Sie sind auf Seite 1von 3

5/15/2011 Tutorial T2

Differential Protection

Differential protection is a unit scheme that compares the current on the primary side of
a transformer with that on the secondary side. Where a difference exists (other than that
due to the voltage ratio) it is assumed that the transformer has developed a fault and the
plant is automatically disconnected by tripping the relevant circuit breakers. The
principle of operation is made possible by virtue of the fact that large transformers are
very efficient and hence under normal operation power-in equals power-out. Differential
protection detects faults on all of the plant and equipment within the protected zone,
including inter-turn short circuits.

Principle of Operation
The operating principle employed by transformer differential protection is the Merz-Price
circulating current system as shown below. Under normal conditions I1and I2 are equal
and opposite such that the resultant current through the relay is zero. An internal fault
produces an unbalance or 'spill' current that is detected by the relay, leading to
operation.

Design Objectives
An ideal scheme is required to be:

Extremely stable under through fault conditions


Very fast to operate for an internal fault

Design Considerations
A number of factors have to be taken into account in designing a scheme to meet these
objectives. These include:

The matching of CT ratios


Current imbalance produced by tap changing
Dealing with zero sequence currents
Phase shift through the transformer
Magnetising inrush current

Each of these is considered further below.

The Matching of CT Ratios


The CTs used for the Protection Scheme will normally be selected from a range of
current transformers with standard ratios such as 1600/1, 1000/5, 200/1 etc. This could

transformerworld.co.uk/diffprot.htm 1/3
5/15/2011 Tutorial T2
mean that the currents fed into the relay from the two sides of the power transformer may
not balance perfectly. Any imbalance must be compensated for and methods used
include the application of biased relays (see below) and/or the use of the interposing CTs
(see below).

Current Imbalance Produced by Tap Changing


A transformer equipped with an on-load tap changer (OLTC) will by definition experience
a change in voltage ratio as it moves over its tapping range. This in turn changes the
ratio of primary to secondary current and produces out-of-balance (or spill) current in the
relay. As the transformer taps further from the balance position, so the magnitude of the
spill current increases. To make the situation worse, as the load on the transformer
increases the magnitude of the spill current increases yet again. And finally through
faults could produce spill currents that exceed the setting of the relay. However, none of
these conditions is 'in zone' and therefore the protection must remain stable ie. it must
not operate. Biased relays provide the solution (see below).

Dealing with Zero Sequence Currents


Earth faults down stream of the transformer may give rise to zero sequence current,
depending upon winding connections and earthing arrangements. Since zero sequence
current does not pass through a transformer, it will be seen on one side only producing
spill current and possible relay operation for an out-of-zone fault. To prevent such
occurrence, zero sequence current must be eliminated from the differential scheme.
This is achieved by using delta connections on the secondary side of any CTs that are
associated with main transformer windings connected in star.

Where CT secondaries are connected in star on one side of a transformer and delta on
the other, allowance must be made for the fact that the secondary currents outside the
delta will only be 1/√3 of the star equivalent.

Phase Shift Through the Transformer


Having eliminated the problem of zero sequence currents (see above) through faults will
still produce positive and negative sequence currents that will be seen by the protection
CTs. These currents may experience a phase shift as they pass through the transformer
depending upon the transformer vector group. CT secondary connections must
compensate to avoid imbalance and a possible mal-operation.

Magnetising Inrush Current


When a transformer is first energised, magnetising inrush has the effect of producing a
high magnitude current for a short period of time. This will be seen by the supply side
CTs only and could be interpreted as an internal fault. Precautions must therefore be
taken to prevent a protection operation. Solutions include building a time delay feature
into the relay and the use of harmonic restraint driven, typically, by the high level of
second harmonic associated with inrush current.

Other Issues

Biased Relays
The use of a bias feature within a differential relay permits low settings and fast operating
times even when a transformer is fitted with an on-load tapchanger (see above). The
effect of the bias is to progressively increase the amount of spill current required for
operation as the magnitude of through current increases. Biased relays are given a
specific characteristic by the manufacturer.

Interposing CTs
The main function of an interposing CT is to balance the currents supplied to the relay

transformerworld.co.uk/diffprot.htm 2/3
5/15/2011 Tutorial T2
where there would otherwise be an imbalance due to the ratios of the main CTs.
Interposing CTs are equipped with a wide range of taps that can be selected by the user
to achieve the balance required.

As the name suggests, an interposing CT is installed between the secondary winding of


the main CT and the relay. They can be used on the primary side or secondary side of
the power transformer being protected, or both. Interposing CTs also provide a
convenient method of establishing a delta connection for the elimination of zero
sequence currents where this is necessary.

Modern Relays
It should be noted that some of the newer digital relays eliminate the need for interposing
CTs by enabling essentials such as phase shift, CT ratios and zero sequence current
elimination to be programed directly into the relay.

Tutorial Index

transformerworld.co.uk/diffprot.htm 3/3

Das könnte Ihnen auch gefallen