Power Switching status Channel 1 Output mode Wire-break monitoring Short-circuit monitoring Channel 2

10 11 12 7 8 9 Pwr 1
NO 1 off off NO 2 off off

Isolating Switching Amplifier IM1-22Ex-R 2-channel

2
NC WB SC NC WB SC

Zone 2: Do not disconnect when live!

IM1-22Ex-R 4 1 5 2 6 3

2-channel isolating switching amplifier with removable terminal blocks Intrinsically safe input circuits EEx ia Area of application according to ATEX: II (1) GD, II 3 G Approved for installation in zone 2, however the device must be installed in a housing which complies with the requirements of EN 6007915 with a minimum protection degree of IP54 Functional safety up to SIL 2 (acc. to EN 61508) Galvanic isolation between input circuits, output circuits and supply voltage Input circuit monitoring for wire-break and short-circuit (can be disabled) 2 relay outputs, each with one NO contact Selectable NO/NC output function Universal supply voltage (20...250 VAC/20...125 VDC)

The isolating switching amplifier type IM122Ex-R is a dual channel device featuring intrinsically safe input circuits. It can be connected to sensors according to EN 60947-5-6 (NAMUR), variable resistors or potential-free contacts. The output circuits feature one relay with one NO contact each. Six front panel programming switches select the output function of each channel (normally open mode = NO/or normally closed mode = NC) and enable separate activation and de-activation of wire-break (WB) and short-circuit (SC) monitoring of each channel.

When using mechanical contacts as the input device, wire-break and short-circuit monitoring must be disabled or shunt resistors must be connected to the contacts (II). (See next page for contact configuration). The green LED on the front cover indicates that the device is powered. The two dual colour LEDs indicate the switching status (yellow) as well as fault conditions (red). When the input circuit monitoring feature is activated, red illuminates to indicate a fault in the input circuit and the respective output relay is de-energised.

II 4 1 1

I BU 4 BN NAMUR +1 +8,2 V 2 YE/RD 1 YE/RD

7 1 10 250 VAC/ 30 VDC 2A 8 500 VA/60 W 2 9 11 Pwr


GN

5 2 2 NAMUR

BU 5 BN +2

12

Power

Hans Turck GmbH & Co.KG D45466 Mlheim/Ruhr Tel. 0208/4952-0 Fax 0208/4952-264 E-Mail: more@turck.com www.turck.com

1 21 /0407

Isolating switching amplifier IM1-22Ex-R

Type Ident-no. Supply voltage U B Line frequency (AC) Power/current consumption Galvanic isolation

IM1-22Ex-R 7541231 20...250 VAC/20...125 VDC 40...70 Hz 3W between input circuit, output circuits and supply voltage for 250 Vrms test voltage 2.5 kVrms according to EN 60947-5-6 (NAMUR), intrinsically safe according to EN 50020 8,2 V 8,2 mA 1.55 mA typ. 0.2 mA 0.1 mA 6 mA

Input circuits Operating characteristics Voltage Current Switching threshold Hysteresis Wire-break threshold Short-circuit threshold Contact configuration Of mechanical switches with active input circuit monitoring function

1...2,2 kW 10...22 kW

resistor module WM1, ident-no. 0912101

Output circuits Switching voltage Switching current per output Switching capacity per output Switching frequency Contact material Ex-Approval acc. to certificate of conformity Maximum nominal values No load voltage U0 Short-circuit current I0 Power P0 Maximum external inductances/capacitances [EEx ia] IIC [EEx ia] IIB Ex nL IIC Ex nL IIB Marking of devices

2 relay outputs with 1 NO contact each 250 VAC/120 VDC 2A 500 VA/60 W 10 Hz silver-alloy + 3 m Au TV 04 ATEX 2553 / TV 06 ATEX 552968 X 9.6 V 11 mA 26 mW 1 2 1 1 mH/1.1 F / 5 mH/0.83 F / 10 mH/0.74 F mH/5,2 F / 10 mH/3,8 F / 20 mH/3,4 F mH/1,9 F / 5 mH/1,4 F / 10 mH/1,2 F mH/11 F / 5 mH/7,5 F / 10 mH/6,6 F II (1) GD [EEx ia] IIC II 3 G Ex nA nC [nL] IIC/IIB T4

LED indications Power Switching status/Fault indication Terminal housing Mounting Connection Connection profile Degree of protection (IEC 60529/EN 60529) Operating temperature

green 2 x yellow/red (dual colour LED) 12-pole, 18 mm wide, Polycarbonate/ABS, flammability class V-0 per UL 94 snap-on clamps for top-hat rail (DIN 50022) or screw terminals for panel mounting removeable terminal blocks, reverse-polarity protected, screw connection, self-lifting 1 x 2.5 mm2, 2 x 1.5 mm2 or 2 x 1.0 mm2 with wire sleeves IP20 -25+70 C

104 89