Ingress Protection Chart

The Ingress Protection (IP) for The first character numeral The second character numeral
all low voltage enclosures up indicates the degree of indicates the degree of
to 1000 V a.c. and 1500 V d.c. protection provided by the protection provided by the
is defined in identical fashion enclosure with respect to enclosure with respect to
by the standards EN 60529 - persons, also to the equipment harmful ingress of water; a
IEC 529 it comprises the inside the enclosure. third character may be used
letters IP followed by two to indicate mechanical
character numerals: strength. An x signifies that no
test has been carried out.

The first character numeral The second character numeral


Protection against solid substances. Protection against liquid substances.

IP Test Short Definition IP Test Short Definition


description description

0 Non-Protected No special protection. 0 Non-Protected No special protection.


1 Protected against A large surface of the 1 Protected against Dripping water (vertical-
solid objects body, such as a hand dripping water ly falling drops) shall
greater than (but no protection have no harmful effect
50mm against deliberate
ø 50 mm access) solid objects
exceeding 50mm in
diameter
2 Protected against Vertically dripping water
2 Protected against Fingers or similar dripping water shall have no harmful
solid objects objects not exceeding when tilted up effect when the
greater than 80mm in length; solid to 15º enclosure is tilted at any
12.5mm objects exceeding 12.5 angle up to 15º from its
ø 12.5 mm mm in diameter normal position

3 Protected against Water falling as a spray


spraying water at an angle up to 60º
3 Protected against Tools, wires, etc...., of from the vertical shall
solid objects diameter or thickness have no harmful effect
greater than greater than 2.5mm;
2.5mm solid objects exceeding
2.5 mm in diameter
ø 2,5 mm
4 Protected against Water splashed against
splashing water the enclosure from any
direction shall have no
4 Protected against Wires or strips of harmful effect
solid objects thickness greater than
greater than 1.0mm; solid objects
1.0mm exceeding 1.0 mm in
diameter 5 Protected against Water projected by a
ø 1 mm
water jets nozzle against the
enclosure from any
5 direction shall have no
Dust-protected Ingress of dust is not
harmful effect
totally prevented but
dust does not enter in
sufficient quantity to 6 Protected against Water from heavy seas
interfere with heavy seas or water projected in
satisfactory operation of powerful jets shall not
the equipment enter the enclosure in
6 Dust-tight No ingress of dust harmful quantities

7 15 cm Protected against Ingress of water in a


the effect of harmful quantity shall not
immersion be possible when
the enclosure is immer-
sed in water under
defined conditions of
pressure and time

8 Protected against The equipment is


m
submersion suitable for continuous
submersion in water
under conditions which
shall be specified by the
manufacturer

312
Type Tested Assemblies

Consumer Units & Distribution Boards Panelboards


As you might expect, consideration has been given to the design The idea of group mounting MCCBs or MCBs on to a vertical
of the enclosure to accommodate the range of MCB and RCCB three phase bus-bar system came from North America during
devices which are suitable for use in domestic or similar installa- the 1960s, where it had been used very effectively for a number
tions, or generally in installations where unskilled persons have of years. The design takes advantage of the modular dimensions
access to their use. This, describes the European Norm covering of the circuit breakers which, together with the simple bus-bar
the requirements of LV Distribution Boards suitable for this appli- system, proved to be very economical and safe. The basic
cation. The full title is: design philosophy behind the panelboard is to provide a three
phase distribution board capable of accommodating MCCBs,
EN 60439-3 which is simple to specify, manufacture and install, and can be
Specification for low voltage switchgear and control switchgear made available “off the shelf” or on a very short delivery cycle.
assemblies. Part 3. Particular requirements for low-voltage
switchgear and control gear assemblies intended to be installed Generally installed for commercial and light industrial application
in places where unskilled persons have access to their use - the panelboard is, however, used in many different types of
applications.
Distribution boards
This standard covers the supplementary requirements for Panelboards are covered by the European Norm for Low-voltage
enclosure distribution boards suitable for indoor use containing Switchgear and Control Gear Assemblies EN 60439 Part 1,
protective devices and intended for use either in domestic which is the specification for type-tested and partially type-
applications or in other places where unskilled persons have tested assemblies (general requirements).
access for their use. Control and/or signalling devices may also
be included. Panelboards are usually type-tested assemblies but, unlike
consumer units and distribution boards, they do not, as yet,
They are for use on ac, with a nominal voltage to earth not have their own particular standard, so care must be taken in
exceeding 300V. The outgoing circuits contain short circuit their selection and application. It is important that the system
protection devices, each having a rated current not exceeding designer understands, and is able to use, the technical informa-
125A with a total incoming load current not exceeding 250A. tion that the manufacturer is required to publish regarding the
panelboard. Most of the information is straightforward and
Customer Distribution Boards which are generally known in presents little problem, except perhaps for internal separation
Ireland as Consumer Units are also included in this Standard. (Form numbers), degree of protection (IP rating) and short-circuit
The additional test requirements are set out in annex ZA which withstand strength.
calls for the assembly to withstand a short-circuit fault of 16kA
when protected by a 100A specified fuse. Internal Separation
The internal separation of assemblies is described EN 60439 and
By definition a customer distribution board or consumer unit is is concerned with three requirements which can be met by the
an integrated assembly, for the control and distribution of elec- suitable arrangement of barriers or partitions.
trical energy, principally in domestic installations, incorporating
manual means of double pole isolation in the incoming circuits, • Protection against contact with live parts belonging to adjacent
and are designed for use exclusively with one or more of the functional units.
following outgoing circuit protective devices: fuses, MCB’s and
RCBO’s. • Limitation of the possibility of initiating and spreading of arcing
The units may also incorporate RCCB’s. Polarity must be faults.
observed throughout and the consumer unit is type tested when
energised through a 100A type II fuse complying with BS1361. • Prevention of the passage of solid foreign bodies from one unit
The rated current of a consumer unit is determined by the rated of an assembly to an adjacent unit.
current of the incoming protective device, usually 63A, 80A or
100A, the rated current of the incoming device(s) is limited to Form numbers are given to some typical forms of
100A. separation -

As there are no diversity factors applied to consumer units, the Form 1 - No separation
incoming circuit and the bus-bar system must be able to carry
their full rated current without exceeding the temperature rise Form 2 - Separation of bus-bars from the functional units
limits.
Form 3 - Separation of bus-bars from the functional units and
separation of all functional units from one another, but
not their outgoing terminals.

Form 4 - Separation of bus-bars from the functional units and


separation of all functional units from one another
including their outgoing terminals.
Invicta

313
Type Tested Assemblies

Degree of Protection of Enclosures Short-Circuit Withstand


The degree of protection provided by an enclosure is The European Normrequires the manufacturer to state the
indicated by the IP code in the following way - following:

Code Letters IP 3 1 C For a panelboard with an incoming MCCB -


(International Protection)
• The maximum allowable value of prospective shortcircuit cur-
First Numeral rent at the terminals of the incoming MCCB.
(Resistance to solid objects 0-6)
For a panelboard where a short-circuit protective device is not
Second Numeral incorporated in the incoming unit (Main Terminals) -
(Resistance to water 0-8)
• The rated short-time withstand current
Additional Letter (optional) • The rated peak withstand current
(Limited entry of solid objects) • The withstand time period if different from one second.

For example, an enclosure with an index IP20 would provide All Invicta panel boards have been independently tested at a UK
protection against solid bodies greater than 12mm but offer no ASTA approved test laboratory.
protection against water; however an index IP31 would provide
protection against solid bodies greater than 2.5mm and in additi- To assist in the selection of the correct panelboard, suitable for
on against vertically dripping water. use on systems having prospective fault levels ranging from 15
to 50kA, Hager have prepared the following simple charts.
Sometimes the letter ‘X’ is used in place of the first or
second numeral to indicate that tests have not been made or are Invicta 250 Panelboard
not considered relevant. For example IP4X provides protection Enclosure - Degree of protection (door closed) IP3X
against a 1mm probe but has not been tested for the ingress of
water. Refer to page 312 for ingress protection chart. Internal Separation Form 3
Bus-bar rated current 800A
Invicta 125 Panelboard Bus-bar rated short-time withstand current 35kA for 1s
Rated conditional short circuit current 40kA - direct
Enclosure - Degree of protection (door closed) IP3X connected
Internal Separation Form 3 with 250A
Bus-bar rated current 400A MCCB
Bus-bar rated short-time withstand current 35kA for 1s outgoing
direct connected
(unconditional) Incoming - Main Terminals 800A
Non-Auto MCCB 800A
Incoming - Main Terminals 400A MCCB 800A
Non-Auto MCCB 400A
MCCB 400A Outgoing - H125 MCCBs 16 to 125A
H250 MCCBs 160 to 250A
6 way
Outgoing - H125 MCCBs 16 to 125A 8 way
4 way 12 way
6 way 18 way
8 way Maximum Prospective Short-circuit level at point of
12 way application with
Maximum Prospective Short-circuit level
at point of application with • Incomer - main terminals - outgoing H125 15kA
• Incomer - main terminals - outgoing only H250 40kA
• Incomer - non-auto MCCB - outgoing H125 15kA
• Incomer - main terminals - outgoing H125 15kA • Incomer - non-auto MCCB - outgoing only H250 40kA
• Incomer - non-auto MCCB - outgoing H125 15kA • Incomer - H400 MCCB - outgoing H125 25kA
• Incomer - H400 MCCB - outgoing H125 25kA • Incomer - H400 MCCB - outgoing only H250 35kA
• Incomer - H800 MCCB - outgoing only H250 50kA
Table 1

314
Invicta 125
- Dimensions
Dimensions
Cat Ref. Height Width Depth
JN304P / JN304P1 976 710 156
JN306P / JN306P1 1053 710 156
JN308P / JN308P1 1130 710 156
JN312P / JN312P1 1284 710 156

Terminals
No. of Neutral Earth
TP Ways
4 2 x 6 x 50mm 2 x 9 x 25mm
6 2 x 9 x 50mm 2 x 12 x 25mm
8 2 x 12 x 50mm 2 x 15 x 25mm
12 2 x 18 x 50mm 2 x 21 x 25mm
Main M12 M10
connection

Extension Boxes
Cat Ref. Height Width Depth
JN201E / JN201E1 250 710 156
JN203E / JN203E1 400 710 156
JN205E 250 710 156
JN206E 400 710 156
JN301A 400 710 156
250 710 156

Invicta

315