SWIMMING POOL

HEAT PUMP UNIT

Installation & Instruction Manual

Model T50HHDTBNA

R407C
rev 9/4/07

SWIMMING POOL HEAT PUMP

Contents
Performance Data Specifications
1. Performance data 2. Dimensions 3. The display 4. Wiring diagram

1 2 3 8 9

Service
1. How to Obtain Service

Attachments
1. The charts displayed for outdoor pools & indoor pools 2. The Installation With Chlorinator 3. Conversion Tables

10 13 14

SWIMMING POOL HEAT PUMP


Specifications
Performance Data of Swimming Pool Heat Pump Unit

Code
Rated heating capacity Input power heating Running current heating COP Power supply Number of compressors Compressor Number of fans Input power of fan Fan rotation speed Noise Water connection size Water flow Water pressure drop Refrigerant(R407C) L Net dimension W H Shipping dimension Weight L W H Net weight
Gross weight

TH50HHDTBNA
W BTU/h W A V/PH/HZ

11300 38500 2306 10.6 4.9 220V/1PH/50HZ 1 Rotary 1 200 830 60 1-1/2 4-7 15 2.3 660 660 850 780 820 1040 87 93

W RPM dB(A) inch m /h Kpa Kg mm


3

mm Kg

Measurement conditions: Outdoor air temp: 24C to 19C, inlet water temp: 27C, ambient temp range: 0~35C

1 3

SWIMMING POOL HEAT PUMP


Power wiring specs

Code Specs

TH50HHDTBNA
4mm
2

Power supply installation condition: Thus a breaker with more than 3mm touching point space.

The dimensions for Swimming Pool Heat Pump Unit- Monobloc

660

660

850

2 3

80

370

SWIMMING POOL HEAT PUMP


1)The functions of the wire controller
Stand by status The LCD display ambient temp. And current mode

Initialization
SET
TEMP

IN

NO.

ROOM OUT VALVE

ROOM

HUM

MIN

C F

MIN

TEMP

C F
ON OFF

FAN AUTO

1 2

AUX

AUX

Press to turn Press M button on and turn off to change modes the units.

Press Set to set operation parameter under stand by status, or check the operation parameter under running or stand by status.

Press AUX to start auxiliary electrical heating

2)How to set operation parameter : Standby status, press SET button to enter Operation Parameter setting interface; Press SET again to start setting (parameter from 00-1 (see the Operation Parameter Table page-5); Under parameter setting, parameter 00-01can be set by pressing or ; 02-10 must be set only after pressing and at the same time for 3s, get a sound of Beep to unlock. Data will be stored in 3s without any press on the controller. Parameter 02-10 must be adjusted by professional technicians. Please note no press in 5s, the LCD will display water-in/water out temp. (under running) or ambient temp. (Under standby status) Whilst running , you can press SET to check current parameter, but data of parameter can not be changed !

Remarks: Standby status means the unit is connected with electricity but not running . Parameter 00-10 can only be changed under standby status!

SET

NO.

SET

NO.

SET

NO.

MIN

Parameter 00 to set inlet water temp. under cooling mode (8-28 C) default setting:12 C

AUX

Parameter 01 to set inlet water temp under heating mode (15-40C) default setting: 40C

AUX

Parameter 02 Total working time of compressor after frosting

AUX

SWIMMING POOL HEAT PUMP

SET

NO.

SET

NO.

SET

NO.

MIN

C
Parameter 03 Setting initialization temp for defrosting " -7C ", (" - " not display, range(0- -30C)

C
Parameter 04 Terms of Exit Defrosting Function (2-30C) default setting:13C

5 3

AUX

AUX

Parameter 05 Max. Time of defrosting (1-12min) Default setting: 8min.

5 3

AUX

SET

NO.

SET

NO.

VALVE

SET

NO.

Parameter 06 System Quantity

Parameter 07 Save setting after power failure 1(yes) 0(No)

AUX

AUX

Parameter 08 Mode: 1 (cooling&heating) 2 auxiliary elec heating (cooling+heating) 3 (heating only)

AUX

SET

NO.

VALVE

SET

NO.

VALVE

" 0 " long time working for water pump " 1 " water pump turns off after the whole unit power off for 30s initialization " 0 ".

AUX

Auto mode default setting: temp 30 C

AUX

4 3

SWIMMING POOL HEAT PUMP


The unit's operation data can be set on the wire controller. Please set according to the table below:
Digit Meaning
Return water temp. Setting (cooling mode) Return water temp. Setting (heating mode) Total working time of compressor after frosting Setting initialization temp for defrosting Terms of exit defrost under heating model Time of exit defrost under heating model System quantity Automatic restarting

Range

Default 12C 27C 40MIN -7C 13C 8 MIN 2


0 (no recording)

Adjust(yes/no)

00 01 02 03 04 05 06 07 08 09 10

8-30C 15-40C 30-90MIN 0--30C 2-30C 1-12MIN 1-2 0-1 1-3 0-1 8-40C

No Yes Yes Yes Yes Yes No Yes No No No

Model (cooling only/heat pump/ auxiliary electrical heating/hot water)


Working mode of water pump Auto mode (return water temp )

3 (hot water)

0 30C

3)How to know the cur rent status?


Water temp. of inlet/outlet
Ambient temp.
Condenser 1 temp.

IN

OUT

ROOM

TEMP

TEMP

AUX

AUX

AUX

Condenser 2 temp.

Under running status , press and to check the current status of the unit! You can check water-in/water out temp, condenser temp and ambient temp, please note no motion on the display for 5s, the LCD will display water-in/water out temp/(under running) or ambient temp. (unit stops)

15

AUX

5 3

SWIMMING POOL HEAT PUMP


4)Controller lock.
Stand by status
Running status

ROOM

IN
TEMP

OUT

TEMP

AUX

AUX

Under running or standby status press and at the same time for 5s, controller will be locked, display as above. Press and again for 5s for unlocking.

5)Troubleshooting
Malfunction
Water in temp. Sensor failure Water out temp. Sensor failure Coil1 sensor failure
Coil 2 sensor failure (proprietary for A type)

Wire Controller
PP 01

Reason
The sensor is open or short circuit The sensor is open or short circuit The sensor is open or short circuit The sensor is open or short circuit The sensor is open or short circuit Insufficient water flow or water pressure difference is too little Insufficient water flow Too low Too low The system1 protection was failure The system2 protection was failure No water/little water in water system. Wrong connections or lack of connection Water flow volume not enough, water pressure difference is too low

Resolution
Check or change the sensor

PP 02

Check or change the sensor

PP 03 PP 04 PP 05

Check or change the sensor Check or change the sensor Check or change the sensor

Ambient sensor failure Temp. differential is too large between water-in and water-out Defrosting under cooling mode The first time freezing protection in winter The second time freezing protection in winter Malfunction of system1 Malfunction of system2 (cut off under low voltage) Flow switch failure Power supply connections wrong (for 3phase unit) Hi/Low pressure protection (for single phase unit) 3 times water-in and water-out temp. difference protection in 30 minutes Defrosting Communication failure

PP 06 PP 07 PP 08 PP 09

Check the water flow volume, or clogged plumbing system Check the water flow volume, or clogged plumbing system

EE 01

Check each protection point of system1 remove the malfunction according to System Protection Board malfunction table. Check each protection point of system2 remove the malfunction according to System Protection Board malfunction table. Check the water flow volume, or clogged plumbing system

EE 02 EE 03

EE 04

Check connections of power cable

EE 05 Defrost code display EE 08

Check the water flow volume, or clogged plumbing system

Wire controller and The PCB connection failure

Check the wire connection

6 3

SWIMMING POOL HEAT PUMP


Connection of PCB illustration

FAN

COMP1

HI FAN
MDOUT

COMP2

PUMP

Chiller 300
WATER KYOUT FROST MDIN KYIN GND GND GND GND GND GND NET SYS 12V 12V
ROOMT PIPE2 PIPE1 OUTWT INWT

Connections explanation:
No.
Symbol
HI FAN PUMP FAN VAL2 VAL1 COMP2 COMP1 AC-L AC-N KYOUT GND MDOUT GND NET GND 12V KYIN MDIN
WATER GND FROST GND SYS GND 12V

VAL2

AC-N

AC-N

AC-L

AC-N

VAL1

Meaning
High speed for fan Water pump (220VAC) Fan motor (220VAC) 4way valve of system2 (220VAC) (no use) 4way valve of system1 (220VAC) Compressor of system2 (220VAC) (no use) Compressor of system1 (220VAC) Live wire

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

Neutral wire On/Off switch (output) (no use) Mode output (no use) Wire controller On/Off Switch (input) (no use) Model (input) (no use) Flow switch (input) ( normal close) Defrost signa l(no use) System protection (input) (normal close) Ambient temp. (input) Temp of fan coil2 ( input) (no use)
Temp of fan coil 1 (input) (no use for split type )

ROOMT PIPE2 PIPE1 OUTWT INTWT

Water out temp (input) Water in temp. (input)

3 7

SWIMMING POOL HEAT PUMP

Electric diagram:

SWIMMING POOL HEAT PUMP WIRING DIAGRAM


FM
N
N

K2 Y/G

DEFROSTING VALVE
BLU BLU

CM C RED BLK C1 S R BLU

RK1

COMP

BLU RED BLU

PUMP

COMP1

HI LOW AC-N

VAL1

AC-N

AC-L

K1
RED

Chiller 300
WATER
N

MDIN

KYIN

GND

GND

GND

SYS

GND

NET

12V

RED BLU Y/G

INWT OUTWT PIPE1 PIPE2

ROOMT

BRN

BLU

Y/G

RED RED Switch for remote control RED RED RED IN

t`

t`

t`

t`

OUT

EXT.

Switch for stream

8 3

LP

Wire Controller

SW1

HP 1

TO POWER SUPPLY

SWIMMING POOL HEAT PUMP


Service
1. How to Obtain Service
For Pool Owner
If you are having a problem with the heater, FIRST perform the consumer troubleshooting steps detailed in Owners Manual then CALL THE INSTALLING DEALER and have them verify that the cause is NOT external (such as tripped breaker, clogged pool filter, inadequate pump run time, etc.) Provide your Dealer with the following information: 1. Serial # located on back panel nameplate . 2. Proof of Installation Date . 3. Description of the Symptoms

For Installing Dealer


If your customer is having a problem with the unit and you as the installing dealer have verified that the cause is NOT external (such as tripped breaker, clogged pool filter, inadequate pump run time, etc.) following these steps will help you obtain the fastest service possible for your customer. Help your customer gather the following information: 1. Serial # located on back panel nameplate . 2. Proof of Installation Date .

Will I Ever Need Freon


Unless your heat pump has a leak in the sealed refrigeration system, the factory charge of freon should last for the life of the unit. Freon is very stable and should not degrade or breakdown even under severe operating conditions. If your unit needs freon, then it has a leak, and adding freon will not solve the problem. The leak must be located and repaired. A licensed HVAC contractor can handle this repair.

9 3

SWIMMING POOL HEAT PUMP


Attachment 1
SWIMMING POOL HEATING SYSTEM EVALUATION 1. The charts displayed for an outdoor pool
Energy flows in a heated pool Energy flows in an unheated pool Pool temperature Range of pool temperature(max exceeded for 5% of the time and min. temperature exceed fo 95% of the time.

Jul

Aug

Sep

Oct

Nov

Dec

Jan

Feb

Mar

Apr

May

Jun

Jul

Aug

Sep

Oct

Nov

Dec

Jan

Feb

Mar

Apr

May

Jun

10 3

SWIMMING POOL HEAT PUMP


2. The charts displayed for an indoor pool
Energy flows for indoor pool. Pool temperature during daytime operating period. Air temperature during daytime operating period. Air humidity during daytime operating period. Pool temperature at night. Air temperature at night. Air humidity at night. Some of the charts are:

Jul

Aug

Sep

Oct

Nov
Outside

Dec

Jan

Feb

Mar

Apr

Jul

Aug

Sep

Oct

Nov

Dec

Jan

Feb

Mar

Apr

3 11

SWIMMING POOL HEAT PUMP

Relative

Jul

Aug

Sep

Oct

Nov

Dec

Jan

Feb

Mar

Apr

May

Jun

The position of installing unit Required clearances:

Top 190 cm above

Outlet

Inlet

Inlet

Heat pump
Side 600 mm Side 600 mm

12 3

SWIMMING POOL HEAT PUMP


Attachment 2
The Installation about Heat Pump & Chlorinator
In-line Chlorinator or Brominator

Filter Heat Pump Water Pump

Check-valve Chlorinator Pool/Spa


Water flow switch installation

HEAT MDOUT KYOUT GND

TITANIUM EXCHANGER

PUMP GND NET

VAL2

VAL1

WATER FLOW SWITCH (inside)

FAN 12V

Chiller 300
WATER FROST MDIN KYIN GND GND GND GND SYS 12V
ROOMT PIPE2 PIPE1 OUTWT INWT

COMP2

COMP1

AC-N

AC-N

AC-N

AC-L

A SERIES

Please start up the water switch (outside), if the inside one (in the machine) is not open since the water flow is not enough.
WATER FLOW SWITCH (outside)

WATER PUMP
WATER FLOW

13 3

SWIMMING POOL HEAT PUMP


Attachment 3 Common Units Conversion
Linear Measure
1 inch =25.4 millimetres 1 foot =12 inches =0.3048 metre 1 yard =3 feet =0.9144 metre 1 (statute) mile =1760 yards =1.609 kilometres 1 nautical mile =1852 m.

Square Measure
1 square inch =6.45 sq.centimetres 1 square foot =144 sq.in.=9.29 sq.decimetres 1 square yard =9 sq.ft. =0.836 sq.metre 1 acre =4840 sq.yd.=0.405 hectare 1 square mile =640 acres =259 hectares

Cubic Measure
1 cubic inch =16.4 cu.centimetres 1 cubic foot =1728 cu.in. =0.0283 cu.metre 1 cubic yard =27 cu.ft. =0.765 cu.metre

Capacity Measure
British 1 pint 20 fluid oz. =34.68 cu.in. =0.568 litre 1 quart =2 pints =1.136 litres 1 gallon =4 quarts =4.546 litres 1 peck =2 gallons =9.092 litres 1 bushel =4 pecks=36.4 litres 1 quarter =8 bushels =2.91 hectolitres American dry 1 pint =33.60 cu.in. =0.550 litre 1 quart =2 pints =1.101 litres 1 peck =8 quarts =8.81 litres 1 bushel =4 pecks =35.3 litres American liquid 1 pint =16 fluid oz. =28.88 cu.in. =0.473 litre 1 quart =2 pints =0.946 litre 1 gallon =4 quarts =3.785 litres

Avoirdupois Weight
1 grain =0.065 gram 1 dram =1.772 grams 1 ounce =16 drams =28.35 grams 1 pound =16 ounces =7000 grains =0.4536 kilogram 1 stone =14 pounds =6.35 kilograms 1 quarter =2 stones =12.70 kilograms 1 hundredweight =4 quarters =50.80 kilograms 1 short ton =2000 pounds =0.907 tonne 1 (long) ton =20 hundredweight =1.016 tonnes

Energy power
1 usrt =3024 kcal/h=3516 w 1 kcal/h =1.163 w 1 kw =860 kcal/h 1 btu/h =0.293 w

Velocity, flux
1 m/s =196.85 fpm 1 cfm = 1.699cmh 1 gpm =0.27276 cmh 1 gpm =0.2271 cmh

Pressure
1 bar =100000 pa 1 psi =0.0703 kgf/cm2 1 kgf/cm2 =98000 pa 1 mm aq. =9.8 pa 1 mm hg =133.28 pa 1 m H2O =9800 pa =0.1 kgf/cm2

14 3