Sie sind auf Seite 1von 1

PURGING INSTRUCTION FOR

FRAMO SUBMERGED CARGO PUMPS


1.0 WHY PURGING THE COFFERDAM ?
- leakage detection
- condition monitoring of the shaft seal system
- avoid that leakages are blocking the cofferdam

2.0 HOW TO PURGE THE COFFERDAM


Preparation:
- place a suitable container underneath the exhaust trap to collect the leakage.
- check that valve and bottom of exhaust trap are not clogged by residue after
last purging operation. Stick up with a pin if necessary.
- check that the drain hole from the relief valve on the purging valve block is
open.
Location and design of purging valve are different for the various pump
types. For technical details, refer to the pumps service manual.
- connect purging medium supply to the snap-on coupling on the purging
valve. (Maximum supply pressure is 7 bar.)
- drain the supply line for condensed water.

Purging:
NOTE: To prevent damage from dangerous cargoes, take necessary
precautions, wear safety gear, and avoid contact with drain from exhaust trap.
- open valve on purging medium supply line
- check that purging medium is coming out of the exhaust trap vent line.
(Cofferdam is open)
- the relief valve on the purging valve block is set to an opening pressure of
3 - 3.5 bar, so a small leakage here is normal
- purge cofferdam in several sequences if required
- drain exhaust trap between each sequence
- disconnect purging medium supply
- close exhaust trap drain valve
- measure the amount of leakage, - evaluate and log the purging result.

3.0 PURGING INTERVALS, -LOGGING OF PURGING RESULT

LOADING VOYAGE DISCHARGE


1. Shortly before loading. 1. 1-2 days after loading. 1. Shortly before
discharging.
2. If no leakage at step 1,
purge every fortnight. 2. Shortly after
discharging.
3. If leakage is detected at
step 1, or at a later stage
during the voyage, purge
this pump every day.

4. If pumps are used for cargo


circulation during the
voyage, the cofferdam
must be purged before start
and after stop.
NOTE! Purging neglection can result in a blocked cofferdam.
The purging form should be filled in with the results from every purging
operation. Each horizontal line in the form represents one cargo in one tank
from loading till discharging. If a ship loads and discharges some tanks more
frequently than other, an extra form should be filled in for these tanks.

4.0 EVALUATION OF THE PUMPING RESULT


4.1 CARGO LEAKAGE
The leakage rate is depending on the type of cargo. A small cargo leakage up to about 0,5 l/day during the pump operation is normal. If the
leakage rate is above 2 l/day, control and necessary action to be taken. See relevant FRAMO purging instruction.

4.2 HYDRAULIC OIL LEAKAGE


A small leakage up to 0,25 l/day during operation is normal. If the leakage rate is increasing above acceptable level, control and necessary
action to be taken. See relevant FRAMO purging instruction.

The ship’s staff on board have the primary responsibility for purging and necessary action to be taken. In case the ship’s staff need
information/advise, contact
FRAMO on telefax no. +47 55 99 93 82. Alternatively call +47 55 99 92 00, or after office hour +47 90 99 00 06,
or E-mail: purging@framo.no

Das könnte Ihnen auch gefallen