Presentation
1 2
Run components Connection components and feed units
From 1000 to 4000 A. For connecting the busbar trunking to transformer terminals or to
4 live aluminium conductors in fixed lengths of 4 metres switchboard connections.
or in 0.50 to 3 metre lengths as required. These components are only available in copper.
2/4 Te
3 4
Components for changing direction Fixing devices
For adapting to all the trunking runs. There are two ways of fixing : horizontal and vertical.
They are available in fixed lengths or made to measure.
Te 2/5
High power busbar trunking
Canalis KTA (1000 to 4000 A)
For low density horizontal distribution in :
industry, commercial and service buildings and infrastructures
Presentation
1 2
Run components Connection components and feed units
From 1000 to 4000 A. For connecting the busbar trunking to switchboard connections.
4 live aluminium conductors. Feeder components in fixed lengths of These components are only available in copper.
4 metres or in 0.50 to 3 metre lengths as required.
Distribution components in fixed lengths of 2 and 4 metres.
2/6 Te
3 4 5
Components for changing direction Fixing devices Tap-off units
For adapting to all the trunking runs. There are two ways of fixing : horizontal and From 400 to 1250 A for Merlin Gerin Compact NS
They are available in fixed lengths or made to vertical. or Compact C circuit-breakers. For low density
measure. tapping off, the units are mounted on components
designed for this purpose.
Te 2/7
High power busbar trunking
Canalis KTA (1000 to 4000 A)
For high density horizontal distribution in :
industry, commercial and service buildings and infrastructures
Presentation
1 2
Run components Connection components and feed units
From 1000 to 4000 A. For connecting the busbar trunking to switchboard connections.
4 live aluminium conductors. Feeder components in fixed lengths of These components are only available in copper.
4 metres or in 0.50 to 3 metre lengths as required.
Distribution components in fixed lengths of 2 and 4 metres.
2/8 Te
3 4 5
Components for changing direction Fixing devices Tap-off units
For adapting to all the trunking runs. There are two ways of fixing : horizontal and There are two types of unit : removable (KS
They are available in fixed lengths or made to vertical. range from 25 to 400 A) and bolt-on for Merlin
measure. Gerin Compact circuit-breakers from 400 to
1250 A.
Te 2/9
High power busbar trunking
Canalis KTA (1000 to 4000 A)
For rising main distribution in :
industry, commercial and service buildings and infrastructures
Presentation
1
Run components
From 1000 to 4000 A.
4 live aluminium conductors,
in 2.50 to 4 metre lengths according to the
height of the floors.
2
Connection components and feed
units
For connecting busbar trunking
to switchboard connections.
These components are only available in copper.
2/10 Te
3
Components for changing direction
For adapting to all the trunking runs.
They are available in fixed lengths or made to measure.
4
Fixing devices
There are two ways of fixing : horizontal and vertical.
5
Tap-off units
There are two types of unit : removable (KS range from
25 to 400 A) and bolt-on for Merlin Gerin Compact
circuit-breakers from 400 to 1250 A.
Te 2/11
High power busbar trunking
Selection guide : Canalis KTA (1000 to 4000 A)
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3 Description
References :
pages 10274/2 to 10279/5
Dimensions :
pages 10280/2 to 10284/3
General
Canalis KTA trunking is designed to feed and distribute high power in industrial, commercial or service buildings. The
standard range is IP 52 (IP 54 as an option). This trunking has a compact design, namely with plated conductors inside
a metal enclosure. The isolated conductor bars are made of aluminium. The range is divided into 7 ratings from 1000 to
4000 A. The insulation used on the conductors is halogen-free 130°C class B polyester.
Joints
Each run component (straight length, elbow, tee, etc) includes its own joint kit (delivered under separate cover). The joint
kit comprises all the parts required to provide a mechanical and electrical joint between two components.
The electrical joint is ensured by a single bolt joint block (1 to 2 bolts per busbar). This ensures continuity for all conductors
of 2500 A upwards, and paralleling of both bars in the same phase.
The bolt is made up of a screw and a contraction nut, the external head of which breaks when the tightening torque is
reached. This device ensures the required contact pressure is applied by the joint block to the live conductors.
When the head of the nut breaks, a red washer is released, showing that the electrical joint has been installed correctly.
For disassembly or maintenance operations, a second head is available. The recommended torque is thus 6 Nm.
The joint block contacts are silver-plated copper.
2/12 Te
High power busbar trunking
Selection guide : Canalis KTA (1000 to 4000 A)
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3 Description
References :
pages 10274/2 to 10279/5
Dimensions :
pages 10280/2 to 10284/3
Run components
There are 4 types of straight length (supplied with their busbar connector), types ET, EA, EB and DB.
Te 2/13
High power busbar trunking
Selection guide : Canalis KTA (1000 to 4000 A)
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3 Description
References :
pages 10274/2 to 10279/5
Dimensions :
pages 10280/2 to 10284/3
To connect KTA trunking to the various terminals or connections of transformers, switchboards, generators, etc, Canalis
offers high-performance connection components to meet all requirements. These components ensure flexible, easy
installation together with quick, easy mounting. They also absorb last minute deviations in civil engineering as they can
be adapted on site. Moreover, connections are made using bolts with snap-off heads which at the same time offer easy
installation (use of a standard spanner for tightening) and visual check before power up.
End cover
2/14 Te
High power busbar trunking
Selection guide : Canalis KTA (1000 to 4000 A)
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3 Description
References :
pages 10274/2 to 10279/5
Dimensions :
pages 10280/2 to 10284/3
yy
@@
ÀÀ
,,
ÀÀy,À@yy
@@
,,
yy @@y,À@yy
ÀÀ
,, @@y,À@
ÀÀ
,,
@@y,À@yy
ÀÀ
,,
yy @@y,À@yy
ÀÀ
,, @@y,À@
ÀÀ
,,
@@y,À@yy
ÀÀ
,,
yy @@y,À@
ÀÀ
,,
Te 2/15
High power busbar trunking
Selection guide : Canalis KTA (1000 to 4000 A)
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3 Description
References :
pages 10274/2 to 10279/5
Dimensions :
pages 10280/2 to 10284/3
i Edgewise tees
Fixing devices
1 Horizontal fixing
1 This consists of a steel bracket and two M10 threaded
rods, 1.2 metres long, the maximum fixing distance is 3
metres.
2 Vertical fixing
This fixes a vertical run component to the structure of the
building.
This type of fixing support has the following advantages :
- The height can be adjusted to correct positioning
errors.
- The spring can be adjusted to ensure the load is
distributed at each level.
2 - The constraints of the building (expansion, vibration
etc) are not transferred to the trunking.
2/16 Te
High power busbar trunking
Selection guide : Canalis KTA (1000 to 4000 A)
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3 Description
References :
pages 10274/2 to 10279/5
Dimensions :
pages 10280/2 to 10284/3
Tap-off units
These are used to instantly connect loads or secondary runs. They conform to installation standards and regulations,
whatever the neutral point connection (TT, IT, TNS or TNC) :
- They can be moved with the power on, with no load.
- The tap-off outlets open and close automatically when units are plugged in or removed.
- When the cover is open, no live part can be accessed and the degree of protection provided is IP 2X.
Tap-off units are produced in a dust and damp proof version, degree of protection IP 54.
A Tap-off units
- Isolation is obtained by removing the unit.
- The electrical equipment and connection terminals can only be accessed when the unit has been removed (power
off).
- A safety device prevents the unit being plugged into the trunking if the cover is not in place.
These units can take certain accessories such as an early break contact on the cover, lead sealing kit, etc.
A
B
PE =
Te 2/17
High power busbar trunking
Selection guide : Canalis KTA (1000 to 4000 A)
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3 Description
References :
pages 10274/2 to 10279/5
Dimensions :
pages 10280/2 to 10284/3
Tap-off units
2/18 Te
High power busbar trunking
Selection guide : Canalis KTA (1000 to 4000 A)
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3 Description
References :
pages 10274/2 to 10279/5
Dimensions :
pages 10280/2 to 10284/3
Te 2/19
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 and 10271/9
Characteristics :
pages 10273/2 and 10273/3 Selection guide
References :
pages 10274/2 to 10279/5
Dimensions :
pages 10280/2 to 10284/3
The rating of a busbar trunking, in amps, represents the maximum intensity of the constant current which the trunking can
continuously support, for an average ambient temperature of 35 °C, and in accordance with standard temperature rises
(IEC 439.2).
Determining the rating according to the temperature rise consists of selecting the busbar trunking rating immediately
above the operating current of the installation. However, as a rule, the intensity of the current which crosses a busbar
trunking is constantly fluctuating. The operating current is therefore defined as that of the constant current which produces
the same thermal effects as the actual current.
It is sometimes difficult to determine the operating current, especially when there is no reading for the installation or for
an equivalent installation. The operating current can be estimated with sufficient precision by calculating the product of
the nominal currents of receivers connected to the busbar trunking by a coefficient known as the “average demand
coefficient”. The average demand coefficient is empirically determined by comparison with existing installations. It is
dependent upon :
- the average quantity of receivers operating
- the load variation of each receiver (a receiver rarely absorbs its maximum power, as peak periods alternate with those
of no-load operation)
- whether several receivers are operating at the same time, whether peaks are superimposed and the duration of these
peaks
As an example, here are a few coefficients for a general mechanical engineering workshop.
2 or 3 0.9
4 or 5 0.8
6 to 9 0.7
10 to 40 0.6
40 plus 0.5
Depending on the ambient temperature, the trunking must be derated (see characteristics pages 10273/2 and 10273/3).
The permissible voltage drop is that which is compatible with the correct operation of the receivers (refer to the
manufacturers' manuals).
i Read the voltage drop in mV/100m/A in the tables on page 10273/3 for the busbar trunking selected according to the
temperature rise.
i Determine the voltage drop for the most disadvantaged receivers, namely those which are the furthest from the source
and for the highest current. If the voltage drop is not permissible, select the rating immediately above.
i Calculate the intensity of the short-circuit current at the points which are considered to be unfavourable.
i Check, by referring to the tables on pages 10273/2 and 10273/3, that the selected rating of the trunking enables it to
withstand this short-circuit current. If this is not the case, there are two possible solutions :
- Select trunking of a higher rating and repeat the checking procedure.
- Provide a protection system which limits current peaks upstream of the trunking.
2/20 Te
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 and 10271/9
Characteristics :
pages 10273/2 and 10273/3 Selection guide
References :
pages 10274/2 to 10279/5
Dimensions :
pages 10280/2 to 10284/3
The table below can be used to determine the rating of the KTA busbar trunking (aluminium conductors) and the source
circuit breaker (Merlin Gerin) according to the power of the transformer.
Calculation assumptions
The following calculation assumptions have been made :
- the short-circuit power of the upstream supply : 500 MVA
- the voltage ratio of the transformers : 20 kV/400 V
The circuit-breaker/trunking coordination table below gives directly the maximum short-circuit current for which the KT
trunking is protected, according to the type of circuit-breaker.
Merlin-Gerin C1001 N 50 50
Compact H 55 70
circuit-breaker L 100 150
C1251 N 50 50
H 55 70
Merlin-Gerin M 10 N1 40 40 40 40
Masterpact M 12 H1 40 50 60 65
circuit-breaker M 16 H2 40 50 60 73
M 10 - 12 L1 55 85 130
M 20 N1 55 55 55 55
M 25 H1 60 73 75 75
H2 60 73 80 86
M 32 H1 75 75 75
M 40 H2 80 86 90
M 50 H1 90
H2 90
Te 2/21
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide :
pages 10272/2 and 10272/3 Characteristics
References :
pages 10274/2 to 10279/5
Dimensions :
pages 10280/2 to 10284/3
General characteristics
Degree of protection (IEC 529) IP 52 for horizontal, edgewise installation and vertical installation, IP 54 as an option.
as standard IP 52 for horizontal, flat installation
Permissible currents
Rated current Ith (2) A 1000 1200 1600 2000 2500 3000 4000
conforming to IEC 439
Multiplying Temperature °C 35 40 45 50
factors of the
rated current
Ith depending Factor 1 0.95 0.90 0.84
on the average
ambient temperature
Conductor characteristics
Live conductors
Rb0ph Average resistance per m /m 0.046 0.038 0.028 0.023 0.019 0.014 0.011
conductor, cold state
(ambient temperature 20 °C)
Rb1ph Average resistance per m /m 0.058 0.048 0.036 0.029 0.026 0.018 0.015
conductor at Ith
(ambient temperature 35 °C)
Xph Average reactance per m /m 0.016 0.015 0.013 0.011 0.008 0.0074 0.007
conductor
Zph Average impedance per m /m 0.06 0.05 0.038 0.031 0.027 0.019 0.017
conductor
(1) For 60 to 400 Hz AC or for DC, please consult your Regional Sales Office.
(2) Rated currents Ith are given for an average ambient temperature of 35 °C and for a casing temperature rise of no more
than 55 °K according to the test conditions of standard EN 60 439.2.
10273/2 Te
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide :
pages 10272/2 and 10272/3 Characteristics
References :
pages 10274/2 to 10279/5
Dimensions :
pages 10280/2 to 10284/3
Other characteristics
Live conductors
Rb1ph ph or phN Average resistance m /m 0.116 0.096 0.072 0.058 0.052 0.036 0.029
of fault loops between
live conductors
Rb2ph ph or phN Average resistance m /m 0.139 0.115 0.086 0.070 0.062 0.043 0.035
of fault loops between
live conductors
Rb1ph PE Average resistance m /m 0.190 0.171 0.151 0.137 0.127 0.111 0.101
of fault loops between
live conductors and PE
Xb1ph ph or phN Average reactance m /m 0.026 0.024 0.022 0.019 0.012 0.010 0.010
of fault loops between
live conductors
Xb1ph PE Average reactance m /m 0.12 0.10 0.10 0.10 0.07 0.056 0.043
of fault loops between
live conductors and PE
Voltage drop Composite voltage drop, hot state, in millivolts per metre and per amp, for three-phase 50 Hz current, with the load
distributed along the run. If the load is concentrated at the end of the run (feed run), voltage drops are half the values
indicated in the table below.
For a power factor ϕ mV/m/A 0.045 0.0383 0.0299 0.0244 0.0206 0.0155 0.0134
of 0.7
For a power factor ϕ mV/m/A 0.048 0.041 0.0317 0.0258 0.0221 0.0163 0.014
of 0.8
For a power factor ϕ mV/m/A 0.051 0.043 0.0329 0.0268 0.0232 0.0168 0.0143
of 0.9
For a power factor ϕ mV/m/A 0.05 0.0416 0.0312 0.0251 0.0225 0.0156 0.013
of 1
Protective conductor
Casing Equivalent copper mm2 130 140 155 165 180 190 200
cross-section
Additional Equivalent copper mm2 300 360 480 600 720 960 1200
conductor cross-section
Average weight
3L + N + PE kg/m 22 23 25 28 31 37 45
3L + N + PER kg/m 24 25 29 33 37 45 55
Te 2/23
KTA-iiEAiii KTA-iiETiii
KTA-iiETiii
KTA-iiEAiii
KTA-iiEBiii
2/24 Te
High power busbar trunking
Description : Canalis KTA (1000 A)
pages 10271/2 to 10271/9 IP 52 run components
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
For feeding
Type Length Number of 3L + N + PE 3L + N + PER
Min…Max tap-offs Reference Reference
mm
N
2001…2500 – KTA-10ET42C KTA-10ET72C
N
For rising main distribution with removable tap-off
Expansion
N
IP 54 joint block (2)
Busbar trunking rating 3L + N + PE 3L + N + PER
Reference Reference
A Weight (kg) Weight (kg)
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
(2) Only order if the run has a feed unit at each end.
N : position of neutral
Te 2/25
High power busbar trunking
Description : Canalis KTA (1200 A)
pages 10271/2 to 10271/9 IP 52 run components
Selection guide :
pages 10272/2 and 10272/3
Caracteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
For feeding
Type Length Number of 3L + N + PE 3L + N + PER
Min…Max tap-offs Reference Reference
mm
N
2001…2500 – KTA-12ET42C KTA-12ET72C
N
For rising main distribution with removable tap-off
Expansion
N
IP 54 joint block (2)
Busbar trunking rating 3L + N + PE 3L + N + PER
Reference Reference
A Weight (kg) Weight (kg)
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
(2) Only order if the run has a feed unit at each end.
N : position of neutral
2/26 Te
High power busbar trunking
Description : Canalis KTA (1600 A)
pages 10271/2 to 10271/9 IP 52 run components
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
For feeding
Type Length Number of 3L + N + PE 3L + N + PER
Min…Max tap-offs Reference Reference
mm
N
2001…2500 – KTA-16ET42C KTA-16ET72C
N
For rising main distribution with removable tap-off
Expansion
N
IP 54 joint block (2)
Busbar trunking rating 3L + N + PE 3L + N + PER
Reference Reference
A Weight (kg) Weight (kg)
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
(2) Only order if the run has a feed unit at each end.
N : position of neutral
Te 2/27
High power busbar trunking
Description : Canalis KTA (2000 A)
pages 10271/2 to 10271/9 IP 52 run components
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
For feeding
Type Length Number of 3L + N + PE 3L + N + PER
Min…Max tap-offs Reference Reference
mm
N
2001…2500 – KTA-20ET42C KTA-20ET72C
N
For rising main distribution with removable tap-off
Expansion
N
IP 54 joint block (2)
Busbar trunking rating 3L + N + PE 3L + N + PER
Reference Reference
A Weight (kg) Weight (kg)
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
(2) Only order if the run has a feed unit at each end.
N : position of neutral
2/28 Te
High power busbar trunking
Description : Canalis KTA (2500 A)
pages 10271/2 to 10271/9 IP 52 run components
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
For feeding
Type Length Number of 3L + N + PE 3L + N + PER
Min…Max tap-offs Référence Reference
mm
N
2001…2500 – KTA-25ET42C KTA-25ET72C
N
For rising main distribution with removable tap-off
Expansion
N
IP 54 joint block (2)
Busbar trunking rating 3L + N + PE 3L + N + PER
Reference Reference
A Weight (kg) Weight (kg)
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
(2) Only order if the run has a feed unit at each end.
N : position of neutral
Te 2/29
High power busbar trunking
Description : Canalis KTA (3000 A)
pages 10271/2 to 10271/9 IP 52 run components
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
For feeding
Type Length Number of 3L + N + PE 3L + N + PER
Min…Max tap-offs Reference Reference
mm
N
2001…2500 – KTA-30ET42C KTA-30ET72C
N
For rising main distribution with removable tap-off
Expansion
N
IP 54 joint block (2)
Busbar trunking rating 3L + N + PE 3L + N + PER
Reference Reference
A Weight (kg) Weight (kg)
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
(2) Only order if the run has a feed unit at each end.
N : position of neutral
2/30 Te
High power busbar trunking
Description : Canalis KTA (4000 A)
pages 10271/2 to 10271/9 IP 52 run components
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
For feeding
Type Length Number of 3L + N + PE 3L + N + PER
Min…Max tap-offs Reference Reference
mm
N
2001…2500 – KTA-40ET42C KTA-40ET72C
N
For rising main distribution with removable tap-off
Expansion
N
IP 54 joint block (2)
Busbar trunking rating 3L + N + PE 3L + N + PER
Reference Reference
A Weight (kg) Weight (kg)
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
(2) Only order if the run has a feed unit at each end.
N : position of neutral
Te 2/31
KT0-iiERiii01 KT0-iiERiii03 KT0-iiERiii05
KT0-iiERiii02 KT0-iiERiii04 KT0-iiERiii06
2/32 Te
High power busbar trunking
Description : Canalis KTA (1000 A)
pages 10271/2 to 10271/9 IP 52 feed units
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
Straight length N1
a Straight length N2
Flat elbow N3
e Made to 200…1000 300…1000 80…250 KT0-13ER42C03 KT0-13ER72C03
e
e measure
a
Flat elbow N4
b
N3
Made to 200…1000 300…1000 80…250 KT0-13ER42C04 KT0-13ER72C04
N4 measure
Edgewise elbow N5
Edgewise elbow N6
N6 e
e e Made to 200…1000 300…1000 80…250 KT0-13ER42C06 KT0-13ER72C06
measure
N e
7 e Straight length, flat outlets N7
e
Made to 235…1000 _ 160…800 KT0-13ER42B07 KT0-13ER72B07
a measure
N a
10
e Edgewise elbow, flat outlets N11
e
e
Made to 200…1000 300…1000 160…800 KT0-13ER43D11 KT0-13ER73D11
measure
(1) To order the feed unit, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
Te 2/33
High power busbar trunking
Description : Canalis KTA (1200 A)
pages 10271/2 to 10271/9 IP 52 feed units
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
Straight length N1
e Straight length N2
e
e
Made to 235…1000 _ 80…250 KT0-16ER41A02 KT0-16ER71A02
measure
a
N
1, Flat elbow N3
N
2
Made to 200…1000 300…1000 80…250 KT0-16ER42C03 KT0-16ER72C03
measure
e
e
e Flat elbow N4
b Edgewise elbow N6
N5
a
a b
e Flat elbow, flat outlets N9
e
e
Made to 200…1000 300…1000 160…800 KT0-16ER43D09 KT0-16ER73D09
measure
N9
N8
Edgewise elbow, flat outlets N10
N a
10 Made to 200…1000 300…1000 160…800 KT0-16ER43D11 KT0-16ER73D11
e measure
e
e
Average weight 43 kg/m 45 kg/m
(1) To order the feed unit, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
2/34 Te
High power busbar trunking
Description : Canalis KTA (1600 A)
pages 10271/2 to 10271/9 IP 52 feed units
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
Straight length N1
a Straight length N2
Flat elbow N3
e
e Made to 200…1000 300…1000 80…250 KT0-20ER42C03 KT0-20ER72C03
e measure
a
b Flat elbow N4
N3
N4 Made to 200…1000 300…1000 80…250 KT0-20ER42C04 KT0-20ER72C04
measure
Edgewise elbow N5
Edgewise elbow N6
N6 e
e e Made to 260…1000 400…1000 80…250 KT0-20ER42C06 KT0-20ER72C06
measure
N e
7 e Straight length, flat outlets N7
e
Made to 235…1000 _ 160…800 KT0-20ER42B07 KT0-20ER72B07
a measure
N a
10
e Edgewise elbow, flat outlets N11
e
e
Made to 260…1000 400…1000 160…800 KT0-20ER43D11 KT0-20ER73D11
measure
(1) To order the feed unit, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
Te 2/35
High power busbar trunking
Description : Canalis KTA (2000 A)
pages 10271/2 to 10271/9 IP 52 feed units
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
Straight length N1
Straight length N2
a
N Made to 235…1000 _ 80…250 KT0-25ER41A02 KT0-25ER71A02
1, measure
N
2
Flat elbow N3
a Flat elbow N4
b
N3 Made to 200…1000 300…1000 80…250 KT0-25ER42C04 KT0-25ER72C04
N4 measure
Edgewise elbow N5
N5
a
Edgewise elbow N6
N6 e
e e Made to 260…1000 400…1000 80…250 KT0-25ER42C06 KT0-25ER72C06
measure
N e
7 e Straight length, flat outlets N7
e
Made to 235…1000 _ 160…800 KT0-25ER42B07 KT0-25ER72B07
a measure
N a
10
e Edgewise elbow, flat outlets N11
e
e Made to 260…1000 400…1000 160…800 KT0-25ER43D11 KT0-25ER73D11
measure
(1) To order the feed unit, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
2/36 Te
High power busbar trunking
Description : Canalis KTA (2500 A)
pages 10271/2 to 10271/9 IP 52 feed units
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
Straight length N1
a Straight length N2
Flat elbow N3
e
e Made to 200…1000 300…1000 80…250 KT0-30ER42C03 KT0-30ER72C03
e measure
a
b Flat elbow N4
N3
N4 Made to 200…1000 300…1000 80…250 KT0-30ER42C04 KT0-30ER72C04
measure
Edgewise elbow N5
Edgewise elbow N6
N6 e
e e Made to 260…1000 400…1000 80…250 KT0-30ER42C06 KT0-30ER72C06
measure
N e
7 e Straight length, flat outlets N7
e
Made to 235…1000 _ 160…800 KT0-30ER42B07 KT0-30ER72B07
a measure
N a
10
e Edgewise elbow, flat outlets N11
e
e
Made to 260…1000 400…1000 160…800 KT0-30ER43D11 KT0-30ER73D11
measure
(1) To order the feed unit, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
Te 2/37
High power busbar trunking
Description : Canalis KTA (3000 A)
pages 10271/2 to 10271/9 IP 52 feed units
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
Straight length N1
a Straight length N2
Flat elbow N3
e Made to 200…1000 300…1000 80…250 KT0-40ER42C03 KT0-40ER72C03
e
e measure
a
Flat elbow N4
b
N3
Made to 200…1000 300…1000 80…250 KT0-40ER42C04 KT0-40ER72C04
N4 measure
Edgewise elbow N5
Edgewise elbow N6
N6 e
e e Made to 340…1000 500…1000 80…250 KT0-40ER42C06 KT0-40ER72C06
measure
N e
7 e Straight length, flat outlets N7
e
Made to 235…1000 _ 160…800 KT0-40ER42B07 KT0-40ER72B07
a measure
N a
10
e Edgewise elbow, flat outlets N11
e
e
Made to 340…1000 500…1000 160…800 KT0-40ER43D11 KT0-40ER73D11
measure
(1) To order the feed unit, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
2/38 Te
High power busbar trunking
Description : Canalis KTA (4000 A)
pages 10271/2 to 10271/9 IP 52 feed units
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
Straight length N1
Flat elbow N3
a Flat elbow N4
b
N3 Made to 200…1000 300…1000 80…250 KT0-50ER42C04 KT0-50ER72C04
N4 measure
Edgewise elbow N5
N5
a
Edgewise elbow N6
N6 e
e e Made to 340…1000 500…1000 80…250 KT0-50ER42C06 KT0-50ER72C06
measure
N a
10
Edgewise elbow, flat outlets N11
e
e
e Made to 340…1000 500…1000 160…800 KT0-50ER43D11 KT0-50ER73D11
measure
(1) To order the feed unit, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
Te 2/39
KT0-iiCS0
KT0-iiYAii24i
KT0-iiYAiii2i KT0-iiYAi106
2/40 Te
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9 Connection accessories
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
A kg
IP 54 protective cover
Use References Weight
KT0-iiCS0
kg
IP 54 end cover
Busbar trunking rating 3L + N + PE
3L + N + PER
Reference Weight
A kg
KT0-00CR1
1000 KT0-13FA 1.400
(1) When ordering, specify the rating of the busbar trunking, the distance between the busbar outlets (dimension e), the
user-definable dimensions indicated, and the position of the neutral.
KT0-iiFA
Te 2/41
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9 Accessories for vibration absorber connection bars
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
(1) The reference corresponds to all the parts required to connect the phases and the neutral including the bolts, washers
and snap-off head nuts.
2/42 Te
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9 Accessories for connection via braids
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
,,
,,
,,
2000 2 (100 x 6) KT0-25YA40236 22.60
,,
,,
,, 3000 4 (100 x 6) KT0-40YA40436 50.40
KT0-iiYAiii36
4000 4 (100 x 6) KT0-50YA40536 57.90
,,
,,,, 4000 4 (100 x 6) KT0-50YA40246 64.40
,,
,,,,
KT0-iiYAii24i
Braids 1000. 1200 2 (100 x 6) KT0-16YA4106 65.00
yyyy
@@
ÀÀ
,, y,À@
@@
ÀÀ
,,
2500 3 (120 x 6) KT0-30YA4106 83.80
y,À@yy
ÀÀ
@@
,,
yy y,À@yy
@@
ÀÀ
,, y,À@
@@
ÀÀ
,, 3000 4 (120 x 6) KT0-40YA4106 110.40
y,À@yy
@@
ÀÀ
,,
yy y,À@yy
@@
ÀÀ
,, y,À@
@@
ÀÀ
,,
y,À@y,À@
@@
ÀÀ
,,
yy
4000 5 (120 x 6) KT0-50YA4106 136.80
(1) The reference corresponds to all the parts required to connect the phases and the neutral including the bolts, washers
KT0-iiYAi106 and snap-off head nuts.
Te 2/43
KTA-iiTCiii
KTA-iiTCiii
KTA-iiLCiii
KTA-iiLCiii
KTA-iiLPiii2
KTA-iiLPiii1
KTA-iiLPiii2
KTA-iiLPiii1
2/44 Te
High power busbar trunking
Description : Canalis KTA (1000 A)
pages 10271/2 to 10271/9 IP 52 tees and simple elbows
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
Elbows (1)
Edgewise LC
a Type Dimension a Dimension b Angle α 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
b
mm mm
N
Fixed 300 300 – KTA-10LC406 KTA-10LC706
Flat N1 at 90° LP
a b
N1 Fixed 300 300 – KTA-10LP4061 KTA-10LP7061
Flat N2 at 90° LP
a b
α N2 Made to 301…1000 301…1000 – KTA-10LP42B2 KTA-10LP72B2
measure
Edgewise TC
N Type Dimension a Dimension b Dimension c 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
mm mm mm
Fixing devices
Type Use Reference Weight
kg
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
Te 2/45
High power busbar trunking
Description : Canalis KTA (1200 A)
pages 10271/2 to 10271/9 IP 52 tees and simple elbows
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
Elbows (1)
Edgewise LC
a Type Dimension a Dimension b Angle α 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
b
mm mm
N
Fixed 300 300 – KTA-12LC406 KTA-12LC706
Flat N1 at 90° LP
a b
N1 Fixed 300 300 – KTA-12LP4061 KTA-12LP7061
Flat N2 at 90° LP
a b
α N2 Made to 301…1000 301…1000 – KTA-12LP42B2 KTA-12LP72B2
measure
Edgewise TC
N Type Dimension a Dimension b Dimension c 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
mm mm mm
Fixing devices
Type Use Reference Weight
kg
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
2/46 Te
High power busbar trunking
Description : Canalis KTA (1600 A)
pages 10271/2 to 10271/9 IP 52 tees and simple elbows
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
Elbows (1)
Edgewise LC
a Type Dimension a Dimension b Angle α 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
b
mm mm
N
Fixed 400 400 – KTA-16LC408 KTA-16LC708
Flat N1 at 90° LP
a b
N1 Fixed 300 300 – KTA-16LP4061 KTA-16LP7061
Flat N2 at 90° LP
a b
α N2 Made to 301…1000 301…1000 – KTA-16LP42B2 KTA-16LP72B2
measure
Edgewise TC
N Type Dimension a Dimension b Dimension c 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
mm mm mm
Fixing devices
Type Use Reference Weight
kg
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
Te 2/47
High power busbar trunking
Description : Canalis KTA (2000 A)
pages 10271/2 to 10271/9 IP 52 tees and simple elbows
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
Elbows (1)
Edgewise LC
a Type Dimension a Dimension b Angle α 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
b
mm mm
N
Fixed 400 400 – KTA-20LC408 KTA-20LC708
Flat N1 at 90° LP
a b
N1 Fixed 300 300 – KTA-20LP4061 KTA-20LP7061
Flat N2 at 90° LP
a b
α N2 Made to 301…1000 301…1000 – KTA-20LP42B2 KTA-20LP72B2
measure
Edgewise TC
N Type Dimension a Dimension b Dimension c 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
mm mm mm
Fixing devices
Type Use Reference Weight
kg
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
2/48 Te
High power busbar trunking
Description : Canalis KTA (2500 A)
pages 10271/2 to 10271/9 IP 52 tees and simple elbows
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
Elbows (1)
Edgewise LC
a Type Dimension a Dimension b Angle α 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
b
mm mm
N
Fixed 400 400 – KTA-25LC408 KTA-25LC708
Flat N1 at 90° LP
a b
N1 Fixed 300 300 – KTA-25LP4061 KTA-25LP7061
Flat N2 at 90° LP
a b
α N2 Made to 301…1000 301…1000 – KTA-25LP42B2 KTA-25LP72B2
measure
Edgewise TC
N Type Dimension a Dimension b Dimension c 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
mm mm mm
Fixing devices
Type Use Reference Weight
kg
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
Te 2/49
High power busbar trunking
Description : Canalis KTA (3000 A)
pages 10271/2 to 10271/9 IP 52 tees and simple elbows
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
Elbows (1)
Edgewise LC
a Type Dimension a Dimension b Angle α 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
b
mm mm
N
Fixed 500 500 – KTA-30LC410 KTA-30LC710
Flat N1 at 90° LP
a b
N1 Fixed 300 300 – KTA-30LP4061 KTA-30LP70611
Flat N2 at 90° LP
a b
α N2 Made 301…1000 301…1000 – KTA-30LP42B2 KTA-30LP72B2
to measure
Edgewise TC
N Type Dimension a Dimension b Dimension c 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
mm mm mm
Fixing devices
Type Use Reference Weight
kg
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
2/50 Te
High power busbar trunking
Description : Canalis KTA (4000 A)
pages 10271/2 to 10271/9 IP 52 tees and simple elbows
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
Elbows (1)
Edgewise LC
a Type Dimension a Dimension b Angle α 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
b
mm mm
N
Fixed 500 500 – KTA-40LC410 KTA-40LC710
Flat N1 at 90° LP
a b
N1 Fixed 300 300 – KTA-40LP4061 KTA-40LP7061
Flat N2 at 90° LP
a b
α N2 Made to 301…1000 301…1000 – KTA-40LP42B2 KTA-40LP72B2
measure
Edgewise TC
N Type Dimension a Dimension b Dimension c 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
mm mm mm
Fixing devices
Type Use Reference Weight
kg
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
Te 2/51
KTA-iiZPiii
KTA-iiZCiii1
KTA-iiTCiii
KTA-iiCPiii4
KTA-iiZCiii2
KTA-iiCPiii1
KTA-iiZLiii2
KTA-iiCPiii2
KTA-iiCPiii3
KTA-iiZLiii4
KTA-iiZLiii2
KTA-iiZLiii1
2/52 Te
High power busbar trunking
Description : Canalis KTA (1000 A)
pages 10271/2 to 10271/9 IP 52 zed units
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
Edgewise ZC
b
N Edgewise ZC
1
a
N2 Made to 300… 230… 300… – KTA-10ZC43D2 KTA-10ZC73D2
b
N Edgewise/flat CP
2
N1 Made to 300 220… 300 – KTA-10CP41A1 KTA-10CP71A1
b a measure 600 –
c
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
Te 2/53
High power busbar trunking
Description : Canalis KTA (1200 A)
pages 10271/2 to 10271/9 IP 52 zed units
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
N Edgewise ZC
1
a
N2 Made to 300… 230… 300… – KTA-12ZC43D2 KTA-12ZC73D2
measure 1000 1000 1000 –
b
Edgewise/flat CP
N
2
N1 Made to 300 220… 300 – KTA-12CP41A1 KTA-12CP71A1
measure 600 –
b a
measure 600 –
N1 N2
N
4 N4 Made to 300 230… 220… 300 KTA-12ZL42B4 KTA-12ZL72B4
N
3 measure 600 600
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
2/54 Te
High power busbar trunking
Description : Canalis KTA (1600 A)
pages 10271/2 to 10271/9 IP 52 zed units
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
N Edgewise ZC
1
a
N2 Made to 400… 350… 400… – KTA-16ZC43D2 KTA-16ZC73D2
measure 1000 1000 1000 –
b
Edgewise/flat CP
N
2
N1 Made to 300 280… 400 – KTA-16CP41A1 KTA-16CP71A1
measure 700 –
b a
measure 700 –
N1 N2
N
4
N N4 Made to 400 350… 280… 300 KTA-16ZL42B4 KTA-16ZL72B4
3 measure 800 700
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
Te 2/55
High power busbar trunking
Description : Canalis KTA (2000 A)
pages 10271/2 to 10271/9 IP 52 zed units
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
c
Edgewise ZC
b
N Edgewise ZC
1
a
N2 Made to 400… 350… 400… – KTA-20ZC43D2 KTA-20ZC73D2
measure 1000 1000 1000 –
b
Edgewise/flat CP
N
2
N1 Made to 300 280… 400 – KTA-20CP41A1 KTA-20CP71A1
measure 700 –
b a
measure 700 –
N1 N2
N3 Made to 300 280… 400 – KTA-20CP41A3 KTA-20CP71A3
measure 700 –
b
a
c
N
4 N4 Made to 400 350… 280… 300 KTA-20ZL42B4 KTA-20ZL72B4
N
3 measure 800 700
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
2/56 Te
High power busbar trunking
Description : Canalis KTA (2500 A)
pages 10271/2 to 10271/9 P 52 zed units
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
N Edgewise ZC
1
a
N2 Made to 400… 350… 400… – KTA-25ZC43D2 KTA-25ZC73D2
b
Edgewise/flat CP
N
2
N1 Made to 300 280… 400 – KTA-25CP41A1 KTA-25CP71A1
b measure 700 –
a
measure 700 –
N1 N2
N
4
N N4 Made to 400 350… 280… 300 KTA-25ZL42B4 KTA-25ZL72B4
3
measure 800 700
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
Te 2/57
High power busbar trunking
Description : Canalis KTA (3000 A)
pages 10271/2 to 10271/9 IP 52 zed units
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
N Edgewise ZC
1
a
N2 Made to 500… 510… 500… – KTA-30ZC43D2 KTA-30ZC73D2
measure 1000 1000 1000 –
b
Edgewise/flat CP
N
2
N1 Made to 300 360… 500 – KTA-30CP42B1 KTA-30CP72B1
measure 800 –
b a
measure 800 –
N1 N2
N
4
N N4 Made to 500 510… 360… 300 KTA-30ZL42B4 KTA-30ZL72B4
3 measure 1000 800
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
2/58 Te
High power busbar trunking
Description : Canalis KTA (4000 A)
pages 10271/2 to 10271/9 IP 52 zed units
Selection guide :
pages 10272/2 and 10272/3
Characteristics : References
pages 10273/2 and 10273/3
Dimensions :
pages 10280/2 to 10284/3
N Edgewise ZC
1
a
N2 Made to 500… 510… 500… – KTA-40ZC43D2 KTA-40ZC73D2
b
Edgewise/flat CP
N
2
N1 Made to 300 360… 500 – KTA-40CP42B1 KTA-40CP72B1
b measure 800 –
a
c
(1) To order a made to measure component, see the procedure on pages 10285/2 to 10285/5.
Ni : position of neutral
Te 2/59
KSE-10DA4
KSE-10DA4
KSE-iiDBi11
KSE-iiDBi11
KT0-iiCB311
2/60 Te
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide :
KS tap-off units, IP 54 dust and damp proof series, for NF fuses
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3
References
Dimensions :
pages 10280/2 to 10284/3
Tap-off unit
Number of conductors 3L + N + PE 3L + PEN 3L + PE
Tap-off scheme
(2)
Tap-off scheme
(2)
KSE-05SF41 Rating Fuse Connection Reference Reference Reference
A size mm2 Weight (kg) Weight (kg) Weight (kg)
Te 2/61
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide : KS tap-off units, IP 54 dust and damp proof series, for DIN and BS fuses
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3 References
Dimensions :
pages 10280/2 to 10284/3
Tap-off units
Number of conductors 3L + N + PE 3L + PEN 3L + PE
Tap-off scheme
(2)
Tap-off scheme
(2)
2/62 Te
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A
pages 10271/2 to 10271/9
Selection guide : KS tap-off units, IP 54 dust and damp proof series, for equipment
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3 References
Dimensions :
pages 10280/2 to 10284/3
Tap-off scheme
(example with circuit-breaker)
(2)
Tap-off units for Merlin Gerin Compact NS fixed circuit breaker (3)
With extended rotary handle, short axis (3)
Number of conductors 3L + N + PE 3L + PEN 3L + PE
Tap-off scheme
(2)
Te 2/63
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9 Straight lengths
Selection guide :
pages 10272/2 and 10272/3
Characteristics : Dimensions
pages 10273/2 and 10273/3
References :
pages 10274/2 to 10279/5
“Feeder”
KTA-iiETiii
h (1)
L
Type of length L
Fixed 4000
Made to measure 500...3000
“Expansion”
KTA-iiDBiii
h (1)
390
3000
1000 1000
2000
Joint block
14
14
350 144
2/64 Te
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 and 10271/9 Straight lengths
Selection guide :
pages 10272/2 and 10272/3
Characteristics : Dimensions
pages 10273/2 and 10273/3
References :
pages 10274/2 to 10279/5
“Horizontal distribution with removable tap-offs”
KTA-iiEAiii
290
1500 500
2000
290 290
Te 2/65
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9 Feed units
Selection guide :
pages 10272/2 and 10272/3
Characteristics : Dimensions
page 10273/2 and 10273/3
References :
pages 10274/2 to 10279/5
Straight end feed boxes Flat elbow end feed boxes
KT0-iiERiii01 and KT0-iiERiii02 KT0-iiERiii03 and KT0-iiERiii04
b h (1)
140
h (1)
a
a
215
215
ERiii01 ERiii02
Rating (A) y a e a e Rating (A) y a b e
1000 and 1200 230 235 120 235...1000 80...250 1000 and 1200 230 200...1000 300...1000 80...250
1600...2500 350 235 120 235...1000 80...250 1600...2500 350 200...1000 300...1000 80...250
3000 and 4000 510 235 120 235...1000 80...250 3000 and 4000 510 200...1000 300...1000 80...250
Rating (A) y a b e
1000 and 1200 230 200...1000 300...1000 80...250
1600...2500 350 260...1000 400...1000 80...250
130 e e e 130 y 3000 and 4000 510 340...1000 500...1000 80...250
50 50
60 60
50
47,5 65 47,5
100
100
60
60
50 50
60
60
50
50
50 50 50 50 50 50 14x20 50
2/66 Te
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide :
Feed units
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3
Dimensions
References :
pages 10274/2 to 10279/5
Straight end feed boxes, flat outlets
KT0-iiERiii07
140
h (1)
a
100
100
Rating (A) y a e
130 e e e 130 y 1000 and 1200 230 235...1000 160...800
1600...2500 350 235...1000 160...800
3000 and 4000 510 235...1000 160...800
Rating (A) y a b e
130 e e e 130 y 1000 and 1200 230 200...1000 300...1000 160...800
1600...2500 350 200...1000 300...1000 160...800
3000 and 4000 510 200...1000 300...1000 160...800
Rating (A) y a b e
1000 and 1200 230 200...1000 300...1000 160...800
130 e e e 130 y 1600...2500 350 260...1000 400...1000 160...800
3000 and 4000 510 340...1000 500...1000 160...800
Te 2/67
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide : Accessories
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3 Dimensions
References :
pages 10274/2 to 10279/5
50 50 50 50 50 50 5 or 6
67,5 65 47,5
50
60
75
75
1000
1000
1000
100 100 100
65 47,5
50
50
60
100
100
120
95
75
100
75
67,5 65
100
1000
75
1000
1000
1000
50
50
120
120
120
100
100
100
100
1000
1000
1000
1000
50
50
120
120
120
100
100
100
1000
1000
1000
2/68 Te
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide :
Accessories
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3
Dimensions
References :
pages 10274/2 to 10279/5
Connector plates
KT0-20YA40236 KT0-25YA40236 KT0-30YA40336 KT0-40YA40436 KT0-50YA40536 KT0-20YA40235
50 50 14 x 20 50 50 50 50 50 50 50 50 55 50 55
6 6 6 6 6 5
65 47,5
65 47,5
50
50
50
60
120
100
100
110
120
102,5
95
50
100
110
110
50
65
100
50
100
100
102,5
50
100
100
110
50
100
50
100
50
50
50
120
110
110
110
110
50
50
50
50
Braids
,,,
KT0-iiYA4106
References L
50
KT0-16YA4106 100
6
KT0-25YA4106 100
=
L
KT0-20YA4106 120
=
KT0-30YA4106 120
600 300 150 KT0-40YA4106 120
KT0-50YA4106 120
300
97,5
17,5
12,5 12,5 16 x ø7
c
17,5
175 150 175
17,5
35 160 35 35 25 500 25 35
References a b c
KT0-16CS0 230 620 200...650
KT0-30CS0 350 620 200...650
KT0-50CS0 510 620 200...650
Te 2/69
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide :
Simple elbows, tees and zed units
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3
Dimensions
References :
pages 10274/2 to 10279/5
b
h (1)
b a α h (1)
Rating (A) a and b fixed a and b made to measure Ratings (A) a and b fixed a and b made to measure α
1000 and 1200 300 301...1000 1000...4000 300 301...1000 90°
1600...2500 400 401...1000
3000 and 4000 500 501...1000
h (1)
α
b
b
a h (1)
140
a c
Rating (A) a and b made to measure α Rating (A) a, b and c made to measure
1000...4000 300...1000 91°...179° 1000 and 1200 300...1000
1600...2500 400...1000
3000 and 4000 500...1000
Flat zed units Edgewise zed units
KTA-iiZPiii KTA-iiZCiiii
h (1)
140
b
b
h (1)
c a h (1) a c 140
2/70 Te
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide :
Zed units
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3
Dimensions
References :
pages 10274/2 to 10279/5
Flat/edgewise zed units
KTA-iiCPiiii
b
h (1)
c
c
a h (1)
140
b
Rating (A) a b c
1000 and 1200 300 220...600 300
1600...2500 300 280...700 400
3000 and 4000 300 360...800 500
h (1)
c a d
140
d
Rating (A) a b c d
1000 and 1200 300 230...600 220...600 300
1600...2500 400 350...800 280...700 300
3000 and 4000 500 510...1000 360...800 300
Te 2/71
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide : Tap-off units
pages 10272/2 et 10272/3
Characteristics :
pages 10273/2 et 10273/3 Dimensions
References :
pages 10274/2 to 10279/5
Removable dust and damp proof tap-off units with/without isolator and fuse carriers
KSE-02CF5 KSE-02CD5
KSE-02CG5
8
8
160
160
50 43
8
50 90
8
93 93
KSE-16SFii
KSE-16SDii
KSE-16SGii
285
430 130 55
455 230
Cable outlet
2/72 Te
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide : Tap-off units with isolator and tap-off units with circuit-breaker
pages 10272/2 and 10272/3
Characteristics :
pages 10273/2 and 10273/3 Dimensions
References :
pages 10274/2 to 10279/5
Removable dust and damp proof tap-off units with isolator for modular equipment
KSE-05DAi KSE-10DAi
195
270 50 113* 70 100 40
395 190 52
Cable outlet
Removable dust and damp proof tap-off units for Merlin Gerin circuit-breaker
KSE-16DBi11 KSE-25DBi11
15
15
163
163
368
368
KSE-40DBi11
18
163
368
780 275
325
Cable outlet
Bolt-on dust and damp proof tap-off units for Merlin Gerin circuit-breaker
KT0-iiCBi11
c
b
Reference a b c
a KT0-06CB 800 350 300
KT0-12CB 1200 550 300
Te 2/73
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide :
pages 10272/2 and 10272/3
Characteristics : Procedure for ordering a made to measure component
pages 10273/2 and 10273/3
References :
pages 10274/2 to 10279/5
Definition of a component
Shape : each shape is characterised by a group of two letters (example : ET for a feeder length).
Dimensions : dimensions are always given in alphabetical order of the measurements (example : a x b x c, etc).
How to order
i Second line
Write the dimensions for the “made to measure” component and any of the options selected :
- If the reference corresponds to a made to measure product, there are one or more variable values : you should
write a x b x etc in alphabetical order.
- If the reference ends in A followed by a number, an option is available (see page 10285/5).
Straight lengths
The nominal length “L” of a straight length is measured from joint axis to joint axis, in millimetres (the joint axis is located
20 mm beyond the end of the bars).
Joint axis
L1
L2
L3
40 N
PE
= =
280
L
Example :
A KTA straight length, rating 1000 A, 3L + N + PE, 1820 mm long, has the following reference :
KTA-10ET42B
L = 1820
2/74 Te
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide :
pages 10272/2 and 10272/3 Procedure for ordering a made to measure component (continued)
Characteristics :
pages 10273/2 and 10273/3
References :
pages 10274/2 to 10279/5
Flat elbows
Example :
A KTA flat elbow, rating 1000 A, 3L + N + PE, type LP, N1 :
- length of limb a = 301 mm
- length of limb b = 500 mm
- angle = 130°
Edgewise elbows
Example :
A KTA edgewise elbow, rating 1000 A, 3L + N + PE, type LC :
- length of limb a = 301 mm
- length of limb b = 500 mm
b
Zed units
Example :
A KTA 4 limb zed unit, rating 1000 A, 3L + N + PE, ZL, type N3 :
- length of limb a = 300 mm
- length of limb b = 400 mm
- length of limb c = 500 mm
- length of limb d = 300 mm
a
has the following reference :
KTA-10ZL42B3
300 x 400 x 500 x 300
d
b
Te 2/75
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide :
pages 10272/2 and 10272/3 Procedure for ordering a made to measure component (continued)
Characteristics :
pages 10273/2 and 10273/3
References :
pages 10274/2 to 10279/5
a
Example :
A straight end feed box for KTA run, rating 1000 A, 3L + N
+ PE, type N2 :
- length of limb a = 450 mm
- distance between N and L3 = 100 mm
- distance between L3 and L2 = 120 mm
- distance between L2 and L1 = 150 mm
b Example :
A flat elbow end feed box, flat outlets for KTA run, rating
1000 A, 3L + N + PE, type N8 :
- length of limb a = 500 mm
- length of limb b = 400 mm
- distance between N and L3 = 250 mm
L1
- distance between L3 and L2 = 180 mm
L2 - distance between L2 and L1 = 250 mm
Note : If the run has a feed unit at each end, an additional joint block will be required.
2/76 Te
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide :
pages 10272/2 and 10272/3 Options, installation precautions
Characteristics :
pages 10273/2 and 10273/3
References :
pages 10274/2 to 10279/5
Options
The degree of protection for standard references is IP 52. To obtain degree IP 54, “A1” should be added at the end of the
standard reference (degree IP 54 can only be obtained by factory assembly). Similarly, if the trunking is to be mounted
outside, “A2” should be added at the end of the standard reference. The product is supplied as IP 54 with an aluminium
cover.
Installation precautions
Edgewise feed
min
100
270 270
min min
Flat feed
50
100
Te 2/77
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide :
pages 10272/2 and 10272/3 Installation precautions (continued)
Characteristics :
pages 10273/2 and 10273/3
References :
pages 10274/2 to 10279/5
Edgewise distribution
1000 min
x x
100
min
The fixing distance takes into account the minimum measurement of 100 mm and measurements x of the tap-off units
(see pages 10284/2 and 10284/3).
Flat distribution
500 min
Fixing distance
3000
2/78 Te
High power busbar trunking
Description : Canalis KTA (1000 to 4000 A)
pages 10271/2 to 10271/9
Selection guide :
pages 10272/2 and 10272/3 Installation precautions
Characteristics :
pages 10273/2 and 10273/3
References :
pages 10274/2 to 10279/5
i Positioning of lengths
If you use floor height lengths (from 2.50 to 4 metres),
position the first joint correctly so that the tap-off outlets
are accessible and the fixing device can be mounted. To
ensure this, a minimum distance of 500 mm between the
floor and the first joint axis is required.
This operation requires a made to measure component
L1.
Tap-off outlet
1000
When the run has a blocking component at one or both ends (end feed box, elbows, tees, etc), above a height of 30 metres
an expansion unit should be used. There should be one expansion unit for every 30 metre section.
Te 2/79