Beruflich Dokumente
Kultur Dokumente
DESIGN GUIDE
REVISIONS
NO. DATE DESCRIPTION BY CHK’D. APP’D. CLIENT
A 14Jun07 For Design TAR
APPROVALS
NAME / INITIALS DATE
PREPARED BY: TODD RUMSEY / TAR 14Jun07
CHECKED BY:
APPROVED BY:
CLIENT APPROVAL:
1 INTRODUCTION
A. The following document summarizes compressed air generation equipment. It is
written for the type of compressed air we specify for a pharmaceutical facility.
2 AIR REQUIREMENTS
A. Compressed air is required for instruments, controls, equipment and is used in the
process. Therefore, we need to pay particular attention to the moisture and
contaminants in the compressed air as it leaves the compressed air generation and
filtration system. The following are three requirements for compressed air systems in
pharmaceutical plants:
1. Oil Free – This item classifies compressors and divides them into two groups: oil-
free compressors and lubricated compressors. It is crucial we specify an oil-free
compressor. All compressors use some sort of lubrication to cool the
compressor much like oil in an automobile engine, however, when we refer to an
oil-free compressor we mean the compressor is specially designed so that the
compressed air is never in contact with the oil. Moving parts in the oil free
compression chamber are lubricated with inert anti-friction coatings on their
surfaces rather than with conventional fluid lubricants.
2. Moisture – Moisture is present in the intake air as humidity. During the process
of compressing the air and subsequently cooling some of the water vapor
condenses into water. This water causes corrosion, freeze in outdoor air lines
and foul the downstream equipment. We refer to the amount of water in the
compressed air as the air’s “dew point”. The dew point is the temperature to
which the air would have to be cooled in order for saturation to occur or in other
words, water droplets would form in the airline. For pharmaceutical facilities we
typically specify the compressed air have a dew point of –40 deg F.
3. Particulates – Particulates are brought into the compressed air stream through
the intake air and can also be added by improperly operating dessicant dryers (to
be discussed later). It is common to have 0.1 micron particulate filter(s) or better
just at the discharge of the compressed air system. An intake air filter is used to
minimize particulates brought into the compressor.
3 AIR COMPRESSORS
A. There are essentially three different types of air compressors; reciprocating, rotary
and centrifugal.
1. Reciprocating compressors are positive displacement compressors. The
reciprocating compressor uses a piston within a cylinder (much like a automobile
engine). The following are details of the reciprocating compressor:
a. This type of compressor is usually choosen for the smaller flow rates (100
scfm and less).
b. Because they are smaller is size the compressor is typically mounted on top
of its receiver and sold as a package. They can be purchased either as a
simplex unit (only one compressor mounted on a receiver) or duplex (two
compressors mounted on a single, common receiver).
a. These types of compressors are for higher flowrates, from 75 to 5,000 scfm
and relatively constant air consumption rates or loads.
b. Rotary compressors “rotate” which leads to a much smoother operation with
less vibration concerns as described under reciprocating compressors.
However, when selecting a compressor, discuss any vibration issues with
the bidder for their recommendations.
c. They can be air cooled or water cooled. If it is water cooled, the water can
come from the tower water supply (ie from the HVAC system) or from a
dedicated cooling water loop. Be careful if you select an air cooled unit
because the heat expelled from these units into the surrounding
4 RECEIVER
A. A receiver is located at the downstream of the air compressors. The receiver is a
carbon steel pressure vessel, positioned either horizontally or vertically, which acts as
storage reservoir, essentially the same as a WFI or USP storage tank. The
compressors load and “fill” the receiver with air to a determined pressure and unload
when that pressure is met (compressors typically do not turn on and completely off,
they load and unload…load means the compressor is filling the receiver, unload
means the compressor’s motor is on, but it is not discharging air, much like an
automobile idling at a traffic light). When the users consume the air, the pressure in
the receiver decreases. When the pressure in the receiver decreases to a particular
point (this is the minimum acceptable pressure required by the users), the
compressors will load and pump air till the receiver is brought back the system’s set
pressure. The advantages of the receiver is as follows:
1. As described above the receiver acts much like a storage vessel, and prevents
the compressors from rapidly loading and unloading. This so-called “short-
cycling” is undesirable because it can be abusive to the equipment.
2. The filters and dryers, located downstream of the receiver, will see a relatively
steady pressure as it leaves the receiver. If the filters and dryers were located
between the compressor and receiver, they would see high swings in flowrates
as the compressor loads and unloads.
3. The receiver is uninsulated and due to it’s relatively large surface area,
dissipates some of the compressed air’s heat to the room, cooling the stored air
a bit. When the air temperature drops some of the moisture will tend to “fall out”
and drop to the bottom of the receiver due to reaching it’s thermodynamic dew
point. There is an “automatic” float operated drain valve on the bottom of the
receiver that opens when the water build ups and closes once the water drops to
a minimum volume. These automatic drain valves are notorious for failing and
do require periodic inspection and maintenance.
5 FILTRATION
A. There are typically two types of filters we use on a compressed air system, coalescing
and particulate. The purpose of a coalescing filter is to remove water and the
particulate filter is to remove dust and resin fines introduced from the dessicant dryer.
B. Coalescing filters (located upstream of the dryer) and particulate filters (located down
stream of the dryer) sets are typically installed in pairs parallel to one another, each
with 100% required capacity. This allows us to replace a filter cartridge without
shutting down the entire compressed air system. The cost of the redundant filter is
inexpensive compared to shutting down the entire plant’s compressed air system to
replace a filter.
C. Coalescing filters are provided with an automatic drain valve (similar to the valve
provided on the bottom of the receiver) to remove the water in the bottom of the
coalescing housing. Particulate filters do not require an automatic drain valve
because all of the water will have been removed by the time it reaches the particulate
6 AIR DRYERS
A. As mentioned above, coalescing filters only remove condensed water, not water
vapor. In order to remove the water vapor to the specified dewpoint, a dryer is used.
There are two types of commonly used dryers, refrigerated and dessicant.
B. Refrigerated Dryers
1. A refrigerated dryer removes the moisture by reducing the temperature of the air.
By utilizing a refrigeration cycle similar to a household air conditioner, the
refrigerated air dryer lowers the temperature of the compressed air stream to just
above the freezing point of the water. Most of the water vapor contained in the
air condenses at the low temperature and the water is collected and removed
from the air stream by a moisture separator. This type of dryer will remove 90%
of the moisture present in the air stream.
END OF DOCUMENT