that no cut-out,link or switch other
than a linked switch arranged to operate simultaneously
on the earthed or earthed neutral conductor and the live
conductors shall be inserted on any supply system.
• Clause 2.1.1.2 states that the earth system resistance
should be such that when a fault occurs against which
the earthing system is designed to give protection,the
protective gear will operate to isolate the faulty portion
of the plant and render it harmless.
API RP 14 F
31
Clause 6.10.3 states the following :
Grounding of electrical equipment on fixed and floating offshore
petroleum facilities in a positive manner is of particular
importance because personnel standing on steel decks or in
contact with steel framing present a low impedance path to
ground ,effectively grounded.In addition,the dampness and salt
deposition contribute to the breakdown of insulation and the
possibility of leakage on the surface of insulators and similar
devices.It is recommended that all metal equipment,such as
skids,vessels etc. be grounded to the steel
structure.Exposed,noncurrent-carrying metal parts of fixed
equipment that may become energized because of any
condition shall be grounded.The physical contact obtained
when equipment is bolted to a steel structure is not necessarily
an adequate effective ground because of paint and possible
corrosion.
To provide the desired safety ,equipment grounding should
accomplish the following :
a) Grounding shall limit the voltage (normally to 42
V maximum) that may be present between the
equipment in question and any other grounded
object with which personnel may be in contact
at the same time.
b) For solidly grounded systems ,grounding should
present a low impedance path for short circuit current to
return to the source of power,thus opening a fuse or tripping a
circuit breaker.This requires that the equipment ground be
bonded to the system ground.
32
EARTH LEAKAGE CURRENTS AND ELCBs
33
Current Effect
1 ~ 10 mA Mild sensation
10 ~ 20 mA Human body remains stuck to the conductor
20 ~ 30 mA Muscle contraction
70 ~ 100 mA The heart begins to vibrate
500 mA Death – Cardiac Arrest / Nervous breakdown
34
The approximate effects of electric current on the human
body:
AC DC
Effect
Current Current
10 1 milliamp Threshold of sensation
milliamps
>60 >10 Strong involuntary muscle contractions.
milliamps milliamps
You may not able to release a live wire.
You may be thrown across the room by
the contraction!
>500 100 Cardiac Arrest!!!!
milliamps milliamps
35
FIVE GOOD REASONS FOR USING ELCBs
30 mA RCCB
The current passing through human body is likely to be
between 80 ~ 240 mA in case of direct contact at 230 V.The
protective device should operate within 50 ms at 240 mA and
240 ms at 80 mA to be within zone-2 (safe) of the IEC
curves.Both these conditions are fulfilled by the 30 mA RCCB
and therefore it provides a very high degree of protection
against electrocution.
37
4. A test button is provided to check the correct operation
of the unit.
5. ELCBs are capable of withstanding starting inrush
currents of motors upto 4 to 8 times the rated current.
6. The ELCBs have excellent short circuit withstand
capability ensuring that there is no damage to the
device itself,till the back-up protection fuse or another
overcurrent device clears the fault.
38
ELECTRIC SHOCK : PREVENTION AND
TREATMENT
Magnitude of Current :
Electric current has the following three harmful effects on the
body :
1. It harms or interferes with proper functioning of the
nervous system and heart
2. It subjects the body to intense heat resulting in burns
3. It causes the muscles to contract.
50 / 60 Hz AC Current Effect
1 mA ~ 2 mA Threshold of sensation
5 mA ~ 10 mA Mild sensation
10 ~ 15 mA Pain
15 ~ 50 mA Muscle paralysis (can’t let go)
50 ~ 100 mA Ventricular Fibrillation
> 100 mA Stop heart or breathing
However, the above figures are approximate only and vary
from person to person depending on physical conditions.
Currents greater than 100 milliamperes can
• Completely stop the heart
• Inhibit breathing in two ways
1. by causing the chest muscles to contract
thereby preventing the lungs from expanding.
2. by blocking the nerve center of the brain that
controls the breathing function.
Path of Current :
When a human body comes in contact with a current carrying
conductor or an object which is at greater potential than earth
due to insulation failure etc. , a current flows through the human
body from the part touching the object/wire (normally one hand)
to ground (normally through the feet) .The path of the current is
very important. And we all know that current always takes the
40
path of least resistance. Let us consider the following two
common cases :
Case 1 : One hand comes in contact with the shock giving
object and the other hand is in contact with the ground then
current will pass from one hand to other through the heart The
shock may prove to be fatal due to heart seizure. To minimize
the risk of current flow through the heart the ‘hand-in-the pocket’
technique is popular with skilled electrical personnel.While
working on electrical systems they keep one hand in pocket or
behind their back thus avoiding the two hands completing a
current circuit through the heart.
Case 2 : Victim standing on ground.The right hand comes in
contact with a shock giving object.Current follows a path from
the right hand to right feet without touching the heart. The
shock may not be fatal in this case.
Duration of Exposure to Current : This also has a very
important bearing on fatality due to electric shock. Safe value of
current in amperes(rms) which a human body can tolerate is
given by the Dalziel’s Formula:
I = 0.165/ sq. root of t for t < 3 secs
And I = 9 mA for t > 3 secs
Where ‘t’ is the time duration in seconds of the flow of current.
Effect of AC Current (mains frequency 50 / 60 Hz) is depicted in
the following graph in IEC 479 and IS 8437.
41
Body Resistance : The resistance offered by the body is
mainly the resistance of the skin. The interior of the human
body is a good conductor due to the abundance of ions in the
body fluids. The body resistance is not constant but varies
under different skin conditions.The two extreme conditions are
depicted below :
Condition Resistance
Dry skin 1,00,000 Ohms
Wet skin 500 Ohms
42
Dry Skin Case : Current = 110 * 1000 / 100000 milliamperes
(mA)
= 1.1 mA
Wet Skin Case : Current = 110 * 1000 / 500 mA = 220 mA
43
The heart produces its own electricity.The electrical system in
the heart consists of a natural pacemaker which generates 60
to 100 electrical pulses per minute which makes out heart
beat.The heart also has a bundle of specialized cells between
the upper chambers (Atria) and the lower chambers (Ventricles)
that conduct the heart’s electrical signals.The electrical system
in the heart makes our ventricles contract and relax in a
rhythmic pattern which results in pumping of blood to the lungs
and other body parts.The heart’s electrical activities can be
monitored and recorded with the help of Electro-Cardio-Gram
(ECG).
44
relaxing and the heart is not able to pump blood to the body
organs. This leads to death due to sudden cardiac arrest.
The current range of 100- to 200-mA. is particularly dangerous
because it is almost certain to result in lethal ventricular
fibrillation. Victims of high-voltage shock usually respond better
to artificial respiration than do victims of low-voltage shock,
probably because the higher current clamps the heart and
hence prevents fibrillation.
AC VERSUS DC CURRENT
Another very important question is : Which is more dangerous
AC or DC ?
Alternating current (AC) is four to five times more dangerous
than direct current (DC). For one thing, AC causes more severe
muscular contractions. For another, AC can lower skin
resistance and thereby increase the shock-current. The skin
resistance goes down rapidly with continued contact because
sweating is stimulated and the skin oils and even the skin itself
are burned away. Consequently, it is extremely important to free
the victim from contact with the current as quickly as possible
before the current increases to the fibrillation-inducing level.
Also, the frequency of the AC influences the effects on the
human body. Unfortunately, the standard electrical power
frequency of 50/60 Hertz is in the most harmful range. At this
frequency, as little as 30 volts can kill. On the other hand,
people have withstood 40,000 volts at a frequency of a million
Hertz or so without fatal effects.
“Let Go” Current : Electric shock causes contraction of the
muscles and many times the victim is unable to free
himself/herself from the current source.The maximum current
that can cause the flexors of the arm to contract but that allows
a person to release his hand is termed as the ‘let-go’ current.
For DC, the let-go current is about 75 mA for an average heathy
person. For AC current, the let-go current is about 15 mA,
depending upon muscle mass.
RELEVANT STANDARDS
Indian Standard IS 8437 : PART 1 & 2 (1993) AND IEC
Publication No. IEC 479 – 1 (1984) : Effects of current passing
through human body.
PREVENTION
It is said that “ Prevention is better than cure”.The following
preventive measures shall be adopted by all of us to safeguard
against the lurking danger of electric shocks :
45
At Home and Office:
46
• Install sockets with automatic protection covers to
minimize the risk to children.
• Always hire a qualified and competent electrician for
electrical works at home. A novice may install a switch
in neutral instead of phase connection which may be
very dangerous.
• Buy only gadgets and appliances of standard reputed
brands. That cheap hair dryer may prove to be very
costly someday.
• Invest in making electricity your friend at home. It is
like investing in a life insurance scheme.
47
• Use of only good quality machines.
• Skilled and competent electricians
• Use of hand gloves.
TREATMENT
In spite of our best efforts , electrical shock incidents do
occur.Hence we must know how to respond to such
situations.If we learn some basic first aid procedures for
electric shock., we may be able to save the life of a person
in case of electric shock.
Electric shocks can result in:
48
a. Tilt head back.
b. Lift chin.
c. Clear out mouth.
a. Pinch nostrils.
b. Give two full breaths.
c. Watch for chest rise and fall.
d. Give one breath every 5 seconds.
49
• Circulation : Check victim’s pulse. If pulse is absent,
begin CPR immediately.
50
Adjust the top leg so that both the hip and knee are bent
at right angles. Gently tilt the head back to keep the airway
open. Keep the person warm until medical help is obtained. If
breathing or circulation stops at any time, roll the person back
on to his or her back and begin CPR.
SUMMARY
Electric current damages the body in three different ways: (1) it harms
or interferes with functioning of the nervous system and heart; (2) it
subjects the body to intense heat; and (3) it causes the muscles to
contract. Electrical shock can be lethal. The hazards must be
understood and general safety rules must be followed.
51
AN INTRODUCTION TO ELECTRICAL
ENGINEERING SOFTWARES
The various aspects of electrical engineering design involve a
lot of complex calculations.Earlier these calculations were done
manually.The process was quite time consuming and the
results were approximate. However, today computer based
design solutions have made inroads in every discipline of
engineering. A number of softwares are now available
encompassing all areas of electrical design.These softwares
make the life of electrical designers and consultants
comfortable,enhance productivity and provide more accurate
results.In India,however, the use of electrical softwares is in a
nascent stage and a very large percentage of working electrical
engineers lack awareness about the same.This subject also
remains largely uncovered by electrical journals and computer
magazines. This article is an attempt to introduce the electrical
engineers to several useful electrical softwares.
52
ETAP has been designed and developed by engineers for engineers to
handle the diverse discipline of power systems in one integrated
package with multiple interface views such as AC & DC networks,
cable raceways, ground grid, GIS, panels, protective device
coordination & selectivity, and AC & DC control system diagrams.
53
SynerGEE® Electric is a simulation software package
3. SKM (www.skm.com) :
Power*Tools for Windows (v. 5.0)
55
IEC_FAULT -- IEC fault analysis.
4. Amtech (www.amtech-power.com) :
AMTECH is a leading software developer producing quality
software specifically for the electrical industry.
56
modules for analysis and reporting, linked by a general-purpose
database.
Modules
• Database Editor • Line Constants
• Short Circuit • Order Production
• One-Line Diagram • Short Circuit Reduction
• Coordination Graphics • Power Flow
• Relay Setting • Breaker Duty Analysis
• System Simulator • Settings Transfer
• Relay Checking Utilities
57
SmartDraw has an extensive collection of electrical symbols
and templates to help you create professional diagrams for:
Electronic Circuits
Automotive Wiring
Circuit Schematics
Electrical Wiring
Digital Circuits
Parallel Circuits
and Much More
8. LightCalc (www.lightcalc.com)
Summary of features:
58
• Finds the proper footcandle level for general, task, and
art lighting.
• Adjust the footcandle level for dark to light rooms and
client age.
• Determines the proper spacing needed.
• Uses both Inverse Square Law and Lumen methods.
• Suggests a grid layout for general lighting.
• Art Lighting - See the light right on artwork!
59
11. Light Table (www.powerangle.com) : Software for
Protective Relay Coordination and Fault Analysis from Power
Angle Software.
60
FAULT LEVELS IN ELECTRICAL SYSTEMS
61
SOURCES OF FAULT CURRENTS
FAULT CALCULATIONS
62
As shown in the figure, according to the short-circuit studies
carried out during plant design , the 11 KV bus-bars and the
circuit-breakers were rated for a fault current of 36.1 KA for
1 sec.
After about 20 years of operation, a new plant was planned
to cater to the future oil and gas production profile.This new
plant is to be an extension of the existing plant there
electrical systems were to be integrated. These systems
were to be designed so as to be capable of operating either
in synchronized or in island mode via an interconnector
arrangement as shown in the following diagram :
64
These fault current limiters can be refurbished and re-used
after clearing a major short-circuit.
65