MicroTech® III
Rooftop and Self Contained Unit Controller
Protocol Information
BACnet® Networks
LONWORKS® Networks
Applied Rooftop Models: RPE, RDE, RPS, RDT, RFS, RDS and RAH
Self-Contained Models: SWT, SWP
Maverick™ II Commercial Rooftop Model: MPS
2 ED15112-8
Alarm Notification ....................................................................................... 84 Low Discharge Temp Fault........................................................................ 102
Alarm Clearing ............................................................................................. 85 Low Pressure Circuit 1 Problem ................................................................ 102
Objects.......................................................................................................... 85 Low Pressure Circuit 2 Problem ................................................................ 102
Clear Alarms................................................................................................. 85 Low Pressure Circuit 3 Problem ................................................................ 103
Notification Class - Faults............................................................................ 86 Low Pressure Circuit 4 Problem ................................................................ 103
Notification Class - Problem........................................................................ 87 Low Pressure Circuit 5 Problem ................................................................ 104
Notification Class - Warnings...................................................................... 88 Low Pressure Circuit 6 Problem ................................................................ 104
Warning Alarm............................................................................................. 90 Low Pressure Circuit 7 Problem ................................................................ 104
Problem Alarm ............................................................................................. 91 Low Pressure Circuit 8 Problem ................................................................ 105
Fault Alarm................................................................................................... 92 Mixed Air Temp Problem .......................................................................... 105
Airflow Fault ................................................................................................ 93 Outdoor Temp Problem.............................................................................. 106
Airflow Switch Warning .............................................................................. 93 Return Temp Problem ................................................................................ 106
Conductivity Warning .................................................................................. 94 Space Temp Problem ................................................................................. 106
Control Temp Fault ...................................................................................... 94 Sump Water Level Problem ....................................................................... 107
Dirty Filter Warning..................................................................................... 94 Waterflow Switch Problem ........................................................................ 107
Discharge Sensor Fault................................................................................. 95 Water Regulating Valve Problem .............................................................. 108
Duct High Limit Fault .................................................................................. 95 BACnet Device Management.......................................................109
Emergency Off Fault.................................................................................... 95 DeviceCommunicationControl - Disable................................................... 109
Entering Fan Temp / Leaving Coil Temp Problem ..................................... 96 DeviceCommunicationControl - Enable.................................................... 109
Entering Water Temp Problem .................................................................... 96 ReinitializeDevice (Reset) ......................................................................... 109
Freeze Fault .................................................................................................. 97 Appendix A: Protocol Implementation
Freeze Problem............................................................................................. 97 Conformance Statement (PICS) ..................................................110
Heat Fail Problem......................................................................................... 97 BACnet Protocol Implementation Conformance Statement ..................... 110
High Discharge Temp Fault ......................................................................... 98 Product Description.................................................................................... 110
High Pressure Circuit 1 Problem ................................................................. 98 BACnet Standardized Device Profile ........................................................ 110
High Pressure Circuit 2 Problem ................................................................. 98 Standard Object Types Supported.............................................................. 112
High Pressure Circuit 3 Problem ................................................................. 99 Data Link Layer Options............................................................................ 115
High Pressure Circuit 4 Problem ................................................................. 99 Segmentation Capability ............................................................................ 115
High Pressure Circuit 5 Problem ............................................................... 100 Device Address Binding ............................................................................ 115
High Pressure Circuit 6 Problem ............................................................... 100 Networking Options ................................................................................... 115
High Pressure Circuit 7 Problem ............................................................... 100 Character Sets Supported ........................................................................... 115
High Pressure Circuit 8 Problem ............................................................... 101 Index ..............................................................................................116
High Return Temp Fault ............................................................................ 101
Revision History
ED15112 September 2008 Preliminary release.
ED15112-1 October 29, 2008 Added 2 notification class objects to BACnet. There are now a total of 3 objects (faults, problems & warnings).
ED15112-2 January 22, 2009 The only change was to the Networking Options section of the Protocol Information Conformance Statement
(PICS). The BBMD does support registration by foreign devices. This was previously marked no. Changed the
enumeration for the Water Regulating Valve object from 0=Open and 1=Closed to 0=normal and 1=alarm.
ED15112-3 March 11, 2009 The only change was to the Standard Object Types Supported section of the Protocol Information Conformance
Statement (PICS).
Present Value, Priority Array were removed from the optional list for Binary Outputs. These properties are
required.
Removed Alarm Value from the optional list for Binary Outputs. This is not a propertie of this object. Also
removed Priority Array from Binary Inputs. This is not a property of this object.
Modified the optional properties for Multi-state Input.
Modified the optional properties for Multi-state Output
ED 15112-4 November, 2009 Added Maverick II (MPS) model. Modified keypad navigation per new global standard. Updated points affected
by removal of BACnet heartbeat function (changed points from commandable to writable and removed reference
to writing at priority 8). Added the following points: Heat Fail 199, Heat Fail Problem BV, ERDAT (AV),
EREhht (AV), ERWhlOnOff (MV), ERWheelSpd (AV), Min OA Flw Spt (AV)
ED 15112-5 December, 2009 Changed ER Discharge Air Temp & ER Exhaust Air Temp BACnet object types from AV to AI.Updated
firmware version from 2506017300 to 2506017301 in Software Revision and PICs sections.
ED 15112-6 February, 2010 Changed ER Wheel Speed BACnet object types from AV15 to AI15. Removed reference to energy recovery
from Return Fan Capacity Input & Exhause Fan Capacity Input (Detailed Data Information section). Changed
Application Mode enumerations in detailed data section. Updated PICS to include software v2506017302.
ED 15112-7 June, 2010 Changed nvoUnitStatus_inAlarm_ to nvo WarnAlarm, nvoProbAlarm, and nvoFaultAlarm in detailed data
section. Updated software revision to v2506017304. Removed references to S7 switch on fig. 4.
ED 15112-8 February 2011 Added Control Temp Source (MSV 39) to BACnet. This is available in application 2506017306. Added DAC
checkbox to Relative Humidity Input on the BACnet Standard Objects Table. Added Low/High Pressure Circuit
Switch 7 and 8, added Low/High Pressure Circuit 7 and 8 Problem, changed Sump Pump Switch to Sump Pump
Water Level Switch, changed Sump Pump Fail Problem to Sump Water Level Problem.
ED15112-8 3
Software Revision
Keypad Menu Path Version Information\App Version=
The software part number is encoded in the controller’s memory and is available for display on the keypad/display. The
part number is available via BACnet® system integration tools. The software part number codification is as follows:
250 6017 3 07
Implied digits on all MicroTech III Air Handling software
Base part number (6017 indicates standard software)
Version
Revision
This edition documents Network Protocols for version 2506017307 of the standard MicroTech® III Unit Controller
application and all subsequent versions until otherwise indicated. However, if your software is of a later version, some of
the information in this document may not completely describe your application.
You can determine the revision of the application software from the keypad/display. The path for this information from the
main menu is Version Information\App Version=.
Reference Documents
Company Number Title Source
McQuay International OM 920 MicroTech III Unit Controls for Applied Rooftop and Self- www.mcquay.com
Contained Systems Operation Manual
American Society of Heating, ANSI/ BACnet® A Data Communication Protocol for Building www.ashrae.org
Refrigerating and Air- ASHRAE 135- Automation and Control Networks
Conditioning Engineers 2004
LonMark Interoperability 078-0120-01G LonMark® Layers 1-6 Interoperability Guidelines, Version www.lonmark.org
Association 3.4
LonMark Interoperability 078-0120-01G LonMark Application Layer Interoperability Guidelines, www.lonmark.org
Association Version 3.4
LonMark Interoperability 8500_10 LonMark Functional Profile: Space Comfort Controller, www.lonmark.org
Association Version 1.0
LonMark Interoperability 8600_10 LonMark Functional Profile: Discharge Air Controller, www.lonmark.org
Association Version
McQuay International ED 15113 MicroTech III Rooftop and Self-Contained Systems BACnet www.mcquay.com
Protocol Implementation and Conformance Statement (PICS)
Echelon Corporation 078-0156-01G LONWORKS FTT-10A Free Topology Transceiver Users www.echelon.com
Guide
Notice
© 2011 McQuay International, Minneapolis MN. All rights reserved throughout the world
McQuay International reserves the right to change any information contained herein without prior notice. The user is
responsible for determining whether this product is appropriate for his or her application.
The following are trademarks or registered trademarks of their respective companies: BACnet from American Society
of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Echelon, LONWORKS, LONMARK, and LonTalk from
Echelon Corporation, Windows from Microsoft Corporation, and McQuay, Maverick II and MicroTech III from McQuay
International.
Limited Warranty
Consult your local McQuay Representative for warranty details. Refer to Form 933-430285Y. To find your local McQuay
Representative, go to www.mcquay.com.
4 ED15112-8
Introduction
This document contains the necessary information you need to incorporate a MicroTech III Unit Controller (i.e. Applied
Roofto, Self-Contained, or Maverick II™ Unit) from McQuay International into a building automation system (BAS). It
lists all BACnet® properties, LONWORKS variables, and corresponding MicroTech III Unit Controller data points. It also
contains the BACnet Protocol Implementation Conformance Statement (PICS). BACnet and LONWORKS terms are not
defined. Refer to the respective specifications for definitions and details.
Protocol Definitions
The MicroTech III Unit Controller can be configured in either an interoperable BACnet or LONWORKS network. The
controller must have the corresponding communication module installed for network integration (see Reference Document
section for corresponding part numbers). There are three communication modules: BACnet/IP, BACnet MS/TP
(Master/Slave Token Passing), and LONWORKS. There are two LONWORKS modules: one in accordance with the LonMark
Space Comfort Controller (General) functional profile and one in accordance with the Discharge Air Controller functional
profile.
BACnet Protocol
BACnet is a standard communication protocol for Building Automation and Control Networks developed by the American
National Standards Institute (ANSI) and American Society of Heating, Refrigeration and Air-conditioning Engineers
(ASHRAE) specified in ANSI/ASHRAE standard 135-2004. It addresses all aspects of the various systems that are applied
to building control systems. BACnet provides the communication infrastructure needed to integrate products manufactured
by different vendors and to integrate building services that are now independent.
LONWORKS Networks
A control network specification for information exchange built upon the use of LonTalk for transmitting data developed by
the Echelon Corporation.
LonTalk Protocol
A protocol developed and owned by the Echelon Corporation. It describes how information should be transmitted between
devices on a control network.
LonMark Certification
LonMark certification is an official acknowledgement by the LonMark Interoperability Association that a product
communicates using the LonTalk protocol and transmits and receives data per a standard LonMark functional profile. The
LONWORKS communication modules are LonMark 3.4 certified in accordance with the Space Comfort Controller (SCC) and
Discharge Air Controller (DAC) functional profiles.
ED15112-8 5
Basic Protocol Information
BACnet Networks
Compatibility
The MicroTech III Unit Controller Unit Controller is tested according to the BACnet Testing Laboratory (BTL) Test Plan.
It is designed to meet the requirements of the BACnet Standard (ANSI/ASHRAE 135-2004) as stated in the Protocol
Implementation and Conformance Statement (PICS). However, it is not BTL listed. The PICS is located at the end of this
manual or the separate PICS document, ED 15113 (available on www.mcquay.com.)
BACnet Objects
MicroTech III Unit Controllers incorporate standard BACnet object types (i.e., object types defined in the BACnet
Standard) that conform to the BACnet Standard. Each object has properties that control unit variables or data points. Some
object types occur more than once in the MicroTech III Unit Controller; each occurrence or instance has different properties
and controls different unit variables or data points. Each instance is designated with a unique instance index. Some
properties can be adjusted (read/write properties, e.g., setpoints) from the network and others can only be interrogated (read-
only properties, e.g., status information).
Each data point accessible from a BACnet network is described with a table that gives the Object Identifier, Property
Identifier, Full BACnet Reference or path, and the Name enumeration of the property.
6 ED15112-8
Example of BACnet Data Point
Keypad Menu Path Standard Menus\Flow Summary\Ret/Exh Fan=
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Output 4 1 Present_Value 85
Full Reference
<Device Name>.ExhFanState.Present_Value
Enumeration
0 = Off
1 = On
Object Identifier
Object Identifiers are each designated with an Object type as defined in the BACnet specification. The first column of the
data point definition gives the object type. This object happens to be Return/Exhaust Fan Status (See page 71.)
The object identifier is a property of the object that you can read from the object. The name of the property is
“Object_Identifier” and the property identifier is 75.
Each object in the unit controller has a unique identifier. BACnet object identifiers are two-part numbers of BACnet Object
Identifier data type. The first part identifies the object type (the first 10 bits of the 32-bit BACnet Object Identifier [See
ANSI/ASHRAE 135-2004 BACnet A Data Communication Protocol for Building Automation and Control Networks]). The
first column of the data point definition gives the object type. The second part identifies the instances of that particular
object type (the last 22 bits of the 32-bit BACnet Object Identifier).
The object identifier is shown in the data points listing as two numbers. The first number is shown in the Type ID column
and designates the Object type enumeration. The second number is shown in the Instance column and designates the
instance of that particular object type.
The object identifier is a property of the object that you can read from the object code. The name of the property is
“Object_Identifier” and the property identifier is 75. The ASHRAE BACnet specification reserves the first 128 numbers for
ASHRAE defined objects. Manufacturers may define additional object types and assign a number above 127 as long as they
conform to the requirements of the ASHRAE BACnet specification.
Each object also has a name. Object names are character strings. The object name is a property of the object that you can
read from the object. The name of the property is “Object_Name” and the property identifier is 77.
Objects are sometimes referred to as an object type and instance number as they are in the BACnet specification. The
example object above would be: Binary Output, Instance 1.
Property Identifier
Each object has a number of properties or attributes. Each property has a unique identifier of BACnet Property Identifier
data type. Property identifiers are an enumerated set; a number identifies each member. The Property Identifier enumeration
number is shown in the Property ID column. In the example above the property identifier is 85.
Property Name
Each property also has a unique name. Property names are character strings and shown in the Property Name column. In the
example above the property name is Present Value.
Full Reference
The full reference is the path of the property within the network where the MicroTech III Unit Controller resides. It is a
character string equivalent to the object identifier and the property identifier. In the example above the full reference is
<Device Name>.ExhFanState.Present_Value.
Enumerated Values
Some properties are standard data types and some are enumerated sets. If the property value is an enumerated set, all
enumerated values and corresponding meaning are given in the Enumeration column of the data point listing.
ED15112-8 7
MicroTech III Unit Controller Device Object
Each BACnet compatible device must have one and only one BACnet Device Object.
Device Object Identifier
The MicroTech III Unit Controller Device Object Identifier uniquely specifies the unit within the network. The device
object type for all devices is fixed by ASHRAE at 8. Therefore the device object instance number must be unique. The
initial Device Object identifier is set at manufacturing. The device object identifier can be read from the unit controller. The
name of the property is “Object_Identifier” and the property identifier is 75.
The initial device object instance number is 1579312. This number must be unique on the entire BACnet network. The
object instance number can be changed via the keypad display. You must cycle power for the change to take effect.
! CAUTION
If another device in the network already has this object identifier (instance number), you must change the instance
number of one device object, so that all devices in the network have a unique device identifier.
8 ED15112-8
Property Identifier Default Value Data Type
Segmentation Supported 107 None BACnetSegmentation
Max Segments Accepted 167 16 Unsigned
Local Time3 57 variable Time
3
Local Date 56 variable Date
UTC Offset 119 -120 (Range: –780 .. 780) Integer
Daylight Savings Status 24 variable Boolean
APDU Segment Timeout 10 2000 Unsigned
APDU Timeout 11 3000 Unsigned
Number of APDU Retries 73 3 Unsigned
Device Address Binding 30 Sequence of BACnetAddressBinding
Database Revision 115 1 Unsigned
Active COV Subscriptions 152 List of BACnetCOVSubsriptions
1. For BACnet IP, the last 6 digits are the last 6 digits of the MAC address. The MAC address is printed a sticker affixed
to the BACnet communication module. For BACnet MS/TP, the last 8 digit are computed from the production number
printed on the bar code label affixed to the side of the module.
2. While the MicroTech III Unit Controller supports the entire set of object types, not all object types are used. See the
Object List for details.
3. The BACnet communication module and the MicroTech III Unit Controller both have their own time clocks. The date
and time read via BACnet could differ from the date and time in the unit controller the date or time is changed via the
keypad display. The two time clocks resynchronize approximately every 60-68 minutes and after every power cycle of
the unit controller or BACnet communication module.
Network Considerations
Access to Properties
Object properties are accessible from the network by specifying the device object identifier, object identifier, and the
property identifier. To access a property, you must specify the object identifier including the device object identifier or the
object name including the device object name and the property identifier.
BACnet/IP Addressing
The BACnet/Internet Protocol (BACnet/IP) address of the MicroTech III Unit Controller in a BACnet/IP network consists
of the four-octet Internet Protocol address followed by the two-octet UDP (User Datagram Protocol) port number. The
BACnet/IP address is a six-octet value analogous to a MAC address. The IP address portion of the BACnet/IP address must
be unique in the BACnet/IP network segment. The default UDP port number in the MicroTech III Unit Controller is 47808
(BAC0 in hexadecimal).
The device object of the MicroTech III Unit Controller contains a Given Internet Protocol Subnet Mask (Default is
255.255.255.0) and a default Given IP address of 127.0.0.1. The controller does support DHCP (Dynamic Host
Configuration Protocol) IP addressing which is enabled by default.
The keypad/display can be used to configure the BACnet/IP addressing. The keypad will display the current IP address
only when the network is connected.
The MicroTech III Unit Controller can be incorporated into a BACnet/IP network dedicated to BACnet devices only or an
Ethernet network shared with BACnet devices and other devices.
ED15112-8 9
Configuring the Unit Controller
The MicroTech III Unit Controller with attached BACnet communication module is ready to operate with the default values
of the various parameters. Default values may be changed with the unit’s keypad or via the network. See the MicroTech III
Unit Controller Operation Manual (OM 920).
10 ED15112-8
LONWORKS Networks
LONWORKS technology, developed by Echelon Corporation, is the basis for LonMark interoperable systems. This
technology is independent of the communications media. The LonMark Interoperable Association has developed standards
for interoperable LONWORKS technology systems. In particular they have published standards for HVAC equipment
including the Discharge Air Controller functional profile and the Space Comfort Controller functional profile. These
profiles specify a number of mandatory and optional standard network variables and standard configuration parameters.
This manual defines these variables and parameters available in the MicroTech III Unit Controller.
Compatibility
The MicroTech III Unit Controller with LONWORKS communication module operates in accordance with the Discharge Air
Controller (DAC) functional profile or the Space Comfort Controller (SCC) functional profile of the LonMark
Interoperability standard.
LONWORKS Variables
MicroTech III Unit Controllers incorporate LONWORKS network variables to access unit data points. The unit controller
uses LONWORKS Standard Network Variable Types (SNVT) from each profile. Some data points can be adjusted (input
network variables, nvi) (read/write attributes, e.g., setpoints) from the network and others can only be interrogated (output
network variables, nvo) (read only attributes, e.g., status information). Configuration variables (nci) are included with the
read/write attributes.
Each data point accessible from a LONWORKS network is described with a table that gives the LONWORKS Name, Profile,
SNVT Type, and SNVT Index. If the variable is a configuration variable the table also includes the SCPT Reference and the
SCPT Index.
SNVT Type
This column gives the name of the standard network variable type from the master list.
SNVT Index
This column gives the number of the standard network variable type from the master list.
SCPT Reference
This column gives the name of the Standard Configuration Parameter Type (SCPT) from the master list.
SCPT Index
This column gives the number of the Standard Configuration Parameter Type (SCPT) from the master list.
Network Considerations
Network Topology
Each LONWORKS Communication Module is equipped with an FTT-10A transceiver for network communications. This
transceiver allows for (1) free topology network wiring schemes using twisted pair (unshielded) cable and (2) polarity
insensitive connections at each node. These features greatly simplify installation and reduce network commissioning
problems. Additional nodes may be added with little regard to existing cable routing.
ED15112-8 11
Free Topology Networks
A LONWORKS “free topology network“ means that devices (nodes) can be connected to the network in a variety of
geometric configurations. For example, devices can be daisy-chained from one device to the next, connected with stub
cables branching off from a main cable, connected using a tree or star topology, or any of these configurations can be mixed
on the same network as shown in Figure 1. Free topology segments require termination for proper transmission
performance. Only one termination is required. It may be placed anywhere along the segment. Refer to Echelon
LONWORKS FTT-10A Transceiver User’s Guide for further details (see Reference Documents section).
Free topology networks may take on the following topologies:
Bus
Ring
Star
Mixed - Any combination of Bus, Ring, and Star
Ring Topology
Star Topology
Singly Terminated Bus Topology
Stub
Termination } Termination
Termination
Mixed Topology
Termination
A network segment is any part of the free topology network in which each conductor is electrically continuous. Each of the
four diagrams is a illustration of a network segment. Some applications may require two or more segments; see “Free
Topology Restrictions.” If necessary, segments can be joined with FTT-10A-to-FTT-10A physical layer repeaters. See
Figure 2. Refer to Echelon LONWORKS FTT-10A Transceiver User’s Guide for further details.
Figure 2. Combining Network Segments with a Repeater
FTT-10A
FTT-10A
Termination Termination
12 ED15112-8
Free Topology Restrictions
Although free topology wiring is very flexible, there are restrictions. A summary follows, refer to the Echelon FTT-10A
User’s Guide for details.
1. The maximum number of nodes per segment is 64.
2. The maximum total bus length depends on the wire size:
Wire Size Maximum Node-to-Node Length Maximum Cable Length
24 AWG 820 ft (250 m) 1476 ft (450 m)
22 AWG 1312 ft (400 m) 1640 ft (500 m)
16 AWG 1640 ft (500 m) 1640 ft (500 m)
The longest cable path between any possible pair of nodes on a segment must not exceed the maximum node-to-node
distance. If two or more paths exist between a pair of nodes (e.g., a loop topology), the longest path should be
considered. Note that in a bus topology, the longest node-to-node distance is equal to the total cable length.
a. The total length of all cable in a segment must not exceed the maximum total cable length.
3. One termination is required in each segment. It may be located anywhere along the segment.
Doubly Terminated Networks
You can extend the maximum total cable length without using a repeater by using doubly-terminated network topology. See
Figure 3. The trade-offs are (1) this network topology must be rigorously followed during the installation and subsequent
retrofits and (2) two terminations must be installed at the ends of the bus for proper transmission performance. Refer to
Echelon LONWORKS FTT-10A Transceiver User’s Guide.
Termination Termination
ED15112-8 13
Device addresses are defined at the time of network configuration. All device addresses have three parts. The first part is the
Domain ID, designating the domain. Devices must be in the same domain in order to communicate with each other. The
second part is the Subnet ID that specifies a collection of up to 127 devices that are on a single channel or a set of channels
connected by repeaters. There may be up to 255 subnets in a domain. The third part is the Node ID that identifies an
individual device within the subnet.
A group is a logical collection of devices within a domain. Groups are assembled with regard for their physical location in
the domain. There may be up to 256 groups in domain. A group address is the address that identifies all devices of the
group. There may be any number of devices in a group when unacknowledged messaging is used. Groups are limited to 64
devices if acknowledged messaging is used.
A broadcast address identifies all devices within a subnet or domain.
LONWORKS network variables for both the Discharge Air Controller and the Space Comfort Controller are defined below.
Variables are used in both the Space Comfort Controller and Discharge Air Controller profiles unless marked otherwise.
Data Integrity
The integrity of some data depends on a valid network connection to maintain current values. The following data points
require a valid network connection if bound. If data points listed in Table 2 do not change after a given time, the controller
reverts to local control. In the case of the LonWorks module, the variables will revert to their default values.
14 ED15112-8
Table 2. Receive Heartbeat Variables
Data Point LonWorks Variable
Occupancy Scheduler Input nviOccSchedule
Application Mode nviApplicCmd
Supply Fan Capacity Input nviSupFanCap
Outdoor Air Temperature nviOutdoorTemp
Space Temperature nviSpaceTemp
Primary Cool Enable nviPriCoolEnable
Primary Heat Enable nviPriHeatEnable
Economizer Enable nviEconEnable
Exhaust Fan Capacity Input nviExhFanCap
Return Fan Capacity Input nviRetFanCap
Water Flow Switch Input nviCWFlow
Space Indoor Air Quality (IAQ) Input nviSpaceIAQ
Relative Humidity Input nviSpaceRH
ED15112-8 15
Typical Application: Minimum Integration
When you have integrated the unit into your network, you can monitor and control unit operation from your workstation. At
a minimum, you can:
Display and monitor a minimum of important data points on your workstation display
Turn the unit on or off from your workstation
Set the schedule from your workstation and
Operate the unit safely
This section gives you the basic information and outlines a procedure to set up the unit for network control.
Network Off
The unit can be turned off over the network by writing to the Application Mode. Writing AUTO to Application Mode
allows the unit controller to determine its mode of operation based on input conditions. Writing OFF to Application Mode
shuts down the unit, etc.
The Emergency Override Mode Flag can also be used to shut down the unit from the network.
16 ED15112-8
Alarms
Alarms in a MicroTech III Unit Controller are divided into three classes: Faults, Problems, and Warnings.
Fault Alarms have the highest priority.
Problem Alarms have medium priority.
Warning Alarms have the lowest priority.
Notification
BACnet
MicroTech III Unit Controllers may have their alarms monitored by one of four methods: 1) individually by BACnet Binary
Values, 2) Alarm value using one BACnet Analog Value, 3) Alarm class, or 4) Notification Classes.
1. To monitor alarms individually, read the Present_Value of the desired Binary Value object. Each alarm has its own
Binary Value object. If the Present_Value is Inactive (0), the alarm is not active. If the Present_Value is Active (1),
the alarm is active.
2. To monitor alarms by alarm value, read the Present_Value property of the Alarm Value Analog Value object. The
Present_Value displays a value that corresponds to the highest priority alarm that is active. It is possible to have
multiple active alarms, but only the highest priority is displayed. For example, if there is a simultaneous Dirty Filter
Warning (value of 24) and a Freeze Fault (value of 252), then the Freeze Fault value of 252 will display in the
Present_Value because it is the higher priority alarm of the two. Once the Freeze Fault condition is corrected and the
fault is cleared, the next priority active alarm value (in this example, value of 24 for Dirty Filter alarm) is displayed.
The values for all alarms are described in the Alarms section tables. If the Present_Value displays a zero, there are no
active alarms.
3. To monitor alarms by alarm class, read the Present_Value of the appropriate Analog Value object (Warnings, Problems
and Faults). The Present_Value displays a value that corresponds to the highest priority alarm that is active for that
particular alarm class. It is possible to have multiple active alarms, but only the highest priority is displayed.
4. To monitor alarms using the Notification Class objects, see the Alarm Notification section.
LONWORKS
MicroTech III Unit Controllers may have their alarms monitored by one of two methods: 1) by using the In_alarm attribute
of nvoUnitStatus or 2) by alarm class.
1. Alarms within MicroTech III Unit Controllers can be monitored individually by using the In Alarm attribute of the Unit
Status Network Variable Output (i.e. nvoUnitStatus_in_alarm). This attribute displays a value that corresponds to the
highest priority alarm that is active. It is possible to have multiple active alarms, but only the highest priority is
displayed in this attribute. For example, if there is a simultaneous Dirty Filter Warning (value of 24) and a Freeze Fault
(value of 252), then the Freeze Fault value of 252 will display in nvoUnitStatus_in_alarm because it is the higher
priority alarm of the two. Once the Freeze Fault condition is corrected and the fault is cleared, the next priority active
alarm value (in this example, value of 24 for Dirty Filter alarm) is displayed. The values for all alarms are described in
the Alarms section tables. If the attribute nvoUnitStatus_in_alarm displays a zero, there are no active alarms.
When the nvoUnitStatus_in_alarm attribute reads a value in the range of 1 to 99, a Warning Alarm is active. When the
attribute reads a value in the range of 100 to 199, a Problem Alarm is active. When the attribute reads a value in the
range of 200 to 255, a Fault Alarm is active.
2. To monitor alarms by alarm class, read nvoWarnAlarm, nvoProbAlarm and nvoFaultAlarm. The value corresponds to
the highest priority alarm that is active. It is possible to have multiple active alarms, but only the highest priority is
displayed.
Clearing
BACnet
MicroTech III Unit Controllers have one Multi-State Value objects that can be used to clear alarms. All alarms of a
particular class may be cleared by writing the appropriate value to the Present Value property of ClearAlarms
(2=ClearAllFaults, 3=ClearAllProblems, 4=ClearAllWarnings). All alarms of all three classes can be cleared by writing a 5
(ClearAllAlarms) to Present_Value. Once the alarms are cleared, the Present_Value of this object goes back to None (1).
LONWORKS
MicroTech III Unit Controllers have one variable that can be used to clear alarms; nviClearAlarms. All alarms of a
particular class may be cleared by writing the appropriate value to nviClearAlarms (1=ClearAllFaults, 2=ClearAllProblems,
ED15112-8 17
3=ClearAllWarnings). All alarms of all three classes can be cleared by writing a 4 (ClearAllAlarms) to nviClearAlarms.
Once the alarms are cleared, this variable goes back to None (0).
18 ED15112-8
Comprehensive Data Point Tables
These comprehensive data point tables contain the significant parameters of specific data points. The shaded data points
with numbers are the data points listed in Table 3.
Read, Write
Instance
(Keypad attributes available as
Object
Page
Type
DAC
SCC
BACnet Standard Objects for Description
network control of the unit)
Unit Status/Settings
Unit State 76 R MSV 15 1=Off, 2=Start, 3=Recirc, 4=FanOnly, 5=MinDAT, 6=Htg,
7=Econo, 8=Clg
McQuay AHU Unit Status 53 R MSV 1 Mode: 1=Enabled, 2=OffMan, 3=OffManCtrl, 4=OffNet,
5=OffAlm, 6=OffFanRetry
Cooling Status 32 R MSV 2 1=Enabled, 2=None, 3=OffAmb, 4=OffAlarm, 5=OffNet,
6=OffMan
Heating Status 45 R MSV 4 1=Enabled, 2=None, 3=OffAmb, 4=OffAlarm (Not Used),
5=OffNet, 6=OffMan
Economizer Status 37 R MSV 3 1=Enabled, 2=None, 3=OffAmb, 4=OffAlarm (Not Used),
5=OffNet, 6=OffMan
Cooling Capacity 32 R AV 1 cooling capacity (%)
Heating Capacity 44 R AV 2 heating capacity (%)
Supply Fan Capacity 74 R AI 8 Current supply fan capacity (%)
Return/Exhaust Fan Capacity 70 R AI 10 Current return or exhaust fan capacity (%)
Economizer Capacity 36 R AV 15 Feedback value (%)
Emergency Override 39 W MSV 10 1=Normal, 2=Off (Shuts unit off via a network signal, puts
Unit Status = OffNet)
Application Mode1 28 W MSV 5 1=Off, 2=HeatOnly, 3=CoolOnly, 4=FanOnly, 5=Auto, 6=NA
Applies only when Ctrl Mode=Auto
Occupancy
Occupancy 58 R MSV 6 1=Occ, 2=Unocc, 3=TntOvrd
Occupancy Mode 59 W MSV 7 1=Occ, 2=Unocc, 3=TntOvrd, 4=Standby (not used) 5=Auto.
Temperatures
Control Temperature 32 R AI 14 Current reading of sensor
Discharge Air Temperature 34 R AI 1 Current reading of sensor
Return Air Temperature 70 R AI 2 Current reading of sensor
Space Temperature 73 R AI 3 Current reading of sensor
Outdoor Air Temperature 63 R AI 4 Current reading of sensor
Entering Fan / Leaving Coil Temp 40 R AI 7 Current reading of sensor
Entering Water Temperature 42 R AI 6 Current reading of sensor
Mixed Air Temperature 55 R AI 5 Current reading of sensor
Flow Status
Exhaust Fan Status 71 R BV 1 0=Off, 1=On
VAV Box Output 78 R MSV 14 N/A 1=Heat (Off), 2=Cool (On)
SAF Spd Control
Duct Static Pressure 35 R AV 6 N/A Current reading of sensor. If unit has two sensors the lower of
the two is displayed
Duct Static Pressure Setpoint 35 W AV 7 N/A Default = 1.00” WC
Remote Supply Fan Capacity 69 W MSV 11 1=DSP, 2=Speed, 3=Space
Control Flag
Supply Fan Capacity Input1 75 W AV 21 N/A Default = 163.835 (Null)
Applies only when MSV11=Speed (2)
RF/EF Spd Control
Building Static Pressure 30 R AI 9 Current reading of sensor value
Building Static Pressure Setpoint 30 W AV 8 Default = 0.050” WC
ED15112-8 19
Network Control Property
Read, Write
Instance
(Keypad attributes available as
Object
Page
Type
DAC
SCC
BACnet Standard Objects for Description
network control of the unit)
20 ED15112-8
Network Control Property
Read, Write
Instance
(Keypad attributes available as
Object
Page
Type
DAC
SCC
BACnet Standard Objects for Description
network control of the unit)
ED15112-8 21
Network Control Property
Read, Write
Instance
(Keypad attributes available as
Object
Page
Type
DAC
SCC
BACnet Standard Objects for Description
network control of the unit)
22 ED15112-8
Network Control Property
Read, Write
Instance
(Keypad attributes available as
Object
Page
Type
DAC
SCC
BACnet Standard Objects for Description
network control of the unit)
Note: Objects that appear in multiple locations on the keypad are only listed in the location they first appear on the
keypad. Not all menus and items shown here will appear on keypad depending upon the specific unit
configuration. Those that do not appear are not applicable to the unit.
ED15112-8 23
LONWORKS Variables
Network Control Property
Keypad attributes available as
LONWORKS Variables for network SNVT/SCPT
Page Variable Name SCC DAC Description
control of the unit Index
System
Unit State 76 nvoUnitStatus 112 Mode 0=AUTO, 1=HEAT,
2=MRNG_WRMUP, 3=COOL, 6=OFF,
9=FAN_ONLY, 10=FREE_COOL,
0XFF=NUL
McQuay AHU Unit Status 53 nvoMcQAHUStatus N/A Mode: 0=Enabled, 1=OffManCtrl, 2=OffMan,
3=OffNet, 4=OffAlm, 5=OffFanRetry
Cooling Status 32 nvoMcQAHUStatus N/A 0=Enabled, 1=None, 2=Off Amb, 3=Off Alarm,
4=Off Net, 5=Off Man
Heating Status 45 nvoMcQAHUStatus N/A 0=Enabled, 1=None, 2=Off Amb, 3=Off Alarm
(Not Used), 4=Off Net, 5=Off Man
Economizer Status 37 nvoMcQAHUStatus N/A 0=Enabled, 1=None, 2=Off Amb, 3=Off Alarm
(Not Used), 4=Off Net, 5=Off Man
Cooling Capacity 32 nvoUnitStatus 112 nvoUnitStatus.cool_output(%)
Heating Capacity 43 nvoUnitStatus 112 nvoUnitStatus.heat_output_primary(%)
Supply Fan Capacity 74 nvoUnitStatus 112 Fan_Output Current supply fan capacity (%)
Return/Exhaust Fan Capacity 70 nvoExhFanStatus 95 Current return or exhaust fan capacity (%)
Economizer Capacity 36 nvoUnitStatus 112 Economizer_Output Feedback value (%)
Emergency Override 39 nviEmergOverride 103 0=NORMAL, 4=SHUTDOWN, 0xFF=NUL
(other states not used)
Application Mode 28 nviApplicMode 108 0=AUTO, 1=HEAT, 3=COOL, 6=OFF,
9=FAN_ONLY (other states not used)
Occupancy
Occupancy 58 nvoEffectOccup 109 0=OCCUPIED, 1=UNOCCUPIED,
2=BYPASS, 3=STANDBY, 0xFF=NUL
Occupancy Mode 59 nviOccManCmd 109 0=OCCUPIED, 1=UNOCCUPIED, 2=
BYPASS, 3=STANDBY, 0xFF=NUL
Temperature
Discharge Air Temperature 34 nvoDischAirTemp 105 Current reading of sensor
Return Air Temperature 70 nvoRATemp 105 Current reading of sensor
Space Temperature 73 nvoSpaceTemp 105 Current reading of sensor
Outdoor Air Temperature 63 nvoOutdoorTemp 105 Current reading of sensor
Entering Fan / Leaving Coil Temp 40 nvoEFT_LCT 105 Current value of sensor
Entering Water Temperature 42 nvoCWTemp 105 Current value of sensor
Mixed Air Temperature 55 nvoMATemp 105 N/A Current value of sensor
Mixed Air Temperature 55 nvoMixedAirTemp 105 N/A Current value of sensor
Flow Summary
Return/Exhaust Fan Status 71 nvoExhFanStatus 95 State: 0=Off, 1=On , -1(0xFF)=Undefined
VAV Box Output 80 nvoVAVBoxOut N/A N/A 0=Heat (Off), 1=Cool (On)
SAF Spd Control
Duct Static Pressure 35 nvoDuctStatPress 113 N/A Current reading of sensor. If unit has two
sensors the lower of the two is displayed
Duct Static Pressure Setpoint 35 nviDuctStaticSP 113 N/A Default = 1.00” WC
Remote Supply Fan Cap Control Flag 69 nviSupFanCtrl N/A 0=Duct Press, 1=Speed
Supply Fan Capacity Input 75 nviSupFanCap 81 N/A Default = 25% Sets the discharge air VFD speed
when Supply Fan Capacity Control Flag is set to
Speed
RF/EF Spd Control
Building Static Pressure 30 nvoBldgStatPress 113 Current reading of sensor value
Building Static Pressure Setpoint 30 nviBldgStaticSP 113 Default = 0.050” WC
Remote Return/Exhaust Fan Cap 68 nviExhRetFanCtrl N/A 0=None, 1=Tracking, 2=Bldg Press, 3=Speed
Control Flag
24 ED15112-8
Network Control Property
Keypad attributes available as
LONWORKS Variables for network SNVT/SCPT
Page Variable Name SCC DAC Description
control of the unit Index
ED15112-8 25
Network Control Property
Keypad attributes available as
LONWORKS Variables for network SNVT/SCPT
Page Variable Name SCC DAC Description
control of the unit Index
26 ED15112-8
Network Control Property
Keypad attributes available as
LONWORKS Variables for network SNVT/SCPT
Page Variable Name SCC DAC Description
control of the unit Index
Note: Objects that appear in multiple locations on the keypad are only listed in the location they first appear on the
keypad. Not all menus and items shown here will appear on keypad depending upon the specific unit
configuration. Those that do not appear are not applicable to the unit.
ED15112-8 27
Detailed Data Point Information
The data points or properties (attributes) defined in this section reference data that is generated in the MicroTech III Unit
Controller.
AHU Loc/Net
Keypad Menu Path Main Menu\BMS Communications\BACnet MSTP Set-Up\AHU Loc/Net=
Main Menu\BMS Communications\BACnet IP Set-Up\AHU Loc/Net=
This read only attribute indicates whether the unit controller is set to use local or network inputs. AHU Loc/Net is only
changeable at the keypad/display.
Measurement Units Data Type Valid Range Uses Heartbeat Default Value
State N/A BACnet: Unsigned Enumerated N/A Network
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Multistate Value 19 38 Present_Value 85
Full Reference
<Device Name>.AHULoc/Net.Present_Value
Enumeration
1 = Network
2 = Local
LonWorks
No LONWORKS equivalent.
Application Mode
Keypad Menu Path Main Menu\View/Set Unit\Unit Status/Settings\Net App Mode=
This read/write attribute sets the unit in an application mode (auto, off, heat only, cool only, or fan only). This attribute has
no affect unless Control Mode is set to Auto. Control Mode is only set at the keypad/display.
Measurement Units Data Type Valid Range Uses Heartbeat Default Value
Mode N/A BACnet: Unsigned Enumerated Yes N/A
LonWorks: Real
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Multistate Value 19 5 Present_Value 85
Full Reference
<Device Name>.ApplicCmd.Present_Value
Enumeration
1= Off
2 = Heat
3= Cool
4= Fan Only
5= Auto
6= N/A
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviApplicMode DAC, SCC Yes SNVT_hvac_mode 108
28 ED15112-8
Enumeration Definitions
Value Identifier Notes
0 HVAC_AUTO Controller automatically changes between application modes
1 HVAC_HEAT Heating only
2 HVAC_MRNG_WRMUP Application-specific morning warm-up (Not Used)1
3 HVAC_COOL Cooling only
4 HVAC_NIGHT_PURGE Application-specific night purge (Not Used) 1
5 HVAC_PRE_COOL Application-specific pre-cool (Not Used) 1
6 HVAC_OFF Controller not controlling outputs
7 HVAC_TEST Equipment being tested (Not Used) 1
8 HVAC_EMERG_HEAT Emergency heat mode (heat pump) (Not Used) 1
9 HVAC_FAN_ONLY Air not conditioned, fan turned on
10 HVAC_FREE_COOL Cooling with compressor not running (Not Used) 1
11 HVAC_ICE Ice-making mode (Not Used) 1
12 HVAC_MAX_HEAT (Not Used) 1
13 HVAC_ECONOMY Controller automatically changes between application modes (Not Used) 1
14 HVAC_DEHUMID Controller automatically changes between application modes (Not Used) 1
0xFF HVAC_NUL Value not available
1. Writing to a state that is not used by the unit controller causes it to control as if HVAC_AUTO (0) was selected.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 1 Present_Value 85
Full Reference
<Device Name>.AirFlwSw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
ED15112-8 29
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 2 Present_Value 85
Full Reference
<Device Name>.AirFlwWrSw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
Application Version
Keypad Menu Path Main Menu\About this AHU\App Version=
This read-only property identifies the version of application software loaded into the unit controller.
Measurement Units Data Type Valid Range Default Value
N/A N/A CharacterString N/A N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Device 8 Variable Application_Software_Version 12
Full Reference
<Device Name>. Application_Software_Version
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 9 Present_Value 85
Full Reference
<Device Name>.BldgStatPress.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoBldgStatPress DAC, Yes SNVT_temp_p 105
McQuayRTU-SCC
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviBldgStaticSP DAC, No SNVT_press_p 113
McQuayRTU-SCC
Conductivity
Keypad Menu Path Main Menu\Commission Unit\Evap Cond Set-Up\Conductivity=
This read only property provides the conductivity of the water in the sump of an evaporative cooled condenser. This
variable only applies to units with evaporative condensing.
Measurement Units Data Type Valid Range Default Value
Conductivity N/A Real 0-5000 N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 12 Present_Value 85
Full Reference
<Device Name>.Conductivity.Present_Value
LONWORKS
LonWorks Name Profile Uses Heartbeat UNVT Type SNVT Number
nvoConductivity McQuayDischargeAir, Yes UNVTconductivity N/A
McQuayRTU-SCC
ED15112-8 31
LONWORKS
No LONWORKS equivalent
Control Temperature
Keypad Menu Path Main Menu\Quick Menu\Control Temp=
Main Menu\View/Set Unit\Temperatures\Control Temp=
This read-only property indicates the current control temperature.
Measurement Units Data Type Valid Range Default Value
Temperature °F / °C Real -50.0–249.998°F N/A
-45.56°–121.11°C
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 14 Present_Value 85
Full Reference
<Device Name>.ControlTemp.Present_Value
LONWORKS
No LONWORKS equivalent
Cooling Capacity
Keypad Menu Path Main Menu\Quick Menu\Clg Capacity=
Main Menu\View/Set Unit\Unit Status\Settings\Clg Capacity=
This read-only property indicates the current percentage of unit maximum cooling capacity. The BACnet property reads
only the subject attribute; however the LONWORKS variable is only a part of the LONWORKS Unit Status network variable.
See Page 76 for details of LONWORKS network variable. The BACnet property only applies to the subject data point. The
LONWORKS variable covers six other data points: Unit State, Heating Capacity, Reheat Capacity, Supply Fan Capacity,
Economizer Capacity, and In Alarm. This variable only applies if the unit is configured for cooling.
Measurement Units Data Type Valid Range Default Value
Percent % BACnet: Real 0-100% N/A
LONWORKS: Structure
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 1 Present_Value 85
Full Reference
<Device Name>.ClgCapacity.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoUnitStatus.cool_output DAC, SCC Yes SNVT_hvac_status 112
Cooling Status
Keypad Menu Path Main Menu\View/Set Unit\Unit Status/Settings\Clg Status=
This read-only attribute indicates whether or not cooling is currently enabled. If cooling is disabled, the reason is indicated.
Measurement Units Data Type Valid Range Default Value
State N/A BACnet: Unsigned Enumerated N/A
LonWorks: Real
32 ED15112-8
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Multistate Value 19 2 Present_Value 85
Full Reference
<Device Name>.ClgStatus.Present_Value
Enumeration
1=Enabled
2=None
3=Off Amb
4=Off Alarm
5=Off Net
6=Off Man
LONWORKS
LONWORKS Name Profile Uses Heartbeat UNVT Type SNVT Index
nvoMcQAHUStatus.ClgStatus McQuayDischargeAir, No UNVTmcQAHUStatus N/A
McQuayRTU-SCC
Enumeration
0=Enabled
1=None
2=Off Ambient
3=Off Alarm
4=Off Net
5=Off Man
Date
Keypad Menu Path Main Menu\View/Set Unit\Date/Time/Schedules\Date=
This read/write property sets the current date of the form day, month, year, and day of the week.
Values Dates as BACnet date data types. See ANSI/ASHRAE 135-2004 for a definition of the data type.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Device 8 Variable Local_Date 56
Full Reference
<Device Name>.Local_Date
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 41 Present_Value 85
Full Reference
<Device Name>.DewpointSP.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviSpaceDewPtSP McQuayDischargeAir, No SNVT_temp_p 105
McQuayRTU-SCC
ED15112-8 33
Dew Point Temperature
Keypad Menu Path Main Menu\View/Set Unit\Dehumidification\Dewpoint=
This read-only attribute indicates the current dew point calculated from the current reading of the optional relative humidity
sensor.
Measurement Units Data Type Valid Range Default Value
Temperature °F / °C Real -50°–150°F N/A
-45.56°–65.56°C
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 20 Present_Value 85
Full Reference
<Device Name>.SpaceDewPt.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoSpaceDewPt SCC, Yes SNVT_temp_p 105
McQuayDischargeAir
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 3 Present_Value 85
Full Reference
<Device Name>.DirtyFilterSw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
34 ED15112-8
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoDischAirTemp DAC, SCC Yes SNVT_temp_p 105
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 6 Present_Value 85
Full Reference
<Device Name>.DuctStatPress.Present_Value
LonWorks
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoDuctStatPress DAC Yes SNVT_press_p 113
ED15112-8 35
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 7 Present_Value 85
Full Reference
<Device Name>.DuctStaticSP.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviDuctStaticSP DAC No SNVT_press_p 113
Economizer Capacity
Keypad Menu Path Main Menu\Quick Menu\OAD/Econo Cap=
Main Menu\View/Set Unit\Economizer\OAD/Econo Cap=
This read-only attribute indicates the current economizer capacity or outdoor air damper position. The BACnet property
reads only the subject attribute; however the LONWORKS variable is only a part of the LONWORKS Unit Status network
variable. See Unit State on page 76 for details of LONWORKS network variable. The BACnet property only applies to the
subject data point. The LONWORKS variable covers six other data points: Unit State (See page 76), Cooling Capacity (See
page 32), Heating Capacity (See page 43), Reheat Capacity (See page 67), Supply Fan Capacity (See page 74), and In
Alarm (See page 88).
Measurement Units Data Type Valid Range Default Value
Percent Percent BACnet: Real 0-100% N/A
LONWORKS: Structure
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 15 Present_Value 85
Full Reference
<Device Name>.EconCapacity.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoUnitStatus.econ_output DAC, SCC Yes SNVT_hvac_status 112
Economizer Enable
Keypad Menu Path Main Menu\Service Menus\Network Input Status\Net Ec Ena Sw=
Main Menu\Service Menus\Network Input Status\Net Ec Ena Vl=
This read/write configuration property enables or disables the economizer. This variable only applies if the unit is
configured for a waterside or airside economizer. In BACnet, if EconEnable is 0, then the economizer is disabled. If it is 1
and EconEnaPercent is 0, the economizer is disabled. If EconEnable is 1 and EconEnaPercent is greater than 0, the
economizer is enabled. The LONWORKS point nviEconEnable has two properties; a State and a Value. When the State = 0,
economizer control through the network is disabled. When State = 1, the Economizer can be controlled through the
network. When the Value = 0 and the State = 1, the economizer is disabled through the LONWORKS network. When the
Value is greater than 0 and the State = 1, the economizer is enabled through the LONWORKS network.
Measurement Units Data Type Valid Range Uses Heartbeat Default Value
State N/A BACnet: Real Enumerated Yes N/A
LONWORKS: Structure
36 ED15112-8
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 32 Present_Value 85
Full Reference
<Device Name>.EconEnable.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviEconEnable DAC, SCC Yes SNVT_switch 95
Valid Range
State Value Economizer
0 N/A Disabled
1 0 Disabled
1 1-100% Enabled
-1(0xFF) N/A Auto (invalid)
Economizer Status
Keypad Menu Path Main Menu\View/Set Unit\Unit Status/Settings\EconoStatus=
This read-only attribute indicates whether or not the economizer is currently enabled. If the economizer is disabled, the
reason is indicated.
Measurement Units Data Type Valid Range Default Value
State N/A BACnet: Unsigned Enumerated N/A
LonWorks: Real
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Multistate Value 19 3 Present_Value 85
Full Reference
<Device Name>.EconoStatus.Present_Value
Enumeration
1=Enabled
2=None
3=Off Amb
4=Off Alarm (Not Used)
5=Off Net
6=Off Man
7=Off Dehum
ED15112-8 37
LONWORKS
LONWORKS Name Profile Uses Heartbeat UNVT Type SNVT Number
nvoMcQAHUStatus.EconStatus McQuayDischargeAir, No UNVTmcQAHUStatus N/A
McQuayRTU-SCC
Enumeration
0=Enabled
1=None
2=Off Amb
3=Off Alarm (Not Used)
4=Off Net
5=Off Man
6=Off Dehum
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 39 Present_Value 85
Full Reference
<Device Name>.EffDATempSP.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoEffDATempSp DAC Yes SNVT_temp_p 105
38 ED15112-8
Measurement Units Data Type Valid Range Default Value
Temperature °F / °C Real 0.0°-100.0°F N/A
-17.78°-37.78°C
BACnet
No BACnet equivalent.
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type Number
nvoEffectSetpt SCC, Yes SNVT_temp_p 105
McQuayDischargeAir
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 22 Present_Value 85
Full Reference
<Device Name>.EmergencyOffSw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
Emergency Override
Keypad Menu Path Main Menu\View/Set Unit\Unit Status/Settings\Emerg Mode=
This read/write property shuts off the unit controller. If this property is set to Off, the unit controller cannot start based on a
time clock or any other means. The only way to start the unit controller is to change the value to Normal. If a value other
than Off or EMERG_SHUTDOWN, is written, this variable reverts back to Normal.
Measurement Units Data Type Valid Range Uses Heartbeat Default Value
N/A N/A BACnet: Unsigned Enumerated No Normal
LonWorks: Real
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Multistate Value 19 10 Present_Value 85
Full Reference
<Device Name>.EmergOverride.Present_Value
Enumeration
1 = Normal
2 = Off
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviEmergOverride DAC, SCC No SNVT_hvac_emerg 103
ED15112-8 39
Enumeration Definitions
Value Identifier Notes
0 EMERG_NORMAL No emergency mode
1 EMERG_PRESSURIZE Emergency pressurize mode (not used)
2 EMERG_DEPRESSURIZE Emergency depressurize mode (not used)
3 EMERG_PURGE Emergency purge mode (not used)
4 EMERG_SHUTDOWN Emergency shutdown mode
5 EMERG_FIRE (not used)
0xFF EMERG_NUL Value not available
Enumeration Correspondence
BACnet Lon
1 Normal 0 EMERG_NORMAL
1 Normal 1 EMERG_PRESSURIZE
1 Normal 2 EMERG_DEPRESSURIZE
1 Normal 3 EMERG_PURGE
2 Off 4 EMERG_SHUTDOWN
1 Normal 5 EMERG_FIRE
1 Normal 0xFF EMERG_NUL
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 16 Present_Value 85
Full Reference
<Device Name>.ERDAT.Present_Value
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 17 Present_Value 85
Full Reference
<Device Name>.ERExhTemp.Present_Value
LONWORKS
No LONWORKS equivalent.
40 ED15112-8
Energy Recovery Wheel Status
Keypad Menu Path Main Menu\Commission Unit\Energy Rec Set-Up\Wheel==
This read-only attribute indicates the command status (On or Off) of the energy recovery wheel.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Multi-State Value 0 37 Present_Value 85
Full Reference
<Device Name>.ERWhlOnOff.Present_Value
Enumeration
0 = Off
1 = On
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 15 Present_Value 85
Full Reference
<Device Name>.ERWheelSpd.Present_Value
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 7 Present_Value 85
Full Reference
<Device Name>.EFT_LCT.Present_Value
ED15112-8 41
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoEFT_LCT DAC, SCC Yes SNVT_temp_p 105
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 6 Present_Value 85
Full Reference
<Device Name>.CWTemp.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoCWTemp DAC, Yes SNVT_temp_p 105
McQuayRTU-SCC
This read-only property indicates the current capacity of the exhaust fans.
Measurement Units Data Type Valid Range Default Value
Fan Status N/A BACnet: Real Enumerated N/A
LONWORKS: Structure
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 Present_Value 85
Full Reference
<Device Name>.ExhFanValue.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoExhFanStatus.value DAC, Yes SNVT_switch 95
McQuayRTU-SCC
Field Definitions
Field Units Valid Range Notes
value % of Full Scale 0-100% 0-100%
state N/A 0, 1 0=Off, 1=On
42 ED15112-8
Exhaust Fan Capacity Input
Keypad Menu Path Main Menu\Commission Unit\RF/EF Set-Up\Rem ExhF Cap=
This read/write property is used to override the local exhaust fan capacity control. EF Cap Ctrl must be set to Speed for the
MicroTech III Unit Controller to use this remote capacity for control. This variable only applies to units that are configured
for modulating exhaust fan or that are configured for prop exhaust.
Measurement Units Data Type Valid Range Uses Heartbeat Default Value
Capacity Percent Real 0-100% Yes N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 23 Present_Value 85
Full Reference
<Device Name>.ExhFanCapNetIn.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviExhFanCap DAC, Yes SNVT_lev_percent 81
McQuayRTU-SCC
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 19 Present_Value 85
Full Reference
<Device Name>.FreezeFltSw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
ED15112-8 43
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 20 Present_Value 85
Full Reference
<Device Name>.FreezeSw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 23 Present_Value
Full Reference
<Device Name>.FSGAlarmSw.Present_Value
Enumeration
0 – Normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
Heating Capacity
Keypad Menu Path Main Menu\Quick Menu\Htg Capacity=
Main Menu\View/Set Unit\Unit Status/Settings\Htg Capacity=
This read-only attribute indicates the current percentage of unit maximum heating capacity. The BACnet property reads
only the subject attribute and only applies to the subject data point. The LONWORKS variable is only a part of the
LONWORKS Unit Status network variable. See Unit State on page 76 for details of LONWORKS network variable. The
LONWORKS variable covers six other data points: Unit State (See page 76), Supply Fan Capacity (See page 74), Secondary
Heating (Reheat) Capacity (See page 67), Economizer Capacity (See page 36), and In Alarm (See page 88). This variable
only applies to units configured with heating.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 2 Present_Value 85
Full Reference
<Device Name>.HtgCapacity.Present_Value
44 ED15112-8
LONWORKS
LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoUnitStatus.heat_output_primary DAC, SCC Yes SNVT_hvac_status 112
Heating Status
Keypad Menu Path Main Menu\View/Set Unit\Unit Status/Settings\Htg Status=
This read-only attribute indicates whether or not heating is currently enabled. If heating is disabled, the reason is indicated.
Measurement Units Data Type Valid Range Default Value
State N/A BACnet: Unsigned Enumerated N/A
LonWorks: Real
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Multistate Value 19 4 Present_Value 85
Full Reference
<Device Name>.HtgStatus.Present_Value
Enumeration
1=Enabled
2=None
3=Off Amb
4=Off Alarm (Not Used)
5=Off Net
6=Off Man
LONWORKS
LONWORKS Name Profile Uses Heartbeat UNVT Type SNVT Number
nvoMcQAHUStatus.HtgStatus McQuayDischargeAir, No UNVTmcQAHUStatus N/A
McQuayRTU-SCC
Enumeration
0=Enabled
1=None
2=Off Amb
3=Off Alarm (Not Used)
4=Off Net
5=Off Man
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 4 Present_Value 85
Full Reference
<Device Name>.HiPress1Sw.Present_Value
Enumeration
0 – Open
1 – Closed
ED15112-8 45
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 5 Present_Value 85
Full Reference
<Device Name>.HiPress2Sw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 6 Present_Value 85
Full Reference
<Device Name>.HiPress3Sw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
46 ED15112-8
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 7 Present_Value 85
Full Reference
<Device Name>.HiPress4Sw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 8 Present_Value 85
Full Reference
<Device Name>.HiPress5Sw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 9 Present_Value 85
Full Reference
<Device Name>.HiPress6Sw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
ED15112-8 47
High Pressure Circuit 7 Switch
Keypad Menu Path No Keypad Equivalent
This read-only BACnet object indicates the condition of the High Pressure Circuit 7 Switch (Closed (1) or Open (0)). The
OffNormal state of this object indicates a High Pressure Circuit 7 Problem.
Measurement Units Data Type Valid Range Default Value
Alarm N/A Enumerated 0-1 N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 26 Present_Value 85
Full Reference
<Device Name>.HiPress7Sw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 27 Present_Value 85
Full Reference
<Device Name>.HiPress8Sw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
BACnet
No BACnet equivalent.
48 ED15112-8
LONWORKS
LonWorks Name Profile SNVT Type SNVT Index SCPT Reference SCPT Index
nciHvacType SCC SNVT_hvac_type 145 SCPThvacType 169
Local OA Temperature
Keypad Menu Path No Keypad Equivalent
This read-only attribute indicates the current outdoor air temperature from the local outdoor air temperature sensor. This
variable only applies if the unit is configured for an outdoor air temperature sensor.
Measurement Units Data Type Valid Range Default Value
Temperature °F / °C Real -50°–150°F N/A
-45.56°-65.56°C
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 5 Present_Value 85
Full Reference
<Device Name>.LocalOATemp.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoLocalOATemp DAC, Yes SNVT_temp_p 105
McQuayRTU-SCC
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 4 Present_Value 85
Full Reference
<Device Name>.LocalSpaceTmp.Present_Value
ED15112-8 49
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoLocalSpaceTmp SCC, Yes SNVT_temp_p 105
McQuayDischargeAir
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 11 Present_Value 85
Full Reference
<Device Name>.LoPress2Sw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
50 ED15112-8
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 12 Present_Value 85
Full Reference
<Device Name>.LoPress3Sw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 13 Present_Value 85
Full Reference
<Device Name>.LoPress4Sw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 14 Present_Value 85
Full Reference
<Device Name>.LoPress5Sw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
ED15112-8 51
Low Pressure Circuit 6 Switch
Keypad Menu Path No Keypad Equivalent
This read-only BACnet object indicates the condition of the Low Pressure Circuit 6 Switch (Closed (1) or Open (0)). The
OffNormal state of this object indicates a Low Pressure Circuit 6 Problem.
Measurement Units Data Type Valid Range Default Value
Alarm N/A Enumerated 0-1 N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 15 Present_Value 85
Full Reference
<Device Name>.LoPress6Sw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 24 Present_Value 85
Full Reference
<Device Name>.LoPress7Sw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
52 ED15112-8
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 25 Present_Value 85
Full Reference
<Device Name>.LoPress8Sw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 18 Present_Value 85
Full Reference
<Device Name>.DefaultDATHtgSetpt.Present_Value
LONWORKS
LONWORKS Name Profile SNVT Type SNVT Index SCPT Reference SCPT Index
nciDAHtSP DAC SNVT_temp_p 105 SCPTdischargeAirHeatingSetpoint 184
ED15112-8 53
LONWORKS
LONWORKS Name Profile Uses Heartbeat UNVT Type SNVT Number
nvoMcQAHUStatus.Mode McQuayDischargeAir, Yes UNVTmcQAHUStatus N/A
McQuayRTU-SCC
Measurement UNVTmcQAHUStatus
Type Category Structure
Type Size 2 bytes
Valid Range (Resolution) See Below. The value –1 (NUL) represents invalid value.
Uses Receive Heartbeat Yes
Field Definitions
Field Description
EconStatus 0 = Enabled
1 = None
2 = Off Ambient
3 = Off Alarm
4 = Off Net
5= Off Man
6= Off Dehum
ClgStatus 0 = Enabled
1 = None
2 = Off Ambient
3 = Off Alarm
4 = Off Net
5= Off Man
HtgStatus 0 = Enabled
1 = None
2 = Off Ambient
3 = Off Alarm
4 = Off Net
5= Off Man
Mode 0 = Enabled,
1 = Off Man
2 = Off Man Ctrl
3 = Off Net
4 = Off Alarm
5 = Off Fan Retry
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 14 Present_Value 85
Full Reference
<Device Name>.DefaultDATClgSetpt.Present_Value
54 ED15112-8
LONWORKS
LONWORKS Name Profile SNVT Type SNVT Index SCPT Reference SCPT Index
nciDAClSP DAC SNVT_temp_p 105 N/A N/A
BACnet
No BACnet equivalent.
LONWORKS
LONWORKS Name Profile SNVT Type SNVT Index SCPT Reference SCPT Index
nciMinOutTm DAC, SCC SNVT_time_sec 107 SCPTminSendTime 52
The following network variables are limited by nciMinOutTm if the timer is greater than zero:
Send Heartbeat Table
nvoMcQAHUStatus nvoLocalOATemp nvoEffDATempSp
nvoUnitStatus nvoEFT_LCT nvoEffectSetpt
nvoEffectOccup nvoDuctStatPress nvoExhFanStatus
nvoDischAirTemp nvoBldgStatPress nvoConductivity
nvoRATemp nvoSpaceRH nvoMATemp
nvoSpaceTemp nvoSpaceDewPt nvoCWTemp
nvoOutdoorTemp nvoSpaceCO2 nvoOAFlow
nvoLocalSpaceTmp
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 5 Present_Value 85
Full Reference
<Device Name>.MATemp.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoMATemp DAC Yes SNVT_temp_p 105
ED15112-8 55
Network Discharge Air Cooling Setpoint
Keypad Menu Path Main Menu\Service Menus\Network Input Status\Net Dat Clg Spt
This read/write property sets the Network Cooling Discharge Setpoint. This setpoint is set to this value when reset type is
set to network. The unit controller internally limits the Present Value that is written between the Min Clg Spt (AV14) and
the Max Clg Spt (see the Cooling menu on the unit controller keypad/display).
Measurement Units Data Type Valid Range Uses Heartbeat Default Value
Temperature °F / °C Real 39.992 – 100.0°F No 55°F / 12.78°C
4.44°–37.78°C
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 13 Present_Value 85
Full Reference
<Device Name>.DAClgSetpt.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviDAClSP DAC No SNVT_temp_p 105
Measurement Units Data Type Valid Range Uses Heartbeat Default Value
Temperature °F / °C Real 39.992–140.0°F No 100°F / 37.78°C
4.44°–60°C
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 17 Present_Value 85
Full Reference
<Device Name>.DAHtgSetpt.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviDAHtSP DAC No SNVT_temp_p 105
Object Request
Keypad Menu Path No Keypad Equivalent
This input network variable provides the mechanism to request an operation or a mode for a functional block within a
device. A request consists of an object ID (the object_id field) and an object request (the object_request field). The object
ID is the functional block index for a functional block on the device. The Node Object functional block is index zero. The
remaining functional blocks are numbered sequentially, starting with one.
56 ED15112-8
RQ_UPDATE_STATUS - Requests the status of the specified functional block to be sent to the nvoStatus output
network variable. The state of the functional block is unchanged. An RQ_ UPDATE_STATUS request that specifies
the Node Object functional block is a request for the status of the device and all functional blocks on the device. The
status bits of the Node Object (with the exception of invalid_request and invalid_id) are defined to be the inclusive-
OR of the status bits of all the other functional blocks in the device; with the possible addition of error conditions and
other conditions attributed to the device as a whole, rather than to any individual functional block. For example, if
comm_failure is supported for the Node Object, then it should be set when reporting the Node Object functional block
status whenever any of the functional blocks in the device reports communications failure, as well as when there is a
communications failure at the device level.
RQ_REPORT_MASK - Requests a status mask reporting the status bits that are supported by the specified functional
block to be sent to the nvoStatus output network variable. A one bit in the status mask means that the device may set
the corresponding bit in the object status when the condition defined for that bit occurs. A zero bit in the status mask
means that the bit is never set by the device.
Measurement Units Data Type Valid Range Uses Heartbeat Default Value
Object Request N/A Structure N/A No N/A
BACnet
No BACnet equivalent
LONWORKS
LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Number
nviRequest Node Object No SNVT_obj_status 93
Object Status
Keypad Menu Path No Keypad Equivalent
This output network variable reports the status for any functional block on a device. It is also used to report the status of the
entire device and all functional blocks on the device. A status update consists of an object ID (the object_id field) and
multiple status fields. The object ID is the functional block index as described under nviRequest. If the object ID is zero,
the status of the device itself and all functional blocks on the device is reported. The status fields are one-bit bitfields. The
only supported status fields are the report_mask, invalid_id, and invalid_request fields; all other status fields are not
supported.
invalid_request - Set to one if an unsupported request code is received on the nviRequest input network variable.
invalid_id - Set to one if a request is received for a functional block index that is not defined in the device. No further
checking of the request code is required when set to one.
ED15112-8 57
report_mask Set to one if an RQ_REPORT_MASK request is received by the nviRequest input network variable,
and the nvoStatus output network variable is set to contain the status mask. The status mask is an nvoStatus value that
describes the status bits that are supported beyond the three mandatory status bits. The status mask consists of all fields
in the nvoStatus output network variable, with the exception of the report_mask, invalid_id, and invalid_request
fields. A one bit in the mask means that the functional block may set the corresponding bit in the nvoStatus output
network variable when the condition defined for that bit occurs. A zero bit means that the functional block may never
set the bit.
Field Definitions
Field Units Valid Range Notes
object_id unsigned long 0 to 65,535 2 bytes
invalid_id unsigned 0, 1 1 bit (offset 0)
invalid_request unsigned 0, 1 1 bit (offset 1)
Disabled unsigned 0, 1 1 bit (offset 2) - Not Used
out_of_limits unsigned 0, 1 1 bit (offset 3) - Not Used
open_circuit unsigned 0, 1 1 bit (offset 4) - Not Used
out_of_service unsigned 0, 1 1 bit (offset 5) - Not Used
mechanical_fault unsigned 0, 1 1 bit (offset 6) - Not Used
feedback_failure unsigned 0, 1 1 bit (offset 7) - Not Used
over_range unsigned 0, 1 1 bit (offset 0) - Not Used
under_range unsigned 0, 1 1 bit (offset 1) - Not Used
electrical_fault unsigned 0, 1 1 bit (offset 2) - Not Used
unable_to_measure unsigned 0, 1 1 bit (offset 3) - Not Used
comm_failure unsigned 0, 1 1 bit (offset 4) - Not Used
fail_self_test unsigned 0, 1 1 bit (offset 5) - Not Used
Self_test_in_progress unsigned 0, 1 1 bit (offset 6) - Not Used
locked_out unsigned 0, 1 1 bit (offset 7) - Not Used
manual_control unsigned 0, 1 1 bit (offset 0) - Not Used
in_alarm unsigned 0, 1 1 bit (offset 1) - Not Used
in_override unsigned 0, 1 1 bit (offset 2) - Not Used
report_mask unsigned 0, 1 1 bit (offset 3)
programming_mode unsigned 0, 1 1 bit (offset 4) - Not Used
programming_fail unsigned 0, 1 1 bit (offset 5) - Not Used
Alarm_notify_disabled unsigned 0, 1 1 bit (offset 6) - Not Used
reset_complete unsigned 0, 1 1 bit (offset 7) - Not Used
reserved2 unsigned 0 to 0 8 bits (offset 0) - Not Used
Occupancy
Keypad Menu Path Main Menu\View/Set Unit\Occupancy\Occupancy=
This read-only property indicates if the unit is currently in an occupied, unoccupied, or tenant override mode of operation.
Measurement Units Data Type Valid Range Default Value
Occupancy N/A BACnet: Unsigned Enumerated N/A
LonWorks: Real
58 ED15112-8
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Multistate Value 19 6 Present_Value 85
Full Reference
<Device Name>.EffectOccup.Present_Value
Enumeration
1 = Occ
2 = Unocc
3 = TntOvrd
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoEffectOccup DAC, SCC Yes SNVT_occupancy 109
Enumeration Definitions
Value Identifier Notes
0 OC_OCCUPIED Area is occupied
1 OC_UNOCCUPIED Area is unoccupied
2 OC_BYPASS Area is temporarily occupied for the bypass period
3 OC_STANDBY Area is temporarily unoccupied
0xFF OC_NUL Value not available
Enumeration Correspondence
BACnet Occupancy Lon SNVT_occupancy
1 Occ 0 OC_OCCUPIED
2 Unocc 1 OC_UNOCCUPIED
3 TntOvrd 2 OC_BYPASS
1 Occ 3 OC_STANDBY
3 Auto 0xFF OC_NUL
Occupancy Mode
Keypad Menu Path Main Menu\Service Menus\Network Input Status\OccManCmd
This read/write property sets the unit into a different occupancy mode. The request is typically sent by a wall-mounted
occupant-interface module or a supervisory node, typically used to manually control occupancy modes or to override the
scheduled occupancy. This input is used with nviOccSchedule to determine the effective occupancy mode. Refer to
Occupancy (nvoEffectOccup) section for more information.
Measurement Units Data Type Valid Range Uses Heartbeat Default Value
Mode N/A BACnet: Unsigned Enumerated No Auto or NUL
LonWorks: Real
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Multistate Value 19 7 Present_Value 85
Full Reference
<Device Name>.OccManCmd.Present_Value
Enumeration
1 = Occ
2 = Unocc
3 = TntOvrd
4 = Standby (Same as Occ)
5 = Auto
ED15112-8 59
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviOccManCmd DAC, SCC No SNVT_occupancy 109
Enumeration Definitions
Value Identifier Notes
0 OC_OCCUPIED Area is occupied
1 OC_UNOCCUPIED Area is unoccupied
2 OC_BYPASS Area is temporarily occupied for the bypass period
3 OC_STANDBY Controller reacts as if the area is occupied.
0xFF OC_NUL Value not available
Enumeration Correspondence
BACnet nviOccManCmd Lon SNVT_occupancy
1 Occ 0 OC_OCCUPIED
2 Unocc 1 OC_UNOCCUPIED
3 TntOvrd (Bypass) 2 OC_BYPASS
1 Occ 3 OC_STANDBY
4 Auto 0xFF OC_NUL
Field Definitions
Field Data Point Reference Units Valid Range Notes
current_state Occupancy Scheduler Input occup_t current scheduled occupancy state
next_state Occupancy Scheduler Next occup_t next scheduled occupancy state
time_to_next_state Occupancy Scheduler Time minutes 0 to 65534 65535=Null
Enumeration Correspondence
BACnet LONWORKS
1 Occupied 0 OC_OCCUPIED
0 Unoccupied 1 OC_UNOCCUPIED
3 TntOvrd 2 OC_BYPASS
1 Occupied 3 OC_STANDBY
5 NUL 0xFF OC_NUL
ED15112-8 61
LONWORKS
LONWORKS Name Profile SCPT Reference SCPT Index SNVT Type SNVT Index
nciSetpoints.Occupied_Cool DAC, SCC SCPTsetPnts 60 SNVT_temp_setpt 106
Field Definitions
Field Notes
Occupied_cool Occupied Cooling Setpoint
Standby_cool Standby Cooling Setpoint (Not Used)
Unoccupied_cool Unoccupied Cooling Setpoint
Occupied_heat Occupied Heating Setpoint
Standby_heat Standby Heating Setpoint (Not Used)
Unoccupied_heat Unoccupied Heating Setpoint
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 11 Present_Value 85
Full Reference
<Device Name>.OccHeatSP.Present_Value
LONWORKS
LONWORKS Name Profile SCPT Reference SCPT Index SNVT Type SNVT Index
nciSetpoints.occupied_heat DAC, SCC SCPTsetPnts 60 SNVT_temp_setpt 106
Field Definitions
Field Notes
Occupied_cool Occupied Cooling Setpoint
Standby_cool Standby Cooling Setpoint (Not Used)
Unoccupied_cool Unoccupied Cooling Setpoint
Occupied_heat Occupied Heating Setpoint
Standby_heat Standby Heating Setpoint (Not Used)
Unoccupied_heat Unoccupied Heating Setpoint
62 ED15112-8
Measurement Units Data Type Valid Range Uses Heartbeat Default Value
Position Percent Real 0–100% No N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 16 Present_Value 85
Full Reference
<Device Name>.MinOAPosNetIn.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviOAMinPos DAC, SCC No SNVT_lev_percent 81
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 4 Present_Value 85
Full Reference
<Device Name>.OutdoorTemp.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoOutdoorTemp DAC, SCC Yes SNVT_temp_p 105
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 29 Present_Value 85
Full Reference
<Device Name>.OutdoorTempInput.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviOutdoorTemp DAC, SCC Yes SNVT_temp_p 105
ED15112-8 63
Outdoor Airflow
Keypad Menu Path Main Menu\Commission Unit\Min OA Set-Up\OA Flow=
This read-only property indicates the Outdoor Airflow. This variable only applies to units configured for design flow.
Measurement Units Data Type Valid Range Default Value
Flow Volume ft3/min (CFM) or l/s BACnet: Real 0-60007.25 CFM N/A
LonWorks: Unsigned Long 0-28320 l/s
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 42 Present_Value 85
Full Reference
<Device Name>.OAFlow.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoOAFlow DAC, Yes SNVT_flow 15
McQuayRTU-SCC
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 53 Present_Value 85
Full Reference
<Device Name>.MinOAFlowSpt.Present_Value
LONWORKS
No LONWORKS equivalent.
64 ED15112-8
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 34 Present_Value 85
Full Reference
<Device Name>.CoolEnable.Present_Value
Enumeration
0 = Off
1 = Enable
LONWORKS
LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Number
nviPriCoolEnable DAC, Yes SNVT_switch 95
McQuayRTU-SCC
Valid Range
State Value Cooling
0 N/A Disabled
1 0 Disabled
1 1-100 Enabled. Value equals the percentage of cooling that is enabled when State equals 1.
-1(0xFF) N/A Auto (invalid)
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 36 Present_Value 85
Full Reference
<Device Name>.HeatEnable.Present_Value
Enumeration
0 = Off
1 = Enable
ED15112-8 65
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 37 Present_Value 85
Full Reference
<Device Name>.HeatEnablePct.Present_Value
LONWORKS
LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Number
nviPriHeatEnable DAC, Yes SNVT_switch 95
McQuayRTU-SCC
Valid Range
State Value Heating
0 N/A Disabled
1 0 Disabled
1 1-100 Enabled. Value equals the percentage of cooling that is enabled when State equals 1.
-1(0xFF) N/A Auto (invalid)
Receive Heartbeat
Keypad Menu Path Main Menu\BMS Communications\LON Set-Up\Rcv Hrt Bt=
This read/write configuration property defines the maximum time that elapses after the last update to a specified network
variable input before the unit starts to use its default values.
Measurement Units Data Type Valid Range Default Value
Time Seconds BACnet: Real 0.0–6553.4 sec 0 seconds
LonWorks: Unsigned Long
BACnet*
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 43 Present_Value 85
Full Reference
<Device Name>.ReceiveHeartbeat.Present_Value
*Note: This point is not supported for BACnet with MicroTech III unit controller application version 2506017300or newer.
LONWORKS
There are three categories for deciding to use Receive Heartbeat that are based on the network input variable being specified
in the Receive Heartbeat table and being bound. The unit controller uses Category 1 and Category 2.
66 ED15112-8
Network Specified for Receive Bound? Result: Use Receive
Variable Input Heartbeat in Table? Heartbeat?
Category 1 Yes Yes Yes
Category 2 Yes No Manufacture Defined
Category 3 Yes Don’t Care No
LONWORKS Name Profile SNVT Type SNVT Index SCPT Reference SCPT Index
nciRcvHrtBt DAC, SCC SNVT_time_sec 107 SCPTmaxRcvTime 48
Reheat Capacity
Keypad Menu Path Main Menu\Quick Menu\Reheat Cap=
Main Menu\View/Set Unit\Unit Status/Settings\Reheat Cap=
Main Menu\View/Set Unit\Dehumidification\Reheat Cap=
This read-only attribute indicates the current percentage of unit reheat capacity. The BACnet property reads only the
subject attribute and only applies to the subject data point. The LONWORKS variable is only a part of the LONWORKS Unit
Status network variable. See Unit State on page 76 for details of LONWORKS network variable. The LONWORKS variable
covers six other data points: Unit State (See page 76), Supply Fan Capacity (See page 74), Cooling Capacity (See page 32),
Heating Capacity (See page 43), Economizer Capacity (See page 36), and In Alarm (See page 88).
This variable only applies to units configured with cooling.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 44 Present_Value 85
Full Reference
<Device Name>.ReheatCapacity.Present_Value
LONWORKS
LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoUnitStatus.heat_output_secondary DAC, SCC Yes SNVT_hvac_status 112
Relative Humidity
Keypad Menu Path Main Menu\Quick Menu\Rel Humidity=
Main Menu\View/Set Unit\Unit Status/Settings\Rel Humidity=
Main Menu\View/Set Unit\Dehumidification\Rel Humidity=
Main Menu\Commission Unit\Energy Rec Set-Up\Rel Humidity=
This read-only property indicates the current reading of the optional relative humidity sensor.
Measurement Units Data Type Valid Range Default Value
Relative Humidity Percent Real 0%–100% N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 11 Present_Value 85
Full Reference
<Device Name>.SpaceRH.Present_Value
Enumeration
1=DSP
2=Speed
3=Space
ED15112-8 67
LONWORKS
LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoSpaceRH DAC, SCC Yes SNVT_lev_percent 81
Enumeration
0=DSP
1=Speed
2=Space
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 19 Present_Value 85
Full Reference
<Device Name>.SpaceRHNetIn.Present_Value
LONWORKS
LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Index
nviSpaceRH DAC, SCC Yes SNVT_lev_percent 81
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 40 Present_Value 85
Full Reference
<Device Name>.HumiditySP.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviSpaceDehumSP DAC, No SNVT_lev_percent 81
McQuayRTU-SCC
68 ED15112-8
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Multistate Value 19 12 Present_Value 85
Full Reference
<Device Name>.ExhRetFanCtrl.Present_Value
Enumeration
1= None
2= Tracking
3= BldgP
4= Speed
5= OAD
LONWORKS
LONWORKS Name Profile Uses Heartbeat UNVT Type SNVT Index
nviExhRetFanCtrl McQuayDischargeAir, No UNVTexhRetFanCtrl N/A
McQuayRTU-SCC
Enumeration
0= None
1= Tracking
2= Bldg Pres
3= Speed
LONWORKS
LONWORKS Name Profile Uses Heartbeat UNVT Type SNVT Index
nviSupFanCtrl McQuayDischargeAir No UNVTsupFanCtrl N/A
Enumeration
0 = Duct Press
1 = Speed
ED15112-8 69
Return Air Temperature
Keypad Menu Path Main Menu\View/Set Unit\Temperatures\Return Air=
This read-only attribute that indicates the current reading from the unit return air temperature sensor. This variable only
applies if the unit is configured for a return air sensor.
Measurement Units Data Type Valid Range Default Value
Temperature °F / °C Real -20°–199.994°F N/A
-28.89°–93.33°C
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 2 Present_Value 85
Full Reference
<Device Name>.RATemp.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoRATemp DAC, Yes SNVT_temp_p 105
McQuayRTU-SCC
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 10 Present_Value 85
Full Reference
<Device Name>.ExhFanValue.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoExhFanStatus.value DAC, No SNVT_switch N/A
McQuayRTU-SCC
Field Definitions
Field Units Valid Range Notes
value % of Full Scale 0-100% 0-100%
state N/A 0, 1 0=Off, 1=On
70 ED15112-8
Exhaust Fan Status
Keypad Menu Path Main Menu\View/Set Unit\Flow Status\Ret/Exh Fan=
This read-only property indicates whether the unit controller is commanding the return or exhaust fan on. This variable only
applies to units configured for a return/exhaust fan.
Measurement Units Data Type Valid Range Default Value
Fan Status N/A BACnet: Enumerated Enumerated N/A
LONWORKS: Structure
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 1 Present_Value 85
Full Reference
<Device Name>.ExhFanState.Present_Value
Enumeration
0 = Off
1 = On
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoExhFanStatus.State DAC, No SNVT_switch N/A
McQuayRTU-SCC
Field Definitions
Field Units Valid Range Notes
value % of Full Scale 0-100% 0-100%
state N/A 0, 1 0=Off, 1=On
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 22 Present_Value 85
Full Reference
<Device Name>.RetFanCapNetIn.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviRetFanCap DAC, McQuayRTU-SCC Yes SNVT_lev_percent 81
ED15112-8 71
Send Heartbeat
Keypad Menu Path Main Menu\BMS Communications\LON Set-Up\SndHrtBt=
This read/write configuration property defines maximum period of time that expires before the specified network variable
output is automatically updated.
Measurement Units Data Type Valid Range Default Value
Time Seconds Fixed Point Scalar - unsigned long 0.0–6553.4 sec 60 seconds
BACnet
No BACnet equivalent.
LONWORKS
The ability to send a heartbeat is a requirement for LONWORKS devices. Network variable outputs for Send Heartbeat are
defined in one of two categories based on whether or not they are specified in the Send Heartbeat table.
Network Variable Output Specified for Send Heartbeat in Table? Result: Use Send Heartbeat?
Category 1 Yes Yes
Category 2 No Manufacture Defined
Space CO2
Keypad Menu Path Main Menu\Commission Unit\Min OA Set-Up\IAQ PPM=
This read-only attribute indicates the current space CO2 level from the optional space CO2 sensor. This value reflects the
network input nviSpaceIAQ (if valid) or the value from a locally wired sensor if Min OA Type is set to IAQ VDC or IAQ
mA. This variable only applies if the unit is configured for an airside economizer and Min OA Type is set to IAQ VDC or
IAQ mA.
Measurement Units Data Type Valid Range Default Value
Concentration ppm Real 0-5000 ppm N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 13 Present_Value 85
Full Reference
<Device Name>.SpaceCO2.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoSpaceCO2 SCC, Yes SNVT_ppm 29
McQuayDischargeAir
72 ED15112-8
Space IAQ Input
Keypad Menu Path Main Menu\Service Menus\Network Input Status\Net Space IAQ=
This read/write attribute indicates the current space CO2 level from the network. This value takes priority over a locally
wired sensor. This variable only applies if Min OA Type is set to IAQ VDC or IAQ mA.
Measurement Units Data Type Valid Range Uses Heartbeat Default Value
Concentration ppm Real 0-5000 ppm Yes 32767 (Null)
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 31 Present_Value 85
Full Reference
<Device Name>.SpaceIAQNetIn.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviSpaceIAQ SCC, Yes SNVT_ppm 29
McQuayDischargeAir
Space Temperature
Keypad Menu Path Main Menu\View/Set Unit\Temperatures\Space Temp=
This read-only attribute indicates the current space or zone temperature from the optional space air temperature sensor. This
variable only applies if the unit is configured for a space temperature sensor.
Note: If the optional space temperature sensor is not installed and a BACnet or LONWORKS network is not writing to the
space temperature, the Space Sensor attribute in the Unit Configuration menu of the keypad/display should be set
to No to disable the alarm function associated with an open circuit at the space temperature sensor input.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 3 Present_Value 85
Full Reference
<Device Name>.SpaceTemp.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoSpaceTemp DAC, SCC Yes SNVT_temp_p 105
Measurement Units Data Type Valid Range Uses Heartbeat Default Value
Temperature °F / °C Real 0°–150°F Yes 327.67 (Null)
-17.78°-65.56°C
ED15112-8 73
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 28 Present_Value 85
Full Reference
<Device Name>.SpaceTempInput.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviSpaceTemp DAC, SCC Yes SNVT_temp_p 105
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 16 Present_Value 85
Full Reference
<Device Name>.SmpWtrLvlSw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Input 0 8 Present_Value 85
Full Reference
<Device Name>.FanSpd.Present_Value
74 ED15112-8
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoUnitStatus.fan_output DAC, SCC Yes SNVT_hvac_status 112
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 21 Present_Value 85
Full Reference
<Device Name>.SupFanCapNetIn.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviSupFanCap DAC Yes SNVT_lev_percent 81
Note: On space comfort control units the Space Setpoint Type must not be set to Tstat, otherwise the space setpoint
adjustment on the optional space sensor overrides the Temperature Setpoint Input (nviSetpoint).
Measurement Units Data Type Valid Range Uses Heartbeat Default Value
Temperature °F / °C Fixed Point Scalar - signed long -17.78°–37.7°C No N/A
BACnet
No BACnet equivalent.
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviSetpoint SCC, No SNVT_temp_p 105
McQuayDischargeAir
Time
Keypad Menu Path Main Menu\View/Set Unit\Date/Time/Schedules\Time=
This read/write property sets the current time of the form hours, minutes, seconds, and hundredths of a second. See
ANSI/ASHRAE 135-2004 for a definition of the data type.
Measurement Units Data Type Valid Range Default Value
Time hours, minutes, seconds, BACnet time data types N/A N/A
and hundredths of a second
ED15112-8 75
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Device 8 Variable Local Time 57
Full Reference
<Device Name>.Local Time
Unit State
Keypad Menu Path Main Menu\Unit State=
Main Menu\Quick Menu\Unit State=
Main Menu\View/Set Unit\Unit Status/Settings\Unit State=
This read-only property indicates the current unit operating state. This is a LONWORKS only variable that covers six other
data points: Supply Fan Capacity (See page 74), Cooling Capacity (See page 32), Heating Capacity (See page 43), Reheat
Capacity (See page 67), Economizer Capacity (See page 36), and In Alarm (See page 88).
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Multistate Value 19 15 Present_Value 85
Full Reference
<Device Name>.UnitState.Present_Value
Enumeration
1 = Off
2= Start
3= Recirc
4= FanOnly
5= MinDAT
6= Htg
7= Econo
8= Clg
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Number
nvoUnitStatus.Mode DAC, SCC Yes SNVT_hvac_status 112
76 ED15112-8
14 HVAC_DEHUMID Not Used
15 HVAC_CALIBRATE Not Used
16 HVAC_EMERG_COOL Not Used
17 HVAC_EMERG_STEAM Not Used
0xFF OC_NUL Value not available
Unit Support
Keypad Menu Path Main Menu\BMS Communications\BACnet IP Set-Up\Unit Support=
Main Menu\BMS Communications\BACnet MSTP Set-Up\Unit Support=
This is a BACnet-only variable that sets the units that are sent from the main controller to the BACnet network. If the value
is Off, the units is always Metric. If the value is On, the units depend on how the keypad/display is setup. If the keypad is
displaying Metric, BACnet will display Metric. If the keypad is setup to display English Units, BACnet will display
English units. The power must be cycled on the unit controller for this change to take effect.
Measurement Units Data Type Valid Range Default Value
Unit Support N/A BACnet: Unsigned Off (Always Metric) On (2)
LONWORKS: Structure On
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Multistate Value 19 16 Present_Value 85
Full Reference
<Device Name>.UnitSupport.Present_Value
Enumeration
1 = Off
2 = On
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 10 Present_Value 85
Full Reference
<Device Name>.UnoccCoolSetpt.Present_Value
LONWORKS
LONWORKS Name Profile SCPT Reference SCPT Index SNVT Type SNVT Index
nciSetpoints.unoccupied_cool DAC, SCC SCPTsetPnts 60 SNVT_temp_setpt 106
ED15112-8 77
Field Definitions
Field Notes
Occupied_cool Occupied Cooling Setpoint
Standby_cool Standby Cooling Setpoint (Not Used)
Unoccupied_cool Unoccupied Cooling Setpoint
Occupied_heat Occupied Heating Setpoint
Standby_heat Standby Heating Setpoint (Not Used)
Unoccupied_heat Unoccupied Heating Setpoint
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 12 Present_Value 85
Full Reference
<Device Name>.UnoccHeatSetpt.Present_Value
LONWORKS
LONWORKS Name Profile SCPT Reference SCPT Index SNVT Type SNVT Index
nciSetpoints.unoccupied_heat DAC, SCC SCPTsetPnts 60 SNVT_ temp_setpt 106
Field Definitions
Field Notes
Occupied_cool Occupied Cooling Setpoint
Standby_cool Standby Cooling Setpoint (Not Used)
Unoccupied_cool Unoccupied Cooling Setpoint
Occupied_heat Occupied Heating Setpoint
Standby_heat Standby Heating Setpoint (Not Used)
Unoccupied_heat Unoccupied Heating Setpoint
78 ED15112-8
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Multistate Value 19 14 Present_Value 85
Full Reference
<Device Name>.VAVBoxOutput.Present_Value
Enumeration
1 = Heat (Off)
2 = Cool (On)
LONWORKS
LonWorks Name Profile Uses Heartbeat UNVT Type SNVT Number
nvoVAVBoxOut McQuayDischargeAir No UNVTvavBoxOutput N/A
Enumeration
0 = Heat (Off)
1 = Cool (On)
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 17 Present_Value 85
Full Reference
<Device Name>.WtrFlwSw.Present_Value
Enumeration
0 – Open
1 – Closed
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 3 18 Present_Value 85
Full Reference
<Device Name>.WtrRegVlv.Present_Value
Enumeration
0 – normal
1 – alarm
ED15112-8 79
LONWORKS
No LONWORKS equivalent.
Measurement Units Data Type Valid Range Uses Heartbeat Default Value
Flow Status N/A BACnet: Real Enumerated Yes N/A
LONWORKS: Structure
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 38 Present_Value 85
Full Reference
<Device Name>.WaterflowSwitch.Present_Value
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nviCWFlow DAC, Yes SNVT_switch 95
McQuayRTU-SCC
Valid Range
State Value Waterflow Switch
0 N/A Disabled
1 0 Disabled
1 1-100% Enabled
-1 (0xFF) N/A Auto (invalid)
80 ED15112-8
Alarms
Two methods of obtaining alarm information are available in the MicroTech III Unit Controller: 1) by monitoring individual
alarms and 2) by monitoring alarms according to alarm class.
Alarms are divided into three classes: Faults, Problems, and Warnings. Fault alarms have the highest priority. Problem
alarms have the next priority. Warning alarms have the lowest priority. The alarms within each class are also prioritized.
Refer to the MicroTech III Unit Controller Operation Manual (OM 920) for a description of each alarm.
The MicroTech III Unit Controller has various ways of managing alarms, depending on the protocol. Using one of these
mechanisms, alarms can be recognized and acknowledged by alarm class or individually, and cleared from the network by
alarm class. Refer to Tables 4, 5, and 6 for details.
The following tables describe the alarm messages, indication, and method of clearing Fault, Problem, and Warning alarms.
Alarms are listed in order of priority.
ED15112-8 81
Problem Alarms (Medium Priority)
Table 5. Problem Alarms in Order of Priority
Alarm Message Indication Clear
Freeze Freezestat tripped while SAF was off and a waterside economizer, chilled water coil, hot water Automatic
coil, or steam coil is installed on the unit.
MAT Sensor The Mixed Air Temperature sensor is not Reliable (Either In alarm or Not Present) for longer Automatic
than the Temperature Alarm Delay (Default = 30 seconds)
EWT Sensor The Entering Water Temperature Sensor is not Reliable (Either In alarm or Not Present) for Automatic
longer than the Temperature Alarm Delay (Default = 30 seconds)
OAT Sensor The Outdoor Air Temperature Sensor is not Reliable (A valid Outside Air Temperature value Automatic
is not provided via the network and the Outside Air Temperature sensor is either In alarm OR
Not Present) for longer than the Temperature Alarm Delay (Default = 30 seconds)
Space Sensor The Space Sensor is not Reliable (A valid Space Temperature value is not provided via the Automatic
network and the Space Temperature sensor is either In alarm OR Not Present) for longer than
the Temperature Alarm Delay (Default = 30 seconds)
Return Sensor The Return Air Sensor is not Reliable (Either In alarm or Not Present) for longer than the Automatic
Temperature Alarm Delay (Default = 30 seconds)
Ent_LCT Sensor The Entering Fan Temperature/Leaving Coil Temperature is not reliable (either in alarm or not Automatic
present) for longer than the temperature alarm delay (defaul=30seconds)
Sump Pump Fail Cooling has been limited to stage zero due to sump pump fail conditions three times between Manual
2:00AM of one day and 2:00AM of the next day.
Hi Pres-Ckt1 High Pressure switch SW1 input is in the alarm (Open) position. Manual
Hi Pres-Ckt2 High Pressure switch SW2 input is in the alarm (Open) position. Manual
Hi Pres-Ckt3 High Pressure switch SW3 input is in the alarm (Open) position. Manual
Hi Pres-Ckt4 High Pressure switch SW4 input is in the alarm (Open) position. Manual
Hi Pres-Ckt5 High Pressure switch SW5 input is in the alarm (Open) position. Manual
Hi Pres-Ckt6 High Pressure switch SW6 input is in the alarm (Open) position. Manual
Lo Pres-Ckt1 The Low Press SW1 input has been in the alarm (Open) position for longer than the Pressure Automatic
Alarm Delay (Default = 10 seconds) AND
A compressor on Circuit #1 has been on for longer than the Low Pressure Alarm Delay
(Default = 65 seconds)
Lo Pres-Ckt2 The Low Press SW2 input has been in the alarm (Open) position for longer than the Pressure Automatic
Alarm Delay (Default = 10 seconds) AND
A compressor on Circuit #2 has been on for longer than the Low Pressure Alarm Delay
(Default = 65 seconds)
Lo Pres-Ckt3 The Low Press SW3 input has been in the alarm (Open) position for longer than the Pressure Automatic
Alarm Delay (Default = 10 seconds) AND
A compressor on Circuit #3 has been on for longer than the Low Pressure Alarm Delay
(Default = 65 seconds)
Lo Pres-Ckt4 The Low Press SW4 input has been in the alarm (Open) position for longer than the Pressure Automatic
Alarm Delay (Default = 10 seconds) AND
A compressor on Circuit #4 has been on for longer than the Low Pressure Alarm Delay
(Default = 65 seconds)
Lo Pres-Ckt5 The Low Press SW5 input has been in the alarm (Open) position for longer than the Pressure Automatic
Alarm Delay (Default = 10 seconds) AND
A compressor on Circuit #5 has been on for longer than the Low Pressure Alarm Delay
(Default = 65 seconds)
Lo Pres-Ckt6 The Low Press SW6 input has been in the alarm (Open) position for longer than the Pressure Automatic
Alarm Delay (Default = 10 seconds) AND
A compressor on Circuit #6 has been on for longer than the Low Pressure Alarm Delay
(Default = 65 seconds)
Water RegValve Water Regulating Valve is installed AND Manual
A compressor on either circuit # 1 or circuit # 2 is turned on. AND
EWT is less than 58F AND
The greater of the two refrigerant condensing pressure readings is below the Head Pressure
Setpoint by more than the deadband
Waterflow Switch Lack of water flow is indicated by an open water flow switch or a Network signal AND Automatic
Either of the following is true:
The Bypass Valve has been open for more than the Bypass Valve Timer.
A water side economizer is installed and its position is greater than 50%
Heat Fail Problem McQuay gas heat flame safeguard (FSG) device is off on safety lockout. Automatic
82 ED15112-8
Warning Alarms (Lowest Priority)
Table 6. Warning Alarms in Order of Priority
Alarm Message Indication Clear
Conductivity Conductivity valve is above alarm setpoint value. Manual
Airflow Switch Airflow switch is in the Flow (Closed) position AND the supply fan is Off for more than Manual
30 minutes.
Dirty Filter The filter switch input is in the alarm (Open) position Manual
Alarm Monitoring
The MicroTech III Unit Controller provides individual alarm identification through a unique value for each alarm. The
value assigned to each alarm is the same for both BACnet and LONWORKS applications.
BACnet
MicroTech III Unit Controllers may have alarms monitored by one of four methods: 1) individually by BACnet Binary
Value Objects, 2) alarm value using one BACnet Analog Values, 3) alarm class or 4) Notification Classes.
1. To monitor alarms individually, read the Present_Value of the desired Binary Value. Each alarm has its own Binary
Value object. If the Present_Value is Inactive (0), the alarm is not active. If the Present_Value is Active (1), the alarm
is active.
2. To monitor alarms by alarm value, read the Present_Value property of the Alarm Value Analog Value object. The
Present_Value displays a value that corresponds to the highest priority alarm that is active. It is possible to have
multiple active alarms, but only the highest priority is displayed. For example, if there is a simultaneous Dirty Filter
Warning (value of 24) and a Freeze Fault (value of 252), then the Freeze Fault value of 252 will display in the
Present_Value because it is the higher priority alarm of the two. Once the Freeze Fault condition is corrected and the
fault is cleared, the next priority active alarm value (in this example, value of 24 for Dirty Filter alarm) is displayed.
The values for all alarms are described in the Alarms section tables. If the Present_Value displays a zero, there are no
active alarms.
3. To monitor alarms by alarm class, read the Present_Value of the appropriate Analog Value object (Warnings, Problems
and faults). The Present_Value displays a value that corresponds to the highest priority alarm that is active. It is
possible to have multiple active alarms, but only the highest priority is displayed.
4. To monitor alarms using the Notification Class objects, see the Alarm Notification section.
LONWORKS
MicroTech III Unit Controllers may have their alarms monitored by one of two methods: 1) using the In_alarm attribute of
nvoUnitStatus, or 2) alarm class.
1. Alarms can be monitored individually by using the In Alarm attribute of the Unit Status Network Variable Output (i.e.
nvoUnitStatus_in_alarm). This attribute displays a value that corresponds to the highest priority alarm that is active. It
is possible to have multiple active alarms, but only the highest priority is displayed in this attribute. For example, if
there is a simultaneous Dirty Filter Warning (value of 24) and a Freeze Fault (value of 252), then the Freeze Fault value
of 252 will display in nvoUnitStatus_in_alarm because it is the higher priority alarm of the two. Once the Freeze Fault
condition is corrected and the fault is cleared, the next priority active alarm value (in this example, value of 24 for Dirty
Filter alarm) is displayed. The values for all alarms are described in the Alarms section tables. If the attribute
nvoUnitStatus_in_alarm displays a zero, there are no active alarms.
Alarms may also be monitored by alarm class if desired. When the nvoUnitStatus_in_alarm attribute reads a value in
the range of 1 to 99, a Warning Alarm is active. When the attribute reads a value in the range of 100 to 199, a Problem
Alarm is active. When the attribute reads a value in the range of 200 to 255, a Fault Alarm is active.
2. To monitor alarms by alarm class, read nvoWarnAlarm, nvoProbAlarm and nvoFaultAlarm. The value corresponds to
the highest priority alarm that is active. It is possible to have multiple active alarms, but only the highest priority is
displayed.
ED15112-8 83
Alarm Notification
The MicroTech III Unit Controller has three Notification Class objects for alarms and uses intrinsic reporting which allows
the controller to generate event notifications directed to one or more recipients (maximum 20 recipients). There is one
notification class object for each class of alarms (faults, problems and warnings). You must subscribe to the notification
class objects in order to use them. The Recipient List property must indicate when and to which device notification should
be made. This is a standard BACnet data type as defined in ANSI/ASHRAE 135-2004, BACnet A Data Communication
Protocol for Building Automation and Control Networks.
The Event_Enable property of each object can be used to separeatly enable and disable reporting of To-OffNormal, To-
Fault, and To-Normal events. For example, if you do not want an event to be generated when the object returns to a normal
state after being in alarm, set the To-Normal bit of the objects Event_Enable property to 0. The tables below show the
objects that support intrisic reporting grouped with the notification classes they report to:
84 ED15112-8
Recipient List Property
The recipient list property (Recipient_List), of the Notification Class object, is a list of standard BACnet data type
BACnetDestination elements. This data type consists of the following elements:
Element Standard BACnet Data Type Description
Valid Days BACnetDaysOfWeek The set of days of the week that the destination may be
used between the From Time and the To Time
From Time, To Time Time The window of time (inclusive) when the destination is
visible on the days of the week in Valid Days
Recipient BACnet Recipient The destination devices to receive the notification. A
maximum of 20 destination devices is supported.
Process Identifier Unsigned The handle of a process within the recipient device
that is to receive the event notification
Issue Confirmed Notification Boolean (TRUE) if confirmed notifications are to be sent and
(FALSE) if unconfirmed notifications are to be sent
Transitions BACnetEventTransitionBits A set of three flags that indicate the transition (TO-
OFFNORMAL, TO-FAULT, and TO-NORMAL that
the recipient is suitable.
If the BACnet workstation or BACnet device supports intrinsic alarming, but is unable to subscribe to the recipient list
property of the notification class object, the workstation or device can still receive alarm notification by adding its Device
Instance to the “NC Dev 1=” or “NC Dev 2=” items on the keypad/display. These items are located on the IP Setup or
MSTP Setup menus. Power must by cycled for changes to these items to take effect. Once power is cycled, the unit
controller sends out a “Who-Is” command directed at the device. If the device reponds, the unit controller sends out
Unconfirmed Notifications for all alarms that are generated in the application. If the device does not respond to the Who-Is,
the unit controller will periodically send out the Who-Is until the device responds.
Alarm Clearing
BACnet
Alarms can be cleared via BACnet by setting the ClearAlms variable to value greater than 1. To clear alarms by alarm
class, change the Present_Value property to a 2 to clear all faults, a 3 to clear all problems or a 4 to clear all warnings.
Setting this variable to a 5 will clear all alarms in all three alarm classes. After the alarms are cleared, this variable will
return to None (1).
LONWORKS
Alarms can be cleared by alarm class using nviClearAlarms. To clear alarms in a particular class, set the value of
nviClearAlarms to the appropriate value (1=Clear Faults, 2=Clear Problems, 3=Clear Warnings & 4=Clear All). If the unit
is still in the alarm condition, the In Alarm attribute of the Unit Status Network Variable Output (nvoUnitStatus.in_alarm)
again reads the number corresponding to the highest priority active alarm that still exists.
Objects
Clear Alarms
Keypad Menu Path Main Menu\Alarm Lists\Active Alarms\ClrAlms=
This read/write property clears all active alarms or all active alarms in a particular alarm class.
Measurement Units Data Type Valid Range Uses Heartbeat Default Value
Alarms N/A BACnet: Unsigned Enumerated No N/A
LONWORKS: Structure
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Multistate Value 19 13 Present_Value 85
Full Reference
<Device Name>.ClearAlarms.Present_Value
ED15112-8 85
Enumeration
1= None
2= ClrFlts
3= ClrPrblms
4= ClrWrngs
5= ClrAllAlms
LONWORKS
LonWorks Name Profile Uses Heartbeat UNVT Type SNVT Number
nviClearAlarms McQuayDischargeAir, No UNVTclearAlarm N/A
McQuayRTU-SCC
Enumeration
0= None
1= Clear All Faults
2= Clear All Problems
3= Clear All Warnings
4= Clear All Alarms
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Notification Class 15 1 recipient_list 102
Full Reference
<Device Name>.NC1-Faults.recipient_list1, 2
1
If the BACnet Workstation is unable to subscribe to the recipient_list, you can still subscribe to alarms on the unit controller keypad/display. Navigate to the IP Setup or MSTP
Setup menu and enter the Device Instance of the device to receive the alarms in the “NC Dev 1=” or “NC Dev 2=” entries. You must cycle power after changing these
properties from the keypad/display.
2
Maximum of 20 recipients at one time.
LONWORKS
No LonWorks equivalent.
86 ED15112-8
Notification Class - Problem
Keypad Menu Path No Keypad Equivalent
These read/write properties allows subsciption to alarm notifications. The Recipient_List conveys a list of one or more
recipients to which notifications will be sent. The Ack_Required property tells wether acknoledgment is requird in
notifications generated for To-OffNormal, To-Fault, and To-Normal event transistions. The Priority conveys the priority to
be used for event notifications to To-OffNormal, To-Fault and To-Normal events. See the Alarm Notification section (see
page 84) for more information including a list of objects that report events to this notification class.
Measurement Units Data Type Valid Range Default Value
Notification N/A List of BACnetDestination N/A N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Notification Class 15 2 recipient_list 102
Full Reference
<Device Name>.NC1-Problems.recipient_list1, 2
1
If the BACnet Workstation is unable to subscribe to the recipient_list, you can still subscribe to alarms on the unit controller keypad/display. Navigate to
the IP Setup or MSTP Setup menu and enter the Device Instance of the device to receive the alarms in the “NC Dev 1=” or “NC Dev 2=” entries. You
must cycle power after changing these properties from the keypad/display.
2
Maximum of 20 recipients at one time.
LONWORKS
No LonWorks equivalent.
ED15112-8 87
Notification Class - Warnings
Keypad Menu Path No Keypad Equivalent
These read/write properties allows subsciption to alarm notifications. The Recipient_List conveys a list of one or more
recipients to which notifications will be sent. The Ack_Required property tells wether acknoledgment is requird in
notifications generated for To-OffNormal, To-Fault, and To-Normal event transistions. The Priority conveys the priority to
be used for event notifications to To-OffNormal, To-Fault and To-Normal events. See the Alarm Notification section (see
page 84) for more information including a list of objects that report events to this notification class.
Measurement Units Data Type Valid Range Default Value
Notification N/A List of BACnetDestination N/A N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Notification Class 15 3 recipient_list 102
Full Reference
<Device Name>.NC1-Warnings.recipient_list1, 2
1
If the BACnet Workstation is unable to subscribe to the recipient_list, you can still subscribe to alarms on the unit controller keypad/display. Navigate to
the IP Setup or MSTP Setup menu and enter the Device Instance of the device to receive the alarms in the “NC Dev 1=” or “NC Dev 2=” entries. You
must cycle power after changing these properties from the keypad display.
2
Maximum of 20 recipients at one time.
LONWORKS
No LonWorks equivalent.
Alarm Value
Keypad Menu Path No Keypad Equivalent
This object allows individual notification of the highest priority active alarm. The value in the table below is the largest
number in its enumeration that corresponds to an active alarm. This object is set to zero if no alarms are active.
88 ED15112-8
Property Value
0 – No Active Alarms
24 - Dirty Filter
28 – Airflow Sw
32 – Conductivity
137 – Waterflow Sw
140 – Water Regulating Valve
154 – Low Pressure – Circuit 6
155 – Low Pressure – Circuit 5
156 – Low Pressure – Circuit 4
157 – Low Pressure – Circuit 3
158 – Low Pressure – Circuit 2
159 – Low Pressure – Circuit 1
162 – High Pressure – Circuit 6
163 – High Pressure – Circuit 5
164 – High Pressure – Circuit 4
165 – High Pressure – Circuit 3
166 – High Pressure – Circuit 2
167 – High Pressure – Circuit 1
169 – Sump Pump Fail
179 – EFT_LCT Problem
182– Return Air Sensor Problem
185 – Space Sensor Problem
188 – OAT Sensor Problem
191 – EWT Problem
194 – MAT Problem
197 – Freeze Problem
199 – Heat Fail Problem
208 – Airflow Fault
212 – Low Discharge Air Temp
216 – High Discharge Air Temp
220 – High Return Air Temp
224 – Duct High Limit
228 – Discharge Sensor Fail
244 – Control Temp Fault
250 – Emergency Stop Fault
252 – Freeze Fault
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoUnitStatus.in_alarm DAC, SCC Yes SNVT_hvac_status 112
ED15112-8 89
Property Value
0 – No Active Warnings
24 - Dirty Filter
28 – Airflow Sw
32 – Conductivity
137 – Waterflow Sw
140 – Water Regulating Valve
154 – Low Pressure – Circuit 6
155 – Low Pressure – Circuit 5
156 – Low Pressure – Circuit 4
157 – Low Pressure – Circuit 3
158 – Low Pressure – Circuit 2
159 – Low Pressure – Circuit 1
162 – High Pressure – Circuit 6
163 – High Pressure – Circuit 5
164 – High Pressure – Circuit 4
165 – High Pressure – Circuit 3
166 – High Pressure – Circuit 2
167 – High Pressure – Circuit 1
169 – Sump Pump Fail
179 – EFT_LCT Problem
182– Return Air Sensor Problem
185 – Space Sensor Problem
188 – OAT Sensor Problem
191 – EWT Problem
194 – MAT Problem
197 – Freeze Problem
199 – Heat Fail Problem
208 – Airflow Fault
212 – Low Discharge Air Temp
216 – High Discharge Air Temp
220 – High Return Air Temp
224 – Duct High Limit
228 – Discharge Sensor Fail
244 – Control Temp Fault
250 – Emergency Stop Fault
252 – Freeze Fault
Warning Alarm
Keypad Menu Path No Keypad Equivalent
This object allows individual notification of the highest priority active warning alarm. The value in the table below is the
largest number in its enumeration that corresponds to an active alarm. This object is set to zero if no warning alarms are
active.
Measurement Units Data Type Valid Range Default Value
Alarms N/A BACnet: Real Enumerated N/A
LONWORKS: Structure
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 24 Present_Value 85
Full Reference
<Device Name>.ActiveWarning.Present_Value
90 ED15112-8
Enumeration
0 – No Active Alarms
24 - Dirty Filter
28 – Airflow Sw
32 – Conductivity
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoWarnAlarm DAC, SCC Yes SNVT_hvac_status 112
Property Value
0 – No Active Warnings
24 - Dirty Filter
28 – Airflow Sw
32 – Conductivity
Problem Alarm
Keypad Menu Path No Keypad Equivalent
This object allows individual notification of the highest priority active problem alarm. The value in the table below is the
largest number in its enumeration that corresponds to an active alarm. This object is set to zero if no problem alarms are
active.
Measurement Units Data Type Valid Range Default Value
Alarms N/A BACnet: Real Enumerated N/A
LONWORKS: Structure
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 25 Present_Value 85
Full Reference
<Device Name>.ActiveProblem.Present_Value
Enumeration
0 – No Active Alarms
137 – Waterflow Sw
140 – Water Regulating Valve
154 – Low Pressure – Circuit 6
155 – Low Pressure – Circuit 5
156 – Low Pressure – Circuit 4
157 – Low Pressure – Circuit 3
158 – Low Pressure – Circuit 2
159 – Low Pressure – Circuit 1
162 – High Pressure – Circuit 6
163 – High Pressure – Circuit 5
164 – High Pressure – Circuit 4
165 – High Pressure – Circuit 3
166 – High Pressure – Circuit 2
167 – High Pressure – Circuit 1
169 – Sump Pump Fail
179 – EFT_LCT Problem
182– Return Air Sensor Problem
185 – Space Sensor Problem
188 – OAT Sensor Problem
191 – EWT Problem
194 – MAT Problem
197 – Freeze Problem
199 – Heat Fail Problem
ED15112-8 91
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoProbAlarm DAC, SCC Yes SNVT_hvac_status 112
Property Value
0 – No Active Warnings
137 – Waterflow Sw
140 – Water Regulating Valve
154 – Low Pressure – Circuit 6
155 – Low Pressure – Circuit 5
156 – Low Pressure – Circuit 4
157 – Low Pressure – Circuit 3
158 – Low Pressure – Circuit 2
159 – Low Pressure – Circuit 1
162 – High Pressure – Circuit 6
163 – High Pressure – Circuit 5
164 – High Pressure – Circuit 4
165 – High Pressure – Circuit 3
166 – High Pressure – Circuit 2
167 – High Pressure – Circuit 1
169 – Sump Pump Fail
179 – EFT_LCT Problem
182– Return Air Sensor Problem
185 – Space Sensor Problem
188 – OAT Sensor Problem
191 – EWT Problem
194 – MAT Problem
197 – Freeze Problem
199 – Heat Fail Problem
Fault Alarm
Keypad Menu Path No Keypad Equivalent
This object allows individual notification of the highest priority active fault alarm. The value in the table below is the
largest number in its enumeration that corresponds to an active alarm. This object is set to zero if no fault alarms are active.
Measurement Units Data Type Valid Range Default Value
Alarms N/A BACnet: Real Enumerated N/A
LONWORKS: Structure
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Analog Value 2 26 Present_Value 85
Full Reference
<Device Name>.ActiveFault.Present_Value
Enumeration
0 – No Active Alarms
208 – Airflow Fault
212 – Low Discharge Air Temp
216 – High Discharge Air Temp
220 – High Return Air Temp
224 – Duct High Limit
228 – Discharge Sensor Fail
244 – Control Temp Fault
250 – Emergency Stop Fault
252 – Freeze Fault
92 ED15112-8
LONWORKS
LONWORKS Name Profile Uses Heartbeat SNVT Type SNVT Index
nvoFaultAlarm DAC, SCC Yes SNVT_hvac_status 112
Property Value
0 – No Active Warnings
208 – Airflow Fault
212 – Low Discharge Air Temp
216 – High Discharge Air Temp
220 – High Return Air Temp
224 – Duct High Limit
228 – Discharge Sensor Fail
244 – Control Temp Fault
250 – Emergency Stop Fault
252 – Freeze Fault
Airflow Fault
Keypad Menu Path No Keypad Equivalent
This read-only BACnet object indicates whether the Airflow Fault alarm is active (1) or not (0).
Measurement Units Data Type Valid Range Default Value
Alarm N/A Enumerated 0-1 N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 27 Present_Value 85
Full Reference
<Device Name>.AirflowFlt.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 2 Present_Value 85
Full Reference
<Device Name>.AFSwWrn.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
ED15112-8 93
Conductivity Warning
Keypad Menu Path No Keypad Equivalent
This read-only BACnet object indicates whether the Conductivity Warning alarm is active (1) or not active (0). This
variable applies only to unit configured for evaporative condensing.
Measurement Units Data Type Valid Range Default Value
Alarm N/A Enumerated 0-1 N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 3 Present_Value 85
Full Reference
<Device Name>.ConductivityWrn.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 28 Present_Value 85
Full Reference
<Device Name>.ControlTempFlt.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 4 Present_Value 85
Full Reference
<Device Name>.DrtyFltrWrn.Present_Value
Enumeration
0 – normal
1 – Alarm
94 ED15112-8
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 29 Present_Value 85
Full Reference
<Device Name>.DischSensorFlt.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 30 Present_Value 85
Full Reference
<Device Name>.DuctHiLmtFlt.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
ED15112-8 95
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 31 Present_Value 85
Full Reference
<Device Name>.EmergencyOffFlt.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 5 Present_Value 85
Full Reference
<Device Name>.EFT_LCTPrb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 6 Present_Value 85
Full Reference
<Device Name>.EntWtrTmpPrb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
96 ED15112-8
Freeze Fault
Keypad Menu Path No Keypad Equivalent
This read-only BACnet object indicates whether the Freeze Fault alarm is active (1) or not active (0).
Measurement Units Data Type Valid Range Default Value
Alarm N/A Enumerated 0-1 N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 32 Present_Value 85
Full Reference
<Device Name>.FreezeFault.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
Freeze Problem
Keypad Menu Path No Keypad Equivalent
This read-only BACnet object indicates whether the Freeze Problem alarm is active (1) or not active (0). This variable
applies only to units configured for at least one of the following: waterside economizer, face and bypass heating, steam/hot
water heating, chilled water cooling or face and bypass cooling.
Measurement Units Data Type Valid Range Default Value
Alarm N/A Enumerated 0-1 N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 7 Present_Value 85
Full Reference
<Device Name>.FreezePrb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Input 5 38 Present_Value 85
Full Reference
<Device Name>.HeatFailProb.Present_Value
Enumeration
0 – Normal
1 – Alarm
ED15112-8 97
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 33 Present_Value 85
Full Reference
<Device Name>.HiDischTmpFlt.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 8 Present_Value 85
Full Reference
<Device Name>.HiPressCkt1Prb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
98 ED15112-8
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 9 Present_Value 85
Full Reference
<Device Name>.HiPressCkt2Prb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 10 Present_Value 85
Full Reference
<Device Name>.HiPressCkt3Prb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 11 Present_Value 85
Full Reference
<Device Name>.HiPressCkt4Prb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
ED15112-8 99
High Pressure Circuit 5 Problem
Keypad Menu Path No Keypad Equivalent
This read-only BACnet object indicates whether the High Pressure Circuit 5 Problem alarm is active (1) or not active (0).
This variable applies only to units configured for five mechanical cooling circuits.
Measurement Units Data Type Valid Range Default Value
Alarm N/A Enumerated 0-1 N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 12 Present_Value 85
Full Reference
<Device Name>.HiPressCkt5Prb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 13 Present_Value 85
Full Reference
<Device Name>.HiPressCkt6Prb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
100 ED15112-8
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 52 Present_Value 85
Full Reference
<Device Name>.HiPressCkt7Prb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 53 Present_Value 85
Full Reference
<Device Name>.HiPressCkt8Prb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 34 Present_Value 85
Full Reference
<Device Name>.HiReturnTmpFlt.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
ED15112-8 101
Low Discharge Temp Fault
Keypad Menu Path No Keypad Equivalent
This read-only BACnet object indicates whether the Low Discharge Temperature Fault alarm is active (1) or not active (0).
Measurement Units Data Type Valid Range Default Value
Alarm N/A Enumerated 0-1 N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 35 Present_Value 85
Full Reference
<Device Name>.LoDischTmpFlt.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 14 Present_Value 85
Full Reference
<Device Name>.LoPressCkt1Prb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
102 ED15112-8
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 15 Present_Value 85
Full Reference
<Device Name>.LoPressCkt2Prb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 16 Present_Value 85
Full Reference
<Device Name>.LoPressCkt3Prb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 17 Present_Value 85
Full Reference
<Device Name>.LoPressCkt4Prb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
ED15112-8 103
Low Pressure Circuit 5 Problem
Keypad Menu Path No Keypad Equivalent
This read-only BACnet object indicates whether the Low Pressure Circuit 5 Problem alarm is active (1) or not active (0).
This variable applies only to units configured for five or more mechanical cooling circuits.
Measurement Units Data Type Valid Range Default Value
Alarm N/A Enumerated 0-1 N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 18 Present_Value 85
Full Reference
<Device Name>.LoPressCkt5Prb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 19 Present_Value 85
Full Reference
<Device Name>.LoPressCkt6Prb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
104 ED15112-8
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 50 Present_Value 85
Full Reference
<Device Name>.LoPressCkt7Prb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 51 Present_Value 85
Full Reference
<Device Name>.LoPressCkt8Prb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 20 Present_Value 85
Full Reference
<Device Name>.MixAirTmpPrb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
ED15112-8 105
Outdoor Temp Problem
Keypad Menu Path No Keypad Equivalent
This read-only BACnet object indicates whether the Outdoor Temperature Problem alarm is active (1) or not active (0).
This variable applies only to units configured for an outdoor temperature sensor.
Measurement Units Data Type Valid Range Default Value
Alarm N/A Enumerated 0-1 N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 21 Present_Value 85
Full Reference
<Device Name>.OutdoorTmpPrb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 22 Present_Value 85
Full Reference
<Device Name>.ReturnTmpPrb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
106 ED15112-8
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 23 Present_Value 85
Full Reference
<Device Name>.SpaceTmpPrb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 24 Present_Value 85
Full Reference
<Device Name>.SmpWtrLvlPrb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 25 Present_Value 85
Full Reference
<Device Name>.WtrFlowSwPrb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
ED15112-8 107
Water Regulating Valve Problem
Keypad Menu Path No Keypad Equivalent
This read-only BACnet object indicates whether the Water Regulating Valve Problem alarm is active (1) or not active (0).
This variable applies only to units configured for head pressure control.
Measurement Units Data Type Valid Range Default Value
Alarm N/A Enumerated 0-1 N/A
BACnet
Object Identifier Property
Object Type Type ID Instance Name ID
Binary Value 5 26 Present_Value 85
Full Reference
<Device Name>.WtrRegVlvPrb.Present_Value
Enumeration
0 – normal
1 – Alarm
LONWORKS
No LONWORKS equivalent.
108 ED15112-8
BACnet Device Management
The following functions are specific to the BACnet device. These functions are used for maintenance and testing. A network
management tool such as VTS is typically used to issue the network commands.
DeviceCommunicationControl - Disable
The purpose of this command is to reduce network traffic for diagnostic testing of the BACnet network. When the BACnet
Communication module receives a network command to Disable communications it stops communicating information to the
network. An optional time may be specified for how long to suspend communications. The unit continues to operate during
the Disabled state.
DeviceCommunicationControl - Enable
When the BACnet Communication module receives a network command to Enable communications, MicroTech III AHU
communications to BACnet is restored.
ReinitializeDevice (Reset)
When the BACnet Communication module is capable of receiving a network ReinitializeDevice command to reboot itself
(cold start or warm start). The funcationality of a cold and warm start are the same and simple reboot the BACnet
Communication module. No password is required.
ED15112-8 109
Appendix A: Protocol Implementation Conformance
Statement (PICS)
This section contains the Protocol Implementation Conformance Statement (PICS) for the MicroTech III Unit Controller
from McQuay International as required by ANSI/ASHRAE (American National Standards Institute/American Society of
Heating, Refrigeration, and Air Conditioning Engineers) Standard 135-2004, BACnet; A Data Communication Protocol for
Building Automation and Control Networks.
Product Description
The MicroTech III Unit Controller with optional BACnet Communication Module is a microprocessor-based controller
designed to operate McQuay International Air Handling (Applied Rooftop, Self-Contained, or Maverick II Commercial
Rooftop) Units and be integrated into BACnet building automation systems.
The controller provides normal temperature, static pressure and ventilation control and alarm monitoring with alarm-
specific component shutdown in critical system conditions. Access to temperatures, pressures, operating states, alarm
messages, control parameters and schedules is available through an equipment-mounted keypad/display and the BACnet
control network.
110 ED15112-8
BACnet Interoperability Building Blocks (BIBBs) Supported
BIBB Name Designation
Data Sharing – ReadProperty – B DS-RP-B
Data Sharing – ReadPropertyMultiple – B DS-RPM-B
Data Sharing – WriteProperty – B DS-WP-B
Data Sharing – WritePropertyMultiple – B DS-WPM-B
Data Sharing – COV – B DS-COV-B
Data Sharing – ReadProperty – A DS-RP-A
Data Sharing – WriteProperty – A DS-WP-A
Data Sharing – COV – A DS-COV-A
Alarm & Event – Notification Internal - B AE-N-I-B
Alarm & Event – ACK –B AE-ACK-B
Alarm & Event – Information - B AE-INFO-B
Alarm & Event – Alarm Summary - B AE-ASUM-B
Scheduling – Internal - B SCHED-I-B
Device Management – Dynamic Device Binding – A DM-DDB-A
Device Management – Dynamic Device Binding – B DM-DDB-B
Device Management – Dynamic Object Binding – B DM-DOB-B
Device Management – Device Communication Control – B DM-DCC-B
Device Management – TimeSynchronization – B DM-TS-B
Device Management – UTCTimeSynchronization – B DM-UTS-B
Device Management – Reinitialize Device – B DM-RD-B
Device Management – List Manipulation – B DM-LM-B
ED15112-8 111
Standard Object Types Supported
Deleteable
Object-Type Optional Properties Supported Writeable Properties Not Required To Be Writeable
Creatable
112 ED15112-8
Deleteable
Object-Type Optional Properties Supported Writeable Properties Not Required To Be Writeable
Creatable
Binary Input Description Present_Value
Reliability Event_Enable
Inactive_Text
Active_Text
Notification_Class
Acked_Transitions
Event_Enable
Alarm_Value
Notify_Type
Time_Delay
Event_Time_Stamps
Binary Output Description Present_Value
Reliability Event_Enable
Inactive_Text
Active_Text
Notification_Class
Feedback_Value
Acked_Transitions
Event_Enable
Notify_Type
Time_Delay
Event_Time_Stamps
Binary Value Description Acked_Transitions
Reliability Event_Enable
Inactive_Text Present_Value1
Active_Text
Priority_Array
Relinquish_Default
Notification_Class
Acked_Transitions
Event_Enable
Alarm_Value
Notify_Type
Time_Delay
Event_Time_Stamps
Device Description Description
Location Location
Active_Cov_Subsription (<=50) Max_ADPU_Length_Accepted(1476>= x >=50)
Local_Time UTC_Offset
Local_Date Max_Segments_Accepted
UTC_Offset ADPU_Segment_Timeout (>100)
ADPU_Segment_Timeout APDU_Timeout (>100)
Daylight_Savings_Status Number_Of_APDU_Retries
Max_Segments_Accepted Segmentation_Supported
Max_Master (MS/TP only) Max_Master (MS/TP only)
Max_Info_Frames (MS/TP only) Max_Info_Frames (MS/TP only)
ED15112-8 113
Deleteable
Object-Type Optional Properties Supported Writeable Properties Not Required To Be Writeable
Creatable
Multi-State Input Description
State_Text
Notification_Class
Acked_Transitions
Event_Enable
Notify_Type
Time_Delay
Alarm_Values
Fault_Values
Reliability
Event_Time_Stamps
Multi-State Description Event_Enable
Output Reliability
State_Text
Notification_Class
Acked_Transitions
Event_Enable
Notify_Type
Time_Delay
Event_Time_Stamps
Feedback_Value
Multi-State Value Description Present_Value1
Priority_Array Event_Enable
Relinquish_Default
Notification_Class
Reliability
Acked_Transitions
Event_Enable
Alarm_Values
Fault_Values
Notify_Type
Time_Delay
Event_Time_Stamps
State_Text
Notification Class Description Object_Name
Description
Recipient_List (Max 20)
Priority
Ack_Required
Calendar Description Date_List (Max 10)
Schedule Weekly_Schedule Object_Name
Exception_Schedule Effective_Period
Weekly_Schedule
Exception_Schedule
List_Of_Object_Property_Refs
1
Some objects of this type are read only. For those objects, the Present_Value is not commandable or writable.
2
Changes to this property do not take effect until the power is cycled on the unit controller. After changing COV_Increment, you must
wait at least one minute before cycling power. Otherwise, this change will not be saved.
114 ED15112-8
Data Link Layer Options
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800
MS/TP slave (Clause 9), baud rate(s): 9600, 19200, 38400, 76800
Segmentation Capability
Segmented requests supported Window Size: 4 for IP and 1 for MS/TP
Segmented responses supported Window Size: 4 for IP and 1 for MS/TP
Networking Options
Router, Clause 6 – List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP,
etc.
Annex H, BACnet Tunneling Router over IP
BACnet/IP Broadcast Management Device (BBMD)
Number of BDT entries:
Does the BBMD Support registration by Foreign Devices? Yes No
ED15112-8 115
Index
Airflow Fault, 22, 84, 93 Freeze Switch (Fault), 23, 43, 44, 97
Airflow Switch, 23, 29 Freeze Switch (Problem), 23, 43
Airflow Switch (Warning), 23, 29 Full Reference, 7
Airflow Switch Warning, 22, 84, 93 Heating Capacity, 19, 24, 44
Alarm Notification, 84, 86, 87, 88 Heating Status, 19, 24, 45
Alarm Value, 88 High Discharge Temp Fault, 22, 84, 98
Alarm Value, 22 High Pressure Circuit 1 Problem, 22, 84, 98
Application Mode, 15, 16, 19, 24, 28 High Pressure Circuit 1 Switch, 23, 45
Application Version, 21, 30 High Pressure Circuit 2 Problem, 22, 84, 98
ASHRAE, 5, 7, 33, 75, 110 High Pressure Circuit 2 Switch, 23, 46
BACnet Standard Objects, 16, 19 High Pressure Circuit 3 Problem, 22, 84, 99
BACnet/IP, 5, 9 High Pressure Circuit 3 Switch, 23, 46
BIBBs, 110, 111 High Pressure Circuit 4 Problem, 22, 84, 99
Building Static Pressure, 19, 24, 30 High Pressure Circuit 4 Switch, 23, 46
Building Static Pressure Setpoint, 19, 24, 30 High Pressure Circuit 5 Problem, 22, 84, 100
Clear Alarms, 21, 26, 85 High Pressure Circuit 5 Switch, 23, 47
Clearing, 85 High Pressure Circuit 6 Problem, 22, 84, 100, 101
Conductivity, 20, 25, 31 High Pressure Circuit 6 Switch, 23, 47, 48
Conductivity Warning, 22, 84, 94 High Return Temp Fault, 22, 84, 101
Control Temp Fault, 22, 84, 94 High Return Temp Problem, 84
Control Temp Source, 20, 31 HVAC Unit Type Identifier, 26, 48
Control Temperature, 19, 32 In Alarm, 26, 85
Cooling Capacity, 19, 24, 32 Instance, 7
Cooling Status, 19, 24, 32 interoperable, 5, 11
Date, 9, 33, 113 IP address, 9
Device Object, 8 IP Subnet Mask, 9
Dew Point Setpoint, 20, 25, 33 Local OA Temperature, 21, 26, 49
Dew Point Temperature, 20, 25, 34 Local Space Temperature, 21, 26, 49
Dirty Filter Switch, 23, 34 LonWorks Variables, 11, 16, 24
Dirty Filter Warning, 22, 84, 94 Low Discharge Temp Fault, 22, 84, 102
Discharge Air Controller profile, 5, 14 Low Pressure Circuit 1 Problem, 22, 84, 102
Discharge Air Cooling Setpoint, 25 Low Pressure Circuit 1 Switch, 23, 50
Discharge Air Heating Setpoint, 25 Low Pressure Circuit 2 Problem, 22, 84, 102
Discharge Air Temperature, 19, 24, 34 Low Pressure Circuit 2 Switch, 23, 50
Discharge Sensor Fault, 22, 84, 95 Low Pressure Circuit 3 Problem, 22, 84, 103
doubly-terminated network, 13 Low Pressure Circuit 3 Switch, 23, 50
Duct High Limit Fault, 22, 84, 95 Low Pressure Circuit 4 Problem, 22, 84, 103
Duct High Limit Switch, 23, 35 Low Pressure Circuit 4 Switch, 23, 51
Duct Static Pressure, 16, 19, 24, 35, 69 Low Pressure Circuit 5 Problem, 22, 84, 104, 105
Duct Static Pressure Setpoint, 16, 19, 24, 35 Low Pressure Circuit 5 Switch, 23, 51
Economizer Capacity, 19, 24, 36 Low Pressure Circuit 6 Problem, 22, 84, 104
Economizer Enable, 15, 21, 25, 36 Low Pressure Circuit 6 Switch, 23, 52
Economizer Status, 19, 24, 37 MAC address, 9
Eff Discharge Air Temp Setpoint, 21 Maximum Discharge Air Heating Setpoint, 20, 25, 53
Effective Cooling Discharge Setpoint, 61 McQuay AHU Unit Status, 19, 24, 53
Effective Cooling Enable Setpoint, 38 Minimum Discharge Air Cooling Setpoint, 20, 25, 54
Effective Discharge Air Temperature Setpoint, 38 Minimum Send Time, 26, 55
Effective Discharge Setpoint, 26 Mixed Air Temp Problem, 23, 84, 105
Effective Enable Setpoint, 26 Mixed Air Temperature, 19, 24, 55
Effective Heating Discharge Setpoint, 62 MSTP, 5, 10
Effective Heating Enable Setpoint, 38 Network Discharge Air Cooling Setpoint, 20, 56
Effective Minimum Outdoor Damper Position Setpoint, 62 Network Discharge Air Heating Setpoint, 20, 56
Effective Setpoint Output, 38, 75 Neuron, 13, 14
Emergency Off Fault, 22, 84, 95 Notice, 4
Emergency Off Switch, 23, 39 Notification, 17
Emergency Override, 16, 19, 24, 39 Notification Class - Faults, 21, 86
Entering Fan / Leaving Coil Temp, 19, 24, 41 Notification Class - Problems, 21, 87
Entering Fan Temp / Leaving Coil Temp Problem, 22, 84, 96 Notification Class - Warnings, 21, 88
Entering Water Temp Problem, 22, 84, 96 Object Identifier, 7
Entering Water Temperature, 19, 24, 42 Object Request, 27, 56
Ethernet, 9 Object Status, 27, 57
Example of BACnet Data Point, 7 Object Type, 7
Exhaust Fan Capacity, 42 Occupancy, 15, 19, 24, 58, 59
Exhaust Fan Capacity Input, 15, 20, 25, 43 Occupancy Mode, 16, 19, 24, 59, 60
Exhaust Fan Status, 7, 19, 71 Occupancy Scheduler Input, 21, 25, 60
Fault Alarm, 21, 26, 92 Occupied Cooling Setpoint, 16, 20, 25, 61
Fault Alarms, 81, 82 Occupied Heating Setpoint, 16, 20, 25, 62
free topology, 11, 13 Outdoor Air Damper Min Position Input, 21, 26
Freeze Fault, 22, 84, 97 Outdoor Air Damper Minimum Position Input, 62
Freeze Problem, 22, 23, 84, 97 Outdoor Air Damper Position, 62
116 ED15112-8
Outdoor Air Temperature, 15, 16, 19, 24, 63 Space Temperature, 15, 19, 24, 73
Outdoor Air Temperature Input, 20, 25, 63 Space Temperature Input, 21, 25, 73
Outdoor Airflow, 20, 25, 64 Standard Configuration Parameter Type, 11
Outdoor Temp Problem, 23, 84, 106 Standard Network Variable Types, 11
Primary Cool Enable, 15, 25, 64 Sump Pump Fail Problem, 23, 84, 107
Primary CoolEnable, 21 Sump Pump Switch, 23, 74
Primary Heat Enable, 15, 21, 25, 65 Supply Fan Capacity, 19, 24, 74, 75
Problem Alarm, 21, 26, 91 Supply Fan Capacity Input, 15, 19, 24, 69, 75
Problem Alarms, 82 Temperature Setpoint Input, 26, 38, 75
Protocol Implementation Conformance Statement, 5, 110 Time, 9, 75, 113
Receive Heartbeat, 20, 25, 66 Type Enumeration, 7
Reheat Capacity, 20, 25, 67 UDP, 9
Relative Humidity, 20, 25, 67 Unit State, 16, 19, 24, 76
Relative Humidity Input, 15, 21, 26, 68 Unit Status, 19, 85
Relative Humidity Setpoint, 20, 25, 68 Unit Support, 20, 77
Remote Return/Exhaust Fan Capacity Control Flag, 20, 24, 68, 71 Unoccupied Cooling Setpoint, 16, 20, 25, 77
Remote Supply Fan Capacity Control Flag, 19, 24, 69 Unoccupied Heating Setpoint, 16, 20, 25, 78
Return Air Temperature, 16, 19, 24, 70 VAV Box Output, 19, 24, 78
Return Fan Capacity Input, 15, 20, 25, 71 Warning Alarm, 21, 26, 90
Return Temp Problem, 23, 106 Warning Alarms, 83
Return/Exhaust Fan Capacity, 19, 24, 70 Water Flow Switch, 23, 79
Return/Exhaust Fan Status, 24 Water Flow Switch Input, 15
Send Heartbeat, 25, 72 Water Regulating Valve, 23, 79
service pin, 14 Water Regulating Valve Problem, 23, 84, 108
Space CO2, 20, 25, 72 Waterflow Switch, 21
Space Comfort Controller, 5, 11, 14 Waterflow Switch Input, 26, 80
Space IAQ Input, 15, 21, 26, 73 Waterflow Switch Problem, 23, 84, 107
Space Setpoint Type, 75 XIF, 14
Space Temp Problem, 23, 84, 106
This document contains the most current product information as of this printing. For the most current product
information, please go to www.mcquay.com.
ED15112-8 117