METALS
Electrical properties
Table 3.1 indicates the electrical properties of the c o m m o n metals used in cables.
Taking price into consideration, copper and aluminium are clearly the best choice for
conductors but there has been some experience with sodium. Reference to this is m a d e
in chapter 4 which also contains information on the variation of resistance with
temperature.
Physical properties
The physical properties of metals used for conductors and sheaths are given in table 3.2.
Except for the conductors of self-supporting overhead cables, copper is invariably used
in the annealed condition. Solid aluminium conductors are also mainly in a soft
condition but stranded aluminium conductors are 3H (hard) to H. Aluminium sheaths
33
34 Electric Cables Handbook
are now extruded directly onto cables and hence o f soft temper but a small a m o u n t o f
work hardening occurs during corrugation.
Copper conductors
Because of the way it can readily be rolled into rod and then drawn to wire, together
with its excellent electrical conductivity, copper was virtually unchallenged as a
conductor for all types of insulated cable for well over 50 years. Indeed, in the electrical
world, the International Electrotechnical Commission established an International
Annealed Copper Standard (IACS) with copper o f resistivity of 1.724[a~ cm at 20°C
assigned as 100%. National specifications for copper can be found in the publication
High Conductivity Coppers, Technical Data TN27 which is produced and issued by the
Copper Development Association. This publication also forms part of the contents of a
C D - R O M , Megabytes on Copper, available from the same Association.
The grade and quality of copper is very i m p o r t a n t and the high conductivity copper
used for electrical purposes comfortably exceeds the 100% I A C S value. Conductivity is
greatly influenced by impurities and by mechanical working. Consequently, the purity is
of the order of 99.99%, which nowadays is obtained by final electrolytic refining.
Fortunately, the mechanical strength of annealed wire is adequate for nearly all types
of insulated cable. If any minor working of the material occurs during conductor
manufacture, e.g. in compacting to reduce the overall dimensions, allowance has to be
made for work hardening by increasing the copper volume to compensate for the
reduction in conductance. In an extreme case, such as the use of hard drawn copper for
self-supporting overhead lines, this may a m o u n t to as m u c h as 3%.
Almost the only unsatisfactory feature of copper is the way that the price fluctuates
widely with the world supply and demand. An example of the scale of fluctuations that
can be experienced is shown in fig. 3.1, where the monthly low and high cash trends for
1995 are presented. The extreme values for the year are £1680 and £2030 per tonne. I f
its use could always be justified economically it would not have competitors. However,
over the last two decades aluminium has become a replacement in the power
distribution field solely on the basis of cost.
Materials Used in Cables 35
20501-
20001-
1850"
1800- --
'10
c
0
o_
=
1750"
1700-
1650.
I
1600
t'~ r~ ¢-~ t'~
-~ E o E E
~ < ® ~ ® ®
0 > o
U- Q; 0 Q)
co z n
Fig. 3.1 Copper cash trends (monthly low and high figures, 1995)
Aluminium conductors
Although aluminium did not make much serious impact until the price o f copper soared
in the late 1950s, it is surprising to find that a relatively substantial a m o u n t was used
between 1909 and 1912. Figure 3.2 shows a sophisticated low voltage paper insulated
d.c. cable made in quantity by British Insulated Cables at Prescot during this period.
This particular cable was taken out of service in 1967 and was just as perfect as when
installed. Even the jointing was of interest as each shaped wire had an individual sleeve
secured by pinch-screws.
Unlike copper, the mechanical strength of annealed aluminium is rather low for soft
single wire or stranded conductors but fortunately conductivity is little changed by
working. Consequently the temper o f wire used is commonly known as a broad 4Lhard
grade. Tensile strength is relatively unimportant and this grade covers ranges which in
the aluminium industry spread from l h a r d to fully hard, the main requirement being to
specify a maximum of 205 M N / m 2, which avoids the use of wire having too little
elongation before fracture on bending. Aluminium, however, can also be used in solid
as distinct from stranded form and in this case a soft temper is desirable to keep the
stiffness of the conductor to a minimum. Such conductors are mostly produced by hot
extrusion, which provides an almost annealed temper, and the upper limit o f tensile
strength is fixed at 80 M N / m 2 for sizes above 35 mm 2. F o r small sizes this limit is rather
low to exclude some stretching during cable processing and also there are advantages
in producing the conductors by drawing. The maximum is therefore in the range
125-165 M N / m 2 according to size.
Compared with copper, aluminium has a number o f technical disadvantages, all of
which can be satisfactorily overcome to benefit from its economic attraction. The
advantage of a low density of one-third that of copper is partly offset by its low
conductivity o f 61% that of copper, but for equal conductance the weight of the
expensive conductor metal required is almost exactly halved. However, the cross-
sectional conductor area has to be increased by a factor o f 1.6 and this means extra
36 Electric Cables Handbook
Fig. 3.2 +230Vd.c. cable installed in London in 1911 and removed from service in 1967
Impurities, as distinct from alloying additions, do not greatly affect the conductivity
of aluminium but a grade known as EC (electrical conductivity) is commonly accepted
in the aluminium industry. The basic British Standards for wrought aluminium for
electrical purposes, i.e. BS 2627, 'Wire', and BS 3988, 'Solid conductors for insulated
cables', define the purity as 99.5% minimum, with limits for individual impurities. More
recently, in 1991, the British Standard BS6360 'Specification for Conductors in
Insulated Cables and Cords' was issued. This includes the requirements for both
aluminium and copper conductors.
By controlling the amounts of copper, silicon and iron and/or small amounts of other
metals, it is possible to create a range of 'dilute alloys', without much sacrifice of
conductivity but with particular strength properties to cater for special requirements in
manufacture and jointing, e.g. for single-wire conductors for telephone cables. No
applications have been found for such compositions for power or wiring cables.
A particular disadvantage of aluminium for electrical purposes is the thin, hard
protective oxide skin which is so valuable in giving corrosion protection to aluminium
installed above ground. Satisfactory techniques for removing it for making soldered
joints or to break it up by appropriate designs of compression or mechanical joint have
long been developed, but it is always necessary to emphasise that jointers must exercise
care and attention when following prescribed instructions in detail. This emphasis
applied more particularly to soldering and plumbing, and modern techniques for power
cable conductor jointing have been centred on mechanical methods capable of easy
adoption by less expert operatives.
Apart from the oxide film, there is another factor which has contributed to lack of
success in one particular field of use, namely wiring cables. The low yield or proof
stress of aluminium means that if the conductor is only held, for example, by a
single pinch-screw, as is common in many wiring cable accessories, there can be
relaxation and development of a high resistance joint. Overheating and failure may
then follow. It is difficult to ensure that all accessories are specially designed for
aluminium, and although large-scale installations have been undertaken in North
America the problems have not been overcome and the use of aluminium wiring
cable has been halted.
Corrosion protection is covered elsewhere and all that need be mentioned here is that,
whilst claims for aluminium having excellent corrosion resistance are true if made in
relation to dry indoor situations, or even outdoors if drying off is rapid after rain, cable
engineers must ensure that bare aluminium is not left exposed anywhere. Cable situations
are rarely dry; for example in the base of outdoor pillars corrosion can be rapid.
Protection in a form such as heat-shrink sleeving should always be used.
Lead sheaths
Lead has served the cable industry well since the end of the last century, but, because of
its weight and softness and the need for good plumbing skill, few users will regret that
its use has diminished significantly. Although the overall incidence of faults associated
with the lead sheath itself has been quite small, large users are likely to have met them at
some time. They can be divided into four categories:
Fatigue
Lead has comparatively low resistance to fatigue and fig. 3.3 shows a typical case of
sheath fracture associated with cracks in the crystal boundaries. Figure 3.4 indicates the
effect after etching and illustrates why such failures used to be erroneously attributed to
crystallisation. Most sheath fatigue fractures are caused by vibration, either during
transport over a long distance to site, or by installation on bridges, in ships, alongside
railways or in overhead catenary systems etc. In such cases the vibration frequency is
usually high and the amplitude low. Other situations arise where the frequency is low
and the amplitude high, so that the effect is more akin to repeated bending, e.g. due to
thermal expansion and contraction with bodily longitudinal movement. This can occur
in jointing manholes for cables in ducts or with unsecured cables on racks or trays
exposed to solar heating and/or having pronounced load cycles. In all such installations
it is important to prevent the expansion being accommodated in a local loop or offset.
Much can be done to prevent such failures. If long intercontinental transport is
involved it is important for the cable ends to be fixed tightly so that there is no loose
cable which can vibrate separately from the whole drum. Installations should also be
planned to accommodate expansion and contraction uniformly along the whole length.
However, the main factor is that lead alloys are available to provide increased fatigue
resistance according to the requirement.
British practice is based on the use of unalloyed lead, alloy E (0.4% tin, 0.2%
antimony) and alloy B (0.85% antimony), which have respective fatigue endurance
limits (106 cycles) of 2.8, 6.3 and 9.3 MN/m 2. An exception is that ½C (0.2% tin, 0.1%
cadmium) has better properties for internal pressure cables. Unalloyed lead is quite
satisfactory for most cables, including armoured cables to be shipped overseas. Alloy E
should be used for unarmoured cables and when vibration is suspected. Alloy B is only
required for severe cases, e.g. cables on bridges and for catenary suspension. If there is
any doubt, advice should be sought from the cablemaker. The use of high purity lead is
undesirable (see later).
Different alloys are often favoured in other countries. For the duct jointing manhole
requirements in the USA, various combinations of lead/arsenic/tellurium/bismuth
compositions have shown particularly good properties, the contents of each alloying
Materials Used in Cables 39
Fig. 3.3 Surface of lead sheath showing Fig. 3.4 Etched surface of lead sheath to show
typical cracking due to fatigue the fatigue cracks at crystal boundaries
metal varying between 0.05% and 0.15%. In continental Europe there has been some
preference for alloys containing copper (0.03%-0.05%), often with an addition o f
tellurium (0.04%). Alloys containing antimony in proportions from 0.35% to 1.0% are
also used.
Extrusion defects
When lead sheathing was carried out on hydraulic vertical ram presses, defects were
sometimes caused by the entrapment of impurities as the press cylinder was refilled with
molten lead. This can be overcome by the Glover tray principle in which the charging is
automatic from a bowl of liquid lead on the top of the extrusion cylinder. Such presses
have now largely been replaced by continuous screw type extruders which also
overcame the occasional faulty stop mark that occurred when ram presses were stopped
for recharging with lead.
case of fluid-filled cables it is important to select an alloy which is not subject to grain
growth during the heating period that occurs with one method of impregnation.
Correct choice of alloy for all internal pressure cables is therefore vital. Much testing
is required with conditions relating not only to cable design and processing but also to
the particular type o f extruder to be used for sheathing. Extrusion temperature, grain
size and segregation effects all have a bearing on subsequent stability. Nowadays most
cables in this category are of the fluid-filled type, lead sheathed on a screw press, and
~C alloy has given outstanding service.
Corrosion
Some lead water pipes have survived since R o m a n times but lead may corrode in peaty
or highly alkaline soils. Protection in the form of bitumen or bituminised hessian tape
plus bitumen is normally adequate. Where corrosion does occur the analysis o f
corrosion products will normally show the cause and over the years the main source o f
trouble has been stray direct currents, e.g. from tramways, leaving the sheath.
Purity
Some cable users had a preference for specifying high purity virgin lead. Much
commercial lead is now refined to 99.99% purity and such a material is really best
avoided as it can lead to very large grain size with a single crystal across the sheath. Such a
structure is particularly weak in fatigue and creep properties. BS 801 allows a maximum
impurity content of 0.1% and some alloying metals such as tin or antimony are often
added with advantage up to this limit. While being convenient for the utilisation o f
manufacturing scrap it also provides a better sheath than very high purity lead.
Aluminiumsheaths
A move to reduce the use of lead in U K cables was made in the early 1950s. This
involved marketing 1 kV paper cables which utilised a novel and successful sheathing
procedure involving pulling the insulated cores into a length of oversize aluminium
tubing and then drawing either through a die to reduce the diameter or through a
rotating nut to form a cable sheath with a corrugated rib.
Unfortunately initially it was not appreciated that the apparently good corrosion
resistance of aluminium in free air did not apply to buried conditions. Moreover it had
not then been established that relatively short time tests on small buried samples were not
representative of the differential concentration cell type of corrosion mechanism which
applied with long lengths of aluminium. Consequently the bituminous type finishes,
satisfactory for lead sheaths, were used with somewhat disastrous consequences.
Nevertheless, it was immediately apparent that aluminium sheaths were quite
practicable for handling, up to at least 100 mm diameter, and that they had an economic
attraction for internal pressure cables because of the lack of need for sheath
reinforcement. The corrosion problem was first overcome by the use of plastic and
rubber tapes (chapter 5). Extruded PVC was then coming in as an insulating material and
was an obvious choice for providing a reasonably tough protective jacket for aluminium
sheaths. The combination became an accepted alternative to lead sheaths in the late
1950s and within a decade had become the preferred choice for pressurised cables.
For solid type cables there was little further activity until the later 1960s when,
following experience in Germany, interest developed in the use of combined neutral/
Materials Used in Cables 41
earth distribution cables. The Consac cable (chapter 22) used the aluminium sheath as a
conductor and created an economic design which was soon used in large quantity
(BS5593 1978 (1991)). By this time sheathing by direct extrusion was replacing the
tube sinking process, with the advantages of reduced cost and a lower permissible
sheath thickness. The latter arose because thickness is determined by the ability of
the sheath to bend without any serious buckling and the softer extruded material is
more favourable in this respect.
In the early 1970s the economic advantage of aluminium was extended to I 1 kV
paper insulated cables, as used by the UK Electricity Companies. A price saving of the
order of 20% was obtained at the time.
CorrosioR
Much may be written and indeed has been published about the vulnerability of
aluminium to corrosion and the mechanism by which it may be quickly penetrated by
pinholes. Various aspects are the formation of corrosion cells by differential
concentration and aeration conditions, crevice attack and avoidance of contact with
more electropositive metals. For cables, however, discussions can be avoided by
stipulating that aluminium must never be left exposed and sheaths must always have
appropriate protective finishes. Extruded PVC, polyethylene and high density
polyethylene (chapter 5) have been proved by experience.
Steel tape
This is mild steel of thickness 0.5 mm to 0.8 mm according to cable diameter. The
smaller sizes are cold rolled and the larger hot rolled. They are coated with bitumen by
the supplier and again subsequently during the armouring process. On the basis that
42 Electric Cables Handbook
most external damage to cables occurs in the first few years of life it probably does not
matter that corrosion may be severe after a few more years. On the other hand it can be
argued, as it was with CNE cables (chapter 22), that at 0.5m depth of burial most
damage is due to heavy mechanical plant and the cable would suffer severely whether
armoured or not, i.e. steel tape armour fulfils little purpose.
Continental European practice tends to favour narrow flat steel strip instead of wire
armour but this is probably due to history rather than to any technical or economic
difference. If there is a good case for ensuring that either strip or tape armour has long
life then galvanising is possible and, although much more expensive, such material is
often preferred in the Middle and Far East.
Non-magnetic armour
For single-core cables in a.c. circuits, it is usually preferable to use non-magnetic
material. Wire rather than tape is generally adopted to secure adequate mechanical
protection. Stainless steel is difficult to justify on cost grounds and aluminium is the
normal choice.
BS 6346:1989 caters for PVC cables with aluminium strip armour. Whilst useful if it
is necessary to carry high earth fault currents, the degree of mechanical protection
obtained is not as good as with steel wire armour. Such strip armour now also tends to
be more expensive and is little used.
Paper
Paper for cable making consists of a felted mat of long cellulose fibres derived by
chemical treatment of wood pulp, which mostly comes from North America and
Scandinavia. Digestion with sodium sulphide and caustic soda at high temperature and
pressure removes impurities such as lignin and resins. The paper construction is
generally of 2-ply form, but some 3-ply is used at the highest voltages. The important
physical properties required are controlled by the amount of beating of the pulp,
together with the quantity of thin pulp (93%-95% water) fed to a rotating wire mesh
on which the paper is formed and the amount of subsequent calendering. These factors
determine the thickness, apparent density and impermeability, all of which have to be
adjusted according to the cable type and voltage.
Materials Used in Cables 43
The thicknesses of paper normally used are from 65 to 190 gm. The density varies
from 650 to 1000kg/m 3, and as the density of the actual fibres is around 1500 kg/m 3 a
considerable volume of the space within the fibres is available for filling with
impregnating compound. The impermeability, i.e. the porosity, of the paper can be
adjusted independently of density and can have important effects on final mechanical
and electrical properties. Tensile strength and, more particularly, tearing resistance also
have to be controlled according to application and bending requirements and may have
to take account of the width of the tape which is used. The tensile strength in the
longitudinal and transverse directions is in a ratio of about 2:1.
Vast quantities of water are used in paper making, up to 200 or even 300 tonnes per
tonne of paper, and the quality of the water is important for obtaining the required
electrical properties of the paper. For very high voltage transmission cables, the water
has to be of deionised quality to achieve the highest degree of purity.
The actual properties of the paper selected by the cable manufacturer have also to be
related to the paper-impregnant combination and this is discussed later. Among many
important factors is the ability to obtain a good cable bending performance because
individual layers must slide over each other. Insulation thicknesses vary from 0.6 to
over 30 mm according to voltage and electrical stress and the bending problems increase
progressively with thickness. In addition, to achieve strict control over the individual
paper tape widths and application tensions, the surface finish of the paper is highly
important, as is the tensile strength and thickness, these being increased towards the
outside of the insulation from mechanical considerations. Adjacent to the conductor,
where the electrical stress is highest, thinner papers may be used.
reduction in the permittivity of PPL cable compared to paper cable gives the benefit of a
reduction in the stress in the oil butt gaps. Refer to table 30.2 for typical properties of
PPL insulation.
.005
~ Approximate set point
A Early MIND / ~ of compound
O
._o
~cm .004
-003 compound " ~ /
c
m
{3.
a,,
"6
' 002
/¢ ~
/omoun
Modern MIND
o
O
.0o, .............. -
I
30 5'0 zb I 90
, 110 130
J
Temperature (°C)
Fig. 3.5 Typical coefficient of expansion versus temperature relationships for mass-impregnated
non-draining compound
strength and the properties are chosen to give an elevated softening temperature with
suitable plasticity over the operational temperature range.
Some forms of microcrystalline waxes are obtained from the residues resulting from
the distillation of crude petroleum oils after a solvent extraction process. Others are
derived when the Sasol technique is used in the production of petrol from coal,
principally at present in South Africa. The important feature of microwaxes is their
ability to hold or occlude oil, i.e. to stop the oil from separating from the mixture. This
property is not possessed by macrowaxes such as paraffin wax or the common mineral
waxes, which have a much more coarse crystal structure. Because non-draining
compounds are of complex composition, there may nevertheless be some slight
movement of some of the constituents at elevated temperatures just below the set point
of the compound and consequently a slight loss of relatively fluid impregnant when a
vertical sample of cable is heated in an oven for a drainage test. The total amount is
quite small and together with the expulsion due to thermal expansion of the compound
an amount of 1%-3% is permitted by cable specifications.
Progressive improvements to MIND compounds were made during the 1950s and
1960s. The early compounds contained a high proportion of microcrystalline waxes
having a high coefficient of expansion. This meant that during the impregnation cooling
process, after the compound had reached its set point, no further compound could feed
into the insulation and in the final cooling to room temperature some very small
contraction voids were formed. Figure 3.5 shows that the problem was overcome by
later developments using different waxes. The coefficient of expansion has been much
reduced and the shape of the expansion coefficient-temperature relationship has been
changed so that more expansion occurs above the set point temperature of the
compound. As the compounds were patented, full details have not been published and
this is probably the reason that statements have been made in other countries that non-
draining cables suffer from lower breakdown strength and short-circuit performance.
UK experience has shown that, although the earlier compounds also had somewhat
46 Electric Cables Handbook
lower impulse and a.c. breakdown strength than oil-rosin compounds, the long-term
performance has been much better because the insulation remained fully impregnated
with no loss of impregnant.
Different circumstances apply to high voltage pressure type cables because of the
better electrical quality necessary and the fact that the drainage problem does not arise.
The pre-impregnated paper construction for gas-filled cables uses compounds with
petroleum jelly and polyisobutylene for viscosity control. For fluid-filled cables, the
impregnant must be very fluid so that it readily flows from the cable into pressure tanks
during heating and back on cooling. Resistance to gas evolution under electrical stress
and to oxidation are other key properties necessary. Although highly refined mineral
oils were used for many decades, the increasing stress requirement for modern cables
has led to a change to the use of synthetic alkylates of dodecylbenzene type.
m
i
m
t
50/50 Registration 35t65 Registration
Fig. 3.6 Effect of paper layer registrations on butt-gap alignment: one paper between aligning
gaps with 50/50 registration and two papers with 35/65
Materials Used in Cables 47
0.004
0.003
0
G
0.002
0.001
for the 10-30kV range but for transmission cables it needs to be kept below 0.1%,
Increase in paper density increases the dielectric losses and also the differential
between the permittivity of the paper and the impregnant, so causing greater stresses
in the latter. Effects of partial discharge in butt gaps and dielectric losses are o f
particular importance for transmission cables and are considered in greater detail in
chapter 33.
Figure 3.7 illustrates typical examples of the dielectric loss angle versus temperature
relationship for dry paper, impregnating compounds and impregnated paper for
various types of cables. The actual values may be somewhat displaced according to
Material Temperature
20°C IO0°C
moisture content. The loss angle and permittivity of the composite dielectric are
related to the density of the paper. As the density of the paper increases, and the
space occupied by the impregnant decreases, the higher loss angle and permittivity of
the paper predominate and hence they increase in the composite material. However,
other factors are also involved such as the purity of the paper pulp, to which
reference has been made.
Table 3.3 gives similar data for permittivity. The relative permittivity of dry paper is
related to the ratio of paper fibres and air, as the permittivity of the fibres is of the order of
5.5 compared with 1.0 for air. With increasing density of paper the fibre ratio increases,
and the permittivity of a paper tape is within the range 1.7-3.2 according to density.
In tonnage terms, synthetic polymers have replaced natural materials such as paper,
mineral oil and natural rubber for the insulation of distribution and wiring type cables
and for the oversheathing of cables in general. The range of polymers available is
extensive and variations in chemical composition enable specific mechanical, electrical
and thermal properties to be obtained. Where appropriate, these properties may be
further modified by the addition of specific fillers, plasticisers, softness extenders,
colourants, antioxidants and many other ingredients.
As the variety of polymeric materials has grown, it has become increasingly difficult
to place them all within easy general definitions. A polymer is a molecule, or a
substance consisting of molecules, composed of one or a few structural units repeated
many times. However, this definition embraces not only synthetic materials but also
materials such as paper (cellulose).
In the cable industry the term polymeric material is taken to signify polymers which
are plastics or rubbers. British Standards define plastics as materials based on synthetic
or modified natural polymers which at some stage of manufacture can be formed to
shape by flow, aided in many cases by heat and pressure. Rubbers are considered to be
solid materials, with elastic properties, which are made from latex derived from living
plants or synthetically and used in the manufacture of rubber products.
An elastomer is a material which returns rapidly to approximately its initial shape
after substantial deformation at room temperature by a weak stress and release of that
stress. In cable technology the terms 'rubber' and 'elastomer' are used synonymously
and interchangeably, although 'rubber' to many implies 'natural rubber'.
Plastics may be further divided into thermoplastics and thermosets. A thermoplastic
is a material in which the molecules are held together by physical rather than chemical
bonds. This means that once the material is above its melting point it can flow. The
process is reversible and upon cooling the material hardens. A typical example is
polyvinyl chloride (PVC). The molecules in a thermoset are held together by chemical
bonds which are not easily broken. This means that on heating the polymer does not
soften sufficiently to be reshaped. Typical examples are crosslinked polyethylene
(XLPE) and elastomers. Unlike thermoplastics, thermosets are insoluble and infusible,
i.e. they will not fuse together. Many thermoplastics may be converted to thermosets by
appropriate treatment to induce 'crosslinking', e.g. by the addition of a suitable
chemical crosslinking agent or by irradiation. Rubbers for cable insulation and sheath,
whether natural or synthetic, are normally crosslinked.
Materials Used in Cables 49
The definition o f the terms used in the rubber industry is given in BS 3558: 1980.
C o m m o n names and abbreviations for plastics and rubbers are given in BS 3502:
Parts 1 and 2: 1991.
Table 3.4 shows the typical properties o f some cable insulating and sheathing materials.
Thermoplasticb
Polyvinyl chloride insulation TI 1 12.5 125 70 5
Polyvinyl chloride sheath TM l 12.5 125 70 5
Polyvinyl chloride insulation TI 2 10 150 70 5
Polyvinyl chloride sheath TM 2 10 150 70 5
Polyvinyl chloride insulation TI 3 15 150 90 5
Polyvinyl chloride insulation TI4 12.5 125 70 -25
Polyvinyl chloride sheath TM 3 10 150 85 5
Polyvinyl chloride sheath 5 12.5 125 85 5
Polyethylene c insulation PE 03 7 300 70 -60
Polyethylene c insulation PE 2 7 300 70 -60
Polyethylene sheath TS 2 12.5 300 90
Ordinary duty elastomericb
Rubber insulation El4 5 200 60 -25
Rubber sheath EM 1 7 300 60 -25
Heat resistant insulation GP4 6.5 200 90 -25
Hard insulation GP 6 8.5 200 90 -25
Low temperature insulation EI 6 5 200 90 -40
Flame retardant insulation OR 1 7 200 85 -30
Oil resistant, sheath EM 2 10 300 60 -25
flame retardant
Silicone rubber insulation E12 5 150 180 5
Ethylene insulation El3 6.5 200 110 -25
vinyl acetate
Crosslinked insulation GP8 12.5 200 90 -40
polyethylene
a Maximum temperature for sustained operation and minimum temperature for installation of
cables from BS 7540:1994
b BS 7655:1994 and amendments where appropriate
c BS 6234 for insulation types of polythylene
Table 3.5 shows the electrical properties o f typical insulating materials used in cables.
C o m p o u n d s with improved electrical properties are required for p o w e r distribution
cables operating above 3kV. I E C 5 0 2 requires the p r o d u c t o f permittivity and
dielectric loss angle to be below 0.75 within the temperature range f r o m a m b i e n t to
85°C (chapter 20). In addition the D L A at 80°C m u s t n o t exceed the value at 60°C.
The m a j o r reason for these electrical requirements is that w h e n a length o f o p e n
circuited P V C cable is energised, provided that the voltage is sufficiently high, the
insulation will b e c o m e w a r m even t h o u g h no current is passing t h r o u g h the c o n d u c t o r .
The effect is caused by dielectric heating and the energy loss is given by the e q u a t i o n
Thermoplastic
Polyvinyl chloride TI 1 2× l0 ll 6-7 0.1
Polyvinyl chloride 2 1× 1012 445 0.08-0.1
Polyvinyl chloride TI 2 2x 10 u 6-7 0.094). 1
Polyvinyl chloride 4 1x 109 5-6 0.07-0.13
Polyvinyl chloride 5 5× l0 ll 6 0.9
Polyethylene LD PE03 1x l016 2.35 0.0003
Polyethylene LD PE2 1X 1016 2.35 0.0003
Polyethylene HD 1x 1016 2.35 0.0006
Polypropylene 1× 1016 2.25 0.0005
Elastomeric
General purpose GP rubber E11 2x 1012 4-4.5 0.01-0.03
Heat-resisting MEPR rubber GP4 7x 1012 3-4 0.01-0.02
Flame-retardant rubber FR 1 5× 1012 4.5-5 0.02-0.04
Flame-retardant rubber FR2 1x 1013 4-5 0.015 0.035
OFR rubber OR 1 1x 10 l° 8-11 0.05-0.10
Silicone rubber E12 2× 10 z2 2.9-3.5 0.002-0.02
Ethylene-vinyl acetate EI 3 2× 1012 2.5-3.5 0.002-0.02
Hard ethylene-propylene rubber GP6 2X 1013 3.2 0.01
Crosslinked polyethylene GP 8 1x 1014 2.3-5.2 0.0004-0.005
BS 7655 Parts 3 and 4 for PVC types; Parts 1 and 2 for elastomeric types; and BS6234 for
polyethylene types
Materials Used in Cables 51
B A
u~
c3
E.
O
._~
D
o 1o 20 30 40 50 60 io 8o 9o
Temperature (°C)
Fig. 3,8 Thermal stability of high voltage PVC compounds illustrated by dependence on the
dielectric loss-temperature relationship
Thermoplastic materials
Many of the major thermoplastics in use today were developed in the 1930s and
although some were used for specialised applications during the 1940s it was not until
52 Electric Cables Handbook
the early 1950s that polyvinyl chloride (PVC) and polyethylene (PE) came into
widespread use for electric cables.
~CH2--CH--
I
Cl
PVC polymer cannot be processed by extrusion without the addition of materials
which, inter alia, act as processing aids, e.g. plasticisers and lubricants. PVC is also
strongly polar, because of the C--CI dipole moment, and the addition of plasticisers
also shifts the electrical loss peaks to a lower temperature at constant frequency.
The properties of PVC are such that some grades are suitable as insulation materials
up to 6 kV.
Apart from the plasticisers, other additions to the PVC resin to produce compounds
for electrical applications include fillers and stabilisers. The resin itself is characterised
by its molecular weight and freedom from impurities. The most common plasticiser for
general purpose compounds is dioctyl phthalate and it is often used in conjunction with
a secondary plasticiser such as a chlorinated extender (e.g. Cereclor).
A common filler is calcium carbonate, usually whiting, and it may be coated with a
lubricant such as calcium stearate to aid extrudability. It is not just a diluent but
increases the resistance of the compound to hot deformation. The most common
general purpose stabilisers are lead carbonate and dibasic lead sulphate.
The whole formulation is optimised for mechanical and electrical properties, ease of
processing and cost. The requirements for PVC insulation and sheathing compounds
are given in BS7655. In the IEC format they are included in the standards for the
particular cable types, e.g. IEC 502.
In addition to the general purpose compounds, other formulations are available for
particular applications. Where higher temperature resistance is required, e.g. for the
oversheathing of cables with thermosetting insulation, a less volatile plasticiser such as
didecyl phthalate is beneficial. For high temperature insulation, di-tridecyl phthalate
may be used. For low temperature applications, PVC can be compounded to be flexible
at -40°C by omitting fillers and substituting sebacate or adipate ester plasticisers for
part of the normal phthalates. It is now more usual to use rubber or other thermosetting
materials for such situations. Where PVC is used in power distribution cables operating
above 3kV the filler level is reduced to reduce water absorption under service
conditions, and the secondary plasticiser is omitted to reduce the dielectric loss angle.
The DLA-temperature curves of PVC compounds suitable for low voltage and high
voltage use are illustrated in fig. 3.9.
Coloured oversheaths are sometimes used in accordance with an identification code,
and when buried they may darken or change to a black colour. This is caused by a
reaction between sulphur compounds in the ground and lead stabilisers, with the
formation of lead sulphide. The problem was originally overcome by the use of the
more expensive calcium/barium/cadmium stabiliser systems but the elimination of
cadmium on health and safety grounds has resulted in modern coloured oversheaths
being stabilised by calcium/zinc type systems. While PVC is not as susceptible to
Materials Used & Cables 53
0.10-
LV PVIv C
0.08-
t,-
t~
0.06.
0
=,.
O)
0.04
a
0.02-
Polyethylene
Polyethylene is a semicrystalline polymer with the repeat unit - - C H 2 - - C H 2 - - . It is
available in a variety of grades, differing in chemical structure, molecular weight
and density, which are obtained by the use of different methods of polymerisation.
High density polyethylenes (HDPE), with densities of 945-960kg/m 3, have fewer
and shorter chain branches than low density polyethylenes (LDPE) having densi-
ties of 916-930kg/m 3. Very low density polyethylenes (VLDPE) have densities of
854-910 kg/m 3. A higher density is a direct consequence of higher crystallinity resulting
from reduced chain branching. Among other properties which increase with crystal-
linity are stiffness and melting point. The crystalline melting point increases from 1 l0 to
130°C as the density increases from 916 to 960kg/m 3. The crystaUinity of LDPE is
typically 45%-55% while that of HDPE is 70%-80%.
Two newer classes of polyethylenes which are now being used for cable sheathing are
linear low density polyethylene (LLDPE), made by a low pressure process similar to
that used for HDPE, and medium density polyethylene (MDPE).
Although the properties of polyethylene are often suitable for sheathing applications, it
is more often used as an insulation as it is a non-polar material with excellent electrical
characteristics. Much of the small electrical loss (DLA approximately 10-4) is due to
impurities such as oxidation products generated during processing or residues from the
54 Electric Cables Handbook
polymerisation process. LDPE is used for both insulation and oversheathing. HDPE finds
fewer applications and is mainly used for oversheathing (chapter 5). When polyethylene
was first introduced for oversheathing some failures occurred due to environmental stress
cracking but this problem was overcome by the incorporation of 5% butyl rubber. More
recently the use of copolymers and higher molecular weight polymers having melt flow
indices (MFI) of 0.3 or less (2.16 kg load at 190°C) has also been successful. For insulation
grades attention is given to the molecular weight distribution and the purity of the
polymers. For many applications the only compounding ingredient is a small amount of
antioxidant to prevent oxidation during processing and subsequent use. UK grades are
covered by BS 6234.
Normal grades of LDPE have melting points in the range 110-115°C but begin to
soften in the 80-90°C region. For this reason the maximum continuous operating
temperature of LDPE is limited to 70°C unless it is crosslinked (XLPE), when the
operating temperature can be increased to 90°C. HDPE softens above 110°C.
In direct contact with copper conductors or screening tapes, some embrittlement may
occur and this can be rapid at elevated temperatures. This is caused by oxidation, which
is catalysed by copper, and is inhibited by suitable choice of antioxidant. Polymerised
1,2-dihydro-2,2,4-trimethylquinoline type is used for general purpose applications but
for more severe conditions a copper inhibitor of bishydrazine type is also used.
Polyethylenes are also susceptible to oxidative degradation induced by ultraviolet
radiation and for this reason the addition is recommended to oversheaths of 2.5% of a
fine particle size (20 p.m) carbon black.
A wide range of compositions can be obtained by the incorporation of other
materials. The addition of fillers is limited because they lead to brittleness but small
amounts of butyl or ethylene-propylene rubber may be added to maintain flexibility.
An alternative approach is to use an ethylene copolymer, in which case the second
component increases the flexibility. Vinyl acetate and alkyl acrylates are widely used as
the comonomers and the resulting polymers, when filled with a suitable carbon black,
provide a semiconducting grade with reasonable flexibility. Copolymerisation may also
give considerable improvement in environmental stress cracking resistance for
oversheathing applications. Like all hydrocarbons polyethylene burns readily, which
limits its use in applications where flame retardancy is important.
Polypropylene
The repeated basic unit of polypropylene is
CH3
I
--CH2 - - C H ~
Thermoplastic elastomers
Thermoplastic elastomers are processible on thermoplastic and modified rubber
equipment and have the feel and recovery of vulcanised rubber. A unique property
Materials Used in Cables 55
balance includes outstanding oil resistance, heat ageing and weather resistance coupled
with good general rubber properties. Several types are available, block copolymers and
physical blends of thermoplastics or elastomers dispersed in a thermoplastic matrix.
Nylon
The group of nylon materials contain units which are similar to
O O O
I1 II II
--R'-- C--NH--R--NH--C--R . . C . NH
.
where R and W are usually alkylene groups. These condensation polymers may be
formed from a dibasic acid and a diamine to produce nylon 6, nylon 66 or nylon 11,
where the digits represent the number of carbon atoms in the polymer chain. These
materials have differing softening points, abrasion resistance, and water absorption
and are used in applications where tough, abrasion resistant materials are required
(e.g. oversheathing). Some have good resistance to softening up to about 200°C.
Polyurethanes
Polyurethanes are characterised by the urethane group
O
II
--NH--C--O--
Fluorinated polymers
Polytetrafluoroethylene (PTFE) is by far the most important member of this group and
has a repeat unit of
-- CF 2 -- CF 2 --
The polymer is non-polar and has outstanding electrical properties. It cannot really be
considered to be a true thermoplastic because the melt viscosity is so high that extrusion
is not possible. The insulation has to be applied to conductors by a cold shaping
operation followed by a sintering process to cause the polymer particles to fuse and
coalesce. The good electrical properties are combined with very high resistance to
chemicals and temperature: service operation up to 260°C is possible.
56 Electric Cables Handbook
Because of the high cost and difficulty in processing PTFE, much attention has been
given to other fluorinated monomers which are melt processable. Commercial names of
materials include FEP (DuPont, TFE copolymer with hexafluoropropylene), Tefzel
(DuPont, TFE copolymer with ethylene), Halar (Allied Chemical, ethylene copolymer
with chlorotrifluoroethylene), PFA (DuPont, perfluoroalkoxy branched polymers) and
Dyflor (Dynamit Nobel, polyvinylidene fluoride).
#---k 2 - - - k
O O
Thermoset materials
In the cable industry thermoset polymers have two distinct fields of application. Firstly
rubber type materials having intrinsic flexibility or other required property (e.g. oil
resistance) need to be crosslinked to cater for the thermal conditions arising when some
types of sheath are applied, as well as to provide the required service performance.
Secondly crosslinking provides greater resistance to thermal deformation at higher
cable operating temperature. The need for crosslinking tends to increase cost and so
when a thermoplastic material such as PVC can be used satisfactorily, e.g. for domestic
and industrial wiring cables, it is generally preferred.
In general, specifications are prepared for a particular polymer type but some, such
as BS7655, 'Specification of Insulating and Sheathing Materials for Cables', define
performance characteristics.
CH3
I
-- CH2-- C~ CH--CH 2 --
or --CHz--CH--
I
CH
II
CH2
The properties of SBR are affected by the styrene-to-butadiene ratio and also by the
butadiene configurations (1,2, cis-l,4, trans-l,4). SBR was used for the same
applications as natural rubber and the two were often used in blends according to
the economic conditions. Nowadays, SBR tends to be used as a modifier in rubber
formulations.
CH3
I
mCHzmCm
I
CH3
58 Electric Cables Handbook
Ethylene-propylene rubber ( EP R )
The term EPR encompasses a range of polymers which fall into two classes. Firstly the
saturated copolymers of ethylene and propylene (EPM) form a minor class in which
organic peroxides have to be used for crosslinking. The structural units may be
arranged randomly or in blocks:
CH3
I
--CH2--CH2~ and ~CH2 - - C H - -
(1)
O ~-
CH3
0- 0- C
~;|H3
~ - ~ heat
~.> 2
~ C - O*
I 3
CH
Dicumyl peroxide
(2) CH
0* + RH > <~ ~H3
-C
I
- OH + R*
CH 3
Cumyl alcohol
I heat
v
~ C = CH2 + H20
a -Methyl styrene Water
(3) ~H 3 ~H 3
heat
O C-0*
CH 3
!
, >
(3- C : 0 + CH 3
Acetophenone
(4) CH 3 + RH > CH 4 + R*
(6) ~H 3 CH
~ C-0*
l
+ AH > ~ C - O H + ~ *
(7) CH 3 + CH 3 > CH 3 - CH 3
Ethane
RH = Polyethylene chain
AH = Antloxidant
* = Free radicals
Preparation of G r a f t
RH = Polyethylene
(2) ~H 3
C - OH + R*
I
~H3 CH 3
(3) OCH 3
R* + C H 2 = CH - Si - O C H 3 > R - C H 2 - CH - - OCH 3
I I
OCH 3 OCH 3
R - CH 2 - CH - Si - OCH 3 + RH > R - C H 2 - CH 2- Si - O C H 3 + R*
I
I OCH 3
OCH 3
Crosslinkin~
Catalyst CH
(5) ~CH 3
R - CH 2 - CH 2 - Si - O C H 3 + H20 > R - CH 2 - C H 2 - Si - O H + C H 3 O H
I I
OCH 3 OCH 3
2 R - CH 2 - CH 2 - Si - O H > R - CH 2 - ?i - 0 - Si - CH 2 - CH 2 - R
R - CH 2 - CH 2 - ~i - OH > R - C H 2 - CH 2 - ~i - 0 - Sil - C H 2 - C H 2 - R
OCH 3 OCH 3 OCH 3 + CH30H
+ FCH3
R - CH 2 - CH 2 - Si - O C H 3
~CH 3
Fig. 3.11 Schematic crosslinking mechanism for polyethylene with silane
this reason the extraction method has now been superseded by an elongation test under
a fixed load at 200°C.
A further development of the Sioplas materials has been made by BICC and
Maillefer. This process (Monosil) introduces all the ingredients together by metering
them into the extruder so that the separate grafting stage is eliminated. This ensures
that the material is free from contamination and is thus suitable for cables in the
10-30kV range. It also removes problems due to the limited storage life of the graft
polymer and reduces processing costs.
Because water remains as the crosslinking agent and has to diffuse into the material,
the cure time required is proportional to the square of the thickness. This places a
limitation on extrusion thicknesses which can be handled within a reasonable time
scale. Currently, cure times are of the order of 4 hours at 90°C in water for insulation of
2.5 mm thickness.
Crosslinking by irradiation
Irradiation with fast electrons or ~,-rays produces crosslinking by a mechanism which is
chemically similar to the use of peroxides. It works by a radical process with hydrogen
being evolved. The material to be irradiated comprises only polyethylene with an
antioxidant and so there is no problem of pre-cure in the extruder. However, the
process is only economically suitable for relatively small insulation thicknesses.
--CH2--CH --
I
O
I
CO
I
CH3
Silicone rubber
Silicone rubbers have the general chemical structure
R
I
--Si~O--
I
R
where R is usually methyl or phenyl. Some vinyl groups are also introduced to facilitate
peroxide crosslinking, which with silicones, unlike other rubbers, can be carried out in
hot air.
Silicones have outstanding properties, especially in resistance to high temperatures,
180°C being the normal operating limit. At ambient temperatures the mechanical
properties are somewhat inferior to those of the more commonly used materials,
particularly for sheathing applications. Silica fillers are generally used to provide
reinforcement.
CI
I
CH 2 - - C ~ C H - - C H 2
It has rarely been used by itself for insulation but is often used blended with natural
rubber. Its major use is as a very tough flexible sheathing material. Polychloroprene
compounds have good abrasion and tear resistance together with good resistance to
swelling and to chemical attack by a wide range of natural oils and aliphatic
hydrocarbons. They do not normally support combustion.
- - C H 2 - - C H ~ C H - - CH2 -
and
CN
I
- - C H 2- - C H - -
and
--CH2--CH --
I
CH
II
CH2
Fluorocarbon rubbers
The fluorocarbon rubbers find application for sheathing where very good resistance to
oils is required at high temperatures. The best known material is a copolymer of
vinylidene fluoride and hexafluoropropylene (Viton).
SUMMARY
Tables 3.6 and 3.7 summarise the main uses of thermoplastic and thermoset materials in
cables.
There are many factors which determine the maximum operating temperature of a
material. F o r some thermoplastics, such as polyethylene, the main determining factor is
resistance to deformation. For most thermosets and indeed some thermoplastics,
service life is determined by the susceptibility of the material to thermal degradation at
elevated temperatures. The most common form of degradation is that due to heat and
oxygen. Hydrocarbon polymers oxidise thermally and, because the process is
autocatalytic, large changes in mechanical and electrical properties usually accompany
the onset of oxidation. The chemical process is illustrated in fig. 3.12. The number of
Materials Used in Cables 65
r~
~o~ .~
~ o ~
~.~ ~_
.o ~ "~
0
r..)
.~ ~ ~;> ~
Oo~
"~ 0 <
~,~ ~ o
.~
~ "~ ~ .~ -
f2~ 0
-o= .~ ~ ~ ~9 .~p. p-,
0
0 ,.0
0
q=
r~
f. c~
< 0 0
c~
o~
< <
0
,.0
c~
0,,
I D-.. oo 0.,
c~
"6
Z
"0
E o
.z:
p..,
o
0
0 0 0
Z
66 Electric Cables H a n d b o o k
ca
t&O
¢11
ca ca
0 ,.0
ca
0
,.~
~o ~ o
ca
ca
"~ ~ ;~ ca ~ . . . ~
"~ "~ ~ ~
ca ~
f2~',-, ~. ~ " .a .°
e~
ca ~°~.~-~
•
".~ ~ N .° ,.
~ ~~
,~ ~ o.~ ~ ~'~
~ 0,.~ ,.0
o
Zo ~. ~N ;~ 2~ o ~ . ~ g~
z ~°~ 2~ aas ~ o s
ff
0
~g
e~ N
-d
o
b~ +.a
.E 0 ".~
0
o o o
~ 7
ca
a ca
,.a
ca
,,4 ca
o
~N
[..,
Materials Used in Cables 67
A. Initiation
B. Propagation
C. Termination
CH3
I
--CH2--C~CH--CH-- less stable than --CH2--CH--
I I
H H
Furthermore, since hydrogen abstraction is the key reaction, the most stable polymers
will be those which either have no hydrogen atoms or other labile groups
68 Electric Cables Handbook
CH3--H 435
~-H 435
CH3CH2CH2--H 410
(CH3)2CH--H 393
(CHa)aC--H 381
CH2=CH~EH2--H 356
(e.g. PTFE) or have hydrogen atoms which are relatively inert in methyl or phenyl
groups (e.g. silicones). Antioxidants have removable hydrogens, usually in amine or
phenol moieties. However, the resultant antioxidant radicals are relatively stable and
propagation ceases.
Accelerated ageing tests are often performed to assess the thermal endurance
properties of the material. Guidance on these tests for electrical insulation materials is
given in IEC 214. In these tests it is often found in practice that a plot of the logarithm
of material life against the reciprocal of the absolute temperature is linear. However, it
is unlikely that extrapolations can be readily justified, as the physical manifestation of
degradation is often the result of many reactions of differing importance at high and
low temperatures. For example, at low temperatures chain scission predominates in the
degradation of polyethylene in the early stages with crosslinking predominating after
long time periods. At higher temperatures crosslinking occurs from the start. Also, as
oxygen is mainly taken up by the amorphous regions, the life of semicrystalline
polymers such as polyethylene may be considerably increased below their melting
points (about 100°C). The diffusion of air through cables is relatively slow and for this
reason ageing studies on materials should always be accompanied by studies on
complete cables. Contact with incompatible materials may also affect ageing
performance.
In certain polymers other chemical reactions occur alongside those of chain scission
and crosslinking outlined above. For example, PVC compounds evolve hydrogen
chloride at high temperatures and, using time to first evolution as the failure criterion,
Arrhenius plots can be constructed. In this type of polymer metallic compounds are
often used as the chain terminators.
Polymers differ in their susceptibility to ultraviolet radiation. The problem is usually
confined to a thin surface craze but cracks can propagate through the harder materials
such as polypropylene. The addition of suitable carbon black provides adequate screen-
ing. The organic chromophore type of UV stabiliser is rarely used in cable sheathing.
Finally, one type of degradation, once common, has now almost disappeared.
Cracking due to ozone is a common problem with NR as main chain scission occurs at
the carbon-carbon double bonds which results in cracks under strain. The problem is
much less severe with PCP and non-existent with CSP, EPR, butyl and the common
thermoplastics.