Product data sheet 140CPU67160

Characteristics Unity HSBY processor with multimode Ethernet


- Modicon Quantum - 1024 KB - 266MHz

Main
Range of product Modicon Quantum automation platform
Product or component Unity processor
type
Mathematical copro- Without
cessor

It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Complementary
Clock frequency 266 MHz
Number of slots 2
16
10
6
4

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
Number of racks 2 local rack(s)

This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.

Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Number of distributed I/O station 63 station(s) - 1 rack(s) - 3 distributed network(s)
Number of remote I/O station 31 station(s) - 2 remote rack(s)
Discrete I/O number Unlimited (26 slots max) - local
31744 inputs, 31744 outputs - remote
8000 inputs, 8000 outputs per network - distributed
Analogue I/O number Unlimited (26 slots max) - local
500 inputs, 500 outputs per network - distributed
1984 inputs,1984 outputs - remote
Application specific I/O Serial link
Counter
High-speed interrupt inputs
Accurate time stamping
Number of optional modules 6 (Ethernet, Modbus, Modbus Plus, Profibus DP, Sy/Max)
Maximum number of connections 4 (AS-Interface) - remote
6 (Modbus Plus) - local
Unlimited (AS-Interface) - local
1 (Modbus) - RS232/485 Modbus/ASCII
2 (AS-Interface) - distributed
1 (USB)
6 (Ethernet TCP/IP) - local
6 (Profibus DP) - local
Integrated connection type 1 USB
1 Modbus
1 Ethernet TCP/IP
1 Modbus Plus
Redundancy Modbus Plus
Power supplies
Remote I/O networks
Ethernet TCP/IP
Checks Hot standby
Process control

Apr 23, 2011


1
Memory capacity 256 kB - located data and configuration - without PCMCIA card
7168 kB - program - with PCMCIA card
1024 kB - program and unlocated data - without PCMCIA card
128 kB - located internal data
1024 kB - configuration and located/unlocated data - with PCMCIA card
65528 bytes - located internal bits
2 MB internal RAM - without PCMCIA card
1024 kB - unlocated internal data
Switch function Key switch memory port on/off
Application structure 32 timer interrupt tasks
128 I/O interrupt tasks
4 auxiliary tasks
1 cyclic/periodic master task
1 periodic fast task
128 interrupt tasks
Execution time per instruction 0.045...0.06 µs on word
0.045...0.06 µs on fixed-point arithmetic
0.0525...0.075 µs Boolean
0.4...0.5 µs floating points
Execution time for 1 K instruction 10.07 65 % Boolean and 35 % numerical
10.28 100 % Boolean
System overhead 0.2 ms - fast task
1 ms - master task
Bus current requirement 2500 mA
Local signalling 1 LED green for Ethernet activity (COM)
1 LED red for Ethernet collision
Electrical connection 1 female connector SUB-D 9 for connecting to the Modbus Plus network
1 connector MT-RJ (multimode fiber optic) for interconnecting primary and sec-
ondary PLCs up to 4 Km
1 connector RJ45 for connecting Modbus bus
1 connector RJ45 for connecting Ethernet network

Environment
Product certifications UL
CSA
CE
Standards HazLoc

2
Product data sheet 140CPU67160
Dimensions Drawings

Racks for Modules Mounting

Dimensions

(1) 2 slots
(2) 3 slots
(3) 4 slots
(4) 6 slots
(5) 10 slots
(6) 16 slots
Depth with modules : 104 mm/4.09 in.

3
Product data sheet 140CPU67160
Technical Description

CPU Module

Front Panel Switches


CPU11302 front panel switches Two, three-position slide switches are located on the front of the CPU. The left switch is used for memory
protection when in the top position and no memory protection in the middle and bottom positions. The three-position slide switch on the right
is used to select the communication parameter settings for the Modbus (RS-232) ports.
The following figure shows the three options that are available for the CPU11302.

The CPU hardware defaults to bridge mode when the front panel switch is set to RTU or ASCII mode. When networking controllers, a panel
device connected to the CPU Modbus port can communicate with the controller to which it is connected, as well as log into any nodes on the
Modbus Plus network.
CPU11302 ASCII communication port parameters Setting the slide switch to the top position assigns ASCII functionality to the port; the
following communication parameters are set and cannot be changed.
ASCII Communication Port Parameters

Baud 2,400

Parity Even

Data Bits 7

Stop Bits 1

Device Address Rear panel rotary switch setting


CPU11302 RTU communication port parameters Setting the slide switch to the middle position assigns remote terminal unit (RTU)
functionality to the port; the following communication parameters are set and cannot be changed.
RTU Communication Port Parameters

Baud 9,600

Parity Even

Data Bits 8

Stop Bits 1

Device Address Rear panel rotary switch setting


CPU11302 valid communication port parameters Setting the slide switch to the bottom position gives you the ability to assign communication
parameters to the port in software; the following parameters are valid.
Valid Communication Port Parameters

Baud 19,200 1,200

9,600 600

7,200 300

4,800 150

3,600 134.5

2,400 110

2,000 75

1,800 50

Data Bits 7/8

Stop Bits 1/2

Parity Enable/Disable Odd/Even

Device Address 1 ... 247