Rating 0.5 Amp to 125 Amps 1 Pole to 4 Pole Full Range tested for 10000 Amps Isolators upto 125 Amps AC22A Lighting & inductive load series B & C Designed for utmost safety Conforms to IS & IEC specs.

LINE

NOIDA UP 0607

Mfd. By

W E

C O N N E C T

F O R

L I F E

Vision

Delton Cables Ltd. is an ISO 9001: 2000 certified company committed to Quality and Customer Satisfaction. Delton provides competence in Cable technology covering measurement, control, communication and power distribution applications for different environmental conditions, as used in exploration, metal, oil, refining or gas processing sites, petrochemical, chemical, power generation and similar applications. Our specialization is in manufacturing tailor made cables as per customers specifications. Established in the year 1948 with a foresighted vision, a pioneering spirit, innovative approach, indigenously developed technology, the expertise of a highly motivated and professional team, excellent infrastructure facilities and sales network together synergised for the ultimate expression of customer delight, quality and safety.

Delton Conquer Fear


New Delgard SFP* MCBs from Delton using new engineering plastics for mechanical strength, higher operational endurance and highly flame retardant body material is aiming to set new standards for simple but superior electrical circuit protection to conquer fear of electrical fires due to short circuits and damage to electrical equipments due to over load performance, dependability and protection are strong in-built features. Delton is an established name in the electrical industry. Delton products have been the first choice of discerning buyers and demanding customers. Our Switchgears including MCBs are being manufactured in our well equipped and modern plant with state of the art R&D facilities. Our Miniature Circuit Breaker has been tested for 10 KA short circuit capacity at CPRI, Bhopal.

*Super Fast Protection

Miniature Circuit Breaker

W E

C O N N E C T

F O R

L I F E

Miniature Circuit Breaker


Delgard Miniature Circuit Brakers are used to control & protect electrical circuits from overload & short circuit current, conforming to the latest IS 8828:1996 & IEC 898:95 specifications. Delgard MCBs and Distribution Boards offer easy & reliable solutions. Besides the routine and type tests at CPRI, Delgard MCBs are subjected to additional tests for greater safety , better & reliable performance. Function / Mechanism Thermal Release - Under overload condition the bimetal strip deflects and trips the operating mechanism Magnetic release - In case of short circuit high current the magnetic coil activates the plunger to strikes and trips the operating mechanism Design & Construction Delgard SFP* MCBs have been developed & designed to provide total safety, ease of ON installation & connection, offer easier identification of faulty circuits and quick restoration. Mid Trip : Under fault condition the MCB Trips and the knob comes in the center position. This MID TRIP clearly indicates that MCB has tripped due to fault and not any mischief. OFF Energy Saving: The low power loss as stipulated in the IS 8828:96 & IEC 898:95 has been taken care in designing of Delton MCBs. The low watt loss figures of Delton MCB contributes significantly to the energy saving. DIN Rail Mounting: Delton MCBs can be mounted on standard 35 mm Din Rail by snap action. No time wastage in installing and replacing. The special lockable design of Snap Pusher / Din Rail clip makes the removal of MCB effortless. Shock Proof: Finger and hand touch safe. Tested as per the test clause 9.6 of IS 8828:1996 & IEC 898:95 protection against electric shock. Housing : The housing of MCB is injection moulded from special grade PBT as per international specifications. The housing and other moulded components are fire retardant, anti-tracking and non hygroscopic. The housing can with stand high temperature and is impact resistant. The non-hygroscopic nature of PBT material makes the MCB shock proof under humid conditions. Isolation: Contacts made of pure silver inlaid into copper strip, ensure long life and operational safety against contact welding and erosion. Current Limiting Action: Current limiting action ensures that the MCB operate before the full prospective fault current is allowed to develop. Minimum let through energy in the event of fault ensures the safety & protection of wires / cables and downstream equipment in the system. Operating Mechanism: Delton MCB Internal View of Delgard MCB have a quick make & break Trip Free Mechanism. In the event of an over current or short circuit the MCB Outgoing Terminal automatically interrupts all poles even if the MCB toggle is held in ON position. Easy Installation: The design of Arc - Chutes Solenoid terminals makes the wiring easier. Knob / Dolly Fix Contact Combination box type terminals with Plunger Arc - runner combination head screws on both sides Moving Contact with deep serrations ensure spark less Bimetallic Strip and firm connections. The bigger terminal size can accommodate higher Incoming Terminal conductor size for better termination. ( Dual Termination) The bi-connection facility simplifies connection in various application areas.
MID TRIP POSITION

W E

C O N N E C T

F O R

L I F E

Tripping Characteristic

Technical Information
Rating Voltage Rating No. of Poles Breaking Capacity Characteristics curves : : : : : 0.5 to 125 Amps 240/415V AC & DC 1P ,1P+N,2P ,3P+N,4P ,3P 10000 Amps (10KA) B & C Curve # D on Request

MCB
Standard Conformity Type/Series Rated Current (In) Rated Voltage (ac) (Ue) Rated Frequency Nos. of Poles (Execution) Rated Short Circuit Breaking Capacity kA Utilization Category Magnetic Release Setting Rated Insulation Voltage (Ui) Rated Impulse Voltage (Uimp) Electrical / Mechanical Endurance (Min. no. of operations) Ambient Temperature Terminal Capacity (max) Vibration Shock Protection Class Installation Position Mounting Case & Cover (oC) sq.mm g 30,000 -5 to +55 25 3 40mm free fall 30,000 -5 to +55 25 3 40mm free fall 30,000 -5 to +55 25 3 40mm free fall IP-20 Vertical / Horizontal Clip on DIN Rail (35mm) V kV 10 M10 (3-5)In 660 4 A V Hz 240/415 50 / 60 B IS 8828: 96 & IEC 898-1995 C 0.5 - 63 & 80-125 240/415 50 / 60 10 M10 (5-10)In 660 4 240/415 10 M10 (10-20)In 660 4 D#

ISOLATOR
IS 13947-3: 93 & IEC 60947-3: 2001 40 - 63 & 80-125 240/415 50 / 60 1P 2P 3P 4P , , , AC 22A 660 4 30,000 -5 to +55 25 5 40mm free fall

1P 1P+N, 2P 3P 3P+N, 4P , , ,

Moulded, from special grade PBT as per international specifications.

LOAD

NOIDA UP 0607

Mfd. By

LOAD

LINE

63 A
415V~

ISOLATO

Current Limiting Design


Voltage across MCB contacts at opening

In a current limiting breaker, the tripping mechanism & arc control is so designed that under short circuit conditions, the contacts are physically separated and
Voltage

the electrodynamic forces set up by fault current assist the extinction in less than half cycle.
TIME

The figure shows the current limiting effect of a circuit breakers. Fault Traces for Voltage & Current 0 = = = = Point of fault initiation Contact opening time (i.e., beginning of arc) Current / Voltage peak (i.e., limitation of current) Arc extinction time

Current

A Cut-off Current B cut off current Fault Current (Max. Prop.) t2 TIME

tx t1 t2

tx

t1

(i.e., complete shutdown of fault current)

LINE

NOIDA UP 0607

Mfd. By

Technical Data Characteristics Curves


Thermal Tripping
1.13In 1.45In

W E

C O N N E C T

F O R

L I F E

Magnetic Tripping Tripping current I2 1.45 x In Time t =1hr <1hr =1hr 1.45 x In <1hr =1hr 1.45 x In <1hr 10xIn 20 x In 5xIn 10 x In Hold I4 3xIn 5 x In Trip current I5 Time Limits t =0.1s <0.1s =0.1s <0.1s =0.1s <0.1s Limits current

Type of MCB B Curve

No tripping current I1 1.13 x In 1.13 x In 1.13 x In

120 60 30
min

10000 5000

1000 500

10 5 2 1 tv[s]

C Curve D Curve
B Curve

100 5

1 0.5 0.1

C Curve D Curve

Tripping Characteristics
Based on the Tripping Characteristics, MCBs are available in B, C and D curve to suit different types of applications. B Curve: for protection of electrical circuits with equipment that does not cause surge current (lighting and distribution circuits) Short circuit release is set to (3 - 5) In

0.01

0.006 0.002 0.001 1 l1 l2 2 l3 3 l4 l5 5 10 l4 l5 20 30 40 60 l5 80 X ln

C Curve: for protection of electrical circuits with equipment that causes surge current (inductive loads and motor circuits) Short circuit release is set to (5 - 10) In D Curve: for protection of electrical circuits which causes high inrush current, typically 12-15 times the thermal rated current (transformers, X-ray machines etc.) Short circuit release is set to (10 - 20) In

Ambient Temperatures Compensation / Diversity Factor Chart


K1 Maximum Permissible Rated Current (K2 Factor)
K2 1.0 Diversity Factor (K2 Factor)

Let through energy I2T

103 9 6 125A 4

160A

32A

1.5 1.4
0.9
Let through l t

40A/63A

25A 20A 16A

1.3
Factor

3
2

100A 10A 6A 80A 63A

2 1.5 104 8 50A

1.2 1.1 1.0 0.9 0.8 0.7 1-4A

0.8

4A 35A 2A 25A

40-63A
0.7
4 3

16-32A 6A 10A
0.6 1 2 3 4 5 6 7 8 9 10 11

2 1.5 10 2 4x10 5
3

-25 Graph 1

-10 0

10

20

30

40
0

50

60

Number of pole together with gap in between Graph 2

10

1.5

8 10

1.5

Amb. Temp. ( C)

Prospective Fault Current (kA)

Fuse Characteristics MCB Characteristics

Calculation Example Solution

In / switch 4 MCBs with In K1 K2 In / pole

= = = = =

K1 x K2 x In 10A, and the amb. temp. is 50oC kept with no gap in between 0.89 (from graph 1) 0.78 (from graph 2) 0.89 x 0.78 x 10=6.94 A

W E

C O N N E C T

F O R

L I F E

Selection Chart The power loss value declared are at rated current.
Type of MCB "C" series "C" series "C" series "C" series "C" series "B" series "B" series "B" series "B" series "B" series B series "C" series "C" series "B" series "B" series "B" series "B" series "B" series "B" series "B" series "B" series 63 80 100 125 13.0 Under Consideration Under Consideration Under Consideration 7.2 Under Consideration Under Consideration Under Consideration Rated Current Amp. 10A 16A 20A 3A 4A 32A 10A 6A 10A 6A 10A 2A 8A 6A 10A 16A 32A 6A 8A 8A 10A 1 2 4 6 8 10 13 16 20 Max. allowable Watt loss per pole as per IS : 8828-1996, IEC 898-95 3 3 3 3.0 3.0 3.0 3.5 3.5 4.5 4.5 6.0 7.5 9.0 Delton MCB Max. Watt Loss per pole 1.3 1.5 2.2 0.7 0.9 1.3 1.6 2.1 2.3 3.0 3.3 3.5 6.0

For Household Application


Appliance Capacity watt watt(Load) (230 VAC I ph) Air Conditioner 1.0 tonnes 1.5 tonnes 2.0 tonnes Refrigerator Oven cum Griller Oven Only Hot Plate Only Room Heater ` Washing Machine Washing Machine With heater Water Heater (Storage/instant) 1000W 2000W 3000W 6000W Electric iron Auto toaster (2 silces) Electric Kettle 1200W 1500W 750W 1250W 1300W 165 litres 350 litres 4500W 1750W 750W 2000W 1000W 2000W 300W Current Rating of MCB

25 32 40 50

Rating of MCBs for lighting ("B" Series)


Lamp (Watt) 20W 40W 8 12 2 10 12 60W 1 4 8 12 80W 1 2 5 8 12 100W 1 2 4
"B" seris MCB is used for all lighting Application

Rating of MCBs for Motor ("C Series)


Rating (A) 1 1.5 0.5 2 2.5 0.5 1.5 3 4 0.5 1 2 4 5 1 1.5 2.5 Motor HP 1.0 1.5 2.0 3.0 5.0 6.0 7.5 10.0 12.5 15.0 17.5 20.0 25.0 30.0 35.0 0.75 1.10 1.50 2.25 3.75 4.50 5.50 7.50 9.30 11.00 13.00 15.00 18.50 22.50 26.00 8A 10A 13A 16A 20A 25A 25A 32A 40A 50A 63A kW Star Delta MCB Ratings DOL 1.5A 2.5A 3.0A 5.0A 8.0A 10.0A 13.0A 16.0A 20.0A 25.0A 25.0A 32.0A 40.0A 50.0A 63.0A

Number of Lamps

Dimension

W E

C O N N E C T

F O R

L I F E

MCB & ISOLATOR 0.5 to 63 Amps

5.0

35.5 44.8

81.7

450 65.0

17.5

17.5 35

17.5 52.5

17.5 70

SP

SP-N/DP

TP

TP-N/FP

MCB & ISOLATOR 80 to 125 Amps

35.7

45.0 98.0

65.0

17.5

17.5 35

17.5 52.5

17.5 70

SP

SP-N/DP

TP

TP-N/FP

W E

C O N N E C T

F O R

L I F E

Product Range

LOAD

LOAD

NOIDA UP 0607

LINE

NOIDA UP 0607

Mfd. By

Mfd. By

LINE

415V~ 10000 3

63 A
415V~

1 2

5
O

C-40
415V~ 10000 3

ISOLATOR

1 3 5 7 2 4 6 8 FP

4 6 TP

LOAD

NOIDA UP 0607

LOAD

NOIDA UP 0607

LINE

NOIDA UP 0607

Mfd. By

C-40

LOAD

Mfd. By

Mfd. By

LOAD

NOIDA UP 0607

Mfd. By

LINE

LINE

C-40
O
415V~ 10000 3

1 2

C-40

5
O

415V~ 10000 3

1 3 5 7 2 4 6 8 FP

4 6 TP

63 A
415V~

ISOLATOR

LOAD

NOIDA UP 0607

LOAD

LINE

LOAD

NOIDA UP 0607

Mfd. By

63 A
415V~

LINE

ISOLATOR

1 3 5 7 2 4 6 8 FP

C-40
O
415V~ 10000 3