High Efficiency
Condensing Boilers
Models covered by this manual:
U-Series
Utility U70HE U90HE U120HE
Utility Pumped UP70HE UP90HE
Utility System US70HE US90HE
Utility Combi UC70HE UC90HE
K-Series
Kabin Pak K70HE K90HE K120HE
Kabin Pak Pumped KP70HE KP90HE
Kabin Pak System KS70HE KS90HE
Kabin Pak Combi KC70HE KC90HE
Commissioning
This appliance must be commissioned. Failure to commission the
boiler will invalidate the warranty. After commissioning ensure that
the attached guarantee registration card is completed and returned.
Servicing
To ensure continued reliable operation and fuel economy
it is recommended that the boiler is serviced annually
by a Warmflow or an OFTEC registered technician.
NI Customers Only
Warmflow Engineering Service division (NI) provides an
excellent back-up service, operating a team of OFTEC trained
engineers who can meet all the servicing, commissioning
and breakdown requirements for your appliance.
LISBURN MANCHESTER
Lissue Industrial Estate, Moira Road, 144 Bradford Road,
Lisburn, Co Antrim, N Ireland, BT28 2RF Manchester, M40 7AS
Tel: (028) 9262 1515 Tel: (0161) 205 4202
Fax: (028) 9262 0869 Fax: (0161) 205 4818
Email: sales@warmflow.co.uk Email: sales@warmflowgb.co.uk
technical@warmflow.co.uk technical@warmflowgb.co.uk
service@warmflow.co.uk service@warmflowgb.co.uk
This manual is accurate at the date of printing (E&OE) but will be superseded and should be disregarded
Code 3307
if specifications and/or appearances are changed in the interests of continued product improvement.
Contents Page
User Instructions......................................................................................................................................................................2
5.0 Flues
5.1 Installation of Balanced Flues.........................................................................................................................42
5.2 Conventional Flues.........................................................................................................................................44
5.3 Flue Terminal Positions...................................................................................................................................44
8.0 Burners
8.1 RDB Burner....................................................................................................................................................50
8.2 Oil Pump........................................................................................................................................................50
8.3 Electrical Connections....................................................................................................................................50
8.4 Electrode Setting............................................................................................................................................51
8.5 Burner Start-Up Cycle....................................................................................................................................51
8.6 Air Damper Adjustment..................................................................................................................................51
13.0 Spares
13.1 RDB 2.2 Spares.............................................................................................................................................60
13.2 Pipe Spares....................................................................................................................................................61
13.3 Boiler Short Parts List.....................................................................................................................................62
Commissioning/Service Record..............................................................................................................................64
Page
USER INSTRUCTIONS
Dual Thermostat
Burner Lockout
When the pressure jet oil fired burner stops after Burner Lock Out Reset
failing to fire the red reset button will be illuminated.
This indicates that there is a fault or there is no
fuel getting to the burner. The house holder should
only reset the burner twice in succession. If the
burner continues to lockout contact Warmflow or
your service engineer.
Page
Filling Loop
Page
CONDENSING BOILER INSTALLATION
REQUIREMENTS
The Warmflow condensing boiler can be fitted to most installations using
standard practices and techniques.
As the water temperature in the system rises the pluming effect will
diminish. Even where pluming is not visible the boiler is still operating
more efficiently than a standard boiler.
Page
BEFORE FITTING A COMBI BOILER
THE INSTALLER MUST CHECK:
1. What the maximum hot water demand is likely to be placed on the
boiler. Not every installation is suitable for a Combi boiler. Systems
requiring very high hot water flow rates may be better suited with an
unvented cylinder.
3. Where the mains water pressure is supplied via a borehole pump and
accumulator the pressure variation must not affect the thermostatic
mixer valve. (Contact Warmflow for further details).
4. The hardness of the mains water supply. Systems with hard water must
be fitted with a suitable chemical scale preventer (eg Fernox Quantomat
or Combimate alternatively contact Warmflow for further details).
5. That the flow from any one hot water outlet does not exceed the
maximum recommended. This applies particularly to baths which are
usually fitted with larger taps and larger bore supply pipes. It may be
necessary to restrict the flow to these taps by reducing the bore of the
supply pipework (eg 15mm) or by fitting a restrictor into the pipework.
6. That any outlet when opened does not starve all the other outlets of hot
water. If more than one outlet is open at the same time then the total
flow from all the outlets should not exceed the maximum flow rate of
the boiler.
7. That any showers being supplied with hot water by the boiler are
compatible with this type of appliance (contact Warmflow for further
details).
It should be noted that the boiler has been factory fitted with an
18 litre/min flow restrictor.
Page
1.0 General Information
1.1 Introduction
Note: All our domestic appliances have been independently tested and
accredited as exceeding the minimum SEDBUK efficiency levels required for
its type, in compliance with the Building Regulations Approved Document
L1A, L1B for England and Wales, the Building Standards (Scotland)
Regulations Section 6, Part F northern Ireland and Part L Republic of
Ireland.
Warmflow oil fired condensing boilers are designed to burn Class C2 (28 sec
redwood) kerosine and to be used on a fully pumped system, and are suitable for
connection to sealed heating systems.
As standard the Combi and System boilers are fitted with a system expansion
vessel, circulating pumps, filling loop, pressure gauge and safety valve. An optional
7-day electronic programmer kit is also available.
The Combi can provide at mains pressure domestic hot water without the need for
a storage cylinder.
The manufacturer’s guarantees are void if the appliance is not installed and
commissioned in accordance with the recommendations made herein.
The installation of the boiler must be in accordance with the following regulations.
Page
1.3 Combi General Requirements
The boiler will have a DHW priority when both domestic hot water (DHW) and central
heating (CH) are selected. So if the flow switch is closed or the heat store has not
been satisfied the entire output of the boiler is directed to DHW before the boiler will
switch over to CH. When fully cold it can take up to 20 minutes for the heat store to
be satisfied.
After a draw-off of 120L at 24L/min, with an average temperature rise of 32°C, the
thermal store has a recovery time of approximately 7 mins.
Note: If HW has not been selected no hot water can be produced even if the heat
store is up to temperature.
Where there is a build up of excess heat in the boiler primary heat exchanger and
the central heating has not been selected then the pump over-run thermostat
will operate. The excess heat will then be pumped into the heat store. Once the
temperature has fallen in the boiler and the pump over-run stat is satisfied or the
central heating pump starts to operate, then the hot water pump will stop.
Before firing make sure the baffles have not been dislodged in transit. To achieve
maximum efficiency push the primary heat exchanger baffles in the direction of
the arrows as shown. The secondary heat exchanger spring baffles must be fully
inserted into the heat exchanger tubes (narrow end first).
Page
1.5 Components
5 4
1. Heat Exchanger
3 12
2. Condensing Unit
2 3. Auto Air Vent
4 4. Service Door
5. ‘Dual-Safe’ Thermostat
5 6. Heat Exchanger Baffles
11
6 7. Service Door
8. Service Door Cover
9. Condensate Trap
10. Riello RDB 2.2 Burner
11. Heating Flow Connection
12. Heating Return Connection
7 1
8
10
Page
1.5.3 U-Series Utility – Pumped (UPHE) – Key Components
15 3 1. Heat Exchanger
2. Condensing Unit
5 4 3. Pipework Assembly
4. Pressure Relief Valve
6 5. Auto Air Vent
6. Circulating Pump
16 7. Auto Air Vent
7 8. Service Door
2 9. ‘Dual-Safe’ Thermostat
8 10. Heat Exchanger Baffles
9 11. Service Door
10 12. Service Door Cover
13. Condensate Trap
14. Riello RDB 2.2 Burner
15. Heating Flow Connection
16. Heating Return Connection
11 1
12
13
14
2
3
Page
1.5.5 U-Series Utility – Combi (UCHE) – Key Components
5 1. Heat Exchanger
2. Heat Store
3. Condensing Unit
4. Service Door
5. Pipework Assembly
6 6. Plate Heat Exchanger
7. Twin Head Pump
3 8. Condensate Trap
7 9. Service Door
4
10. Service Door Cover
11. Control Panel
8
12. Expansion Vessel
13. Riello RDB 2.2 Burner
2 14. Heat Exchanger Baffles
(see dimension drawing
for details of connections)
1
9 11
14 10
13 12
Page 10
1.5.7 K-Series Kabin Pak – Casing Components
5
4
1. Boiler Assembly
2. Top Casing (removable)
3. Flue Assembly (removable)
4. Rear Flue Casing
5. Blanking Plug (removable)
6. Rear Casing (removable)
7. Side Casing
8. Front Casing (removable)
Page 11
1.5.8 K-Series Kabin Pak – Pre-Wired (KHE) – Key Components
1. Heat Exchanger
3 12
2. Condensing Unit
3. Auto Air Vent
4 2 4. Service Door
5. ‘Dual-Safe’ Thermostat
5 6. Heat Exchanger Baffles
6 11
7. Service Door
8. Service Door Cover
9. Condensate Trap
10. Riello RDB 2.2 Burner
11. Heating Flow Connection
12. Heating Return Connection
7 1
8
10
15 3 1. Heat Exchanger
2. Condensing Unit
5 4
3. Pipework Assembly
4. Pressure Relief Valve
5. Auto Air Vent
6
6. Circulating Pump
7. Auto Air Vent
7 16 8. Service Door
9. ‘Dual-Safe’ Thermostat
10. Heat Exchanger Baffles
8 2 11. Service Door
9 12. Service Door Cover
10 13. Condensate Trap
14. Riello RDB 2.2 Burner
15. Heating Flow Connection
16. Heating Return Connection
11 1
12
13
14
Page 12
1.5.10 K-Series Kabin Pak – System (KSHE) – Key Components
2
3
1. Heat Exchanger
5 2. Heat Store
3. Condensing Unit
4. Service Door
5. Pipework Assembly
6 6. Plate Heat Exchanger
7. Twin Head Pump
3 8. Condensate Trap
7
4 9. Service Door
10. Service Door Cover
8 11. Control Panel
12. Expansion Vessel
13. Riello RDB 2.2 Burner
2 14. Heat Exchanger Baffles
(see dimension drawing
for details of connections)
1 9 11
14 10
13 12
Page 13
1.5.12 K Series Kabin Pak – Combi (KCHE) – Control Panel
Page 14
2.0 Technical Details
Power
On
YES
NO
Timer Calling
For Heat
YES
NO HW
Selected
YES
NO
YES
NO YES NO
NO
NO
NO
NO
YES Burner
Fires
Page 15
2.2 Dimensions
MODEL A B C D E F G H J K L M N
U~ 865 413 601 666 766 42 104 583 50 75 86 134 21
UP~ 865 413 601 666 766 42 104 583 50 75 86 134 21
US~ 865 413 601 666 766 42 104 583 50 75 86 134 21
MODEL A B C D E F G H J K L M N P Q R S
UC~ 596 865 601 766 134 207 390 841 817 840 845 74 115 167 205 310 666
Page 16
2.2.3 K-Series Kabin Pak (KHE, KPHE & KSHE Models)
MODEL A B C D E F G H J K L M N P Q
K~ 413 900 700 773 210 95 161 67 40 90 40 67 705 50 50
KP~ 413 900 700 773 210 95 161 67 40 90 40 67 705 50 50
KS~ 413 900 700 773 210 95 161 67 40 90 40 67 705 50 50
MODEL A B C D E F G H J K L M N P Q R S
KC~ 600 900 700 772 210 95 161 67 40 90 40 67 705 50 50 396 209
Page 17
2.3 Flue Options, Components & Dimensions
Page 18
2.3.2 Warmflow HE Boiler Flue Components: 80/125 Ø
Note:
1. Flue fitting kit required.
2. If terminal is less than 2 metres above ground level terminal guard must be fitted.
3. Extension pipes and flue adaptor lengths quoted are effective lengths and not the actual length
of the piece.
4. All dimensions in mm unless otherwise stated.
Page 19
2.3.3 Vertical & High Level Terminal Options
15 8.0 5.0
21 8.0 5.0
26 8.0 5.0
30 6.0 3.5
33 4.0 2.5
Note:
1. All flues can utilise any combination of bends, straights, adaptors and terminals.
2. Ensure flue is arranged such that it falls continuously towards the boiler.
3 The Low Level Balanced Flue Kit can use any combination of flue extension pieces up to the
maximum equivalent length depending upon boiler output as illustrated in the above table.
Page 20
2.4 Condensate Disposal
The Warmflow high efficiency condensing boiler is supplied with a factory fitted, self
sealing condensate trap. The trap has been fitted inside the boiler casings to the
right hand side.
The condensate drainage pipe within the boiler is a flexible plastic hose which can
be trimmed to length. 3/4” or 22mm pipe should be connected to the flexible hose.
The pipe should not be made from steel or copper. The drainage pipe may run
into an internal soil stack or waste pipe, an external gulley, hopper or soakaway as
shown below.
The boiler when fully condensing will produce a maximum of 1.5 litres per hour of
condensate. It is recommended that the drainage pipe should have a minimum fall
of 1:20.
Page 21
2.5 Technical Data
Smoke Bacarach 0 0 0
Kerosene Settings
Oil Pump bar 7.0 8.0 8.0 8.0 8.0 7.0 7.0 8.0 10.0
Pressure psi 100 116 116 116 116 100 100 116 145
Max CO2 % 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5
Approx Fuel litres/h 1.65 1.98 2.35 2.35 2.65 2.98 2.98 3.40 3.81
Flow Rate gals/h 0.36 0.44 0.52 0.52 0.58 0.65 0.65 0.75 0.84
Water litres 22 22 22
Content gals 4.8 4.8 4.8
Page 22
2.5.2 U-Series Utility – Pumped (UPHE)
Smoke Bacarach 0 0
Kerosene Settings
Water litres 22 22
Content gals 4.8 4.8
Page 23
2.5.3 U-Series Utility – System (USHE)
Smoke Bacarach 0 0
Kerosene Settings
Water litres 22 22
Content gals 4.8 4.8
Page 24
2.5.4 U-Series Utility – Combi (UCHE)
Page 25
2.5.5 K-Series Kabin Pak – Pre-Wired (KHE)
Smoke Bacarach 0 0 0
Kerosene Settings
Oil Pump bar 7.0 8.0 8.0 8.0 8.0 7.0 7.0 8.0 10.0
Pressure psi 100 116 116 116 116 100 100 116 145
Max CO2 % 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5
Approx Fuel litres/h 1.65 1.98 2.35 2.35 2.65 2.98 2.98 3.40 3.81
Flow Rate gals/h 0.36 0.44 0.52 0.52 0.58 0.65 0.65 0.75 0.84
Water litres 22 22 22
Content gals 4.8 4.8 4.8
Page 26
2.5.6 K-Series Kabin Pak – Pumped (KPHE)
Smoke Bacarach 0 0
Kerosene Settings
Water litres 22 22
Content gals 4.8 4.8
Page 27
2.5.7 K-Series Kabin Pak – System (KSHE)
Smoke Bacarach 0 0
Kerosene Settings
Water litres 22 22
Content gals 4.8 4.8
Page 28
2.5.8 K-Series Kabin Pak – Combi (KCHE)
Page 29
3.0 Electricity Supply & Wiring Details
The boiler/burner and other external electrical equipment should be wired with heat
resistant cable via a fused double pole isolating switch which should be fitted with a
5 amp fuse.
The appliance must be effectively earthed and all external wiring should comply with
current IEE Regulations.
To Burner
Warning: Do not fit any other wires or loop wires to this stat as this will bypass the
thermostats.
Neutral
Earth
Live
CONTROL BOX
535SE/LD Fan
Housing
M
Photoresistance
Motor
Black
Oil Valve White M
Blue
Capacitor
Page 30
BL
ON/OFF
3.3
SWITCHES 1
BR
2
BR BR MAINS ON
W
3 LAMP (GREEN)
CH DHW BL
4 W
P BL
P
5
BR BR LOCK-OUT
6 LAMP (RED)
BK
P BURNER
3.3.1 Wiring Diagram
BL
W
Combi Wiring Details
PCB CONTROLLER BR
BL
TANK 19 7
THERMOSTAT BK
O 20 8
G/Y
TANK LIMIT
THERMOSTAT
21 9
O
C
BK
N.C.
N.O.
Y 22 10
FLOW
C
23 11 EARTH POST
N.C.
N.O.
SWITCH Y
COIL
BK 24 12
C
N.C.
N.O.
25 13
BK BL G/Y
Page 31
26 14
BL
N N
27 15
P W E
DHW BR 28 16 W
PUMP L1 L1
BL 29 17 BR
R
30 18 MAINS PLUG
R
R
BR
BOILER LIMIT
THERMOSTAT P - Purple
O - Orange
G/Y R Y - Yellow
W G R - Red
W - White
CH BR - Brown
G/Y
PUMP BL - Blue
3 2 B - Black
Nc No O O G/Y - Green/Yellow
COM Nc PUMP OVER RUN A1
PUMP OVER G - Grey
THERMOSTAT R R
No 4 COM A2 RUN RELAY LIMIT
EARTH POST
THERMOSTAT
BR BL BOILER LAMP (YELLOW)
Y THERMOSTAT
The 3 pin mains plug must be supplied with a permanent live to allow the pump over-run stat and relay to operate correctly.
WIRING A LOW PRESSURE SWITCH
LOCKOUT
LAMP
(GREEN)
3.3.2 Wiring Schematic
15 7
16 H/L RESET
LAMP N
(YELLOW)
BOILER LIMIT STAT
10
N 23 22 N.O.
1 16 15 7
6 FLOW SWITCH
Page 32
25 24 17
4
COIL
3 19 20 21 NC
E TANK STAT BOILER STAT
PUMP OVER
C
COIL
N N 13 RUN RELAY
C.H. 26 NO
N
12
1 5
18
TRIPLE POLE RELAY
N.O.
N.C. 30 WIRING N
28 C
BLOCK 29
C.H. PUMP
3.3.3 Fitting a Room Thermostat to a Combi
PCB
26 27 28 29 30
N
5
ROOM THERMOSTAT
Remove the purple wire from no 5 and no 28 on the PCB and wire the thermostat
as shown. The room thermostat should be located where it is not subjected to
extraneous heat gains, direct sunlight or draughts.
PERMANENT
LIVE
3 4 5 6
In order to provide frost protection for the fabric of the building a frost thermostat
should be fitted in the coldest room in the house and to prevent over heating of the
property a pipe thermostat should be fitted on the return pipe close to the boiler.
The Kabin Pak Combi boiler is factory fitted with a frost thermostat as standard.
The condensing Combi boilers have been fitted with a pump over-run thermostat.
In order for the thermostat to work effectively the boiler must be supplied with a
permanent live. Failure to do this will result in nuisance trip outs.
Page 33
3.4 Installation of a Warmflow Combi Optional Programmer (PC1)
4. With a sharp knife cut out the outline of the panel knockout through the facia label
from the front of the panel.
5. With a hacksaw blade or snips remove the knockout piece ensuring that all metal
tags or burrs have been removed from the hole.
6. Feed the programmer and harness through the hole from the front of the panel.
7. Secure in position by attaching the securing bracket to the rear of the programmer.
10. Close the control panel cover and reconnect the electrical supply.
11. Using the operational instructions in section 12 or supplied with the programmer, set
the switching times.
Page 34
3.5 Standard Timers for Combis
COM COM
This bypasses the central heating and hot E N L OFF ON OFF ON
water on/off switch.
12
11
If the connection to terminal 12 is not made
the mains on lamp is also bypassed. EARTH
POST
COM COM
EARTH
POST
Page 35
3.6.2 General Requirements
1. The optional programmer as supplied will supply power to the pump and burner via
the central heating channel.
2. When connecting to external controls, eg ‘Y’ plan or ‘S’ plan it will be necessary to
remove the loop between 3 and 12 on the thermal block.
3. Secure control box to the horizontal casing bracket (2 screws) and right hand side
(1 screw).
4. Connect the thermostat, circulating pump and the mains supply to the leads on the
rear of the control box.
5. Two examples of system wiring are shown in section 3.6.4 and 3.6.5 of the manual.
6. When fitting the programmer to a standard utility boiler remove the pump lead from
the box. A spare cable clamp is supplied to connect the new cable from the installer
supplied pump.
8. Close the control panel cover (2 screws) and reconnect the electrical supply.
9. Using the operational instructions in section 12 of the manual or supplied with the
programmer, set the switching times.
Page 36
3.6.4 Honeywell ‘Y’ Plan – Independent CH & DHW (Fully Pumped Only)
Note: Before fitting programmer remove loop between 3 and 12 on the terminal block.
Page 37
3.6.5 Honeywell ‘S’ Plan – Independent CH & DHW (Fully Pumped Only)
Note: Before fitting programmer remove loop between 3 and 12 on the terminal block.
Page 38
4.0 Oil Supply
1. Oil Tank
Steel tanks constructed to BS799 : PART 5 should be painted on the outside only
and mounted on piers to prevent corrosion. Plastic oil tanks are also available and
can be suitable for installation at ground level. However, oil should never be stored in
translucent plastic containers.
The tank outlet should be at a height to provide sufficient clearance to allow for
proper maintenance of any isolation valve oil filter or water separator fitted.
2. The pipe from the oil tank to the burner should be run in copper, steel or aluminium.
Galvanised pipe and fittings should not be used. The pipework should terminate close
to the boiler and be fitted with an isolating valve and filter. It is also recommended
that a remote sensing fire valve should be fitted to the oil line preferably before the oil
line enters the building (BS5410 : PART 1).
Depending on the position of the tank a two pipe system may be required. One and
two pipe oil systems are shown below. As an alternative to a two pipe system a
Tigerloop or other approved de-aerator. may be used.
Total Maximum Pipe Length (m) Note: Plastic oil level gauges may shrink when
Head H(m) 0.5 1 1.5 2 exposed to kerosene thus allowing the ingress of
ID 8mm 10 20 40 60 water. Pump failures due to water contamination
ID 10mm 20 40 80 100 are not covered under the warranty.
Page 39
4.2 Two Pipe System
Page 40
4.4 One Pipe Lift System
Page 41
5.0 Flues
High Level
Balanced
Flue
FLUE TERMINAL
TOP PANEL
OPTIONAL
EXTENSION PIECES FLUE
GASKET
HORIZONTAL
FLUE ADAPTOR
TEST HOLE
PLUG
AIR INTAKE
COVER
RIELLO RDB
BURNER
Low Level
Balanced Flue
Page 42
5.1.1 Installation of a Balanced Flue
1. Make a suitable sized hole in the wall or ceiling for the flue kit. Add the dimensions
given in section 2 as required. The cavities around the opening must be sealed and
protected by a non-combustable sleeve.
3. Break out the required knock out piece in the casing panel for the flue.
4. Carefully fit the inner and out seals to the flue adaptor. After fitting the seals to the
flue smear them with the lubricant supplied.
5. Place the gasket correctly on the boiler and locate the flue adaptor over this, fixing
it in position using the nuts and bolts provided. For the low level flue side outlet
options on white case boilers it will be necessary to manoeuvre the adaptor through
the side panel before fixing it to the boiler after the blanking plate has been removed.
Push boiler into position against the wall.
6. If fitting extension pieces or bends ensure the seals are correctly fitted and lubricated
before pushing through the wall and attaching to the flue adaptor.
7. Slide the flue terminal into position with a twisting movement ensuring that it
protrudes through the wall by a minimum of 175mm and a maximum of 225mm or
through the roof by a minimum of 665mm.
8. Seal the gap between the flue and the wall both inside and out after which the
protective basket must be fitted to the wall over the flue terminal.
9. After removing the air inlet cover fit the air intake adaptor spigot and gasket to the
burner. Connect one end of the air duct to the flue and the other end to the air
intake spigot on the burner. Both ends should be securely fastened with the jubilee
clips.
10. The boiler is now ready to be connected to the plumbing, oil supply and mains
electricity.
11. The side casings of the boilers have been designed with knockouts to allow the oil
pipe and electric cable to pass unnoticed inside the unit.
Note: Where a knockout has been removed ensure that a grommet or cable gland
is fitted to the hole prior to passing any cable through it.
12. A test hole for commissioning purposes has been provided on the secondary heat
exchanger door.
Page 43
5.2 Conventional Flues TERRACOTA POT
Considered good practice
but is not a guarantee of
The flue should be designed in overcoming down drafts
2 metres max
and bottom. The starter piece should
be sealed into the conventional flue TEST POINT
135°
adaptor using a high temperature
silicone sealant, fire cement must not FLUE PIPE BENDS
be used. DO NOT USE 90°
Attention should be given to the position of the flue discharge; we recommend the
following guidelines be adopted.
1. The flue should not discharge beneath opening windows or within 2 metres of other
accesses to the building.
2. The flue should not discharge near internal/external corners of the building where
turbulent wind conditions could occur.
6. The actual siting of the flue should be determined by the installer after consultation
with the householder.
8. Account must be made of the pluming from the flue. If it is likely to be a nuisance
to the householder the use of a vertical balanced flue or conventional flue should be
considered.
Page 44
MINIMUM DISTANCES TO TERMINALS IN MILLIMETRES AS MEASURED FROM
THE TOP OF THE CHIMNEY OR THE RIM OF A LOW LEVEL DISCHARGE OPENING
A Directly below an opening, air brick, opening window etc. 600 600
F From an internal or external corner or surface or boundary alongside the terminal. 300 600
M Above the highest point of an intersection with the roof. 600 600
O Above a vertical structure less than 750mm from the side of the terminal. 600 750
Terminating positions must be at least 1.8 metres distant from an oil storage
tank unless a wall with at least 30 min fire resistance and extending higher and
wider than the tank is provided between the tank and the terminating position.
Page 45
6.0 Air Supply for Combustion & Ventilation
(see BS5410)
When the boiler is sited in a cellar where the only access for combustion and
ventilation air is at high level then the combustion air should be ducted to low level.
Boiler in Room
Boiler in Compartment
Page 46
7.0 Installation Requirements
The boiler installation must be in compliance with BS5410 : PART 1 and the Building
Regulations.
7.1.1 Hearth
The boiler hearth temperature is between 50°C and 85°C and should be stood on
a rigid, non-porous, non-combustible base, which is not softened by warmth, to
comply with the Building Regulations.
24” (600mm) Clearance should be provided above and in front of the boiler to allow
for routine servicing.
The heating system should be installed to HVCA current codes of practice. Before
installing the boiler the new or existing system should be thoroughly flushed to clear
all sludge or other foreign matter such as solder, steel wool and copper fillings. We
recommend that the system is cleaned out in accordance with BS5449 and BS7593
using a suitable non-corrosive commission cleanser. It is further recommended that
a suitable corrosion inhibitor is added to the heating system, which will not damage
the synthetic rubber parts within the boiler.
In addition to any factory fitted air vents it is recommended that another air vent is
fitted at the highest point in the system. Where the flow pipework drops down from
the boiler the installer must ensure that an automatic air vent is fitted to the top of
the pipework to prevent air being trapped in the boiler.
Drain cock(s) should be fitted to a bottom connection on the boiler and to the lowest
points in the system to enable the system to be fully drained.
Where there is a risk to the boiler or installation from frost then a suitable frost
thermostat should be fitted. Alternatively the system could be dosed with an anti
freeze agent. The Kabin Pak Combi boiler is factory fitted with a frost thermostat as
standard.
All connections to the appliance should be made with compression fittings, with the
last 600mm of the primary flow and return pipework made from copper.
Page 47
7.2 Sealed Systems
A 12 litre expansion vessel charged to 0.5 bar is supplied with both the system
and Combi boiler. This can accommodate a maximum combined boiler and system
volume of approximately 150 litres. If this volume is exceeded an additional vessel
will be required. Refer to BS7074: PART 1 or BS5449 for details of sizing. The
values given in the table are for total system values which includes the primary water
capacity. See page 12 and 13.
VESSEL VOLUMES
0.5 2.1 4.2 6.3 8.3 10.5 12.5 14.6 16.7 18.7 20.8 22.9 25.0
Initial Charge
1.0 2.7 5.4 8.2 10.9 13.6 16.3 19.1 21.8 24.5 27.2 30.0 32.7
1.5 2.9 7.8 11.7 15.6 19.5 23.4 27.3 31.2 35.1 39.0 42.9 46.8
Total System
Volume 25 50 75 100 125 150 175 200 225 250 275 300
The pressure in the vessel(s) should be checked annually during the normal boiler
service by fitting a gauge to the schrader valve on the vessel. Ensure the system
pressure is at zero to ensure an accurate reading.
As standard, a filling point complete with a filling loop has been included within
the appliance. The temporary hose must be disconnected after filling. A system
pressure when cold of 1 bar is recommended. After filling, vent all air from the
system. Ensure the caps on the automatic air vents are loose or removed and bleed
both circulating pumps.
Water loss from the system as indicated by a reduction in pressure on the pressure
gauge may be made up through the filling loop. In the first week of operation it is
normal to see a drop in system pressure. After this time the system pressure must
be rechecked and the system refilled. Failure to do so may lead to boiler faults.
Any pressure relief valve fitted to the boiler or system must be able to discharge
externally to a drain where the discharge can be seen but cannot cause any injury
or damage. No other valves should be positioned between the relief valve and
discharge termination.
Where there is a catastrophic loss of water from the system the boiler thermostats
may fail to operate which would result in serious damage to the appliance. To prevent
this it is recommended that a low pressure cut out switch set at 0.2 bar is fitted to
the system and wired in series with the boiler limit thermostat (see page 16).
Page 48
7.3 Combi Domestic Hot Water
To reduce the likelihood of leaking joints the mains water supply pressure must not
exceed the factory test pressure of 5 bar. If the mains water pressure exceeds 2 bar
then a pressure reducing valve must be fitted. The final 600mm of the mains supply
pipe to the appliance must be in copper. The flow rate of water from individual taps
is dependant on the number of outlets being operated together, as well as the
length and size of pipework in the system and the mains supply pressure. Whenever
a pressure reducing valve or any other device containing a non-return valve is fitted
to the mains water supply pipe entering the boiler, it is recommended that a mini
expansion vessel, suitable for use on potable water, is fitted between the device and
the closed tap.
Although many of the DHW components are designed to resist lime scale formation,
in areas of hard water it may still be necessary to fit an inline chemical water softener.
For further information contact Warmflow and your local water company.
To ensure economic use, the pipe runs between the boiler and the taps should be as
short as possible and insulated to reduce heat loss. For boilers that have to be sited
remotely from the main point of use, there is likely to be very long pipe runs which
can lead to excessive water usage and poor fuel efficiency. It is recommended that
a pumped hot water return is used in order to improve HW reaction times. Contact
Warmflow for details.
7.3.5 Boreholes
Where the mains water supply to the boiler is fed from a borehole via a pump and
accumulator arrangement the variable pressure can cause the mixer valve to go to
its fail safe settings thus preventing the outlet water temperature from achieving a
suitable level. In order to minimise the pressure variations it is recommended that
differential on the borehole pump pressure switch is kept as low as possible without
adversely affecting the pump motor. The accumulator must be as large as possible
in order to reduce the rate of pressure change and a pressure reducing valve (PRV)
must be situated between the pump and accumulator and the boiler. The PRV must
be set slightly below the minimum setting of the pressure switch on the pump.
Page 49
8.0 Burners
The burner is fitted with the correct nozzle and the pressure set. All that is further
required before commissioning, is to connect the oil and electricity supply.
The burner is supplied for use with a one pipe system. For use on a two pipe
system, it is necessary to remove the return port plug and fit a small by-pass plug as
shown.
1. Suction Line
2. Return Line
3. By-Pass Screw
4. Gauge Connection
5. Pressure Adjuster
6. Suction Gauge Connection
7. Valve
8. Auxiliary Pressure Test Point
The boiler control equipment and the burner are provided ex works, it is only
necessary to connect a 230V 50Hz supply in accordance with the electrical
drawings.
Page 50
8.4 Electrode Setting
Motor
Ignition Transformer
Valve
Flame
Lock-Out Lamp
~ 12s ~ 12s ~ 5s
The air damper is set in factory. This regulation is purely indicative. Each installation
however, has its own unpredictable working conditions: actual nozzle output;
positive or negative pressure in the combustion-chamber, the need of excess air,
etc. All these conditions may require a different air damper setting.
Air Damper (A) – 15/21 Burner Only Air Damper (B)
Air Damper (A) – The main air damper can be set in Air Damper (B) – The purpose of
either of two positions. To set the positions of the damper, this damper is to perform a fine-
proceed as follows: Remove the secondary air damper (B) tuning of the inlet air. Tuning of this
loosening the screws (1). Loosen the screw (2) and rotate device is possible by turning the
the main air damper (A) to the required position. Retighten screw (3).
the screw (2) and put back the secondary air damper (B).
Page 51
9.0 Commissioning & Servicing
9.1 Commissioning
Note: It is the responsibility of the installer to ensure that the boiler is properly
commissioned by an OFTEC trained and registered technician. Failure to do
so WILL invalidate ALL warranties.
Combustion tests must be carried out using a Combustion Analyser. The pump
pressure can be checked by fitting a manifold and a pressure gauge to the oil
pump.
Before firing ensure that all the baffles are in place as they may have been displaced
during transit as shown on page 7. Switch the boiler on, ensuring all controls are
calling for heat. Typical burner settings and test data are shown in section 2.5.
Check the smoke reading, CO2 content and flue gas temperature with the boiler up
to temperature. Testing while the boiler is still relatively cold gives inaccurate results
and leads to incorrect adjustments being made.
Where a balanced flue has been fitted ensure the air duct connecting the flue and
burner has been properly connected before commissioning.
9.2 Servicing
Additionally when servicing special attention should be paid to the condition of the
oil nozzle, flexible oil line, fuel filter, door insulation, sealing rope and secondary heat
exchanger door seal, if found defective they must be replaced.
Note: Second year or other extended warranties will be invalidated if the appliance
is not serviced annually by a Warmflow or OFTEC trained and registered
technician.
Page 52
YES Lock Out NO Lock Out after YES YES Pump YES YES Combustion YES Combustion
Burner Ignition Nozzle
Motor Runs within 12 second Spark Proved Produces Atomising Fuel Air Set Head Set
1 second purge Pressure Correct Correct
10.1 Riello RDB
NO NO NO NO NO YES
NO NO NO NO NO NO
Check Replace Motor Replace the Drive Coupling Replace the Contaminated Boiler or Flue
Boiler Controls Capacitor Control Box Broken Coil and/or Fuel Filter Blocked
Stem Valve
NO
Page 53
Repair or
Replace Oil
Pump
If B/F
Motor gives YES Coil of YES YES application
Photo Cell Replace
50 Volts to Solenoid remove burner
Functional Control Box
White Wire Functional snorkel tube
and retest
NO NO NO OK
Switch on power,
set selectors
for CH on and
DHW off.
Check boiler
YES Is lockout lamp Does boiler NO
thermostat,
Refer to burner on burner or cycle on its
fault finding. replace if
panel lit? thermostat? necessary.
NO
NO
Is there continuity
Check wiring, NO across the boiler
replace boiler stat connections
thermostat. 17 and 18 on the
PCB?
YES
Is there continuity
Check relay and NO across the
PCB, replace if connections
necessary. 28 and 30 on
the PCB?
YES YES
Check power
from clock or HEATING IS
switch, check WORKING
wiring fuses and NORMALLY
mains supply.
Page 54
11.2 Domestic Hot Water
Switch on power,
set selectors to CH
off and DHW on.
NO Is there continuity NO
Is DHW pump Check wiring, replace
working? across connection 20 tank thermostat.
and 21 on the PCB?
YES YES
NO
Is there continuity Check wiring, replace
across 25 and 27? relay, replace PCB.
YES
Check wiring,
replace pump.
NO NO
NO YES
NO YES
NO
Check wiring, replace Is there continuinity With tap closed, switch
tank limit stat. across 23 and 22? the CH switch to on.
YES
NO NO
Check wiring, replace Is there continuinity
relay, replace PCB. across 22 and 16? Do radiators get hot? Check CH fault finding.
YES YES
YES
YES
BOILER IS WORKING
NORMALLY
Page 55
12.0 Optional Boiler Mounted Digital Timer
When you first install the Cr2032 battery (by removing the clear plastic strip from the
rear of the timer) you must press the ‘RESET’ button, the LCD display will display
fully for 3 seconds. Then LCD display will change to ‘5:2d’. You can press DAY
button to select ‘7d’, ‘24H’ programme mode.
When you finalise the setting, press the CLOCK button for normal operation.
Page 56
12.1.2 Built in Programme
For convenience, the timer module has a built in programme, however, it can be
easily adjusted (see section 12.5 To Change the Programmes).
AUTO: To run your time schedule for period one or two or three each day.
1. Press and hold CLOCK button then press DAY button to select current day
of the week.
2. Press and hold CLOCK button then press HOUR button until the correct
hour is displayed.
3. Press and hold CLOCK button then press MINUTE button until the correct
minute is displayed.
Page 57
12.1.5 To Set Programme Period
Press and hold DAY button and press MIN until the correct programme period is
displayed.
Press TIMER button each time to toggle through the ON and OFF settings.
1. Press TIMER key repeatedly until the particular ON or OFF time appears.
2. Press HOUR button and MINUTE button to set new ON or OFF time.
Page 58
12.1.8 Manual Select
This function is only applicable when your timer is set on AUTO mode.
You can temporarily override the normal switching times by pressing the ADV key.
The temporarily override won’t affect the normal programme after execution of the
override.
4. To cancel override by pressing CH ADV or HW ADV and the ‘AUTO’ will stop
flash.
2. You now have approx 5 second to enter desired length of time by pressing
CH ADV or HW ADV key once for each hour the new time set should be in
affect.
3. The MANUAL HOUR function will bring the unit ON 1 hour to 3 hours in the
OFF mode.
4. The MANUAL HOUR function will bring the unit OFF 1 hour to 3 hours in the
ON mode.
6. The MANUAL HOUR function will bring the unit ON 1 hour to 3 hours in off,
clock will count down immediately.
7. When MANUAL HOUR function will extend by 1 hour to 3 hours while ON,
clock will count down after the programmed ON is finished.
Press CH ADV or HW ADV button again the LCD display and switching status will
return to normal.
Page 59
13.0 Spares
No CODE 3514157 3514257 3514557 DESCRIPTION No CODE 3514157 3514257 3514557 DESCRIPTION
1 3008512 • • • Gasket 15 3000439 • • • Pump Seal
2 3006384 • • • Flange 16 3008654 • • • Pump
3 3002551 • Cup-Shaped Head 17 3007162 • • • O-Ring
3 3001079 • Cup-Shaped Head 18 3008653 • • • Filter O-Ring
3 3020055 • Cup-Shaped Head 19 3003602 • • • Connector
4 3008860 • • • Electrode Assembly 20 3005720 • • • Flexible Oil Line
5 3008875 • • • Screw 21 3008644 • • • Tube
6 3008861 • • • Nozzle Holder 22 3008876 • • • Pressure Gauge
7 3008862 • • • Collar 23 3000443 • • • Joint
8 3008794 • • • High Voltage Lead 24 3008648 • • • Coil-Shell & Knob
9 3008647 • • Air Damper Assembly 25 3008650 • • • Motor
9 3008839 • Air Damper Assembly 25 3002836 • • • Motor & Capacitor
10 3005788 • • • Fan 26 3008649 • • • Protection
11 3007541 • • • PE Cell 27 3008652 • • • Control Box 535RSE/LD
12 3002837 • • • Capacitor 4.5µF 28 3008851 • • • Lead Coil
13 3007582 • • • Needle Valve 29 3008879 • • • Cover
14 3008651 • • • Regulator 30 3008878 • • • Kit Seals
Page 60
13.2 Pipe Spares
Page 61
13.3 Short Parts List – Boiler
When ordering replacement casing panels it should be noted that due to the painting
process there may be some variation in colour.
Page 62
14.0 Your Guarantee, Terms & Conditions
The boiler, including all controls, plate heat The boiler must be installed, commissioned
exchangers and associated equipment and serviced in accordance with the
contained within the boiler casing, the installation instructions supplied with the
burner and flue system if supplied by boiler.
Warmflow against defective parts and faulty
workmanship, for period of 12 months Warmflow will accept no liability for the cost
from the date of installation, providing of repairs resulting from incorrect installation,
the boiler is installed and commissioned inadequate commissioning, lack of regular
in accordance with the installation maintenance, misuse, tampering or repair
instructions supplied with the boiler. The by unqualified persons.
period of guarantee will be increased to 24
months providing: All repairs must be authorised in writing by
Warmflow prior to any work being carried
• The guarantee registration form is fully out. Unauthorised claims are not covered by
completed and returned to Warmflow the guarantee.
within 30 days from the date of
installation, or 90 days from the date If the boiler has not been installed within
code stamped on the appliance. 3 months from the date of despatch from
Warmflow, then the warranty will deem to
• The boiler must be installed and have started.
commissioned by a Warmflow or other
competent engineer, who is OFTEC Labour charges associated with the
registered. Commissioning of the boiler replacement of heat exchangers or thermal
must be completed immediately after heat stores will be calculated on a sliding
the boiler is installed. scale depending on the boiler output up to a
set maximum. Contact Warmflow for current
• The boiler must be serviced by a prices.
Warmflow or other competent engineer,
who is OFTEC registered, 12 months Faults and any associated costs occurring
after the date of installation and due to lack of fuel, power, water supply or
thereafter, at 12 monthly intervals. scale formation are not covered by these
guarantees.
NOTE: In Northern Ireland and the
Republic of Ireland the period of Claims for consequential loss or damage are
guarantee can only be increased to not covered by these guarantees.
24 months through the purchase of an
extended warranty. In the event of a breakdown please
contact your commissioning engineer
The water jacket and thermal store (in the who should then contact our service
case of a combination boiler) for a total department whilst at your home, to
of 5 years from the appliance date code, report the fault.
subject to the above conditions being
complied with. The statutory rights of the customer are not
affected by the guarantee.
Warmflow reserves the right to repair or
replace components within the guarantee NB: The nozzle supplied with the boiler is
period at a time and location that is most deemed to be an expendable item and is
convenient to the company. therefore excluded from the guarantee.
Page 63
Commission/Service Record Boiler Serial No |__|__|__|__|__|__|__|__|
In order that your boiler gives you many years of economical trouble free use and to validate the
warranty, this boiler must be commissioned upon installation and serviced annually. Contact Warmflow
for an approved engineer within your area.
ON
Date of Commission ______________________ Date of 1st Service ______________________
I 1
S CE
Company Name ______________________ Company Name ______________________
Engineer Name
M IS
______________________ Engineer Name
RV I
______________________
Engineer Signature
Telephone No COM
______________________
______________________
SE
Engineer Signature ______________________
Telephone No ______________________
Telephone No
SE
Engineer Signature ______________________
______________________ Telephone No
SE
Engineer Signature ______________________
______________________
Telephone No
SE
Engineer Signature ______________________
______________________ Telephone No
SE
Engineer Signature ______________________
______________________
Telephone No
SE
Engineer Signature ______________________
______________________ Telephone No
SE
Engineer Signature ______________________
______________________
S E
Engineer Signature ______________________
S E
Engineer Signature ______________________
Telephone No ______________________ Telephone No ______________________
Page 64
YOUR DETAILS
Email Address
|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|
House Number/Name/Street
|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|
Town/City
|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|
County Postcode
|__|__|__|__|__|__|__|__|__|__|__|__|__| |__|__|__|__|__|__|__|__|
PRODUCT DETAILS
(found on warranty label located on the front or inside front of the appliance)
TEAR ALONG PERFORATION
Date of Installation
|__|__|__|__|__|__|__|__|
NAME OF INSTALLER
To help keep your details accurate we may use information we receive from our partners. You can ask for a copy
of your details (for a small fee) and to correct any inaccuracies. To make sure we follow your instructions correctly
and to improve our service we may monitor or record our communications with you. Please note that failure to
provide some or all of the information requested does not affect your statutory rights but may affect the quality of
the service provided.