DESIGN BRIEF

MECHANICAL AND ELECTRICAL SERVICES


DESIGN BRIEF REPORT

1.0 OBJECTIVES

The objectives of this report are as follows: -

- to outline system concepts


- to established basic design criteria

1.1 BACKGROUND OF PROJECT

The proposed M & E building services is for the whole complex which consists
the following buildings

a) Sekolah Menengah Pendidikan Khas Vokasional, Merbok, Kedah.

The M & E building services will be designed for this complex with an
approached to implement cost efficiency for capital cost, operating cost,
operational flexibility and maintainability.

1.2 SCOPE OF SERVICES

The description of the scope of services covered in this report are as follows: -

Mechanical Services - Appendix 'A'


Electrical Services - Appendix 'B'

VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.


Page 2 of 18
DESIGN BRIEF

APPENDIX 'A'
MECHANICAL SERVICES

VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.


Page 3 of 18
DESIGN BRIEF

2.0 The scope of work covered under the mechanical services shall consist the
followings: -

(a) Fire Protection System


(b) Air-Conditioning and Ventilation System
(c) Internal Sanitary and Cold Water Pluming services
(d) Compressed Air System
(e) Fuel System
(f) Lift Installation

2.1 The following scope of services shall be included for specific building
which require such system installation.

2.2 The design shall be in accordance with standard engineering practice and
shall comply the regulations and By Laws of the following authorities: -

(a) Jabatan Keselamatan Dan Kesihatan Pekerja


(b) Suruhanjaya Tenaga Malaysia
(c) Jabatan Bomba Dan Penyelamat Malaysia
(d) Jabatan Bekalan Air

And other authorities having jurisdiction over the mechanical installation in the locality.

3.0 FIRE PROTECTION SYSTEM

3.1 GENERAL

3.1.1 To ensure the safety of occupants in the building. An adequate fire


protection system proposed to the various buildings shall be of standards
confirming the rules regulation codes are requirements of the followings: -

(a) Jabatan Bomba Dan Penyelamat Malaysia


(b) Relevant British Code Of Practice
(c) Relevant British Standard Specifications
(d) Uniform Building By-Law

3.1.2 The following Fire Protection System as required by Uniform


Building By-Law and Jabatan Bomba Dan Penyelamat Malaysia shall be
installed for this development.

(a) Fire Protection and Alarm System


(b) Portable Fire Extinguishers
(c) Automatic Carbon Dioxide Extinguishing System
VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.
Page 4 of 18
DESIGN BRIEF

(d) Hose Reel System


(e) External Hydrant System
(f) Exit Signs and Emergency Lights

3.2 FIRE DETECTION AND ALARM SYSTEM

Self-addressing Fully Analogue Addressable Fire Detection and Alarm System


shall propose. The type shall be closed loop with linkage to the central
monitoring unit fibre optic converter via fibre optic cable.

3.3 PORTABLE FIRE EXTINGUISHER

Fire extinguishers shall be wall-mounted type recessed to Architect detail and


generally located as follows.

TYPE LOCATION
ABC DRY POWDER CO² Escape staircase, lobbies, corridor,
electrical rooms, generator room.

3.4 AUTOMATIC CARBON DIOXIDE SYSTEM

Automatic fixed carbon dioxide system shall be installed in the unmanned


electrical sub-station and electrical plat room.

3.5 EXTERNAL FIRE HYDRANT SYSTEM

The system shall consist of double outlet pillar hydrants, which shall be tapped off
from the external water mains. The hydrant shall be positioned along the service
road accessible to fire fighting vehicle.

3.6 HOSE REEL SYSTEM

There shall be a hose reel system serving the buildings: -

- One duty pump


- One standby pump
- Water storage tank (approx: 2,400 gallons)
- Distribution pipe works
- Hose reel stations

VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.


Page 5 of 18
DESIGN BRIEF

4.0 AIR-CONDITIONING AND VENTILATION SYSTEM

The air conditioning system shall be design to meet requirement of comfort


cooling as per JKR Specification.

For comfort air-conditioning, the normal design indoor conditioning shall be


about 23º - 25º units relative humidity between 55-65%.

The proposed type air-conditioning systems shall be: -

(a) Multi split system with advanced refrigerant control (flow/volume)


(b) Split Unit

Ventilation shall be provided for toilets and other specific rooms by the used of
extractor fans.

5.0 INTERNAL SANITARY AND COLD WATER SERVICES

Cold water from the external reticulation shall be fed directly to storage tanks.
The water will be distributed to the sanitary fittings. The system shall be design
to meet the requirement of JBA and other regulating authorities.

6.0 LIFT INSTALLATION-BLOCK BANGUNAN PENTADBIRAN (PASSENGER


LIFT & GOOD LIFT) SETOR BARANG KES KENDERAAN

The proposed design shall be in compliance to the requirement of Jabatan


Keselamatan Dan Kesihatan Pekerja and confirm to British Standard
Specification for electric Lifts BS 2655, part 1, 2 and 3.

The propose design are base on the following criteria


- To enhance passenger services
- To improve total quality and reliability
- To save energy
- To avoid and minimise vandalism to the equipment.

7.0 The lift shall be 4nos. with 24 passengers and 1630kg capacity, 105mpm traction
type with alternating current variable voltage, variable frequency (ACVVVF)
drive control. The handicap features shall be provided. The status of the lift
operation shall be monitored at the supervising panel in the fire central room.

VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.


Page 6 of 18
DESIGN BRIEF

8.0 SUMMARY OF DESIGN & INSTALLATION STANDARDS

The following standards of practice and authorities requirements shall form part
of the design and installation guides:-
STANDARDS

a) Air-conditioning ASHRAE
b) Mechanical Ventilation ASHRAE & UBBL
c) Fire Alarm System BS5839 Part 1 & Jabatan Bomba
d) Hosereel BS5306 Part 1 & Jabatan Bomba
e) Fixed CO2 System NFPA12 & Jabatan Bomba
f) Lift BS2655 Part 1 & JKKP
g) Internal Sanitary MBAS
h) Cold Water Plumbing Jabatan Bekalan Air

9.0 SUMMARY OF DESIGN CRITERIA

The design of the mechanical services shall follow the criteria indicated below:

a) Air Conditioning parameter

AREA TEMPERATURE HUMIDITY


Office 75 + 20F 55 + 5% RH
Lobby 79 + 20F 55 + 5% RH
Computer Room 68 + 20F 50 + 5% RH
Conference Room 75 + 20F 55 + 5% RH
General Areas 75 + 20F 55 + 5% RH

b) Fresh air requirement for air-conditioned space

In accordance to UBBL and ASHRAE recommendations.

c) Mechanical ventilation air requirement for non air-conditioned space

i) Circulation area 6 air changes per hour


ii) Toilet 10 air changes per hour
iii) Workshop 10 air changes per hour
iv) Main Switch room 10 air changes per hour
v) Transformer room 10 air changes per hour
vi) Store 6 air changes per hour

VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.


Page 7 of 18
DESIGN BRIEF

d) Compressed air Minimum 2.5m³/min at 8 bar

e) The rest of the basic mechanical services shall follow the respective
relevant standards of practice.

10.0 SUMMARY OF MAJOR INSTALLATION MATERIALS

The following types of major installation materials shall be used:

MATERIALS
a) Air Conditioning parameter

i) Condenser water pipe Class `C’ galvanised iron with


factory wrapped bituminous tape
for underground

ii) Main duct & branch duct GI sheet metal with fibreglass
insulation of 1 inch 2 Ib for last
floor and 1 inch 1 Ib for the rest
below with isolated aluminium foil
covering.

iii) Condenser drain pipe Class `D’ UPVC with armaflex


insulation.

iv) Diffuser and grilles Anodised or epoxy coated


aluminium.

b) Fire alarm & protection

i) Fire alarm cable Twisted pair PVC screened


ii) Hose-reel pipe Class `C’ Galvanised Iron
iii) Dry riser Class `C’ Galvanised Iron
iv) CO2 system Schedule 40 carbon steel
v) Hose-reel tank Hot dipped galvanised press steel

c) Cold water & Sanitary plumbing

i) Internal coldwater pipe ABS or approved equivalent


ii) External coldwater pipe HDPE
iii) Water tank FRP
iv) Above ground sanitary pipe UPVC
v) Below ground sanitary pipe Brown UPVC (for diameter
100mm and above)

VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.


Page 8 of 18
DESIGN BRIEF

APPENDIX 'B'
ELECTRICAL SERVICES

VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.


Page 9 of 18
DESIGN BRIEF

1. SCOPE OF SERVICES

The scope of works for the Electrical Services are as follow: -

a) Low voltage reticulation and distribution system


b) Internal lighting and small power installation
c) External and compound lighting
d) Standby generator
e) Lightning and surge protection
f) Earthing system
g) Public Address System
h) CCTV system
i) MATV system
j) Audio Visual System
k) Information Technology and Telephone system including PABX

2. DESIGN CONCEPTS

The following design concept shall be adapted:

2.1 LOW TENSION RETICULATION AND DISTRIBUTION SYSTEM

The low tension reticulation and distribution systems shall be complete


with distribution boards, feeder pillars, underground cables etc.

All service mains, distribution mains, sub-mains and sub-circuits install


externally shall be of underground armoured cables. The main
switchboards shall be installed with automatic power factor correction
capacitor bank such that the power factor of the installation shall be not
less than 0.85 lagging at any load condition. The switchboards shall be
modular and protected using relays.

2.2 INTERNAL LOW TENSION ELECTRICAL

The electrical intake source into the building shall be at 415V three phase
supply from 11/0.415kV TNB Substation.

The incoming supply mains of XLPE/SWA/PVC cables from the


substation to the new switchboard shall be laid directly underground.

Each block of building shall have at least a switchboard, each floor of a


building depending on the loads and other requirements shall have at least
two distribution boards and will be located strategically located to serve
the load centres and shall have at least 30% spare capacity for future
extension.
VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.
Page 10 of 18
DESIGN BRIEF

All cabling and wiring, whether for electrical services or other services
shall be in concealed conduits/trunking/cable trays/cable ladders. All
conduits installed shall be UPVC high impact conduits to the BS 4421 and
all trunking shall be of galvanised sheet steel and finished with two coats
of epoxy paint (Standard orange colour)

2.3. INTERIOR LIGHTING

Generally, recessed type, mirror reflector fluorescent lighting with low


loss ballast will be used for offices, computer rooms, conference rooms,
stores with ceiling and etc.

Recessed down light with energy saving lamp will be provided for
corridors, lobbies, toilets, open staircase and car porch. Surface type
mirror reflector fluorescent for enclosed staircase. Bare fluorescent for M
& E plant rooms.

Loading and unloading areas. The illumination levels shall follows the
criteria give in section of this proposal brief or to IES recommendation.

Sufficient emergency light and keluar sign light wired to essential supply
will be provided in accordance to the authority requirement. Self
contained emergency light and keluar sign will be backed up by sealed
lead acid battery for a period 3 to 4 hours.

The lighting systems shall be designed by arrangement of alternating


circuits, proper grouping of lighting switches, separate switching etc. so
that unnecessary light fittings can be switch if desired.

2.4 EXTERNAL LIGHTING INSTALLATIONS

Basically the luminaries at the main approached roads to the building


entrances will be mounted on 4m height pole and the rest on 3.5m height
pole. Wall mounted light fittings shall be used where pole mounted light
fittings are not suitable. The lantern shall be of SON type.

2.5 SWITCHED SOCKET OUTLETS

Switch socket outlets in accordance to the criteria set forth in section 5 of


this proposal brief will be provided. Additional socket outlet points shall
be provided where required to meet requirements for data points and other
M & E equipment. The cabling scheme will be designed either in radial or
ring circuit in accordance to IEE regulation.

VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.


Page 11 of 18
DESIGN BRIEF

2.6 STANDBY GENERATOR

The standby generator will be provided. Sufficient to supply to all


essential loads which are as follows: -

(i) emergency and essential lighting


(ii) Fire alarm Panel
(iii) Hose Reel Pump
(iv) Fireman’s Lift
(v) Emergency PA, Fireman Intercom and CCTV Systems
(vi) Essential Power Points

The generating set shall be with all necessary equipment and accessories
such as nicked cadmium battery daily fuel tank, fuel piping system, proper
monitoring control and alarm systems etc. according to the normal
practice. The noise level shall of acceptable value.

2.7 PUBLIC ADDRESS SYSTEM

The design shall provide facilities for background music and emergency
paging with zone selection in accordance to Bomba’s requirements.

2.8 MASTER ANTENNAE TELIVISION SYSTEM (MATV)

Where required appropriate channelised 75 ohms MATV system shall be


provided for reception of the following stations:-

i. RTM 1 & 2

ii. TV 3

iii. NTV 7

2.9 LIGHTNING, SURGE PROTECTION SYSTEMS

2.9.1 Lightning protection system using copper tape shall be provided


and it shall comply to BS6651: “Protection of Structure Against
Lighting”.

VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.


Page 12 of 18
DESIGN BRIEF

2.9.2 Surge Protection System/devices shall be provided for the main


electrical distribution system including sub-switch boards,
computers, electronic equipment, fire alarm panel, PABX
equipment and UPS equipment, etc which are susceptible to
lightning and switching surges.

3. CLOSED CIRCUIT TV (CCTV)

The CCTV systems shall use the latest technology with new generation model for
cameras, monitor and central panel.

4. TELEPHONE INSTALLATION AND INFORMATION TECHNOLOGY

4.1 EXTERNAL TELECOMMUNICATION INSTALLATION

External telecommunication infrastructure works complete with ducting,


manholes, junction boxes etc shall be provided.

The works shall comply with the requirements of Telekom Malaysia Bhd.

4.2 INTERNAL TELECOMMUNICATION INSTALLATION

The installation shall come complete with under floor trunking, junction boxes,
internal wiring, telephone outlet terminals, distribution boxes, risers, SDF and
quick connect type terminal blocks and lightning arrestors PABX, etc.

All terminal blocks for external cables, whether trunk lines or extension lines
shall be provided with properly rated lightning arrestor.

Internal under floor trunking layouts shall be in accordance with the guidelines of
the Telekom Malaysia Bhd.

Public telephone shall be provided in public waiting areas such as in the cafeteria
and canteen

4.3 INFORMATION TECHNOLOGY

To installation shall include Riser Backbone and Horizontal cabling using fibre
optic cables complete with switches and UTP CAT 6 cable will be used to
connect up to RJ 45 faceplate.

VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.


Page 13 of 18
DESIGN BRIEF

5. DESIGN CRITERIA

The designs of the electrical services shall follow generally the criteria indicated
below: -
a. The selection of cable size shall be based on the recommended current
carrying capacity and voltage drop in the IEE regulation.

b. The illumination level shall be in accordance with the IES Codes which
are as follows: -

i. Social area 150 lux


ii. Circulation area 250 lux
iii. Sport and leisure 300 lux
iv. Offices, reception areas, waiting areas 350 lux

c. The number of 13A switched socket outlet for general usage shall be as
follows:-

i. One for every 10sq. meters of area

ii. One for every 5 meters of corridor length.

d. The rest of the basic electrical service shall follow the respective standard
of practice.

6. DESIGN STANDARDS

The following standards of practice and authorities requirements shall form part
of the design and installation guides.

Standard
a) Low Voltage reticulation and distribution IEE
b) Interior lighting IES
c) Emergency lighting BS 5266
d) External lighting BS 5489 Part 3
e) Lightning Protection system BS 6651
f) Public Address System BS 6259
g) MATV BS 5603 Part 1
h) Standby Generator Set BS 649
i) Fireman Intercom Jabatan Bomba

VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.


Page 14 of 18
DESIGN BRIEF

7. TYPE OF MAJOR INSTALLATION MATERIALS

The following types of major installation materials shall be used.

a Sub-mains and riser wall XLPE or PVC


b. Underground cables XLPE/SWA/PVC
c Fire resistance cables FR
d. P.A. loudspeaker cables Twisted pair PVC
e MATV & CCTV cables Screened coaxial
f Fireman intercom cables PVC
g Power outlet and lighting cables PVC
h Concealed conduits High impact UPVC
i Exposed conduits Galvanised iron
j Cable trunking Epoxy coated sheet steel
k Cable trays Epoxy coated perforated sheet steel
l Data telephone points UTP CAT 6

VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.


Page 15 of 18
DESIGN BRIEF

AUTHORITIES
FEEDBACK

VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.


Page 16 of 18
DESIGN BRIEF

REPORT ON LOCAL AUTHORITIES FEEDBACK FOR


MECHANICAL & ELECTRICAL SERVICES.

This report is based on our discussion with the authorities as follows :-

Tenaga Nasional Berhad, Sungai Petani, Kedah.

Telekom Malaysia , Sungai Petani, Kedah.

Jabatan Bekalan Air Kedah.

Jabatan Bomba dan Penyelamat Kedah.

Majlis Perbandaran Sungai Petani, Kedah

The feedback obtained from the above authorities shall be used as our design guideline
based on our discussion.

1. Tenaga Nasional Berhad.

Our visit to Tenaga Nasional Berhad, Sungai Petani, Kedah on 19th. February 2008 and
meet Jurutera Perancang Kawasan ( Sungai Petani ), Puan Norhasni was refered :

• TNB on principal agreed the supply shall based on double chamber sub-station for
the proposed of this development.

• TNB highlighted that the MSB Room to be built attached together to the sub-
station.

• This is to meet the requirements for the voltage drop allowable by TNB.

• The maximum distance for MSB Room shall be 25 meter from the sub-station.

2. Telekom Malaysia.

Telekom Malaysia Sungai Petani, Kedah required that the infrastructure cabling for the
Sekolah Menengah Pedidikan Khas Vokasional, Merbok, Kedah to existing.

VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.


Page 17 of 18
DESIGN BRIEF

3. Jabatan Bekalan Air Kedah.

JBA highlighted that the infrastructure mains for water supply is along the main road near
MRSM. Therefore we were advised to connect to this main water reticulation.

4. Jabatan Bomba dan Penyelamat Kedah.

Vision Intellect Consulting Engineers Sdn. Bhd. to submit Fire Protection System and
complied to Uniform Building By Law.

5. Majlis Perbandaran Sungai Petani

Vision Intellect Consulting Engineers Sdn. Bhd. to submit Internal Sanitary System and
complied to all local authorities requirements for the above..

VISION INTELLECT CONSULTING ENGINEERS SDN. BHD.


Page 18 of 18