Beruflich Dokumente
Kultur Dokumente
In a Harmonic Environment
Low voltage automatic capacitor or filter banks typically use a delay time of 30 –
40 seconds between steps. This delay time is chosen to ensure that the capacitors have
discharged prior to being re-connected. The long delay time limits the autobank’s ability
to track rapidly changing loads. The slow response time may result in an overload
condition in filter banks. Consider the case where a large harmonic producing load is
turned on. The initial steps of the filter could be overloaded before the autobank has
time to connect the required compensation. Acceptable solutions must account for this
switching delay.
Automatic banks use a power factor controller to switch capacitor, or filter steps
in and out. The compensation level connected is based on the power factor need not
the harmonic filtering need. A control method based on power factor works well with
standard capacitor banks. However, when the application involves harmonic filters the
control method may not be valid. Reactive power and harmonic current are not always
proportional. AC drives have a high power factor and the power factor for DC drives can
range from 20% - 85% depending on the application. The variability in the relationship
between the power factor and harmonic current may result in an unbalance between the
need for power factor correction and the need for harmonic filtering. When the filtering
requirement exceeds the power factor need the filter may be overloaded.
The discussion above noted the variability between a load’s reactive power and
the level of harmonic current. AC drives have a power factor around 95%. The power
factor of a DC drive can vary from 20% to 85%. However, the current distortion for AC
and DC drives are similar. The uncertainty concerning the relationship between power
factor and harmonic current should cause one to pause when considering automatic
switch filters.
Having detailed the primary concerns of automatic switching passive filter we will now
seek an acceptable solution. ABB developed the Automatic Anti-Resonance Bank to
address each of the potential issues raised concerning the design and operation of
automatic filter banks. The typical Anti-Resonance Bank uses a tuning point of the
4.08th. This tuning point, and conservative sizing of components protects the Anti-
Resonance bank against overloads due to switching delays, changes in the network,
and the variability between the load’s reactive power and harmonic current. Simply
stated the Anti-Resonance Bank has sufficient design margin to address all of the
application issues which could overload a filter bank tuned to 4.7th harmonic. ABB’s Anti-
Resonance Bank significantly increases the reliability and the range of applications
where the automatic switching filter bank can be used safely. To achieve the same
safety margin with a bank tuned to the 4.7th harmonic a rms current rating of more than
twice the fundamental current would be required. Typically systems that use 4.7th tuning
are only rated for approximately 1.5 times the fundamental current.
The following case study is taken from a typical industrial application. A 1500 KVA, 5%
impedance transformer feeds a facility with a peak load of 650KW at a power factor of
81%. Approximately 50% of the total load is harmonic producing and the total harmonic
current distortion is 17%. The available short circuit power at the point of common
coupling is 117MVA. The object is to reduce the distortion to IEEE-519 levels and
improve the power factor to above 98%.
Based on the existing load conditions IEEE-519 recommends that the total harmonic
current distortion be no higher than 15%. Currently the total harmonic distortion exceeds
the recommended level and the fifth harmonic current distortion exceeds the 12% level
recommended by IEEE-519. A 350Kvar automatic Anti-Resonance bank was designed
to fulfill the customer requirements. The power factor was improved beyond 98%, and
the distortion was limited as required. The total harmonic current distortion was reduced
to 10.7% and the voltage distortion on the customer’s system was reduced from 5% to
2.9%. The Anti-Resonance Bank met or exceeded each of the customer’s requirements
while providing a reliable solution that addresses the concerns of automatic filter banks.
There are cases where the Anti-Resonance Bank, nor a filter system tuned to the 4.7th,
will be able to reduce the distortion to IEEE recommended levels. In such cases ABB
would propose a comprehensive approach selecting from the broadest range of passive
and active filter technology in the industry. Based on the types of loads employed and
their operational characteristics an appropriate solution would be reached.