Data Sheet 5875A 12/1999
5875A 1
IB L2 BOX TEMP 2/2 M12
Table of Contents
Function ........................................................................................................................................... 1
Internal Circuit Diagram ................................................................................................................... 4
Safety Note ...................................................................................................................................... 5
Installation and Connection Instructions .......................................................................................... 5
Sensor Connection ........................................................................................................................... 6
Connection of the Shield .................................................................................................................. 8
Connection Examples .................................................................................................................... 11
Programming Data ......................................................................................................................... 12
INTERBUS Process Data Words ................................................................................................... 12
Tolerances ..................................................................................................................................... 22
Technical Data ............................................................................................................................... 32
Ordering Data ................................................................................................................................35
2 5875A
IB L2 BOX TEMP 2/2 M12
R e s e rv e d
F E 5 8 7 5 A 0 1 1
5875A 3
IB L2 BOX TEMP 2/2 M12
2 4 V
2 4 V
L P C 2
C E E P R O M
5 8 7 5 A 0 0 3
Key:
INTERBUS Loop 2 connection C Microprocessor
Electrically erasable programmable
Filter E E P R O M
read-only memory
DC/DC converter with electrical
Analog digital converter
isolation
L P C 2 INTERBUS protocol chip Amplifier
4 5875A
IB L2 BOX TEMP 2/2 M12
Safety Note
Make sure there is no isolating voltage specified between the analog inputs and
INTERBUS Loop when configuring the system. That means, for example, that the user
must provide signals with safe isolation for thermistor detection, if necessary.
5875A 5
IB L2 BOX TEMP 2/2 M12
Sensor Connection
0 2 0 1
1 2
IN
O U T
IB L 2 B O X T E M P
2 /2 M 1 2
D IA G
3
5 54250008
2 1
Figure 5 General pin assignment of the
In p u t 2 In p u t 1 5-pos. sensor sockets
R e s e rv e d
1 Sensor supply
5 8 7 5 A 0 0 4
2 Sensor input signal +
Figure 4 Location of the sensor sockets 3 Sensor input signal -
4 Analog ground
5 Reserved
Pin assignment of the sensor sockets - Resistance temperature detectors (RTDs)
Pin assignment of the sensor sockets - Thermocouples (TC) and voltage signals
6 5875A
IB L2 BOX TEMP 2/2 M12
A B C D E
m V
R e s e rv e d R e s e rv e d R e s e rv e d R e s e rv e d R e s e rv e d
5 4 2 5 A 0 0 9
Figure 6 Examples for the connection of 2-, 3-, and 4-wire sensors
A 4-wire RTDs
B 3-wire RTDs
C 2-wire RTDs
D Thermocouples
E Voltage signals
5875A 7
IB L2 BOX TEMP 2/2 M12
A 1 A 2
5 8 7 5 A 0 0 7
8 5875A
IB L2 BOX TEMP 2/2 M12
The shield of the sensor cable is connected with the shield plate by means of the M12 metal
connector.
0 2 0 1
IN
O U T
IB L 2 B O X T E M P
2 /2 M 1 2
D IA G
2 1
5 8 7 5 A 0 0 8
R e s e rv e d
0 2 0 1
IN
O U T
IB L 2 B O X T E M P
2 /2 M 1 2
D IA G
< 3 0 c m
2 1
R e s e rv e d
1 2 5 8 7 5 A 0 0 9
• Strip a portion of the insulation off the sensor cable within 30 cm (11.811 in.) of the sensor input
at the module (1).
• Use a screw to connect the shield clamp (2) to PE (protective earth ground) potential.
5875A 9
IB L2 BOX TEMP 2/2 M12
Example Extension of the Equalizing Conductor With Thermal Element Terminal Blocks
0 2 0 1
IN
O U T
IB L 2 B O X T E M P
2 /2 M 1 2
D IA G
+
-
2 1
E q u a liz in g c o n d u c to r
R e s e rv e d
C e n tra l
M T K D te r m in a l
g r o u n d in g p o in t
P E
T h e r m o c o u p le
5 8 7 5 A 0 1 0
Figure 10 Extension of the equalizing conductor using thermal element terminal blocks
Thermal element terminal blocks (MTKD... type from Phoenix Contact) are available for the extension
of thermocouple extension wires.
If you are using an MTKD terminal, the cable is grounded on a central grounding point. In
this case, do not install the shield on the module.
To avoid reduced functionality due to EMI, the cable between the MTKD terminal and the
module must not be longer than 1 m (3.3 ft.).
10 5875A
IB L2 BOX TEMP 2/2 M12
Connection Examples
The grounding of the shielded cable is shown schematically in Figure 11 and Figure 12.
Connect the shield according to the grounding options given on page 8.
0 2 0 1 0 2 0 1
IN IN
O U T O U T
IB L 2 B O X T E M P IB L 2 B O X T E M P
2 /2 M 1 2 2 /2 M 1 2
D IA G D IA G
+ + +
- -
2 1 2 1
-
R e s e rv e d R e s e rv e d
A B A B
5 8 7 5 A 0 0 5 5 8 7 5 A 0 0 6
A Measuring point; e.g., 700°C (1292°F) A Measuring point; e.g., 700°C (1292°F)
(measurement across resistor)
B External cold junction; e.g., 0°C (32°F)
B Measuring point; e.g., 700°C (1292°F) (e.g., ice water)
(measurement across thermocouple with
module internal cold junction compensation)
The internal cold junction compensation can be switched off for differential temperature
measurement.
5875A 11
IB L2 BOX TEMP 2/2 M12
Programming Data
ID code 73hex (115dec)
Length code 02hex
Input address area 4 bytes
Output address area 4 bytes
Parameter channel (PCP) 0 bytes
Register length 4 bytes
Assignment of the Sensor Sockets to the INTERBUS Input Data Word (see page 18)
12 5875A
IB L2 BOX TEMP 2/2 M12
5875A 13
IB L2 BOX TEMP 2/2 M12
P ro c e s s d a ta w o rd 1 P ro c e s s d a ta w o rd 2
C h a n n e l 1 C h a n n e l 2
M S B L S B
1 5 1 4 1 3 1 2 1 1 1 0 9 8 7 6 5 4 3 2 1 0
R T D -R 0 c o d e T e m p e ra tu re S e n s o r ty p e
u n it / C o ld ju n c tio n
R e s o lu tio n c o m p e n s a tio n
5 4 2 5 A 0 1 1
Figure 13 Sequence of the process data output words in the INTERBUS ring and representation of
the bits of the first process data word
14 5875A
IB L2 BOX TEMP 2/2 M12
5875A 15
IB L2 BOX TEMP 2/2 M12
The internal cold junction temperature can be read with the set sensor type “cold junction
sensor” (15hex).
16 5875A
IB L2 BOX TEMP 2/2 M12
Examples for the Configuration With Normal Mode (INTERBUS OUT 2 = 0000hex)
5875A 17
IB L2 BOX TEMP 2/2 M12
P ro c e s s d a ta w o rd 1 P ro c e s s d a ta w o rd 2
C h a n n e l 1 C h a n n e l 2
M S B L S B
1 5 1 4 1 3 1 2 1 1 1 0 9 8 7 6 5 4 3 2 1 0
S B A V
5 4 2 5 A 0 1 4
Figure 14 Sequence of the process data input words in the INTERBUS ring and representation of
the bits of the first process data word
Key:
SB Sign bit
AV Analog value (measured value)
The measured value is displayed as a 16 bit value in the two’s complement of the process data. With
0.01 K resolution, the temperature range to be mapped in the process data is limited. If a value is out
of this range, the error message “Out of temperature range” is generated for the channel.
18 5875A
IB L2 BOX TEMP 2/2 M12
5875A 19
IB L2 BOX TEMP 2/2 M12
Error Messages
In normal mode, every process data input word is assigned to the temperature value of the
corresponding channel. If the channel receives invalid temperature values, an error code is written to
the corresponding process data input word. This error code specifies the state of the channel.
The error message “Internal I/O supply voltage error” is global and does not refer to one channel.
The error message is therefore output to both process data input words. A module error is also
indicated and no ADC values are processed.
The error message “Open circuit” is not valid for linear voltages (sensor types U1 and U2
(see “Sensor Type (Bit 4 to Bit 0)” on page 17).
P ro c e s s d a ta w o rd 1 P ro c e s s d a ta w o rd 2
C h a n n e l 1 C h a n n e l 2
M S B L S B
1 5 1 4 1 3 1 2 1 1 1 0 9 8 7 6 5 4 3 2 1 0
E 0 h e x R e s e rv e d O p e n c ir c u it
R e s e rv e d
O u t o f ra n g e
E r r o r in th e in te r n a l
I/O s u p p ly v o lta g e
M e a s u r e d v a lu e in v a lid 5 4 2 5 B 0 1 2
Figure 15 Assignment of the process data input words when an error occurs
Power Up
No configuration is preset upon the connection of the module. The module writes the error
message “Measured value invalid” to both process data input words. The first measured
value appears within 1.8 seconds (maximum) after a valid configuration has been written.
20 5875A
IB L2 BOX TEMP 2/2 M12
Limit Values
The limits of the overload capability for Pt and Ni sensors according to DIN and SAMA are effective
for R0 = 100 Ω. For other R0, the values converted proportional to R0 = 100 Ω are effective.
The error message “Out of temperature range” is generated when the value is out of the overload
capability.
5875A 21
IB L2 BOX TEMP 2/2 M12
Tolerances
Tolerances of the RTD and R Inputs at an Ambient Temperature of TU = +25°C
Sensor Type Measuring Range for Typical Total Error Maximum Total Error
the Tolerances Relative Absolute Relative Absolute
Pt 100 DIN -200°C to +850°C ±0.053% ±0.45 K ±0.224% ±1.91 K
-328°F to 1562°F
Pt 100 SAMA -200°C to +850°C ±0.053% ±0.45 K ±0.224% ±1.91 K
-328°F to 1562°F
Pt 1000 DIN -200°C to +850°C ±0.046% ±0.39 K ±0.321% ±2.73 K
-328°F to 1562°F
Ni 100 DIN -60°C to +180°C ±0.127% ±0.23 K ±0.538% ±0.97 K
-76°F to +356°F
Ni 100 SAMA -60°C to +180°C ±0.127% ±0.23 K ±0.538% ±0.97 K
-76°F to +356°F
Ni L&G -50°C to +160°C ±0.118% ±0.19 K ±0.825% ±1.32 K
-58°F to +320°F
Cu 10 SAMA -70°C to +500°C ±0.779% ±3.90 K ±1.949% ±9.74 K
-94°F to +932°F
KTY 81 -55°C to +150°C ±0.078% ±0.12 K ±0.550% ±0.83 K
-67°F to +302°F
Cu 50 -50°C to +200°C ±0.245% ±0.49 K ±1.058% ±2.12 K
-58°F to +392°F
Cu 53 -50°C to +180°C ±0.266% ±0.48 K ±1.154% ±2.08 K
-58°F to +356°F
R 0 Ω to R 8000 Ω 0 Ω to 4000 Ω ±0.019% ±1.52 Ω ±0.133% ±10.64 Ω
(linear)
(1/2 measuring
range)
R 0 Ω to R 8000 Ω 0 Ω to 8000 Ω ±0.064% ±5.10 Ω ±0.447% ±35.72 Ω
(linear)
22 5875A
IB L2 BOX TEMP 2/2 M12
The data listed on the previous page contains offset, gain, and linearity error. Errors
caused by EMI are not included.
All percentage data refers to the corresponding positive final value of the measuring range.
The maximum tolerance indications contain the maximum tolerances that are theoretically
possible at the lowest sensitivity in the corresponding measuring ranges. The maximum
tolerances that are theoretically possible for the calibration and test equipment are taken
into account.
The maximum tolerance indications of the platinum, nickel, and KTY 81 resistance sensors
include a resistance for the incoming cable of 200 mΩ (this corresponds to a copper line
of approximately 1.5 m x 0.25 mm2 [24 AWG]).
5875A 23
IB L2 BOX TEMP 2/2 M12
24 5875A
IB L2 BOX TEMP 2/2 M12
The data listed on the previous page contains offset, gain, and linearity error. Errors
caused by EMI are not included.
All percentage data refers to the corresponding positive final value of the measuring range.
The maximum tolerance values contain the maximum tolerances that are theoretically
possible at unfavorable ambient temperature (-25°C or +60°C [-13°F or +140°F]) and the
lowest sensitivity in the corresponding measuring ranges. The maximum tolerances that
are theoretically possible for the calibration and test equipment are taken into account.
The maximum tolerance indications of the platinum, nickel, and KTY 81 resistance sensors
include a resistance of the incoming cable of 200 mΩ (this corresponds to a copper line of
approximately 1.5 m x 0.25 mm2 [24 AWG]).
5875A 25
IB L2 BOX TEMP 2/2 M12
* Below the indicated range, more errors are expected because of the low sensitivity of the sensor
elements.
In this range, “double” tolerances can occur for the sensor types S and R.
26 5875A
IB L2 BOX TEMP 2/2 M12
5875A 27
IB L2 BOX TEMP 2/2 M12
* Below the indicated range, more errors are expected because of the low sensitivity of the sensor
elements.
In this range, “double” tolerances can occur for the sensor types S and R.
28 5875A
IB L2 BOX TEMP 2/2 M12
5875A 29
IB L2 BOX TEMP 2/2 M12
Typical Total Error with Internal Cold Junction Compensation at an Ambient Temperature of
TU = +25°C
Input Sensor Measuring Range for Relative Absolute
Type the Tolerances* Error Error
J -210°C to +1200°C ±0.091% ±1.09 K
Thermo- -346°F to +2192°F
couples K -200°C to +1372°C* ±0.083% ±1.14 K
-328°F to +2501°F
Typical Total Error with Internal Cold Junction Compensation at an Ambient Temperature of
TU = -25°C to +60°C
Input Sensor Measuring Range for Relative Absolute
Type the Tolerances* Error Error
J -210°C to +1200°C ±0.175% ±2.10 K
Thermo- -346°F to +2192°F
couples K -200°C to +1372°C* ±0.159% ±2.18 K
-328°F to +2501°F
* The tolerances of the sensor elements and, if necessary, the tolerances caused by EMI
must also be taken into account.
30 5875A
IB L2 BOX TEMP 2/2 M12
5875A 31
IB L2 BOX TEMP 2/2 M12
Technical Data
General
Housing dimensions (width x height x depth) 62 mm x 60 mm x 95 mm
(2.441 in. x 2.362 in. x 3.740 in.)
Weight 125 g
Operating mode Process data operation with 2 INTERBUS IN
words and 2 INTERBUS OUT words
Connection type of the sensors 2-, 3-, or 4-wire technology
Total power consumption 1.2 W, typical; 1.8 W, maximum
Indications regarding ambient temperature, humidity, air pressure, and degree of
protection are different to the indications in the manual.
32 5875A
IB L2 BOX TEMP 2/2 M12
General (continued)
Processor monitoring Watchdog circuit
Preferred installation position Panel mounting
Functional earth ground connection Via grounded mounting plate
Interface
INTERBUS interface INTERBUS Loop cable
Power Consumption
Supply voltage USL 24 V DC
Current consumption of USL 50 mA, typical; 75 mA, maximum
Total power consumption 1.2 W, typical; 1.8 W, maximum
Analog Inputs for Resistance Temperature Detectors (RTD) and Thermocouples (TC)
Number 2
Connecting the RTD sensors 2-, 3-, and 4-wire termination in 2-wire
technology
Connecting the TC sensors 2-wire, shielded equalizing conductor for TC with
encapsulated sensors
Sensor types that can be used (RTD) Pt 100, Pt 1000, Ni..., Cu..., KTY, R 8000
Sensor types that can be used (TC) E, J, K, L, N, R, S, T, U
Standards of characteristic curves for TC DIN IEC 60584-1: 1984 (E, J, K, N, R, S, T)
sensors DIN 43710 (U, L)
Voltage input ranges -20 mV to +2400 mV and -20 mV to +150 mV
Temperature measuring unit °C, °F, mV, Ω can be selected
Temperature measuring range (value range) See table on page 21
Resolution of the measured values See table on page 16
Measuring principle Sigma-delta method
Representation of output value 16-bit two's complement, left-justified
5875A 33
IB L2 BOX TEMP 2/2 M12
Analog Inputs for Resistance Temperature Detectors (RTD) and Thermocouples (TC)
Process data update of 2 channels (incl.
detection and transmission to the process data
registers)
RTD / R 0 Ω to R 8000 Ω (linear) Normal operation: 100 ms, maximum
Cyclical calibration operation:1.40 s, maximum
TC without cold junction compensation Normal operation: 200 ms, maximum
Cyclical calibration operation:1.50 s, maximum
TC with cold junction compensation Normal operation: 250 ms, maximum
Cyclical calibration operation:1.55 s, maximum
Input filter Digital filter
Limit frequency of the digital filter 22.6 Hz
34 5875A
IB L2 BOX TEMP 2/2 M12
Ordering Data
Description Order Designation Order No.
INTERBUS Loop 2 module with two analog IB L2 BOX TEMP 2/2 M12 27 31 92 4
temperature input channels on female M12 sensor
connectors
BK module with INTERBUS Loop 2 branch; IBS L2 IP 24 BK-T 27 23 47 9
IP 65 protection
Protective caps (package unit: 5 pcs.)
IBS IP PROT IO 27 59 91 9
for unused M12 sockets
M12 connectors for IB L2 ... modules
Straight version, with PG7/M12 SACC-M12MS-5CON-PG7 16 62 25 6
Angled version, with PG7/M12 SACC-M12MR-5CON-PG7 16 62 26 9
Metal sensor connector, straight version SACC-M12MS-5CON-PG7- 16 93 41 6
SH
Metal sensor connector, angled version SACC-M12MR-5CON-PG7- 16 93 42 9
SH
INTERBUS Loop cable 2 x 1.5 mm2 (green) with
IBSL SLC Cu2/1,5-Meter 27 21 62 0
meters marked on the cable
INTERBUS Loop set consisting of:
50 zack markers SSZB WH and IBSL ZB-SET 27 21 98 9
15 protective caps for M12 sensor sockets
INTERBUS Loop set consisting of:
10 PG13,5 grommet, compression ring, splice
ring, and black cap nut
10 PG11 grommet, compression ring, splice ring, IBSL PG-SET 27 21 99 2
and green cap nut
5 Filler plugs for the actuator supply of DO and
DIO modules
For further accessories for the connection to M12 sockets please refer to the Phoenix Contact
Catalog Part 2 “PLUSCON”.
Shield plate (replacement) IB L2 SHIELD 27 32 41 5
INTERBUS Loop 2 System Manual IB L2 SYS PRO UM E 27 43 49 1
5875A 35
IB L2 BOX TEMP 2/2 M12
36 5875A