Beruflich Dokumente
Kultur Dokumente
QualityControl
Field Manual
1-877-234-5268
www.ceilcotecc.com
TABLE OF CONTENTS
Chapter 1 ……………………………………………………..Introduction
1.1. SCOPE
1.1.1. This Quality Control Manual outlines the functions and duties of QC personnel at
lining/coating jobsites where a Quality Control Program is established to monitor
field activities. Information contained within this manual describes the reporting,
inspection, documentation and testing procedures established to adequately
promote an effective Quality Control/Quality Assurance Program.
1.2. OBJECTIVE
2.1 QUALIFICATION
Field QC/QA personnel will be approved by Ceilcote. They shall be experienced and
knowledgeable of the standard installation and testing practices in the corrosion
resistant lining/coating industry.
2.2 REPORTING
Field QC/QA personnel shall report directly to the Ceilcote Quality Control Supervisor.
2.3 RESPONSIBILITIES
Field QC/QA personnel will perform all visual and physical tests and inspections as
required by the appropriate Ceilcote Bulletins, Specifications and Quality Control
Procedures. These tests and inspections will be conducted in a thorough professional
manner to insure installation compliance. Responsibility for the acceptance or the
rejection of any work is a QC/QA function. Conflicts regarding the interpretation or
determination of work quality, environmental conditions, acceptability of substrates,
application methods and techniques, materials and record keeping will be reported
directly to the Field Foreman/Superintendent and Ceilcote’s Quality Control Supervisor.
Ceilcote’s Management and R&D Department must approve in writing all deviations
from procedures, methods, interpretations, testing and standard practices prior to their
implementation. Field QC/QA will remain independent of the installation crew in the
performance of their duties.
3. INSPECTION FORMS
3.1 NON-CONFORMANCE REPORT
This form is used to document conditions, work or areas that are unacceptable to any
work process. The discrepancy noted on the report should specify the exact procedure,
specification or other governing data that supports the stated non-conformance. Non-
Conformance Reports should be preceded with an inspection report that lists a
discrepancy. The Non-Conformance Report is issued if the discrepancy is not
adequately corrected after a sufficient amount of time has been allowed for the
correction. A copy of this form is contained within this Chapter as Supplement “A”.
This form is used to note the date, acceptance and exceptions, if applicable, for the
release of equipment for lining/coating application. Parameters of work and the
appropriate Drawing Numbers should be stated on the form. Equipment Inspection
Reports and/or Non-Conformance Reports could be incorporated into this report or
separate reports should be used to supplement this form to indicate appropriate
information. A copy of this form is contained within this Chapter as Supplement “B”.
The item(s) listed below are in non0conformance to (specifications) (procedures) (other) ____
Comments:
cc:
EQUIPMENT ACCEPTANCE REPORT
DATE: _________________________ CEILCOTE JOB NO.: ________________________
___________________________________________________________________________
___________________________________________________________________________
________________________________________
FIELD SUPERINTENDENT, FOREMAN, QC
________________________________________
AUTHORIZED CUSTOMER REPRESENTATIVE
CHAPTER 4
4. PRE-WORK INSPECTION
4.1.1 Pre-Work Inspections of substrates in work areas shall be completed prior to the
start of the lining/coating application in the areas. These inspections will be
documented on the Equipment Acceptance Report with all results and findings
stated on the report. This form is Supplement “A” in Chapter 3. Areas that are
inaccessible to inspection, (ie lack of scaffold, no lighting, beneath water, no
entry permit etc.) shall be noted on the Inspection Report with an explanation of
the inaccessibility. Inspection of these areas shall occur when access is
available and all results and finding shall be stated on an inspection report.
4.2.1 Steel and Alloy substrate inspections shall conform to ASTM, STP837- Manual of
Protective Linings for Flue Gas Desulfurization Systems, Chapter 4 - Design and
Fabrication of System Components. This Manual, Supplement “A” in this Chapter
4, contains the guidelines for acceptable steel substrate conditions, welds,
appurtenances, gouges, stampings, structural members and nozzles and
Ceilcote’s CPT-2 “Steel Substrate Specification to Receive Monolithic lining”.
4.3.2 Established inspection guidelines shall be reviewed prior with all concerned
parties prior to all inspections.
4.4 EXCEPTIONS
4.6.1 All additional Inspection Requirements beyond the control documents above shall
be stated as an addendum to the appropriate section before implementation.
CHAPTER 4
SUPPLIMENT “A”
March 2006
********************************************************************************************
1. This document has been prepared to assist specifiers in the preparation of steel
substrates for Ceilcote Corrosion Control Products.
2. This specification defines the necessary practices for surface preparation of steel
tanks and other steel equipment.
********************************************************************************************
CPT-2
STEEL SUBSTRATE
SPECIFICATION TO RECEIVE
MONOLITHIC LININGS
The specification information below is intended for use by architects, engineers or other
specifiers in defining the criteria needed for acceptable substrates.
1.0 MATERIAL
1.1 Material shall be new full weight carbon steel that is free from laminations or
other physical imperfections.
2.0 CONSTRUCTION
.1 Tanks and other steel structures shall be of welded construction and shall
be fabricated, in accordance with standard commercial practices to obtain
an economical product of uniform quality.
2.2 Design
.1 When steel plates, are stiffened with "I" beams, angles, channels or buck
stay, the stiffening members should be welded to the exterior steel
surfaces if possible.
.1 All closed tanks or vessels shall be fitted with at least one (1) manhole or
manway at least 12 inches by 20 inches or 18 inches in diameter.
.1 Tank nozzles shall be flanged design where possible and should be over 2
inches in diameter. Threaded nozzles should be avoided. Flanged
nozzles 2 inches and greater in diameter shall have maximum length in
accordance with the following schedule:
3.0 WELDING
.1 All welds shall be ground to remove all sharp edges, laps, undercuts and
other surface irregularities and projections. All weld splatter shall be
removed. Chipping, may be utilized if followed by grinding for finish.
.1 All sharp edges and fillets, and similar abrupt contours shall be rounded
off, be grinding or machining to a 1/8" minimum radius. A 1/4" radius at
fillets or changes in contour is preferred.
4.1 Removal
.1 Internal components such as heating coils, which are not lined, shall be
removed (if possible) from the tank prior to the lining operation.
CPT-2
STEEL SUBSTRATE
SPECIFICATION TO RECEIVE
MONOLITHIC LININGS
5.0 TESTING
6.0 CLEANING
Any dirt, grease, oil, chemical, corrosion products or other foreign materials, which
cannot be removed by sandblasting, shall be thoroughly; cleaned from the surfaces to
be lined by the tank fabricator.
CHAPTER 4
SUPPLIMENT “B”
AND
October 2004
********************************************************************************************
********************************************************************************************
CS-10
QUALITY OF CONCRETE SURFACE
GUIDELINE SPECIFICATION
The specification information below is intended for use by architects, engineers, or other
specifiers in defining the criteria needed for acceptable substrates.
1.0 SCOPE
1.1 This specification defines the quality of the concrete surface required for the
application of Ceilcote tank linings and coatings.
1.2 This specification covers a new concrete only.
2.0 DISCUSSION
2.2 Two basic types of concrete surfaces are present in all tanks:
.1 The floor, which is cast as a slab, may have laitance on the surface
(a skin of under cured concrete) or a curing membrane.
.2 The walls, which have had their initial cure under a form, are less
likely to have laitance or under cured cement. Almost invariably the
walls will contain air pockets or voids. Formed surfaces may have
form release agents or retarded cement, which may produce a
bond breaker to any applied lining or coating.
3.1 Appearance: The following defects must be repaired before the lining can
proceed:
Air Pockets
Pinholes Indicating Hidden Air Pockets
Tie Holes
Form Burrs
Honeycombs
Cracks, Cold Joints, Control Joints
3.1.1 These defects may be corrected by the contractor; refer to Ceilcote
Recommended Practice Number CP-11
3.2 Surface Tensile Strength: Floors and walls must be free of the following
contaminants that affect the surface strength of the concrete:
Form Oils
Curing Sealer
Soft Concrete
Laitance
March 2005
********************************************************************************************
1. This document has been prepared to assist specifiers in the repair and
preparation of concrete for Ceilcote Corrosion Control Products.
2. This specification defines the necessary practices for preparing of the concrete
surface.
********************************************************************************************
CP-11
REPAIR AND PREPARATION
OF CONCRETE FOR LINING
The specification information below is intended for use by architects, engineers or other
specifiers in defining the criteria needed for the repair and installation of the concrete before
application of the lining system.
1.0 SCOPE
1.1 This is recommended practice for preparing concrete surfaces to comply with
Ceilcote Construction Specification Number CS-10.
1.2 This practice is for new or old concrete surfaces to receive Ceilcote Linings or
Coatings.
1.3 This recommended practice is published to provide the user of Ceilcote products
with information concerning repair methods that have been employed with
success in past installations. Its publication does not constitute a warranty of any
sort by CEILCOTE.
Whether or not the concrete is blasted, the holes should be filled before
lining, particularly if sun will shine on surface during lining or coating.
.2 Cement does not bond well to cured concrete; the lining may pull it loose
from base concrete due to shrinkage of the repair concrete.
CP-11
REPAIR AND PREPARATION
OF CONCRETE FOR LINING
.3 Cement does not cure well in thin layers, resulting from filling small air
pockets; thin sections tend to dry out before they hydrate producing poor
surfaces for bonding.
Again, our lining may pull this poorly cured cement from the concrete
surface.
.1 These are the preferred repair materials and are available from Ceilcote.
Type S-11 Powder is the base for filling compounds. Prior to lining with a
polyester type lining, the S-11 Powder is mixed with Ceilcote 380 Primer
and troweled on. If the lining is to be epoxy, the S-11 Powder is mixed
with 680 Primer.
.1 Mix hardener and liquid together for at least 1 minute with a powered
beater.
.2 Add the powder and mix until a smooth thixotropic paste is formed. The
proper consistency should not fall from a trowel at a thickness of 1 1/2"
and should trowel like whipped butter. More or less powder may be used.
.3 Use the trowel like a squeegee, stroking in four directions so all holes
become filled even with the surface of the concrete. Only a very thin film
should remain on the concrete, and this can be the primer for linings that
do not require spark testing.
.4 Allow to dry (8-12 hours depending on temperature) and then inspect for
partially filled holes. They must be filled with an additional paste.
CP-11
REPAIR AND PREPARATION
OF CONCRETE FOR LINING
Ceilcote 380 Primer/Liquid - 1 gal Hardener No. 2 - 3 fl. oz. Type S-11 Powder -
2 gal (approximately 9-14 pounds). Ceilcote 310 Ceilpatch can also be used.
.2 Add the powder and mix until a smooth thixotropic paste is formed. The
proper consistency should not fall from the trowel at a thickness of 1 1/2"
and should trowel like whipped butter. More or less powder may be used.
.3 Allow to cure (8-16 hours depending on temperature) and then inspect for
missed voids. Apply more fill if necessary.
.4 Allow to dry (4-8 hours depending on temperature) and then inspect for
partially filled holes or shrinkage cracks. Shrinkage cracks may form in
larger voids; they must be filled with an additional application of paste.
2.7 Cracks
After the lining has cured, the strip is covered with at least two layers of 1
1/2-oz. glass mat impregnated with a resin compatible with the lining and
resistant to the environment. The overlay must bond 3" onto the lining on
each side of the strip.
.1 Water may seep through porous concrete, especially if there are sections
of honeycomb. A tank properly waterproofed on the exterior will not leak.
If this has not been done and leakage occurs, there are two methods that
may stop it:
.2 Hydraulic Cement Method: Chip out a substantial "V" groove in the area of
leakage and pack it full of fast setting cement.
This method is not a sure remedy. After pumping has stopped more leaks
may show up. If the water table is very high, it may not be possible to
guarantee results with the lining even though lining was applied while
concrete was dry. Dryness of the concrete should be tested with a rubber
mat or plastic film covering the surface for 8 hours starting early morning,
without a sign of condensation on the underside, before proceeding with
lining.
CHAPTER 5
5. SURFACE PREPARATION VERIFICATIONS
5.1.1.1 The compressed air supply should be checked for the presence of
contaminants in the air stream to determine air purity. Testing of the air
supply at initial start-up should be accomplished to evaluate and
establish acceptable air purity for the compressed air prior to actual
work start-up. If moisture is present in the air stream water traps and
moisture filters should be installed just before the blasting pot to remove
the water. Oil removing coalescer filters may also be installed to
remove oil mists if they are present in the air stream. Pressure tests of
the air stream should be taken periodically to assure that the air
pressure into the blast pot and at the nozzle is adequate.
5.1.4.1 Humidity and dew point measurements shall be taken at the start of
each work shift and at established intervals thereafter to verify
acceptable standards and minimum. Environmental conditions, dew
point, humidity and temperature requirements are contained in the
appropriate Ceilcote Installation/Specification. Environmental
conditions measurements are obtained per ANSI/ASTM E-337 found in
this chapter as Supplement "C". Deviations to these restrictions may
occur with some abrasive blasting operations on steel steel/alloy
substrates particularly when previous linings/coatings are being
repaired and/or replaced.
5.1.5 PRIMING
5.3.1 Q.C. personnel will record and maintain the following documentation
records for abrasive blast cleaning.
1.) Environment conditions of the work areas for steel steel/alloy substrates only.
2.) Abrasive blasting dates of the areas cleaned.
3.) Surface profile measurements of the blast cleaned areas for steel steel/alloy
substrates only.
4.) Priming dates of all blast cleaned areas.
5.) Batch number placement of the primer.
March 2005
********************************************************************************************
1. This document has been prepared to assist specifiers in the proper procedures
needed to prepare concrete for Ceilcote Corrosion Control Products.
********************************************************************************************
CP-14
SURFACE PREPARATION
OF CONCRETE FLOORS
The specification information below is intended for use by architects, engineers or other
specifiers in defining the criteria needed for proper surface preparation.
NEW CONCRETE
1.1 Discussion: During the finishing operation water-rich cement rises to the
surface. When this cement dries, it leaves a weak and powdery film called
laitance. This film must be removed so the floor topping can bond to the stronger
composition of cement paste and sand below.
1.2 Finishing Methods: The preferred finish is "once over" with steel trowel. This
method provides the strongest, most uniform concrete surface. Screed, broom or
wood float finishing is not as desirable since they may leave an irregular surface;
often too weak for suitable surfacing.
1.3 Surfacing Curing and Hardening Treatments: Do not use these unless they are
compatible with the surfacing; they may reduce adhesion of the surfacing and
may require subsequent mechanical removal.
1.4 Concrete Cure Time: It is best to cure new concrete 28 days prior to applying a
monolithic topping. This is not always practical and exceptions can be made.
.3 The major problem with curing is the water content. This can be checked
by taping a 1' square of polyethylene or other clear film to the floor. If
condensation appears on the underside of the film within 8 hours, the
concrete is not dry enough.
CP-14
SURFACE PREPARATION
OF CONCRETE FLOORS
2.3 Shot blasting: This mechanical preparation propels steel shot at a high velocity
onto a surface. It is a self-contained system with a vacuum, which minimizes
dust.
2.4 Water Blasting: Utilizing high pressure, low water volume may also be employed
when dust or grit is a problem.
OLD CONCRETE
1.0 DISCUSSION
It is important to know the history of existing concrete. This should include not only the
chemicals to which it has been exposed but also construction details: Is concrete
poured directly on soil or clay or is there a sand or gravel bed? Is there a vapor barrier?
How far under the floor is the water table? Answers to these questions may influence
the type of surface preparation used.
2.0 CLEANING
2.1 To determine if contamination is present on concrete, perform a spot test with a
1: 1 solution of hydrochloric acid and water. If the acid foams, proceed to section
2.2. If it does not foam the concrete is either contaminated or covered with a
sealer. If contaminated, scrub with solvent (1, 1, 1 Trichloroethane,
perchlorethylene or naptha can be used in conjunction with an industrial
detergent) and then spot test again. It may be necessary to remove
contaminated concrete exposing sound substrate.
2.2 Abrasive blasting is the recommended method for substrate preparation. If dust
is a problem, wet abrasive blasting may be used. Note that concrete must be dry
before application of polymer system. Enclosed portable blast units such as
"blastrac" are now available on a local basis which can be leased, rented, or
purchased to accomplish such a task without a great deal of dust.
CP-14
SURFACE PREPARATION
OF CONCRETE FLOORS
Concrete that is badly saturated with oils, caustics, or sugars must be removed and
replaced with new concrete. The new concrete must be bonded with an adhesive such
as Ceilcote's 17 Adhesive and, after curing, prepared as new concrete.
4.1 There are four possibilities for leveling the floor to original grade. The choice may
be governed by economics or time.
5.0 CRACKS
Treatment of cracks depends on several factors: size (both length and width) and
expected temperature variations. Narrow, short cracks in areas with little temperature
variation can usually be covered with a layer of fiberglass before topping. Larger cracks
that are expected to move can sometimes be bridged with glass that is disbonded one
or two inches on each side of the crack, then topped. Very large cracks may be treated
as expansion joints according to Ceilcote's Construction Practice CP-16 and Ceilcote
Construction Specification CS-15.
CHAPTER 5
SUPPLIMENT “B”
Easy to use, place the Comparator against an area of the test surface, compare in turn the four
sectors of the Comparator against the test surface using the X7 magnifier, placed so that the
test surface is viewed simultaneously with a segment of the Comparator, the nearest profile to
the Comparator determines the grade.
The different grades are defined as follows. Fine grade profiles equal to segment 1 and up to
but excluding segment 2, Medium grade profiles equal to segment 2 and up to but excluding
segment 3 and Coarse grade profiles equal to segment 3 and up to but excluding segment 4.
Supplied in a Protective Wallet.
Part Numbers
R2006 - ISO Surface Roughness Comparator (Grit)
R2007 - ISO Surface Roughness Comparator (Shot)
RA001 - X7 Illuminated Magnifier
CHAPTER 5
SUPPLIMENT “C”
ENVIRONMENTAL CONDITIONS
Attached is ANSI / ASTM E-337, which outlines the techniques andrequirements to determine
relative humidity and dew point temperatures in determining environmental conditions.
Surface Thermometer
Elcometer 113 Magnetic Thermometer
The Elcometer 113 Magnetic Thermometer indicates the surface temperature of steel and
other magnetic materials continuously.
The thermometer is based on a bimetallic strip and therefore does not require batteries. It is
available in four scale ranges.
A- Customer’s name
B- Jobsite location (city & state)
C- Job number
D- Equipment number or identification
E- Witness’ signature representing the customer
F- Witness’ company
G- Date of readings
H- Time of readings (four readings per day)
I- Dry bulb temperature reading
J- Wet bulb temperature reading
K- Relative humidity percent taken from table VI
L- Surface temperature of equipment being lined
M- Dew point temperature taken from table I
N- Subtract dewpoint temperature from surface temperature
O- Weather conditions: R=rain, C=cloudy, F=fog, S=sunny
P- Number of hours of lost time due to weather conditions and readings
Q- Number of men unable to work due to weather conditions and readings
R- Total hours of lost time (no. hours times no. of men)
S- Readings recorder signature
T- Acceptable / Not Acceptable
PROJECT NO :C
LINING Q.C. RECORD ITEM NO :D
PSYCHROMETRIC READINGS LOCATION :B
CLIENT : A SIGNATURE
INSPECTION NOTICE NO : CLIENT APPLICATOR CEILCOTE
CLIENT’S INSPECTOR : / G / /G / / G /
APPLICATOR’S INSPECTOR : E S
CEILCOTE’S INSPECTOR :
DRY BULB WET BULB REL. HUM. SURF. DEW DIFF. WEATH. LOST NO. TOTAL ACCEPT. /
DATE TIME °F °F % TEMP. POINT °F COND. TIME MEN. HOURS NOT ACCEPT.
°F °F
G H I J K L M N O P Q R T
H I J K L M N O P Q R T
H I J K L M N O P Q R T
H I J K L M N O P Q R T
G H I J K L M N O P Q R T
H I J K L M N O P Q R T
H I J K L M N O P Q R T
H I J K L M N O P Q R T
G H I J K L M N O P Q R T
H I J K L M N O P Q R T
H I J K L M N O P Q R T
H I J K L M N O P Q R T
G H I J K L M N O P Q R T
H I J K L M N O P Q R T
H I J K L M N O P Q R T
H I J K L M N O P Q R T
G H I J K L M N O P Q R T
H I J K L M N O P Q R T
H I J K L M N O P Q R T
H I J K L M N O P Q R T
G H I J K L M N O P Q R T
H I J K L M N O P Q R T
H I J K L M N O P Q R T
H I J K L M N O P Q R T
G H I J K L M N O P Q R T
H I J K L M N O P Q R T
H I J K L M N O P Q R T
H I J K L M N O P Q R T
Legend: ACC=Acceptable NA= Not Acceptable Weather Conditions R=rain, C=cloudy, F=fog, S=sunny
PROJECT NO :
LINING Q.C. RECORD ITEM NO :
PSYCHROMETRIC READINGS LOCATION :
CLIENT : SIGNATURE
INSPECTION NOTICE NO : CLIENT APPLICATOR CEILCOTE
CLIENT’S INSPECTOR : / / / / / /
APPLICATOR’S INSPECTOR :
CEILCOTE’S INSPECTOR :
DRY BULB WET BULB REL. HUM. SURF. DEW DIFF. WEATH. LOST NO. TOTAL ACCEPT. /
DATE TIME °F °F % TEMP. POINT °F COND. TIME MEN. HOURS NOT ACCEPT.
°F °F
Legend: ACC=Acceptable NA= Not Acceptable Weather Conditions R=rain, C=cloudy, F=fog, S=sunny
PROJECT NO :
LINING Q.C. RECORD ITEM NO :
ACCEPTANCE INSPECTION OF LOCATION :
STEEL EQUIPMENT SIGNATURE
INSPECTION NOTICE NO : CLIENT APPLICATOR CEILCOTE
CLIENT’S INSPECTOR : / / / / / /
APPLICATOR’S INSPECTOR :
CEILCOTE’S INSPECTOR :
SPECIFICATIONS OKAY
SUBSTRATE / SURFACE CONDITION REMARKS
REQUIREMENT (9)
Cleanliness
Debris None
Oil or Grease or Contaminants None
Wax Markings None
Standing Water None
Construction
Dimensional Check Complies with
Contract Dwg
Manholes 18” ∅ or 12” x 20”
Nozzle Design Flanged
Nozzle Sizes ≥ 2”
Nozzle Lengths see Spec CPT-2
Abnormal Deflection on Tank Bottom None
Sharp Corners/Edges Rad. 1/8” / 1/4”
Inaccessible Parts to Coat/Grind None
Bolt Holes/Perforations Rad. 1/8” / 3/8”
Plate Defects: Scabs, Rollovers, Laminations None
Layout Marks Round Bottom
Internal Components
Attachments Removed
Testing
Hydrostatic Tests & Repair Completed
Welding
Welding, No Intermittent Welds Continuous
Sharp Edges None
Laps / Rollovers None
Undercuts None
Porosity None
Spatter None
Accessibility to Grinding Yes
Smoothness Yes
Additional Comments:
___________________________________________________________________________________________
___________________________________________________________________________________________
___________________________________________________________________________________________
___________________________________________________________________________________________
PROJECT NO :
LINING Q.C. RECORD ITEM NO :
WET FILM THICKNESS SUMMARY LOCATION :
(CONCRETE SUBSTRATE) SIGNATURE
INSPECTION NOTICE NO : CLIENT APPLICATOR CEILCOTE
CLIENT’S INSPECTOR : / / / / / /
APPLICATOR’S INSPECTOR :
CEILCOTE’S INSPECTOR :
AVERAGE WET FILM THICKNESS
LOCATION MATERIAL: __________________ MEASUREMENT SUMMARY REMARKS
BASECOAT TOPCOAT TOTAL THICKNESS
Additional Comments:
___________________________________________________________________________________________
___________________________________________________________________________________________
___________________________________________________________________________________________
___________________________________________________________________________________________
CHAPTER 6
6.1 PRIMING
6.1.3.1 Some Ceilcote Primers (i.e. Ceilcote 380 Primer) should be tested for
styrene sensitivity prior to basecoat application per Supplement "C"
Styrene Sensitivity Testing of this chapter. Other primers may have time
limitations regarding exposure time prior to basecoat application,
consult the appropriate Ceilcote Company Installation Procedure /
Specifications for this specific primer regarding this.
6.1.4.1 During application and after initial cure of the primer a visual inspection
shall be conducted to identify areas of unacceptable workmanship,
drips, runs. un-cured areas or other deficiencies.
CHAPTER 6 (Cont.)
6.2 BASECOAT APPLICATION
6.2.3.1 During application and after initial cure of the basecoat a visual
inspection shall be conducted to identify areas of unacceptable
workmanship, visual defects, sags, runs, un-cured areas or other
deficiencies.
6.3.3.1 During application and after initial cure of the topcoat, a visual
inspection shall be conducted to identify areas of unacceptable
workmanship, visual defects, sags, runs, un-cured areas or other
deficiencies.
CHAPTER 6 (Cont.)
6.4 SUBSEQUENT COATS - ADDITIONAL COAT APPLICATION
6.4.1 Any addition coats will be subject to the conditions as stated in 6.3.1. 6.3.2. and
6.3.3.
6.5.1 Quality Control personnel will record, document and maintain the following:
6.6 REPAIRS
6.6.1 Repairs are to be made per the appropriate Ceilcote Company Installation
Procedure / Specifications for the material applied.
Hold the face of the wet-film gage perpendicular to the surface where the freshly applied
material is in place. Press the gage firmly and evenly into the material until it rests on the
substrate. After a few seconds withdraw the gage evenly without sliding it across the surface.
The wet-film thickness of the material being tested will .be between the highest probe with
material present and the next higher probe without material present on the gage. If material
appears on a11 probes, rotate the gage to the next highest scale; if no material is present
rotate the gage to the next lowest scale and repeat the measurement technique. Readings
must always be taken immediately after material application. Gages must be cleaned with
solvent soaked rages immediately after each measurement.
CHAPTER 6
SUPPLEMENT "B"
To check for the presence of moisture in concrete tape a sheet of polyethylene (sq. ft. x 1 sq.
ft. minimum) at 4 mils thick, onto the concrete, completely sealing this area. After
approximately 24 hours lift off the polyethylene sheet and observe for the presence of water or
moisture droplets. If either water or moisture droplets are present then the concrete is
considered to contain moisture.
CHAPTER 6
SUPPLEMENT "C"
The styrene sensitivity test for Vinyl Ester Primers such as 380 Primer is accomplished by
wetting a small area of the primer with styrene or acetone, using a rag or brush. If this primed
surface area becomes tacky or is softened the surface is deemed styrene sensitive and
acceptable for material application. If it does not become tacky or softened it is deemed
styrene insensitive and not acceptable for material application.
CHAPTER 7
7.1.1 The Ceilcote Company's Spark Testing Practice STP-1 (Supplement "A" in this
chapter) outlines the qualifications, equipment and procedures to properly
evaluate and test linings/coatings using a high voltage detector or spark tester as
it is commonly called. All linings/coating installed over a conductive substrate
(steel steel/alloy) should be spark tested prior to being placed in service, unless
otherwise noted.
7.1.2 Calibration records of the spark test equipment shall conform to the requirements
of Chapter 9 - Instrumentation Calibration/Standards.
7.1.3 Q.C. documentation of the spark test, should list the date of the original (first)
spark test and the date or dates of the retesting of any repair areas.
NOTE: The spark test is an installation and application aid to identify a holiday
or imperfection. It should not be used to evaluate the quality, performance or
workmanship of a lining or coating. The test itself is destructive in nature and
extreme care should be taken in the set-up and execution of this test to provide
adequate and reliable testing results.
7.2.1 The Steel Structures Painting Council Procedure SSPC-PA2, Paint Application
Specification #2, Measurement of Dry Paint Thickness with Magnetic Gages
(Supplement "B") in this chapter outlines the procedure to accurately measure
dry film thickness of a lining or coating (non-magnetic) over a magnetic substrate,
typically carbon steel.
7.2.2 Calibration records of the dry film thickness test equipment shall conform to the
requirements of Chapter 9 – Instrumentation Calibration/Standards.
7.2.3 Q.C. documentation of the dry film thickness test should list the date of the
original test with the thickness results of each reading average based on a 6 ft.
grid system. All areas repaired should list the date of retesting and the thickness
results.
NOTE: Strong magnetic fields from welding equipment or power lines may
interfere with the operation of the gages. Periodic calibration checks of the
testing instrument on the substrate to be tested is recommended to increase
reading reliability whenever possible.
CHAPTER 7
7.4 Additional requirements to any areas within the chapter should be stated as a
addendum to the appropriate Ceilcote Installation Procedure/Specifications.
7.5 Concrete substrates which are lined or coated may be spark tested by using an
appropriate conductive primer. Consult Ceilcote for details.
CHAPTER 7
SUPPLEMENT "A"
HIGH VOLTAGE HOLIDAY DETECTION
(SPARK TESTING) PRACTICE
(STP-1)
SCOPE: The objective of spark testing a lining or coating is to identify a holiday or imperfection
that may lead to passage of corrosive material to the substrate. This is done by imposing an
electrical stress across the non-conductive surface (Ceilcote lining or coating) at such a
voltage that a spark will easily arc if a pin hole or air gap exists to the conductive
substrate.
POLICY: Spark testing should be used as an aid in the application of a lining or coating, and
not to determine or evaluate the quality, performance or physical characteristics of a lining or
coating. Spark testing will detect cracks, internal voids, holidays, and thin spots within a
Ceilcote lining or coating. Due to the destructive nature of the test spark testing will only be
done once prior to the actual use of the lining or coating under projected service conditions
and at the recommended testing voltage only. Testing at higher than recommended voltages
may be destructive and burn holes through a good lining. Spark testing is not recommended
for linings or coatings that have already been in service.
EQUIPMENT: Wet sponge type spark testers are unsatisfactory for testing Ceilcote linings and
coatings. Spark testing units capable of producing either straight D.C. or a pulsating D.C.
spark at a range of 0 volts to 25,000 volts are preferred. Equipment of this type includes the
following:
1. Electro-Technics High Frequency Generator - Model 30-60C
2. Tinker-Razor Holiday Detector - Model A-P and Model A-P/A-C
Units may be 115 VAC or battery operated. Other spark testing equipment may be
suitable. Questions concerning the selection or use of various spark testing
instruments should be directed to Ceilcote, Research and Development Dept.
CALIBRATION: Verification and measurement of the voltage being generated for testing may
be done using one of the following instruments:
The following voltages are recommended for spark testing Ceilcote linings and coatings:
PRODUCT VOLTAGE
2500, 6400, 6640, 6650, 695 Ceilcrete 15 000 - 20.000
505 CorolineSeries (except 505.2) 15 000 - 20,000
25, 61, 64, 74. 652 Lining 15 000 - 20.000
505.2 Coroline, 68 Lining 7 000 - 10.000
100 Flakeline Series 7 000 - 10.000
200 FlakelineSeries 3 000 - 5.000
300 Flakeline Series 2 000 - 3,000
661 Flaketar 2 000 - 3.000
* Linings and coatings not listed above will be tested at 100 volts per mil based on
the stated target thickness of that product.
COMMENTS:
1. Grounding - All test equipment should be grounded either to the electrical source
with 115 VAC powered units or the substrate with battery powered units or both.
Steel substrates should be electrically grounded to a common ground prior to
testing.
2. Cure Time - All linings and coatings must be cured prior to spark testing and shall
not exhibit soft spots or residual solvent on the surface. Qualified personnel shall
determine degree of cure prior to spark testing.
4. Safety - As with all electrical test equipment care should be taken in the set-up
and use of spark testing equipment to avoid electrical shock to the operator and
personnel in the work area.
IP-1
GUIDELINE SPECIFICATION
FOR HOLIDAY TESTING
MARCH 2006
********************************************************************************************
The specification information below is intended for use by architects, engineers or other
specifiers in defining the criteria needed for proper inspection.
1.0 CAUTION
2.0 SCOPE
2.1 The purpose of spark testing is to detect holidays in a lining so that a corrosive
environment cannot find a free passage to the substrate. This is done by imposing
electrical stress across the lining to a conductive substrate (usually carbon steel or
a conductive primer) and using a voltage such that a spark will easily arc if a hole
exists through the lining.
3.0 POLICY
3.1 Our policy is to use approximately 100 volts per mil based on the normal thickness
of the lining. This insures that there will still be enough voltage to jump on air gap
at the maximum lining thickness.
3.2 Spark testing should be used as an aide in the application of a lining or coating, and
not to determine or evaluate the quality, performance or physical characteristics of
a lining or coating. Spark testing will detect cracks, internal voids, holidays, and thin
spots within a Ceilcote lining or coating. Due to the destructive nature of the test,
spark testing should only be done once prior to the actual use of the lining or
coating under projected service conditions, and at the recommended voltages. This
may be destructive and burn holes through a good lining. Spark testing is not
recommended for linings or coatings that have already been in service.
IP-1
GUIDELINE SPECIFICATION
FOR HOLIDAY TESTING
3.3 Where equipment is to be lined prior to final erection, it is advisable to spark test
only after erection so that any lining damage due to handling will be detected at that
time.
3.4 Even though this test is a semi-destructive test, it is a necessity to ensure a pinhole
free lining/coating. When spark-testing make passes quickly to minimize damage.
Leaks will be detected at recommended voltages immediately.
4.0 QUALIFICATION
4.1 Personnel performing the spark testing must be knowledgeable and trained in the
correct methods and voltage requirements of each lining and coating to be tested.
4.2 The following voltages are recommended for detecting holiday in Ceilcote linings
and coatings:
Product Voltage
5. EQUIPMENT
5.1 Wet sponge type low voltage spark testers are used for coating systems under 20
mils in thickness. Spark testing units capable of producing either straight DC or a
pulsating DC voltage at a range of 0 volts to 25,000 volts are preferred. Equipment
of this type includes the following:
6. CALIBRATION
6.1 Verification and measurement of the voltage being generated for testing may be
done using one of the following instruments:
7. COMMENTS
7.1 Grounding:
All test equipment should be grounded either to the electrical source with 115 VAC
powered units or the substrate with battery-powered units or both. Steel substrates
should be electrically grounded to a common ground prior to testing.
All linings and coatings must be cured prior to spark testing and shall not exhibit soft
spots or residual solvent on the surface. Qualified personnel shall determine
degree of cure prior to spark testing (normal temperatures, next day is generally
adequate).
IP-1
GUIDELINE SPECIFICATION
FOR HOLIDAY TESTING
There is evidence that high voltage testing of linings that have been in service may
burn holes or give false readings. Because there is a relatively high electrical stress
put on the lining during spark testing and since the lining has a finite dielectric
strength, areas in the lining where the lining is thin or where a void exists but does
not go all the way through will usually break down, causing a hole all the way
through to the steel, resulting in a visible strong spark.
When you spark test, in addition to finding existing holes, you are actually breaking
down the lining, making new holes where the dielectric strength is exceeded.
7.5 Corona:
Corona does not indicate pinholes as this is indicated by a spark to the substrate.
The presence of a Corona does not indicate irregularities of the linings or coating.
7.6 Pinholes:
The wet sponge test method is not recommended for coatings 20 mils or less in
thickness.
7.8 As with all electrical test equipment, care should be taken in the set-up and use of
spark testing equipment to avoid electrical shock to the operator and personnel in
the work area.
CHAPTER 8
8. QUALITY CONTROL RECORDS
8.1.3 Abrasive Blasting Records - Psychrometer readings and abrasive blast test are
recorded on forms describing the work area, abrasive blast profile and dates of
abrasive blasting and priming on a daily basis. Areas requiring re-work are
listed on these drawings to show where the affected areas are located.
Supplement "C" this chapter depicts this documentation.
8.1.4 Lining Records - lining application dates and batch number placement are
recorded on forms describing the work area. These contain the lining records for
all lining operations on a daily basis. Supplement "D" this chapter, depicts this
documentation.
8.1.5 Spark Test Records - the spark test dates and results of areas tested showing
areas of leak repairs and are recorded on forms describing the work area.
Repair and retesting dates of leak areas are listed. Supplement "E" this
chapter, depicts this documentation.
8.1.6 Dry Film Test Records - the dry film thickness measurement obtained on a
6ft grid layout on the lining surface. Areas of over-thickness and under-
thickness are noted on these records. All measurements are recorded on forms
describing the work area. Supplement "F" this chapter, reflects this
documentation.
8.1.9 Record Disposition - Q.C. records are to be distributed when the lining/coating
installation is complete. Upon completion they are to be distributed in book form
to the authorized agencies. Originals are to be compiled and returned to
Ceilcote for evaluation and retention.
CHAPTER 8
SUPPLEMENT "A" THRU "F"
EXAMPLES OF REPORTS
SUPPLEMENT
Comments:
LINING Q.C. RECORD SHEET NO : OF
Basecoat Topcoat
Material Material
LOCATION / AREA BATCH WET FILM SURFACE BATCH WET FILM SURFACE
# THICKNESS CHECK # THICKNESS CHECK
Comments:
SHEET NO : OF
DATE : EQUIPMENT NO :
INSPECTOR : JOBSITE :
REPORT NO. : :
DATE : EQUIPMENT NO :
INSPECTOR : JOBSITE :
REPORT NO. : :
__________________________________________________________________________________
__________________________________________________________________________________
__________________________________________________________________________________
__________________________________________________________________________________
_________________________________________
AUTHORIZED CEILCOTE SIGNATURE
_________________________________________
AUTHORIZED CUSTOMER REPRESENTATIVE SIGNATURE
PROJECT NO :
LINING Q.C. RECORD ITEM NO :
NON-CONFORMANCE REPORT LOCATION :
SIGNATURE
INSPECTION NOTICE NO : CLIENT APPLICATOR CEILCOTE
CLIENT’S INSPECTOR : / / / / / /
APPLICATOR’S INSPECTOR :
CEILCOTE’S INSPECTOR :
Date: ...................................................................
Non-Conformance
Corrected On: ..................................................... Verified By: ......................................................
Comments: .................................................................................................................................................
......................................................................................................................................................................
......................................................................................................................................................................
......................................................................................................................................................................
Legend:
ACC : Acceptable
NA : Not Acceptable
Legend:
ACC : Acceptable
NA : Not Acceptable
Legend:
ACC : Acceptable
NA : Not Acceptable
Legend:
ACC : Acceptable
NA : Not Acceptable
Date: ...................................................................
Non-Conformance
Corrected On: ..................................................... Verified By: ......................................................
Comments: .................................................................................................................................................
......................................................................................................................................................................
......................................................................................................................................................................
......................................................................................................................................................................