Maintenance

Node Construction
A30828-X1160-M-2-7620

Construction

Maintenance Node

Important Notice on Product Safety


Elevated voltages are inevitably present at specific points in this electrical equipment. Some of the parts may also have elevated operating temperatures. Non-observance of these conditions and the safety instructions can result in personal injury or in property damage. Therefore, only trained and qualified personnel may install and maintain the system. The system complies with the standard EN 60950 / IEC 60950. All equipment connected has to comply with the applicable safety standards.

The same text in German: Wichtiger Hinweis zur Produktsicherheit In elektrischen Anlagen stehen zwangslufig bestimmte Teile der Gerte unter Spannung. Einige Teile knnen auch eine hohe Betriebstemperatur aufweisen. Eine Nichtbeachtung dieser Situation und der Warnungshinweise kann zu Krperverletzungen und Sachschden fhren. Deshalb wird vorausgesetzt, dass nur geschultes und qualifiziertes Personal die Anlagen installiert und wartet. Das System entspricht den Anforderungen der EN 60950 / IEC 60950. Angeschlossene Gerte mssen die zutreffenden Sicherheitsbestimmungen erfllen.

Trademarks: All designations used in this document can be trademarks, the use of which by third parties for their own purposes could violate the rights of their owners.

Copyright (C) Siemens AG 2002.


Issued by the Information and Communication Networks Group Hofmannstrae 51 D-81359 Mnchen Technical modifications possible. Technical specifications and features are binding only insofar as they are specifically and expressly agreed upon in a written contract.

A30828-X1160-M-2-7620

Maintenance Node

Construction

Reason for Update


Summary: New Hardware F:LTGP(B) UI-LTGP, M:DEC480 Details: Chapter/Section 2.61...91 3.4.1 4.6.17 Reason for Update F:LTGP and F:STMI in R:LTGN F:LTGP(B) for UI-LTGP M:DEC480

Issue History
Issue Number 1 Date of issue Reason for Update

08/2002

A30828-X1160-M-2-7620

Construction

Maintenance Node

A30828-X1160-M-2-7620

Maintenance Node

Construction

This document consists of a total of 775 pages. All pages are issue 2.

Contents
1 2 2.1 2.2 2.3 2.4 2.5 2.5.1 2.5.2 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.18 2.19 2.20 2.21 2.22 2.23 2.24 2.25 2.26 2.27 2.28 2.29 2.30 2.31 2.32 2.33 2.34 2.35 2.36 2.37 2.38 2.39 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:CE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:CCNP/SILTD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:CP113A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:CP113B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:CP113C. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CP113C with F:PIOP(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CP113C with F:PIOP(B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:CP113E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DEVB. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DEVD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUA Configuration ABAB or C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUA Configuration ABBB or C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration DEDE or F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration GEGE or F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration DEGE or F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration GEDE or F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration DDDD / DDD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration GGGG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration DDD, GGG, DGG, DDG, GDD, GGD . . . . . . . . . . . R:DLUB Configuration GEIJ or L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration GJIJ / GJI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration DEIJ or L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration IJDE or F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration IJGE or F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration IJGJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration DDD(F) with FAN . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration DED(F) with FAN . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration DEG(F) with FAN . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration DEI(L) with FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration GED(F) with FAN . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration GEG(F) with FAN . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration IJD(F) with FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB Configuration GEG with FMX2S/SNUS/SMA1K . . . . . . . . . . . . . . R:DLUB Configuration GGF with FMX2S/SNUS/SMA1K . . . . . . . . . . . . . . R:DLUB Configuration GGG with FMX2S/SNUS/SMA1K . . . . . . . . . . . . . R:DLUG Configuration ABAB or C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:DLUA for DSU Configuration ABAB or C . . . . . . . . . . . . . . . . . . . . . . . . R:DLUA for DSU Configuration ABBB or C . . . . . . . . . . . . . . . . . . . . . . . . R:DLUA for DSU Configuration ABB-Modem . . . . . . . . . . . . . . . . . . . . . . . R:DLUB for DSU Configuration GEGE or F . . . . . . . . . . . . . . . . . . . . . . . . R:DLUB for DSU Configuration GE-Modem . . . . . . . . . . . . . . . . . . . . . . . . 19 22 25 26 27 28 28 30 32 34 38 39 41 42 44 46 48 50 52 53 55 57 59 61 63 65 67 68 70 72 74 76 78 80 81 83 85 87 89 90 92 94

A30828-X1160-M-2-7620

Construction

Maintenance Node

2.40 2.41 2.42 2.43 2.44 2.45 2.46 2.47 2.48 2.49 2.50 2.51 2.52 2.53 2.54 2.55 2.56 2.57 2.58 2.59 2.60 2.61 2.62 2.63 2.64 2.65 2.66 2.67 2.68 2.69 2.70 2.71 2.72 2.73 2.74 2.75 2.76 2.77 2.78 2.79 2.80 2.81 2.82 2.83 2.84 2.85 2.86

R:DSU/LTG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 R:DSM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 R:HTI/RTI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 R:HTI/RTI with SDHI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 R:HTI/RTI with one F:LTGN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 R:HTI/RTI with SDHI and one F:LTGN . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 R:HTI/RTI with two F:LTGN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 R:HTI/RTI with SDHI and two F:LTGN. . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 R:HTI/RTI with three F:LTGN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 R:HTI/RTI with SDHI and three F:LTGN . . . . . . . . . . . . . . . . . . . . . . . . . . 105 R:LTGB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 R:LTGC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 R:LTGC/CR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 R:LTGD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 R:LTGF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 R:LTGG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 R:LTGG with LTGH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 R:LTGM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114 R:LTGM with DLUV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 R:LTGM with LTGG and DLUV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 R:LTGM with LTGG and LTGH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119 R:LTGN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 R:LTGN with LTGG or LTGH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122 R:LTGN with F:SDHI and FAN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 R:LTGN with F:SDHI without FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124 R:LTGN with DLUV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 R:LTGN with DLUV and LTGG or LTGH . . . . . . . . . . . . . . . . . . . . . . . . . . 127 R:LTGN with TSG, cabling from above . . . . . . . . . . . . . . . . . . . . . . . . . . . 128 R:LTGN with TSG, cabling from below . . . . . . . . . . . . . . . . . . . . . . . . . . . 129 R:LTGN with TSG and MB/CCG, cabling from above . . . . . . . . . . . . . . . . 130 R:LTGN with TSG and MB/CCG, cabling from below . . . . . . . . . . . . . . . . 131 R:LTGN with SSG, cabling from above . . . . . . . . . . . . . . . . . . . . . . . . . . . 132 R:LTGN with SSG, cabling from below . . . . . . . . . . . . . . . . . . . . . . . . . . . 133 R:LTGN with SSG and MB/CCG, cabling from above . . . . . . . . . . . . . . . . 134 R:LTGN with SSG and MB/CCG, cabling from below . . . . . . . . . . . . . . . . 135 R:LTGN with MBD and CCGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136 R:LTGN with MBD and SSG, cabling from above . . . . . . . . . . . . . . . . . . . 137 R:LTGN with MBD and SSG, cabling from below . . . . . . . . . . . . . . . . . . . 139 R:LTGN with MBD and TSG, cabling from above . . . . . . . . . . . . . . . . . . . 140 R:LTGN with MBD and TSG, cabling from below . . . . . . . . . . . . . . . . . . . 141 R:LTGN with MBD and SNMUX, cabling from above . . . . . . . . . . . . . . . . 142 R:LTGN with MBD and SNMUX, cabling from below. . . . . . . . . . . . . . . . . 144 R:LTGN with MBD and SNCARE, cabling from above . . . . . . . . . . . . . . . 145 R:LTGN with MBD and SNCARE, cabling from below. . . . . . . . . . . . . . . . 146 R:LTGN with SNMUX, without FAN, cabling from above. . . . . . . . . . . . . . 147 R:LTGN with SNMUX, without FAN, cabling from below . . . . . . . . . . . . . . 148 R:LTGN with SNMUX and FAN, cabling from above . . . . . . . . . . . . . . . . . 149

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.87 2.88 2.89 2.90 2.91 2.92 2.93 2.94 2.95 2.96 2.97 2.98 2.99 2.100 2.101 2.102 2.103 2.103.1 2.103.2 2.103.3 2.103.4 2.104 2.105 2.105.1 2.105.2 2.105.3 2.105.4 2.106 2.106.1 2.106.2 2.106.3 2.106.4 2.107 2.108 2.109 2.110 2.111 2.112 2.113 2.114 2.115 2.116 2.117 2.118 2.119 2.120 2.121

R:LTGN with SNMUX and FAN, cabling from below . . . . . . . . . . . . . . . . R:LTGN with SNCARE, cabling from above . . . . . . . . . . . . . . . . . . . . . . . R:LTGN with SNCARE, cabling from below . . . . . . . . . . . . . . . . . . . . . . . R:LTGN with 4 SNMUX and FAN, cabling from above . . . . . . . . . . . . . . . R:LTGN with 4 SNMUX and FAN, cabling from below . . . . . . . . . . . . . . . R:STMI/LTG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:STMI/LTG with DLUV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:STMI/LTG with SNMUX(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:STMI/LTG with SNMUX(A) and DLUV . . . . . . . . . . . . . . . . . . . . . . . . . R:STMI/LTG with SNMUX(B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:STMI/LTG with SNMUX(B) and DLUV . . . . . . . . . . . . . . . . . . . . . . . . . R:STMI/LTG with TSG(B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:STMI/LTG with TSG(B) and DLUV . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:MB/CCG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:MB/CCG with FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:MBD/CCGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SE (-C2539-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SE (-C2539-X100). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SE (-C2539-X100) with Profibus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SE (-C2539-X600). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SILTD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SSNC (basic rack). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SSNC (basic rack minimal configuration) . . . . . . . . . . . . . . . . . . . . . . . R:SSNC (basic rack maximal configuration with 1 SCE and ASN(E)) . . . R:SSNC (basic rack with 1 SCE and ASN(H)) . . . . . . . . . . . . . . . . . . . . . R:SSNC (basic rack with 2 SCE and ASN(H)) . . . . . . . . . . . . . . . . . . . . . R:SSNC (extension rack) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SSNC (extension rack with 1 SCE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SSNC (extension rack with 2 SCE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SSNC (extension rack with 3 SCE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SSNC (extension rack with 4 SCE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SN (with DCCXI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SN (with DCCCS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SN(B) / SNMUX / LTGG (cabling from above) . . . . . . . . . . . . . . . . . . . R:SN(B) / SNMUX / LTGG (cabling from below) . . . . . . . . . . . . . . . . . . . R:SN(B) / SNCARE / LTGG (cabling from above) . . . . . . . . . . . . . . . . . . R:SN(B) / SNCARE / LTGG (cabling from below) . . . . . . . . . . . . . . . . . . R:SN(B)/LTGM (cabling from above) . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SN(B)/LTGM (cabling from below) . . . . . . . . . . . . . . . . . . . . . . . . . . . . R:SN(B)/LTGM/SNCARE (cabling from above) . . . . . . . . . . . . . . . . . . . . R:SN(B)/LTGM/SNCARE (cabling from below) . . . . . . . . . . . . . . . . . . . . R:SN(B)/LTGM/SNMUX (cabling from above) . . . . . . . . . . . . . . . . . . . . . R:SN(B)/LTGM/SNMUX (cabling from below) . . . . . . . . . . . . . . . . . . . . . R:SN(B)/MB/LTGM (cabling from above) . . . . . . . . . . . . . . . . . . . . . . . . . R:SN(B)/MB/LTGM (cabling from below) . . . . . . . . . . . . . . . . . . . . . . . . . R:SND/MBD/LTGM (with SNCARE, cabling from above). . . . . . . . . . . . .

150 151 152 153 154 155 157 159 161 163 164 166 168 170 171 172 173 173 174 176 177 178 180 180 181 182 183 185 185 186 187 188 189 190 191 192 193 194 195 197 199 201 203 205 207 209 211

A30828-X1160-M-2-7620

Construction

Maintenance Node

2.122 2.123 2.124 2.125 2.126 2.127 2.128 2.129 2.130 2.131 2.132 2.133 2.134 2.135 2.136 2.137 3 3.1 3.1.1 3.1.2 3.2 3.2.1 3.2.2 3.2.3 3.2.4 3.2.5 3.2.6 3.2.7 3.2.8 3.2.9 3.2.10 3.2.11 3.2.12 3.2.13 3.2.14 3.2.15 3.3 3.3.1 3.3.2 3.3.3 3.3.4 3.3.5 3.3.6 3.3.7 3.3.8 3.3.9 3.3.10

R:SND/MBD/LTGM (with SNCARE, cabling from below) . . . . . . . . . . . . . 213 R:SND/MBD/LTGM (with SNMUX, cabling from above) . . . . . . . . . . . . . . 215 R:SND/MBD/LTGM (with SNMUX, cabling from below) . . . . . . . . . . . . . . 217 R:SND/SNMAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219 R:SSG(B)/LTGG (cabling from above). . . . . . . . . . . . . . . . . . . . . . . . . . . . 220 R:SSG(B)/LTGG (cabling from below) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221 R:SSG(B)/LTGM (cabling from above) . . . . . . . . . . . . . . . . . . . . . . . . . . . 222 R:SSG(B)/LTGM (cabling from below). . . . . . . . . . . . . . . . . . . . . . . . . . . . 224 R:SSG(B)/MB/LTGM (cabling from above) . . . . . . . . . . . . . . . . . . . . . . . . 225 R:SSG(B)/MB/LTGM (cabling from below) . . . . . . . . . . . . . . . . . . . . . . . . 227 R:TSG(B)/LTGG (cabling from above). . . . . . . . . . . . . . . . . . . . . . . . . . . . 228 R:TSG(B)/LTGG (cabling from below) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230 R:TSG(B)/LTGM (cabling from above). . . . . . . . . . . . . . . . . . . . . . . . . . . . 231 R:TSG(B)/LTGM (cabling from below) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233 R:TSG(B)/MB/LTGM (cabling from above) . . . . . . . . . . . . . . . . . . . . . . . . 235 R:TSG(B)/MB/LTGM (cabling from below). . . . . . . . . . . . . . . . . . . . . . . . . 237 Module Frames . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239 F:CCS7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240 F:CCNP(B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240 F:SILTD(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242 F:CP113 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244 F:BIOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246 F:BPCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254 F:CMY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259 F:DEV(E) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262 F:DEV(F) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263 F:EIOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 264 F:EPCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274 F:IOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276 F:MI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281 F:PBC(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283 F:PI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287 F:PIOP(A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289 F:PIOP(B). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292 F:P/IOC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302 Profibus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 304 F:DLU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305 F:DLU(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307 F:DLU(B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310 F:DLU(C) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313 F:DLU(D) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315 F:DLU(E) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 318 F:DLU(F) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321 F:DLU(G) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323 F:DLU(I) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326 F:DLU(J). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 328 F:DLU(L) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.3.11 3.3.12 3.3.13 3.3.14 3.3.15 3.3.16 3.3.17 3.3.18 3.3.19 3.3.20 3.3.21 3.4 3.4.1 3.4.2 3.4.3 3.4.4 3.4.5 3.4.6 3.4.7 3.4.8 3.4.9 3.4.10 3.4.11 3.5 3.5.1 3.5.2 3.5.3 3.6 3.6.1 3.6.2 3.6.3 3.6.4 3.6.5 3.6.6 3.6.7 3.6.8 3.6.9 3.6.10 3.7 3.7.1 3.7.2 3.7.3 3.7.4 3.8 3.8.1 3.8.2 3.8.3

F:DLUG(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:DLUG(B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:DLUG(C) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:DLUV(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:DLU(A) for DSU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:DLU(B) for DSU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:DLU(C) for DSU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:DLU(E) for DSU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:DLU(F) for DSU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:DLU(G) for DSU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:MODEM(D) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:LTG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:LTGP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:LTGN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:LTGM(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:LTGG(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:LTGH(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:LTGF(A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:LTGB(A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:LTGC(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:CR(A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:LTGD(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:CRES(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:MB/CCG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:MB/CCG(B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:MBD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:CCGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:RSU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:RSU (basic frame) (module side) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:RSU (basic frame) (backplane) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:RSU (basic frame) (cabling) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:RSU (extension frame) (module side) . . . . . . . . . . . . . . . . . . . . . . . . . . F:RSU (extension frame 0) (backplane) . . . . . . . . . . . . . . . . . . . . . . . . . . F:RSU (extension frame 0) (cabling) . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:RSU (extension frame 1) (backplane) . . . . . . . . . . . . . . . . . . . . . . . . . . F:RSU (extension frame 1) (cabling) . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:RSU (extension frame 2) (backplane) . . . . . . . . . . . . . . . . . . . . . . . . . . F:RSU (extension frame 2) (cabling) . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:SDHI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:SDHI4 (module side) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:SDHI2 (module side) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:SDHI (backplane) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:SDHI (cabling) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:SMSC(C) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:SMSC(C)-0 (module side) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:SMSC(C)-1 (module side) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F:SMSC(C)-0 (backplane) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

332 336 338 340 341 344 347 349 352 354 356 357 359 372 381 385 395 396 401 408 410 411 413 415 415 429 445 451 451 452 452 454 454 455 456 456 457 457 459 459 459 460 460 462 462 462 463

A30828-X1160-M-2-7620

Construction

Maintenance Node

3.8.4 3.8.5 3.9 3.9.1 3.9.2 3.9.3 3.9.4 3.9.5 3.9.6 3.9.7 3.9.8 3.9.9 3.9.10 3.10 3.10.1 3.10.2 3.10.3 3.10.4 3.11 3.11.1 3.11.2 3.11.3 3.11.4 3.11.5 3.12 3.12.1 3.12.2 3.12.3 3.13 3.13.1 3.13.2 3.13.3 3.13.4 3.13.5 3.13.6 4 4.1 4.1.1 4.1.2 4.1.3 4.1.4 4.1.5 4.1.6 4.1.7 4.2 4.2.1 4.2.2

F:SMSC(C)-1 (backplane) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 463 F:SMSC(C) (cabling) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 464 F:SN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 469 F:SN(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 470 F:SSG(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 472 F:TSG(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 479 F:DCC(B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 482 F:TSG(B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 482 F:SSG(B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 487 F:SNMAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 493 F:SNMUX(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 497 F:SNMUX(B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 503 F:SNCARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 508 F:SSNC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 512 F:SCB. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 512 F:SCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 517 F:ASN(E) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 524 F:ASN(H) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 529 F:STMI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 533 F:STMI (module side). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 533 LTU-Types for LTG in B operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 534 LTU-Types for LTG in C operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 535 F:STMI (backplane) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 536 F:STMI (cabling). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 536 F:SYPC(A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 539 F:SYPC(A) (module side). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 539 F:SYPC(A) (backplane) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 539 F:SYPC(A) (cabling) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 540 Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 542 FAN (B5681) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 542 FAN-BOX (B5877) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543 FAN-BOX (U102) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 544 FANTRAY (U103) (U2620) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 545 FAN (U2623) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 546 FAN-BOX (U2624) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 547 Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 548 CCG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 549 CCGES (-Q146-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 550 CCGED (-Q147-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 551 CCGB (-Q887-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 552 CCGXXA (-Q888-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 553 CDEX (-Q900-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 559 CDEX (-Q900-X100-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 561 CDEX (-Q900-X200-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 562 CCS7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 563 MH:SIMP (-Q1017-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 563 MUXMA (-Q1117-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 563

10

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.2.3 4.2.4 4.2.5 4.2.6 4.2.7 4.3 4.3.1 4.3.2 4.3.3 4.3.4 4.3.5 4.3.6 4.3.7 4.3.8 4.3.9 4.3.10 4.3.11 4.3.12 4.3.13 4.3.14 4.3.15 4.3.16 4.3.17 4.3.18 4.3.19 4.3.20 4.3.21 4.3.22 4.3.23 4.3.24 4.4 4.4.1 4.4.2 4.4.3 4.4.4 4.4.5 4.4.6 4.4.7 4.4.8 4.4.9 4.4.10 4.4.11 4.4.12 4.4.13 4.4.14 4.4.15 4.4.16

PMU:CPI (-Q1180-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PMU:SIMP (-Q1179-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SILTC (-Q766-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SILTD (-Q1023-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SIPA (-Q1016-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CP113 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AMPC (-Q1388-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BCM (-Q1252-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BCTI (-Q946-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CMYE (-Q244-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CMY2C (-Q963-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CMYC (-Q1255-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CMYM (-Q1256-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPCL (-Q933-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPEX (-Q930-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IF:MDD (-Q976-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IK:DTD (-Q975-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IOP:AUC (-Q1169-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IOP:MB (-Q954-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IOP:SCDV (-Q952-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IOP:TA (-Q956-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IOP:UNI (-Q1257-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LCUB (-Q1114-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LAUB (-Q1115-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PEX (-Q1251-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PEXE (-Q242-) (-Q243-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PIA (-Q1253-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PIDAT (-Q940-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MUH (-Q1088-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MTI (-Q1254-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCCCA (-Q5619-A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCCCB (-Q5619-B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCCCC (-Q5619-C) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCCCK (-Q5619-K) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCCCL (-Q5619-L) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCCCR (-Q5619-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCCCS (-Q5619-S) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCCCV (-Q5619-V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCCDC (-Q5862-C) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCCDD (-Q5862-D) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCCDE (-Q5862-E) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCCDF (-Q5862-F). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCCDK (-Q6104-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCCDM (-Q6111-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCCDQ (-Q6125-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCCDR (-Q6129-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

564 564 565 566 568 569 570 571 572 572 573 573 574 575 575 576 576 576 577 578 582 582 583 583 584 585 586 587 588 589 590 591 592 592 593 593 594 594 595 595 596 596 596 596 597 597 597

A30828-X1160-M-2-7620

11

Construction

Maintenance Node

4.4.17 4.4.18 4.4.19 4.4.20 4.4.21 4.4.22 4.4.23 4.4.24 4.5 4.5.1 4.5.2 4.5.3 4.5.4 4.5.5 4.5.6 4.5.7 4.5.8 4.5.9 4.5.10 4.5.11 4.5.12 4.5.13 4.5.14 4.5.15 4.5.16 4.5.17 4.5.18 4.5.19 4.5.20 4.5.21 4.5.22 4.5.23 4.5.24 4.5.25 4.5.26 4.5.27 4.5.28 4.5.29 4.5.30 4.5.31 4.5.32 4.5.33 4.5.34 4.5.35 4.5.36 4.5.37 4.5.38

DCCDU (-Q6131-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 597 DCCDW (-Q6133-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 598 DCCMC (-Q5883-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 598 DCCMD (-Q5897-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 598 DCCMR (-Q5619-R100). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 598 DCCMS (-Q5619-S100) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 599 DCCMS (-Q5897-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 599 DCCXI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 599 DLU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 600 BDB (-Q808-), (-Q1002-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 602 BDCG (-Q809-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 602 BDE (-Q807-), (-Q1003-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 603 DIU:LDID (-Q1109-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 603 DIUDA (-Q806-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 604 DIUDC (-Q1007-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 605 DLUC (-Q968-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 606 DLUC (-Q112-, -Q113-, Q114-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 607 DLUS (-Q1492-), (-Q1493-), (-Q1494-) . . . . . . . . . . . . . . . . . . . . . . . . . . . 608 DLUV (-Q1498-), (-Q126-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 610 DSU modems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 611 EMSP (-Q1094-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 613 EMSP (-Q828-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 613 FMTU (-Q1112-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 614 FMTU (-Q117-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 614 FTEM (-Q957-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 614 GCG (-Q1322-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 615 IWEx (-Q144-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 616 IWEx (-Q1177-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 621 IWESx (-Q1178-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 622 LMEM (-Q811-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 623 LVMM (-Q812-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 623 LTCD (-Q124-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 624 LTCD (-Q1495-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 625 LTOD (-Q1496-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 626 MGB (-Q1323-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 627 MTAM (-Q1066-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 628 OMX16D (-Q1497-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 629 RGB (-Q1324-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 630 RGMG (-Q813-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 631 RGMG (-Q895-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 633 SASC (-Q1133-), (-Q22-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 634 SASCG (-Q111-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 634 SLMA (-Q1011-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 635 SLMD (-Q838-), (-Q965-), (-Q1101-), (-Q1103-), (-Q1192-) . . . . . . . . . . . 635 SLMD (-Q210-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 636 SLMD (-Q52-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 637 SLMI:AMA (-Q225-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 637

12

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.39 4.5.40 4.5.41 4.5.42 4.5.43 4.5.44 4.5.45 4.5.46 4.6 4.6.1 4.6.2 4.6.3 4.6.4 4.6.5 4.6.6 4.6.7 4.6.8 4.6.9 4.6.10 4.6.11 4.6.12 4.6.13 4.6.14 4.6.15 4.6.16 4.6.17 4.6.18 4.6.19 4.6.20 4.6.21 4.6.22 4.6.23 4.6.24 4.6.25 4.6.26 4.6.27 4.6.28 4.6.29 4.6.30 4.6.31 4.6.32 4.6.33 4.6.34 4.6.35 4.6.36 4.6.37 4.6.38

SLMI:FMA (-Q164-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SLMI:FMB (-Q200-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SLMI:MPB (-Q143-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SLMI:PHA (-Q142-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SLMI:PHA (-Q170-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SLMI:PHB (-Q192-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SLMI:SDA (-Q155-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SLMX (-Q1338-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LTG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ATCO (-Q267-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ATE:TM (-Q969-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ATE:N (-Q94-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CGSM (-Q1185-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . COUC (-Q31-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CRM:R1 (-Q913-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CRM8:R1 (-Q1105-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CRM:R2 (-Q913-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CRM8:R2 (-Q1105-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CRM:SC (-Q913-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CRPC (-Q264-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CRPC (-Q913-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CRP8 (-Q1105-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DCRCx (-Q743-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEC120 (-Q1467-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEC120 (-Q1467-X100) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEC480 (-Q328-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DESA (-A162-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DESB_A1 (-B163-A1-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DESB_B1 (-B163-B1-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DIU30A (-Q562-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DIU30B (-Q563-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DIU30D (-Q876-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DIU30F (-Q876-X200-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DIU120A (-Q1346-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DIU:LDIB (-Q1107-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DIU:LDIM (-Q1343-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ETEAE (-Q670-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GCG:LTGY (-Q724-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GPLC (-Q1349-X301-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GPLD (-Q1349-X401-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GPLSD (-Q1339-X401-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GPLSE (-Q1339-X601-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GPNLD (-Q28-X200-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GPNLE (-Q28-X600-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GPNYC (-Q27-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GPNYD (-Q27-X200-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GPNYE (-Q27-X600-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

638 638 639 640 641 642 643 643 644 646 647 648 649 649 650 651 651 652 652 653 654 655 655 655 656 658 659 659 660 661 662 663 664 665 665 666 666 669 669 670 670 671 672 673 674 675 675

A30828-X1160-M-2-7620

13

Construction

Maintenance Node

4.6.39 4.6.40 4.6.41 4.6.42 4.6.43 4.6.44 4.6.45 4.6.46 4.6.47 4.6.48 4.6.49 4.6.50 4.6.51 4.6.52 4.6.53 4.6.54 4.6.55 4.6.56 4.6.57 4.6.58 4.6.59 4.6.60 4.6.61 4.6.62 4.6.63 4.6.64 4.6.65 4.6.66 4.6.67 4.6.68 4.6.69 4.6.70 4.6.71 4.6.72 4.6.73 4.6.74 4.7 4.7.1 4.7.2 4.7.3 4.7.4 4.8 4.8.1 4.8.2 4.8.3 4.8.4 4.8.5

GPNZC (-Q26-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 676 GPNZD (-Q26-X200-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 677 GPNZE (-Q26-X600-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 678 GPPYF (-Q277-X000 -) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 679 GPPYG (-Q277-X100 -) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 680 GPPYH (-Q277-X200 -) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 681 GPPYI (-Q277-X300 -) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 682 GPPZF (-Q302-X000 -) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 683 GPPZG (-Q302-X100 -) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 684 GPPZH (-Q302-X200 -) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 685 GPPZI (-Q302-X300 -) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 686 GSM (-Q1340-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 686 MCAA (-Q729-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 686 MCT (-Q63-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 687 MDTOG (-Q1105-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 687 MDTOG (-Q1490-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 688 OCE:MUPx (-Q1030-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 688 OCE:SPC (-Q1031-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 689 OCE:SPM (-Q1401-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 689 OCE:N (-Q165-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 690 PHMA (-Q1469-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 690 PMUx (-Q1141-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 691 PMUE (-Q1141-X600-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 691 RM:CTC (-Q829-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 692 RM:CTC (-Q913-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 692 SCR (-Q1445-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 693 SILCB (-Q1110-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 694 SILCD (-Q1110-X200-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 694 SILC:DLU (-Q783-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 695 SILC:PA (-Q783-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 695 TEM:COP (-Q606-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 696 TEM:LE (-Q607-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 699 TOGB (-Q738-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 699 TOGC (-Q1290-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 699 TOGD (-Q1291-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 700 VPU (-Q190-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 700 MB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 701 MBDA (-Q54-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 701 MBDC (-Q55-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 702 MBDCG (-Q56-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 703 MBDH (-Q57-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 704 RSU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 705 AMUX (-Q104-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 705 DIU240A (-Q106-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 706 DIU240B (-Q107-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 707 RSUC (-Q98-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 708 MH (-Q97-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 709

14

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.8.6 4.8.7 4.9 4.9.1 4.9.2 4.10 4.10.1 4.10.2 4.10.3 4.10.4 4.10.5 4.10.6 4.10.7 4.11 4.11.1 4.11.2 4.11.3 4.11.4 4.11.5 4.11.6 4.11.7 4.12 4.12.1 4.12.2 4.12.3 4.12.4 4.12.5 4.12.6 4.12.7 4.12.8 4.12.9 4.12.10 4.12.11 4.12.12 4.12.13 4.12.14 4.12.15 4.13 4.13.1 4.13.2 4.13.3 4.13.4 4.13.5 4.13.6 4.13.7 4.13.8 4.14

TSIMA (-Q105-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TSIMB (-Q105-X100) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SDHI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OIM*W (-D3559-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OIM*P (-D3560-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SMSC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CCGB (-Q887-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CCGXXA (-Q888-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CDEX (-Q900-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CDEX (-Q900-X100-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PU:SYCR (-Q867-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T/RM:SYCR (-Q868-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T/RM:SYCR (-Q868-X200-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LILD (-Q70-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LILE (-Q263-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MATC (-Q73-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MATM (-Q72-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MUXC (-Q71-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OFC (-Q264-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SNOPT (-Q280-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SSNC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ACCG (Q145) (Q1022) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ALIB (Q1065) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AMXE (Q1019) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASMG16/16 (Q1034) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GMX:E (Q1032) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LIC:2A (Q1014). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LIC:1,5A (Q1013) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MDD (U2594) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MOD (Q1028) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MPUC (SA,512MB)(Q82-X401) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MPUC (AP,512MB)(Q80-X401) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MPUC (equipment side) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MPUD (Q83) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MPUD (Q85-X801) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PSAG (Q6124) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . STMI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GPSF (-Q278-X000-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GPSG (-Q278-X100-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GPSH (-Q278-X200-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GPSI (-Q278-X300-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . STMI:E(W) (-Q300-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . STMI:E(P) (-Q301-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . STMI:O(W) (-Q298-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . STMI:O(P) (-Q299-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SYP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

710 711 712 712 713 714 714 714 714 714 714 714 719 725 725 726 727 727 728 728 729 730 730 732 732 733 733 734 735 736 736 737 737 738 738 739 739 740 740 741 742 743 744 745 746 747 748

A30828-X1160-M-2-7620

15

Construction

Maintenance Node

4.14.1 4.14.2 4.14.3 4.14.4 4.14.5 4.14.6 4.14.7 4.14.8 4.14.9 4.14.10 4.14.11 4.14.12 4.14.13

COM:SYPC (-Q758-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 748 RM:EA (-Q760-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 749 T/RM:SYPC (-Q761-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 750 T/RM:SYPC (-Q761-X100-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 751 TXA:SYPC (-Q759-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 752 ACC:SYPD (-Q776-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 756 DYM:SYPD (-Q708-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 757 EWA:SYPD (-Q5517-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 759 T/RM:SYPD (-Q709-X-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 760 T/RM:SYPD (-Q709-X100-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 760 PBSL32J (-U2607-). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 762 PBSL8RO (-U2608-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 766 PBSLV24 (-U2609-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 770

16

A30828-X1160-M-2-7620

Maintenance Node

Construction

1 Introduction
The construction manual contains all the hardware components of a network node that are relevant for fault clearance using maintenance and nonstandard manuals. The construction manual is divided into the following sections: Racks (division, layout of fuse panel) Module Frames (module side, backplane, cabling) Modules (faceplate, component side, switch settings, displays)

A30828-X1160-M-2-7620

17

Construction

Maintenance Node

18

A30828-X1160-M-2-7620

Maintenance Node

Construction

2 Racks
2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.18 2.19 2.20 2.21 2.22 2.23 2.24 2.25 2.26 2.27 2.28 2.29 2.30 2.31 2.32 2.33 2.34 2.35 2.36 2.37 2.38 2.39 2.40 2.41 2.42 2.43 2.44 2.45 R:CE R:CCNP/SILTD R:CP113A R:CP113B R:CP113C R:CP113E R:DEVB R:DEVD R:DLUA Configuration ABAB or C R:DLUA Configuration ABBB or C R:DLUB Configuration DEDE or F R:DLUB Configuration GEGE or F R:DLUB Configuration DEGE or F R:DLUB Configuration GEDE or F R:DLUB Configuration DDDD / DDD R:DLUB Configuration GGGG R:DLUB Configuration DDD, GGG, DGG, DDG, GDD, GGD R:DLUB Configuration GEIJ or L R:DLUB Configuration GJIJ / GJI R:DLUB Configuration DEIJ or L R:DLUB Configuration IJDE or F R:DLUB Configuration IJGE or F R:DLUB Configuration IJGJ R:DLUB Configuration DDD(F) with FAN R:DLUB Configuration DED(F) with FAN R:DLUB Configuration DEG(F) with FAN R:DLUB Configuration DEI(L) with FAN R:DLUB Configuration GED(F) with FAN R:DLUB Configuration GEG(F) with FAN R:DLUB Configuration IJD(F) with FAN R:DLUB Configuration GEG with FMX2S/SNUS/SMA1K R:DLUB Configuration GGF with FMX2S/SNUS/SMA1K R:DLUB Configuration GGG with FMX2S/SNUS/SMA1K R:DLUG Configuration ABAB or C R:DLUA for DSU Configuration ABAB or C R:DLUA for DSU Configuration ABBB or C R:DLUA for DSU Configuration ABB-Modem R:DLUB for DSU Configuration GEGE or F R:DLUB for DSU Configuration GE-Modem R:DSU/LTG R:DSM R:HTI/RTI R:HTI/RTI with SDHI R:HTI/RTI with one F:LTGN R:HTI/RTI with SDHI and one F:LTGN

A30828-X1160-M-2-7620

19

Construction

Maintenance Node

2.46 2.47 2.48 2.49 2.50 2.51 2.52 2.53 2.54 2.55 2.56 2.57 2.58 2.59 2.60 2.61 2.62 2.63 2.64 2.65 2.66 2.67 2.68 2.69 2.70 2.71 2.72 2.73 2.74 2.75 2.76 2.77 2.78 2.79 2.80 2.81 2.82 2.83 2.84 2.85 2.86 2.87 2.88 2.89 2.90 2.91 2.92

R:HTI/RTI with two F:LTGN R:HTI/RTI with SDHI and two F:LTGN R:HTI/RTI with three F:LTGN R:HTI/RTI with SDHI and three F:LTGN R:LTGB R:LTGC R:LTGC/CR R:LTGD R:LTGF R:LTGG R:LTGG with LTGH R:LTGM R:LTGM with DLUV R:LTGM with LTGG and DLUV R:LTGM with LTGG and LTGH R:LTGN R:LTGN with LTGG or LTGH R:LTGN with F:SDHI and FAN R:LTGN with F:SDHI without FAN R:LTGN with DLUV R:LTGN with DLUV and LTGG or LTGH R:LTGN with TSG, cabling from above R:LTGN with TSG, cabling from below R:LTGN with TSG and MB/CCG, cabling from above R:LTGN with TSG and MB/CCG, cabling from below R:LTGN with SSG, cabling from above R:LTGN with SSG, cabling from below R:LTGN with SSG and MB/CCG, cabling from above R:LTGN with SSG and MB/CCG, cabling from below R:LTGN with MBD and CCGE R:LTGN with MBD and SSG, cabling from above R:LTGN with MBD and SSG, cabling from below R:LTGN with MBD and TSG, cabling from above R:LTGN with MBD and TSG, cabling from below R:LTGN with MBD and SNMUX, cabling from above R:LTGN with MBD and SNMUX, cabling from below R:LTGN with MBD and SNCARE, cabling from above R:LTGN with MBD and SNCARE, cabling from below R:LTGN with SNMUX, without FAN, cabling from above R:LTGN with SNMUX, without FAN, cabling from above R:LTGN with SNMUX and FAN, cabling from above R:LTGN with SNMUX and FAN, cabling from below R:LTGN with SNCARE, cabling from above R:LTGN with SNCARE, cabling from below R:LTGN with 4 SNMUX and FAN, cabling from above R:LTGN with 4 SNMUX and FAN, cabling from below R:STMI/LTG

20

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.93 2.94 2.95 2.96 2.97 2.98 2.99 2.100 2.101 2.102 2.103 2.104 2.105 2.106 2.107 2.108 2.109 2.110 2.111 2.112 2.113 2.114 2.115 2.116 2.117 2.118 2.119 2.120 2.121 2.122 2.123 2.124 2.125 2.126 2.127 2.128 2.129 2.130 2.131 2.132 2.133 2.134 2.135 2.136 2.137

R:STMI/LTG with DLUV R:STMI/LTG with SNMUX(A) R:STMI/LTG with SNMUX(A) and DLUV R:STMI/LTG with SNMUX(B) R:STMI/LTG with SNMUX(B) and DLUV R:STMI/LTG with TSG(B) R:STMI/LTG with TSG(B) and DLUV R:MB/CCG R:MB/CCG with FAN R:MBD/CCGE R:SE R:SILTD R:SSNC (basic rack) R:SSNC (extension rack) R:SN (with DCCXI) R:SN (with DCCCS) R:SN(B) / SNMUX / LTGG (cabling from above) R:SN(B) / SNMUX / LTGG (cabling from below) R:SN(B) / SNCARE / LTGG (cabling from above) R:SN(B) / SNCARE / LTGG (cabling from below) R:SN(B)/LTGM (cabling from above) R:SN(B)/LTGM (cabling from below) R:SN(B)/LTGM/SNCARE (cabling from above) R:SN(B)/LTGM/SNCARE (cabling from below) R:SN(B)/LTGM/SNMUX (cabling from above) R:SN(B)/LTGM/SNMUX (cabling from below) R:SN(B)/MB/LTGM (cabling from above) R:SN(B)/MB/LTGM (cabling from below) R:SND/MBD/LTGM (with SNCARE, cabling from above) R:SND/MBD/LTGM (with SNCARE, cabling from below) R:SND/MBD/LTGM (with SNMUX, cabling from above) R:SND/MBD/LTGM (with SNMUX, cabling from below) R:SND/SNMAT R:SSG(B)/LTGG (cabling from above) R:SSG(B)/LTGG (cabling from below) R:SSG(B)/LTGM (cabling from above) R:SSG(B)/LTGM (cabling from below) R:SSG(B)/MB/LTGM (cabling from above) R:SSG(B)/MB/LTGM (cabling from below) R:TSG(B)/LTGG (cabling from above) R:TSG(B)/LTGG (cabling from below) R:TSG(B)/LTGM (cabling from above) R:TSG(B)/LTGM (cabling from below) R:TSG(B)/MB/LTGM (cabling from above) R:TSG(B)/MB/LTGM (cabling from below)

A30828-X1160-M-2-7620

21

Construction

Maintenance Node

2.1

R:CE
Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:SMSC(C) 0

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:SMSC(C) 1 F:PIOP(A) 0 or F:PIOP(B) 0 FAN (B5681) F:PBC(A) 0

MUT04 F:SMSC(C) 0 MUT03 F:SMSC(C) 1 MUT08 MUT05 FAN (B5681) F:PIOP(A) 0 or F:PIOP(B) 0 F:PBC(A) 0 MUT09 MUT07 F:PBC(A) 0 F:PIOP(A) 1 or F:PIOP(B) 1 FAN-BOX (B5877) rack 7 ft.

MUT04 MUT08 MUT03

F:PBC(A) 1 FAN (B5681) F:PIOP(A) 1 or F:PIOP(B) 1 F:DEV(F)) 1 FAN-BOX (B5877)

MUT06

MUT05

MUT06

MUT10

MUT07 MUT11

MUT11

rack 8 ft.

FU 02 04 06 08

MUT MUT02 MUT02 MUT02 MUT02

Unit F:SMSC(C) - 0 F:SMSC(C) - 0 F:SMSC(C) - 0 F:SMSC(C) - 0 C101 / DCC for SYCR C153/ DCC for CCG 0 SYPD 0 / SYPD 1 C259 / DCC for MB 0

MOLOC

Tab. 2.1

Fuse Assignment R:CE without SSNC connection to

22

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 10 11 23 25 27 29 03 05 07 09 12 13 14 15 16 17 18 19 20 21 22 32 24 26 28 30 01 33 31

MUT MUT02 MUT02 MUT04 MUT04 MUT04 MUT04 MUT03 MUT03 MUT03 MUT03 MUT08 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT06 MUT09 MUT07 MUT07 MUT07 MUT07 MUT10 MUT10 MUT11

Unit F:SMSC(C) - 0 F:SMSC(C) - 0 F:SMSC(C) - 1 F:SMSC(C) - 1 F:SMSC(C) - 1 F:SMSC(C) - 1 F:PIOP(A) - 0 F:PIOP(A) - 0 F:PIOP(A) - 0 F:PIOP(A) - 0 FAN F:PBC(A) - 0 F:PBC(A) - 0 F:PBC(A) - 0 F:PBC(A) - 0 F:PBC(A) - 0 F:PBC(A) - 1 F:PBC(A) - 1 F:PBC(A) - 1 F:PBC(A) - 1 F:PBC(A) - 1 FAN F:PIOP(A) - 1 F:PIOP(A) - 1 F:PIOP(A) - 1 F:PIOP(A) - 1 F:DEV(F) *) F:DEV(F) FAN-BOX

MOLOC C343P1 / DCC for SN0 external horn/ external alarm C101 / DCC for CDEX C153 / DCC for CCG1 C259 / DCC MB1 C343P1 / DCC for SN1 C101P1 / free for CAP C127P1 / DCC for IOC 0 C249P1 / On-board converter from M:LAUB C337P1 / DCC for M:IOPG 0

C101P1 / DCC for BAP 0 C125P1 / free C151P1 / DCC for M:BCMY 0 C159P1 / On-board converter from M:BCM 0 C339P1 / DCC for M:CMY 0 C101P1 / DCC for BAP1 C125P1 / free C151P1 / DCC for M:BCMY1 C159P1 / On-board converter from M:BCM1 C339P1 / DCC for M:CMY1 optional C101P1 / free for CAP C127P1 / DCC for IOC1 C249P1 / On-board converter from M:LAUB C337P1 / DCC for IOPG 1 MDD 0 / MOD 0 only in 8 ft-rack MDD 1 / MOD 1 only in 8 ft-rack

Tab. 2.1

Fuse Assignment R:CE without SSNC connection to

FU 02 04 06 08 10

MUT MUT02 MUT02 MUT02 MUT02 MUT02

Unit F:SMSC(C) - 0 F:SMSC(C) - 0 F:SMSC(C) - 0 F:SMSC(C) - 0 F:SMSC(C) - 0 C101 / DCC for SYCR

MOLOC

C153 / DCC for CCG 0 SYPD 0 / SYPD 1 C259 / DCC for MB 0 C343P1 / DCC for SN 0

Tab. 2.2

Fuse Assignment R:CE with SSNC connection to

A30828-X1160-M-2-7620

23

Construction

Maintenance Node

FU 11 23 25 27 29 03 05 07 09 12 13 14 15 16 17 18 19 20 21 22 32 24 26 28 30 01 33 31

MUT MUT02 MUT04 MUT04 MUT04 MUT04 MUT03 MUT03 MUT03 MUT03 MUT08 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT06 MUT09 MUT07 MUT07 MUT07 MUT07 MUT10 MUT10 MUT11

Unit F:SMSC(C) - 0 F:SMSC(C) - 1 F:SMSC(C) - 1 F:SMSC(C) - 1 F:SMSC(C) - 1 F:PIOP(B) - 0 F:PIOP(B) - 0 F:PIOP(B) - 0 F:PIOP(B) - 0 FAN F:PBC(A) - 0 F:PBC(A) - 0 F:PBC(A) - 0 F:PBC(A) - 0 F:PBC(A) - 0 F:PBC(A) - 1 F:PBC(A) - 1 F:PBC(A) - 1 F:PBC(A) - 1 F:PBC(A) - 1 FAN F:PIOP(B) - 1 F:PIOP(B) - 1 F:PIOP(B) - 1 F:PIOP(B) - 1 F:DEV(F) *) F:DEV(F) FAN-BOX

MOLOC external horn/ external alarm C101 / DCC for CDEX C153 / DCC for CCG 1 C259 / DCC for MB 1 C343 / DCC for SN 1 C101P1 / DCC for CAP4 C131P1 / free for IOC C257P5 / M:LAUB (all) for On-board converter C341P1 / DCC for M:IOPG 0 and DCC for IOP 0

C101P1 / DCC for BAP 0 C125P1 / free for IOC 0 C151P1 / DCC for M:BCMY 0 C159P1 / On-board converter from M:BCM 0 C339P1 / DCC for M:CMY 0 C101P1 / DCC for BAP1 C125P1 / free for IOC C151P1 / DCC for M:BCMY 1 C159P1 / On-board converter from M:BCM C339P1 / DCC for M:CMY1 optional C101P1 / DCC for CAP3 C131P1 / free for IOC C257P5 / On-board converter from M:LAUB C341P1 / DCC for IOPG 1 and DCC for IOC 1 MDD 0 / MOD 0 only in 8 ft-rack MDD 1 / MOD 1 only in 8 ft-rack

Tab. 2.2

Fuse Assignment R:CE with SSNC connection to

24

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.2

R:CCNP/SILTD
Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:SILTD(A)

MUT01 MUT02 Fuse Panel MUT01

F:SILTD(A)

MUT04

F:SILTD(A)

MUT02

F:SILTD(A)

MUT06 F:SILTD(A) MUT04

F:SILTD(A)

MUT06

F:CCNP(B)

MUT08

F:CCNP(B)

MUT08

F:CCNP(B)

MUT10

F:CCNP(B)

MUT10

rack 8 ft.

rack 7 ft.

FU 01 11 03 13 07 17 05 06 15 16

MUT MUT02 MUT02 MUT04 MUT04 MUT06 MUT06 MUT08 MUT08 MUT10 MUT10 F:SILTD 0 F:SILTD 0 F:SILTD 1 F:SILTD 1 F:SILTD 2 F:SILTD 2

Unit A001 A120 A001 A120 A001 A120 A001 MUXM A120 CCNP A001 MUXM A120 CCNP

MOLOC

F:CCNP(B) 0 F:CCNP(B) 0 F:CCNP(B) 1 F:CCNP(B) 1

Tab. 2.3

Fuse Assignment R:CCNP/ SILTD

A30828-X1160-M-2-7620

25

Construction

Maintenance Node

2.3

R:CP113A
Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel

MUT01 MUT03 Fuse Panel MUT01 MUT03

F:CMY 0

F:CMY 1 FAN (B5681) F:MI 0

MUT04 MUT05

F:CMY 0

F:CMY 1 MUT06 FAN (B5681) F:MI 1 MUT07 F:MI 0

MUT04 MUT05 MUT06

F:MI 1 F:P/IOC MUT09

MUT07

F:P/IOC

MUT09

F:P/IOC

MUT10

F:P/IOC FAN-BOX (B5877) rack 7 ft.

MUT10

FAN-BOX (B5877) rack 8 ft.

MUT12

MUT12

FU 02 12 07 04 14 05 06 15 16 17 19 20

MUT MUT03 MUT04 MUT05 MUT06 MUT07 MUT09 MUT09 MUT10 MUT10 MUT12 MUT01 MUT01

Unit F:CMY 0 F:CMY 1 FAN F:MI 0 F:MI 1 F:P/IOC 0 F:P/IOC 0 F:P/IOC 1 F:P/IOC 1 FAN- BOX AD:RAL AD:RAL

MOLOC C101 / DCC for M:MUH and C327/ DCC for M:CMY 0 of the BCMY 0 C101 / DCC for M:MUH and C327/ DCC for M:CMY 1 of the BCMY 1 AIC1 C101 / DCC for PI and C327 / DCC for MI C101 / DCC for PI and C327 / DCC for MI C101 / DCC for BAP 0 C327 / DCC for IOC 0 C101 / DCC for BAP 1 C327 / DCC for IOC 1 AIC 0 AB-

Tab. 2.4

Fuse Assignment R:CP113A

26

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.4

R:CP113B
Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:P/IOC 2

MUT01 MUT03 Fuse Panel MUT01 MUT03

F:P/IOC 3

MUT04 MUT05

F:P/IOC 2

FAN (B5681) F:PI 0

F:P/IOC 3 MUT06 FAN (B5681) F:PI 1 MUT07 F:PI 0

MUT04 MUT05 MUT06

F:PI 1 F:P/IOC 4 MUT09

MUT07

F:P/IOC 4

MUT08

F:P/IOC 5

MUT10

F:P/IOC 5 FAN-BOX (B5877) rack 7 ft.

MUT10 MUT12

FAN-BOX (B5877)

MUT12

rack 8 ft.

FU 01 02 11 12 07 03 13 05 06 15 16 17

MUT MUT03 MUT03 MUT04 MUT04 MUT05 MUT06 MUT07 MUT09 MUT09 MUT10 MUT10 MUT12

Unit F:P/IOC 2 F:P/IOC 2 F:P/IOC 3 F:P/IOC 3 FAN F:PI 0 F:PI 1 F:P/IOC 4 F:P/IOC 4 F:P/IOC 5 F:P/IOC 5 FAN- BOX C101 / DCC for CAP 0 C327 / DCC for IOC 2 C101 / DCC for CAP 1 C327 / DCC for IOC 3 AIC 17 C101 / DCC for BCMY 0 C101 / DCC for BCMY 1 C101 / DCC for CAP 2 C327 / DCC for CAP 3 C101 / DCC for CAP 4 C327 / DCC for CAP5 AIC 16

MOLOC

Tab. 2.5

Fuse Assignment R:CP113B

A30828-X1160-M-2-7620

27

Construction

Maintenance Node

FU 19 20

MUT MUT01 MUT01 AD:RAL AD:RA

Unit AB-

MOLOC

Tab. 2.5

Fuse Assignment R:CP113B

2.5
2.5.1

R:CP113C
CP113C with F:PIOP(A)
Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:PIOP(A) 2

MUT01 MUT02 Fuse Panel F:PIOP(A) 2 MUT01 MUT02

F:PIOP(A) 0 FAN (B5681) F:PBC(A) 0

MUT03 MUT04 MUT05

F:PIOP(A) 0 FAN (B5681) F:PBC(A) 0

MUT03 MUT04 MUT05

F:PBC(A) 1

MUT06

F:PIOP(A) 1 FAN (B5681) F:PIOP(A) 3

MUT07 MUT08 MUT09 F:PBC(A) 1 MUT06

F:PIOP(A) 1

MUT07

F:DEV(F) or F:DEV(E) FAN-BOX (B5877)

MUT10

F:PIOP(A) 3 FAN-BOX (B5877) rack 7 ft.

MUT09 MUT11

MUT11

rack 8 ft.

28

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 02 04 06 08 03 05 07 09 12 13 14 15 16 17 18 19 20 21 22 23 25 27 29 32 24 26 28 30 01 33 31

MUT MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT04 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT06 MUT07 MUT07 MUT07 MUT07 MUT08 MUT09 MUT09 MUT09 MUT09 MUT10 MUT10 MUT11

Unit F:PIOP(A) 2 F:PIOP(A) 2 F:PIOP(A) 2 F:PIOP(A) 2 F:PIOP(A) 0 F:PIOP(A) 0 F:PIOP(A) 0 F:PIOP(A) 0 FAN F:PBC 0 F:PBC 0 F:PBC 0 F:PBC 0 F:PBC 0 F:PBC 1 F:PBC 1 F:PBC 1 F:PBC 1 F:PBC 1 F:PIOP(A) 1 F:PIOP(A) 1 F:PIOP(A) 1 F:PIOP(A) 1 FAN F:PIOP(A) 3 F:PIOP(A) 3 F:PIOP(A) 3 F:PIOP(A) 3 F:DEV(F) or DEV(E) F:DEV(F) or DEV(E) FAN-BOX

MOLOC C101P1 / DCC for CAP 4 (Proc.10) C127P1 / DCC for IOC 2 (Proc. 5) C249P1 / On-board converter from M:LAUB (all) C337P1 DCC for IOPs C101P1 / DCC for CAP 2 (Proc. 8) C127P1 / DCC for IOC 0 (Proc.1) C249P1 /On-board converter from M:LAUB (all) C337P1 DCC for IOPs F2 / F1 C101P1 / DCC for BAP 0 (Proc. 0) C125P1 / DCC for CAP 0 (Proc. 4) C151P1 / DCC for BCMY 0 C159P1 / On-board converter of the M:BCM 0 C339P1 / DCC for CMY 0 C101P1 / DCC for BAP 1 (Proc. 2) C125P1 / DCC for CAP 1 (Proc. 6) C151P1 / DCC for BCMY 1 C159P1 / On-board converter of the M:BCM 1 C339P1 / DCC for CMY 1 C101P1 / DCC for CAP 3 (Proc. 9) C127P1 / DCC for IOC 1 (Proc. 3) C249P1 / On-board converter from M:LAUB (all) C337P1 / DCC for IOPs F2 / F1 (optional) C101P1 / DCC for CAP 5 (Proc.11) C127P1 / DCC for IOC 3 (Proc. 7) C249P1 / On-board converter from M:LAUB (all) C337P1 / DCC for IOPs MDD 0 / MOD 0 MDD 1 / MOD 1 X21 / X22

Tab. 2.6

Fuse Assignment R:CP113C with F:PIOP(A)

A30828-X1160-M-2-7620

29

Construction

Maintenance Node

2.5.2

CP113C with F:PIOP(B)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:PIOP(B) 2

MUT01 MUT02 Fuse Panel F:PIOP(B) 2 MUT04 MUT05 F:PIOP(B) F:PIOP(A) 0 FAN (B5681) F:PBC(A) 0 MUT01 MUT02

F:PIOP(B) 0 FAN (B5681) F:PBC(A) 0

MUT03

MUT03 MUT04 MUT05

F:PBC(A) 1

MUT06

F:PIOP(B) 1 FAN (B5681) F:PIOP(B) 3

MUT07 MUT08 MUT09 F:PBC(A) 1 MUT06

F:PIOP(B) 1

MUT07

F:DEV(F) or F:DEV(E) FAN-BOX (B5877) rack 8 ft.

MUT10

F:PIOP(B) 3 FAN-BOX (B5877) rack 7 ft.

MUT09 MUT11

MUT11

FU 02 04 06 08 03

MUT MUT02 MUT02 MUT02 MUT02 MUT03

Unit F:PIOP(B) 2 F:PIOP(B) 2 F:PIOP(B) 2 F:PIOP(B) 2 F:PIOP(B) 0

MOLOC C101P1 C131P1 C257P5 C341P1 C101P1

CLASSIC DCC for CAP 4 (Proc. 10) DCC for CAP 8 (Proc. 14) M:LAUB DCC for IOPs / IOC2 (Proc. 5) DCC for CAP 2 (Proc. 8)

INNOVATION DCC for CAP 4 (Proc. 10) DCC for CAP 6 (Proc. 14) M:LAUB CAP 8 or IOC 2 (Proc.5) AMP0 (Proc. 8)

Tab. 2.7

Fuse Assignment R:CP113C with F:PIOP(B)

30

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 05 07 09 12 13 14 15 16 17 18 19 20 21 22 23 25 27 29 32 24 26 28 30 01 33 31

MUT MUT03 MUT03 MUT03 MUT04 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT06 MUT07 MUT07 MUT07 MUT07 MUT08 MUT09 MUT09 MUT09 MUT09 MUT10 MUT10 MUT11

Unit F:PIOP(B) 0 F:PIOP(B) 0 F:PIOP(B) 0 FAN F:PBC 0 F:PBC 0 F:PBC 0 F:PBC 0 F:PBC 0 F:PBC 1 F:PBC 1 F:PBC 1 F:PBC 1 F:PBC 1 F:PIOP(B) 1 F:PIOP(B) 1 F:PIOP(B) 1 F:PIOP(B) 1 FAN F:PIOP(B) 3 F:PIOP(B) 3 F:PIOP(B) 3 F:PIOP(B) 3 F:DEV(F) DEV(E) FAN- BOX

MOLOC C131P1 C257P5 C341P1 F2 / F1 C101P1 C125P1 C151P1 C159P1 C339P1 C101P1 C125P1 C151P1 C159P1 C339P1 C101P1 C131P1 C257P5 C341P11 F2 / F1 C101P1 C131P1 C257P5 C341P1 BAP 0 CAP 0 BCMY 0 BCM 0 CMY 0 BAP 1 CAP 1 BCMY 1 BCM 1 CMY 1

CLASSIC DCC for CAP 6 (Proc. 12) M:LAUB DCC for IOPs / OC0 (Proc. 1)

INNOVATION DCC for CAP 2 (Proc. 12) M:LAUB IOC 0 / IOP 0 (Proc. 1)

BAP 0 CAP 0 BCMY 0 BCM 0 CMY 0 BAP 1 CAP 1 BCMY 1 BCM 1 CMY 1 AMP 1 (Proc. 9) DCC for CAP 3(Proc. 13) M:LAUB DCC for IOPs

DCC for CAP 3 (Proc. 9) DCC for CAP 7 (Proc. 13) M:LAUB DCC for IOPs (Proc. 3)

DCC for CAP 5 (Proc. 11) DCC for CAP 9 (Proc. 15) M:LAUB DCC for IOPs (Proc. 7) MDD 0 / MOD 0 MDD 1/ MOD 1

DCC for CAP 5 (Proc. 11) DCC for CAP 7 (Proc.15) M:LAUB CAP 9 or IOC 3 (Proc. 7)

X22/X21

Tab. 2.7

Fuse Assignment R:CP113C with F:PIOP(B)

A30828-X1160-M-2-7620

31

Construction

Maintenance Node

2.6

R:CP113E
Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 09 10 11 12 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel

MUT01

Fuse Panel

MUT01

F:EIOP

MUT03

F:EIOP

MUT03

F:EIOP

MUT04

F:EIOP

MUT04

F:BIOP FANTRAY (U103) (U2620)

MUT05 MUT06 MUT07

F:BIOP FANTRAY (U103) (U2620)

MUT05 MUT06

F:BPCE

F:BPCE

MUT07

F:EPCE

MUT08

F:EPCE

MUT08

FAN-BOX (U102)

MUT10

FAN-BOX (U102)

MUT10

rack 8 ft.

rack 7 ft.

FU 30 31 32 10 11 12 08 09 28 29

MUT MUT03 MUT03 MUT03 MUT04 MUT04 MUT04 MUT05 MUT05 MUT05 MUT05

Unit F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:BIOP F:BIOP F:BIOP F:BIOP

Connector C101P1 / DCCMD 0, LAUB 0 and 1 C323P1 / DCCMD 1, LAUB 2 and 3 C341P1 / DCCMD 2, LAUB 4 and 5 C101P1 / DCCMD 0, LAUB 0 and 1 C323P1 / DCCMD 1, LAUB 2 and 3 C341P1 / DCCMD 2, LAUB 4 and 5 C101P1 / DCCMD 0 and 1 - side0 C203P1 / LAUB 0 and 1 - side 0 C233P1 / DCCMD 0 and 1 - side 1 C335P1 / LAUB 0 and 1 - side 1

Tab. 2.8

Fuse Assignment R:CP113E

32

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 07 27 05 25 06 26 02 22 03 23 04 24 01 21

MUT MUT06 MUT06 MUT07 MUT07 MUT07 MUT07 MUT08 MUT08 MUT08 MUT08 MUT08 MUT08 MUT10 MUT10

Unit FANTRAY FANTRAY F:BPCE F:BPCE F:BPCE F:BPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE FANBOX FANBOX X1 / X2 X6 / X7 C209 X1, module side 0 C209 X2, module side 0 C285 X1, module side 1 C285 X2, module side 1

Connector

C141 X1, MODE 0 and MDDE 0 C141 X2, MODE 0 and MDDE 0 C243 X1, CAP 8, 10, 12, 14 C243 X2, CAP 9, 11, 13, 15 C359 X1, MODE 1 and MDDE 1 C359 X2, MODE 1 and MDDE 1 X1 / X2 X6 / X7

Tab. 2.8

Fuse Assignment R:CP113E

A30828-X1160-M-2-7620

33

Construction

Maintenance Node

2.7

R:DEVB
R:DEVB - C2631 Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:MODEM F:MODEM

MUT01 MUT02 MUT03

D:MTD 1

MUT04

D:MTD 0

MUT07

D:DCIRB0 or F:MODEM D:DCIRB1 or F:MODEM rack 8 ft.

MUT10 MUT11

FU 05 02 19 20 MUT04 MUT07 MUT10 MUT11

MUT MTD 1 MTD 0 F:MODEM or D:DCIRB 0 F:MODEM or D:DCIRB 1

Tab. 2.9

Fuse Assignment R:DEVB - C2631

34

A30828-X1160-M-2-7620

Maintenance Node

Construction

R:DEVB - C2717 Fuse Panel


FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:MODEM F:MODEM

MUT01 MUT02 MUT03

D:MTD 1

MUT04

D:MTD 0

MUT07

D:DCIRB0 or F:MODEM D:DCIRB1 or F:MODEM rack 8 ft.

MUT10 MUT11

FU 11 01 19 20 MUT04 MUT07 MUT10 MUT11

MUT MTD 1 MTD 0 DCIRC 0 DCIRC 1

Unit MTD 1 MTD 0

MOLOC

Supply voltage for F:MODEM / MUT02 Supply voltage for F:MODEM / MUT03

Tab. 2.10

Fuse Assignment R:DEVB - C2717 -

A30828-X1160-M-2-7620

35

Construction

Maintenance Node

R:DEVB - C2723 - Variant 1


Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel

MUT01

D:MTD 1

MUT03

D:MTD 0

MUT04

F:DEV(F) or F:DEV(E) FAN (B5681) 0 FAN (B5681) 1 FILTER:FAN

MUT10 MUT11 MUT12 MUT13

rack 7 ft.

FU 11 01 02 12 03 13 MUT03 MUT04 MUT10 MUT10 MUT11 MUT12

MUT MTD 1 MTD 0

Unit MTD 1 MTD 0 MDD 0 MDD 1

MOLOC

F:DEV(E) or F:DEV(F) F:DEV(E) or F:DEV(F) Fan 0 Fan 1

Tab. 2.11

Fuse Assignment R:DEVB - C2723 - Variant 1

36

A30828-X1160-M-2-7620

Maintenance Node

Construction

R:DEVB - C2723 - Variant 2


Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel A Shelf 0 F:DLU(A) for DSU C Shelf 1 F:MODEM(D)

MUT01

MUT02

MUT03

D:MTD

MUT04

F:DEV(F) or F:DEV(E) FAN (B5681) 0 FAN (B5681) 1 FILTER:FAN rack 7 ft.

MUT10 MUT11 MUT12 MUT13

FU 05 06 15 16 11 01 02 12 03 13

MUT MUT02 MUT02 MUT02 MUT02 MUT03 MUT04 MUT10 MUT10 MUT11 MUT12 F:DLU(A) F:DLU(A) F:DLU(A) F:DLU(A)

Unit A001, A058, A119

MOLOC

A010 - A052, A089 - A113 C001, C058, C119 C010 - C052, C089 - C113

F:MODEM (D) MTD F:DEV(E) or F:DEV(F) F:DEV(E) or F:DEV(F Fan 0 Fan 1 MTD MDD 0 MDD 1 Fan 0 Fan 1

Tab. 2.12

Fuse Assignment R:DEVB - 2723 - Variant 2

A30828-X1160-M-2-7620

37

Construction

Maintenance Node

2.8

R:DEVD
Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel

MUT01

F:IOP 0 / 2

MUT03

Fuse Panel

MUT01

F:IOP 1 / 3

MUT04

F:IOP 2

MUT06

FAN (B5681)

MUT05

F:IOP 3 FAN (B5681)

MUT07 MUT08 MUT03

D:MTD

MUT06

F:IOP 0

F:IOP 1 FAN (B5681) F:DEV(F) or F:DEV(E) FAN-BOX (B5877) MUT08 F:DEV(F) or F:DEV(E) FAN-BOX (B5877) rack 7 ft.

MUT04 MUT10 MUT05 MUT12

MUT12

rack 8 ft.

FU 01 02 05 06 11 12 15 16 04 09 10 03

MUT in rack 8 ft. MUT03 / F:IOP 0/2 MUT03 / F:IOP 0/2 MUT03 / F:IOP 0/2 MUT03 / F:IOP 0/2 MUT04 / F:IOP 1/3 MUT04 / F:IOP 1/3 MUT04 / F:IOP 1/3 MUT04 / F:IOP 1/3

MOLOC in 8 ft. C101 C331 M:LAUB M:LAUB C101 C331 M:LAUB M:LAUB

MUT in rack 7 ft. MUT03 / F:IOP 0 MUT03 / F:IOP 0 MUT03 / F:IOP 0 MUT03 / F:IOP 0 MUT04 / F:IOP 1 MUT04 / F:IOP 1 MUT04 / F:IOP 1 MUT04 / F:IOP 1 MUT06 / F:IOP 2 MUT06 / F:IOP 2 MUT06 / F:IOP 2

MOLOC in 7 ft. C101 C331 M:LAUB M:LAUB C101 C331 M:LAUB M:LAUB C331 M:LAUB M:LAUB C101

MUT06 / MTD 0

MTD

MUT06 / F:IOP 2

Tab. 2.13

Fuse Assignment R:DEVD

38

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 13 18 19 20 14 07

MUT in rack 8 ft.

MOLOC in 8 ft.

MUT in rack 7 ft. MUT07 / F:IOP 3 MUT07 / F:IOP 3 MUT07 / F:IOP 3 MUT07 / F:IOP 3

MOLOC in 7 ft. C101 C331 M:LAUB M:LAUB

MUT05 / FAN MUT08 / F:DEV(F)/(E) MDD0 / MOD0

MUT08 / FAN MUT10 / FAN MUT05 / F:DEV(F)/(E) MUT05 / F:DEV(F)/(E) MUT12 / FAN-BOX

MDD 0 / MOD 0 MDD 1 / MOD 1

17 08

MUT08 / F:DEV(F)/(E) MUT12 / FAN-BOX

MDD1 / MOD1

Tab. 2.13

Fuse Assignment R:DEVD

2.9

R:DLUA Conguration ABAB or C


Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel A Shelf 0 F:DLU(A) C Shelf 1

MUT01

MUT02 A

Fuse Panel Shelf 0 F:DLU(A)

MUT01

Shelf 2 F:DLU(B) MUT03 C A

MUT02

Shelf 1 Shelf 2 F:DLU(B) MUT03

Shelf 3

Shelf 0 F:DLU(A) MUT05

C A

Shelf 3 Shelf 0 F:DLU(A) MUT05

C A

Shelf 1 Shelf 2 F:DLU(B) MUT06

Shelf 1 Shelf 2 F:DLU(C)

Shelf 3 rack 8 ft.

MUT06

rack 7 ft.

A30828-X1160-M-2-7620

39

Construction

Maintenance Node

FU 01 05 11 15 02 06 12 16 03 07 13 17 04

MUT MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT05 MUT05 MUT05 MUT05 MUT06

Unit F:DLU(A) / Shelf 0 F:DLU(A) / Shelf 0 F:DLU(A) / Shelf 1 F:DLU(A) / Shelf 1 F:DLU(B) / Shelf 2 F:DLU(B) / Shelf 2 F:DLU(B) / Shelf 3 F:DLU(B) / Shelf 3 F:DLU(A) / Shelf 0 F:DLU(A) / Shelf 0 F:DLU(A) / Shelf 1 F:DLU(A) / Shelf 1 F:DLU(B) / Shelf 2 or F:DLU(C) / Shelf 2 F:DLU(B) / Shelf 2 or F:DLU(C) / Shelf 2 F:DLU(B) / Shelf 3 F:DLU(B) / Shelf 3 A001, A058, A119

MOLOC

A010 - A052, A089 - A113 C001, C058, C119 C010 - C052, C089 - C113 A001, A119 A010 - A052, A071 - A113 C001, C119 C010 - C052, C071 - C113 A001, A058, A119 A010 - A052, A089 - A113 C001, C058, C119 C010 - C052, C089 - C113 A001, A119

08

MUT06

A010 - A052, A071 - A113

14 18

MUT06 MUT06

C001, C119 C010 - C052, C071 - C113

Tab. 2.14

Fuse Assignment R:DLUA, Conguration ABAB or C

40

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.10

R:DLUA Conguration ABBB or C


Fuse Panel 8 ft. rack
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel A Shelf 0 F:DLU(A) C A Shelf 1 Shelf 2 F:DLU(B) C Shelf 3

MUT01

MUT02 A

Fuse Panel Shelf 0 F:DLU(A)

MUT01

MUT02

MUT03

C A

Shelf 1 Shelf 2 F:DLU(B) MUT03

Shelf 4 F:DLU(B) MUT05

C A

Shelf 3 Shelf 4 F:DLU(B) MUT05

C A

Shelf 5 Shelf 6 F:DLU(B) MUT06

Shelf 5 Shelf 6 F:DLU(C)

Shelf 7 rack 8 ft.

MUT06

rack 7 ft.

FU 01 05 11 15 02 06 12 16 03 07 13 17

MUT MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT05 MUT05 MUT05 MUT05

Unit F:DLU(A) / Shelf 0 F:DLU(A) / Shelf 0 F:DLU(A) / Shelf 1 F:DLU(A) / Shelf 1 F:DLU(B) / Shelf 2 F:DLU(B) / Shelf 2 F:DLU(B) / Shelf 3 F:DLU(B) / Shelf 3 F:DLU(B) / Shelf 4 F:DLU(B) / Shelf 4 F:DLU(B) / Shelf 5 F:DLU(B) / Shelf 5 A001, A058, A119

MOLOC

A010 - A052, A089 - A113 C001, C058, C119 C010 - C052, C089 - C113 A001, A119 A010 - A052, A071 - A113 C001, C119 C010 - C052, C071 - C113 A001, A119 A010 - A052, A071 - A113 C001, C119 C010 - C052, C071 - C113

Tab. 2.15

Fuse Assignment R:DLUA, Conguration ABBB or C

A30828-X1160-M-2-7620

41

Construction

Maintenance Node

FU 04

MUT MUT06

Unit F:DLU(B) / Shelf 6 or F:DLU(C) / Shelf 6 F:DLU(B) / Shelf 6 or F:DLU(C) / Shelf 6 F:DLU(B) / Shelf 7 F:DLU(B) / Shelf 7 A001, A119

MOLOC

08

MUT06

A010 - A052, A071 - A113

14 18

MUT06 MUT06

C001, C119 C010 - C052, C071 - C113

Tab. 2.15

Fuse Assignment R:DLUA, Conguration ABBB or C

2.11

R:DLUB Conguration DEDE or F


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(D) C A Shelf 1 Shelf 2 F:DLU(E) C Shelf 3

MUT01

MUT02 A

Fuse Panel Shelf 0 F:DLU(D)

MUT01

MUT02

MUT03

C A

Shelf 1 Shelf 2 F:DLU(E) MUT03

Shelf 0 F:DLU(D) MUT05

C A

Shelf 3 Shelf 0 F:DLU(D) MUT05

C A

Shelf 1 Shelf 2 F:DLU(E) MUT06

Shelf 1 Shelf 2 F:DLU(F) MUT06

Shelf 3 rack 8 ft.

rack 7 ft.

42

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 01 02 03 04 05 06 07 08 09 10 11 12 13 14 18 19 20 21 22 23 24

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 / MUT06

Unit F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 A001 - A057 A068 - A121

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A068 - A086 A123, A092 - A110 C001, C015 - C033 C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001 - A057 A068 - A121 C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A001, A015 - A033 A008, A039 - A057 A008, A039 - A057 A116, A068 - A086 A116, A074 - A092 A123, A092 - A110 A123, A098 - A110 C001, C015 - C033 C008, C039 - C057 C116, C068 - C086 C123, C092 - C110

25

MUT06 MUT06

26

MUT06 MUT06

27

MUT06 MUT06

28 29 30 31

MUT06 MUT06 MUT06 MUT06

Tab. 2.16

Fuse Assignment R:DLUB, Conguration DEDE or F

A30828-X1160-M-2-7620

43

Construction

Maintenance Node

2.12

R:DLUB Conguration GEGE or F


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(G) C A Shelf 1 Shelf 2 F:DLU(E) C Shelf 3

MUT01

MUT02 A

Fuse Panel Shelf 0 F:DLU(G)

MUT01

MUT02

MUT03

C A

Shelf 1 Shelf 2 F:DLU(E) MUT03

Shelf 0 F:DLU(G) MUT05

C A

Shelf 3 Shelf 0 F:DLU(G) MUT05

C A

Shelf 1 Shelf 2 F:DLU(E) MUT06

Shelf 1 Shelf 2 F:DLU(F) MUT06

Shelf 3 rack 8 ft.

rack 7 ft.

FU 01 02 03 04 05 06 07 08 09 10 11

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 3 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A068 - A086 A123, A092 - A110 C001, C015 - C033

Tab. 2.17

Fuse Assignment R:DLUB, Conguration GEGE or F

44

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 12 13 14 18 19 20 21 22 23 24

MUT MUT03 MUT03 MUT03 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06

Unit F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A001, A015 - A033 A008, A039 - A057 A008, A039 - A057 A116, A068 - A086 A116, A074 - A092 A123, A092 - A110 A123, A098 - A110 C001, C015 - C033 C008, C039 - C057 C116, C068 - C086 C123, C092 - C110

25

MUT06 MUT06

26

MUT06 MUT06

27

MUT06 MUT06

28 29 30 31

MUT06 MUT06 MUT06 MUT06

Tab. 2.17

Fuse Assignment R:DLUB, Conguration GEGE or F

A30828-X1160-M-2-7620

45

Construction

Maintenance Node

2.13

R:DLUB Conguration DEGE or F


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(D) C A Shelf 1 Shelf 2 F:DLU(E) C Shelf 3

MUT01

MUT02 A

Fuse Panel Shelf 0 F:DLU(D)

MUT01

MUT02

MUT03

C A

Shelf 1 Shelf 2 F:DLU(E) MUT03

Shelf 0 F:DLU(G) MUT05

C A

Shelf 3 Shelf 0 F:DLU(G) MUT05

C A

Shelf 1 Shelf 2 F:DLU(E) MUT06

Shelf 1 Shelf 2 F:DLU(F) rack 7 ft. MOLOC

Shelf 3 rack 8 ft.

MUT06

FU 01 02 03 04 05 06 07 08 09 10 11 12

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 A001 - A057 A068 - A121

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A068 - A086 A123, A092 - A110 C001, C015 - C033 C008, C039 - C057

Tab. 2.18

Fuse Assignment R:DLUB, Conguration DEGE or F

46

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 13 14 18 19 20 21 22 23 24

MUT MUT03 MUT03 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06

Unit F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 C116, C068 - C086 C123, C092 - C110 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A001, A015 - A033 A008, A039 - A057 A008, A039 - A057 A116, A068 - A086 A116, A074 - A092 A123, A092 - A110 A123, A098 - A110 C001, C015 - C033 C008, C039 - C057 C116, C068 - C086 C123, C092 - C110

25

MUT06 MUT06

26

MUT06 MUT06

27

MUT06 MUT06

28 29 30 31

MUT06 MUT06 MUT06 MUT06

Tab. 2.18

Fuse Assignment R:DLUB, Conguration DEGE or F

A30828-X1160-M-2-7620

47

Construction

Maintenance Node

2.14

R:DLUB Conguration GEDE or F


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(G) C A Shelf 1 Shelf 2 F:DLU(E) C Shelf 3

MUT01

MUT02 A

Fuse Panel Shelf 0 F:DLU(G)

MUT01

MUT02

MUT03

C A

Shelf 1 Shelf 2 F:DLU(E) MUT03

Shelf 0 F:DLU(D) MUT05

C A

Shelf 3 Shelf 0 F:DLU(D) MUT05

C A

Shelf 1 Shelf 2 F:DLU(E) MUT06

Shelf 1 Shelf 2 F:DLU(F)

Shelf 3 rack 8 ft.

MUT06

rack 7 ft.

FU 01 02 03 04 05 06 07 08 09 10 11 12

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A068 - A086 A123, A092 - A110 C001, C015 - C033 C008, C039 - C057

Tab. 2.19

Fuse Assignment R:DLUB, Conguration GEDE or F

48

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 13 14 18 19 20 21 22 23 24

MUT MUT03 MUT03 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06

Unit F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 C116, C068 - C086 C123, C092 - C110 A001 - A057 A068 - A121

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A001, A015 - A033 A008, A039 - A057 A008, A039 - A057 A116, A068 - A086 A116, A074 - A092 A123, A092 - A110 A123, A098 - A110 C001, C015 - C033 C008, C039 - C057 C116, C068 - C086 C123, C092 - C110

25

MUT06 MUT06

26

MUT06 MUT06

27

MUT06 MUT06

28 29 30 31

MUT06 MUT06 MUT06 MUT06

Tab. 2.19

Fuse Assignment R:DLUB, Conguration GEDE or F

A30828-X1160-M-2-7620

49

Construction

Maintenance Node

2.15

R:DLUB Conguration DDDD / DDD


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(D) C A Shelf 1 Shelf 0 F:DLU(D) C Shelf 1

MUT01

MUT02 A

Fuse Panel Shelf 0 F:DLU(D)

MUT01

MUT02

MUT03

C A

Shelf 1 Shelf 0 F:DLU(D) MUT03

Shelf 0 C F:DLU(D) MUT05 A

Shelf 1 Shelf 0 F:DLU(D) MUT05

C A

Shelf 1 Shelf 0

C F:DLU(D) MUT06

Shelf 1

Shelf 1 rack 8 ft.

rack 7 ft.

FU 01 02 03 04 05 06 07 09 11 12 13 14

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001 - A057 A066 - A124 C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110

Tab. 2.20

Fuse Assignment R:DLUB, Conguration DDDD / DDD

50

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 18 19 20 21 22 23 24 26 28 29 30 31

MUT MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06

Unit F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001 - A057 A066 - A124 C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110

Tab. 2.20

Fuse Assignment R:DLUB, Conguration DDDD / DDD

A30828-X1160-M-2-7620

51

Construction

Maintenance Node

2.16

R:DLUB Conguration GGGG


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(G) C A Shelf 1 Shelf 0 F:DLU(G) C Shelf 1

MUT01

MUT02

MUT03

Shelf 0 F:DLU(G) MUT05

C A

Shelf 1 Shelf 0 F:DLU(G) MUT06

Shelf 1 rack 8 ft.

FU 01 02 03 04 05 06 07 09 11 12 13 14

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001 - A057 A066 - A124 C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110

Tab. 2.21

Fuse Assignment R:DLUB, Conguration GGGG

52

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 18 19 20 21 22 23 24 26 28 29 30 31

MUT MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06

Unit F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001 - A057 A066 - A124 C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110

Tab. 2.21

Fuse Assignment R:DLUB, Conguration GGGG

2.17

R:DLUB Conguration DDD, GGG, DGG, DDG, GDD, GGD


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(D) or F:DLU(G) Shelf 1

MUT01

MUT02 A

Fuse Panel Shelf 0 F:DLU(D) or F:DLU(G) Shelf 1 Shelf 0 F:DLU(D) or F:DLU(G) Shelf 1 Shelf 0 F:DLU(D) or F:DLU(G) Shelf 1

MUT01

MUT02

C A

MUT03

C A

Shelf 0 F:DLU(D) or F:DLU(G) Shelf 1 Shelf 0 F:DLU(D) or F:DLU(G) Shelf 1 rack 8 ft.

C MUT05 A

MUT05

C MUT06

rack 7 ft.

A30828-X1160-M-2-7620

53

Construction

Maintenance Node

FU 01 02 03 04 05 06 07 09 11 12 13 14 18 19 20 21 22 23

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05

Unit F:DLU(D) or F:DLU(G) / Shelf 0 F:DLU(D) or F:DLU(G) / Shelf 0 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 0 F:DLU(D) or F:DLU(G) / Shelf 0 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 0 F:DLU(D) or F:DLU(G) / Shelf 0 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 1 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001 - A057 A066 - A124 C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001 - A057 A066 - A124 C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110

Tab. 2.22

Fuse Assignment R:DLUB, Cong. DDD, GGG, DGG, DDG, GDD, GGD

54

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.18

R:DLUB Conguration GEIJ or L


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(G) C A Shelf 1 Shelf 2 F:DLU(E) C Shelf 3

MUT01

MUT02 A

Fuse Panel Shelf 0 F:DLU(G)

MUT01

MUT02

MUT03

C A

Shelf 1 Shelf 2 F:DLU(E) MUT03

Shelf 0 F:DLU(I) MUT05

C A

Shelf 3 Shelf 0 F:DLU(I) MUT05

C A

Shelf 1 Shelf 2 F:DLU(J) MUT06

C A

Shelf 1 F:DLU(L)

Shelf 3 rack 8 ft.

MUT06

rack 7 ft.

FU 01 02 03 04 05 06 07 08 09 10 11 12

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A068 - A086 A123, A092 - A110 C001, C015 - C033 C008, C039 - C057

Tab. 2.23

Fuse Assignment R:DLUB, Conguration GEIJ or L

A30828-X1160-M-2-7620

55

Construction

Maintenance Node

FU 13 14 18 19 20 21 22 23 24 25 26 27 28 29 30 31

MUT MUT03 MUT03 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06

Unit F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(I) / Shelf 0 F:DLU(I) / Shelf 0 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 C116, C068 - C086 C123, C092 - C110 C101 - C213 C231 - C345 E101, E129 - E165 E115, E177 - E213 E331, E231 - E271 E345, E283 - E319 C101, C129 - C165 C115, C177 - C213 C331, C235 - C271 C345, C283 - C319 E101, E129 - E165 E115, E177 - E213 E331, E235 - E271 E345, E283 - E319

MOLOC

Tab. 2.23

Fuse Assignment R:DLUB, Conguration GEIJ or L

56

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.19

R:DLUB Conguration GJIJ / GJI


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(G) C A Shelf 1 Shelf 2 F:DLU(J) C Shelf 3

MUT01

MUT02 A

Fuse Panel Shelf 0 F:DLU(G)

MUT01

MUT02

MUT03

C A

Shelf 1 Shelf 0 F:DLU(J) MUT03

Shelf 0 F:DLU(I) MUT05

C A

Shelf 1 Shelf 0 F:DLU(I) MUT05

C A

Shelf 1 Shelf 2 F:DLU(J) MUT06

Shelf 1

Shelf 3 rack 8 ft.

rack 7 ft.

FU 01 02 03 04 05 06 07 08 09 10 11 12

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 C101, C129 - C165 C115, C177 - C213 C331, C235 - C271 C345, C283 - C319 E101, E129 - E165 E115, E177 - E213

Tab. 2.24

Fuse Assignment R:DLUB, Conguration GJIJ / GJI

A30828-X1160-M-2-7620

57

Construction

Maintenance Node

FU 13 14 18 19 20 21 22 23 24 25 26 27 28 29 30 31

MUT MUT03 MUT03 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06

Unit F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 F:DLU(I) / Shelf 0 F:DLU(I) / Shelf 0 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3

MOLOC E331, E235 - E271 E345, E283 - E319 C101 - C213 C231 - C345 E101, E129 - E165 E115, E177 - E213 E331, E231 - E271 E345, E283 - E319 C101, C129 - C165 C115, C177 - C213 C331, C235 - C271 C345, C283 - C319 E101, E129 - E165 E115, E177 - E213 E331, E235 - E271 E345, E283 - E319

Tab. 2.24

Fuse Assignment R:DLUB, Conguration GJIJ / GJI

58

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.20

R:DLUB Conguration DEIJ or L


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(D) C A Shelf 1 Shelf 2 F:DLU(E) C Shelf 3

MUT01

MUT02 A

Fuse Panel Shelf 0 F:DLU(D)

MUT01

MUT02

MUT03

C A

Shelf 1 Shelf 2 F:DLU(E) MUT03

Shelf 0 F:DLU(I) MUT05

C A

Shelf 3 Shelf 0 F:DLU(I) MUT05

C A

Shelf 1 Shelf 2 F:DLU(J) MUT06

Shelf 1

Shelf 3 rack 8 ft.

F:DLU(L)

MUT06

rack 7 ft.

FU 01 02 03 04 05 06 07 08 09 10 11 12

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 A001 - A057 A068 - A121

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A068 - A086 A123, A092 - A110 C001, C015 - C033 C008, C039 - C057

Tab. 2.25

Fuse Assignment R:DLUB, Conguration DEIJ or L

A30828-X1160-M-2-7620

59

Construction

Maintenance Node

FU 13 14 18 19 20 21 22 23 24 25 26 27 28 29 30 31

MUT MUT03 MUT03 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06

Unit F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(I) / Shelf 0 F:DLU(I) / Shelf 0 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3

MOLOC C116, C068 - C086 C123, C092 - C110 C101 - C213 C231 - C345 E101, E129 - E165 E115, E177 - E213 E331, E231 - E271 E345, E283 - E319 C101, C129 - C165 C115, C177 - C213 C331, C235 - C271 C345, C283 - C319 E101, E129 - E165 E115, E177 - E213 E331, E235 - E271 E345, E283 - E319

Tab. 2.25

Fuse Assignment R:DLUB, Conguration DEIJ or L

60

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.21

R:DLUB Conguration IJDE or F


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(I) C A Shelf 1 Shelf 2 F:DLU(J) C Shelf 3

MUT01

MUT02 A

Fuse Panel Shelf 0 F:DLU(I)

MUT01

MUT02

MUT03

C A

Shelf 1 Shelf 2 F:DLU(J) MUT03

Shelf 0 F:DLU(D) MUT05

C A

Shelf 3 Shelf 0 F:DLU(D) MUT05

C A

Shelf 1 Shelf 2 F:DLU(E) MUT06

Shelf 1 Shelf 2 F:DLU(F)

Shelf 3 rack 8 ft.

MUT06

rack7 ft.

FU 01 02 03 04 05 06 07 08 09 10 11 12

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(I) / Shelf 0 F:DLU(I) / Shelf 0 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 C101 - C213 C231 - C345

MOLOC

E101, E129 - E165 E115, E177 - E213 E331, E231 - E271 E345, E283 - E319 C101, C129 - C165 C115, C177 - C213 C331, C235 - C271 C345, C283 - C319 E101, E129 - E165 E115, E177 - E213

Tab. 2.26

Fuse Assignment R:DLUB, Conguration IJDE or F

A30828-X1160-M-2-7620

61

Construction

Maintenance Node

FU 13 14 18 19 20 21 22 23 24

MUT MUT03 MUT03 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06

Unit F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3

MOLOC E331, E235 - E271 E345, E283 - E319 A001- A057 A066- A124 C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A001, A015 - A033 A008, A039 - A057 A008, A039 - A057 A116, A068 - A086 A116, A074 - A092 A123, A092 - A110 A123, A098 - A110 C001, C015 - C033 C008, C039 - C057 C116, C068 - C086 C123, C092 - C110

25

MUT06 MUT06

26

MUT06 MUT06

27

MUT06 MUT06

28 29 30 31

MUT06 MUT06 MUT06 MUT06

Tab. 2.26

Fuse Assignment R:DLUB, Conguration IJDE or F

62

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.22

R:DLUB Conguration IJGE or F


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(I) C A Shelf 1 Shelf 2 F:DLU(J) C Shelf 3

MUT01

MUT02 A

Fuse Panel Shelf 0 F:DLU(I)

MUT01

MUT02

MUT03

C A

Shelf 1 Shelf 2 F:DLU(J) MUT03

Shelf 0 F:DLU(G) MUT05

C A

Shelf 3 Shelf 0 F:DLU(G) MUT05

C A

Shelf 1 Shelf 2 F:DLU(E) MUT06

Shelf 1 Shelf 2 F:DLU(F)

Shelf 3 rack 8 ft.

MUT06

rack7 ft.

FU 01 02 03 04 05 06 07 08 09 10 11 12

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(I) / Shelf 0 F:DLU(I) / Shelf 0 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 C101 - C213 C231 - C345

MOLOC

E101, E129 - E165 E115, E177 - E213 E331, E231 - E271 E345, E283 - E319 C101, C129 - C165 C115, C177 - C213 C331, C235 - C271 C345, C283 - C319 E101, E129 - E165 E115, E177 - E213

Tab. 2.27

Fuse Assignment R:DLUB, Conguration IJGE or F

A30828-X1160-M-2-7620

63

Construction

Maintenance Node

FU 13 14 18 19 20 21 22 23 24

MUT MUT03 MUT03 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06

Unit F:DLU(J) / Shelf 3 F:DLU(J) / Shelf F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3

MOLOC E331, E235 - E271 E345, E283 - E319 A001 - A057 A066 - A124 C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A001, A015 - A033 A008, A039 - A057 A008, A039 - A057 A116, A068 - A086 A116, A074 - A092 A123, A092 - A110 A123, A098 - A110 C001, C015 - C033 C008, C039 - C057 C116, C068 - C086 C123, C092 - C110

25

MUT06 MUT06

26

MUT06 MUT06

27

MUT06 MUT06

28 29 30 31

MUT06 MUT06 MUT06 MUT06

Tab. 2.27

Fuse Assignment R:DLUB, Conguration IJGE or F

64

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.23

R:DLUB Conguration IJGJ


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(I) C A Shelf 1 Shelf 2 F:DLU(J) C Shelf 3

MUT01

MUT02

MUT03

Shelf 0 F:DLU(G) MUT05

C A

Shelf 1 Shelf 2 F:DLU(J) MUT06

Shelf 3 rack 8 ft.

FU 01 02 03 04 05 06 07 08 09 10 11 12

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(I) / Shelf 0 F:DLU(I) / Shelf 0 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 C101 - C213 C231 - C345 E101, E129 - E165 E115, E177 - E213 E331, E231 - E271 E345, E283 - E319 C101, C129 - C165 C115, C177 - C213 C331, C235 - C271 C345, C283 - C319 E101, E129 - E165 E115, E177 - E213

MOLOC

Tab. 2.28

Fuse Assignment R:DLUB, Conguration IJGJ

A30828-X1160-M-2-7620

65

Construction

Maintenance Node

FU 13 14 18 19 20 21 22 23 24 25 26 27 28 29 30 31

MUT MUT03 MUT03 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06

Unit F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 E331, E235 - E271 E345, E283 - E319 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 C101, C129 - C165 C115, C177 - C213 C331, C235 - C271 C345, C283 - C319 E101, E129 - E165 E115, E177 - E213 E331, E235 - E271 E345, E283 - E319

Tab. 2.28

Fuse Assignment R:DLUB, Conguration IJGJ

66

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.24

R:DLUB Conguration DDD(F) with FAN


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0

MUT01

Fuse Panel F:DLU(D) MUT02 A Shelf 0 F:DLU(D)

MUT01

C A

Shelf 1 Shelf 2 F:DLU(D) MUT03

MUT02

C A MUT04 C

Shelf 1 Shelf 2 F:DLU(D) MUT03

Shelf 3 FAN (B5681)

Shelf 3 FAN (B5681) MUT04

Shelf 0 F:DLU(D)) MUT05 A MUT06 C MUT17 Shelf 0 F:DLU(D) Shelf 1 FAN-BOX (B5877) MUT17 MUT15

Shelf 1 F:DLU(F)

Shelf 2 FAN-BOX (B5877)

rack 8 ft.

rack 7 ft.

FU 01 02 03 04 05 06 07 09 11 12 13 14

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 A001 - A057 A068 - A121

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001 - A057 A066 - A124 C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110

Tab. 2.29

Fuse Assignment R:DLUB, Conguration DDD(F) with FAN

A30828-X1160-M-2-7620

67

Construction

Maintenance Node

FU 28 18 19 20 21 22 23 24 25 26 27 31

MUT MUT04 MUT05 MUT05 MUT05/15 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT17 FAN

Unit FAN A001 - A057 A066 - A124

MOLOC

F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 FAN-BOX

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A074 - A092 A123, A098 - A110 FAN-BOX

Tab. 2.29

Fuse Assignment R:DLUB, Conguration DDD(F) with FAN

2.25

R:DLUB Conguration DED(F) with FAN


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0

MUT01

Fuse Panel F:DLU(D) MUT02 A Shelf 0 F:DLU(D)

MUT01

C A

Shelf 1 Shelf 2 F:DLU(E) MUT03

MUT02

C A MUT04 C

Shelf 1 Shelf 2 F:DLU(E) MUT03

Shelf 3 FAN (B5681)

Shelf 3 FAN (B5681) MUT04

Shelf 0 F:DLU(D) MUT05 A Shelf 0 F:DLU(D) Shelf 2 MUT15

Shelf 1

F:DLU(F) FAN-BOX (B5877)

MUT06

Shelf 1 FAN-BOX (B5877) MUT17

MUT17

rack 8 ft.

rack 7 ft.

68

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 01 02 03 04 05 06 07 08 09 10 11 12 13 14 28 18 19 20 21 22 23 24 25 26 27 31

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03 MUT04 MUT05 MUT05 MUT05/15 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT17

Unit F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 FAN F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 FAN-BOX A001 - A057 A068 - A121

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A068 - A086 A123, A092 - A110 C001, C015 - C033 C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 FAN A001 - A057 A066 - A124 C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A074 - A092 A123, A098 - A110 FAN-BOX

Tab. 2.30

Fuse Assignment R:DLUB, Conguration DED(F) with FAN

A30828-X1160-M-2-7620

69

Construction

Maintenance Node

2.26

R:DLUB Conguration DEG(F) with FAN


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(D) C A Shelf 1

MUT01 Fuse Panel MUT02 A Shelf 0 F:DLU(D) MUT02

MUT01

Shelf 2 F:DLU(E) MUT03

C A MUT04 C

Shelf 1 Shelf 2 F:DLU(E) MUT03

Shelf 3 FAN (B5681)

Shelf 3 FAN (B5681) MUT04

Shelf 0 F:DLU(G) MUT05 A Shelf 0 F:DLU(G) MUT15

Shelf 1 F:DLU(F) Shelf 2 FAN-BOX (B5877)

MUT06

Shelf 1 FAN-BOX (B5877) MUT17

MUT17

rack 8 ft.

rack 7ft.

FU 01 02 03 04 05 06 07 08 09 10 11

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 3 A001 - A057 A068 - A121

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A068 - A086 A123, A092 - A110 C001, C015 - C033

Tab. 2.31

Fuse Assignment R:DLUB Conguration DEG(F) with FAN

70

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 12 13 14 28 18 19 20 21 22 23 24 25 26 27 31

MUT MUT03 MUT03 MUT03 MUT04 MUT05 MUT05 MUT05/15 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT17

Unit F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 FAN F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 FAN-BOX C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 FAN A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A074 - A092 A123, A098 - A110 FAN-BOX

Tab. 2.31

Fuse Assignment R:DLUB Conguration DEG(F) with FAN

A30828-X1160-M-2-7620

71

Construction

Maintenance Node

2.27

R:DLUB Conguration DEI(L) with FAN


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(D) C A Shelf 1

MUT01 Fuse Panel MUT02 A Shelf 0 F:DLU(D) MUT02

MUT01

Shelf 2 F:DLU(E) MUT03

C A MUT04 C

Shelf 1 Shelf 2 F:DLU(E) MUT03

Shelf 3 FAN (B5681)

Shelf 3 FAN (B5681) MUT04

Shelf 0 F:DLU(I) MUT05 A Shelf 0 F:DLU(I) F:DLU(L) MUT15

Shelf 1

Shelf 2 FAN-BOX (B5877)

MUT06

Shelf 1 FAN-BOX (B5877) MUT17

MUT17

rack 8 ft.

rack7 ft.

FU 01 02 03 04 05 06 07 08 09 10 11

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 3 A001 - A057 A068 - A121

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A068 - A086 A123, A092 - A110 C001, C015 - C033

Tab. 2.32

Fuse Assignment R:DLUB, Conguration DEI(L) with FAN

72

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 12 13 14 28 18 19 20 21 22 23 24 25 26 27 31

MUT MUT03 MUT03 MUT03 MUT04 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT17

Unit F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 FAN F:DLU(I) / Shelf 0 F:DLU(I) / Shelf 0 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(L) / Shelf 2 F:DLU(L) / Shelf 2 F:DLU(L) / Shelf 2 F:DLU(L) / Shelf 2 FAN-BOX C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 FAN C101 - C213 C231 - C345 E101, E129 - E165 E115, E177 - E213 E331, E231 - E271 E345, E283 - E319 C101, C129 - C165 C115, C177 - C213 C331, C235 - C271 C345, C283 - C319 FAN-BOX

MOLOC

Tab. 2.32

Fuse Assignment R:DLUB, Conguration DEI(L) with FAN

A30828-X1160-M-2-7620

73

Construction

Maintenance Node

2.28

R:DLUB Conguration GED(F) with FAN


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(G) C A Shelf 1

MUT01 Fuse Panel MUT02 A Shelf 0 F:DLU(G) MUT02

MUT01

Shelf 2 F:DLU(E) MUT03

C A

Shelf 1 Shelf 2 F:DLU(E) MUT03

Shelf 3 FAN (B5681) MUT04

C A Shelf 0

Shelf 3 FAN (B5681) MUT04

F:DLU(D) C Shelf 1 F:DLU(F) Shelf 2 FAN-BOX (B5877)

MUT05 A Shelf 0 F:DLU(D) MUT06 C MUT17 MUT15

Shelf 1 FAN-BOX (B5877) MUT17

rack 8 ft.

rack7 ft.

FU 01 02 03 04 05 06 07 08 09 10 11

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 3 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A068 - A086 A123, A092 - A110 C001, C015 - C033

Tab. 2.33

Fuse Assignment R:DLUB, Conguration GED(F) with FAN

74

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 12 13 14 28 18 19 20 21 22 23 24 25 26 27 31

MUT MUT03 MUT03 MUT03 MUT04 MUT05 MUT05 MUT05/15 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT17

Unit F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 FAN F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 FAN-BOX C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 FAN A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A074 - A092 A123, A098 - A110 FAN-BOX

Tab. 2.33

Fuse Assignment R:DLUB, Conguration GED(F) with FAN

A30828-X1160-M-2-7620

75

Construction

Maintenance Node

2.29

R:DLUB Conguration GEG(F) with FAN


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(G) C A Shelf 1 Shelf 2 F:DLU(E) C Shelf 3 FAN (B5681) A Shelf 0

MUT01 Fuse Panel MUT02 A Shelf 0 F:DLU(G) C MUT03 A Shelf 2 F:DLU(E) MUT04 C Shelf 3 FAN (B5681) MUT04 MUT03 Shelf 1 MUT02 MUT01

F:DLU(G) C Shelf 1 Shelf 2 F:DLU(F) FAN-BOX (B5877)

MUT05 A Shelf 0 F:DLU(G) MUT15

MUT06 MUT17

Shelf 1 FAN-BOX (B5877) MUT17

rack 8 ft.

rack 7 ft.

FU 01 02 03 04 05 06 07 08 09 10 11 MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03

MUT

Unit F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 3 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A068 - A086 A123, A092 - A110 C001, C015 - C033

Tab. 2.34

Fuse Assignment R:DLUB, Conguration GEG(F) with FAN

76

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 12 13 07 28 18 19 20 21 22 23 24 25 26 27 31 MUT03 MUT03 MUT03 MUT04 MUT05 MUT05

MUT

Unit F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 2 FAN F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 FAN-BOX C008, C039 - C057 C116, C068 - C086 A001, A015 - A033 FAN A001 - A057 A066 - A124

MOLOC

MUT05/15 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT17

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A074 - A092 A123, A098 - A110 FAN-BOX

Tab. 2.34

Fuse Assignment R:DLUB, Conguration GEG(F) with FAN

A30828-X1160-M-2-7620

77

Construction

Maintenance Node

2.30

R:DLUB Conguration IJD(F) with FAN


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(I) C A Shelf 1 Shelf 2 F:DLU(J) C Shelf 3 FAN (B5681) A Shelf 0 F:DLU(D) C Shelf 1 F:DLU(F) A Shelf 2 FAN-BOX (B5877)

MUT01

Fuse Panel MUT02 A Shelf 0 F:DLU(I) C MUT03 A Shelf 2 F:DLU(J) MUT04 C MUT05 A Shelf 3 FAN (B5681) Shelf 0 F:DLU(D) MUT06 C Shelf 1 FAN-BOX (B5877) Shelf 1

MUT01

MUT02

MUT03

MUT04

MUT15

MUT17

MUT17

rack 8 ft.

rack 7 ft.

FU 01 02 03 04 05 06 07 08 09 10 11

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(I) / Shelf 0 F:DLU(I) / Shelf 0 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(I) / Shelf 1 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 2 F:DLU(J) / Shelf 3 C101 - C213 C231 - C345 E101, E129 - E165 E115, E177 - E213 E331, E231 - E271 E345, E283 - E319 C101, C129 - C165 C115, C177 - C213 C331, C235 - C271 C345, C283 - C319 E101, E129 - E165

MOLOC

Tab. 2.35

Fuse Assignment R:DLUB, Conguration IJD(F) with FAN

78

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 12 13 14 28 18 19 20 21 22 23 24 25 26 27 31

MUT MUT03 MUT03 MUT03 MUT04 MUT05 MUT05 MUT05/15 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT17

Unit F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 F:DLU(J) / Shelf 3 FAN F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(D) / Shelf 1 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 FAN-BOX E115, E177 - E213 E331, E235 - E271 E345, E283 - E319 FAN A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A074 - A092 A123, A098 - A110 FAN-BOX

Tab. 2.35

Fuse Assignment R:DLUB, Conguration IJD(F) with FAN

A30828-X1160-M-2-7620

79

Construction

Maintenance Node

2.31

R:DLUB Conguration GEG with FMX2S/SNUS/SMA1K


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(G) C A Shelf 1 Shelf 2 F:DLU(E) C Shelf 3

MUT01

MUT02

MUT03

Shelf 0 F:DLU(G) MUT05

Shelf 1

HOLDER-J (FMX2S / SNUS / SMA1K)

MUT06

rack 8 ft.

FU 01 02 03 04 05 06 07 08 09 10 11 12 MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03

MUT

Unit F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A068 - A086 A123, A092 - A110 C001, C015 - C033 C008, C039 - C057

Tab. 2.36

Fuse Assignment R:DLUB, GEG with FMX2S/SNUS/SMA1K

80

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 13 14 18 19 20 21 22 23 25 27 29 31 MUT03 MUT03 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06

MUT

Unit F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:SMA1K F:SMA1K F:FMX2S and F:SNUS F:FMX2S and F:SNUS X141 X142

MOLOC C116, C068 - C086 C123, C092 - C110 A001 - A057 A066 - A124 C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110

Tab. 2.36

Fuse Assignment R:DLUB, GEG with FMX2S/SNUS/SMA1K

2.32

R:DLUB Conguration GGF with FMX2S/SNUS/SMA1K


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(G) C A Shelf 1 Shelf 0 F:DLU(G) C Shelf 1 Shelf 2 F:DLU(F)

MUT01

MUT02

MUT03

MUT05

HOLDER-J (FMX2S / SNUS / SMA1K)

MUT06

rack 7 ft.

A30828-X1160-M-2-7620

81

Construction

Maintenance Node

FU 01 02 03 04 05 06 07 09 11 12 13 14 18 19 20 22 25 27 29 31 MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06

MUT

Unit F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 F:DLU(F) / Shelf 2 F:SMA1K F:SMA1K F:FMX2S and F:SNUS F:FMX2S and F:SNUS X141 X142 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001 - A057 A066 - A124 C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A008, A039 - A057 A123, A098 - A110 A001, A015 - A033 A116, A074 - A092

Tab. 2.37

Fuse Assignment R:DLUB, G-G-F with FMX2S/SNUS/SMA1K

82

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.33

R:DLUB Conguration GGG with FMX2S/SNUS/SMA1K


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(G) C A Shelf 1 Shelf 0 F:DLU(G) C Shelf 1

MUT01

MUT02

MUT03

Shelf 0 F:DLU(G) MUT05

C A

Shelf 1

HOLDER-J (FMX2S / SNUS / SMA1K) C rack 8 ft.

MUT06

FU 01 02 03 04 05 06 07 09 11 12 13 MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03

MUT

Unit F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001 - A057 A066 - A124 C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086

Tab. 2.38

Fuse Assignment R:DLUB, GGG with FMX2S/SNUS/SMA1K

A30828-X1160-M-2-7620

83

Construction

Maintenance Node

FU 14 18 19 20 21 22 23 25 27 29 31 MUT03 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06

MUT

Unit F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:SMA1K F:SMA1K F:FMX2S and F:SNUS F:FMX2S and F:SNUS X141 X142

MOLOC C123, C092 - C110 A001 - A057 A066 - A124 C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110

Tab. 2.38

Fuse Assignment R:DLUB, GGG with FMX2S/SNUS/SMA1K

84

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.34

R:DLUG Conguration ABAB or C


Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 09 10 11 12 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel C Shelf 0 F:DLUG(A) E C Shelf 1 Shelf 2 F:DLUG(B) E Shelf 3

MUT01

MUT02 C

Fuse Panel Shelf 0 F:DLUG(A)

MUT01

MUT02

MUT03

E C

Shelf 1 Shelf 2 F:DLUG(B) MUT03

Shelf 0 E F:DLUG(A) MUT05 C

Shelf 3 Shelf 0 F:DLUG(A) MUT05

E C

Shelf 1 Shelf 2

E F:DLUG(B) MUT06 C

Shelf 1 Shelf 2 F:DLUG(C) rack 7 ft. MOLOC C101 - C213 and C247 - C345 E101 - E213 and E247 - E345 C223 (Pool-DCC) C101 - C213 and C247 - C345 E101 - E213 and E247 - E345 E223 (Pool-DCC) C101 - C213 and C247 - C345 E101 - E213 and E247 - E345 C223 (Pool-DCC) C101 - C213 and C247 - C345 E101 - E213 and E247 - E345

Shelf 3 rack 8 ft.

MUT06

FU 01 02 03 21 22 23 04 05 06 24 25

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLUG(A) / Shelf 0 F:DLUG(A) / Shelf 1 F:DLUG(A) / Shelf 0 F:DLUG(A) / Shelf 0 F:DLUG(A) / Shelf 1 F:DLUG(A) / Shelf 1 F:DLUG(B) / Shelf 2 F:DLUG(B) / Shelf 3 F:DLUG(B) / Shelf 2 F:DLUG(B) / Shelf 2 F:DLUG(B) / Shelf 3

Tab. 2.39

Fuse Assignment R:DLUG, Conguration ABAB or C

A30828-X1160-M-2-7620

85

Construction

Maintenance Node

FU 26 07 08 09 27 28 29 10 11

MUT MUT03 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06

Unit F:DLUG(B) / Shelf 3 F:DLUG(A) / Shelf 0 F:DLUG(A) / Shelf 1 F:DLUG(A) / Shelf 0 F:DLUG(A) / Shelf 0 F:DLUG(A) / Shelf 1 F:DLUG(A) / Shelf 1 F:DLUG(B) or F:DLUG(C) / Shelf 2 F:DLUG(B) / Shelf 3 F:DLUG(C) / Shelf 2 F:DLUG(B) or F:DLUG(C) / Shelf 2 F:DLUG(B) or F:DLUG(C) / Shelf 2 F:DLUG(B) / Shelf 3 F:DLUG(C) / Shelf 2 F:DLUG(B) / Shelf 3

MOLOC E223 (Pool-DCC) C101 - C213 and C247 - C345 E101 - E213 and E247 - E345 C223 (Pool-DCC) C101 - C213 and C247 - C345 E101 - E213 and E247 - E345 E223 (Pool-DCC) C101 - C213 and C247 - C345 E101 - E213 and E247 - E345 C213 (BDG3) C223 (Pool-DCC) C101 - C213 and C247 - C345 E101 - E213 and E247 - E345 C213 (BDG3) E223 (Pool-DCC)

12 30 31

MUT06 MUT06 MUT06 MUT06

32

MUT06

Tab. 2.39

Fuse Assignment R:DLUG, Conguration ABAB or C

86

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.35

R:DLUA for DSU Conguration ABAB or C


Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel A Shelf 0 F:DLU(A) for DSU C Shelf 1

MUT01

MUT02 A

Fuse Panel Shelf 0 F:DLU(A) for DSU

MUT01

Shelf 2 F:DLU(B) for DSU MUT03 C A

MUT02

Shelf 1 Shelf 2 F:DLU(B) for DSU MUT03

Shelf 3

Shelf 0 F:DLU(A) for DSU MUT05

C A

Shelf 3 Shelf 0 F:DLU(A) for DSU MUT05

C A

Shelf 1 Shelf 2 F:DLU(B) for DSU MUT06

Shelf 1 Shelf 2 F:DLU(C) for DSU

Shelf 3 rack 8 ft.

MUT06

rack 7 ft.

FU 01 05 11 15 02 06 12 16 03 07 13 17

MUT MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT05 MUT05 MUT05 MUT05

Unit F:DLU(A) / Shelf 0 F:DLU(A) / Shelf 0 F:DLU(A) / Shelf 1 F:DLU(A) / Shelf 1 F:DLU(B) / Shelf 2 F:DLU(B) / Shelf 2 F:DLU(B) / Shelf 3 F:DLU(B) / Shelf 3 F:DLU(A) / Shelf 0 F:DLU(A) / Shelf 0 F:DLU(A) / Shelf 1 F:DLU(A) / Shelf 1 A001, A058, A119

MOLOC

A010 - A052, A089 - A113 C001, C058, C119 C010 - C052, C089 - C113 A001, A119 A010 - A052, A071 - A113 C001, C119 C010 - C052, C071 - C113 A001, A058, A119 A010 - A052, A089 - A113 C001, C058, C119 C010 - C052, C089 - C113

Tab. 2.40

Fuse Assignment R:DLUA for DLU, Conguration ABAB or C

A30828-X1160-M-2-7620

87

Construction

Maintenance Node

FU 04

MUT MUT06

Unit F:DLU(B) / Shelf 2 or F:DLU(C) / Shelf 2 F:DLU(B) / Shelf 2 or F:DLU(C) / Shelf 2 F:DLU(B) / Shelf 3 F:DLU(B) / Shelf 3 A001, A119

MOLOC

08

MUT06

A010 - A052, A071 - A113

14 18

MUT06 MUT06

C001, C119 C010 - C052, C071 - C113

Tab. 2.40

Fuse Assignment R:DLUA for DLU, Conguration ABAB or C

88

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.36

R:DLUA for DSU Conguration ABBB or C


Fuse Panel 8 ft. rack
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel A Shelf 0 F:DLU(A) for DSU C A Shelf 1 Shelf 2 F:DLU(B) for DSU C Shelf 3

MUT01

MUT02 A

Fuse Panel Shelf 0 F:DLU(A) for DSU

MUT01

MUT02

MUT03

C A

Shelf 1 Shelf 2 F:DLU(B) for DSU MUT03

Shelf 4 F:DLU(B) for DSU MUT05

C A

Shelf 3 Shelf 4 F:DLU(B) for DSU MUT05

C A

Shelf 5 Shelf 6 F:DLU(B) for DSU MUT06

Shelf 5 Shelf 2 F:DLU(C) for DSU

Shelf 7 rack 8 ft.

MUT06

rack 7 ft.

FU 01 05 11 15 02 06 12 16 03 07 13 17

MUT MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT05 MUT05 MUT05 MUT05

Unit F:DLU(A) / Shelf 0 F:DLU(A) / Shelf 0 F:DLU(A) / Shelf 1 F:DLU(A) / Shelf 1 F:DLU(B) / Shelf 2 F:DLU(B) / Shelf 2 F:DLU(B) / Shelf 3 F:DLU(B) / Shelf 3 F:DLU(B) / Shelf 4 F:DLU(B) / Shelf 4 F:DLU(B) / Shelf 5 F:DLU(B) / Shelf 5 A001, A058, A119

MOLOC

A010 - A052, A089 - A113 C001, C058, C119 C010 - C052, C089 - C113 A001, A119 A010 - A052, A071 - A113 C001, C119 C010 - C052, C071 - C113 A001, A119 A010 - A052, A071 - A113 C001, C119 C010 - C052, C071 - C113

Tab. 2.41

Fuse Assignment R:DLUA for DSU, Conguration ABBB or C

A30828-X1160-M-2-7620

89

Construction

Maintenance Node

FU 04

MUT MUT06

Unit F:DLU(B) / Shelf 2 or F:DLU(C) / Shelf 2 F:DLU(B) / Shelf 2 or F:DLU(C) / Shelf 2 F:DLU(B) / Shelf 7 F:DLU(B) / Shelf 7 A001, A119

MOLOC

08

MUT06

A010 - A052, A071 - A113

14 18

MUT06 MUT06

C001, C119 C010 - C052, C071 - C113

Tab. 2.41

Fuse Assignment R:DLUA for DSU, Conguration ABBB or C

2.37

R:DLUA for DSU Conguration ABB-Modem


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0

MUT01

Fuse Panel F:DLU(A) for DSU MUT02 A Shelf 0 F:DLU(A) for DSU

MUT01

C A

Shelf 1 Shelf 2 F:DLU(B) for DSU MUT03

MUT02

C A

Shelf 1 Shelf 2 F:DLU(B) for DSU MUT03

C A

Shelf 3 Shelf 4 F:DLU(B) for DSU MUT05

Shelf 3

Shelf 5

Shelf 4 F:DLU(B) for DSU MUT05

C F:MODEM(D) MUT06

Shelf 5

F:MODEM(D) rack 8 ft.

MUT07

F:MODEM(D) rack 7 ft.

MUT06

90

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 01 05 11 15 02 06 12 16 03 07 13 17 04 14

MUT MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT05 MUT05 MUT05 MUT05 MUT06 MUT07

Unit F:DLU(A) / Shelf 0 F:DLU(A) / Shelf 0 F:DLU(A) / Shelf 1 F:DLU(A) / Shelf 1 F:DLU(B) / Shelf 2 F:DLU(B) / Shelf 2 F:DLU(B) / Shelf 3 F:DLU(B) / Shelf 3 F:DLU(B) / Shelf 4 F:DLU(B) / Shelf 4 F:DLU(B) / Shelf 5 F:DLU(B) / Shelf 5 F:MODEM(D) F:MODEM(D) A001, A058, A119

MOLOC

A010 - A052, A089 - A113 C001, C058, C119 C010 - C052, C089 - C113 A001, A119 A010 - A052, A071 - A113 C001, C119 C010 - C052, C071 - C113 A001, A119 A010 - A052, A071 - A113 C001, C119 C010 - C052, C071 - C113 X27 X27

Tab. 2.42

Fuse Assignment R:DLUA for DSU , Conguration ABB-Modem

A30828-X1160-M-2-7620

91

Construction

Maintenance Node

2.38

R:DLUB for DSU Conguration GEGE or F


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0 F:DLU(G) for DSU C A Shelf 1 Shelf 2 F:DLU(E) for DSU C Shelf 3

MUT01

MUT02 A

Fuse Panel Shelf 0 F:DLU(G) for DSU

MUT01

MUT02

MUT03

C A

Shelf 1 Shelf 2 F:DLU(E) for DSU MUT03

Shelf 0 F:DLU(G) for DSU MUT05

C A

Shelf 3 Shelf 0 F:DLU(G) for DSU MUT05

C A

Shelf 1 Shelf 2 F:DLU(E) for DSU MUT06

Shelf 1 Shelf 2 F:DLU(F) for DSU

Shelf 3 rack 8 ft.

MUT06

rack 7 ft.

FU 01 02

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(D) or F:DLU(G) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 3 A001 - A057 A068 - A121 A066 - A124

MOLOC

03 04 05 06 07 08 09 10 11

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A068 - A086 A123, A092 - A110 C001, C015 - C033

Tab. 2.43

Fuse Assignment R:DLUB for DSU, Conguration GEGE or F

92

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 12 13 14 18 19

MUT MUT03 MUT03 MUT03 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06 MUT06

Unit F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(D) or F:DLU(G) / Shelf 0 F:DLU(D) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(D) or F:DLU(G) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3

MOLOC C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001 - A057 A068 - A121 A066 - A124 C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A068 - A086 A123, A092 - A110 C001, C015 - C033 C008, C039 - C057 C116, C068 - C086 C123, C092 - C110

20 21 22 23 24 25 26 27 28 29 30 31

Tab. 2.43

Fuse Assignment R:DLUB for DSU, Conguration GEGE or F

A30828-X1160-M-2-7620

93

Construction

Maintenance Node

2.39

R:DLUB for DSU Conguration GE-Modem


Fuse Panel
FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel A Shelf 0

MUT01

Fuse Panel F:DLU(G) for DSU MUT02 A Shelf 0 F:DLU(G) for DSU

MUT01

C A

Shelf 1 Shelf 2 F:DLU(E) for DSU MUT03

MUT02

C A MUT05 C

Shelf 1 Shelf 2 F:DLU(E) for DSU MUT03

Shelf 3 F:MODEM(D)

Shelf 3 F:MODEM(D) F:MODEM(D) F:MODEM(D) F:MODEM(D) rack 7 ft. MUT05

F:MODEM(D)

MUT06

F:MODEM(D)

MUT07

MUT06 MUT07 MUT08

F:MODEM(D)

MUT08 MUT09

F:MODEM(D) rack 8 ft.

FU 01 02 03 04 05 06 07 08 09 10 11 12

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT03 MUT03

Unit F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 0 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(G) / Shelf 1 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 2 F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 A001 - A057 A066 - A124

MOLOC

C001, C015 - C033, C057 if MGB inserted C008, C039 - C057 C116, C068 - C086 C123, C092 - C110 A001, A015 - A033 A008, A039 - A057 A116, A068 - A086 A123, A092 - A110 C001, C015 - C033 C008, C039 - C057

Tab. 2.44

Fuse Assignment R:DLUB for DSU, Conguration GE-Modem

94

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 13 14 19 21 23 25 27

MUT MUT03 MUT03 MUT05 MUT06 MUT07 MUT08 MUT09

Unit F:DLU(E) / Shelf 3 F:DLU(E) / Shelf 3 F:MODEM(D) F:MODEM(D) F:MODEM(D) F:MODEM(D) F:MODEM(D) C116, C068 - C086 C123, C092 - C110 X27 X27 X27 X27 X27

MOLOC

Tab. 2.44

Fuse Assignment R:DLUB for DSU, Conguration GE-Modem

2.40

R:DSU/LTG
Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel C Shelf 0 F:DLU(A) for DSU or F:DLU(G) for DSU Shelf 1 F:MODEM(D)

MUT01

MUT02

MUT03 MUT04

F:LTGN

F:LTGG(A)

MUT05

F:DEV(F) FAN (B5681) FAN (B5681) rack 7 ft.

MUT10 MUT11 MUT12

FU 01

MUT MUT02 MUT02

Unit F:DLU(A) / Shelf 0 F:DLU(A) / Shelf 0 F:DLU(A) / Shelf 1 F:DLU(A) / Shelf 1

MOLOC

02

MUT02 MUT02

Tab. 2.45

Fuse Assignment R:DSU/LTG

A30828-X1160-M-2-7620

95

Construction

Maintenance Node

FU 03

MUT MUT02 MUT02

Unit F:DLU(A) / Shelf 2 F:DLU(G) / Shelf 2 F:DLU(A) / Shelf 3 F:DLU(G) / Shelf 3 F:DLU(A) / Shelf 4 F:DLU(A) / Shelf 4 F:DLU(A) / Shelf 5 F:DLU(A) / Shelf 5 F:MODEM(D) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGG(A) F:LTGG(A) F:DEV(F) F:DEV(F) FAN FAN A101 (left LTG) A123 (right LTG) MDD 1, MOD 1 MDD 0, MOD 0 X27

MOLOC

25

MUT02 MUT02

26

MUT02 MUT02

32 27 08 04 28 05 29 06 30 07 31

MUT02 MUT02 MUT03 MUT04 MUT04 MUT05 MUT05 MUT10 MUT10 MUT11 MUT12

Tab. 2.45

Fuse Assignment R:DSU/LTG

96

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.41

R:DSM
Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:MODEM(D) F:MODEM(D) F:MODEM(D) F:MODEM(D) F:MODEM(D) F:MODEM(D)

MUT01 MUT02 MUT03 MUT04

Fuse Panel F:MODEM(D) F:MODEM(D) F:MODEM(D) F:MODEM(D) F:MODEM(D) F:MODEM(D)

MUT01 MUT02 MUT03 MUT04 MUT06 MUT07 MUT08

MUT06 MUT07 MUT08

rack 8 ft.

rack 7 ft.

FU 01 02 03 04 05 06 MUT02 MUT03 MUT04 MUT06 MUT07 MUT08

MUT F:MODEM(D) F:MODEM(D) F:MODEM(D) F:MODEM(D) F:MODEM(D) F:MODEM(D)

Unit X27 X27 X27 X27 X27 X27

MOLOC

Tab. 2.46

Fuse Assignment R:DSM

A30828-X1160-M-2-7620

97

Construction

Maintenance Node

2.42

R:HTI/RTI
Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel

MUT01

Fuse Panel C F:RSU 4 MUT03

MUT01

C C F:RSU 3 MUT05

F:RSU 4

MUT03

F:RSU 2

MUT06 C F:RSU 3 MUT05

F:RSU 1

MUT08 C F:RSU 2 MUT06

F:RSU 1

MUT08

rack 8 ft.

rack 7 ft.

(1*) Basic frame F:RSU or extension F:RSU in a second R:HTI/RTI (2*) 1st extension frame F:RSU (3*) 2nd extension frame F:RSU (4*) 3rd extension frame F:RSU
FU 01, 03, 25, 27 02, 04, 26, 28 05, 06, 29, 30 07, 08, 31, 32 MUT03 MUT05 MUT06 MUT08 MUT F:RSU F:RSU F:RSU F:RSU Unit

Tab. 2.47

Fuse Assignment R:HTI/RTI

98

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.43

R:HTI/RTI with SDHI


Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 09 10 11 12 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel

MUT01

F:RSU 4

Fuse Panel MUT03

MUT01

F:RSU 4

MUT03

F:RSU 3

MUT05

F:RSU 3

MUT05

F:RSU 2

MUT06

F:RSU 2

MUT06

F:RSU 1

MUT08

F:RSU 1

MUT08

F:SDHI FAN (B5681) FAN (B5681) FILTER:FAN rack 8 ft.

MUT09 MUT12 MUT13 MUT14

F:SDHI FAN (B5681) FAN (B5681) FILTER:FAN rack 7 ft.

MUT09 MUT12 MUT13 MUT14

(1*) Basic frame F:RSU or extension F:RSU in a second R:HTI/RTI (2*) 1st extension frame F:RSU (3*) 2nd extension frame F:RSU (4*) 3rd extension frame F:RSU
FU 02, 03, 22, 23 04, 05, 24, 25 08, 09, 28, 29 10, 11, 30, 31 12, 32 07 27 MUT03 MUT05 MUT06 MUT08 MUT09 MUT12 MUT13 MUT F:RSU F:RSU F:RSU F:RSU F:SDHI FAN FAN Unit

Tab. 2.48

Fuse Assignment R:HTI/RTI with F:SDHI and FAN

A30828-X1160-M-2-7620

99

Construction

Maintenance Node

2.44

R:HTI/RTI with one F:LTGN


Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel C F:LTGN

MUT01 MUT02 Fuse Panel C F:LTGN MUT01 MUT02

F:RSU 3

MUT05 C F:RSU 3 MUT05

F:RSU 2

MUT06 C F:RSU 2 MUT06

F:RSU 1

MUT08 C F:RSU 1 MUT08

rack 8 ft.

rack 7 ft.

(1*) Basic frame F:RSU or extension F:RSU in a second R:HTI/RTI (2*) 1st extension frame F:RSU (3*) 2nd extension frame F:RSU
FU 01, 25 02, 04, 26, 28 05, 06, 29, 30 07, 08, 31, 32 MUT02 MUT05 MUT06 MUT08 MUT Unit F:LTGN(A), (B), (C) F:RSU F:RSU F:RSU

Tab. 2.49

Fuse Assignment R:HTI/RTI with one F:LTGN

100

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.45

R:HTI/RTI with SDHI and one F:LTGN


Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 09 10 11 12 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel C F:LTGN

MUT01 MUT02 Fuse Panel C F:LTGN MUT01 MUT02

F:RSU 3

MUT05

F:RSU 3

MUT05

F:RSU 2

MUT06

F:RSU 2

MUT06

F:RSU 1

MUT08

F:RSU 1

MUT08

F:SDHI FAN (B5681) FAN (B5681) FILTER:FAN rack 8 ft.

MUT09 MUT12 MUT13 MUT14

F:LTGN FAN (B5681) FAN (B5681) FILTER:FAN rack 7 ft.

MUT09 MUT12 MUT13 MUT14

(1*) Basic frame F:RSU or extension F:RSU in a second R:HTI/RTI (2*) 1st extension frame F:RSU (3*) 2nd extension frame F:RSU
FU 01, 21 04, 05, 24, 25 08, 09, 28, 29 10, 11, 30, 31 12, 32 07 27 MUT02 MUT05 MUT06 MUT08 MUT09 MUT12 MUT13 MUT Unit F:LTGN(A), (B), (C) F:RSU F:RSU F:RSU F:SHDI FAN FAN

Tab. 2.50

Fuse Assignment R:HTI/RTI with one F:LTGN, SDHI and FAN

A30828-X1160-M-2-7620

101

Construction

Maintenance Node

2.46

R:HTI/RTI with two F:LTGN


Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel C F:LTGN

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGN

MUT03 C F:LTGN

F:LTGN

MUT03

F:RSU 2

MUT06 C F:RSU 2 MUT06

F:RSU 1

MUT08 C F:RSU 1 MUT08

rack 8 ft.

rack 7 ft.

(1*) Basic frame F:RSU or extension F:RSU in a second R:HTI/RTI (2*) 1st extension frame F:RSU
FU 01, 25 02, 26 05, 06, 29, 30 07, 08, 31, 32 MUT02 MUT03 MUT06 MUT08 MUT F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:RSU F:RSU Unit

Tab. 2.51

Fuse Assignment R:HTI/RTI with two F:LTGN

102

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.47

R:HTI/RTI with SDHI and two F:LTGN


Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 09 10 11 12 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel C F:LTGN

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGN

MUT03 C

F:LTGN

F:LTGN

MUT03

F:RSU 2

MUT06

F:RSU 2

MUT06

F:RSU 1

MUT08

F:RSU 1

MUT08

F:SDHI FAN (B5681) FAN (B5681) FILTER:FAN rack 8 ft.

MUT09 MUT12 MUT13 MUT14

F:SDHI FAN (B5681) FAN (B5681) FILTER:FAN rack 7 ft.

MUT09 MUT12 MUT13 MUT14

(1*) Basic frame F:RSU or extension F:RSU in a second R:HTI/RTI (2*) 1st extension frame F:RSU
FU 01, 21 03, 23 08, 09, 28, 29 10, 11, 30, 31 12, 32 07 27 MUT02 MUT03 MUT06 MUT08 MUT09 MUT12 MUT13 MUT F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:RSU F:RSU F:SDHI FAN FAN Unit

Tab. 2.52

Fuse Assignment R:HTI/RTI with two F:LTGN, SDHI and FAN

A30828-X1160-M-2-7620

103

Construction

Maintenance Node

2.48

R:HTI/RTI with three F:LTGN


Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel C F:LTGN

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGN

MUT03 C F:LTGN

C C F:LTGN MUT05 C

F:LTGN

MUT03

F:LTGN

MUT05

F:RSU 1

MUT08 C F:RSU 1 MUT08

rack 8 ft.

rack 7 ft.

(1*) Basic frame F:RSU or extension F:RSU in a second R:HTI/RTI


FU 01, 25 02, 26 03, 27 07, 08, 31, 32 MUT02 MUT03 MUT05 MUT08 MUT Unit F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:RSU

Tab. 2.53

Fuse Assignment R:HTI/RTI with three F:LTGN

104

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.49

R:HTI/RTI with SDHI and three F:LTGN


Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 09 10 11 12 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel C F:LTGN

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGN

MUT03 C

F:LTGN

C C F:LTGN MUT05 C

F:LTGN

MUT03

F:LTGN

MUT05

F:RSU 1

MUT08

F:RSU 1

MUT08

F:SDHI FAN (B5681) FAN (B5681) FILTER:FAN rack 8 ft.

MUT09 MUT12 MUT13 MUT14

F:SDHI FAN (B5681) FAN (B5681) FILTER:FAN rack 7 ft.

MUT09 MUT12 MUT13 MUT14

(1*) Basic frame F:RSU or extension F:RSU in a second R:HTI/RTI


FU 01, 21 03, 23 05, 25 10, 11, 30, 31 12, 32 07 27 MUT02 MUT03 MUT05 MUT08 MUT09 MUT12 MUT13 MUT Unit F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:RSU F:SDHI FAN FAN

Tab. 2.54

Fuse Assignment R:HTI/RTI with three F:LTGN, SDHI and FAN

A30828-X1160-M-2-7620

105

Construction

Maintenance Node

2.50

R:LTGB
Fuse Panel
FU 01 03 05 07 09 06 07 08 09 10 11 12 13 14 FU-A

FU FU

01 02

03 05 04 06

07 08

09 10

11 12

13 14

15 16

17 18

19 20

FU FU FU-N

Fuse Panel A F:LTGB(A) C A F:LTGB(A) C

MUT01

MUT02

MUT03

A F:LTGB(A) C A F:LTGB(A) C rack 8 ft. MUT06 MUT05

FU-A 03 01 02 06 04 05 09 07 08 12

FU-N 03 01 02 13 11 12 06 04 05 16 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT05 MUT05 MUT05 MUT06

MUT

Unit F:LTGB(A) 0 F:LTGB(A) 0 F:LTGB(A) 0 F:LTGB(A) 1 F:LTGB(A) 1 F:LTGB(A) 1 F:LTGB(A) 2 F:LTGB(A) 2 F:LTGB(A) 2 F:LTGB(A) 3

MOLOC Supply voltage for all LTU C001, C013 C103, C115 Supply voltage for all LTU C001, C013 C103, C115 Supply voltage for all LTU C001, C013 C103, C115 Supply voltage for all LTU

Tab. 2.55

Fuse Assignment R:LTGB

106

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU-A 10 11

FU-N 14 15 MUT06 MUT06

MUT

Unit F:LTGB(A) 3 F:LTGB(A) 3 C001, C013 C103, C115

MOLOC

Tab. 2.55

Fuse Assignment R:LTGB

2.51

R:LTGC
Fuse Panel
FU 01 03 05 07 09 06 07 08 09 10 11 12 13 14 FU-A

FU FU

01 02

03 05 04 06

07 08

09 10

11 12

13 14

15 16

17 18

19 20

FU FU FU-N

Fuse Panel

MUT01

F:LTGC(A)

MUT02

F:LTGC(A)

MUT03

F:LTGC(A)

MUT04

F:LTGC(A)

MUT05

F:LTGC(A)

MUT06

F:LTGC(A)

MUT07

rack 8 ft.

FU-A 01 02 03 04

FU-N 01 02 03 11 MUT02 MUT03 MUT04 MUT05

MUT

Unit F:LTGC(A) 0 F:LTGC(A) 1 F:LTGC(A) 2 F:LTGC(A) 3 A001, A115 A001, A115 A001, A115 A001, A115

MOLOC

Tab. 2.56

Fuse Assignment R:LTGC

A30828-X1160-M-2-7620

107

Construction

Maintenance Node

FU-A 05 06

FU-N 12 13 MUT06 MUT07

MUT

Unit F:LTGC(A) 4 F:LTGC(A) 5 A001, A115 A001, A115

MOLOC

Tab. 2.56

Fuse Assignment R:LTGC

2.52

R:LTGC/CR
Fuse Panel
FU 01 03 05 07 09 06 07 08 09 10 11 12 13 14 FU-A

FU FU

01 02

03 05 04 06

07 08

09 10

11 12

13 14

15 16

17 18

19 20

FU FU FU-N

Fuse Panel

MUT01

F:LTGC(A) 0

MUT02

*
A F:CR(A) 0 F:CR(A) 1 MUT03

F:LTGC(A) 1

MUT04

F:LTGC(A) 2

MUT05

*
*): Half of module frame A F:CR(A) belongs to the LTGC above it, other half to the LTGC below it, and each half is electriA cally connected to the relevant LTGC F:CR(A) 2 F:CR(A) 3 MUT06

F:LTGC(A) 3

MUT07

rack 8 ft.

FU-A 01

FU-N 01 MUT02 MUT03

MUT

Unit F:LTGC(A) 0 F:CR(A) 0 F:LTGC(A) 1 F:CR(A) 1 A001, A115 A001 A001, A115 A115

MOLOC

02

03

MUT04 MUT03

Tab. 2.57

Fuse Assignment R:LTGC/CR

108

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU-A 03

FU-N 11 MUT05 MUT06

MUT

Unit F:LTGC(A) 2 F:CR(A) 2 F:LTGC(A) 3 F:CR(A) 3 A001, A115 A001 A001, A115 A115

MOLOC

04

13

MUT07 MUT06

Tab. 2.57

Fuse Assignment R:LTGC/CR

2.53

R:LTGD
Fuse Panel
FU 01 03 05 07 09 06 07 08 09 10 11 12 13 14 FU-A

FU FU

01 02

03 05 04 06

07 08

09 10

11 12

13 14

15 16

17 18

19 20

FU FU FU-N

Fuse Panel

MUT01

F:CRES(A)

MUT02

F:LTGD(A)

MUT03

F:CRES(A)

MUT04

F:CRES(A)

MUT05

F:LTGD(A)

MUT06

F:CRES(A)

MUT07

rack 8 ft.

FU-A 01 02

FU-N 01 02 MUT02 MUT02

MUT

Unit F:CRES(A) 0 F:CRES(A) 0 A001 A115

MOLOC

Tab. 2.58

Fuse Assignment R:LTGD

A30828-X1160-M-2-7620

109

Construction

Maintenance Node

FU-A 03 04 05 06 07 08 09 10

FU-N 03 05 06 11 12 13 15 16 MUT03 MUT04 MUT04 MUT05 MUT05 MUT06 MUT07 MUT07

MUT

Unit F:LTGD(A) 0 F:CRES(A) 1 F:CRES(A) 1 F:CRES(A) 2 F:CRES(A) 2 F:LTGD(A) 1 F:CRES(A) 3 F:CRES(A) 3 A001, A115 A001 A115 A001 A115 A001, A115 A001 A115

MOLOC

Tab. 2.58

Fuse Assignment R:LTGD

2.54

R:LTGF
Fuse Panel
FU FU 01 02 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

Fuse Panel

MUT01

F:LTGF(A)

MUT02

F:LTGF(A)

MUT03

F:LTGF(A)

MUT04

F:LTGF(A)

MUT05

F:LTGF(A)

MUT06

F:LTGF(A)

MUT07

rack 8 ft.

110

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 01 02 03 11 12 13

MUT MUT02 MUT03 MUT04 MUT05 MUT06 MUT07 F:LTGF(A) 0 F:LTGF(A) 1 F:LTGF(A) 2 F:LTGF(A) 3 F:LTGF(A) 4 F:LTGF(A) 5

Unit A117 A117 A117 A117 A117 A117

MOLOC

Tab. 2.59

Fuse Assignment R:LTGF

2.55

R:LTGG
Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:LTGG(A)

MUT01 MUT02 Fuse Panel MUT01

F:LTGG(A)

MUT03

F:LTGG(A)

MUT02

F:LTGG(A)

MUT04

F:LTGG(A)

MUT03

F:LTGG(A) F:LTGG(A) MUT05

MUT04

F:LTGG(A)

MUT06

F:LTGG(A)

MUT05

F:LTGG(A)

MUT06

rack 8 ft.

rack 7 ft.

A30828-X1160-M-2-7620

111

Construction

Maintenance Node

FU 01 02 11 12 03 04 13 14 05 06 MUT02 MUT02 MUT03 MUT03 MUT04 MUT04 MUT05 MUT05 MUT06 MUT06

MUT

Unit F:LTGG(A) 0 F:LTGG(A) 0 F:LTGG(A) 1 F:LTGG(A) 1 F:LTGG(A) 2 F:LTGG(A) 2 F:LTGG(A) 3 F:LTGG(A) 3 F:LTGG(A) 4 F:LTGG(A) 4 A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG)

MOLOC

Tab. 2.60

Fuse Assignment R:LTGG

2.56

R:LTGG with LTGH


Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:LTGG(A)

MUT01 MUT02 Fuse Panel MUT01

F:LTGG(A)

MUT03

F:LTGG(A)

MUT02

F:LTGG(A)

MUT04

F:LTGG(A)

MUT03

F:LTGG(A) F:LTGG(A) MUT05

MUT04

F:LTGG(A) F:LTGH(A) MUT07

MUT05

F:LTGH(A)

MUT06

rack 8 ft.

rack 7 ft.

112

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 01 02 11 12 03 04 13 14 15 16 MUT02 MUT02 MUT03 MUT03 MUT04 MUT04 MUT05 MUT05 MUT07 MUT07

MUT F:LTGG(A) 0 F:LTGG(A) 0 F:LTGG(A) 1 F:LTGG(A) 1 F:LTGG(A) 2 F:LTGG(A) 2 F:LTGG(A) 3 F:LTGG(A) 3 F:LTGH(A) 4 F:LTGH(A) 4

Unit A001 (left LTG)

MOLOC

A123 (right LTG) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG)

Tab. 2.61

Fuse Assignment R:LTGG/H

A30828-X1160-M-2-7620

113

Construction

Maintenance Node

2.57

R:LTGM
Fuse Panel FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:LTGM(A)

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGM(A)

MUT03

F:LTGM(A)

F:LTGM(A)

MUT04

F:LTGM(A)

MUT03

F:LTGM(A) F:LTGM(A) MUT05

MUT04

F:LTGM(A)

MUT06

F:LTGM(A)

MUT06

F:LTGM(A) F:LTGM(A) MUT07

MUT07

rack 8 ft.

rack 7 ft.

FU 01 02 03 04 05 19 20 21 22 23 06

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT04

Unit F:LTGM(A) 0 F:LTGM(A) 0 F:LTGM(A) 0 F:LTGM(A) 0 F:LTGM(A) 0 F:LTGM(A) 1 F:LTGM(A) 1 F:LTGM(A) 1 F:LTGM(A) 1 F:LTGM(A) 1 F:LTGM(A) 2 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0

MOLOC

Tab. 2.62

Fuse Assignment R:LTGM

114

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 07 08 09 10 24 25 26 27 28 11 12 13 14 15 29 30 31 32 33

MUT MUT04 MUT04 MUT04 MUT04 MUT05 MUT05 MUT05 MUT05 MUT05 MUT06 MUT06 MUT06 MUT06 MUT06 MUT07 MUT07 MUT07 MUT07 MUT07

Unit F:LTGM(A) 2 F:LTGM(A) 2 F:LTGM(A) 2 F:LTGM(A) 2 F:LTGM(A) 3 F:LTGM(A) 3 F:LTGM(A) 3 F:LTGM(A) 3 F:LTGM(A) 3 F:LTGM(A) 4 F:LTGM(A) 4 F:LTGM(A) 4 F:LTGM(A) 4 F:LTGM(A) 4 F:LTGM(A) 5 F:LTGM(A) 5 F:LTGM(A) 5 F:LTGM(A) 5 F:LTGM(A) 5 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4

MOLOC

Tab. 2.62

Fuse Assignment R:LTGM

A30828-X1160-M-2-7620

115

Construction

Maintenance Node

2.58

R:LTGM with DLUV


Fuse Panel FU 01 03 05 07 09 11 13 15 17 Panel Fuse 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel F:LTGM(A)

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGM(A)

MUT03

F:LTGM(A)

F:LTGM(A)

MUT04

F:LTGM(A)

MUT03

F:LTGM(A) F:LTGM(A) MUT06

MUT04

F:LTGM(A) F:DLUV(A) MUT07

MUT06

F:DLUV(A)

MUT07

rack 8 ft.

rack 7 ft.

FU 01 02 03 04 05 19 20 21 22 23 06 MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT04

MUT

Unit F:LTGM(A) 0 F:LTGM(A) 0 F:LTGM(A) 0 F:LTGM(A) 0 F:LTGM(A) 0 F:LTGM(A) 1 F:LTGM(A) 1 F:LTGM(A) 1 F:LTGM(A) 1 F:LTGM(A) 1 F:LTGM(A) 2 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0

MOLOC

Tab. 2.63

Fuse Assignment R:LTGM/DLUV

116

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 07 08 09 10 24 25 26 27 28 16 MUT04 MUT04 MUT04 MUT04 MUT05 MUT05 MUT05 MUT05 MUT05 MUT07

MUT

Unit F:LTGM(A) 2 F:LTGM(A) 2 F:LTGM(A) 2 F:LTGM(A) 2 F:LTGM(A) 3 F:LTGM(A) 3 F:LTGM(A) 3 F:LTGM(A) 3 F:LTGM(A) 3 F:DLUV(A) C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4

MOLOC

C123 Supply voltage for DLUV0, DLUV1, DLUV2, DLUV3 C187 Supply voltage for DLUV4, DLUV5, DLUV6, DLUV7 C251 Supply voltage for DLUV8, DLUV9, DLUV10, DLUV11 C313 Supply voltage for DLUV12, DLUV13, DLUV14, DLUV15

17

MUT07

F:DLUV(A)

32

MUT07

F:DLUV(A)

33

MUT07

F:DLUV(A)

Tab. 2.63

Fuse Assignment R:LTGM/DLUV

A30828-X1160-M-2-7620

117

Construction

Maintenance Node

2.59

R:LTGM with LTGG and DLUV


Fuse Panel FU 01 03 05 07 09 11 13 15 17 Panel Fuse 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel F:LTGM(A)

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGM(A)

MUT03

F:LTGM(A)

F:LTGM(A)

MUT04

F:LTGM(A)

MUT03

F:LTGM(A) F:LTGG(A) MUT06

MUT04

F:LTGG(A) F:DLUV(A) MUT07

MUT06

F:DLUV(A)

MUT07

rack 8 ft.

rack 7 ft.

FU 01 02 03 04 05 19 20 21 22 23 06

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT04

Unit F:LTGM(A) 0 F:LTGM(A) 0 F:LTGM(A) 0 F:LTGM(A) 0 F:LTGM(A) 0 F:LTGM(A) 1 F:LTGM(A) 1 F:LTGM(A) 1 F:LTGM(A) 1 F:LTGM(A) 1 F:LTGM(A) 2 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0

MOLOC

Tab. 2.64

Fuse Assignment R:LTGM/LTGG/DLUV

118

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 07 08 09 10 12 18 16 17 32 33

MUT MUT04 MUT04 MUT04 MUT04 MUT06 MUT06 MUT07 MUT07 MUT07 MUT07

Unit F:LTGM(A) 2 F:LTGM(A) 2 F:LTGM(A) 2 F:LTGM(A) 2 F:LTGG(A) F:LTGG(A) F:DLUV(A F:DLUV(A F:DLUV(A F:DLUV(A C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 A101 (left LTG) A123 (right LTG)

MOLOC

C123 Supply voltage for DLUV0, DLUV1, DLUV2, DLUV3 C187 Supply voltage for DLUV4, DLUV5, DLUV6, DLUV7 C251 Supply voltage for DLUV8, DLUV9, DLUV10, DLUV11 C313 Supply voltage for DLUV12, DLUV13, DLUV14, DLUV15

Tab. 2.64

Fuse Assignment R:LTGM/LTGG/DLUV

2.60

R:LTGM with LTGG and LTGH


Fuse Panel FU 01 03 05 07 09 11 13 15 17 Panel Fuse 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel F:LTGM(A)

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGM(A)

MUT03

F:LTGM(A)

F:LTGM(A)

MUT04

F:LTGM(A)

MUT03

F:LTGM(A)

MUT04

F:LTGG(A)

MUT06 F:LTGG(A) MUT06

F:LTGH(A)

MUT07 F:LTGH(A) MUT07

rack 8 ft.

rack 7 ft.

A30828-X1160-M-2-7620

119

Construction

Maintenance Node

FU 01 02 03 04 05 19 20 21 22 23 06 07 08 09 10 12 18 17 33

MUT MUT02 MUT02 MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT04 MUT04 MUT04 MUT04 MUT04 MUT06 MUT06 MUT07 MUT07

Unit F:LTGM(A) 0 F:LTGM(A) 0 F:LTGM(A) 0 F:LTGM(A) 0 F:LTGM(A) 0 F:LTGM(A) 1 F:LTGM(A) 1 F:LTGM(A) 1 F:LTGM(A) 1 F:LTGM(A) 1 F:LTGM(A) 2 F:LTGM(A) 2 F:LTGM(A) 2 F:LTGM(A) 2 F:LTGM(A) 2 F:LTGG(A) F:LTGG(A) F:LTGH(A) F:LTGH(A) C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 A101 (left LTG) A123 (right LTG) A101 (left LTG) A123 (right LTG)

MOLOC

Tab. 2.65

Fuse Assignment R:LTGM/G/H

120

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.61

R:LTGN
Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGN

MUT03 F:LTGN

F:LTGN

MUT04 F:LTGN MUT03

F:LTGN F:LTGN MUT05 F:LTGN

MUT04

MUT05

F:LTGP or F:STMI FAN-BOX (U2624)

MUT07

F:LTGP or F:STMI FAN-BOX (U2624)

MUT07

MUT13

MUT13

rack 8 ft.

rack 7 ft.

FU 01, 25 02, 26 03, 27 05, 29 06, 30 07, 31 MUT02 MUT03 MUT04 MUT07 MUT07 MUT13

MUT F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C)

Unit

F:LTGP/F:STMI / C151 X1/X2, C121 X1/X2 (LTG 1-16) F:LTGP/F:STMI / C281 X1/X2, C151 X1/X2 (LTG 17-32) FAN-BOX (U2624)

Tab. 2.66

Fuse Assignment R:LTGN

A30828-X1160-M-2-7620

121

Construction

Maintenance Node

2.62

R:LTGN with LTGG or LTGH


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGN

MUT03 F:LTGN

F:LTGN

MUT04 F:LTGN MUT03

F:LTGN

MUT04

F:LTGG(A) / F:LTGH(A)

MUT07

F:LTGG(A) / F:LTGH(A)

MUT07

rack 8 ft.

rack 7 ft.

FU 01, 25 02, 26 03, 27 06 30 MUT02 MUT03 MUT04 MUT07 MUT07

MUT

Unit F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C)

MOLOC

A001 (left LTG) A123 (right LTG)

Tab. 2.67

Fuse Assignment R:LTGN (with LTGG or LTGH)

122

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.63

R:LTGN with F:SDHI and FAN


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGN

MUT03 F:LTGN

F:LTGN

MUT04

F:LTGN

MUT03

F:LTGN F:LTGN MUT05

MUT04

F:LTGN

MUT05

F:SDHI FAN (B5681) FAN (B5681) FILTER:FAN rack 8 ft.

MUT07 MUT12 MUT13 MUT14

F:SDHI FAN (B5681) FAN (B5681) FILTER:FAN rack 7 ft.

MUT07 MUT12 MUT13 MUT14

FU 01, 25 02, 26 03, 27 04, 28 06, 30 07 31 MUT02 MUT03 MUT04 MUT05 MUT07 MUT12 MUT13

MUT F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:SDHI2 or F:SDHI4 FAN FAN

Unit

Tab. 2.68

Fuse Assignment R:LTGN with F:SDHI and FAN

A30828-X1160-M-2-7620

123

Construction

Maintenance Node

2.64

R:LTGN with F:SDHI without FAN


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGN

MUT03 F:LTGN

F:LTGN

MUT04

F:LTGN

MUT03

F:LTGN

MUT04

F:SDHI

MUT07

F:SDHI

MUT07

rack 8 ft.

rack 7 ft.

FU 01, 25 02, 26 03, 27 06, 30 MUT02 MUT03 MUT04 MUT07

MUT F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:SDHI2 or F:SDHI4

Unit

Tab. 2.69

Fuse Assignment R:LTGN with F:SDHI without FAN

124

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.65

R:LTGN with DLUV


R:LTGN with one F:DLUV(A)
Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02

Fuse Panel F:LTGN

MUT01 MUT02

F:DLUV(A)

MUT03

F:LTGN

MUT04

F:DLUV(A)

MUT03

F:LTGN

MUT04

F:LTGN

MUT05

F:LTGN

MUT05

F:LTGP or F:STMI FAN-BOX (U2624) rack 8 ft.

MUT07

F:LTGP or F:STMI FAN-BOX (U2624) rack 7 ft.

MUT07

MUT13

MUT13

FU 01, 25 02 05 26 29 03, 27 04, 28 05,29 06, 30 07, 31

MUT MUT02 MUT03 MUT03 MUT03 MUT03 MUT04 MUT05 MUT08 MUT08 MUT13

Unit F:LTGN(A), (B), (C) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGP/F:STMI F:LTGP/F:STMI FAN-BOX

MOLOC

C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15

C151 X1/X2, C121 X1/X2 (LTG1-16) C281 X1/X2, C251 X1/X2 (LTG17-32) X1/X2 - X6/X7

Tab. 2.70

Fuse Assignment R:LTGN/1F:DLUV

A30828-X1160-M-2-7620

125

Construction

Maintenance Node

R:LTGN with two F:DLUV(A)

Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02

Fuse Panel F:LTGN

MUT01 MUT02

F:DLUV(A)

MUT03

F:LTGN

MUT04

F:DLUV(A)

MUT03

F:DLUV(A)

MUT10

F:LTGN

MUT04

F:DLUV(A)

MUT10

rack 8 ft.

rack 7 ft.

FU 01, 25 02 05 26 29 03, 27 06 07 31 30

MUT MUT02 MUT03 MUT03 MUT03 MUT03 MUT04 MUT10 MUT10 MUT10 MUT10

Unit F:LTGN(A), (B), (C) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:LTGN(A), (B), (C) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A)

MOLOC

C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15

C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15

Tab. 2.71

Fuse Assignment R:LTGN/2 F:DLUV

126

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.66

R:LTGN with DLUV and LTGG or LTGH


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02

Fuse Panel F:LTGN

MUT01 MUT02

F:DLUV(A)

MUT03

F:LTGN

MUT04

F:DLUV(A)

MUT03

F:LTGN

MUT04

F:LTGG(A) / F:LTGH(A)

MUT07

F:LTGG(A) / F:LTGH(A)

MUT07

rack 8 ft.

rack 7 ft.

FU 01, 25 02 05 26 29 03, 27 06 30

MUT MUT02 MUT03 MUT03 MUT03 MUT03 MUT04 MUT07 MUT07

Unit F:LTGN(A), (B), (C) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C)

MOLOC

C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15

A001 (left LTG) A123 (right LTG)

Tab. 2.72

Fuse Assignment R:LTGN/DLUV/LTGG or LTGH

A30828-X1160-M-2-7620

127

Construction

Maintenance Node

2.67

R:LTGN with TSG, cabling from above


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:TSG(B) 0

MUT01 MUT02

Fuse Panel F:TSG(B) 0

MUT01 MUT02

F:TSG(B) 1

MUT03

F:LTGN

MUT04

F:TSG(B) 1

MUT03

F:LTGN

MUT04

F:LTGN

MUT05

F:LTGN

MUT05

F:LTGN

MUT06 #

F:LTGN

MUT06 #

F:LTGP or F:STMI FAN-BOX (U2624)

MUT07

F:LTGP or F:STMI FAN-BOX (U2624) rack 7 ft.

MUT07

MUT13

MUT13

rack 8 ft. # MUT06 is empty if F:LTGP or F:STMI are installed in MUT07

FU 01 25 03, 27 04, 28 05, 29 05, 29 06, 30 07, 31

MUT MUT02 MUT03 MUT04 MUT05 MUT06 MUT07 MUT07 MUT13

Unit F:TSG(B) F:TSG(B) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGP/F:STMI F:LTGP/F:STMI FAN-BOX

MOLOC C331 / TSG 0-x C331 / TSG 1-x

C151 X1/X2, C121 X1/X2 (LTG1-16) C281 X1/X2, C251 X1/X2 (LTG17-32) X1/X2 -X6/X7

Tab. 2.73

Fuse Assignment R:LTGN/TSG (cabling from above)

128

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.68

R:LTGN with TSG, cabling from below


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02

Fuse Panel F:LTGN

MUT01 MUT02

F:LTGN

MUT03

F:LTGN

MUT04

F:LTGN

MUT03

F:LTGN

MUT04

F:TSG(B) 0

MUT06

F:TSG(B) 0 F:TSG(B) 1

MUT06

F:TSG(B) 1

MUT07

MUT07

rack 8 ft.

rack 7 ft.

FU 01, 25 02, 26 03, 27 05 29 MUT02 MUT03 MUT04 MUT06 MUT07

MUT

Unit F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:TSG(B) F:TSG(B)

MOLOC

C331 / TSG 0-x C331 / TSG 1-x

Tab. 2.74

Fuse Assignment R:LTGN/TSG (cabling from below)

A30828-X1160-M-2-7620

129

Construction

Maintenance Node

2.69

R:LTGN with TSG and MB/CCG, cabling from above


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:TSG(B) 0

MUT01 MUT02

Fuse Panel F:TSG(B) 0 F:TSG(B)

MUT01 MUT02

F:TSG(B)

MUT03

F:MB/CCG(B) 0

MUT04 MUT05

MUT03

F:MB/CCG(B) 1

F:MB/CCG(B) 0

MUT04

F:MB/CCG(B) 1

MUT05

F:LTGN

MUT06 #

F:LTGP or F:STMI FAN-BOX (U2624) rack 8 ft.

MUT07

F:LTGP or F:STMI or F:LTGN FAN-BOX (U2624)

MUT07

MUT13

MUT13

rack 7 ft.

# MUT06 is empty if F:LTGP or F:STMI are installed in MUT07

FU 01 25 03 04 27 28 05, 29 06, 30 05, 29 06, 30 07, 31

MUT MUT02 MUT03 MUT04 MUT04 MUT05 MUT05 MUT06 MUT07 MUT07 MUT07 MUT13 F:TSG(B) F:TSG(B)

Unit

MOLOC C331/ TSG 0-x C331/ TSG 1-x A001 (MB 0) A121 (CCG 0) A001 (MB 1) A121 (CCG 1)

F:MB/CCG(B) F:MB/CCG(B) F:MB/CCG(B) F:MB/CCG(B) F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGP/F:STMI F:LTGP/F:STMI FAN-BOX

C151 X1/X2, C121 X1/X2 (LTG1-16) C281 X1/X2, C251 X1/X2 (LTG17-32) X1/X2 - X6/X7

Tab. 2.75

Fuse Assignment R:LTGN/TSG/MB/CCG (cabling from above)

130

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.70

R:LTGN with TSG and MB/CCG, cabling from below

Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02

Fuse Panel F:LTGN

MUT01 MUT02

F:MB/CCG(B) 0

MUT04 F:MB/CCG(B) 0 MUT04

F:MB/CCG(B) 1

MUT05

F:MB/CCG(B) 1

MUT05

F:TSG(B) 0 F:TSG(B) 1

MUT06

F:TSG(B) 0 F:TSG(B) 1

MUT06

MUT07

MUT07

rack 8 ft.

rack 7 ft.

FU 01, 25 03 04 27 28 05 29 MUT02 MUT04 MUT04 MUT05 MUT05 MUT06 MUT07

MUT

Unit F:LTGN(A), (B), (C) F:MB/CCG(B) F:MB/CCG(B) F:MB/CCG(B) F:MB/CCG(B) F:TSG(B) F:TSG(B) A001 (MB) A121 (CCG) A001 (MB) A121 (CCG)

MOLOC

C331 / TSG 0-x C331 / TSG 1-x

Tab. 2.76

Fuse Assignment R:LTGN/TSG/MB/CCG (cabling from below)

A30828-X1160-M-2-7620

131

Construction

Maintenance Node

2.71

R:LTGN with SSG, cabling from above


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:SSG(B) 0

MUT01 MUT02

Fuse Panel F:SSG(B) 0

MUT01 MUT02

F:SSG(B) 1

MUT03

F:LTGN

MUT04

F:SSG(B) 1

MUT03

F:LTGN

MUT04

F:LTGN

MUT05

F:LTGN

MUT05

F:LTGP or F:STMI FAN-BOX (U2624)

MUT07

F:LTGP or F:STMI FAN-BOX (U2624) rack 7 ft.

MUT07

MUT13

MUT13

rack 8 ft.

FU 01 02 25 26 03, 27 04, 28 05, 29 06, 30 07, 31 MUT02 MUT02 MUT03 MUT03 MUT04 MUT05 MUT07 MUT07 MUT13

MUT F:SSG(B) F:SSG(B) F:SSG(B) F:SSG(B)

Unit

MOLOC C101 (SSG-0-0 or SSG-0-2) C331 (SSG-0-1 or SSG-0-3) C101 (SSG-1-0 or SSG-1-2) C331 (SSG-1-0 or SSG-1-3)

F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:LTGP/F:STMI F:LTGP/F:STMI FAN-BOX C151 X1/X2, C121 X1/X2 (LTG1-16) C281 X1/X2, C251 X1/X2 (LTG17-32) X1/X2 - X6/X7

Tab. 2.77

Fuse Assignment R:LTGN/SSG (cabling from above)

132

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.72

R:LTGN with SSG, cabling from below


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02

Fuse Panel F:LTGN

MUT01 MUT02

F:LTGN

MUT03

F:LTGN

MUT03

F:SSG(B) 0

MUT06

F:SSG(B) 0

MUT06

F:SSG(B) 1

MUT07

F:SSG(B) 1

MUT07

rack 8 ft.

rack 7 ft.

FU 01, 25 02, 26 05 06 29 30 MUT02 MUT03 MUT06 MUT06 MUT07 MUT07

MUT

Unit F:LTGN(A), (B), (C) F:LTGN(A), (B), (C) F:SSG(B) F:SSG(B) F:SSG(B) F:SSG(B)

MOLOC

C101 (SSG-0-0 or SSG-0-2) C331 (SSG-0-1 or SSG-0-3) C101 (SSG-1-0 or SSG-1-2) C331 (SSG-1-0 or SSG-1-3)

Tab. 2.78

Fuse Assignment R:LTGN/SSG (cabling from below)

A30828-X1160-M-2-7620

133

Construction

Maintenance Node

2.73

R:LTGN with SSG and MB/CCG, cabling from above


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:SSG(B) 0

MUT01 MUT02

Fuse Panel F:SSG(B) 0

MUT01 MUT02

F:SSG(B) 1

MUT03

F:MB/CCG(B) 0

MUT04

F:SSG(B) 1

MUT03

F:MB/CCG(B) 1

MUT05

F:MB/CCG(B) 0

MUT04

F:MB/CCG(B) 1

MUT05

F:LTGP or F:STMI FAN-BOX (U2624) rack 8 ft.

MUT07

F:LTGP or F:STMI FAN-BOX (U2624) rack 7 ft.

MUT07

MUT13

MUT13

FU 01 02 25 26 03 04 27 28 05, 29 06, 30 07, 31 MUT02 MUT02 MUT03 MUT03 MUT04 MUT04 MUT05 MUT05 MUT07 MUT07 MUT13

MUT

Unit F:SSG(B) F:SSG(B) F:SSG(B) F:SSG(B) F:MB/CCG(B) F:MB/CCG(B) F:MB/CCG(B) F:MB/CCG(B) F:LTGP/F:STMI F:LTGP/F:STMI FAN-BOX

MOLOC C101 (SSG-0-0 or SSG-0-2) C331 (SSG-0-1 or SSG-0-3) C101 (SSG-1-0 or SSG-1-2) C331 (SSG-1-0 or SSG-1-3) A001 (MB 0) A121 (CCG 0) A001 (MB 1) A121 (CCG 1) C151 X1/X2, C121 X1/X2 (LTG1-16) C281 X1/X2, C251 X1/X2 (LTG17-32) X1/X2 - X6/X7

Tab. 2.79

Fuse Assignment R:LTGN/TSG/MB/CCG (cabling from above)

134

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.74

R:LTGN with SSG and MB/CCG, cabling from below


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel

MUT01

Fuse Panel

MUT01

F:MB/CCG(B) 0

MUT04 MUT04

F:MB/CCG(B) 1

MUT05

F:MB/CCG(B) 0

F:MB/CCG(B) 1

MUT05

F:SSG(B) 0

MUT06

F:SSG(B) 0

MUT06

F:SSG(B) 1

MUT07

F:SSG(B) 1

MUT07

rack 8 ft.

rack 7 ft.

FU 03 04 27 28 05 06 29 30

MUT MUT04 MUT04 MUT05 MUT05 MUT06 MUT06 MUT07 MUT07

Unit F:MB/CCG(B) F:MB/CCG(B) F:MB/CCG(B) F:MB/CCG(B) F:SSG(B) F:SSG(B) F:SSG(B) F:SSG(B) A001 (MB 0) A121 (CCG 0) A001 (MB 1) A121 (CCG 1)

MOLOC

C101 (SSG-0-0 or SSG-0-2) C331 (SSG-0-1 or SSG-0-3) C101 (SSG-1-0 or SSG-1-2) C331 (SSG-1-0 or SSG-1-3)

Tab. 2.80

Fuse Assignment R:LTGN/TSG/MB/CCG (cabling from below)

A30828-X1160-M-2-7620

135

Construction

Maintenance Node

2.75

R:LTGN with MBD and CCGE


Fuse Panel 8 ft. rack
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel 7 ft. rack


ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel

MUT01

Fuse Panel F:LTGN FAN (B5681) F:MBD 0 MUT03 F:LTGN MUT11 MUT04 F:LTGN

MUT01 MUT02

MUT03

F:MBD 1

MUT05

F:MBD 0

MUT04

F:MBD 1 FAN (B5681) F:LTGN MUT06

MUT05 MUT06

F:CCGE FAN-BOX (B5877) FAN-BOX (U2624) rack 8 ft.

MUT07

F:CCGE FAN-BOX (B5877) FAN-BOX (U2624) rack 7 ft.

MUT07

MUT12

MUT12

FU 01, 25 02, 26 04 05, 29 06, 30 MUT02 / F:LTGN(A), (B), (C) MUT03 / F:LTGN(A), (B), (C)

MUT

rack 8 ft. MUT11 / FAN - rack 7 ft. MUT06 / FAN MUT06 / F:LTGN(A), (B), (C) MUT07 / F:CCGE - FU06 CCG0, FU30 CCG1

Tab. 2.81

Fuse Assignment R:LTGN/MBD/CCGE

136

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 07 08 31 32 05, 29 27 07, 31

MUT MUT04 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT04 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT05 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT05 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT06 / F:LTGN(A), (B), (C) MUT12 / FAN-BOX (B5877) MUT13 / FANB-OX (U2624)

Tab. 2.81

Fuse Assignment R:LTGN/MBD/CCGE

2.76

R:LTGN with MBD and SSG, cabling from above


Fuse Panel 8 ft. rack
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:SSG(B) 0

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:SSG(B) 1 FAN (B5681) F:MBD 0

MUT03 F:SSG(B) 0 MUT11 MUT04 F:SSG(B) 1 MUT03

F:MBD 1

MUT05

F:MBD 0

MUT04

F:MBD 1 FAN (B5681) F:LTGN F:LTGP or F:STMI or F:LTGN FAN-BOX (B5877) FAN-BOX (U2624) rack 8 ft. MUT06 # F:LTGP or F:STMI or F:LTGN FAN-BOX (B5877) FAN-BOX (U2624) rack 7 ft.

MUT05 MUT06

MUT07 MUT12 MUT13

MUT07 MUT12 MUT13

# MUT06 is empty if F:LTGP or F:STMI are installed in MUT07

A30828-X1160-M-2-7620

137

Construction

Maintenance Node

FU 01, 02 25, 26 04 07 08 31 32 05, 29 06, 30 05, 29 06, 30 27 07, 31 MUT02 / F:SSG(B) SSG 0-x MUT03 / F:SSG(B) SSG 1-x

MUT

rack 8 ft. MUT11 / FAN - rack 7 ft. MUT06 / FAN MUT04 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT04 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT05 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT05 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT06 / F:LTGN(A), (B), (C) MUT07 / F:LTGN(A), (B), (C) MUT07 / F:LTGP/F:STMI / C151 X1/X2, C121 X1/X2 (LTG 1-16) MUT07 / F:LTGP/F:STMI / C181 X1/X2, C251 X1/X2 (LTG 17-32) MUT12 / FAN-BOX (B5877) MUT13 / FAN-BOX (U2624)

Tab. 2.82

Fuse Assignment R:LTGN (with SSG and MBD) (cabling from above)

138

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.77

R:LTGN with MBD and SSG, cabling from below


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02 Fuse Panel MUT01

F:LTGN FAN (B5681) F:MBD 0

MUT03 F:LTGN MUT11 MUT04 FAN (B5681) MUT02 MUT03

F:MBD 1

F:MBD 0 MUT05 F:MBD 1

MUT04

MUT05

F:SSG(B) 0

MUT06

F:SSG(B) 0

MUT06

F:SSG(B) 1

MUT07

F:SSG(B) 1

MUT07

FAN-BOX (B5877)

MUT12

FAN-BOX (B5877)

MUT12

rack 8 ft.

rack 7 ft.

FU 01, 25 02, 26 04 07 08 31 32 05, 06 29, 30 27 MUT02 / F:LTGN(A), (B), (C) MUT03 / F:LTGN(A), (B), (C)

MUT

in rack 8 ft. MUT11 / Fan - in rack 7 ft. MUT03 / Fan MUT04 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT04 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT05 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT05 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT06 / F:SSG(B) SSG 0-x MUT07 / F:SSG(B) SSG 1-x MUT12 / FAN-BOX

Tab. 2.83

Fuse Assignment R:LTGN (with SSG and MBD) (cabling from below)

A30828-X1160-M-2-7620

139

Construction

Maintenance Node

2.78

R:LTGN with MBD and TSG, cabling from above


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:TSG(B) 0

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:TSG(B) 1 FAN (B5681) F:MBD 0

MUT03 F:TSG(B) 0 MUT11 MUT04 F:TSG(B) 1 MUT03

F:MBD 1

MUT05

F:MBD 0

MUT04

F:MBD 1 FAN (B5681) F:LTGN F:LTGP or F:STMI or F:LTGN FAN-BOX (B5877) FAN-BOX (U2624) MUT06 # F:LTGP or F:STMI or F:LTGN FAN-BOX (B5877) FAN-BOX (U2624)

MUT05 MUT06

MUT07 MUT12 MUT13

MUT07 MUT12 MUT13

rack 8 ft. rack 7 ft. # MUT06 is empty if F:LTGP or F:STMI are installed in MUT07

FU 01 25 04 07 08 31 32 05, 29 06, 30 05, 29 06, 30 MUT02 / F:TSG(B) / TSG 0-x MUT03 / F:TSG(B) /TSG 1-x

MUT

in rack 8 ft. MUT11 / Fan - in rack 7 ft. MUT06 / Fan MUT04 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT04 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT05 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT05 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT06 / F:LTGN(A), (B), (C) MUT07 / F:LTGN(A), (B), (C) MUT07/ F:LTGP/F:STMI /C151 X1/X2, C121 X1/X2 (LTG 1-16) MUT07/ F:LTGP/F:STMI /C281 X1/X2, C251 X1/X2 (LTG 17-32)

Tab. 2.84

Fuse Assignment R:LTGN (with TSG and MBD) (cabling from above)

140

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 27 07, 31 MUT12 / FAN-BOX (B5877) MUT12 / FAN-BOX (U2624)

MUT

Tab. 2.84

Fuse Assignment R:LTGN (with TSG and MBD) (cabling from above)

2.79

R:LTGN with MBD and TSG, cabling from below


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02 Fuse Panel MUT01

F:LTGN FAN (B5681) F:MBD 0

MUT03 F:LTGN MUT11 MUT04 FAN (B5681) MUT02 MUT03

F:MBD 1

F:MBD 0 MUT05 F:MBD 1

MUT04

MUT05

F:TSG(B) 0

MUT06

F:TSG(B) 0

MUT06

F:TSG(B) 1

MUT07

F:TSG(B) 1

MUT07

FAN-BOX (B5877)

MUT12

FAN-BOX (B5877)

MUT12

rack 8 ft.

rack 7 ft.

FU 01, 25 02, 26 04 07 08 MUT02 / F:LTGN(A), (B), (C) MUT03 / F:LTGN(A), (B), (C)

MUT

in rack 8 ft. MUT11 / Fan - in rack 7 ft. MUT03 / Fan MUT04 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT04 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG)

Tab. 2.85

Fuse Assignment R:LTGN (with TSG and MBD) (cabling from below)

A30828-X1160-M-2-7620

141

Construction

Maintenance Node

FU 31 32 05 29 27

MUT MUT05 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT05 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT06 / F:TSG(B) / TSG 0-x MUT07 / F:TSG(B) / TSG 1-x MUT12 / FAN-BOX

Tab. 2.85

Fuse Assignment R:LTGN (with TSG and MBD) (cabling from below)

2.80

R:LTGN with MBD and SNMUX, cabling from above


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:SNMUX(A) 0

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:SNMUX(A) 1 FAN (B5681) F:MBD 0

MUT03 F:SNMUX(A) 0 MUT11 MUT04 F:SNMUX(A) 1 MUT03

F:MBD 1

MUT05

F:MBD 0

MUT04

F:MBD 1 FAN (B5681)

MUT05 MUT06

F:LTGN F:LTGP or F:STMI or F:LTGN FAN-BOX (B5877) FAN-BOX (U2624) rack 8 ft.

MUT06 #

MUT07 MUT12 MUT13

F:LTGP or F:STMI or F:LTGN FAN-BOX (B5877) FAN-BOX (U2624) rack 7 ft.

MUT07 MUT12 MUT13

# MUT06 is empty if F:LTGP or F:STMI are installed in MUT07

142

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 01 02 25 26 04 07 08 31 32 05, 29 06, 30 05, 29 06, 30 27 07, 31 MUT02 / F:SNMUX / SN 0 MUT02 / F:SNMUX / SN 0 MUT03 / F:SNMUX / SN 1 MUT03 / F:SNMUX / SN 1

MUT

in rack 8 ft. MUT11 / Fan - in rack 7 ft. MUT06 / Fan MUT04 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT04 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT05 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT05 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT06 / F:LTGN(A), (B), (C) MUT07 / F:LTGN(A), (B), (C) MUT07/ F:LTGP/F:STMI / C151 X1/X2, C121 X1/X2 (LTG 1-16) MUT07/ F:LTGP/F:STMI / C281 X1/X2, C251 X1/X2 (LTG 17-32) MUT12 / FAN-BOX (B5877) MUT12 / FAN-BOX (U2624)

Tab. 2.86

Fuse Assignment R:LTGN (with SNMUX and MBD) (cabling from above)

A30828-X1160-M-2-7620

143

Construction

Maintenance Node

2.81

R:LTGN with MBD and SNMUX, cabling from below


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02 Fuse Panel MUT01

F:LTGN FAN (B5681) F:MBD 0

MUT03 F:LTGN MUT11 MUT04 FAN (B5681) MUT02 MUT03

F:MBD 1

F:MBD 0 MUT05 F:MBD 1

MUT04

MUT05

F:SNMUX(A) 0

MUT06

F:SNMUX(A) 0

MUT06

F:SNMUX(A) 1

MUT07

F:SNMUX(A) 1

MUT07

FAN-BOX (B5877)

MUT12

FAN-BOX (B5877)

MUT12

rack 8 ft. FU 01, 25 02, 26 04 07 08 31 32 05 06 29 30 27 MUT02 / F:LTGN(A), (B), (C) MUT03 / F:LTGN(A), (B), (C) MUT

rack 7 ft.

in rack 8 ft. MUT11 / Fan - in rack 7 ft. MUT03 / Fan MUT04 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT04 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT05 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT05 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT06 / F:SNMUX / SN 0 MUT06 / F:SNMUX / SN 0 MUT07 / F:SNMUX / SN 1 MUT07 / F:SNMUX / SN 1 MUT12 / FAN-BOX

Tab. 2.87

Fuse Assignment R:LTGN (with SNMUX and MBD) (cabling from below)

144

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.82

R:LTGN with MBD and SNCARE, cabling from above


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:SNCARE

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:SNCARE FAN (B5681) F:MBD 0

MUT03 F:SNCARE MUT11 MUT04 F:SNCARE MUT03

F:MBD 1

MUT05

F:MBD 0

MUT04

F:MBD 1 FAN (B5681) MUT06 # F:LTGP or F:STMI or F:LTGN FAN-BOX (B5877) FAN-BOX (U2624) rack 7 ft.

MUT05 MUT06

F:LTGN F:LTGP or F:STMI or F:LTGN FAN-BOX (B5877) FAN-BOX (U2624) rack 8 ft.

MUT07 MUT12 MUT13

MUT07 MUT12 MUT13

# MUT06 is empty if F:LTGP or F:STMI are installed in MUT07

FU 04 07 08 31 32 05, 29 06, 30 05, 29 06, 30 27 07, 31

MUT in rack 8 ft. MUT11 / Fan - in rack 7 ft. MUT06 / Fan MUT04 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT04 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT05 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT05 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT06 / F:LTGN(A), (B), (C) MUT07 / F:LTGN(A), (B), (C) MUT07/ F:LTGP/F:STMI / C151 X1/X2, C121 X1/X2 (LTG 1-16) MUT07/ F:LTGP/F:STMI / C281 X1/X2, C251 X1/X2 (LTG 17-32) MUT12 / FAN-BOX (B5877) MUT12 / FAN-BOX (U2624)

Tab. 2.88

Fuse Assignment R:LTGN (with SNCARE and MBD) (cabling from above)

A30828-X1160-M-2-7620

145

Construction

Maintenance Node

2.83

R:LTGN with MBD and SNCARE, cabling from below


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02 Fuse Panel MUT01

F:LTGN FAN (B5681) F:MBD 0

MUT03 F:LTGN MUT11 MUT04 FAN (B5681) MUT02 MUT03

F:MBD 1

F:MBD 0 MUT05 F:MBD 1

MUT04

MUT05

F:SNCARE

MUT06

F:SNCARE

MUT06

F:SNCARE

MUT07

F:SNCARE

MUT07

FAN-BOX (B5877)

MUT12

FAN-BOX (B5877)

MUT12

rack 8 ft.

rack 7 ft.

FU 01, 25 02, 26 04 07 08 31 32 27 MUT02 / F:LTGN(A), (B), (C) MUT03 / F:LTGN(A), (B), (C)

MUT

in rack 8 ft. MUT11 / Fan - in rack 7 ft. MUT03 / Fan MUT04 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT04 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT05 / F:MBD (MBDH 0, 1, 6, 7, MBDA 0, 2, MBDC, MBDCG) MUT05 / F:MBD (MBDH 2, 3, 4, 5, MBDA 1, 3, 4, MBDC, MBDCG) MUT12 / FAN-BOX

Tab. 2.89

Fuse Assignment R:LTGN (with SNCARE and MBD) (cabling from below)

146

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.84

R:LTGN with SNMUX, without FAN, cabling from above


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:SNMUX(A) 0 MUT02 Fuse Panel F:SNMUX(A) 1 MUT03 F:SNMUX(A) 0 MUT02

F:SNMUX(A) 1

MUT03

F:LTGN

MUT05 F:LTGN MUT05

F:LTGN

MUT06

F:LTGN

MUT06

rack 8 ft.

rack 7 ft.

FU 01, 02 25, 26 04, 28 05, 29 MUT 02 / F:SNMUX(A) / SN 0 MUT 03 / F:SNMUX(A) / SN 1 MUT 05 / F:LTGN (A), (B), (C) MUT 06 / F:LTGN (A), (B), (C)

MUT

Tab. 2.90

Fuse Assignment R:LTGN (with SNMUX, without FAN, cabling from above)

A30828-X1160-M-2-7620

147

Construction

Maintenance Node

2.85

R:LTGN with SNMUX, without FAN, cabling from below


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGN

MUT03

F:LTGN

F:LTGN

MUT03

F:SNMUX(A) 0

MUT06

F:SNMUX(A) 0

MUT06

F:SNMUX(A) 1

MUT07

F:SNMUX(A) 1

MUT07

rack 8 ft.

rack 7 ft.

FU 01, 25 02, 26 05, 06 29, 30 MUT 02 / F:LTGN (A), (B), (C) MUT 03 / F:LTGN (A), (B), (C) MUT 06 / F:SNMUX (A) / SN 0 MUT 07 / F:SNMUX (A) / SN 1

MUT

Tab. 2.91

Fuse Assignment R:LTGN (with SNMUX, without FAN, cabling from below)

148

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.86

R:LTGN with SNMUX and FAN, cabling from above


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:SNMUX(A) 0

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:SNMUX(A) 1

MUT03

F:SNMUX(A) 0

F:LTGN

MUT04

F:SNMUX(A) 1

MUT03

F:LTGN F:LTGN MUT05 F:LTGN F:LTGN MUT06

MUT04

MUT05

F:LTGN

MUT06

F:LTGN FAN (B5681) FAN (B5681) FILTER:FAN rack 8 ft.

MUT07 MUT12 MUT13 MUT14

F:LTGN FAN (B5681) FAN (B5681) FILTER:FAN rack 7 ft.

MUT07 MUT12 MUT13 MUT14

FU 01, 02 25, 26 03, 27 04, 28 05, 29 06, 30 07 31 MUT 02 / F:SNMUX (A) / SN 0 MUT 03 / F:SNMUX (A) / SN 0 MUT 04 / F:LTGN (A), (B), (C) MUT 05 / F:LTGN (A), (B), (C) MUT 06 / F:LTGN (A), (B), (C) MUT 07 / F:LTGN (A), (B), (C) MUT 12 / FAN MUT 13 / FAN

MUT

Tab. 2.92

Fuse Assignment LTGN (with SNMUX and Fan, cabling from above)

A30828-X1160-M-2-7620

149

Construction

Maintenance Node

2.87

R:LTGN with SNMUX and FAN, cabling from below


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGN

MUT03

F:LTGN

F:LTGN

MUT04

F:LTGN

MUT03

F:LTGN F:LTGN MUT05 F:LTGN F:SNMUX(A) 0 MUT06

MUT04

MUT05

F:SNMUX(A) 0

MUT06

F:SNMUX(A) 1 FAN (B5681) FAN (B5681) FILTER:FAN rack 8 ft. FU 01, 25 02, 26 03, 27 04, 28 05, 06 29, 30 07 31 MUT 02 / F:LTGN (A), (B), (C) MUT 03 / F:LTGN (A), (B), (C) MUT 04 / F:LTGN (A), (B), (C) MUT 05 / F:LTGN (A), (B), (C) MUT 06 / F:SNMUX (A) / SN 0 MUT 07 / F:SNMUX (A) / SN 1 MUT 12 / FAN MUT 13 / FAN

MUT07 MUT12 MUT13 MUT14

F:SNMUX(A) 1 FAN (B5681) FAN (B5681) FILTER:FAN rack 7 ft.

MUT07 MUT12 MUT13 MUT14

MUT

Tab. 2.93

Fuse Assignment LTGN (with SNMUX and Fan, cabling from below)

150

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.88

R:LTGN with SNCARE, cabling from above


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:SNCARE

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:SNCARE

MUT03

F:SNCARE

F:LTGN

MUT04

F:SNCARE

MUT03

F:LTGN F:LTGN MUT05 F:LTGN F:LTGN MUT06

MUT04

MUT05

F:LTGN

MUT06

F:LTGN

MUT07

F:LTGN

MUT07

rack 8 ft.

rack 7 ft.

FU 03, 27 04, 28 05, 29 06, 30 MUT 04 MUT 05 MUT 06 MUT 07

MUT

Unit F:LTGN (A), (B), (C) F:LTGN (A), (B), (C) F:LTGN (A), (B), (C) F:LTGN (A), (B), (C)

Tab. 2.94

Fuse Assignment LTGN (with SNCARE, cabling from above)

A30828-X1160-M-2-7620

151

Construction

Maintenance Node

2.89

R:LTGN with SNCARE, cabling from below


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGN

MUT03

F:LTGN

F:LTGN

MUT04

F:LTGN

MUT03

F:LTGN F:LTGN MUT05 F:LTGN F:SNCARE MUT06

MUT04

MUT05

F:SNCARE

MUT06

F:SNCARE

MUT07

F:SNCARE

MUT07

rack 8 ft.

rack 7 ft.

FU 01, 25 02, 26 03, 27 04, 28 MUT 02 MUT 03 MUT 04 MUT 05

MUT F:LTGN (A), (B), (C) F:LTGN (A), (B), (C) F:LTGN (A), (B), (C) F:LTGN (A), (B), (C)

Unit

Tab. 2.95

Fuse Assignment LTGN (with SNMUX and Fan, cabling from below)

152

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.90

R:LTGN with 4 SNMUX and FAN, cabling from above


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:SNMUX(A) 0

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:SNMUX(A) 1

MUT03

F:SNMUX(A) 0

F:SNMUX(A) 0

MUT04

F:SNMUX(A) 1

MUT03

F:SNMUX(A) 0 F:SNMUX(A) 1 MUT05

MUT04

F:SNMUX(A) 1

MUT05

F:LTGN

MUT06

F:LTGN

MUT06

F:LTGN FAN (B5681) FAN (B5681) FILTER:FAN rack 8 ft.

MUT07 MUT12 MUT13 MUT14

F:LTGN FAN (B5681) FAN (B5681) FILTER:FAN rack 7 ft.

MUT07 MUT12 MUT13 MUT14

FU 01, 02 25, 26 03, 04 27, 28 05, 29 06, 30 07 31 MUT 02 MUT 03 MUT 04 MUT 05 MUT 06 MUT 07 MUT 12 MUT 13

MUT F:SNMUX (A) / SN 0 F:SNMUX (A) / SN 1

Unit

F:SNMUX (A) (nur bei Einsatz virtueller LTG) F:SNMUX (A) (nur bei Einsatz virtueller LTG) F:LTGN (A), (B), (C) F:LTGN (A), (B), (C) FAN FAN

Tab. 2.96

Fuse Assignment LTGN (with 4 SNMUX and FAN, cabling from above)

A30828-X1160-M-2-7620

153

Construction

Maintenance Node

2.91

R:LTGN with 4 SNMUX and FAN, cabling from below


Fuse Panel
ON OFF ON OFF

01 02 03 04 05 06 0708

25 26 2728 2930 31 32

Fuse Panel F:LTGN

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGN

MUT03

F:LTGN

F:SNMUX(A) 0

MUT04

F:LTGN

MUT03

F:SNMUX(A) 0 F:SNMUX(A) 1 MUT05 F:SNMUX(A) 1 F:SNMUX(A) 0 MUT06

MUT04

MUT05

F:SNMUX(A) 0

MUT06

F:SNMUX(A) 1 FAN (B5681) FAN (B5681) FILTER:FAN rack 8 ft.

MUT07 MUT12 MUT13 MUT14

F:SNMUX(A) 1 FAN (B5681) FAN (B5681) FILTER:FAN rack 7 ft.

MUT07 MUT12 MUT13 MUT14

FU 01, 25 02, 26 03, 04 27, 28 05, 06 29, 30 07 31 MUT 02 MUT 03 MUT 04 MUT 05 MUT 06 MUT 07 MUT 12 MUT 13

MUT F:LTGN (A), (B), (C) F:LTGN (A), (B), (C)

MUT

F:SNMUX (A) (nur bei Einsatz virtueller LTG) F:SNMUX (A) (nur bei Einsatz virtueller LTG) F:SNMUX (A) / SN 0 F:SNMUX (A) / SN 1 FAN FAN

Tab. 2.97

Fuse Assignment LTGN (with 4 SNMUX and FAN, cabling from below)

154

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.92

R:STMI/LTG
Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 09 10 11 12 21 22 23 24 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel F:LTGP or F:STMI F:LTGP or F:STMI FAN (U2623) F:LTGP or F:STMI F:LTGP or F:STMI FAN (U2623) F:LTGP or F:STMI F:LTGP or F:STMI FAN-BOX (U2624)

MUT01 MUT02 Fuse Panel MUT03 MUT10 MUT04 F:LTGP or F:STMI F:LTGP or F:STMI F:LTGP or F:STMI FAN (U2623) MUT06 F:LTGP or F:STMI F:LTGP or F:STMI FAN-BOX (U2624) rack 7 ft. Unit MOLOC C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 MUT01

MUT03

MUT04

MUT05 MUT11

MUT05 MUT11 MUT06

MUT07

MUT07 MUT12

MUT12

rack 8 ft. FU 11,31 MUT MUT02

F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI FANTRAY F:LTGP(A) F:STMI F:LTGP(A) F:STMI

12, 32

MUT02

09, 29

MUT03

10, 30

MUT03

10, 29 07, 27

MUT10 MUT04

08, 28

MUT04

Tab. 2.98

Fuse Assignment R:STMI/LTG

A30828-X1160-M-2-7620

155

Construction

Maintenance Node

FU 05, 25

MUT MUT05

Unit F:LTGP(A) F:STMI F:LTGP(A) F:STMI FANTRAY F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI FAN-BOX C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7

MOLOC

06, 26

MUT05

06, 25 03, 23

MUT11 MUT06

04, 24

MUT06

01, 21

MUT07

02, 22

MUT07

02, 21

MUT11

Tab. 2.98

Fuse Assignment R:STMI/LTG

156

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.93

R:STMI/LTG with DLUV


Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 09 10 11 12 21 22 23 24 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel F:DLUV(A)

MUT01 MUT02 Fuse Panel MUT01

F:DLUV(A) FAN (U2623) F:LTGP or F:STMI F:LTGP or F:STMI FAN (U2623) F:LTGP or F:STMI F:LTGP or F:STMI FAN-BOX (U2624)

MUT03 MUT10 MUT04 F:DLUV(A) MUT05 MUT11 MUT06 F:LTGP or F:STMI FAN (U2623) F:LTGP or F:STMI F:LTGP or F:STMI FAN-BOX (U2624) rack 7 ft. MUT04

F:DLUV(A)

MUT03

MUT05 MUT11 MUT06

MUT07

MUT07 MUT12

MUT12

rack 8 ft.

Fuse Assignment R:STMI/LTG with DLUV for Rack 8 ft. FU 11 12 31 32 09 10 29 30 10, 29 07, 27 MUT MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT10 MUT04 Unit F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) FANTRAY F:LTGP(A) F:STMI C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15 C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15 X1/X2 - X6/X7 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) MOLOC

Tab. 2.99

Fuse Assignment R:STMI/LTG with DLUV for Rack 8 ft.

A30828-X1160-M-2-7620

157

Construction

Maintenance Node

Fuse Assignment R:STMI/LTG with DLUV for Rack 8 ft. FU 08, 28 MUT MUT04 Unit F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI FANTRAY F:LTGP(A) F:STMI 04, 24 MUT06 F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI FAN-BOX C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7 MOLOC

05, 25

MUT05

06, 26

MUT05

06, 25 03, 23

MUT11 MUT06

01, 21

MUT07

02, 22

MUT07

02, 21

MUT11

Tab. 2.99

Fuse Assignment R:STMI/LTG with DLUV for Rack 8 ft.

Fuse Assignment R:STMI/LTG with DLUV for Rack 7 ft. FU 09 10 29 30 07 08 27 28 05, 25 MUT MUT03 MUT03 MUT03 MUT03 MUT04 MUT04 MUT04 MUT04 MUT05 Unit F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:LTGP(A) F:STMI F:LTGP(A) F:STMI FANTRAY F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15 C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) MOLOC

06, 26

MUT05

06, 25 03, 23

MUT11 MUT06

04, 24

MUT06

01, 21

MUT07

Tab. 2.100 Fuse Assignment R:STMI/LTG with DLUV for Rack 7 ft.

158

A30828-X1160-M-2-7620

Maintenance Node

Construction

Fuse Assignment R:STMI/LTG with DLUV for Rack 7 ft. FU 02, 22 MUT MUT07 Unit F:LTGP(A) F:STMI FANBOX C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7 MOLOC

02, 21

MUT11

Tab. 2.100 Fuse Assignment R:STMI/LTG with DLUV for Rack 7 ft.

2.94

R:STMI/LTG with SNMUX(A)


Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 09 10 11 12 21 22 23 24 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel F:LTGP or F:STMI F:LTGP or F:STMI FAN (U2623) F:LTGP or F:STMI F:LTGP or F:STMI FAN (U2623) F:SNMUX(A) 0

MUT01 MUT02 Fuse Panel MUT03 MUT10 MUT04 F:LTGP or F:STMI F:LTGP or F:STMI F:LTGP or F:STMI FAN (U2623) F:SNMUX(A) 0 MUT01

MUT03

MUT04

MUT05 MUT11 MUT06

MUT05 MUT11 MUT06

F:SNMUX(A) 1

MUT07

F:SNMUX(A) 1

MUT07

FAN-BOX (U2624)

MUT12

FAN-BOX (U2624)

MUT12

rack 8 ft.

rack 7 ft.

FU 11, 31

MUT MUT02

Unit F:LTGP(A) F:STMI F:LTGP(A) F:STMI C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32

MOLOC

12, 32

MUT02

Tab. 2.101 Fuse Assignment R:STMI/LTG with SNMUX(A)

A30828-X1160-M-2-7620

159

Construction

Maintenance Node

FU 09, 29

MUT MUT03

Unit F:LTGP(A) F:STMI F:LTGP(A) F:STMI FANTRAY F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI FANTRAY F:SNMUX(A) F:SNMUX(A) FAN-BOX C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7 PUE2/MUE2 - PUE1/MUE1 PUE2/MUE2 - PUE1/MUE1 X1/X2 - X6/X7

MOLOC

10, 30

MUT03

10, 29 07, 27

MUT10 MUT04

08, 28

MUT04

05, 25

MUT05

06, 26

MUT05

06, 25 01, 03 02, 22 02, 21

MUT11 MUT06 MUT07 MUT11

Tab. 2.101 Fuse Assignment R:STMI/LTG with SNMUX(A)

160

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.95

R:STMI/LTG with SNMUX(A) and DLUV


Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 09 10 11 12 21 22 23 24 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel F:DLUV(A)

MUT01 MUT02 Fuse Panel MUT01

F:DLUV(A) FAN (U2623) F:LTGP or F:STMI F:LTGP or F:STMI FAN (U2623) F:SNMUX(A) 0

MUT03 MUT10 MUT04

F:DLUV(A)

MUT03

F:DLUV(A) F:LTGP or F:STMI FAN (U2623) F:SNMUX(A) 0

MUT04

MUT05 MUT11 MUT06

MUT05 MUT11 MUT06

F:SNMUX(A) 1

MUT07

F:SNMUX(A) 1

MUT07

FAN-BOX (U2624)

MUT12

FAN-BOX (U2624)

MUT12

rack 8 ft.

rack 7 ft.

Fuse Assignment R:STMI/LTG with SNMUX(A) and DLUV for Rack 8 ft. FU 11 12 31 32 09 10 29 30 10, 29 MUT MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT10 Unit F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) FANTRAY C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15 C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15 X1/X2 - X6/X7 MOLOC

Tab. 2.102 Fuse Assignment R:STMI/LTG with SNMUX(A) and DLUV for 8 ft. Rack

A30828-X1160-M-2-7620

161

Construction

Maintenance Node

Fuse Assignment R:STMI/LTG with SNMUX(A) and DLUV for Rack 8 ft. FU 07, 27 MUT MUT04 Unit F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI FANTRAY F:SNMUX(A) F:SNMUX(A) FANBOX C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7 PUE2/MUE2 - PUE1/MUE1 PUE2/MUE2 - PUE1/MUE1 X1/X2 - X6/X7 MOLOC

08, 28

MUT04

05, 25

MUT05

06, 26

MUT05

06, 25 01, 03 02, 22 02, 21

MUT11 MUT06 MUT07 MUT11

Tab. 2.102 Fuse Assignment R:STMI/LTG with SNMUX(A) and DLUV for 8 ft. Rack

Fuse Assignment R:STMI/LTG with SNMUX(A) and DLUV for Rack 7 ft. FU 09 10 29 30 07 08 27 28 05, 25 MUT MUT03 MUT03 MUT03 MUT03 MUT04 MUT04 MUT04 MUT04 MUT05 Unit F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:LTGP(A) F:STMI F:LTGP(A) F:STMI FANTRAY F:SNMUX(A) F:SNMUX(A) FAN-BOX C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15 C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7 PUE2/MUE2 - PUE1/MUE1 PUE2/MUE2 - PUE1/MUE1 X1/X2 - X6/X7 MOLOC

06, 26

MUT05

06, 25 01, 03 02, 22 02, 21

MUT11 MUT06 MUT07 MUT11

Tab. 2.103 Fuse Assignment R:STMI/LTG with SNMUX(A) and DLUV for 7 ft. Rack

162

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.96

R:STMI/LTG with SNMUX(B)


Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 09 10 11 12 21 22 23 24 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel F:LTGP or F:STMI F:LTGP or F:STMI FAN (U2623) F:LTGP or F:STMI F:LTGP or F:STMI FAN (U2623)

MUT01 MUT02 Fuse Panel MUT03 MUT10 MUT04 MUT01

F:LTGP or F:STMI F:LTGP or F:STMI F:LTGP or F:STMI FAN (U2623)

MUT03

MUT05 MUT11

MUT04

MUT05 MUT11

F:SNMUX(B)

MUT07

F:SNMUX(B)

MUT07

FAN-BOX (U2624)

MUT12

FAN-BOX (U2624)

MUT12

rack 8 ft.

rack 7 ft.

FU 11, 31

MUT MUT02

Unit F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI FANTRAY F:LTGP(A) F:STMI F:LTGP(A) F:STMI C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32

MOLOC

12, 32

MUT02

09, 29

MUT03

10, 30

MUT03

10, 29 07, 27

MUT10 MUT04

08, 28

MUT04

Tab. 2.104 Fuse Assignment R:STMI/LTG with SNMUX(B)

A30828-X1160-M-2-7620

163

Construction

Maintenance Node

FU 05, 25

MUT MUT05

Unit F:LTGP(A) F:STMI F:LTGP(A) F:STMI FANTRAY F:SNMUX(B) F:SNMUX(B) FAN-BOX C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7 C153 X1/X2 (SN 0) C281 X1/X2 (SN 1) X1/X2 - X6/X7

MOLOC

06, 26

MUT05

06, 25 01, 03 02, 22 02, 21

MUT11 MUT06 MUT07 MUT12

Tab. 2.104 Fuse Assignment R:STMI/LTG with SNMUX(B)

2.97

R:STMI/LTG with SNMUX(B) and DLUV


Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 09 10 11 12 21 22 23 24 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel F:DLUV(A)

MUT01 MUT02 Fuse Panel MUT01

F:DLUV(A) FAN (U2623) F:LTGP or F:STMI F:LTGP or F:STMI FAN (U2623)

MUT03 MUT10 F:DLUV(A) MUT04 F:DLUV(A) MUT05 MUT11 F:LTGP or F:STMI FAN (U2623) MUT04 MUT03

MUT05 MUT11

F:SNMUX(B)

MUT07

F:SNMUX(B)

MUT07

FAN-BOX (U2624)

MUT12

FAN-BOX (U2624)

MUT12

rack 8 ft.

rack 7 ft.

164

A30828-X1160-M-2-7620

Maintenance Node

Construction

Fuse Assignment R:STMI/LTG with SNMUX(B) and DLUV for Rack 8 ft. FU 11 12 31 32 09 10 29 30 10, 29 07, 27 MUT MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT10 MUT04 Unit F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) FANTRAY F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI FANTRAY F:SNMUX(B) F:SNMUX(B) FAN-BOX C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15 C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15 X1/X2 - X6/X7 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7 C153 X1/X2 (SN0) C281 X1/X2 (SN1) X1/X2 - X6/X7 MOLOC

08, 28

MUT04

05, 25

MUT05

06, 26

MUT05

06 25 01, 03 02, 22 02, 21

MUT11 MUT06 MUT07 MUT11

Tab. 2.105 Fuse Assignment R:STMI/LTG with SNMUX(B) and DLUV for 8 ft. Rack

Fuse Assignment R:STMI/LTG with SNMUX(B) and DLUV for Rack 7 ft. FU 09 10 29 30 07 08 27 28 05, 25 MUT MUT03 MUT03 MUT03 MUT03 MUT04 MUT04 MUT04 MUT04 MUT05 Unit F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:LTGP(A) F:STMI F:LTGP(A) F:STMI C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15 C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 MOLOC

06, 26

MUT05

Tab. 2.106 Fuse Assignment R:STMI/LTG with SNMUX(B) and DLUV for 7 ft. Rack

A30828-X1160-M-2-7620

165

Construction

Maintenance Node

Fuse Assignment R:STMI/LTG with SNMUX(B) and DLUV for Rack 7 ft. FU 06, 25 01, 03 02, 22 02, 21 MUT MUT11 MUT06 MUT07 MUT11 Unit FANTRAY F:SNMUX(B) F:SNMUX(B) FAN-BOX X1/X2 - X6/X7 C153 X1/X2 (SN0) C281 X1/X2 (SN1) X1/X2 - X6/X7 MOLOC

Tab. 2.106 Fuse Assignment R:STMI/LTG with SNMUX(B) and DLUV for 7 ft. Rack

2.98

R:STMI/LTG with TSG(B)


Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 09 10 11 12 21 22 23 24 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel

MUT01

Fuse Panel

MUT01

F:LTGP or F:STMI F:LTGP or F:STMI

MUT04 F:LTGP or F:STMI F:LTGP or F:STMI MUT11 MUT06 FAN (U2623) F:TSG(B) 0 MUT04

MUT05

MUT05 MUT11 MUT06

FAN (U2623) F:TSG(B) 0

F:TSG(B) 1

MUT07

F:TSG(B) 1

MUT07

FAN-BOX (U2624)

MUT12

FAN-BOX (U2624)

MUT12

rack 8 ft.

rack 7 ft.

166

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 07, 27

MUT MUT04

Unit F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI FANTRAY F:TSG(B) F:TSG(B) FAN-BOX C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7 UE1 (SN0) UE1 (SN1) X1/X2 - X6/X7

MOLOC

08, 28

MUT04

05, 25

MUT05

06, 26

MUT05

06 25 01 22 02, 21

MUT11 MUT06 MUT07 MUT11

Tab. 2.107 Fuse Assignment R:STMI/LTG with TSG(B)

A30828-X1160-M-2-7620

167

Construction

Maintenance Node

2.99

R:STMI/LTG with TSG(B) and DLUV


Fuse Panel
ON OFF 01 02 03 04 05 06 07 08 09 10 11 12 21 22 23 24 25 26 27 28 29 30 31 32 ON OFF

Fuse Panel F:DLUV(A)

MUT01 MUT02 Fuse Panel MUT01

F:DLUV(A) FAN (U2623) F:LTGP or F:STMI F:LTGP or F:STMI FAN (U2623) F:TSG(B) 0

MUT03 MUT10 F:DLUV(A)

MUT03

MUT04

F:DLUV(A) F:LTGP or F:STMI FAN (U2623) F:TSG(B) 0

MUT04

MUT05 MUT11 MUT06

MUT05 MUT11 MUT06

F:TSG(B) 1

MUT07

F:TSG(B) 1

MUT07

FAN-BOX (U2624)

MUT12

FAN-BOX (U2624)

MUT12

rack 8 ft.

rack 7 ft.

Fuse Assignment R:STMI/LTG with TSG(B) and DLUV for Rack 8 ft. FU 11 12 31 32 09 10 29 30 10, 29 MUT MUT02 MUT02 MUT02 MUT02 MUT03 MUT03 MUT03 MUT03 MUT10 Unit F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) FANTRAY C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15 C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15 X1/X2 - X6/X7 MOLOC

Tab. 2.108 Fuse Assignment R:STMI/LTG with TSG(B) and DLUV for Rack 8 ft.

168

A30828-X1160-M-2-7620

Maintenance Node

Construction

Fuse Assignment R:STMI/LTG with TSG(B) and DLUV for Rack 8 ft. FU 07, 27 MUT MUT04 Unit F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI F:LTGP(A) F:STMI FANTRAY F:TSG(B) F:TSG(B) FAN-BOX C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7 UE1 (SN0) UE1 (SN1) X1/X2 - X6/X7 MOLOC

08, 28

MUT04

05, 25

MUT05

06, 26

MUT05

06 25 01 22 02, 21

MUT11 MUT06 MUT07 MUT11

Tab. 2.108 Fuse Assignment R:STMI/LTG with TSG(B) and DLUV for Rack 8 ft.

Fuse Assignment R:STMI/LTG with TSG(B) and DLUV for Rack 7 ft. FU 09 10 29 30 07 08 27 28 10, 29 05, 25 MUT MUT03 MUT03 MUT03 MUT03 MUT04 MUT04 MUT04 MUT04 MUT10 MUT05 Unit F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) F:DLUV(A) FANTRAY F:LTGP(A) F:STMI F:LTGP(A) F:STMI FANTRAY F:TSG(B) F:TSG(B) FAN-BOX C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15 C123P1 for DLUV0, 1, 2, 3 C187P1 for DLUV4, 5, 6, 7 C251P1 for DLUV8, 9, 10, 11 C313P1 for DLUV12, 13, 14, 15 X1/X2 - X6/X7 C151 X1/X2 (LTG1-16) C121 X1/X2 (LTG1-16) C281 X1/X2 (LTG 17-32) C251 X1/X2 (LTG 17-32 X1/X2 - X6/X7 UE1 (SN0) UE1 (SN1) X1/X2 - X6/X7 MOLOC

06, 26

MUT05

06 25 01 22 02, 21

MUT11 MUT06 MUT07 MUT11

Tab. 2.109 Fuse Assignment R:STMI/LTG with TSG(B) and DLUV for Rack 7 ft.

A30828-X1160-M-2-7620

169

Construction

Maintenance Node

2.100

R:MB/CCG
Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:MB/CCG(B) 0

MUT01 MUT02

Fuse Panel F:MB/CCG(B) 0

MUT01 MUT02

F:MB/CCG(B) 1

MUT03

F:MB/CCG(B) 1

MUT03

F:SYPC(A)

MUT05

F:SYPC(A)

MUT05

F:MB/CCG(B) 0

MUT08

F:MB/CCG(B) 0 F:MB/CCG(B)

MUT08

F:MB/CCG(B) 1

MUT09

F:MB/CCG(B) 1

MUT09

rack 8 ft. FU 01 02 11 12 03 05 06 07 08 09 15 04 14 MUT MUT02 / F:MB/CCG(B) MUT02 / F:MB/CCG(B) MUT03 / F:MB/CCG(B) MUT03 / F:MB/CCG(B) MUT05 / F:SYPC(A) MUT05 / SYPC MUT05 / SYPC MUT05 / SYPC MUT05 / SYPC MUT05 / F:SYPC(A) MUT05 / F:SYPC(A) MUT08 / F:MB/CCG(B) MUT09 / F:MB/CCG(B) A001 (MB 0) A121 (CCG 0) A001 (MB 1) A121 (CCG 1) A001 (DCCCR) SYPD1 SYPD2 SYPD3 SYPD0 A043 (TXA:SYPC) A116 (DCCCL) A001 (MB 0) A001 (MB 1)

rack 7 ft. MOLOC

Tab. 2.110 Fuse Assignment R:MB/CCG

170

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.101

R:MB/CCG with FAN


Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:MB/CCG(B) 0

MUT01 MUT02

Fuse Panel F:MB/CCG(B) 0

MUT01 MUT02

F:MB/CCG(B) 1

MUT03

F:MB/CCG(B) 1

MUT03

F:SYPC(A) FAN (B5681) F:MBD 0

MUT05 F:SYPC(A) MUT06 FAN (B5681) MUT07 F:MBD 0 MUT06 MUT08 MUT05

F:MBD 1

MUT08

F:MBD 1

MUT09

FAN-BOX (B5877)

MUT10

FAN-BOX (B5877) rack 7 ft.

MUT10

rack 8 ft.

FU 01, 02 03, 05, 06, 07, 08, 09, 15 11, 12 03 04 14 15

MUT MUT02 / MB/CCG 0 MUT02 / MB/CCG 1 MUT10 / FAN-BOX MUT07 / MBD 0 MUT07 / MBD 0 MUT08 / MBD 1 MUT08 / MBD 1 C109P1 C341P1 C109P1 C341P1

MOLOC

Tab. 2.111 Fuse Assignment MD/CCG with FAN

A30828-X1160-M-2-7620

171

Construction

Maintenance Node

2.102

R:MBD/CCGE
Fuse Panel
ON OFF 01 02 03 05 07 09 11 13 15 04 06 08 10 12 14 16 17 50 49 18 19 20 21 23 25 27 29 31 22 24 26 28 30 32 ON OFF

Fuse Panel

MUT01

Fuse Panel

MUT01

F:MBD 0

MUT02

F:MBD 0

MUT02

F:MBD 1 FANTRAY (U103) (U2620) F:CCGE

MUT03 MUT05 MUT06

F:MBD 1 FANTRAY (U103) (U2620) F:CCGE

MUT03 MUT05 MUT06

F:SCB

MUT07

F:SCB

MUT08

IDF # FAN-BOX (U102) rack 8 ft.

MUT19 #) MUT10

IDF # FAN-BOX (U102)

MUT09 MUT10

rack 7 ft. #) mounting position on rear side of rack

FU 04 05 28 29 03 30 02 31 06 27

MUT MUT04 / F:MBD 0 MUT04 / F:MBD 0 MUT05 / F:MBD 1 MUT05 / F:MBD 1 MUT06 / FANTRAY MUT06 / FANTRAY MUT07 / F:CCGE MUT07 / F:CCGE MUT09 / F:SCB MUT09 / F:SCB C109P1 C341P1 C109P1 C341P1 X1 / X2 X6 / X7 C137P1 C269P1 C179P1 C191P1

MOLOC

Tab. 2.112 Fuse Assignment R:MBD/CCGE

172

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 01 32

MUT MUT10 / FAN-BOX MUT10 / FAN-BOX X1 / X2 X6 / X7

MOLOC

Tab. 2.112 Fuse Assignment R:MBD/CCGE

2.103
2.103.1

R:SE
R:SE (-C2539-)
Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel

MUT01

Fuse Panel DAS(A) MUT03 DAS(A) DAS(A) MUT04 DAS(A)

MUT01

MUT03

MUT04

DAS(A)

MUT07 DAS(A) MUT07

DAS(A)

MUT08 DAS(A) MUT08

rack 8 ft. FU 02 05 12 13 MUT MUT03 / DAS(A) MUT04 / DAS(A) MUT07 / DAS(A) MUT08 / DAS(A) Supply voltage for DAS Supply voltage for DAS Supply voltage for DAS Supply voltage for DAS

rack 7 ft. MOLOC

Tab. 2.113 Fuse Assignment R:SE (-C2539-)

A30828-X1160-M-2-7620

173

Construction

Maintenance Node

2.103.2

R:SE (-C2539-X100)
Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel DAS300 or DAS400 DAS300 or DAS400 F:SYPC(A) DAS300 or DAS400 DAS300 or DAS400 DAS300 or DAS400 DAS300 or DAS400 F:SYPC(A) DAS300 or DAS400 DAS300 or DAS400 DAS300 or DAS400 DAS300 or DAS400 DAS300 or DAS400 DAS300 or DAS400 rack 8 ft.

MUT01 MUT02 MUT03 MUT04 MUT05 MUT06 MUT07 MUT16 MUT17 MUT18 MUT09 MUT10 MUT11 MUT14 MUT15

FU 01 11 04 03 13 02 15 06 12 14 05

MUT MUT02 / DAS300 or DAS400 MUT03 / DAS300 or DAS400 MUT04 / DAS300 or DAS400 MUT05 / DAS300 or DAS400 MUT06 / DAS300 or DAS400 MUT07 / DAS300 or DAS400 MUT09 / DAS300 or DAS400 MUT10 / DAS300 or DAS400 MUT16 / DAS300 or DAS400 MUT17 / DAS300 or DAS400 MUT18 / DAS300 or DAS400 Supply voltage for DAS Supply voltage for DAS Supply voltage for DAS Supply voltage for DAS Supply voltage for DAS Supply voltage for DAS Supply voltage for DAS Supply voltage for DAS Supply voltage for DAS Supply voltage for DAS Supply voltage for DAS

MOLOC

Tab. 2.114 Fuse Assignment R:SE (-C2539-X100)

174

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 07

MUT MUT14 / DAS300 or DAS400 MUT04 / F:SYPC(A) MUT17 / F:SYPC(A) Supply voltage for DAS A001 (DCCCR) A001 (DCCCR) SYPD1 SYPD1 SYPD2 SYPD2 A043 (TXA:SYPC) A043 (TXA:SYPC) A116 (DCCCL) A116 (DCCCL) SYPD3 SYPD3 SYPD0 SYPD0

MOLOC

08

MUT04 / SYPD MUT17 / SYPD

09

MUT04 / SYPD MUT17 / SYPD

10

MUT04 / F:SYPC(A) MUT17 / F:SYPC(A)

16

MUT04 / F:SYPC(A) MUT17 / F:SYPC(A)

17

MUT04 / SYPD MUT17 / SYPD

18

MUT04 / SYPD MUT17 / SYPD

Tab. 2.114 Fuse Assignment R:SE (-C2539-X100)

A30828-X1160-M-2-7620

175

Construction

Maintenance Node

2.103.3

R:SE (-C2539-X100) with Profibus


Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel

MUT01

Holdr-F (Profibus)

MUT04

Holdr-F (Profibus)

MUT06

Holdr-F (Profibus)

MUT19

rack 8 ft.

FU 07 08 09

MUT MUT04 or 06 or 19 MUT04 or 06 or 19 MUT04 or 06 or 19

MOLOC Supply voltage for Profibus 5 and 6 Supply voltage for Profibus 2 and 4 Supply voltage for Profibus 1 and 3

Tab. 2.115 Fuse Assignment R:SE (-C2539-X100) with Probus

176

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.103.4

R:SE (-C2539-X600)
Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel

MUT01

F:SYPC(A) DAS300 or DAS400 DAS300 or DAS400 DAS300 or DAS400 DAS300 or DAS400 F:SYPC(A) DAS(A)

MUT04 MUT05 MUT06 MUT07 MUT16 MUT17 MUT08

rack 8 ft.

FU 03 13 02 12 07

MUT MUT05 / DAS300 or DAS400 MUT06 / DAS300 or DAS400 MUT07 / DAS300 or DAS400 MUT08 / DAS(A) MUT04 / F:SYPC(A) MUT17 / F:SYPC(A)

MOLOC Supply voltage for DAS Supply voltage for DAS Supply voltage for DAS Supply voltage for DAS A001 (DCCCR) A001 (DCCCR) SYPD1 SYPD1 SYPD2 SYPD2 A043 (TXA:SYPC) A043 (TXA:SYPC)

08

MUT04 / SYPD MUT17 / SYPD

09

MUT04 / SYPD MUT17 / SYPD

10

MUT04 / F:SYPC(A) MUT17 / F:SYPC(A)

Tab. 2.116 Fuse Assignment R:SE (-C2539-X600)

A30828-X1160-M-2-7620

177

Construction

Maintenance Node

FU 16

MUT MUT04 / F:SYPC(A) MUT17 / F:SYPC(A) A116 (DCCCL) A116 (DCCCL) SYPD3 SYPD3 SYPD0 SYPD0

MOLOC

17

MUT04 / SYPD MUT17 / SYPD

18

MUT04 / SYPD MUT17 / SYPD

Tab. 2.116 Fuse Assignment R:SE (-C2539-X600)

2.104

R:SILTD
Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:SILTD(A)

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:SILTD(A)

MUT03

F:SILTD(A)

F:SILTD(A)

MUT03

F:SILTD(A)

MUT04

F:SILTD(A)

MUT04

F:SILTD(A)

MUT05

F:SILTD(A)

MUT05

F:SILTD(A) F:SILTD(A) MUT06 F:SILTD(A) F:SILTD(A) MUT07

MUT06

MUT07

rack 8 ft.

rack 7 ft.

178

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 01 11 03 13 05 15 07 17 09 19 10 20

MUT MUT02 / F:SILTD 0 MUT02 / F:SILTD 0 MUT03 / F:SILTD 1 MUT03 / F:SILTD 1 MUT04 / F:SILTD 2 MUT04 / F:SILTD 2 MUT05 / F:SILTD 3 MUT05 / F:SILTD 3 MUT06 / F:SILTD 4 MUT06 / F:SILTD 4 MUT07 / F:SILTD 5 MUT07 / F:SILTD 5 A001 A120 A001 A120 A001 A120 A001 A120 A001 A120 A001 A120

MOLOC

Tab. 2.117 Fuse Assignment R:SILTD

A30828-X1160-M-2-7620

179

Construction

Maintenance Node

2.105
2.105.1

R:SSNC (basic rack)


R:SSNC (basic rack minimal configuration)
Fuse Panel
ON OFF 01 02 03 05 07 09 11 13 15 04 06 08 10 12 14 16 17 50 49 18 19 20 21 23 25 27 29 31 22 24 26 28 30 32 ON OFF

Fuse Panel

MUT01

Fuse Panel

MUT01

FANTRAY (U103) (U2620) IDF #

MUT07 MUT18 #) MUT09

FANTRAY (U103) (U2620) IDF #

MUT07 MUT18 #)

F:SCB

F:SCB

MUT09

FAN-BOX (U102)

MUT10

FAN-BOX (U102)

MUT10

rack 8 ft.

rack 7 ft. #) mounting position on rear side of rack

FU 01, 32 02 31 10, 32 49, 50 MUT07 MUT09 MUT09 MUT10 MUT01

MUT

Connector X2/X1, X7/X6 C179P1 C191P1 X6/X7, X1/X2 Fan Tray F:SCB side 0 F:SCB side 1 FAN-BOX reserved for SM:ALMC

Unit

Tab. 2.118 Fuse Assignment R:SSNC (basic rack minimal conguration)

180

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.105.2

R:SSNC (basic rack maximal configuration with 1 SCE and ASN(E))


Fuse Panel
ON OFF 01 02 03 05 07 09 11 13 15 04 06 08 10 12 14 16 17 50 49 18 19 20 21 23 25 27 29 31 22 24 26 28 30 32 ON OFF

Fuse Panel FANTRAY (U103) (U2620) F:SCE

MUT01 MUT02 Fuse Panel MUT03 FANTRAY (U103) (U2620) F:SCE MUT01 MUT02 MUT03

IDF #

MUT14 #) IDF # MUT14 #)

F:ASN(E)1

MUT05 F:ASN(E) 1 MUT05

F:ASN(E) 0

MUT07 F:ASN(E) 0 MUT07

IDF #

MUT18 #) MUT09

IDF #

MUT18 #)

F:SCB

F:SCB

MUT09

FAN-BOX (U102)

MUT10

FAN-BOX (U102)

MUT10

rack 8 ft.

rack 7 ft. #) mounting position on rear side of rack

FU 01, 32 08, 24 09, 25 28 29 30 03 04 05 02 MUT02 MUT03 MUT03 MUT05 MUT05 MUT05 MUT07 MUT07 MUT07 MUT09

MUT

Connector X2/X1, X7/X6 D221P4, D261P4 D221P5, D261P5 C263P1 C263P3 C263P5 C263P1 C263P3 C263P5 C179P1 Fan Tray

Unit

F:SCE side 0 (voltage input 0, 1 per module) F:SCE side 1 (voltage input 0, 1 per module) F:ASN(E) 1 F:ASN(E) 1 F:ASN(E) 1 F:ASN(E) 0 F:ASN(E) 0 F:ASN(E) 0 F:SCB side 0

Tab. 2.119 Fuse Assignment R:SSNC (basic rack max. conf. with 1 SCE and ASN(E))

A30828-X1160-M-2-7620

181

Construction

Maintenance Node

FU 31 10, 32 49, 50 MUT09 MUT10 MUT01

MUT

Connector C191P1 X6/X7, X1/X2 F:SCB side 1 FAN-BOX reserved for SM:ALMC

Unit

Tab. 2.119 Fuse Assignment R:SSNC (basic rack max. conf. with 1 SCE and ASN(E))

2.105.3

R:SSNC (basic rack with 1 SCE and ASN(H))


Fuse Panel
ON OFF 01 02 03 05 07 09 11 13 15 04 06 08 10 12 14 16 17 50 49 18 19 20 21 23 25 27 29 31 22 24 26 28 30 32 ON OFF

Fuse Panel

MUT01

Fuse Panel

MUT01

FANTRAY (U103) (U2620)

MUT03 FANTRAY (U103) (U2620) MUT03

F:SCE IDF F:ASN(H) IDF F:SCB

MUT05 MUT16 #) F:SCE IDF MUT07 F:ASN(H) MUT18 #) IDF MUT09 F:SCB MUT09 MUT18 #) MUT07 MUT05 MUT16 #)

FAN-BOX (U102)

MUT10

FAN-BOX (U102)

MUT10

rack 8 ft.

rack 7 ft. #) mounting position on rear side of rack

FU 01, 32 04, 28 05, 29 MUT03 MUT05 MUT05

MUT

Connector X2/X1, X7/X6 D221P4, D261P4 D221P5, D261P5 Fan Tray

Unit

F:SCE side 0 (voltage input 0, 1 per module) F:SCE side 1 (voltage input 0, 1 per module)

Tab. 2.120 Fuse Assignment R:SSNC (basic rack with 1 SCE and ASN(H))

182

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 03 26 02 31 10, 32 49, 50 MUT07 MUT07 MUT09 MUT09 MUT10 MUT01

MUT

Connector C147P1 C295P1 C179P1 C191P1 X6/X7, X1/X2 F:ASN(H) ASN 0 F:ASN(H) ASN 1 F:SCB side 0 F:SCB side 1 FAN-BOX reserved for SM:ALMC

Unit

Tab. 2.120 Fuse Assignment R:SSNC (basic rack with 1 SCE and ASN(H))

2.105.4

R:SSNC (basic rack with 2 SCE and ASN(H))


Fuse Panel
ON OFF 01 02 03 05 07 09 11 13 15 04 06 08 10 12 14 16 17 50 49 18 19 20 21 23 25 27 29 31 22 24 26 28 30 32 ON OFF

Fuse Panel FANTRAY (U103) (U2620) F:SCE

MUT01 MUT02 Fuse Panel MUT03 FANTRAY (U103) (U2620) F:SCE IDF # MUT01 MUT02 MUT03 MUT14 #) MUT05

IDF #

MUT14 #)

F:SCE

MUT05 F:SCE

IDF #

MUT16 #) IDF # MUT16 #) MUT07 MUT18 #) MUT09

F:ASN(H)

MUT07 F:ASN(H)

IDF #

MUT18 #)

IDF # F:SCB FAN-BOX (U102)

F:SCB

MUT09

FAN-BOX (U102)

MUT10

MUT10

rack 8 ft.

rack 7 ft. #) mounting position on rear side of rack

A30828-X1160-M-2-7620

183

Construction

Maintenance Node

FU 01, 32 08, 24 09, 25 04, 28 05, 29 03 26 02 31 10, 32 49, 50 MUT02 MUT03 MUT03 MUT05 MUT05 MUT07 MUT07 MUT09 MUT09 MUT10 MUT01

MUT

Connector X2/X1, X7/X6 D221P4, D261P4 D221P5, D261P5 D221P4, D261P4 D221P5, D261P5 C147P1 C295P1 C179P1 C191P1 X6/X7, X1/X2 Fan Tray

Unit

F:SCE side 0 (voltage input 0, 1 per module) F:SCE side 1 (voltage input 0, 1 per module) F:SCE side 0 (voltage input 0, 1 per module) F:SCE side 1 (voltage input 0, 1 per module) F:ASN(H) ASN 0 F:ASN(H) ASN 1 F:SCB side 0 F:SCB side 1 FAN-BOX reserved for SM:ALMC

Tab. 2.121 Fuse Assignment R:SSNC (basic rack with 2 SCE and ASN(H))

184

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.106
2.106.1

R:SSNC (extension rack)


R:SSNC (extension rack with 1 SCE)
Fuse Panel
ON OFF 01 02 03 05 07 09 11 13 15 04 06 08 10 12 14 16 17 50 49 18 19 20 21 23 25 27 29 31 22 24 26 28 30 32 ON OFF

Fuse Panel

MUT01

Fuse Panel

MUT01

FANTRAY (U103) (U2620)

MUT07

FANTRAY (U103) (U2620)

MUT07

F:SCE IDF FAN-BOX (U102)

MUT09 MUT19 #) MUT10

F:SCE IDF FAN-BOX (U102)

MUT09 MUT19 #) MUT10

rack 8 ft.

rack 7 ft. #) mounting position on rear side of rack

FU 01, 32 02, 30 03, 31 10, 32 49, 50 MUT07 MUT09 MUT09 MUT10

MUT

Connector X2/X1, X7/X6 D221P4, D261P4 D221P5, D261P5 X6/X7, X1/X2 Fan Tray

Unit

F:SCE side 0 (voltage input 0, 1 per module) F:SCE side 1 (voltage input 0, 1 per module) FAN-BOX reserved for SM:ALMC

Tab. 2.122 Fuse Assignment R:SSNC (extension rack with 1 SCE)

A30828-X1160-M-2-7620

185

Construction

Maintenance Node

2.106.2

R:SSNC (extension rack with 2 SCE)


Fuse Panel
ON OFF 01 02 03 05 07 09 11 13 15 04 06 08 10 12 14 16 17 50 49 18 19 20 21 23 25 27 29 31 22 24 26 28 30 32 ON OFF

Fuse Panel

MUT01

Fuse Panel

MUT01

FANTRAY (U103) (U2620)

MUT05 FANTRAY (U103) (U2620) MUT05

F:SCE IDF F:SCE IDF FAN-BOX (U102)

MUT07 F:SCE MUT18 #) IDF MUT09 MUT19 #) MUT10 F:SCE IDF FAN-BOX (U102) MUT18 #) MUT09 MUT19 #) MUT10 MUT07

rack 8 ft.

rack 7 ft. #) mounting position on rear side of rack

FU 01, 32 06, 26 07, 27 02, 30 03, 31 10, 32 49, 50 MUT05 MUT07 MUT07 MUT09 MUT09 MUT10

MUT

Connector X2/X1 D221P4, D261P4 D221P5, D261P5 D221P4, D261P4 D221P5, D261P5 X6/X7, X1/X2 Fan Tray

Unit

F:SCE side 0 (voltage input 0, 1 per module) F:SCE side 1 (voltage input 0, 1 per module) F:SCE side 0 (voltage input 0, 1 per module) F:SCE side 1 (voltage input 0, 1 per module) FAN-BOX reserved for SM:ALMC

Tab. 2.123 Fuse Assignment R:SSNC (extension rack with 2 SCE)

186

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.106.3

R:SSNC (extension rack with 3 SCE)


Fuse Panel
ON OFF 01 02 03 05 07 09 11 13 15 04 06 08 10 12 14 16 17 50 49 18 19 20 21 23 25 27 29 31 22 24 26 28 30 32 ON OFF

Fuse Panel

MUT01

Fuse Panel

MUT01

FANTRAY (U103) (U2620)

MUT03 FANTRAY (U103) (U2620) MUT03

F:SCE IDF F:SCE IDF F:SCE IDF FAN-BOX (U102)

MUT05 F:SCE MUT16 #) IDF MUT07 F:SCE MUT18 #) IDF MUT09 MUT19 #) MUT10 F:SCE IDF FAN-BOX (U102) MUT18 #) MUT09 MUT19 #) MUT10 MUT07 MUT16 #) MUT05

rack 8 ft.

rack 7 ft. #) mounting position on rear side of rack

FU 01, 32 04, 28 05, 29 06, 26 07, 27 02, 30 03, 31 10, 32 49, 50 MUT03 MUT05 MUT05 MUT07 MUT07 MUT09 MUT09 MUT10

MUT

Connector X2/X1, X7/X6 D221P4, D261P4 D221P5, D261P5 D221P4, D261P4 D221P5, D261P5 D221P4, D261P4 D221P5, D261P5 X6/X7, X1/X2 Fan Tray

Unit

F:SCE side 0 (voltage input 0, 1 per module) F:SCE side 1 (voltage input 0, 1 per module) F:SCE side 0 (voltage input 0, 1 per module) F:SCE side 1 (voltage input 0, 1 per module) F:SCE side 0 (voltage input 0, 1 per module) F:SCE side 1 (voltage input 0, 1 per module) FAN-BOX reserved for SM:ALMC

Tab. 2.124 Fuse Assignment R:SSNC (extension rack with 3 SCE)

A30828-X1160-M-2-7620

187

Construction

Maintenance Node

2.106.4

R:SSNC (extension rack with 4 SCE)


Fuse Panel
ON OFF 01 02 03 05 07 09 11 13 15 04 06 08 10 12 14 16 17 50 49 18 19 20 21 23 25 27 29 31 22 24 26 28 30 32 ON OFF

Fuse Panel FANTRAY (U103) (U2620) F:SCE IDF F:SCE IDF F:SCE IDF F:SCE IDF FAN-BOX (U102)

MUT01 MUT02 Fuse Panel MUT03 MUT14 #) MUT05 MUT16 #) IDF MUT07 F:SCE MUT18 #) IDF MUT09 MUT19 #) MUT10 F:SCE IDF FAN-BOX (U102) MUT18 #) MUT09 MUT19 #) MUT10 MUT07 MUT16 #) FANTRAY (U103) (U2620) F:SCE IDF F:SCE MUT01 MUT02 MUT03 MUT14 #) MUT05

rack 8 ft.

rack 7 ft. #) mounting position on rear side of rack

FU 01 08, 24 09, 25 04, 28 05, 29 06, 26 07, 27 02, 30 03, 31 MUT02 MUT03 MUT03 MUT05 MUT05 MUT07 MUT07 MUT09 MUT09

MUT

Connector X2/X1, X7/X6 D221P4, D261P4 D221P5, D261P5 D221P4, D261P4 D221P5, D261P5 D221P4, D261P4 D221P5, D261P5 D221P4, D261P4 D221P5, D261P5 Fan Tray

Unit

F:SCE side 0 (voltage input 0, 1 per module) F:SCE side 1 (voltage input 0, 1 per module) F:SCE side 0 (voltage input 0, 1 per module) F:SCE side 1 (voltage input 0, 1 per module) F:SCE side 0 (voltage input 0, 1 per module) F:SCE side 1 (voltage input 0, 1 per module) F:SCE side 0 (voltage input 0, 1 per module) F:SCE side 1 (voltage input 0, 1 per module)

Tab. 2.125 Fuse Assignment R:SSNC (extension rack with 4 SCE)

188

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 10, 32 49, 50 MUT10

MUT

Connector X6/X7, X1/X2 FAN-BOX reserved for SM:ALMC

Unit

Tab. 2.125 Fuse Assignment R:SSNC (extension rack with 4 SCE)

2.107

R:SN (with DCCXI)


Fuse Panel
FU 01 02 03 04 05 06 07 08 09 10 11 12 13 14 FU-A

FU FU

01 02

03 05 04 06

07 08

09 10

11 12

13 14

15 16

17 18

19 20

FU FU FU-N

Fuse Panel A F:SN(A) 0 or F:SSG(A) 0 or F:TSG(A) 0 F:SN(A) 1 or F:SSG(A) 1 or F:TSG(A) 1

MUT01

MUT02

C A

MUT03

DCCXI 00 DCCXI 01 DCCXI 10 DCCXI 11

MUT04 MUT05 MUT06 MUT07

rack 8 ft.

FU-A 01 02 03 04

FU-N 01 02 03 04

MUT MUT04 / F:DCCXI 00 MUT05 / F:DCCXI 01 MUT06 / F:DCCXI 10 MUT07 / F:DCCXI 11 SN-0 / TSG 0 / SSG 0 SN-0 / TSG 0 / SSG 0 SN-1 / TSG 1 / SSG 1 SN-1 / TSG 1 / SSG 1

MOLOC

Tab. 2.126 Fuse Assignment R:SN (with DCCXI)

A30828-X1160-M-2-7620

189

Construction

Maintenance Node

2.108

R:SN (with DCCCS)


Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel A F:SN(A) 0 or F:SSG(A) 0 or F:TSG(A) 0 F:SN(A) 1 or F:SSG(A) 1 or F:TSG(A) 1

MUT01

MUT02

C A

MUT03

F:DCC(B)

MUT09

rack 8 ft.

FU 01 02 03 11 12 13 MUT09 / F:DCC(B) 0 MUT09 / F:DCC(B) 0 MUT09 / F:DCC(B) 0 MUT09 / F:DCC(B) 1 MUT09 / F:DCC(B) 1 MUT09 / F:DCC(B) 1

MUT A001 for SN-0 A017 for SN-0 A033 for SN-0 A067 for SN-1 A083 for SN-1 A099 for SN-1

MOLOC

Tab. 2.127 Fuse Assignment R:SN with DCCCS

190

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.109

R:SN(B) / SNMUX / LTGG (cabling from above)


Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:SNMUX(A) 0

MUT01 MUT02 Fuse Panel MUT01

F:SNMUX(A) 1

MUT03 F:SNMUX(A) 0 MUT02

F:LTGG(A)

MUT04 F:SNMUX(A) 1 MUT03

F:LTGG(A) F:LTGG(A) MUT05

MUT04

F:LTGG(A)

MUT06

F:LTGG(A)

MUT05

F:LTGG(A)

MUT06

F:LTGG(A)

MUT06

rack 8 ft. FU 01 02 11 12 03 04 13 14 05 06 15 16 MUT MUT02 / F:SNMUX(A) MUT02 / F:SNMUX(A) MUT03 / F:SNMUX(A) MUT03 / F:SNMUX(A) MUT04 / F:LTGG(A) MUT04 / F:LTGG(A) MUT05 / F:LTGG(A) MUT05 / F:LTGG(A) MUT06 / F:LTGG(A) MUT06 / F:LTGG(A) MUT07 / F:LTGG(A) MUT07 / F:LTGG(A) SN0 SN0 SN1 SN1 A101 (left LTG) A123 (right LTG) A101 (left LTG) A123 (right LTG) A101 (left LTG) A123 (right LTG) A101 (left LTG) A123 (right LTG)

rack 7 ft. MOLOC

Tab. 2.128 Fuse Assignment R:SN(B) / SNMUX / LTGG (cabling from above)

A30828-X1160-M-2-7620

191

Construction

Maintenance Node

2.110

R:SN(B) / SNMUX / LTGG (cabling from below)


Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:LTGG(A)

MUT01 MUT02 Fuse Panel MUT01

F:LTGG(A)

MUT03 F:LTGG(A) MUT02

F:LTGG(A)

MUT04 F:LTGG(A) MUT03

F:LTGG(A) F:LTGG(A) MUT05

MUT04

F:SNMUX(A) 0

MUT06

F:SNMUX(A) 0

MUT06

F:SNMUX(A) 1

MUT07

F:SNMUX(A) 1

MUT07

rack 8 ft.

rack 7 ft.

FU 05 06 15 16 03 04 13 14 01 02 11 12

MUT MUT02 / F:LTGG(A) MUT02 / F:LTGG(A) MUT03 / F:LTGG(A) MUT03 / F:LTGG(A) MUT04 / F:LTGG(A) MUT04 / F:LTGG(A) MUT05 / F:LTGG(A) MUT05 / F:LTGG(A) MUT06 / F:SNMUX(A) MUT06 / F:SNMUX(A) MUT07 / F:SNMUX(A) MUT07 / F:SNMUX(A) A101 (left LTG) A123 (right LTG) A101 (left LTG) A123 (right LTG) A101 (left LTG) A123 (right LTG) A101 (left LTG) A123 (right LTG) SN0 SN0 SN1 SN1

MOLOC

Tab. 2.129 Fuse Assignment R:SN(B) / SNMUX / LTGG (cabling from below)

192

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.111

R:SN(B) / SNCARE / LTGG (cabling from above)


Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:SNCARE

MUT01 MUT02 Fuse Panel MUT01

F:SNCARE

MUT03 F:SNCARE MUT02

F:LTGG(A)

MUT04 F:SNCARE MUT03

F:LTGG(A) F:LTGG(A) MUT05

MUT04

F:LTGG(A)

MUT06

F:LTGG(A)

MUT05

F:LTGG(A)

MUT07

F:LTGG(A)

MUT06

rack 8 ft.

rack 7 ft.

FU 03 04 05 06 13 14 15 16

MUT MUT04 / F:LTGG(A) MUT04 / F:LTGG(A) MUT06 / F:LTGG(A) MUT06 / F:LTGG(A) MUT05 / F:LTGG(A) MUT05 / F:LTGG(A) MUT07 / F:LTGG(A) MUT07 / F:LTGG(A) A101 (left LTG) A123 (right LTG) A101 (left LTG) A123 (right LTG) A101 (left LTG) A123 (right LTG) A101 (left LTG) A123 (right LTG)

MOLOC

Tab. 2.130 Fuse Assignment R:SN(B) / SNCARE / LTGG (cabling from above)

A30828-X1160-M-2-7620

193

Construction

Maintenance Node

2.112

R:SN(B) / SNCARE / LTGG (cabling from below)


Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:LTGG(A)

MUT01 MUT02 Fuse Panel MUT01

F:LTGG(A)

MUT03 F:LTGG(A) MUT02

F:LTGG(A)

MUT04 F:LTGG(A) MUT03

F:LTGG(A) F:LTGG(A) MUT05

MUT04

F:SNCARE

MUT06

F:SNCARE

MUT06

F:SNCARE

MUT07

F:SNCARE

MUT07

rack 8 ft.

rack 7 ft.

FU 05 06 15 16 03 04 13 14

MUT MUT02 / F:LTGG(A) MUT02 / F:LTGG(A) MUT03 / F:LTGG(A) MUT03 / F:LTGG(A) MUT04 / F:LTGG(A) MUT04 / F:LTGG(A) MUT05 / F:LTGG(A) MUT05 / F:LTGG(A) A101 (left LTG) A123 (right LTG) A101 (left LTG) A123 (right LTG) A101 (left LTG) A123 (right LTG) A101 (left LTG) A123 (right LTG)

MOLOC

Tab. 2.131 Fuse Assignment R:SN(B) / SNCARE / LTGG (cabling from below)

194

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.113

R:SN(B)/LTGM (cabling from above)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:TSG(B) 0

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:TSG(B) 1

MUT03 F:TSG(B) 0

F:LTGM(A)

MUT04 F:TSG(B) 1 MUT03

F:LTGM(A) F:LTGM(A) MUT05

MUT04

F:LTGM(A)

MUT06

F:LTGM(A)

MUT06

F:LTGM(A)

MUT07

F:LTGM(A)

MUT07

rack 8 ft.

rack 7 ft.

FU 01 32 08 09 10 11

MUT MUT02 / F:TSG(B) MUT03 / F:TSG(B) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) C331 / SN-0 C331 / SN-1 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3

MOLOC

Tab. 2.132 Fuse Assignment R:SN(B)/LTGM (cabling from above)

A30828-X1160-M-2-7620

195

Construction

Maintenance Node

FU 12 22 23 24 25 26 03 04 05 06 07 27 28 29 30 31

MUT MUT04 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4

MOLOC

Tab. 2.132 Fuse Assignment R:SN(B)/LTGM (cabling from above)

196

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.114

R:SN(B)/LTGM (cabling from below)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:LTGM(A)

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGM(A)

MUT03 F:LTGM(A)

F:LTGM(A)

MUT04 F:LTGM(A) MUT03

F:LTGM(A)

MUT05

F:LTGM(A)

MUT04

F:TSG(B) 0

MUT06 F:TSG(B) 0 MUT06

F:TSG(B) 1

MUT07 F:TSG(B) 1 MUT07

rack 8 ft.

rack 7 ft.

FU 03 04 05 06 07 27

MUT MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT03 / F:LTGM(A) C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0

MOLOC

Tab. 2.133 Fuse Assignment R:SN(B)/LTGM (cabling from below)

A30828-X1160-M-2-7620

197

Construction

Maintenance Node

FU 28 29 30 31 08 09 10 11 12 22 23 24 25 26 01 32

MUT MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT06 / F:TSG(B) MUT07 / F:TSG(B) C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C331 / SN-0 C331 / SN-1

MOLOC

Tab. 2.133 Fuse Assignment R:SN(B)/LTGM (cabling from below)

198

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.115

R:SN(B)/LTGM/SNCARE (cabling from above)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:SNCARE

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:SNCARE

MUT03 F:SNCARE

F:LTGM(A)

MUT04 F:SNCARE MUT03

F:LTGM(A) F:LTGM(A) MUT05

MUT04

F:LTGM(A)

MUT06

F:LTGM(A)

MUT06

F:LTGM(A)

MUT07

F:LTGM(A)

MUT07

rack 8 ft.

rack 7 ft.

FU 08 09 10 11 12 22

MUT MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT05 / F:LTGM(A) C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0

MOLOC

Tab. 2.134 Fuse Assignment R:SN(B)/LTGM/SNCARE (cabling from above)

A30828-X1160-M-2-7620

199

Construction

Maintenance Node

FU 23 24 25 26 03 04 05 06 07 27 28 29 30 31

MUT MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4

MOLOC

Tab. 2.134 Fuse Assignment R:SN(B)/LTGM/SNCARE (cabling from above)

200

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.116

R:SN(B)/LTGM/SNCARE (cabling from below)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:LTGM(A)

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGM(A)

MUT03 F:LTGM(A)

F:LTGM(A)

MUT04 F:LTGM(A) MUT03

F:LTGM(A) F:LTGM(A) MUT05

MUT04

F:SNCARE

MUT06 F:SNCARE MUT06

F:SNCARE

MUT07 F:SNCARE MUT07

rack 8 ft.

rack 7 ft.

FU 03 04 05 06 07 27

MUT MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT03 / F:LTGM(A) C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0

MOLOC

Tab. 2.135 Fuse Assignment R:SN(B)/LTGM/SNCARE (cabling from below)

A30828-X1160-M-2-7620

201

Construction

Maintenance Node

FU 28 29 30 31 08 09 10 11 12 22 23 24 25 26

MUT MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4

MOLOC

Tab. 2.135 Fuse Assignment R:SN(B)/LTGM/SNCARE (cabling from below)

202

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.117

R:SN(B)/LTGM/SNMUX (cabling from above)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:SNMUX(A) 0

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:SNMUX(A) 1

MUT03 F:SNMUX(A) 0

F:LTGM(A)

MUT04 F:SNMUX(A) 1 MUT03

F:LTGM(A) F:LTGM(A) MUT05

MUT04

F:LTGM(A)

MUT06

F:LTGM(A)

MUT06

F:LTGM(A)

MUT07

F:LTGM(A)

MUT07

rack 8 ft.

rack 7 ft.

FU 01 02 32 33 08 09

MUT MUT02 / F:SNMUX MUT02 / F:SNMUX MUT03 / F:SNMUX MUT03 / F:SNMUX MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) SN0 SN0 SN1 SN1 C101 / LTG 0 C151 / LTG 1

MOLOC

Tab. 2.136 Fuse Assignment R:SN(B)/LTGM/SNMUX (cabling from above)

A30828-X1160-M-2-7620

203

Construction

Maintenance Node

FU 10 11 12 22 23 24 25 26 03 04 05 06 07 27 28 29 30 31

MUT MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4

MOLOC

Tab. 2.136 Fuse Assignment R:SN(B)/LTGM/SNMUX (cabling from above)

204

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.118

R:SN(B)/LTGM/SNMUX (cabling from below)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:LTGM(A)

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGM(A)

MUT03 F:LTGM(A)

F:LTGM(A)

MUT04 F:LTGM(A) MUT03

F:LTGM(A) F:LTGM(A) MUT05

MUT04

F:SNMUX(A) 0

MUT06 F:SNMUX(A) 0 MUT06

F:SNMUX(A) 1

MUT07 F:SNMUX(A) 1 MUT07

rack 8 ft.

rack 7 ft.

FU 03 04 05 06 07

MUT MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4

MOLOC

Tab. 2.137 Fuse Assignment R:SN(B)/LTGM/SNMUX (cabling from below)

A30828-X1160-M-2-7620

205

Construction

Maintenance Node

FU 27 28 29 30 31 08 09 10 11 12 22 23 24 25 26 01 02 32 33

MUT MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT06 / F:SNMUX MUT06 / F:SNMUX MUT07 / F:SNMUX MUT07 / F:SNMUX C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 SN0 SN0 SN1 SN1

MOLOC

Tab. 2.137 Fuse Assignment R:SN(B)/LTGM/SNMUX (cabling from below)

206

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.119

R:SN(B)/MB/LTGM (cabling from above)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:TSG(B) 0

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:TSG(B) 1

MUT03 F:TSG(B) 0

F:MB/CCG(B) 0

MUT04 F:TSG(B) 1 MUT03

F:MB/CCG(B) 1

MUT05 F:MB/CCG(B) 0 MUT04

F:LTGM(A)

MUT06

F:MB/CCG(B) 1

MUT05

F:LTGM(A)

MUT07

F:LTGM(A)

MUT06

rack 8 ft.

rack 7 ft.

FU 01 32 08 09 22 23

MUT MUT02 / F:TSG(B) MUT03 / F:TSG(B) MUT04 / F:MB/CCG(B) MUT04 / F:MB/CCG(B) MUT04 / F:MB/CCG(B) MUT04 / F:MB/CCG(B) C331 (SN 0) C331 (SN 1) A001 / MB 0 A121 / CCG 0 A001 / MB 1 A!21 / CCG 1

MOLOC

Tab. 2.138 Fuse Assignment R:TSG(B)/LTGM (cabling from above)

A30828-X1160-M-2-7620

207

Construction

Maintenance Node

FU 03 04 05 06 07 27 28 29 30 31

MUT MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4

MOLOC

Tab. 2.138 Fuse Assignment R:TSG(B)/LTGM (cabling from above)

208

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.120

R:SN(B)/MB/LTGM (cabling from below)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:LTGM(A)

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGM(A)

MUT03 F:LTGM(A)

F:MB/CCG(B) 0

MUT04

F:MB/CCG(B) 1

MUT05

F:MB/CCG(B) 0

MUT04 MUT05

F:TSG(B) 0

MUT06

F:MB/CCG(B) 1

F:TSG(B) 1

MUT07

F:TSG(B) 0

MUT06

F:TSG(B) 1

MUT07

rack 8 ft.

rack 7 ft.

FU 03 04 05 06 07

MUT MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4

MOLOC

Tab. 2.139 Fuse Assignment R:SN(B)/MB/LTGM (cabling from below)

A30828-X1160-M-2-7620

209

Construction

Maintenance Node

FU 27 28 29 30 31 08 09 22 23 01 32

MUT MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT04 / F:MB/CCG(B) MUT04 / F:MB/CCG(B) MUT05 / F:MB/CCG(B) MUT05 / F:MB/CCG(B) MUT06 / F:TSG(B) MUT07 / F:TSG(B) C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 A001 / MB 0 A121 / CCG 0 A001 / MB 1 A121 / CCG 1 C331 / (SN 0) C331 / (SN 1)

MOLOC

Tab. 2.139 Fuse Assignment R:SN(B)/MB/LTGM (cabling from below)

210

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.121

R:SND/MBD/LTGM (with SNCARE, cabling from above)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:SNCARE

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:SNCARE

MUT03 F:SNCARE

FAN (B5681) F:MBD 0

MUT11 F:SNCARE MUT04 F:MBD 0 MUT04 MUT03

F:MBD 1

MUT05 F:MBD 1 MUT05 MUT06

F:LTGM(A)

MUT06

FAN (B5681)

F:LTGM(A)

MUT07

F:LTGM(A)

MUT07

FAN-BOX (B5877)

MUT12

FAN (B5681) FILTER:FAN

MUT10 MUT12

rack 8 ft.

rack 7 ft.

FU 08 09 18 19

MUT in 8 ft. MUT04 / F:MBD MUT04 / F:MBD MUT05 / F:MBD MUT05 / F:MBD

MOLOC C109P1 C341P1 C109P1 C341P1

MUT in 7 ft. MUT04 / F:MBD MUT04 / F:MBD MUT05 / F:MBD MUT05 / F:MBD

MOLOC C109P1 C341P1 C109P1 C341P1

Tab. 2.140 Fuse Assignment R:SN(D)/MBD/LTGM (with SNCARE, cabling from above)

A30828-X1160-M-2-7620

211

Construction

Maintenance Node

FU 03 04 05 06 07 27 28 29 30 31 10 20

MUT in 8 ft. MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT11 / FAN MUT12 / FAN-BOX

MOLOC C101P1 / LTG 0 C151P1 / LTG 1 C203P1 / LTG 2 C255P1 / LTG 3 C305P1 / LTG 4 C101P1 / LTG 0 C151P1 / LTG 1 C203P1 / LTG 2 C255P1 / LTG 3 C305P1 / LTG 4

MUT in 7 ft.

MOLOC

MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT06 / FAN MUT10 / FAN

C101P1 / LTG 0 C151P1 / LTG 1 C203P1 / LTG 2 C255P1 / LTG 3 C305P1 / LTG 4

Tab. 2.140 Fuse Assignment R:SN(D)/MBD/LTGM (with SNCARE, cabling from above)

212

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.122

R:SND/MBD/LTGM (with SNCARE, cabling from below)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:LTGM(A)

MUT01 MUT02 Fuse Panel MUT01 MUT02 MUT03 MUT04

F:LTGM(A)

MUT03

F:LTGM(A) FAN (B5681) F:MBD 0

FAN (B5681) F:MBD 0

MUT11 MUT04

F:MBD 1

MUT05

F:MBD 1

MUT05

F:SNCARE

MUT06

F:SNCARE

MUT06

F:SNCARE

MUT07

F:SNCARE

MUT07

FAN-BOX (B5877)

MUT12

FAN (B5681) FILTER:FAN

MUT10 MUT12

rack 8 ft.

rack 7 ft.

FU 03 04 05 06

MUT in 8 ft. MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A)

MOLOC C101P1 / LTG 0 C151P1 / LTG 1 C203P1 / LTG 2 C255P1 / LTG 3

MUT in 7 ft. MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A)

MOLOC C101P1 / LTG 0 C151P1 / LTG 1 C203P1 / LTG 2 C255P1 / LTG 3

Tab. 2.141 Fuse Assignment R:SN(D)/MBD/LTGM (with SNCARE, cabling from below)

A30828-X1160-M-2-7620

213

Construction

Maintenance Node

FU 07 27 28 29 30 31 08 09 18 19 10 20

MUT in 8 ft. MUT02 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT04 / F:MBD MUT04 / F:MBD MUT05 / F:MBD MUT05 / F:MBD MUT11 / FAN MUT12 / FAN-BOX

MOLOC C305P1 / LTG 4 C101P1 / LTG 0 C151P1 / LTG 1 C203P1 / LTG 2 C255P1 / LTG 3 C305P1 / LTG 4 C109P1 C341P1 C109P1 C341P1

MUT in 7 ft. MUT02 / F:LTGM(A)

MOLOC C305P1 / LTG 4

MUT04 / F:MBD MUT04 / F:MBD MUT05 / F:MBD MUT05 / F:MBD MUT03 / FAN MUT10 / FAN

C109P1 C341P1 C109P1 C341P1

Tab. 2.141 Fuse Assignment R:SN(D)/MBD/LTGM (with SNCARE, cabling from below)

214

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.123

R:SND/MBD/LTGM (with SNMUX, cabling from above)


Fuse Panel FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:SNMUX(A) 0

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:SNMUX(A) 1

MUT03 F:SNMUX(A) 0

FAN (B5681) F:MBD 0

MUT11 F:SNMUX(A) 1 MUT04 F:MBD 0 MUT04 MUT03

F:MBD 1

MUT05 F:MBD 1 MUT05 MUT06

F:LTGM(A)

MUT06

FAN (B5681)

F:LTGM(A)

F:LTGM(A)

MUT07

FAN-BOX (B5877)

MUT12

FAN (B5681) FILTER:FAN

MUT10 MUT12

rack 8 ft.

rack 7 ft.

FU 01 02 08 09 18 19 03 04 05 06

MUT in 8 ft. MUT02 / F:SNMUX(A) MUT03 / F:SNMUX(A) MUT04 / F:MBD MUT04 / F:MBD MUT05 / F:MBD MUT05 / F:MBD MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A)

MOLOC

MUT in 7 ft. MUT02 / F:SNMUX(A) MUT03 / F:SNMUX(A)

MOLOC

C109P1 C341P1 C109P1 C341P1 C101P1 / LTG 0 C151P1 / LTG 1 C203P1 / LTG 2 C255P1 / LTG 3

MUT04 / F:MBD MUT04 / F:MBD MUT05 / F:MBD MUT05 / F:MBD

C109P1 C341P1 C109P1 C341P1

Tab. 2.142 Fuse Assignment R:SN(D)/MBD/LTGM (with SNMUX, cabling from above)

A30828-X1160-M-2-7620

215

Construction

Maintenance Node

FU 07 27 28 29 30 31 10 20

MUT in 8 ft. MUT06 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT11 / FAN MUT12 / FAN-BOX

MOLOC C305P1 / LTG 4 C101P1 / LTG 0 C151P1 / LTG 1 C203P1 / LTG 2 C255P1 / LTG 3 C305P1 / LTG 4

MUT in 7 ft.

MOLOC

MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT06 / FAN MUT10 / FAN

C101P1 / LTG 0 C151P1 / LTG 1 C203P1 / LTG 2 C255P1 / LTG 3 C305P1 / LTG 4

Tab. 2.142 Fuse Assignment R:SN(D)/MBD/LTGM (with SNMUX, cabling from above)

216

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.124

R:SND/MBD/LTGM (with SNMUX, cabling from below)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:LTGM(A)

MUT01 MUT02 Fuse Panel MUT01 MUT02 MUT03 MUT04

F:LTGM(A)

MUT03

F:LTGM(A) FAN (B5681) F:MBD 0

FAN (B5681) F:MBD 0

MUT11 MUT04

F:MBD 1

MUT05

F:MBD 1

MUT05

F:SNMUX(A) 0

MUT06

F:SNMUX(A) 0

MUT06

F:SNMUX(A) 1

MUT07

F:SNMUX(A) 1

MUT07

FAN-BOX (B5877)

MUT12

FAN (B5681) FILTER:FAN

MUT10 MUT12

rack 8 ft.

rack 7 ft.

FU 03 04 05 06 07

MUT in 8 ft. MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A)

MOLOC C101P1 / LTG 0 C151P1 / LTG 1 C203P1 / LTG 2 C255P1 / LTG 3 C305P1 / LTG 4

MUT in 7 ft. MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A)

MOLOC C101P1 / LTG 0 C151P1 / LTG 1 C203P1 / LTG 2 C255P1 / LTG 3 C305P1 / LTG 4

Tab. 2.143 Fuse Assignment R:SN(D)/MBD/LTGM (with SNMUX, cabling from below)

A30828-X1160-M-2-7620

217

Construction

Maintenance Node

FU 08 27 28 29 30 31 09 18 19 01 02 10 20

MUT in 8 ft. MUT02 / F:MBD MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT04 / F:MBD MUT05 / F:MBD MUT05 / F:MBD MUT06 / F:SNMUX(A) MUT07 / F:SNMUX(A) MUT11 / FAN MUT12 / FAN-BOX

MOLOC C109P1 C101P1 / LTG 0 C151P1 / LTG 1 C203P1 / LTG 2 C255P1 / LTG 3 C305P1 / LTG 4 C341P1 C109P1 C341P1

MUT in 7 ft. MUT04 / F:MBD

MOLOC C109P1

MUT04 / F:MBD MUT05 / F:MBD MUT05 / F:MBD MUT06 / F:SNMUX(A) MUT07 / F:SNMUX(A) MUT03 / FAN MUT10 / FAN

C341P1 C109P1 C341P1

Tab. 2.143 Fuse Assignment R:SN(D)/MBD/LTGM (with SNMUX, cabling from below)

218

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.125

R:SND/SNMAT
Fuse Panel
ON OFF 01 02 03 05 07 09 11 13 15 04 06 08 10 12 14 16 17 50 49 18 19 20 21 23 25 27 29 31 22 24 26 28 30 32 ON OFF

Fuse Panel

MUT01

Fuse Panel

MUT01

FANTRAY (U103) (U2620) F:SNMAT 0 FANTRAY (U103) (U2620) F:SNMAT 1

MUT04 MUT05

FANTRAY (U103) (U2620) F:SNMAT 0 FANTRAY (U103) (U2620) F:SNMAT 1

MUT04

MUT05 MUT06 MUT07

MUT06

MUT07

FAN-BOX (U102)

MUT08

FAN-BOX (U102)

MUT08

rack 8 ft.

rack 7 ft.

FU 03 01 02 29 31 32 04, 30

MUT MUT04 / FAN TRAY MUT05 / F:SNMAT MUT05 / F:SNMAT MUT06 / FAN TRAY MUT07 / SNMAT MUT07 / SNMAT MUT08 / FAN-BOX C239P1 / SN1 D239P4 / SN1 C239P1 / SN0 D239P4 / SN0

MOLOC

Tab. 2.144 Fuse Assignment SND/SNMAT

A30828-X1160-M-2-7620

219

Construction

Maintenance Node

2.126

R:SSG(B)/LTGG (cabling from above)


Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:SSG(B) 0

MUT01 MUT02 Fuse Panel MUT01

F:SSG(B) 1

MUT03 F:SSG(B) 0 MUT02

F:LTGG(A)

MUT04 F:SSG(B) 1 MUT03

F:LTGG(A) F:LTGG(A) MUT05

MUT04

F:LTGG(A)

MUT06

F:LTGG(A)

MUT05

F:LTGG(A)

MUT06

rack 8 ft.

rack 7 ft.

FU 01 02 11 12 03 04 13 14 05 06 15 16

MUT MUT02 / F:SSG(B) MUT02 / F:SSG(B) MUT03 / F:SSG(B) MUT03 / F:SSG(B) MUT04 / F:LTGGA) MUT04 / F:LTGG(A) MUT05 / F:LTGG(A) MUT05 / F:LTGG(A) MUT06 / F:LTGG(A) MUT06 / F:LTGG(A) MUT07 / F:LTGG(A) MUT07 / F:LTGG(A) C101 (SSG-0-0 or SSG-0-2) C331 (SSG-0-1 or SSG-0-3) C101 (SSG-1-0 or SSG-1-2) C331 (SSG-1-1 or SSG-1-3) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG)

MOLOC

Tab. 2.145 Fuse Assignment R:SSG(B)/LTGG (cabling from above)

220

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.127

R:SSG(B)/LTGG (cabling from below)


Fuse Panel
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:LTGG(A)

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGG(A)

MUT03 F:LTGG(A)

F:LTGG(A)

MUT04 F:LTGG(A) MUT03

F:LTGG(A)

MUT04

F:SSG(B) 0

MUT06 F:SSG(B) 0 MUT06

F:SSG(B) 1

MUT07 F:SSG(B) 1 MUT07

rack 8 ft.

rack 7 ft.

FU 05 06 15 16 03 04 13 14 01 02 11 12

MUT MUT02 / F:LTGG(A) MUT02 / F:LTGG(A) MUT03 / F:LTGG(A) MUT03 / F:LTGG(A) MUT04 / F:LTGG(A) MUT04 / F:LTGG(A) MUT05 / F:LTGG(A) MUT05 / F:LTGG(A) MUT06 / F:SSG(B) MUT06 / F:SSG(B) MUT07 / F:SSG(B) MUT07 / F:SSG(B) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG) C101 / (SSG-0-0 or SSG-0-2) C331 / (SSG-0-1 or SSG-0-3) C101 / (SSG-1-0 or SSG-1-2) C331 / (SSG-1-1 or SSG-1-3)

MOLOC

Tab. 2.146 Fuse Assignment R:SSG(B)/LTGG (cabling from below)

A30828-X1160-M-2-7620

221

Construction

Maintenance Node

2.128

R:SSG(B)/LTGM (cabling from above)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 Panel Fuse 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel F:SSG(B) 0

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:SSG(B) 1

MUT03 F:SSG(B) 0

F:LTGM(A)

MUT04 F:SSG(B) 1 MUT03

F:LTGM(A) F:LTGM(A) MUT05

MUT04

F:LTGM(A)

MUT06

F:LTGM(A)

MUT06

F:LTGM(A)

MUT07

rack 8 ft.

rack 7 ft.

FU 01 02 32 33 08 09

MUT MUT02 / F:SSG(B) MUT02 / F:SSG(B) MUT03 / F:SSG(B) MUT03 / F:SSG(B) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) C101 (SSG-0-0 or SSG-0-2) C331 (SSG-0-1 or SSG-0-3) C101 (SSG-1-0 or SSG-1-2) C331 (SSG-1-1 or SSG-1-3) C101 / LTG 0 C151 / LTG 1

MOLOC

Tab. 2.147 Fuse Assignment R:SSG(B)/LTGM (cabling from above)

222

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 10 11 12 22 23 24 25 26 03 04 05 06 07 27 28 29 30 31

MUT MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4

MOLOC

Tab. 2.147 Fuse Assignment R:SSG(B)/LTGM (cabling from above)

A30828-X1160-M-2-7620

223

Construction

Maintenance Node

2.129

R:SSG(B)/LTGM (cabling from below)


Fuse Panel FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:LTGM(A)

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGM(A)

MUT03 F:LTGM(A)

F:LTGM(A)

MUT04 F:LTGM(A) MUT03

F:LTGM(A)

MUT04

F:SSG(B) 0

MUT06 F:SSG(B) 0 MUT06

F:SSG(B) 1

MUT07 F:SSG(B) 1 MUT07

rack 8 ft.

rack 7 ft.

FU 03 04 05 06 07 27 28 29 30 31 08

MUT MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT04 / F:LTGM(A) C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0

MOLOC

Tab. 2.148 Fuse Assignment R:SSG(B)/LTGM (cabling from below)

224

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 09 10 11 12 01 32 02 33

MUT MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT06 / F:SSG(B) MUT06 / F:SSG(B) MUT07 / F:SSG(B) MUT07 / F:SSG(B) C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / (SSG-0-0 or SSG-0-2) C331 / (SSG-0-1 or SSG-0-3) C101 / (SSG-1-0 or SSG-1-2) C331 / (SSG-1-1 or SSG-1-3)

MOLOC

Tab. 2.148 Fuse Assignment R:SSG(B)/LTGM (cabling from below)

2.130

R:SSG(B)/MB/LTGM (cabling from above)


Fuse Panel FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:SSG(B) 0

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:SSG(B) 1

MUT03 F:SSG(B) 0

F:MB/CCG(B) 0

MUT04 F:SSG(B) 1 MUT03

F:MB/CCG(B) 1

MUT05 F:MB/CCG(B) 0 MUT04

F:LTGM(A)

MUT06

F:MB/CCG(B) 1

MUT05

F:LTGM(A)

MUT06

rack 8 ft.

rack 7 ft.

A30828-X1160-M-2-7620

225

Construction

Maintenance Node

FU 01 02 32 33 08 09 22 23 03 04 05 06 07

MUT MUT03 / F:SSG(B) MUT03 / F:SSG(B) MUT03 / F:SSG(B) MUT03 / F:SSG(B) MUT04 / F:MB/CCG(B) MUT04 / F:MB/CCG(B) MUT04 / F:MB/CCG(B) MUT04 / F:MB/CCG(B) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) C101 (SSG-0-0 or SSG-0-2) C331 (SSG-0-1 or SSG-0-3) C101 (SSG-1-0 or SSG-1-2) C331 (SSG-1-1 or SSG-1-3) A001 / MB 0 A121 / CCG 0 A001 / MB 1 A121 / CCG 1 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4

MOLOC

Tab. 2.149 Fuse Assignment R:SSG(B)/LTGM (cabling from above)

226

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.131

R:SSG(B)/MB/LTGM (cabling from below)


Fuse Panel FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:SSG(B)

MUT01 MUT02 Fuse Panel F:LTGM(A) MUT01 MUT02

F:MB/CCG(B)

MUT04

F:MB/CCG(B)

MUT05

F:MB/CCG(B)

MUT04 MUT05

F:SSG(B) 0

MUT06

F:MB/CCG(B)

F:SSG(B) 1

MUT07

F:SSG(B) 0

MUT06

F:SSG(B) 1

MUT07

rack 8 ft.

rack 7 ft.

FU 03 04 05 06 07 08 09 22 23 01 02

MUT MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT04 / F:MB/CCG(B) MUT04 / F:MB/CCG(B) MUT05 / F:MB/CCG(B) MUT05 / F:MB/CCG(B) MUT06 / F:SSG(B) MUT06 / F:SSG(B) C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 A001 / MB 0 A121 / CCG 0 A001 / MB 1 A121 / CCG 1 C101 (SSG-0-0 or SSG-0-2) C331 (SSG-0-1 or SSG-0-3)

MOLOC

Tab. 2.150 Fuse Assignment R:SSG(B)/MB/LTGM (cabling from below)

A30828-X1160-M-2-7620

227

Construction

Maintenance Node

FU 32 33

MUT MUT07 / F:SSG(B) MUT07 / F:SSG(B) C101 (SSG-1-0 or SSG-1-2) C331 (SSG-1-1 or SSG-1-3)

MOLOC

Tab. 2.150 Fuse Assignment R:SSG(B)/MB/LTGM (cabling from below)

2.132

R:TSG(B)/LTGG (cabling from above)


Fuse Panel 8 ft. rack
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel 7 ft. rack


FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:TSG(B) 0

MUT01 MUT02 Fuse Panel MUT01

F:TSG(B) 1

MUT03 F:TSG(B) 0 MUT02

F:LTGG(A)

MUT04 F:TSG(B) 1 MUT03

F:LTGG(A) F:LTGG(A) MUT05

MUT04

F:LTGG(A)

MUT06

F:LTGG(A)

MUT05

F:LTGG(A)

MUT07

F:LTGG(A)

MUT06

rack 8 ft.

rack 7 ft.

228

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 01 11 03 04 13 14 05 06 15 16

MUT MUT02 / F:TSG(B) MUT03 / F:TSG(B) MUT04 / F:LTGGA) MUT04 / F:LTGG(A) MUT05 / F:LTGG(A) MUT05 / F:LTGG(A) MUT06 / F:LTGG(A) MUT06 / F:LTGG(A) MUT07 / F:LTGG(A) MUT07 / F:LTGG(A) C331 (TSG-0-tsg) C331 (TSG-1-tsg) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG)

MOLOC

Tab. 2.151 Fuse Assignment R:TSG(B)/LTGG (cabling from above)

A30828-X1160-M-2-7620

229

Construction

Maintenance Node

2.133

R:TSG(B)/LTGG (cabling from below)


Fuse Panel 8 ft. rack
FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel 7 ft. rack


FU 01 03 05 04 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 FU FU

FU 02

Fuse Panel F:LTGG(A)

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGG(A)

MUT03 F:LTGG(A)

F:LTGG(A)

MUT04 F:LTGG(A) MUT03

F:LTGG(A) F:LTGG(A) MUT05

MUT04

F:TSG(B) 0

MUT06 F:TSG(B) 0 MUT06

F:TSG(B) 1

MUT07 F:TSG(B) 1 MUT07

rack 8 ft.

rack 7 ft.

FU 05 06 15 16 03 04 13 14

MUT MUT02 / F:LTGG(A) MUT02 / F:LTGG(A) MUT03 / F:LTGG(A) MUT03 / F:LTGG(A) MUT04 / F:LTGG(A) MUT04 / F:LTGG(A) MUT05 / F:LTGG(A) MUT05 / F:LTGG(A) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG) A001 (left LTG) A123 (right LTG)

MOLOC

Tab. 2.152 Fuse Assignment R:TSG(B)/LTGG (cabling from below)

230

A30828-X1160-M-2-7620

Maintenance Node

Construction

FU 02 12

MUT MUT06 / F:TSG(B) MUT07 / F:TSG(B) C331 / (TSG-0-tsg) C331 / (SSG-1-tsg)

MOLOC

Tab. 2.152 Fuse Assignment R:TSG(B)/LTGG (cabling from below)

2.134

R:TSG(B)/LTGM (cabling from above)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 Panel Fuse 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel F:TSG(B) 0

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:TSG(B) 1

MUT03 F:TSG(B) 0

F:LTGM(A)

MUT04 F:TSG(B) 1 MUT03

F:LTGM(A) F:LTGM(A) MUT05

MUT04

F:LTGM(A)

MUT06

F:LTGM(A)

MUT06

F:LTGM(A)

MUT07

F:LTGM(A)

MUT07

rack 8 ft.

rack 7 ft.

A30828-X1160-M-2-7620

231

Construction

Maintenance Node

FU 01 32 08 09 10 11 12 22 23 24 25 26 03 04 05 06 07 27 28 29 30 31

MUT MUT02 / F:TSG(B) MUT03 / F:TSG(B) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) C331 (TSG-0-tsg) C331 (TSG-1-tsg) C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4

MOLOC

Tab. 2.153 Fuse Assignment R:TSG(B)/LTGM (cabling from above)

232

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.135

R:TSG(B)/LTGM (cabling from below)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 Panel Fuse 19 21 23 25 27 29 31 33 FU FU 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 FU

Fuse Panel F:LTGM(A)

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGM(A)

MUT03 F:LTGM(A)

F:LTGM(A)

MUT04 F:LTGM(A) MUT03

F:LTGM(A) F:LTGM(A) MUT05

MUT04

F:TSG(B) 0 F:TSG

MUT06 F:TSG(B) 0 MUT06

F:TSG(B) 1

MUT07 F:TSG(B) 1 MUT07

rack 8 ft.

rack 7 ft.

FU 03 04 05 06 07

MUT MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4

MOLOC

Tab. 2.154 Fuse Assignment R:TSG(B)/LTGM (cabling from below)

A30828-X1160-M-2-7620

233

Construction

Maintenance Node

FU 27 28 29 30 31 08 09 10 11 12 22 23 24 25 26 01 32

MUT MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT04 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT05 / F:LTGM(A) MUT06 / F:TSG(B) MUT07 / F:TSG(B) C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C331 / (TSG-0-tsg) C331 / (TSG-1-tsg)

MOLOC

Tab. 2.154 Fuse Assignment R:TSG(B)/LTGM (cabling from below)

234

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.136

R:TSG(B)/MB/LTGM (cabling from above)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:TSG(B) 0

MUT01 MUT02 Fuse Panel MUT01

F:TSG(B) 1

MUT03 F:TSG(B) 0 MUT02

F:MB/CCG(B) 0

MUT04 F:TSG(B) 1 MUT05 F:MB/CCG(B) 0 MUT04 MUT03

F:MB/CCG(B) 1

F:LTGM(A)

MUT06

F:MB/CCG(B) 1

MUT05

F:LTGM(A)

MUT07

F:LTGM(A)

MUT06

rack 8 ft.

rack 7 ft.

FU 01 32 08 09

MUT MUT02 / F:TSG(B) MUT03 / F:TSG(B) MUT04 / F:MB/CCG(B) MUT04 / F:MB/CCG(B) C331 (TSG-0-tsg) C331 (TSG-1-tsg) A001 / MB 0 A121 / CCG 0

MOLOC

Tab. 2.155 Fuse Assignment R:TSG(B)/LTGM (cabling from above)

A30828-X1160-M-2-7620

235

Construction

Maintenance Node

FU 22 23 03 04 05 06 07 27 28 29 30 31

MUT MUT04 / F:MB/CCG(B) MUT04 / F:MB/CCG(B) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT06 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) MUT07 / F:LTGM(A) A001 / MB 1 A121 / CCG 1 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4

MOLOC

Tab. 2.155 Fuse Assignment R:TSG(B)/LTGM (cabling from above)

236

A30828-X1160-M-2-7620

Maintenance Node

Construction

2.137

R:TSG(B)/MB/LTGM (cabling from below)


Fuse Panel 8 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel 7 ft. rack FU 01 03 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 FU

FU

02 04 06 08 10 12 14 16 18 20 22 24 26 28 30

32

FU

Fuse Panel F:LTGM(A)

MUT01 MUT02 Fuse Panel MUT01 MUT02

F:LTGM(A)

MUT03

F:LTGM(A)

F:MB/CCG(B) 0

MUT04

F:MB/CCG(B) 1

MUT05

F:MB/CCG(B) 0

MUT04

F:MB/CCG(B) 1 F:TSG(B) 0 MUT06 F:TSG(B) 0 F:TSG(B) 1 MUT07 F:TSG(B) 1

MUT05

MUT06

MUT07

rack 8 ft.

rack 7 ft.

FU 03 04 05 06

MUT MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) MUT02 / F:LTGM(A) C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3

MOLOC

Tab. 2.156 Fuse Assignment R:SN(B)/MB/LTGM (cabling from below)

A30828-X1160-M-2-7620

237

Construction

Maintenance Node

FU 07 27 28 29 30 31 08 09 22 23 01 32

MUT MUT02 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT03 / F:LTGM(A) MUT04 / F:MB/CCG(B) MUT04 / F:MB/CCG(B) MUT05 / F:MB/CCG(B) MUT05 / F:MB/CCG(B) MUT06 / F:TSG(B) MUT07 / F:TSG(B) C305 / LTG 4 C101 / LTG 0 C151 / LTG 1 C203 / LTG 2 C255 / LTG 3 C305 / LTG 4 A001 / MB 0 A121 / CCG 0 A001 / MB 1 A121 / CCG 1 C331 / (TSG-0-tsg) C331 / (TSG-1-tsg)

MOLOC

Tab. 2.156 Fuse Assignment R:SN(B)/MB/LTGM (cabling from below)

238

A30828-X1160-M-2-7620

Maintenance Node

Construction

3 Module Frames
3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 3.10 3.11 3.12 3.13 F:CCS7 F:CP113 F:DLU F:LTG F:MB/CCG F:RSU F:SDHI F:SMSC(C) F:SN F:SSNC F:STMI F:SYPC(A) Fan

A30828-X1160-M-2-7620

239

Construction

Maintenance Node

3.1

F:CCS7
3.1.1 3.1.1.1 3.1.1.2 3.1.1.3 3.1.2 3.1.2.1 3.1.2.2 3.1.2.3 F:CCNP(B) F:CCNP(B) (module side) F:CCNP(B) (backplane) F:CCNP(B) (cabling) F:SILTD(A) F:SILTD(A) (module side) F:SILTD(A) (backplane) F:SILTD(A) (cabling)

3.1.1 3.1.1.1

F:CCNP(B) F:CCNP(B) (module side)

B
A095 PMU:SIMP A085 MH:SIMP A105 PMU:CPI A111 IOC:CPI A013 MUXMA A019 MUXMB A024 MUXMA A030 MUXMB A100 MU:CPI A001 DCCCL A117 DCCCL

A035 SIPA

A041 SIPA

A047 SIPA

A053 SIPA

A061 SIPA

A067 SIPA

A073 SIPA

Modules with displays and switches in F:CCNP(B) MUXMA (-Q1117-) SIPA (-Q1016-) DCCCL (-Q5619-L) MH:SIMP (-Q1017-) PMU:SIMP (-Q1179-) PMU:CPI (-Q1180-)

Tab. 3.1

Modules with display and switches in F:CCNP(B)

A079 SIPA

240

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.1.1.2

F:CCNP(B) (backplane)

SILTC SILTC

SILTC SILTC

SILTC SILTC

SILTC SILTC

SILTC SILTC

SILTC SILTC

SILTC SILTC

SILTC SILTC

SN0/1 SN0/1

SILTC SILTC

SILTC SILTC

SILTC SILTC

SILTC SILTC

SILTC SILTC

SILTC SILTC

SILTC SILTC

114 108

082 079

076 073

070 067 064 061

056 053

050 047

044 041

038 035

SILTC SILTC

CP-1 CP-0

027 024

3.1.1.3

F:CCNP(B) (cabling)
Cable from F:CCNP/SILTD-0 SIPA-0, Cable A035 SIPA-0, Cable B035 SIPA-0, Cable A038 SIPA-0, Cable B038 SIPA-1, Cable A041 SIPA-1, Cable B041 SIPA-1, Cable A044 SIPA-1, Cable B044 SIPA-2, Cable A047 SIPA-2, Cable B047 SIPA-2, Cable A050 SIPA-2, Cable B050 SIPA-3, Cable A053 SIPA-3, Cable B053 SIPA-3, Cable A056 SIPA-3, Cable B056 SIPA-4, Cable A061 SIPA-4, Cable B061 SIPA-4, Cable A064 SIPA-4, Cable B064 SIPA-5, Cable A067 SIPA-5, Cable B067 SIPA-5, Cable A070 SIPA-5, Cable B070 Cable to Cable from F:CCNP/SILTD-1 SIPA-0, Cable A035 SIPA-0, Cable B035 SIPA-0, Cable A038 SIPA-0, Cable B038 SIPA-1, Cable A041 SIPA-1, Cable B041 SIPA-1, Cable A044 SIPA-1, Cable B044 SIPA-2, Cable A047 SIPA-2, Cable B047 SIPA-2, Cable A050 SIPA-2, Cable B050 SIPA-3, Cable A053 SIPA-3, Cable B053 SIPA-3, Cable A056 SIPA-3, Cable B056 SIPA-4, Cable A061 SIPA-4, Cable B061 SIPA-4, Cable A064 SIPA-4, Cable B064 SIPA-5, Cable A067 SIPA-5, Cable B067 SIPA-5, Cable A070 SIPA-5, Cable B070 Cable to

F:SILTD-1, SILTC-00, A056 F:SILTD-1, SILTC-01, A073 F:SILTD-2, SILTC-02, A056 F:SILTD-2, SILTC-03, A073 F:SILTD-3, SILTC-04, A056 F:SILTD-3, SILTC-05, A073 F:SILTD-4, SILTC-06, A056 F:SILTD-4, SILTC-07, A073 F:SILTD-5, SILTC-08, A056 F:SILTD-5, SILTC-09, A073 F:SILTD-6, SILTC-10, A056 F:SILTD-6, SILTC-11, A073 F:SILTD-7, SILTC-12, A056 F:SILTD-7, SILTC-13, A073 F:SILTD-8, SILTC-14, A056 F:SILTD-8, SILTC-15, A073 F:SILTD-09, SILTC-16, A056 F:SILTD-09, SILTC-17, A073 F:SILTD-10, SILTC-18, A056 F:SILTD-10, SILTC-19, A073 F:SILTD-11, SILTC-20, A056 F:SILTD-11, SILTC-21, A073 F:SILTD-12, SILTC-22, A056 F:SILTD-12, SILTC-23, A073

F:SILTD-1, SILTC-00, B056 F:SILTD-1, SILTC-01, B073 F:SILTD-2, SILTC-02, B056 F:SILTD-2, SILTC-03, B073 F:SILTD-3, SILTC-04, B056 F:SILTD-3, SILTC-05, B073 F:SILTD-4, SILTC-06, B056 F:SILTD-4, SILTC-07, B073 F:SILTD-5, SILTC-08, B056 F:SILTD-5, SILTC-09, B073 F:SILTD-6, SILTC-10, B056 F:SILTD-6, SILTC-11, B073 F:SILTD-7, SILTC-12, B056 F:SILTD-7, SILTC-13, B073 F:SILTD-8, SILTC-14, B056 F:SILTD-8, SILTC-16, B073 F:SILTD-09, SILTC-16, B056 F:SILTD-09, SILTC-17, B073 F:SILTD-10, SILTC-18, B056 F:SILTD-10, SILTC-19, B073 F:SILTD-11, SILTC-20, B056 F:SILTD-11, SILTC-21, B073 F:SILTD-12, SILTC-22, B056 F:SILTD-12, SILTC-23, B073

Tab. 3.2

F:CCNP(B) (cabling)

016 013

SN0/1 SN0/1

CP-1 CP-0

A30828-X1160-M-2-7620

241

Construction

Maintenance Node

Cable from F:CCNP/SILTD-0 SIPA-6, Cable A073 SIPA-6, Cable B073 SIPA-6, Cable A076 SIPA-6, Cable B076 SIPA-7, Cable A079 SIPA-7, Cable B079 SIPA-7, Cable A082 SIPA-7, Cable B082 MUXM Cable A013 Cable A016 Cable A024 Cable A027 CPI-0 Cable A108 Cable B108 Cable A114 Cable B114

Cable to

Cable from F:CCNP/SILTD-1 SIPA-6, Cable A073 SIPA-6, Cable B073 SIPA-6, Cable A076 SIPA-6, Cable B076 SIPA-7, Cable A079 SIPA-7, Cable B079 SIPA-7, Cable A082 SIPA-7, Cable B082 MUXM Cable A013 Cable A016 Cable A024 Cable A027 CPI-1 Cable A108 Cable B108 Cable A114 Cable B114

Cable to

F:SILTD-13, SILTC-24, A056 F:SILTD-13, SILTC-25, A073 F:SILTD-14, SILTC-26, A056 F:SILTD-14, SILTC-27, A073 F:SILTD-15, SILTC-28, A056 F:SILTD-15, SILTC-29, A073 F:SILTD-16, SILTC-30, A056 F:SILTD-16, SILTC-31, A073 SN-0

F:SILTD-13, SILTC-24, B056 F:SILTD-13, SILTC-25, B073 F:SILTD-14, SILTC-26, B056 F:SILTD-14, SILTC-27, B073 F:SILTD-15, SILTC-28, B056 F:SILTD-15, SILTC-29, B073 F:SILTD-16, SILTC-30, B056 F:SILTD-16, SILTC-31, B073 SN-1

CPxxx-0 CPxxx-0 CPxxx-1 CPxxx-1

CPxxx-0 CPxxx-0 CPxxx-1 CPxxx-1

Tab. 3.2

F:CCNP(B) (cabling)

3.1.2 3.1.2.1

F:SILTD(A) F:SILTD(A) (module side)

B
DCCCL DCCCR DCCCR A117 DCCCL A120 MUXS MUXS SILTD SILTD SILTD SILTD SILTD SILTD SILTD SILTD SILTC SILTC SILTD SILTD SILTD SILTD SILTD SILTD SILTD A107 SILTD A112

A001

A007

A013

A018

A023

A028

A033

A038

A043

A048

A053

A059

A065

A070

A076

A082

A087

A092

A097

Modules with displays and switches in F:SILTD(A) SILTC (-Q766-) DCCCL (-Q5619-L) DCCCR (-Q5619-) SILTD (-Q1023-)

Tab. 3.3

Modules with display and switches in F:SILTD(A)

242

A30828-X1160-M-2-7620

A102

Maintenance Node

Construction

3.1.2.2

F:SILTD(A) (backplane)

SIPA

073

SIPA

3.1.2.3

F:SILTD(A) (cabling)
Cabling see: 3.1.1.3 "F:CCNP(B) (cabling)"

056

SIPA

SIPA

A30828-X1160-M-2-7620

243

Construction

Maintenance Node

3.2

F:CP113
3.2.1 3.2.1.1 3.2.1.2 3.2.1.3 3.2.2 3.2.2.1 3.2.2.2 3.2.2.3 3.2.3 3.2.3.1 3.2.3.2 3.2.3.3 3.2.4 3.2.4.1 3.2.5 3.2.5.1 3.2.5.2 3.2.6 3.2.6.1 3.2.6.2 3.2.6.3 3.2.7 3.2.7.1 3.2.7.2 3.2.7.3 3.2.8 3.2.8.1 3.2.8.2 3.2.8.3 3.2.8.4 3.2.8.5 3.2.8.6 3.2.9 3.2.9.1 3.2.9.2 3.2.9.3 3.2.10 3.2.10.1 3.2.10.2 3.2.10.3 3.2.11 3.2.11.1 3.2.11.2 3.2.11.3 3.2.12 F:BIOP F:BIOP (module side) F:BIOP (backplane) F:BIOP (cabling) F:BPCE F:BPCE (module side) F:BPCE (backplane) F:BPCE (cabling) F:CMY F:CMY (module side) F:CMY (backplane) F:CMY (cabling) F:DEV(E) F:DEV(E) (module side) F:DEV(F) F:DEV(F) (module side) F:DEV(F) (backplane) F:EIOP F:EIOP (module side) F:EIOP (backplane) F:EIOP (cabling) F:EPCE F:EPCE (module side) F:EPCE (backplane) F:EPCE (cabling) F:IOP F:IOP0/1 (module side) F:IOP0/1 (backplane) F:IOP0/1 (cabling) F:IOP2/3 (module side) F:IOP2/3 (backplane) F:IOP2/3 (cabling) F:MI F:MI for BCMY (module side) F:MI for BCMY (backplane) F:MI for BCMY (cabling) F:PBC(A) F:PBC(A) (module side) F:PBC(A) (backplane) F:PBC(A) (cabling) F:PI F:PI for BCMY (module side) F:PI for BCMY (backplane) F:PI for BCMY (cabling) F:PIOP(A)

244

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.2.12.1 3.2.12.2 3.2.12.3 3.2.13 3.2.13.1 3.2.13.2 3.2.13.3 3.2.14 3.2.14.1 3.2.14.2 3.2.14.3 3.2.15

F:PIOP(A) (module side) F:PIOP(A) (backplane) F:PIOP(A) (cabling) F:PIOP(B) F:PIOP(B) (module side) F:PIOP(B) (backplane) F:PIOP(B) (cabling) F:P/IOC F:P/IOC (module side) F:P/IOC (backplane) F:P/IOC (cabling) Profibus

A30828-X1160-M-2-7620

245

Construction

Maintenance Node

3.2.1 3.2.1.1

F:BIOP F:BIOP (module side)


innovation IOC 0 and IOC 1 IOC 0
10)10) 9) 6) 5) 4) 3) 2) 1) 10)10)

IOC 1
9) 6) 5) 4) 3) 2) 1)

LCUB / IOPUNI IOPMB / IOPUNI IOPMB

D
DCCMD LAUB LCUB LAUB

LAUB LCUB LAUB LCUB / IOPUNI IOPMB / IOPUNI IOPMB

DCCMD

DCCMD

C101

C117

C125 C133

C141 C149

C157

C167

C175 C183

C191

C203

C233

C249 C257

C265 C273 C281

C289

C299 C307 C315

C323

1) 2) 3)

IOPTA, only in IOP frames connected to IOC 0 and 1: system clock and radio and clock connection IOPMB, only in IOP frames connected to IOC 0 and 1: connection of CCG and PROFIBUS IOPUNI, only in IOP frames connected to IOC 0 and 1: connection of MDD and MOD (in F:EPCE), Boot-PC, 2 serial HDLC-IF V.24, X.21 IOPMB, only in IOP frames connected to IOC 0 and 1: MBD basic connection IOPMB, only in IOP frames connected to IOC 0 and 1: 1. additional MBD connection (if required) IOPMB, only in IOP frames connected to IOC 0 and 1: 2. additional MBD connection (if required) IOPUNI, connection of 3 serial HDLC-IF V.24, X.21 LAUB + LCUB, connection of 2 x X.25-IF; distribute in F:BIOP left and right side equally for reason of failure!

4) 5) 6) 9) 10)

246

A30828-X1160-M-2-7620

C335

DCCMD

IOPMB IOPUNI

IOPMB IOPUNI IOPMB

IOPMB

IOPTA

IOPTA

Maintenance Node

Construction

innovation IOC 2 and IOC 3 IOC 2


10)10) 9) 9) 9) 10)10)

IOC 3
9) 9) 9)

LCUB / IOPUNI IOPUNI

D
DCCMD LAUB LCUB LAUB

LAUB LCUB LAUB LCUB / IOPUNI IOPUNI

DCCMD

DCCMD

C101

C117

C125 C133

C141 C149

C175

C203

C233

C249 C257

C265 C273 C281

C307

9) 10)

IOPUNI, connection of 3 serial HDLC-IF V.24, X.21 LAUB + LCUB, connection of 2 x X.25-IF; distribute in F:BIOP left and right side equally for reason of failure!

classic IOC 2 and IOC 3 IOC 2


10)10) 7) 7) 8) 9) 10)10)

IOC 3
7) 7) 8) 9)

D
DCCMD DCCMD DCCMD DCCMD C335 IOPMB IOPUNI IOPMB IOPUNI LCUB IOPMB IOPMB LAUB LCUB LAUB LCUB IOPMB IOPMB LAUB LCUB LAUB

C101

C117

C125 C133

C141 C149

C157

C167

C175

C203

C233

C249 C257

C265 C273 C281

C289

7) 8) 9) 10)

IOPMB, only in IOP frames connected to IOC 2 and 3: additional MBD connection DE54 IOPMB, only in IOP frames connected to IOC 2 and 3: connection of CCNP in DE54 only IOPUNI, connection of 3 serial HDLC-IF V.24, X.21 LAUB + LCUB, connection of 2 x X.25-IF; distribute in F:BIOP left and right side equally for reason of failure!

C299 C307

A30828-X1160-M-2-7620

C335

DCCMD

IOPUNI

IOPUNI

247

Construction

Maintenance Node

Modules with displays and switches in F:BIOP DCCMD (-Q5897-) LAUB (-Q1115-) IOP:MB (-Q954-) LCUB (-Q1114-) IOP:UNI (-Q1257-) IOP:TA (-Q956-)

Tab. 3.4

Modules with displays and switches in F:BIOP

3.2.1.2

F:BIOP (backplane)
P1

10 9 6
2 1

8 8

8 8 8 8 13 8 8 8 8 5 5 13

10 9 6

8 8 8 8

8 8 8 8 13 8 8 8 8 5 5 13

3
1

P2

11 9 6

1
3 3

2 1 1 2 2

11 9 6 11 9 6 12 9
7

3 3 3

2
P3

11 9 6 8 12 9
8
7

2
P4

2
P5

3
2

12 14
2 2

12 14 12
5 5 2 5 5

P1

12
2

P2

12
2 2

12
4 4 4 4

P3 P4

12 12

12 12

4 4

4 4

3.2.1.3

F:BIOP (cabling)
Power supply cabling (Connector 1)
Connector 1 1 1 1 MOLOC C101P1 C203P1 C233P1 C257P5 Port primary connection DCCDM 0 and 1 - side 0 primary connection LAUB 0 and 1 - side 0 primary connection DCCDM 0 and 1 - side 1 primary connection LAUB 0 and 1 - side 1 Connection To the breaker panel of the rack To the breaker panel of the rack To the breaker panel of the rack To the breaker panel of the rack

Tab. 3.5

Power supply cabling (Connector 1)

Cabling F:BIOP (clock supply, alarming and other)


Connector 10 10 12 12 14 14 Unit F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP MOLOC 05C197P1 05C329P1 05C197P4 05C329P4 05C183P5 05C315P5 Connection To F:MODEM (Radio clock) To F:MODEM (Radio clock) Alarm cabling to AD:RAL (Rack internal alarms) Alarm cabling to AD:RAL (Rack internal alarms) To Profibus PBSL To Profibus PBSL

Tab. 3.6

Cabling F:BIOP (clock supply, alarming and other)

248

A30828-X1160-M-2-7620

Maintenance Node

Construction

Cabling F:BIOP <----> F:BPCE (Connector 2) F:BIOP is connected to IOC 0 and IOC 1 BUS for Input/Output Control
From F:BIOP Connector 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Unit F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP MOLOC 05C211P1 05C211P2 05C211P3 05C211P4 05C211P5 05D211P1 05D211P2 05C343P1 05C343P2 05C343P3 05C343P4 05C343P5 05D343P1 05D343P2 Unit F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE To F:BPCE MOLOC 07C171P1 07C171P2 07C171P3 07C171P4 07C171P5 07C209P3 07C209P5 07C309P1 07C309P2 07C309P3 07C309P4 07C309P5 07C285P3 07C285P5 Remark IOC 0 IOC 0 IOC 0 IOC 0 IOC 0 IOC 0 IOC 0 IOC 1 IOC 1 IOC 1 IOC 1 IOC 1 IOC 1 IOC 1

Tab. 3.7

Cabling F:BIOP <----> F:BPCE (Connector 2)

Cabling F:BIOP <----> F:BPCE (Connector 2) F:BIOP is connected to IOC 2 and IOC 3 BUS for Input/Output Control
From F:BIOP Connector 2 2 2 2 2 2 2 2 2 2 2 Unit F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP MOLOC 05C211P1 05C211P2 05C211P3 05C211P4 05C211P5 05D211P1 05D211P2 05C343P1 05C343P2 05C343P3 05C343P4 Unit F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE To F:BPCE MOLOC 07C115P1 07C115P2 07C115P3 07C115P4 07C115P5 07C209P4 07D209P1 07C365P1 07C365P2 07C365P3 07C365P4 Remark IOC 2 IOC 2 IOC 2 IOC 2 IOC 2 IOC 2 IOC 2 IOC 3 IOC 3 IOC 3 IOC 3

Tab. 3.8

Cabling F:BIOP <----> F:BPCE (Connector 2)

A30828-X1160-M-2-7620

249

Construction

Maintenance Node

From F:BIOP Connector 2 2 2 Unit F:BIOP F:BIOP F:BIOP MOLOC 05C343P5 05D343P1 05D343P2 Unit F:BPCE F:BPCE F:BPCE

To F:BPCE MOLOC 07C365P5 07C285P4 07D285P1 Remark IOC 3 IOC 3 IOC 3

Tab. 3.8

Cabling F:BIOP <----> F:BPCE (Connector 2)

Cabling F:BIOP <----> F:BIOP (Connector 3, 4) Connection LAUB - , LCUB - partner


From F:BIOP Connector 3 3 3 3 3 3 3 3 Unit F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP MOLOC 05C109P1 05C109P2 05C109P3 05C109P4 05C241P1 05C241P2 05C241P3 05C241P4 4 4 4 4 4 4 4 4 Connector To F:BIOP Unit F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP MOLOC 05D249P3 05D249P4 05D265P3 05D265P4 05D117P3 05D117P4 05D133P3 05D133P4

Tab. 3.9

Cabling F:BIOP <----> F:BIOP (Connector 3, 4)

Cabling F:BIOP MOLOC for data link cables (Connector 5, 6, 7) Mounting locations of data link cables 2 links per M:LAUB
Connector 5 5 5 5 5 5 5 5 6 MOLOC 05C117P4 05D117P1 05C133P4 05D133P1 05C249P4 05D249P1 05C265P4 05D265P1 05C175P1 PC connection if F:BIOP is connected to IOC 0 and 1 Remarks all connection can be used for X.21 or V.24 or V35 data links

Tab. 3.10

Cabling F:BIOP MOLOC for data link cables

250

A30828-X1160-M-2-7620

Maintenance Node

Construction

Connector 6 6 6 6 6 7 7

MOLOC 05C175P2 05C175P3 05C307P1 05C307P2 05C307P3 05C175P4 05C307P4 To F:EPCE 08C119 MOD 0 To F:EPCE 08C337 MOD 1

Remarks all connection can be used for V.24, V.28 or X.21/V.11 data links

Tab. 3.10

Cabling F:BIOP MOLOC for data link cables

Cabling F:BIOP <---> F:MB/CCG(B) EWSD Classic (Connector 8)


From F:BIOP Connector 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 Unit F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP MOLOC 05C157P2 05C289P2 05C157P1 05C289P1 05C157P4 05C289P4 05C157P3 05C289P3 05C149P2 05C281P2 05C149P1 05C281P1 05C149P4 05C281P4 05C149P3 05C281P3 Unit F:MB/CCG(B) MBUS-0-2 F:MB/CCG(B) MBUS-0-2 F:MB/CCG(B) MBUS-0-2 F:MB/CCG(B) MBUS-0-2 F:MB/CCG(B) MBUS-1-2 F:MB/CCG(B) MBUS-1-2 F:MB/CCG(B) MBUS-1-2 F:MB/CCG(B) MBUS-1-2 F:MB/CCG(B) MBUS-0-3 F:MB/CCG(B) MBUS-0-3 F:MB/CCG(B) MBUS-0-3 F:MB/CCG(B) MBUS-0-3 F:MB/CCG(B) MBUS-1-3 F:MB/CCG(B) MBUS-1-3 F:MB/CCG(B) MBUS-1-3 F:MB/CCG(B) MBUS-1-3 To F:MB/CCG(B) MOLOC 02/04 A046 02/04 A052 02/04 B046 02/04 B052 03/05 A046 03/05 A052 03/05 B046 03/05 B052 08/04 A046 08/04 A052 08/04 B046 08/04 B052 09/05 A046 09/05 A052 09/05 B046 09/05 B052

Tab. 3.11

Cabling F:BIOP <---> F:MB/CCG(B) EWSD Classic

Cabling F:BIOP <--> F:MBD (Connector 8) Innovation


From F:BIOP (F:BIOP is connected to IOC0 and IOC1) Connector 8 8 Unit MOLOC Unit To MBD

MOLOC

F:BIOP (M:IOPMBs in MOLOCs C167 and C299) F:BIOP (M:IOPMBs in MOLOCs C167 and C299)

05C167P2 05C167P1

F:MBD0 / MBDC F:MBD0 / MBDC

C173P1 C189P1

Tab. 3.12

Cabling F:BIOP <--> F:MBD EWSD Innovation

A30828-X1160-M-2-7620

251

Construction

Maintenance Node

From F:BIOP (F:BIOP is connected to IOC0 and IOC1) Connector 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 Unit MOLOC Unit

To MBD

MOLOC

F:BIOP (M:IOPMBs in MOLOCs C167 and C299) F:BIOP (M:IOPMBs in MOLOCs C167 and C299) F:BIOP (M:IOPMBs in MOLOCs C167 and C299) F:BIOP (M:IOPMBs in MOLOCs C167 and C299) F:BIOP (M:IOPMBs in MOLOCs C167 and C299) F:BIOP (M:IOPMBs in MOLOCs C167 and C299) F:BIOP (M:IOPMBs in MOLOCs C157 and C289) F:BIOP (M:IOPMBs in MOLOCs C157 and C289) F:BIOP (M:IOPMBs in MOLOCs C157 and C289) F:BIOP (M:IOPMBs in MOLOCs C157 and C289) F:BIOP (M:IOPMBs in MOLOCs C157 and C289) F:BIOP (M:IOPMBs in MOLOCs C157 and C289) F:BIOP (M:IOPMBs in MOLOCs C157 and C289) F:BIOP (M:IOPMBs in MOLOCs C157 and C289) F:BIOP (M:IOPMBs in MOLOCs C149 and C281) F:BIOP (M:IOPMBs in MOLOCs C149 and C281) F:BIOP (M:IOPMBs in MOLOCs C149 and C281) F:BIOP (M:IOPMBs in MOLOCs C149 and C281) F:BIOP (M:IOPMBs in MOLOCs C149 and C281) F:BIOP (M:IOPMBs in MOLOCs C149 and C281) F:BIOP (M:IOPMBs in MOLOCs C149 and C281) F:BIOP (M:IOPMBs in MOLOCs C149 and C281)

05C299P2 05C299P1 05C167P4 05C167P3 05C299P4 05C299P3 05C157P1 05C157P2 05C289P1 05C289P2 05C157P3 05C157P4 05C289P3 05C289P4 05C281P1 05C281P2 05C149P1 05C149P2 05C281P3 05C281P4 05C149P3 05C149P4

F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC

C195P1 C201P1 C173P1 C189P1 C195P1 C201P1 C189P2 C189P3 C195P2 C195P3 C189P2 C189P3 C195P2 C195P3 C189P4 C189P5 C201P2 C201P3 C189P4 C189P5 C201P2 C201P3

Tab. 3.12

Cabling F:BIOP <--> F:MBD EWSD Innovation

Cabling F:BIOP <--> F:MB/CCG(B) (Connector 9, 11) Clock cables and cross-joint cables
From F:BIOP (F:BIOP is connected to IOC0 and IOC1) Connector 9 9 9 9 9 9 F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP Unit MOLOC 05C183P2 05C315P2 05C183P1 05C315P1 05C183P4 05C315P4 To F:MB/CCG(A)

Unit F:MB/CCG(A) CCG 0 F:MB/CCG(A) CCG 0 F:MB/CCG(A) CCG 0 F:MB/CCG(A) CCG 0 F:MB/CCG(A) CCG 1 F:MB/CCG(A) CCG 1

MOLOC 02A095 02A101 02B095 02B101 03A095 03A101

Tab. 3.13

Cabling F:BIOP <--> F:MB/CCG(B)

252

A30828-X1160-M-2-7620

Maintenance Node

Construction

From F:BIOP (F:BIOP is connected to IOC0 and IOC1) Connector 9 9 11 11 11 11 F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP Unit MOLOC 05C183P3 05C315P3 05C329P2 05C197P2 05C329P3 05C197P3

To F:MB/CCG(A)

Unit F:MB/CCG(A) CCG 1 F:MB/CCG(A) CCG 1 F:MB/CCG(A) CCG 0 F:MB/CCG(A) CCG 0 F:MB/CCG(A) CCG 1 F:MB/CCG(A) CCG 1

MOLOC 03B095 03B101 02A071 02B071 03A071 03B071

Tab. 3.13

Cabling F:BIOP <--> F:MB/CCG(B)

Cabling F:BIOP <--> F:CCGE (Connector 9, 11) Clock cables and cross-joint cables
From F:BIOP (F:BIOP is connected to IOC0 and IOC1) Connector 9 9 9 9 9 9 9 9 11 11 11 11 F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP Unit MOLOC 05C183P2 05C315P2 05C183P1 05C315P1 05C183P4 05C315P4 05C183P3 05C315P3 05C329P2 05C197P2 05C329P3 05C197P3 Unit F:CCGE CCG 0 F:CCGE CCG 0 F:CCGE CCG 0 F:CCGE CCG 0 F:CCGE CCG 1 F:CCGE CCG 1 F:CCGE CCG 1 F:CCGE CCG 1 F:CCGE CCG 0 F:CCGE CCG 0 F:CCGE CCG 1 F:CCGE CCG 1 To F:CCGE

MOLOC D131P2 D137P2 D131P3 D137P3 D263P2 D269P2 D263P3 D269P3 C125P2 C119P2 C257P2 C251P2

Tab. 3.14

Cabling F:BIOP <--> F:CCG

A30828-X1160-M-2-7620

253

Construction

Maintenance Node

3.2.2 3.2.2.1

F:BPCE F:BPCE (module side)


CAP8/IOC2 CP113E Innovation AMP0 AMP1 CAP4 CAP2 CAP0 CAP1 CAP3 CAP5 BAP0 BAP1 IOC0 IOC1 CAP9/IOC3 IOC3

CAP6

CP113E Classic CAP8 CAP6 CAP4 CAP0 CAP2 CAP3 CAP1 CAP5 CAP7 CAP9 BAP0 BAP1 IOC2 IOC0 IOC1

D
CMYE 0 CONE CMY 1 PEXE PEXE PEXE PEXE PEXE PEXE PEXE PEXE PEXE PEXE PEXE PEXE PEXE C115 PEXE PEXE C365 3 1 3 1 3 1 3 1 3 1 PEXE C379

C101

C129

C143

C157

C171

C185

C199

C219

C243

C257

C275

C295

C309

C323

C337

Modules with displays and switches in F:BPCE PEX (-Q1251-) IOP:MB (-Q954-) CMYE (-Q244-)

Tab. 3.15

Modules with displays and switches in F:BPCE

3.2.2.2

F:BPCE (backplane)
P1 P2 P3 3 1 3 1 3 1 3 1 3 1 4
3 0 3 0 3 0 3 0 3 0

2 2 3 3 3 3 5

6 6 7 7 7 7 7 7

1 1 1 1 1 1 5

1 1 1 1 1 1 5

2 2
3 0 3 0 3 0 3 0

6 6 7 7 7 7 7 7

3 0 3 0 3 0 3 0 3 0

P4 P5 P1 P2

P3 P4 P5 5

7 7

7 7

254

A30828-X1160-M-2-7620

C351

CAP7

Maintenance Node

Construction

3.2.2.3

F:BPCE (cabling)
Cabling F:BPCE <----> F:BPCE (Connector 1) Internal connection
From F:BIOP Connector 1 1 1 1 1 1 Unit F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE MOLOC 07C227P3 07C227P4 07C227P5 07D227P1 07C227P1 07C227P2 1 1 1 1 1 1 Connector To F:BIOP Unit F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE MOLOC 07C265P3 07C265P4 07C265P5 07D265P1 07C265P1 07C265P2

Tab. 3.16

Cabling F:BPCE <----> F:BPCE (Connector 1)

Power supply cabling (Connector 2)


Connector 2 2 MOLOC C209P1 C285P1 primary connection primary connection Port Connection To the breaker panel of the rack To the breaker panel of the rack

Tab. 3.17

Power supply cabling (Connector 1)

A30828-X1160-M-2-7620

255

Construction

Maintenance Node

Cabling F:BPCE <----> F:BIOP (Connector 30) F:BIOP is connected to IOC 0 and IOC 1 BUS for Input/Output Control
From F:BPCE Connector 30 30 30 30 30 30 30 30 30 30 30 30 30 30 Unit F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE MOLOC 07C171P1 07C171P2 07C171P3 07C171P4 07C171P5 07C209P3 07C209P5 07C309P1 07C309P2 07C309P3 07C309P4 07C309P5 07C285P3 07C285P5 Unit F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP To F:BIOP MOLOC 05C211P1 05C211P2 05C211P3 05C211P4 05C211P5 05D211P1 05D211P2 05C343P1 05C343P2 05C343P3 05C343P4 05C343P5 05D343P1 05D343P2 Remark IOC 0 IOC 0 IOC 0 IOC 0 IOC 0 IOC 0 IOC 0 IOC 1 IOC 1 IOC 1 IOC 1 IOC 1 IOC 1 IOC 1

Tab. 3.18

Cabling F:BPCE <----> F:BIOP (Connector 30)

Cabling F:BPCE <----> F:BIOP (Connector 31) F:BIOP is connected to IOC 2 and IOC 3 BUS for Input/Output Control
From F:BPCE Connector 31 31 31 31 31 31 31 31 31 31 31 Unit F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE MOLOC 07C115P1 07C115P2 07C115P3 07C115P4 07C115P5 07C209P4 07D209P1 07C365P1 07C365P2 07C365P3 07C365P4 Unit F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP F:BIOP To F:BIOP MOLOC 05C211P1 05C211P2 05C211P3 05C211P4 05C211P5 05D211P1 05D211P2 05C343P1 05C343P2 05C343P3 05C343P4 Remark IOC 2 IOC 2 IOC 2 IOC 2 IOC 2 IOC 2 IOC 2 IOC 3 IOC 3 IOC 3 IOC 3

Tab. 3.19

Cabling F:BPCE <----> F:BIOP (Connector 31)

256

A30828-X1160-M-2-7620

Maintenance Node

Construction

From F:BPCE Connector 31 31 31 Unit F:BPCE F:BPCE F:BPCE MOLOC 07C365P5 07C285P4 07D285P1 Unit F:BIOP F:BIOP F:BIOP

To F:BIOP MOLOC 05C343P5 05D343P1 05D343P2 Remark IOC 3 IOC 3 IOC 3

Tab. 3.19

Cabling F:BPCE <----> F:BIOP (Connector 31)

Cabling F:BPCE <----> F:EIOP (Connector 30) F:EIOP is connected to IOC 0 and IOC 1 BUS for Input/Output Control
From F:BPCE Connector 30 30 30 30 30 30 30 30 30 30 30 30 30 30 Unit F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE MOLOC 07C171P1 07C171P2 07C171P3 07C171P4 07C171P5 07C209P3 07C209P5 07C309P1 07C309P2 07C309P3 07C309P4 07C309P5 07C285P3 07C285P5 Unit F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP To F:EIOP MOLOC 03C333P1 03C333P2 03C333P3 03C333P4 03C333P5 03D333P1 03D333P2 04C333P1 04C333P2 04C333P3 04C333P4 04C333P5 04D333P1 04D333P2 Remark IOC 0 IOC 0 IOC 0 IOC 0 IOC 0 IOC 0 IOC 0 IOC 1 IOC 1 IOC 1 IOC 1 IOC 1 IOC 1 IOC 1

Tab. 3.20

Cabling F:BPCE <----> F:EIOP (Connector 30)

Cabling F:BPCE <----> F:EIOP (Connector 31) F:EIOP is connected to IOC 2 and IOC 3 BUS for Input/Output Control
From F:BPCE Connector 31 31 31 31 Unit F:BPCE F:BPCE F:BPCE F:BPCE MOLOC 07C115P1 07C115P2 07C115P3 07C115P4 Unit F:EIOP F:EIOP F:EIOP F:EIOP To F:EIOP MOLOC 03C333P1 03C333P2 03C333P3 03C333P4 Remark IOC 2 IOC 2 IOC 2 IOC 2

Tab. 3.21

Cabling F:BPCE <----> F:EIOP (Connector 31)

A30828-X1160-M-2-7620

257

Construction

Maintenance Node

From F:BPCE Connector 31 31 31 31 31 31 31 31 31 31 Unit F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE MOLOC 07C115P5 07C209P4 07D209P1 07C365P1 07C365P2 07C365P3 07C365P4 07C365P5 07C285P4 07D285P1 Unit F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP

To F:EIOP MOLOC 03C333P5 03D333P1 03D333P2 04C333P1 04C333P2 04C333P3 04C333P4 04C333P5 04D333P1 04D333P2 Remark IOC 2 IOC 2 IOC 2 IOC 3 IOC 3 IOC 3 IOC 3 IOC 3 IOC 3 IOC 3

Tab. 3.21

Cabling F:BPCE <----> F:EIOP (Connector 31)

Cabling F:BPCE <----> F:EPCE (Connector 4, 6, 7)


From F:BPCE Connector 4 4 6 6 6 6 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE Unit MOLOC 07C157P1 07C323P1 07C199P1 07C199P2 07C275P1 07C275P2 07C199P3 07C275P3 07C199P4 07C275P4 07C199P5 07C275P5 07D199P1 07D275P1 07D199P2 07D275P2 07D199P3 07D275P3 07D199P4 07D275P4 07D199P5 F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE Unit To F:EPCE MOLOC 08C181P5 08C305P5 08C181P3 08C305P4 08C181P4 08C305P3 08D191P1 08D191P2 08D205P1 08D205P2 08D219P1 08D219P2 08D233P1 08D233P2 08D253P1 08D253P2 08D267P1 08D267P2 08D281P1 08D281P2 08D295P1

Tab. 3.22

Cabling F:BPCE <----> F:EPCE (Connector 4, 6, 7)

258

A30828-X1160-M-2-7620

Maintenance Node

Construction

From F:BPCE Connector 7 F:BPCE Unit MOLOC 07D275P5 F:EPCE Unit

To F:EPCE MOLOC 08D295P2

Tab. 3.22

Cabling F:BPCE <----> F:EPCE (Connector 4, 6, 7)

Cabling F:BPCE <----> F:SCB (Connector 5) FOTX-Module to AMX


From F:BPCE Connector 5 5 5 5 5 5 5 5 F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE Unit MOLOC 07D209W3 07D209W2 07D285W3 07D285W2 07D209W5 07D209W4 07D285W5 07D285W4 F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB Unit To F:SCB MOLOC 09D149W4 09D149W5 09D169W4 09D169W5 09D211W4 09D211W5 09D231W4 09D231W5

Tab. 3.23

Cabling F:BPCE <----> F:SCB (Connector 5)

3.2.3 3.2.3.1

F:CMY F:CMY (module side)

MUH - Bank 0 MUH - Bank 2 MUH - Bank 1 MUH - Bank 3 MUH - Bank 0 MUH - Bank 2 MUH - Bank 1 MUH - Bank 3 MUH - Bank 0 MUH - Bank 2 MUH - Bank 1 MUH - Bank 3 MUH - Bank 0 MUH - Bank 2 MUH - Bank 1 MUH - Bank 3

D
DCCx

CMYMP CMYA CMYD CMYMP CMYA CMYD C283 C291 C297 C305 C313 C319

C125 C131 C137 C143 C149 C155 C161 C167 C175 C181 C187 C193 C199 C205 C211 C217

C227

C241 C249

C263

The units CMY0 and CMY1 must be filled with similar memory extensions in order that different module types may be used in CMY0 and CMY1.

C327

DCCMS

CMY2C

CMY1C CMY2C

CMY1C

A30828-X1160-M-2-7620

259

Construction

Maintenance Node

Modules with displays and switches in F:CMY MUH (-Q1088-) DCCMS (-Q5619-S100) CMY2C (-Q963-)

Tab. 3.24

Modules with display and switches in F:CMY

CMY-Developed
Memory extension/ Mbyte *) 64 Number of the X800Modules Number of the X600Modules 4 4 128 4 8 192 256 4 16 320 384 512 576 640 768 832 896 1024 4 4 8 8 8 12 12 12 16 4 4 4 4 4 4 5 6 8 9 10 12 13 14 16 12 3 4 2 Number of the X500Modules Number of the X550Modules Memory-extension in Blocks of 64 Mbyte 1

Tab. 3.25

CMY-Developed

The MUH-modules are put resembles in quadripartite-groups [BG-Types]. It will be begin on the left hand side with the quadripartite-group with the largest memoryextension. Gaps between the single MUH-modules have not permitted. *) Basis is the 4 Mbit DRAM.

260

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.2.3.2

F:CMY (backplane)
MI MI MI MI MI MI P1 P2

P3 P4 P5 P1 P2

D
P3 P4 MI MI MI MI

345 339 333

MI MI

3.2.3.3

F:CMY (cabling)
Clock cabling F:CMY0/1 to F:MI0/1
From F:CMY Connector TACT TACT TACT TACT TACT TACT TACT TACT Unit F:CMY 0 F:CMY 1 F:CMY 0 F:CMY 1 F:CMY 0 F:CMY 1 F:CMY 0 F:CMY 1 MOLOC 03C271P4 04C271P4 03C277P4 04C277P4 03D271P1 04D271P1 03D277P1 04D277P1 F:MI 0 F:MI 0 F:MI 0 F:MI 0 F:MI 1 F:MI 1 F:MI 1 F:MI 1 Unit To F:MI MOLOC 06C297P1 06C305P1 06D297P4 06D305P4 07C297P1 07C305P1 07D297P4 07D305P4

Tab. 3.26

Clock cabling F:CMY<----> F:MI

Cabling F:CMY0/1 to F:MI0/1


From F:CMY Connector MI MI MI MI Unit F:CMY 0 F:CMY 0 F:CMY 0 F:CMY 1 MOLOC 03C333P4 03C339P1 03D339P1 04C333P4 F:MI 0 F:MI 0 F:MI 0 F:MI 0 Unit To F:MI MOLOC 06C297P1 06C305P1 06D297P4 06D305P4

Tab. 3.27

Cabling F:CMY<----> F:MI

277 271

TACT TACT

MI MI MI

TACT TACT

MI MI MI

A30828-X1160-M-2-7620

261

Construction

Maintenance Node

From F:CMY Connector MI MI MI MI MI MI MI MI Unit F:CMY 1 F:CMY 1 F:CMY 0 F:CMY 0 F:CMY 0 F:CMY 1 F:CMY 1 F:CMY 1 MOLOC 04C339P1 04D339P1 03D333P1 03C345P1 03D345P1 04D333P1 04C345P1 04D345P1 F:MI 1 F:MI 1 F:MI 1 F:MI 1 F:MI 1 F:MI 1 F:MI 1 F:MI 1 Unit

To F:MI MOLOC 07C297P1 07C305P1 07D297P4 07D305P4 07C297P1 07C305P1 07D297P4 07D305P4

Tab. 3.27

Cabling F:CMY<----> F:MI

3.2.4 3.2.4.1

F:DEV(E) F:DEV(E) (module side)

A
MDD 0 MDD 1

A001

DCCDA for MDD 0

A013

A090

262

A30828-X1160-M-2-7620

A115

DCCDA for MDD 1

Maintenance Node

Construction

3.2.5 3.2.5.1

F:DEV(F) F:DEV(F) (module side)

FAN

FAN

MOD 0

DCCDA for MOD 1 A115


from IOP:UNI0

DCCDA for MOD 0

DCCDA for MDD 0

A001

A029

A049

A056

A067

A095

3.2.5.2

F:DEV(F) (backplane)
from IOP:MDD1 from IOP:UNI1 from IOP:MDD0

DCCDA

DCCDA

Screening plate

Screening plate

r
Device 1

r
Device 0

A30828-X1160-M-2-7620

263

A122

DCCDA for MDD 1

MOD 1

MDD 0

MDD 1

Construction

Maintenance Node

3.2.6 3.2.6.1

F:EIOP F:EIOP (module side)


innovation IOC 0 and IOC 1
10)10) 9) 8) 7) 6) 5) 4) 3) 2) 1) 11)

D
C101 DCCMD C311 IOPTA C197 LAUB C323 DCCMD C237 IOPUNI C245 IOPUNI C295 IOPUNI C303 IOPMB C253 IOPMB C271 IOPMB C261 IOPMB C279 IOPMB C287 IOPMB C149 LCUB C117 LAUB C129 LCUB C157 LAUB C169 LCUB C177 LAUB C189 LCUB C209 LCUB C217 LAUB C229 LCUB C137 LAUB DCCMD C337

1) 2) 3)

IOPTA, only in IOP frames connected to IOC 0 and 1: system clock and radio and clock connection IOPMB, only in IOP frames connected to IOC 0 and 1: connection of CCG and PROFIBUS IOPUNI, only in IOP frames connected to IOC 0 and 1: connection of MDD and MOD (in F:EPCE), Boot-PC, 2 serial HDLC-IF V.24, X.21 IOPMB, only in IOP frames connected to IOC 0 and 1: MBD basic connection IOPMB, only in IOP frames connected to IOC 0 and 1: 1. additional MBD connection (if required) IOPMB, only in IOP frames connected to IOC 0 and 1: 2. additional MBD connection (if required) IOPMB, only in IOP frames connected to IOC 0 and 1: 3. additional MBD connection (if required) IOPMB, only in IOP frames connected to IOC 0 and 1: 4. additional MBD connection (if required) IOPUNI, connection of 3 serial HDLC-IF V.24, X.21 LAUB + LCUB, connection of 2 x X.25-IF; distribute in F:BIOP left and right side equally for reason of failure! This 3.DCCMD is necessary, if more than 160W power are necessary here the value for calculation: IOPMB 10, IOPUNI 18W, LCUB 20W, IOPTA 25W

4) 5) 6) 7) 8) 9) 10)

11)

264

A30828-X1160-M-2-7620

Maintenance Node

Construction

innovation IOC 2 and IOC 3


10)10) 9) 9) 9)

D
C101 DCCMD C237 IOPUNI C245 IOPUNI C295 IOPUNI C311 IOPTA C149 LCUB C117 LAUB C129 LCUB C157 LAUB C169 LCUB C177 LAUB C189 LCUB C197 LAUB C209 LCUB C217 LAUB C229 LCUB C137 LAUB DCCMD 11) C323 DCCMD

9) 10)

IOPUNI, connection of 3 serial HDLC-IF V.24, X.21 LAUB + LCUB, connection of 2 x X.25-IF; distribute in F:BIOP left and right side equally for reason of failure!

classic IOC 0 and IOC 1


10)10) 9) 8) 6) 5) 4) 3) 2) 1)

D
C101 DCCMD C237 IOPUNI C245 IOPUNI C253 IOPUNI C295 IOPUNI C303 IOPMB C271 IOPMB C261 IOPMB C279 IOPMB C287 IOPMB C311 IOPTA C149 LCUB C117 LAUB C129 LCUB C157 LAUB C169 LCUB C177 LAUB C189 LCUB C197 LAUB C209 LCUB C217 LAUB C229 LCUB C137 LAUB DCCMD

1) 2) 3)

IOPTA, only in IOP frames connected to IOC 0 and 1: system clock and radio and clock connection IOPMB, only in IOP frames connected to IOC 0 and 1: connection of CCG IOPUNI, only in IOP frames connected to IOC 0 and 1: connection of MDD and MOD (in F:EPCE), NetM-Boot, 2 serial HDLC-IF V.24, X.21 IOPMB, only in IOP frames connected to IOC 0 and 1: SYPC / PROFIBUS IOPMB, only in IOP frames connected to IOC 0 and 1: MB basic connection for DE4, DE51 IOPMB, only in IOP frames connected to IOC 0 and 1: MB connection for DE52

4) 5) 6)

A30828-X1160-M-2-7620

265

C337

C337

Construction

Maintenance Node

8) 9) 10) 11)

IOPMB, only in IOP frames connected to IOC 0 and 1: connection of CCNP in DE4, DE51 and DE52 IOPMB, only in IOP frames connected to IOC 0 and 1: connection of 3 serial HDLC-IF V.24, X.21 LAUB + LCUB, connection of 2 x X.25-IF; distribute in both F:EIOP equally for reason of failure! This 3.DCCMD is necessary, if more than 160W power are necessary here the value for calculation: IOPMB 10, IOPUNI 18W, LCUB 20W, IOPTA 25W

Modules with displays and switches in F:EIOP DCCMD (-Q5897-) LAUB (-Q1115-) IOP:MB (-Q954-) LCUB (-Q1114-) IOP:UNI (-Q1257-) IOP:TA (-Q956-)

Tab. 3.28

Modules with displays and switches in F:EIOP

3.2.6.2

F:EIOP (backplane)

P1

2
1 1
2

10 11

9 6 8 8 8 9 6 8 8 8

8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8

13

3
61

13

51

13

41

13

3
31

13

3
21

13

3
11

P2

3
62

3
52

3
42

3
32

3
22

3
12

C P3
P4 P5 P1

2
2 2 2 2

11 8 9 6 8 8 8 12 12 12 12

9 7 8 8 8

14
5 5 5 5 5 5

D P2
P3 P4

4
51

4
41

4
31

4
21

4
11

12 12

61

4
62

4
52

4
42

4
32

4
22

4
12

3.2.6.3

F:EIOP (cabling)
Power supply cabling (Connector 1)
Connector 1 1 1 MOLOC C101P1 C323P1 C341P1 Port primary connection DCCDM primary connection DCCDM primary connection DCCDM Connection To the breaker panel of the rack To the breaker panel of the rack To the breaker panel of the rack

Tab. 3.29

Power supply cabling (Connector 1)

Cabling F:EIOP <----> F:BPCE (Connector 2) F:EIOP is connected to IOC 0 and IOC 1 BUS for Input/Output Control

266

A30828-X1160-M-2-7620

Maintenance Node

Construction

From F:EIOP Connector 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Unit F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP MOLOC 03C333P1 03C333P2 03C333P3 03C333P4 03C333P5 03D333P1 03D333P2 04C333P1 04C333P2 04C333P3 04C333P4 04C333P5 04D333P1 04D333P2 Unit F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE

To F:BPCE MOLOC 07C171P1 07C171P2 07C171P3 07C171P4 07C171P5 07C209P3 07C209P5 07C309P1 07C309P2 07C309P3 07C309P4 07C309P5 07C285P3 07C285P5 Remark IOC 0 IOC 0 IOC 0 IOC 0 IOC 0 IOC 0 IOC 0 IOC 1 IOC 1 IOC 1 IOC 1 IOC 1 IOC 1 IOC 1

Tab. 3.30

Cabling F:EIOP <----> F:BPCE (Connector 2)

Cabling F:BPCE <----> F:EIOP (Connector 2) F:EIOP is connected to IOC 2 and IOC 3 BUS for Input/Output Control
From F:EIOP Connector 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Unit F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP MOLOC 03C333P1 03C333P2 03C333P3 03C333P4 03C333P5 03D333P1 03D333P2 04C333P1 04C333P2 04C333P3 04C333P4 04C333P5 04D333P1 04D333P2 Unit F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE To F:BPCE MOLOC 07C115P1 07C115P2 07C115P3 07C115P4 07C115P5 07C209P4 07D209P1 07C365P1 07C365P2 07C365P3 07C365P4 07C365P5 07C285P4 07D285P1 Remark IOC 2 IOC 2 IOC 2 IOC 2 IOC 2 IOC 2 IOC 2 IOC 3 IOC 3 IOC 3 IOC 3 IOC 3 IOC 3 IOC 3

Tab. 3.31

Cabling F:BPCE <----> F:EIOP (Connector 2)

A30828-X1160-M-2-7620

267

Construction

Maintenance Node

Cabling F:EIOP <---> F:EIOP (Connector 3, 4) Internal cabling


From F:EIOP 0 Connector 3 / 11 3 / 12 4 / 11 4 / 12 3 / 21 3 / 22 4 / 21 4 / 22 3 / 31 3 / 32 4 / 31 4 / 32 3 / 41 3 / 42 4 / 41 4 / 42 3 / 51 3 / 52 4 / 51 4 / 52 3 / 61 3 / 62 4 / 61 4 / 62 Unit F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP MOLOC 03C123P1 03C123P2 03D117P3 03D117P4 03C143P1 03C143P2 03D137P3 03D137P4 03C163P1 03C163P2 03D157P3 03D157P4 03C183P1 03C183P2 03D177P3 03D177P4 03C203P1 03C203P2 03D197P3 03D197P4 03C223P1 03C223P2 03D217P3 03D217P4 Connector 4 / 11 4 / 12 3 / 11 3 / 12 4 / 21 4 / 22 3 / 21 3 / 22 4 / 31 4 / 32 3 / 31 3 / 32 4 / 41 4 / 42 3 / 41 3 / 42 4 / 51 4 / 52 3 / 51 3 / 52 4 / 61 4 / 62 3 / 61 3 / 62 To F:EIOP 1 Unit F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP MOLOC 04D117P3 04D117P4 04C123P1 04C123P2 04D137P3 04D137P4 04C143P1 04C143P2 04D157P3 04D157P4 04C163P1 04C163P2 04D177P3 04D177P4 04C183P1 04C183P2 04D197P3 04D197P4 04C203P1 04C203P2 04D217P3 04D217P4 04C223P1 04C223P2

Tab. 3.32

Cabling F:EIOP <----> F:EIOP (Connector 3, 4)

Cabling F:EIOP MOLOC for data link cables (Connector 5) Mounting locations of data link cables 2 links per M:LAUB

268

A30828-X1160-M-2-7620

Maintenance Node

Construction

Connector 5 5 5 5 5 5 5 5 5 5 5 5

MOLOC 03/04C117P4 03/04D117P1 03/04C137P4 03/04D137P1 03/04C157P4 03/04D157P1 03/04C177P4 03/04D177P1 03/04C197P4 03/04D197P1 03/04C217P4 03/04D217P1

Remarks all connection can be used for X.21 or V.24 or V35 data links

Tab. 3.33

Cabling F:EIOP MOLOC for data link cables

Cabling (Connector 6, 7)
Connector 6 MOLOC 03C295P1 Connection Connection for PC 0 or OMT PC via MODEM, if both F:EIOP are connected to IOC 0 and 1 Connection for PC 0 or OMT PC via MODEM, if both F:EIOP are connected to IOC 0 and 1 To F:EPCE 08C119 MOD 0 To F:EPCE 08C337 MOD 1

04C295P1

7 7

03C295P4 04C295P4

Tab. 3.34

Cabling (Connector 6, 7)

A30828-X1160-M-2-7620

269

Construction

Maintenance Node

Cabling F:EIOP <---> F:MB/CCG(B) (Connector 8) Classic EIOP to MBB in EWSD classic with DE4, DE51 and DE52
From EIOP Capacity SN(63LTG) and SN(126LTG) Connector 8 8 8 8 8 8 8 8 SN(252LTG) 8 8 8 8 8 8 8 8 Unit F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP MOLOC 03C279P2 04C279P2 03C279P1 04C279P1 03C279P4 04C279P4 03C279P3 04C279P3 03C271P2 04C271P2 03C271P1 04C271P1 03C271P4 04C271P4 03C271P3 04C271P3 Unit MBUS-0-0 (MBG00) MBUS-0-0 (MBG00) MBUS-0-0 (MBG00) MBUS-0-0 (MBG00) MBUS-1-0 (MBG10) MBUS-1-0 (MBG10) MBUS-1-0 (MBG10) MBUS-1-0 (MBG10) MBUS-0-1 (MBG01) MBUS-0-1 (MBG01) MBUS-0-1 (MBG01) MBUS-0-1 (MBG01) MBUS-1-1 (MBG11) MBUS-1-1 (MBG11) MBUS-1-1 (MBG11) MBUS-1-1 (MBG11) To MBB MOLOC 02/04*) A046 02/04 A052 02/04 B046 02/04 B052 03/05 A046 03/05 A052 03/05 B046 03/05 B052 08/04 A046 08/04 A052 08/04 B046 08/04 B052 09/05 A046 09/05 A052 09/05 B046 09/05 B052

*) = MUT02 and 03, 08 and 09 in R:MB/CCG, MUT04 and 05 in R:SN/MB/LTGM

Tab. 3.35

Cabling F:EIOP <----> F:MB/CCG(B) Classic

Cabling F:EIOP <--> F:MBD (Connector 8) Innovation


From F:EIOP (Both F:EIOP are connected to IC0 and IC1) Connector 8 8 8 8 8 8 8 8 8 8 8 Unit F:EIOP (M:IOPMB in MOLOC C287 exists) F:EIOP(M:IOPMB in MOLOC C287 exists) F:EIOP(M:IOPMB in MOLOC C287 exists) F:EIOP(M:IOPMB in MOLOC C287 exists) F:EIOP(M:IOPMB in MOLOC C287 exists) F:EIOP(M:IOPMB in MOLOC C287 exists) F:EIOP(M:IOPMB in MOLOC C287 exists) F:EIOP(M:IOPMB in MOLOC C287 exists) F:EIOP (M:IOPMB in MOLOC C279 exists) F:EIOP (M:IOPMB in MOLOC C279 exists) F:EIOP (M:IOPMB in MOLOC C279 exists) MOLOC 03 C287P2 03 C287P1 04 C287P2 04 C287P1 03 C287P4 03 C287P3 04 C287P4 04 C287P3 03 C279P1 03 C279P2 04 C279P1 To MBD

Unit F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC

MOLOC C173P1 C189P1 C195P1 C201P1 C173P1 C189P1 C195P1 C201P1 C189P2 C189P3 C195P2

Tab. 3.36

Cabling F:EIOP <---------> F:MBD

270

A30828-X1160-M-2-7620

Maintenance Node

Construction

From F:EIOP (Both F:EIOP are connected to IC0 and IC1) Connector 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 Unit F:EIOP (M:IOPMB in MOLOC C279 exists) F:EIOP (M:IOPMB in MOLOC C279 exists) F:EIOP (M:IOPMB in MOLOC C279 exists) F:EIOP (M:IOPMB in MOLOC C279 exists) F:EIOP (M:IOPMB in MOLOC C279 exists) F:EIOP (M:IOPMB in MOLOC C271 exists) F:EIOP (M:IOPMB in MOLOC C271 exists) F:EIOP (M:IOPMB in MOLOC C271 exists) F:EIOP (M:IOPMB in MOLOC C271 exists) F:EIOP (M:IOPMB in MOLOC C271 exists) F:EIOP (M:IOPMB in MOLOC C271 exists) F:EIOP (M:IOPMB in MOLOC C271 exists) F:EIOP (M:IOPMB in MOLOC C271 exists) F:EIOP (M:IOPMB in MOLOC C261 exists) F:EIOP (M:IOPMB in MOLOC C261 exists) F:EIOP (M:IOPMB in MOLOC C261 exists) F:EIOP (M:IOPMB in MOLOC C261 exists) F:EIOP (M:IOPMB in MOLOC C261 exists) F:EIOP (M:IOPMB in MOLOC C261 exists) F:EIOP (M:IOPMB in MOLOC C261 exists) F:EIOP (M:IOPMB in MOLOC C261 exists) F:EIOP (M:IOPMB in MOLOC C253 exists) F:EIOP (M:IOPMB in MOLOC C253 exists) F:EIOP (M:IOPMB in MOLOC C253 exists) F:EIOP (M:IOPMB in MOLOC C253 exists) F:EIOP (M:IOPMB in MOLOC C253 exists) F:EIOP (M:IOPMB in MOLOC C253 exists) F:EIOP (M:IOPMB in MOLOC C253 exists) F:EIOP (M:IOPMB in MOLOC C253 exists) MOLOC 04 C279P2 03 C279P3 03 C279P4 04 C279P3 04 C279P4 03 C271P1 03 C271P2 04 C271P1 04 C271P2 03 C271P3 03 C271P4 04 C271P3 04 C271P4 03 C261P1 03 C261P2 04 C261P1 04 C261P2 03 C261P3 03 C261P4 04 C261P3 04 C261P4 03 C253P1 03 C253P2 04 C253P1 04 C253P2 03 C253P3 03 C253P4 04 C253P3 04 C253P4

To MBD

Unit F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC

MOLOC C195P3 C189P2 C189P3 C195P2 C195P3 C189P4 C189P5 C201P2 C201P3 C189P4 C189P5 C201P2 C201P3 C195P4 C195P5 C201P4 C201P5 C195P4 C195P5 C201P4 C201P5 D189P1 D189P2 D195P1 D195P2 D189P1 D189P2 D195P1 D195P2

Tab. 3.36

Cabling F:EIOP <---------> F:MBD

A30828-X1160-M-2-7620

271

Construction

Maintenance Node

Cabling F:EIOP <--> F:SYPC(A) (Connector 8) EWSD Classic


From F:EIOP Connector 8 8 8 8 F:EIOP F:EIOP F:EIOP F:EIOP Unit MOLOC 03C287P1 04C287P1 03C287P2 04C287P2 Unit F:SYPC(A) F:SYPC(A) F:SYPC(A) F:SYPC(A) To SYPC(A) MOLOC B010 B016 A010 A016

Tab. 3.37

Cabling F:EIOP <---------> F:SYPC(A)

Cabling F:EIOP <--> F:CCNP(B) (Connector 8) EWSD Classic


From F:EIOP Connector 8 8 8 8 8 8 8 8 F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP Unit MOLOC 03C261P2 03C261P4 03C261P1 03C261P3 04C261P2 04C261P4 04C261P1 04C261P3 Unit F:CCNP(B) 0 F:CCNP(B) 1 F:CCNP(B) 0 F:CCNP(B) 1 F:CCNP(B) 0 F:CCNP(B) 1 F:CCNP(B) 0 F:CCNP(B) 1 To CCNP(A) MOLOC 08A108 10A108 08B108 10B108 08A114 10A114 08B114 10B114

Tab. 3.38

Cabling F:EIOP <---------> F:CCNP(B)

Cabling F:EIOP <--> F:CCGE (Connector 9, 11) Clock cables and cross-joint cables
From F:EIOP To F:CCGE

Connector 9 9 9 9 9 9 9 9 11 11 F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP

Unit

MOLOC 03C303P2 03C303P1 03C303P4 03C303P3 04C303P2 04C303P1 04C303P4 04C303P3 03C317P2 03C317P3

Unit F:CCGE CCG 0 F:CCGE CCG 0 F:CCGE CCG 1 F:CCGE CCG 1 F:CCGE CCG 0 F:CCGE CCG 0 F:CCGE CCG 1 F:CCGE CCG 1 F:CCGE CCG 0 F:CCGE CCG 1

MOLOC D131P2 D131P2 D263P2 D263P3 D137P2 D137P3 D269P2 D269P3 C119P2 C251P2

Tab. 3.39

Cabling F:EIOP <--> F:CCGE

272

A30828-X1160-M-2-7620

Maintenance Node

Construction

From F:EIOP

To F:CCGE

Connector 11 11 F:EIOP F:EIOP

Unit

MOLOC 04C317P2 04C317P3

Unit F:CCGE CCG 0 F:CCGE CCG 1

MOLOC C125P2 C257P2

Tab. 3.39

Cabling F:EIOP <--> F:CCGE

Cabling F:EIOP <--> CCGA in F:MB/CCG(B) (Connector 9, 11) Clock cables and cross-joint cables
From F:EIOP To F:MB/CCG(B)

Connector 9 9 9 9 9 9 9 9 11 11 11 11 F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP

Unit

MOLOC 03C303P2 03C303P1 03C303P4 03C303P3 04C303P2 04C303P1 04C303P4 04C303P3 03C317P2 03C317P3 04C317P2 04C317P3

Unit F:MB/CCG(B) CCG 0 F:MB/CCG(B) CCG 0 F:MB/CCG(B) CCG 1 F:MB/CCG(B) CCG 1 F:MB/CCG(B) CCG 0 F:MB/CCG(B) CCG 0 F:MB/CCG(B) CCG 1 F:MB/CCG(B) CCG 1 F:MB/CCG(B) CCG 0 F:MB/CCG(B) CCG 1 F:MB/CCG(B) CCG 0 F:MB/CCG(B) CCG 1

MOLOC A095 B095 A095 B095 A101 B101 A101 B101 B071 B071 A071 A071

Tab. 3.40

Cabling F:EIOP <--> CCGA in F:MB/CCG(B)

Cabling F:EIOP alarming (Connector 12, 14)


Connector 12 12 12 12 14 14 Unit F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP F:EIOP MOLOC 03C317P4 04C317P4 03C317P4 04C317P4 03C3033P5 04C303P5 Connection Alarm cabling to AD:RAL (Rack internal alarms) 8 FT Rack Alarm cabling to AD:RAL (Rack internal alarms) 8 FT Rack Alarm cabling to AD:RAL (Rack internal alarms) 7 FT Rack Alarm cabling to AD:RAL (Rack internal alarms) 7 FT Rack To Profibus PBSL To Profibus PBSL

Tab. 3.41

Cabling F:EIOP (alarming)

A30828-X1160-M-2-7620

273

Construction

Maintenance Node

3.2.7 3.2.7.1

F:EPCE F:EPCE (module side)

D
MODE 0 MODE 1 MDDE 0 MDDE 1 6
0 0

C127

C155

C345

3.2.7.2

F:EPCE (backplane)
P1 1 P2 P3 P4 P5 P1 P2

6
1 1

6
1 0

2 2 3 5 5 5 5 5 5 5

2 6 2
0 1

4
5 5 5 5 5 5 5 5 5

D P3
P4 P5 4 4

3.2.7.3

F:EPCE (cabling)
Cabling F:BPCE <----> F:EPCE (Connector 2, 3, 5)
To F:EPCE Connector 3 F:EPCE Unit MOLOC 08C181P5 F:BPCE Unit From F:BPCE MOLOC 07C157P1

Tab. 3.42

Cabling F:BPCE <----> F:EPCE (Connector 2, 3, 5)

274

A30828-X1160-M-2-7620

C373

Maintenance Node

Construction

To F:EPCE Connector 3 2 2 2 2 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE F:EPCE Unit MOLOC 08C305P5 08C181P3 08C305P4 08C181P4 08C305P3 08D191P1 08D191P2 08D205P1 08D205P2 08D219P1 08D219P2 08D233P1 08D233P2 08D253P1 08D253P2 08D267P1 08D267P2 08D281P1 08D281P2 08D295P1 08D295P2 F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE F:BPCE Unit

From F:BPCE MOLOC 07C323P1 07C199P1 07C199P2 07C275P1 07C275P2 07C199P3 07C275P3 07C199P4 07C275P4 07C199P5 07C275P5 07D199P1 07D275P1 07D199P2 07D275P2 07D199P3 07D275P3 07D199P4 07D275P4 07D199P5 07D275P5

Tab. 3.42

Cabling F:BPCE <----> F:EPCE (Connector 2, 3, 5)

Cabling (Connector 6)
From F:EPCE Connector 6 6 6 6 Connection F:EPCE 08C119 MOD 0 F:EPCE 08C337 MOD 1 F:EPCE 08C119 MOD 0 F:EPCE 08C337 MOD 1 To F:BIOP/F:EIOP Unit F:BIOP F:BIOP F:EIOP F:EIOP MOLOC 03C295P4 04C295P4 03C295P4 04C295P4

Tab. 3.43

Cabling (Connector 6)

A30828-X1160-M-2-7620

275

Construction

Maintenance Node

3.2.8 3.2.8.1

F:IOP F:IOP0/1 (module side)


B:IOC

9 10 0

12

13

14

15

11

C285 LCUB / IOPSCDV/X C293 LAUB

C245 IKDTD / IOPUNI C253 IFMDD

D
C101 DCCMS C135 IOPMB C143 IOPMB C151 IOPMB C159 IOPMB C125 IOPTA IOPUNI

C265 IKDTD / IOPUNI C273 LAUB

C305 LCUB / IOPSCDV/X

IOPMB IOPAUC IOPUNI / IOPAUC

IOPAUC IOPSCDV

Modules with displays and switches in F:IOP0/1 IOP:MB (-Q954-) IOP:TA (-Q956-) LCUB (-Q1114-) DCCMS (-Q5619-S100) IOP:UNI (-Q1257-) IF:MDD (-Q976-) LAUB (-Q1115-) IOP:SCDV (-Q952-) IK:DTD (-Q975-) DCCMR (-Q5619-R100)

Tab. 3.44

Modules with display and switches in F:IOP0/1

Notes for the accounting locations F:IOP0/1 C159: M:IOPMB If M:IOPMB is tted as IOP for MBG-1 (essential for DE52) in the F:IOP0, the MBG-1 must also be available in F:IOP1. C183: M:IOPMB If M:IOPMB is tted as IOP for CCNC in the F:IOP0, MBG-1 must also be available in the F:IOP1 (assignment CCNC in F:IOP0/F:IOP1 only up to DE52 in F:IOP2/F:IOP3 for DE54). C215: M:IOPSCDV Direct connection PC-0 and connection possibility for 1 to 3 data links (HDLC V.24/V.28) C245: M:IKDTD/MTD or M:IOPUNI and C233: M:IFMTD/MTD or free If M:IKDTD/MTD is tted in mounting-location C245, the M:IFMTD/MTD must be available in mounting-location C233. If M:IOPUNI is tted as IOP for a MTD in mounting-location C245, mounting-location C233 must be free.

C225 CLB C233 IFMTD

C175 C183 C191 C199 C207 C215

276

A30828-X1160-M-2-7620

C313 DCCMR

Maintenance Node

Construction

C265: M:IKDTD/MDD or M:IOPUNI and C253: M:IFMDD/MDD or free If M:IKDTD/MDD or M:IOPUNI is tted in the F:IOP0, the M: IKDTD/MDD or M:IOPUNI must also be available in F:IOP1. If M:IKDTD/MDD is tted in mounting-location C265, the M:IFMDD/MDD must be available in mounting-location C253. If M:IOPUNI is tted as IOP for a MDD 4,5 GB in mounting-location C256, the mounting-location C253 must be free. C285 and C305: M:IOPSCDV or M:IOPSCDX 4 Data links (HDLC V.24/V.28) for operation of module IOPSCDV 4 Data links (HDLC X.21/V.11) for operation of module IOPSCDX C273/C285 and C293/C305: M:LCUB and M:LAUB 2 Data links X.25; one IOPLAU pair (M:LCUB and M:LAUB) each are operated as partner for failure reasons in the F:IOP0/F:IOP2 and F:IOP1/F:IOP3.

Assignment of logical/physical IOPMB numbers


F:IOP0 and F:IOP1 IOPMB IOPMB-00 IOPMB-01 IOPMB-32 IOPMB-33 IOPMB-34 IOPMB-35 IOPMB-40 IOPMB-41 IOPMB-42 IOPMB-43 MOLOC F:IOP0 / C183 F:IOP1 / C183 F:IOP0 / C151 F:IOP1 / C151 F:IOP0 / C159 F:IOP1 / C159 F:IOP0 / C135 F:IOP1 / C135 F:IOP0 / C143 F:IOP1 / C143 Remarks CCNP 0-0 (only to SN:252LTG) CCNP 1-0 (only to SN:252LTG) MBUL0-0, MBUS0-0, MBUL0-1 MBUL1-0, MBUS1-0, MBUL1-1 MBUL0-2, MBUS0-1, MBUL0-3 MBUL1-2, MBUS1-1, MBUL1-3 CCG0 CCG1 SYP SYP

Tab. 3.45

Assignment of logical/physical IOPMB numbers

A30828-X1160-M-2-7620

277

Construction

Maintenance Node

3.2.8.2

F:IOP0/1 (backplane)
CCNPCCNPCCNPCCNP MB0/2MB0/2MB0/2MB0/2 MB0/2 MB0/2MB0/2MB0/2 SYPCSYPC CCG1 CCG1CCG0CCG0 SCDVSCDVSCDVSCDV LAU LAU
P1 P2

2*

IOC IOC

P3 P4 P5

MTD

P1

IOC IOC

1*

5* 225 215 183 159 151 143 135 125

P2

LAU LAU

MTD

MTD

P3 P4

IOC

319

299 293 285 279 273

253

233

8*

7*

3.2.8.3

F:IOP0/1 (cabling)
C319P3, C139P4, D319P2 - D319P4 C299P1, C299P2 1*: C293P4, D293P1 D293P3, D293P4 2*: C285P1 - C285P4 IOC, input/output control LAU-LCU (Partner connection) X.21, V.24, V.35 HDLC (IOP:SCDP) LAU-LCU (Partner connection) V.24, V.28 HDLC (IOP:SCDV) or X.21, V.11 HDLC (IOP:SCDX) connected to C279P1, C279P2 to partner IOP connected to D273P3, D273P4 to partner IOP NT0, network management free PAD NT1 (ISO-FT) IOC Channel 0: PC, peripheral circuit Channel 1: V.24, V.28 HDLC Channel 2: V.24, V.28 HDLC Channel 3: V.24, V.28 HDLC in F:IOP0/1: CCNP (in SN:63LTG, SN:126LTG, SN:252LTG), in F:IOP2/3: CCNP (in SN:504LTG) in F:IOP0/1: MB1, in F:IOP2/3: MB3 in F:IOP0/1: MB0, in F:IOP2/3: MB2 CCG0 CCG1

D273P3, D273P4 C279P1, C279P2 03C273P4 03D273P1 04C273P1 04D273P1 3*: D225P2 C215P1 (IOP:SCDV) C215P2 (IOP:SCDV) C215P3 (IOP:SCDV) C215P4 (IOP:SCDV) C183P1 - C183P4

C159P1 - D159P4 C151P1 - C151P4 D135P1 - D135P2 D135P3 - D135P4

Tab. 3.46

Cabling F:IOP0/1

278

A30828-X1160-M-2-7620

107

IOC IOC IOC

3*

6*

IOC

1* 2*

4*

IOC

2*

BST

2*

Maintenance Node

Construction

4*: C119P4 5*: D119P1 6*: D119P2 7*: D119P3 8*: D119P4 C107P1

AD:RAL, adapter for rack alarm (R:CP113A) AD:RAL, adapter for rack alarm (R:DEV) AD:RAL, adapter for rack alarm (R:CP113B) AD:RAL, adapter for rack alarm (R:DEV) AD:RAL, adapter for rack alarm (R:DEV) F:IOP voltage supervision from IOC (+5V and GRD), jumpers (BST)

Tab. 3.46

Cabling F:IOP0/1

3.2.8.4

F:IOP2/3 (module side)


B:IOC

12

13

14

15

11

LCUB / IOPSCDV/X LAUB

IKDTD / LAUB

CLB IFMTD / LAUB

D
IOPSCDV/X DCCMS IOPMB IOPMB IOPMB

LCUB / IOPSCDV/X C305

C151 C159 C167

C253

C265 C273

C101

C225 C233

C245

Modules with displays and switches in F:IOP2/3 IOP:MB (-Q954-) IOP:TA (-Q956-) LAUB (-Q1115-) IOP:UNI (-Q1257-) IK:DTD (-Q975-) DCCMR (-Q5619-R100) IOP:SCDV (-Q952-) LCUB (-Q1114-) DCCMS (-Q5619-S100)

Tab. 3.47

Modules with displays and switches in F:IOP2/3

Notes for the accounting locations F:IOP2/3 C159: M:IOPMB If M:IOPMB is tted as IOP for MBG-2 (essential for SN:504LTG) in the F:IOP2, the MBG-3 must also be available in F:IOP3. C183: M:IOPMB If M:IOPMB is tted as IOP for CCNC in the F:IOP0, MBG-1 must also be available in the F:IOP1 (assignment CCNC in F:IOP0/F:IOP1 only up to SN:252LTG in F:IOP2/F:IOP3 for SN:504LTG).

C215

C285

C293

C313

DCCMR

LAUB

LAUB

LAUB

A30828-X1160-M-2-7620

279

Construction

Maintenance Node

C215: M:IOPSCDV or M:IOPSCDX 4 Data links (HDLC V.24/V.28) for operation of module IOPSCDV 4 Data links (HDLC X.21/V.11) for operation of module IOPSCDX C225: M:CLB Processor interface for PR05 and PR07 is essential when operating F:IOP2 and F:IOP3. IOC-2 (PRO5) must be available in F:P/IOC2. IOC-3 (PRO7) must be available in F:P/IOC3. C233/C245 and C253/C265, C273/C285 and C293/C305: M:LCUB and M:LAUB 2 Data links X.25; one IOPLAU pair (M:LCUB and M:LAUB) each are operated as partner for failure reasons in the F:IOP2/F:IOP3.

Assignment of logical/physical IOPMB numbers


F:IOP2 and F:IOP3 IOPMB IOPMB-00 IOPMB-01 IOPMB-36 IOPMB-37 IOPMB-38 IOPMB-39 MOLOC F:IOP2 / C167 F:IOP3 / C167 F:IOP2 / C151 F:IOP3 / C151 F:IOP2 / C159 F:IOP3 / C159 Remarks CCNP 0-0 (only SN:504LTG) CCNP 1-0 (only SN:504LTG) MBUL0-4, MBUS0-2, MBUL0-5 MBUL1-4, MBUS1-2, MBUL1-5 MBUL0-6, MBUS0-3, MBUL0-7 MBUL1-6, MBUS1-3, MBUL1-7

Tab. 3.48

Assignment of logical/physical IOPMB numbers

3.2.8.5

F:IOP2/3 (backplane)
See 3.2.8.2 "F:IOP0/1 (backplane)"

3.2.8.6

F:IOP2/3 (cabling)
See 3.2.8.3 "F:IOP0/1 (cabling)"

280

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.2.9 3.2.9.1

F:MI F:MI for BCMY (module side)


PI
IOC 1 BAP 1 PRO 3 PRO 2 BAP 0 IOC 0 PRO 0 PRO1

MI

D
C327 DCCMS PIADR PIDAT PIADR PIDAT PIADR PIDAT PIADR PIDAT DARB CARB BCTI

BBFR

BBFR

BBFR BBFR

BCLK BCLK C297 C305

C157 C163 C169 C175 C181 C189 C197

When extending PRO8 = CAP2 in F:P/IOC2 the following is extremely necessary: M:BBFR bus buffer extension to mounting location C243 and C249 in F:MI.

Modules with displays and switches in F:MI BCTI (-Q946-) DCCMS (-Q5619-S100) PIDAT (-Q940-)

Tab. 3.49

Modules with displays and switches in F:MI

C209

C261 C269 C277 C285

C125 C131 C139 C145

C243 C249

C219

C319 BCLK

MIAD

MIAD CMIB CMIB

A30828-X1160-M-2-7620

281

Construction

Maintenance Node

3.2.9.2

F:MI for BCMY (backplane)


CMY1 CMY1 CMY1 CMY1 345 CMY0 CMY0 CMY0CMY0 339 CMY0 399 Addresses Tact Tact Tact Tact 319 Pro11 Pro10 Pro9 Pro8 313 PI CMY 305 PI PI MI CMY 297 Trace PI Pro3 Pro2 PRO Pro0 291 Pro1 237 PI2 231 PI1 225 PI0 203 189 181 Pro3 Pro3 Pro3 175 Pro1 Pro1 Pro1 163 151 Pro2 Pro2 Pro2 145 Pro0 Pro0 PRO Pro0 131 Pro3 Pro3 Pro3 Pro3 119 Pro1 Pro1 Pro1 Pro1 113 Pro0 Pro0 Pro0 Pro0 107 MI MI MI MI MI MI MI MI MI Pro2 Pro2 Pro2 Pro2

Addresses

PI2 PI1

PI2 PI1

PI0 PI0

PI0

C2

C3 C4 C5

MI PI2 PI1

PI1

PI1

PI0

PI0

C1

MI

CMY1 CMY1 CMY1 CMY1 CMY0 CMY0 CMY0 CMY0 Data CMY1

PI CMY MI Pro7 Pro6 Pro5 Pro4

Tact Tact Tact Tact

MI PI2 PI1

PI2

PI0

MI

D1 D2

PI0

Data

PI2 PI1

D3 D4

CMY0

MI

PI2 PI1

PI0

PI0

PI

PI2 PI1

PI2

PI

MI

PI

MI

PI

3.2.9.3

F:MI for BCMY (cabling)


C107, D107, C113, C119 D113P1 - D113P4 D119P1 - D119P4 PI clock, 16 MHz, C151P4 PI clock, 8 MHz, D151P1 MI C181P4 Processor alarm/control signals PIO/MI connection to C203P1 - C203P4 PIO/MI connection to D203P1 - D203P4 PI/MI connection to C297P3 connected to D297P2 DARB/CARB connection to PI2 C189P2 (either cable or wired in backplane) DARB/CARB connection to PI2 C189P1 (either cable or wired in backplane) connected to MI C297P2 connected to MI D297P3 CMY clock

MI D181P1

MI C237P4 MI D237P1 C297P1, D297P4 C305P1, D305P4 C291P1 - C291P4 D291P1 - D291P4 C313P1 - C313P4

Processor clock (PRO0 - PRO3) 8 MHz Processor clock (PRO4 - PRO7) 8 MHz Processor clock (PRO8 - PRO11/PROB) 8 MHz

Tab. 3.50

Cabling F:MI for BCMY

282

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.2.10 3.2.10.1

F:PBC(A) F:PBC(A) (module side)


1) 2) 3) 4) 5) 6) 7)

D
DCCMD DCCMD DCCMD DCCMD C339 CMYM CMYM CMYM C319 CMYM C331 CMYC BCM PEX PEX MTI C257 PIA PIA PIA C233 PIA C249

C117

C101

C125

C143

C167

C201

C217

C287

1)

BAP 0 (Proc 0) in F:PBC(A) 0 BAP 1 (Proc 2) in F:PBC(A) 1 CAP 0 (Proc 4) in F:PBC(A) 0 CAP 1 (Proc 6) in F:PBC(A) 1 IF for Proc 0-3 in F:PBC(A) 0/1 IF for Proc 4-7 in F:PBC(A) 0/1 IF for Proc 8-11 in F:PBC(A) 0/1 IF for Proc 12-15 in F:PBC(A) 0/1 capacity of Common Memory must be identical in F:PBC(A)0/1! equipping sequence fro C295 to C331

2)

3) 4) 5) 6) 7)

BCM (-Q1252-) DCCMD (-Q5897-) PIA (-Q1253-)

C151

Modules with displays and switches in F:PBC(A) CMYC (-Q1255-) MTI (-Q1254-) CMYM (-Q1256-) PEX (-Q1251-)

Tab. 3.51

Modules with display and switches in F:PBC(A)

C295

C307

A30828-X1160-M-2-7620

283

Construction

Maintenance Node

3.2.10.2

F:PBC(A) (backplane)

10

10

2
7

C1 C2 C3 10 10 9 9 9 C4 C5 D1 9 D2 D3 9 9 9 9 1 D4 9 9 9 9

3 2

11

339

277 269

239

223

207

191

175 167 159

3 2

151

143

125 117 MOLOC

11

3.2.10.3

F:PBC(A) (cabling)
Cabling F:PBC(A) <----> F:PIOP(B) (Connector 2, 9
From F:PBC(A) Connector 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 Unit F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 MOLOC C191P3 C191P3 D191P3 D191P3 C207P3 C207P3 D207P3 D207P3 C223P1 C223P1 C223P3 C223P3 D223P1 D223P1 D223P3 D223P3 C239P1 Unit F:PIOP(B) 0 F:PIOP(B) 0 F:PIOP(B) 1 F:PIOP(B) 1 F:PIOP(B) 2 F:PIOP(B) 2 F:PIOP(B) 3 F:PIOP(B) 3 F:PIOP(B) 0 F:PIOP(B) 0 F:PIOP(B) 1 F:PIOP(B) 1 F:PIOP(B) 2 F:PIOP(B) 2 F:PIOP(B) 3 F:PIOP(B) 3 F:PIOP(B) 0 To F:PIOP(B)

C179P1 C179P3 C179P1 C179P3 C179P1 C179P3 C179P1 C179P3 C119P1 C119P3 C119P1 C119P3 C119P1 C119P3 C119P1 C119P3 C149P1

Tab. 3.52

Cabling F:PBC(A) <---> F:PIOP(B) (Connector 2, 9)

284

A30828-X1160-M-2-7620

101

Maintenance Node

Construction

From F:PBC(A) Connector 9 9 9 9 9 9 9 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Unit F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 MOLOC C239P1 C239P3 C239P3 D239P1 D239P1 D239P3 D239P3 C159P3 C159P3 D159P3 D159P3 C159P4 C159P4 D159P4 D159P4 C175P1 C175P1 C175P3 C175P3 D175P1 D175P1 D175P3 D175P3 C175P2 C175P2 C175P4 C175P4 D175P2 D175P2 D175P4 D175P4 Unit F:PIOP(B) 0 F:PIOP(B) 1 F:PIOP(B) 1 F:PIOP(B) 2 F:PIOP(B) 2 F:PIOP(B) 3 F:PIOP(B) 3 F:PIOP(B) 0 F:PIOP(B) 0 F:PIOP(B) 1 F:PIOP(B) 1 F:PIOP(B) 2 F:PIOP(B) 2 F:PIOP(B) 3 F:PIOP(B) 3 F:PIOP(B) 0 F:PIOP(B) 0 F:PIOP(B) 1 F:PIOP(B) 1 F:PIOP(B) 2 F:PIOP(B) 2 F:PIOP(B) 3 F:PIOP(B) 3 F:PIOP(B) 0 F:PIOP(B) 0 F:PIOP(B) 1 F:PIOP(B) 1 F:PIOP(B) 2 F:PIOP(B) 2 F:PIOP(B) 3 F:PIOP(B) 3

To F:PIOP(B) MOLOC C149P3 C149P1 C149P3 C149P1 C149P3 C149P1 C149P3 C179P5 D179P1 C179P5 D179P1 C179P5 D179P1 C179P5 D179P1 C119P5 D119P1 C119P5 D119P1 C119P5 D119P1 C119P5 D119P1 C149P5 D149P1 C149P5 D149P1 C149P5 D149P1 C149P5 D149P1

Tab. 3.52

Cabling F:PBC(A) <---> F:PIOP(B) (Connector 2, 9)

A30828-X1160-M-2-7620

285

Construction

Maintenance Node

Cabling F:PBC(A) internal (Connector 1, 2, 3, 9, 10, 11)


From F:PBC(A) Connector 2 1 2 1 3 3 3 3 11 9 11 9 10 10 10 10 Unit F:PBC(A) 0 F:PBC(A) 0 F:PBC(A) 0 F:PBC(A) 0 F:PBC(A) 0 F:PBC(A) 0 F:PBC(A) 0 F:PBC(A) 0 F:PBC(A) 0 F:PBC(A) 0 F:PBC(A) 0 F:PBC(A) 0 F:PBC(A) 0 F:PBC(A) 0 F:PBC(A) 0 F:PBC(A) 0 MOLOC 05C175P5 05D277P4 05D159P1 05D117P1 05C167P2 05C167P3 05D167P2 05D167P3 05C117P3 05D191P1 05C143P3 05D207P1 05C269P1 05C269P3 05C277P1 05C277P3 1 2 1 2 3 3 3 3 9 11 9 11 10 10 10 10 Connector To F:PBC(A) Unit F:PBC(A) 1 F:PBC(A) 1 F:PBC(A) 1 F:PBC(A) 1 F:PBC(A) 1 F:PBC(A) 1 F:PBC(A) 1 F:PBC(A) 1 F:PBC(A) 1 F:PBC(A) 1 F:PBC(A) 1 F:PBC(A) 1 F:PBC(A) 1 F:PBC(A) 1 F:PBC(A) 1 F:PBC(A) 1 MOLOC 06D277P4 06C175P5 06D117P1 06D159P1 06C167P3 06C167P2 06D167P3 06D167P2 06D191P1 06C117P3 06D207P1 06C143P3 06C277P1 06C277P3 06C269P1 06C269P3

Tab. 3.53

Cabling F:PBC(A) internal (Connector 1, 2, 3, 9, 10, 11)

286

A30828-X1160-M-2-7620

Maintenance Node

3.2.11.2

3.2.11.1

3.2.11

A30828-X1160-M-2-7620 C D

F:PI

D C
C101 DCCMS
P3 P2 P1

Tab. 3.54

PI - group 1

DCCMS (-Q5619-S100)

P4

P3

P2

P1

P5

P4

2*

2*

2*

2*

PRO9 PRO9PRO9PRO9 339

C125

PIADR

CAP 0 CAP 1 PRO 4 PRO 6

2*

2*

2*

319

C133 C141 C149 C163 C171 C179 C187 C195 PIADR

PIDAT PIADR PIDAT

PRO9PRO9PRO9 303 289 1* 1* 281

IOC 2 IOC 3 PRO5 PRO 7

F:PI for BCMY (backplane)

F:PI for BCMY (module side)

Modules with displays and switches in F:PI

Modules with displays and switches in F:PI

MI - Group 2 PIDAT PIADR PIDAT DARB


249 1* 1* 1* 239

MI

MI

PRO8 PRO8PRO8 265

MI

MI

MI

MI

MI

MI

1*

MI - group 2

MI

MI

MI

MI

PRO8 PRO8PRO8PRO8 229

MI

MI

MI

MI

PRO7PRO7PRO7 PRO7 217

MI

MI

MI

DARB C249 C257 C265 C273 C281

MI

PRO5 PRO5PRO5 PRO5 207 MI 195

PRO7PRO7 PRO7 187

PIADR PIDAT PIADR PIDAT PIADR PIDAT C295 C303 C311 C319 PIADR PIDAT

PRO5PRO5PRO5 171 157

MI

MI

CAP 2 CAP 4 CAP 3 CAP 5 PRO 8 PRO 10 PRO 9 PRO 11

PI - Group 1

PRO6PRO6 PRO6 149 PR

PRO4 PRO4 PRO4 133

Construction

PRO6PRO6PRO6 PRO6

PRO4 PRO4PRO4PRO4 113

287

Construction

Maintenance Node

3.2.11.3

F:PI for BCMY (cabling)


06C113P1, 06C113P4 06D113P1, 06D113P4 06C195P4, 06D195P1 07C195P4, 07D195P1 06D207P1, 06D207P4 07D207P1, 07D207P4 06D217P1, 06D217P4 07D217P1, 07D217P4 06D229P1, 06D229P4 07D229P1, 07D229P4 06D239P1, 06D239P4 07D239P1, 07D239P4 06C249P4, 06D249P1 07C249P4, 07D249P1 06C339P1, 06C139P4 06D339P1, 06D139P4 CMY PI MI PRO 06C113P1 - 06C113P4 06D113P1 - 06D113P4 Processor alarm/control signals Processor alarm/control signals DARB1 control signals to F:MI (BCMY0, R:CP113A) DARB1 control signals to F:MI (BCMY1, R:CP113A) PI1/MI connection to F:MI (BCMY0, R:CP113A), data PI1/MI connection to F:MI (BCMY1, R:CP113A), addresses PI1/MI connection to F:MI (BCMY0, R:CP113A), addresses PI1/MI connection to F:MI (BCMY1, R:CP113A), data PI2/MI connection to F:MI (BCMY0, R:CP113A) PI2/MI connection to F:MI (BCMY1, R:CP113A) PI2/MI connection to F:MI (BCMY0, R:CP113A) PI2/MI connection to F:MI (BCMY1, R:CP113A) DARB2 control signals to F:MI (BCMY0, R:CP113A) DARB2 control signals to F:MI (BCMY1, R:CP113A) Processor alarm/control signals Processor alarm/control signals Common memory Processor interface unit Memory interface unit Processor Processor alarm/control signals Processor alarm/control signals

Tab. 3.55

Cabling F:PI for BCMY

288

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.2.12 3.2.12.1

F:PIOP(A) F:PIOP(A) (module side)


1) 2) 3) 3) 4) 4) 4) 5) 6) 7) 7) 8) 9) 10) 4) 11)

LCUB / IOPUNI / IOPAUC

LCUB / IOPUNI / IOPAUC

D
DCCMD DCCMD

LCUB / IOPUNI / IOPAUC

C101

C119

C153

C145

C165

C177

C221

C233

C189

C199

C211

C243

C127

C255

C269

C279

C291

C301

C311

IOPUNI

1)

CAP2(Proc 8) in F:PIOP(A) 0 CAP3(Proc 9) in F:PIOP(A) 1 CAP4(Proc 10) in F:PIOP(A) 2 CAP5(Proc 11) in F:PIOP(A) 3 IOC0 (Proc IOC1 (Proc IOC2 (Proc IOC3 (Proc 1) in F:PIOP(A) 0 3) in F:PIOP(A) 1 5) in F:PIOP(A) 2 7) in F:PIOP(A) 3

2)

3)

for connection of 2 X.25-IF distribute in F:PIOP(A) 0+1 or 2+3 (equipping sequence from C153 to C233) for connection of 3 serial HDLC-IF (V.24 or X.21) or 2 SCSI-IF (no MDD, only MOD or MTD) for connection of MDD0, MOD0 and/or MTD0; PC0; 1 or 2 V.24, X.21-IF in PIOP(A) 0 for connection of MDD1, MOD1 and/or MTD1; PC1; 1 or 2 V.24, X.21-IF in PIOP(A) 1 for CCNC connection in F:PIOP(A) 0/1 not equipped when DE54 or in F:PIOP(A) 2/3 for DE54 only. for MBD connection in F:PIOP(A) 0/1 (C279 for DE51, C269 for DE52) and additionally in F:PIOP(A) 2/3 for DE54 only. for SYP or PROFIBUS connection in F:PIOP(A) 0/1 for CCG connection in F:PIOP(A) 0/1 for rack alarms and radio clock connection in F:PIOP(A) 0/1 power supply for IOPs on C153 to C321

4) 5)

6) 7)

8) 9) 10) 11)

C321

A30828-X1160-M-2-7620

289

C337

DCCMD

IOPUNI

IOPMB

IOPMB

IOPMB

IOPMB

IOPMB

IOPTA

LAUB

LAUB

LAUB

LAUB

LAUB

PEX

PEX

Construction

Maintenance Node

Modules with displays and switches in F:PIOP(A) PEX (-Q1251-) IOP:UNI (-Q1257-) IOP:TA (-Q956-) LAUB (-Q1115-) IOP:AUC (-Q1169-) DCCMD (-Q5897-) LCUB (-Q1114-) IOP:MB (-Q954-)

Tab. 3.56

Modules with displays and switches in F:PIOP(A)

Assignment of logical/physical IOPMB numbers


F:PIOP(A)0 and F:PIOP(A)1 IOPMB IOPMB-00 IOPMB-01 IOPMB-32 IOPMB-33 IOPMB-34 IOPMB-35 IOPMB-40 IOPMB-41 IOPMB-42 IOPMB-43 MOLOC F:PIOP(A)0 / C255 F:PIOP(A)1 / C255 F:PIOP(A)0 / C279 F:PIOP(A)1 / C279 F:PIOP(A)0 / C269 F:PIOP(A)1 / C269 F:PIOP(A)0 / C301 F:PIOP(A)1 / C301 F:PIOP(A)0 / C291 F:PIOP(A)1 / C291 Remarks CCNP 0-0 (only to SN:252LTG) (only without SSNC) CCNP 1-0 (only to SN:252LTG) (only without SSNC) MBUL0-0, MBUS0-0, MBUL0-1 MBUL1-0, MBUS1-0, MBUL1-1 MBUL0-2, MBUS0-1, MBUL0-3 MBUL1-2, MBUS1-1, MBUL1-3 CCG0 CCG1 SYP SYP

Tab. 3.57

Assignment of logical/physical IOPMB numbers

F:PIOP(A)2 and F:PIOP(A)3 IOPMB IOPMB-00 IOPMB-01 IOPMB-36 IOPMB-37 IOPMB-38 IOPMB-39 MOLOC F:PIOP(A)2 / C255 F:PIOP(A)3 / C255 F:PIOP(A)2 / C279 F:PIOP(A)3 / C279 F:PIOP(A)2 / C269 F:PIOP(A)3 / C269 Remarks CCNP 0-0 (only to SN:504LTG)(only without SSNC) CCNP 1-0 (only to SN:504LTG) (only without SSNC) MBUL0-4, MBUS0-2, MBUL0-5 MBUL1-4, MBUS1-2, MBUL1-5 MBUL0-6, MBUS0-3, MBUL0-7 MBUL1-6, MBUS1-3, MBUL1-7

Tab. 3.58

Assignment of logical/physical IOPMB numbers

290

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.2.12.2

F:PIOP(A) (backplane)
337 329 301 291 279 269 255 249 243 227 221 205 199 189 183 177 159 153 145 127 119 101

11*

11*

8* 8* 14* 9* PC

9* 11*

11*

4*

5*

6*

7*

P1
17* 3*

PIA*

PIA*

16*

11*

11*

P2

3*

6*

7*

PIA*

12*

12*

P4 P5

10*

12*

12*

2*

4*

6*

7*

8*

13*

13*

12*

12*

12*

P1 P2

11*

11*

P3 P4

11*

11*

11*

11*

3.2.12.3

F:PIOP(A) (cabling)
1* 2* 3* 4* 5* 6* AD:RAL, Adapter for rack alarm (R:DEV.) AD:RAL, Adapter for rack alarm (R:CP113C) CCG (Clock) CCG (in F:PIOP0) SYPC MBG0, message buffer group (in F:PIOP0) MBG2, message buffer group (in F:PIOP2) MBG1, message buffer group (in F:PIOP1) MBG3, message buffer group (in F:PIOP3) CCNP, (processor common channel signaling network control (F:PIOP0/1 for SN:126LTG, SN:252LTG) V.24, V.28/X.21, V.11 HDLC (OMC) SCSI interface (MDD, MTD) LAU - LCU (partner connection) X.21, V.24, V.35 HDLC BCM (Clock), bus clock generator and control for maintenance FP - M:LAUB, fuse panel - line adaptation unit, module B, BX.25 or X.25 interface FP - CAP, fuse panel - call processor FP - IOC, fuse panel - input/output control FP - IOPG, fuse panel - input/output processor group FP - M:LAUB, fuse panel - line adaptation unit, module B, BX.25 or X.25 interface

7*

8*

9* 10* 11* 12* 13* 14* 15* 16* 17* PIA*

Tab. 3.59

Cabling F:PIOP

11*

11*

1*

12*

13*

1*

13*

PIA*

4*

P3

8*

9*

9*

9* 11*

11*

4*

5*

6*

7*

A30828-X1160-M-2-7620

291

15*

Construction

Maintenance Node

3.2.13 3.2.13.1

F:PIOP(B) F:PIOP(B) (module side)


classic (for CCNC connection)
1) 2) 3) 4) 4) 5) 5) 5) 5) 6) 7) 8) 9) 10) 11) 12) 13)

LCUB / IOPUNI

LCUB / IOPUNI

LCUB / IOPUNI

DCCMD

DCCMD

LCUB / IOPUNI

D
DCCMD

C101

C161

C119

C149

C179

C227

C235

C243

C199

C215

C251

C305

C321

C191

C207

C131

C263

C271

C281

C289

C297

C313

C329

IOPTA

1)

CAP2 (Proc 8) in F:PIOP(B) 0 CAP3 (Proc 9) in F:PIOP(B) 1 CAP4 (Proc 10) in F:PIOP(B) 2 CAP5 (Proc 11) in F:PIOP(B) 3 CAP6 (Proc 12) in F:PIOP(B) 0 CAP7 (Proc 13) in F:PIOP(B) 1 CAP8 (Proc 14) in F:PIOP(B) 2 CAP9 (Proc 15) in F:PIOP(B) 3 IOC0 (Proc IOC1 (Proc IOC2 (Proc IOC3 (Proc 1) in F:PIOP(B) 0 3) in F:PIOP(B) 1 5) in F:PIOP(B) 2 7) in F:PIOP(B) 3

2)

3)

4)

for connection of 2 X.25-IF distribute in F:PIOP(B) 0+1 oder 2+3 equally for reason of failure! (equipping sequence from C191 to C271) for connection of 3 serial HDLC-IF (V.24 or X.21) or 2 SCSI-IF (no MDD, only MOD or MTD) for connection of MDD0, MOD0; PC0; 1 or 2 V.24, X.21-IF in PIOP(B) 0 for connection of MDD1, MOD1; PC1; 1 or 2 V.24, X.21-IF in PIOP(B) 1 for CCNC connection in F:PIOP(B) 0/1 not equipped when DE54 or in F:PIOP(B) 2/3 for DE54 only for MBD connection in F:PIOP(B) 0/1 (C305 for DE51, C297 and C305 for DE52) and additionally in F:PIOP(B) 2/3 for DE54 only for SYPC or PROFIBUS connection in F:PIOP(B) 0/1 for CCG connection in F:PIOP(B) 0/1 for rack alarms and radio clock connection in F:PIOP(B) 0/1 power supply for IOPs on C191 to C329

5) 6)

7) 8)

9) 10) 11) 12)

292

A30828-X1160-M-2-7620

C341

DCCMD

IOPUNI

IOPMB

IOPMB

IOPMB

IOPMB

IOPMB

LAUB

LCUB

LAUB

LAUB

LAUB

PEX

PEX

LAUB

PEX

Maintenance Node

Construction

innovation (for SSNC-C connection)


1) 2) 3) 4) 4) 5) 5) 5) 7) 6) 7) 7) 7) 7) 8) 9) 10)

LCUB / IOPUNI

LCUB / IOPUNI

LCUB / IOPUNI

D
PEX / AMPC DCCMD DCCMD DCCMD

LCUB / IOPUNI / IOPMB

C101

C161

C119

C149

C179

C227

C235

C243

C199

C215

C251

C305

C321

C191

C207

C131

C263

C271

C281

C289

C297

C313

C329

IOPTA

1)

AMP0 (Proc 8) = AMPC + FOTX in F:PIOP(B) 0 AMP1 (Proc 9) = AMPC + FOTX in F:PIOP(B) 1 CAP4 (Proc 10) = PEX in F:PIOP(B) 2 CAP5 (Proc 11) = PEX in F:PIOP(B) 3 CAP2 (Proc 12) in F:PIOP(B) 0 CAP3 (Proc 13) in F:PIOP(B) 1 CAP6 (Proc 14) in F:PIOP(B) 2 CAP7 (Proc 15) in F:PIOP(B) 3 IOC0 (Proc 1) in F:PIOP(B) 0 IOC1 (Proc 3) in F:PIOP(B) 1 CAP8 or IOC2 (Proc 5) in F:PIOP(B) 2 CAP9 or IOC3 (Proc 7) in F:PIOP(B) 3 for connection of 2 X.25-IF distribute in F:PIOP(B) 0+1 or 2/3 equally for reason of failures! (equipping sequence from C191 to C271) for connection of 3 serial HDLC-IF (V.24 or X.21) or 2 SCSI-IF (no MDD, only MOD or MTD) for connection of MDD0, MOD0; PC0; 1 or 2 V.24, X.21-IF in PIOP(B) 0 for connection of MDD1, MOD1; PC1; 1 or 2 V.24, X.21-IF in PIOP(B) 1 for MBD connection in F:PIOP(B) 0/1 for CCG and PROFIBUS connection in F:PIOP(B) 0/1 for rack alarms and radio clock connection in F:PIOP(B) 0/1 power supply for IOPs on C191 to C329

2)

3)

4)

5) 6)

7) 8) 9) 10)

A30828-X1160-M-2-7620

293

C341

DCCMD

IOPUNI

IOPMB

IOPMB

IOPMB

IOPMB

IOPMB

LAUB

LCUB

LAUB

LAUB

LAUB

PEX

LAUB

PEX

Construction

Maintenance Node

Modules with displays and switches in F:PIOP(B) AMPC (-Q1388-) IOP:MB (-Q954-) LCUB (-Q1114-) BCM (-Q1252-) IOP:TA (-Q956-) LAUB (-Q1115-) DCCMD (-Q5897-) IOP:UNI (-Q1257-) PEX (-Q1251-)

Tab. 3.60

Modules in F:PIOP(B)

Assignment of logical/physical IOPMB numbers For F:PIOP(B) S30804-B2692-X200 and MBD


F:PIOP(B)0 and F:PIOP(B)1 IOPMB MOLOC local IOPMB-42 IOPMB-43 IOPMB-32 IOPMB-33 IOPMB-34 IOPMB-35 IOPMB-00 IOPMB-01 IOPMB-40 IOPMB-41 F:PIOP(B)0 / C313 F:PIOP(B)1 / C313 F:PIOP(B)0 / C305 F:PIOP(B)1 / C305 F:PIOP(B)0 / C297 F:PIOP(B)1 / C297 F:PIOP(B)0 / C289 F:PIOP(B)1 / C289 F:PIOP(B)0 / C321 F:PIOP(B)1 / C321 for max 410 LTG for max 410 LTG for max 820 LTG for max 820 LTG for max 1230 LTG for max 1230 LTG for max 1640 LTG for max 1640 LTG Exchange Type transit for max 650 LTG for max 650 LTG for max 1300 LTG for max 1300 LTG for max 1950 LTG for max 1950 LTG for max 2016 LTG for max 2016 LTG international for max 405 LTG for max 405 LTG for max 810 LTG for max 810 LTG for max 1215 LTG for max 1215 LTG for max 1620 LTG for max 1620 LTG

Connection to CCG and Profibus Connection to CCG and Profibus

Tab. 3.61

Assignment of logical/physical IOPMB numbers

3.2.13.2

F:PIOP(B) (backplane)
16 P1 1 P2

6#4

6#1

4a

4a

4a

15

12 11a

14#5

6#5 14#4

14#3

14#2

11b 11c

15 11

6#2

4b

13

P4 P5 P1

13

17 17

10

4b

6#3

13

P2 P3 P4

13

13

4b

341 335 329

13

305 297 289 281 271

263 257 251

243 235 227 221 215 207 199 191

179

169

149

139 131

119

321 313

294

A30828-X1160-M-2-7620

109 101

P3

11d

14#1

Maintenance Node

Construction

3.2.13.3

F:PIOP(B) (cabling)
Power supply cabling (Connector 1, 2)
Connector 1 1 1 2 MOLOC C341P1 C131P1 C101P1 C257P5 Port primary connection DCCDM C341 primary connection DCCDM C131 and C161 primary connection DCCDM C101 primary connection for LAUB Connection To the breaker panel of the rack To the breaker panel of the rack To the breaker panel of the rack To the breaker panel of the rack

Tab. 3.62

Power supply cabling (Connector 1, 2)

Cabling F:PIOP(B) <----> F:PBC(A) (Connector 4a, 4b, 5)


From F:PIOP(B) Connector 4a 4b 4a 4b 4a 4b 4a 4b 4a 4b 4a 4b 4a 4b 4a 4b 4a 4b 4a 4b 4a 4b 4a 4b 5 Unit F:PIOP(B) 0 F:PIOP(B) 0 F:PIOP(B) 1 F:PIOP(B) 1 F:PIOP(B) 2 F:PIOP(B) 2 F:PIOP(B) 3 F:PIOP(B) 3 F:PIOP(B) 0 F:PIOP(B) 0 F:PIOP(B) 1 F:PIOP(B) 1 F:PIOP(B) 2 F:PIOP(B) 2 F:PIOP(B) 3 F:PIOP(B) 3 F:PIOP(B) 0 F:PIOP(B) 0 F:PIOP(B) 1 F:PIOP(B) 1 F:PIOP(B) 2 F:PIOP(B) 2 F:PIOP(B) 3 F:PIOP(B) 3 F:PIOP(B) 0 MOLOC C179P1 C179P3 C179P1 C179P3 C179P1 C179P3 C179P1 C179P3 C119P1 C119P3 C119P1 C119P3 C119P1 C119P3 C119P1 C119P3 C149P1 C149P3 C149P1 C149P3 C149P1 C149P3 C149P1 C149P3 C179P5 Unit F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 To F:PBC(A) MOLOC C191P3 C191P3 D191P3 D191P3 C207P3 C207P3 D207P3 D207P3 C223P1 C223P1 C223P3 C223P3 D223P1 D223P1 D223P3 D223P3 C239P1 C239P1 C239P3 C239P3 D239P1 D239P1 D239P3 D239P3 C159P3

Tab. 3.63

Cabling F:PIOP(B) <---> F:PBC(A) (Connector 4a, 4b, 5)

A30828-X1160-M-2-7620

295

Construction

Maintenance Node

From F:PIOP(B) Connector 5 5 5 5 5 5 5 5 5 5 4b 4a 4b 4a 4b 4a 4b 4a 4b 4a 4b 4a 4b Unit F:PIOP(B) 0 F:PIOP(B) 1 F:PIOP(B) 1 F:PIOP(B) 2 F:PIOP(B) 2 F:PIOP(B) 3 F:PIOP(B) 3 F:PIOP(B) 0 F:PIOP(B) 0 F:PIOP(B) 1 F:PIOP(B) 1 F:PIOP(B) 2 F:PIOP(B) 2 F:PIOP(B) 3 F:PIOP(B) 3 F:PIOP(B) 0 F:PIOP(B) 0 F:PIOP(B) 1 F:PIOP(B) 1 F:PIOP(B) 2 F:PIOP(B) 2 F:PIOP(B) 3 F:PIOP(B) 3 MOLOC D179P1 C179P5 D179P1 C179P5 D179P1 C179P5 D179P1 C119P5 D119P1 C119P5 D119P1 C119P5 D119P1 C119P5 D119P1 C149P5 D149P1 C149P5 D149P1 C149P5 D149P1 C149P5 D149P1 Unit F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1 F:PBC(A) 0 F:PBC(A) 1

To F:PBC(A) MOLOC C159P3 D159P3 D159P3 C159P4 C159P4 D159P4 D159P4 C175P1 C175P1 C175P3 C175P3 D175P1 D175P1 D175P3 D175P3 C175P2 C175P2 C175P4 C175P4 D175P2 D175P2 D175P4 D175P4

Tab. 3.63

Cabling F:PIOP(B) <---> F:PBC(A) (Connector 4a, 4b, 5)

Cabling F:PIOP(B) 0/2 <----> F:PIOB(B) 1/3 (Connector 6, 7)


From F:PIOP(B) 0/2 Connector 6#1 6#1 7 7 6#2 6#2 7 7 Unit F:PIOP(B) 0/2 F:PIOP(B) 0/2 F:PIOP(B) 0/2 F:PIOP(B) 0/2 F:PIOP(B) 0/2 F:PIOP(B) 0/2 F:PIOP(B) 0/2 F:PIOP(B) 0/2 MOLOC C221P1 C221P2 D191P3 D191P4 C221P3 C221P4 D207P3 D207P4 7 7 6#1 6#1 7 7 6#2 6#2 Connector To F:PIOB(B) 1/3 Unit F:PIOP(B) 1/3 F:PIOP(B) 1/3 F:PIOP(B) 1/3 F:PIOP(B) 1/3 F:PIOP(B) 1/3 F:PIOP(B) 1/3 F:PIOP(B) 1/3 F:PIOP(B) 1/3 MOLOC C191P3 C191P3 C221P1 C221P2 D207P3 D207P4 C221P3 C221P4

Tab. 3.64

Cabling F:PIOP(B) 0/2<---> F:PIOP(B) 1/3 (Connector 6, 7)

296

A30828-X1160-M-2-7620

Maintenance Node

Construction

From F:PIOP(B) 0/2 Connector 6#3 6#3 7 7 6#4 6#4 7 7 6#5 6#5 7 7 Unit F:PIOP(B) 0/2 F:PIOP(B) 0/2 F:PIOP(B) 0/2 F:PIOP(B) 0/2 F:PIOP(B) 0/2 F:PIOP(B) 0/2 F:PIOP(B) 0/2 F:PIOP(B) 0/2 F:PIOP(B) 0/2 F:PIOP(B) 0/2 F:PIOP(B) 0/2 F:PIOP(B) 0/2 MOLOC C221P5 D221P1 D227P3 D227P4 C257P1 C257P2 D243P3 D243P4 C257P3 C257P4 D263P3 D263P4 7 7 6#3 6#3 7 7 6#4 6#4 7 7 6#5 6#5 Connector

To F:PIOB(B) 1/3 Unit F:PIOP(B) 1/3 F:PIOP(B) 1/3 F:PIOP(B) 1/3 F:PIOP(B) 1/3 F:PIOP(B) 1/3 F:PIOP(B) 1/3 F:PIOP(B) 1/3 F:PIOP(B) 1/3 F:PIOP(B) 1/3 F:PIOP(B) 1/3 F:PIOP(B) 1/3 F:PIOP(B) 1/3 MOLOC D227P3 D227P4 C221P5 D221P1 D243P3 D243P4 C257P1 C257P2 D263P3 D263P4 C257P3 C257P4

Tab. 3.64

Cabling F:PIOP(B) 0/2<---> F:PIOP(B) 1/3 (Connector 6, 7)

Cabling F:PIOP(B) (clock supply, alarming and other)


Connector 9 10 10 13 13 16 17 17 Unit F:PIOP(B) 0/1 F:PIOP(B) 0 F:PIOP(B) 0 F:PIOP(B) 0/1 F:PIOP(B) 0/1 F:PIOP(B) 0/1 F:PIOP(B) 0/1 F:PIOP(B) 0/1 MOLOC C281P1 C281P4 C281P4 C335P4 D335P1 C335P1 C291P5 C313P5 Connection Connection for PC, OMT PC via MODEM F:DEV(F) MDD 0 F:DEV(F) MDD 1 Alarm cabling to AD:RAL Alarm cabling to AD:RAL To F:MODEM (Radio clock) To Profibus PBSL To Profibus PBSL

Tab. 3.65

Cabling F:PIOP(B) (clock supply, alarming and other)

Cabling F:PIOP(B) <--> F:SCB (Connector 3)


From PIOP(B) Connector 3 (OPTO) 3 (OPTO) 3 (OPTO) 3 (OPTO) 3 (OPTO) 3 (OPTO) Unit F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)0 MOLOC 03 C109P3 03 C109P2 07 C109P3 07 C109P2 03 D109P3 03 D109P2 F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB Unit To F:SCB MOLOC 09D149P4 09D149P5 09D169P4 09D169P5 09D211P4 09D211P5

Tab. 3.66

Cabling F:PIOP(B) <---> F:SCB (Connector 3)

A30828-X1160-M-2-7620

297

Construction

Maintenance Node

From PIOP(B) Connector 3 (OPTO) 3 (OPTO) Unit F:PIOP(B)1 F:PIOP(B)1 MOLOC 07 D109P3 07 D109P2 F:SCB F:SCB Unit

To F:SCB MOLOC 09D231P4 09D231P5

Tab. 3.66

Cabling F:PIOP(B) <---> F:SCB (Connector 3)

Cabling F:PIOP(B) <--> F:MBD (Connector 11a, 11b, 11c, 11d) (Innovation)
From PIOP(B) Connector 11a 11a 11a 11a 11a 11a 11a 11a 11b 11b 11b 11b 11b 11b 11b 11b 11c 11c 11c 11c 11c 11c 11c 11c 11d 11d 11d 11d 11d Unit F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)0 MOLOC 03 C313P2 03 C313P1 07 C313P2 07 C313P1 03 C313P4 03 C313P3 07 C313P4 07 C313P3 03 C305P1 03 C305P2 07 C305P1 07 C305P2 03 C305P3 03 C305P4 07 C305P3 07 C305P4 07 C297P1 07 C297P2 03 C297P1 03 C297P2 07 C297P3 07 C297P4 03 C297P3 03 C297P4 03 C289P1 03 C289P2 07 C289P1 07 C289P2 03 C289P3 Unit F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC To MBD MOLOC C173P1 C189P1 C195P1 C201P1 C173P1 C189P1 C195P1 C201P1 C189P2 C189P3 C195P2 C195P3 C189P2 C189P3 C195P2 C195P3 C189P4 C189P5 C201P2 C201P3 C189P4 C189P5 C201P2 C201P3 C195P4 C195P5 C201P4 C201P5 C195P4

Tab. 3.67

Cabling F:PIOP(B) <---> F:MBD (Connector 11a, 11b, 11c, 11d)

298

A30828-X1160-M-2-7620

Maintenance Node

Construction

From PIOP(B) Connector 11d 11d 11d Unit F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)0 MOLOC 03 C289P4 07 C289P3 07 C289P4 Unit F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC

To MBD MOLOC C195P5 C201P4 C201P5

Tab. 3.67

Cabling F:PIOP(B) <---> F:MBD (Connector 11a, 11b, 11c, 11d)

Cabling F:PIOP(B) <--> F:MBD (Connector 11b, 11c) EWSD Classic


From CP113C, F:PIOP(B) Capacity State SN(63LTG) and SN(126LTG) Connector 11b 11b 11b 11b 11b 11b 11b 11b SN(252LTG) 11c 11c 11c 11c 11c 11c 11c 11c SN(504LTG) 11b 11b 11c 11c 11b 11b 11c 11c 11b 11b 11c 11c 11b 11b 11c 11c Unit F:PIOP(B) 0 F:PIOP(B) 1 MOLOC 03 C305P2 03 C305P1 07 C305P2 07 C305P1 03 C305P4 03 C305P3 07 C305P4 07 C305P3 03 C297P1 03 C297P2 07 C297P1 07 C297P2 03 C297P3 03 C297P4 07 C297P3 07 C297P4 09 C305P1 09 C305P2 02 C297P1 02 C297P2 09 C305P3 09 C305P4 02 C297P3 02 C297P4 02 C305P1 02 C305P2 09 C297P1 09 C297P2 02 C305P3 02 C305P4 09 C297P3 05 C297P4 To MBD Unit F:MBD0 / MBDC MOLOC C173P1 C189P1 C195P1 C201P1 C173P1 C189P1 C195P1 C201P1 C189P2 C189P3 C195P2 C195P3 C189P2 C189P3 C195P2 C195P3 C189P4 C189P5 C195P4 C195P5 C189P4 C189P5 C195P4 C195P5 C201P2 C201P3 C201P4 C201P5 C201P2 C201P3 C201P4 C201P5

F:PIOP(B) 0 F:PIOP(B) 1

F:MBD1 / MBDC

F:PIOP(B) 0 F:PIOP(B) 1

F:MBD0 / MBDC

F:PIOP(B) 0 F:PIOP(B) 1

F:MBD1 / MBDC

F:PIOP(B) 3 F:PIOP(B) 2

F:MBD0/MBDC

F:PIOP(B) 3 F:PIOP(B) 2

F:MBD1/MBDC

F:PIOP(B) 2 F:PIOP(B) 3

F:MBD0/MBDC

F:PIOP(B) 2 F:PIOP(B) 3

F:MBD1/MBDC

Tab. 3.68

Cabling F:PIOP(B) <---> F:MBD

A30828-X1160-M-2-7620

299

Construction

Maintenance Node

Cabling F:PIOP(B) <--> F:CCGE / (Connector 12, 13)


From PIOP(B) Connector 13 13 13 13 12 12 12 12 12 12 12 12 Unit F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 MOLOC 03 C335P2 07 C335P2 03 C335P3 07 C335P3 03 C321P2 03 C321P1 07 C321P2 07 C321P1 03 C321P4 03 C321P3 07 C321P4 07 C321P3 Unit F:CCGE F:CCGE F:CCGE F:CCGE F:CCGE F:CCGE F:CCGE F:CCGE F:CCGE F:CCGE F:CCGE F:CCGE To CCGE MOLOC C119P2 C125P2 C251P2 C257P2 D131P2 D131P3 D137P2 D137P3 D263P2 D263P3 D269P2 D269P3

Tab. 3.69

Cabling F:PIOP(B) <---> F:CCGE (Connector 12, 13)

Cabling PIOP(B) <----> F:MB/CCG(B)


F:PIOP(B) Capacity Stage SN(63LTG) and SN(126LTG) Connector 11b 11b 11b 11b 11b 11b 11b 11b SN(252LTG) 11c 11c 11c 11c 11c 11c 11c 11c Unit PIOP(B) 0 PIOP(B) 1 PIOP(B) 0 PIOP(B) 1 PIOP(B) 0 PIOP(B) 1 PIOP(B) 0 PIOP(B) 1 PIOP(B) 0 PIOP(B) 1 PIOP(B) 0 PIOP(B) 1 PIOP(B) 0 PIOP(B) 1 PIOP(B) 0 PIOP(B) 1 MOLOC 03 C305P2 07 C305P2 03 C305P1 07 C305P1 03 C305P4 07 C305P4 03 C305P3 07 C305P3 03 C297P2 07 C297P2 03 C297P1 07 C297P1 03 C297P4 07 C297P4 03 C297P3 07 C297P3 Unit MBUS-0-0 (MBG00) MBUS-0-0 (MBG00) MBUS-0-0 (MBG00) MBUS-0-0 (MBG00) MBUS-1-0 (MBG10) MBUS-1-0 (MBG10) MBUS-1-0 (MBG10) MBUS-1-0 (MBG10) MBUS-0-1 (MBG01) MBUS-0-1 (MBG01) MBUS-0-1 (MBG01) MBUS-0-1 (MBG01) MBUS-1-1 (MBG11) MBUS-1-1 (MBG11) MBUS-1-1 (MBG11) MBUS-1-1 (MBG11) F:MB/CCG(B) MOLOC 02/04 A046 02/04 A052 02/04 B046 02/04 B052 03/05 A046 03/05 A052 03/05 B046 03/05 B052 08/04 A046 08/04 A052 08/04 B046 08/04 B052 09/05 A046 09/05 A052 09/05 B046 09/05 B052

Tab. 3.70

F:MB/CCG(B): cables MB - F:PIOP(B) (CP113C)

300

A30828-X1160-M-2-7620

Maintenance Node

Construction

F:PIOP(B) Capacity Stage SN(504LTG) Connector 11b 11b 11b 11b 11b 11b 11b 11b 11c 11c 11c 11c 11c 11c 11c 11c Unit PIOP(B) 2 PIOP(B) 3 PIOP(B) 2 PIOP(B) 3 PIOP(B) 2 PIOP(B) 3 PIOP(B) 2 PIOP(B) 3 PIOP(B) 2 PIOP(B) 3 PIOP(B) 2 PIOP(B) 3 PIOP(B) 2 PIOP(B) 3 PIOP(B) 2 PIOP(B) 3 MOLOC 02 C305P2 09 C305P2 02 C305P1 09 C305P1 02 C305P4 09 C305P4 02 C305P3 09 C305P3 02 C297P2 09 C297P2 02 C297P1 09 C297P1 02 C297P4 09 C297P4 02 C297P3 09 C297P3 Unit

F:MB/CCG(B) MOLOC 02/04 A046 02/04 A052 02/04 B046 02/04 B052 03/05 A046 03/05 A052 03/05 B046 03/05 B052 08/04 A046 08/04 A052 08/04 B046 08/04 B052 09/05 A046 09/05 A052 09/05 B046 09/05 B052

MBUS-0-2 (MBG02) MBUS-0-2 (MBG02) MBUS-0-2 (MBG02) MBUS-0-2 (MBG02) MBUS-1-2 (MBG12) MBUS-1-2 (MBG12) MBUS-1-2 (MBG12) MBUS-1-2 (MBG12) MBUS-0-3 (MBG03) MBUS-0-3 (MBG03) MBUS-0-3 (MBG03) MBUS-0-3 (MBG03) MBUS-1-3 (MBG13) MBUS-1-3 (MBG13) MBUS-1-3 (MBG13) MBUS-1-3 (MBG13)

Tab. 3.70

F:MB/CCG(B): cables MB - F:PIOP(B) (CP113C)

Cabling PIOP(B) <----> CCGA


From PIOP(B) Connector 12 12 12 12 12 12 12 12 15 15 15 15 Unit F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 MOLOC 03 C321P2 03 C321P1 07 C321P2 07 C321P1 03 C321P4 03 C321P3 07 C321P4 07 C321P3 03 C335P2 03 C335P3 07 C335P2 07 C335P3 Unit F:MBCCG(A) CCG 0 F:MBCCG(A) CCG 0 F:MBCCG(A) CCG 0 F:MBCCG(A) CCG 0 F:MBCCG(A) CCG 1 F:MBCCG(A) CCG 1 F:MBCCG(A) CCG 1 F:MBCCG(A) CCG 1 F:MBCCG(A) CCG 0 F:MBCCG(A) CCG 1 F:MBCCG(A) CCG 0 F:MBCCG(A) CCG 1 To CCGA MOLOC A095 B095 A101 B101 A095 B095 A101 B101 B071 B071 A071 A071

Tab. 3.71

Cabling PIOP(B) <---> CCGA (Connector 12)

A30828-X1160-M-2-7620

301

Construction

Maintenance Node

3.2.14 3.2.14.1

F:P/IOC F:P/IOC (module side)


BAP0/1 or CAP0/1/2/4 IOC0/1/2/3 or CAP3/5

D
C101 DCCMS CPCIB C327 DCCMS

CPCIB CPCIA CPCC CPAC

CPEX MUH MUH CPCL CPCC CPAC C205 CPEX C213 CPEX

C223 CPAC C231 CPCC C239 CPCL

C249 IOCIF

C125 C133 C141 C149 C157 C165 C173 C179 C189 C197

C265 IOCIF

Note BAP0 (Proc0), IOC0 (Proc1) BAP1 (Proc2), IOC1 (Proc3) CAP0 (Proc4), IOC2 (Proc5) CAP1 (Proc6), IOC3 (Proc7) CAP2 (Proc8), CAP3 (Proc9) CAP4 (Proc10), CAP5 (Proc11)

in F:P/OC0 in F:P/OC1 in F:P/OC2 in F:P/OC3 in F:P/OC4 in F:P/OC5

Modules with displays and switches in F:P/IOC MUH (-Q1088-) CPEX (-Q930-) CPCL (-Q933-) DCCMS (-Q5619-S100)

Tab. 3.72

Modules with displays and switches in F:P/IOC

302

A30828-X1160-M-2-7620

C281 C287 C295 C303 C311 C319

MUH CPEX CPAC CPCC CPCIA

Maintenance Node

Construction

3.2.14.2

F:P/IOC (backplane)
343 335 319 IOP IOP IOP 257 125 109
117

PI PI

PI PI MI PI MI PI BAP BAP PI PI

P3 P4 P5

PI

PI PI

MI

IOP IOP IOP

MI

P1 P2

PI

PI

D
P3 P4

PI

PI

PI

PI PI

IOC0/1/2/3 or CAP3/5

BAP0/1 or CAP0/1/2/4

3.2.14.3

F:P/IOC (cabling)
BAP BAP IOP IOP IOP IOP IOP IOP MI MI PI PI PI PI PI MI IOP BAP D179P3 D179P4 C257P1 -> 03C319P3 C257P2 -> 03C319P4 C257P3 -> 03D225P2 D257P1 -> 03D319P2 D257P2 -> 03D319P3 D257P3 -> 03C319P4 C319P4 D319P1 09C335P1 - 09C335P3 09D335P2 - 09D335P4 09C343P1 - 09C343P4 09D343P1 - 09D343P4 Processor interface unit Memory interface Input/output processor Base processor Recovery lines to partner BAP 10D179P4 Recovery lines to partner BAP 10D179P3 BIOC (R:CP113A) to F:IOP (R:DEVD) BIOC (R:CP113A) to F:IOP (R:DEVD) BIOC (R:CP113A) to F:IOP (R:DEVD) BIOC (R:CP113A) to F:IOP (R:DEVD) BIOC (R:CP113A) to F:IOP (R:DEVD) BIOC (R:CP113A) to F:IOP (R:DEVD) BCMY0 clock (06C291P2) BCMY1 clock (07C291P2) BCMY0 addresses and data (BUS0) BCMY1 addresses and data (BUS1) Processor alarms/control signals (BUS0) Processor alarms/control signals (BUS1)

Tab. 3.73

Cabling F:P/IOC

A30828-X1160-M-2-7620

PI

PI

PI

PI

PI

PI

PI PI

P2

PI PI

PI

P1

109

303

Construction

Maintenance Node

3.2.15

Profibus
PBSL PBSL PBSL PBSL PBSL PBSL

1-6 PBSL32I (U2607)= Profibus for up to 32 external alarm inputs

304

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.3

F:DLU
3.3.1 3.3.1.1 3.3.1.2 3.3.1.3 3.3.2 3.3.2.1 3.3.2.2 3.3.2.3 3.3.3 3.3.3.1 3.3.3.2 3.3.3.3 3.3.4 3.3.4.1 3.3.4.2 3.3.4.3 3.3.5 3.3.5.1 3.3.5.2 3.3.5.3 3.3.6 3.3.6.1 3.3.6.2 3.3.6.3 3.3.7 3.3.7.1 3.3.7.2 3.3.7.3 3.3.8 3.3.8.1 3.3.8.2 3.3.8.3 3.3.9 3.3.9.1 3.3.9.2 3.3.9.3 3.3.10 3.3.10.1 3.3.10.2 3.3.10.3 3.3.11 3.3.11.1 3.3.11.2 3.3.11.3 3.3.12 F:DLU(A) F:DLU(A) (module side) F:DLU(A) (backplane) F:DLU(A) (cabling) F:DLU(B) F:DLU(B) (module side) F:DLU(B) (backplane) F:DLU(B) (cabling) F:DLU(C) F:DLU(C) (module side) F:DLU(C) (backplane) F:DLU(C) (cabling) F:DLU(D) F:DLU(D) (module side) F:DLU(D) (backplane) F:DLU(D) (cabling) F:DLU(E) F:DLU(E) (module side) F:DLU(E) (backplane) F:DLU(E) (cabling) F:DLU(F) F:DLU(F) (module side) F:DLU(F) (backplane) F:DLU(F) (cabling) F:DLU(G) F:DLU(G) (module side) F:DLU(G) (backplane) F:DLU(G) (cabling) F:DLU(I) F:DLU(I) (module side) F:DLU(I) (backplane) F:DLU(I) (cabling) F:DLU(J) F:DLU(J) (module side) F:DLU(J) (backplane) F:DLU(J) (cabling) F:DLU(L) F:DLU(L) (module side) F:DLU(L) (backplane) F:DLU(L) (cabling) F:DLUG(A) F:DLUG(A) (module side) F:DLUG(A) (backplane) F:DLUG(A) (cabling) F:DLUG(B)

A30828-X1160-M-2-7620

305

Construction

Maintenance Node

3.3.12.1 3.3.12.2 3.3.12.3 3.3.13 3.3.13.1 3.3.13.2 3.3.13.3 3.3.14 3.3.14.1 3.3.14.2 3.3.14.3 3.3.15 3.3.15.1 3.3.15.2 3.3.15.3 3.3.16 3.3.16.1 3.3.16.2 3.3.16.3 3.3.17 3.3.17.1 3.3.17.2 3.3.17.3 3.3.18 3.3.18.1 3.3.18.2 3.3.18.3 3.3.19 3.3.19.1 3.3.19.2 3.3.19.3 3.3.20 3.3.20.1 3.3.20.2 3.3.20.3 3.3.21 3.3.21.1 3.3.21.2

F:DLUG(B) (module side) F:DLUG(B) (backplane) F:DLUG(B) (cabling) F:DLUG(C) F:DLUG(C) (module side) F:DLUG(C) (backplane) F:DLUG(C) (cabling) F:DLUV(A) F:DLUV(A) (module side) F:DLUV(A) (backplane) F:DLUV(A) (cabling) F:DLU(A) for DSU F:DLU(A) for DSU (module side) F:DLU(A) for DSU (backplane) F:DLU(A) for DSU (cabling) F:DLU(B) for DSU F:DLU(B) for DSU (module side) F:DLU(B) for DSU (backplane) F:DLU(B) for DSU (cabling) F:DLU(C) for DSU F:DLU(C) for DSU (module side) F:DLU(C) for DSU (backplane) F:DLU(C) for DSU (cabling) F:DLU(E) for DSU F:DLU(E) for DSU (module side) F:DLU(E) for DSU (backplane) F:DLU(E) (cabling) for DSU F:DLU(F) for DSU F:DLU(F) for DSU (backplane) F:DLU(F) for DSU (backplane) F:DLU(F) for DSU (cabling) F:DLU(E) for DSU F:DLU(G) for DSU (module side) F:DLU(G) for DSU (backplane) F:DLU(G) for DSU (cabling) F:MODEM(D) F:MODEM(D) for DSU Type GPT F:MODEM(D) for DSU Type NEUHAUS

306

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.3.1 3.3.1.1

F:DLU(A) F:DLU(A) (module side)


10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9

A
Shelf 0 LMEM / LCMM
*1 *1

FTEM / FMTU

SLM / LVMM

SLM / SASC

SLM / SASC

SLM / EMSP

DCC 0-0

SLM

A028

A010

A052

A077

DLUC0

SLM

SLM

SLM

SLM

A095

A101

A058

A083

A107

A016

A022

A034

A040

A046

A001

A065

A071

*1

Module SASC (mounting location 0-2) occupies 2 MOLOCs.

10

11

A089

12

13

14

C
*2

15

A113

A119 C119 DCC 1-1 Shelf 1

SLM / COTU / PHub0

D
DCC 1-0 SLM SLM SLM SLM

C001

C010

C016

C022

C028

C034

C040

C046

C052

C058

C065

C071

C077

C083

C089

C095

C101

C107

Modules PHub0 (mounting location 4) also occupy the adjacent mounting location (mounting location 5).

*2

Modules with displays and switches in F:DLU(A) BDB (-Q808-), (-Q1002-) DIU:LDID (-Q1109-) DLUC (-Q968-) FTEM (-Q957-) BDCG (-Q809-) DCCCR (-Q5619-) EMSP (-Q828-) LMEM (-Q811-) DIUDA (-Q806-) DCCDC (-Q5862-C) EMSP (-Q1094-) LVMM (-Q812-) DIUDC (-Q1007-) DCCDD (-Q5862-D) FMTU (-Q1112-) MTAM (-Q1066-)

Tab. 3.74

Modules with displays and switches in DLU(A)

C113

SLM / LTBAM

SLM / MTAM

SLM / EMSP

DIU1 / LDI1

RGMG1

BDCG1

LTBAM

DLUC1

BDB1

SLM

SLM

SLM

SLM

DCC 0-1

SLM / ALEX

DIU0 / LDI0

RGMG0

BDCG0

BDB0

SLM

A30828-X1160-M-2-7620

307

Construction

Maintenance Node

Modules with displays and switches in F:DLU(A) RGMG (-Q895-) SASC (-Q1133-), (-Q22-) SLMI:PHA (-Q142-) RGMG (-Q813-) SLMA (-Q1011-) SLMD (-Q838-), (-Q965-), (-Q1101-), (-Q1103-), (-Q1192-) SLMI:AMA (-Q225-) SLMI:FMA (-Q164-)

Tab. 3.74

Modules with displays and switches in DLU(A)

3.3.1.2

F:DLU(A) (backplane)
A027 HVT6 L3 L2 L1 L0 HVT7A015 A015 A083 A080 A074 A071 A068 A119 A089 A101 A061 A113 A052 A039 A001 BST2 BST5 Shelf 1 DIU-INTERN DIU-INTERN DLUC-INTERN DLUC-INTERN or or C001 Shelf 0 C015 HVT14 C015

EXT1 NC2 1 INT2

A
HVT1 HVT2 HVT3 BST1 LTE1 INT1

HVT4

EXT2

HVT5

B098

B086 B086 B080

B074

B
TRACE LTE2 INT4 EXT3 INT3 INT5

C119 C116 C113 C110 C107 C104 C101 C098

C083 C080

C089

C074 C071 C068

C061

B061

HVT10

HVT11

HVT12

D116

D098

D
TRACE LTE4 INT12 INT11 EXT8 INT13 EXT7

3.3.1.3

F:DLU(A) (cabling)
INT1 A080 - internal cable to F:DLU(B) to F:DLU(C) INT2 A068 - internal cable to F:DLU(B) to F:DLU(C) A074 A074 A061 A061

Tab. 3.75

Cabling F:DLU(A)

D086 D083 D080

D074

D061

308

A30828-X1160-M-2-7620

HVT13

EXT5 NC2 2 INT10

C
BST3 EXT4 HVT8 INT6 BST4 INT7 HVT9 INT8

EXT6

LTE3 INT9

C052

C039

C027

L4

Maintenance Node

Construction

INT3

B098 - internal cable

to F:DLU(B) to F:DLU(C)

D098 B104 B074 B074 D061 B061 A092 A092 A092 A092 C074 A068 C061 A055 B098 B098 D074 D074 B061 B055

TEST-CABLE

or

TEST-CABLE/ MP-CABLE CDBUS-CABLE or

INT4

B080 - internal cable

to F:DLU(B) to F:DLU(C)

INT5

B061 - internal cable

to F:DLU(B) to F:DLU(C)

RING-CABLE RING-CABLE TEST-CABLE TEST-CABLE TEST-CABLE TEST-CABLE DIU-INTERN DIU-INTERN DLUC-INTERN DLUC-INTERN TEST-CABLE TEST-CABLE CDBUS-CABLE

or

INT6

C110 - internal cable

to F:DLU(B) to F:DLU(C)

or

INT7 INT8 INT9

C104 - internal cable C098 - internal cable C080 - internal cable

to F:DLU(B) to F:DLU(B) to F:DLU(B) to F:DLU(C)

or

INT10

C068 - internal cable

to F:DLU(B) to F:DLU(C)

or

INT11

D098 - internal cable

to F:DLU(B) to F:DLU(C)

or

INT12

D080 - internal cable

to F:DLU(B) to F:DLU(C)

or

INT13

D061 - internal cable

to F:DLU(B) to F:DLU(C)

RING-CABLE RING-CABLE

or

EXT1 EXT2 EXT3 EXT4 EXT5 EXT6 EXT7 EXT8

A074 - external cable A061 - external cable B074 - external cable C116 - external cable C074 - external cable C061 - external cable D116 - external cable D074 - external cable

to F:DLU(B) to F:DLU(B) to F:DLU(B) to F:DLU(B) to F:DLU(B) to F:DLU(B) to F:DLU(B) to F:DLU(B)

A074 A061 B074 C113 C074 C061 D110 D074

DIU-INTERN DLUC-INTERN CDBUS-CABLE MTA-CABLE DIU-INTERN DLUC-INTERN MTA-CABLE CDBUS-CABLE

HVTxx - cable to MDF BST1 - BST5: Jumper LTE1 - LTE4: For local DLU: cable for LTG. For remote: cable to MDF L0 - L5: Cable connectors TRACE: Trace-CABLE NC2: Module NC2 plugged in here

Tab. 3.75

Cabling F:DLU(A)

A30828-X1160-M-2-7620

309

Construction

Maintenance Node

3.3.2 3.3.2.1

F:DLU(B) F:DLU(B) (module side)


10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9

A
Shelf 2 or 4 or 6 Shelf 3 or 5 or 7

DCC 2-0 or 4-0 or 6-0

SLM

A028

SLM

A010

A052

A077

A101

A095

A107

A016

A022

A034

A040

A046

A058

A001

A065

A071

A083

*1

Modules PHub0 and PHub1 (mounting locations 4 and 10) also occupy the adjacent mounting locations (mounting locations 5 and 11). 10 11 12 13 14 15 C113 C119 DCC 3-1 or 5-1 or 7-1 SLM 0 1 2 3 4 5 6 7 8 9

DCC 3-0 or 5-0 or 7-0

*1

SLM / PHub0

SLM / PHub1

*1

SLM*1

BDE0

SLM

SLM*1

BDE1

A089

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

C028

C052

C010

C077

SLM

C095

C101

C058

C016

C022

C034

C040

C046

C001

C065

C071

C083

*1

Modules PHub0 and PHub1 (mounting locations 4 and 10) also occupy the adjacent mounting locations (mounting locations 5 and 11).

Modules with displays and switches in F:DLU(B) BDE (-Q807-), (-Q1003-) SLMI:AMA (-Q225-) DCCCR (-Q5619-) SLMX (-Q1338-) DCCDC (-Q5862-C) SLMI:FMA (-Q164-) DCCDD (-Q5862-D) SLMI:PHA (-Q142-) SLMA (-Q1011-)

SLMD (-Q838-), (-Q965-), (-Q1101-), (-Q1103-), (-Q1192-)

Tab. 3.76

Modules with displays and switches in DLU(B)

C089

310

A30828-X1160-M-2-7620

C107

SLM

A113

A119

DCC 2-1 or 4-1 or 6-1

SLM / PHub0 *1

SLM / PHub1

SLM*1

*1

SLM*1

BDE0

BDE1

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

Maintenance Node

Construction

3.3.2.2

F:DLU(B) (backplane)
A077 A074 A068 A016 A119 A092 A089 A061 A055 A052 A101 A113 A040 A028 A001 C001 Shelf 3 or 5 or 7 BST4 Shelf 2 or 4 or 6 BST2

A
HVT1 HVT2 INT1 HVT3 INT5 HVT5 HVT6 HVT7 HVT4 INT2 INT3 HVT8 HVT16 or or or C016 BST1 INT4 C061 INT9 B061

B098

B074 INT7 C077 C074

INT6

C119

C101

C113

C068

INT8

B068

C055 C052

C089

C040

HVT10

HVT11

HVT12 INT10

INT13 HVT13

HVT14

D098

D074

D
INT14 INT15 INT16 INT17

3.3.2.3

F:DLU(B) (cabling)
INT1 A092 - internal cable to F:DLU(A) to F:DLU(A) to F:DLU(A) INT2 A074 - internal cable to F:DLU(A) to F:DLU(A) to F:DLU(B) INT3 INT4 A068 - internal cable A061 - internal cable to F:DLU(B) to F:DLU(A) to F:DLU(A) to F:DLU(B) INT5 A055 - internal cable to F:DLU(B) C098 C104 C110 A074 A080 A068 A074 A061 A068 A055 A061 TEST-CABLE TEST-CABLE TEST-CABLE DIU-INTERN DIU-INTERN DIU-INTERN DIU-INTERN DLUC-INTERN DLUC-INTERN DLUC-INTERN DLUC-INTERN

Tab. 3.77

Cabling F:DLU(B)

D068

D061

HVT15

INT11

HVT9

INT12

C
BST3

C028

A30828-X1160-M-2-7620

311

Construction

Maintenance Node

INT6

B098 - internal cable

to F:DLU(A) to F:DLU(B)

D098 D098 B074 B080 B068 B074 B074 B061 D061 D061 C074 C080 C068 C074 A068 C061 C068 C055 C061 D098 B098 B098 D074 D080 D068 D074 D074 B061 B061 B055

TEST-CABLE TEST-CABLE

or

INT7

B074 - internal cable

to F:DLU(A) to F:DLU(A) to F:DLU(B)

or CDBUS-CABLE

INT8

B068 - internal cable

to F:DLU(B) to F:DLU(C)

CDBUS-CABLE

or

INT9

B061 - internal cable

to F:DLU(A) to F:DLU(A) to F:DLU(B)

RING-CABLE RING-CABLE RING-CABLE DIU-INTERN DIU-INTERN DIU-INTERN DIU-INTERN DIU-INTERN DLUC-INTERN DLUC-INTERN DLUC-INTERN DLUC-INTERN TEST-CABLE TEST-CABLE MP-CABLE

or

INT10

C074 - internal cable

to F:DLU(A) to F:DLU(A) to F:DLU(B)

or

INT11

C068 - internal cable

to F:DLU(B) to F:DLU(C)

or

INT12

C061 - internal cable

to F:DLU(A) to F:DLU(A) to F:DLU(B)

or

INT13 INT14

C055 - internal cable D098 - internal cable

to F:DLU(B) to F:DLU(A) to F:DLU(B) to F:DLU(C)

or

INT15

D074 - internal cable

to F:DLU(A) to F:DLU(A) to F:DLU(B)

or CDBUS-CABLE

INT16

D068 - internal cable

to F:DLU(B) to F:DLU(C)

CDBUS-CABLE

or

INT17

D061 - internal cable

to F:DLU(A) to F:DLU(B) to F:DLU(C)

RING-CABLE RING-CABLE RING-CABLE

or

HVTxx - cable to MDF BST1 - BST4: Jumper

Tab. 3.77

Cabling F:DLU(B)

312

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.3.3 3.3.3.1

F:DLU(C) F:DLU(C) (module side)


10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9

A
Shelf 2 or 4 or 6 Shelf 2 or 4 or 6

DCC 2-0 or 4-0 or 6-0

SLM / PHub0

SLM*1

SLM

SLM

SLM

SLM

SLM

SLM

A028

A010

A052

A077

SLM

A095

A101

A083

A107

A016

A046

A058

A022

A034

A001

A040

A065

A071

*1

Modules PHub0 and PHub1 (mounting locations 4 and 10) also occupy the adjacent mounting locations (mounting locations 5 and 11).

Modules with displays and switches in F:DLU(C) BDE (-Q807-), (-Q1003-) SLMI:AMA (-Q225-) DCCCR (-Q5619-) SLMX (-Q1338-) DCCDC (-Q5862-C) SLMI:FMA (-Q164-) DCCDD (-Q5862-D) SLMI:PHA (-Q142-) SLMA (-Q1011-)

SLMD (-Q838-), (-Q965-), (-Q1101-), (-Q1103-), (-Q1192-)

Tab. 3.78

Modules with displays and switches in DLU(C)

3.3.3.2

F:DLU(C) (backplane)
A119 A061 A101 A113 A092 A089 A077 A074 A068 A055 A052 A040 A028 A016 A001 BST2

A
HVT1 HVT2 HVT6 INT1 HVT3 HVT4 INT2 INT5 HVT5 HVT7 HVT8 BST1 INT3 INT4

B104

B098

B074

B061

B
INT6 INT7 INT8

B068

INT10

INT9

INT11

B055

A089

A113

A119

DCC 2-1 or 4-1 or 6-1

SLM / PHub1 *1

*1

SLM*1

BDE0

BDE1

SLM

SLM

SLM

SLM

SLM

A30828-X1160-M-2-7620

313

Construction

Maintenance Node

3.3.3.3

F:DLU(C) (cabling)
INT1 A092 - internal cable to F:DLU(A) to F:DLU(A) to F:DLU(A) INT2 A074 - internal cable to F:DLU(A) to F:DLU(B) INT3 A068 - internal cable to F:DLU(A) to F:DLU(B) INT4 A061 - internal cable to F:DLU(A) to F:DLU(B) INT5 A055 - internal cable to F:DLU(A) to F:DLU(B) INT6 INT7 B104 - internal cable B098 - internal cable to F:DLU(A) to F:DLU(A) to F:DLU(B) INT8 B074 -internal cable to F:DLU(A) to F:DLU(B) INT9 B068 - internal cable to F:DLU(A) to F:DLU(B) INT10 INT11 B061 - internal cable B055 - internal cable to F:DLU(A) to F:DLU(A) to F:DLU(B) C098 C104 C110 A080 A068 C080 C068 A068 A055 C068 C055 B098 D098 D098 B080 B068 D080 D068 B061 D061 D061 RING-CABLE RING-CABLE RING-CABLE or or TEST-CABLE TEST-CABLE TEST-CABLE DIU-INTERN DIU-INTERN DIU-INTERN DIU-INTERN DLUC-INTERN DLUC-INTERN DLUC-INTERN DLUC-INTERN TEST-CABLE/MP-CABLE TEST-CABLE TEST-CABLE or or or or or or or

HVTxx - cable to MDF BST1 - BST2: Jumper

Tab. 3.79

Cabling F:DLU(C)

314

A30828-X1160-M-2-7620

Maintenance Node

3.3.4

3.3.4.1

A30828-X1160-M-2-7620 B
DCC 1-0 *2 A001 A010 A015 A021 A027 A033 A039 A045 A051 A057 A064 A068 A074 A080 A086 11 12 13 14 15 A092 A098 A104 A110 A116 A121 Shelf 1 DLUC0 DIU0 / LDI0 GCG0 BD0 GCG1 DIU0 / LDI1 DLUC1 SLM / ALEX SLM / MTAM EMSP/ LTBAM SLM / LTBAM SLM / EMSP RGB1 DCC 0-2 Shelf 0 11 12 13 14 15 8 7 FMTU LCMM SLM / SASC
*1

D A C
*1

C001 DCC 1-1 *2 RGB0 SLM / EMSP SLM / SASC


*1

DCC 0-0

F:DLU(D)

C008 SLM SLM 1 2 3


*1

C015

0 1 2 3 4

C021 SLM SLM SLM / PHub0 SLM*1 5 6 7 SLM SLM / MGB BD1 SLM SLM 9 10 SLM / PHub1 *1 SLM*1 SLM SLM SLM SLM DCC 1-2 *2 DCC 1-3 *2 8 4

C027

C033

F:DLU(D) (module side)

C039

C045

C051

C057

C064

C068

Module SASC (mounting location 0-1) occupies 2 MOLOCs.

C074

C080

C086

C092

C098

C104

C110

C116

*1 Modules PHub0 and PHub1 (mounting locations 4 and 10) also occupy the adjacent mounting locations (mounting locations 5 and 11).

*2 Both DCC positions 1-0 and 1-1 or 1-2 and 1-3 can be replaced by a DCC, depending on operation.

Construction

C123

315

316

Construction

3.3.4.2

Tab. 3.80

MGB (-Q1323-)

EMSP (-Q828-)

DIUDA (-Q806-)

SLMA (-Q1011-)

SLMI:AMA (-Q225-)

DCCDD (-Q5862-D)

F:DLU(D) (backplane)

D A
BSTS3 INT2 MTA3 MTA4 HVT24 HVT2 HVT31 PROM INT3 PDC11 TRACE1 EXT3 PDC10 EXT1 NC2 EXT2 NC2 PDC00 TEST1 HVT4 TEST2 HVT5 HVT6 HVT7 INT5 BSTS4 Shelf 1 C001 Shelf 0 B010 BSTS2 A001 B077 B074 B071 B068 A074 A071 A068 A060 A057 A051 A042 A033 A030 A027 A021 A015 B083 A086 A092 B095 B101 B107 A116 HVT1 A107 MTA1 HVT/MTA2 A104 A101 INT1 BSTTST A098 B116 HVT8 BSTIWE1 HVT9 BSTSLC1 HVT10 BSTIWE2 HVT11 HVT12 BSTIWE3 HVT13 BSTSLC2 HVT14 BSTIWE4 HVT15 EXT4 TRACE0 PDC01 INT4 PROM B042 HVT16 BSTIWE5 HVT17 BSTSLC3 HVT18 BSTIWE6 HVT19 B057 B054 B051 B048 HVT20 BSTIWE7 HVT21 BSTSLC4 HVT22 BSTIWE8 HVT23 C033 C030 C027 C024 C021 C018 C015 C057 C054 C051 C048 C045 C042 C039 C086 C083 C080 C077 C074 C071 C068 C110 C107 C104 C101 C098 C095 C092

C
BSTS1 C116 A121 SLMI:FMA (-Q164-) SLMI:PHA (-Q142-) SLMX (-Q1338-)

EMSP (-Q1094-) RGB (-Q1324-) FMTU (-Q1112-)

MTAM (-Q1066-)

DIUDC (-Q1007-) DIU:LDID (-Q1109-)

DCCDC (-Q5862-C) DCCDF (-Q5862-F)

Modules with displays and switches in DLU(D)

Modules with displays and switches in F:DLU(D)

SLMD (-Q838-), (-Q965-), (-Q1101-), (-Q1103-), (-Q1192-)

DLUC (-Q968-)

GCG (-Q1322-)

DCCDK (-Q6104-)

SASC (-Q1133-), (-Q22-)

A30828-X1160-M-2-7620

Maintenance Node

Maintenance Node

Construction

3.3.4.3

F:DLU(D) (cabling)
INT1 A101 - internal cable to F:DLU(E) to F:DLU(F) INT2 B116 - internal cable to F:DLU(E) to F:DLU(F) INT3 B077 - internal cable to F:DLU(E) to F:DLU(F) INT4 B048 - internal cable to F:DLU(E) to F:DLU(F) INT5 B010 - internal cable to F:DLU(E) to F:DLU(F) B083 B083 B113 B113 B060 B060 A060 A060 B012 B012 TEST-CABLE TEST-CABLE RING-1 CABLE RING-1 CABLE DIU-INTERN DIU-INTERN DLUC-INTERN DLUC-INTERN RING-0 CABLE RING-0 CABLE or or or or or

EXT1 EXT2 EXT3 EXT4

A071 - external cable A060 - external cable B068 - external cable B057 - external cable

to F:DLU to F:DLU to F:DLU to F:DLU

GCG1-INT GCG0-INT GCG-OUT GCG-OUT

1) 1) 2) 2)

HVT1 - HVT24: cable to MDF MTA1 - MTA4: MTA type A: from A104 to A107 MTA type B: from B107 to HVT PDC10 PDC00 PDC11 PDC01 A074 A051 B074 B051 PCM link from /to LTG (PDC 1-0) PCM link from/to LTG (PDC 0-0) PCM link from/to LTG (PDC 1-1) PCM link from/to LTG (PDC 0-1)

3) 4) 4)

BSTS1 - BSTS5: Jumper BSTTST: Jumper for test bus (if no MTA used) BSTSL C1 - BSTSLC4: Jumper for SLC 96 BSTIWE1 - BSTIWE8: Jumper for IWE TEST: DLU-external test bus (1x to HVT; 1x to next DLU in the same rack) PROM: Module for loading the SLM TRACE: Connector for SDE on 8 PCM links (system 0 or 1) NC2: System clock decoupling module (clock from GCG)

Tab. 3.81

Cabling F:DLU(D)

1) Clock and frame alignment signal from another DLU in the same rack 2) Clock and frame alignment signal to another DLU in the same rack 3) Spare switch connection via MDF 24 4) Rack-changing cables when R:DLUB and R:DLU are used in one exchange

A30828-X1160-M-2-7620

317

Construction

Maintenance Node

3.3.5 3.3.5.1

F:DLU(E) F:DLU(E) (module side)


10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9

SLM / PHub0 *1

DCC 2-0 *2

DCC 2-1 *2

*2

SLM*1

A001

A008

A015

A021

A027

A033

A039

A045

A051

A057

A064

A068

A074

A080

A086

A092

A098

A104

A110

A116

*1

Modules PHub0 and PHub1 (mounting locations 4 and 10) also occupy the adjacent mounting locations (mounting locations 5 and 11).
*2

Both DCC positions 2-0 and 2-1 or 2-2 and 2-3 can be replaced by a DCC, depending on operation.

10

11 12

13

14

15

A123 C123 DCC 3-3 *2 Shelf 3

SLM / PHub0 *1

DCC 3-0 *2

DCC 3-1 *2

SLM*1

C001

C008

C015

C021

C027

C033

C039

C045

C051

C057

C064

C068

C074

C080

C086

C092

C098

C104

C110

*1

Modules PHub0 and PHub1 (mounting locations 4 and 10) also occupy the adjacent mounting locations (mounting locations 5 and 11). *2 Both DCC positions 3-0 and 3-1 or 3-2 and 3-3 can be replaced by a DCC, depending on operation.

318

A30828-X1160-M-2-7620

C116

DCC 3-2

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM*1

SLM

SLM

SLM

SLM

BD3

*2

SLM / PHub1

*1

DCC 2-3 *2

SLM / PHub1

*1

DCC 2-2

SLM*1

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

BD2

Shelf 2

Maintenance Node

3.3.5.3

3.3.5.2

A30828-X1160-M-2-7620 B D A C Tab. 3.82


SLMA (-Q1011-) BSTS3 INT2 C110 HVT17 BSTIWE9 C107 C104 HVT18 BSTSLC5 C101 C098 HVT19 BSTIWE10 C095 C092 HVT20 HVT1 BSTIWE1 HVT2 BSTSLC1 HVT3 BSTIWE2 HVT4 INT3 B083 HVT5 BSTIWE3 HVT6 BSTSLC2 HVT7 BSTIWE4 HVT8 INT1 HVT9 BSTIWE5 HVT10 BSTSLC3 HVT11 BSTIWE6 HVT12 INT4 B060 HVT13 BSTIWE7 HVT14 BSTSLC4 HVT15 BSTIWE8 HVT16 INT5 BSTS4 Shelf 3 C001 Shelf 2 B012 A086 A083 A080 A077 A074 A071 A068 A060 A057 A054 A051 A048 A045 A042 A039 A033 A030 A027 A024 A021 A018 A015 C086 HVT21 BSTIWE11 C083 C080 HVT22 BSTSLC6 C077 C074 HVT23 BSTIWE12 C071 C068 HVT24 C057 HVT25 BSTIWE13 C054 C051 HVT26 BSTSLC7 C048 C045 HVT27 BSTIWE14 C042 C039 HVT28 C033 HVT29 BSTIWE15 C030 C027 HVT30 BSTSLC8 C024 C021 HVT31 BSTIWE16 C018 C015 HVT32 A110 A107 A104 A101 A098 A095 A092 B113 SLMI:AMA (-Q225-) DCCDD (-Q5862-D)

INT2

INT1

Tab. 3.83
C116 BSTS1 A116

F:DLU(E) (cabling)

F:DLU(E) (backplane)

B113 - internal cable

A060 - internal cable

Cabling F:DLU(E) with F:DLU(D)

Cabling F:DLU(E)
BSTS2 A001

SLMI:FMA (-Q164-)

DCCDC (-Q5862-C)

Modules with displays and switches in DLU(E)

Modules with displays and switches in F:DLU(E)

SLMD (-Q838-), (-Q965-), (-Q1101-), (-Q1103-), (-Q1192-)

to F:DLU(F)

to F:DLU(D)

to F:DLU(D)

DCCDF (-Q5862-F)

SLMI:PHA (-Q142-)

B113

B116

B048

INT-CABLE

RING-1 CABLE

RING-1 CABLE

SLMX (-Q1338-)

DCCDK (-Q6104-)

or

1)

Construction

319

Construction

Maintenance Node

INT3

B083 - internal cable

to F:DLU(D) to F:DLU(F)

A101 B083 B077 B060 B010 B012

TEST-CABLE TEST-CABLE INT-CABLE INT-CABLE RING-0 CABLE RING-0 CABLE

or

INT4

B060 - internal cable

to F:DLU(D) to F:DLU(F)

or 1) or

INT5

B012 - internal cable

to F:DLU(D) to F:DLU(F)

HVT1 - HVT32: cable to MDF BSTS1 - BSTS4: Jumper BSTSL C1 - BSTSLC8: Jumper for SLC 96 BSTIWE1 - BSTIWE16: Jumper for IWE

Tab. 3.83

Cabling F:DLU(E)

1) PCM-, CD-Bus, Control-Net, system 0 or 1 Cabling F:DLU(E) with F:DLU(G)


INT1 INT2 A060 - internal cable B113 - internal cable to F:DLU(G) to F:DLU(G) to F:DLU(F) INT3 B083 - internal cable to F:DLU(G) to F:DLU(F) INT4 B060 - internal cable to F:DLU(G) to F:DLU(F) INT5 B012 - internal cable to F:DLU(G) to F:DLU(F) B060 B124 B113 A100 B083 B069 B060 B010 B012 SYS0-CABLE RING-1 CABLE RING-1 CABLE TEST-CABLE TEST-CABLE SYS1-CABLE INT-CABLE RING-0 CABLE RING-0 CABLE or or or or

HVT1 - HVT32: cable to MDF BSTS1 - BSTS4: Jumper BSTSL C1 - BSTSLC8: Jumper for SLC 96 BSTIWE1 - BSTIWE16: Jumper for IWE

Tab. 3.84

Cabling F:DLU(E)

320

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.3.6 3.3.6.1

F:DLU(F) F:DLU(F) (module side)


10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9

*1

DCC 2-0 *2

DCC 2-1 *2

DCC 2-2 *2

SLM*1

A001

A008

A015

A021

A027

A033

A039

A045

A051

A057

A064

A068

A074

A080

A086

A092

A098

A104

A110

A116

Modules PHub0 and PHub1 (mounting locations 4 and 10) also occupy the adjacent mounting locations (mounting locations 5 and 11). *2 Both DCC positions 2-0 and 2-1 or 2-2 and 2-3 can be replaced by a DCC, depending on operation.

*1

Modules with displays and switches in F:DLU(F) DCCDD (-Q5862-D) SLMA (-Q1011-) SLMI:AMA (-Q225-) DCCDC (-Q5862-C) DCCDF (-Q5862-F) DCCDK (-Q6104-)

SLMD (-Q838-), (-Q965-), (-Q1101-), (-Q1103-), (-Q1192-) SLMI:FMA (-Q164-) SLMI:PHA (-Q142-) SLMX (-Q1338-)

Tab. 3.85

Modules with displays and switches in DLU(F)

3.3.6.2

F:DLU(F) (backplane)
A110 A107 A104 A101 A098 A095 A092 A086 A083 A080 A077 A074 A033 A030 A027 A024 A021 A018 A015 A060 A057 A054 A051 A048 A045 A042 A039 A116 A001 BSTS4 INT5 Shelf 2 B113 B083 B060 B012

HVT1 BSTIWE1 HVT2 BSTSLC1 HVT3 BSTIWE2 HVT4

HVT5 BSTIWE3 HVT6 BSTSLC2 HVT7

INT1 HVT8 BSTIWE4 HVT9 BSTSLC3 HVT10 BSTIWE5 HVT11

BSTS1

INT2

INT3

INT4

HVT12 BSTIWE6 HVT13 BSTSLC4 HVT14 BSTIWE7 HVT15

A123

DCC 2-3 *2

SLM / PHub0

SLM / PHub1

*1

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM*1

SLM

SLM

SLM

SLM

BD2

BD3

A30828-X1160-M-2-7620

Shelf 2

321

Construction

Maintenance Node

3.3.6.3

F:DLU(F) (cabling)
Cabling F:DLU(F) with F:DLU(D)
INT1 INT2 A060 - internal cable B113 - internal cable to F:DLU(D) to F:DLU(D) to F:DLU(E) INT3 B083 - internal cable to F:DLU(D) to F:DLU(E) INT4 B060 -internal cable to F:DLU(D) to F:DLU(E) INT5 B012 - internal cable to F:DLU(D) to F:DLU(E) B048 B116 B113 A101 B083 B077 B060 B010 B012 INT-CABLE RING-1 CABLE RING-1 CABLE TEST-CABLE TEST-CABLE INT-CABLE INT-CABLE RING-0 CABLE RING-0 CABLE or 1) or or 1) or

HVT1 - HVT15: cable to MDF BSTS1 - BSTS2: Jumper BSTSL C1 - BSTSLC4: Jumper for SLC 96 BSTIWE1 - BSTIWE7: Jumper for IWE

Tab. 3.86

Cabling F:DLU(F)

Cabling F:DLU(F) with F:DLU(G)


INT1 INT2 A060 - internal cable B113 - internal cable to F:DLU(G) to F:DLU(G) to F:DLU(E) INT3 B083 - internal cable to F:DLU(G) to F:DLU(E) INT4 B060 -internal cable to F:DLU(G) to F:DLU(E) INT5 B012 - internal cable to F:DLU(G) to F:DLU(E) B060 B124 B113 A100 B083 B069 B060 B010 B012 SYS0-CABLE RING-1 CABLE RING-1 CABLE TEST-CABLE TEST-CABLE SYS1-CABLE INT-CABLE RING-0 CABLE RING-0 CABLE or or or or

HVT1 - HVT15: cable to MDF BSTS1 - BSTS2: Jumper BSTSL C1 - BSTSLC4: Jumper for SLC 96 BSTIWE1 - BSTIWE7: Jumper for IWE

Tab. 3.87

Cabling F:DLU(F)

322

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.3.7 3.3.7.1

F:DLU(G) F:DLU(G) (module side)


10 11 12 13 14 15 0 1 2 3 4 5 6 9

SLM / LTCD / LTOD

SLM / LTCD / LTOD

LTBAM / EMSP

SLM / LTBAM

LCMM / SLM

SLM / MTAM

SLM / EMSP

DCC 0-0 *1

DCC 0-2 *1

SLM / EMSP

SLM / SASC

SLM / ALEX

RGB0 *1

A001

A010

A015

A021

A027

A033

A039

A045

A051

A057

A066

A073

A079

A085

A091

A097

A103

A109

A115

*1

DCC positions 0-0 or 0-2 can require the mounting location of the adjacent RGB0 or RGB1, depending on the equipment complement. In this case no RGB is created.

10

11 12

13

14

C
SLM / MGB / LTCD / LTOD

15

A124

RGB1 *1

DLUS0

DLUS1

FMTU

SLM

SLM

SLM

SLM / LTCD / LTOD

SLM / LTCD / LTOD

SLM / LTCD / LTOD

SLM / LTCD / LTOD

DCC 1-0 *2

*2

DCC 1-2 *2

C001

C008

C015

C021

C027

C033

C039

C045

C051

C057

C068

C074

C080

C086

C092

C098

C104

C110

C116

*1

Modules PHub0 and PHub1 (mounting locations 4 and 10) also occupy the adjacent mounting locations (mounting locations 5 and 11).

Both DCC positions 1-0 and 1-1 or 1-2 and 1-3 can be replaced by a DCC, depending on operation. For SLM plug-in positions 1-2 and 1-3 or 1-3 and 1-4 or 1-11 and 1-12 or 1-12 and 1-13 a DLUV or OMX16D can be created.
*3

*2

C123

DCC 1-3 *2

SLM*1 / *3

SLM / LTCD / LTOD

SLM*3

SLM / PHub1

DCC 1-1

PHub0

SLM*3

SLM*3

*1

SLM*1

*1

SLM*3

SLM*3

SLM

SLM

Shelf 1

A30828-X1160-M-2-7620

Shelf 0

323

324

Construction

3.3.7.2

Tab. 3.88

RGB (-Q1324-)

EMSP (-Q828-)

LTOD (-Q1496-)

DCCDQ (-Q6125-)

SLMI:FMA (-Q164-)

DCCDD (-Q5862-D)

F:DLU(G) (backplane)

D A
BSTS3 HVT15 MTAB MTAB HVT14/SSW B095 HVT3 HVT4 A080 A077 A073 A069 A066 A086 A092 B101 B106 C110 HVT1 MTA A HVT2/MTAA TEST int BSTST A110 A106 A103 A100 A097

C
RING1 C116 BSTS1 A116 B124

DLUV

MGB (-Q1323-)

EMSP (-Q1094-)

SLMI:PHA (-Q142-)

DCCDC (-Q5862-C)

DLUV C080 HVT20 BSTSLC2 C077 C074 HVT21 HVT22 HVT23 C051 HVT24 BSTSLC3 C048 C045 HVT25 C057 B060 SYS0 PDC0x/BST B057 C068 B069 SYS1 PDC1x/BST B066 HVT5 NC2 HVT6/HDSL DLUTRC1 SDHCLK1 DLUTRC0 A060 SDHCLK0 A057 A054 NC2 HVT7/HDSL A051 ALEXTTL A048 A045 HVT8 TEST ext A042 A039 HVT9 HVT10 TEST ext HVT11 HVT12 HVT13 RING0 BSTS4 Shelf 1 C001 Shelf 0 B010 BSTS2 A001 A033 A030 A027 A021 A015

SASC (-Q1133-), (-Q22-)

SLMD (-Q838-), (-Q965-), (-Q1101-), (-Q1103-), (-Q1192-)

DLUS (-Q1492-), (-Q1493-), (-Q1494-)

HVT16 BSTSLC1 HVT17 OMX HVT18 OMX HVT191

C104 C100 C097 C095 C092 C089 C086

SLMA (-Q1011-)

FMTU (-Q1112-)

MTAM (-Q1066-)

Modules with displays and switches in DLU(G)

DCCDF (-Q5862-F)

Modules with displays and switches in F:DLU(G)

DLUV

DLUV

HVT26 OMX HVT27 OMX HVT28 BSTSLC4 HVT29 HVT30 C015

C039 C036 C033 C030 C027 C024 C021

LTCD (-Q1495-)

DCCDK (-Q6104-)

OMX16D (-Q1497-)

SLMI:AMA (-Q225-)

DLUV (-Q1498-), (-Q126-)

A30828-X1160-M-2-7620

Maintenance Node

Maintenance Node

Construction

3.3.7.3

F:DLU(G) (cabling)
ALEXTTL: Connector for external alarms, connected to ALEX interface at DLUS0 and DLUS1 Jumper plug for connection of PDC-signals to LTCD or LTOD Jumper plug for super pre-mating (+5V via inductor), only for DCCDD, DCCCR, DCCDH Jumper plug for test bus (if no MTA) Jumper plug for SLC 96 Connector for DLU-Tracer (Address- and Data-Bus, Control-signals from CPU) Module as 10 x V5.1 interfaces Cable for HDSL signals to transmission distribution frame Subscriber cable to the MDF DLU external MTA bus (type A or type B) According to rack configuration connected with F:DLU(J)-C313 or F:DLU(I)-C313 or F:DLU(G)-A103 and vice versa (A103 with A106) System clock decoupling module (clock from GCG) Connector for OMX16D-applications Primary digital carrier to/from LTG (PDC0-0, PDC0-1, PDC1-0, PDC1-1) Ring distribution system 0 or 1 RING0: According to rack configuration connected with F:DLU(E)B012 or F:DLU(F)-B0113 RING1: According to rack configuration connected with F:DLU(E)B012 or F:DLU(F)-B0113 Separate clock source for clock generator (SDH-net) Spare-switch circuit via MDF PCM-, CD bus, control-Net system 0 or 1 SYS0: According to rack configuration connected with F:DLU(J)C219, F:DLU(E)-A060, F:DLU(F)-A060 or F:DLU(L)-C219 SYS1: According to rack configuration connected with F:DLU(J)D219, F:DLU(E)-B060, F:DLU(F)-B060 or F:DLU(L)-D219 DLU external testbus (1x to MDF; 1x to next DLU in the same rack) DLU internal test bus (also for MTA) According to rack configuration connected with F:DLU(J)-D277, F:DLU(E)-B083, F:DLU(F)-B083 or F:DLU(L)-D277 Connector for SDE with 8 PCM line system 0 or 1)

BST: BSTS1 - BSTS4:

BSTTST: BSTSLC1 - BSTSLC4: DLUTRC0 / 1:

DLUV: HDSL: HVT1 - HVT30: MTA-A/B:

NC2: OMX: PDC0x or PDC1x:

RING0/1:

SDHCLK0/1: SSW: SYS0/1:

TEST ext: TEST int:

TRACE0/1:

Tab. 3.89

Cabling F:DLU(G)

A30828-X1160-M-2-7620

325

326

Construction

3.3.8.1

3.3.8

F:DLU(I) (module side)

Tab. 3.90
DCC 1-0

F E
*1

D C
DCC 0-0

F:DLU(I)

E101

C101

DCCDQ (-Q6125-) SLMI C129 C141 C153 C165 C177 C189 C201 C213 C231 C247 C259 C271 C283 C295 14 15 C307 C319 C331 PHub0 DLUS0 DLUS1 PHub1 SLMI SLMI/ALEX SLMI SLMI/LTBAM SLMI/LTBAM SLMI DCC 0-2 9 10 11 12 13 14 15 SLMI SLMI SLMI SLMI
*1

E129 SLMI SLMI SLMI SLMI SLMI empty PHub0 PHub1/SLMI empty SLMI SLMI SLMI SLMI SLMI SLMI DCC 1-2 13 11 12 10 9 8 7 6 5 4 3 2 1 SLMI*1

0 SLMI

0 1 2 3 4 5 6

E141

E153

E165

DLUS (-Q1492-), (-Q1493-), (-Q1494-) For SLM plug-in positions 0-1 and 0-2 a SASCE can be created. Shelf 1 Shelf 0

E177

E189

SLMI:MPB (-Q143-)

E201

E213

E231

E247

E259

Modules with displays and switches in DLU(I)

E271

Modules with displays and switches in F:DLU(I)

SLMI:PHB (-Q192-)

E283

E295

E307

E319

A30828-X1160-M-2-7620

E331

Maintenance Node

Maintenance Node

3.3.8.2

A30828-X1160-M-2-7620 F E
BSTS xxx D349 BSTS xxx HVT HVT HVT HVT E271 E265 E259 E283 E295 E307 xxx xxx F295 F283 F271 F259 F247 / E247 F231 HVT/DF DF F213 F204 / E204 F189 F177 F165 F153 F141 F129 xxx DF HVT HVT HVT HVT HVT HVT BSTS BSTS Shelf 1 E195 E189 E177 E165 E153 E141 E129 E115 E101 Shelf 0 E231 E213 xxx xxx xxx DF xxx xxx DF xxx xxx xxx xxx xxx F307 F319 E319 xxx HVT xxx INT4 xxx xxx xxx xxx xxx xxx INT2 DF INT1 DF xxx xxx xxx xxx xxx xxx xxx xxx xxx xxx E331 E345 D319 D313 D307 D301 D295 D289 D283 D271 D259 D247 D237 D231 D219 D213 D201 D189 D177 D171 D165 D153 D147 D141 D129 D119 HVT xxx HVT

F:DLU(I) (backplane)

D
BSTS BSTS HVT HVT HVT HVT HVT xxx DF DF HVT HVT HVT HVT HVT RCU HVT HVT xxx BSTS

INT5/HVT C307 C301 INT3 C295 HVT C283 C277 C271 C259 HVT/DF xxx DF C247 C237 C231 C219 C213 C201 C189 C177 C171 C165 C153 C147 C141 C129 C119 C101

C
C349 C331 C319

Construction

327

Construction

Maintenance Node

3.3.8.3

F:DLU(I) (cabling)
Cabling F:DLU(I) with F:DLU(I), F:DLU(J), F:DLU(L) or F:DLU(G)
INT1 INT2 INT3 INT4 INT5 D219 - internal cable D237 - internal cable C301 - internal cable D301 - internal cable C307 - internal cable to F:DLU(J) to F:DLU(L) to F:DLU(J) to F:DLU(L) to F:DLU(J) to F:DLU(L) to F:DLU(I) to F:DLU(I) to F:DLU(G) C219 C219 D219 D219 D277 D277 C295 C313 A106

HVT: Subscriber cable to MDF DF: cables to separate external distributors SIPAC_S connector (E204 or E247): external connection (e.g. Router) BSTS - BSTS: Jumper RCU: cable for stand-alone service control (connector for CON:SASC or SASCE) xxx: not used

Tab. 3.91

Cabling F:DLU(I)

3.3.9 3.3.9.1

F:DLU(J) F:DLU(J) (module side)


10 11 12 13 14 15 5 6 0 1 2 3 4 7 8 9

D
DCC 2-0 PHub0 empty SLMI SLMI SLMI SLMI SLMI SLMI SLMI SLMI BD2

PHub1 / SLMI

C101

C129

C141

C153

C165

C177

C189

C201

C213

C227

C235

C247

C259

C271

C283

C295

C307

C319

328

A30828-X1160-M-2-7620

C331

DCC 2-2

SLMI

SLMI

SLMI

SLMI

SLMI

Shelf 2

Maintenance Node

3.3.9.2

A30828-X1160-M-2-7620 Tab. 3.92


E101 DCC 3-0

DCCDQ (-Q6125-)

D
BSTS3 BSTS3 D319 HVT HVT HVT HVT HVT DF/HVT HVT HVT C219 C213 C235 C247 C259 C271 E189 E201 E213 E227 E235 E247 E259 E271 E283 E295 E307 E319 C129 C115 C101 BSTS4 Shelf 2 Shelf 3 E331 C283 E177 C295 E165 SLMI SLMI SLMI PHub0 SLMI BD3 SLMI PHub1 SLMI SLMI SLMI SLMI SLMI SLMI DCC 3-2 C307 E153 SLMI C319 D307 D295 E141 SLMI C331 E129 SLMI

C
C345

0 1 2 3 4 5 6 7

xxx

xxx

F:DLU(J) (backplane)

xxx D283 D277 D271 D259 D247 D235 D219 INT1 HVT D213 D201 / C201 D189 D177 D165 D153 D141 D129 BSTS4 HVT HVT HVT C153 C141 HVT C165 HVT C177 DF C189

xxx INT3 xxx

SLMI:MPB (-Q143-)

xxx

xxx

xxx

INT2 xxx DF

8 9 10 11 12 13 14 15

Modules with displays and switches in DLU(J)

SLMI:PHB (-Q192-)

xxx

xxx

Modules with displays and switches in F:DLU(J)

xxx

xxx

xxx

xxx

Construction

329

Construction

Maintenance Node

E345

E331

E319

E307

E295

E283

E271

E259

E247

E235

E213

E201

E189

E177

E165

E153

E141

E129

E115 BSTS4

HVT/DF

BSTS3

BSTS3

BSTS4 Shelf 3

HVT

HVT

HVT

HVT

HVT

HVT

HVT

HVT

HVT

HVT

HVT

HVT

HVT

F319

F307

F295

F283

F271

F259

F247

F235

F213

F201

F189

F177

F165

F153

F141

xxx

xxx

xxx

xxx

xxx

xxx

xxx

xxx

xxx

xxx

xxx

xxx

xxx

xxx

xxx

3.3.9.3

F:DLU(J) (cabling)
cabling F:DLU(J) with F:DLU(I)
INT1 INT2 INT3 C219 - internal cable D219 - internal cable D277 - internal cable to F:DLU(I) to F:DLU(I) to F:DLU(I) D219 D237 C301

HVT: Subscriber cable to MDF DF: cables to separate external distributors SIPAC_S connector (C204): external connection (e.g. Router) BSTS - BSTS: Jumper xxx: not used

Tab. 3.93

Cabling F:DLU(J)

330

A30828-X1160-M-2-7620

xxx

F129

HVT

DF

E101

Maintenance Node

3.3.10.2

3.3.10.1

3.3.10

A30828-X1160-M-2-7620 D C Tab. 3.94


C101 DCC 2-0 C115 C129 SLMI SLMI SLMI SLMI SLMI PHub0_0 PHub0_1 SLMI BD2 BD3 C247 C259 C271 C283 C295 C307 C319 C331 C345 Shelf 2 SLMI / PHub1_0 SLMI / PHub1_1 SLMI SLMI SLMI SLMI SLMI DCC 2-2 8 C235 9 10 11 12 13 14 15 C141 C153 C165 C177 C189 C201 C213 C227 0 1 2 3 4 5 6 7

F:DLU(L)

DCCDQ (-Q6125-)

D
BSTS3 BSTS3 HVT HVT HVT HVT HVT DF/HVT HVT HVT INT1 HVT C219 C213 C235 C247 C259 C271 C283 C295 C307 C319 C331

C
C345

xxx

D319

xxx

D307

F:DLU(L) (backplane)

F:DLU(L) (module side)

xxx

D295

xxx INT3 xxx

D283 D277 D271

SLMI:MPB (-Q143-)

xxx

D259

xxx

D247

xxx

D235

INT2 xxx DF DF ,HVT HVT HVT HVT HVT BSTS4 BSTS4 C101 C115 C129 C141 C153 C165 C177 C189

D219 D213

D201 / C201

SLMI:PHA (-Q142-)

xxx

D189

Modules with displays and switches in F:DLU(L)

xxx

D177

Modules with displays and switches in F:DLU(L)

xxx

D165

xxx

D153

xxx

D141

xxx

D129

Construction

Shelf 2

331

Construction

Maintenance Node

3.3.10.3

F:DLU(L) (cabling)
cabling F:DLU(L) with F:DLU(I) or F:DLU(G)
INT1 INT2 INT3 C219 - internal cable D219 - internal cable D277 - internal cable to F:DLU(I) to F:DLU(G) to F:DLU(I) to F:DLU(G) to F:DLU(I) to F:DLU(G) D219 B060 D237 B069 C301 A100

HVT: Subscriber cable to MDF DF: cables to separate external distributors SIPAC_S connector (C204): external connection (e.g. Router) BSTS - BSTS: Jumper xxx: not used

Tab. 3.95

Cabling F:DLU(L)

3.3.11 3.3.11.1

F:DLUG(A) F:DLUG(A) (module side)


10 11 12 13 14 15 C345 DCC
*1/SLM*2

SLM /LTBAM

SLM*2/LTBAM

DCC *1/SLM*2

SLM*2/PHub0

Pool-DCC

SLM*2/PHub1

DLUC0

SLM*2

*2

*2

SLM*2

SLM*2

SLM*2

SLM*2

SLM*2

SLM*2

BDG0

SLM

C101

C115

C129

C143

C157

C171

C185

C199

C213

C223

C247

C261

C275

C289

C303

C317

*1: The DCC may occupy the adjacent mounting location, depending on the variant. *2: Instead of module SLM a module of type LTCD, ALEX or SASCG can also be inserted.

332

A30828-X1160-M-2-7620

C331

SLM

*2

Shelf 0

Maintenance Node

3.3.11.2

A30828-X1160-M-2-7620 C
E101 E115 E129 E143 E157 E171 E185 E199 E213 SLM*2 SLM*2/PHub_x SLM*2/PHub0 DLUC1 BDG1 SLM*2/DLUV SLM*2/DLUV SLM*2 DCC *1/SLM*2

D F
HVT HVT HVT HVT HVT HVT C275 C289 C303 C317 C331 C345 DCCDU (-Q6131-) HVT/DF NC2_0 HVT PHub1/0 Gr.1 Pow DR CD223 C229 C223 C261 C254 C247 C238 E223 E247 E261 E275 E289 E303 E317 E331 E345 Pool-DCC SLM*2/PHub1 SLM*2/PHub_y SLM*2 SLM*2/DLUV SLM*2/DLUV SLM*2 SLM*2 DCC *1/SLM*2 Shelf 1 C213 C206 C199 C192 C185 SASCG (-Q111-) DCCDW (-Q6133-)

E
0 1 2 3 4 5 6

Tab. 3.96

HVT

D345

DCCDR (-Q6129-)

HVT

D331

HVT

D317

HVT

D303

DLUC (-Q112-, -Q113-, Q114-)

HVT

D289

F:DLUG(A) (backplane)

HVT

D275

HVT

D261

HVT D247 PHub1/0 Gr.2

Pow DR CD247

Pool DCC

8 9 10 11 12 13 14 15

BDG0 D206 XCC/SDH XCC/SDH PDC 01 PDC 00 SYS 03 SYS 0 SYS 01 SYS 0 HVT D185 HVT HVT/DF TSTintnoMTA HVT TSTint w.MTA HVT/MTAA in MTAA out HVT TST ext HVT HVT Shelf 0 C101 C171 C164 C157 C150 C143 C136 C129 C122 C115

Modules with displays and switches in DLUG(A)

Modules with displays and switches in F:DLUG(A)

HVT D171 DLUC Alex D164 HVT/SSW D157

*1: The DCC may occupy the adjacent mounting location, depending on the variant. *2: Instead of module SLM a module of type LTCD can also be inserted.

HVT MTAB HVT TST dis HVT

D143 D136 D129 D122 D115

LTCD (-Q124-)

SLMI:PHB (-Q192-)

HVT

D101

Construction

333

Construction

Maintenance Node

E345

E331

E317

E303 E296 E289 E282 E275

E261 E254 E247 E238

E229

E223

E213 E206 E199 E192 E185

E171

E157

E143 E136 E129 E122 E115 HVT DLUV HVT DLUV HVT

HVT NC2_1 HVT/DF PHub_x

E
HVT DLUV HVT DLUV HVT HVT HVT HVT

BDG1 F206 XCC/SDH XCC/SDH PDC 11 PDC 10 SYS 13 SYS 1 SYS 11 SYS 1 HVT HVT/DF F185

HVT

HVT

HVT HVT F101 Shelf 1

F345

F331

F317

F303 F296 F289 F282 F275

F261

F247

F171

F157

Pool DCC

Pow DR EF223

HVT PHub_y

HVT DLUV HVT DLUV HVT

3.3.11.3

F:DLUG(A) (cabling)
BDGx: DF: DLUC Alex: DLUV: HVT MTAA in MTAA out MTAB NC2_0 or 2_1: PDC0x or PDC1x: Connector for the bus distributor module Lines to separate external distributors Connector for DLUC-internal alarm module ALEX Connector interface of module DLUV (10 x V5.1 interfaces) Connector for subscriber lines to the main distribution frame Connector on the back of module TBA for incoming DLU test bus Connector on the back of module TBA for outgoing DLU test bus Connector for MTAB test access (access to two DLU-internal test branches) System clock extraction module (clock from the GCG of the DLUC) PDC link to/from LTG DLUC0: PDC0-0-0, PDC0-0-1, PDC0-0-2, PDC0-0-3, PDC0-0-4, PDC0-1-0, PDC0-1-0, PDC0-1-2, PDC0-1-3, PDC0-1-4) DLUC1: PDC1-0-0, PDC1-0-1, PDC1-0-2, PDC1-0-3, PDC1-0-4, PDC1-1-0, PDC1-1-0, PDC1-1-2, PDC1-1-3, PDC1-1-4) Connector for the Internet modules SLMI:PHx for connection to the backbone or in the case of cascading to the associated PHub 1/0 Gr.1 or Gr.2 Connector for the Internet modules SLMI:PHx for connection to the backbone or in the case of cascading to the associated PHub_x or PHub_y Connector for Pool DCC. The Pool DCC feeds the modules of type SLMA32 in the entire DLU with additional supply voltages (e.g. ringing voltage) Connector for connecting SDH transmission equipment Spare switch connection Connector for PCM, CD bus, control net, system 0 or 1 Connector for external test equipment Discharge connector for testing SLMD with TEST-SLMA32 Connector for DLU-internal test bus (also for MTA) Connector for test with MTA (jumper --> no MTA)

PHub_x or PHub_y PHub 1/0 Gr.1 or Gr2 Pool DCC and Pow DR SDH: SSW: SYS 0x SYS 0 or SYS 1x SYS 1: TST ext: TST dis: TST int: TST int. w. MTA:

Tab. 3.97

cabling F:DLUG(A) - connector designations

334

A30828-X1160-M-2-7620

HVT DLUV HVT DLUV HVT

HVT

HVT

HVT

HVT

HVT

HVT

F143 F136 F129 F122 F115

E101

Maintenance Node

Construction

TST int no MTA: XCC:

Jumper for test without MTA Connector for cross channel connection between the DLUCs

Tab. 3.97

cabling F:DLUG(A) - connector designations

SYS 0x

C192 - internal cable

to F:DLUG(B) to F:DLUG(C)

C213 C199 E213 C213 C206

or

SYS 1x

E192 - internal cable

to F:DLUG(B) to F:DLUG(C)

or

XCC/SDH/Ext

D206 - internal cable C206, E206 F206 - internal cable

to F:DLUG(A)

Distribution frame (DF) to F:DLUG(A) to F:DLUG(B) to F:DLUG(C) E206 C150 C150 C150 C150 or or

TST int w. MTA

C150 - internal cable

TST int no MTA

C164 - internal cable

to F:DLUG(B) to F:DLUG(C)

DLUC Alex MTAA out

D164 C136 - internal cable

MDF to F:DLUG(A) C143 or

Distribution frame (DF) MTAB TSText TSTdis PDC xx DLUV D136 C122 D122 C199, D199, E199, F199 MDF or Distribution frame (DF) Distribution frame (DF) Distribution frame (DF) Distribution frame (DF)

E122, E136, E282, E296 Distribution frame (DF) F122, F136, F282, F296

Tab. 3.98

Cabling F:DLUG(A)

A30828-X1160-M-2-7620

335

Construction

Maintenance Node

3.3.12 3.3.12.1

F:DLUG(B) F:DLUG(B) (module side)


10 11 12 13 14 15 15 E345 DCC
*1/SLM

SLM//PHub0

DCC *1/SLM

Pool-DCC

SLM/PHub1

BDG2

C101

C115

C129

C143

C157

C171

C185

C199

C213

C223

C247

C261

C275

C289

C303

C317

C331

*1: DCC may occupy the adjacent mounting location, depending on the variant.

10

11

12

13

14

C345 Shelf 3

SLM/PHub_x

Pool-DCC

SLM/PHub_y

DCC *1/SLM

SLM/PHub0

SLM/PHub1

BDG3

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

E101

E115

E129

E143

E157

E171

E185

E199

E213

E223

E247

E261

E275

E289

E303

E317

*1: DCC may occupy the adjacent mounting location, depending on the variant.

Modules with displays and switches in F:DLUG(B) DCCDR (-Q6129-) DCCDW (-Q6133-) SLMI:PHB (-Q192-)

Tab. 3.99

Modules with displays and switches in DLUG(B)

336

A30828-X1160-M-2-7620

E331

SLM

DCC

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

*1/SLM

Shelf 2

Maintenance Node

Construction

3.3.12.2

F:DLUG(B) (backplane)
C303 C317 C345 C331 C199 C275 C261 C247 C238 C289 C229 C185 C171 C129 C223 C157 HVT TST_fra_bev C150 C143 HVT C213 C115 HVT C101 HVT HVT HVT F101 Shelf 3 F199 F185 F171 F157 F143 F129 Pool DCC BDG3 HVT HVT HVT HVT HVT HVT HVT F115 E101 HVT D101 Shelf 2 D129 HVT E129 HVT HVT E115 HVT D115

HVT/DF

C
HVT HVT HVT HVT HVT HVT

Pow DR CD223

HVT PHub1/0 Gr.1

HVT

HVT

D345

D303

D331

D317

D289

D275

HVT D247 PHub1/0 Gr.2

D199

D185

HVT

Pool DCC

E345

E331

E317

E303

E289

E275

E261

E247 E238

E229

E223

E213

E199

E185

E171

E157

HVT/DF PHub_x

HVT/DF

HVT/DF

E
HVT HVT HVT HVT HVT HVT HVT

Pow DR EF223

HVT

HVT

F345

F331

F317

F303

F289

F275

F261

3.3.12.3

F:DLUG(B) (cabling)
BDGx: DF: HVT: PHub_x or PHub_y: Connector for the bus distributor module Lines to separate external distributors Connector for subscriber lines to the main distribution frame Connector for the Internet modules SLMI:PHx for connection to the backbone or in the case of cascading to the associated PHubs 1/0 Gr.1 or Gr.2 Connector for the Internet modules SLMI:PHx for connection to the backbone or in the case of cascading to the associated PHub_x or PHub_y Connector for Pool DCC. Pool DCC feeds the modules of type SLMA32 in the entire DLU with additional supply voltages (e.g. ringing voltage) Connector for DLU-internal test bus (also for MTA). Connection from the previous module frame incoming. Connector for DLU-internal test bus (also for MTA). Connection to the next module frame outgoing.

PHub 1/0 Gr.1 or Gr2: Pool DCC and Pow DR xx xxx: TST_fra_bev: TST_fr_nxt:

Tab. 3.100 Cabling F:DLUG(B) - connector designation

HVT PHub_y

HVT

HVT

HVT

HVT

HVT

HVT

HVT

F247

HVT

E143

D157 HVT TST_fr_nxt D150 HVT D143

D261

BDG2

HVT

HVT

HVT

HVT

HVT

HVT

HVT

HVT

HVT

HVT

D171

HVT

A30828-X1160-M-2-7620

337

Construction

Maintenance Node

BDG2 BDG3 TST_fra_bev

C213 - internal cable E213 - internal cable C150 - internal cable

to F:DLUG(A) to F:DLUG(A) to F:DLUG(A) to F:DLUG(A)

C192 E192 C150 C164 or

Tab. 3.101 F:DLUG(B) (cabling)

3.3.13 3.3.13.1

F:DLUG(C) F:DLUG(C) (module side)


10 11 12 13 14 15 C345 DCC
*1/SLM

SLM//PHub0

DCC *1/SLM

Pool-DCC

SLM/PHub1

BDG2

BDG3

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

SLM

C101

C115

C129

C143

C157

C171

C185

C199

C213

C247

C261

C275

C289

C303

C317

*1: DCC may occupy the adjacent mounting location, depending on the variant.

Modules with displays and switches in F:DLUG(C) DCCDR (-Q6129-) DCCDW (-Q6133-) SLMI:PHB (-Q192-)

Tab. 3.102 Modules with displays and switches in DLUG(C)

338

A30828-X1160-M-2-7620

C331

E223

SLM

Shelf 2

Maintenance Node

Construction

3.3.13.2

F:DLUG(C) (backplane)
C345 C331 C317 C303 C289 C275 C261 C247 C238 C229 C223 C213 C199 C185 C171 C157 HVT TST_fra_bev C150 C143 HVT C129 C115 HVT C101 HVT HVT D101 Shelf 2 D129 HVT HVT D115

HVT/DF

HVT/DF

C
HVT HVT HVT HVT HVT HVT

Pow DR CD223

HVT PHub1/0 Gr.1

HVT

HVT

D345

D331

D317

D303

D289

D275

D261

D247

D199

D185

D157

Pool DCC

BDG2

HVT

HVT

HVT

HVT

HVT

HVT

HVT

HVT

HVT

HVT

HVT

D171

HVT

3.3.13.3

F:DLUG(C) (cabling)
BDGx: DF: HVT: PHub_x or PHub_y: Connector for the bus distributor module Lines to separate external distributors Connector for subscriber lines to the main distribution frame Connector for the Internet modules SLMI:PHx for connection to the backbone or in the case of cascading to the associated PHubs 1/0 Gr.1 or Gr.2 Connector for the Internet modules SLMI:PHx for connection to the backbone or in the case of cascading to the associated PHub_x or PHub_y Connector for Pool DCC. Pool DCC feeds the modules of type SLMA32 in the entire DLU with additional supply voltages (e.g. ringing voltage) Connector for DLU-internal test bus (also for MTA). Connection from the previous module frame incoming.

PHub 1/0 Gr.1 or Gr2: Pool DCC and Pow DR xx xxx: TST_fra_bev:

Tab. 3.103 cabling F:DLUG(C) - connector designation

BDG2 BDG3 TST_fra_bev

C213 - internal cable E213 - internal cable C150 - internal cable

to F:DLUG(A) to F:DLUG(A) to F:DLUG(A) to F:DLUG(A)

C192 E192 C150 C164 or

Tab. 3.104 F:DLUG(B) (cabling)

HVT

D143

HVT

A30828-X1160-M-2-7620

339

Construction

Maintenance Node

3.3.14 3.3.14.1

F:DLUV(A) F:DLUV(A) (module side)


10 11 12 13 14 DLUV C323 15 0 1 2 3 4 5 6 7 8 DLUV 9 DLUV

D
DLUV DLUV DLUV DLUV DLUV DLUV DLUV DLUV DLUV DLUV DLUV DLUV DLUV

C101

C117

C133

C149

C165

C181

C197

C213

C229

C245

C261

C277

C293

C307

Modules with displays and switches in F:DLUV(A) DLUV (-Q1498-), (-Q126-)

Tab. 3.105 Modules with displays and switches in DLUV(A)

3.3.14.2

F:DLUV(A) (backplane)
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 C 2 3 4 5 1 2 D 3 4 2 3 4 5 1 2 3 4 2 3 4 5 1 2 3 4 2 3 4 5 1 2 3 4 2 3 4 5 1 2 3 4 2 3 4 5 1 2 3 4 2 3 4 5 1 2 3 4 2 3 4 5 1 2 3 4 2 3 4 5 1 2 3 4 2 3 4 5 1 2 3 4 2 3 4 5 1 2 3 4 2 3 4 5 1 2 3 4 2 3 4 5 1 2 3 4 2 3 4 5 1 2 3 4
9

2 3 4 5 1 2 3 4

2 3 4 5 1 2 3 4
8

2 3 4 5 1 2 3 4

2 3 4 5 1 2 3 4
7

2 3 4 5 1 2 3 4

2 3 4 5 1 2 3 4
6

2 3 4 5 1 2 3 4
5

2 3 4 5 1 2 3 4

2 3 4 5 1 2 3 4

2 3 4 5 1 2 3 4

2 3 4 5 1 2 3 4

2 3 4 5 1 2 3 4
3

2 3 4 5 1 2 3 4

2 3 4 5 1 2 3 4
2

2 3 4 5 1 2 3 4

C339

2 3 4 5 1 2 3 4

2 3 4 5 1 2 3 4
0

2 3 4 5 1 2 3 4

15

14

13

12

11

10

X = DLUV module slot Y = adjacent slot

340

A30828-X1160-M-2-7620

Maintenance Node

3.3.15.1 3.3.15

3.3.14.3

A30828-X1160-M-2-7620
LDI

ALEX

PCM30

C001 0 A010 A016 A022 2 3 4 5 6 7 A028 A034 A040 A046 A052 IWESA / IWE:HS RGMG0 BDB0 BDCG0 DLUC0 DIU0 / LDI0 8 9 10 11 IWEA / IWE:HS IWESA / IWE:HS IWEA / IWE:HS IWESA / IWE:HS DCCDC 0-1 Shelf 0 12 13 14 15 A058 A065 8 A071 A077 A083 A089 A095 A101 A107 A113 A119 9 10 11 12 13 14 15 IWEA / IWE:HS IWESA / IWE:HS IWEA / IWE:HS IWESA / IWE:HS IWEA / IWE:HS IWESA / IWE:HS 1 1 2 3 4 5 6 7 IWEA 0

DCCDC 1-0 A001

D A
DCCDC 0-0

Power supply

Connection

C010

IWEA

C016

IWESA / IWE:HS

C022

IWEA / IWE:HS

D3

F:DLU(A) for DSU

C028

IWESA / IWE:HS

F:DLUV(A) (cabling)

C034

IWEA / IWE:HS

C040

IWESA / IWE:HS

Tab. 3.106 Cabling F:DLUV(A)

C046

IWEA / IWE:HS

DLUV MOLOC Pos.

C1, C2, C3, C4, D1, D2

C052

IWESA / IWE:HS

F:DLU(A) for DSU (module side)

C058

RGMG1

C065

BDB1

C071

BDCG1

C077

DLUC1

C3, C4, D1, D2

C083

DIU1 / LDI1

C089

IWE:HS

C095

IWEA / IWE:HS

DLUV next MOLOC Pos.

C101

IWESA / IWE:HS

C1, C2 (each fourth module only)

C107

C113

IWE:HS

C119

DCCDC 1-1

Construction

Shelf 1

341

Construction

Maintenance Node

Modules with displays and switches in F:DLU(A) for DSU BDB (-Q808-), (-Q1002-) DIUDC (-Q1007-) IWESx (-Q1178-) BDCG (-Q809-) DIU:LDID (-Q1109-) IWEx (-Q144-) DCCDC (-Q5862-C) DLUC (-Q968-) RGMG (-Q813-) DIUDA (-Q806-) IWEx (-Q1177-)

Tab. 3.107 Modules with displays and switches in DLU(A) for DSU

3.3.15.2

F:DLU(A) for DSU (backplane)


A027 MOD5 L3 L2 L1 L0 A015 A015 MOD6 A083 A080 A074 A071 A068 A119 A101 A061 A113 A052 A039 A001 BST2 BST5 Shelf 1 DIU-INTERN DIU-INTERN DLUC-INTERN DLUC-INTERN or or C001 Shelf 0 C015 HVT14 C015

MOD1

MOD2

MOD3

EXT1 NC2 1 INT2

BST1

LTE1 INT1

EXT2

MOD4

B098

B086 B086 B080

B074

B
TRACE LTE2 INT4 EXT3 INT3 INT5

C119 C116 C113 C110 C107 C104 C101 C098

C083 C080

C089

C074 C071 C068

C061

B061

HVT10

HVT11

HVT12

D116

D098

D
TRACE LTE4 INT12 INT11 EXT8 INT13 EXT7

3.3.15.3

F:DLU(A) for DSU (cabling)


INT1 A080 - internal cable to F:DLU(B) to F:DLU(C) INT2 A068 - internal cable to F:DLU(B) to F:DLU(C) A074 A074 A061 A061

Tab. 3.108 Cabling F:DLU(A) for DSU

D086 D083 D080

D074

D061

342

A30828-X1160-M-2-7620

HVT13

EXT5 NC2 2 INT10

C
BST3 EXT4 HVT8 INT6 BST4 INT7 HVT9 INT8

EXT6

LTE3 INT9

C052

C039

C027

L4

Maintenance Node

Construction

INT3

B098 - internal cable

to F:DLU(B) to F:DLU(C)

D098 B104 B074 B074 D061 B061 A092 A092 A092 A092 C074 A068 C061 A055 B098 B098 D074 D074 B061 B055

TEST-CABLE

or

TEST-CABLE/ MP-CABLE CDBUS-CABLE or

INT4

B080 - internal cable

to F:DLU(B) to F:DLU(C)

INT5

B061 - internal cable

to F:DLU(B) to F:DLU(C)

RING-CABLE RING-CABLE TEST-CABLE TEST-CABLE TEST-CABLE TEST-CABLE DIU-INTERN DIU-INTERN DLUC-INTERN DLUC-INTERN TEST-CABLE TEST-CABLE CDBUS-CABLE

or

INT6

C110 - internal cable

to F:DLU(B) to F:DLU(C)

or

INT7 INT8 INT9

C104 - internal cable C098 - internal cable C080 - internal cable

to F:DLU(B) to F:DLU(B) to F:DLU(B) to F:DLU(C)

or

INT10

C068 - internal cable

to F:DLU(B) to F:DLU(C)

or

INT11

D098 - internal cable

to F:DLU(B) to F:DLU(C)

or

INT12

D080 - internal cable

to F:DLU(B) to F:DLU(C)

or

INT13

D061 - internal cable

to F:DLU(B) to F:DLU(C)

RING-CABLE RING-CABLE

or

EXT1 EXT2 EXT3 EXT4 EXT5 EXT6 EXT7 EXT8

A074 - external cable A061 - external cable B074 - external cable C116 - external cable C074 - external cable C061 - external cable D116 - external cable D074 - external cable

to F:DLU(B) to F:DLU(B) to F:DLU(B) to F:DLU(B) to F:DLU(B) to F:DLU(B) to F:DLU(B) to F:DLU(B)

A074 A061 B074 C113 C074 C061 D110 D074

DIU-INTERN DLUC-INTERN CDBUS-CABLE MTA-CABLE DIU-INTERN DLUC-INTERN MTA-CABLE CDBUS-CABLE

HVTxx - cable to MDF BST1 - BST5: Jumper LTE1 - LTE4: For local DLU: cable for LTG. For remote: cable to MDF L0 - L5: Cable connectors TRACE: Trace-CABLE NC2: Module NC2 plugged in here

Tab. 3.108 Cabling F:DLU(A) for DSU

A30828-X1160-M-2-7620

343

344

Construction

3.3.16.1 3.3.16

C001 C010 C016 C022 2 3 A028 A034 A040 A046 A052 A058 A065 8 9 10 11 12 13 14 15 A071 A077 A083 A089 A095 A101 A107 A113 A119 BDE0 BDE1 IWE:HS / IWEA IWE:HS / IWESA IWE:HS / IWEA IWE:HS / IWESA IWE:HS / IWEA IWE:HS / IWESA IWE:HS / IWEA IWE:HS / IWESA DCCDC 2-1 or 4-1 or 6-1 Shelf 2 or 4 or 6 IWE:HS / IWEA IWE:HS IWESA IWE:HS / IWESA IWE:HS / IWEA 4 5 6 7 IWE:HS / IWESA C028 C034 C040 C046 C052 IWE:HS / IWESA BDE0 BDE1 IWE:HS / IWEA IWE:HS / IWESA IWE:HS / IWEA IWE:HS / IWESA IWE:HS / IWEA IWE:HS / IWESA IWE:HS / IWEA IWE:HS / IWESA DCCDC 3-1 or 5-1 or 7-1 Shelf 3 or 5 or 7 C058 C065 C071 C077 C083 C089 C095 C101 C107 C113 C119 IWE:HS / IWEA IWE:HS / IWESA IWE:HS / IWEA IWE:HS / IWESA IWE:HS / IWEA A022 IWE:HS / IWEA IWE:HS / IWESA A016 1 IWE:HS / IWESA IWE:HS / IWEA 0 A010 IWE:HS / IWEA

DCCDC 3-0 or 5-0 or 7-0 A001

D A C
DCCDC 2-0 or 4-0 or 6-0 0 1 2 3 4 5 6 7

F:DLU(B) for DSU

F:DLU(B) for DSU (module side)

IWEx (-Q144-) 8 9 10 11 12 13 14 15

BDE (-Q807-), (-Q1003-)

DCCDC (-Q5862-C)

IWEx (-Q1177-)

Tab. 3.109 Modules with displays and switches in DLU(B) for DSU

Modules with displays and switches in F:DLU(B) for DSU

IWESx (-Q1178-)

A30828-X1160-M-2-7620

Maintenance Node

Maintenance Node

Construction

3.3.16.2

F:DLU(B) for DSU (backplane)


A077 A074 A068 A016 A119 A092 A089 A061 A055 A052 A101 A113 A040 A028 A001 C001 Shelf 3 or 5 or 7 BST4 Shelf 2 or 4 or 6 BST2

MOD1

MOD2

A
BST1

INT1 HVT3

INT5 HVT5

HVT6

HVT7

HVT4 INT2

B098

INT3

B074

B068

INT6

INT7

C119

INT8

C101

C061

INT9

B061

C113

C077 C074

C068

C055 C052

C089

C040

HVT10

HVT14

HVT11

HVT12 INT10

INT13 HVT13

D098

D074

D
INT14 INT15 INT16 INT17

3.3.16.3

F:DLU(B) for DSU (cabling)


INT1 A092 - internal cable to F:DLU(A) to F:DLU(A) to F:DLU(A) INT2 A074 - internal cable to F:DLU(A) to F:DLU(A) to F:DLU(B) INT3 INT4 A068 - internal cable A061 - internal cable to F:DLU(B) to F:DLU(A) to F:DLU(A) to F:DLU(B) INT5 A055 - internal cable to F:DLU(B) C098 C104 C110 A074 A080 A068 A074 A061 A068 A055 A061 TEST-CABLE TEST-CABLE TEST-CABLE DIU-INTERN DIU-INTERN DIU-INTERN DIU-INTERN DLUC-INTERN DLUC-INTERN DLUC-INTERN DLUC-INTERN or or or

Tab. 3.110 Cabling F:DLU(B) for DSU

D068

D061

HVT15

HVT16

INT11

HVT9

INT12

C
BST3

C028

C016

HVT8

INT4

A30828-X1160-M-2-7620

345

Construction

Maintenance Node

INT6

B098 - internal cable

to F:DLU(A) to F:DLU(B)

D098 D098 B074 B080 B068 B074 B074 B061 D061 D061 C074 C080 C068 C074 A068 C061 C068 C055 C061 D098 B098 B098 D074 D080 D068 D074 D074 B061 B061 B055

TEST-CABLE TEST-CABLE

or

INT7

B074 - internal cable

to F:DLU(A) to F:DLU(A) to F:DLU(B)

or CDBUS-CABLE

INT8

B068 - internal cable

to F:DLU(B) to F:DLU(C)

CDBUS-CABLE

or

INT9

B061 - internal cable

to F:DLU(A) to F:DLU(A) to F:DLU(B)

RING-CABLE RING-CABLE RING-CABLE DIU-INTERN DIU-INTERN DIU-INTERN DIU-INTERN DIU-INTERN DLUC-INTERN DLUC-INTERN DLUC-INTERN DLUC-INTERN TEST-CABLE TEST-CABLE MP-CABLE

or

INT10

C074 - internal cable

to F:DLU(A) to F:DLU(A) to F:DLU(B)

or

INT11

C068 - internal cable

to F:DLU(B) to F:DLU(C)

or

INT12

C061 - internal cable

to F:DLU(A) to F:DLU(A) to F:DLU(B)

or

INT13 INT14

C055 - internal cable D098 - internal cable

to F:DLU(B) to F:DLU(A) to F:DLU(B) to F:DLU(C)

or

INT15

D074 - internal cable

to F:DLU(A) to F:DLU(A) to F:DLU(B)

or CDBUS-CABLE

INT16

D068 - internal cable

to F:DLU(B) to F:DLU(C)

CDBUS-CABLE

or

INT17

D061 - internal cable

to F:DLU(A) to F:DLU(B) to F:DLU(C)

RING-CABLE RING-CABLE RING-CABLE

or

HVTxx - cable to MDF BST1 - BST4: Jumper

Tab. 3.110 Cabling F:DLU(B) for DSU

346

A30828-X1160-M-2-7620

Maintenance Node

3.3.17.2

3.3.17.1

3.3.17

A30828-X1160-M-2-7620 B A A
BST1 HVT1 A016 A022 A028 A034 A040 A046 A052 A058 A065 A071 A077 A083 A089 A095 A101 A107 A113 A119 IWE:HS / WEA IWE:HS / WESA IWE:HS / WEA IWE:HS / WESA BDE0 BDE1 IWE:HS / WEA IWE:HS / WESA IWE:HS / WEA IWE:HS / WESA IWE:HS / WEA IWE:HS / WESA IWE:HS / WEA IWE:HS / WESA DCCDC 2-1 or 4-1 or 6-1 Shelf 2 or 4 or 6 8 9 10 11 12 13 14 15 IWE:HS / WESA IWE:HS / WEA IWE:HS / WESA A113 A010 IWE:HS / WEA A119 A001 DCCDC 2-0 or 4-0 or 6-0 0 1 2 3 4 5 6 7 HVT2 INT1 HVT3 A092 A089 A101

B
HVT4 INT2 INT3 INT4 INT5 HVT5 A055 A052 A061 A068 A077 A074 DCCDC (-Q5862-C) IWEx (-Q1177-) HVT6 A040 Modules with displays and switches in F:DLU(C) for DSU HVT7 A028 HVT8 A016 IWESx (-Q1178-) BST2 Shelf 2 or 4 or 6 A001

INT6

B104

F:DLU(C) for DSU

BDE (-Q807-), (-Q1003-)

INT7

B098

INT8

B074

F:DLU(C) for DSU (backplane)

F:DLU(C) for DSU (module side)

INT9

B068

INT10

B061

Tab. 3.111 Modules with displays and switches in DLU(C) for DSU

INT11

B055

Construction

347

Construction

Maintenance Node

3.3.17.3

F:DLU(C) for DSU (cabling)


INT1 A092 - internal cable to F:DLU(A) to F:DLU(A) to F:DLU(A) INT2 A074 - internal cable to F:DLU(A) to F:DLU(B) INT3 A068 - internal cable to F:DLU(A) to F:DLU(B) INT4 A061 - internal cable to F:DLU(A) to F:DLU(B) INT5 A055 - internal cable to F:DLU(A) to F:DLU(B) INT6 INT7 B104 - internal cable B098 - internal cable to F:DLU(A) to F:DLU(A) to F:DLU(B) INT8 B074 -internal cable to F:DLU(A) to F:DLU(B) INT9 B068 - internal cable to F:DLU(A) to F:DLU(B) INT10 INT11 B061 - internal cable B055 - internal cable to F:DLU(A) to F:DLU(A) to F:DLU(B) C098 C104 C110 A080 A068 C080 C068 A068 A055 C068 C055 B098 D098 D098 B080 B068 D080 D068 B061 D061 D061 RING-CABLE RING-CABLE RING-CABLE or or TEST-CABLE TEST-CABLE TEST-CABLE DIU-INTERN DIU-INTERN DIU-INTERN DIU-INTERN DLUC-INTERN DLUC-INTERN DLUC-INTERN DLUC-INTERN TEST-CABLE/MP-CABLE TEST-CABLE TEST-CABLE or or or or or or or

HVTxx - cable to MDF BST1 - BST2: Jumper

Tab. 3.112 Cabling F:DLU(C)

348

A30828-X1160-M-2-7620

Maintenance Node

3.3.18.1

3.3.18

A30828-X1160-M-2-7620 B
C001 A001 A008 IWE:HS A015 A021 A027 A033 A039 A045 A051 A057 A064 8 9 10 11 12 13 14 15 A068 A074 A080 A086 A092 A098 A104 A110 A116 A123 Shelf 3 Shelf 2 IWE:HS IWE:HS IWE:HS BD2 IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS DCCDC 2-2 8 9 10 11 12 13 14 15 IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS 1 2 3 4 5 6 7 IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS BD3 IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS DCCDC 3-2 0 IWE:HS 0 1 2 3 4 5 6 7 C008 C015 C021 C027 C033 C039 C045 C051 C057 C064 C068 C074 C080 C086 C092 C098 C104 C110 C116 C123

F:DLU(E) for DSU

F:DLU(E) for DSU (module side)

DCCDC (-Q5862-C) DCCDC 3-0

D A C
DCCDC 2-0

IWEx (-Q144-)

Tab. 3.113 Modules with displays and switches in DLU(E) for DSU

Modules with displays and switches in F:DLU(E) for DSU

Construction

349

350

Construction

3.3.18.3

3.3.18.2

INT4

INT3

INT2

INT1

Cabling F:DLU(E) with F:DLU(D)

F:DLU(E) (cabling) for DSU

F:DLU(E) for DSU (backplane)

INT5

D
BSTS3 INT2 C110 HVT17 BSTIWE9 C107 C104 HVT18 BSTSLC5 C101 C098 HVT19 BSTIWE10 C095 C092 HVT20 C086 HVT21 BSTIWE11 C083 C080 HVT22 BSTSLC6 C077 C074 HVT23 BSTIWE12 C071 C068 HVT24 C057 HVT25 BSTIWE13 C054 C051 HVT26 BSTSLC7 C048 C045 HVT27 BSTIWE14 C042 C039 HVT28 C033 HVT29 BSTIWE15 C030 C027 HVT30 BSTSLC8 C024 C021 HVT31 BSTIWE16 C018 C015 HVT32 INT5 BSTS4 Shelf 3 C001 Shelf 2 INT3 B083 B113

C
C116

B060 - internal cable

B083 - internal cable

B113 - internal cable

A060 - internal cable

B012 - internal cable

BSTS1 HVT1 BSTIWE1 HVT2 BSTSLC1 HVT3 BSTIWE2 HVT4 HVT5 BSTIWE3 HVT6 BSTSLC2 HVT7 BSTIWE4 HVT8 INT4 B060 INT1 HVT9 BSTIWE5 HVT10 BSTSLC3 HVT11 BSTIWE6 HVT12 HVT13 BSTIWE7 HVT14 BSTSLC4 HVT15 BSTIWE8 HVT16 B012

A116 A110 A107 A104 A101 A098 A095 A092 A086 A083 A080 A077 A074 A071 A068 A060 A057 A054 A051 A048 A045 A042 A039 A033 A030 A027 A024 A021 A018 A015

Tab. 3.114 Cabling F:DLU(E) for DSU


to F:DLU(D) B048 INT-CABLE 1) BSTS2

to F:DLU(F)

to F:DLU(F)

to F:DLU(F)

to F:DLU(F)

to F:DLU(D)

to F:DLU(D)

to F:DLU(D)

to F:DLU(D)

B083

B113

B012

B060

B077

A101

B116

B010

TEST-CABLE

RING-1 CABLE

INT-CABLE

INT-CABLE

TEST-CABLE

RING-0 CABLE

RING-1 CABLE

RING-0 CABLE

or

or 1)

or

or

A30828-X1160-M-2-7620

Maintenance Node

A001

Maintenance Node

Construction

HVT1 - HVT32: cable to MDF BSTS1 - BSTS4: Jumper BSTSL C1 - BSTSLC8: Jumper for SLC 96 BSTIWE1 - BSTIWE16: Jumper for IWE

Tab. 3.114 Cabling F:DLU(E) for DSU 1) PCM-, CD-Bus, Control-Net, system 0 or 1 Cabling F:DLU(E) with F:DLU(G)
INT1 INT2 A060 - internal cable B113 - internal cable to F:DLU(G) to F:DLU(G) to F:DLU(F) INT3 B083 - internal cable to F:DLU(G) to F:DLU(F) INT4 B060 - internal cable to F:DLU(G) to F:DLU(F) INT5 B012 - internal cable to F:DLU(G) to F:DLU(F) B060 B124 B113 A100 B083 B069 B060 B010 B012 SYS0-CABLE RING-1 CABLE RING-1 CABLE TEST-CABLE TEST-CABLE SYS1-CABLE INT-CABLE RING-0 CABLE RING-0 CABLE or or or or

HVT1 - HVT32: cable to MDF BSTS1 - BSTS4: Jumper BSTSL C1 - BSTSLC8: Jumper for SLC 96 BSTIWE1 - BSTIWE16: Jumper for IWE

Tab. 3.115 Cabling F:DLU(E) for DSU

A30828-X1160-M-2-7620

351

352

Construction

3.3.19.2 3.3.19
B A

3.3.19.1

B
BSTS1 A021 A027 A033 A039 A045 A051 IWE:HS IWE:HS BD2 BD3 IWE:HS A074 A080 A086 A092 A098 A104 A110 A116 BSTS4 Shelf 2 A001 A123 Shelf 2 IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS DCCDC 2-2 A057 A064 A068 IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS

A001 A008 A015 IWE:HS

DCCDC 2-0

A
A116

0 1 2 3 4 5 6 7

F:DLU(F) for DSU

DCCDC (-Q5862-C)

INT2 HVT1 BSTIWE1 HVT2 BSTSLC1 HVT3 BSTIWE2 HVT4 IWEx (-Q144-) HVT5 BSTIWE3 HVT6 BSTSLC2 HVT7 A086 A083 A080 A077 A074 A110 A107 A104 A101 A098 A095 A092

B113

F:DLU(F) for DSU (backplane)

F:DLU(F) for DSU (module side)

INT3

B083

INT4

B060

8 9 10 11 12 13 14 15

Tab. 3.116 Modules with displays and switches in DLU(F) for DSU

Modules with displays and switches in F:DLU(F) for DSU

INT1 HVT8 BSTIWE4 HVT9 BSTSLC3 HVT10 BSTIWE5 HVT11 HVT12 BSTIWE6 HVT13 BSTSLC4 HVT14 BSTIWE7 HVT15 A033 A030 A027 A024 A021 A018 A015

A060 A057 A054 A051 A048 A045 A042 A039

A30828-X1160-M-2-7620

INT5

B012

Maintenance Node

Maintenance Node

Construction

3.3.19.3

F:DLU(F) for DSU (cabling)


Cabling F:DLU(F) with F:DLU(D)
INT1 INT2 A060 - internal cable B113 - internal cable to F:DLU(D) to F:DLU(D) to F:DLU(E) INT3 B083 - internal cable to F:DLU(D) to F:DLU(E) INT4 B060 -internal cable to F:DLU(D) to F:DLU(E) INT5 B012 - internal cable to F:DLU(D) to F:DLU(E) B048 B116 B113 A101 B083 B077 B060 B010 B012 INT-CABLE RING-1 CABLE RING-1 CABLE TEST-CABLE TEST-CABLE INT-CABLE INT-CABLE RING-0 CABLE RING-0 CABLE or 1) or or 1) or

HVT1 - HVT15: cable to MDF BSTS1 - BSTS2: Jumper BSTSL C1 - BSTSLC4: Jumper for SLC 96 BSTIWE1 - BSTIWE7: Jumper for IWE

Tab. 3.117 Cabling F:DLU(F) for DSU Cabling F:DLU(F) with F:DLU(G)
INT1 INT2 A060 - internal cable B113 - internal cable to F:DLU(G) to F:DLU(G) to F:DLU(E) INT3 B083 - internal cable to F:DLU(G) to F:DLU(E) INT4 B060 -internal cable to F:DLU(G) to F:DLU(E) INT5 B012 - internal cable to F:DLU(G) to F:DLU(E) B060 B124 B113 A100 B083 B069 B060 B010 B012 SYS0-CABLE RING-1 CABLE RING-1 CABLE TEST-CABLE TEST-CABLE SYS1-CABLE INT-CABLE RING-0 CABLE RING-0 CABLE or or or or

HVT1 - HVT15: cable to MDF BSTS1 - BSTS2: Jumper BSTSL C1 - BSTSLC4: Jumper for SLC 96 BSTIWE1 - BSTIWE7: Jumper for IWE

Tab. 3.118 Cabling F:DLU(F) for DSU

A30828-X1160-M-2-7620

353

354

Construction

3.3.20.1 3.3.20

C001 A001 A010 IWE:HS A015 A021 A027 A033 A039 A045 A051 A057 A066 A073 A079 A085 A091 13 14 15 A097 A103 A109 A115 A124 Shelf 1 Shelf 0 IWE:HS IWE:HS DCCDC 0-2 IWE:HS DLUS0 DLUS1 IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS 1 2 3 4 5 6 7 8 9 10 11 12 IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS IWE:HS DCCDC 1-2 0

DCCDC 1-0 DCCDC 0-0

D A C

C008

F:DLU(G) for DSU

F:DLU(G) for DSU (module side)


0 1 2 3 4 5 6

DCCDC (-Q5862-C) 9 10 11 12 13 14 15

C015

C021

C027

C033

C039

C045

C051

C057

C068

C074

Modules with displays and switches in F:DLU(G) for DSU

DLUS (-Q1492-), (-Q1493-), (-Q1494-)

C080

C086

C092

C098

Tab. 3.119 Modules with displays and switches in DLU(G) for DSU

C104

C110

C116

IWEx (-Q144-)

A30828-X1160-M-2-7620

C123

Maintenance Node

Maintenance Node

Construction

3.3.20.2

F:DLU(G) for DSU (backplane)


DLUTRC0 A060 SDHCLK0 A057 A054 NC2 HVT7/HDSL A051 ALEXTTL A048 A045 HVT8 TEST ext A042 A039 HVT9 A110 A106 A103 A100 A097 A080 A077 A073 A069 A066 A116 A092 A033 A030 A027 A086 A021 A015 A001 BSTS2 RING0 B010 BSTS4 Shelf 1 C001 Shelf 0 DLUV DLUV HVT30 C015

HVT1 MTA A HVT2/MTAA TEST int BSTST

HVT5 NC2 HVT6/HDSL DLUTRC1 SDHCLK1

BSTS1

HVT14/SSW B095

C104 C100 C097 C095 C092 C089 C086

C057

B060 SYS0 PDC0x/BST B057

B069 SYS1 PDC1x/BST B066

B124

RING1

MTAB

B106

MTAB

B101

C080 HVT20 BSTSLC2 C077 C074 HVT21

HVT16 BSTSLC1 HVT17 OMX HVT18 OMX HVT191

C051 HVT24 BSTSLC3 C048 C045 HVT25

BSTS3

HVT15

D
DLUV DLUV

3.3.20.3

F:DLU(G) for DSU (cabling)


ALEXTTL: Connector for external alarms, connected to ALEX interface at DLUS0 and DLUS1 Jumper plug for connection of PDC-signals to LTCD or LTOD Jumper plug for super pre-mating (+5V via inductor), only for DCCDD, DCCCR, DCCDH Jumper plug for test bus (if no MTA) Jumper plug for SLC 96 Connector for DLU-Tracer (Address- and Data-Bus, Control-signals from CPU) Module as 10 x V5.1 interfaces Cable for HDSL signals to transmission distribution frame Subscriber cable to the MDF DLU external MTA bus (type A or type B) System clock decoupling module (clock from GCG)

BST: BSTS1 - BSTS4:

BSTTST: BSTSLC1 - BSTSLC4: DLUTRC0 / 1:

DLUV: HDSL: HVT1 - HVT30: MTA-A/B: NC2:

Tab. 3.120 Cabling F:DLU(G) for DSU

HVT22

HVT23

HVT26 OMX HVT27 OMX HVT28 BSTSLC4 HVT29

C039 C036 C033 C030 C027 C024 C021

C116

C110

C068

HVT12

HVT3

HVT4

HVT13

HVT10 TEST ext HVT11

A30828-X1160-M-2-7620

355

Construction

Maintenance Node

OMX: PDC0x or PDC1x:

Connector for OMX16D-applications Primary digital carrier to/from LTG (PDC0-0, PDC0-1, PDC1-0, PDC1-1) Ring distribution system 0 or 1 Separate clock source for clock generator (SDH-net) Spare-switch circuit via MDF PCM-, CD bus, control-Net system 0 or 1 DLU external testbus (1x to MDF; 1x to next DLU in the same rack) DLU internal test bus (also for MTA) Connector for SDE with 8 PCM line system 0 or 1)

RING0/1: SDHCLK0/1: SSW: SYS0/1: TEST ext: TEST int: TRACE0/1:

Tab. 3.120 Cabling F:DLU(G) for DSU

3.3.21 3.3.21.1

F:MODEM(D) F:MODEM(D) for DSU Type GPT

MODEM 10

MODEM 11

MODEM 12

MODEM 13

MODEM 14 MODEM 12

MODEM 1

MODEM 2

MODEM 3

MODEM 4

MODEM 5

MODEM 6

MODEM 7

MODEM 8

MODEM 9

3.3.21.2

F:MODEM(D) for DSU Type NEUHAUS

MODEM 10

MODEM 11

MODEM 1

MODEM 2

MODEM 3

MODEM 4

MODEM 5

MODEM 6

MODEM 7

MODEM 8

MODEM 9

356

A30828-X1160-M-2-7620

PSU

PSU

Maintenance Node

Construction

3.4

F:LTG
3.4.1 3.4.1.1 3.4.1.2 3.4.1.3 3.4.1.4 3.4.1.5 3.4.1.6 3.4.1.7 3.4.1.8 3.4.1.9 3.4.2 3.4.2.1 3.4.2.2 3.4.2.3 3.4.2.4 3.4.2.5 3.4.2.6 3.4.2.7 3.4.2.8 3.4.2.9 3.4.2.10 3.4.2.11 3.4.2.12 3.4.3 3.4.3.1 3.4.3.2 3.4.3.3 3.4.3.4 3.4.3.5 3.4.4 3.4.4.1 3.4.4.2 3.4.4.3 3.4.4.4 3.4.4.5 3.4.4.6 3.4.4.7 3.4.4.8 3.4.4.9 3.4.4.10 3.4.4.11 3.4.4.12 3.4.4.13 3.4.4.14 3.4.4.15 F:LTGP F:LTGP(A) (module side) F:LTGP(B) (module side) LTU-Types for LTGP(A) in B operation LTU-Types for LTGP(A) in C operation LTU-Types for F:LTGP(B) as UI-LTG, F:LTGP(A) (backplane) F:LTGP(A) (cabling) F:LTGP(B) (backplane) F:LTGP(B) (cabling) F:LTGN F:LTGN(A) (module side) F:LTGN(B) (module side) F:LTGN(C) (module side) LTU-types for F:LTGN in B operation LTU-types for F:LTGN in C operation LTU-types for F:LTGN(C) as UI-LTGN F:LTGN(A) (backplane) F:LTGN(A) (cabling) F:LTGN(B) (backplane) F:LTGN(B) (cabling) F:LTGN(C) (backplane) F:LTGN(C) (cabling) F:LTGM(A) F:LTGM(A) (module side) LTU-types for F:LTGM(A) in B operation LTU-types for F:LTGM(A) in C operation F:LTGM(A) (backplane) F:LTGM(A) (cabling) F:LTGG(A) F:LTGG(A) with DIU30 in B operation (module side) LTU-types for F:LTGG(A) with DIU30 in B operation F:LTGG(A) with DIU30 in B operation (backplane) F:LTGG(A) with DIU30 in B operation (cabling) F:LTGG(A) with DIU30 in C operation (module side) LTU-types for F:LTGG(A) with DIU30 in C operation F:LTGG(A) with DIU30 in C operation (backplane) F:LTGG(A) with DIU30 in C operation (cabling) F:LTGG(A) with DIU24 (module side) LTU-types for F:LTGG(A) with DIU24 F:LTGG(A) with DIU24 (backplane) F:LTGG(A) with DIU24 (cabling) F:LTGG(A) as UI-LTGG (module side) LTU-types for F:LTGG(A) as UI-LTGG, F:LTGG(A) as UI-LTG (backplane)

A30828-X1160-M-2-7620

357

Construction

Maintenance Node

3.4.4.16 3.4.5 3.4.5.1 3.4.5.2 3.4.5.3 3.4.6 3.4.6.1 3.4.6.2 3.4.6.3 3.4.6.4 3.4.6.5 3.4.6.6 3.4.6.7 3.4.6.8 3.4.7 3.4.7.1 3.4.7.2 3.4.7.3 3.4.7.4 3.4.7.5 3.4.7.6 3.4.7.7 3.4.7.8 3.4.8 3.4.8.1 3.4.8.2 3.4.8.3 3.4.8.4 3.4.9 3.4.9.1 3.4.9.2 3.4.9.3 3.4.10 3.4.10.1 3.4.10.2 3.4.10.3 3.4.10.4 3.4.11 3.4.11.1 3.4.11.2 3.4.11.3

F:LTGG(A) as UI-LTG (cabling) F:LTGH(A) F:LTGH(A) (module side) F:LTGH(A) (backplane) F:LTGH(A) (cabling) F:LTGF(A) F:LTGF(A) in B operation (module side) LTU-types for F:LTGF(A) in B operation F:LTGF(A) in B operation (backplane) F:LTGF(A) in B operation (cabling) F:LTGF(A) in C operation (module side) LTU-Types for F:LTGF(A) in C operation, F:LTGF(A) in C operation (backplane) F:LTGF(A) in C operation (cabling) F:LTGB(A) F:LTGB(A) with DIU30 (module side) LTU-types for F:LTGB(A) with DIU30 F:LTGB(A) with DIU30 (backplane) F:LTGB(A) with DIU30 (cabling) F:LTGB(A) with DIU24 (module side) LTU-types for F:LTGB(A) with DIU24 F:LTGB(A) with DIU24 (backplane) F:LTGB(A) with DIU24 (cabling) F:LTGC(A) F:LTGC(A) (module side) LTU-Types for F:LTGC(A) F:LTGC(A) (backplane) F:LTGC(A) (cabling) F:CR(A) F:CR(A) (module side) F:CR(A) (backplane) F:CR(A) (cabling) F:LTGD(A) F:LTGD(A) (module side) LTU-Types for F:LTGD(A) F:LTGD(A) (backplane) F:LTGD(A) (cabling) F:CRES(A) F:CRES(A) (module side) F:CRES(A) (backplane) F:CRES(A) (cabling)

358

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.4.1 3.4.1.1

F:LTGP F:LTGP(A) (module side)


LTG number 1-16 LTG number 17-32

D
LTU:S LTU:S LTU:S LTU:S LTU:S LTU:S LTU:S LTU:S C343 GPP GPP GPP GPP GPP GPP GPP GPP C331

C107

C119

C131

C143

C177

C189

C201

C213

C237

C249

C261

C273

C307

GPP types GPPYF (-Q277-X000 -) GPPYG (-Q277-X100 -) GPPYH (-Q277-X200 -) GPPYI (-Q277-X300 -) GPPZF (-Q302-X000 -) GPPZG (-Q302-X100 -) GPPZH (-Q302-X200 -) GPPZI (-Q302-X300 -)

Remarks with 4 LTG functions, 128 Mbyte memory, SILC, MDTOG, PCM30 with 4 LTG functions, 256 Mbyte memory, SILC, MDTOG, PCM30 with 4 LTG functions, 512 Mbyte memory, SILC, MDTOG, PCM30 with 4 LTG functions, 1 Gbyte memory, SILC, MDTOG, PCM30 with 4 LTG functions, 128 Mbyte memory, SILC, MDTOG, PCM24 with 4 LTG functions, 256 Mbyte memory, SILC, MDTOG, PCM24 with 4 LTG functions, 512 Mbyte memory, SILC, MDTOG, PCM24 with 4 LTG functions, 1 Gbyte memory, SILC, MDTOG, PCM24

Tab. 3.121 Basic types of GPP modules

Modules LTU:S ATCO (-Q267-) DEC120 (-Q1467-X100) DEC480 (-Q328-) MCT (-Q63-) OCE:N (-Q165-) PHMA (-Q1469-)

Remarks Automatic Test and Conference Unit for LTG Digital Echo Compensator with 120 channels (4 x PCM30) Digital Echo Compensator with 480 channels (16 x PCM30) Mid Call Trigger Operationallity Controlled Equipment for Announcement Packet Handler Module A (High performance SILC)

Tab. 3.122 Modules with display and switches in LTU:S

C319

A30828-X1160-M-2-7620

359

Construction

Maintenance Node

3.4.1.2

F:LTGP(B) (module side)


LTG number 1-16 LTG number 17-32

VPU 0 / OCE

LTU:S

LTU:S

LTU:S

LTU:S

LTU:S

C101

C117

C131

C143

C177

C189

C201

C213

C237

C249

C261

C273

C307

C319

C331

GPP types GPPYF (-Q277-X000 -) GPPYG (-Q277-X100 -) GPPYH (-Q277-X200 -) GPPYI (-Q277-X300 -)

Remarks with 4 LTG functions, 128 Mbyte memory, SILC, MDTOG, PCM30 with 4 LTG functions, 256 Mbyte memory, SILC, MDTOG, PCM30 with 4 LTG functions, 512 Mbyte memory, SILC, MDTOG, PCM30 with 4 LTG functions, 1 Gbyte memory, SILC, MDTOG, PCM30

Tab. 3.123 Basic types of GPP modules

Modules LTU:S / VPU / OCE ATCO (-Q267-) DEC120 (-Q1467-X100) DEC480 (-Q328-) MCT (-Q63-) OCE:N (-Q165-) PHMA (-Q1469-) VPU (-Q190-)

Remarks Automatic Test and Conference Unit for LTG Digital Echo Compensator with 120 channels (4 x PCM30) Digital Echo Compensator with 480 channels (16 x PCM30) Mid Call Trigger Operationallity Controlled Equipment for Announcement Packet Handler Module A (High performance SILC) Sprach Erkennungseinrichtung

Tab. 3.124 Modules with display and switches in LTU:S

360

A30828-X1160-M-2-7620

C343

LTU:S

VPU 1

OCE

GPP

GPP

GPP

GPP

GPP

GPP

GPP

Maintenance Node

Construction

3.4.1.3

LTU-Types for LTGP(A) in B operation


LTUType D30 APPLIC 0 CASCAS CCSCAS CCSCCS CASRCA CCSDLU EXTDLU V52IF CCSPA ATE ATM U08 V01 V02 V03 V03 V04 V05 V05 V06 V08 V09 V09 V10 V10 V11 V15 V99 Y25 MCT INS PMA X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 1 X X X X X X X X 2 X X X X X X X X LTU-Number 3 X X X X X X X X X X (X) X X X X X X X 4 5 6 7 SU 0/1 connection of PCM30 with CAS connection of PCM30 with CCS/CAS connection of PCM30 with CCS announcement connection connection DLU with CCS connection DLU (extension) V5.2 interface primary rate access connection ATEMAIN, M:ATCO in LTU:S (1) ATETM, M:ATCO in LTU:S (1) M:OCE:N in LTU:S version15 (2) code receiver for MFC:R2 on GPxx code receiver push button dialing on GPxx code receiver push button dialing on GPxx TLFB trunk test with SULIM ETEAE without HW Responder (1) Test transformer, without HW code receiver for MFC:R1 on GPxx test position TWS/LWS (3) code receiver push button dialing on GPxx TLF/RBS wake up service / RSCI CME TWS/LWS MDTOG on GPxx CTC only in SU 0 on GPxx COU, M:ATCO in LTU:S (1) M:MCT in LTU:S SILC-function on GPxx M:PHMA in LTU:S (expanded SILC-function) Remarks

Tab. 3.125 LTU-Types for LTG in B operation

(1)

When using M:ATCO: The ATE functions occupy the LTU5. The COU function always uses LTU3. Both functionalities of the ATCO module can work simultaneously in B operation

A30828-X1160-M-2-7620

361

Construction

Maintenance Node

(2)

For 31 announcement ports U08 in LTU3 For 62 announcement ports LTU3 master, LTU5 slave LTU3 must be kept free when LTU type V08 is created

(3)

3.4.1.4

LTU-Types for LTGP(A) in C operation


LTUType D30 APPLIC 0 CASCAS CCSCAS CCSCCS CASRCA ATE ATM U08 V01 V02 V04 V05 V05 V06 V08 V10 V10 V11 V99 Y25 MCT X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 1 X X X X LTU-Number 2 X X X X 3 X X X X X X X (X) X X X X 4 7 SU 0/1 4/5 connection of PCM30 with CAS connection of PCM30 with CCS/CAS connection of PCM30 with CCS primary rate access connection ATEMAIN, M:ATCO in LTU:S (1) ATETM, M:ATCO in LTU:S (1) M:OCE:N in LTU:S version 15 (2) code receiver for MFC:R2 on GPxx code receiver push button dialing on GPxx ETEAE without HW Responder Test transformer, without HW code receiver for MFC:R1 on GPxx test position TWS/LWS wake up service Software Loop TWS/LWS RM:CTC only in SU module 0 on GPxx M:ATCO in LTU:S (1) M:MCT in LTU:S Remarks

Tab. 3.126 LTU-Types for LTG in C operation

(1)

When using M:ATCO: The ATE functions occupy the LTU3. The COU function always uses LTU3. Both functionalities of the ATCO module can not work simultaneously in C operation. The two functions ATE and COU must work separately. For 31 announcement ports the LTU type U08 has to be created in LTU3. For 62 announcement ports LTU3 (master), LTU7 (slave).

(2)

362

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.4.1.5

LTU-Types for F:LTGP(B) as UI-LTG,


LTUType U08 VP0 X (X) ANWG 0 1 LTU-Number 2 3 X 4 5 (X) 6 7 SU 0/1 M:OCE:N (1) M:VPU (2) Remarks

Tab. 3.127 F:LTGP(B) as UI-LTG, LTU-Types

(1)

Stand - alone mode: For 31 announcement ports U08 in LTU3 For 62 announcement ports LTU3 master, LTU5 slave UI-LTG: LTU3 always with MODVAR=0-1, Port 0 = Testport, Port 1-31 announcement ports. LTU5 with MODVAR=0-1, or MODVAR=0-2. When MODVAR=0-2, all 32 ports are for announcements. If no MODVAR is entered for LTU type VP0, port 0-15 is assigned. If MODVAR =1-2 is entered, port 0-31 is assigned. This is a prerequisite for using 63 UI ports in the UI-LTGN.

(2)

3.4.1.6

F:LTGP(A) (backplane)
Shelf 1
SDC3 SDC2 SDC1 SDC0 PCM1 PCM1 PCM PCM0 SDC3 SDC2 SDC1 SDC0 PCM1 PCM1 PCM0 PCM0 CCG3 CCG2 CCG1 CCG0 SDC3 SDC2 SDC1 SDC0 PCM1 PCM1 PCM0 PCM0 SDC3 SDC2 SDC1 SDC0 PCM1 PCM1 PCM0 PCM0

Shelf 0
CCG3 CCG2 CCG1 CCG0 SDC3 SDC2 SDC1 SDC0 PCM1 PCM1 PCM0 PCM0 SDC3 SDC2 SDC1 SDC0 PCM1 PCM1 PCM0 PCM0

P1 P2

X1 X2

X1 X2

P3 P4 P5

SDC3 SDC2 SDC1 SDC0 PCM3 PCM3 PCM2 PCM2

SDC3 SDC2 SDC1 SDC0 PCM3 PCM3 PCM2 PCM2

SDC3 SDC2 SDC1 SDC0 PCM3 PCM3 PCM2 PCM2

SDC3 SDC2 SDC1 SDC0 PCM3 PCM3 PCM2 PCM2

SDC3 SDC2 SDC1 SDC0 PCM3 PCM3 PCM2 PCM2

SDC3 SDC2 SDC1 SDC0 PCM1 PCM1 PCM PCM0

SDC3 SDC2 SDC1 SDC0 PCM3 PCM3 PCM2 PCM2

P1 P2

SDC3 SDC2 SDC1 SDC0 PCM3 PCM3 PCM2 PCM2

D
P3 P4

331 325

307 301 293

285

261 255

237 231

201 195

177 171

163 155

131 125

3.4.1.7

F:LTGP(A) (cabling)
Connector X1 / X2 MOLOC C151P1 Port Power supply Connection To the breaker panel of the rack

Tab. 3.128 Cabling F:LTGP(A)

A30828-X1160-M-2-7620

107 101

SDC3 SDC2 SDC1 SDC0 PCM3 PCM3 PCM2 PCM2

SNOPT-1

SNOPT-1

SDC3 SDC2 SDC1 SDC0 PCM1 PCM1 PCM0 PCM0

SNOPT-0

SNOPT-0

363

Construction

Maintenance Node

Connector X1 / X2 SNOPT- 0 SNOPT- 1 SNOPT- 0 SNOPT- 1 CCG0 CCG1 CCG2 CCG3 CCG0 CCG1 CCG2 CCG3 PCM0 PCM0 PCM1 PCM1 PCM2 PCM2 PCM3 PCM3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 PCM0 PCM0 PCM1 PCM1 PCM2 PCM2 PCM3 PCM3

MOLOC C281P1 C163P2 D163P1 C293P2 D293P1 C155P1 C155P2 C155P3 C155P4 C285P1 C285P2 C285P3 C285P4 C101P1 C101P2 C101P3 C101P4 D101P1 D101P2 D101P3 D101P4 C107P1 C107P2 C107P3 C107P4 D107P1 D107P2 D107P3 D107P4 C125P1 C125P2 C125P3 C125P4 D125P1 D125P2 D125P3 D125P4

Port Power supply Optolink Optolink Optolink Optolink CCKL0 CCKL1 CCKL2 CCKL3 CCKL0 CCKL1 CCKL2 CCKL3 PCM 0-0 / 0-1 PCM 0-2 / 0-3 PCM 1-0 / 1-1 PCM 1-2 / 1-3 PCM 2-0 / 0-1 PCM 2-2 / 0-3 PCM 3-0 / 3-1 PCM 3-2 / 3-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 PCM 0-0 / 0-1 PCM 0-2 / 0-3 PCM 1-0 / 1-1 PCM 1-2 / 1-3 PCM 2-0 / 0-1 PCM 2-2 / 0-3 PCM 3-0 / 3-1 PCM 3-2 / 3-3

Connection To the breaker panel of the rack SDC interface shelf 0 --> F:SNMUX(B) SN 0 SDC interface shelf 0 --> F:SNMUX(B) SN 1 SDC interface shelf 1 --> F:SNMUX(B) SN 0 SDC interface shelf 1 --> F:SNMUX(B) SN 1 Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG PCM interface 0, 1, 2, 3 of LTG 0 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 1 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 2 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 3 of the GPP --> DLU or MDF SDC interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC interface of LTG 0, 1, 2, 3 GPP --> SN 1

PCM interface 0, 1, 2, 3 of LTG 0 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 1 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 2 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 3 of the GPP --> DLU or MDF

Tab. 3.128 Cabling F:LTGP(A)

364

A30828-X1160-M-2-7620

Maintenance Node

Construction

Connector SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 PCM0 PCM0 PCM1 PCM1 PCM2 PCM2 PCM3 PCM3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 PCM0 PCM0 PCM1 PCM1 PCM2 PCM2 PCM3 PCM3 SDC0 SDC1 SDC2 SDC3

MOLOC C131P1 C131P2 C131P3 C131P4 D131P1 D131P2 D131P3 D131P4 C171P1 C171P2 C171P3 C171P4 D171P1 D171P2 D171P3 D171P4 C177P1 C177P2 C177P3 C177P4 D177P1 D177P2 D177P3 D177P4 C195P1 C195P2 C195P3 C195P4 D195P1 D195P2 D195P3 D195P4 C201P1 C201P2 C201P3 C201P4

Port SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 PCM 0-0 / 0-1 PCM 0-2 / 0-3 PCM 1-0 / 1-1 PCM 1-2 / 1-3 PCM 2-0 / 0-1 PCM 2-2 / 0-3 PCM 3-0 / 3-1 PCM 3-2 / 3-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 PCM 0-0 / 0-1 PCM 0-2 / 0-3 PCM 1-0 / 1-1 PCM 1-2 / 1-3 PCM 2-0 / 0-1 PCM 2-2 / 0-3 PCM 3-0 / 3-1 PCM 3-2 / 3-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3

Connection SDC interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC interface of LTG 0, 1, 2, 3 GPP --> SN 1

PCM interface 0, 1, 2, 3 of LTG 0 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 1 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 2 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 3 of the GPP --> DLU or MDF SDC interface of LTG 0, 1, 2, 3 GPP --> SN

SDC interface of LTG 0, 1, 2, 3 GPP --> SN 1

PCM interface 0, 1, 2, 3 of LTG 0 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 1 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 2 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 3 of the GPP --> DLU or MDF SDC interface of LTG 0, 1, 2, 3 GPP --> SN 0

Tab. 3.128 Cabling F:LTGP(A)

A30828-X1160-M-2-7620

365

Construction

Maintenance Node

Connector SDC0 SDC1 SDC2 SDC3 PCM0 PCM0 PCM1 PCM1 PCM2 PCM2 PCM3 PCM3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 PCM0 PCM0 PCM1 PCM1 PCM2 PCM2 PCM3 PCM3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 PCM0 PCM0

MOLOC D201P1 D201P2 D201P3 D201P4 C231P1 C231P2 C231P3 C231P4 D231P1 D231P2 D231P3 D231P4 C237P1 C237P2 C237P3 C237P4 D237P1 D237P2 D237P3 D237P4 C255P1 C255P2 C255P3 C255P4 D255P1 D255P2 D255P3 D255P4 C261P1 C261P2 C261P3 C261P4 D261P1 D261P2 D261P3 D261P4 C301P1 C301P2

Port SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 PCM 0-0 / 0-1 PCM 0-2 / 0-3 PCM 1-0 / 1-1 PCM 1-2 / 1-3 PCM 2-0 / 0-1 PCM 2-2 / 0-3 PCM 3-0 / 3-1 PCM 3-2 / 3-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 PCM 0-0 / 0-1 PCM 0-2 / 0-3 PCM 1-0 / 1-1 PCM 1-2 / 1-3 PCM 2-0 / 0-1 PCM 2-2 / 0-3 PCM 3-0 / 3-1 PCM 3-2 / 3-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 PCM 0-0 / 0-1 PCM 0-2 / 0-3

Connection SDC interface of LTG 0, 1, 2, 3 GPP --> SN 1

PCM interface 0, 1, 2, 3 of LTG 0 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 1 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 2 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 3 of the GPP --> DLU or MDF SDC interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC interface of LTG 0, 1, 2, 3 GPP --> SN 1

PCM interface 0, 1, 2, 3 of LTG 0 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 1 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 2 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 3 of the GPP --> DLU or MDF SDC interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC interface of LTG 0, 1, 2, 3 GPP --> SN 1

PCM interface 0, 1, 2, 3 of LTG 0 of the GPP --> DLU or MDF

Tab. 3.128 Cabling F:LTGP(A)

366

A30828-X1160-M-2-7620

Maintenance Node

Construction

Connector PCM1 PCM1 PCM2 PCM2 PCM3 PCM3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 PCM0 PCM0 PCM1 PCM1 PCM2 PCM2 PCM3 PCM3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3

MOLOC C301P3 C301P4 D301P1 D301P2 D301P3 D301P4 C307P1 C307P2 C307P3 C307P4 D307P1 D307P2 D307P3 D307P4 C325P1 C325P2 C325P3 C325P4 D325P1 D325P2 D325P3 D325P4 C331P1 C331P2 C331P3 C331P4 D331P1 D331P2 D331P3 D331P4

Port PCM 1-0 / 1-1 PCM 1-2 / 1-3 PCM 2-0 / 0-1 PCM 2-2 / 0-3 PCM 3-0 / 3-1 PCM 3-2 / 3-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 PCM 0-0 / 0-1 PCM 0-2 / 0-3 PCM 1-0 / 1-1 PCM 1-2 / 1-3 PCM 2-0 / 0-1 PCM 2-2 / 0-3 PCM 3-0 / 3-1 PCM 3-2 / 3-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3

Connection PCM interface 0, 1, 2, 3 of LTG 1 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 2 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 3 of the GPP --> DLU or MDF SDC interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC interface of LTG 0, 1, 2, 3 GPP --> SN 1

PCM interface 0, 1, 2, 3 of LTG 0 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 1 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 2 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 3 of the GPP --> DLU or MDF SDC interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC interface of LTG 0, 1, 2, 3 GPP --> SN 1

Tab. 3.128 Cabling F:LTGP(A)

A30828-X1160-M-2-7620

367

Construction

Maintenance Node

3.4.1.8

F:LTGP(B) (backplane)
Shelf 1
SDC3 SDC2 SDC1 SDC0 PCM1 PCM1 PCM0 PCM0 SDC3 SDC2 SDC1 SDC0 PCM1 PCM1 PCM0 PCM0 CCG3 CCG2 CCG1 CCG0 SDC3 SDC2 SDC1 SDC0 PCM1 PCM1 PCM0 PCM0 SDC3 SDC2 SDC1 SDC0 PCM1 PCM1 PCM0 PCM0

Shelf 0
CCG3 CCG2 CCG1 CCG0 SDC3 SDC2 SDC1 SDC0 PCM1 PCM1 PCM0 PCM0 SDC3 SDC2 SDC1 SDC0 PCM1 PCM1 PCM0 PCM0

P1 P2

X1 X2

X1 X2

P4 P5

SDC3 SDC2 SDC1 SDC0 PCM3 PCM3 PCM2 PCM2

SDC3 SDC2 SDC1 SDC0 PCM3 PCM3 PCM2 PCM2

SDC3 SDC2 SDC1 SDC0 PCM3 PCM3 PCM2 PCM2

SDC3 SDC2 SDC1 SDC0 PCM3 PCM3 PCM2 PCM2

SDC3 SDC2 SDC1 SDC0 PCM3 PCM3 PCM2 PCM2

P1 P2

SDC3 SDC2 SDC1 SDC0 PCM3 PCM3 PCM2 PCM2

SDC3 SDC2 SDC1 SDC0 PCM3 PCM3 PCM2 PCM2

SNOPT-1

SNOPT-1

P3 P4

331 325

307 301 293

285

261 255

237 231

201 195

177 171

163 155

131 125

3.4.1.9

F:LTGP(B) (cabling)
Connector X1 / X2 X1 / X2 SNOPT- 0 SNOPT- 1 SNOPT- 0 SNOPT- 1 CCG0 CCG1 CCG2 CCG3 CCG0 CCG1 CCG2 CCG3 TRACER OCA VPU0 VPU1 MOLOC C151P1 C281P1 C163P2 D163P1 C293P2 D293P1 C155P1 C155P2 C155P3 C155P4 C285P1 C285P2 C285P3 C285P4 C109P1 D109P2 D109P3 D109P4 Port Power supply Power supply Optolink Optolink Optolink Optolink CCKL0 CCKL1 CCKL2 CCKL3 CCKL0 CCKL1 CCKL2 CCKL3 SPH 2...7,9,10 Transmit/Receive Transmit/Receive Transmit/Receive Connection To the breaker panel of the rack To the breaker panel of the rack SDC interface shelf 0 --> F:SNMUX(B) SN 0 SDC interface shelf 0 --> F:SNMUX(B) SN 1 SDC interface shelf 1 --> F:SNMUX(B) SN 0 SDC interface shelf 1 --> F:SNMUX(B) SN 1 Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG Tracer connection for communication between UI_LTG and subscriber. Ethernet cable OCANEQ Ethernet cable VPU 0 Ethernet cable VPU 1

Tab. 3.129 Cabling F:LTGP(B)

368

A30828-X1160-M-2-7620

109

VPU0 VPU1

OCA

TRACER

P3

SDC3 SDC2 SDC1 SDC0 PCM1 PCM1 PCM0 PCM0

SNOPT-0

SNOPT-0

Maintenance Node

Construction

Connector PCM0 PCM0 PCM1 PCM1 PCM2 PCM2 PCM3 PCM3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 PCM0 PCM0 PCM1 PCM1 PCM2 PCM2 PCM3 PCM3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 PCM0 PCM0 PCM1 PCM1 PCM2 PCM2

MOLOC C125P1 C125P2 C125P3 C125P4 D125P1 D125P2 D125P3 D125P4 C131P1 C131P2 C131P3 C131P4 D131P1 D131P2 D131P3 D131P4 C171P1 C171P2 C171P3 C171P4 D171P1 D171P2 D171P3 D171P4 C177P1 C177P2 C177P3 C177P4 D177P1 D177P2 D177P3 D177P4 C195P1 C195P2 C195P3 C195P4 D195P1 D195P2

Port PCM 0-0 / 0-1 PCM 0-2 / 0-3 PCM 1-0 / 1-1 PCM 1-2 / 1-3 PCM 2-0 / 0-1 PCM 2-2 / 0-3 PCM 3-0 / 3-1 PCM 3-2 / 3-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 PCM 0-0 / 0-1 PCM 0-2 / 0-3 PCM 1-0 / 1-1 PCM 1-2 / 1-3 PCM 2-0 / 0-1 PCM 2-2 / 0-3 PCM 3-0 / 3-1 PCM 3-2 / 3-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 PCM 0-0 / 0-1 PCM 0-2 / 0-3 PCM 1-0 / 1-1 PCM 1-2 / 1-3 PCM 2-0 / 0-1 PCM 2-2 / 0-3

Connection PCM interface 0, 1, 2, 3 of LTG 0 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 1 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 2 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 3 of the GPP --> DLU or MDF SDC interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC interface of LTG 0, 1, 2, 3 GPP --> SN 1

PCM interface 0, 1, 2, 3 of LTG 0 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 1 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 2 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 3 of the GPP --> DLU o r MDF SDC interface of LTG 0, 1, 2, 3 GPP --> SN

SDC interface of LTG 0, 1, 2, 3 GPP --> SN 1

PCM interface 0, 1, 2, 3 of LTG 0 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 1 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 der LTG 2 of the GPP --> DLU or MDF

Tab. 3.129 Cabling F:LTGP(B)

A30828-X1160-M-2-7620

369

Construction

Maintenance Node

Connector PCM3 PCM3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 PCM0 PCM0 PCM1 PCM1 PCM2 PCM2 PCM3 PCM3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 PCM0 PCM0 PCM1 PCM1 PCM2 PCM2 PCM3 PCM3 SDC0 SDC1 SDC2 SDC3

MOLOC D195P3 D195P4 C201P1 C201P2 C201P3 C201P4 D201P1 D201P2 D201P3 D201P4 C231P1 C231P2 C231P3 C231P4 D231P1 D231P2 D231P3 D231P4 C237P1 C237P2 C237P3 C237P4 D237P1 D237P2 D237P3 D237P4 C255P1 C255P2 C255P3 C255P4 D255P1 D255P2 D255P3 D255P4 C261P1 C261P2 C261P3 C261P4

Port PCM 3-0 / 3-1 PCM 3-2 / 3-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 PCM 0-0 / 0-1 PCM 0-2 / 0-3 PCM 1-0 / 1-1 PCM 1-2 / 1-3 PCM 2-0 / 0-1 PCM 2-2 / 0-3 PCM 3-0 / 3-1 PCM 3-2 / 3-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 PCM 0-0 / 0-1 PCM 0-2 / 0-3 PCM 1-0 / 1-1 PCM 1-2 / 1-3 PCM 2-0 / 0-1 PCM 2-2 / 0-3 PCM 3-0 / 3-1 PCM 3-2 / 3-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3

Connection PCM interface 0, 1, 2, 3 der LTG 3 of the GPP --> DLU or MDF SDC interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC interface of LTG 0, 1, 2, 3 GPP --> SN 1

PCM interface 0, 1, 2, 3 of LTG 0 of the GPP --> DLU oder MDF PCM interface 0, 1, 2, 3 of LTG 1 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 2 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 3 of the GPP --> DLU or MDF SDC interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC interface of LTG 0, 1, 2, 3 GPP --> SN 1

PCM interface 0, 1, 2, 3 of LTG 0 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 der LTG 1 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 der LTG 2 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 der LTG 3 of the GPP --> DLU or MDF SDC interface of LTG 0, 1, 2, 3 GPP --> SN 0

Tab. 3.129 Cabling F:LTGP(B)

370

A30828-X1160-M-2-7620

Maintenance Node

Construction

Connector SDC0 SDC1 SDC2 SDC3 PCM0 PCM0 PCM1 PCM1 PCM2 PCM2 PCM3 PCM3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 PCM0 PCM0 PCM1 PCM1 PCM2 PCM2 PCM3 PCM3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3

MOLOC D261P1 D261P2 D261P3 D261P4 C301P1 C301P2 C301P3 C301P4 D301P1 D301P2 D301P3 D301P4 C307P1 C307P2 C307P3 C307P4 D307P1 D307P2 D307P3 D307P4 C325P1 C325P2 C325P3 C325P4 D325P1 D325P2 D325P3 D325P4 C331P1 C331P2 C331P3 C331P4 D331P1 D331P2 D331P3 D331P4 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3

Port

Connection SDC interface of LTG 0, 1, 2, 3 GPP --> SN 1

PCM 0-0 / 0-1 PCM 0-2 / 0-3 PCM 1-0 / 1-1 PCM 1-2 / 1-3 PCM 2-0 / 0-1 PCM 2-2 / 0-3 PCM 3-0 / 3-1 PCM 3-2 / 3-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 PCM 0-0 / 0-1 PCM 0-2 / 0-3 PCM 1-0 / 1-1 PCM 1-2 / 1-3 PCM 2-0 / 0-1 PCM 2-2 / 0-3 PCM 3-0 / 3-1 PCM 3-2 / 3-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3

PCM interface 0, 1, 2, 3 of LTG 0 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 1 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 2 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 3 of the GPP --> DLU or MDF SDC interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC interface of LTG 0, 1, 2, 3 GPP --> SN 1

PCM interface 0, 1, 2, 3 of LTG 0 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 1 of the GPP --> DLU oder MDF PCM interface 0, 1, 2, 3 of LTG 2 of the GPP --> DLU or MDF PCM interface 0, 1, 2, 3 of LTG 3 of the GPP --> DLU or MDF SDC interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC interface der LTG 0, 1, 2, 3 GPP --> SN 1

Tab. 3.129 Cabling F:LTGP(B)

A30828-X1160-M-2-7620

371

Construction

Maintenance Node

3.4.2 3.4.2.1

F:LTGN F:LTGN(A) (module side)


LTG 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

D
GPNx GPNx GPNx GPNx GPNx GPNx GPNx GPNx GPNx GPNx GPNx GPNx GPNx GPNx GPNx C325 GPNx C341

C101

C117

C133

C149

C165

C181

C197

C213

C229

C245

C261

C277

C293

GPN types GPNLD (-Q28-X200-) GPNLE (-Q28-X600-) GPNYC (-Q27-) GPNYD (-Q27-X200-) GPNYE (-Q27-X600-) GPNZC (-Q26-) GPNZD (-Q26-X200-) GPNZE (-Q26-X600-)

Remarks for LDI local DLU interface with 32MByte memory for LDI local DLU interface with 64MByte memory for PCM30 with 16MByte memory (without SILC-component) for PCM30 with 32MByte memory (with SILC-component) for PCM30 with 64MByte memory (with SILC-component) for PCM24 with 16MByte memory (without SILC-component) for PCM24 with 32MByte memory (with SILC-component) for PCM24 with 64MByte memory (with SILC-component)

Tab. 3.130 Basic types of GPN modules

372

A30828-X1160-M-2-7620

C309

Maintenance Node

Construction

3.4.2.2

F:LTGN(B) (module side)


LTG 0 1 2 3 4 5 6 7

C C

D
LTU:S LTU:S LTU:S LTU:S LTU:S LTU:S LTU:S LTU:S C325 GPNx GPNx GPNx GPNx GPNx GPNx GPNx GPNx C341

C101

C117

C133

C149

C165

C181

C197

C213

C229

C245

C261

C277

C293

GPN types GPNLD (-Q28-X200-) GPNLE (-Q28-X600-) GPNYC (-Q27-) GPNYD (-Q27-X200-) GPNYE (-Q27-X600-) GPNZC (-Q26-) GPNZD (-Q26-X200-) GPNZE (-Q26-X600-)

Remarks for LDI local DLU interface with 32MByte memory for LDI (local DLU interface with 64MByte memory for PCM30 with 16MByte memory (without SILC-component) for PCM30 with 32MByte memory (with SILC-component) for PCM30 with 64MByte memory (with SILC-component) for PCM24 with 16MByte memory (without SILC-component) for PCM24 with 32MByte memory (with SILC-component) for PCM24 with 64MByte memory (with SILC-component)

Tab. 3.131 Basic types of GPN modules

Modules LTU:S ATCO (-Q267-) ATE:N (-Q94-) COUC (-Q31-) DEC120 (-Q1467-) MCT (-Q63-) MDTOG (-Q1490-) PHMA (-Q1469-) OCE:N (-Q165-)

Remarks Automatic Test and Conference Unit for LTGM/N Automatic Test Equipment for LTGN/M Conference Unit C (up to 32 subscriber Digital Echo Compensator Mid Call Trigger Modem and Ton Generator Packet Handler Module A (High performance SILC) OCANEQ: speech controller and memory for LTGN

Tab. 3.132 Modules with display and switches in LTU:S

C309

A30828-X1160-M-2-7620

373

Construction

Maintenance Node

3.4.2.3

F:LTGN(C) (module side)


LTG 0 LTG 1

D
OCE:N OCE:N VPU 0 VPU 1 VPU 0 VPU 1 C301 GPNx GPNx C255

C107

C127

C147

C167

C235

GPN types GPNLD (-Q28-X200-) GPNLE (-Q28-X600-) GPNYD (-Q27-X200-) GPNYE (-Q27-X600-)

Remarks for LDI (local DLU interface with 32MByte memory) for LDI (local DLU interface with 64MByte memory for PCM30 with 32MByte memory (with SILC-component) for PCM30 with 64MByte memory (with SILC-component)

Tab. 3.133 Basic types of GPN modules

MOLOC VPU (-Q190-) OCE:N (-Q165-) Voice Processing Unit

Remarks

OCANEQ: speech controller and memory for LTGN

Tab. 3.134 Modules with display and switches in LTGN(C)

374

A30828-X1160-M-2-7620

C281

Maintenance Node

Construction

3.4.2.4

LTU-types for F:LTGN in B operation


LTUType D30 APPLIC 0 CASCAS CCSCAS CCSCCS CASRCA CCSDLU EXTDLU CCSLDI EXTLDI V52IF CCSPA ATE ATM U08 V01 V02 V03 V03 V04 V05 V05 V06 V08 V09 V09 V10 V10 V11 V15 V99 Y25 MCT INS PMA X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 1 X X X X X X X LTU-Number 2 X X X X X X X X X X 3 X X X X X X X X X X X X (X) X X X X X X X 4 5 6 7 SU 0/1 connection of PCM30 with CAS connection of PCM30 with CCS/CAS connection of PCM30 with CCS announcement connection connection DLU with CCS connection DLU (extension) local DLU connection with CCS local DLU connection (extension) V5.2 interface primary rate access connection TEM:LE - function (1) ATE:TM - function (1) M:OCE:N in LTU:S version15 (2) code receiver for MFC:R2 code receiver push button dialing CRP code receiver push button dialing CRP TLFB trunk test with SULIM ETEAE version 13, without HW Responder (1) Test transformer, without HW code receiver for MFC:R1 (a-law) test position TWS/LWS (3) code receiver push button dialing CRP TLF/RBS wake up service / RSCI CME TWS/LWS M:MDTOG in LTU:S RM:CTC only in SU module 0 M:COUC / M:ATOCO (1) M:MCT in LTU:S SILC-function on GPNxx M:PHMA in LTU:S (expanded SILC-function) Remarks

Tab. 3.135 LTU-Types for F:LTGN in B operation

A30828-X1160-M-2-7620

375

Construction

Maintenance Node

(1)

When using M:ATCO: The ATE functions occupy the LTU5. The COU function always uses LTU3. Both functionalities of the ATCO module can work simultaneously in B operation. For 31 announcement ports U08 in LTU3 For 62 announcement ports LTU3 master, LTU5 slave Do not equip LTU 3 if LTU type V08 has been created.

(2)

(3)

3.4.2.5

LTU-types for F:LTGN in C operation


LTUType D30 APPLIC 0 CASCAS CCSCAS CCSCCS CASRCA ATE ATM U08 V01 V02 V04 V05 V05 V06 V08 V10 V10 V11 V99 Y22 Y25 MCT X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 1 X X X X LTU-Number 2 X X X X 3 X X X X X X X (X) X X X X 4 7 SU 0/1 4/5 connection of PCM30 with CAS connection of PCM30 with CCS/CAS connection of PCM30 with CCS announcement connection TEM:LE - function ATE:TM - function M:OCE:N in LTU:S version 15 (1) code receiver for MFC:R2 code receiver push button dialing CRP ETEAE version 13, without HW Responder Test transformer, without HW code receiver for MFC:R1 (a-law) test position TWS/LWS wake up service software Loop TWS/LWS RM:CTC only in SU module 0 M:COUC in LTU:S < version 12 M:COUC in LTU:S version 12 M:MCT in LTU:S Remarks

Tab. 3.136 LTU-Types for LTGN in C operation

(1)

When using M:ATCO: The ATE functions occupy the LTU3. The COU function always uses LTU3. Both functionalities of the ATCO module can not work simultaneously in C operation. The two functions ATE and COU must work separately. For 31 announcement ports the LTU type U08 has to be created in LTU3. For 62 announcement ports LTU3 (master), LTU7 (slave).

(2)

376

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.4.2.6

LTU-types for F:LTGN(C) as UI-LTGN


LTUType U08 VP0 X (X) APPLIC 0 1 LTU-Number 2 3 X 4 5 (X) 6 7 SU 0/1 M:OCE:N version 15 (1) M:VPU version 15 (2) Remarks

Tab. 3.137 LTU-Types for F:LTGN(C) as UI-LTGN

(1)

Stand - alone mode: For 31 announcement ports U08 in LTU3 For 62 announcement ports LTU3 master, LTU5 slave UI-LTG: LTU3 always with MODVAR=0-1, Port 0 = Testport, Port 1-31 announcement ports. LTU5 with MODVAR=0-1, or MODVAR=0-2. When MODVAR=0-2, all 32 ports are for announcements. If no MODVAR is entered for LTU type VP0, port 0-15 is assigned. If MODVAR =1-2 is entered, port 0-31 is assigned. This is a prerequisite for using 63 UI ports in the UI-LTGN.

(2)

3.4.2.7

F:LTGN(A) (backplane)
LTG 15
P1 P2 C1 C2 C3 C4 C5 D1 D2 D3

14

13
C1 C1 C2 C2 C3 C3 C4 C4 C5 C5 D1 D1 D2 D2 D3 D3

12
C1 C2 C3 C4 C5 D1 D2 D3

11
C1 C2 C3 C4 C5 D1 D2 D3

10

8
C1 C2 C3 C4 C5 D1 D2 D3

7
C1 C2 C3 C4 C5 D1 D2 D3

5
C1 C1 C1

4
C1 C2 C3 C4 C5 D1 D2 D3

3
C1 C2 C3 C4 C5 D1 D2 D3

0
C1 C2 C3 C4 C5 D1 D2 D3

C1 C1 C1 C2 C2 C2 C3 C3 C3 C4 C4 C4 C5 C5 C5 D1 D1 D1 D2 D2 D2 D3 D3 D3

C1 C1 C1 C2 C2 C2 C3 C3 C3 C4 C4 C4 C5 C5 C5 D1 D1 D1 D2 D2 D2 D3 D3 D3

C2 C2 C2 C3 C3 C3 C4 C4 C4 C5 C5 C5 D1 D1 D1 D2 D2 D2 D3 D3 D3

P3 P4 P5 P1 P2

D
P3 P4

341

325

317 309

293

277

261

253 245

229

213

197

189 181

165

149

133

125 117

A30828-X1160-M-2-7620

377

101

Construction

Maintenance Node

3.4.2.8

F:LTGN(A) (cabling)
Connector C1/C2 MOLOC C101P1, C117P1, C133P1, C149P1, C165P1, C181P1, C197P1, C213P1, C229P1, C245P1, C261P1, C277P1, C293P1, C309P1, C325P1, C341P1 C101P3, C117P3, C133P3, C149P3, C165P3, C181P3, C197P3, C213P3, C229P3, C245P3, C261P3, C277P3, C293P3, C309P3, C325P3, C341P3 C101P5, C117P5, C133P5, C149P5, C165P5, C181P5, C197P5, C213P5, C229P5, C245P5, C261P5, C277P5, C293P5, C309P5, C325P5, C341P5 D101P2, D117P2, D133P2, D149P2, D165P2, D181P2, D197P2, D213P2, D229P2, D245P2, D261P2, D277P2, D293P2, D309P2, D325P2, D341P2 C101P1, C117P1, C133P1, C149P1, C165P1, C181P1, C197P1, C213P1, C229P1, C245P1, C261P1, C277P1, C293P1, C309P1, C325P1, C341P1 C101P5, C117P5, C133P5, C149P5, C165P5, C181P5, C197P5, C213P5, C229P5, C245P5, C261P5, C277P5, C293P5, C309P5, C325P5, C341P5 C125P1, C189P1, C253P1, C317P1 C125P5, C189P5, C253P5, C317P5 LTGN(A) Cable LDI 0 to DLU

C3/C4

Cable LDI 1 to DLU

C5/D1

Cable LDI 2 to DLU

D2/D3

Cable LDI 3 to DLU

C1/C2/C3/C4

Cable PCM to MDF

C5

Clock supply cable to CCG

C1/C2/C3/C4 C5/D1/D2/D3

Cable to SN 0 or TSG 0-x Cable to SN 1 or TSG 1-x

Tab. 3.138 Cabling F:LTGN(A)

378

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.4.2.9

F:LTGN(B) (backplane)
LTG
P1 P2

7
C1 C2 C3 C4 C5 D1 D2 D3 C1 C2 C3 C4 C5 D1 D2 D3

5
C1 C1 C2 C2 C3 C3 C4 C4 C5 C5 D1 D1 D2 D2 D3 D3

4
C1 C2 C3 C4 C5 D1 D2 D3

3
C1 C2 C3 C4 C5 D1 D2 D3

2
C1 C2 C3 C4 C5 D1 D2 D3

1
C1 C1 C2 C2 C3 C3 C4 C4 C5 C5 D1 D1 D2 D2 D3 D3

0
C1 C2 C3 C4 C5 D1 D2 D3

P3 P4 P5 P1 P2

D
P3 P4

341

309

285 277

245

213

181

157 149

3.4.2.10

F:LTGN(B) (cabling)
Connector C1/C2 MOLOC C117P1, C149P1, C181P1, C213P1, C245P1, C277P1, C309P1, C341P1 C117P3, C149P3, C181P3, C213P3, C245P3, C277P3, C309P3, C341P3 C117P5, C149P5, C181P5, C213P5, C245P5, C277P5, C309P5, C341P5 D2/D3 D117P2, D149P2, D181P2, D213P2, D245P2, D277P2, D309P2, D341P2 C117P1, C149P1, C181P1, C213P1, C245P1, C277P1, C309P1, C341P1 C117P5, C149P5, C181P5, C213P5, C245P5, C277P5, C309P5, C341P5 C157P1, C285P1 C157P5, C285P5 Cable LDI 3 to DLU LTGN(B) Cable LDI 0 to DLU

C3/C4

Cable LDI 1 to DLU

C5/D1

Cable LDI 2 to DLU

C1/C2/C3/C4

Cable PCM to MDF

C5

Clock supply cable to CCG

C1/C2/C3/C4 C5/D1/D2/D3

Cable to SN 0 or TSG 0-x Cable to SN 1 or TSG 1-x

Tab. 3.139 Cabling F:LTGN(B)

117

A30828-X1160-M-2-7620

379

Construction

Maintenance Node

3.4.2.11

F:LTGN(C) (backplane)
P1 P2

P3 P4 P5 P1 P2 P3 P4 SN 0 SN 1

00 01 02 03 04

10 11 12 13 14

SN 0 SN 1

247

223

3.4.2.12

F:LTGN(C) (cabling)
LTG MOLOC 00 / C223P1 01 / C223P2 02 / C223P2 03 / C223P3 04 / C223P3 10 / D223P1 11 / D223P2 12 / D223P2 13 / D223P3 14 / D223P3 SN0 / D119P2, SN0 / D247P2 SN1 / D119P3, SN1 / D247P3 Ethernet-cable VPU 0-0 Ethernet-cable VPU 0-1 Ethernet-cable VPU 0-2 Ethernet-cable VPU 0-3 Ethernet-cable OCANEQ 0 Ethernet-cable VPU 1-0 Ethernet-cable VPU 1-1 Ethernet-cable VPU 1-2 Ethernet-cable VPU 1-3 Ethernet-cable OCANEQ 1 Cable to SN0 or TSG0-X Cable to SN1 or TSG1-X LTGN(C)

Tab. 3.140 Cabling F:LTGN(C)

380

A30828-X1160-M-2-7620

119

Maintenance Node

Construction

3.4.3 3.4.3.1

F:LTGM(A) F:LTGM(A) (module side)


LTG 0 1 2 3 4

D
GSMxxx GSMxxx GSMxxx GSMxxx GSMxxx C331 GPLxx GPLxx GPLxx GPLxx GPLxx C343 LTU:S LTU:S LTU:S LTU:S LTU:S C317 LTU LTU LTU LTU LTU C305

C151

C189

C127

C139

C177

C203

C215

C255

C101

C113

C163

C229

C241

C267

C281

GPL Type GPLC (-Q1349-X301-) GPLD (-Q1349-X401-) GPLSD (-Q1339-X401-) GPLSE (-Q1339-X601-)

Remarks with 16MByte Memory (without SILC-component) with 32MByte Memory (without SILC-component) with 32MByte Memory (with SILC-component) with 64MByte Memory (with SILC-component)

Tab. 3.141 Basic types of GPL modules

Modules LTU:S ATCO (-Q267-) ATE:N (-Q94-) COUC (-Q31-) DEC120 (-Q1467-) MCT (-Q63-) MDTOG (-Q1490-) PHMA (-Q1469-)

Remarks Automatic Test and Conference Unit for LTGM/N Automatic Test Equipment for LTGN/M Conference Unit C (up to 32 subscriber Digital Echo Compensator Mid Call Trigger Modem and Ton Generator Packet Handler Module A (High performance SILC)

Tab. 3.142 Modules with display and switches in LTU:S

C293

A30828-X1160-M-2-7620

381

Construction

Maintenance Node

3.4.3.2

LTU-types for F:LTGM(A) in B operation


LTUType D30 APPLIC 0 CASCAS CCSCAS CCSCCS CASRCA CCSDLU EXTDLU CCSLDI EXTLDI CCSPA V52IF ATE ATM V01 V02 V03 V03 V04 V05 V05 V06 V08 V09 V09 V10 V10 V11 V15 V99 Y25 INS PMA X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 1 X X X X X X X X X X LTU-Number 2 X X X X X X 3 X X X X X X X X X X X X X X X X X X X X 4 5 6 7 SU 0/1 connection for PCM30 with CAS connection for PCM30 with CCS/CAS connection for PCM30 with CCS announcement connection connection DLU with CCS connection DLU (extension) connection DLU with CCS connection DLU (extension) connection for Primary Rate Access V5.2 Interface TEM:LE - function (1) ATE:TM - function (1) code receiver for MFC:R2 (2) code receiver push button dialing CRP (2) code receiver push button dialing CRP (2) TLFB trunk test with SULIM ETEAE version 13, without HW Responder (1) Testtransformer, without HW code receiver for MFC:R1 (2) test position TWS/LWS (3) code receiver push button dialing CRP (2) TLF/RBS wake up service/ RSCI CME TWS/LWS M:MDTOG in LTU:S RM:CTC only in SU module 0 (2) M:COUC / M:ATCO (1) V5.2 without 2. SILC-function V5.2 with extension SILC-function M:PHMA in LTU:S X M:MTC in LTU:S Remarks

MTC

Tab. 3.143 LTU-Types for F:LTGM(A) in B operation

382

A30828-X1160-M-2-7620

Maintenance Node

Construction

(1)

When using M:ATCO: The ATE functions occupy the LTU5. The COU function always uses LTU3. Both functionalities of the ATCO module can work simultaneously in B operation. the code receiver are placed on the module GSMxxxx LTU 3 must be kept free when LTU type V08 is created

(2) (3)

3.4.3.3

LTU-types for F:LTGM(A) in C operation


LTUType D30 APPLIC 0 CASCAS CCSCAS CCSCCS CASRCA ATE ATM V01 V02 V04 V05 V05 V06 V08 V10 V10 V11 V99 Y25 MCT X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X LTU-Number 1 X X X X 2 X X X X 3 X X X X X X X X X X 4 7 0/1 SU 4/5 connection for PCM30 with CAS connection for PCM30 with CCS/CAS connection for PCM30 with CCS announcement connection TEM:LE - function (1) ATE:TM - function (1) code receiver for MFC:R2 (2) code receiver for push button dialing CRP (2) ETEAE version 13, without HW Responder (1) Testtransformer, without HW code receiver for MFC:R1 (2) test position TWS/LWS wake up service SW-LOOP TWS/LWS RM:CTC only in SU module 0 (1) M:COUC / M:ATCO (1) M:MTC in LTU:S Remarks

Tab. 3.144 LTU-Types for F:LTGM(A) in C operation

(1)

When using M:ATCO: The ATE functions occupy the LTU3. The COU function always uses LTU3. Both functionalities of the ATCO module can not work simultaneously in C operation. The two functions ATE and COU must work separately. the code receiver are placed on the module GSMxxxx

(2)

A30828-X1160-M-2-7620

383

Construction

Maintenance Node

3.4.3.4

F:LTGM(A) (backplane)

SN 0

SN 0

SN 0

SN 0

DCC

DCC

SN 0

DCC

P2

LDI 1

LDI 1

LDI 1

LDI 1

SN 1

SN 1

P4 P5

SN 1

SN 1

LDI 2

LDI 2

P1 P2

LDI 2

LDI 2

LDI 3

LDI 3

LDI 3

D
P3 P4

LTGM 4

LTGM 3

LTGM 2

LTGM 1

LDI 3

LTGM 0

3.4.3.5

F:LTGM(A) (cabling)
Connector SN 0 C127P1, C177P1, C229P1, C281P1, C331P1 SN 1 C127P3, C177P3, C229P3, C281P3, C331P3 DCC C101P1, C151P1, C203P1, C255P1, C305P1 LDI 1 C101P3, C151P3, C203P3, C255P3, C305P3 LDI 2 C101P5, C151P5, C203P5, C255P5, C305P5 LDI 3 D101P3, D151P3,D203P3, D255P3, D305P3 LTGM(A) Cable to SN 0 or TSG 0-x

Cable to SN 1 or TSG 1-x

Cable to fuse panel (power supply -48/60V)

Cable to DLU or cable to MDF

Cable to DLU or cable to MDF

Cable to DLU or clock supply to CCG

Tab. 3.145 Cabling F:LTGM(A)

384

A30828-X1160-M-2-7620

LDI 3

LDI 2

LDI 1

SN 1

P3

DCC

DCC

P1

Maintenance Node

Construction

3.4.4 3.4.4.1

F:LTGG(A) F:LTGG(A) with DIU30 in B operation (module side)


left LTGG right LTGG

B
A001 DCCDE A060 CR0/1 A008 LTU 0 A018 LTU 2 A023 LTU 3 A028 LTU 4 A071 LTU 1 A038 GSL A123 DCCDE A043 CGSM A101 CGSM A066 LTU 0 A033 TOG A091 TOG A118 CR0/1 A054 SILCx A013 LTU 1 A048 PMUx A076 LTU 2 A086 LTU 4 A106 PMUx A096 GSL A112 SILCx A081 LTU 3

When TOGD is used, MOLOC A060 or A118 in the SU cannot be used. The module TOGD has the function of both TOG and CTC.

Modules with displays and switches in F:LTGG(A) DCCDE (-Q5862-E) PMUx (-Q1141-) CRM8:R2 (-Q1105-) ETEAE (-Q670-) SCR (-Q1445-) TOGC (-Q1290-) PMUE (-Q1141-X600-) CRP8 (-Q1105-) OCE:MUPx (-Q1030-) TEM:LE (-Q607-) TOGD (-Q1291-) SILCB (-Q1110-) DIU30D (-Q876-) OCE:SPC (-Q1031-) CGSM (-Q1185-) ATE:TM (-Q969-) DIU:LDIB (-Q1107-) OCE:SPM (-Q1401-)

Tab. 3.146 Modules with displays and switches in F:LTGG(A)

A30828-X1160-M-2-7620

385

Construction

Maintenance Node

3.4.4.2

LTU-types for F:LTGG(A) with DIU30 in B operation


LTUType D30 APPLIC 0 CASCAS CCSCAS CCSCCS CASRCA CCSDLU EXTDLU CCSLDI EXTLDI CCSPA ATE ATM U07 X X X X X X X X X X 1 X X X X X X X X X X X X X X X X LTU-Number 2 X X X X X X 3 X X X X X X 4 5 6 7 SU 0/1 connection for PCM30 with CAS connection for PCM30 with CCS/CAS connection for PCM30 with CCS announcement connection connection DLU with CCS connection DLU (extension) LDI Application: LTU 0+2 and/or 1+3 primary rate access connection M:TEM:LE M:ATE:TM see: Variants for INDAS for F:LTGG(A) in B operation X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X code receiver for MFC:R2 code receiver for push button dialing CRP code receiver for push button dialing CRP TLFB trunk test with SULIM ETEAE Responder without HW code receiver for MFC:R1 test position TWS/LWS (1) code receiver for push button dialing CRP TLF/RBS wake up service / RSCI CME TWS/LWS M:MDTOG in LTU:S RM:CTC only in SU module 0 M:COUB Remarks

V01 V02 V03 V03 V04 V05 V05 V06 V08 V09 V09 V10 V10 V11 V15 V99 Y22

Tab. 3.147 LTU-Types for F:LTGG(A) with DIU30 in B operation

(1)

LTU 2 must be kept free when LTU type V08 is created in LTU 6.

386

A30828-X1160-M-2-7620

Maintenance Node

Construction

variants for OCE:SPC and OCE:MUPx MOLOC 1 LTU1 LTU2 LTU3 LTU4 OCE:SPCx OCE:MUPx OCE:SPC OCE:SPC OCE:MUPx OCE:MUPx OCE:SPC OCE:MUPx 2 3 4 OCE:MUPx OCE:SPC OCE:SPC OCE:MUPx

variants for OCE:SPM

OCE:SPM

Tab. 3.148 Variants for INDAS for F:LTGG(A) in B operation

3.4.4.3

F:LTGG(A) with DIU30 in B operation (backplane)

SN 0 / A101

SN 0 / A043

LTE / A081

LTE / A071

LTE / A076

LTE / A066

LTE / A023

LTE / A013 CCG / B013

LTE / A018

CCG / B071

CCG / B066

CCG / B023

SN 1 / B101

CCG / B081

SN 1 / B043

CCG / B076

right LTGG

left LTGG

3.4.4.4

F:LTGG(A) with DIU30 in B operation (cabling)


Connector LTE / A008 LTE / A013 LTE / A018 LTE / A023 CCG / B008 CCG / B013 CCG / B018 CCG / B023 SN 0 / A043 SN 1 / B043 LTE / A066 LTE / A071 DIU 0 cable to MDF DIU 1 cable to MDF DIU 2 cable to MDF DIU 3 cable to MDF Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Cable to SN 0 or TSG 0-x Cable to SN 1 or TSG 1-x DIU 0 cable to MDF DIU 1 cable to MDF LTGG(A)

Tab. 3.149 Cabling F:LTGG(A) with DIU30 in B operation

CCG / B018

CCG / B008

LTE / A008

A30828-X1160-M-2-7620

387

Construction

Maintenance Node

Connector LTE / A076 LTE / A081 CCG / B066 CCG / B071 CCG / B076 CCG / B081 SN 0 / A101 SN 1 / B101 DIU 2 cable to MDF DIU 3 cable to MDF Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Cable to SN 0 or TSG 0-x Cable to SN 1 or TSG 1-x

LTGG(A)

Tab. 3.149 Cabling F:LTGG(A) with DIU30 in B operation

3.4.4.5

F:LTGG(A) with DIU30 in C operation (module side)

left LTGG A

right LTGG

DCCDE

A081

A043

A076

A096

A048

A101

A013

A086

A106

A033

A066

A091

A118

A038

A001

A023

A008

A028

When TOGD is used, MOLOC A028 or A086 in the SU cannot be used. The module TOGD has be function of both TOG and CTC.

A018

Modules with displays and switches in F:LTGG(A) DCCDE (-Q5862-E) PMUx (-Q1141-) CRM8:R2 (-Q1105-) ETEAE (-Q670-) TOGC (-Q1290-) PMUE (-Q1141-X600-) CRP8 (-Q1105-) OCE:MUPx (-Q1030-) TOGD (-Q1291-) ATE:TM (-Q969-) DIU30D (-Q876-) OCE:SPC (-Q1031-) CGSM (-Q1185-) SCR (-Q1445-) TEM:LE (-Q607-) OCE:SPM (-Q1401-)

Tab. 3.150 Modules with displays and switches in F:LTGG(A)

A060

A071

388

A30828-X1160-M-2-7620

A123

DCCDE

CGSM

CGSM

CR0/1

CR4/5

CR0/1

CR4/5

PMUx

PMUx

LTU 0

LTU 1

LTU 2

LTU 3

LTU 0

LTU 1

LTU 2

LTU 3

TOG

TOG

GSL

GSL

Maintenance Node

Construction

3.4.4.6

LTU-types for F:LTGG(A) with DIU30 in C operation


LTUType D30 APPLIC 0 CASCAS CCSCAS CCSCCS CASRCA ATE ATM U07 X X X X LTU-Number 1 X X X X 2 X X X X X X X 3 X X X X X X X 4 0/1 SU 4/5 connection for PCM30 with CAS connection for PCM30 with CCS/CAS connection for PCM30 with CCS announcement connection M:TEM:LE M:ATE:TM see: Variants for INDAS for F:LTGG(A) in C operation X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X code receiver for MFC:R2 code receiver push button dialing CRP ETEAE Responder without HW code receiver for MFC:R1 test position TWS/LWS (1) wake up service SW-LOOP TWS/LWS Responder NBL RM:CTC only in SU module 0 M:COUB Remarks

V01 V02 V04 V05 V05 V06 V08 V10 V10 V11 V14 V99 Y22

Tab. 3.151 LTU-Types for F:LTGG(A) with DIU30 in C operation

(1)

LTU 0 must be kept free when LTU type V08 is created in LTU 4.

variants for OCE:SPC and OCE:MUPx MOLOC 1 LTU1 LTU2 LTU3 SU*4 OCE:SPCx OCE:MUPx OCE:SPC OCE:SPC OCE:MUPx OCE:MUPx OCE:SPC OCE:MUPx 2 3 4 OCE:MUPx OCE:SPC OCE:SPC OCE:MUPx

variants for OCE:SPM

OCE:SPM

Tab. 3.152 Variants for INDAS for F:LTGG(A) in C operation *4 OCE:MUP MOLOC A028 or A086

A30828-X1160-M-2-7620

389

Construction

Maintenance Node

3.4.4.7

F:LTGG(A) with DIU30 in C operation (backplane)

SN 0 / A101

SN 0 / A043

LTE / A081

LTE / A071

LTE / A076

LTE / A066

LTE / A023

LTE / A013 CCG / B013

LTE / A018

CCG / B071

CCG / B066

CCG / B023

SN 1 / B101

CCG / B081

BST / B109

SN 1 / B043

CCG / B076

BST / B051

right LTGG

left LTGG

3.4.4.8

F:LTGG(A) with DIU30 in C operation (cabling)


Connector LTE / A008 LTE / A013 LTE / A018 LTE / A023 CCG / B008 CCG / B013 CCG / B018 CCG / B023 SN 0 / A043 SN 1 / B043 BST / B051 LTE / A066 LTE / A071 LTE / A076 LTE / A081 CCG / B066 CCG / B071 CCG / B076 CCG / B081 SN 0 / A101 SN 1 / B101 BST / B109 DIU 0 cable to MDF DIU 1 cable to MDF DIU 2 cable to MDF DIU 3 cable to MDF Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Cable to SN 0 or TSG 0-x Cable to SN 1 or TSG 1-x Connector for LTGC operation DIU 0 cable to MDF DIU 1 cable to MDF DIU 2 cable to MDF DIU 3 cable to MDF Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Cable to SN 0 or TSG 0-x Cable to SN 1 or TSG 1-x Connector for LTGC operation LTGG(A)

Tab. 3.153 Cabling F:LTGG(A) with DIU30 in C operation

390

A30828-X1160-M-2-7620

CCG / B018

CCG / B008

LTE / A008

Maintenance Node

Construction

3.4.4.9

F:LTGG(A) with DIU24 (module side)


left LTGG A right LTGG

B
DCCDE DCCDE A123 SILCB CGSM CGSM SILCB A112 CR0/1 CR0/1 A118 LTU 0 LTU 1 LTU 2 LTU 3 LTU 4 LTU 0 LTU 1 LTU 2 LTU 3 LTU 4 PMUx PMUx A106 TOG TOG A091 GSL GSL A096

A043

A076

A081

A013

A048

A033

A038

A066

A023

A001

A008

A028

A054

3.4.4.10

LTU-types for F:LTGG(A) with DIU24


LTUType D30 APPLIC 0 CASCAS CCSCAS CCSCCS CASRCA ATE ATM V02 V03 V06 V09 V35 V99 X X X X LTU-Number 1 X X X X 2 X X X X 3 X X X X X X X X X X X X X X X X X X X X 4 0/1 SU 4/5 connection for PCM30 with CAS connection for PCM30 with CCS/CAS connection for PCM30 with CCS announcement connection M:TEM:LE M:ATE:TM code receiver push button dialing CRP code receiver push button dialing CRP code receiver for MFC:R1 code receiver push button dialing CRP MDTOG RM:CTC only in SU module 0 Remarks

Tab. 3.154 LTU-types for F:LTGG(A) with DIU24

A018

A060

A071

A086

A101

A30828-X1160-M-2-7620

391

Construction

Maintenance Node

3.4.4.11

F:LTGG(A) with DIU24 (backplane)

SN 0 / A101

SN 0 / A043

LTE / A086

LTE / A081

LTE / A071

LTE / A076

LTE / A066

LTE / A028

LTE / A023

LTE / A013 CCG / B013

CCG / B028

LTE / A018

CCG / B071

CCG / B066

CCG / B023

SN 1 / B101

CCG / B086

CCG / B081

BST / B112

SN 1 / B043

CCG / B076

BST / B054

right LTGG

left LTGG

3.4.4.12

F:LTGG(A) with DIU24 (cabling)


Connector LTE / A008 LTE / A013 LTE / A018 LTE / A023 LTE / A028 CCG / B008 CCG / B013 CCG / B018 CCG / B023 CCG / B028 SN 0 / A043 SN 1 / B043 BST / B051 LTE / A066 LTE / A071 LTE / A076 LTE / A081 LTE / A086 CCG / B066 CCG / B071 CCG / B076 CCG / B081 DIU 0 cable to MDF DIU 1 cable to MDF DIU 2 cable to MDF DIU 3 cable to MDF DIU 4 cable to MDF Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Cable to SN 0 or TSG 0-x Cable to SN 1 or TSG 1-x Connector for LTGC operation DIU 0 cable to MDF DIU 1 cable to MDF DIU 2 cable to MDF DIU 3 cable to MDF DIU 4 cable to MDF Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG LTGG(A)

Tab. 3.155 Cabling F:LTGG(A) with DIU24

392

A30828-X1160-M-2-7620

CCG / B018

CCG / B008

LTE / A008

Maintenance Node

Construction

Connector CCG / B086 SN 0 / A101 SN 1 / B101 BST / B109 Clock supply cable to CCG Cable to SN 0 or TSG 0-x Cable to SN 1 or TSG 1-x Connector for LTGC operation

LTGG(A)

Tab. 3.155 Cabling F:LTGG(A) with DIU24

3.4.4.13

F:LTGG(A) as UI-LTGG (module side)


left LTGG A right LTGG

DCCDE

A001

A008

A013

A018

A023

A028

A033

A038

A043

A048

A060

A066

A071

A076

A081

A086

A091

A096

A101

A106

A118

Modules with displays and switches in F:LTGG(A) DCCDE (-Q5862-E) PMUx (-Q1141-) OCE:MUPx (-Q1030-) TOGC (-Q1290-) PMUE (-Q1141-X600-) OCE:SPC (-Q1031-) TOGD (-Q1291-) CRP8 (-Q1105-) OCE:SPM (-Q1401-) CGSM (-Q1185-) SCR (-Q1445-)

Tab. 3.156 Modules with displays and switches in F:LTGG(A)

A123

DCCDE

CGSM

CGSM

CR0/1

CR0/1

PMUx

PMUx

LTU 0

LTU 1

LTU 2

LTU 4

LTU 0

LTU 1

LTU 2

LTU 4

LTU3

LTU3

TOG

TOG

GSL

GSL

A30828-X1160-M-2-7620

393

Construction

Maintenance Node

3.4.4.14

LTU-types for F:LTGG(A) as UI-LTGG,


LTUType U07 V02 APPLIC 0 LTU-Number 1 X X X X X 2 3 4 SU 0/1 see: Variants for INDAS for F:LTGG(A) as UI-LTGG CRP8, SCR Remarks

Tab. 3.157 LTU-types for F:LTGG(A) as UI-LTGG

variants for OCE:SPC and OCE:MUP or OCE:SPM MOLOC 1 LTU0 LTU1 LTU2 OCE:MUPx OCE:SPC OCE:MUPx OCE:SPC OCE:MUPx 2

variants for OCE:SPM

OCE:SPM

Tab. 3.158 Variants for INDAS for F:LTGG(A) as UI-LTGG

3.4.4.15

F:LTGG(A) as UI-LTG (backplane)

SN 0 / A101

SN 1 / B101

SN 1 / B043

SN 0 / A043

right LTGG

left LTGG

3.4.4.16

F:LTGG(A) as UI-LTG (cabling)


Connector SN 0 / A043 SN 1 / B043 SN 0 / A101 SN 1 / B101 Cable to SN 0 or TSG 0-x Cable to SN 1 or TSG 1-x Cable to SN 0 or TSG 0-x Cable to SN 1 or TSG 1-x LTGG(A)

Tab. 3.159 Cabling F:LTGG(A) as UI-LTG

394

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.4.5 3.4.5.1

F:LTGH(A) F:LTGH(A) (module side)


left LTGH A right LTGH

DCCDE

FHMA0

FHMA0

FHMA1

FHMA1

CGSM

A080

PMUx

A044

A050

A100

A014

A085

A105

A110

FHMA2

GSL

A034

A090

A116

A001

A019

DCCDE (-Q5862-E)

A024

Modules with displays and switches in F:LTGH(A) CGSM (-Q1185-) PMUx (-Q1141-)

Tab. 3.160 Modules with displays and switches in F:LTGH(A)

3.4.5.2

F:LTGH(A) (backplane)

SN 0 / A101

A039

SN 1 / B101

SN 1 / B043

SN 0 / A043

right LTGG

left LTGG

A123

DCCDE

FHMA2

FHMA3

CGSM

PMUx

GSL

FHMA3

A30828-X1160-M-2-7620

395

Construction

Maintenance Node

3.4.5.3

F:LTGH(A) (cabling)
Connector SN 0 / A043 SN 1 / B043 SN 0 / A101 SN 1 / B101 Cable to SN 0 or TSG 0-x Cable to SN 1 or TSG 1-x Cable to SN 0 or TSG 0-x Cable to SN 1 or TSG 1-x LTGH(A)

Tab. 3.161 Cabling F:LTGH(A)

3.4.6 3.4.6.1

F:LTGF(A) F:LTGF(A) in B operation (module side)

GCG:LTGY

MCAB

MCAA

LTU1

SILCx

GSC

LIU

A087

A001

A071

A105

A021 A027

A038

A049

A066

A054 A061

A011

A033

A043

A081

A006

A093

A016

Modules with displays and switches in F:LTGF(A) DCCCS (-Q5619-S) PMUx (-Q1141-) SILCB (-Q1110-) DIU:LDIB (-Q1107-) CRM:R2 (-Q913-) MDTOG (-Q1105-) TOGB (-Q738-) PMUE (-Q1141-X600-) SILCD (-Q1110-X200-) OCE:MUPx (-Q1030-) CRPC (-Q913-) ETEAE (-Q670-) TOGC (-Q1290-) SILC:DLU (-Q783-) DIU30D (-Q876-) OCE:SPC (-Q1031-) RM:CTC (-Q913-) TEM:LE (-Q607-) GCG:LTGY (-Q724-) SILC:PA (-Q783-) DIU30F (-Q876-X200-) OCE:SPM (-Q1401-) ATE:TM (-Q969-)

Tab. 3.162 Modules with displays and switches in F:LTGF(A)

396

A30828-X1160-M-2-7620

A099

A111

A117

DCCCS 5V

B
SMXC TOGx LTU0 LTU2 LTU3 LTU4 PSC

CR0 / RM:CTC

SILCx

PMUx

LTU6

CR1

CR2

Maintenance Node

Construction

3.4.6.2

LTU-types for F:LTGF(A) in B operation


LTUType D30 APPLIC 0 CASCAS CCSCAS CCSCCS CASRCA CCSDLU EXTDLU CCSLDI EXTLDI CCSPA ATE ATM U07 X X X X X X X X X X X 1 X X X X X X X X X X X X X X X LTU-Number 2 X X X X X X 3 X X X X X X 4 5 6 7 0 SU 1/2 connection for PCM30 with CAS connection for PCM30 with CCS/CAS connection for PCM30 with CCS announcement connection connection DLU with CCS connection DLU (extension) LDI Application: LTU 0+2 and/or 1+3 connection for primary rate access M:TEM:LE M:ATE:TM see: Variants for INDAS for F:LTGF(A) in B operation X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X code receiver for MFC:R2 code receiver push button dialing CRP code receiver push button dialing CRP TLFB trunk test with SULIM ETEAE Responder without HW test position TWS/LWS (1) code receiver push button dialing CRP TLF/RBS wake up service / RSCI CME TWS/LWS M:MDTOG RM:CTC only in SU module 0 M:COUB Remarks

V01 V02 V03 V03 V04 V05 V05 V08 V09 V09 V10 V10 V11 V15 V99 Y22

Tab. 3.163 LTU-Types for F:LTGF(A) in B operation

(1)

LTU 2 must be kept free when LTU type V08 is created LTU 6.

A30828-X1160-M-2-7620

397

Construction

Maintenance Node

variants for OCE:SPC and OCE:MUPx MOLOC 1 LTU1 LTU2 LTU3 LTU4 OCE:SPCx OCE:MUPx OCE:SPC OCE:SPC OCE:MUPx OCE:MUPx OCE:SPC OCE:MUPx 2 3 4 OCE:MUPx OCE:SPC OCE:SPC OCE:MUPx

variants for OCE:SPM

OCE:SPM

Tab. 3.164 Variants for INDAS for F:LTGF(A) in B operation

3.4.6.3

F:LTGF(A) in B operation (backplane)

LTE / A016

SN0 / A054

LTE / A011

LTE / A006 CCG / B006

3.4.6.4

F:LTGF(A) in B operation (cabling)


Connector LTE / A001 LTE / A006 LTE / A011 LTE / A016 CCG / B001 CCG / B006 CCG / B011 CCG / B016 SN 0 / A054 SN 1 / B054 DIU 0 cable to MDF DIU 1 cable to MDF DIU 2 cable to MDF DIU 3 cable to MDF Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Cable to SN 0 or TSG 0-x Cable to SN 1 or TSG 1-x LTGF(A)

Tab. 3.165 Cabling F:LTGF(A) in B operation

SN1 / A054

398

A30828-X1160-M-2-7620

CCG / B016

CCG / B011

CCG / B001

LTE / A001

Maintenance Node

Construction

3.4.6.5

F:LTGF(A) in C operation (module side)

GCG:LTGY

A016

A087

A001

A105

A027

A049

A066

A011

A061

A081

A093

A006

A054

Modules with displays and switches in F:LTGF(A) DCCCS (-Q5619-S) PMUx (-Q1141-) OCE:MUPx (-Q1030-) MDTOG (-Q1105-) ETEAE (-Q670-) TOGB (-Q738-) PMUE (-Q1141-X600-) OCE:SPC (-Q1031-) CRPC (-Q913-) TEM:LE (-Q607-) TOGC (-Q1290-) DIU30D (-Q876-) OCE:SPM (-Q1401-) RM:CTC (-Q913-) GCG:LTGY (-Q724-) DIU30F (-Q876-X200-) CRM:R2 (-Q913-) ATE:TM (-Q969-)

Tab. 3.166 Modules with displays and switches in F:LTGF(A)

3.4.6.6

LTU-Types for F:LTGF(A) in C operation,


LTUType D30 APPLIC LTU-Number 0 CASCAS CCSCAS CCSCCS CASRCA ATE ATM U07 V01 V02 V03 V04 V05 X X X X X X X X 1 X X X X 2 X X X X X X X 3 X X X X X X X X X X 0/1 SU 2/3 connection for PCM30 with CAS connection for PCM30 with CCS/CAS connection for PCM30 with CCS announcement connection M:TEM:LE M:ATE:TM see: Variants for INDAS for F:LTGF(A) in C operation code receiver for MFC:R2 code receiver push button dialing CRP code receiver push button dialing CRP ETEAE Responder Remarks

Tab. 3.167 LTU-Types for F:LTGF(A) in C operation

A099

A111

A117

DCCCS 5V

B
SPMXa SMXC TOGx LTU0 LTU1 LTU2 LTU3

CR0 / RM:CTC

PMUx

CR1

CR2

CR3

LIU

A30828-X1160-M-2-7620

399

Construction

Maintenance Node

LTUType V10 V10 V99 Y22

APPLIC

LTU-Number 0 1 2 X X X X X X X 3 X 0/1 X

SU 2/3 wake up service CME

Remarks

RM:CTC only in SU module 0 M:COUB

Tab. 3.167 LTU-Types for F:LTGF(A) in C operation

(1)

LTU 2 must be kept free when LTU type V 08 is created in LTU 6.

variants for OCE:SPC and OCE:MUPx MOLOC 1 LTU0 LTU1 LTU2 LTU3 OCE:SPCx OCE:MUPx OCE:SPC OCE:SPC OCE:MUPx OCE:MUPx OCE:SPC OCE:MUPx 2 3 4 OCE:MUPx OCE:SPC OCE:SPC OCE:MUPx

variants for OCE:SPM

OCE:SPM

Tab. 3.168 Variants for INDAS for F:LTGF(A) in C operation

3.4.6.7

F:LTGF(A) in C operation (backplane)

LTE / A016

SN0 / A054

LTE / A011

LTE / A006 CCG / B006

3.4.6.8

F:LTGF(A) in C operation (cabling)


Connector LTE / A001 DIU 0 cable to MDF LTGF(A)

Tab. 3.169 Cabling F:LTGF(A) in C operation

SN1 / A054

400

A30828-X1160-M-2-7620

CCG / B016

CCG / B011

CCG / B001

LTE / A001

Maintenance Node

Construction

Connector LTE / A006 LTE / A011 LTE / A016 CCG / B001 CCG / B006 CCG / B011 CCG / B016 SN 0 / A054 SN 1 / B054 DIU 1 cable to MDF DIU 2 cable to MDF DIU 3 cable to MDF Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Cable to SN 0 or TSG 0-x Cable to SN 1 or TSG 1-x

LTGF(A)

Tab. 3.169 Cabling F:LTGF(A) in C operation

3.4.7 3.4.7.1

F:LTGB(A) F:LTGB(A) with DIU30 (module side)

LTU4 / Module 0

LTU0 / Module 0

LTU0 / Module 1

LTU2 / Module 1

LTU3 / Module 0

LTU6 / Module 0

LTU6 / Module 1

LTU2 / Module 0

LTU4 / Module 1

LTU5 / Module 0

LTU1 / Module 0

LTU3 / Module 1

LTU5 / Module 1

LTU7 / Module 0

CR0 / RM:CTC

LTU1 / Module1

LTU7 / Module 1 A109

CR1

A001

A049

A013

A055

A097

A019

A031

A067

A037

A043

A025

A073

A007

A079

A085

A091

A103

A115

CR2

A30828-X1160-M-2-7620

401

Construction

Maintenance Node

DCCCC 5V/12V

GCG:LTGY

DCCCC 5V

SILCx 0

SPMXA

SILCx 1

MCAB

MCAA

TOG

SMX

LIU

PMUx

PSC

A001

A049

A013 A019

A031

A055

A037

A067

A043

A025

A061

A073

A079

Modules with displays and switches in F:LTGB(A) DCCCB (-Q5619-B) PMUx (-Q1141-) SILC:DLU (-Q783-) CRPC (-Q913-) DIU30B (-Q563-) OCE:MUPx (-Q1030-) ETEAE (-Q670-) DCCCC (-Q5619-C) PMUE (-Q1141-X600-) SILC:PA (-Q783-) CRM:R2 (-Q913-) DIU30D (-Q876-) OCE:SPC (-Q1031-) TEM:LE (-Q607-) DCCCL (-Q5619-L) TOGB (-Q738-) SILCB (-Q1110-) RM:CTC (-Q913-) DIU30F (-Q876-X200-) OCE:SPM (-Q1401-) GCG:LTGY (-Q724-) TOGC (-Q1290-) SILCD (-Q1110-X200-) DIU30A (-Q562-) DIU:LDIB (-Q1107-) ATE:TM (-Q969-)

Tab. 3.170 Modules with displays and switches in F:LTGB(A)

A085

402

A30828-X1160-M-2-7620

A091

A103

A115

DCCCL 5V

DCCCB 12V

GSC

Maintenance Node

Construction

3.4.7.2

LTU-types for F:LTGB(A) with DIU30


LTUType APPLIC LTU-Number S U 6 7 0,1, 2 connection for PCM30 with CAS connection for PCM30 with CCS/CAS connection for PCM30 with CCS announcement connection connection DLU with CCS connection DLU (extension) connection for Primary Rate Access X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X M:TEM:LE / TEM:COP M:ATE:TM see: Variants for INDAS for F:LTGB(A) code receiver for MFC:R2 code receiver push button dialing CRPP code receiver push button dialing CRP TLFB trunk test with SULIM ETEAE Responder without HW test position TWS/LWS code receiver push button dialing CRP TLF/RBS wake up service / RSCI TWS/LWS M:MDTOG (only one MDTOG per LTG) RM:CTC only in SU module 0 M:COUB Remarks

D30

CASCAS CCSCAS CCSCCS CASRCA CCSDLU EXTDLU CCSPA

X X X X X X X

X X X X X X X

X X X X X X X

X X X X X X X

ATE ATM U07 V01 V02 V03 V03 V04 V05 V05 V08 V09 V09 V10 V11 V15 V99 Y22

Tab. 3.171 LTU-Types for F:LTGB(A) with DIU30

MOLOC 1 LTU2 Module 0 Module 1

variants for OCE:SPC and OCE:MUPx 2 OCE:SPC OCE:MUPx OCE:MUPx 3 4 OCE:SPC OCE:MUPx

variants for OCE:SPM

Tab. 3.172 Variants for INDAS for F:LTGB(A)

A30828-X1160-M-2-7620

403

Construction

Maintenance Node

MOLOC 1 LTU3 Module 0 Module 1 OCE:SPCx OCE:MUPx

variants for OCE:SPC and OCE:MUPx 2 OCE:SPC 3 OCE:SPC OCE:MUPx 4 OCE:SPC OCE:MUPx

variants for OCE:SPM OCE:SPM

Tab. 3.172 Variants for INDAS for F:LTGB(A)

3.4.7.3

F:LTGB(A) with DIU30 (backplane)

LTE / A049

LTE / A037

CCG / B037

CCG / B025

LTE / A025

SN 0 / C067

BST / C103

CCG / B049

3.4.7.4

F:LTGB(A) with DIU30 (cabling)


Connector LTE / A013 LTE / A025 LTE / A037 LTE / A049 DIU0 cable to MDF or cable to DLU DIU1 cable to MDF or cable to DLU DIU2 cable to MDF or cable to DLU DIU3 cable to MDF or cable to DLU LTGB(A)

Tab. 3.173 Cabling F:LTGB(A) with DIU30

SN 1 / D067

404

A30828-X1160-M-2-7620

BST / C013

CCG / B013

LTE / A013

Maintenance Node

3.4.7.5

A30828-X1160-M-2-7620 B A
BST / C103 BST / C013 CCG / B049 CCG / B037 CCG / B025 CCG / B013 SN 1 / D067 SN 0 / C067 A001 CR0 / RM:CTC A007 CR1 A013 LTU0 / Module 0 A019 LTU0 / Module 1 A025 A031 LTU1 / Module 1 A037 A043 A049 LTU3 / Module 0 A055 CG:DIU24 A061 LTU3 / Module 1 A067 LTU4 / Module 0 LTU4 / Module 1 LTU5 / Module 0 LTU5/ Module 1 LTU6/ Module 0 A073 A079 A085 A091 LTU2 / Module 1 LTU2 / Module 0 LTU1 / Module 0 Connector Cable to SN 0 or TSG 1-x Cable to SN 0 or TSG 0-x Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG

A001

DCCCC 5V

A013

DCCCC 5V/12V

A019

A025

TOG

A031

GSC

A037

MCAB

A043

MCAA

A049

PSC

Tab. 3.173 Cabling F:LTGB(A) with DIU30

A055

SPMXA

F:LTGB(A) with DIU24 (module side)

A061

SILCx 0

A067

LIU

LTGB(A)

A073

SILCx 1

A079

GCG:LTGY

A085

SMX

Link connector must be plugged in if M:DCCCB is nonexistent

Link connector must be plugged in if M:DCCCC is nonexistent

A091

PMUx

A097 LTU6 / Module 1 A103 LTU7 / Module 0 A109 LTU7 / Module 1 A115 CR2

A103

DCCCB 12V

Construction

A115

DCCCL 5V

405

Construction

Maintenance Node

3.4.7.6

LTU-types for F:LTGB(A) with DIU24


LTUType APPLIC 0 1 LTU-Number 2 3 4 5 6 7 SU 0,1 2 connection for PCM24 with CAS connection for PCM24 with CCS/CAS connection for PCM24 with CCS connection DLU with CCS connection DLU (extension) connection for Primary Rate Access X X X X X X X X X X X X X X X X X X X X M:TEM:LE / TEM:COP M:ATE:TM code receiver push button dialing CRP code receiver push button dialing CRP code receiver for MFC:R1 code receiver push button dialing CRP M:MDTOG (only one MDTOG per LTG) RM:CTC only in SU module 0 Remarks

D24

CASCAS CCSCAS CCSCCS CCSDLU EXTDLU CCSPA

X X X X X X

X X X X X X

X X X X X X

X X X X X X

ATE ATM V02 V03 V06 V09 V35 V99

Tab. 3.174 LTU-types for F:LTGB(A) with DIU24

3.4.7.7

F:LTGB(A) with DIU24 (backplane)

LTE / A067

LTE / A049

LTE / A037

CCG / B067

CCG / B037

CCG / B025

LTE / A025

CCG / B049

406

A30828-X1160-M-2-7620

CCG / B013

LTE / A013

Maintenance Node

Construction

SN 0 / C067

BST / C103

3.4.7.8

F:LTGB(A) with DIU24 (cabling)


Connector LTE / A013 LTE / A025 LTE / A037 LTE / A049 LTE / A067 CCG / B013 CCG / B025 CCG / B037 CCG / B049 CCG / B067 SN 0 / C067 SN 1 / D067 BST / C013 BST / C103 DIU0 cable to MDF or cable to DLU DIU1 cable to MDF or cable to DLU DIU2 cable to MDF or cable to DLU DIU3 cable to MDF or cable to DLU DIU4 cable to MDF or cable to DLU Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Cable to SN 0 or TSG 0-x Cable to SN 0 or TSG 1-x Link connector must be plugged in if M:DCCCC is nonexistent Link connector must be plugged in if M:DCCCB is nonexistent LTGB(A)

Tab. 3.175 Cabling F:LTGB(A) with DIU24

SN 1 / D067

BST / C013

A30828-X1160-M-2-7620

407

Construction

Maintenance Node

3.4.8 3.4.8.1

F:LTGC(A) F:LTGC(A) (module side)

GCG:LTGY

A001

A007

A013

A019

A025

A031

A037

A043

A055

A067

A073

A079

A091

A097

A103

A109

Modules with displays and switches in F:LTGC(A) DCCCC (-Q5619-C) PMUE (-Q1141-X600-) CRPC (-Q913-) DIU30D (-Q876-) OCE:SPC (-Q1031-) DCCCL (-Q5619-L) TOGB (-Q738-) CRM:R2 (-Q913-) DIU30F (-Q876-X200-) ATE:TM (-Q969-) GCG:LTGY (-Q724-) TOGC (-Q1290-) DIU30A (-Q562-) OCE:SPM (-Q1401-) ETEAE (-Q670-) PMUx (-Q1141-) RM:CTC (-Q913-) DIU30B (-Q563-) OCE:MUPx (-Q1030-) TEM:LE (-Q607-)

Tab. 3.176 Modules with displays and switches in F:LTGC(A)

3.4.8.2

LTU-Types for F:LTGC(A)


LTUType D30 APPLIC LTU-Number 0 CASCAS CCSCAS CCSCCS CASRCA ATE ATM U07 V04 V05 X X X X X X X X X X 1 X X X X 2 X X X X X X X X X X X X X 3 X X X X SU 0 connection for PCM30 with CAS connection for PCM30 with CCS/CAS connection for PCM30 with CCS announcement connection M:TEM:LE / TEM:COP M:ATE:TM see: Variants for INDAS for F:LTGB(A) ETEAE TEM:LE Remarks

Tab. 3.177 F:LTGC(A), LTU-types

408

A30828-X1160-M-2-7620

A115

DCCCS/DCCCL V5

LTU0 / Module 0

LTU0 / Module 1

LTU1 / Module 0

LTU1 / Module 1

LTU2 / Module 0

LTU2 / Module 1

LTU3 / Module 0

LTU3 / Module 1

CR0 / RM:CTC

RM:CTC

SPMXA

SMXC

PMUx

TOG

LIU

Maintenance Node

Construction

LTUType V10 V99

APPLIC

LTU-Number 0 X 1 X 2 X 3 X

SU 0 wake up service X

Remarks

RM:CTC (When using F:CR(A) RM:CTC is plugged into F:CR(A)) M:COUB

Y22

Tab. 3.177 F:LTGC(A), LTU-types

MOLOC 1 LTU2 Module 0 Module 1 LTU3 Module 0 Module 1 OCE:SPCx OCE:MUPx

Variants for OCE:SPC and OCE:MUPx 2 OCE:SPC OCE:MUPx OCE:SPC OCE:MUPx OCE:SPC OCE:MUPx 3 4 OCE:SPC OCE:MUPx OCE:SPC OCE:MUPx

variants for OCE:SPM

OCE:SPM

Tab. 3.178 Variants for INDAS for F:LTGB(A)

3.4.8.3

F:LTGC(A) (backplane)

SN 0 / A055

LTE / A103

LTE / A025

LTE / A091

INTCR / B070

CCG / B103

CCG / B091

SN 1 / B055

CCG / B025

CCG / B013

LTE / A013

A30828-X1160-M-2-7620

BST / A001

409

Construction

Maintenance Node

3.4.8.4

F:LTGC(A) (cabling)
Connector LTE / A013 LTE / A025 LTE / A091 LTE / A103 CCG / B013 CCG / B025 CCG / B091 CCG / B103 SN 0 / A055 SN 1 / B055 BST / A001 INTCR / C103 DIU 0 cable to MDF DIU 1 cable to MDF DIU 2 cable to MDF DIU 3 cable to MDF Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Clock supply cable to CCG Cable to SN 0 or TSG 0-x Cable to SN 0 or TSG 1-x Link connector must be plugged in if M:DCCCC is nonexistent Internal cable to F:CR(A) B061 or B070 LTGC(A)

Tab. 3.179 Cabling F:LTGC(A)

3.4.9 3.4.9.1

F:CR(A) F:CR(A) (module side)

DCCCL5V

CRx 0 / RM:CTC

CRx 7

A001

A049

A055

A031

A067

A037

A025

A043

A073

A079

A091

A097

A013

A019

A025

Modules with displays and switches in F:CR(A) DCCCA (-Q5619-A) RM:CTC (-Q913-) DCCCL (-Q5619-L) CRPC (-Q913-) CRM:R2 (-Q913-)

Tab. 3.180 Modules with displays and switches in F:CR(A)

410

A30828-X1160-M-2-7620

A103

A109

A115

DCCCL/DCCCA 5V

CRx 0 / RM:CTC

CRx 5

CRx 6

CRx 3

CRx 2

CRx 2

CRx 4

CRx 4

CRx 1

CRx 1

CRx 5

CRx 6

CRx 3

CRx 7

Maintenance Node

Construction

3.4.9.2

F:CR(A) (backplane)

INT 1 / B070

3.4.9.3

F:CR(A) (cabling)
Connector INT 0 / B061 INT1 / B070 Internal cable to F:LTGC(A) 0/2 B070 Internal cable to F:LTGC(A) 1/3 B070 CR(A)

Tab. 3.181 Cabling F:CR(A)

3.4.10 3.4.10.1

F:LTGD(A) F:LTGD(A) (module side)

INT 0 / B061

DIU30A/DIU30D

DIU30A/DIU30D

GCG:LTGY

DIU30A/DIU30D

DIU30A/DIU30D

DCCCC 5V/12V

DIU30B

SPMXB

SMXC

LIU

PMUx

TOG

DIU30B

SDMA

A001

A049

A013

A055

A097

A103

A019

A031

A067

A037

A025

A043

A073

A079

A091

A109

A115

DCCCS/DCCCL V5

DIU30B

DIU30B

A30828-X1160-M-2-7620

411

Construction

Maintenance Node

Modules with displays and switches in F:LTGD(A) DCCCC (-Q5619-C) PMUx (-Q1141-) DIU30A (-Q562-) DCCCL (-Q5619-L) PMUE (-Q1141-X600-) DIU30B (-Q563-) DCCCS (-Q5619-S) TOGB (-Q738-) DIU30D (-Q876-) GCG:LTGY (-Q724-) TOGC (-Q1290-)

Tab. 3.182 Modules with displays and switches in F:LTGD(A)

3.4.10.2

LTU-Types for F:LTGD(A)


LTUType D30 APPLIC LTU-Number 0 NO5CAS CASCAS D30 NO5CAS CASCAS X X 1 X X X X X X 2 3 CRES 0 connection for PCM30 with CAS CRES 1 connection for PCM30 with CAS Remarks

Tab. 3.183 LTU-types for F:LTGD(A)

3.4.10.3

F:LTGD(A) (backplane)

INTA / A061

LTE / A013

SN 0/ A055

LTE / A103

LTE / A091

INTB / B061

3.4.10.4

F:LTGD(A) (cabling)
Connector LTE / A013 LTE / A025 LTE / A091 LTE / A103 INTA / A061 DIU 0 cable to MDF DIU 1 cable to MDF DIU 2 cable to MDF DIU 3 cable to MDF Internal cable LTU0/1 to F:CRES 0/2 LTGD(A)

Tab. 3.184 Cabling F:LTGD(A)

SN 1 / B055

412

A30828-X1160-M-2-7620

LTE / A025

BST / A001

Maintenance Node

Construction

Connector INTB / B061 SN 0 / A055 SN 1 / B055 BST / A001 Intern cable LTU2/3 to F:CRES 1/3 Cable to SN 0 or TSG 0-x Cable to SN 1 or TSG 1-x

LTGD(A)

Link connector must be plugged in if M:DCCCC is nonexistent

Tab. 3.184 Cabling F:LTGD(A)

3.4.11 3.4.11.1

F:CRES(A) F:CRES(A) (module side)

DCCCL/DCCCA 5V

A001

A025

A031

A037

A043

A049

A055

A067

A073

A079

A091

A097

Modules with displays and switches in F:CRES(A) DCCCA (-Q5619-A) DESA (-A162-) DCCCL (-Q5619-L) DESB_A1 (-B163-A1-) RM:CTC (-Q913-) DCRCx (-Q743-)

Tab. 3.185 Modules with displays and switches in F:CRES(A)

A115

DCCCL/DCCCA 5V

RM:CTC

DCRA

DCRB

DCRC

DCRA

DCRB

DCRC

DESA

DESB

DESA

DESB

A30828-X1160-M-2-7620

413

Construction

Maintenance Node

3.4.11.2

F:CRES(A) (backplane)

3.4.11.3

F:CRES(A) (cabling)
Connector INTA / A061 INTB / B061 CRES(A) Interncable to F:LTGD(A) to CCITT No.7 with DES, RM:CTC. Interncable to F:LTGD(A) to CCITT No.5 with or without DES and R2/MFC:R2 with DES.

Tab. 3.186 Cabling F:CRES(A)

INTB / B061

INTA/ A061

414

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.5

F:MB/CCG
3.5.1 3.5.1.1 3.5.1.2 3.5.1.3 3.5.2 3.5.2.1 3.5.2.2 3.5.2.3 3.5.3 3.5.3.1 3.5.3.2 3.5.3.3 F:MB/CCG(B) F:MB/CCG(B) (module side) F:MB/CCG(B) (backplane) F:MB/CCG(B) (cabling) F:MBD F:MBD (module side) F:MBD (backplane) F:MBD (cabling) F:CCGE F:CCGE (module side) F:CCGE (backplane) F:CCGE (cabling)

3.5.1 3.5.1.1

F:MB/CCG(B) F:MB/CCG(B) (module side)

CG/MUX

CCGXXA A111

DCCCS

CCGD

T/RC0

T/RC1

T/RC2

T/RC2

T/RC3

CCGB

T/RC3

IOPC

MDM

MDM

A001

A049

A019

A037

A043

A055

A062

A025

A068

A031

A074

A080

Modules with displays and switches in F:MB/CCG(B) DCCCS (-Q5619-S) DCCCR (-Q5619-) CCGB (-Q887-) CCGXXA (-Q888-)

Tab. 3.187 Modules with displays and switches in F:MB/CCG(B)

A086

A098

A104

A121

DCCCR

B
T/RC1

T/RC0

A30828-X1160-M-2-7620

415

Construction

Maintenance Node

3.5.1.2

F:MB/CCG(B) (backplane)

RES 10 / A124

RES 11 / A117 INT / A114 TAKT / A111 CDEX1 / A108 CGINT / A105 IOP 1 / A101

RES 13 / A071 RES 14 / A068 CCG 0 / A065

IOP 0 / A095 RES 0 / A092 RES 1 / A089 MB 10 / A086 MB 11 / A083 MB 12 / A080 MB 13 / A077

SGC / A040 RES 15/ A037 RES 16 / A034

RES 12 / A074

TSG / A055 IOP 1 / A052

RES 01 / B117 INT / B114 TAKT / B111 CEDEX0 / B108 CGINT / B105

IOP 0 / B095 RES 3 / B092 RES 2 / B089 MB 00 / B086 MB 01 / B083 MB 02 / B080 MB 03 / B077 RES 02 / B074 RES 03 / B071 RES 04 / B068 CCG 1/ B065

SGC / A049

RES 05 / B037 RES 06 / B034

RES 00 / B124

3.5.1.3

F:MB/CCG(B) (cabling)
Cabling MBB <--> CP
Capacity Stage SN(63LTG) and SN(126LTG) Cabling MBB <--> CP113, F:IOP MBUS-0-0 (MBG00) 02/04*) A046 -> IOP0 03/06**) C151P2 MBUS-0-0 (MBG00) 02/04 A052 -> IOP1 04/07 C151P2 MBUS-0-0 (MBG00) 02/04 B046 -> IOP0 03/06 C151P1 MBUS-0-0 (MBG00) 02/04 B052 -> IOP1 04/07 C151P1 MBUS-1-0 (MBG10) 03/05 A046 -> IOP0 03/06 C151P4 MBUS-1-0 (MBG10) 03/05 A052 -> IOP1 04/07 C151P4 MBUS-1-0 (MBG10) 03/05 B046 -> IOP0 03/06 C151P3 MBUS-1-0 (MBG10) 03/05 B052 -> IOP1 04/07 C151P3 SN(252LTG) additional cables in the extension rack R:MB/CCG or in the additional R:SN/MB/LTGM MBUS-0-1 (MBG01) 08/04 A046 -> IOP0 03/06 C159P2 MBUS-0-1 (MBG01) 08/04 A052 -> IOP1 04/07 C159P2 MBUS-0-1 (MBG01) 08/04 B046 -> IOP0 03/06 C159P1 MBUS-0-1 (MBG01) 08/04 B052 -> IOP1 04/07 C159P1 MBUS-1-1 (MBG11) 09/05 A046 -> IOP0 03/06 C159P4 MBUS-1-1 (MBG11) 09/05 A052 -> IOP1 04/07 C159P4 MBUS-1-1 (MBG11) 09/05 B046 -> IOP0 03/06 C159P3 MBUS-1-1 (MBG11) 09/05 B052 -> IOP1 04/07 C159P3

Tab. 3.188 F:MB/CCG(B): cables MB - CP113

IOP 1 / B101

416

A30828-X1160-M-2-7620

RES 3 / B013 RES 2 / B010

TSG / B055 IOP 1 / B052 SGC / B049 IOP 0 / B046

RES 1 / A013 RES 0 / A010

IOP 0/ A046

Maintenance Node

Construction

Capacity Stage SN(504LTG)

Cabling MBB <--> CP113, F:IOP additional cables in the extension rack R:MB/CCG or in the additional R:SN/MB/LTGM MBUS-0-2 (MBG02) 02/04 A046 -> IOP2 03/06 C151P2 MBUS-0-2 (MBG02) 02/04 A052 -> IOP3 04/07 C151P2 MBUS-0-2 (MBG02) 02/04 B046 -> IOP2 03/06 C151P1 MBUS-0-2 (MBG02) 02/04 B052 -> IOP3 04/07 C151P1 MBUS-1-2 (MBG12) 03/05 A046 -> IOP2 03/06 C151P4 MBUS-1-2 (MBG12) 03/05 A052 -> IOP3 04/07 C151P4 MBUS-1-2 (MBG12) 03/05 B046 -> IOP2 03/06 C151P3 MBUS-1-2 (MBG12) 03/05 B052 -> IOP3 04/07 C151P3 MBUS-0-3 (MBG03) 08/04 A046 -> IOP2 03/06 C159P2 MBUS-0-3 (MBG03) 08/04 A052 -> IOP3 04/07 C159P2 MBUS-0-3 (MBG03) 08/04 B046 -> IOP2 03/06 C159P1 MBUS-0-3 (MBG03) 08/04 B052 -> IOP3 04/07 C159P1 MBUS-1-3 (MBG13) 09/05 A046 -> IOP2 03/06 C159P4 MBUS-1-3 (MBG13) 09/05 A052 -> IOP3 04/07 C159P4 MBUS-1-3 (MBG13) 09/05 B046 -> IOP2 03/06 C159P3 MBUS-1-3 (MBG13) 09/05 B052 -> IOP3 04/07 C159P3

*)

MUT02 and 03, 08 and 09 in R:MB/CCG MUT04 and 05 in R:SN/MB/LTGM MUT03 and 04 rack TLG 75 MUT06 and 07 rack TLG 60

**)

Tab. 3.188 F:MB/CCG(B): cables MB - CP113

Capacity Stage SN(63LTG) and SN(126LTG)

Cabling MBB <--> CP113C, F:PIOP(A) MBUS-0-0 (MBG00) 02/04*) A046 -> PIOP(A)0 03 C279P2 MBUS-0-0 (MBG00) 02/04 A052 -> PIOP(A)1 07 C279P2 MBUS-0-0 (MBG00) 02/04 B046 -> PIOP(A)0 03 C279P1 MBUS-0-0 (MBG00) 02/04 B052 -> PIOP(A)1 07 C279P1 MBUS-1-0 (MBG10) 03/05 A046 -> PIOP(A)0 03 C279P4 MBUS-1-0 (MBG10) 03/05 A052 -> PIOP(A)1 07 C279P4 MBUS-1-0 (MBG10) 03/05 B046 -> PIOP(A)0 03 C279P3 MBUS-1-0 (MBG10) 03/05 B052 -> PIOP(A)1 07 C279P3

SN(252LTG)

additional cables in the extension rack MB/CCG or in the additional rack SN/MB/LTGx MBUS-0-1 (MBG01) 02/04*) A046 -> PIOP(A)0 03 C269P2 MBUS-0-1 (MBG01) 02/04 A052 -> PIOP(A)1 07 C269P2 MBUS-0-1 (MBG01) 02/04 B046 -> PIOP(A)0 03 C269P1 MBUS-0-1 (MBG01) 02/04 B052 -> PIOP(A)1 07 C269P1 MBUS-1-1 (MBG11) 03/05 A046 -> PIOP(A)0 03 C269P4 MBUS-1-1 (MBG11) 03/05 A052 -> PIOP(A)1 07 C269P4 MBUS-1-1 (MBG11) 03/05 B046 -> PIOP(A)0 03 C269P3 MBUS-1-1 (MBG11) 03/05 B052 -> PIOP(A)1 07 C269P3

Tab. 3.189 F:MB/CCG(B): cables MB - F:PIOP(A) (CP113C)

A30828-X1160-M-2-7620

417

Construction

Maintenance Node

Capacity Stage SN(504LTG)

Cabling MBB <--> CP113C, F:PIOP(A) additional cables in the extension rack MB/CCG or in the additional rack SN/MB/LTGx MBUS-0-2 (MBG02) 02/04 A046 -> PIOP(A)2 02 C279P2 MBUS-0-2 (MBG02) 02/04 A052 -> PIOP(A)3 09 C279P2 MBUS-0-2 (MBG02) 02/04 B046 -> PIOP(A)2 02 C279P1 MBUS-0-2 (MBG02) 02/04 B052 -> PIOP(A)3 09 C279P1 MBUS-1-2 (MBG12) 03/05 A046 -> PIOP(A)2 02 C279P4 MBUS-1-2 (MBG12) 03/05 A052 -> PIOP(A)3 09 C279P4 MBUS-1-2 (MBG12) 03/05 B046 -> PIOP(A)2 02 C279P3 MBUS-1-2 (MBG12) 03/05 B052 -> PIOP(A)3 09 C279P3 MBUS-0-3 (MBG03) 08/04 A046 -> PIOP(A)2 02 C269P2 MBUS-0-3 (MBG03) 08/04 A052 -> PIOP(A)3 09 C269P2 MBUS-0-3 (MBG03) 08/04 B046 -> PIOP(A)2 02 C269P1 MBUS-0-3 (MBG03) 08/04 B052 -> PIOP(A)3 09 C269P1 MBUS-1-3 (MBG13) 09/05 A046 -> PIOP(A)2 02 C269P4 MBUS-1-3 (MBG13) 09/05 A052 -> PIOP(A)3 09 C269P4 MBUS-1-3 (MBG13) 09/05 B046 -> PIOP(A)2 02 C269P3 MBUS-1-3 (MBG13) 09/05 B052 -> PIOP(A)3 09 C269P3

*)

MUT02 and 03, 08 and 09 in R:MB/CCG MUT04 and 05 in R:SN/MB/LTGM

Tab. 3.189 F:MB/CCG(B): cables MB - F:PIOP(A) (CP113C)

Capacity Stage SN(63LTG) and SN(126LTG)

Cabling MB <--> CP113C, F:PIOP(B) MBUS-0-0 (MBG00) 02/04*) A046 -> PIOP(B)0 03 C305P2 MBUS-0-0 (MBG00) 02/04 A052 -> PIOP(B)1 07 C305P2 MBUS-0-0 (MBG00) 02/04 B046 -> PIOP(B)0 03 C305P1 MBUS-0-0 (MBG00) 02/04 B052 -> PIOP(B)1 07 C305P1 MBUS-1-0 (MBG10) 03/05 A046 -> PIOP(B)0 03 C305P4 MBUS-1-0 (MBG10) 03/05 A052 -> PIOP(B)1 07 C305P4 MBUS-1-0 (MBG10) 03/05 B046 -> PIOP(B)0 03 C305P3 MBUS-1-0 (MBG10) 03/05 B052 -> PIOP(B)1 07 C305P3

SN(252LTG)

additional cables in the extension rack MB/CCG or in the additional rack SN/MB/LTGx MBUS-0-1 (MBG01) 08/04 A046 -> PIOP(B)0 03 C297P2 MBUS-0-1 (MBG01) 08/04 A052 -> PIOP(B)1 07 C297P2 MBUS-0-1 (MBG01) 08/04 B046 -> PIOP(B)0 03 C297P1 MBUS-0-1 (MBG01) 08/04 B052 -> PIOP(B)1 07 C297P1 MBUS-1-1 (MBG11) 09/05 A046 -> PIOP(B)0 03 C297P4 MBUS-1-1 (MBG11) 09/05 A052 -> PIOP(B)1 07 C297P4 MBUS-1-1 (MBG11) 09/05 B046 -> PIOP(B)0 03 C297P3 MBUS-1-1 (MBG11) 09/05 B052 -> PIOP(B)1 07 C297P3

Tab. 3.190 F:MB/CCG(B): cables MB - F:PIOP(B) (CP113C)

418

A30828-X1160-M-2-7620

Maintenance Node

Construction

Capacity Stage SN(504LTG)

Cabling MB <--> CP113C, F:PIOP(B) additional cables in the extension rack MB/CCG or in the additional rack SN/MB/LTGx MBUS-0-2 (MBG02) 02/04 A046 -> PIOP(B)2 02 C305P2 MBUS-0-2 (MBG02) 02/04 A052 -> PIOP(B)3 09 C305P2 MBUS-0-2 (MBG02) 02/04 B046 -> PIOP(B)2 02 C305P1 MBUS-0-2 (MBG02) 02/04 B052 -> PIOP(B)3 09 C305P1 MBUS-1-2 (MBG12) 03/05 A046 -> PIOP(B)2 02 C305P4 MBUS-1-2 (MBG12) 03/05 A052 -> PIOP(B)3 09 C305P4 MBUS-1-2 (MBG12) 03/05 B046 -> PIOP(B)2 02 C305P3 MBUS-1-2 (MBG12) 03/05 B052 -> PIOP(B)3 09 C305P3 MBUS-0-3 (MBG03) 08/04 A046 -> PIOP(B)2 02 C297P2 MBUS-0-3 (MBG03) 08/04 A052 -> PIOP(B)3 09 C297P2 MBUS-0-3 (MBG03) 08/04 B046 -> PIOP(B)2 02 C297P1 MBUS-0-3 (MBG03) 08/04 B052 -> PIOP(B)3 09 C297P1 MBUS-1-3 (MBG13) 09/05 A046 -> PIOP(B)2 02 C297P4 MBUS-1-3 (MBG13) 09/05 A052 -> PIOP(B)3 09 C297P4 MBUS-1-3 (MBG13) 09/05 B046 -> PIOP(B)2 02 C297P3 MBUS-1-3 (MBG13) 09/05 B052 -> PIOP(B)3 09 C297P3

*)

MUT02 and 03, 08 and 09 in R:MB/CCG MUT04 and 05 in R:SN/MB/LTGM

Tab. 3.190 F:MB/CCG(B): cables MB - F:PIOP(B) (CP113C)

Capacity

Cabling MB <--> CP113E, F:EIOP and for SN(504LTG) additionally F:BIOP (Both F:EIOP are connected to IOC0 and IOC1, F:BIOP is connected to IOC0 and IOC1) MBUS-0-0 (MBG00) 02/04*) A046 -> EIOP 03 C279P2 MBUS-0-0 (MBG00) 02/04 A052 -> EIOP 04 C279P2 MBUS-0-0 (MBG00) 02/04 B046 -> EIOP 03 C279P1 MBUS-0-0 (MBG00) 02/04 B052 -> EIOP 04 C279P1 MBUS-1-0 (MBG10) 03/05 A046 -> EIOP 03 C279P4 MBUS-1-0 (MBG10) 03/05 A052 -> EIOP 04 C279P4 MBUS-1-0 (MBG10) 03/05 B046 -> EIOP 03 C279P3 MBUS-1-0 (MBG10) 03/05 B052 -> EIOP 04 C279P3

SN(63LTG) and SN(126LTG)

SN(252LTG)

additional cables in the extension rack R:MB/CCG or in the additional rack SN/MB/LTGx MBUS-0-1 (MBG01) 08/04 A046 -> EIOP 03 C271P2 MBUS-0-1 (MBG01) 08/04 A052 -> EIOP 04 C271P2 MBUS-0-1 (MBG01) 08/04 B046 -> EIOP 03 C271P1 MBUS-0-1 (MBG01) 08/04 B052 -> EIOP 04 C271P1 MBUS-1-1 (MBG11) 09/05 A046 -> EIOP 03 C271P4 MBUS-1-1 (MBG11) 09/05 A052 -> EIOP 04 C271P4 MBUS-1-1 (MBG11) 09/05 B046 -> EIOP 03 C271P3 MBUS-1-1 (MBG11) 09/05 B052 -> EIOP 04 C271P3

Tab. 3.191 F:MB/CCG(B): cables MB - CP113E

A30828-X1160-M-2-7620

419

Construction

Maintenance Node

Capacity

Cabling MB <--> CP113E, F:EIOP and for SN(504LTG) additionally F:BIOP (Both F:EIOP are connected to IOC0 and IOC1, F:BIOP is connected to IOC0 and IOC1) additional cables in the extension rack R:MB/CCG or in the additional rack SN/MB/LTGx MBUS-0-2 (MBG02) 02/04 A046 -> BIOP 05 C157P2 MBUS-0-2 (MBG02) 02/04 A052 -> BIOP 05 C289P2 MBUS-0-2 (MBG02) 02/04 B046 -> BIOP 05 C157P1 MBUS-0-2 (MBG02) 02/04 B052 -> BIOP 05 C289P1 MBUS-1-2 (MBG12) 03/05 A046 -> BIOP 05 C157P4 MBUS-1-2 (MBG12) 03/05 A052 -> BIOP 05 C289P4 MBUS-1-2 (MBG12) 03/05 B046 -> BIOP 05 C157P3 MBUS-1-2 (MBG12) 03/05 B052 -> BIOP 05 C289P3 MBUS-0-3 (MBG03) 08/04 A046 -> BIOP 05 C149P2 MBUS-0-3 (MBG03) 08/04 A052 -> BIOP 05 C281P2 MBUS-0-3 (MBG03) 08/04 B046 -> BIOP 05 C149P1 MBUS-0-3 (MBG03) 08/04 B052 -> BIOP 05 C281P1 MBUS-1-3 (MBG13) 09/05 A046 -> BIOP 05 C149P4 MBUS-1-3 (MBG13) 09/05 A052 -> BIOP 05 C281P4 MBUS-1-3 (MBG13) 09/05 B046 -> BIOP 05 C149P3 MBUS-1-3 (MBG13) 09/05 B052 -> BIOP 05 C281P3

SN(504LTG)

*)

MUT02 and 03, 08 and 09 in R:MB/CCG MUT04 and 05 in R:SN/MB/LTGM

Tab. 3.191 F:MB/CCG(B): cables MB - CP113E Cabling MBB <--> SNA


Cabling MBUS <--> SGC SNA MBUS-0-0 (MB0) 02 A040 -> SN0 02 A061 MBUS-1-0 (MB1) 03 A040 -> SN1 03 A061

Tab. 3.192 F:MB/CCG(B): cables MBUS - SGC SN (63LTG)

Capacity Stage SN(126LTG)

Cabling MBUS <--> SGC:SSG and SGC:TSG MBUS-0-0 (MBG00) 02 B049 -> SSG-0-0 02 A061 MBUS-0-0 (MBG00) 02 A040 -> TSG-0-0 02 A061 MBUS-0-0 (MBG00) 02 A049 -> TSG-0-1 02 A061 MBUS-1-0 (MBG10) 03 B049 -> SSG-1-0 03 A061 MBUS-1-0 (MBG10) 03 A040 -> TSG-1-0 03 A061 MBUS-1-0 (MBG10) 03 A049 -> TSG-1-1 03 A061

Tab. 3.193 F:MB/CCG(B): cables MBUS - SGC:SSG and SGC:TSG

420

A30828-X1160-M-2-7620

Maintenance Node

Construction

Capacity Stage SN(252LTG)

Cabling MBUS <--> SGC:SSG and SGC:TSG additional cables MBUS-0-1 (MBG01) 08 B049 -> SSG-0-1 02 A061 MBUS-0-1 (MBG01) 08 A040 -> TSG-0-2 02 A061 MBUS-0-1 (MBG01) 08 A049 -> TSG-0-3 02 A061 MBUS-1-1 (MBG11) 09 B049 -> SSG-1-1 03 A061 MBUS-1-1 (MBG11) 09 A040 -> TSG-1-2 03 A061 MBUS-1-1 (MBG11) 09 A049 -> TSG-1-3 03 A061

SN(504LTG)

additional cables in the extension rack MB/CCG MBUS-0-2 (MBG02) 02 B049 -> SSG-0-2 02 A061 MBUS-0-2 (MBG02) 02 A040 -> TSG-0-4 02 A061 MBUS-0-2 (MBG02) 02 A049 -> TSG-0-5 02 A061 MBUS-1-2 (MBG12) 03 A040 -> TSG-1-4 03 A061 MBUS-1-2 (MBG12) 03 B049 -> SSG-1-2 03 A061 MBUS-1-2 (MBG12) 03 A049 -> TSG-1-5 03 A061 MBUS-0-3 (MBG03) 08 B049 -> SSG-0-3 02 A061 MBUS-0-3 (MBG03) 08 A040 -> TSG-0-6 02 A061 MBUS-0-3 (MBG03) 08 A049 -> TSG-0-7 02 A061 MBUS-1-3 (MBG13) 09 B049 -> SSG-1-3 03 A061 MBUS-1-3 (MBG13) 09 A040 -> TSG-1-6 03 A061 MBUS-1-3 (MBG13) 09 A049 -> TSG-1-7 03 A061

Tab. 3.193 F:MB/CCG(B): cables MBUS - SGC:SSG and SGC:TSG

Cabling MBUL <--> SNA MBUL-0-0 (MB0) 02 A055 -> SN0 02 A003 MBUL-1-0 (MB1) 03 A055 -> SN1 03 A003

Tab. 3.194 F:MB/CCG(B): cables MBUL - SNA (63LTG)

Capacity Stage SN(126LTG)

Cabling MBUL <--> TSG MBUL-0-0 (MBG00) 02 A055 -> TSG-0-0 02 A003 MBUL-0-1 (MBG00) 02 B055 -> TSG-0-1 02 A003 MBUL-1-0 (MBG10) 03 A055 -> TSG-1-0 03 A003 MBUL-1-1 (MBG10) 03 B055 -> TSG-1-1 03 A003

SN(252LTG)

additional cables MBUL-0-2 (MBG01) 08 A055 -> TSG-0-2 02 A003 *) MBUL-0-3 (MBG01) 08 B055 -> TSG-0-3 02 A003 MBUL-1-2 (MBG11) 09 A055 -> TSG-1-2 03 A003 *) MBUL-1-3 (MBG11) 09 B055 -> TSG-1-3 03 A003

Tab. 3.195 F:MB/CCG(B): cables MBUL <-> TSG

A30828-X1160-M-2-7620

421

Construction

Maintenance Node

Capacity Stage SN(504LTG)

Cabling MBUL <--> TSG additional cables in extension rack MB/CCG MBUL-0-4 (MBG02) 02 A055 -> TSG-0-4 02 A003 *) MBUL-0-5 (MBG02) 02 B055 -> TSG-0-5 02 A003 MBUL-1-4 (MBG12) 03 A055 -> TSG-1-4 03 A003 *) MBUL-1-5 (MBG12) 03 B055 -> TSG-1-5 03 A003 MBUL-0-6 (MBG03) 08 A055 -> TSG-0-6 02 A003 *) MBUL-0-7 (MBG03) 08 B055 -> TSG-0-7 02 A003 MBUL-1-6 (MBG13) 09 A055 -> TSG-1-6 03 A003 *) MBUL-1-7 (MBG13) 09 B055 -> TSG-1-7 03 A003

Tab. 3.195 F:MB/CCG(B): cables MBUL <-> TSG *) For exchanges with SN(252LTG) and SN(504LTG): For clock distribution the first MBU:LTG must be present in all F:MB/CCG(B). If no TSG is connected to this MBU:LTG (reduced capacity), a link connector must be inserted as a termination at the cable outlet to the TSG. Depending on the capacity stage and on the number of connected TSGs, the following link connectors are required:
BST -> 08 A055 with TSG0 or TSG0 and TSG1 BST -> 09 A055

Tab. 3.196 Link connectors for reduced capacity in SN(252LTG)

with TSG0 or TSG0 and TSG1

BST -> 08 A055 BST -> 09 A055 extension rack BST -> 02 A055 BST -> 03 A055 BST -> 08 A055 BST -> 09 A055

with TSG2 or TSG2 and TSG3

extension rack BST -> 02 A055 BST -> 03 A055 BST -> 08 A055 BST -> 09 A055 extension rack BST -> 08 A055 BST -> 09 A055

with TSG4 or TSG4 and TSG5

Tab. 3.197 Link connectors for reduced capacity in SN (504LTG) Cabling MBB <--> SNB
Cables MUBS <--> SGC SNB MBUS-0-0 (MB0) 02 A040 -> SN0 02/06 C229P1 MBUS-1-0 (MB1) 03 A040 -> SN1 03/07 C229P1

Tab. 3.198 F:MB/CCG(B): cables MBUS - SGC SNB (63LTG)

422

A30828-X1160-M-2-7620

Maintenance Node

Construction

Capacity Stage SN(126LTG)

Cables MBUS <--> SGC SSG and TSG MBUS-0-0 (MBG00) 02/04*) B049 -> SSG-0-0 02/06 C171P1 MBUS-0-0 (MBG00) 02/04 A040 -> TSG-0-0 02/06 C229P1 MBUS-0-0 (MBG00) 02/04 A049 -> TSG-0-1 02/06 C229P1 MBUS-1-0 (MBG10) 03/05 B049 -> SSG-1-0 03/07 C171P1 MBUS-1-0 (MBG10) 03/05 A040 -> TSG-1-0 03/07 C229P1 MBUS-1-0 (MBG10) 03/05 A049 -> TSG-1-1 03/07 C229P1

SN(252LTG)

additional cables in R:MB/CCG or in the additional R:SN/MB/LTGx MBUS-0-1 (MBG01) 08 B049 -> SSG-0-1 02/06 C279P1 MBUS-0-1 (MBG01) 08 A040 -> TSG-0-2 02/06 C229P1 MBUS-0-1 (MBG01) 08 A049 -> TSG-0-3 02/06 C229P1 MBUS-1-1 (MBG11) 09 B049 -> SSG-1-1 03/07 C279P1 MBUS-1-1 (MBG11) 09 A040 -> TSG-1-2 03/07 C229P1 MBUS-1-1 (MBG11) 09 A049 -> TSG-1-3 03/07 C229P1

SN(504LTG)

additional cables in the extension rack MB/CCG or in the additional R:SN/MB/LTGx MBUS-0-2 (MBG02) 02 B049 -> SSG-0-2 02/06 C171P1 MBUS-0-2 (MBG02) 02 A040 -> TSG-0-4 02/06 C229P1 MBUS-0-2 (MBG02) 02 A049 -> TSG-0-5 02/06 C229P1 MBUS-1-2 (MBG12) 03 B049 -> SSG-1-2 03/07 C171P1 MBUS-1-2 (MBG12) 03 A040 -> TSG-1-4 03/07 C229P1 MBUS-1-2 (MBG12) 03 A049 -> TSG-1-5 03/07 C229P1 MBUS-0-3 (MBG03) 08 B049 -> SSG-0-3 02/06 C279P1 MBUS-0-3 (MBG03) 08 A040 -> TSG-0-6 02/06 C229P1 MBUS-0-3 (MBG03) 08 A049 -> TSG-0-7 02/06 C229P1 MBUS-1-3 (MBG13) 09 B049 -> SSG-1-3 03/07 C279P1 MBUS-1-3 (MBG13) 09 A040 -> TSG-1-6 03/07 C229P1 MBUS-1-3 (MBG13) 09 A049 -> TSG-1-7 03/07 C229P1

*) for MBUS

MUT02 and 03, 08 and 09 in R:MB/CCG MUT04 and 05 in R:SN/MB/LTGM MUT02 and 03, cable routing at the top MUT06 and 07, cable routing at the bottom

*) for SN

Tab. 3.199 F:MB/CCG(B): cables MBUS - SGC:SSG(B) and TSG(B)

Cables MBUL <--> SNB MBUL-0-0 (MB0) 02 A055 -> SN0 02/06 C109P1 MBUL-1-0 (MB1) 03 A055 -> SN1 03/07 C109P1

Tab. 3.200 F:MB/CCG(B): cables MBUL -> SNB(63LTG)

A30828-X1160-M-2-7620

423

Construction

Maintenance Node

Capacity Stage SN(126LTG)

Cables MBUL <--> TSG MBUL-0-0 (MBG00) 02/04*) A055 -> TSG-0-0 02/06 C109P1 MBUL-0-1 (MBG00) 02/04 B055 -> TSG-0-1 02/06 C109P1 MBUL-1-0 (MBG10) 03/05 A055 -> TSG-1-0 03/07 C109P1 MBUL-1-1 (MBG10) 03/05 B055 -> TSG-1-1 03/07 C109P1

SN(252LTG)

additional cables in R:MB/CCG or in the additional R:SN/MB/LTGx MBUL-0-2 (MBG01) 08/04 A055 -> TSG-0-2 02/06 C109P1**) MBUL-0-3 (MBG01) 08/04 B055 -> TSG-0-3 02/06 C109P1 MBUL-1-2 (MBG11) 09/05 A055 -> TSG-1-2 03/07 C109P1**) MBUL-1-3 (MBG11) 09/05 B055 -> TSG-1-3 03/07 C109P1

SN(504LTG)

additional cables in the extension rack MB/CCG or in the additional R:SN/MB/LTGx MBUL-0-4 (MBG02) 02/04 A055 -> TSG-0-4 02/06 C109P1**) MBUL-0-5 (MBG02) 02/04 B055 -> TSG-0-5 02/06 C109P1 MBUL-1-4 (MBG12) 03/05 A055 -> TSG-1-4 03/07 C109P1**) MBUL-1-5 (MBG12) 03/05 B055 -> TSG-1-5 03/07 C109P1 MBUL-0-6 (MBG03) 08/04 A055 -> TSG-0-6 02/06 C109P1**) MBUL-0-7 (MBG03) 08/04 B055 -> TSG-0-7 02/06 C109P1

*) for MBUL

MUT02 and 03, 08 and 09 in R:MB/CCG MUT04 and 05 in R:SN/MB/LTGM MUT02 and 03, cable routing at the top MUT06 and 07, cable routing at the bottom For clock distribution the first MBU:LTG must be present in all F:MB/CCG(B). If no TSG is connected to this MBU/LTG (reduced capacity), a link connector must be inserted as a termination at the cable outlet to the TSG. Depending on the installed capacity and number of connected TSGs the following link connectors are necessary.

*) for SN

**)

Tab. 3.201 F:MB/CCG(B): cables MBUL <-> TSG(B)

BST -> 08 A055 with TSG0 or TSG0 and TSG1 BST -> 09 A055

Tab. 3.202 Link connectors for reduced capacity in SN(B)(252LTG)

with TSG0 or TSG0 and TSG1

BST -> 08 A055 BST -> 09 A055 extension rack BST -> 02 A055 BST -> 03 A055 BST -> 08 A055 BST -> 09 A055

Tab. 3.203 Link connectors for reduced capacity in SN(B) (504LTG)

424

A30828-X1160-M-2-7620

Maintenance Node

Construction

with TSG2 or TSG2 and TSG3

extension rack BST -> 02 A055 BST -> 03 A055 BST -> 08 A055 BST -> 09 A055 extension rack BST -> 08 A055 BST -> 09 A055

with TSG4 or TSG4 and TSG5

Tab. 3.203 Link connectors for reduced capacity in SN(B) (504LTG) Cabling MBB <--> CCGA
Capacity Stage SN(63LTG) and SN(126LTG) Clock Cables CCG <--> MBUL CCG0 02/04*) A086 -> MBUL-1-0 (MBG10) 03/05 A065 CCG0 02/04 B086 -> MBUL-0-0 (MBG00) 02/04 A065 CCG1 03/05 A086 -> MBUL-1-0 (MBG10) 03/05 B065 CCG1 03/05 B086 -> MBUL-0-0 (MBG00) 02/04 B065 SN(252LTG) additional cables in R:MB/CCG or in the additional R:SN/MB/LTGx CCG0 02/04 A083 -> MBUL-1-2 (MBG11) 09/05 A065 CCG0 02/04 B083 -> MBUL-0-2 (MBG01) 08/04 A065 CCG1 03/05 A083 -> MBUL-1-2 (MBG11) 09/05 A065 CCG1 03/05 B083 -> MBUL-0-2 (MBG01) 08/05 A065 SN(504LTG) additional cables in the extension rack MB/CCG or in the additional R:SN/MB/LTGx CCG0 02/04 A080 -> MBUL-1-4 (MBG12) 03/05 A065 CCG0 02/04 B080 -> MBUL-0-4 (MBG02) 02/04 A065 CCG1 03/05 A080 -> MBUL-1-4 (MBG12) 03/05 B065 CCG1 03/05 B080 -> MBUL-0-4 (MBG02) 02/04 B065 CCG0 02/04 A077 -> MBUL-1-6 (MBG13) 09/05 A065 CCG0 02/04 B077 -> MBUL-0-6 (MBG03) 08/04 A065 CCG1 03/05 A077 -> MBUL-1-6 (MBG13) 09/05 B065 CCG1 03/05 B077 -> MBUL-0-6 (MBG03) 08/04 B065 *) MUT02 and 03, 08 and 09 in R:MB/CCG MUT04 and 05 in R:SN/MB/LTGM

Tab. 3.204 F:MB/CCG(B): cables CCG - MB Internal Cabling CCGA


Internal Cabling 02 B105 --> 03 A105 Cabling CCG-0 <--> CCG-1 for master/slave setting cross-joint connection for 8MHzCCGXXA clock, CCGB clock (master/slave), and serial CCGB data interface

Tab. 3.205 F:MB/CCG(B) cables master/slave

A30828-X1160-M-2-7620

425

Construction

Maintenance Node

Plesiochronous mode 02 B114 --> 03 A114

no reference frequency cabled: Internal cabling CCG-0 <--> CCG-1 Synchronization of CCG1 by CCG0 (plug position A111 and B111 in CCG0 and CCG1 remain free)

Tab. 3.206 F:MB/CCG(B) internal cabling (plesiochronous)

Synchronous mode: Reference Frequency Cabling (external references) 02 A111 CCG0 <-- reference frequency 0 from F:LTGx or F:STMI 03 B111 CCG1 <-- reference frequency 1 from F:LTGx or F:STMI 03 A111 CCG1 <-- reference frequency 2 from F:LTGx or F:STMI 02 B111 CCG0 <-- reference frequency 3 from F:LTGx or F:STMI

Remark

The reference frequencies can also be cabled via a distribution frame from atomic frequency standards or carrier frequency links (exception case)

Tab. 3.207 F:MB/CCG(B) reference frequency cables (synchronous)

Synchronous mode:

Internal cabling CCG0 <--> CCG1 depending on the number of external reference frequencies being applied (regardless of whether the source is PCM (carrier frequency or atomic frequency standard). reference frequency 0 cabled (1 reference frequency) CCG0 --> CCG1 Incoming clock passed on to CCG1 reference frequencies 0 and 1 cabled (2 reference frequencies) CCG0 --> CCG1 Cross-joint connection of reference frequencies reference frequencies 0, 1 and 2 cabled (3 reference frequencies) CCG0 --> CCG1 Cross-joint connection of reference frequencies If reference frequencies 0 to 3 are cabled (4 reference frequencies) no further cabling is necessary here.

02 A112 --> 03 A112 02 A112 --> 03 A112 02 A112 --> 03 A112

Tab. 3.208 F:MB/CCG(B) internal cables (synchronous) Cross-joint connections CCGA and IOP or PIOP, MB, CDEX
Cross-joint cables CCG <--> IOP (CP113) CCG0: 02 A095 --> IOP0: 03 C135P2 CCG0: 02 A101 --> IOP1: 04 C135P2 CCG0: 02 B095 --> IOP0: 03 C135P1 CCG0: 02 B101 --> IOP1: 04 C135P1 CCG1: 03 A095 --> IOP0: 03 C135P4 CCG1: 03 A101 --> IOP1: 04 C135P4 CCG1: 03 B095 --> IOP0: 03 C135P3 CCG1: 03 B101 --> IOP1: 04 C135P3

Tab. 3.209 F:MB/CCG(B) cables CCG <-> CP113

Cross-joint cables CCG <--> PIOP(A) (CP113C) CCG0: 02 A095 --> PIOP(A)0: 03 C301P2 CCG0: 02 A101 --> PIOP(A)1: 07 C301P2 CCG0: 02 B095 --> PIOP(A)0: 03 C301P1 CCG0: 02 B101 --> PIOP(A)1: 07 C301P1 CCG1: 03 A095 --> PIOP(A)0: 03 C301P4 CCG1: 03 A101 --> PIOP(A)1: 07 C301P4 CCG1: 03 B095 --> PIOP(A)0: 03 C301P3 CCG1: 03 B101 --> PIOP(A)1: 07 C301P3

Tab. 3.210 F:MB/CCG(B) cables CCG <-> CP113C, PIOP(A)

426

A30828-X1160-M-2-7620

Maintenance Node

Construction

Clock cables CCG <--> PIOP(A) (CP113C) CCG0: 02 A071 --> PIOP(A)1: 07 C329P2 CCG0: 02 B071 --> PIOP(A)0: 03 C329P2 CCG1: 03 A071 --> PIOP(A)1: 07 C329P3 CCG1: 03 B071 --> PIOP(A)0: 03 C329P3

Tab. 3.211 F:MB/CCG(B) clock cables CCG <-> CP113C, PIOP(A)

Cross-joint cables CCG <--> F:PIOP(B) (CP113C) CCG0: 02 A095 -> PIOP(B)0: 03 C321P2 CCG0: 02 A101 -> PIOP(B)1: 07 C321P2 CCG0: 02 B095 -> PIOP(B)0: 03 C321P1 CCG0: 02 B101 -> PIOP(B)1: 07 C321P1 CCG1: 03 A095 -> PIOP(B)0: 03 C321P4 CCG1: 03 A101 -> PIOP(B)1: 07 C321P4 CCG1: 03 B095 -> PIOP(B)0: 03 C321P3 CCG1: 03 B101 -> PIOP(B)1: 07 C321P3

Tab. 3.212 F:MB/CCG(B) cables CCG <-> CP113C, PIOP(B)

Cross-joint cables CCG <--> CP113E, F:BIOP (F:BIOP is connected to IOC0 and IOC1) CCG0: 02 A095 --> BIOP: 05 C183P2 CCG0: 02 A101 --> BIOP: 05 C315P2 CCG0: 02 B095 --> BIOP: 05 C183P1 CCG0: 02 B101 --> BIOP: 05 C315P1 CCG1: 03 A095 --> BIOP: 05 C183P4 CCG1: 03 A101 --> BIOP: 05 C315P4 CCG1: 03 B095 --> BIOP: 05 C183P3 CCG1: 03 B101 --> BIOP: 05 C315P3

Tab. 3.213 F:MB/CCG(B) cables CCG <-> CP113E, BIOP

Clock cables CCG <--> CP113E, F:BIOP (F:BIOP is connected to IOC0 and IOC1) CCG0: 02 A071 --> BIOP: 05 C329P2 CCG0: 02 B071 --> BIOP: 05 C197P2 CCG1: 03 A071 --> BIOP: 05 C329P3 CCG1: 03 B071 --> BIOP: 05 C197P3

Tab. 3.214 F:MB/CCG(B) clock cables CCG <-> CP113E, BIOP

Cross-joint cables CCG <--> CP113E, F:EIOP (Both F:EIOP are connected to IOC0 and IOC1) CCG0: 02 A095 --> EIOP: 03 C303P2 CCG0: 02 A101 --> EIOP: 04 C303P2 CCG0: 02 B095 --> EIOP: 03 C303P1 CCG0: 02 B101 --> EIOP: 04 C303P1 CCG1: 03 A095 --> EIOP: 03 C303P4 CCG1: 03 A101 --> EIOP: 04 C303P4 CCG1: 03 B095 --> EIOP: 03 C303P3 CCG1: 03 B101 --> EIOP: 04 C303P3

Tab. 3.215 F:MB/CCG(B) cables CCG <-> CP113E, EIOP

Clock cables CCG <--> EIOP (CP113E) CCG0: 02 A071 --> EIOP: 04 C317P2 CCG0: 02 B071 --> EIOP: 03 C317P2 CCG1: 03 A071 --> EIOP: 04 C317P3 CCG1: 03 B071 --> EIOP: 03 C317P3

Tab. 3.216 F:MB/CCG(B) clock cables CCG <-> CP113E, EIOP

A30828-X1160-M-2-7620

427

Construction

Maintenance Node

SN Capacity Stage SN(63LTG) and SN(126LTG)

Cross-joint cables CCG --> MB CCG0 02 A086 -> MBUL-1-0 (MBG10) 03 A065 CCG0 02 B086 -> MBUL-0-0 (MBG00) 02 A065 CCG1 03 A086 -> MBUL-1-0 (MBG10) 03 B065 CCG1 03 B086 -> MBUL-0-0 (MBG00) 02 B065

SN(252LTG)

additional cables CCG0 02 A083 -> MBUL-1-2 (MBG11) 09 A065 CCG0 02 B083 -> MBUL-0-2 (MBG01) 08 A065 CCG1 03 A083 -> MBUL-1-2 (MBG11) 09 A065 CCG1 03 B083 -> MBUL-0-2 (MBG01) 08 A065

SN(504LTG)

additional cables in the extension rack MB/CCG CCG0 02 A080 -> MBUL-1-4 (MBG12) 03 A065 CCG0 02 B080 -> MBUL-0-4 (MBG02) 02 A065 CCG1 03 A080 -> MBUL-1-4 (MBG12) 03 B065 CCG1 03 B080 -> MBUL-0-4 (MBG02) 02 B065 CCG0 02 A077 -> MBUL-1-6 (MBG13) 09 A065 CCG0 02 B077 -> MBUL-0-6 (MBG03) 08 A065 CCG1 03 A077 -> MBUL-1-6 (MBG13) 09 B065 CCG1 03 B077 -> MBUL-0-6 (MBG03) 08 B065

Tab. 3.217 F:MB/CCG(B) cables CCG - MB Cabling CCGA --> SYPC


Cabling CCG --> F:SYPC(A) CCG0: 02 A108 --> CDEX1: 05 A064 CCG0: 02 B108 --> CDEX0: 05 A058 CCG1: 03 A108 --> CDEX1 05 B064 CCG1: 03 B108 --> CDEX0 05 B058

Tab. 3.218 F:MB/CCG(B) cables CCG <-> CDEX

428

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.5.2 3.5.2.1

F:MBD F:MBD (module side)

D
MBDCG MBDH0 MBDA2 MBDH7 MBDA0 MBDH6 MBDH1 MBDH4 MBDA1 MBDH3 MBDA4 MBDA2 MBDA3 C317
1 0 5 1 1 1 1

C101

C117

C133

C165

C223

C149

C183

C207

C235

C267

C301

Modules with displays and switches in F:MBD MBDA (-Q54-) MBDC (-Q55-) MBDCG (-Q56-) MBDH (-Q57-)

Tab. 3.219 Modules with displays and switches in F:MBD

3.5.2.2

F:MBD (backplane)
P1 P2 8 2 8 2 5 1 1 4 4 4
0S 0D 0S

C251

4
0D

C285

C
P3 P4 P5 P1 P2

1 0 5

1 0 5 1 1

1 0 5 1 1 9
aa

4 4 4
2S 1S 1S

1 0 5

5 10 0 10 1 2 0 3 0

4 4 4
2D 1D 1D

4 4 4
3S 3S 2S

4 4 4
3D 3D 2D

D
P3 P4

2 0 3 0 2 1

2 1 2 2 3 2 2 1 3 3

2 0 3 0 2 1 3 1

2 1 2 2 3 2 2 1 3 3 3 3

3 3 1 3

2 0 3 0 2 1 3 1

2 1 2 2 3 2 2 1 3 3 3 3

C333
8 1 8 1 5 10 0 10 1 2 0 3 0 2 1 3 1 2 2 3 2 2 3 3 3

2 2 7 0 2 3 3 6 0 2 2 2 1 3 6 3 3 9 1 3 b

2 2 3 2

4 4 4
5S 4S 4S

4 4 4
5D 4D 4D

2 0 3 0 2 1 3 1

2 1 2 2 3 2 2 1 3 3 3 3

2 2 4 4 4 1 3 6S 6S 5S 3 3 4 4 4 1 3 6D 6D 5D

2 1 2 2 3 2 2 2 1 1 3 3 3 3 1 3 2 0 3 0

MBDH MBDA MBDH MBDA MBDH MBDA MBDH MBD MBDH MBDC 5 1 CG 3 4 4 1 2 3

MBDH MBDA MBDH MBDA MBDH 6 0 7 2 0

A30828-X1160-M-2-7620

MBDH5

MBDC

429

Construction

Maintenance Node

3.5.2.3

F:MBD (cabling)
Cabling MBD <--> SSNC (plug 10...13)
From MBD Connector 10 11 12 13 10 11 12 13 10 11 12 13 10 11 12 13 10 11 12 13 10 11 12 13 10 11 12 13 10 11 12 13 10 11 Unit F:MBD0 / MBDA0 F:MBD0 / MBDA0 F:MBD0 / MBDA0 F:MBD0 / MBDA0 F:MBD1 / MBDA0 F:MBD1 / MBDA0 F:MBD1 / MBDA0 F:MBD1 / MBDA0 F:MBD0 / MBDA1 F:MBD0 / MBDA1 F:MBD0 / MBDA1 F:MBD0 / MBDA1 F:MBD1 / MBDA1 F:MBD1 / MBDA1 F:MBD1 / MBDA1 F:MBD1 / MBDA1 F:MBD0 / MBDA2 F:MBD0 / MBDA2 F:MBD0 / MBDA2 F:MBD0 / MBDA2 F:MBD1 / MBDA2 F:MBD1 / MBDA2 F:MBD1 / MBDA2 F:MBD1 / MBDA2 F:MBD0 / MBDA3 F:MBD0 / MBDA3 F:MBD0 / MBDA3 F:MBD0 / MBDA3 F:MBD1 / MBDA3 F:MBD1 / MBDA3 F:MBD1 / MBDA3 F:MBD1 / MBDA3 F:MBD0 / MBDA4 F:MBD0 / MBDA4 MOLOC C157P1 C157P3 C157P5 D157P2 C157P1 C157P3 C157P5 D157P2 C259P1 C259P3 C259P5 D259P2 C259P1 C259P3 C259P5 D259P2 C125P1 C125P3 C125P5 D125P2 C125P1 C125P3 C125P5 D125P2 C325P1 C325P3 C325P5 D325P2 C325P1 C325P3 C325P5 D325P2 C293P1 C293P3 Unit F:SCB / AMX0 F:SCB / AMX1 F:SCB / AMX0 F:SCB / AMX1 F:SCB / AMX0 F:SCB / AMX1 F:SCB / AMX0 F:SCB / AMX1 F:SCE0 / AMX0 F:SCE0 / AMX1 F:SCE0 / AMX0 F:SCE0 / AMX1 F:SCE0 / AMX0 F:SCE0 / AMX1 F:SCE0 / AMX0 F:SCE0 / AMX1 F:SCE1 / AMX0 F:SCE1 / AMX1 F:SCE1 / AMX0 F:SCE1 / AMX1 F:SCE1 / AMX0 F:SCE1 / AMX1 F:SCE1 / AMX0 F:SCE1 / AMX1 F:SCE1 / AMX0 F:SCE2 / AMX1 F:SCE2 / AMX0 F:SCE2 / AMX1 F:SCE2 / AMX0 F:SCE2 / AMX1 F:SCE2 / AMX0 F:SCE2 / AMX1 F:SCE3 / AMX0 F:SCE3 / AMX1 To SSNC MOLOC C149P1 C211P1 C149P5 C211P5 C149P3 C211P3 D149P2 D211P2 C221P1 C261P1 C221P5 C261P5 C221P3 C261P3 D221P2 D261P2 C221P1 C261P1 C221P5 C261P5 C221P3 C261P3 D221P2 D261P2 C221P1 C261P1 C221P5 C261P5 C221P3 C261P3 D221P2 D261P2 C221P1 C261P1

Tab. 3.220 cables MBD <--> SSNC

430

A30828-X1160-M-2-7620

Maintenance Node

Construction

From MBD Connector 12 13 10 11 12 13 Unit F:MBD0 / MBDA4 F:MBD0 / MBDA4 F:MBD1 / MBDA4 F:MBD1 / MBDA4 F:MBD1 / MBDA4 F:MBD1 / MBDA4 MOLOC C293P5 D293P2 C293P1 C293P3 C293P5 D293P2 Unit

To SSNC MOLOC C221P5 C261P5 C221P3 C261P3 D221P2 D261P2

F:SCE3 / AMX0 F:SCE3 / AMX1 F:SCE3 / AMX0 F:SCE3 / AMX1 F:SCE3 / AMX0 F:SCE3 / AMX1

Tab. 3.220 cables MBD <--> SSNC Cabling MBD <--> SN (Connector 20, 30, 22, 32, 100, 101)
From MBD Connector 100 30 31 100 30 31 101 32 33 101 32 33 100 30 31 100 30 31 101 32 33 101 32 33 Unit F:MBD0 / MBDH0 F:MBD0 / MBDH0 F:MBD0 / MBDH0 F:MBD1 / MBDH0 F:MBD1 / MBDH0 F:MBD1 / MBDH0 F:MBD0 / MBDH0 F:MBD0 / MBDH0 F:MBD0 / MBDH0 F:MBD1 / MBDH0 F:MBD1 / MBDH0 F:MBD1 / MBDH0 F:MBD0 / MBDH1 F:MBD0 / MBDH1 F:MBD0 / MBDH1 F:MBD1 / MBDH1 F:MBD1 / MBDH1 F:MBD1 / MBDH1 F:MBD0 / MBDH1 F:MBD0 / MBDH1 F:MBD0 / MBDH1 F:MBD1 / MBDH1 F:MBD1 / MBDH1 F:MBD1 / MBDH1 MOLOC C109P4 D109P2 D109P4 C109P4 D109P2 D109P4 C109P5 D101P2 D101P4 C109P5 D101P2 D101P4 C215P4 D215P2 D215P4 C215P4 D215P2 D215P4 C215P5 D207P2 D207P4 C215P5 D207P2 D207P4 Unit F:SSG0 / SN0: SSG-0-0 F:SN or F:TSG0 / SN0: TSG-0-0 F:TSG1 / SN0: TSG-0-1 F:SSG0 / SN1: SSG-1-0 F:SN or F:TSG0 / SN1: TSG-1-0 F:TSG1 / SN1: TSG-1-1 F:SSG1 / SN0: SSG-0-1 F:TSG2 / SN0: TSG-0-2 F:TSG3 / SN0: TSG-0-3 F:SSG1 / SN1: SSG-1-1 F:TSG2 / SN1: TSG-1-2 F:TSG3 / SN1: TSG-1-3 F:SSG2 / SN0: SSG-0-2 F:TSG4 / SN0: TSG-0-4 F:TSG5 / SN0: TSG-0-5 F:SSG2 / SN1: SSG-1-2 F:TSG4 / SN1: TSG-1-4 F:TSG5 / SN1: TSG-1-5 F:SSG3 / SN0: SSG-0-3 F:TSG6 / SN0: TSG-0-6 F:TSG7 / SN0: TSG-0-7 F:SSG3 / SN1: SSG-1-3 F:TSG6 / SN1: TSG-1-6 F:TSG7 / SN1: TSG-1-7 To SGC SN MOLOC 02A061 02A061 02A061 03A061 03A061 03A061 02A061 02A061 02A061 03A061 03A061 03A061 02A061 02A061 02A061 03A061 03A061 03A061 02A061 02A061 02A061 03A061 03A061 03A061

Tab. 3.221 cabling SGC- interface MBD <--> SNA

A30828-X1160-M-2-7620

431

Construction

Maintenance Node

From MBD Connector 20 21 20 21 22 23 22 23 20 21 20 21 22 23 22 23 Unit F:MBD0 / MBDH0 F:MBD0 / MBDH0 F:MBD1 / MBDH0 F:MBD1 / MBDH0 F:MBD0 / MBDH0 F:MBD0 / MBDH0 F:MBD1 / MBDH0 F:MBD1 / MBDH0 F:MBD0 / MBDH1 F:MBD0 / MBDH1 F:MBD1 / MBDH1 F:MBD1 / MBDH1 F:MBD0 / MBDH1 F:MBD0 / MBDH1 F:MBD1 / MBDH1 F:MBD1 / MBDH1 MOLOC D109P1 D109P3 D109P1 D109P3 D101P1 D101P3 D101P1 D101P3 D215P1 D215P3 D215P1 D215P3 D207P1 D207P3 D207P1 D207P3 Unit

To SN MOLOC 02A003 02A003 03A003 03A003 02A003 02A003 03A003 03A003 02A003 02A003 03A003 03A003 02A003 02A003 03A003 03A003

F:SN or F:TSG0 / SN0: TSG-0-0 F:TSG1 / SN0: TSG-0-1 F:SN or F:TSG0 / SN1: TSG-1-0 F:TSG1 / SN1: TSG-1-1 F:TSG2 / SN0: TSG-0-2 F:TSG3 / SN0: TSG-0-3 F:TSG2 / SN1: TSG-1-2 F:TSG3 / SN1: TSG-1-3 F:TSG4 / SN0: TSG-0-4 F:TSG5 / SN0: TSG-0-5 F:TSG4 / SN1: TSG-1-4 F:TSG5 / SN1: TSG-1-5 F:TSG6 / SN0: TSG-0-6 F:TSG7 / SN0: TSG-0-7 F:TSG6 / SN1: TSG-1-6 F:TSG7 / SN1: TSG-1-7

Tab. 3.222 Cabling LTG interface MBD <--> SNA Cabling MBD <--> SNB (Connector 20...23, 30...33, 100, 101)
From MBD Connector 100 30 31 100 30 31 101 32 33 101 32 33 100 30 Unit F:MBD0 / MBDH0 F:MBD0 / MBDH0 F:MBD0 / MBDH0 F:MBD1 / MBDH0 F:MBD1 / MBDH0 F:MBD1 / MBDH0 F:MBD0 / MBDH0 F:MBD0 / MBDH0 F:MBD0 / MBDH0 F:MBD1 / MBDH0 F:MBD1 / MBDH0 F:MBD1 / MBDH0 F:MBD0 / MBDH1 F:MBD0 / MBDH1 MOLOC C109P4 D109P2 D109P4 C109P4 D109P2 D109P4 C109P5 D101P2 D101P4 C109P5 D101P2 D101P4 C215P4 D215P2 Unit F:SSG(B)0 / SN0: SSG-0-0 F:TSG(B)0 / SN0: TSG-0-0 F:TSG(B)0 / SN0: TSG-0-1 F:SSG(B)0 / SN1: SSG-1-0 F:TSG(B)0 / SN1: TSG-1-0 F:TSG(B)1 / SN1: TSG-1-1 F:SSG(B)1 / SN0: SSG-0-1 F:TSG(B)2 / SN0: TSG-0-2 F:TSG(B)3 / SN0: TSG-0-3 F:SSG(B)1 / SN1: SSG-1-1 F:TSG(B)2 / SN1: TSG-1-2 F:TSG(B)3 / SN1: TSG-1-3 F:SSG(B)2 / SN0: SSG-0-2 F:TSG(B)4 / SN0: TSG-0-4 To SGC SNB MOLOC C171P1 C229P1 C229P1 C171P1 C229P1 C229P1 C279P1 C229P1 C229P1 C279P1 C229P1 C229P1 C171P1 C229P1

Tab. 3.223 Cabling SGC interface MBD <--> SNB

432

A30828-X1160-M-2-7620

Maintenance Node

Construction

From MBD Connector 31 100 30 31 101 32 33 101 32 33 Unit F:MBD0 / MBDH1 F:MBD1 / MBDH1 F:MBD1 / MBDH1 F:MBD1 / MBDH1 F:MBD0 / MBDH1 F:MBD0 / MBDH1 F:MBD0 / MBDH1 F:MBD1 / MBDH1 F:MBD1 / MBDH1 F:MBD1 / MBDH1 MOLOC D215P4 C215P4 D215P2 D215P4 C215P5 D207P2 D207P4 C215P5 D207P2 D207P4 Unit

To SGC SNB MOLOC C229P1 C171P1 C229P1 C229P1 C279P1 C229P1 C229P1 C279P1 C229P1 C229P1

F:TSG(B)5 / SN0: TSG-0-5 F:SSG(B)2 / SN1: SSG-1-2 F:TSG(B)4 / SN1: TSG-1-4 F:TSG(B)5 / SN1: TSG-1-5 F:SSG(B)3 / SN0: SSG-0-3 F:TSG(B)6 / SN0: TSG-0-6 F:TSG(B)7 / SN0: TSG-0-7 F:SSG(B)3 / SN1: SSG-1-3 F:TSG(B)6 / SN1: TSG-1-6 F:TSG(B)7 / SN1: TSG-1-7

Tab. 3.223 Cabling SGC interface MBD <--> SNB

From MBD Connector 20 21 20 21 22 23 22 23 20 21 20 21 22 23 22 23 Unit F:MBD0 / MBDH0 F:MBD0 / MBDH0 F:MBD1 / MBDH0 F:MBD1 / MBDH0 F:MBD0 / MBDH0 F:MBD0 / MBDH0 F:MBD1 / MBDH0 F:MBD1 / MBDH0 F:MBD0 / MBDH1 F:MBD0 / MBDH1 F:MBD1 / MBDH1 F:MBD1 / MBDH1 F:MBD0 / MBDH1 F:MBD0 / MBDH1 F:MBD1 / MBDH1 F:MBD1 / MBDH1 MOLOC D109P1 D109P3 D109P1 D109P3 D101P1 D101P3 D101P1 D101P3 D215P1 D215P3 D215P1 D215P3 D207P1 D207P3 D207P1 D207P3 Unit

To SNB MOLOC C109P1 C109P1 C109P1 C109P1 C109P1 C109P1 C109P1 C109P1 C109P1 C109P1 C109P1 C109P1 C109P1 C109P1 C109P1 C109P1

F:TSG(B)0 / SN0: TSG-0-0 F:TSG(B)1 / SN0: TSG-0-1 F:TSG(B)0 / SN1: TSG-1-0 F:TSG(B)1 / SN1: TSG-1-1 F:TSG(B)2 / SN0: TSG-0-2 F:TSG(B)3 / SN0: TSG-0-3 F:TSG(B)2 / SN1: TSG-1-2 F:TSG(B)3 / SN1: TSG-1-3 F:TSG(B)4 / SN0: TSG-0-4 F:TSG(B)5 / SN0: TSG-0-5 F:TSG(B)4 / SN1: TSG-1-4 F:TSG(B)5 / SN1: TSG-1-5 F:TSG(B)6 / SN0: TSG-0-6 F:TSG(B)7 / SN0: TSG-0-7 F:TSG(B)6 / SN1: TSG-1-6 F:TSG(B)7 / SN1: TSG-1-7

Tab. 3.224 Cabling LTG interface MBD <--> SNB

A30828-X1160-M-2-7620

433

Construction

Maintenance Node

Cabling MBD <--> SND with F:SNMUX(A) (Connector 7, 20, 21)


From MBD Connector 7 7 7* 7* Unit F:MBD0 / MBDCG F:MBD1 / MBDCG F:MBD0 / MBDCG F:MBD1 / MBDCG MOLOC D229P1 D229P1 D229P1 D229P1 Unit F:SNMAT / SN0 F:SNMAT / SN1 F:SNMUX(A)0 / SN0 F:SNMUX(A)0 / SN1 To SND MOLOC D239P3 D239P3 C235P5 C235P5

* only without F:SNMAT

Tab. 3.225 Cabling MBDCG interface MBD <--> SND

From MBD Connector 20 20 22 22 20 20 22 22 20 20 22 22 20 20 22 22 20 20 22 22 20 20 22 22 20 Unit F:MBD0 / MBDH0 F:MBD1 / MBDH0 F:MBD0 / MBDH0 F:MBD1 / MBDH0 F:MBD0 / MBDH1 F:MBD1 / MBDH1 F:MBD0 / MBDH1 F:MBD1 / MBDH1 F:MBD0 / MBDH2 F:MBD1 / MBDH2 F:MBD0 / MBDH2 F:MBD1 / MBDH2 F:MBD0 / MBDH3 F:MBD1 / MBDH3 F:MBD0 / MBDH3 F:MBD1 / MBDH3 F:MBD0 / MBDH4 F:MBD1 / MBDH4 F:MBD0 / MBDH4 F:MBD1 / MBDH4 F:MBD0 / MBDH5 F:MBD1 / MBDH5 F:MBD0 / MBDH5 F:MBD1 / MBDH5 F:MBD0 / MBDH6 MOLOC D109P1 D109P1 D101P1 D101P1 D215P1 D215P1 D207P1 D207P1 D309P1 D309P1 D301P1 D301P1 D275P1 D275P1 D267P1 D267P1 D243P1 D243P1 D235P1 D235P1 D341P1 D341P1 D333P1 D333P1 D173P1 Unit F:SNMUX(A)0 / SN0 F:SNMUX(A)0 / SN1 F:SNMUX(A)1 / SN0 F:SNMUX(A)1 / SN1 F:SNMUX(A)2 / SN0 F:SNMUX(A)2 / SN1 F:SNMUX(A)3 / SN0 F:SNMUX(A)3 / SN1 F:SNMUX(A)4 / SN0 F:SNMUX(A)4 / SN1 F:SNMUX(A)5 / SN0 F:SNMUX(A)5 / SN1 F:SNMUX(A)6 / SN0 F:SNMUX(A)6 / SN1 F:SNMUX(A)7 / SN0 F:SNMUX(A)7 / SN1 F:SNMUX(A)8 / SN0 F:SNMUX(A)8 / SN1 F:SNMUX(A)9 / SN0 F:SNMUX(A)9 / SN1

To SND MOLOC C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1

F:SNMUX(A)10 / SN0 F:SNMUX(A)10 / SN1 F:SNMUX(A)11 / SN0 F:SNMUX(A)11 / SN1 F:SNMUX(A)12 / SN0

Tab. 3.226 Cabling LTG interface MBD <--> SND

434

A30828-X1160-M-2-7620

Maintenance Node

Construction

From MBD Connector 20 22 22 20 20 22 22 Unit F:MBD1 / MBDH6 F:MBD0 / MBDH6 F:MBD1 / MBDH6 F:MBD0 / MBDH7 F:MBD1 / MBDH7 F:MBD0 / MBDH7 F:MBD1 / MBDH7 MOLOC D173P1 D165P1 D165P1 D141P1 D141P1 D133P1 D133P1 Unit

To SND MOLOC C199P1 C199P1 C199P1 C199P1 C199P1 C199P1 C199P1

F:SNMUX(A)12 / SN1 F:SNMUX(A)13 / SN0 F:SNMUX(A)13 / SN1 F:SNMUX(A)14 / SN0 F:SNMUX(A)14 / SN1 F:SNMUX(A)15 / SN0 F:SNMUX(A)15 / SN1

Tab. 3.226 Cabling LTG interface MBD <--> SND Cabling MBD <--> SND with F:SNMUX(B) (Connector 7, 20, 21)
From MBD Connector 7 7 7* 7* Unit F:MBD0 / MBDCG F:MBD1 / MBDCG F:MBD0 / MBDCG F:MBD1 / MBDCG MOLOC D229P1 D229P1 D229P1 D229P1 Unit F:SNMAT / SN0 F:SNMAT / SN1 F:SNMUX(B)0 / SN0 F:SNMUX(B)0 / SN1 To SND MOLOC D239P3 D239P3 C213P5 C345P5

* only without F:SNMAT

Tab. 3.227 Cabling MBDCG interface MBD <--> SND

From MBD Connector 20 20 22 22 20 20 22 22 20 20 22 22 20 20 Unit F:MBD0 / MBDH0 F:MBD1 / MBDH0 F:MBD0 / MBDH0 F:MBD1 / MBDH0 F:MBD0 / MBDH1 F:MBD1 / MBDH1 F:MBD0 / MBDH1 F:MBD1 / MBDH1 F:MBD0 / MBDH2 F:MBD1 / MBDH2 F:MBD0 / MBDH2 F:MBD1 / MBDH2 F:MBD0 / MBDH3 F:MBD1 / MBDH3 MOLOC D109P1 D109P1 D101P1 D101P1 D215P1 D215P1 D207P1 D207P1 D309P1 D309P1 D301P1 D301P1 D275P1 D275P1 Unit

To SND MOLOC C213P1 C345P1 D213P1 D3451P1 C213P1 C345P1 D213P1 D345P1 C213P1 C345P1 D213P1 D345P1 C213P1 C345P1

F:SNMUX(B)0 / SN0 F:SNMUX(B)0 / SN1 F:SNMUX(B)0 / SN0 F:SNMUX(B)0 / SN1 F:SNMUX(B)1 / SN0 F:SNMUX(B)1 / SN1 F:SNMUX(B)1 / SN0 F:SNMUX(B)1 / SN1 F:SNMUX(B)2 / SN0 F:SNMUX(B)2 / SN1 F:SNMUX(B)2 / SN0 F:SNMUX(B)2 / SN1 F:SNMUX(B)3 / SN0 F:SNMUX(B)3 / SN1

Tab. 3.228 Cabling LTG interface MBD <--> SND

A30828-X1160-M-2-7620

435

Construction

Maintenance Node

From MBD Connector 22 22 20 20 22 22 20 20 22 22 20 20 22 22 20 20 22 22 Unit F:MBD0 / MBDH3 F:MBD1 / MBDH3 F:MBD0 / MBDH4 F:MBD1 / MBDH4 F:MBD0 / MBDH4 F:MBD1 / MBDH4 F:MBD0 / MBDH5 F:MBD1 / MBDH5 F:MBD0 / MBDH5 F:MBD1 / MBDH5 F:MBD0 / MBDH6 F:MBD1 / MBDH6 F:MBD0 / MBDH6 F:MBD1 / MBDH6 F:MBD0 / MBDH7 F:MBD1 / MBDH7 F:MBD0 / MBDH7 F:MBD1 / MBDH7 MOLOC D267P1 D267P1 D243P1 D243P1 D235P1 D235P1 D341P1 D341P1 D333P1 D333P1 D173P1 D173P1 D165P1 D165P1 D141P1 D141P1 D133P1 D133P1 Unit

To SND MOLOC D213P1 D345P1 C213P1 C345P1 D213P1 D345P1 C213P1 C345P1 D213P1 D345P1 C213P1 C345P1 D213P1 D345P1 C213P1 C345P1 D213P1 D345P1

F:SNMUX(B)3 / SN0 F:SNMUX(B)3 / SN1 F:SNMUX(B)4 / SN0 F:SNMUX(B)4/ SN1 F:SNMUX(B)4 / SN0 F:SNMUX(B)4 / SN1 F:SNMUX(B)5 / SN0 F:SNMUX(B)5/ SN1 F:SNMUX(B)5 / SN0 F:SNMUX(B)5 / SN1 F:SNMUX(B)6 / SN0 F:SNMUX(B)6 / SN1 F:SNMUX(B)6 / SN0 F:SNMUX(B)6 / SN1 F:SNMUX(B)7 / SN0 F:SNMUX(B)7 / SN1 F:SNMUX(B)7 / SN0 F:SNMUX(B)7 / SN1

Tab. 3.228 Cabling LTG interface MBD <--> SND MBDE Ethernet and MBD internal cabling (Connector 22, 23, 32, 33)
From MBD Connector 22 23 32 33 22 23 32 33 22 23 32 33 22 Unit F:MBD / MBDE0 F:MBD / MBDE0 F:MBD / MBDE0 F:MBD / MBDE0 F:MBD / MBDE1 F:MBD / MBDE1 F:MBD/ MBDE1 F:MBD / MBDE1 F:MBD/ MBDE2 F:MBD / MBDE2 F:MBD/ MBDE2 F:MBD/ MBDE2 F:MBD/ MBDE3 MOLOC D133P1 D133P3 D133P2 D133P4 D165P1 D165P3 D165P2 D165P4 D333P1 D333P3 D333P2 D333P4 D235P1 Ethernet Unit 1. MBD Ethernet interface --> external 2. MBD Ethernet interface --> external 3. MBD Ethernet interface --> external 4. MBD Ethernet interface --> external 1. MBD Ethernet interface --> external 2. MBD Ethernet interface --> external 3. MBD Ethernet interface --> external 4. MBD Ethernet interface --> external 1. MBD Ethernet interface --> external 2. MBD Ethernet interface --> external 3. MBD Ethernet interface --> external 4. MBD Ethernet interface --> external 1. MBD Ethernet interface --> external

Tab. 3.229 Cabling Ethernet- interface MBD <--> external

436

A30828-X1160-M-2-7620

Maintenance Node

Construction

From MBD Connector 23 32 33 22 23 32 33 Unit F:MBD / MBDE3 F:MBD / MBDE3 F:MBD / MBDE3 F:MBD / MBDE4 F:MBD / MBDE4 F:MBD / MBDE4 F:MBD / MBDE4 MOLOC D235P3 D235P2 D235P4 D267P1 D267P3 D267P2 D267P4

Ethernet Unit 2. MBD Ethernet interface --> external 3. MBD Ethernet interface --> external 4. MBD Ethernet interface --> external 1. MBD Ethernet interface --> external 2. MBD Ethernet interface --> external 3. MBD Ethernet interface --> external 4. MBD Ethernet interface --> external

Tab. 3.229 Cabling Ethernet- interface MBD <--> external Cabling MBD0 <--> MBD1 (Connector 5, 9aa, 9b)
From MBD0 Connector 5 Unit F:MBD0 / MBDH0, MBDA2 F:MBD0 / MBDH1 F:MBD0 / MBDH2, MBDA3 F:MBD0 / MBDE4 or MBDH3, MBDA4 F:MBD0 / MBDE3 or MBDH4, MBDA1 F:MBD0 / MBDE2 or MBDH5 F:MBD0 / MBDE1 or MBDH6, MBDC F:MBD0 / MBDE0 or MBDH7, MBDA0 F:MBD0 / MBDCG F:MBD0 / MBDCG MOLOC C109P3 Unit F:MBD1 / MBDH0, MBDA2 F:MBD1 / MBDH1 F:MBD1 / MBDH2, MBDA3 F:MBD1 / MBDE4 or MBDH3, MBDA4 F:MBD1 / MBDE3 or MBDH4, MBDA1 F:MBD1 / MBDE2 or MBDH5 F:MBD1 / MBDE1 or MBDH6, MBDC F:MBD1 / MBDE0 or MBDH7, MBDA0 F:MBD1 / MBDCG F:MBD1/ MBDCG To MBD1 MOLOC C109P3

5 5

C215P3 C309P3

C215P3 C309P3

C275P3

C275P3

C243P3

C243P3

C341P3

C341P3

C173P3

C173P3

C141P3

C141P3

9aa 9b

C229P3 D229P4

C229P3 D229P4

Tab. 3.230 Cabling MBD0 <--> MBD1 Cabling MBD <--> CP113E/ BIOP (Connector 4) Innovation
From MBD To CP113E, F:BIOP (F:BIOP is connected to IOC0 and IOC1) MOLOC Unit MOLOC

Connector 40D

Unit

F:MBD0 / MBDC

C173P1

F:BIOP (M:IOPMBs in MOLOCs C167 and C299)

05 C167P2

Tab. 3.231 Cabling MBD <---------> CP113E / BIOP

A30828-X1160-M-2-7620

437

Construction

Maintenance Node

From MBD

To CP113E, F:BIOP (F:BIOP is connected to IOC0 and IOC1) MOLOC Unit MOLOC

Connector 40S 40D 40S 40D 40S 40D 40S 41S 41D 41S 41D 41S 41D 41S 41D 42S 42D 42S 42D 42S 42D 42S 42D

Unit

F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC

C189P1 C195P1 C201P1 C173P1 C189P1 C195P1 C201P1 C189P2 C189P3 C195P2 C195P3 C189P2 C189P3 C195P2 C195P3 C189P4 C189P5 C201P2 C201P3 C189P4 C189P5 C201P2 C201P3

F:BIOP (M:IOPMBs in MOLOCs C167 and C299) F:BIOP (M:IOPMBs in MOLOCs C167 and C299) F:BIOP (M:IOPMBs in MOLOCs C167 and C299) F:BIOP (M:IOPMBs in MOLOCs C167 and C299) F:BIOP (M:IOPMBs in MOLOCs C167 and C299) F:BIOP (M:IOPMBs in MOLOCs C167 and C299) F:BIOP (M:IOPMBs in MOLOCs C167 and C299) F:BIOP (M:IOPMBs in MOLOCs C157 and C289) F:BIOP (M:IOPMBs in MOLOCs C157 and C289) F:BIOP (M:IOPMBs in MOLOCs C157 and C289) F:BIOP (M:IOPMBs in MOLOCs C157 and C289) F:BIOP (M:IOPMBs in MOLOCs C157 and C289) F:BIOP (M:IOPMBs in MOLOCs C157 and C289) F:BIOP (M:IOPMBs in MOLOCs C157 and C289) F:BIOP (M:IOPMBs in MOLOCs C157 and C289) F:BIOP (M:IOPMBs in MOLOCs C149 and C281) F:BIOP (M:IOPMBs in MOLOCs C149 and C281) F:BIOP (M:IOPMBs in MOLOCs C149 and C281) F:BIOP (M:IOPMBs in MOLOCs C149 and C281) F:BIOP (M:IOPMBs in MOLOCs C149 and C281) F:BIOP (M:IOPMBs in MOLOCs C149 and C281) F:BIOP (M:IOPMBs in MOLOCs C149 and C281) F:BIOP (M:IOPMBs in MOLOCs C149 and C281)

05 C167P1 05 C299P2 05 C299P1 05 C167P4 05 C167P3 05 C299P4 05 C299P3 05 C157P1 05 C157P2 05 C289P1 05 C289P2 05 C157P3 05 C157P4 05 C289P3 05 C289P4 05 C281P1 05 C281P2 05 C149P1 05 C149P2 05 C281P3 05 C281P4 05 C149P3 05 C149P4

Tab. 3.231 Cabling MBD <---------> CP113E / BIOP Cabling MBD <--> CP113E/ EIOP (Connector 4) Innovation
From MBD To CP113E, F:EIOP (Both F:EIOP are connected to IC0 and IC1) MOLOC C173P1 C189P1 C195P1 C201P1 C173P1 C189P1 Unit F:EIOP (M:IOPMB in MOLOC C287 exists) F:EIOP(M:IOPMB in MOLOC C287 exists) F:EIOP(M:IOPMB in MOLOC C287 exists) F:EIOP(M:IOPMB in MOLOC C287 exists) F:EIOP(M:IOPMB in MOLOC C287 exists) F:EIOP(M:IOPMB in MOLOC C287 exists) MOLOC 03 C287P2 03 C287P1 04 C287P2 04 C287P1 03 C287P4 03 C287P3

Connector 40D 40S 40D 40S 40D 40S

Unit F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC

Tab. 3.232 Cabling MBD <---------> CP113E / EIOP)

438

A30828-X1160-M-2-7620

Maintenance Node

Construction

From MBD

To CP113E, F:EIOP (Both F:EIOP are connected to IC0 and IC1) MOLOC C195P1 C201P1 C189P2 C189P3 C195P2 C195P3 C189P2 C189P3 C195P2 C195P3 C189P4 C189P5 C201P2 C201P3 C189P4 C189P5 C201P2 C201P3 C195P4 C195P5 C201P4 C201P5 C195P4 C195P5 C201P4 C201P5 D189P1 D189P2 D195P1 D195P2 D189P1 D189P2 D195P1 D195P2 Unit F:EIOP(M:IOPMB in MOLOC C287 exists) F:EIOP(M:IOPMB in MOLOC C287 exists) F:EIOP (M:IOPMB in MOLOC C279 exists) F:EIOP (M:IOPMB in MOLOC C279 exists) F:EIOP (M:IOPMB in MOLOC C279 exists) F:EIOP (M:IOPMB in MOLOC C279 exists) F:EIOP (M:IOPMB in MOLOC C279 exists) F:EIOP (M:IOPMB in MOLOC C279 exists) F:EIOP (M:IOPMB in MOLOC C279 exists) F:EIOP (M:IOPMB in MOLOC C279 exists) F:EIOP (M:IOPMB in MOLOC C271 exists) F:EIOP (M:IOPMB in MOLOC C271 exists) F:EIOP (M:IOPMB in MOLOC C271 exists) F:EIOP (M:IOPMB in MOLOC C271 exists) F:EIOP (M:IOPMB in MOLOC C271 exists) F:EIOP (M:IOPMB in MOLOC C271 exists) F:EIOP (M:IOPMB in MOLOC C271 exists) F:EIOP (M:IOPMB in MOLOC C271 exists) F:EIOP (M:IOPMB in MOLOC C261 exists) F:EIOP (M:IOPMB in MOLOC C261 exists) F:EIOP (M:IOPMB in MOLOC C261 exists) F:EIOP (M:IOPMB in MOLOC C261 exists) F:EIOP (M:IOPMB in MOLOC C261 exists) F:EIOP (M:IOPMB in MOLOC C261 exists) F:EIOP (M:IOPMB in MOLOC C261 exists) F:EIOP (M:IOPMB in MOLOC C261 exists) F:EIOP (M:IOPMB in MOLOC C253 exists) F:EIOP (M:IOPMB in MOLOC C253 exists) F:EIOP (M:IOPMB in MOLOC C253 exists) F:EIOP (M:IOPMB in MOLOC C253 exists) F:EIOP (M:IOPMB in MOLOC C253 exists) F:EIOP (M:IOPMB in MOLOC C253 exists) F:EIOP (M:IOPMB in MOLOC C253 exists) F:EIOP (M:IOPMB in MOLOC C253 exists) MOLOC 04 C287P4 04 C287P3 03 C279P1 03 C279P2 04 C27P1 04 C279P2 03 C279P3 03 C279P4 04 C279P3 04 C279P4 03 C271P1 03 C271P2 04 C271P1 04 C271P2 03 C271P3 03 C271P4 04 C271P3 04 C271P4 03 C261P1 03 C261P2 04 C261P1 04 C261P2 03 C261P3 03 C261P4 04 C261P3 04 C261P4 03 C253P1 03 C253P2 04 C253P1 04 C253P2 03 C253P3 03 C253P4 04 C253P3 04 C253P4

Connector 40D 40S 41S 41D 41S 41D 41S 41D 41S 41D 42S 42D 42S 42D 42S 42D 42S 42D 43S 43D 43S 43D 43S 43D 43S 43D 44S 44D 44S 44D 44S 44D 44S 44D

Unit F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC

Tab. 3.232 Cabling MBD <---------> CP113E / EIOP)

A30828-X1160-M-2-7620

439

Construction

Maintenance Node

Cabling MBD <-->CP113E/ EIOP (Connector 4) EWSD Classic


From MBD To CP113E, F:EIOP and for SN(504LTG) additionally F:BIOP MOLOC C173P1 C189P1 C195P1 C201P1 C173P1 C189P1 C195P1 C201P1 F:MBD0 / MBDC C189P2 C189P3 C195P2 C195P3 C189P2 C189P3 C195P2 C195P3 C201P3 C201P2 C189P5 C189P4 C201P3 C201P2 C189P5 C189P4 C195P5 C195P4 C201P5 C201P4 C195P5 C195P4 C201P5 C201P4 F:EIOP Unit F:EIOP MOLOC 03 C279P2 03 C279P1 04 C279P2 04 C279P1 03 C279P4 04 C279P3 03 C279P4 04 C279P3 03 C271P1 04 C271P2 03 C271P1 04 C271P2 03 C271P3 04 C271P4 03 C271P3 04 C271P4 05 C157P2 05 C157P1 05 C289P2 05 C289P1 05 C289P4 05 C157P3 05 C289P4 05 C157P3 05 C149P2 05 C149P1 05 C281P2 05 C281P1 05 C149P4 05 C149P3 05 C281P4 05 C281P3

Capacity State SN(63LTG) and SN(126LTG)

Connector 40D 40S 40D 40S 40D 40S 40D 40S

Unit F:MBD0 / MBDC

F:MBD1 / MBDC

F:EIOP

SN(252LTG)

41D 41S 41D 41S 41D 41S 41D 41S

F:MBD1 / MBDC

F:EIOP

SN(504LTG)

42D 42S 42D 42S 42D 42S 42D 42S 43D 43S 43D 43S 43D 43S 43D 43S

F:MBD0/MBDC

F:BIOP

F:MBD1/MBDC

F:BIOP

F:MBD0/MBDC

F:BIOP

F:MBD1/MBDC

F:BIOP

Tab. 3.233 F:MBD (Classic): Cabling MB - CP113E Cabling MBD <--> CP113C / PIOP(B) (Connector 4) Innovation
From MBD Connector 40D 40S Unit F:MBD0 / MBDC F:MBD0 / MBDC MOLOC C173P1 C189P1 Unit F:PIOP(B)0 F:PIOP(B)0 To CP113C MOLOC 03 C313P2 03 C313P1

Tab. 3.234 Cabling MBD <---------> CP113C / PIOP(B)

440

A30828-X1160-M-2-7620

Maintenance Node

Construction

From MBD Connector 40D 40S 40D 40S 40D 40S 41S 41D 41S 41D 41S 41D 41S 41D 42S 42D 42S 42D 42S 42D 42S 42D 43S 43D 43S 43D 43S 43D 43S 43D Unit F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC MOLOC C195P1 C201P1 C173P1 C189P1 C195P1 C201P1 C189P2 C189P3 C195P2 C195P3 C189P2 C189P3 C195P2 C195P3 C189P4 C189P5 C201P2 C201P3 C189P4 C189P5 C201P2 C201P3 C195P4 C195P5 C201P4 C201P5 C195P4 C195P5 C201P4 C201P5 Unit F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)0 F:PIOP(B)0

To CP113C MOLOC 07 C313P2 07 C313P1 03 C313P4 03 C313P3 07 C313P4 07 C313P3 03 C305P1 03 C305P2 07 C305P1 07 C305P2 03 C305P3 03 C305P4 07 C305P3 07 C305P4 07 C297P1 07 C297P2 03 C297P1 03 C297P2 07 C297P3 07 C297P4 03 C297P3 03 C297P4 03 C289P1 03 C289P2 07 C289P1 07 C289P2 03 C289P3 03 C289P4 07 C289P3 07 C289P4

Tab. 3.234 Cabling MBD <---------> CP113C / PIOP(B)

A30828-X1160-M-2-7620

441

Construction

Maintenance Node

Cabling MBD <-->CP113C/ PIOP(B) (Connector 4) EWSD Classic


From MBD Capacity State SN(63LTG) and SN(126LTG) Connector 40D 40S 40D 40S 40D 40S 40D 40S SN(252LTG) 41D 41S 41D 41S 41D 41S 41D 41S SN(504LTG) 42D 42S 42D 42S 42D 42S 42D 42S 43D 43S 43D 43S 43D 43S 43D 43S F:MBD0 / MBDC Unit F:MBD0 / MBDC MOLOC C173P1 C189P1 C195P1 C201P1 C173P1 C189P1 C195P1 C201P1 C189P2 C189P3 C195P2 C195P3 C189P2 C189P3 C195P2 C195P3 C189P4 C189P5 C195P4 C195P5 C189P4 C189P5 C195P4 C195P5 C201P2 C201P3 C201P4 C201P5 C201P2 C201P3 C201P4 C201P5 F:PIOP(B) To CP113E, F:PIOP(B) Unit F:PIOP(B) MOLOC 03 C305P2 03 C305P1 07 C305P2 07 C305P1 03 C305P4 03 C305P3 07 C305P4 07 C305P3 03 C297P1 03 C297P2 07 C297P1 07 C297P2 03 C297P3 03 C297P4 07 C297P3 07 C297P4 09 C305P1 09 C305P2 05 C297P1 05 C297P2 09 C305P3 09 C305P4 05 C297P3 05 C297P4 02 C305P1 02 C305P2 09 C297P1 09 C297P2 02 C305P3 02 C305P4 09 C297P3 05 C297P4

F:MBD1 / MBDC

F:PIOP(B)

F:MBD1 / MBDC

F:PIOP(B)

F:MBD0/MBDC

F:PIOP(B)

F:MBD1/MBDC

F:PIOP(B)

F:MBD0/MBDC

F:PIOP(B)

F:MBD1/MBDC

F:PIOP(B)

Tab. 3.235 F:MBD (Classic): Cabling MB - CP113E Cabling MBD <--> CP113 / IOP (Connector 4)
From MBD Connector 40D 40S 40D 40S Unit F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC MOLOC C173P1 C189P1 C195P1 C201P1 F:IOP0 F:IOP0 F:IOP1 F:IOP1 Unit To CP113 MOLOC C151P2 C151P1 C151P2 C151P1

Tab. 3.236 Cabling MBD <--> CP113 / IOP

442

A30828-X1160-M-2-7620

Maintenance Node

Construction

From MBD Connector 40D 40S 40D 40S 41S 41D 41S 41D 41S 41D 41S 41D 42S 42D 42S 42D 42S 42D 42S 42D 43S 43D 43S 43D 43S 43D 43S 43D Unit F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC MOLOC C173P1 C189P1 C195P1 C201P1 C189P2 C189P3 C195P2 C195P3 C189P2 C189P3 C195P2 C195P3 C189P4 C189P5 C201P2 C201P3 C189P4 C189P5 C201P2 C201P3 C195P4 C195P5 C201P4 C201P5 C195P4 C195P5 C201P4 C201P5 F:IOP0 F:IOP0 F:IOP1 F:IOP1 F:IOP0 F:IOP0 F:IOP1 F:IOP1 F:IOP0 F:IOP0 F:IOP1 F:IOP1 F:IOP3 F:IOP3 F:IOP2 F:IOP2 F:IOP3 F:IOP3 F:IOP2 F:IOP2 F:IOP2 F:IOP2 F:IOP3 F:IOP3 F:IOP2 F:IOP2 F:IOP3 F:IOP3 Unit

To CP113 MOLOC C151P4 C151P3 C151P4 C151P3 C159P1 C159P2 C159P1 C159P2 C159P3 C159P4 C159P3 C159P4 C151P1 C151P2 C151P1 C151P2 C151P3 C151P4 C151P3 C151P4 C159P1 C159P2 C159P1 C159P2 C159P3 C159P4 C159P3 C159P4

Tab. 3.236 Cabling MBD <--> CP113 / IOP Cabling MBD <--> CP113C / PIOP(A) (Connector 4)
Form MBD Connector 40D 40S 40D Unit F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC MOLOC C173P1 C189P1 C195P1 Unit F:PIOP(A)0 F:PIOP(A)0 F:PIOP(A)1 To CP113 MOLOC 03 C279P2 03 C279P1 07 C279P2

Tab. 3.237 Cabling MBD <---------> CP113 / PIOP(A)

A30828-X1160-M-2-7620

443

Construction

Maintenance Node

Form MBD Connector 40S 40D 40S 40D 40S 41S 41D 41S 41D 41S 41D 41S 41D 42S 42D 42S 42D 42S 42D 42S 42D 43S 43D 43S 43D 43S 43D 43S 43D Unit F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD0 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC F:MBD1 / MBDC MOLOC C201P1 C173P1 C189P1 C195P1 C201P1 C189P2 C189P3 C195P2 C195P3 C189P2 C189P3 C195P2 C195P3 C189P4 C189P5 C201P2 C201P3 C189P4 C189P5 C201P2 C201P3 C195P4 C195P5 C201P4 C201P5 C195P4 C195P5 C201P4 C201P5 Unit F:PIOP(A)1 F:PIOP(A)0 F:PIOP(A)0 F:PIOP(A)1 F:PIOP(A)1 F:PIOP(A)0 F:PIOP(A)0 F:PIOP(A)1 F:PIOP(A)1 F:PIOP(A)0 F:PIOP(A)0 F:PIOP(A)1 F:PIOP(A)1 F:PIOP(A)3 F:PIOP(A)3 F:PIOP(A)2 F:PIOP(A)2 F:PIOP(A)3 F:PIOP(A)3 F:PIOP(A)2 F:PIOP(A)2 F:PIOP(A)2 F:PIOP(A)2 F:PIOP(A)3 F:PIOP(A)3 F:PIOP(A)2 F:PIOP(A)2 F:PIOP(A)3 F:PIOP(A)3

To CP113 MOLOC 07 C279P1 03 C279P4 03 C279P3 07 C279P4 07 C279P3 03 C269P1 03 C269P2 07 C269P1 07 C269P2 03 C269P3 03 C269P4 07 C269P3 07 C269P4 09 C279P1 09 C279P2 02 C279P1 02 C279P2 09 C279P3 09 C279P4 02 C279P3 02 C279P4 02 C269P1 02 C269P2 09 C269P1 09 C269P2 02 C269P3 02 C269P4 09 C269P3 09 C269P4

Tab. 3.237 Cabling MBD <---------> CP113 / PIOP(A) Cabling MBD <--> CCGA
Rack MBD in R:LTGN and CCG in F:MB/CCG Clock cables CCG <--> MBD F:MBD0/MBDCG 04 D229P2 -> CCG0 02/04 B086 F:MBD0/MBDCG 04 D229P3 -> CCG1 03/05 B086 F:MBD1/MBDCG 05 D229P2 -> CCG0 02/04 A086 F:MBD1/MBDCG 05 D229P3 -> CCG1 03/05 A086

Tab. 3.238 Cabling MBD <---------> CCGA

444

A30828-X1160-M-2-7620

Maintenance Node

Construction

Rack MBD in R:MB/CCG and CCG in F:MB/CCG

Clock cables CCG <--> MBD F:MBD0/MBDCG 07 D229P2 -> CCG0 02/04 B086 F:MBD0/MBDCG 07 D229P3 -> CCG1 03/05 B086 F:MBD1/MBDCG 08 D229P2 -> CCG0 02/04 A086 F:MBD1/MBDCG 08 D229P3 -> CCG1 03/05 A086

Tab. 3.238 Cabling MBD <---------> CCGA Cabling MBD<--> CCGE


Rack MBD in R:LTGN and CCG in F:CCGE in R:LTGN Clock cables CCG <--> MBD F:MBD0/MBDCG 04 D229P2 -> CCG0 07 C119P1 F:MBD0/MBDCG 04 D229P3 -> CCG1 07 C251P1 F:MBD1/MBDCG 05 D229P2 -> CCG0 07 C125P1 F:MBD1/MBDCG 05 D229P3 -> CCG1 07 C257P1 F:MBD0/MBDCG 07 D229P2 -> CCG0 07 C119P1 F:MBD0/MBDCG 07 D229P3 -> CCG1 07 C251P1 F:MBD1/MBDCG 08 D229P2 -> CCG0 07 C125P1 F:MBD1/MBDCG 08 D229P3 -> CCG1 07 C257P1

MBD in R:MB/CCG and CCG in F:CCGE in R:LTGN

Tab. 3.239 Cabling MBD <---------> CCGE

3.5.3 3.5.3.1

F:CCGE F:CCGE (module side)


CCG 0
1 2

CCG 1

3 4 5 1

CCGER B

CCGED 1

CCGED 4

CCGED 3

CCGED 2

CCGED 1

CCGES

3 4

C101

C131

C163

C175

C187

C199

C211

C233

C263

CCGES

C295

C307

C319

CCGED 2

CCGERB

C331

CCGED 3

Modules with displays and switches in F:CCGE CCGES (-Q146-) CCGED (-Q147-)

Tab. 3.240 Modules with displays and switches in F:CCGE

A30828-X1160-M-2-7620

C343

CCGED 4

CCGEGPS

CCGEGPS

445

Construction

Maintenance Node

3.5.3.2

F:CCGE (backplane)
P1 P2

33 1 1 1 1 10 1 3 3 5 1 1 1 1 8 11 1 1 1 1 5 9 5 5 33 33 33 33 33 1 1 1 1 4 4 3 3 67 CCG 1 CCG 0 1 1 1 1 8 11 1 1 1 1 1 1 1 1 8 11 1 1 1 1

33 10 1 3 3 5 5 9 5 5 3 3 33 3 3 3 3 33 4 4 3 3 67 8 11

P3 P4 P5 P1

P2 P3 P4

3.5.3.3

F:CCGE (cabling)
Connector 1 for CCG 0 MOLOC C131P1 Connection T3-outlet can always be used (CCGES) 1 cable with 8 x 2,048 MHz coaxial or symmetric T3-outlet, can be used CCGED 1 is plugged

C175P1 / C175P3 C175P5 / D175P2 C187P1 / C187P3 C187P5 / D187P2 C199P1 / C199P3 C199P5 / D199P2 C211P1 / C211P3 C211P5 / D211P2 1 for CCG 1 C263P1

T3-outlet, can be used CCGED 2 is plugged

T3-outlet, can be used CCGED 3 is plugged

T3-outlet, can be used CCGED 4 is plugged

T3-outlet can always be used (CCGES) 1 cable with 8 x 2,048 MHz coaxial or symmetric T3-outlet, can be used CCGED 1 is plugged

C307P1 / C307P3 C307P5/ D307P2 C319P1 / C319P3 C319 P5/ D319P2 C331P1 / C331P3 C331P5 / D331P2 C343P1 / C343P3 C343P5 / D343P2

T3-outlet, can be used CCGED 2 is plugged

T3-outlet, can be used CCGED 3 is plugged

T3-outlet, can be used CCGED 4 is plugged

Tab. 3.241 F:CCGE (Cabling)

446

A30828-X1160-M-2-7620

Maintenance Node

Construction

Connector 3 for CCG 0

MOLOC C119P1 / C119P2 EWSD clock outputs C119P3 / C119P4 C119P5 / D119P1 D119P2 / D119P3 C125P1 / C125P2 C125P3 / C125P4 C125 P5/ D125P1 D125P2 / D125P3 C251P1 / C251P2 EWSD clock outputs C251P3 / C251P4 C251P5 / D251P1 D251P2/ D251P3 C257P1 / C257P2 C257P3/ C257P4 C257 P5/ D257P1 D257P2 / D257P3

Connection

3 for CCG 1

4 for CCG 0 4 for CCG 1 5 for CCG 0

D131P2 / D137P2 D263P2 / D269P2

connection to IOP:MB 0 and IOP:MB 1 connection to IOP:MB 0 and IOP:MB 1

C137 P3/ C137P4 reference inputs for CCG 0 C137P5 / D137P1 03C269 / 04C269 05C269 / 01D269 D125P4 reference inputs for CCG 1

5 for CCG 1

6 for CCG 0

This MOLOC is used for the frame side CCG-0 - cross connect cable to CCG-1 (7 is used when the affected frame side is supposed to be CCG-1) This MOLOC is used for frame side CCG-1 - cross connect cable to CCG-0 (this side of the frame is not displayed in the figure) V24 with clock V24 with clock SAT test plug SAT test plug power supply for CCG 0 power supply for CCG 1 connection for extension module CCGGPS or CCGERB connection for extension module CCGGPS or CCGERB

7 for CCG 1

D251P4

8 for CCG 0 8 for CCG 1 9 for CCG 0 9 for CCG 1 10 for CCG 0 10 for CCG 1 11 for CCG 0 11 for CCG 1

C101P4 / C163P4 C233 P4/ C295P4 C143P5 C275P5 C137P1 C269P1 C101P5 / C163P5 C233P5 / C295P5

Tab. 3.241 F:CCGE (Cabling) Internal cabling CCGE


Internal Cabling D125P4 --> D251P4 Cabling CCG-0 <--> CCG-1 The cross connect cable between left and right side is used as communication channel between CCG-0 and CCG-1 and indentifies the frame side CCG-0

Tab. 3.242 F:CCGE Cabling CCG-0 - CCG-1

A30828-X1160-M-2-7620

447

Construction

Maintenance Node

References input (external references) C137P3 CCG0 <-- reference frequency 1 from F:LTGx or F:STMI C137P4 CCG0 <-- reference frequency 2 from F:LTGx or F:STMI C137P5 CCG0 <-- reference frequency 3 from F:LTGx or F:STMI D137P1 CCG0 <-- reference frequency 4 from F:LTGx or F:STMI C269P3 CCG1 <-- reference frequency 1 from F:LTGx or F:STMI C269P4 CCG1 <-- reference frequency 2 from F:LTGx or F:STMI C269P5 CCG1 <-- reference frequency 3 from F:LTGx or F:STMI D269P1 CCG1 <-- reference frequency 4 from F:LTGx or F:STMI

Note

further clock reference sources: T4 output of an SDH device (Synchronous Equipment Clock), T3 signal from CS, Rubidium-Normal

Tab. 3.243 F:CCGE Cabling reference frequency Cross-joint connections CCGE and PIOP
Cross-joint cables CCG <--> PIOP(A) (CP113C) CCG0: D131P2 --> PIOP(A)0: 03 C301P2 CCG0: D131P3 --> PIOP(A)0: 03 C301P1 CCG0: D137P2 --> PIOP(A)1: 07 C301P2 CCG0: D137P3 --> PIOP(A)1: 07 C301P1 CCG1: D263P2 --> PIOP(A)0: 03 C301P4 CCG1: D263P3 --> PIOP(A)0: 03 C301P3 CCG1: D269P2 --> PIOP(A)1: 07 C301P4 CCG1: D269P3 --> PIOP(A)1: 07 C301P3

Tab. 3.244 F:CCGE Cabling CCG <-> CP113C, PIOP(A)

Clock cables CCG <--> PIOP(A) (CP113C) CCG0: C119P2 --> PIOP(A)0: 03 C329P2 CCG0: C125P2 --> PIOP(A)1: 07 C329P2 CCG1: C251P2 --> PIOP(A)0: 03 C329P3 CCG1: C257P2 --> PIOP(A)1: 07 C329P3

Tab. 3.245 F:CCGE clock cables CCG <-> CP113C, PIOP(A)

Cross-joint cables CCG <--> F:PIOP(B) (CP113C) CCG0: D131P2 --> PIOP(B)0: 03 C321P2 CCG0: D131P3 --> PIOP(B)0: 03 C321P1 CCG0: D137P2 --> PIOP(B)1: 07 C321P2 CCG0: D137P3 --> PIOP(B)1: 07 C321P1 CCG1: D263P2 --> PIOP(B)0: 03 C321P4 CCG1: D263P3 --> PIOP(B)0: 03 C321P3 CCG1: D269P2 --> PIOP(B)1: 07 C321P4 CCG1: D269P3 --> PIOP(B)1: 07 C321P3

Tab. 3.246 F:CCGE Cabling CCG <-> CP113C, PIOP(B)

Clock Cables CCG <--> PIOP(B) (CP113C) CCG0: C119P2 --> PIOP(B)0: 03 C335P2 CCG0: C125P2 --> PIOP(B)1: 07 C335P2 CCG1: C251P2 --> PIOP(B)0: 03 C335P3 CCG1: C257P2 --> PIOP(B)1: 07 C335P3

Tab. 3.247 F:CCGE clock cables CCG <-> CP113C, PIOP(B)

448

A30828-X1160-M-2-7620

Maintenance Node

Construction

Cross-joint cables CCG <--> F:BIOP (CP113E) CCG0: D131P2 --> BIOP: 05 C183P2 CCG0: D131P3 --> BIOP: 05 C183P1 CCG0: D137P2 --> BIOP: 05 C315P2 CCG0: D137P3 --> BIOP: 05 C315P1 CCG1: D263P2 --> BIOP: 05 C183P4 CCG1: D263P3 --> BIOP: 05 C183P3 CCG1: D269P2 --> BIOP: 05 C315P4 CCG1: D269P3 --> BIOP: 05 C315P3

Tab. 3.248 F:CCGE Cabling CCG <-> CP113E, BIOP

Clock Cables CCG <--> F:BIOP (CP113E) CCG0: C119P2 --> BIOP: 05 C197P2 CCG0: C125P2 --> BIOP: 05 C329P2 CCG1: C251P2 --> BIOP: 05 C197P3 CCG1: C257P2 --> BIOP: 05 C329P3

Tab. 3.249 F:CCGE clock cables CCG <-> CP113E, BIOP

Cross-joint cables CCG <--> CP113E, F:EIOP (Both F:EIOP are connected to IOC0 and IOC1) CCG0: D131P2 --> EIOP: 03 C303P2 CCG0: D131P3 --> EIOP: 03 C303P1 CCG0: D137P2 --> EIOP: 04 C303P2 CCG0: D137P3 --> EIOP: 04 C303P1 CCG1: D263P2 --> EIOP: 03 C303P4 CCG1: D263P3 --> EIOP: 03 C303P3 CCG1: D269P2 --> EIOP: 04 C303P4 CCG1: D269P3 --> EIOP: 04 C303P3

Tab. 3.250 F:CCGE Cabling CCG <-> CP113E, EIOP

Clock cables CCG <--> CP113E, F:EIOP (Both F:EIOP are connected to IOC0 and IOC1) CCG0: C119P2 --> EIOP: 03 C317P2 CCG0: C125P2 --> EIOP: 04 C317P2 CCG1: C251P2 --> EIOP: 03 C317P3 CCG1: C257P2 --> EIOP: 04 C317P3

Tab. 3.251 F:CCGE clock cables CCG <-> CP113E, EIOP Cross-joint connections CCGE and MBD
Rack CCG and MBD in R:LTGN Clock Cables CCG <--> MBD CCG0 07 C119P1 -> F:MBD0/MBDCG 04 D229P2 CCG0 07 C125P1 -> F:MBD1/MBDCG 05 D229P2 CCG1 07 C251P1 -> F:MBD0/MBDCG 04 D229P3 CCG1 07 C257P1 -> F:MBD1/MBDCG 05 D229P3 CCG in R:LTGN and MBD in R:MB/CCG CCG0 07 C119P1 -> F:MBD0/MBDCG 07 D229P2 CCG0 07 C125P1 -> F:MBD1/MBDCG 08 D229P2 CCG1 07 C251P1 -> F:MBD0/MBDCG 07 D229P3 CCG1 07 C257P1 -> F:MBD1/MBDCG 08 D229P3

Tab. 3.252 F:CCGE EWSD clock cables CCGE <-> MBDE

A30828-X1160-M-2-7620

449

Construction

Maintenance Node

Cabling CCGE --> External Installations


Cabling CCGED1 --> External Installations CCG0: C175P1 --> 1. Cable with 8 x 2,048 MHz CCG0: C175P3 --> 2. Cable with 8 x 2,048 MHz CCG0: C175P5 --> 3. Cable with 8 x 2,048 MHz CCG0: D175P2 --> 4. Cable with 8 x 2,048 MHz CCG1: C307P1 --> 1. Cable with 8 x 2,048 MHz CCG1: C307P3 --> 2. Cable with 8 x 2,048 MHz CCG1: C307P5 --> 3. Cable with 8 x 2,048 MHz CCG1: D307P2 --> 4. Cable with 8 x 2,048 MHz

Tab. 3.253 F:CCGE Cabling CCGED1 -- > External Installations

Cabling CCGED2 --> External Installations CCG0: C187P1 --> 1. Cable with 8 x 2,048 MHz CCG0: C187P3 --> 2. Cable with 8 x 2,048 MHz CCG0: C187P5 --> 3. Cable with 8 x 2,048 MHz CCG0: D187P2 --> 4. Cable with 8 x 2,048 MHz CCG1: C319P1 --> 1. Cable with 8 x 2,048 MHz CCG1: C319P3 --> 2. Cable with 8 x 2,048 MHz CCG1: C319P5 --> 3. Cable with 8 x 2,048 MHz CCG1: D319P2 --> 4. Cable with 8 x 2,048 MHz

Tab. 3.254 F:CCGE Cabling CCGED2 -- > External Installations

Cabling CCGED3 --> External Installations CCG0: C199P1 --> 1. Cable with 8 x 2,048 MHz CCG0: C199P3 --> 2. Cable with 8 x 2,048 MHz CCG0: C199P5 --> 3. Cable with 8 x 2,048 MHz CCG0: D199P2 --> 4. Cable with 8 x 2,048 MHz CCG1: C331P1 --> 1. Cable with 8 x 2,048 MHz CCG1: C331P3 --> 2. Cable with 8 x 2,048 MHz CCG1: C331P5 --> 3. Cable with 8 x 2,048 MHz CCG1: D331P2 --> 4. Cable with 8 x 2,048 MHz

Tab. 3.255 F:CCGE Cabling CCGED3 -- > External Installations

Cabling CCGED4 --> External Installations CCG0: C211P1 --> 1. Cable with 8 x 2,048 MHz CCG0: C211P3 --> 2. Cable with 8 x 2,048 MHz CCG0: C211P5 --> 3. Cable with 8 x 2,048 MHz CCG0: D211P2 --> 4. Cable with 8 x 2,048 MHz CCG1: C343P1 --> 1. Cable with 8 x 2,048 MHz CCG1: C343P3 --> 2. Cable with 8 x 2,048 MHz CCG1: C343P5 --> 3. Cable with 8 x 2,048 MHz CCG1: D343P2 --> 4. Cable with 8 x 2,048 MHz

Tab. 3.256 F:CCGE Cabling CCGED4 -- > External Installations

450

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.6

F:RSU
3.6.1 3.6.2 3.6.3 3.6.4 3.6.5 3.6.6 3.6.7 3.6.8 3.6.9 3.6.10 F:RSU (basic frame) (module side) F:RSU (basic frame) (backplane) F:RSU (basic frame) (cabling) F:RSU (extension frame) (module side) F:RSU (extension frame 0) (backplane) F:RSU (extension frame 0) (cabling) F:RSU (extension frame 1) (backplane) F:RSU (extension frame 1) (cabling) F:RSU (extension frame 2) (backplane) F:RSU (extension frame 2) (cabling)

3.6.1

F:RSU (basic frame) (module side)


side 0
P1 P2

side 1

C P3
P4 P5 P1

DIU240A 1

DIU240A 2

DIU240A 0

DIU240A 3

DIU240A 4 C331

AMUX

P3 P4

AMUX

MH

C199

C211

C233

C249

C283

C303

C101

C151

C187

C265

C319

C117

C133

Modules with displays and switches in F:RSU RSUC (-Q98-) DIU240A (-Q106-) MH (-Q97-) AMUX (-Q104-) TSIMB (-Q105-X100)

Tab. 3.257 Modules with displays and switches in F:RSU

C171

A30828-X1160-M-2-7620

C343

DIU240A 5

P2

TSIMB

AMUX

TSIMB

RSUC

AMUX

RSUC

MH

451

Construction

Maintenance Node

3.6.2

F:RSU (basic frame) (backplane)


08 00 00
HST00 HST01 HST10 HST11 HST20 HST21

P1 PDC_5_0 P2 PDC_4_0 XCD1 PDC_3_0

HST00 HST01 HST10 HST11 HST20 HST21

09

02 01 XCA1

PDC_3_0

PDC_1_0

PDC_0_0

09

08

01
EXTO0 EXTO1 EXTO2

EXT I EXTO0 EXTO1 EXTO2

10

P3 P4 P5

11

11

03

03 06
BSS 0 BSP 1

02 07 05 04

HTI

XCD0

13

PDC_3_1

PDC_5_1

PDC_4_1

PDC_2_1

P1

HSA 0 HSA 1

PDC_1_1

PDC_0_1

P2 P3 P4

BSS1

17

side 1

3.6.3

F:RSU (basic frame) (cabling)


Connector XCA0 / C125P1 --> XCD1 / C325P1 XCD0 / C179P5 --> XCA1 / C258P1 HTI / C125P5 HTI / C258P5 PDC_0_0 / C187P1 PDC_0_1 / C187P5 PDC_1_0 / C199P1 PDC_1_1 / C199P5 PDC_2_0 / C211P1 PDC_2_1 / C211P5 PDC_3_0 / C319P1 PDC_3_1 / C319P5 PDC_4_0 / C331P1 PDC_4_1 / C331P5 PDC_5_0 / C343P1 PDC_5_1 / C343P5 00,01,02,03,04 / C133P1,2,3,4,5 05,06,07 / D133P1,2,3 08,09,10,11,12 / C171P1,2,3,4,5 13,14,15 / D171P1,2,3 16,17 / D179P3,4 00,01,02,03,04 / C265P1,2,3,4,5 05,06,07 / D265P1,2,3 Remarks internal cable side 0 and side 1 internal cable side 0 and side 1 connector plugged, basic frame side 0 in HTI function connector plugged, basic frame side 1 in HTI function PDC interface 0, 1, 2, 3 to DIU240A 0 PDC interface 4, 5, 6, 7 to DIU240A 0 PDC interface 0, 1, 2, 3 to DIU240A 1 PDC interface 4, 5, 6, 7 to DIU240A 1 PDC interface 0, 1, 2, 3 to DIU240A 2 PDC interface 4, 5, 6, 7 to DIU240A 2 PDC interface 0, 1, 2, 3 to DIU240A 3 PDC interface 4, 5, 6, 7 to DIU240A 3 PDC interface 0, 1, 2, 3 to DIU240A 4 PDC interface 4, 5, 6, 7 to DIU240A 4 PDC interface 0, 1, 2, 3 to DIU240A 5 PDC interface 4, 5, 6, 7 to DIU240A 5 SDC interface 0,1,2,3,4 to LTG (RTI) to SN (HTI) SDC interface 5,6,7 to LTG (RTI) to SN (HTI) SDC interface 8,9,10,11,12 to LTG (RTI) to SN (HTI) SDC interface 13,14,15 to LTG (RTI) to SN (HTI) SDC interface 16,17 to LTG (RTI) to SN (HTI) SDC interface 0,1,2,3,4 to LTG (RTI) to SN (HTI) SDC interface 5,6,7 to LTG (RTI) to SN (HTI)

Tab. 3.258 F:RSU (basic frame) (cabling)

17

side 0

452

A30828-X1160-M-2-7620

HSA 0 HSA 1

16

14

07

06

BSP1

15

16

15

14

EXT I

13

05

HTI

12

04

12

XCA0

10

Maintenance Node

Construction

Connector 08,09,10,11,12 / C303P1,2,3,4,5 13,14,15 / D303P1,2,3 16,17 / D311P3,4 BSP0, BSS0 / D125P3,4 BSP1, BSS1 / D258P3,4 EXTO0 / C141P5 EXTO1 / C141P4 EXTO2 / C141P3 HST00 / D161P2 HST01 / D161P1 HST10 / C161P5 HST11 / C161P4 HST20 / C161P3 HST21 / C161P2 EXTO0 / C273P5 EXTO1 / C273P4 EXTO2 / C273P3 HST00 / D293P2 HST01 / D293P1 HST10 / C293P5 HST11 / C293P4 HST20 / C293P3 HST21 / C293P2

Remarks SDC interface 8,9,10,11,12 to LTG (RTI) to SN (HTI) SDC interface 13,14,15 to LTG (RTI) to SN (HTI) SDC interface 16,17 to LTG (RTI) to SN (HTI) SDH clock interface SDH clock interface internal cable to extension frame 0 D141P1 internal cable to extension frame 1 D141P1 internal cable to extension frame 2 D141P1 internal cable to extension frame 0 D151P3 internal cable to extension frame 0 D151P2 internal cable to extension frame 1 D151P3 internal cable to extension frame 1 D151P2 internal cable to extension frame 2 D151P3 internal cable to extension frame 2 D151P2 internal cable to extension frame 0 D273P1 internal cable to extension frame 1 D273P1 internal cable to extension frame 2 D273P1 internal cable to extension frame 0 D283P3 internal cable to extension frame 0 D283P2 internal cable to extension frame 1 D283P3 internal cable to extension frame 1 D283P2 internal cable to extension frame 2 D283P3 internal cable to extension frame 2 D283P2

Tab. 3.258 F:RSU (basic frame) (cabling)

A30828-X1160-M-2-7620

453

454

Construction

3.6.5
C D

3.6.4

D
P3 P4 P2 P2 P1 P3 P5 P4 P4 P2 P1

P1

C P3

P3 P2 P1 P5 PDC_11_1 PDC_10_1 PDC_10_0 XCD1 PDC_9_0 PDC_11_0

MH (-Q97-)

P4

C101 MH MH AMUX C117 C133

PDC_9_1 34 33 32 29 28 26 31 30 27

35

side 0

AMUX (-Q104-)

F:RSU (extension frame 0) (backplane)

F:RSU (extension frame) (module side)

Tab. 3.259 Modules with displays and switches in F:RSU

Modules with displays and switches in F:RSU

side 1
EXT I

HSA 0 HSA 1

C171 C187 C199 C211

AMUX DIU240A DIU240A DIU240A

25 23 20 19 XCA1 22 21

24

18

BSS1

BSP1

PDC_8_1 PDC_7_1 PDC_6_1 XCD0 32 26 31 30 29 28 27 22 PDC_6_0 PDC_7_0

PDC_8_0

C233 C249 C265

MH MH AMUX

DIU240A (-Q106-)

35

34

side 0
EXT I

side 1

HSA 0 HSA 1

C303
22 XCA0 21 20 19 18

AMUX C319 C331 C343 DIU240A DIU240A DIU240A

25

24

23

A30828-X1160-M-2-7620

Maintenance Node

BSS 0 BSP 1

Maintenance Node

Construction

3.6.6

F:RSU (extension frame 0) (cabling)


Connector XCA0 / C125P1 --> XCD1 / C325P1 XCD0 / C179P5 --> XCA1 / C258P1 PDC_6_0 / C187P1 PDC_6_1 / C187P5 PDC_7_0 / C199P1 PDC_7_1 / C199P5 PDC_8_0 / C211P1 PDC_8_1 / C211P5 PDC_9_0 / C319P1 PDC_9_1 / C319P5 PDC_10_0 / C331P1 PDC_10_1 / C331P5 PDC_11_0 / C343P1 PDC_11_1 / C343P5 18,19,20,21,22 / C133P1,2,3,4,5 23,24,25 / D133P1,2,3 26,27,28,29,30 / C171P1,2,3,4,5 31,32,33 / D171P1,2,3 34,35 / D179P3,4 18,19,20,21,22 / C265P1,2,3,4,5 23,24,25 / D265P1,2,3 26,27,28,29,30 / C303P1,2,3,4,5 31,32,33 / D303P1,2,3 34,35 / D311P3,4 BSP0, BSS0 / D125P3,4 BSP1, BSS1 / D258P3,4 EXT I / D141P1 HSA 0 / D151P3 HSA 1 / D151P2 EXT I / D273P1 HSA 0 / D283P3 HSA 1 / D283P2 Remarks internal cable side 0 and side 1 internal cable side 0 and side 1 PDC interface 0, 1, 2, 3 to DIU240A 6 PDC interface 4, 5, 6, 7 to DIU240A 6 PDC interface 0, 1, 2, 3 to DIU240A 7 PDC interface 4, 5, 6, 7 to DIU240A 7 PDC interface 0, 1, 2, 3 to DIU240A 8 PDC interface 4, 5, 6, 7 to DIU240A 8 PDC interface 0, 1, 2, 3 to DIU240A 9 PDC interface 4, 5, 6, 7 to DIU240A 9 PDC interface 0, 1, 2, 3 to DIU240A 10 PDC interface 4, 5, 6, 7 to DIU240A 10 PDC interface 0, 1, 2, 3 to DIU240A 11 PDC interface 4, 5, 6, 7 to DIU240A 11 SDC interface 18,19,20,21,22 to LTG (RTI) to SN (HTI) SDC interface 23,24,25 to LTG (RTI) to SN (HTI) SDC interface 26,27,28,29,30 to LTG (RTI) to SN (HTI) SDC interface 31,32,33 to LTG (RTI) to SN (HTI) SDC interface 34,35 to LTG (RTI) to SN (HTI) SDC interface 18,19,20,21,22 to LTG (RTI) to SN (HTI) SDC interface 23,24,25 to LTG (RTI) to SN (HTI) SDC interface 26,27,28,29,30 to LTG (RTI) to SN (HTI) SDC interface 31,32,33 to LTG (RTI) to SN (HTI) SDC interface 34,35 to LTG (RTI) to SN (HTI) SDH clock interface SDH clock interface internal cable to basic frame EXTO0 / C141P5 internal cable to basic frame HST00 / D161P2 internal cable to basic frame HST01 / D161P1 internal cable to basic frame EXTO0 / C273P5 internal cable to basic frame HST00 / D293P2 internal cable to basic frame HST01 / D293P1

Tab. 3.260 F:RSU (extension frame 0) (cabling)

A30828-X1160-M-2-7620

455

Construction

Maintenance Node

3.6.7

F:RSU (extension frame 1) (backplane)


44 36 36 37
EXT I HSA 0 HSA 1

P1 PDC_17_0 PDC_16_0 XCD1 PDC_15_0 P2

PDC_14_0

PDC_13_0

PDC_12_0

45

38 37 XCA1

45

44

46

C P3
P4 P5

47

47

39

48

48

40

PDC_17_1

PDC_16_1

PDC_15_1

PDC_14_1

PDC_13_1

PDC_12_1

XCD0

EXT I

49

49

P1

HSA 0 HSA 1

41

P3 P4

side 1

side 0

3.6.8

F:RSU (extension frame 1) (cabling)


Connector XCA0 / C125P1 --> XCD1 / C325P1 XCD0 / C179P5 --> XCA1 / C258P1 PDC_12_0 / C187P1 PDC_12_1 / C187P5 PDC_13_0 / C199P1 PDC_13_1 / C199P5 PDC_14_0 / C211P1 PDC_14_1 / C211P5 PDC_15_0 / C319P1 PDC_15_1 / C319P5 PDC_16_0 / C331P1 PDC_16_1 / C331P5 PDC_17_0 / C343P1 PDC_17_1 / C343P5 36,37,38,39,40 / C133P1,2,3,4,5 41,42,43 / D133P1,2,3 44,45,46,47,48 / C171P1,2,3,4,5 49,50,51 / D171P1,2,3 52,53 / D179P3,4 36,37,38,39,40 / C265P1,2,3,4,5 41,42,43 / D265P1,2,3 44,45,46,47,48 / C303P1,2,3,4,5 49,50,51 / D303P1,2,3 Remarks internal cable side 0 and side 1 internal cable side 0 and side 1 PDC interface 0, 1, 2, 3 to DIU240A 12 PDC interface 4, 5, 6, 7 to DIU240A 12 PDC interface 0, 1, 2, 3 to DIU240A 13 PDC interface 4, 5, 6, 7 to DIU240A 13 PDC interface 0, 1, 2, 3 to DIU240A 14 PDC interface 4, 5, 6, 7 to DIU240A 14 PDC interface 0, 1, 2, 3 to DIU240A 15 PDC interface 4, 5, 6, 7 to DIU240A 15 PDC interface 0, 1, 2, 3 to DIU240A 16 PDC interface 4, 5, 6, 7 to DIU240A 16 PDC interface 0, 1, 2, 3 to DIU240A 17 PDC interface 4, 5, 6, 7 to DIU240A 17 SDC interface 36,37,38,39,40 to LTG (RTI) to SN (HTI) SDC interface 41,42,43 to LTG (RTI) to SN (HTI) SDC interface 44,45,46,47,48 to LTG (RTI) to SN (HTI) SDC interface 49,50,51 to LTG (RTI) to SN (HTI) SDC interface 52,53 to LTG (RTI) to SN (HTI) SDC interface 36,37,38,39,40 to LTG (RTI) to SN (HTI) SDC interface 41,42,43 to LTG (RTI) to SN (HTI) SDC interface 44,45,46,47,48 to LTG (RTI) to SN (HTI) SDC interface 49,50,51 to LTG (RTI) to SN (HTI)

Tab. 3.261 F:RSU (extension frame 1) (cabling)

456

A30828-X1160-M-2-7620

BSS 0 BSP 1

P2

52

50

42

50

43

BSP1

51

BSS1

53

53

52

51

43

42

41

40

39

38

XCA0

46

Maintenance Node

Construction

Connector 52,53 / D311P3,4 BSP0, BSS0 / D125P3,4 BSP1, BSS1 / D258P3,4 EXT I / D141P1 HSA 0 / D151P3 HSA 1 / D151P2 EXT I / D273P1 HSA 0 / D283P3 HSA 1 / D283P2

Remarks SDC interface 52,53 to LTG (RTI) to SN (HTI) SDH clock interface SDH clock interface internal cable to basic frame EXTO1 / C141P4 internal cable to basic frame HST10 / C161P5 internal cable to basic frame HST11 / C161P4 internal cable to basic frame EXTO1 / C273P4 internal cable to basic frame HST10 / C293P5 internal cable to basic frame HST11 / C293P4

Tab. 3.261 F:RSU (extension frame 1) (cabling)

3.6.9

F:RSU (extension frame 2) (backplane)


62 54 54 55
EXT I HSA 0 HSA 1

P1 PDC_23_0 PDC_22_0 XCD1 PDC_21_0 P2

PDC_20_0

PDC_19_0

PDC_18_0

63

56 55 XCA1

63

62

64

C P3
P4 P5

65

65

57

66

66

58

PDC_23_1

PDC_22_1

PDC_21_1

PDC_20_1

PDC_19_1

PDC_18_1

XCD0

EXT I

67

67

P1

HSA 0 HSA 1

59

P3 P4

side 1

side 0

3.6.10

F:RSU (extension frame 2) (cabling)


Connector XCA0 / C125P1 --> XCD1 / C325P1 XCD0 / C179P5 --> XCA1 / C258P1 PDC_18_0 / C187P1 PDC_18_1 / C187P5 PDC_19_0 / C199P1 PDC_19_1 / C199P5 PDC_20_0 / C211P1 PDC_20_1 / C211P5 PDC_21_0 / C319P1 PDC_21_1 / C319P5 Remarks internal cable side 0 and side 1 internal cable side 0 and side 1 PDC interface 0, 1, 2, 3 to DIU240A 18 PDC interface 4, 5, 6, 7 to DIU240A 18 PDC interface 0, 1, 2, 3 to DIU240A 19 PDC interface 4, 5, 6, 7 to DIU240A 19 PDC interface 0, 1, 2, 3 to DIU240A 20 PDC interface 4, 5, 6, 7 to DIU240A 20 PDC interface 0, 1, 2, 3 to DIU240A 21 PDC interface 4, 5, 6, 7 to DIU240A 21

Tab. 3.262 F:RSU (extension frame 2) (cabling)

BSS 0 BSP 1

P2

70

68

60

68

61

BSP1

69

BSS1

71

71

70

69

61

60

59

58

57

56

XCA0

64

A30828-X1160-M-2-7620

457

Construction

Maintenance Node

Connector PDC_22_0 / C331P1 PDC_22_1 / C331P5 PDC_23_0 / C343P1 PDC_23_1 / C343P5 54,55,56,57,58 / C133P1,2,3,4,5 59,60,61 / D133P1,2,3 62,63,64,65,66 / C171P1,2,3,4,5 67,68,69 / D171P1,2,3 70,71 / D179P3,4 54,55,56,57,58 / C265P1,2,3,4,5 59,60,61 / D265P1,2,3 62,63,64,65,66 / C303P1,2,3,4,5 67,68,69 / D303P1,2,3 70,71 / D311P3,4 BSP0, BSS0 / D125P3,4 BSP1, BSS1 / D258P3,4 EXT I / D141P1 HSA 0 / D151P3 HSA 1 / D151P2 EXT I / D273P1 HSA 0 / D283P3 HSA 1 / D283P2

Remarks PDC interface 0, 1, 2, 3 to DIU240A 22 PDC interface 4, 5, 6, 7 to DIU240A 22 PDC interface 0, 1, 2, 3 to DIU240A 23 PDC interface 4, 5, 6, 7 to DIU240A 23 SDC interface 54,55,56,57,58 to LTG (RTI) to SN (HTI) SDC interface 59,60,61 to LTG (RTI) to SN (HTI) SDC interface 62,63,64,65,66 to LTG (RTI) to SN (HTI) SDC interface 67,68,69 to LTG (RTI) to SN (HTI) SDC interface 70,71 to LTG (RTI) to SN (HTI) SDC interface 54,55,56,57,58 to LTG (RTI) to SN (HTI) SDC interface 59,60,61 to LTG (RTI) to SN (HTI) SDC interface 62,63,64,65,66 to LTG (RTI) to SN (HTI) SDC interface 67,68,69 to LTG (RTI) to SN (HTI) SDC interface 70,71 to LTG (RTI) to SN (HTI) SDH clock interface SDH clock interface internal cable to basic frame EXTO2 / C141P3 internal cable to basic frame HST20 / C161P3 internal cable to basic frame HST21 / C161P2 internal cable to basic frame EXTO2 / C273P3 internal cable to basic frame HST20 / C293P3 internal cable to basic frame HST21 / C293P2

Tab. 3.262 F:RSU (extension frame 2) (cabling)

458

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.7

F:SDHI
3.7.1 3.7.2 3.7.3 3.7.4 F:SDHI4 (module side) F:SDHI2 (module side) F:SDHI (backplane) F:SDHI (cabling)

3.7.1

F:SDHI4 (module side)

SDHI 0

SDHI 1

SDHI 2

SDHI 3

OIMW 0

OIMW 2

OIMP 0

OIMW 1

OIMW 3

C141

OIMP 1

OIMP 2

C206

C271

C320

C125

C119

3.7.2

F:SDHI2 (module side)


SDHI 0 SDHI 2

C141 OIMP 0

C125

Modules with displays and switches in F:SDHI OIM*W (-D3559-) OIM*P (-D3560-)

Tab. 3.263 Modules with displays and switches in F:SDHI

C255

C271 OIMP 2

OIMW 0

OIMW 2

C255

A30828-X1160-M-2-7620

C336 459

OIMP 3

Construction

Maintenance Node

3.7.3

F:SDHI (backplane)
C/D306
A01 A02 A03 A04 A03 A04 A05 A06 A07 A08 A09 A10 A11 A12 A13 A14 A13 A14 A15 A16 A17 A18 A19 A20 A19 A20 A17 A18 A19 A20 A16 A17 A18 A19 A20 A15 A16 A17 A18 A11 A12 A13 A14 A15 A16 A09 A10 A11 A12 A13 A14 A07 A08 A09 A10 A11 A12 A06 A07 A08 A09 A10 A05 A06 A07 A08

C/D241
A01 A02

C/D176
A01 A02 A03 A04

C/D111
A01 A02 A03 A04 A05 A06

A05

A15

SDHI 3

SDHI 2

SDHI 1

SDHI 0

3.7.4

F:SDHI (cabling)
PCM Connection plug A05 to A20
SDHI 0 MOLOC C111 / A05 C111 / A06 C111 / A07 C111 / A08 C111 / A09 C111 / A10 D111 / A11 D111 / A12 D111 / A13 D111 / A14 D111 / A15 D111 / A16 D111 / A17 D111 / A18 D111 / A19 D111 / A20 PCM 61 - 63 57 - 60 53 - 56 49 - 52 45 - 48 41 - 44 37 - 40 33 - 36 29 - 32 25 - 28 21 - 24 17 - 20 13 - 16 09 - 12 05 - 08 01 - 03 SDHI 1 MOLOC C176 / A05 C176 / A06 C176 / A07 C176 / A08 C176 / A09 C176 / A10 D176 / A11 D176 / A12 D176 / A13 D176 / A14 D176 / A15 D176 / A16 D176 / A17 D176 / A18 D176 / A19 D176 / A20 PCM 61 - 63 57 - 60 53 - 56 49 - 52 45 - 48 41 - 44 37 - 40 33 - 36 29 - 32 25 - 28 21 - 24 17 - 20 13 - 16 09 - 12 05 - 08 01 - 03 SDHI 2 MOLOC C241 / A05 C241 / A06 C241 / A07 C241 / A08 C241 / A09 C241 / A10 D241 / A11 D241 / A12 D241 / A13 D241 / A14 D241 / A15 D241 / A16 D241 / A17 D241 / A18 D241 / A19 D241 / A20 PCM 61 - 63 57 - 60 53 - 56 49 - 52 45 - 48 41 - 44 37 - 40 33 - 36 29 - 32 25 - 28 21 - 24 17 - 20 13 - 16 09 - 12 05 - 08 01 - 03 SDHI 3 MOLOC C306 / A05 C306 / A06 C306 / A07 C306 / A08 C306 / A09 C306 / A10 D306 / A11 D306 / A12 D306 / A13 D306 / A14 D306 / A15 D306 / A16 D306 / A17 D306 / A18 D306 / A19 D306 / A20 PCM 61 - 63 57 - 60 53 - 56 49 - 52 45 - 48 41 - 44 37 - 40 33 - 36 29 - 32 25 - 28 21 - 24 17 - 20 13 - 16 09 - 12 05 - 08 01 - 03

Tab. 3.264 PCM connection plug A05 to A20

460

A30828-X1160-M-2-7620

Maintenance Node

Construction

Connection plug A01 to A04


Plug A01 E T2M0AT3 GND D T2M0BT3 C GND GND B T2M0AT4 A T2M0BT4 GND T3 / T4 clock TYPE

A02

VFSTAI GND QF_TXD QF_RXD

VSTBI

GND GND

VSTAO

VSTBO

EOW Q/F Interface RS232

A03

GND GND DV11TAI DV11TBI

STIF_0

GND GND

STIF_1

GND

Telemetrie-Interface

TV11TAO TV11TBO

DV11RAO DV11RBO

TV11RAO TV11RAO

V11 Interface V11 Interface

A04

RCVP GND AUI_TXP AUI_TXN

RCVN

GND GND

XMTP P12V

XMTN GND

Ethernet 10BT Ethernet AUI

AUI_RXP AUI_RXN

AUI_CDP AUI_CDN

Tab. 3.265 connection plug A01 to A04

A30828-X1160-M-2-7620

461

462

Construction

3.8.2
C D

3.8.1

3.8

3.8.1 3.8.2 3.8.3 3.8.4 3.8.5

D
C101 DCCCR

C101 C119 GCGR PU:SYCR T/RM:SYCR DCCCR CCGD CCGB CCGXXA C129 C141 C153 C171 C179 C187

DCCCR

F:SMSC(C)

C129

CDEX 0

C141

CDEX 1

C153

DCCCR

C171

CCGD

C179

CCGB

F:SMSC(C)-1 (module side)

F:SMSC(C)-0 (module side)

F:SMSC(C)-0 (module side) F:SMSC(C)-1 (module side) F:SMSC(C)-0 (backplane) F:SMSC(C)-1 (backplane) F:SMSC(C) (cabling)

C187 C209 T/RC 1 T/RC 0 CG/MUX MDM IOPC DCCCE C219 C229 C239 C249 C259

CCGXXA

C209

T/RC 1

C219

T/RC 0

C229

CG/MUX

C239

MDM

C249

IOPC

C259

DCCCE C279 C291 C303 C311 C323 C335 C343

C279

TSMB 0

TSMB 0 TSMB 1 SSM16B TSMB 2 TSMB 3 SGCB DCCMC

C291

TSMB 1

C303

SSM16B

C311

TSMB 2

C323

TSMB 3

C335

SGCB

A30828-X1160-M-2-7620

Maintenance Node

C343

DCCMC

Maintenance Node

3.8.4

3.8.3

A30828-X1160-M-2-7620 C C D
P3 P4 P4 P2 P1 P2 P1 P2 P3 P3 P1 P1 P2

P3

CCGB (-Q887-)

DCCMC (-Q5883-)

PU:SYCR (-Q867-)

F:SMSC(C)-1 (backplane)

F:SMSC(C)-0 (backplane)

Tab. 3.266 Modules with displays and switches in F:SMSC(C)

P4
P5
MB LTG 29 LTG 31 LTG 27 LTG 25 LTG 28 LTG 26 LTG 24 LTG 30 LTG 19 LTG 21 LTG 17 LTG 23 LTG 20 LTG 18 LTG 16 LTG 22 LTG 11 LTG 15 LTG 13 LTG 09 LTG 12 LTG 10 LTG 08 LTG 14 LTG 03 LTG 07 LTG 05 LTG 01 LTG 04 LTG 02 MB LTG 06 IOP0 / D271 IOP1 / D265 RES00 / D253 IOP0 / D271 IOP1 / D265 RES10 / D253 SN:SGC / D243 SN:TSG / C229 CCG:MB / C223 RES11 / C213 RES12 / C199 MASTER:INT / C193 REF0 / C187 CCG:INT / C181 IOP0 / D165 IOP1 / D159 IOP0 / C165 IOP1 / C159 IOP0 / C271 IOP1 / 265 RES10 / C253 SN:SGC / C243 SN:TSG / C229 CCG:MB / C223 RES11 / C213 RES12 / C199 MASTER:INT / C193 REF0 / C187 CCG:INT / C181 IOP0 / C165 / C165 IOP1 / C159 / C159

P4
P5

MB LTG 29 LTG 31 LTG 27 LTG 25 LTG 28 LTG 26 LTG 24 LTG 30 LTG 19 LTG 21 LTG 17 LTG 23 LTG 20 LTG 18 LTG 16 LTG 22

LTG 11 LTG 15 LTG 13 LTG 09 LTG 12 LTG 10 LTG 08 LTG 14 LTG 03 LTG 07 LTG 05 LTG 01 LTG 04 LTG 02 MB LTG 06

CCGXXA (-Q888-)

IOP0 / D271 IOP1 / D265

T/RM:SYCR (-Q868-)

RES00 / D253

CCG:MB / D223

CCG:MB / D223 RES01 / D213 RES02 / D199 MASTER:INT / D193 REF1 / D187 CCG:INT / D181

CDEX (-Q900-)

RES01 / D213

Modules with displays and switches in F:SMSC(C)

T/RM:SYCR (-Q868-X200-)

RES02 / D199 MASTER:INT / D193 REF1 / D187 CCG:INT / D181

IOP0 / D165 IOP1 / D159

CEDEX:INT / C147 TACT / C141

SYPD:MDF / D141 SYPD0 / C135

DCCCR (-Q5619-)

CEDEX:INT / D147 TACT / D141 CEDEX / MDF / D135 TACT / D129 RES03 / D123 TACT / C129 RES13 / C123

RES03 / D123 IOP0 / D113 IOP1 / D107

RES13 / C123 IOP0 / C113 IOP1 / C107

CDEX (-Q900-X100-)

Construction

463

Construction

Maintenance Node

3.8.5

F:SMSC(C) (cabling)
Cabling master/slave and CDEX
Internal Cabling 02 D181--> 04 C181 02 D147 --> 04 C147 CCG-0 <--> CCG-1 Internal cabling for master/slave setting CCG0 --> CCG1 CDEX synchronization

Tab. 3.267 F:SMSC(C) cabling master/slave and CDEX Internal cabling (plesiochronous)
Plesiochronous mode: 02 D193 --> 04 C193 no reference frequency cabled: Internal cabling CCG 0-= <--> CCG-1 CCG1 Synchronization of CCG1 by CCG0

Tab. 3.268 F:SMSC(C) Internal cabling (plesiochronous) Reference frequency cabling


Synchronous mode: Reference Frequency Cabling (external references) 02 C187 CCG0 <-- reference frequency 0 from F:LTGx 03 D187 CCG1 <-- reference frequency 1 from F:LTGx 03 C187 CCG1 <-- reference frequency 2 from F:LTGx 02 D187 CCG0 <-- reference frequency 3 from F:LTGx Note

The reference frequencies can also be cabled via a distribution frame from atomic frequency standards or carrier frequency links (exceptional case)

Tab. 3.269 F:SMSC(C) reference frequency cabling Internal cabling (Synchron)


Synchronous mode: Internal cabling CCG0 <--> CCG1 depending on the number of external reference frequencies being applied (regardless of whether the source is PCM, CF or atomic frequency standard) reference frequencies 0 or reference frequencies 0 and 1 cabled (one or two reference frequencies) CCG0 --> CCG1 Incoming clock passed on to CCG1 resp. cross-joint connection of reference frequencies reference frequencies 0, 1 and 2 cabled (3 reference frequencies) CCG0 --> CCG1 Cross-joint connection of reference frequencies If reference frequencies 0 to 3 are cabled (4 reference frequencies) no further cabling is necessary here.

02 C193--> 04 C193

02 D193 --> 04 D193

Tab. 3.270 F:SMSC(C) internal cabling (synchronous)

464

A30828-X1160-M-2-7620

Maintenance Node

Construction

Cabling CCG <--> MB


Cabling CCG <--> MB 02 D223 --> 04 C223 02 C223 --> 02 C223 04 D223 --> 04 D223 cross-joint connection MB0 <--> CCG1 and MB1 <--> CCG0 link connector for MB0 <--> CCG0 link connector for MB1 <--> CCG1

Tab. 3.271 F:SMSC(C) cables CCG <-> MB Cabling CCG <--> PIOP(A)
Cross-joint connection CCG <--> PIOP(A), CP113CR CCG0: 02 D165 -> PIOP(A)0: 03 C301P1 CCG0: 02 C165 -> PIOP(A)0: 03 C301P2 CCG0: 02 D159 -> PIOP(A)1: 07 C301P1 CCG0: 02 C159 -> PIOP(A)1: 07 C301P2 CCG1: 04 D165 -> PIOP(A)0: 03 C301P3 CCG1: 04 C165 -> PIOP(A)0: 03 C301P4 CCG1: 04 D159 -> PIOP(A)0: 07 C301P3 CCG1: 04 C159 -> PIOP(A)1: 07 C301P4

Tab. 3.272 F:SMSC(C) cables CCG <-> CP113CR, PIOP(A)

Clock cables CCG <--> F:PIOP(A) (CP113C) CCG0: 02 C199 -> PIOP(A)1: 07 C329P2 CCG0: 02 D199 -> PIOP(A)0: 03 C329P2 CCG1: 04 C199 -> PIOP(A)1: 07 C329P3 CCG1: 04 D199 -> PIOP(A)0: 03 C329P3

Tab. 3.273 F:SMSC(C) clock cables CCG <-> PIOP(A) Cabling CCG <--> PIOP(B)
Cross-joint connection CCG <--> PIOP(B), CP113CR CCG0: 02 D165 -> PIOP(B)0: 03 C321P1 CCG0: 02 C165 -> PIOP(B)0: 03 C321P2 CCG0: 02 D159 -> PIOP(B)1: 07 C321P1 CCG0: 02 C159 -> PIOP(B)1: 07 C321P2 CCG1: 04 D165 -> PIOP(B)0: 03 C321P3 CCG1: 04 C165 -> PIOP(B)0: 03 C321P4 CCG1: 04 D159 -> PIOP(B)0: 07 C321P3 CCG1: 04 C159 -> PIOP(B)1: 07 C321P4

Tab. 3.274 F:SMSC(C) cables CCG <-> CP113CR, PIOP(B)

Clock cables CCG <--> F:PIOP(B), CP113CR CCG0: 02 C199 -> PIOP(B)1: 07 C335P2 CCG0: 02 D199 -> PIOP(B)0: 03 C335P2 CCG1: 04 C199 -> PIOP(B)1: 07 C335P3 CCG1: 04 D199 -> PIOP(B)0: 03 C335P3

Tab. 3.275 F:SMSC(C) clock cables CCG <-> PIOP(B) Cabling CDEX --> HVT
Cabling CDEX --> HVT 04 C129 -> HVT 04 D129 -> HVT Connection CDEX0, Tact 0-1 Connection CDEX0, Tact 2-3

Tab. 3.276 F:SMSC(C) cabling CDEX --> HVT

A30828-X1160-M-2-7620

465

Construction

Maintenance Node

Cabling CDEX --> HVT 04 C141 -> HVT 04 D141 -> HVT 04 C129 -> HVT 04 D129 -> HVT 04 C141 -> HVT 04 D141 -> HVT Connection CDEX1, Tact 0-1 Connection CDEX1, Tact 2-3 Connection CDEX0, Tact 0-1 Connection CDEX0, Tact 2-3 Connection CDEX1, Tact 0-1 Connection CDEX1, Tact 2-3

Tab. 3.276 F:SMSC(C) cabling CDEX --> HVT Cabling MB --> IOP:MB
Cabling MB --> IOP:MB 02 D271 -> 03 C279P1 02 C271 -> 03 C279P2 04 D271 -> 03 C279P3 04 C271 -> 03 C279P4 02 D265 -> 07 C279P1 02 C265 -> 07 C279P2 04 D265 -> 07 C279P3 04 C265 -> 07 C279P4

Tab. 3.277 F:SMSC(C): cabling MB - IOP:MB Cabling MB --> F:PIOP(B)


Cabling MB --> F:PIOP(B) 02 D271 -> 03 C305P1 02 C271 -> 03 C305P2 04 D271 -> 03 C305P3 04 C271 -> 03 C305P4 02 D265 -> 07 C305P1 02 C265 -> 07 C305P2 04 D265 -> 07 C305P3 04 C265 -> 07 C305P4

Tab. 3.278 F:SMSC(C): cabling MB - F:PIOP(B) Cabling SN(B) --> MB


Cabling SN(B) --> MB 02 C279P1 -> 02 C229 02 C335P1 -> 02 C243 04 C279P1 -> 04 C229 04 C335P1 -> 04 C243

Tab. 3.279 F:SMSC(C): cabling SN(B) - MB

466

A30828-X1160-M-2-7620

Maintenance Node

Construction

Cabling SYCR --> SYPD0


Cabling SYCR --> SYPD0 02 C135 -> SYPD0 SPD0 remote without MDF

Tab. 3.280 F:SMSC(C) cabling SYCR - SYPD0 Cabling SYCR --> HVT
Cabling SYCR --> MDF 02 D141 -> HVT MDF-Interface (SYPD 1 external alarm generators, external fault signaling equipment.

Tab. 3.281 F:SMSC(C) cabling SYCR- MDF Cabling SYCR --> PIOP(A)
Cabling SYCR --> PIOP(A) 02 D107 -> 07 C291P1 02 C107 -> 07 C291P2 04 D113 -> 03 C291P1 04 C113 -> 03 C291P2

Tab. 3.282 F:SMSC(C) cabling SYCR - PIOP(A) Cabling SYCR --> PIOP(B)
Cabling SYCR --> PIOP(B) 02 D107 -> 07 C313P1 02 C107 -> 07 C313P2 04 D113 -> 03 C313P1 04 C113 -> 03 C313P2

Tab. 3.283 F:SMSC(C) cabling SYCR - PIOP(B) Cabling F:SMSC(C) LTG All LTGxx are connected with SN0 (MUT02) and SN1 (MUT04).
Connector LTG01 LTG02 LTG03 LTG04 LTG05 LTG06 LTG07 MOLOC C285P2 C279P3 C285P4 C279P5 D285P1 D279P2 D285P3 Connector LTG17 LTG18 LTG19 LTG20 LTG21 LTG22 LTG23 MOLOC C317P2 C311P3 C317P4 C311P5 D317P1 D311P2 D317P3

Tab. 3.284 F:SMSC(C) cabling LTG

A30828-X1160-M-2-7620

467

Construction

Maintenance Node

Connector LTG08 LTG09 LTG10 LTG11 LTG12 LTG13 LTG14 LTG15 LTG16

MOLOC C291P1 C297P2 C291P3 C297P4 C291P5 D297P1 D291P2 D297P3 C311P1

Connector LTG24 LTG25 LTG26 LTG27 LTG28 LTG29 LTG30 LTG31

MOLOC C323P1 C329P2 C323P3 C329P4 C323P5 D329P1 D323P2 D329P3

Tab. 3.284 F:SMSC(C) cabling LTG

468

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.9

F:SN
SNA 3.9.1 3.9.1.1 3.9.1.2 3.9.1.3 3.9.2 3.9.2.1 3.9.2.2 3.9.2.3 3.9.3 3.9.3.1 3.9.3.2 3.9.3.3 3.9.4 SNB 3.9.5 3.9.5.1 3.9.5.2 3.9.5.3 3.9.5.4 3.9.5.5 3.9.5.6 3.9.6 3.9.6.1 3.9.6.2 3.9.6.3 SND 3.9.7 3.9.7.1 3.9.7.2 3.9.7.3 3.9.8 3.9.8.1 3.9.8.2 3.9.8.3 3.9.9 3.9.9.1 3.9.9.2 3.9.9.3 3.9.10 3.9.10.1 3.9.10.2 F:SN(A) F:SN(A) (module side) F:SN(A) (backplane) F:SN(A) (cabling) F:SSG(A) F:SSG(A) (module side) F:SSG(A) (backplane) F:SSG(A) (cabling) F:TSG(A) F:TSG(A) (module side) F:TSG(A) (backplane) F:TSG(A) (cabling) F:DCC(B) F:TSG(B) F:TSG(B) SN(63LTG) (module side) F:TSG(B) SN(63LTG) (backplane) F:TSG(B) SN(63LTG) (cabling) F:TSG(B) (module side) F:TSG(B) (backplane) F:TSG(B) (cabling) F:SSG(B) F:SSG(B) (module side) F:SSG(B) (backplane) F:SSG(B) (cabling) F:SNMAT F:SNMAT (module side) F:SNMAT (backplane) F:SNMAT (cabling) F:SNMUX(A) F:SNMUX(A) (module side) F:SNMUX(A) (backplane) F:SNMUX(A) (cabling) F:SNMUX(B) F:SNMUX(B) (module side) F:SNMUX(B) (backplane) F:SNMUX(B) (cabling) F:SNCARE F:SNCARE (backplane) F:SNCARE (cabling)

A30828-X1160-M-2-7620

469

470

Construction

3.9.1.1

3.9.1

D A C

F:SN(A)

C001 TSM 08 LIL 08 A006 A011 A016 LIL 01 TSM 02 LIL 02 TSM 03 LIL 03 SSM16/16 00 A021 A026 A031 A036 A041 TSM 01 TSM 09 LIL 09 TSM 10 LIL 10 TSM 11 LIL 11 SSM16/16 02 LIL 00 TSM 00 C006 C011 C016 C021 C026 C031 C036 C041

F:SN(A) (module side)

A001

C061 SGC SSM16/16 03 C067

A061 A067

SGC SSM16/16 01

C087 TSM 12 LIL 12 TSM 13 LIL 13 TSM 14 LIL 14 TSM 15 LIL 15 C092 C097 C102 C107 C112 C117 C122

A087 TSM 04 A092 LIL 04 A097 TSM 05 A102 LIL 05 A107 TSM 06 A112 LIL 06 A117 TSM 07 A122 LIL 07

A30828-X1160-M-2-7620

Maintenance Node

Maintenance Node

3.9.1.3

3.9.1.2

A30828-X1160-M-2-7620 B
LTG 63 / D122 LTG 62 / D119 LTG 59 / D112 LTG 58 / D109 LTG 55 / D102 LTG 54 / D099 LTG 51 / D092 LTG 50 / D089 LTG 49 / C092 LTG 48 / C089 LTG 53 / C102 LTG 52 / C099 LTG 23 / B102 LTG 22 / B099 LTG 19 / B092 LTG 18 / B089 LTG 57 / C112 LTG 56 / C109 LTG 27 / B112 LTG 26 / B109

D A
LTG 61 / C122 LTG 60 / C119 LTG 31 / B122 LTG 30 / B119

LTG 29 / A122 LTG 28 / A119 LTG 25 / A112 LTG 24 / A109 LTG 21 / A102 LTG 20 / A099 LTG 17 / A092 LTG 16 / A089

F:SN(A) (cabling)

Cabling F:SN -> F:MBD

F:SN(A) (backplane)

SN-0: 02 A061 -> F:MBD0: D109P2

SN-0: 02 A003 -> F:MBD0: D109P1

SN-0

SN-0

SN-0: 02 A003 -> MBUL-0-0: 02 A055

Cabling F:SN -> F:MB/CCG(B)

Tab. 3.285 cabling F:SN -> F:MBD

SN-0: 02 A061 -> MBUS-0-0: 02 A040 SN-1 SN-1: 03 A003 -> F:MBD1: D109P1
LTG 47 / D036 LTG 46 / D033 LTG 43 / D026 LTG 42 / D023 LTG 39 / D016 LTG 38 / D013 LTG 35 / D006 LTG 34 / D003 LTG 45 / C036 LTG 44 / C033 LTG 41 / C026 LTG 40 / C023 LTG 37 / C016 LTG 36 / C013 LTG 33 / C006 LTG 32 / C003 LTG 15 / B036 LTG 14 / B033 LTG 11 / B026 LTG 10 / B023 LTG 07 / B016 LTG 06 / B013 LTG 03 / B006 LTG 02 / B003

Tab. 3.286 cabling F:SN -> F:MB/CCG(B)

MB / A061

SN-1: 03 A061 -> F:MBD1: D109P2

SN-1

SN-1: 03 A003 -> MBUL-1-0: 03 A055

SN-1: 03 A061 -> MBUS-1-0: 03 A040

LTG 13 / A036 LTG 12 / A033 LTG 09 / A026 LTG 08 / A023 LTG 05 / A016 LTG 04 / A013 LTG 01 / A006 MB / A003

Construction

471

472

Construction

3.9.2.1 3.9.2

B A

D C

C001 SSM8/15 08 T/RC2 A006 LIS 00 A011 SSM8/15 01 A016 LIS 01 A021 SSM8/15 02 A026 LIS 02 A031 SSM8/15 03 A036 LIS 03 A041 SSM16/16 00 A047 A053 SSM16/16 08 A057 SSM16/16 12 A061 LIM A067 SSM16/16 01 A073 SSM16/16 05 A079 SSM16/16 09 A083 SSM16/16 13 SSM8/15 12 LIS 12 SSM8/15 13 LIS 13 SSM8/15 14 LIS 14 SSM8/15 15 LIS 15 A087 SSM8/15 04 A092 LIS 04 A097 SSM8/15 05 A102 LIS 05 SSM16/16 04 SSM8/15 09 T/RC2 SSM8/15 10 LIS 10 SSM8/15 11 LIS 11 SSM16/16 02 SSM16/16 06 SSM16/16 10 SSM16/16 14

A001 SSM8/15 00

F:SSG(A)

C006

C011

C016

Cabling F:SN -> LTG

C021

C026

C031

F:SSG(A) (module side)

C036

C041

C047

C053

C057

C061 SGC SSM16/16 03 SSM16/16 07

C067

C073

C079 SSM16/16 11

C087

All LTGxx are connected with SN-0 (MUT02) and SN-1 (MUT03).

C092

C097

C102

C107

C112

C117

A107 SSM8/15 06 A112 LIS 06 A117 SSM8/15 07 A122 LIS 07

A30828-X1160-M-2-7620

Maintenance Node

C122

Maintenance Node

3.9.2.3

3.9.2.2

A30828-X1160-M-2-7620 B A
TSG / B122 TSG / B119 TSG / B112 TSG / B109 TSG / B102 TSG / B099 TSG / B092 TSG / B089 TSG / A092 TSG / A089 TSG / A102 TSG / A099 TSG / B102 TSG / B099 TSG / B092 TSG / B089 TSG / A112 TSG / A109 TSG / B112 TSG / B109

D
TSG / A122 TSG / A119 TSG / B122 TSG / B119

TSG / A122 TSG / A119 TSG / A112 TSG / A109 TSG / A102 TSG / A099 TSG / A092 TSG / A089

F:SSG(A) (cabling)

Cabling F:SSG -> F:MBD

F:SSG(A) (backplane)

SN-0

SSG-0-3 02 A061 -> F:MBD0: C215P5 SN-1


TSG / B036 TSG / B033 TSG / B026 TSG / B023 TSG / B016 TSG / B013 TSG / B006 TSG / B003 TSG / A036 TSG / A033 TSG / A026 TSG / A023 TSG / A016 TSG / A013 TSG / A006 TSG / A003 TSG / B036 TSG / B033 TSG / B026 TSG / B023 TSG / B016 TSG / B013 TSG / B006 TSG / B003

SSG-0-2 02 A061 -> F:MBD0: C215P4

SSG-0-1 02 A061 -> F:MBD0: C109P5

SSG-0-0 02 A061 -> F:MBD0: C109P4

Tab. 3.287 Cabling F:SSG -> F:MBD

MB / A061

SSG-1-3 03 A061 -> F:MBD1: C215P5

SSG-1-2 03 A061 -> F:MBD1: C215P4

SSG-1-1 03 A061 -> F:MBD1: C109P5

SSG-1-0 03 A061 -> F:MBD1: C109P4

TSG / A036 TSG / A033 TSG / A026 TSG / A023 TSG / A016 TSG / A013 TSG / A006 TSG / A003

Construction

473

Construction

Maintenance Node

Cabling F:SSG -> F:MB/CCG(B)


SN-0 SSG-0-0 02 A061 -> MBUS-0-0 02 B049 SSG-0-1 02 A061 -> MBUS-0-1 08 B049 SSG-0-2 02 A061 -> MBUS-0-2 02 B049 SSG-0-3 02 A061 -> MBUS-0-3 08 B049 SN-1 SSG-1-0 03 A061 -> MBUS-1-0 03 B049 SSG-1-1 03 A061 -> MBUS-1-1 09 B049 SSG-1-2 03 A061 -> MBUS-1-2 03 B049 SSG-1-3 03 A061 -> MBUS-1-3 09 B049

Tab. 3.288 Cabling F:SSG -> F:MB/CCG(B) Internal cabling SN(504LTG) TSGx -> SSG
TSGx MUT TSG0 --> SSG B003 B003 B003 B003 A003 A003 A003 A003 B003 B003 B003 B003 A003 A003 A003 A003 B006 B006 B006 B006 A006 A006 A006 A006 B006 B006 B006 S S G 0 0 1 1 0 0 1 1 2 2 3 3 2 2 3 3 0 0 1 1 0 0 1 1 2 2 3 TSG1 --> SSG B023 B023 B023 B023 A023 A023 A023 A023 B023 B023 B023 B023 A023 A023 A023 A023 B026 B026 B026 B026 A026 A026 A026 A026 B026 B026 B026 TSG2 --> SSG B089 B089 B089 B089 A089 A089 A089 A089 B089 B089 B089 B089 A089 A089 A089 A089 B092 B092 B092 B092 A092 A092 A092 A092 B092 B092 B092 TSG3 --> SSG B109 B109 B109 B109 A109 A109 A109 A109 B109 B109 B109 B109 A109 A109 A109 A109 B112 B112 B112 B112 A112 A112 A112 A112 B112 B112 B112 TSG4 --> SSG D003 D003 D003 D003 C003 C003 C003 C003 D003 D003 D003 D003 C003 C003 C003 C003 D006 D006 D006 D006 C006 C006 C006 C006 D006 D006 D006 TSG5 --> SSG D023 D023 D023 D023 C023 C023 C023 C023 D023 D023 D023 D023 C023 C023 C023 C023 D026 D026 D026 D026 C026 C026 C026 C026 D026 D026 D026 TSG6 --> SSG D089 D089 D089 D089 C089 C089 C089 C089 D089 D089 D089 D089 C089 C089 C089 C089 D092 D092 D092 D092 C092 C092 C092 C092 D092 D092 D092 TSG7 --> SSG D109 D109 D109 D109 C109 C109 C109 C109 D109 D109 D109 D109 C109 C109 C109 C109 D112 D112 D112 D112 C112 C112 C112 C112 D112 D112 D112

02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 03 03 03

A041 A044 A067 A070 B041 B044 B067 B070 C041 C044 C067 C070 D041 D044 D067 D070 A041 A044 A067 A070 B041 B044 B067 B070 C041 C044 C067

02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02

Tab. 3.289 Internal cabling SN(504LTG)

474

A30828-X1160-M-2-7620

Maintenance Node

Construction

TSGx

MUT

TSG0 --> SSG B006 A006 A006 A006 A006 B013 B013 B013 B013 A013 A013 A013 A013 B013 B013 B013 B013 A013 A013 A013 A013 B016 B016 B016 B016 A016 A016 A016 A016 B016 B016 B016 B016 A016 A016 A016 A016

S S G 3 2 2 3 3 0 0 1 1 0 0 1 1 2 2 3 3 2 2 3 3 0 0 1 1 0 0 1 1 2 2 3 3 2 2 3 3

TSG1 --> SSG B026 A026 A026 A026 A026 B033 B033 B033 B033 A033 A033 A033 A033 B033 B033 B033 B033 A033 A033 A033 A033 B036 B036 B036 B036 A036 A036 A036 A036 B036 B036 B036 B036 A036 A036 A036 A036

TSG2 --> SSG B092 A092 A092 A092 A092 B099 B099 B099 B099 A099 A099 A099 A099 B099 B099 B099 B099 A099 A099 A099 A099 B102 B102 B102 B102 A102 A102 A102 A102 B102 B102 B102 B102 A102 A102 A102 A102

TSG3 --> SSG B112 A112 A112 A112 A112 B119 B119 B119 B119 A119 A119 A119 A119 B119 B119 B119 B119 A119 A119 A119 A119 B122 B122 B122 B122 A122 A122 A122 A122 B122 B122 B122 B122 A122 A122 A122 A122

TSG4 --> SSG D006 C006 C006 C006 C006 D013 D013 D013 D013 C013 C013 C013 C013 D013 D013 D013 D013 C013 C013 C013 C013 D016 D016 D016 D016 C016 C016 C016 C016 D016 D016 D016 D016 C016 C016 C016 C016

TSG5 --> SSG D026 C026 C026 C026 C026 D033 D033 D033 D033 C033 C033 C033 C033 D033 D033 D033 D033 C033 C033 C033 C033 D036 D036 D036 D036 C036 C036 C036 C036 D036 D036 D036 D036 C036 C036 C036 C036

TSG6 --> SSG D092 C092 C092 C092 C092 D099 D099 D099 D099 C099 C099 C099 C099 D099 D099 D099 D099 C099 C099 C099 C099 D102 D102 D102 D102 C102 C102 C102 C102 D102 D102 D102 D102 C102 C102 C102 C102

TSG7 --> SSG D112 C112 C112 C112 C112 D119 D119 D119 D119 C119 C119 C119 C119 D119 D119 D119 D119 C119 C119 C119 C119 D122 D122 D122 D122 C122 C122 C122 C122 D122 D122 D122 D122 C122 C122 C122 C122

03 03 03 03 03 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03

C070 D041 D044 D067 D070 A047 A050 A073 A076 B047 B050 B073 B076 C047 C050 C073 C076 D047 D050 D073 D076 A047 A050 A073 A076 B047 B050 B073 B076 C047 C050 C073 C076 D047 D050 D073 D076

03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03

Tab. 3.289 Internal cabling SN(504LTG)

A30828-X1160-M-2-7620

475

Construction

Maintenance Node

Internal cabling SN(252LTG) TSGx -> SSG


TSGx 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 02 02 02 02 02 A041 A044 A067 A070 B041 B044 B067 B070 C041 C044 C067 C070 D041 D044 D067 D070 A041 A044 A067 A070 B041 B044 B067 B070 C041 C044 C067 C070 D041 D044 D067 D070 A047 A050 A073 A076 B047 MUT 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 TSG0 --> SSG B003 B003 B003 B003 A003 A003 A003 A003 D003 D003 D003 D003 C003 C003 C003 C003 B006 B006 B006 B006 A006 A006 A006 A006 D006 D006 D006 D006 C006 C006 C006 C006 B013 B013 B013 B013 A013 SSG 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 TSG1 --> SSG B023 B023 B023 B023 A023 A023 A023 A023 D023 D023 D023 D023 C023 C023 C023 C023 B026 B026 B026 B026 A026 A026 A026 A026 D026 D026 D026 D026 C026 C026 C026 C026 B033 B033 B033 B033 A033 TSG2 --> SSG B089 B089 B089 B089 A089 A089 A089 A089 D089 D089 D089 D089 C089 C089 C089 C089 B092 B092 B092 B092 A092 A092 A092 A092 D092 D092 D092 D092 C092 C092 C092 C092 B099 B099 B099 B099 A099 TSG3 --> SSG B109 B109 B109 B109 A109 A109 A109 A109 D109 D109 D109 D109 C109 C109 C109 C109 B112 B112 B112 B112 A112 A112 A112 A112 D112 D112 D112 D112 C112 C112 C112 C112 B119 B119 B119 B119 A119

Tab. 3.290 Internal cabling SN(252LTG)

476

A30828-X1160-M-2-7620

Maintenance Node

Construction

TSGx 02 02 02 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 B050 B073 B076 C047 C050 C073 C076 D047 D050 D073 D076 A047 A050 A073 A076 B047 B050 B073 B076 C047 C050 C073 C076 D047 D050 D073 D076

MUT 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03

TSG0 --> SSG A013 A013 A013 D013 D013 D013 D013 C013 C013 C013 C013 B016 B016 B016 B016 A016 A016 A016 A016 D016 D016 D016 D016 C016 C016 C016 C016 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1

SSG

TSG1 --> SSG A033 A033 A033 D033 D033 D033 D033 C033 C033 C033 C033 B036 B036 B036 B036 A036 A036 A036 A036 D036 D036 D036 D036 C036 C036 C036 C036

TSG2 --> SSG A099 A099 A099 D099 D099 D099 D099 C099 C099 C099 C099 B102 B102 B102 B102 A102 A102 A102 A102 D102 D102 D102 D102 C102 C102 C102 C102

TSG3 --> SSG A119 A119 A119 D119 D119 D119 D119 C119 C119 C119 C119 B122 B122 B122 B122 A122 A122 A122 A122 D122 D122 D122 D122 C122 C122 C122 C122

Tab. 3.290 Internal cabling SN(252LTG) Internal cabling SN(126LTG) TSGx --> SSG
TSGx 02 02 02 02 02 02 A041 A044 A067 A070 B041 B044 02 03 02 03 02 03 MUT TSG0 --> SSG B003 B003 B089 B089 A003 A003 0 0 0 0 0 0 SSG TSG1 --> SSG B023 B023 B109 B109 A023 A023

Tab. 3.291 Internal cabling SN(126LTG)

A30828-X1160-M-2-7620

477

Construction

Maintenance Node

TSGx 02 02 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 02 02 02 02 02 02 02 02 02 02 02 02 B067 B070 C041 C044 C067 C070 D041 D044 D067 D070 A041 A044 A067 A070 B041 B044 B067 B070 C041 C044 C067 C070 D041 D044 D067 D070 A047 A050 A073 A076 B047 B050 B073 B076 C047 C050 C073 C076 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03

MUT

TSG0 --> SSG A089 A089 D003 D003 D089 D089 C003 C003 C089 C089 B006 B006 B092 B092 A006 A006 A092 A092 D006 D006 D092 D092 C006 C006 C092 C092 B013 B013 B099 B099 A013 A013 A099 A099 D013 D013 D099 D099 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

SSG

TSG1 --> SSG A109 A109 D023 D023 D109 D109 C023 C023 C109 C109 B026 B026 B112 B112 A026 A026 A112 A112 D026 D026 D112 D112 C026 C026 C112 C112 B033 B033 B119 B119 A033 A033 A119 A119 D033 D033 D119 D119

Tab. 3.291 Internal cabling SN(126LTG)

478

A30828-X1160-M-2-7620

Maintenance Node

Construction

TSGx 02 02 02 02 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 D047 D050 D073 D076 A047 A050 A073 A076 B047 B050 B073 B076 C047 C050 C073 C076 D047 D050 D073 D076 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03 02 03

MUT

TSG0 --> SSG C013 C013 C099 C099 B016 B016 B102 B102 A016 A016 A102 A102 D016 D016 D102 D102 C016 C016 C102 C102 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

SSG

TSG1 --> SSG C033 C033 C119 C119 B036 B036 B122 B122 A036 A036 A122 A122 D036 D036 D122 D122 C036 C036 C122 C122

Tab. 3.291 Internal cabling SN(126LTG)

3.9.3 3.9.3.1

F:TSG(A) F:TSG(A) (module side)

B
TSM 04 TSM 05 TSM 06 TSM 00 TSM 01 TSM 02 TSM 03 TSM 07 A117 LIL 04 LIS 00 LIS 04 LIL 01 LIL 02 LIL 03 LIS 01 LIL 00 A061 LIM LIS 05 LIL 05 LIL 06 A112 LIL 07 A122

A092

A087

A097

A001

A026

A036

A070

A021

A006

A011

A031

A044

A016

A050

A076

A102

A107

A30828-X1160-M-2-7620

479

480

Construction

3.9.3.2

B A

LTG / D122 LTG / D119

LTG / D112 LTG / D109

LTG / D102 LTG / D099

F:TSG(A) (backplane)

LTG / D092 LTG / D089

SSG / D076 SSG / D073 SSG / D070 SSG / D067 SSG / A076 SSG / A073 SSG / A070 SSG / A067 MB / A061

SSG / D050 SSG / D047 SSG / D044 SSG / D041 SSG / A050 SSG / A047 SSG / A044 SSG / A041 LTG / A036 LTG / A033 LTG / A026 LTG / A023 LTG / A016 LTG / A013 LTG / A006 LTG / A003 LTG / B036 LTG / B033 LTG / B026 LTG / B023 LTG / B016 LTG / B013 LTG / B006 LTG / B003

LTG / D036 LTG / D033

LTG / D026 LTG / D023

LTG / D016 LTG / D013

A30828-X1160-M-2-7620

Maintenance Node

LTG / D006 LTG / D003

D
LTG / B122 LTG / B119 LTG / A122 LTG / A119

LTG / C122 LTG / C119

LTG / C112 LTG / C109 LTG / B112 LTG / B109

LTG / C102 LTG / C099 LTG / B102 LTG / B099

LTG / C092 LTG / C089 LTG / B092 LTG / B089

SSG / C076 SSG / C073 SSG / C070 SSG / C067

SSG / C050 SSG / C047 SSG / C044 SSG / C041

TSG / C036 LTG / C033

LTG / C026 LTG / C023

LTG / C016 LTG / C013

LTG / C006 LTG / C003

C
C001 TSM 08 C006 LIL 08 C011 TSM 09 C016 LIL 09 C021 TSM 10 C026 LIL 10 C031 TSM 11 C036 LIL 11 C044 LIS 02
SSG / B076 SSG / B073 SSG / B070 SSG / B067 LTG / A112 LTG / A109 LTG / A102 LTG / A099 LTG / A092 LTG / A089

C050 LIS 06 C061 SSG

C070 LIS 03
SSG / B050 SSG / B047 SSG / B044 SSG / B041

C076 LIS 07

C087 TSM 12 C092 LIL 12 C097 TSM 13 C102 LIL 13 C107 TSM 14 C112 LIL 14 C117 TSM 15 C122 LIL 15

Maintenance Node

Construction

3.9.3.3

F:TSG(A) (cabling)
Cabling F:TSG -> F:MBD:
SN-0 TSG-0-0 02 A003 -> F:MBD0: D109P1 TSG-0-0 02 A061 -> F:MBD0: D109P2 TSG-0-1 02 A003 -> F:MBD0: D109P3 TSG-0-1 02 A061 -> F:MBD0: D109P4 TSG-0-2 02 A003 -> F:MBD0: D101P1 TSG-0-2 02 A061 -> F:MBD0: D101P2 TSG-0-3 02 A003 -> F:MBD0: D101P3 TSG-0-3 02 A061 -> F:MBD0: D101P4 TSG-0-4 02 A003 -> F:MBD0: D215P1 TSG-0-4 02 A061 -> F:MBD0: D215P2 TSG-0-5 02 A003 -> F:MBD0: D215P3 TSG-0-5 02 A061 -> F:MBD0: D215P4 TSG-0-6 02 A003 -> F:MBD0: D207P1 TSG-0-6 02 A061 -> F:MBD0: D207P2 TSG-0-7 02 A003 -> F:MBD0: D207P3 TSG-0-7 02 A061 -> F:MBD0: D207P4 SN-1 TSG-1-0 03 A003 -> F:MBD1: D109P1 TSG-1-0 03 A061 -> F:MBD1: D109P2 TSG-1-1 03 A003 -> F:MBD1: D109P3 TSG-1-1 03 A061 -> F:MBD1: D109P4 TSG-1-2 03 A003 -> F:MBD1: D101P1 TSG-1-2 03 A061 -> F:MBD1: D101P2 TSG-1-3 03 A003 -> F:MBD1: D101P3 TSG-1-3 03 A061 -> F:MBD1: D101P4 TSG-1-4 03 A003 -> F:MBD1: D215P1 TSG-1-4 03 A061 -> F:MBD1: D215P2 TSG-1-5 03 A003 -> F:MBD1: D215P3 TSG-1-5 03 A061 -> F:MBD1: D215P4 TSG-1-6 03 A003 -> F:MBD1: D207P1 TSG-1-6 03 A061 -> F:MBD1: D207P2 TSG-1-7 03 A003 -> F:MBD1: D207P3 TSG-1-7 03 A061 -> F:MBD1: D207P4

Tab. 3.292 Cabling F:TSG -> F:MBD Cabling F:TSG -> F:MB/CCG(B):
SN-0 TSG-0-0 02 A003 -> MBUL-0-0 02 A055 TSG-0-0 02 A061 -> MBUS-0-0 02 A040 TSG-0-1 02 A003 -> MBUL-0-1 02 B055 TSG-0-1 02 A061 -> MBUS-0-0 02 A049 TSG-0-2 02 A003 -> MBUL-0-2 08 A055 TSG-0-2 02 A061 -> MBUS-0-1 08 A040 TSG-0-3 02 A003 -> MBUL-0-3 08 B055 TSG-0-3 02 A061 -> MBUS-0-1 08 A049 TSG-0-4 02 A003 -> MBUL-0-4 02 A055 TSG-0-4 02 A061 -> MBUS-0-2 02 A040 TSG-0-5 02 A003 -> MBUL-0-5 02 B055 TSG-0-5 02 A061 -> MBUS-0-2 02 A049 TSG-0-6 02 A003 -> MBUL-0-6 08 A055 TSG-0-6 02 A061 -> MBUS-0-3 08 A040 SN-1 TSG-1-0 03 A003 -> MBUL-1-0 03 A055 TSG-1-0 03 A061 -> MBUS-1-0 03 A040 TSG-1-1 03 A003 -> MBUL-1-1 03 B055 TSG-1-1 03 A061 -> MBUS-1-0 03 A049 TSG-1-2 03 A003 -> MBUL-1-2 09 A055 TSG-1-2 03 A061 -> MBUS-1-1 09 A040 TSG-1-3 03 A003 -> MBUL-1-3 09 B055 TSG-1-3 03 A061 -> MBUS-1-1 09 A049 TSG-1-4 03 A003 -> MBUL-1-4 03 A055 TSG-1-4 03 A061 -> MBUS-1-2 03 A040 TSG-1-5 03 A003 -> MBUL-1-5 03 B055 TSG-1-5 03 A061 -> MBUS-1-2 03 A049 TSG-1-6 03 A003 -> MBUL-1-6 09 A055 TSG-1-6 03 A061 -> MBUS-1-3 09 A040

Tab. 3.293 Cabling F:TSG -> MB/CCG(B)

A30828-X1160-M-2-7620

481

Construction

Maintenance Node

SN-0 TSG-0-7 02 A003 -> MBUL-0-7 08 B055 TSG-0-7 02 A061 -> MBUS-0-3 08 A049

SN-1 TSG-1-7 03 A003 -> MBUL-1-7 09 B055 TSG-1-7 03 A061 -> MBUS-1-3 09 A049

Tab. 3.293 Cabling F:TSG -> MB/CCG(B) Cabling F:TSG -> LTG: All LTGxx are connected with SN-0 (MUT02) and SN-1 (MUT03). Internal cabling TSG <--> SSG: (see Tab. 3.289)

3.9.4

F:DCC(B)

B
DCCCS DCCCS DCCCS DCCCS DCCCS DCCCS A099

A001

A017

A033

A067

3.9.5 3.9.5.1

F:TSG(B) F:TSG(B) SN(63LTG) (module side)

D
C215 SSM16B C323 TSMB 7 C331 DCCMS C271 TSMB 4 C109 TSMB 0 C131 TSMB 1 C153 TSMB 2 C291 TSMB 5 C175 TSMB 3 C311 TSMB 6 C229 SSGB

A083

482

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.9.5.2

F:TSG(B) SN(63LTG) (backplane)


LTG 52 LTG 50 LTG 48 LTG 54 LTG 55 LTG 53 LTG 51 LTG 49 LTG 44 LTG 42 LTG 40 LTG 46 LTG 45 LTG 43 LTG 41 LTG 47 LTG 38 LTG 36 LTG 34 LTG 32 LTG 37 LTG 39 LTG 35 LTG 33 LTG 56 LTG 28 LTG 26 LTG 24 LTG 30 LTG 27 LTG 25 LTG 29 LTG 31 P1 LTG 57 P2 LTG 20 LTG 18 LTG 16 LTG 22 LTG 19 LTG 17 LTG 21 LTG 23 LTG 14 LTG 12 LTG 10 LTG 08 LTG 11 LTG 09 LTG 13 LTG 15

MB

P3 P4 P5 P1 P2 P3 P4

3.9.5.3

F:TSG(B) SN(63LTG) (cabling)


Cabling F:TSG(B) -> F:MBD
SN-0 SN-0: 02/06 C109P1 -> F:MBD0: D109P1 SN-0: 02/06 C229P1 -> F:MBD0: D109P2 SN-1 SN-1: 03/07 C109P1 -> F:MBD1: D109P1 SN-1: 03/07 C229P1 -> F:MBD1: D109P2

MUT02 or 03: cabling from above, MUT 06 or 07 cabling from below

Tab. 3.294 Cabling F:TSG(B) -> F:MB/CCG(B) Cabling F:TSG(B) -> F:MB/CCG(B)
SN-0 SN-0: 02/06 C109P1 -> MBUL-0-0: 02 A055 SN-0: 02/06 C229P1 -> MBUS-0-0: 02 A040 SN-1 SN-1: 03/07 C109P1 -> MBUL-1-0: 03 A055 SN-1: 03/07 C229P1 -> MBUS-1-0: 03 A040

MUT02 or 03: cabling from above, MUT 06 or 07 cabling from below For MBUL, MBUS in R:SN/MB/LTGM: MBUL-0-0 and MBUS-0-0 are located in MUT04, MBUL-1-0 and MBUS-1-0 are located in MUT05

Tab. 3.295 Cabling F:TSG(B) -> F:MB/CCG(B) Cabling F:TSG(B) -> LTG All LTGxx are connected with SN0 (MUT02 or MUT06) and SN1 (MUT03 or MUT07).
Connector LTG01 LTG02 LTG03 MOLOC C103P2 C109P3 C103P4 Connector LTG22 LTG23 LTG24 MOLOC D153P2 D147P3 C175P1 Connector LTG43 LTG44 LTG45 MOLOC C285P4 C291P5 D285P1

Tab. 3.296 F:TSG(B) cabling LTG

LTG 63

A30828-X1160-M-2-7620

LTG 02 MB LTG 06 LTG 04 LTG 03 LTG 01 LTG 05 LTG 07

LTG 59 LTG 61

LTG 62

LTG 60

LTG 58

483

Construction

Maintenance Node

Connector LTG04 LTG05 LTG06 LTG07 LTG08 LTG09 LTG10 LTG11 LTG12 LTG13 LTG14 LTG15 LTG16 LTG17 LTG18 LTG19 LTG20 LTG21

MOLOC C109P5 D103P1 D109P2 D103P3 C131P1 C125P2 C131P3 C125P4 C131P5 D125P1 D131P2 D125P3 C153P1 C147P2 C153P3 C147P4 C153P5 D147P1

Connector LTG25 LTG26 LTG27 LTG28 LTG29 LTG30 LTG31 LTG32 LTG33 LTG34 LTG35 LTG36 LTG37 LTG38 LTG39 LTG40 LTG41 LTG42

MOLOC C169P2 C175P3 C169P4 C175P5 D169P1 D175P2 D169P3 C271P1 C265P2 C271P3 C265P4 C271P5 D265P1 D271P2 D265P3 C291P1 C285P2 C291P3

Connector LTG46 LTG47 LTG48 LTG49 LTG50 LTG51 LTG52 LTG53 LTG54 LTG55 LTG56 LTG57 LTG58 LTG59 LTG60 LTG61 LTG62 LTG63

MOLOC D291P2 D285P3 C311P1 C305P2 C311P3 C305P4 C311P5 D305P1 D311P2 D305P3 C323P1 C337P2 C323P3 C337P4 C323P5 D337P1 D323P2 D337P3

Tab. 3.296 F:TSG(B) cabling LTG

3.9.5.4

F:TSG(B) (module side)

D
C323 TSMB 7 C331 DCCMS C271 TSMB 4 C109 TSMB 0 C131 TSMB 1 C153 TSMB 2 C291 TSMB 5 C175 TSMB 3 C253 LISB 3 C311 TSMB 6 C187 LISB 0 C203 LISB 1 C229 SGCB C241 LISB 2

484

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.9.5.5

F:TSG(B) (backplane)
LTG 52 LTG 50 LTG 48 LTG 54 LTG 55 LTG 53 LTG 51 LTG 49 LTG 44 LTG 42 LTG 40 LTG 46 LTG 45 LTG 43 LTG 41 LTG 47 LTG 38 LTG 36 LTG 34 LTG 32 LTG 37 LTG 39 LTG 35 LTG 33 LTG 56 LTG 28 LTG 26 LTG 24 LTG 30 LTG 27 LTG 25 LTG 29 LTG 31 SSG SSG SSG SSG P1 LTG 57 P2 LTG 20 LTG 18 LTG 16 LTG 22 LTG 19 LTG 17 LTG 21 LTG 23 LTG 14 LTG 12 LTG 10 LTG 08 LTG 11 LTG 09 LTG 13 LTG 15

MB

SSG

LTG 61

SSG

SSG

LTG 63

SSG

SSG

SSG

P4

3.9.5.6

F:TSG(B) (cabling)
Cabling F:TSG(B) -> F:MBD
SN-0 TSG-0-0: 02/06C109P1 -> F:MBD0: D109P1 TSG-0-0: 02/06C229P1 -> F:MBD0: D109P2 TSG-0-1: 02/06C109P1 -> F:MBD0: D109P3 TSG-0-1: 02/06C229P1 -> F:MBD0: D109P4 TSG-0-2: 02/06C109P1 -> F:MBD0: D101P1 TSG-0-2: 02/06C229P1 -> F:MBD0:D101P2 TSG-0-3: 02/06C109P1 -> F:MBD0: D101P3 TSG-0-3: 02/06C229P1 -> F:MBD0: D101P4 TSG-0-4: 02/06C109P1 -> F:MBD0: D215P1 TSG-0-4: 02/06C229P1 -> F:MBD0: D215P2 TSG-0-5: 02/06C109P1 -> F:MBD0: D215P3 TSG-0-5: 02/06C229P1 -> F:MBD0: D215P4 TSG-0-6: 02/06C109P1 -> F:MBD0: D207P1 TSG-0-6: 02/06C229P1 -> F:MBD0: D207P2 TSG-0-7: 02/06C109P1 -> F:MBD0: D207P3 TSG-0-7: 02/06C229P1 -> F:MBD0: D207P4 SN-1 TSG-1-0: 03/07C109P1 -> F:MBD1: D109P1 TSG-1-0: 03/07C229P1 -> F:MBD1: D109P2 TSG-1-1: 03/07C109P1 -> F:MBD1: D109P3 TSG-1-1: 03/07C229P1 -> F:MBD1: D109P4 TSG-1-2: 03/07C109P1 -> F:MBD1: D101P1 TSG-1-2: 03/07C229P1 -> F:MBD1: D101P2 TSG-1-3: 03/07C109P1 -> F:MBD1: D101P3 TSG-1-3: 03/07C229P1 -> F:MBD1: D101P4 TSG-1-4: 03/07C109P1 -> F:MBD1: D215P1 TSG-1-4: 03/07C229P1 -> F:MBD1: D215P2 TSG-1-5: 03/07C109P1 -> F:MBD1: D215P3 TSG-1-5: 03/07C229P1 -> F:MBD1: D215P4 TSG-1-6: 03/07C109P1 -> F:MBD1: D207P1 TSG-1-6: 03/07C229P1 -> F:MBD1: D207P2 TSG-1-7: 03/07C109P1 -> F:MBD1: D207P3 TSG-1-7: 03/07C229P1 -> F:MBD1: D207P4

F:TSG(B): MUT02 or 03 -> cabling from above, MUT 06 or 07 -> cabling from below.

Tab. 3.297 Cabling F:TSG(B) -> F:MBD

SSG

P3

LTG 62

P2

SSG

SSG

P1

LTG 60

P5

LTG 59

P4

SSG

SSG

SSG

P3

A30828-X1160-M-2-7620

LTG 02 MB LTG 06 LTG 04 LTG 03 LTG 01 LTG 05 LTG 07

LTG 58

485

Construction

Maintenance Node

Cabling F:TSG(B) -> F:MB/CCG(B):


SN-0 TSG-0-0: 02/06C109P1 -> MBUL-0-0: 02A055 TSG-0-0: 02/06C229P1 -> MBUS-0-0: 02A040 TSG-0-1: 02/06C109P1 -> MBUL-0-1: 02B055 TSG-0-1: 02/06C229P1 -> MBUS-0-0: 02A049 TSG-0-2: 02/06C109P1 -> MBUL-0-2: 08A055 TSG-0-2: 02/06C229P1 -> MBUS-0-1: 08A040 TSG-0-3: 02/06C109P1 -> MBUL-0-3: 08B055 TSG-0-3: 02/06C229P1 -> MBUL-0-1: 08A049 TSG-0-4: 02/06C109P1 -> MBUL-0-4: 02A055 TSG-0-4: 02/06C229P1 -> MBUS-0-2: 02A040 TSG-0-5: 02/06C109P1 -> MBUL-0-5: 02B055 TSG-0-5: 02/06C229P1 -> MBUS-0-2: 02A049 TSG-0-6: 02/06C109P1 -> MBUL-0-6: 08A055 TSG-0-6: 02/06C229P1 -> MBUS-0-3: 08A040 TSG-0-7: 02/06C109P1 -> MBUL-0-7: 08B055 TSG-0-7: 02/06C229P1 -> MBUS-0-3: 08A049 SN-1 TSG-1-0: 03/07C109P1 -> MBUL-1-0: 03A055 TSG-1-0: 03/07C229P1 -> MBUS-1-0: 03A040 TSG-1-1: 03/07C109P1 -> MBUL-1-1: 03B055 TSG-1-1: 03/07C229P1 -> MBUS-1-0: 03A049 TSG-1-2: 03/07C109P1 -> MBUL-1-2: 09A055 TSG-1-2: 03/07C229P1 -> MBUS-1-1: 09A040 TSG-1-3: 03/07C109P1 -> MBUL-1-3: 09B055 TSG-1-3: 03/07C229P1 -> MBUS-1-1: 09A049 TSG-1-4: 03/07C109P1 -> MBUL-1-4: 03A055 TSG-1-4: 03/07C229P1 -> MBUS-1-2: 03A040 TSG-1-5: 03/07C109P1 -> MBUL-1-5: 03B055 TSG-1-5: 03/07C229P1 -> MBUS-1-2: 03A049 TSG-1-6: 03/07C109P1 -> MBUL-1-6: 09A055 TSG-1-6: 03/07C229P1 -> MBUS-1-3: 09A040 TSG-1-7: 03/07C109P1 -> MBUL-1-7: 09B055 TSG-1-7: 03/07C229P1 -> MBUS-1-3: 09A049

F:TSG(B): MUT02 or 03 -> cabling from above, MUT 06 or 07 -> cabling from below. For MBUL, MBUS in R:SN/MB/LTGM: MBUL-0-x and MBUS-0-x are located in MUT04, MBUL-1-x and MBUS-1-x are located in MUT05

Tab. 3.298 Cabling F:TSG(B) -> F:MB/CCG(B) Cabling F:TSG(B) -> LTG: All LTGxx are connected with SN-0 (MUT02 or MUT06) and SN-1 (MUT03 or MUT07). (see Tab. 3.296) Internal cabling TSG(B) <--> SSG(B): (see Tab. 3.301)

486

A30828-X1160-M-2-7620

Maintenance Node

3.9.6

3.9.6.2

3.9.6.1

A30828-X1160-M-2-7620 D C
P3 P4 P2 P1 P2 P1 P3 P5

F:SSG(B)

F:SSG(B) (backplane)

F:SSG(B) (module side)

P4

C101 DCCMS

TSG

TSG

TSG TSG

C125 SSM8B 0

TSG TSG TSG TSG TSG TSG MB TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG MB TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG TSG

TSG

right SSG SSG-0-1, SSG-1-1 SSG-0-3, SSG-1-3 C135 C143 C151 SSM8B 1 SSM16B 0 SSM8B 2 SSM8B 3 SSGCB SSM8B 4 SSM8B 5 SSM16B 1 SSM8B 6 SSM8B 7 SSM8B 0 SSM8B 1 SSM16B 0 SSM8B 2 C271 C279 C287 C299 C307 C315 C323 C331 SSM8B 3 SSGCB SSM8B 4 SSM8B 5 SSM16B 1 SSM8B 6 SSM8B 7 DCCMS C163 C171 C179 C191 C199 C207 C219 C231 C243 C251 C259

left SSG SSG-0-0, SSG-1-0 SSG-0-2, SSG-1-2

left SSG SSG-0-0, SSG-1-0 SSG-0-2, SSG-1-2

right SSG SSG-0-1, SSG-1-1 SSG-0-3, SSG-1-3

Construction

487

Construction

Maintenance Node

3.9.6.3

F:SSG(B) (cabling)
Cabling F:SSG(B) -> F:MBD
SN-0 SSG-0-0: 02/06C171P1 -> F:MBD0: C109P4 SSG-0-1: 02/06C279P1 -> F:MBD0: C109P5 SSG-0-2: 02/06C171P1 -> F:MBD0: C215P4 SSG-0-3: 02/06C279P1 -> F:MBD0: C215P5 SN-1 SSG-1-0: 03/07C171P1 -> F:MBD1: C109P4 SSG-1-1: 03/07C279P1 -> F:MBD1: C109P5 SSG-1-2: 03/07C171P1 -> F:MBD1: C215P4 SSG-1-3: 03/07C279P1 -> F:MBD1: C215P5

F:SSG(B): MUT02 or 03: cabling from above, MUT 06 or 07 cabling from below.

Tab. 3.299 Cabling F:SSG(B) -> F:MBD Cabling F:SSG(B) -> F:MB/CCG(B):
SN-0 SSG-0-0: 02/06C171P1 -> MBUS-0-0: 02B049 SSG-0-1: 02/06C279P1 -> MBUS-0-1: 08B049 SSG-0-2: 02/06C171P1 -> MBUS-0-2: 02B049 SSG-0-3: 02/06C279P1 -> MBUL-0-3: 08B049 SN-1 SSG-1-0: 03/07C171P1 -> MBUS-1-0: 03B049 SSG-1-1: 03/07C279P1 -> MBUS-1-1: 09B049 SSG-1-2: 03/07C171P1 -> MBUS-1-2: 03B049 SSG-1-3: 03/07C279P1 -> MBUS-1-3: 09B049

F:SSG(B): MUT02 or 03: cabling from above, MUT 06 or 07 cabling from below. For MBUL, MBUS in R:SN/MB/LTGM: MBUL-0-x and MBUS-0-x are located in MUT04, MBUL-1-x and MBUS-1-x are located in MUT05

Tab. 3.300 Cabling F:SSG(B) -> F:MB/CCG(B) Internal cabling SN(B)(504LTG) TSG(B)x --> SSG(B): Cabling from above: F:SSG(B), F:TSG(B) are located in MUT02 and MUT03. Cabling from below: F:SSG(B), F:TSG(B) are located in MUT06 and MUT07. Table interpretation for cabling from below: MUT02 -> MUT06, MUT03 -> MUT07
TSG(B)x TSG(B)0 -> SSG(B) P1 P3 P1 P3 P1 P3 P1 P3 02 02 02 02 02 02 02 02 C125 C125 C231 C231 C125 C125 C231 C231 P3 P1 P3 P1 P3 P1 P3 P1 S S G 0 0 1 1 2 2 3 3 02 02 02 02 02 02 02 02 TSG(B)1 -> SSG(B) C135 C135 C243 C243 C135 C135 C243 C243 P3 P1 P3 P1 P3 P1 P3 P1 S S G 0 0 1 1 2 2 3 3 02 02 02 02 02 02 02 02 TSG(B) -> SSG(B) C151 C151 C259 C259 C151 C151 C259 C259 P3 P1 P3 P1 P3 P1 P3 P1 S S G 0 0 1 1 2 2 3 3 02 02 02 02 02 02 02 02 TSG(B)3 -> SSG(B) C163 C163 C271 C271 C163 C163 C271 C271 P3 P1 P3 P1 P3 P1 P3 P1 S S G 0 0 1 1 2 2 3 3

02 02 02 02 02 02 02 02

C187 C187 C203 C203 C241 C241 C253 C253

Tab. 3.301 Internal cabling SN(B)(504LTG) TSG(B)0 - TSG(B)3

488

A30828-X1160-M-2-7620

Maintenance Node

Construction

TSG(B)x

TSG(B)0 -> SSG(B) P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 03 03 03 03 03 03 03 03 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 C125 C125 C231 C231 C125 C125 C231 C231 D125 D125 D231 D231 D125 D125 D231 D231 D125 D125 D231 D231 D125 D125 D231 D231 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1

S S G 0 0 1 1 2 2 3 3 0 0 1 1 2 2 3 3 0 0 1 1 2 2 3 3 03 03 03 03 03 03 03 03 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03

TSG(B)1 -> SSG(B) C135 C135 C243 C243 C135 C135 C243 C243 D135 D135 D243 D243 D135 D135 D243 D243 D135 D135 D243 D243 D135 D135 D243 D243 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1

S S G 0 0 1 1 2 2 3 3 0 0 1 1 2 2 3 3 0 0 1 1 2 2 3 3 03 03 03 03 03 03 03 03 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03

TSG(B) -> SSG(B) C151 C151 C259 C259 C151 C151 C259 C259 D151 D151 D259 D259 D151 D151 D259 D259 D151 D151 D259 D259 D151 D151 D259 D259 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1

S S G 0 0 1 1 2 2 3 3 0 0 1 1 2 2 3 3 0 0 1 1 2 2 3 3 03 03 03 03 03 03 03 03 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03

TSG(B)3 -> SSG(B) C163 C163 C271 C271 C163 C163 C271 C271 D163 D163 D271 D271 D163 D163 D271 D271 D163 D163 D271 D271 D163 D163 D271 D271 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1

S S G 0 0 1 1 2 2 3 3 0 0 1 1 2 2 3 3 0 0 1 1 2 2 3 3

02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03

D187 D187 D203 D203 D241 D241 D253 D253 C187 C187 C203 C203 C241 C241 C253 C253 D187 D187 D203 D203 D241 D241 D253 D253

Tab. 3.301 Internal cabling SN(B)(504LTG) TSG(B)0 - TSG(B)3

TSG(B)x

TSG(B)4 -> SSG(B) P1 P3 P1 P3 P1 P3 P1 02 02 02 02 02 02 02 C179 C179 C287 C287 C179 C179 C287 P3 P1 P3 P1 P3 P1 P3

S S G 0 0 1 1 2 2 3 02 02 02 02 02 02 02

TSG(B)5 -> SSG(B) C191 C191 C299 C299 C191 C191 C299 P3 P1 P3 P1 P3 P1 P3

S S G 0 02 0 02 1 02 1 02 2 02 2 02 3 02

TSG(B)6 -> SSG(B) C207 C207 C315 C315 C207 C207 C315 P3 P1 P3 P1 P3 P1 P3

S S G 0 02 0 02 1 02 1 02 2 02 2 02 3 02

TSG(B)7 -> SSG(B) C219 C219 C323 C323 C219 C219 C323 P3 P1 P3 P1 P3 P1 P3

S S G 0 0 1 1 2 2 3

02 02 02 02 02 02 02

C187 C187 C203 C203 C241 C241 C253

Tab. 3.302 Internal cabling SN(B)(504LTG) TSG(B)4 - TSG(B)7

A30828-X1160-M-2-7620

489

Construction

Maintenance Node

TSG(B)x

TSG(B)4 -> SSG(B) P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 02 03 03 03 03 03 03 03 03 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 C287 C179 C179 C287 C287 C179 C179 C287 C287 D179 D179 D287 D287 D179 D179 D287 D287 D179 D179 D287 D287 D179 D179 D287 D287 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1

S S G 3 0 0 1 1 2 2 3 3 0 0 1 1 2 2 3 3 0 0 1 1 2 2 3 3 02 03 03 03 03 03 03 03 03 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03

TSG(B)5 -> SSG(B) C299 C191 C191 C299 C299 C191 C191 C299 C299 D191 D191 D299 D299 D191 D191 D299 D299 D191 D191 D299 D299 D191 D191 D299 D299 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1

S S G 3 02 0 03 0 03 1 03 1 03 2 03 2 03 3 03 3 03 0 02 0 02 1 02 1 02 2 02 2 02 3 02 3 02 0 03 0 03 1 03 1 03 2 03 2 03 3 03 3 03

TSG(B)6 -> SSG(B) C315 C207 C207 C315 C315 C207 C207 C315 C315 D207 D207 D315 D315 D207 D207 D315 D315 D207 D207 D315 D315 D207 D207 D315 D315 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1

S S G 3 02 0 03 0 03 1 03 1 03 2 03 2 03 3 03 3 03 0 02 0 02 1 02 1 02 2 02 2 02 3 02 3 03 0 03 0 03 1 03 1 03 2 03 2 03 3 03 3 03

TSG(B)7 -> SSG(B) C323 C219 C219 C323 C323 C219 C219 C323 C323 D219 D219 D323 D323 D219 D219 D323 D323 D219 D219 D323 D323 D219 D219 D323 D323 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1

S S G 3 0 0 1 1 2 2 3 3 0 0 1 1 2 2 3 3 0 0 1 1 2 2 3 3

02 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03

C253 D187 D187 D203 D203 D241 D241 D253 D253 C187 C187 C203 C203 C241 C241 C253 C253 D187 D187 D203 D203 D241 D241 D253 D253

Tab. 3.302 Internal cabling SN(B)(504LTG) TSG(B)4 - TSG(B)7 Internal cabling SN(B)(252LTG) TSG(B)x --> SSG(B): Cabling from above: F:SSG(B), F:TSG(B) are located in MUT02 and MUT03. Cabling from below: F:SSG(B), F:TSG(B) are located in MUT06 and MUT07. Table interpretation for cabling from below: MUT02 -> MUT06, MUT03 -> MUT07

490

A30828-X1160-M-2-7620

Maintenance Node

Construction

TSG(B)x

TSG(B)0 -> SSG(B) P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 C125 C125 C231 C231 C179 C179 C287 C287 C125 C125 C231 C231 C179 C179 C287 C287 D125 D125 D231 D231 D179 D179 D287 D287 D125 D125 D231 D231 D179 D179 D287 D287 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1

S S G 0 02 0 02 1 02 1 02 0 02 0 02 1 02 1 02 0 03 0 03 1 03 1 03 0 03 0 03 1 03 1 03 0 02 0 02 1 02 1 02 0 02 0 02 1 02 1 02 0 03 0 03 1 03 1 03 0 03 0 03 1 03 1 03

TSG(B)1 -> SSG(B) C135 C135 C243 C243 C191 C191 C299 C299 C135 C135 C243 C243 C191 C191 C299 C299 D135 D135 D243 D243 D191 D191 D299 D299 D135 D135 D243 D243 D191 D191 D299 D299 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1

S S G 0 02 0 02 1 02 1 02 0 02 0 02 1 02 1 02 0 03 0 03 1 03 1 03 0 03 0 03 1 03 1 03 0 02 0 02 1 02 1 02 0 02 0 02 1 02 1 02 0 03 0 03 1 03 1 03 0 03 0 03 1 03 1 03

TSG(B)2 -> SSG(B) C151 C151 C259 C259 C207 C207 C315 C315 C151 C151 C259 C259 C207 C207 C315 C315 D151 D151 D259 D259 D207 D207 D315 D315 D151 D151 D259 D259 D207 D207 D315 D315 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1

S S G 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03

TSG(B)3 -> SSG(B) C163 C163 C271 C271 C219 C219 C323 C323 C163 C163 C271 C271 C219 C219 C323 C323 D163 D163 D271 D271 D219 D219 D323 D323 D163 D163 D271 D271 D219 D219 D323 D323 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1

S S G 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1

02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03

C187 C187 C203 C203 C241 C241 C253 C253 D187 D187 D203 D203 D241 D241 D253 D253 C187 C187 C203 C203 C241 C241 C253 C253 D187 D187 D203 D203 D241 D241 D253 D253

Tab. 3.303 Internal cabling SN(B)(252LTG)

A30828-X1160-M-2-7620

491

Construction

Maintenance Node

Internal cabling SN(B)(126LTG) TSG(B)x --> SSG(B): Cabling from above: F:SSG(B), F:TSG(B) are located in MUT02 and MUT03. Cabling from below: F:SSG(B), F:TSG(B) are located in MUT06 and MUT07. Table interpretation for cabling from below: MUT02 -> MUT06, MUT03 -> MUT07
TSG(B)x 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 C187 C187 C203 C203 C241 C241 C253 C253 D187 D187 D203 D203 D241 D241 D253 D253 C187 C187 C203 C203 C241 C241 C253 C253 D187 D187 D203 D203 D241 D241 D253 D253 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 TSG(B)0 -> SSG(B) C125 C125 C151 C151 C179 C179 C207 C207 C125 C125 C151 C151 C179 C179 C207 C207 D125 D125 D151 D151 D179 D179 D207 D207 D125 D125 D151 D151 D179 D179 D207 D207 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SSG TSG(B)1 -> SSG(B) 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 02 02 02 02 02 02 02 02 03 03 03 03 03 03 03 03 C135 C135 C163 C163 C191 C191 C219 C219 C135 C135 C163 C163 C191 C191 C219 C219 D135 D135 D163 D163 D191 D191 D219 D219 D135 D135 D163 D163 D191 D191 D219 D219 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 P3 P1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SSG

Tab. 3.304 Internal cabling SN(B)(126LTG)

492

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.9.7 3.9.7.1

F:SNMAT F:SNMAT (module side)

D
MATM 0 MATM 1 MATM 2 MATM 5 MATM 3 MATM 4 MATM 6 MATM 7
O M L 10 O M L 01

C113

C147

C181

C215

C239

MATC

C267

C301

C335

Modules with displays and switches in F:SNMAT MATC (-Q73-) MATM (-Q72-)

Tab. 3.305 Modules with displays and switches in F:SNMAT

3.9.7.2

F:SNMAT (backplane)
C1 C2 C3 C4 C5 D1 D2 D3 D4 D5 O M L 73 O M L 72 O M L 63 O M L 62 O M L 53 O M L 52 O M L 43 O M M L B 42 O M L 33 O M L 32 O M L 23 O M L 22 O M L 13 O M L 12 O M L 03 O M L 02 O M L 71 O M L 70 O M L 61 O M L 60 O M L 51 O M L 50 O M L 41 O M L 40 P W R A O M L 31 O M L 30 O M L 21 O M L 20 O M L 11 O M L 00

P W R B

325

381

313

291

257

227

205

279

159

C369 137 125 103

359

347

239 235

193

171

A30828-X1160-M-2-7620

493

Construction

Maintenance Node

3.9.7.3

F:SNMAT (cabling)
Cabling voltage supply
F:SNMAT --> Breaker Panel Connector PRWA 05C235P1 06C235P1 PRWB 05D235P4 06D235P4 MOLOC Connection 48/60V for M:MATM 0...3 48/60V for M:MATM 0...3 48/60V for M:MATM 4...7 48/60V for M:MATM 4...7 FU 01 FU 31 FU 02 FU 32 Fuse

Tab. 3.306 Cabling voltage supply Cabling F:SNMAT -> F:MBD


SN-0 Connector MBC from -> to Connector MBC SN-1 from -> to

F:SNMAT0 D235P3 -> F:MBD0 D229P1

F:SNMAT1 D235P3 -> F:MBD1 D229P1

Tab. 3.307 Cabling F:SNMAT -> F:MBD Cabling F:SNMAT -> F:SNMUX(A)
SN-0 Connector OML00 OML01 OML02 OML03 OML10 OML11 OML12 OML13 OML20 OML21 OML22 OML23 OML30 OML31 OML32 F:SNMAT --> F:SNMUX(A) Connector OML00 OML01 OML02 OML03 OML10 OML11 OML12 OML13 OML20 OML21 OML22 OML23 OML30 OML31 OML32 SN-1 F:SNMAT --> F:SNMUX(A)

05C103P1 --> SNMUX0 02/06C213P2 05C125P1 --> SNMUX0 02/06C237P2 05D103P1 --> SNMUX1 02/06C213P2 05D125P1 --> SNMUX1 02/06C237P2 05C137P1 --> SNMUX2 02/06C213P2 05C159P1 --> SNMUX2 02/06C237P2 05D137P1 --> SNMUX3 02/06C213P2 05D159P1 --> SNMUX3 02/06C237P2 05C171P1 --> SNMUX4 02/06C213P2 05C193P1 --> SNMUX4 02/06C237P2 05D171P1 --> SNMUX5 02/06C213P2 05D193P1 --> SNMUX5 02/06C237P2 05C205P1 --> SNMUX6 02/06C213P2 05C227P1 --> SNMUX6 02/06C237P2 05D205P1 --> SNMUX7 02/06C213P2

07C103P1 --> SNMUX0 03/07C213P2 07C125P1 --> SNMUX0 03/07C237P2 07D103P1 --> SNMUX1 03/07C213P2 07D125P1 --> SNMUX1 03/07C237P2 07C137P1 --> SNMUX2 03/07C213P2 07C159P1 --> SNMUX2 03/07C237P2 07D137P1 --> SNMUX3 03/07C213P2 07D159P1 --> SNMUX3 03/07C237P2 07C171P1 --> SNMUX4 03/07C213P2 07C193P1 --> SNMUX4 03/07C237P2 07D171P1 --> SNMUX5 03/07C213P2 07D193P1 --> SNMUX5 03/07C237P2 07C205P1 --> SNMUX6 03/07C213P2 07C227P1 --> SNMUX6 03/07C237P2 07D205P1 --> SNMUX7 03/07C213P2

Tab. 3.308 Cabling F:SNMAT -> F:SNMUX(A)

494

A30828-X1160-M-2-7620

Maintenance Node

Construction

SN-0 Connector OML33 OML40 OML41 OML42 OML43 OML50 OML51 OML52 OML53 OML60 OML61 OML62 OML63 OML70 OML71 OML72 OML73 F:SNMAT --> F:SNMUX(A) Connector OML33 OML40 OML41 OML42 OML43 OML50 OML51 OML52 OML53 OML60 OML61 OML62 OML63 OML70 OML71 OML72 OML73

SN-1 F:SNMAT --> F:SNMUX(A)

05D207P1 --> SNMUX7 02/06C237P2 05C257P1 --> SNMUX8 02/06C213P2 05C279P1 --> SNMUX8 02/06C237P2 05D257P1 --> SNMUX9 02/06C213P2 05D279P1 --> SNMUX9 02/06C237P2 05C291P1 --> SNMUX10 02/06C213P2 05C313P1 --> SNMUX10 02/06C237P2 05D291P1 --> SNMUX11 02/06C213P2 05D313P1 --> SNMUX11 02/06C237P2 05C325P1 --> SNMUX12 02/06C213P2 05C347P1 --> SNMUX12 02/06C237P2 05D325P1 --> SNMUX13 02/06C213P2 05D347P1 --> SNMUX13 02/06C237P2 05C359P1 --> SNMUX14 02/06C213P2 05C381P1 --> SNMUX14 02/06C237P2 05D359P1 --> SNMUX15 02/06C213P2 05D381P1 --> SNMUX15 02/06C237P2

07D227P1 --> SNMUX7 03/07C237P2 07C257P1 --> SNMUX8 03/07C213P2 07C279P1 --> SNMUX8 03/07C237P2 07D257P1 --> SNMUX9 03/07C213P2 07D279P1 --> SNMUX9 03/07C237P2 07C291P1 --> SNMUX10 03/07C213P2 07C313P1 --> SNMUX10 03/07C237P2 07D291P1 --> SNMUX11 03/07C213P2 07D313P1 --> SNMUX11 03/07C237P2 07C325P1 --> SNMUX12 03/07C213P2 07C347P1 --> SNMUX12 03/07C237P2 07D325P1 --> SNMUX13 03/07C213P2 07D347P1 --> SNMUX13 03/07C237P2 07C359P1 --> SNMUX14 03/07C213P2 07C381P1 --> SNMUX14 03/07C237P2 07D359P1 --> SNMUX15 03/07C213P2 07D381P1 --> SNMUX15 03/07C237P2

Tab. 3.308 Cabling F:SNMAT -> F:SNMUX(A) Cabling F:SNMAT -> F:SNMUX(B)
SN-0 Connector OML00 OML01 OML02 OML03 OML10 OML11 OML12 OML13 OML20 OML21 OML22 OML23 F:SNMAT --> F:SNMUX(B) Connector OML00 OML01 OML02 OML03 OML10 OML11 OML12 OML13 OML20 OML21 OML22 OML23 SN-1 F:SNMAT --> F:SNMUX(B)

MATM0 05C103P1 --> SNMUX0 C103P1 MATM0 05C125P1 --> SNMUX0 C103P5 MATM0 05D103P1 --> SNMUX1 C205P1 MATM0 05D125P1 --> SNMUX1 C205P5 MATM1 05C137P1 --> SNMUX2 C103P1 MATM1 05C159P1 --> SNMUX2 C103P5 MATM1 05D137P1 --> SNMUX3 C205P1 MATM1 05D159P1 --> SNMUX3 C205P5 MATM2 05C171P1 --> SNMUX4 C103P1 MATM2 05C193P1 --> SNMUX4 C103P5 MATM2 05D171P1 --> SNMUX5 C205P1 MATM2 05D193P1 --> SNMUX5 C205P5

MATM0 07C103P1 --> SNMUX0 C235P1 MATM0 07C125P1 --> SNMUX0 C235P5 MATM0 07D103P1 --> SNMUX1 C337P1 MATM0 07D125P1 --> SNMUX1 C337P5 MATM1 07C137P1 --> SNMUX2 C235P1 MATM1 07C159P1 --> SNMUX2 C235P5 MATM1 07D137P1 --> SNMUX3 C337P1 MATM1 07D159P1 --> SNMUX3 C337P5 MATM2 07C171P1 --> SNMUX4 C235P1 MATM2 07C193P1 --> SNMUX4 C235P5 MATM2 07D171P1 --> SNMUX5 C337P1 MATM2 07D193P1 --> SNMUX5 C337P5

Tab. 3.309 Cabling F:SNMAT -> F:SNMUX(B)

A30828-X1160-M-2-7620

495

Construction

Maintenance Node

SN-0 Connector OML30 OML31 OML32 OML33 OML40 OML41 OML42 OML43 OML50 OML51 OML52 OML53 OML60 OML61 OML62 OML63 OML70 OML71 OML72 OML73 F:SNMAT --> F:SNMUX(B) Connector OML30 OML31 OML32 OML33 OML40 OML41 OML42 OML43 OML50 OML51 OML52 OML53 OML60 OML61 OML62 OML63 OML70 OML71 OML72 OML73

SN-1 F:SNMAT --> F:SNMUX(B)

MATM3 05C205P1 --> SNMUX6 C103P1 MATM3 05C227P1 --> SNMUX6 C103P5 MATM3 05D205P1 --> SNMUX7 C205P1 MATM3 05D207P1 --> SNMUX7 C205P5 MATM4 05C257P1 --> SNMUX8 C103P1 MATM4 05C279P1 --> SNMUX8 C103P5 MATM4 05D257P1 --> SNMUX9 C205P1 MATM4 05D279P1 --> SNMUX9 C205P5 MATM5 05C291P1 --> SNMUX10 C103P1 MATM5 05C313P1 --> SNMUX10 C103P5 MATM5 05D291P1 --> SNMUX11 C205P1 MATM5 05D313P1 --> SNMUX11 C205P5 MATM6 05C325P1 --> SNMUX12 C103P1 MATM6 05C347P1 --> SNMUX12 C103P5 MATM6 05D325P1 --> SNMUX13 C205P1 MATM6 05D347P1 --> SNMUX13 C205P5 MATM7 05C359P1 --> SNMUX14 C103P1 MATM7 05C381P1 --> SNMUX14 C103P5 MATM7 05D359P1 --> SNMUX15 C205P1 MATM7 05D381P1 --> SNMUX15 C205P5

MATM3 07C205P1 --> SNMUX6 C235P1 MATM3 07C227P1 --> SNMUX6 C235P5 MATM3 07D205P1 --> SNMUX7 C337P1 MATM3 07D227P1 --> SNMUX7 C337P5 MATM4 07C257P1 --> SNMUX8 C235P1 MATM4 07C279P1 --> SNMUX8 C235P5 MATM4 07D257P1 --> SNMUX9 C337P1 MATM4 07D279P1 --> SNMUX9 C337P5 MATM5 07C291P1 --> SNMUX10 C235P1 MATM5 07C313P1 --> SNMUX10 C235P5 MATM5 07D291P1 --> SNMUX11 C337P1 MATM5 07D313P1 --> SNMUX11 C337P5 MATM6 07C325P1 --> SNMUX12 C235P1 MATM6 07C347P1 --> SNMUX12 C235P5 MATM6 07D325P1 --> SNMUX13 C337P1 MATM6 07D347P1 --> SNMUX13 C337P5 MATM7 07C359P1 --> SNMUX14 C235P1 MATM7 07C381P1 --> SNMUX14 C235P5 MATM7 07D359P1 --> SNMUX15 C337P1 MATM7 07D381P1 --> SNMUX15 C337P5

Tab. 3.309 Cabling F:SNMAT -> F:SNMUX(B)

496

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.9.8 3.9.8.1

F:SNMUX(A) F:SNMUX(A) (module side)

D
LILD 0 LILD 4 LILD 1 LILD 2 LILD 5 LILD 6 LILD 7 LILD 3
LILD-0 8 72 - 75 17 18 27 28 92 - 95 84 - 87 29 30 31 22 23 20 76 - 79 68 - 71 21 19

C119

C143

C167

C191

C225

MUXC

C253

C277

C301

Modules with displays and switches in F:SNMUX(A) LILD (-Q70-) MUXC (-Q71-)

Tab. 3.310 Modules with displays and switches in F:SNMUX(A)

3.9.8.2

F:SNMUX(A) (backplane)
F:SNMUX(A) (backplane) with SU1 and SU4 cable connector (with 4 cable)
LILD-3 C1 C2 C3 C4 C5 D1 D2 D3 D4 62 63 60 61 54 55 58 59 52 124 - 127 116 - 119 53 56 57 50 51 44 45 46 47 38 39 48 120 - 123 112 - 115 49 LILD-7 LILD-2 40 41 42 43 36 108 - 111 100 - 103 37 34 35 32 104 - 107 96 - 99 33 O M L 1 O M L 0 LILD-6 A 88 - 91 80 - 83 B C D E LILD-5 LILD-1 24 25 26 16 LILD-4

65 66 10 67
12

C325
9 2 11 4 13 14 15 6 7 5 3 1

173 167 161 155

199

191 185

331 325 319 313

301 295

283 277 271 265

253 247

237

213

143 137

A30828-X1160-M-2-7620

125 119 113 107

497

498
D4 D3 D2 D1 C5 C4 C3 C2 C1 D4 62 60 58 59 57 61 63 LILD-3 D3 D2 D1 C5 C4 C3 C2 C1 56 LILD-3

Construction

325 319
60 - 63 52 - 55 52 54 51 55 53 56 - 59 48 - 51

48

50

331 325 319 313 301


46

LILD-7

301 295
124 - 127 116 - 119 LILD-7 120 - 123 112 - 115 45 47 40 - 43 32 - 35 39 44 - 47 36 - 39

116 - 119 / 124 - 127 112 - 115 / 120 - 123 44 43 42 41 40

49

LILD-2

LILD-2

277 271
LILD-6

36

34

38

32

283 277 271 265 253 237

33

LILD-6

253 247
108 - 111 100 - 103 104 - 107 96 - 99 O M L 1

100 - 103 / 108 - 111 96 - 99 / 104 - 107

37

35

237

O M L 1

213
O M L 0 E D C B A

213
E D

O M L 0 C B A

199 191 185


92 - 95 84 - 87 28 - 31 20 - 23 76 - 79 24 - 27 16 - 19 88 - 91 80 - 83

199
LILD-5

LILD-5

191

84 - 87 / 92 - 95 30 29 31 28

80 - 83 / 88 - 91 26 27 25 24

F:SNMUX(A) (backplane) with SU1 and SU4 cable connector (with 8 cable)

LILD-1

F:SNMUX(A) (backplane) with 4SU cable connector (with 4 cable)

LILD-1

167 161 143 137


68 - 71 12 - 15

20

18

22

16

173 167 161 155


72 - 75

17

21

19

23

LILD-4

141
67 3 66 2 65
8 - 11

LILD-4

68 - 71 / 76 - 79 14 13 15 12

65 -67 / 72 - 75 8 10 9 11

LILD-0

LILD-0

119 113

4-7

A30828-X1160-M-2-7620

Maintenance Node

125 119 113 107

Maintenance Node

Construction

3.9.8.3

F:SNMUX(A) (cabling)
Cabling F:SNMUX(A) --> F:SNMUX(A)
SN-0 Connector OML0 OML1 SNMUX1 -> SNMUX2 02/06C213P2 -> 02/06C213P2 02/06C237P2 -> 02/06C237P2 Connector OML0 OML1 SN-1 SNMUX1 -> SNMUX2 03/07C213P2 -> 03/07C213P2 03/07C237P2 -> 03/07C237P2

Tab. 3.311 Cabling F:SNMUX(A) -> F:SNMUX(A) Cabling F:SNMUX(A) --> F:SNMAT Cabling: (see Tab. 3.309) Cabling F:SNMUX(A) with SU1 and SU4 cable connector (with 4 cable) 1. Cabling F:SNMUX(A) --> LTG with 1SU cable connector Valid for LTGSET 00, 02, 04, 06, 08, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30. All LTGxx are connected with SN0 (MUT02 or MUT06) and SN1 (MUT03 or MUT07).
LTG 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 Connector 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 MOLOC C107P2 C113P3 C107P4 C113P5 D107P1 D113P2 D107P3 C125P1 C119P2 C125P3 C119P4 C125P5 D119P1 D125P2 D119P3 C161P1 C155P2 C161P3 C155P4 C161P5 D155P1 LTG 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 Connector 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 MOLOC D161P2 D155P3 C173P1 C167P2 C173P3 C167P4 C173P5 D167P1 D173P2 D167P3 C271P1 C265P2 C271P3 C265P4 C271P5 D265P1 D271P2 D265P3 C283P1 C277P2 C283P3 LTG 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 Connector 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 MOLOC C277P4 C283P5 D277P1 D283P2 D277P3 C319P1 C313P2 C319P3 C313P4 C319P5 D313P1 D319P2 D313P3 C331P1 C325P2 C331P3 C325P4 C331P5 D325P1 D331P2 D325P3

Tab. 3.312 F:SNMUX(A) --> LTG with 1SU cable connector

A30828-X1160-M-2-7620

499

Construction

Maintenance Node

2. Cabling F:SNMUX(A) --> LTG with 4SU cable connector with 4er cable Valid for LTGSET 01, 03, 05, 07, 09, 11, 13, 15, 17, 19, 21, 23, 25, 27, 29, 31. Cabling LTG 01, 02 and 03 with SU1 cable connector. All LTGxx are connected with SN0 (MUT02 or MUT06) and SN1 (MUT03 or MUT07).
LTG 01 02 03 04, 05,06, 07 08, 09, 10, 11 12, 13, 14, 15 16, 17, 18, 19 20, 21, 22, 23 24, 25, 26, 27 28, 29, 30, 31 32, 33, 34, 35 36, 37, 38 39 40, 41, 42, 43 44, 45, 46, 47 48, 49, 50, 51 52, 53, 54, 55 56, 57, 58, 59 60, 61, 62, 63 65 66 67 68-69-70-71 72-73-74-75 76-77-78-79 80-81-82-83 84-85-86-87 88-89-90-91 92-93-94-95 96-97-98-99 100-101-102-103 104-105-106-107 108-109-110-111 112-113-114-115 116-117-118-119 120-121-122-123 124-125-126-127 Connector C137P2 C137P3 C137P4 C137P5 C143P1 C143P5 C185P1 C185P5 C191P1 C191P5 C247P1 C247P5 C253P1 C253P5 C295P1 C295P5 C301P1 C301P1 MOLOC

Tab. 3.313 F:SNMUX(A) --> LTG with 4SU cable connector with 4 cable Cabling F:SNMUX(A) with SU1 and SU4 cable connector with 8 cable connector 1. Cabling F:SNMUX(A) --> LTG with 1SU cable connector Valid for LTGSET 00, 02, 04, 06, 08, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30. All LTGxx are connected with SN0 (MUT02 or MUT06) and SN1 (MUT03 or MUT07).
LTG 01 02 03 04 05 06 07 08 Connector 1 2 3 4 5 6 7 8 MOLOC C107P2 C113P3 C107P4 C113P5 D107P1 D113P2 D107P3 C125P1 LTG 22 23 24 25 26 27 28 29 Connector 22 23 24 25 26 27 28 29 MOLOC D161P2 D155P3 C173P1 C167P2 C173P3 C167P4 C173P5 D167P1 LTG 43 44 45 46 47 48 49 50 Connector 43 44 45 46 47 48 49 50 MOLOC C277P4 C283P5 D277P1 D283P2 D277P3 C319P1 C313P2 C319P3

Tab. 3.314 F:SNMUX(A) --> LTG with 1SU cable connector

500

A30828-X1160-M-2-7620

Maintenance Node

Construction

LTG 09 10 11 12 13 14 15 16 17 18 19 20 21

Connector 9 10 11 12 13 14 15 16 17 18 19 20 21

MOLOC C119P2 C125P3 C119P4 C125P5 D119P1 D125P2 D119P3 C161P1 C155P2 C161P3 C155P4 C161P5 D155P1

LTG 30 31 32 33 34 35 36 37 38 39 40 41 42

Connector 30 31 32 33 34 35 36 37 38 39 40 41 42

MOLOC D173P2 D167P3 C271P1 C265P2 C271P3 C265P4 C271P5 D265P1 D271P2 D265P3 C283P1 C277P2 C283P3

LTG 51 52 53 54 55 56 57 58 59 60 61 62 63

Connector 51 52 53 54 55 56 57 58 59 60 61 62 63

MOLOC C313P4 C319P5 D313P1 D319P2 D313P3 C331P1 C325P2 C331P3 C325P4 C331P5 D325P1 D331P2 D325P3

Tab. 3.314 F:SNMUX(A) --> LTG with 1SU cable connector 2. Cabling F:SNMUX(A) <--> F:SNCARE with 4SU cable connector with 8 cable Valid for LTGSET 01, 03, 05, 07, 09, 11, 13, 15, 17, 19, 21, 23, 25, 27, 29, 31.
SN-0 Connector 64-72-65-73-66-7467-75 68-76-69-77-70-7871-79 80-88-81-89-82-9083-91 84-92-85-93-86, 9487-95 96-104-97-105-98106-99-107 100-108-101-109102-110-103-111 112-120-113-121114-122-115-123 116-124-117-125118-126-171-127 F:SNMUX(A) --> F:SNCARE 02C143P1 --> 02/06C119P1 Connector 64-72-65-73-6674-67-75 68-76-69-77-7078-71-79 80-88-81-89-8290-83-91 84-92-85-93-86, 94-87-95 96-104-97-105-98106-99-107 100-108-101-109102-110-103-111 112-120-113-121114-122-115-123 116-124-117-125118-126-171-127 SN-1 F:SNMUX(A) --> F:SNCARE 03C143P1 --> 03/07C119P1

02C143P5 --> 02/06C119P5

03C143P5 --> 03/07C119P5

02C191P1 --> 02/06C167P1

03D191P1 --> 03/07C167P1

02D191P5 --> 02/06C167P5

03D191P1 --> 03/07C167P5

02C253P1 --> 02/06C277P1

03C253P1 --> 03/07C277P1

02C253P5 --> 02/06C277P5

03C253P5 --> 03/07C277P5

02C301P1 --> 02/06C325P1

03C301P1 --> 03/07C325P1

02C301P5 --> 02/06C325P5

03C301P5 --> 03/07C325P5

Tab. 3.315 cabling F:SNMUX(A) -> F:SNCARE

A30828-X1160-M-2-7620

501

Construction

Maintenance Node

Cabling F:SNMUX(A) with 4SU cable connector with 4 cable Cabling LTG 01, 02 and 03 with SU1 cable connector. All LTGxx are connected with SN0 (MUT02 or MUT06) and SN1 (MUT03 or MUT07).
1. LTG SET in F:SNMUX(A) LTG 01 02 03 04, 05,06, 07 08, 09, 10, 11 12, 13, 14, 15 16, 17, 18, 19 20, 21, 22, 23 24, 25, 26, 27 28, 29, 30, 31 32, 33, 34, 35 36, 37, 38, 39 40, 41, 42, 43 44, 45, 46, 47 48, 49, 50, 51 52, 53, 54, 55 56, 57, 58, 59 60, 61, 62, 63 1 2 3 4-5-6-7 8-9-10-11 12-13-14-15 16-17-18-19 20-21-22-23 24-25-26-27 28-29-30-31 32-33-34-35 36-37-38-39 40-41-42-43 44-45-46-47 48-49-50-51 52-53-54-55 56-57-58-59 60-61-62-63 Connector MOLOC C113P2 C113P3 C113P4 C113P5 C119P1 C119P5 C161P1 C161P5 C167P1 C167P5 C271P1 C271P5 C277P1 C277P5 C319P1 C319P5 C325P1 C325P1 01 02 03 04, 05,06, 07 08, 09, 10, 11 12, 13, 14, 15 16, 17, 18, 19 20, 21, 22, 23 24, 25, 26, 27 28, 29, 30, 31 32, 33, 34, 35 36, 37, 38, 39 40, 41, 42, 43 44, 45, 46, 47 48, 49, 50, 51 52, 53, 54, 55 56, 57, 58, 59 60, 61, 62, 63 LTG 65 66 67 68-69-70-71 72-73-74-75 76-77-78-79 80-81-82-83 84-85-86-87 88-89-90-91 92-93-94-95 96-97-98-99 100-101-102-103 104-105-106-107 108-109-110-111 112-113-114-115 116-117-118-119 120-121-122-123 124-125-126-127 2. LTG SET in F:SNMUX(A) Connector MOLOC C137P2 C137P3 C137P4 C137P5 C143P1 C143P5 C185P1 C185P5 C191P1 C191P5 C247P1 C247P5 C253P1 C253P5 C295P1 C295P5 C301P1 C301P1

Tab. 3.316 F:SNMUX(A) -> LTG with 4SU cable connector with 4 cable

502

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.9.9 3.9.9.1

F:SNMUX(B) F:SNMUX(B) (module side)


SN 0 SN 1

D
MUXC 0 MUXC 1 MUXC 0 LILE 1 MUXC 1
O F C 0 O F C 1 O F C 2 O F C 3 L8 O F C 0 O F C 1 O F C 2 O F C 3 O O F F C C 4 4 O F C 5 O F C 5

LILE 0

LILE 1

C111 C117 #

C195 C191 #

C243 C249 #

LILE 0

# Mounting locations of modules MUCX 0 and MUCX 1 if no additional F:SNMUX and no F:SNMAT are used.

Modules with displays and switches in F:SNMUX(B) LILE (-Q263-) MUXC (-Q71-)

Tab. 3.317 Modules with displays and switches in F:SNMUX(B)

3.9.9.2

F:SNMUX(B) (backplane)
SN 1
P1 P2 LT 00 BT 00 LT 00 BT 01 BS 0 LT 10 BT 10 LT 11 BT 11 O M L 10 L143 L142 L141 L140 L139 L138 L137 L136 L135 L134 L133 L132 L131 L130 L129 LT 00 O M L 00 BT 00 LT 01 O M O F C 0 O F C 1 O F C 2 O F C 3 O F C 4 O O F F C C 4 0 O F C 1 O F C 2 O F C 3 L143 L142 L141 L140 L139 L138 L137 L136 L135 L134 L133 L132 L131 L130 L129 L8

SN 0
O M L 00

L10 L9 L2 L1

P3 P4 P5 P1 P2

L14 L13 L12 L11 L6 L5 L4 L3

O M L 11

L15 L7

P3 P4

BS 1

LT 11 BT 11

BS 1

269

185 179

169

157 147

137

L15 L7

O O F F C C 6 6 O O F F C C 7 7

O M L 01

LT 10 BT 10

O M L 11

O O F F C C 6 6 O F C 7 O F C 7

L14 L13 L12 L11 L6 L5 L4 L3

O O F F C C 5 5

L BT 10 01 BS 0

L10 L9 L2 L1

C327 C323 #
O M L 01

C137

C169

C269

C301

345

337

317 311 301

289 279

261 255

235

213

205

129 123

A30828-X1160-M-2-7620

503

103

Construction

Maintenance Node

3.9.9.3

F:SNMUX(B) (cabling)
Connector OML 00 MOLOC C103P1 Type Optolink Connection SNMUX (snmux=even) <--> SNMAT OML00 MATM or SNMUXB <--> SNMUXA OML 00 (DE6.0) SNMUX (snmux=even) <--> SNMAT OML01 MATM or SNMUXB <--> SNMUXA OML 01 (DE6.0) SNMUX (snmux=odd) <--> SNMAT OML02 MATM SNMUX (snmux=odd) <--> SNMAT OML03 MATM SNMUX (snmux=even) <--> SNOPT for LTG 1 - 15 (ltgset=0,4,8,12,16,20,24,28) SNMUX (snmux=even) <--> SNOPT for LTG 16 - 31 (ltgset=0,4,8,12,16,20,24,28) SNMUX (snmux=even) <--> SNOPT for LTG 32 - 47 (ltgset=0,4,8,12,16,20,24,28) SNMUX (snmux=even) <--> SNOPT for LTG 48 - 63 (ltgset=0,4,8,12,16,20,24,28) SNMUX (snmux=even) <--> SNOPT for LTG 1 - 15 (ltgset=1,5,9,13,17,21,25,29) SNMUX (snmux=even) <--> SNOPT for LTG 16 - 31 (ltgset=1,5,9,13,17,21,25,29) SNMUX (snmux=even) <--> SNOPT for LTG 32 - 47 (ltgset=1,5,9,13,17,21,25,29) SNMUX (snmux=even) <--> SNOPT for LTG 48 - 63 (ltgset=1,5,9,13,17,21,25,29) SNMUX (snmux=odd) <--> SNOPT for LTG 1 - 15 (ltgset=2,6,10,14,18,22,26,30) SNMUX (snmux=odd) <--> SNOPT for LTG 16 - 31 (ltgset=2,6,10,14,18,22,26,30) SNMUX (snmux=odd) <--> SNOPT for LTG 32 - 47 (ltgset=2,6,10,14,18,22,26,30) SNMUX (snmux=odd) <--> SNOPT for LTG 48 - 63 (ltgset=2,6,10,14,18,22,26,30) SNMUX (snmux=odd) <--> SNOPT for LTG 1 - 15 (ltgset=3,7,11,15,19,23,27,31) SNMUX (snmux=odd) <--> SNOPT for LTG 16 - 31 (ltgset=3,7,11,15,19,23,27,31) SNMUX (snmux=odd) <--> SNOPT for LTG 32 - 47 (ltgset=3,7,11,15,19,23,27,31) SNMUX (snmux=odd) <--> SNOPT for LTG 48 - 63 (ltgset=3,7,11,15,19,23,27,31) LILE0 <--> LTG 1 LILE0 <--> LTG 2 LILE0 <--> LTG 3

OML 01

C103P5

Optolink

OML 10 OML 11 OFC 0

C205P1 C205P5 C137P2

Optolink Optolink Optolink

OFC 1

C137P4

Optolink

OFC 2

D137P1

Optolink

OFC 3

D137P3

Optolink

OFC 4

C147P2

Optolink

OFC 5

C147P4

Optolink

OFC 6

D147P1

Optolink

OFC 7

D147P3

Optolink

OFC 0

C169P2

Optolink

OFC 1

C169P4

Optolink

OFC 2

D169P1

Optolink

OFC 3

D169P3

Optolink

OFC 4

C157P2

Optolink

OFC 5

C157P4

Optolink

OFC 6

D157P1

Optolink

OFC 7

D157P3

Optolink

L1 L2 L3

C123P2 C123P3 C123P4

Copper Copper Copper

Tab. 3.318 Plug connections F:SNMUX(B) backplane SN-side 0

504

A30828-X1160-M-2-7620

Maintenance Node

Construction

Connector L4 L5 L6 L7 L8 L9 L 10 L 11 L 12 L 13 L 14 L 15 L 129 L 130 L 131 L 132 L 133 L 134 L 135 L 136 L 137 L 138 L 139 L 140 L 141 L 142 L 143 LT 00 BT 00

MOLOC C123P5 D123P1 D123P2 D123P3 C129P1 C129P2 C129P3 C129P4 C129P5 D129P1 D129P2 D129P3 C179P2 C179P3 C179P4 C179P5 D179P1 D179P2 D179P3 C185P1 C185P2 C185P3 C185P4 C185P5 D185P1 D185P2 D185P3 C213P1 C213P2

Type Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper LILE0 <--> LTG 4 LILE0 <--> LTG 5 LILE0 <--> LTG 6 LILE0 <--> LTG 7 LILE0 <--> LTG 8 LILE0 <--> LTG 9 LILE0 <--> LTG 10 LILE0 <--> LTG 11 LILE0 <--> LTG 12 LILE0 <--> LTG 13 LILE0 <--> LTG 14 LILE0 <--> LTG 15 LILE1 <--> LTG 1 LILE1 <--> LTG 2 LILE1 <--> LTG 3 LILE1 <--> LTG 4 LILE1 <--> LTG 5 LILE1 <--> LTG 6 LILE1 <--> LTG 7 LILE1 <--> LTG 8 LILE1 <--> LTG 9 LILE1 <--> LTG 10 LILE1 <--> LTG 11 LILE1 <--> LTG 12 LILE1 <--> LTG 13 LILE1 <--> LTG 14 LILE1 <--> LTG 15

Connection

LTG Maintenance Interface LILE0 <--> MBU:LTG0 on MBDH MUXC0 (S1) <--> SGC:TSG 0 on MBDH (in DE without Subscriber SNMAT) LILE0 <--> MBU:LTG1 auf MBIH MUXC0 (S1) <--> SGC:TSG1 on MBDH (in DE without SNMAT) MUXC0 (S3) <--> SGC:SSG0 on MBDH (in DE without SNMAT) LILE1 <--> MBU:LTG 2 MUXC1 (S1) <--> SGC:TSG 2 on MBDH (in DE without SNMAT) LILE1 <--> MBU:LTG3 MUXC1 (S1) <--> SGC:TSG3 on MBDH (in DE without SNMAT) MUXC1 (S3) <--> SGC:SSG1 on MBDH (in DE without SNMAT)

LT 01 BT 01 BS 0 LT 10 BT 10 LT 11 BT 11 BS 1

C213P3 C213P4 C213P5 D213P1 D213P2 D213P3 D213P4 D185P4

Copper Copper Copper Copper Copper Copper Copper Copper

Tab. 3.318 Plug connections F:SNMUX(B) backplane SN-side 0

A30828-X1160-M-2-7620

505

Construction

Maintenance Node

Connector OML 00

MOLOC C235P1

Type Optolink

Connection SNMUX (snmux=even) <--> SNMAT OML00 MATM or SNMUXB <--> SNMUXA OML 00 (DE6.0) SNMUX (snmux=even) <--> SNMAT OML01 MATM or SNMUXB <--> SNMUXA OML 01 (DE6.0) SNMUX (snmux=odd) <--> SNMAT OML02 MATM SNMUX (snmux=odd) <--> SNMAT OML03 MATM SNMUX (snmux=even) <--> SNOPT for LTG 1 - 15 (ltgset=0,4,8,12,16,20,24,28) SNMUX (snmux=even) <--> SNOPT for LTG 16 - 31 (ltgset=0,4,8,12,16,20,24,28)

OML 01

C235P5

Optolink

OML 10 OML 11 OFC 0

C337P1 C337P5 C269P2

Optolink Optolink Optolink

OFC 1

C269P4

Optolink

OFC 2

D269P1

Optolink

SNMUX (snmux=even) <--> SNOPT for LTG 32 - 47 (ltgset=0,4,8,12,16,20,24,28) SNMUX (snmux=even) <--> SNOPT for LTG 48 - 63 (ltgset=0,4,8,12,16,20,24,28) SNMUX (snmux=even) <--> SNOPT for LTG 1 - 15 (ltgset=1,5,9,13,17,21,25,29) SNMUX (snmux=even) <--> SNOPT for LTG 16 - 31 (ltgset=1,5,9,13,17,21,25,29) SNMUX (snmux=even) <--> SNOPT for LTG 32 - 47 (ltgset=1,5,9,13,17,21,25,29) SNMUX (snmux=even) <--> SNOPT for LTG 48 - 63 (ltgset=1,5,9,13,17,21,25,29) SNMUX (snmux=odd) <--> SNOPT for LTG 1 - 15 (ltgset=2,6,10,14,18,22,26,30) SNMUX (snmux=odd) <--> SNOPT for LTG 16 - 31 (ltgset=2,6,10,14,18,22,26,30) SNMUX (snmux=odd) <--> SNOPT for LTG 32 - 47 (ltgset=2,6,10,14,18,22,26,30) SNMUX (snmux=odd) <--> SNOPT for LTG 48 - 63 (ltgset=2,6,10,14,18,22,26,30) SNMUX (snmux=odd) <--> SNOPT for LTG 1 - 15 (ltgset=3,7,11,15,19,23,27,31) SNMUX (snmux=odd) <--> SNOPT for LTG 16 - 31 (ltgset=3,7,11,15,19,23,27,31) SNMUX (snmux=odd) <--> SNOPT for LTG 32 - 47 (ltgset=3,7,11,15,19,23,27,31) SNMUX (snmux=odd) <--> SNOPT for LTG 48 - 63 (ltgset=3,7,11,15,19,23,27,31) LILE0 <--> LTG 1 LILE0 <--> LTG 2 LILE0 <--> LTG 3 LILE0 <--> LTG 4

OFC 3

D269P3

Optolink

OFC 4

C279P2

Optolink

OFC 5

C279P4

Optolink

OFC 6

D279P1

Optolink

OFC 7

D279P3

Optolink

OFC 0

C301P2

Optolink

OFC 1

C301P4

Optolink

OFC 2

D301P1

Optolink

OFC 3

D301P3

Optolink

OFC 4

C289P2

Optolink

OFC 5

C289P4

Optolink

OFC 6

D289P1

Optolink

OFC 7

D289P3

Optolink

L1 L2 L3 L4

C255P2 C255P3 C255P4 C255P5

Copper Copper Copper Copper

Tab. 3.319 Plug connections SNMUX backplane SN-side 1

506

A30828-X1160-M-2-7620

Maintenance Node

Construction

Connector L5 L6 L7 L8 L9 L 10 L 11 L 12 L 13 L 14 L 15 L 129 L 130 L 131 L 132 L 133 L 134 L 135 L 136 L 137 L 138 L 139 L 140 L 141 L 142 L 143 LT 00 BT 00 LT 01 BT 01 BS 0 LT 10 BT 10 LT 11 BT 11 BS 1

MOLOC D255P1 D255P2 D255P3 C261P1 C261P2 C261P3 C261P4 C261P5 D261P1 D261P2 D261P3 C311P2 C311P3 C311P4 C311P5 D311P1 D311P2 D311P3 C317P1 C317P2 C317P3 C317P4 C317P5 D317P1 D317P2 D317P3 C345P1 C345P2 C345P3 C345P4 C345P5 D345P1 D345P2 D345P3 D345P4 D317P4

Type Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper LILE0 <--> LTG 5 LILE0 <--> LTG 6 LILE0 <--> LTG 7 LILE0 <--> LTG 8 LILE0 <--> LTG 9 LILE0 <--> LTG 10 LILE0 <--> LTG 11 LILE0 <--> LTG 12 LILE0 <--> LTG 13 LILE0 <--> LTG 14 LILE0 <--> LTG 15 LILE1 <--> LTG 1 LILE1 <--> LTG 2 LILE1 <--> LTG 3 LILE1 <--> LTG 4 LILE1 <--> LTG 5 LILE1 <--> LTG 6 LILE1 <--> LTG 7 LILE1 <--> LTG 8 LILE1 <--> LTG 9 LILE1 <--> LTG 10 LILE1 <--> LTG 11 LILE1 <--> LTG 12 LILE1 <--> LTG 13 LILE1 <--> LTG 14 LILE1 <--> LTG 15

Connection

LILE0 <--> MBU:LTG0 on MBIH MUXC0 (S1) <--> SGC:TSG 0 on MBDH (in DE without SNMAT) LILE0 <--> MBU:LTG1 auf MBIH MUXC0 (S1) <--> SGC:TSG 1 on MBDH (in DE without SNMAT) MUXC0 (S3) <--> SGC:SSG0 on MBDH (in DE without SNMAT) LILE1 <--> MBU:LTG 2 MUXC1 (S1) <--> SGC:TSG 2 on MBDH (in DE without SNMAT) LILE1 <--> MBU:LTG3 MUXC1 (S1) <--> SGC:TSG3 on MBDH (in DE without SNMAT) MUXC1 (S3) <--> SGC:SSG1 on MBDH (in DE without SNMAT)

Tab. 3.319 Plug connections SNMUX backplane SN-side 1

A30828-X1160-M-2-7620

507

Construction

Maintenance Node

3.9.10 3.9.10.1

F:SNCARE F:SNCARE (backplane)


F:SNCARE (backplane) with 4SU (with 4 cable) and 4SU (with 8 cable)
P1 P2 56 57 48 48 56 32 40 40 32 41 33 33 41 24 16 16 24 0 8 8 9 1 1 9 2 10 10 2 11 3 3 11 12 4 4 12 13 5 5 13 14 5 5 14 6 15 15 6

P3 P4 P5 P1

49 49 57 50 50 58 58 59 51 51 59 60 52 52 60 53 61 61 53 62 54 54 62 63 55 55 63

25 17 17 25 26 18 18 26 2719 19 27 20 28 28 20 29 21 21 29 30 22 22 30 31 23 23 31

42 34 34 42 43 35 35 43 44 36 36 44 37 45 45 37 46 38 38 46 39 47 47 39

P2 P3 P4

F:SNCARE (backplane) with 1SU and 4SU (with 8 cable)


P1 P2 56 48 56 48 40 41 42 32 40 32 33 41 33 26 24 16 16 24 25 17 25 17 10 8 0 8 9 1 9 1

P3 P4 P5 P1

57 49 49 57 50 50 58 58 51 51 59 59 60 52 52 60 61 53 61 62 54 54 62 63 55 63 55 53

34 34 42 43 35 35 43 36 36 44 45 37 37 45 38 38 46 47 39 47 39

18 18 26 19 19 27 27 20 20 28 29 21 29 21

2 2 10 3 3 11 11 4 4 12 13 5 13 5

44

28

12

P2 P3 P4

46

30

22 22 30 31 23 31 23

14

5 6 14 15 6 15 7

508

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.9.10.2

F:SNCARE (cabling)
F:SNCARE (cabling) with SU4 cable connector (with 4 and 8 cable) Cabling F:SNCARE --> LTG with 4SU cable connector with 4 cable Valid for LTGSET 01, 03, 05, 07, 09, 11, 13, 15, 17, 19, 21, 23, 25, 27, 29, 31. All LTGxx are connected with SN0 (MUT02 or MUT06) and SN1 (MUT03 or MUT07).
LTG 01 02 03 04, 05 ,06, 07 08, 09, 10, 11 12, 13, 14, 15 16, 17, 18, 19 20, 21, 22, 23 24, 25, 26, 27 28, 29, 30, 31 32, 33, 34, 35 36, 37, 38, 39 40, 41, 42, 43 44, 45, 46, 47 48, 49, 50, 51 52, 53, 54, 55 56, 57, 58, 59 60, 61, 62, 63 1 2 3 4-5-6-7 8-9-10-11 12-13-14-15 16-17-18-19 20-21-22-23 24-25-26-27 28-29-30-31 32-33-34-35 36-37-38-39 40-41-42-43 44-45-46-47 48-49-50-51 52-53-54-55 56-57-58-59 60-61-62-63 Connector C113P2 C113P3 C113P4 C113P5 C125P1 C125P5 C161P1 C161P5 C173P1 C173P5 C271P1 C271P5 C283P1 C283P5 C319P1 C319P5 C331P1 C331P1 MOLOC

Tab. 3.320 F:SNCARE(A) --> LTG with 4SU cable connector with 4 cable Cabling F:SNCARE <--> F:SNMUX(A) with 4SU cable connector with 8 cable for 2. LTG SET
SN-0 Connector 0-8-1-9-2-10-3-11 4-12-5-13-6-14-715 16-24-17-25-1826-19-27 20-28-21-29-2230-23-31 F:SNCARE --> F:SNMUX(A) 02/06C119P1 --> 02C143P1 02/06C119P5 --> 02C143P5 Connector 0-8-1-9-2-10-3-11 4-12-5-13-6-14-7-15 SN-1 F:SNCARE --> F:SNMUX(A) 03/07C119P1 --> 03C143P1 03/07C119P5 --> 03C143P5

02/06C167P1 --> 02C191P1

16-24-17-25-18-2619-27 20-28-21-29-22-3023-31

03/07C167P1 --> 03D191P1

02/06C167P5 --> 02D191P5

03/07C167P5 --> 03D191P5

Tab. 3.321 Cabling F:SNCARE -> F:SNMUX(A)

A30828-X1160-M-2-7620

509

Construction

Maintenance Node

SN-0 Connector 32-40-33-41-3442-35-43 36-44-37-45-3846-39-47 48-56-49-57-5058-51-59 52-60-53-61-5462-55-63 F:SNCARE --> F:SNMUX(A) 02/06C277P1 --> 02C253P1 Connector 32-40-33-41-34-4235-43 36-44-37-45-38-4639-47 48-56-49-57-50-5851-59 52-60-53-61-54-6255-63

SN-1 F:SNCARE --> F:SNMUX(A) 03/07C277P1 --> 03C253P1

02/06C277P5 --> 02C253P5

03/07C277P5 --> 03C253P5

02/06C325P1 --> 02C301P1

03/07C325P1 --> 03C301P1

02/06C325P5 --> 02C301P5

03/07C325P5 --> 03C301P5

Tab. 3.321 Cabling F:SNCARE -> F:SNMUX(A) F:SNCARE (Cabling) with SU1 and SU4 cable connector (with 8 cable) Cabling F:SNCARE --> LTG with 1SU cable connector Valid for LTGSET 01, 03, 05, 07, 09, 11, 13, 15, 17, 19, 21, 23, 25, 27, 29, 31. All LTGxx are connected with SN0 (MUT02 or MUT06) and SN1 (MUT03 or MUT07).
LTG Connector 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 MOLOC LTG Connector 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 MOLOC LTG Connector 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 MOLOC

01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21

C107P2 C113P3 C107P4 C113P5 D107P1 D113P2 D107P3 C125P1 C119P2 C125P3 C119P4 C125P5 D119P1 D125P2 D119P3 C161P1 C155P2 C161P3 C155P4 C161P5 D155P1

22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42

D161P2 D155P3 C173P1 C167P2 C173P3 C167P4 C173P5 D167P1 D173P2 D167P3 C271P1 C265P2 C271P3 C265P4 C271P5 D265P1 D271P2 D265P3 C283P1 C277P2 C283P3

43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63

C277P4 C283P5 D277P1 D283P2 D277P3 C319P1 C313P2 C319P3 C313P4 C319P5 D313P1 D319P2 D313P3 C331P1 C325P2 C331P3 C325P4 C331P5 D325P1 D331P2 D325P3

Tab. 3.322 F:SNCARE --> LTG with 1SU cable connector

510

A30828-X1160-M-2-7620

Maintenance Node

Construction

Cabling F:SNCARE <--> F:SNMUX(A) with 4SU cable connector with 8 cable Valid for LTGSET 01, 03, 05, 07, 09, 11, 13, 15, 17, 19, 21, 23, 25, 27, 29, 31.
SN-0 Connector 0-8-1-9-2-10-3-11 4-12-5-13-6-14-715 16-24-17-25-1826-19-27 20-28-21-29-2230-23-31 32-40-33-41-3442-35-43 36-44-37-45-3846-39-47 48-56-49-57-5058-51-59 52-60-53-61-5462-55-63 F:SNCARE --> F:SNMUX(A) 02/06C119P1 --> 02C143P1 02/06C119P5 --> 02C143P5 Connector 0-8-1-9-2-10-3-11 4-12-5-13-6-14-715 16-24-17-25-1826-19-27 20-28-21-29-2230-23-31 32-40-33-41-3442-35-43 36-44-37-45-3846-39-47 48-56-49-57-5058-51-59 52-60-53-61-5462-55-63 SN-1 F:SNCARE --> F:SNMUX(A) 03/07C119P1 --> 03C143P1 03/07C119P5 --> 03C143P5

02/06C167P1 --> 02C191P1

03/07C167P1 --> 03D191P1

02/06C167P5 --> 02D191P5

03/07C167P5 --> 03D191P5

02/06C277P1 --> 02C253P1

03/07C277P1 --> 03C253P1

02/06C277P5 --> 02C253P5

03/07C277P5 --> 03C253P5

02/06C325P1 --> 02C301P1

03/07C325P1 --> 03C301P1

02/06C325P5 --> 02C301P5

03/07C325P5 --> 03C301P5

Tab. 3.323 Cabling F:SNCARE -> F:SNMUX(A)

A30828-X1160-M-2-7620

511

Construction

Maintenance Node

3.10

F:SSNC
3.10.1 3.10.1.1 3.10.1.2 3.10.1.3 3.10.2 3.10.2.1 3.10.2.2 3.10.2.3 3.10.3 3.10.3.1 3.10.3.2 3.10.3.3 3.10.4 3.10.4.1 3.10.4.2 3.10.4.3 F:SCB F:SCB (module side) F:SCB (backplane) F:SCB (cabling) F:SCE F:SCE (module side) F:SCE (backplane) F:SCE (cabling) F:ASN(E) F:ASN(E) (module side) F:ASN(E) (backplane) F:ASN(E) (cabling) F:ASN(H) F:ASN(H) (module side) F:ASN(H) (backplane) F:ASN(H) (cabling)

3.10.1 3.10.1.1

F:SCB F:SCB (module side)


P1 P2

P3 P4 P5 P1 LIC or MPU 00 LIC or MPU 01 LIC or MPU 10 LIC or MPU 11 P2

MPU:SA 00

MPU:SA 01

ACCG 00

ACCG 01

AMXE 00

AMXE 01

D P3
P4 P5

IMDD 01 C339

MOD 00

C103

C127

C139

C159

C179

C191

C201

C221

C243

C275

C299

C319

C115

Modules with displays and switches in F:SCB LIC:2A (Q1014) MPUD (Q83) ALIB (Q1065) LIC:1,5A (Q1013) MPUD (Q85-X801) MDD (U2594) MPUC (SA,512MB)(Q82-X401) AMXE (Q1019) MOD (Q1028) MPUC (AP,512MB)(Q80-X401) ACCG (Q145) (Q1022)

Tab. 3.324 Modules with displays and switches in F:SCB

512

A30828-X1160-M-2-7620

C361

MOD 01

MDD 00

ALIB

Maintenance Node

Construction

3.10.1.2

F:SCB (backplane)
P1 P2
17 17 16 16 5

14 14

15

15

6 6

3
1

P3

10 3 11 12
22 22

3 20
14

P4 P5

3
14

P1 P2

3
P3 P4 P5 28 28 21 21 20 20
6 6 6

4
24

4
28 28

375 375

363

351

329

319 309

299

275

263

251

231

211

191

179

169

149

127

115

285

233

Strapping plugs Connector 20 C169P4 code plug ACCG0 / 1 D285P4 code plug MPU-SA0 D285P5 code plug MPU-SA1 Connector 22 C233P4 SCSI term. MDD/MOD Plane 0 C377P4 SCSI term. MDD/MOD Plane 1

3.10.1.3

F:SCB (cabling)
for example: C263P1, C263R1 P is the upper plug within one system unit; R is the lower plug within one system unit; Cabling F:SCB <--> IDF (Connector 1
From F:SCB Connector 1 1 Unit F:SCB F:SCB MOLOC C103P2 C103P4 IDF x001, E1-sym./COAX, DS1-sym IDF x003, E1-sym./COAX, DS1-sym To IDF / Strapping Plug

Tab. 3.325 F:SCB <---> IDF (Connector 1)

139

A30828-X1160-M-2-7620

513

103

Construction

Maintenance Node

Cabling F:SCB <--> Ethernet (Connector 21, 28)


From F:SCB Connector 21 21 28 28 28 28 Unit F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB MOLOC 09D309P3 09D329P3 09D299P5 09D319P5 09D127P5 09D139P5 AUI interface to MPU(SA)0 AUI interface to MPU(SA)1 MPU(SA)0 only frame X2755 MPU(SA)1 only frame X2755 MPU10 only frame X2755 MPU11 only frame X2755 Ethernet interface

Tab. 3.326 F:SCB <---> Ethernet (Connector 21, 28) Cabling F:SCB <--> F:MBD (Connector 3)
From F:SCB Connector 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX Unit F:SCB / AMX0 F:SCB / AMX1 F:SCB / AMX0 F:SCB / AMX1 F:SCB / AMX0 F:SCB / AMX1 F:SCB / AMX0 F:SCB / AMX1 MOLOC 09C149P1 (P2) 09C211P1 (P2) 09C149P5 (P1) 09C211P5 (P1) 09D149P3 (P4) 09C211P3 (P4) 09D149P2 (P3) 09D211P2 (P3) To F:MBD Unit F:MBD0 / MBDA0 F:MBD0 / MBDA0 F:MBD0 / MBDA0 F:MBD0 / MBDA0 F:MBD1 / MBDA0 F:MBD1 / MBDA0 F:MBD1 / MBDA0 F:MBD1 / MBDA0 MOLOC C157P1 C157P3 C157P5 D157P2 C157P1 C157P3 C157P5 D157P2

Tab. 3.327 Cabling F:SCB <--> F:MBD Cabling F:SCB <----> F:BPCE (Connector 4)
From F:SCB Connector 4 - FOTX 4 - FOTX 4 - FOTX 4 - FOTX F:SCB F:SCB F:SCB F:SCB Unit MOLOC 09D149P4 (P5) 09D169P4 (P5) 09D211P4 (P5) 09D231P4 (P5) F:BPCE F:BPCE F:BPCE F:BPCE Unit To F:BPCE MOLOC 07D209P3 (P2) 07D285P3 (P2) 07D209P5 (P2) 07D285P5 (P2)

Tab. 3.328 Cabling F:SCB <----> F:BPCE (Connector 4)

514

A30828-X1160-M-2-7620

Maintenance Node

Construction

Cabling F:SCB <--> F:PIOP(B) (Connector 4)


From F:SCB Connector 4 - FOTX 4 - FOTX 4 - FOTX 4 - FOTX F:SCB F:SCB F:SCB F:SCB Unit MOLOC 09D149P4 (P5) 09D169P4 (P5) 09D211P4 (P5) 09D231P4 (P5) Unit F:PIOP(B)0 F:PIOP(B)1 F:PIOP(B)0 F:PIOP(B)1 To F:PIOP(B) MOLOC 03C109P3 (P2) 07C109P3 (P2) 03D109P3 (P2) 07D109P3 (P2)

Tab. 3.329 Cabling F:SCB <---> F:PIOP(B) (Connector 4) Cabling F:SCB <----> F:SCE (Connector 6, 24)
From F:SCB Connector 6 6 6 6 6 6 24 Unit F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB MOLOC 09C169P2 09C169R2 09C169P3 09D251P4 09D251R4 09D251P5 09D191P5 Unit F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE, ext. rack To F:SCE MOLOC 03C241P1 05C241P1 07C241P1 03C241P2 05C241P2 07C241P2 07C241P3 Alarm out Clock interface T0 out next frame plane 1 Clock interface T0 out next frame plane 0 Remarks

Tab. 3.330 Cabling F:SCB <----> F:SCE (Connector 6, 24) Cabling F:SCB <----> F:ASN(E) (Connector 5, 12, 14, 16)
From F:SCB Connector 5 5 12 14 14 14 14 16 16 Unit F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB MOLOC 09C251P1 09C169P1 09C191P5 09C169P5 09C231P1 09C231P2 09D169P1 09C263P1 09C263R1 To F:ASN(E) Unit F:ASN(E) 1 F:ASN(E) 1 F:ASN(E) 0 F:ASN(E) 0 F:ASN(E) 1 F:ASN(E) 1 F:ASN(E) 0 F:ASN(E) 0 F:ASN(E) 1 MOLOC 05C103P1 07C103P1 07C123P2 07C133P3 05C133P3 05C133P4 07C133P4 07C123R2 05C123R2 Line timing out Alarm out ASN interface RTTL interface Remarks

Tab. 3.331 Cabling F:SCB <----> F:ASN(E) (Connector 5, 12, 14, 16)

A30828-X1160-M-2-7620

515

Construction

Maintenance Node

Cabling F:SCB <----> Breaker panel (Connector 11)


From F:SCB Connector 11 F:SCB Unit MOLOC 09C191P4 ALMC alarm in To Breaker panel Unit

Tab. 3.332 Cabling F:SCB <----> Breaker panel (Connector 11) Cabling F:SCB <----> F:ASN(H) (Connector 5, 12,14, 16)
From F:SCB Connector 5 5 5 12 14 14 14 14 16 16 F:SCB F:SCB bas. Rack F:SCB ext. Rack 1 F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB Unit MOLOC 09C169P1 09C251P1 09C251P1 09C191P5 09C169P5 09C169P1 09C231P1 09C231P2 09C263P1 09C263R1 To F:ASN(H) Unit F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) MOLOC 07C173P2 07D321R1 07D321P2 07C163P1 07C111P3 07C111P4 07C259P3 07C259P4 07C173R2 07C321R2 Line timing out Alarm out ASN interface RTTL interface Remarks

Tab. 3.333 Cabling F:SCB <----> F:ASN(H) (Connector 5, 12,14, 16) Cabling F:SCB internal (Connector 10, 14, 15, 16, 17)
From F:SCB Connector 10 (**) 14 (*) 14 (*) 15 (#) 16 / 17 (*) F:SCB F:SCB F:SCB F:SCB F:SCB Unit MOLOC 09C191P3 09C169P5 09C231P1 09C251P2 09C263P1 Unit Radio Clock F:SCB F:SCB F:SCB F:SCB 09D169P1 09C231P2 09C263P2 09C275P1 To F:SCB MOLOC

(*) Reference clock in F:SCB if F:ASN(E) is not existing (**) only for stand alone (#) Frame internal in every F:SCB

Tab. 3.334 Cabling F:SCB internal (Connector 10, 14, 15 16, 17)

516

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.10.2 3.10.2.1

F:SCE F:SCE (module side)

P1 P2

P3 P4 P5 P1

LIC or MPU 20

LIC or MPU 21

LIC or MPU 30

LIC or MPU 31

LIC or MPU 40

LIC or MPU 41

LIC or MPU 50

LIC or MPU 51

LIC or MPU 00

LIC or MPU 01

LIC or MPU 10

LIC or MPU 11

LIC or MPU 60

LIC or MPU 61

LIC or MPU 70 C363

ACCG 00

ACCG 01

AMXE 00

P4 P5

C103

C115

C127

C139

C151

C163

C175

C187

C211

C231

C251

C271

AMXE 01

D P3

C291

C303

C315

C327

C339

C351

Modules with displays and switches in F:SCE LIC:2A (Q1014) MPUD (Q83) LIC:1,5A (Q1013) MPUD (Q85-X801) MPUC (SA,512MB)(Q82-X401) AMXE (Q1019) MPUC (AP,512MB)(Q80-X401) ACCG (Q145) (Q1022)

Tab. 3.335 Modules with displays and switches in F:SCE

A30828-X1160-M-2-7620

517

C375

LIC or MPU 71

P2

Construction

Maintenance Node

3.10.2.2

F:SCE (backplane)
P1 P2 1 1 1 1 1 1 1 1 1 1 1 1
6 6 6 5 6 6 6

5 5

1 1 1 1

1 1

1 1 1

1 1 1 1

1 1

P3 P4 P5 P1 P2

14 3 14 14 3 14 14 3 14 14

11 3 12

14 14 14 3 14

1 1

1 1 1

16 16

14 3 14 14 14 24 24 24 24 24 24 24 20

P3 P4 P5 24 24 24 24 24 24 24 20

14

281

375

363

351

339

327

315

303

291

261

241

221

201

187

175

163

151

139

127

115

3.10.2.3

F:SCE (cabling)
for example: C263P1, C263R1 P is the upper plug within one system unit; R is the lower plug within one system unit; Cabling F:SCE <--> IDF and Strapping plugs (Connector 1) LIC interfaces
From F:SCE Connector 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Unit F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE MOLOC C103P2 C103P4 C115P2/P3/P4/P5 C127P2 C127P4 C139P2/P3/P4/P5 C151P2 C151P4 C163P2/P3/P4/P5 C175P2 C175P4 C187P2/P3/P4/P5 C339P2 C339P4 C351P2/P3/P4/P5 IDF x005, E1- sym./COAX, /DS1- COAX IDF x007, E1- sym./COAX, /DS1- COAX strapping plugs IDF x013, E1- sym./COAX, /DS1- COAX IDF x015, E1- sym./COAX, /DS1- COAX strapping plugs IDF x001, E1- sym./COAX, /DS1- COAX (*) IDF x003, E1- sym./COAX, /DS1- COAX (*) strapping plugs (*) IDF x009, E1- sym./COAX, /DS1- COAX IDF x011, E1- sym./COAX, /DS1- COAX strapping plugs IDF x017, E1- sym./COAX, /DS1- COAX IDF x019, E1- sym./COAX, /DS1- COAX strapping plugs To IDF / Strapping Plug

Tab. 3.336 Cabling F:SCE <-> IDF and strapping plugs (connector 1)

518

A30828-X1160-M-2-7620

103

Maintenance Node

Construction

From F:SCE Connector 1 1 1 1 1 1 1 Unit F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE MOLOC C363P2 C363P4 C375P2/P3/P4/P5 C151P3 C151P4 C163P2 C163P4

To IDF / Strapping Plug

IDF x025, E1- sym./COAX, /DS1- COAX IDF x027, E1- sym./COAX, /DS1- COAX strapping plugs IDF x001/ Port 0 for Mobile Networks (*) IDF x001/ Port 1 for Mobile Networks (*) IDF x002/ Port 0 for Mobile Networks (*) IDF x002/ Port 1 for Mobile Networks (*)

Tab. 3.336 Cabling F:SCE <-> IDF and strapping plugs (connector 1) Cabling F:SCE <--> F:MBD (Connector 3)
From SSNC Connector 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX Unit F:SCE0 / AMX0 F:SCE0 / AMX1 F:SCE0 / AMX0 F:SCE0 / AMX1 F:SCE0 / AMX0 F:SCE0 / AMX1 F:SCE0 / AMX0 F:SCE0 / AMX1 F:SCE1 / AMX0 F:SCE1 / AMX1 F:SCE1 / AMX0 F:SCE1 / AMX1 F:SCE1 / AMX0 F:SCE1 / AMX1 F:SCE1 / AMX0 F:SCE1 / AMX1 F:SCE1 / AMX0 F:SCE2 / AMX1 F:SCE2 / AMX0 F:SCE2 / AMX1 F:SCE2 / AMX0 F:SCE2 / AMX1 F:SCE2 / AMX0 F:SCE2 / AMX1 MOLOC C221P1 C262P1 C221P5 C261P5 C221P1 C261P1 C221P5 C261P5 C221P1 C261P1 C221P5 C261P5 C221P1 C261P1 C221P5 C261P5 C221P1 C261P1 C221P5 C261P5 C221P1 C261P1 C221P5 C261P5 Unit F:MBD0 / MBDA1 F:MBD0 / MBDA1 F:MBD0 / MBDA1 F:MBD0 / MBDA1 F:MBD1 / MBDA1 F:MBD1 / MBDA1 F:MBD1 / MBDA1 F:MBD1 / MBDA1 F:MBD0 / MBDA2 F:MBD0 / MBDA2 F:MBD0 / MBDA2 F:MBD0 / MBDA2 F:MBD1 / MBDA2 F:MBD1 / MBDA2 F:MBD1 / MBDA2 F:MBD1 / MBDA2 F:MBD0 / MBDA3 F:MBD0 / MBDA3 F:MBD0 / MBDA3 F:MBD0 / MBDA3 F:MBD1 / MBDA3 F:MBD1 / MBDA3 F:MBD1 / MBDA3 F:MBD1 / MBDA3 To MBD MOLOC C259P1 C259P3 C259P5 D259P2 C259P1 C259P3 C259P5 D259P2 C125P1 C125P3 C125P5 D125P2 C125P1 C125P3 C125P5 D125P2 C325P1 C325P3 C325P5 D325P2 C325P1 C325P3 C325P5 D325P2

Tab. 3.337 Cabling F:SCE<--> F:MBD

A30828-X1160-M-2-7620

519

Construction

Maintenance Node

From SSNC Connector 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX 3 - FOTX Unit F:SCE3 / AMX0 F:SCE3 / AMX1 F:SCE3 / AMX0 F:SCE3 / AMX1 F:SCE3 / AMX0 F:SCE3 / AMX1 F:SCE3 / AMX0 F:SCE3 / AMX1 MOLOC C221P1 C261P1 C221P5 C261P5 C221P1 C261P1 C221P5 C261P5 Unit

To MBD MOLOC C293P1 C293P3 C293P5 D293P2 C293P1 C293P3 C293P5 D293P2

F:MBD0 / MBDA4 F:MBD0 / MBDA4 F:MBD0 / MBDA4 F:MBD0 / MBDA4 F:MBD1 / MBDA4 F:MBD1 / MBDA4 F:MBD1 / MBDA4 F:MBD1 / MBDA4

Tab. 3.337 Cabling F:SCE<--> F:MBD

520

A30828-X1160-M-2-7620

Maintenance Node

Construction

Cabling F:SCE <----> F:SCB (Connector 5, 11) Clock in basic rack from F:SCB to F:SCE MUT03 Clock in basic rack from F:SCB to F:SCE MUT05 Clock in extension rack from F:SCB to F:SCE MUT07
From F:SCE Connector 5 5 5 5 5 5 5 11 F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE ext. rack F:SCE ext. rack F:SCE Unit MOLOC 03C241P2 03C241P1 05C241P2 05C241P1 07C241P1 07C241P1 07C241P2 07C241P3 Unit F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB ext. rack F:SCB ext. rack F:SCB To F:SCB MOLOC 09D251P4 09C169P2 09D251R4 09C169R2 09C169P3 09D251P5 09C169P5 09C191P5 Alarm out RTTL interface Remarks

Tab. 3.338 Cabling F:SCE <----> F:SCB (Connector 5, 11) Cabling F:SCE internal (Connector 5, 6, 11, 12, 20)
From F:SCE Connector 5-6 5-6 5-6 5-6 5-6 5-6 11 12 - 11 12 - 11 12 - 11 20 Unit F:SCE ext. rack F:SCE ext. rack F:SCE ext. rack F:SCE ext. rack F:SCE ext. rack F:SCE ext. rack MOLOC 03C241P1 03C241P2 05C241P1 05C241P2 07C241P1 07C241P2 Unit F:SCE ext. rack F:SCE ext. rack F:SCE ext. rack F:SCE ext. rack F:SCE ext. rack F:SCE ext. rack F:SCE ext. rack F:SCE F:SCE F:SCE To F:SCE MOLOC 09C201P1 09C281P1 09C201R1 09C281R1 09C201P2 09C281P2 09C241P3 07C241P3 05C241P3 03C241P3 Code plug Alarming Clock connections Remarks

from Breaker Panel ALMC ext. rack F:SCE F:SCE F:SCE F:SCE 09C241P4 07C241P4 05C241P4 D291P5

strapping plug in every F:SCE

Tab. 3.339 Cabling F:SCE internal (Connector 5, 6, 11, 12, 20)

A30828-X1160-M-2-7620

521

Construction

Maintenance Node

Cabling F:SCE <--> F:ASN(E) (Connector 5, 11, 14, 16) 14: ASN interface
From F:SCE Connector 5 (*) 5 (*) 5 (#) 5 (#) 11 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 16 16 Unit F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE MOLOC 09D241P2 09D241P1 09D241P2 09D241P1 03C241P3 C201P3 C201P4 C281P3 C281P4 C201P5 D201P1 C281P5 D281P1 D201P2 D201P3 D281P2 D281P3 D201P4 D201P5 D281P4 D281P5 03D241P2 03D241R2 Unit F:ASN(E) 1 F:ASN(E) 0 F:ASN(E) 1 F:ASN(E) 0 F:ASN(E) F:ASN(E) 0 F:ASN(E) 0 F:ASN(E) 1 F:ASN(E) 1 F:ASN(E) 0 F:ASN(E) 0 F:ASN(E) 1 F:ASN(E) 1 F:ASN(E) 0 F:ASN(E) 0 F:ASN(E) 1 F:ASN(E) 1 F:ASN(E) 0 F:ASN(E) 0 F:ASN(E) 1 F:ASN(E) 1 F:ASN(E) 0 F:ASN(E) 1 MOLOC 05C103R1 07C103R1 05C103P2 07C103P2 05C123P3 07Cx 07Cx 05Cx 05Cx 07Cx 07Cx 05Cx 05Cx 07Cx 07Cx 05Cx 05Cx 07Cx 07Cx 05Cx 05Cx 07C123P3 05C123P3 Line timing 3. additional connection (connection 3) 2. additional connection (connection 2) 1. additional connection (connection 1) Alarming Basic connection (connection 0) To F:ASN(E) Remarks Clock connections

(*) Clock to F:SCE MUT09 in 1. extension rack (#) Clock to F:SCE MUT09 in 2. extension rack

Tab. 3.340 Cabling F:SCE <--> F:ASN(E) (Connector 5, 11, 14, 16) Cabling F:SCE <--> F:ASN(H) (Connector 5, 11, 14, 16) 14: ASN interface

522

A30828-X1160-M-2-7620

Maintenance Node

Construction

From F:SCE Connector 5 (*) 5 (*) 5 (#) 5 (#) 11 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 16 16 16 16 Unit MOLOC Unit MOLOC

To F:ASN(H) Remarks

F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE

09D241P2 09D241P1 09D241P2 09D241P1 5C241P3 C201P3 C201P4 C281P3 C281P4 C201P5 D201P1 C281P5 D281P1 D201P2 D201P3 D281P2 D281P3 D201P4 D201P5 D281P4 D281P5 03D241P2 03D241R2 05D241P2 05D241R2

F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H)

07D321P2 07D173P2 07D321R2 07D173R2 7C311P2 07Cx Plane 0 07Cx Plane 0 07Cx Plane 1 07Cx Plane 1 07Cx Plane 0 07Cx Plane 0 07Cx Plane 1 07Cx Plane 1 07Cx Plane 0 07Cx Plane 0 07Cx Plane 1 07Cx Plane 1 07Cx Plane 0 07Cx Plane 0 07Cx Plane 1 07Cx Plane 1 07C123P3 07C321P3 07C123R3 07C321R3

Clock connections

Alarming Basic connection (connection 0)

1. additional connection (connection

2. additional connection (connection 2)

3. additional connection (connection 3)

Line timing

(*) Clock to F:SCE MUT09 in 1. extension rack (#) Clock to F:SCE MUT09 in 2. extension rack

Tab. 3.341 Cabling F:SCE <--> F:ASN(H) (Connector 5, 11, 14, 16) Cabling F:SCE Ethernet interface MPU (Connector 24)
From F:SCE Connector 24 24 24 Unit F:SCE F:SCE F:SCE MOLOC D109P5 D121P5 D133P5 MPU 00 MPU 01 MPU 10 Ethernet interface

Tab. 3.342 Cabling Ethernet interface MPU (Connector 24)

A30828-X1160-M-2-7620

523

Construction

Maintenance Node

From F:SCE Connector 24 24 24 24 24 24 24 24 24 24 24 24 24 Unit F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE MOLOC D145P5 D157P5 D169P5 D181P5 D193P5 D302P5 D313P5 D323P5 D333P5 D343P5 D355P5 D365P5 D376P5 MPU 11 MPU 20 MPU 21 MPU 30 MPU 31 MPU 40 MPU 41 MPU 50 MPU 51 MPU 60 MPU 61 MPU 70 MPU 71

Ethernet interface

Tab. 3.342 Cabling Ethernet interface MPU (Connector 24)

3.10.3 3.10.3.1

F:ASN(E) F:ASN(E) (module side)

D
GMX 0 GMX 1 GMX 1 GMX 1 GMX 1 GMX 1 GMX 2 ASMG GMX 3 C373 ACCG PSAG C277

C113

C141

C171

C171

C193

C241

C295

C321

Modules with displays and switches in F:ASN(E) ACCG (Q145) (Q1022) GMX:E (Q1032) ASMG16/16 (Q1034) PSAG (Q6124)

Tab. 3.343 Modules with displays and switches in F:ASN(E)

524

A30828-X1160-M-2-7620

C347

Maintenance Node

Construction

3.10.3.2

F:ASN(E) (backplane)
P1 P2 PA + PA R4 T4 R5 T5 R6 T6 R7 T7 R0 R4 T0 T4 R0 R4 T0 T4 R0 R4 T0 T4 R0 T0 R1 T1 R2 T2 R3 T3 SC SC PB + PB PC + PC R4 T4 R5 T5 R6 T6 R7 T7 R0 R4 T0 T4 R0 R4 T0 T4 R0 R4 T0 T4 R0 T0 R1 T1 R2 ASC T2 ASC R3 T3 ASC
CSO C0 RTL C1 RTL C2 CSI CSI

P3 P4 P5 P1 P2

R1 R5 T1 T5

R1 R5 T1 T5

R1 R5 T1 T5

R1 R5 T1 T5

R1 R5 T1 T5

R1 R5 T1 T5

R2 R6 T2 T6

R2 R6 T2 T6

R2 R6 T2 T6

R2 R6 T2 T6

R2 R6 T2 T6

R2 R6 T2 T6

P3 P4 P5

R3 R7 T3 T7

R3 R7 T3 T7

R3 R7 T3 T7

R3 R7 T3 T7

R3 R7 T3 T7

R3 R7 T3 T7

381

365

355

339

328

313

303

287

263

227

211

201

185

175

159

149

133

123

Strapping plug Connector SC

A30828-X1160-M-2-7620

525

103

Construction

Maintenance Node

3.10.3.3

F:ASN(E) (cabling)
for example: C263P1, C263R1 P is the upper plug within one system unit; R is the lower plug within one system unit; Power supply cabling (Connector PAx, PBx, PCx)
Connector PA+ PAPB+ PBPC+ PCPA+ PAPB+ PBPC+ PCMOLOC 05C263P1 05C263P2 05C263P3 05C263P4 05C263P5 05D263P1 07C263P1 07C263P2 07C263P3 07C263P4 07C263P5 057D263P1 Voltage supply side 0 Voltage supply side 0 Voltage supply side 05 Voltage supply side 0 Voltage supply side 0 Voltage supply side 0 Voltage supply side 1 Voltage supply side 1 Voltage supply side 1 Voltage supply side 1 Voltage supply side 1 Voltage supply side 1 Connection Breaker panel of the rack fuse 03 Breaker panel of the rack fuse 04 Breaker panel of the rack fuse 05 Breaker panel of the rack fuse 03 Breaker panel of the rack fuse 04 Breaker panel of the rack fuse 05 Breaker panel of the rack fuse 28 Breaker panel of the rack fuse 29 Breaker panel of the rack fuse 30 Breaker panel of the rack fuse 28 Breaker panel of the rack fuse 29 Breaker panel of the rack fuse 30

Tab. 3.344 Power supply cabling (Connector PAx, PBx, PCx) Cabling F:ASN(E) <----> F:SCB
To F:ASN(E) Connector C0 (*) C0 (*) C0 (#) C0 (#) CSi CSi RTL ASC Unit F:ASN(E) 0 F:ASN(E) 1 F:ASN(E) 0 F:ASN(E) 1 F:ASN(E) 0 F:ASN(E) 1 F:ASN(E) 0 F:ASN(E) 0 MOLOC 07C103P1 05C103P1 07C103R1 05C103R1 07C123R2 05C123R2 07C123P2 07D123P2 From F:SCB Unit F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB F:SCB MOLOC 09C251P1 09C169P1 09C169P1 09C251P1 09C263P1 09C263R1 09C191P5 09C191P5 RTTL interface Alarming Line timing Clock connections Remarks

(*) Clock basic rack (#) Clock in first extension rack

Tab. 3.345 Cabling F:ASN(E) <----> F:SCB

526

A30828-X1160-M-2-7620

Maintenance Node

Construction

Cabling F:ASN(E) <----> F:SCE (Connector CSI, Cx)


To F:ASN(E) Connector CSI CSI C1 C1 C2 C2 ASC Unit F:ASN(E) 1 F:ASN(E) 0 F:ASN(E) 1 F:ASN(E) 0 F:ASN(E) 1 F:ASN(E) 0 F:ASN(E) 1 MOLOC 05C123P3 07C123P3 05C103R1 07C103R1 05C103P2 07C103P2 05D123P3 From F:SCE Unit F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE MOLOC 03D241R2 03D241P2 09C241P2 09C241P1 09C241P2 09C241P1 03C241P3 Alarming Clock connections Remarks

Tab. 3.346 Cabling F:ASN(E) <----> F:SCE (Connector CSI, Cx) Cabling F:ASN(E) internal
To F:ASN(E) Connector CSi - RTL RTL ASC ASC ASC ASC ASC Unit F:ASN(E) 0 F:ASN(E) 0 F:ASN(E) 0 F:ASN(E) 1 F:ASN(E) 1 F:ASN(E) 0 F:ASN(E) 0 MOLOC 07C123P3 07C123P2 07C123R1 05C123R1 05D123P2 07D123P3 07D123P5 F:ASN(E) 0 F:ASN(E) 1 F:ASN(E) 1 07D123P3 05D123P2 05D123P5 Cross Link ACCG Alarming From F:ASN(E) Unit F:ASN(E) 1 F:ASN(E) 1 MOLOC 05D123P2 05C123P2 External sym. reference clock Clock connections Remarks

Tab. 3.347 Cabling F:ASN(E) internal Cabling F:ASN(E) <---> F:SCB (Connector Rx, Tx)
Connector Tx= to SCB Rx= to ASN R0 T0 R0 T0 From F:ASN(E) Unit F:ASN(E)0 / GMX0 Port 0-3 F:ASN(E)0 / GMX0 Port 0-3 F:ASN(E)1 / GMX0 Port 0-3 F:ASN(E)1 / GMX0 Port 0-3 MOLOC 07C133P3 07C133P4 05C133P3 05C133P4 Unit F:SCB F:SCB F:SCB F:SCB To F:SCB MOLOC 09C169P5 09D169P1 09C231P1 09D231P2 Basic connection Remarks

Tab. 3.348 Cabling F:ASN(E) <---> F:SCB

A30828-X1160-M-2-7620

527

Construction

Maintenance Node

Cabling F:ASN(E) <---> F:SCE (Connector Rx, Tx)


Connector Tx= to SCE Rx= to ASN Connector R1/ T1- R3 / T3 R1/ T1- R3 / T3 R4/ T4- R7 / T7 R4/ T4- R7 / T7 R0/ T0- R3 / T3 R0/ T0- R3 / T3 R4/ T4- R7 / T7 R4/ T4- R7 / T7 R0/ T0- R3 / T3 R0/ T0- R3 / T3 R4/ T4- R7 / T7 R4/ T4- R7 / T7 R0/ T0- R3 / T3 R0/ T0- R3 / T3 R4/ T4- R7 / T7 R4/ T4- R7 / T7 R0/ T0- R3 / T3 R0/ T0- R3 / T3 R4/ T4- R7 / T7 R4/ T4- R7 / T7 R0/ T0- R3 / T3 R0/ T0- R3 / T3 R4/ T4- R7 / T7 R4/ T4- R7 / T7 R0/ T0- R3 / T3 R0/ T0- R3 / T3 R4/ T4- R7 / T7 R4/ T4- R7 / T7 R0/ T0- R3 / T3 R0/ T0- R3 / T3 R4/ T4- R7 / T7 R4/ T4- R7 / T7 MOLOC 07C133 05C133 07C149 05C149 07C159 05C159 07C175 05C175 07C339 05C339 07C355 05C355 07C365 05C365 07C381 05C381 07C185 05C185 07C201 05C201 07C211 05C211 07C201 05C201 07C287 05C287 07C303 05C303 07C313 05C313 07C329 05C329 From F:ASN(E) To F:SCE Remarks

Unit F:ASN(E)0 / GMX0 Port 4-15 F:ASN(E)1 / GMX0 Port 4-15 F:ASN(E)0 / GMX0 Port 16-31 F:ASN(E)1 / GMX0 Port 16-31 F:ASN(E)0 / GMX1 Port 32-47 F:ASN(E)1 / GMX1 Port 32-47 F:ASN(E)0 / GMX1 Port 48-63 F:ASN(E)1 / GMX1 Port 48-63 F:ASN(E)0 / GMX2 Port 64-79 F:ASN(E)1 / GMX2 Port 64-79 F:ASN(E)0 / GMX2 Port 80-95 F:ASN(E)1 / GMX2 Port 80-95 F:ASN(E)0 / GMX3 Port 96-111 F:ASN(E)1 / GMX3 Port 96-111 F:ASN(E)0 / GMX3 Port 112-127 F:ASN(E)1 / GMX3 Port 112-127 F:ASN(E)0 / GMX4 Port 128-143 F:ASN(E)1 / GMX4 Port 128-143 F:ASN(E)0 / GMX4 Port 144-159 F:ASN(E)1 / GMX4 Port 144-159 F:ASN(E)0 / GMX5 Port 160-175 F:ASN(E)1 / GMX5 Port 160-175 F:ASN(E)0 / GMX5 Port 176-191 F:ASN(E)1 / GMX5 Port 176-191 F:ASN(E)0 / GMX6 Port 192-207 F:ASN(E)1 / GMX6 Port 192-207 F:ASN(E)0 / GMX6 Port 208-223 F:ASN(E)1 / GMX6 Port 208-223 F:ASN(E)0 / GMX7 Port 224-239 F:ASN(E)1 / GMX7 Port 224-239 F:ASN(E)0 / GMX7 Port 240-255 F:ASN(E)1 / GMX7 Port 240-255

Unit F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE 1. 2. and 3. additional connection in GMX0 4. 5. 6. and 7. additional connection in GMX0 1. 2. 3. and 4. additional connection in GMX1 4. 5. 6. and 7. additional connection in GMX1 1. 2. 3. and 4. additional connection in GMX2 4. 5. 6. and 7. additional connection in GMX2 1. 2. 3. and 4. additional connection in GMX3 4. 5. 6. and 7. additional connection in GMX3 1. 2. 3. and 4. additional connection in GMX4 4. 5. 6. and 7. additional connection in GMX4 1. 2. 3. and 4. additional connection in GMX5 4. 5. 6. and 7. additional connection in GMX5 1. 2. 3. and 4. additional connection in GMX6 4. 5. 6. and 7. additional connection in GMX6 1. 2. 3. and 4. additional connection in GMX7 4. 5. 6. and 7. additional connection in GMX7

Tab. 3.349 Cabling F:ASN(E) <---> F:SCE

528

A30828-X1160-M-2-7620

Maintenance Node

Construction

Cabling F:ASN(E) <--> IDF (Connector CSO)


From F:ASN Connector CSO CSO Unit F:ASN(E) 1 F:ASN(E) 0 MOLOC 05C123R1 07C123R1 IDF 18x20 reference clock IDF 18x13 reference clock To IDF

Tab. 3.350 F:SCB <---> IDF (Connector CSO)

3.10.4 3.10.4.1

F:ASN(H) F:ASN(H) (module side)

D
GMX 1 GMX 0 GMX 2 GMX 3 GMX 0 GMX 1 GMX 2 C355 GMX 3 C373 ASMG ASMG C303 ACCG ACCG C339 PSAG PSAG C287

C103

C121

C139

GMX:E (Q1032)

C155

Modules with displays and switches in F:ASN(H) PSAG (Q6124) ACCG (Q145) (Q1022) ASMG16/16 (Q1034)

Tab. 3.351 Modules with displays and switches in F:ASN(H)

C191

C207

C225

C251

C269

A30828-X1160-M-2-7620

529

Construction

Maintenance Node

3.10.4.2

F:ASN(H) (backplane)
Plane 1
P1 P2
C08 R28 R24 T28 T24 R29 R25 T29 T25 R30 R26 T30 T26 R31 R27 T31 T27 B08 Ste C80 C08

Plane 0
B08 B21 Ste B80 B08 B81 B08 Ste B08 B82 R04 R00 T04 T00 R05 R01 T05 T01 R06 R02 T06 T02 R07 R03 T07 T03 R28 R24 T28 T24 R29 R25 T29 T25 R30 R26 T30 T26 R31 R27 T31 T27 R20 R16 T20 T16 R21 R17 T21 T17 R22 R18 T22 T18 R23 R19 T23 T19 B82 R12 R08 T12 T08 R13 R09 T14 T09 R04 R00 T04 T00 R05 R01 T05 T01 R06 R02 T06 T02 R07 R03 T07 T03

B08 C81 B22 Ste C82 C82 R12 R08 T12 T08 R13 R09 T13 T09

P3 P4 P5 P1 P2

R20 R16 T20 T16 R21 R17 T21 T17 R22 R18 T22 T18 R23 R19 T23 T19

C90

B90

C91 R14 R10 C92 T14 T10 R15 R11 T15 T11

B91 R14 R10 B92 T14 T10 R15 R11 T15 T11

P3 P4 P5

381

363

347

331

321

311

295

277

259

233

215

199

183

173

163

147

129

3.10.4.3

F:ASN(H) (cabling)
for example: C263P1, C263R1 P is the upper plug within one system unit; R is the lower plug within one system unit; Cabling F:ASN(H) <----> F:SCB (Connector Bxx, Cxx) Clock connections
From F:ASN(H) Connector B21 B80 C80 B81/ C81 B82 C82 B90 C90 B91 C91 B91 C91 B92 C92 Unit F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) F:ASN(H) MOLOC 07C163P1 07C173R1 07C321R1 07C173P2 07C173R2 07C321R2 07C173R1 07C321R1 07D173P2 07D321P2 07D173P2 07D321P2 07D173R2 07D321R2 F:ASN(H) F:SCB F:SCB F:SCB bas. rack F:SCB bas. rack F:SCB ext. rack 1 F:SCB ext. rack 1 F:SCE ext. rack 1 F:SCE ext. rack 1 F:SCE ext. rack 2 F:SCE ext. rack 2 07C321P2 09C263P1 09C263R1 09C169P1 09C251P1 09C169P1 09C251P1 09C241P1 09C241P2 09C241P1 09C241P2 F:SCB Unit To F:SCB MOLOC 09C191P5 Clock connections Ref. Clock sym/COAX Ref. Clock sym/COAX Ref. Clock cross over Additional ref. clock Additional ref. clock Clock connections Clock connections Clock connections Clock connections Clock connections Clock connections Clock connections Clock connections Remarks

Tab. 3.352 Cabling F:SCB <----> F:ASN(H) (Connector Bxx, Cxx)

530

A30828-X1160-M-2-7620

111

Maintenance Node

Construction

Cabling F:ASN(H) internal


From F:ASN(H) Connector B08 / C08 B08 / C08 B81 / C81 Unit F:ASN(H) F:ASN(H) F:ASN(H) MOLOC 07C163P2 07C199P2 07C173P2 Unit F:ASN(H) F:ASN(H) F:ASN(H) To F:SCB MOLOC 07C311P1 07C347P2 07C321P2 Clock connection Alarming Remarks

Tab. 3.353 Cabling F:ASN(H) internal Cabling F:ASN(H) <--> F:SCB


Connector Tx= to SCB Rx= to ASN Connector R00 / Plane 0 T00 / Plane 0 R00 / Plane 1 T00 / Plane 1 From F:ASN(H) To F:SCB Remarks

Unit F:ASN(H) / GMX0 Port 0-3 F:ASN(H) / GMX0 Port 0-3 F:ASN(H) / GMX0 Port 0-3 F:ASN(H) / GMX0 Port 0-3

MOLOC 07C111P3 07C111P4 07C259P3 07C259P4

Unit F:SCB F:SCB F:SCB F:SCB

MOLOC 09C169P5 09D169P1 09C231P1 09D231P2 Basic connections

Tab. 3.354 Cabling F:ASN(H) <---> F:SCB Cabling F:ASN(H) <---> F:SCE
Connector Tx= to SCE Rx= to ASN Connector R01/ T01- R03 / T03 R01/ T01- R03 / T03 R04/ T04- R07 / T07 R04/ T04- R07 / T07 R08/ T08- R11 / T11 R08/ T08- R11 / T11 R12/ T12- R15 / T15 R12/ T12- R15 / T15 R16/ T16- R19 / T19 R16/ T16- R19 / T19 R20/ T20- R23 / T23 R20/ T20- R23 / T23 MOLOC 07C111 07C259 07C129 07C277 07C147 07C295 07C163 07C311 07C183 05C331 07C199 05C347 From F:ASN(H) To F:SCE Remarks

Unit F:ASN(H) / GMX0 Port 4-15 F:ASN(H) / GMX0 Port 4-15 F:ASN(H) / GMX0 Port 16-31 F:ASN(H) / GMX0 Port 16-31 F:ASN(H) / GMX1 Port 32-47 F:ASN(H) / GMX1 Port 32-47 F:ASN(H) / GMX1 Port 48-63 F:ASN(H) / GMX1 Port 48-63 F:ASN(H) / GMX2 Port 64-79 F:ASN(H) / GMX2 Port 64-79 F:ASN(H) / GMX2 Port 80-95 F:ASN(H) / GMX2 Port 80-95

Unit F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE F:SCE 1. 2. and 3. additional connection in GMX0 4. 5. 6. and 7. additional connection in GMX0 1. 2. 3. and 4. additional connection in GMX1 4. 5. 6. and 7. additional connection in GMX1 1. 2. 3. and 4. additional connection in GMX2 4. 5. 6. and 7. additional connection in GMX2

Tab. 3.355 Cabling F:ASN(H) <---> F:SCE

A30828-X1160-M-2-7620

531

Construction

Maintenance Node

Connector Tx= to SCE Rx= to ASN Connector R24/ T24- R27 / T27 R24/ T24- R27 / T27 R28/ T28- R31 / T31 R28/ T28- R31 / T31 MOLOC 07C215 05C363 07C233 05C381

From F:ASN(H)

To F:SCE

Remarks

Unit F:ASN(H) / GMX3 Port 96-111 F:ASN(H) / GMX3 Port 96-111 F:ASN(H) / GMX3 Port 112-127 F:ASN(H) / GMX3 Port 112-127

Unit F:SCE F:SCE F:SCE F:SCE 1. 2. 3. and 4. additional connection in GMX3 4. 5. 6. and 7. additional connection in GMX3

Tab. 3.355 Cabling F:ASN(H) <---> F:SCE

532

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.11
3.11.1

F:STMI
F:STMI (module side)
LTG number 1-16 LTG number 17-32

D
LTU:S LTU:S LTU:S LTU:S LTU:S LTU:S LTU:S LTU:S GPSx GPSx GPSx GPSx GPSx GPSx GPSx GPSx STMI STMI STMI C331 STMI C343

C101

C113

C125

C137

C153

C165

C177

C189

C201

C213

C231

C243

C255

C267

C283

C295

C307

GPSx types GPSF (-Q278-X000-) GPSG (-Q278-X100-) GPSH (-Q278-X200-) GPSI (-Q278-X300-)

Remarks with 4 LTG functions, 128 Mbyte memory, SILC, MDTOG, 63 x E1 with 4 LTG functions, 256 Mbyte memory, SILC, MDTOG, 63 x E1 with 4 LTG functions, 512 Mbyte memory, SILC, MDTOG, 63 x E1 with 4 LTG functions, 1 Gbyte memory, SILC, MDTOG, 63 x E1

Tab. 3.356 Basic types of GPS modules

Modules LTU:S ATCO (-Q267-) DEC120 (-Q1467-) MCT (-Q63-) PHMA (-Q1469-)

Remarks Automatic Test and Conference Unit for LTGM/N Digital Echo Compensator Mid Call Trigger Packet Handler Module A (High performance SILC)

Tab. 3.357 Modules with display and switches in LTU:S

STMI types STMI:E(W) (-Q300-) STMI:E(P) (-Q301-) STMI:O(W) (-Q298-) STMI:O(P) (-Q299-)

Remarks working module with electrical interface protection module with electrical interface working module with optical interface protection module with optical interface

Tab. 3.358 Basic types of STMI modules

C319

A30828-X1160-M-2-7620

533

Construction

Maintenance Node

3.11.2

LTU-Types for LTG in B operation


LTUType D30 ANWG 0 CASCAS CCSCAS CCSCCS CASRCA CCSDLU EXTDLU V52IF CCSPA ATE ATM V01 V02 V03 V03 V04 V05 V05 V06 V08 V09 V09 V10 V10 V11 V15 V99 Y25 MCT INS PMA X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 1 X X X X X X X X LTU-Number 2 X X X X X X X X 3 X X X X X X X X X X X X X X X X X 4 5 6 7 SU 0/1 connection of PCM30 with CAS connection of PCM30 with CCS/CAS connection of PCM30 with CCS announcement connection connection DLU with CCS connection DLU (extension) V5.2 interface primary rate access connection ATEMAIN, M:ATCO in LTU:S (1) ATETM, M:ATCO in LTU:S (1) code receiver for MFC:R2 code receiver push button dialing CRP code receiver push button dialing CRP TLFB trunk test with SULIM ETEAE version13, without HW Responder Test transformer, without HW code receiver for MFC:R1 (a-law) test position TWS/LWS (2) code receiver push button dialing CRP TLF/RBS wake up service / RSCI CME TWS/LWS MDTOG CTC only in SU 0 COU, M:ATCO in LTU:S (1) M:MCT in LTU:S SILC-function on GP M:PHMA in LTU:S (expanded SILC-function) Remarks

Tab. 3.359 LTU-Types for LTG in B operation (1) By use of M:ATCO: The ATE functions occupies the LTU5. The COU functions always uses LTU3. Both functionalities of the ATCO module can work simultaneously in B operation (2) LTU3 must be kept free when LTU type V08 is created

534

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.11.3

LTU-Types for LTG in C operation


LTUType D30 ANWG 0 CASCAS CCSCAS CCSCCS CASRCA ATE ATM V01 V02 V04 V05 V05 V06 V08 V10 V10 V11 V99 Y25 MCT x X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 1 X X X X LTU-Number 2 X X X X 3 X X X X X X X X X X 4 7 SU 0/1 4/5 connection of PCM30 with CAS connection of PCM30 with CCS/CAS connection of PCM30 with CCS primary rate access connection ATEMAIN, M:ATCO in LTU:S (1) ATETM, M:ATCO in LTU:S (1) code receiver for MFC:R2 code receiver push button dialing CRP ETEAE version13, without HW Responder Test transformer, without HW code receiver for MFC:R1 (a-law) test position TWS/LWS wake up service Software Loop TWS/LWS RM:CTC only in SU module 0 COU, M:ATCO in LTU:S (1) M:MCT in LTU:S Remarks

Tab. 3.360 LTU-Types for LTG in C operation (1) By use of M:ATCO: The ATE functions occupies the LTU3. The COU functions always uses LTU3. Both functionalities of the ATCO module can not work simultaneously in C operation. The two functions ATE and COU must work separately.

A30828-X1160-M-2-7620

535

Construction

Maintenance Node

3.11.4

F:STMI (backplane)

CCG3 CCG2 CCG1 CCG0 SDC3 SDC2 SDC1 SDC0

CCG3 CCG2 CCG1 CCG0 SDC3 SDC2 SDC1 SDC0

SDC3 SDC2 SDC1 SDC0

INF4

SDC3 SDC2 SDC1 SDC0

SDC3 SDC2 SDC1 SDC0

SDC3 SDC2 SDC1 SDC0

P1 P2

SNOPT-0

P3 P4 P5

X2

SNOPT-0

X1

SDC3 SDC2 SDC1 SDC0

X1 X2

SDC3 SDC2 SDC1 SDC0

SDC3 SDC2 SDC1 SDC0

SDC3 SDC2 SDC1 SDC0

SDC3 SDC2 SDC1 SDC0

SDC3 SDC2 SDC1 SDC0

P1 P2

SDC3 SDC2 SDC1 SDC0

D
P3 P4

183 177

283

275

153

313 307

255 251

145

SDC3 SDC2 SDC1 SDC0

343

331

231

213

201

3.11.5

F:STMI (cabling)
Connector X1 / X2 X1 / X2 INF1 INF2 INF3 INF4 SNOPT- 0 SNOPT- 1 SNOPT- 0 SNOPT- 1 CCG0 CCG1 CCG2 CCG3 CCG0 CCG1 CCG2 CCG3 MOLOC C121P1 C251P1 C201P1 C213P1 C331P1 C343P1 C145P2 D145P1 C275P2 D275P1 C183P1 C183P2 C183P3 C183P4 C313P1 C313P2 C313P3 C313P4 Port Power supply Power supply optical/electrical optical/electrical optical/electrical optical/electrical Optolink Optolink Optolink Optolink CCKL0 CCKL1 CCKL2 CCKL3 CCKL0 CCKL1 CCKL2 CCKL3 Connection To the breaker panel of the rack To the breaker panel of the rack Interface transport 63x E1 Interface transport 63x E1 Interface transport 63x E1 Interface transport 63x E1 SDC 00-15 shelf 0 --> F:SNMUX(B) SN 0 SDC 00-15 shelf 0 --> F:SNMUX(B) SN 1 SDC 16-31 shelf 1 --> F:SNMUX(B) SN 0 SDC 16-31 shelf 1 --> F:SNMUX(B) SN 1 Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG Reference clock to central clock generator CCG

Tab. 3.361 F:STMI (cabling)

536

A30828-X1160-M-2-7620

125 121

101

SDC3 SDC2 SDC1 SDC0

SNOPT-1

SNOPT-1

SDC3 SDC2 SDC1 SDC0

INF3

INF2

INF1

Maintenance Node

Construction

Connector SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3

MOLOC C101P1 C101P2 C101P3 C101P4 D101P1 D101P2 D101P3 D101P4 C125P1 C125P2 C125P3 C125P4 D125P1 D125P2 D125P3 D125P4 C153P1 C153P2 C153P3 C153P4 D153P1 D153P2 D153P3 D153P4 C177P1 C177P2 C177P3 C177P4 D177P1 D177P2 D177P3 D177P4 C231P1 C231P2 C231P3 C231P4

Port SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3

Connection SDC- interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC- interface of LTG 0, 1, 2, 3 GPP --> SN 1

SDC- interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC- interface of LTG 0, 1, 2, 3 GPP --> SN 1

SDC- interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC- interface of LTG 0, 1, 2, 3 GPP --> SN 1

SDC- interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC- interface of LTG 0, 1, 2, 3 GPP --> SN 1

SDC- interface of LTG 0, 1, 2, 3 GPP --> SN 0

Tab. 3.361 F:STMI (cabling)

A30828-X1160-M-2-7620

537

Construction

Maintenance Node

Connector SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2 SDC3 SDC0 SDC1 SDC2

MOLOC D231P1 D231P2 D231P3 D231P4 C255P1 C255P2 C255P3 C255P4 D255P1 D255P2 D255P3 D255P4 C283P1 C283P2 C283P3 C283P4 D283P1 D283P2 D283P3 D283P4 C307P1 C307P2 C307P3 C307P4 D307P1 D307P2 D307P3

Port SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2 SDC 1-3 SDC 0-0 SDC 0-1 SDC 0-2 SDC 0-3 SDC 1-0 SDC 1-1 SDC 1-2

Connection SDC- interface of LTG 0, 1, 2, 3 GPP --> SN 1

SDC- interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC- interface of LTG 0, 1, 2, 3 GPP --> SN 1

SDC- interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC- interface of LTG 0, 1, 2, 3 GPP --> SN 1

SDC- interface of LTG 0, 1, 2, 3 GPP --> SN 0

SDC- interface of LTG 0, 1, 2, 3 GPP --> SN 1

Tab. 3.361 F:STMI (cabling)

538

A30828-X1160-M-2-7620

Maintenance Node

3.12.2

3.12.1

3.12

A30828-X1160-M-2-7620 B A 3.12.1 3.12.2 3.12.3


A001 DCCCR IOC:SYPC COM:SYPC RM:EA T/RM:SYPC (0) T/RM:SYPC (1) TXA:SYPC A013 A019 A025 A031 A037 A043

F:SYPC(A)

DCCCR (-Q5619-)

TXA:SYPC (-Q759-)

COM:SYPC (-Q758-)

CDEX9 / B109

CDEX8 / B103

CDEX7 / B097

F:SYPC(A) (backplane)

CDEX6 / B091

F:SYPC(A) (module side)

CDEX5 / B085

F:SYPC(A) (module side) F:SYPC(A) (backplane) F:SYPC(A) (cabling)

RM:EA (-Q760-)

CDEX4 / B079

DCCCL (-Q5619-L)

CDEX3 / B073

CDEX2 / B067 CDEX1 / B064

CDEX1 / B061 CDEX0 / B058

CDEX0 / B055

EXT2 / B046

T/RM:SYPC (-Q761-)

Tab. 3.362 Modules with displays and switches in F:SYPC(A)

SYPD3 / B040

Modules with displays and switches in F:SYPC(A)

SYPD0 / B034

MDF / B028

IOP1 / B016

T/RM:SYPC (-Q761-X100-)

CDEX (-Q900-X100-)

IOP0 / B010

B
A055 CDEX0 CDEX1 CDEX2 CDEX3 CDEX4 A085 A091 A097 A103 A109 A116 CDEX5 CDEX6 CDEX7 CDEX8 CDEX9 DCCCL A061 A067 A073 A079 CDEX (-Q900-)

MDF / A119

CDEX9 / A109

CDEX8 / A103

CDEX7 / A097

CDEX6 / A091

CDEX5 / A085

CDEX4 / A079

CDEX3 / A073

CDEX2 / A067 CDEX1 / A064

CDEX1 / A061 CDEX0 / A058 CDEX0 / A055

EXT1 / A046

SYPD1 / A040

SYPD2 / A034

MDF / A028

MDF ext / A022

IOP1 / A016

Construction

IOP0 / A010

539

Construction

Maintenance Node

3.12.3

F:SYPC(A) (cabling)
Connector IOP0 / A010 IOP0 / B010 IOP1 / A016 IOP1 / B016 MDF ext / A022 MDF / A028 MDF / B028 SYPD2 / A034 SYPD0 / B034 SYPD1 / A040 SYPD3 / B040 EXT1 / A046 EXT2 / B046 CDEX0 / A055 CDEX0 / B055 CDEX0 / A058 CDEX0 / B058 CDEX1 / A061 CDEX1 / B061 CDEX1 / A064 CDEX1 / B064 CDEX2 / A067 CDEX2 / B067 CDEX3 / A073 CDEX3 / B073 CDEX4 / A079 CDEX4 / B079 CDEX5 / A085 CDEX5 / B085 CDEX6 / A091 CDEX6 / B091 CDEX7 / A097 CDEX7 / B097 CDEX8 / A103 CDEX8 / B103 CDEX9 / A109 CDEX9 / B109 F:SYPC(A) Cable from CP-IOP0 / PIOP(A) / PIOP(B) Cable from CP-IOP0 / PIOP(A) / PIOP(B) Cable from CP-IOP1 / PIOP(A) / PIOP(B) Cable from CP-IOP1 / PIOP(A) / PIOP(B) MDF connection for external alarms (MDF ext) MDF connection for SYPD0 ... 3 MDF connection for SYPD4 ... 7 Direct connection for SYPD2 or CT Direct connection SYPD0 Direct connection for SYPD1 Direct connection for SYP3 Connector for external fault signaling unit (AL1A ...AL12B) Connector for external fault signaling unit (AL13A ...AL24B) Clock output from CDEX0 Clock output from CDEX0 Clock input: CCG0 for CDEX0 Clock input: CCG1 for CDEX0 Clock output from CDEX1 Clock output from CDEX1 Clock input: CCG0 for CDEX1 Clock input: CCG1 for CDEX1 Clock output from CDEX2 Clock output from CDEX2 Clock output from CDEX3 Clock output from CDEX3 Clock output from CDEX4 Clock output from CDEX4 Clock output from CDEX5 Clock output from CDEX5 Clock output from CDEX6 Clock output from CDEX6 Clock output from CDEX7 Clock output from CDEX7 Clock output from CDEX8 Clock output from CDEX8 Clock output from CDEX9 Clock output from CDEX9

Tab. 3.363 Cabling F:SYPC(A)

540

A30828-X1160-M-2-7620

Maintenance Node

Construction

Connector MDF / A119

F:SYPC(A) MDF connection for CDEX alarm outputs

Tab. 3.363 Cabling F:SYPC(A)

A30828-X1160-M-2-7620

541

Construction

Maintenance Node

3.13

Fan
3.13.1 3.13.2 3.13.3 3.13.4 3.13.5 3.13.6 FAN (B5681) FAN-BOX (B5877) FAN-BOX (U102) FANTRAY (U103) (U2620) FAN (U2623) FAN-BOX (U2624)

3.13.1

FAN (B5681)

RUN

M5

M4

M3

M2

M1

M6

M7

M8

M9

M10

542

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.13.2

FAN-BOX (B5877)

Achtung vor dem Filterwechsel ist die Fanbox auszuschalten Caution Before changing the filter switch off the fan box

M4

M3

M1

M5

M6

M2

A30828-X1160-M-2-7620

543

Construction

Maintenance Node

3.13.3

FAN-BOX (U102)

1
RUN

Achtung vor dem Filterwechsel ist die Fanbox auszuschalten Caution Before changing the filter switch off the fan box

M5

M6

M7

M8

M4

M3

M2

M1

power supply

alarm circuit

power supply

544

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.13.4

FANTRAY (U103) (U2620)

RUN

M5

M4

M3

M2

M1

M6

M7

M8

M9

M10

power supply

alarm circuit

power supply

ALARM

A30828-X1160-M-2-7620

545

Construction

Maintenance Node

3.13.5

FAN (U2623)

M5

M4

M3

M2

M1

M6

M7

M8

M9

M10

power supply

alarm circuit

power supply

ALARM

546

A30828-X1160-M-2-7620

Maintenance Node

Construction

3.13.6

FAN-BOX (U2624)

RUN

Achtung vor dem Filterwechsel ist die Fanbox auszuschalten Caution Before changing the filter switch off the fan box

M4

M3

M1

M5

M6

M2

power supply

alarm circuit

power supply

A30828-X1160-M-2-7620

547

Construction

Maintenance Node

4 Modules
4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12 4.13 4.14 CCG CCS7 CP113 DCC DLU LTG MB RSU SDHI SMSC SN SSNC STMI SYP

548

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.1

CCG
4.1.1 4.1.2 4.1.3 4.1.4 4.1.5 4.1.6 4.1.7 CCGES (-Q146-) CCGED (-Q147-) CCGB (-Q887-) CCGXXA (-Q888-) CDEX (-Q900-) CDEX (-Q900-X100-) CDEX (-Q900-X200-)

A30828-X1160-M-2-7620

549

Construction

Maintenance Node

4.1.1

CCGES (-Q146-)
CCGES
RESET

Synchronization modules ES

Key
RUN ERR STAT

Reset module with bootstrap

q q q q q q

q q q q q q

R1 R2 R3 R4 GPS

LED see: LED description

SYNC HOLD MODE ACT DISAB OUT

qq qq

SIG1

Test jack V24 Test jack

For control measurement V24 Interface for connecting a service PC For control measurement

SIG2

DEBUG

V24

DEBUG

Test adapter interface

LED STAT

green on on off flashing off off on on an

red Normal operation

Description

In operation, error occurred, partial failure possible Total failure Boot process running Boot error Good reference detected and selected for synchronization Good reference detected, standby for synchronization Reference detected but not suitable for synchronization Reference signal not detected or not available Good reference detected and selected for synchronization Good reference detected, standby for synchronization Reference detected but not suitable for synchronization Reference signal not detected or not available Synchronized to reference (*) Capture process, synchronization to reference in progress Hold-over, no synchronization Warming-up phase, output signal not standard

flashing off on on off off on on off off on an off

R1...R4

on on off off

GPS

on on off off

MODE

on on off off

Tab. 4.1

LED description

550

A30828-X1160-M-2-7620

Maintenance Node

Construction

LED OUT

green on off off off on off

red

Description Clock outputs: EWSD and T3 active Clock outputs: disabled (DISAB/MBL) Clock outputs: EWSD standby / T3 active

Tab. 4.1

LED description

(*) If no reference is available, i.e. the green LEDs of R1...R4 and GPS are off, the module can still operate in synchronism if synchronization is possible via the redundant unit (slave mode). Likewise, capture or pull-in is possible after a brief error on the input signal, although the reference remains selected.

4.1.2

CCGED (-Q147-)
CCGED

Synchronization modules ED

RUN ERR

RUN LED ERR LED

RUN on: CCGED in operation ERR on: CCGED disabled

q q

T3CLK

Test jack

T3 output

A30828-X1160-M-2-7620

551

Construction

Maintenance Node

4.1.3

CCGB (-Q887-)
CCGB Central Clock Generator B

green LED
S

M on: CCG(A) is MASTER (clock output enabled) S on: CCG(A) is SLAVE (clock output disabled) DIS on: module CCGB is disabled. No clock distribution is possible. CCG(A) is configured to UNA or MBL. DEF on: module CCGB is defective. The CCG(A) is configured to UNA or MBL

yellow LED
DIS

red LED
UNA

red LED

VCO

Test jack

Jack VCO for checking the frequency of the CCGB oscillator (nominal frequency/output frequency generated by the CCG is 2048kHz).

CCGB
S3 S2 S1

There are 4 DIP-FIX switches mounted on every CCGB module: S1, ..., S4. S1, S2, and S3: are always closed. These switches are not used at present. S4: Contact 1-3 are closed for 8kHz clock to CP113.

DIP-FIX switches

3 S4 12

552

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.1.4

CCGXXA (-Q888-)

CCGXXA

Central Clock Generator XXA

0 REF 1

q q q q
MODE

green LED red LED

REF see: Interpretation of LED indicating REF on the module faceplate

qP q 1 qF q2 qA q 3 qB q 4
CRA

red LED red LED red LED red LED

MODE see: Interpretation of LED indicating MODE on the module faceplate

q q
AL

yellow / red LED CRA see: Interpretation of LED indicating CRA on the module faceplate red LED AL see: Interpretation of LED AL on the module faceplate Test jack Test jack Test jack Test jack Test jack Test jack Test jack Test jacks see: Use of jacks on the module faceplate

VCO REF0 LO GND REF1 L1 GND

REF red LED off off on on green LED off on off on Interpretation for state of reference clock signals 0 (left) and 1 (right) Reference frequency not in use or not indented for use Reference frequency good and in use Reference frequency faulty (for more than 128 seconds) Reference frequency faulty (for less than 128 seconds

Tab. 4.2

Interpretation of LED indicating REF on the module faceplate

Mode LED Meaning Interpretation for state of sychronization and operating mode on P Plesiochronous mode Free running mode Plesiochronous mode; no reference frequency is expected or used. Free running mode; no reference frequency is used (at this time). off Synchronous mode; a reference frequency is expected and used. A reference frequency is used.

Tab. 4.3

Interpretation of LED indicating MODE on the module faceplate

A30828-X1160-M-2-7620

553

Construction

Maintenance Node

Mode LED Meaning Interpretation for state of sychronization and operating mode on A Lock phase A Lock phase A (=transient condition with P regulation, i.e. coarse regulation) with respect to an applied reference frequency. Lock phase B (=transient condition with PI regulation, i.e. fine tuning) with respect to an applied reference frequency. 1-4 Synchronization states 1 to 4 Only one of these LED is lit at any one time. It indicates the synchronization state (ascending from 1 to 4) of the CCGXXA frequency with respect to the reference frequency. in all other states. off

Lock phase B

in all other states.

Tab. 4.3

Interpretation of LED indicating MODE on the module faceplate

CRA yellow LED red LED Interpretation for state of regulation characteristics (use of possible range) less than 75% between 75% and 88% between 88% and 100% 100% (Note: LED AL is on)

off on off on

off off on on

Tab. 4.4

Interpretation of LED indicating CRA on the module faceplate

AL LED AL on Interpretation General CCGXXA alarm: Module CCGXXA is not functioning correctly or the power supply to module CCGXXA was not provided continuously throughout the last 30 minutes (or was switched on less than 30 minutes ago). CCG(A) is configured to UNA or MBL. In all other states of CCG(A), LED AL is off.

off

Tab. 4.5

Interpretation of LED AL on the module faceplate

554

A30828-X1160-M-2-7620

Maintenance Node

Construction

Test jack VCO

Use Test jack for checking the frequency of the CCGXXA oscillator. The nominal frequency is 4096 kHz. Test jacks for checking the first reference frequency (REF0), if applied, or the second reference frequency (REF1)

REF0 / REF1

L0 / L1 and asso- If one or more reference frequencies are applied, this pair of jacks can be used to meaciated jacks with sure the input level of the first (L0) or second (L1) reference frequency. When measuring ground potential current in the 100A range, values of between 40 A and 120 A indicate a satisfactory input level.

Tab. 4.6

Use of jacks on the module faceplate

CCGXXA
S3 S2 S1

Settings of the DIP-FIX (see 4.1.4.1) Settings of the DIP-FIX switches and solder pins on the input modules (see 4.1.4.2)

DIP-FIX switches S5 2 3 S4 1

Input module 1 Reference frequency 0/2 Input module 2 Reference frequency 1/3

CCGXXA Variants according to the input module used (see 4.1.4.7)

4.1.4.1

CCGXXA: Settings of DIP-FIX Switches


S1, S2, S3: The M:CCGXXA microprocessor is shown via switches S1 and S2 whether the reference frequencies 0 and/or 1 are to be used for synchronization. A precondition is that the M:CCGXXA is equipped with input modules. These switches are not in the line designation for the reference frequency. Both switch must be closed in standard practice (two input modules on CCGXXA) and for allocation with two reference frequencies. In plesiochronous CCG is to be pulled (e.g. CCG-0 synchronizes CCG-1), switches S1 and S2 on the CCGXXA are open in CCG-0. If a plesiochronous CCG is to be pulled at regular intervals (e.g. every three months) with a rubidium standard at a greater frequency accuracy, the cable plug must be plugged into the backplane plug-in position C187 in F:SMSC(C) of the M:CCGXXA. The CCG-0 detects the reference frequency (with switch S1 open) and synchronizes to the reference frequency of the rubidium standard. Switch S3 is used to define the priority of the applied reference frequencies.

A30828-X1160-M-2-7620

555

Construction

Maintenance Node

S1 closed: open: S2 closed: open: S3 closed: open: S4: always closed

Input module 1 is installed and the associated external reference frequency is connected for possible use. Input module 1 is not installed or there is no associated external reference frequency present. Input module 2 is installed and the associated external reference frequency is connected for possible use Input module 2 is not installed or there is no associated external reference frequency present. The reference frequency from input module 1 has priority. The reference frequency from input module 2 has priority.

This switch connects the control voltage from the DAC output to the VCO input. S5: 8,192 MHz or a 4,096 MHz-VCO may be used on the module CCGXXA. Contacts 1 - 3 are closed when a 8,192 MHz-VCO is used. Contacts 2 - 3 are closed when a 4,096 MHz-VCO is used.

4.1.4.2

DIP-FIX Switches and Solder Pins on the Input Modules


A pair of CCG(A)s in an exchange can be synchronized by a maximum of four external reference frequencies - two reference frequencies can be connected to each CCGXXA module. Each CCGXXA module is equipped with two specific input modules for this purpose. Both unbalanced (coaxial) and balanced (two-wire) lines can be connected to the inputs. Input modules

F EDC (solder pins)

DIP-FIX-Switch 7 2 1 3

DIP-FIX-Switch 8 1

556

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.1.4.3

Input Module Type 1 (D319)


Input module type 1 can receive an external reference frequency of 2.048 MHz or 300 kHz. In the digital interface DIU30, 2048 MHz can be either extracted from the 2.408 MBit/s signal (PCM30) or it can be switched on by SDH transmission equipment, atomic frequency standards or other reference clock sources. The module can be set to: a) Operating variant 300 kHz, unbalanced: DIP-FIX 7: position 1-2 DIP-FIX 8: open D-E-F soldered in b) Operating variant 300 kHz, balanced: DIP-FIX 7: position 1-2 DIP-FIX 8: open C-D soldered in c) Operating variant 2048 kHz, unbalanced: DIP-FIX 7: position 1-3 DIP-FIX 8: closed D-E-F soldered in d) Operating variant 2048 kHz, balanced: DIP-FIX 7: position 1-3 DIP-FIX 8: closed C-D soldered in

4.1.4.4

Input Module Type 2 (D320)


Input module type 2 can receive an external reference frequency of 5 or 10 MHz. This module is used, when an atomic frequency standard has only a 5 MHz/10MHz clock output interface. This module has no solder pins. The module can be set to: a) Operating variant 5 MHz, unbalanced: DIP-FIX 7: position 1-2 DIP-FIX 8: open No soldered links b) Operating variant 10 MHz, unbalanced: DIP-FIX 7: position 1-2 DIP-FIX 8: open No soldered links

4.1.4.5

Input Module Type 3 (D337)


Input module type 3 can receive an external reference frequency of 308 MHz or 1544 kHz. In the digital interface DIU24, 2048 MHz can be either extracted from the 2.408 MBit/s signal (PCM24) or it can be switched on by SDH transmission equipment, atomic frequency standards or other reference clock sources. The module can be set to: a) Operating variant 308 kHz, unbalanced: DIP-FIX 7: position 1-2 DIP-FIX 8: open D-E-F soldered in

A30828-X1160-M-2-7620

557

Construction

Maintenance Node

b) Operating variant 308 kHz, balanced: DIP-FIX 7: position 1-2 DIP-FIX 8: open C-D soldered in c) Operating variant 1544kHz, unbalanced: DIP-FIX 7: position 1-3 DIP-FIX 8: closed D-E-F soldered in d) Operating variant 1544 kHz, balanced: DIP-FIX 7: position 1-3 DIP-FIX 8: closed C-D soldered in

4.1.4.6

CCGXXA Variants According to the Input Module Used


The numbers used in place of XX in the module name CCGXXA and the part -Xxx- of the serial number of this module vary according to the Types of the two input modules used. Example: S30810-Q888-Xxx-x/xx (xs represent variables) Type 1 Type 2 Type 3 (D319) (D320) (D337) for for for 300 kHz / 2048 kHz 5000 kHz/100000 kHz 308 kHz / 1544 kHz

The following allocation table applies to:


Input module 1 Input module 2 CCGXXA name CCG11A CCG13A CCG22A CCG33A X4 X11 X8 X7 S30810-Qxxxx -...-x/xx

Type 1 (D319) Type 1 (D319) Type 2 (D320) Type 3 (D337)

Type 1 (D319) Type 3 (D337) Type 2 (D320) Type 3 (D337)

Tab. 4.7

CCGXXA variants

4.1.4.7

Assignment of CCGXXA-Reference Frequency Inputs


0 Reference Frequencies: Plesiochronous Mode In plesiochronous mode, CCG(A)-0 and CCG(A)-1 operate differently CCG(A)-0: operates in plesiochronous mode; Input module 1 is installed so that the necessary periodic adjustment of the CCG(A) frequencies. (Switch S1 on module CCGXXA is open) Input module 2 is not required. operates in synchronous mode as slave to CCG(A)-0 with a predefined synchronization frequency of 2048 kHz via input module Input module 2 is not required. (CCGXA = CCG10A)

CCG(A)-1

558

A30828-X1160-M-2-7620

Maintenance Node

Construction

1 - 4 Reference Frequencies: Synchronous Mode


Number of reference frequencies IM-1 1 2 3 4 P1 P1 P2 P1 P2 P1 P2 CCG(A)-0 IM-2 P1 P1 P3 P3 P2 P1 P4 IM-1 CCG(A)-1 IM-2

Tab. 4.8

Distribution of priorities of the reference frequencies

Number of reference frequencies IM-1 1 2 3 4 Ref-0* Ref-0* Ref-0* Ref-0*

CCG(A)-0 IM-2 IM-1 Ref-0 Ref-1 Ref-1 Ref-3* Ref-0 Ref-2* Ref-2*

CCG(A)-1 IM-2

Ref-1* Ref-1* Ref-1*

Tab. 4.9

Distribution of the reference frequencies

*) The reference frequencies marked * are connected directly to this CCG(A); those not marked are received via cable from the output of the partner CCG(A)

4.1.5

CDEX (-Q900-)
CDEX Clock Distributor External

REF0 REF1

yellow LED yellow LED

RF0 on: Synchronization clock from CCG0 (Clock 0). RF1 on: Synchronization clock from CCG1 (Clock 1). SYN flashing 9 seconds: during clock switchover SYN off: clock switch successful SYN on: no clock CD on: distributed clock available

SYN

q
CD

red LED green LED

ALT

Key

ALT key: This key is used to check the monitoring functions manually. While the key is held down a) a failure of the CDEX oscillator is simulated i.e. the green LED CD goes out. b) a total incoming clock pulse failure and a PLL i.e. the red LED SYN lights up. When the key is released, the PLL synchronous failure alarm is reset for approx. 9 seconds; during this time the red LED SYN flashes.

A30828-X1160-M-2-7620

559

Construction

Maintenance Node

CDEX

49 T2 DP1 T3 DP2 T4 DP3 T5 DP4 52 31 249 250 229 251 252 231 50 29 51

Clock Distributor External Transformers T2, T3,T4, T5 DIP-Fix switches DP 1, DP2, DP 3, DP4 The 2048 kHz clock pulse is distributed via the four output transformers T2 up to 5 of the CDEX module. The secondary side is symmetrical. In case of a symmetrical connection the cable must not be connected to pin 29, 31, 229 or 231. If, however, the connection is to be via an unbalanced cable, the appropriate DIP-FIX switch (DP1, DP2, DP3 or DP4) must be closed: Assignment of Clock outputs to module pins DP 1 straps pin 29 and 50 to ground. DP 2 straps pin 31 and 52 to ground. DP 3 straps pin 229 and 250 to ground. DP 4 straps pin 231 and 252 to ground.

560

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.1.6

CDEX (-Q900-X100-)
CDEX Clock Distributor External

REF0 REF1

q q SYN q
CD ALT

yellow LED yellow LED red LED green LED Key

RF0 on: Synchronization clock from CCG0 (Clock 0). RF1 on: Synchronization clock from CCG1 (Clock 1). SYN flashing 9 seconds: during clock switchover SYN off: clock switch successful SYN on: no clock CD on: distributed clock available ALT key: This key is used to check the monitoring functions manually. While the key is held down a) a failure of the CDEX oscillator is simulated i.e. the green LED CD goes out. b) a total incoming clock pulse failure and a PLL i.e. the red LED SYN lights up. When the key is released, the PLL synchronous failure alarm is reset for approx. 9 seconds; during this time the red LED SYN flashes.

CDEX

49 T2 DP1 T3 DP2 T4 DP3 T5 DP4 52 31 249 250 229 251 252 231 50 29 51

Clock Distributor External Transformers T2, T3, T4, T5 DIP-Fix switches DP 1, DP2, DP 3, DP4 The 2048 kHz clock pulse is distributed via the four output transformers T2 up to 5 of the CDEX module. The secondary side is symmetrical. In case of a symmetrical connection the cable must not be connected to pin 29, 31, 229 or 231. If, however, the connection is to be via an unbalanced cable, the appropriate DIP-FIX switch (DP1, DP2, DP3 or DP4) must be closed: Assignment of Clock outputs to module pins DP 1 straps pin 29 to ground. DP 2 straps pin 31 to ground. DP 3 straps pin 229 to ground. DP 4 straps pin 231 to ground.

A30828-X1160-M-2-7620

561

Construction

Maintenance Node

4.1.7

CDEX (-Q900-X200-)
CDEX Clock Distributor External

REF0

yellow LED
REF1

RF0 on: Synchronization clock from CCG0 (Clock 0). RF1 on: Synchronization clock from CCG1 (Clock 1). SYN flashing 9 seconds: during clock switchover SYN off: clock switch successful SYN on: no clock CD on: distributed clock available ALT key: This key is used to check the monitoring functions manually. While the key is held down a) a failure of the CDEX oscillator is simulated i.e. the green LED CD goes out. b) a total incoming clock pulse failure and a PLL i.e. the red LED SYN lights up. When the key is released, the PLL synchronous failure alarm is reset for approx. 9 seconds; during this time the red LED SYN flashes.

yellow LED
SYN

q
CD

red LED green LED

ALT

Key

CDEX

T1

49 50 29 51

Clock Distributor External Transformers T1, T2, T3, T4 Switches S2 and S3 The 2048 kHz clock pulse is distributed via the four output transformers T1 up to 4 of the CDEX module. The secondary side is symmetrical. In case of a symmetrical connection the cable must not be connected to pin 29, 31, 229 or 231. If a coaxial cable is used for the connection, the relevant DIP-Fix switch (S2, S3) should only be closed if the cable shield is to be grounded.

T2 1 2 T3

S2
4 3

52 31 249 250 229 251

T4 1 2

S3
4 3

252 231

562

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.2

CCS7
4.2.1 4.2.2 4.2.3 4.2.4 4.2.5 4.2.6 4.2.7 MH:SIMP (-Q1017-) MUXMA (-Q1117-) PMU:CPI (-Q1180-) PMU:SIMP (-Q1179-) SILTC (-Q766-) SILTD (-Q1023-) SIPA (-Q1016-)

4.2.1

MH:SIMP (-Q1017-)
MH:SIMP LED1

Message Handler for signaling management Processor yellow LED LED on: during recovery LED off: after recovery, normal operation switch S1: resets the MH:SIMP (SIMP) and starts the self-test

q
S1

switch

V24

V24 interface

4.2.2

MUXMA (-Q1117-)
MUXMA LED1

Master Multiplexer Module A Watchdog status: LED 1 on, if the watchdog function has been canceled. Status display SN: LED 2 on, briefly after S1 is switched or LED flashes continuously if the SN is in OST UNA or MBL. S1: resets the MUXM and starts the self-test

q
LED2

red LED

q
S1 V24

yellow LED

switch

V24 interface

S2

switch

activates/deactivates the watchdog function, for normal operation, the watchdog must be activated (LED 1 off).

A30828-X1160-M-2-7620

563

Construction

Maintenance Node

4.2.3

PMU:CPI (-Q1180-)
PMU:CPI Processor Memory Unit for Coordination Processor Interface LED1

q
S1

red LED green LED

LED on, if the watchdog function has been canceled, for normal operation, the watchdog must be activated (LED 1 off). LED on, when the PMU:CPI is not loaded. LED off, when the PMU:CPI is loaded. resets the CPI and starts the self-test.

LED2

switch
V24

V24 interface

S2

switch
LED3

activates/deactivates the watchdog. for normal operation, the watchdog must be activated (LED 1 off). Test status display LED3 on: during a test section LED3 off: if the test was successful. Test status display LED4 on: during a test section LED4 off: if the test was successful.

q
LED4

yellow LED

yellow LED

4.2.4

PMU:SIMP (-Q1179-)
PMU: SIMP LED1

Processor Memory Unit for Coordination Processor Interface red LED LED on, if the watchdog function has been canceled, for normal operation, the watchdog must be activated (LED 1 off). LED on, when the PMU:CPI is not loaded. LED off, when the PMU:CPI is loaded. resets the CPI and starts the self-test.

q
S1

LED2

green LED switch

V24

V24 interface
S2

switch
LED3

activates/deactivates the watchdog. for normal operation, the watchdog must be activated (LED 1 off). Test status display LED3 on: during a test section LED3 off: if the test was successful. Test status display LED4 on: during a test section LED4 off: if the test was successful.

q
LED4

yellow LED

yellow LED

564

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.2.5

SILTC (-Q766-)
SILTC H1

Signaling Link Terminal Control red LED green LED switch LED on, if the watchdog function has been canceled, for normal operation, the watchdog must be activated (LED H 1 off). LED on, when the SILTC is not loaded. LED off, when the SILTC is loaded. resets the SILTD and starts the self-test.

q q
S1

H2

S2

switch
V24

activates/deactivates the watchdog, for normal operation, the watchdog must be activated (LED H1 off).

V24 interface

H3

q
H4

yellow LED

Test status display LED on, during a test section and off if the test was successful. During operation: LED 3 is on: The links of this group active via SN-0 During operation: LED 3 is off: The links of this group active via SN-1. Test status display LED on during a test section and off if the test was successful.

yellow LED

SILTC

S20

S20 SW Clock

A30828-X1160-M-2-7620

565

Construction

Maintenance Node

4.2.6

SILTD (-Q1023-)
SILTD

Signaling Link Terminal Digital

q q
S1 S2 H2

H1

red LED green LED switch switch

LED H1 on, if the watchdog function has been canceled, for normal operation, the watchdog must be activated. (LED H1 off). LED2 on, when the SILTD is not loaded. LED2 off, when the SILTD is loaded. activates/deactivates the watchdog, for normal operation, the watchdog must be activated (LED H1 off). resets the SILTD and starts the self-test. LED H5 on, during the EPROM test. LED H5 off, if the test was successful. During operation: Flashes briefly while messages are being received. LED H6 on, during the EPROM test. LED H6 off, if the test was successful. During operation: Flashes briefly while messages are being received. LED H7 on, during the RAM test, destructive. LED H7 off, if the test was successful.

q
H6

H5

yellow LED

q
H7

yellow LED

yellow LED

V24 interface
H3

q
H4

yellow LED

LED H3 on, during the timer, DMA, interrupt controller tests. LED H3 off, if the test was successful. LED H3 During operation: L3 out of service LED H4 on, during the port, HDLC, SIT tests. LED H4 off, if the test was successful. LED H4 During operation: L3 initial alignment

yellow LED

SILTD

S21 2
31

3 1 31

S07
2 31

S06
2 31

S09
2

S08
2

S12

S11

S10

566

A30828-X1160-M-2-7620

Maintenance Node

Construction

Switch S06...09

Position 2-3 2-1 MUX or SIT Modem MUX or SIT Modem +12V Modem +12V Modem -12V

Operating with

S10...12 S10 S11 S12 S21

off 1-2 1-2 1-2

MUX(TXD,RXD) bit inversion 2-3 off 2-1 no bit inversion bit inversion switchable with SW

Tab. 4.10

Switch position SILTD (-Q1023-) (up to issue 13)

SILTD S8

3 3 12

S9
12

3 S5
12

3 S6
12 6 3 6 3

S4
4512 7 S7 5 3 1 4512 8 6 4 2

S3

Switch S03...04

Position 2-3, 5-6 1-3, 4-6 MUX or SIT Modem MUX or SIT Modem S1 (- 12V) Modem S2 (+12V) Modem S3 (+12V)

For / Operating with

S7

off 1-2 3-4 5-6

S6

MUX(TXD,RXD) bit inversion 2-3 off 1-3 no bit inversion bit inversion switchable with SW set by manufacturer

S 5 (int.)

2-3

Tab. 4.11

Switch position SILTD (-Q1023-) (up to issue 14)

A30828-X1160-M-2-7620

567

Construction

Maintenance Node

Switch S 8 (int.) S 9 (int.)) 2-3 2-3

Position

For / Operating with set by manufacturer set by manufacturer

Tab. 4.11

Switch position SILTD (-Q1023-) (up to issue 14)

4.2.7

SIPA (-Q1016-)
SIPA LED1

Signaling Periphery Adapter

red LED

LED1 on, if the watchdog function has been canceled, for normal operation, the watchdog must be activated LED1 (off). LED2 on, when the SIPA is not loaded. LED2 off, when the SIPA is loaded. resets the SIPA and starts the self-test. Test status display LED3 on, during a test section LED3 off if the test was successful. activates/deactivates the watchdog, for normal operation, the watchdog must be activated (LED1 off).

LED2

q
S1

green LED switch

LED3

yellow LED
S2

switch

SIPA

S3

S3 for activating / deactivating the SW-clock on timer chip. Open clock is activated.

568

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.3

CP113
4.3.1 4.3.2 4.3.3 4.3.4 4.3.5 4.3.6 4.3.7 4.3.8 4.3.9 4.3.10 4.3.11 4.3.12 4.3.13 4.3.14 4.3.15 4.3.16 4.3.17 4.3.18 4.3.19 4.3.20 4.3.21 4.3.22 4.3.23 4.3.24 AMPC (-Q1388-) BCM (-Q1252-) BCTI (-Q946-) CMYE (-Q244-) CMY2C (-Q963-) CMYC (-Q1255-) CMYM (-Q1256-) CPCL (-Q933-) CPEX (-Q930-) IF:MDD (-Q976-) IK:DTD (-Q975-) IOP:AUC (-Q1169-) IOP:MB (-Q954-) IOP:SCDV (-Q952-) IOP:TA (-Q956-) IOP:UNI (-Q1257-) LCUB (-Q1114-) LAUB (-Q1115-) PEX (-Q1251-) PEXE (-Q242-) (-Q243-) PIA (-Q1253-) PIDAT (-Q940-) MUH (-Q1088-) MTI (-Q1254-)

A30828-X1160-M-2-7620

569

Construction

Maintenance Node

4.3.1

AMPC (-Q1388-)
AMPC

ATM Bridge Processor Type C

X100 X200

X100 INT

X200 ADL X300 ADH

LED Meaning LED 1 off red LED 2 LED 3 off off Meaning AMPC has no power HW fault AMPC no fault; state OP AMPC is being tested (initialized) red green Interface to the BCMY-0 is locked Interface to the BCMY-0 is accessible red green Interface to the BCMY-1 is locked Interface to the BCMY-1 is accessible

X300

LED 1 LED 2 LED 3


X500

green green +/-

X500 CTL

X600 X700

X600 IND

X700 to MP:CP

570

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.3.2

BCM (-Q1252-)
BCM

Bus Clock Generator and Maintenance Controller Meaning the LEDs MST CG0 off CG1 off ILBS off Meaning BCM has no power Fault detected in module BCM BCM is carrying voltage, is free and operable. BCM is being tested or initialized BCM is in default status BCMY1 red green red green BCM has not selected the clock generator BCMY0 BCM has selected the clock generator BCMY0 BCM has not selected the clock generator BCMY1 BCM has selected the clock generator BCMY1 red green SPLIT switch or ILB over MP is set SPLIT switch or ILB over MP is reset

MST CG0 CG1 ILBS

off red green flashing green yellow

BOOT

X600

Key: Start HW recovery


SPLIT

Switch:

Activating the SPLIT switch allows the CP113C/CR to be split into two independent system halves (only possible after carrying out SW_SPLIT).The effect of the SPLIT switch is not cancelled by RESET or configuration commands.

A30828-X1160-M-2-7620

571

Construction

Maintenance Node

4.3.3

BCTI (-Q946-)
BCTI SPB0

Bus control and tracer interface

LED SPB0: Switch:

Inhibit bit display for CMY0. Lights up if inhibit bit set. The inhibit bit can be set manually with the switch. Standard setting is OFF, which means that the inhibit bit is not set.

OFF X100
SPB1

Connector of a HW-Tracer

q
OFF

X200

Connector of a HW-Tracer

LED SPB1 Switch:

Inhibit bit display for CMY1. Lights up if inhibit bit set The inhibit bit can be set manually with the switch. Standard setting is OFF, which means that the inhibit bit is not set.

4.3.4

CMYE (-Q244-)
CMYE

Common Memmory for CP113E

BOOT SPLIT

BOOT: Activates boot program of the associated BAP SPLIT: Activates the split line of the associated BAP
MASTER ILB MST

LED MASTER/red

Meaning interface blocked interface open interface blocked interface open hardware fault in operation initialization or self-test

V24 connectio for PC


MP

MASTER/green ILB/red

TR113E

................ ................ ................ ................ ................

ILB/green MST/red Hardware Tracer MST/green MST/flashes green

572

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.3.5

CMY2C (-Q963-)
CMY2C

Common memory control, part 2

12-15

Bit:
8-11

Alphanumerical dot matrix display for off-line diagnosis result Alphanumerical dot matrix display for off-line diagnosis result

Bit:
4-7

Bit:
0-3

Alphanumerical dot matrix display for off-line diagnosis result Alphanumerical dot matrix display for off-line diagnosis result

Bit:

DIAG0

q q

LED DIAG0: LED DIAG2: Push-button:

DIAG2 DIAG ALIND

Diagnosis: = Diagnosis 0 (1) LED DIAG 0 on = Diagnosis 2 (2) LED DIAG 2 on LED DIAG 0 and LED DIAG 2 on = Diagnosis 3 (3) Diagnosis key: to start control diagnosis (1), to start medium diagnosis (2), to start component location diagnosis (3) Alarm symptoms display key: to display the next symptoms byte and its byte number Reset key: to reset the unit CMY without destroying the contents of the memory

Push-button:
RESET

Push-but-

4.3.6

CMYC (-Q1255-)
CMYC

Common Memory Control Meaning the LEDs MST off ILB0 off ILB1 off Meaning Module CMYC without voltage. The LED or its drive circuit is faulty. Fault detected in module CMYC. Module CMYC is carrying voltage, is fault free and operable. Module CMYC is being tested or initialized. red green Interface of module CMYC to BCMY0 blocked. Interface of module CMYC to BCMY0 open. red green Interface of module CMYC to BCMY1 blocked. Interface of module CMYC to BCMY1 open.

MST ILB0 ILB1

red green flashing green

X600

MP:CP113C

A30828-X1160-M-2-7620

573

Construction

Maintenance Node

4.3.7

CMYM (-Q1256-)
CMYM

Common Memory Medium

MST

MST: LED off: LED red: LED green: LED flashing green:

Module CMYM without voltage. The LED or its drive circuit is faulty. Fault detected in module CMYM. Module CMYM is carrying voltage, is fault free and operable. Module CMYM is being tested or initialized.

574

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.3.8

CPCL (-Q933-)
CPCL

Coordination processor, coupling logic

Display:
2

Alphanumerical dot matrix display for the off-line diagnosis result and the CP load Alphanumerical dot matrix display for the off-line diagnosis result and the CP load Alphanumerical dot matrix display for the off-line diagnosis result and the CP load Alphanumerical dot matrix display for the off-line diagnosis result and the CP load

Display:
1

Display:
0

Display:

TEST BOOT

Switch:

Switch comparator logic on/off

Key:
RES

Start HW recovery Reset processor locally using output from the PEX-PROM version number Diagnostic register display of the guiding PU in the lower switch position (1) and the running PU in the higher switch position (0). The off-line diagnosis is started by pressing BOOT and RESET key are simultaneously.

Key:
DIAD 1 0

Switch:

4.3.9

CPEX (-Q930-)
CPEX Switch settings for 1-Mbit-EPROM: E1 - A1 = closed E3 - A2 = closed E5 - A3 = closed E7 - A4 = closed Switch settings for 2-Mbit-EPROM: E2 - A1 = closed E4 - A2 = closed E6 - A3 = closed E8 - A4 = closed

E1 E2 E3 E4 E5 E6 E7 E8

A1 A2 A3 A4

A30828-X1160-M-2-7620

575

Construction

Maintenance Node

4.3.10

IF:MDD (-Q976-)
IF:MDD H2

Interface for magnetic disk device

q
H1

LED H2:

LED on: if magnetic disk is being written

LED H1:

LED on: if magnetic disk is being read

4.3.11

IK:DTD (-Q975-)
IK:DTD

IOP kernel for magnetic disk and tape device

q q q q
DIAG D3 D2 D1

D0

LED D0: LED D1: LED D2: LED D3: Key:

LED display to show the off-line diagnosis steps LED display to show the off-line diagnosis steps LED display to show the off-line diagnosis steps LED display to show the off-line diagnosis steps Start off-line diagnosis

4.3.12

IOP:AUC (-Q1169-)
IOP: AUC RES

Input/output processor for authentication center

L2 L1 L0

L2 LED: LED display to show the off-line diagnosis steps L1 LED: LED display to show the off-line diagnosis steps L0 LED: LED display to show the off-line diagnosis steps

576

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.3.13

IOP:MB (-Q954-)
IOP: MB

Input/output processor for message buffer

IBREQ

LED off: LED red: LED green: LED flashing green

IOP:MB voltage error Fault detected in module IOPUNI. IOP:MB is fault free and operable. IOP:MB is in reset status

X600

X500

A30828-X1160-M-2-7620

577

Construction

Maintenance Node

4.3.14

IOP:SCDV (-Q952-)
IOP: SCDV

Input/output processor for serial data communication devices

q
D1

D0

LED D0:

LED display to show the off-line diagnosis steps

q
D2

LED D1:

LED display to show the off-line diagnosis steps

q
DIAG

LED D2:

LED display to show the off-line diagnosis steps

Key:

Start off-line diagnosis

Module in function status 01 (FUS T01) (S13 and S14 side by side)
IOP:SCDV

Switches for setting Switches for setting the channel mode the transmission rate ON ON OFF OFF 12345678 12345678 S12 S11 S10 S14 S13

S09

Switches for setting the channel addresses

S08

S07

S06

S05

S04

S03

S02

S01

578

A30828-X1160-M-2-7620

Maintenance Node

Construction

Module in function status 01 (FUS T02) (S13 and S14 side by side)
IOP:SCDV
Switches for setting the channel mode ON OFF 12345678 S14 ON OFF 12345678 S13 S12 S11 S10 S09 Switches for setting the transmission rate

Switches for setting the channel addresses

S08

S07

S06

S05

S04

S03

S02

S01

The switches S01 to S08 must be set alternately to 1 and 0: S01 to 1; S02 to 0; S03 to 1; etc. Switches S09 to S12 must all be set to 9. Allocation of the switches: If HDLC data links are connected, the modems on the DCP side are set to clock mode internal and modems on the CP side are set to the slave mode.
Channel Port address (Hex) Channel address Rotary switch (Hex) S02 S04 S06 S08 S01 S03 S05 S07 Mode slide switch Transmission rate Rotary switch (Hex) S09 S10 S11 S12

00 01 02 03

006018XX 00601AXX 00601CXX 00601EXX

S13 5 . . . 8 S13 1 . . . 4 S14 5 . . . 8 S14 1 . . . 4

Tab. 4.12

IOPSCDV (-Q952-) Allocation of the switches

Channel

Switch lower upper S01 S03 S05 S07 S02 S04 S06 S08

Channel address (Hex) 00 . . . FF 00 . . . FF 00 . . . FF 00 . . . FF

00 01 02 03

Tab. 4.13

IOPSCDV (-Q952-) Setting of the channel addresses S01 . . . S08

The set value must agree with the parameter LINKADR of the PDN generating command XSTAT.

A30828-X1160-M-2-7620

579

Construction

Maintenance Node

Transmission rate bit/s (baud) 64000 56000 48000 19200 9600 7200 4800 3600 2400 2000 1600 1200 600 D C B A 9 8 7 6 5 4 3 2 1

Switch setting (Hex)

Tab. 4.14

IOPSCDV (-Q952-) Setting of the transmission rate for channels 00 . . . 03 with switches S09 . . . S12

IOPSCDV (-Q952-) Setting Channel Mode FUST01


Switch S14 Channel 03 Channel 02 ON OFF 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 Switch S13 Channel 01 Channel 00 ON OFF

ON = Handshaking OMT - IOP OFF = No Handshaking OMT - IOP ON = Clock extern OFF = Clock intern ON = direkter Anschlu, for PC or Data link Direct Connection fr PC oder Data link OFF = Connection via modem for PC or Data link with IOPSCDV: with IOPSCDX: ON = Data link OFF = PC The switch must be Stellung ON Der Schalter mu inset to ON. sein.

580

A30828-X1160-M-2-7620

Maintenance Node

Construction

IOPSCDV (-Q952-) Setting Channel Mode FUST02


Switch S14 Channel 03 Channel 02 ON OFF 1 2 3 4 5 6 7 8

Switch S13 Channel 01 Channel 00 ON OFF 1 2 3 4 5 6 7 8

ON = Handshaking OMT - IOP OFF = No Handshaking OMT - IOP ON = Clock intern OFF = Clock extern ON = DCE OFF = DTE ON = HDLC OFF = PC

A30828-X1160-M-2-7620

581

Construction

Maintenance Node

4.3.15

IOP:TA (-Q956-)
IOP:TA

Input/output processor for time and alarms

HOURS

Hours:
MINUTES

2-digit 7-segment showing the time or the elapsed time of a test

Minutes:
SECONDS

2-digit 7-segment showing the time or the elapsed time of a test

Seconds:
STATUS

2-digit 7-segment showing the time or the elapsed time of a test

Operating states: 2-digit 7-segment status display

DISPLAY ON

Key:

When the key is pressed, the time is displayed for about 4 minutes

DIAG

Key:

When the key is pressed, the off-line diagnosis is started.

4.3.16

IOP:UNI (-Q1257-)
IOP: UNI

Input/output processor unified for O&M devices

MST

LED off: LED red: LED green: LED flashing green:

Module IOPUNI voltage. error. Fault detected in module IOPUNI. Module IOPUNI is carrying voltage, is fault free and operable. Module IOPUNI is being tested or initialized.

X600

MP:CP113C

582

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.3.17

LCUB (-Q1114-)
LCUB

Line control unit, module B for IOPLAU

RESET

RESET key to start the off-line diagnosis

MST: green/ red/ yellow LED: Operating state of the module L2: green/ red/ yellow LED: LED display to show the off-line diagnosis steps
MST L2 L1 L0

MST LED LED L2, L1, L0

L1: green/ red/ yellow LED: LED display to show the off-line diagnosis steps L0: green/ red/ yellow LED: LED display to show the off-line diagnosis steps

4.3.18

LAUB (-Q1115-)
LAUB

Line adaptation unit, module B for IOPLAU

MST

MST LED LCUO LED LCUP LED

MST: green/ red LED: Operating state of the module

LCUO LCUP

LCU0:
DL0 DL1

DL0 LED DL1 LED

green/ red LED:

LED lights up if module is selected by the own LCUB

LCUP: green/ red LED: DL0: green/ red LED: DL1: green/ red LED:

LED lights up if module is selected by the partner LCUB

Data link 0

Data link 1

A30828-X1160-M-2-7620

583

Construction

Maintenance Node

4.3.19

PEX (-Q1251-)
PEX X100

Program execution part

Meaning the LEDs MST off red green ILB0 off ILB1 off Meaning Module PEX without voltage. The LED or its drive circuit is faulty. Fault detected in module PEX. Module PEX is carrying voltage, is fault free and operable Module PEX is being tested or initialized. red green red green Interface of module PEX to BCMY0 blocked. Interface of module PEX to BCMY0 open. Interface of module PEX to BCMY1 blocked. Interface of module PEX to BCMY1 open.

X300
MST ILB0 ILB1

X200 X700 X600 X500

flashing green

584

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.3.20

PEXE (-Q242-) (-Q243-)


PEXE

Progam Execution Part

PWR power on
PWR

ILB1 ILB0 MST

LED MST/red MST/green hardware fault in operation

Meaning

Connection for Maintenace Panel V24 connectio for PC


MP V.24

MST/flashes green ILB0/red ILB0/green ILB1/red ILB1/green

initialization or self-test interface blocked interface open interface blocked interface open

TR113E

................ ................ ................ ................ ................


A30828-X1160-M-2-7620

Hardware Tracer TR113E

585

Construction

Maintenance Node

4.3.21

PIA (-Q1253-)
PIA

Processor Interface and Arbiter

MST

MST: LED off: LED red LED: LED green: LED flashing green:

Module PIA without voltage. The LED or its drive circuit is faulty. Fault detected in module PIA. Module PIA is carrying voltage, is fault free and operable. Module PIA is being tested or initialized.

586

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.3.22

PIDAT (-Q940-)
PIDAT

Processor interface, data bus

q
SPB OFF

LED SPB: Switch:

Lights up if inhibit bit is set. The switch is for the manual setting of the inhibit bit (Standard setting is OFF).

A30828-X1160-M-2-7620

587

Construction

Maintenance Node

4.3.23

MUH (-Q1088-)
MUH

1 2 3 4 1 0

The module is equipped with 1-Mbit-RAM or 4-Mbit-RAM chips. Furthermore, according to the required memory capacity, the module can be used with different capacity stages of the storage medium. The module contains a coding switch for matching the memory addressing to the possible equipment variants. Setting of the coding switch:
4M-RAM Q10881M-RAM Q1088Coding switch 1 Coding switch 2 Capacity state 100% 75% 50% 25%

X800 X700 X600 X500

X400 X300 X200 X100

ON OFF ON OFF

ON ON OFF OFF

Tab. 4.15

MUH (-Q1088-) Setting of the coding switch (part 1)

RAM size 1 Mbit 4 Mbit OFF ON

Coding switch 3 ON OFF

Coding switch 4

Tab. 4.16

MUH (-Q1088-) Setting of the coding switch (part 2)

Variants of LMY for unit BAP/CAP/IOC (mounting location C165)


Unit BAP0/BAP1 CAP0 to CAP5 IOC0 to IOC3 Memory capacity 16 Mbyte Module M:MUH -Q1088-X400 (16 Mbyte, 1-Mbit-DRAM)

Tab. 4.17

Variants of LMY capacity for unit BAP/CAP/IOC (mounting location C165)

588

A30828-X1160-M-2-7620

Maintenance Node

Construction

Unit CAP0 to CAP5 IOC0 to IOC3 BAP0/BAP1 CAP0 to CAP5 IOC0 to IOC3

Memory capacity 16 Mbyte

Module M:MUH -Q1088-X500 (16 Mbyte, 4-Mbit-DRAM) M:MUH -Q1088-X600 (32 Mbyte, 4-Mbit-DRAM)

32 Mbyte

Tab. 4.17

Variants of LMY capacity for unit BAP/CAP/IOC (mounting location C165)

Variants of LMY for unit BAP/CAP (mounting location C173) Expansion of memory capacity from 16 Mbyte to 32 Mbyte with M:MUH -Q1088-X400 (16 Mbyte, 1-Mbit-DRAM). Variants of LMY for unit IOC (mounting location C281) Either of modules M:MUH -Q1088-X200 (8 Mbytes, 1-Mbit-DRAM) or -X400 (16 Mbytes, 1-Mbit-DRAM) or -X500 (16 Mbytes, 4-Mbit-DRAM) can be inserted. Units (IOC0, IOC1, IOC2 and IOC3, PRO1, PRO3, PRO5, PRO7) must however be equipped with the same memory configuration, i.e., a module M:MUH of the same type must be used.

4.3.24

MTI (-Q1254-)
MTI

Memory and Tracer Interface

MST

MST: LED off: LED red: LED green: LED flashing green:

Module MTI without voltage. The LED or its drive circuit is faulty. Fault detected in module MTI. Module MTI is carrying voltage, is fault free and operable. Module MTI is being tested or initialized.

A30828-X1160-M-2-7620

589

Construction

Maintenance Node

4.4

DCC
4.4.1 4.4.2 4.4.3 4.4.4 4.4.5 4.4.6 4.4.7 4.4.8 4.4.9 4.4.10 4.4.11 4.4.12 4.4.13 4.4.14 4.4.15 4.4.16 4.4.17 4.4.18 4.4.19 4.4.20 4.4.21 4.4.22 4.4.23 4.4.24 DCCCA (-Q5619-A) DCCCB (-Q5619-B) DCCCC (-Q5619-C) DCCCK (-Q5619-K) DCCCL (-Q5619-L) DCCCR (-Q5619-) DCCCS (-Q5619-S) DCCCV (-Q5619-V) DCCDC (-Q5862-C) DCCDD (-Q5862-D) DCCDE (-Q5862-E) DCCDF (-Q5862-F) DCCDK (-Q6104-) DCCDM (-Q6111-) DCCDQ (-Q6125-) DCCDR (-Q6129-) DCCDU (-Q6131-) DCCDW (-Q6133-) DCCMC (-Q5883-) DCCMD (-Q5897-) DCCMR (-Q5619-R100) DCCMS (-Q5619-S100) DCCMS (-Q5897-) DCCXI

590

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.4.1

DCCCA (-Q5619-A)
DCCCA H2

Direct Current Converter A

q H1 q
S1

H2 LED H1 LED S1 switch

H2 on: current converter is on H1 on: current converter is on switch up: current converter on switch down: current converter off

0V

Test jack (optional)


5V

Test jack (optional)

A30828-X1160-M-2-7620

591

Construction

Maintenance Node

4.4.2

DCCCB (-Q5619-B)
DCCCB Direct Current Converter B

q
S1

G8

green LED switch

G8 on: current converter is on switch up: current converter on switch down: current converter off

Test jack (optional)


12V

Test jack (optional)

4.4.3

DCCCC (-Q5619-C)
DCCCC

Direct Current Converter C

G23

q
S1

green LED switch

G23 on: current converter is on switch up: current converter on switch down: current converter off

Test jack (optional)


12V

Test jack (optional)


+

Test jack (optional)


5V

Test jack (optional)

592

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.4.4

DCCCK (-Q5619-K)
DCCCK Direct Current Converter K

q
S1

G8

green LED switch

G8 on: current converter is on switch up: current converter on switch down: current converter off

Test jack (optional)


60V

Test jack (optional)

4.4.5

DCCCL (-Q5619-L)
DCCCL Direct Current Converter L

q
S1

G8

green LED switch

G8 on: current converter is on switch up: current converter on switch down: current converter off

Test jack (optional) Test jack (optional)

5V

A30828-X1160-M-2-7620

593

Construction

Maintenance Node

4.4.6

DCCCR (-Q5619-)
DCCCR

Direct Current Converter R

G48

q
S1

green LED switch

G48 on: current converter is on switch up: current converter on switch down: current converter off

+ 12V

Test jack (optional)


+ 5V

Test jack (optional)


0V - 5V - 12V

Test jack (optional) Test jack (optional) Test jack (optional)

4.4.7

DCCCS (-Q5619-S)
DCCCS Direct Current Converter S

q
S1

G8

green LED switch

H1 on: current converter is on switch up: current converter on switch down: current converter off

Test jack (optional)


5V

Test jack (optional)

594

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.4.8

DCCCV (-Q5619-V)
DCCCV

Direct Current Converter V

q
S1

H1

green LED switch

H1 on: current converter is on switch up: current converter on switch down: current converter off

+ +

Test jack (optional)


93V

Test jack (optional)

DCCCV Delivery status: B2, B3 and B4 closed Operating status: B2, B3 and B4 closed when UA = -93V B2, B3 and B4 open when UA = -77V

B2 Jumper B3 B4

4.4.9

DCCDC (-Q5862-C)
DCCDC Direct Current Converter DC

q
S1

H1

green LED switch

H1 on: current converter is on switch up: current converter on switch down: current converter off

A30828-X1160-M-2-7620

595

Construction

Maintenance Node

4.4.10

DCCDD (-Q5862-D)
DCCDD Direct Current Converter DD

q
S1

H1

green LED switch

H1 on: current converter is on switch up: current converter on switch down: current converter off

4.4.11

DCCDE (-Q5862-E)
DCCDE Direct Current Converter DE

q
S1

H1

green LED switch

H1 on: current converter is on switch up: current converter on switch down: current converter off

4.4.12

DCCDF (-Q5862-F)
DCCDF Direct Current Converter DF

q
S1

H1

green LED switch

H1 on: current converter is on switch up: current converter on switch down: current converter off

4.4.13

DCCDK (-Q6104-)
DCCDK Direct Current Converter DK

q
S1

H1

green LED switch

H1 on: current converter is on switch up: current converter on switch down: current converter off

596

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.4.14

DCCDM (-Q6111-)
DCCDM Direct Current Converter DM

q
S1

H1

green LED switch

H1 on: current converter is on switch up: current converter on switch down: current converter off

4.4.15

DCCDQ (-Q6125-)
DCCDQ Direct Current Converter DQ

q
S1

H1

green LED switch

H1 on: current converter is on switch up: current converter on switch down: current converter off

4.4.16

DCCDR (-Q6129-)
DCCDR Direct Current Converter

H1

green LED

H1 on: current converter is on

4.4.17

DCCDU (-Q6131-)
DCCDU Direct Current Converter

q
S1

H1

green LED switch

H1 on: current converter is on switch up: current converter on switch down: current converter off

A30828-X1160-M-2-7620

597

Construction

Maintenance Node

4.4.18

DCCDW (-Q6133-)
DCCDW Direct Current Converter

q
S1

H1

green LED switch

H1 on: current converter is on switch up: current converter on switch down: current converter off

4.4.19

DCCMC (-Q5883-)
DCCMC Direct Current Converter MC

q H2 q
S1

H1

green LED switch

H1, H2 on: current converter is on switch up: current converter on switch down: current converter off

4.4.20

DCCMD (-Q5897-)
DCCMD Direct Current Converter MD

q H2 q
S1

H1

green LED switch

H1, H2 on: current converter is on switch up: current converter on switch down: current converter off

4.4.21

DCCMR (-Q5619-R100)
DCCMR

Direct Current Converter MR

G48

q
S1

green LED switch

G48 on: current converter is on switch up: current converter on switch down: current converter off

598

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.4.22

DCCMS (-Q5619-S100)
DCCMS

Direct Current Converter MS

q
S1

H1

green LED switch

H1 on: current converter is on switch up: current converter on switch down: current converter off

4.4.23

DCCMS (-Q5897-)
DCCMS H2

Direct Current Converter MS

q H1 q
S1

H2 LED H1 LED S1 switch

H2 on: current converter is on H1 on: current converter is on switch up: current converter on switch down: current converter off

0V

Test jack (optional)


5V

Test jack (optional)

4.4.24

DCCXI q q
ON OFF

A30828-X1160-M-2-7620

599

Construction

Maintenance Node

4.5

DLU
4.5.1 4.5.2 4.5.3 4.5.4 4.5.5 4.5.6 4.5.7 4.5.8 4.5.9 4.5.10 4.5.11 4.5.12 4.5.13 4.5.14 4.5.15 4.5.16 4.5.17 4.5.18 4.5.19 4.5.20 4.5.21 4.5.22 4.5.23 4.5.24 4.5.25 4.5.26 4.5.27 4.5.28 4.5.29 4.5.30 4.5.31 4.5.32 4.5.33 4.5.34 4.5.35 4.5.36 4.5.37 4.5.38 4.5.39 4.5.40 4.5.41 4.5.42 4.5.43 BDB (-Q808-), (-Q1002-) BDCG (-Q809-) BDE (-Q807-), (-Q1003-) DIU:LDID (-Q1109-) DIUDA (-Q806-) DIUDC (-Q1007-) DLUC (-Q968-) DLUC (-Q112-, -Q113-, Q114-) DLUS (-Q1492-), (-Q1493-), (-Q1494-) DLUV (-Q1498-), (-Q126-) DSU modems EMSP (-Q1094-) EMSP (-Q828-) FMTU (-Q1112-) FMTU (-Q117-) FTEM (-Q957-) GCG (-Q1322-) IWEx (-Q144-) IWEx (-Q1177-) IWESx (-Q1178-) LMEM (-Q811-) LVMM (-Q812-) LTCD (-Q124-) LTCD (-Q1495-) LTOD (-Q1496-) MGB (-Q1323-) MTAM (-Q1066-) OMX16D (-Q1497-) RGB (-Q1324-) RGMG (-Q813-) RGMG (-Q895-) SASC (-Q1133-), (-Q22-) SASCG (-Q111-) SLMA (-Q1011-) SLMD (-Q838-), (-Q965-), (-Q1101-), (-Q1103-), (-Q1192-) SLMD (-Q210-) SLMD (-Q52-) SLMI:AMA (-Q225-) SLMI:FMA (-Q164-) SLMI:FMB (-Q200-) SLMI:MPB (-Q143-) SLMI:PHA (-Q142-) SLMI:PHA (-Q170-)

600

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.44 4.5.45 4.5.46

SLMI:PHB (-Q192-) SLMI:SDA (-Q155-) SLMX (-Q1338-)

A30828-X1160-M-2-7620

601

Construction

Maintenance Node

4.5.1

BDB (-Q808-), (-Q1002-)


BDB

Bus Distributer Basic Module

q q q q

Incandescent lamp (optional) Incandescent lamp (optional) Incandescent lamp (optional) Incandescent lamp (optional)

The function of the lamps is overload protection in the ringing voltage distributor. If the two upper or lower lamps are on, an overload condition exist in the ringing voltage distributor of the relevant semi-shelf. If a subscriber goes off-hook during the ringing phase the two lamps light briefly. If three or more subscribers in the shelf are fed ringing current the filaments glow.

On the BDB module in shelf 0, the two upper lamps indicate an overload condition in the ringing voltage distributor of the left semi-shelf. The two lower lamps indicate an overload condition in the ringing voltage distributor of the right semi-shelf. On the BDB module in shelf 1, the two upper lamps indicate an overload condition in the ringing voltage distributor of the left semi-shelf. The two lower lamps indicate an overload condition in the ringing voltage distributor of the right semi-shelf

4.5.2

BDCG (-Q809-)
BDCG

Bus Distributer Module with Clock Generator

q
LCM

yellow LED Switch

LED M on: Clock generator is MASTER LED M off: Clock generator is SLAVE For switching from MASTER to SLAVE and vice versa (the switching is only effective on BDCG1). Switch up: BDCG0 ist MASTER / Switch down: BDCG1 ist MASTER LED LCM on: VCO is synchronized by the 8-kHz clock. LED LCM off: VCO is synchronized by the 8-kHz clock supplied from the partner module. LED DCM on: Clock (CLK) and frame synchronization pulse (FS) are fed to DLU from this module. LED UNA on: Failure of clock generator (CG)

q q q

green LED

DCM UNA

green LED red LED

602

A30828-X1160-M-2-7620

Maintenance Node

Construction

BDCG

Switch settings: Delivery status: Switch S2 in position INT Operation status: INT: internal synchronization EXT: external synchronization

S2

EXT

4.5.3

BDE (-Q807-), (-Q1003-)


BDE

Bus Distributor Extension Module

q q

INT

Incandescent lamp (optional) Incandescent lamp (optional)

The function of the lamps is overload protection in the ringing voltage distribtor If a subscriber goes off-hook during the ringing phase the two lamps light briefly. If three or more subscribers in the shelf are fed ringing current the filaments glow.

4.5.4

DIU:LDID (-Q1109-)
LDID

Local Digital Interface Unit, type D

q MA q

IN

red LED red LED

LED IN on: LDID out of service LED MA on: Failure on 4MBit/s link is detected

A30828-X1160-M-2-7620

603

Construction

Maintenance Node

LDID

With switch S1 is the selection between function of a DIUDB (US-Market) and a DIUDC (WM) possible: Settings switch S1: DIUDC: 1-2 closed, 3-4 closed DIUDB: 1-2 open, 3-4 open (other settings are not used)

S1 4 2

3 1

4.5.5

DIUDA (-Q806-)
DIUDA

Digital Interface Unit for DLU, type A

q MA0 q
SA0

IN

red LED red LED Test jack

LED IN on: DIU is out of order LED MA0 on: failure on 2MBit/s link 0 is detected Trace terminal for alarm signal MA0 (active L) LED SA0 on: alarm indication signal AIS or D-Bit for link 0 is received Trace terminal for alarm signal SA0 (active L) LED MA1 on: failure on 2MBit/s link 1 is detected Trace terminal for alarm signal MA1 (active L) LED SA1 on: alarm indication signal AIS or D-Bit for link 1 is received Trace terminal for alarm signal SA1 (active L)

q q q

red LED Test jack

MA1

red LED Test jack

SA1

red LED Test jack

GND

Test jack

Common reference potential for tracing alarm signal MA and SA

604

A30828-X1160-M-2-7620

Maintenance Node

Construction

DIUDA

X2

X1 X3

X1, X3: Link inserted with 75 Ohm coaxcial cable and grounded receiver shield. X2, X4: Link inserted with 75 Ohm coaxcial cable and grounded transmitter shield. X5: The country specific tone is set.

Switch X5 3 1 2 X4

Delivery status: connection 3-2 closed

4.5.6

DIUDC (-Q1007-)
DIUDC GND

Digital Interface Unit for DLU, type C

Test jack

Ground potential is applied to this jack (optional) LED IN on: DIU out of service LED SA0 on: alarm indication signal AIS or D-Bit for link 0 is received LED MA0 on: failure on 2MBit/s link 0 is detected LED SA1 on: alarm indication signal AIS or D-Bit for link 1 is received LED MA1 on: failure on 2MBit/s link 1 is detected SEL connected with GND: link 1 alarms are traced. SEL open: link 0 alarms are traced (optional). If the incoming PCM signal fails, log 0 applied to this jack (optional) If there is a permanent one in the pulse frame, log 0 is applied to this jack (optional) If the frame alignment is lost, log 0 is applied to this jack (optional) If the D bit is set in the frame service word, log 0 applied to this jack (optional) If there is a CRC4 fault, log 0 is applied to this jack (optional)

q q MA0 q SA1 q MA1 q


SA0 SEL NOS

IN

red LED red LED red LED red LED red LED Test jack Test jack

AIS

Test jack
LPF

Test jack
D-B

Test jack
CER

Test jack

A30828-X1160-M-2-7620

605

Construction

Maintenance Node

DIUDC
S10 S9 S8 S7 S6 S5

S2 S1

S4

Switch S11 1 2 3

S3

Switch 1, 2, 3, 4: open: lines 120 Ohm, symmetric closed: lines 75 Ohm, coaxial Switch 5: open: CRC4 not activ closed: CRC4 activ Switch 6: open: HDB3-code supervision DT closed: HDB3-code supervision CCITT Switch 7, 8: not used Switch 9, 10, 11: country-specific Delivery status: S1... S4 open, S5 closed, S6, S9... S11 country-specific

4.5.7

DLUC (-Q968-)
DLUC

Digital Line Unit Control

q
T1

G1

green LED Switch

LED G1 flashes every 1.2 s: DLU has normal operation LED G1 flashes every 0.7 s: DLU has emergency service. T1 is currently not used. LED G2 flashes every 10 s: CCS link is not disturbed. LED G2 flashes every 480 ms: CCS link is disturbed. Operation of T2 causes reset of all processors on the DLUC module (optional).

q
T2

G2

red LED Switch

606

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.8

DLUC (-Q112-, -Q113-, Q114-)


DLUC ERR RUN

Digital Line Unit Control

q q M q

red LED green LED green LED Switch

DLUC status (for operation see table below) DLUC status (for operation see table below) LED on: Clock generator is MASTER. LED off: Clock generator is SLAVE. For switching from MASTER to SLAVE and vice versa. Switch up: clock generator is ON / Switch down: clock generator is OFF. Screw thread for fixing the testadapter LED on: VCO is synchronized by the 8-kHz clock. LED off: VCO is synchronized by the 8-kHz clock supplied from the partner module. LED on: Clock (CLK) and frame synchronization pulse (FS) are fed to DLU from this module. LED on: failure on PDC link is detected.

M/S

q DCM q PDC q

LCM

green LED green LED yellow LED

V.24-interface for testadapter

Operation status Power failure or fuse failure (total failure) DRAM-Test and FW-Decompressing Start up No CCS after start up or CCS failurel > 40 sec. Watchdog expired HW failure (failure in service), HW failure (out of operation) BoST running, no faults detected BoST running, at least one fault detected off off off

LED ERR off

LED RUN

flash very quickly LED go out for a short time LED go out for a short time LED light up for a short time LED light up for a short time off flash flash

LED light up for a short time off on on off on

A30828-X1160-M-2-7620

607

Construction

Maintenance Node

DLUC

Switch CRC4: open: CRC4 not activ closed: CRC4 activ Switch EXTCLK: EXTCLK open: external synchronization EXTCLK closed: internal synchronization

Delivery status: CRC4 open EXTCLK closed

CRC4

EXTCLK

4.5.9

DLUS (-Q1492-), (-Q1493-), (-Q1494-)


DLUS N/S CCS

Digital Line Unit Control

q q

red LED red LED Switch

RES

LED N/S flashes every 1.2 s: DLU has normal operation. LED N/S flashes every 0.7 s: DLU has emergency service. LED CCS flashes every 10 s: CCS link is not disturbed. LED CCS flashes every 480 ms: CCS link is disturbed. Operation of RES causes reset of all processors on the DLUC module (optional).

AL0 AL1 FLT

q q q

red LED red LED (optional) red LED

LED AL0 on: PDC0 fault (DIU) LED AL1 on: PDC1 fault (DIU) LED FLT on: DIU or GCG fault

q DCM q M q M/S

LCM

green LED green LED green LED Switch

LED on: VCO is synchronized by the 8-kHz clock. LED off: VCO is synchronized by the 8-kHz clock supplied from the partner module. LED on: Clock (CLK) and frame synchronization pulse (FS) are fed to DLU from this module. LED on: Clock generator is MASTER. LED off: Clock generator is SLAVE. For switching from MASTER to SLAVE and vice versa. Switch up: clock generator is ON / Switch down: clock generator is OFF.

608

A30828-X1160-M-2-7620

Maintenance Node

Construction

DLUS (-Q1492-)
Switch S4 (synchronization): Setting synchronization (internal or external) Switch S5 (CCS and length): CCS not inverted: S5-1 closed CCS inverted: S5-1 open Length 0-114 feet: S5-2, S5-3 and S5-4 closed Length 82-213 feet: S5-2 open, S5-3 and S5-4 closed Length 180-311 feet: S5-2 closed, S5-3 open, S5-4 closed Length 279-410 feet: S5-2 and S5-3 open, S5-4 closed Length 377-508 feet: S5-2 and S5-3 closed, S5-4 open Length 476-607 feet: S5-2 open, S5-3 closed, S5-4 open Length 574-689 feet: S5-2 closed, S5-3 and S5-4 open Not defined: S5-2, S5-3 and S5-4 open Delivery status: S4 in position INT S5 closed S6 open Switch S6 (line code): B8ZS: open AMI: closed

DLUS
Switch S4

EXT INT

Switch S6 S5-4 S5-3 S5-2 S5-1 Switch S5

DLUS (-Q1493-)
DLUS
Switch S4

EXT INT

Switch S4 (synchronization): Setting synchronization (internal or external) Switch S6 (CRC4): CRC4 on: open CRC4 off: closed

Switch S6

Delivery status: S4 in position INT S6 open

A30828-X1160-M-2-7620

609

Construction

Maintenance Node

DLUS (-Q1494-)
DLUS Switch S7 (LDI Mode): LDI30: open LDI24: closed Switch S8 (CCS): CCS not inverted: closed CCS inverted: open

Switch S8 Switch S7

Delivery status: S7 open S8 closed

4.5.10

DLUV (-Q1498-), (-Q126-)


DLUV

DLU for V5.1 Interfaces

BOST

red LED

For operation see table below

MODE

green LED

For operation see table below LED red off on on off flash off on

TEST

Power failure; defective converter or fuse BoST Start up Normal operation No CCS following start up or CCS failure > 40s Waiting for watchdog timeout Fault

green off flash flash flash flash flash off

V.24-interface for testadapter and tracer

610

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.11 4.5.11.1

DSU modems Modem (-Q1249-X-) type GPT


MODEM

Modem Module (GPT)

q q q q

red LED

operating voltage

yellow LED TRANSMIT green LED RECEIVE

orange LED carrier signal

LED light up when active

4.5.11.2

Modem (-Q1249-X101-) type NEUHAUS


MODEM

Modem Module (NEUHAUS) red LED red LED red LED red LED red LED red LED red LED operating voltage modem in error-free operation DTR modem has setup connection carrier signal TRANSMIT RECEIVE

q
Power

q
MODEM OK

q
DTR

q
OFFHOOK

q
DCD

q
TXDATA

q
RXDATA

LED light up when active

A30828-X1160-M-2-7620

611

Construction

Maintenance Node

4.5.11.3

PSU (-Q5882-X-) type GPT


PSU

Power Supply Unit for GPT modem red LED output voltage

q
PWR Monitor

q
Mains In

green LED

input voltage

LED light up when active

4.5.11.4

PSU (-Q5882-X100-) type NEUHAUS

PSU

Power Supply Unit for NEUHAUS green LED power supply +5V

q q
V1

q q
V2

green LED

power supply +12V

q q
V3

green LED power supply -12V

LED light up when active. Operating voltages are set with trimmers V1 - V3. They are not to be altered by service personnel.

612

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.12

EMSP (-Q1094-)
EMSP BSY ERR

Emergency Service Equipment for Push-button Subscibers

q q

green LED red LED

LED BSY on: one or more receivers are seized LED ERR on: hardware fault

4.5.13

EMSP (-Q828-)
EMSP

Emergency Service Equipment for Push-button Subscibers

q q q q q q

green LED green LED

LED on: signal recognized (code receiver 0) LED on: code receiver 0 seized

green LED green LED

LED on: signal recognized (code receiver 1) LED on: code receiver 1 seized

green LED green LED

LED on: signal recognized (code receiver 2) LED on: code receiver 2 seized

A30828-X1160-M-2-7620

613

Construction

Maintenance Node

4.5.14

FMTU (-Q1112-)
FMTU

Function Module for Test Unit

V1

yellow LED

LED V1 on: FMTU is seized for a test. LED flash: after the module is inserted until the loading of the required data is finished.

4.5.15

FMTU (-Q117-)
FMTU

Function Module for Test Unit

BEL

green LED

LED BEL on: FMTU is seized for a test. LED flash: after the module is inserted until the loading of the required data is finished.

4.5.16

FTEM (-Q957-)
FTEM

Function Test Module for SLMA

q
AA AB

BL

green LED Test jack Test jack

LED BL on: module is seized by a test job. LED flash: after the module is inserted until the loading of the required data is finished. AA and AB are trace connections for the potentials on the A- and B-wires of the line circuit or line side to be tested.

614

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.17

GCG (-Q1322-)
GCG

Group clock generator

q
RES LCM DCM

yellow LED Switch

LED M on: Clock generator is MASTER. LED M off: Clock generator is SLAVE. For switching from MASTER to SLAVE and vice versa. (the switching is only effective on GCG1). Switch up: GCG0 is MASTER / Switch down: GCG1 is MASTER LED LCM on: VCO is synchronized by the 8-kHz clock. LED LCM off: VCO is synchronized by the 8-kHz clock supplied from the partner module. LED DCM on: Clock (CLK) and frame synchronization pulse (FS) are fed to DLU from this module. LED UNA on: Failure of clock generator (CG)

q q UNA q

green LED

green LED red LED

A30828-X1160-M-2-7620

615

Construction

Maintenance Node

4.5.18

IWEx (-Q144-)
IWEx

Interworking function module x (x = D, E) - High Speed

X100
H1 H2 H3 H4 H5 H6 H7 H8

X100: RAP Connector Babyboard LED (H1 - H4): For further information to LED signaling see following table TIP (H5, H6) and ICP (H7, H8) LED: For further information to LED signaling see following table X400: RMP Connector

X400

X500

X500: RDP Connector

X600
S1

X600: RTP Connector

S1: Key for EPost Request


S2

S2: Key for reset

Note: All connectors on the board are test-connectors for the factory

In case of connecting this IWEx with external modem (housed in a modem frame), LED H1 - H3 will be permanently off. The external modem is connected to the EMB.

External Modem interface Board (EMB) Condition SLIC idle SLIC active

LED H4

off green

Tab. 4.18

IWEx (-Q144-) LED description H4

616

A30828-X1160-M-2-7620

Maintenance Node

Construction

Analog Modem subboard (AMB) Condition Modem not operating Modem OK Offhook Offhook and DCD (data carier detected) Sending RxD data Offhook and DCD (data carier detected) Receiving TxD data Offhook and DCD (data carier detected) Sending RxD data and receiving TxD data

LED H1

LED H2

LED H3 and H4

off green red yellow

off off off green

yellow

red

LED H3 and H4 are permanently off. They can be used in future for indicating the status of the 2nd modem if an AMB with 2 analog modems is used.

yellow

yellow

Tab. 4.19

IWEx (-Q144-) LED description H1-H4

TIP Boot phase Condition TIP reset or TIP not completely programmed by ICP TIP started, running Basic POST TIP sleep mode

LED H5

LED H6

red off off

off green (2.5Hz) green

Tab. 4.20

IWEx (-Q144-) LED description H5-H6 - TIP Boot phase

TIP OS phase Condition Diagnostic test (MNT) during first 3 seconds of OS phase Idle Call: setup Call: synchronizing with mobile network Call: synchronizing with fixed network Call: active Call: failure detected during a call Test: active LTG PCM looptest (CTS) Test: TIP diagnostic failure Any other condition
1) Since LTG initiates a PCM looptest every 20 sec, LED H6

LED H5

LED H6

yellow (10Hz) yellow (5Hz) green (0.5Hz) green (5Hz) green (10Hz) green red green 1) red off will be green for ca. 0.5 sec every

20 sec

Tab. 4.21

IWEx (-Q144-) LED description H5-H6 - TIP OS phase

A30828-X1160-M-2-7620

617

Construction

Maintenance Node

ICP Boot phase Normal condition, without RMP IWEx reset Hardware failure: reset line remains active or clocks are missing. ICP CPU or ICP base RAM failure Loader running, checking the presence of RMP BPOST started, no error Error found before BPOST is started or error found in BPOST test, BPOST not finished BPOST finished with no errors BPOST finished, test failed; Base RAM or flash error BPOST finished, test failed; ICP internal BPOST finished, test failed; TIP or CNP Boot finished, system handover to OSU

Duration

LED H7

LED H8

< 6 sec unlimited

red red

off off

< 2 sec < 20 sec < 20 sec

off yellow) yellow / red (4Hz)

off off off

< 2 sec ICP halted, press reset button < 1 sec

yellow red (8Hz)


1) 1) 1)

off yellow red green green

red (8Hz) red (8Hz) green

1) Whenever LED H7 flashes fast (8Hz) the system is halted; it is possible to connect a RMPC to the serial

port X400 to communicate with the IWEx, except when a firmware error is detected (both LEDs flashing fast). In this case it may not be possible to communicate with the RMP.

Tab. 4.22

IWEx (-Q144-) LED description H7-H8 - ICP Boot phase

Extended test ICP boot condition, without RMP IWEx reset Loader running, checking the presence of RMP BPOST started, key S1 on the front panel has was pressed during this condition BPOST started, EPOST request detected

Duration < 6 sec < 2 sec < 20 sec

LED H7 red off yellow off off off

LED H8

< 20 sec

yellow

yellow (0.5Hz)1) yellow (0.5Hz)1) yellow yellow

BPOST started with error, EPOST request detected

< 20 sec

yellow / red (4Hz) yellow yellow / red (4Hz) yellow

BPOST finished with no errors, EPOST started BPOST with error, EPOST started

< 60 sec < 60 sec

BPOST with no error, EPOST started and has already detected an error

< 60 sec

yellow / red (4Hz)

Tab. 4.23

IWEx (-Q144-) LED description H7-H8 - during EPOST

618

A30828-X1160-M-2-7620

Maintenance Node

Construction

Extended test ICP boot condition, without RMP EPOST finished; no errors in EPOST and BPOST EPOST finished; ICP core error EPOST finished; ICP peripheral error

Duration ICP halted, press reset button

LED H7 green (8Hz) red (8Hz) red (8Hz)


2) 2)

LED H8 green (8Hz) red (4Hz) yellow / red (4Hz) green / red (4Hz) yellow (4Hz) yellow / green (4Hz) green (4Hz)

EPOST finished; DRAM error

red (8Hz)2) red (8Hz)2) red (8Hz)2)

EPOST finished; FEPROM error EPOST finished; CNP error

EPOST finished; TIP error


1)

red (8Hz)2)

Detection of key S1 was pressed is confirmed by LED H8 becoming yellow (Extended POST request detected). 2) Whenever LED H7 flashes fast (8Hz) the system is halted; it is possible to connect a RMPC to the serial port X400 to communicate with the IWEx, except when a firmware error is detected (both LEDs flashing fast). In this case it may not be possible to communicate with the RMP.

Tab. 4.23

IWEx (-Q144-) LED description H7-H8 - during EPOST

ICP condition with RMP connected to X400 BPOST started, key S1 is not pressed BPOST started, EPOST request detected BPOST finished, EPOST request detected ICP is waiting until the user presses a key on the local PC BPOST finished; no EPOST request

Duration < 20 sec < 20 sec RMP: press any key to continue

LED H7 yellow yellow yellow

LED H8 green (0.5Hz) yellow / green (0.5Hz)1)

see: IWEx (-Q144-) LED description H7-H8 - ICP Boot phase see: IWEx (-Q144-) LED description H7-H8 - during EPOST

EPOST finished; with or without errors

RMP is showing one of its menu and is waiting for a selection to be made by the RMPC user

waiting for input of the RMP user < 300 sec

off

green

RMP is busy (e.g. downloading new firmware)


1)

yellow

green

In case the EPOST request is received in the beginning of the first condition (BPOST started, key S1 on the front panel is not pressed), it is possible that LED H8 becomes off/yellow (1Hz). LED H8 being intermittently green, indicates that the ICP has detected the presence of RMPC.

Tab. 4.24

IWEx (-Q144-) LED description H7-H8 - with X400

ICP normal operation Condition Card is waiting for a call Card has been seized for a call, call is not yet active Call active

LED H7

green yellow yellow (8Hz)

Tab. 4.25

IWEx (-Q144-) LED description H7 - during ICP OS

A30828-X1160-M-2-7620

619

Construction

Maintenance Node

ICP normal operation Condition Call has been released, waiting for acknowledge red

LED H7

Tab. 4.25

IWEx (-Q144-) LED description H7 - during ICP OS

ICP normal operation Condition ICP has booted and is now waiting for polling from the DLUC DLUC has started polling, the IWEx has sent a recovery request to DLUC and is waiting for the first recovery data from DLUC/LTG Recovery data received, dard is ready for a call Card has been placed in maintenance mode by LTG Call active Performing diagnosis Something went wrong, fatal error INI INI

OST

OSTT

LED H8

INI/STB INI/STB

red (0.5Hz) yellow

ACT MBL/CBL any any any

INI/STB INI/STB ACT SEZ DST

green (0.5Hz) yellow (0.5Hz) green (4Hz) yellow (4Hz) red (4Hz)

Tab. 4.26

IWEx (-Q144-) LED description H8 - during ICP OS

620

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.19

IWEx (-Q1177-)
IWEx H1

Interworking function module x (x = A, B, C, D, E or F)

q H2 q H3 q

red LED yellow LED green LED

only switches ON if fault occurs only switches ON during initialisation phase only switches ON when seized with a CALL

S1

S1: Key for hardware program interruption


S2

S2: Key for reset

IWEx

Interworking function module x (x = A, B, C, D, E or F)

Delivery status: S3 open

Jumper S3

A30828-X1160-M-2-7620

621

Construction

Maintenance Node

4.5.20

IWESx (-Q1178-)

IWESx H2

Interworking function unit x (x = A, B, C, D, E or F)

q H1 q H3 q

yellow LED red LED green LED

General: green LED is activated if IWE is seized with a CALL red LED is activated when a fault occurs yellow LED flashes during fault-free operation Otherwise the display control has 4 different status which are defined in the following table:

Status H2 (yellow) RESET HW-Test Task Manager Connection setup / cancel


S1

LED H1 (red) ON ON ON OFF OFF H3 (green) ON ON OFF OFF see the following table

ON OFF flashes flashes OFF

When the red LED is active for Task manager a HW fault was detected S1: Key for reset

LED H3 flashing status: flash very slowly: flash very slowly: flash quickly: ON: OFF:

Significance Service assignment (SZB-Ack.) Timeslot assignment (DLI/TSA-Ack.) synchronization controlled from mobile network (ACTIVATE-Ack.) synchronization controlled from network (GO-Ack.) not seized (RLI-Ack.)

622

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.21

LMEM (-Q811-)
LMEM Line Measuring Module for SLMA Delivery status: B1 removed Operation status: B1 soldered when Ub = -48V

Jumper B1

4.5.22

LVMM (-Q812-)
LVMM
Jumper B1 B2 B4 B5 B3

Level Measuring Module for SLMA Delivery status: B1, B5 are soldered Jumpers are soldered on a country-specific basis.

A30828-X1160-M-2-7620

623

Construction

Maintenance Node

4.5.23

LTCD (-Q124-)
LTCD H1

Line Termination Copper for DLU green LED red LED Switch For operation see table below For operation see table below Service switch for test loop in the LT-module (Local Analog Loop) Service switch for test loop in the NT-side (Remote Digital Loop)

q H2 q S1
S2

Switch

LED H1 on off off on on flash

LED H2 off off on on flash on

Alarm and status signalling Operation status Non-operation voltage Urgent alarm (A-Alarm) Fault / service alarm (S-Alarm) Non-urgent alarm (B-Alarm) Laser-restart

LTCD
X7 X10

X8

X9

X3 X13

X14

F5

X11 X12 X6

Jumper X8/X9 (Impedance System 0): Pin 1 and 2: 75 Ohm Pin 2 and 3: 120 Ohm Jumper X7/X10 (Impedance System 1): Pin 1 and 2: 75 Ohm Pin 2 and 3: 120 Ohm Jumper X6 (Setting LT/NT): Pin 1 and 2: NT Pin 2 and 3: LT Pin 2 and 3: disabled Jumper X11 (ILMT test signal) Pin 1 and 2: disabled Pin 2 and 3: activated Jumper X12 (SSP test signal) Pin 1 and 2: disabled Pin 2 and 3: activated Jumper X13 (LTC_RXD1-signal) Pin 1 and 2: disabled Pin 2 and 3: activated Jumper X14 (INTCN-signal) Pin 1 and 2: disabled Pin 2 and 3: activated Test connector X3 Only for test Miniaturfuse F5

624

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.24

LTCD (-Q1495-)
LTCD STATUS ALARM

Line Termination Copper for DLU green LED red LED For operation see table below For operation see table below

q q

S1

Switch
S2

Service switch for test loop in the LT-module (Local Analog Loop) Service switch for test loop in the NT-side (Remote Digital Loop)

Switch

LED (STATUS) on off off on on flash Copper Line Termination

LED (ALARM) off off on on flash on

Alarm and status signalling Operation status Non-operation voltage Urgent alarm (A-Alarm) Fault / service alarm (S-Alarm) Non-urgent alarm (B-Alarm) Laser-restart

LTCD
X7 X10

X8

X9

X13 X14

X11 X12 X6

X15

X4 X5

Jumper X8/X9 (Impedance System 0): Pin 1 and 2: 75 Ohm Pin 2 and 3: 120 Ohm Jumper X7/X10 (Impedance System 1): Pin 1 and 2: 75 Ohm Pin 2 and 3: 120 Ohm Jumper X6 (Setting LT/NT): Pin 1 and 2: NT Pin 2 and 3: LT Jumper X4/X5 (Power supply): Pin 1 and 2: closed Jumper X15 (PRS signal): Pin 1 and 2: activated Pin 2 and 3: disabled Jumper X11 (ILMT test signal) Pin 1 and 2: disabled Pin 2 and 3: activated Jumper X12 (SSP test signal) Pin 1 and 2: disabled Pin 2 and 3: activated Jumper X13 (LTC_RXD1-signal) Pin 1 and 2: disabled Pin 2 and 3: activated Jumper X14 (INTCN-signal) Pin 1 and 2: disabled Pin 2 and 3: activated

A30828-X1160-M-2-7620

625

Construction

Maintenance Node

4.5.25

LTOD (-Q1496-)
LTOD ON

Line Termination Optic for DLU

q INT q
LAS

green LED red LED

For operation see table below For operation see table below

Switch

Laser-restart

LED (ON) on off off on on flash

LED (INT) off off on on flash any

Alarm and status signalling Operation status Non-operation voltage Urgent alarm (A-Alarm) Fault / service alarm (S-Alarm) Non-urgent alarm (B-Alarm) Laser-restart

Optical line termination

LTOD

ON

OFF

Setting of Switch S5: 1 = ON: only for setting (laser ON) 1 = OFF: only for setting (laser OFF) 2 = not relevant 3 = not relevant 4 = not relevant 5 = not relevant 6 = not relevant 7 = ON: operation mode 7 = OFF: test mode for test field 8 = ON: LED signalling for stand-alone operation 8 = OFF: LED signalling for monitored operation (operation mode)

626

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.26

MGB (-Q1323-)
MGB

Meter Pulse Generator type B

V29

q
S1

green LED

LED on: operation mode

Switch

Switch up: MGB on Switch down: MGB off

X23

Test jack
X24

Metering AC output can be checked between test jacks X23 and X24 Test jack

MGB
W1

Switch 2 (frequency): 12kHz: 2-3 closed 16kHz: 1-3 closed Switch 3 (voltage): 4.8V: 1-2 open and 3-4 closed 5.25V: 1-2 closed and 3-4 open 8.2V: 1-2 open and 3-4 open W1 soldered Delivery status: 16kHz, 8.2V, W1 soldered

Switch S3 Switch S2 1 2 3 4 2

3 1

A30828-X1160-M-2-7620

627

Construction

Maintenance Node

4.5.27

MTAM (-Q1066-)
MTAM

Metallic Test Access Module 4 LEDs are needed for each side. The LEDs indicate the current state of the signal wires. Only the LED that is linked to the signal wire state lit. The table below shows the state of the signal wires and the corresponding outputs.

q q NL0 q NH0 q
PL0

PH0

green LED green LED green LED green LED

Explanation LED: 1= LED on, 0 = LED off Status Range (mA) HIGH POS. 21 to 210 6 to 18 -3 to +3 -6 to -18 -21 to -210 NH 0 0 0 0 1 NL 0 0 0 1 0 LED PL 0 1 0 0 0 PH 1 0 0 0 0

q PL1 q NL1 q NH1 q

PH1

green LED green LED green LED green LED

LOW POS. OPEN LOW NEG. HIGH NEG.

MTAM

Switch S103 3 1 S105 3 1 S101 1 S102 1 S104 3 1 S106 3 1 4 2 4 2 3 2 3 2 4 2 4 2

Notes on use: If the local OMT accesses the ground loop indirectly via the MTAM, switches S101 or S102 must be in position 1-3. The switches must be in position 1-2 if the local OMT accesses the ground loop directly. Test Bus Access Interface Configuration: Switches S103, S104, S105 and S106 consist of connection pairs. One for tip and one for ringing voltage. The two switches must operate together. Status A: Normal operation, all switches (S103 to S106) are open. Status B: Minimum MTA configuration. No TBA modules are installed and the first MTA module is involved. MTAM circuits 0 and 1 are connected to test bus 0 and 1 respectively. (S103, 105=closed, S104, 106=open) Status C: Minimum MTA configuration. No TBA modules are installed and the second MTA module is involved. MTAM circuits 0 and 1 are connected to test bus 2 and 3 respectively. (S103, 105=open, S104, 106=closed)

628

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.28

OMX16D (-Q1497-)
OMX16D ON

Optical Multiplexer

q INT q
LAS

green LED red LED

For operation see table below For operation see table below

Switch

Laser-restart

LED (ON) on off off on flash

LED (INT) off off on flash any

Alarm and status signalling Operation mode Non-operation voltage No signal input, BER-alarm (34Mbit/s signal), LPOWER HIGH, buffer overflow of receiver or transmitter AIS-alarm, BER-alarm, LBIAS HIGH, LPOWER LOW Laser-restart

Optical line termination

OMX16D

Test connector X37 and X38: (only for module compensation)

X38

X37

A30828-X1160-M-2-7620

629

Construction

Maintenance Node

4.5.29

RGB (-Q1324-)
RGB

Ringing Generator, type B

q
S1

H1

green LED

LED on: operation mode

Switch

Switch up: RGB on Switch down: RGB off

X3

Test jack
X4

Ringing AC output can be checked between test jacks X3 and X4 Test jack

RGB

F2

Switch S3 21

F1

13 11 9 7 5 3 1

Switch S2 14 12 10 8 6 4 2

Switch S2 (frequency): 16.666Hz: 1-2 closed, 3-4 open, 5-6 open, 7-8 open 20Hz: 1-2 open, 3-4 closed, 5-6 open, 7-8 open 25Hz: 1-2 open, 3-4 open, 5-6 closed, 7-8 open 50Hz: 1-2 open, 3-4 open, 5-6 open, 7-8 closed Switch S2 (voltage): 65V: 9-10 open, 11-12 open, 13-14 closed 70V: 9-10 open, 11-12 closed, 13-14 open 90V: 9-10 closed, 11-12 open, 13-14 open 98V: 9-10 open, 11-12 open, 13-14 open Switch S3 (current limiting): 65V / 70V: 1-3 closed 90V / 98V: 2-3 closed Miniaturfuse F2 and F5

Delivery status: 25Hz, 90V

630

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.30

RGMG (-Q813-)
RGMG

Ringing Current Generator and Meter Pulse Generator

V33

q
S1

green LED Switch

LED on: operation mode Switch up: RGMG on Switch down: RGMG off

X21

Test jack
X22

Test jack
X23

Ringing AC output can be checked between test jacks X21 and X22

Test jack
X24

Metering AC output can be checked between test jacks X23 and X24

Test jack

RGMG
W3 W2

W1

W5 W4 1 3 5 S4 S2 2 4 6 S7 12 3

Switch S2 (frequency): 16.666Hz: 1-2 closed, 3-4 open, 5-6 open 20Hz: 1-2 open, 3-4 open, 5-6 closed 25Hz: 1-2 open, 3-4 closed, 5-6 open Switch S4 (voltage): 70V: 1-2 open 90V: 1-2 closed Switch S7 (frequency): 12kHz: 2-3 closed 16kHz: 1-3 closed Jumper W1-W5: W1-W5 are soldered

Delivery status: 16,66Hz, 90V, 16kHz

A30828-X1160-M-2-7620

631

Construction

Maintenance Node

RGMG
B3 B2

B1 B5 Switch S1-S5 1 2 34 5 ON OFF B4 S7 12

Switch 3

Switch 1... 4 (frequency): 16.666Hz: S1... 4 in position OFF 20Hz: 1-2 S1 and S3 in position ON, S2 and S4 in position OFF 25Hz: 1-2 S2 and S4 in position ON, S1 and S3 in position OFF Switch 5 (voltage): 70V: position OFF 90V: position ON Switch 7 (frequency): 12kHz: 2-3 closed 16kHz: 1-3 closed Jumper B1-B5: B1-B5 are soldered

Delivery status: 16,66Hz, 90V, 16kHz, B1...5 are soldered

RGMG
B3 B2

Jumper B1-B11: B1-B11 are soldered

B1 B7 B8 B9 B6 B10 B4 B11 B5

Delivery status: 50 Hz, 65 V; 12 kHz

632

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.31

RGMG (-Q895-)
RGMG

Ringing Current Generator and Meter Pulse Generator

V33

q
HS

green LED Switch

LED on: operation mode Switch up: RGMG on Switch down: RGMG off

X21

Test jack
X22

Ringing AC output can be checked between test jacks X21 and X22

Test jack
X23

Test jack
X24

Metering AC output can be checked between test jacks X23 and X24 Test jack

RGMG
W3 W2

Jumper W1-W5: W1-W5 are soldered

W1

W5 W4

A30828-X1160-M-2-7620

633

Construction

Maintenance Node

4.5.32

SASC (-Q1133-), (-Q22-)


SASC IN

Stand Alone Service Control

q L2 q L1 q L0 q

red LED yellow LED yellow LED yellow LED

LED on: SASC processor is inoperable LED off: SASC processor is active L2 0 0 0 0 1 1 1 L1 0 0 1 1 0 1 1 L0 0 1 0 1 1 0 1 invalid state idle / self-test in BOOT download of code in progress operation mode operation status ACT transition to SAS SAS is active Explanation LED

interface for testadapter and tracer (optional)

4.5.33

SASCG (-Q111-)
SASCG IN

Stand Alone Service Control for DLUG

q L2 q L1 q L0 q

red LED green LED green LED green LED

LED on: SASC processor is inoperable LED off: SASC processor is active L2 0 0 0 0 1 1 1 L1 0 0 1 1 0 1 1 L0 0 1 0 1 1 0 1 invalid state idle / self-test in BOOT download of code in progress operation mode operation status ACT transition to SAS SAS is active Explanation LED

PC

interface for testadapter and tracer (optional)

634

A30828-X1160-M-2-7620

Maintenance Node

Construction

SASCG

X2

X6

F1

Connector X2, X6 and X7 (optional) Only for test and loading firmware Miniaturfuse F5

X7

4.5.34

SLMA (-Q1011-)

SLMA

Subscriber Line Module, analog LED off: LED on: SLC 0 busy SLC 1 busy SLC 2 busy SLC 3 busy LED flash: the line to the PABX is interrupted the line to the PABX is interrupted the line to the PABX is interrupted the line to the PABX is interrupted green LED green LED green LED green LED SLC 0 in idle status SLC 1 in idle status SLC 2 in idle status SLC 3 in idle status

q q q q

4.5.35

SLMD (-Q838-), (-Q965-), (-Q1101-), (-Q1103-), (-Q1192-)


SLMD

Subscriber Line Module, digital

H1

yellow LED

LED H1 on: SLMD is loaded and operable LED flash: the watchdog on the SLMD is activated

A30828-X1160-M-2-7620

635

Construction

Maintenance Node

SLMD (-Q838-), (-Q965-), (-Q1192-)


SLMD
Switch S1 1 2

Switch 1 (voltage): -60V: position 1 -93V: position 2

Delivery status: -93V

SLMD (-Q1101-), (-Q1103-)


SLMD
Switch S1 1 2

Switch 1 (voltage): -60V: position 1 -93V: position 2

Delivery status: -60V

Note: The module can also be operated with 97V supply voltage.

4.5.36

SLMD (-Q210-)
SLMD
Switch 1 (voltage): -60V: position 1 -97V: position 2

Switch S1 1 2

636

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.37

SLMD (-Q52-)
SLMD Switch 1 (voltage): -60V: position 1 -97V: position 2

Switch S1 2 1

4.5.38

SLMI:AMA (-Q225-)
SLMI

Subscriber Line Module, internet

ATM25 0 1

ATM25-interface

SLMI:AMA
X20

X5 X700

F1

X21

Miniaturfuse F1 Test connector X5 and X700: Only for test Connector X20 and X21: Connector to module ASPI (ADSL Splitter for ISDN (-Q256-))

A30828-X1160-M-2-7620

637

Construction

Maintenance Node

4.5.39

SLMI:FMA (-Q164-)
SLMI

Subscriber Line Module, internet

ATM25 0 1

ATM25-interface

SLMI:FMA

Switch S370 3 2 1 OFF ON


X825 ................. ................. X370 F5

Switch S370 Delivery status: S370-1 in position ON S370-2 and 3 in position OFF Setting (function): S370-1 in position ON: reset for test activated S370-2 in position ON: JTAG-interface X370 activated S370-3 not used Test connector X370 (JTAG-interface) Only for test Miniaturfuse F5 Test connector X825 (UART-interface) Only for test

4.5.40

SLMI:FMB (-Q200-)
SLMI:FMB
Switch S370 Delivery status: S370-1 in position ON S370-2 and 3 in position OFF Setting (function): S370-1 in position ON: reset for test activated S370-2 in position ON: JTAG-interface X370 activated S370-3 not used Test connector X370 (JTAG-interface) Only for test Miniaturfuse F5 Test connector X825 (UART-interface) Only for test

Switch S370 3 2 1 OFF ON


X825 ................. ................. X370 F5

638

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.41

SLMI:MPB (-Q143-)
SLMI

Subscriber Line Module, internet

interface for testadapter and tracer (optional)

SLMI:MPB

Test connector X7 and X5 (optional) Only for test Miniaturfuse F5

X5 F5 X7

A30828-X1160-M-2-7620

639

Construction

Maintenance Node

4.5.42

SLMI:PHA (-Q142-)
SLMI:PHA H1

Subscriber Line Module (packet hub) for high bit rate internet modules, type A red LED green LED 100BASE-T-interface

q H2 q

ATM25-interfaces 0-7
V24

LED H1 on on off off


E3/T3 E3/T3

LED H2 flash very quickly off flash flash very slowly

Alarm and status signalling Power-Up selftest Selftest failure operation mode (module is MBL) operation mode (module is ACT)

RS232 (V.24) interface E3/T3-interface (Rx) E3/T3-interface (Tx)

640

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.43

SLMI:PHA (-Q170-)
Subscriber Line Module (packet hub) for high bit rate internet modules, type A

SLMI:PHA

qq

STAT red LED (left), green LED (right): Alarm and status signalling

RES RS232
ATM25

Switch for RESET RS232 interface


8 ATM25 interfaces (0-15)

LED STAT (red) on on off


7 15 100 B/T

LED STAT (green) flash quickly off flash flash slowly

Alarm and status signalling Power-Up selftest Selftest failure Operation mode (module is MBL) Operation mode (module is ACT)

off

100BASE-T interface E3/T3 interfaces (Tx and Rx)

Tx

Rx

SLMI:PHA
X11
................. .................

Miniaturfuse F1 Test connector X32-X37: Only for test Connector X11: Connection of transformer module
F1 X33 X37 X32

A30828-X1160-M-2-7620

641

Construction

Maintenance Node

4.5.44

SLMI:PHB (-Q192-)
SLMI:PHB STAT

Subscriber Line Module (packet hub) for high bit rate internet modules, type B

qq
RES

red LED(left), green LED(right): status signalling

Switch for RESET

V24

RS232

RS232-interface for test

LED STAT (red) on on off off

LED STAT (green) flash quickly off flash flash slowly

Alarm and status signalling Power-Up selftest Selftest failure operation mode (module is MBL) operation mode (module is ACT)

SLMI:PHB
X11
................. .................

Miniaturfuse F1 Test connector X6-X37: Only for test

F1

X25

X22 X23 X6 X24

X28 X27

X37 X32

X31

642

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.5.45

SLMI:SDA (-Q155-)
SLMI

Subscriber Line Module, internet

ATM25 0

ATM25 interface
1

ATM25 0 1

4.5.46

SLMX (-Q1338-)
SLMX

Subscriber Line Module for V5.1-interfaces

SE0 IN0 MA0 SA0 SE1 IN1 MA1 SA1

green LED yellow LED red LED red LED green LED yellow LED red LED red LED

SE0 or SE1 IN0 or IN1 MA0 or MA1 SA0 or SA1

LED on: Level 1 is active LED flash: ALCO alarm counter overflow LED on: V5 interface is out of order LED on: DSV failure (maintenance alarm) LED on: DSV fault (service alarm)

PWR green LED

PWR

LED on: power supply is connected, watchdog faulty LED flash: watchdog is active

A30828-X1160-M-2-7620

643

Construction

Maintenance Node

4.6

LTG
4.6.1 4.6.2 4.6.3 4.6.4 4.6.5 4.6.6 4.6.7 4.6.8 4.6.9 4.6.10 4.6.11 4.6.12 4.6.13 4.6.14 4.6.15 4.6.16 4.6.17 4.6.18 4.6.19 4.6.20 4.6.21 4.6.22 4.6.23 4.6.24 4.6.25 4.6.26 4.6.27 4.6.28 4.6.29 4.6.30 4.6.31 4.6.32 4.6.33 4.6.34 4.6.35 4.6.36 4.6.37 4.6.38 4.6.39 4.6.40 4.6.41 4.6.42 4.6.43 4.6.44 4.6.45 ATCO (-Q267-) ATE:TM (-Q969-) ATE:N (-Q94-) CGSM (-Q1185-) COUC (-Q31-) CRM:R1 (-Q913-) CRM8:R1 (-Q1105-) CRM:R2 (-Q913-) CRM8:R2 (-Q1105-) CRM:SC (-Q913-) CRPC (-Q264-) CRPC (-Q913-) CRP8 (-Q1105-) DCRCx (-Q743-) DEC120 (-Q1467-) DEC120 (-Q1467-X100) DEC480 (-Q328-) DESA (-A162-) DESB_A1 (-B163-A1-) DESB_B1 (-B163-B1-) DIU30A (-Q562-) DIU30B (-Q563-) DIU30D (-Q876-) DIU30F (-Q876-X200-) DIU120A (-Q1346-) DIU:LDIB (-Q1107-) DIU:LDIM (-Q1343-) ETEAE (-Q670-) GCG:LTGY (-Q724-) GPLC (-Q1349-X301-) GPLD (-Q1349-X401-) GPLSD (-Q1339-X401-) GPLSE (-Q1339-X601-) GPNLD (-Q28-X200-) GPNLE (-Q28-X600-) GPNYC (-Q27-) GPNYD (-Q27-X200-) GPNYE (-Q27-X600-) GPNZC (-Q26-) GPNZD (-Q26-X200-) GPNZE (-Q26-X600-) GPPYF (-Q277-X000 -) GPPYG (-Q277-X100 -) GPPYH (-Q277-X200 -) GPPYI (-Q277-X300 -)

644

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.46 4.6.47 4.6.48 4.6.49 4.6.50 4.6.51 4.6.52 4.6.53 4.6.54 4.6.55 4.6.56 4.6.57 4.6.58 4.6.59 4.6.60 4.6.61 4.6.62 4.6.63 4.6.64 4.6.65 4.6.66 4.6.67 4.6.68 4.6.69 4.6.70 4.6.71 4.6.72 4.6.73 4.6.74

GPPZF (-Q302-X000 -) GPPZG (-Q302-X100 -) GPPZH (-Q302-X200 -) GPPZI (-Q302-X300 -) GSM (-Q1340-) MCAA (-Q729-) MCT (-Q63-) MDTOG (-Q1105-) MDTOG (-Q1490-) OCE:MUPx (-Q1030-) OCE:SPC (-Q1031-) OCE:SPM (-Q1401-) OCE:N (-Q165-) PHMA (-Q1469-) PMUx (-Q1141-) PMUE (-Q1141-X600-) RM:CTC (-Q829-) RM:CTC (-Q913-) SCR (-Q1445-) SILCB (-Q1110-) SILCD (-Q1110-X200-) SILC:DLU (-Q783-) SILC:PA (-Q783-) TEM:COP (-Q606-) TEM:LE (-Q607-) TOGB (-Q738-) TOGC (-Q1290-) TOGD (-Q1291-) VPU (-Q190-)

A30828-X1160-M-2-7620

645

Construction

Maintenance Node

4.6.1

ATCO (-Q267-)
ATCO

Automatic Test and Conference Unit for LTG

Switch Module hardware reset


RES

q
ERR

red LED green LED

LED ERR off off on on flashing blips off off on off on off on

LED RUN

State of the board power failure normal operation hardware fault fuse alarm with unit in service transient state, initialization, configuration, loading or self-test communication link to GP is down, unit is O.K. ATCO is in out-of-service state

q
RUN

blips

V24

V24 Interface

Note: Flashing: 600 to 700mS LED on, 600 to 700mS LED off Blips: 80 to 100mS LED on, 1000 to 1200mS LED off

ATCO
OFF

S1 ON 1 2 3 4 5 6 7 8

The assignment of the DIL switch S1 see: Tab. 4.27

Switch 1

Setting Bootloader

State OFF ON Bootloader disabled

Meaning

Bootloader enabled only via V.24 disabled enabled only if switch #1 closed

Boot Loader via SMX#1

OFF ON

Tab. 4.27

Switch positions S1 on the ATCO

646

A30828-X1160-M-2-7620

Maintenance Node

Construction

Switch 3

Setting available

State OFF ON

Meaning

Operation mode (LTGC) Companding law

OFF ON OFF ON

ATE mode COU mode - Law A - Law TEM:LE - BEL, YUG TEM:LE - WM, DTAG ATE:TM operating mode (switches 5 and 6 unused) TEM:LE operating mode the FW recognizes automatically the operation mode based on messages from the GP the operation mode is determined by switch 7

Variant

OFF ON

Operation mode Automatic operation for ATE mode

OFF ON ON

OFF

Tab. 4.27

Switch positions S1 on the ATCO

4.6.2

ATE:TM (-Q969-)
ATE:TM H1

Automatic Test Equipment for Transmission Measurements

q
H2

green LED green LED

H1 on: transmit operating state H2 on: transmit operating receiver

A30828-X1160-M-2-7620

647

Construction

Maintenance Node

4.6.3

ATE:N (-Q94-)
ATE:N

Automatic Test Equipment for LTGM/N

BOST

red LED green LED green LED

BOST on: board self test (BOST) detects a failure TRSM and REC on: Module not initiated or hardware fault TRSM and REC off: Module initiated TRSM flashes: transmitter active REC flashes: receiver active

TRSM

REC

serial interface connector for service PC

648

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.4

CGSM (-Q1185-)
CGSM

Clock Generator and Signal Multiplexer

SYNC

q PU q GCG q
MU

red LED red LED red LED red LED

SYNC on: no MCH of the LTG is active PU on: Boots-Checksum incorrect, ASIC or some other chip faulty GCG on: Watchdog faulty
GCG

MU on: Memory error on the PMU

4.6.5

COUC (-Q31-)
COUC

Conference Unit C

BOST

red LED

BOST on: board self test (BOST) detects a failure

serial interface connector PC

COUC

DIP-FIX switch S1: S1 open = A-law S1 closed = -law

S1 DIP-FIX switch

A30828-X1160-M-2-7620

649

Construction

Maintenance Node

4.6.6

CRM:R1 (-Q913-)
CRM:R1 Code Receiver for Multifrequency R1 Signaling

SIGO

SIG0 on: signal recognized (code receiver 0)


BSY0 SIG1 BSY1

BSY0 on: code receiver 0 seized SIG1 on: signal recognized (code receiver 1) BSY1 on: code receiver 1 seized

SSW SIG2

SIG2 on: signal recognized (code receiver 2)


BSY2

BSY2 on: code receiver 2 seized


SIG3

SIG3 on: signal recognized (code receiver 3)


BSY3

BSY3 on: code receiver 3 seized

up: code receiver enabled/ down: code receiver disabled

CRM:R1
S1 DIP-FIX switch

DIP-FIX switches: S1 open = int. program memory S1 closed = ext. program memory S2 closed / S3 open = 4-device module S4 open = watchdog enabled
DIL switch S5: 1 2 3 4 5 6 7 8 1 0

DIL switch S5 1 2 3 4 5 6 7 8 1 0 S3 DIP-FIX switch S4 S2

CRM:R1 A-law function


1 2 3 4 5 6 7 8

1 0

CRM:R1 -law function

650

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.7

CRM8:R1 (-Q1105-)
CRM8: R1 ERR

Code Receiver for Mehrfrequency R1 Signaling

red LED green LED

ERR on: hardware faulty BSY on: one or more receivers are seized

BSY

4.6.8

CRM:R2 (-Q913-)
CRM:R2

Code Receiver for Mehrfrequency R2 Signaling

SIGO

green LED
BSY0 SIG1 BSY1

SIG0 on: signal recognized (code receiver 0) BSY0 on: code receiver 0 seized SIG1 on: signal recognized (code receiver 1) BSY1 on: code receiver 1 seized

green LED green LED green LED

SSW SIG2 BSY2

green LED green LED

SIG2 on: signal recognized (code receiver 2) BSY2 on: code receiver 2 seized SIG3 on: signal recognized (code receiver 3) BSY3 on: code receiver 3 seized up: code receiver enabled/ down: code receiver disabled

SIG3 BSY3

green LED green LED

switches

CRM:R2
S1 DIP-FIX switch

DIP-FIX switches: S1 open = int. program memory S1 closed = ext. program memory S2 closed / S3 open = 4-device module S4 open = watchdog enabled

DIL switch S5 1 2 3 4 5 6 7 8 1 0 S3 DIP-FIX switch S4 S2

DIL switch S5: 1 2 3 4 5 6 7 8 1 0 1 2 3 4 5 6 7 8 1 0

CRM:R2 A-law function

CRM:R2 -law function

A30828-X1160-M-2-7620

651

Construction

Maintenance Node

4.6.9

CRM8:R2 (-Q1105-)
CRM8: R2 ERR

Code Receiver for Mehrfrequency R2 Signaling

red LED green LED

ERR on: hardware faulty BSY on: one or more receiver are seized

BSY

4.6.10

CRM:SC (-Q913-)
CRM:SC

Code Receiver for Mehrfrequency SC Signaling

SIGO

green LED
BSY0 SIG1 BSY1

SIG0 on: signal recognized (code receiver 0) BSY0 on: code receiver 0 seized SIG1 on: signal recognized (code receiver 1) BSY1 on: code receiver 1 seized

green LED green LED green LED

SSW SIG2 BSY2

green LED green LED

SIG2 on: signal recognized (code receiver 2) BSY2 on: code receiver 2 seized SIG3 on: signal recognized (code receiver 3) BSY3 on: code receiver 3 seized

SIG3 BSY3

green LED green LED

switches

up: code receiver enabled/ down: code receiver disabled

CRM:SC
S1 DIP-FIX switch

DIP-FIX switches: S1 open = int. program memory S1 closed = ext. program memory S2 closed / S3 open = 4-device module S4 open = watchdog enabled

DIL switch S5 1 2 3 4 5 6 7 8 1 0 S3 DIP-FIX switch S4 S2

DIL switch S5: 1 2 3 4 5 6 7 8 1 0

CRM:SC A-law function

652

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.11

CRPC (-Q264-)
CRPC

Code Receiver for Pushbutton

SIGO BSY0 SIG1 BSY1

green LED green LED green LED green LED

SIG0 on: signal recognized (code receiver 0) BSY0 on: code receiver 0 seized SIG1 on: signal recognized (code receiver 1) BSY1 on: code receiver 1 seized
SIG3

SSW SIG2

green LED
BSY2

SIG2 on: signal recognized (code receiver 2) BSY2 on: code receiver 2 seized SIG3 on: signal recognized (code receiver 3) BSY3 on: code receiver 3 seized

green LED
SIG3

green LED
BSY3

green LED

switches

up: code receiver enabled/ down: code receiver disabled

A30828-X1160-M-2-7620

653

Construction

Maintenance Node

4.6.12

CRPC (-Q913-)
CRPC

Code Receiver for Pushbutton

SIGO BSY0 SIG1 BSY1

green LED green LED green LED green LED

SIG0 on: signal recognized (code receiver 0) BSY0 on: code receiver 0 seized SIG1 on: signal recognized (code receiver 1) BSY1 on: code receiver 1 seized

SSW SIG2 BSY2 SIG3

green LED green LED green LED

SIG2 on: signal recognized (code receiver 2) BSY2 on: code receiver 2 seized SIG3 on: signal recognized (code receiver 3) BSY3 on: code receiver 3 seized

BSY3

green LED

switches

up: code receiver enabled/ down: code receiver disabled

CRPC
S1 DIP-FIX switch

DIP-FIX switches: S1 open = int. program memory S1 closed = ext. program memory S2 closed / S3 open = 4-device module S4 open = watchdog enabled

DIL switch S5 1 2 3 4 5 6 7 8 1 0 S3 DIP-FIX switch S4 S2

DIL switch S5: 1 2 3 4 5 6 7 8 1 0 1 2 3 4 5 6 7 8 1 0

CRPC A-law function

CRPC -law function

654

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.13

CRP8 (-Q1105-)
CRP8

Code Receiver for Pushbutton

q BSY q

ERR

red LED green LED

ERR on: hardware faulty BSY on: one or more receiver are seized

4.6.14

DCRCx (-Q743-)
DCRCx
S2 F

Digital Code Receiver C


BE

DIP-FIX switch

DIP-FIX switches: S1 S2 A-D B-F A-D E-F C-D E-F

Meaning 1 Kbyte PROM 1 Kbyte PROM 1 Kbyte PROM

D S1 CA

4.6.15

DEC120 (-Q1467-)
DEC120 BOST

Digital Echo Compensator (120 channel)

red LED

BOST on: board self test (BOST) detects a failure

Seriel diagnostics interface with PC connection for reading out levels, attennation, switching status and coefficients. Notes are also output when looking for errors after alarm signals

A30828-X1160-M-2-7620

655

Construction

Maintenance Node

DEC120
DIP-FIX-switch 2 4 6 8 10 12 14 16 S4 1 3 5 7 9 11 13 15

S2 1-2 closed: switching center 2-3 closed: mobile switching center S4 9-10 open: A-law 9-10 closed: -law all other DIP-FIX of the S4 must be open

1 3 S2

4.6.16

DEC120 (-Q1467-X100)
DEC120 BOST

Digital Echo Compensator (120 channel)

red LED

BOST on: board self test (BOST) detects a failure

Seriel diagnostics interface with PC connection for reading out levels, attennation, switching status and coefficients. Notes are also output when looking for errors after alarm signals

V24

656

A30828-X1160-M-2-7620

Maintenance Node

Construction

DEC120

Link connector 20 18 16 14 12 10 8 6 4 2 X9 19 17 15 13 11 9 7 5 3 1

X9 1-2 3-4 5-6 7-8 9 - 10 11 - 12 13 - 14 15 - 16 17 - 18 19 - 20

open These connections must be open

closed

Extended tone suppression Speech protection as per ITU Echo detection up to 0dB A-law Self-test enabled PRE disabled

Tone suppression as per ITU (<400ms) Extended speech protection Echo detection as per ITU up to 6dB -law Self-test disabled PRE enabled

Note: All connections of X9, with the exception of 15 - 16, are open in normal operation!

A30828-X1160-M-2-7620

657

Construction

Maintenance Node

4.6.17

DEC480 (-Q328-)
DEC480

Digital Echo Compensator (480 channel) DEC0 connected to LTG0 on the GPxx. DEC1 connected to LTG1 on the GPxx. DEC2 connected to LTG2 on the GPxx. DEC3 connected to LTG3 on the GPxx.

DEC 0 DEC 1 DEC 2 DEC 3 S0 S1 S2 S3

DEC 0, 1, 2, 3 - LED red all LEDs are off if a LED permanently red if a LED blinking normal operation

State of the board

the initial self-test during boot is running a failure is found on the module the initial self-test cannot be executed because the 8MHz clock (CKC) fails or is out of tolerance.

Strap S0, S1, S2, S3 If a V.24 connection with the DEC0 is needed, S0 must be closed, S1, 2 and 3 must be open. If a V.24 connection with the DEC1 is needed, S1 must be closed, S0, 2 and 3 must be open. If a V.24 connection with the DEC2 is needed, S2 must be closed, S0, 1 and 3 must be open. If a V.24 connection with the DEC3 is needed, S3 must be closed, S0, 1 and 2 must be open. Only one strap may be put, if a connection should be produced between DEC480 and a maintenance PC

V.24 Interface for connection to the maintenance PC


V.24

DEC480 DIP-FIX Switch S1 clossed: S1 open: -law A-law

DIP-FIX-Switch

S2 and S3 must be open 12 3

658

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.18

DESA (-A162-)
DESA
M NO D C

Digital Echo Suppressor A

F E

AB

The wire links are soldered by the manufacturer.

solder pins
U V W T S R GH I

4.6.19

DESB_A1 (-B163-A1-)
DESB_A1 Digital Echo Suppressor B

The wire links are soldered by the manufacturer

solder pins b c e a d f

A30828-X1160-M-2-7620

659

Construction

Maintenance Node

4.6.20

DESB_B1 (-B163-B1-)
DESB_B1
S6 a b c 3 2 1 S12

Digital Echo Suppressor B DIP-FIX switches: S6 must be closed S8...S13 1-3 closed = operating mode 1 2-3 closed = operating mode 2 operating mode 1: Echo suppressing. Modules DESA and DESB plugged operating mode 2: Echo suppressing. Only module DESB plugged

3 3 2 1 S9 3

2 S13 1 2 1

S11

DIP-FIX-switch 3

2 1 S10

2 1

S8

660

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.21

DIU30A (-Q562-)
DIU30A Digital Interface Unit 30A

SE IN

green LED yellow LED red LED red LED red LED

SE on: channel seized for switching SE flashes: ALCO alarm counter overflow IN on: DIU out of service (UNA, MBL, PLA) MA on: maintenance alarm SA on: service alarm NA on: PCM-N-bit alarm

q MA q
SA NA

DIU30A

B1 B2 Link connectors

B1: Link inserted with 75 Ohm coaxcial cable and grounded receiver shield. B2: Link inserted with 75 Ohm coaxcial cable and grounded transmitter shield.

A30828-X1160-M-2-7620

661

Construction

Maintenance Node

4.6.22

DIU30B (-Q563-)
DIU30B Digital Interface Unit 30B

All test jacks are at high impedance for logic 1 (except GND).
AIS

Test jack
LPF

Test jack has logic 0 if in two consecutive pulse frames not more than 1 bi1 is set to logic 0. Test jack has logic 0 if there is loss of pulseframe alignment. Test jack has logic 0 if the D bit set in the pulseframe service word.. Test jack has logic 0 if the signaling frame alignment word is faulty or the invalid pattern 0000xxxx is received in a signal word twice in succession. Test jack has ground potential.

Test jack
DBF

Test jack
LSF

Test jack
GND

Test jack

DIU30B
S1 3

DIP-FIX S2 3 S3 3 S4 3

The jumpers are inserted as required for the country concerned, according to the relevant signaling plan. DIP-FIX switch S3 and S4: S3 S4 Injection of DIALP, DIALPC1 in 3-2 3-2 signal bit- a 3-2 3-1 signal bit- b 3-1 3-2 signal bit- c 3-1 3-1 signal bit- d

1 2 1 2 1 2 1 2

DIP-FIX switch S1 and S2: S1 S2 Injection of FERN on 3-1 3-1 signal bit- c

662

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.23

DIU30D (-Q876-)
DIU30D GND SE

Digital Interface Unit 30D Test jack green LED yellow LED red LED red LED red LED Test jack Ground potential is applied to this jack SE on: channel seized for switching SE flashes: ALCO alarm counter overflow IN on: DIU out of service (UNA, MBL, PLA) MA on: maintenance alarm SA on: service alarm NA on: PCM-N-bit Alarm If there is a CRC4 fault, log 0 is applied to this jack (optional) If there is a permanent one in the pulse frame, log 0 is applied to this jack (optional) If the frame alignment is lost, log 0 is applied to this jack (optional) If the signal frame alignment is lost, log 0 applied to this jack (optional) Is the D bit is set in the frame service word, log 0 applied to this jack (optional) Is the incoming PCM signal fails, log 0 applied to this jack (optional)

q IN q MA q SA q NA q
CER AIS

Test jack
LPF

Test jack
LSF

Test jack
D-B

Test jack
NOS

Test jack

DIU30D
X3 link connector X2 X1

X1: Link inserted with 75 Ohm coaxcial cable and grounded receiver shield. X2: Link inserted with 75 Ohm coaxcial cable and grounded transmittershield. X3: open for ICE test DIU processor X4: open for ICE test DIU processor

X4

A30828-X1160-M-2-7620

663

Construction

Maintenance Node

4.6.24

DIU30F (-Q876-X200-)
DIU30F GND SE

Digital Interface Unit 30F Test jack green LED yellow LED red LED red LED red LED Test jack Ground potential is applied to this jack SE on: channel seized for switching SE flashes: ALCO alarm counter overflow IN on: DIU out of service (UNA, MBL, PLA) MA on: maintenance alarm SA on: service alarm NA on: PCM-N-bit Alarm If there is a CRC4 fault, log 0 is applied to this jack (optional) If there is a permanent one in the pulse frame, log 0 is applied to this jack (optional) If the frame alignment is lost, log 0 is applied to this jack (optional) If the signal frame alignment is lost, log 0 applied to this jack (optional) Is the D bit is set in the frame service word, log 0 applied to this jack (optional) Is the incoming PCM signal fails, log 0 applied to this jack (optional)

q IN q MA q SA q NA q
CER AIS

Test jack
LPF

Test jack
LSF

Test jack
D-B

Test jack
NOS

Test jack

DIU30F
X3 Link connectors X2 X1

X1: Link inserted with 75 Ohm coaxcial cable and grounded receiver shield. X2: Link inserted with 75 Ohm coaxcial cable and grounded transmittershield. X3: open for ICE test DIU processor X4: open for ICE test DIU processor

X4

664

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.25

DIU120A (-Q1346-)
DIU120A Digital Interface Unit 120A BOST

red LED
MA0

LED on: board self test (BOST) detects a failure MA0 on: maintenance alarm, service alarm or PCM-N-Bit alarm is detected MA0 flashes: ALCO alarm counter overflow IN0 on: DIU or PCM out of service MA1 on: maintenance alarm, service alarm or PCM-N-Bit alarm is detected MA1 flashes: ALCO alarm counter overflow IN1 on: DIU or PCM out of service

red LED
IN0

yellow LED
MA1

red LED
IN1

yellow LED

MA2

red LED
IN2

yellow LED
MA3

MA2 on: maintenance alarm, service alarm or PCM-N-Bit alarm is detected MA2 flashes: ALCO alarm counter overflow IN2 on: DIU or PCM out of service MA3 on: maintenance alarm, service alarm or PCM-N-Bit alarm is detected MA3 flashes: ALCO alarm counter overflow IN3 on: DIU or PCM out of service PWR on: DC/DC converter is on PON switch up: DC/DC converter on / PON switch down: DC/DC converter off

red LED
IN3

yellow LED
PWR

green LED
PON

switches

4.6.26

DIU:LDIB (-Q1107-)
DIU: LDIB

Digital Interface Unit for local DLU

SE

green LED
IN

SE on: channel seized for switching SE flashes: ALCO alarm counter overflow IN on: DIU out of service (UNA, MBL, PLA) MA on: maintenance alarm

yellow LED
MA

red LED

A30828-X1160-M-2-7620

665

Construction

Maintenance Node

4.6.27

DIU:LDIM (-Q1343-)
DIU: LDIM BOST

Digital Interface Unit for locale DLU Interface red LED LED on: board self test (BOST) detects a failure

MA0 IN0

red LED yellow LED

MA0 on: failure on 4MBit/s link is detected SE MA0 flashes: ALCO alarm counter overflow IN0 on: DIU is out of order (UNA, MBL, PLA)

MA1 IN1 PON

red LED yellow LED

MA1 on: failure on 4MBit/s link is detected MA1 flashes: ALCO alarm counter overflow IN1 on: DIU is out of order (UNA, MBL, PLA)

MA2

red LED
IN2

MA1 on: failure on 4MBit/s link is detected MA1 flashes: ALCO alarm counter overflow IN1 on: DIU is out of order (UNA, MBL, PLA) MA2 and IN2 on: DIU:LDIM is in double operation mode (route is not switched on or set up)

yellow LED
PWR

green LED switches

PWR on: DC/DC converter is on PON switch up: DC/DC converter on / PON-switch down: DC/DC converter off

4.6.28

ETEAE (-Q670-)
ETEAE

End to end Test Equipment, answer Equipment

q q q

red LED red LED red LED red LED

LED on: transmission 0 seized LED on: transmission 1 seized LED on: transmission 2 seized LED on: transmission 3 seized

666

A30828-X1160-M-2-7620

Maintenance Node

Construction

ETEAE
1 2 3 4 5 6 7 8 1 0 DIL switch S1

The assignment of the DIL switch S1 see: Tab. 4.28

The attenuation of the test transmission is set with switch S1. The attenuation range is between +3.0 dB and -25.0 dBm:
Attenuation (dBm) Value (hexadecimal) 1 (128) +3.0 +2.5 +2.0 +1.5 +1.0 +0.5 +0.0 -0.5 -1.0 -1.5 -2.0 -2.5 -3.0 -3.5 -4.0 -4.5 -5.0 -5.5 -6.0 -6.5 -7.0 -7.5 E8 E4 E2 E0 DE DA D8 D4 D2 CE CC CA C8 C4 C2 C0 BE BA B8 B6 B2 B0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 2 (64) 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 3 (32) 0 0 0 0 1 1 1 1 1 0 0 0 0 0 0 0 1 1 1 1 1 1 Switch setting 4 (16) 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 1 1 1 0 0 0 5 (8) 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 1 0 0 1 0 0 6 (4) 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 0 1 1 0 1 1 0 7 (2) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 (1)

Tab. 4.28

Switch settings for setting the attenuation

A30828-X1160-M-2-7620

667

Construction

Maintenance Node

Attenuation (dBm)

Value (hexadecimal) 1 (128) 2 (64) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 3 (32)

Switch setting 4 (16) 0 0 0 0 0 0 0 1 1 1 1 1 0 0 0 0 0 0 0 1 1 1 1 1 0 0 0 0 0 0 0 1 1 1 1 1 1 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 1 1 0 0 5 (8) 1 0 0 1 1 0 0 1 0 1 0 0 1 0 0 1 1 0 0 1 0 1 0 0 1 0 0 1 1 0 0 1 0 1 0 6 (4) 0 1 0 1 0 1 0 0 0 1 1 0 0 1 0 1 0 1 0 0 0 1 1 0 0 1 0 1 0 1 0 0 0 0 1 7 (2) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 (1)

-8.0 -8.5 -9.0 -9.5 -10.0 -10.5 -11.0 -11.5 -12.0 -12.5 -13.0 -13.5 -14.0 -14.5 -15.0 -15.5 -16.0 -16.5 -17.0 -17.5 -18.0 -18.5 -19.0 -19.5 -20.0 -20.5 -21.0 -21.5 -22.0 -22.5 -23.0 -23.5 -24.0 -24.5 -25.0

AC AA A8 A6 A4 A2 A0 9C 98 96 92 90 8C 8A 88 86 84 82 80 7C 78 76 72 70 6C 6A 68 66 64 62 60 5C 58 54 52

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Tab. 4.28

Switch settings for setting the attenuation

668

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.29

GCG:LTGY (-Q724-)
GCG: LTGY

Group Clock Generator for LTG

SYNC

q PU q GCG q
MU

red LED red LED red LED red LED

SYNC on: no MCH of the LTG is active PU on: boots-checksum incorrect, ASIC or some other chip faulty GCG on: GCG-watchdog faulty MU on: memory error on the PMU

NB these LEDs should only be read while the bootsrap program (BOOT) is running

4.6.30

GPLC (-Q1349-X301-)
GPLC BOST

Group Processor for LTGM (16MB) red LED green LED red LED red LED Switch BOST on: board self test (BOST) detects a failure BOOT on: boot LTG. BOOT flashes every 2 seconds: LTG ready for loading. BOOT flashes every second: LTG is being loaded via a MCH. BOOT flashes twice every second: LTG is being loaded via both MCH. SYN on: no MCH of LTG is active LED on: watchdog faulty Hardware reset of LTG

q BOOT q SYN q q
RES

WDG

V24

V24 Interface

A30828-X1160-M-2-7620

669

Construction

Maintenance Node

4.6.31

GPLD (-Q1349-X401-)
GPLD BOST

Group Processor for LTGM (32MB) red LED green LED red LED red LED Switch BOST on: board self test (BOST) detects a failure BOOT on: boot LTG. BOOT flashes every 2 seconds: LTG ready for loading. BOOT flashes every second: LTG is being loaded via a MCH. BOOT flashes twice every second: LTG is being loaded via both MCH. SYN on: no MCH of LTG is active LED on: watchdog is faulty Hardware reset of LTG

q BOOT q SYN q q
RES

WDG

V24

V24 Interface

Boot-FLASH and SILC-FLASH Update as well as reading out additional BOST results

4.6.32

GPLSD (-Q1339-X401-)
GPLSD BOST

Group Processor for LTGM with SILC function (32MB) red LED green LED red LED red LED Switch BOST on: board self test (BOST) detects a failure BOOT on: boot LTG. BOOT flashes every 2 seconds: LTG ready for loading. BOOT flashes every second: LTG is being loaded via a MCH. BOOT flashes twice every second: LTG is being loaded via both MCH. SYN on: no MCH of LTG is active LED on: watchdog is faulty Hardware reset of LTG

q BOOT q SYN q q
RES

WDG

V24

V24 Interface

670

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.33

GPLSE (-Q1339-X601-)
GPLSE BOST

Group Processor for LTGM with SILC function (64MB) red LED green LED red LED red LED Switch BOST on: board self test (BOST) detects a failure BOOT on: boot LTG. BOOT flashes every 2 seconds: LTG ready for loading. BOOT flashes every second: LTG is being loaded via a MCH. BOOT flashes twice every second: LTG is being loaded via both MCH. SYN on: no MCH of LTG is active LED on: watchdog is faulty Hardware reset of LTG

q BOOT q SYN q q
RES

WDG

V24

V24 Interface

Boot-FLASH and SILC-FLASH Update as well as reading out additional BOST results

A30828-X1160-M-2-7620

671

Construction

Maintenance Node

4.6.34

GPNLD (-Q28-X200-)
GPNLD BOST BOOT

Group Processor for LTGN, for LDI (local DLU Interface) with 32Mbyte Memory red LED green LED BOST on: board self test (BOST) detects a failure BOOT on: boot LTG. BOOT flashes every 2 seconds: LTG ready for loading. BOOT flashes every second: LTG is being loaded via a MCH. BOOT flashes twice every second: LTG is being loaded via both MCH. SYN on: none MCH of LTG is active Hardware reset of LTG

q q SYN q

red LED Switch

RES

PWR

green LED Switch

PWR on: DC/DC converter on (GPN and (optional) LTU:S) PON switch up: DC/DC converter on (GPN and (optional) LTU:S) PON switch down: DC/DC converter off (GPN and (optional) LTU:S)

PON

V24

V24 Interface

GP and IOP Boot-FLASH and SILC-FLASH Update as well as reading out additional BOST results

672

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.35

GPNLE (-Q28-X600-)
GPNLE BOST

Group Processor for LTGN, for LDI (local DLU Interface) with 64Mbyte Memory BOST LED BOOT LED BOST on: board self test (BOST) detects a failure BOOT on: boot LTG. BOOT flashes every 2 seconds: LTG ready for loading. BOOT flashes every second: LTG is being loaded via a MCH. BOOT flashes twice every second: LTG is being loaded via both MCH. SYN on: none MCH of LTG is active Hardware reset of LTG

q BOOT q
SYN

SYN LED Switch

RES

PWR

PWR LED Switch

PWR on: DC/DC converter on (GPN and (optional) LTU:S) PON switch up: DC/DC converter on (GPN and (optional) LTU:S) PON switch down: DC/DC converter off (GPN and (optional) LTU:S)

PON

V24

V24 Interface

Boot-FLASH and SILC-FLASH Update as well as reading out additional BOST results

A30828-X1160-M-2-7620

673

Construction

Maintenance Node

4.6.36

GPNYC (-Q27-)
GPNYC BOST

Group processor for LTGN, for PCM30 with 16Mbyte memory (without SILC component) red LED green LED red LED BOST on: board self test (BOST) detects a failure BOOT on: boot LTG. BOOT flashes every 2 seconds: LTG ready for loading. BOOT flashes every second: LTG is being loaded via a MCH. BOOT flashes twice every second: LTG is being loaded via both MCH. SYN on: none MCH of LTG is active Hardware reset of LTG

q BOOT q
SYN

RES

Switch

PWR

green LED Switch

PWR on: DC/DC converter on (GPN and (optional) LTU:S) PON switch up: DC/DC converter on (GPN and (optional) LTU:S) PON switch down: DC/DC converter off (GPN and (optional) LTU:S)

PON

V24

V24 Interface

GP and IOP Boot-FLASH and SILC-FLASH Update as well as reading out additional BOST results

674

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.37

GPNYD (-Q27-X200-)
GPNYD BOST

Group Processor for LTGN, for PCM30 with 32Mbyte Memory (with SILC component) red LED green LED BOST on: board self test (BOST) detects a failure BOOT on: boot LTG. BOOT flashes every 2 seconds: LTG ready for loading. BOOT flashes every second: LTG is being loaded via a MCH. BOOT flashes twice every second: LTG is being loaded via both MCH. SYN on: none MCH of LTG is active

q BOOT q
SYN

red LED

RES

Switch

Hardware reset of LTG

PWR

green LED Switch

PWR on: DC/DC converter on (GPN and (optional) LTU:S) PON switch up: DC/DC converter on (GPN and (optional) LTU:S) PON switch down: DC/DC converter off (GPN and (optional) LTU:S)

PON

V24

V24 Interface

Boot-FLASH, IOP-FLASH and DSP-FLASH Update as well as reading out additional BOST results

4.6.38

GPNYE (-Q27-X600-)
GPNYE BOST

Group Processor for LTGN, for PCM30 with 64Mbyte Memory (with SILC) BOST LED BOOT LED BOST on: board self test (BOST) detects a failure BOOT on: boot LTG. BOOT flashes every 2 seconds: LTG ready for loading. BOOT flashes every second: LTG is being loaded via a MCH. BOOT flashes twice every second: LTG is being loaded via both MCH. SYN on: none MCH of the LTG is active Hardware reset of LTG

q BOOT q
SYN

q
RES

SYN LED Switch

PWR

PWR LED Switch

PWR on: DC/DC converter an (GPN and (optional) LTU:S) PON switch up: DC/DC converter on (GPN and (optional) LTU:S) PON switch down: DC/DC converter off (GPN and (optional) LTU:S)

PON

V24

V24 Interface

Boot-FLASH, IOP-FLASH and DSP-FLASH Update as well as reading out additional BOST results

A30828-X1160-M-2-7620

675

Construction

Maintenance Node

4.6.39

GPNZC (-Q26-)
GPNZC BOST

Group Processor for LTGN, for PCM24 with 16Mbyte Memory (without SILC component) red LED green LED red LED Switch BOST on: board self test (BOST) detects a failure BOOT on: boot LTG. BOOT flashes every 2 seconds: LTG ready for loading. BOOT flashes every second: LTG is being loaded via a MCH. BOOT flashes twice every second: LTG is being loaded via both MCH. SYN on: none MCH of LTG is active Hardware reset of LTG

q BOOT q SYN q
RES

PWR

green LED Switch

PWR on: DC/DC converter on (GPN and (optional) LTU:S) PON switch up: DC/DC converter on (GPN and (optional) LTU:S) PON switch down: DC/DC converter off (GPN and (optional) LTU:S)

PON

V24

V24 Interface

Boot-FLASH, IOP-FLASH and DSP-FLASH Update as well as reading out additional BOST results

676

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.40

GPNZD (-Q26-X200-)
GPNZD BOST

Group Processor for LTGN, for PCM24 with 32Mbyte Memory (with SILC component) red LED green LED red LED Switch BOST on: board self test (BOST) detects a failure BOOT on: boot LTG. BOOT flashes every 2 seconds: LTG ready for loading. BOOT flashes every second: LTG is being loaded via a MCH. BOOT flashes twice every second: LTG is being loaded via both MCH. SYN on: none MCH of LTG is active Hardware reset of LTG

q BOOT q SYN q
RES

PWR

green LED Switch

PWR on: DC/DC converter on (GPN and (optional) LTU:S) PON switch up: DC/DC converter on (GPN and (optional) LTU:S) PON switch down: DC/DC converter off (GPN and (optional) LTU:S)

PON

V24

V24 Interface

Boot-FLASH, IOP-FLASH and DSP-FLASH Update as well as reading out additional BOST results

A30828-X1160-M-2-7620

677

Construction

Maintenance Node

4.6.41

GPNZE (-Q26-X600-)
GPNZE BOST

Group Processor for LTGN, for PCM24 with 64Mbyte Memory (with SILC) red LED green LED red LED Switch BOST on: board self test (BOST) detects a failure BOOT on: boot LTG. BOOT flashes every 2 seconds: LTG ready for loading. BOOT flashes every second: LTG is being loaded via a MCH. BOOT flashes twice every second: LTG is being loaded via both MCH. SYN on: no MCH of LTG is active Hardware reset of LTG

q BOOT q SYN q
RES

PWR

green LED Switch

PWR on: DC/DC converter on (GPN and (optional) LTU:S) PON switch up: DC/DC converter on (GPN and (optional) LTU:S) PON switch down: DC/DC converter off (GPN and (optional) LTU:S)

PON

V24

V24 Interface

Boot-FLASH, IOP-FLASH and DSP-FLASH Update as well as reading out additional BOST results

678

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.42

GPPYF (-Q277-X000 -)
GPPYF

Group processor module with 4 LTG functions, 128Mbyte memory for PCM 30 Switch up: Power on Switch in central position: Power off Switch downwards press.: Module hardware reset. LTG 0 = 1st LTG on the module.LTG 1 = 2nd LTG on the module. LTG 2 = 3rd LTG on the module.LTG 3 = 4th LTG on the module. LED red LED green all off Module status power failure or all LTG have loaded code and are not in service (PLA, MBL or UNA). LTG has loaded code and is not in service (PLA, MBL or UNA). normal service hardware fault; after manual reset/power one the red LED LTG1 light while BOST is running. initialization, configuration, loading or self-test, no faults module has loaded no code and is not in service (PLA, MBL or UNA).

PWR Switch LTG 0 LTG 1 LTG 2 LTG 3

all off

off off on

off on off

off V24 Interface flashes briefly


V24

flashes flashes

A30828-X1160-M-2-7620

679

Construction

Maintenance Node

4.6.43

GPPYG (-Q277-X100 -)
GPPYG

Group processor module with 4 LTG functions, 256Mbyte memory for PCM 30 Switch up: Power on Switch in central position: Power off Switch downwards press.: Module hardware reset. LTG 0 = 1st LTG on the module.LTG 1 = 2nd LTG on the module. LTG 2 = 3rd LTG on the module.LTG 3 = 4th LTG on the module. LED red LED green all off Module status power failure or all LTG have loaded code and are not in service (PLA, MBL or UNA). LTG has loaded code and is not in service (PLA, MBL or UNA). normal service hardware fault; after manual reset/power one the red LED LTG1 light while BOST is running. initialization, configuration, loading or self-test, no faults module has loaded no code and is not in service (PLA, MBL or UNA).

PWR Switch LTG 0 LTG 1 LTG 2 LTG 3

all off

off off on

off on off

off V24 Interface flashes briefly


V24

flashes flashes

680

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.44

GPPYH (-Q277-X200 -)
GPPYH

Group processor module with 4 LTG functions, 512Mbyte memory for PCM 30 Switch up: Power on Switch in central position: Power off Switch downwards press.: Module hardware reset. LTG 0 = 1st LTG on the module.LTG 1 = 2nd LTG on the module. LTG 2 = 3rd LTG on the module.LTG 3 = 4th LTG on the module. LED red LED green all off Module status power failure or all LTG have loaded code and are not in service (PLA, MBL or UNA). LTG has loaded code and is not in service (PLA, MBL or UNA). normal service hardware fault; after manual reset/power one the red LED LTG1 light while BOST is running. initialization, configuration, loading or self-test, no faults module has loaded no code and is not in service (PLA, MBL or UNA).

PWR Switch LTG 0 LTG 1 LTG 2 LTG 3

all off

off off on

off on off

off V24 Interface flashes briefly


V24

flashes flashes

A30828-X1160-M-2-7620

681

Construction

Maintenance Node

4.6.45

GPPYI (-Q277-X300 -)
GPPYI

Group processor module with 4 LTG functions, 1Gbyte memory for PCM 30 Switch Switch up: Power on Switch in central position: Power off Switch downwards press.: Module hardware reset. LTG 0 = 1st LTG on the module.LTG 1 = 2nd LTG on the module. LTG 2 = 3rd LTG on the module.LTG 3 = 4th LTG on the module. LED red LED green all off Module status power failure or all LTG have loaded code and are not in service (PLA, MBL or UNA). LTG has loaded code and is not in service (PLA, MBL or UNA). normal service hardware fault; after manual reset/power one the red LED LTG1 light while BOST is running. initialization, configuration, loading or self-test, no faults module has loaded no code and is not in service (PLA, MBL or UNA).

PWR LTG 0 LTG 1 LTG 2 LTG 3

all off

off off on

off on off

off V24 Interface flashes briefly


V24

flashes flashes

682

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.46

GPPZF (-Q302-X000 -)
GPPZF

Group processor module with 4 LTG functions, 128Mbyte memory for PCM 24 Switch Switch up: Power on Switch in central position: Power off Switch downwards press.: Module hardware reset. LTG 0 = 1st LTG on the module.LTG 1 = 2nd LTG on the module. LTG 2 = 3rd LTG on the module.LTG 3 = 4th LTG on the module. LED red LED green all off Module status power failure or all LTG have loaded code and are not in service (PLA, MBL or UNA). LTG has loaded code and is not in service (PLA, MBL or UNA). normal service hardware fault; after manual reset/power one the red LED LTG1 light while BOST is running. initialization, configuration, loading or self-test, no faults module has loaded no code and is not in service (PLA, MBL or UNA).

PWR LTG 0 LTG 1 LTG 2 LTG 3

all off

off off on

off on off

off V24 Interface flashes briefly


V24

flashes flashes

A30828-X1160-M-2-7620

683

Construction

Maintenance Node

4.6.47

GPPZG (-Q302-X100 -)
GPPZG

Group processor module with 4 LTG functions, 256Mbyte memory for PCM 24 Switch up: Power on Switch in central position: Power off PWR Switch Switch downwards press.: Module hardware reset. LTG 0 = 1st LTG on the module.LTG 1 = 2nd LTG on the module. LTG 2 = 3rd LTG on the module.LTG 3 = 4th LTG on the module. LED red LED green all off Module status power failure or all LTG have loaded code and are not in service (PLA, MBL or UNA). LTG has loaded code and is not in service (PLA, MBL or UNA). normal service hardware fault; after manual reset/power one the red LED LTG1 light while BOST is running. initialization, configuration, loading or self-test, no faults module has loaded no code and is not in service (PLA, MBL or UNA).

LTG 0 LTG 1 LTG 2 LTG 3

all off

off off on

off on off

off V24 Interface flashes briefly


V24

flashes flashes

684

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.48

GPPZH (-Q302-X200 -)
GPPZH

Group processor module with 4 LTG functions, 512Mbyte memory for PCM 24 Switch up: Power on Switch in central position: Power off PWR Switch Switch downwards press.: Module hardware reset. LTG 0 = 1st LTG on the module.LTG 1 = 2nd LTG on the module. LTG 2 = 3rd LTG on the module.LTG 3 = 4th LTG on the module. LED red LED green all off Module status power failure or all LTG have loaded code and are not in service (PLA, MBL or UNA). LTG has loaded code and is not in service (PLA, MBL or UNA). normal service hardware fault; after manual reset/power one the red LED LTG1 light while BOST is running. initialization, configuration, loading or self-test, no faults module has loaded no code and is not in service (PLA, MBL or UNA).

LTG 0 LTG 1 LTG 2 LTG 3

all off

off off on

off on off

off V24 Interface flashes briefly


V24

flashes flashes

A30828-X1160-M-2-7620

685

Construction

Maintenance Node

4.6.49

GPPZI (-Q302-X300 -)
GPPZI

Group processor module with 4 LTG functions, 1Gbyte memory for PCM 24 Switch up: Power on Switch in central position: Power off PWR Switch Switch downwards press.: Module hardware reset. LTG 0 = 1st LTG on the module.LTG 1 = 2nd LTG on the module. LTG 2 = 3rd LTG on the module.LTG 3 = 4th LTG on the module. LED red LED green all off Module status power failure or all LTG have loaded code and are not in service (PLA, MBL or UNA). LTG has loaded code and is not in service (PLA, MBL or UNA). normal service hardware fault; after manual reset/power one the red LED LTG1 light while BOST is running. initialization, configuration, loading or self-test, no faults module has loaded no code and is not in service (PLA, MBL or UNA).

LTG 0 LTG 1 LTG 2 LTG 3

all off

off off on

off on off

off V24 Interface flashes briefly


V24

flashes flashes

4.6.50

GSM (-Q1340-)
GSM
BOST

Group Switch and Signaling Unit for LTGM red LED BOST on: board self test (BOST) detects a failure

4.6.51

MCAA (-Q729-)
MCAA Speech Memory and Attenuation

wire bridges RP 19 18 1 0V 5V

RP1...RP19: Counter presetting

686

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.52

MCT (-Q63-)
MCT

Mid Call Trigger

BOST

red LED

BOST on: board self test (BOST) detects a failure

serial interface connector for service PC

MCT

DIP-FIX switch S1: S1 open = A-law S1 closed = -law

S1 DIP-FIX switch

4.6.53

MDTOG (-Q1105-)
MDTOG
ERR

MODEM and Tone Generator (8 Ports)

red LED
BSY

ERR on: hardware faulty BSY on: one or more receiver are seized

green LED

A30828-X1160-M-2-7620

687

Construction

Maintenance Node

4.6.54

MDTOG (-Q1490-)
MDTOG
ERR

MODEM and Tone Generator (8 Ports)

red LED

ERR on: hardware faulty

4.6.55

OCE:MUPx (-Q1030-)
OCE: MUPx

Memory Unit for the operationally Controlled Equipment for Announcement

G1

green LED

G1 on: memory unit is seized

Connector for connecting cable

688

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.56

OCE:SPC (-Q1031-)
OCE: SPC

Stored-Program Control for the operationally Controlled Equipment for Announcement

G1

green LED

G1 on: control is seized

Connector for connecting cable

4.6.57

OCE:SPM (-Q1401-)
OCE: SPM

Speech Memory and Speech Control for the operationallity Controlled Equipment for Announcement

RUN ERROR

q q

green LED red LED Switch

RUN on: control is seized ERROR on: control is defect Hardware reset

RESET

serial interface connector for service PC

parallel interface connector for service PC

A30828-X1160-M-2-7620

689

Construction

Maintenance Node

4.6.58

OCE:N (-Q165-)
OCE:N RUN

Operationallity Controlled Equipment for Announcement for LTGN RUN LED ERR LED RUN LED ERR LED Switch RUN on: CMP control is seized ERR on: CMP control is defect RUN on: SMP control is seized ERR on: SMP control is defect Hardware reset

q ERR q RUN q ERR q

RESET

Ethernet Interface

4.6.59

PHMA (-Q1469-)
PHMA BOST

Packet Handler Modul A

q
RESET

red LED

BOST on: board self test (BOST) detects a failure

Switch

Hardware reset

V24

V24 Interface

690

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.60

PMUx (-Q1141-)
PMUx ACT

Processing Unit, Signal Buffer and Memory green LED ACT lit: Bus activities detected by the bus controller (BCU).

RESET G33

Switch
HS BOOT

LTG hardware reset

green LED

BOOT on: boot LTG. BOOT flashes every 2 seconds: LTG ready for loading. BOOT flashes every second: LTG is being loaded via a MCH. BOOT flashes twice every second: LTG is being loaded via both MCH.

4.6.61

PMUE (-Q1141-X600-)
PMUE BOST

Processing Unit, Signal Buffer and Memory E (64MB)

q
RESET BOOT

red LED switches

BOST on: board self test (BOST) detects a failure LTG hardware reset BOOT on: boot LTG. BOOT flashes every 2 seconds: LTG ready for loading. BOOT flashes every second: LTG is being loaded via a MCH. BOOT flashes twice every second: LTG is being loaded via both MCH.

green LED

If there is a label WDGDIS on the module faceplate, this should be ignored..

V24

V24 Interface for Boot-FLASH, as well as reading out additional BOST results

A30828-X1160-M-2-7620

691

Construction

Maintenance Node

4.6.62

RM:CTC (-Q829-)
RM:CTC

Receiver Module for continuity Check

green LED green LED green LED green LED

LED on: CTC 0 is seized LED on: CTC 1 is seized LED on: CTC 2 is seized LED on: CTC 3 is seized

4.6.63

RM:CTC (-Q913-)
RM:CTC

Receiver Module for continuity Check

SIG0

green LED
BSY0

SIG0 on: signal recognized (CTC 0) BSY0 on: CTC 0 is seized SIG1 on: signal recognized (CTC 1) BSY1 on: CTC 1 is seized

green LED green LED green LED

SIG1 BSY1

PON SIG2 BSY2 SIG3 BSY3

green LED green LED green LED green LED

SIG2 on: signal recognized (CTC 2) BSY2 on: CTC 2 is seized SIG3 on: signal recognized (CTC 3) BSY3 on: CTC 3 is seized

Switch

up: CTC enabled/ down: CTC disabled

692

A30828-X1160-M-2-7620

Maintenance Node

Construction

RM:CTC
S1 DIP-FIX switch

DIP-FIX switches: S1 open = int. program memory S1 closed = ext. program memory S2 closed / S3 open = 4-device module S4 open = watchdog enabled

DIL switch S5 1 2 3 4 5 6 7 8 1 0 S3 DIP-FIX switch S4 S2 1 0

DIL switch S5: 1 2 3 4 5 6 7 8

RM:CTC A-law function


1 2 3 4 5 6 7 8

1 0

RM:CTC -law function

4.6.64

SCR (-Q1445-)
SCR ERR

Module for Speech recognition and Code Receiver red LED ERR on: hardware faulty

BSY

green LED

BSY on: one or more receivers are seized

serial interface connector for service PC

parallel interface connector for service PC

A30828-X1160-M-2-7620

693

Construction

Maintenance Node

4.6.65

SILCB (-Q1110-)
SILCB
DIP-FIX-switch S1 S2 S3 S4

Signaling Link Control B

The switches on the module have no significance

4.6.66

SILCD (-Q1110-X200-)
SILCD
DIP-FIX-switch S1 S2 S3 S4

Signaling Link Control D

The switches on the module have no significance

694

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.67

SILC:DLU (-Q783-)
SILC: DLU

Signaling Link Control for DLU

LED off, or is permanently on: SILC is faulty


SILC0

red LED

LED flashes (1s on, 1s off): SILC in order, no message exchange, no synchronization LED flashes (250ms on, 250ms off): SILC in order overload, message exchange not possible LED flashes (250ms on, 10s off): Silc in order, message exchange takes place

SILC0

Switch
SILC0

red LED

SILC0

Switch

switch: resetting the processor 8085 for SILC

4.6.68

SILC:PA (-Q783-)
SILC:PA

Signaling Link Control for PA


SILC0

SILC0

q
SILC0 SILC0

red LED

LED on: SILC is faulty LED flashes slowly: SILC in order, no message exchange

Switch

LED flashes rapidly: SILC in order, connection setup for message exchange faulty LED off: Silc in order, message exchange takes place

red LED

SILC0

Switch

switch: resetting the processor 8085 for SILC

A30828-X1160-M-2-7620

695

Construction

Maintenance Node

4.6.69

TEM:COP (-Q606-)
TEM:COP

Test Equipment Module for Control Panel


C

RL DB V

red LED

Meaning of the LED see: Tab. 4.29

MS TPT

display
TPT/M MA SPT

Meaning of the display see: Tab. 4.30

pushbuttons

Meaning of the keys see Tab. 4.31

FS LT LR

rotary switch

Meaning of the rotary switch setting see: Tab. 4.32

EXCH E/C M

LINE E/C M

Test jack Jack

Meaning of the jacks see: Tab. 4.33

GND PJ SP

TEM:COP

DIP-FIX 2

DIL switch settings: GIE 16 switch 1 = 1: - 23.3 dBm switch 2 = 1: - 11.8 dBm switch 3 = 1: + 1.4 dBm switch 4 = 1: + 12.3 dBm
1 2 3 4

DIL switch

1 0 GIE 50

GIE 50 switch 1 = 1: switch 2 = 1: switch 3 = 1: switch 4 = 1:

not used 60 V eff 45 V eff 30 V eff

1 2 3 4 DIL switch 1 0 GIE 16 DIP-FIX 1

In each case, only one of the switches GIE 16 and GIE 50 is set to on.

Standard switch settings: GIE 16 and GIE 50 only switch 2 on DIP-FIX 2 closed (only LTGA with 16 kHz)

LED RL C DB V

Meaning Call LED, on when the ATE:ST directory number is called on when the C-wires are seized Measurement value LED, lit for digital display of attenuation level in dB Measurement value LED, lit for digital display of voltage in V

Tab. 4.29

Meaning of the LEDs on the module faceplate

696

A30828-X1160-M-2-7620

Maintenance Node

Construction

LED MS TPT

Meaning Measurement value LED, lit for digital display of time in ms Lit for digital display of test point number

Tab. 4.29

Meaning of the LEDs on the module faceplate

Display General displays _ _ _ _ _ _ _ _ _ _ _ _ ATE:ST seized Unit under test connected Test program running Self-test running

Meaning

Additional display for single-step running X x100 _ X x100 X x10 X x10 X x1 X x1 Display of measurement and test results: X +/x10 X x10 X x1000 _ X x100 X x10 X x100 X x100 X x10 X x10 X. x1 X. x1 X x10 X x1 X x1 X. x1 0 No measurement result _ Additional information on the message received by the unit under test _ Job code 2 of the message received by the unit under test X x0,1 X x0,1 X x1 _ Number of pulses counted Time measurement (ms) Level measurement (dB) (If an incorrect frequency is detected during level measurement with frequency evaluation, the display flashes) Potential measurement (V) Test point number reached when a fault is detected Test point number reached

Tab. 4.30

Meaning of the display on the module faceplate

Pushbutton TPT/M

Meaning

Used to switch from test point display (TPT) to measurement value display (M). LED TPT is lit when a test point is displayed. When a measurement value is displayed, the appropriate measurement value LED is lit. Test step key for manual advance to the next test point

STP

Tab. 4.31

Function of the keys on the module faceplate

A30828-X1160-M-2-7620

697

Construction

Maintenance Node

Pushbutton MA

Meaning

Manual level measurement Push button to indicate the use of one of the three rotary switches to the GP so that manual level measurements can be carried out. The key only influences the GP if the test program is at a test step.

Tab. 4.31

Function of the keys on the module faceplate

Switch setting

FS set transmit frequency

LT level transmit _ +3.14 dB 0.00 dB -1.00 dB -3.50 dB -4.50 dB -10.00 dB -10.50 dB -11.00 dB -30.00 dB _

LR level receive

0 1 2 3 4 5 6 7 9 9

_ 421 Hz 820 Hz 842 Hz 914 Hz 1000 Hz 1103 Hz 1400 Hz 2947 Hz 914/1400 Hz

not evaluated evaluated (via A-filter) evaluated (via Q-filter) evaluated _

Tab. 4.32

Meaning of the rotary switch settings on the module faceplate

Test jack E/C, M GND PJ SP

Meaning Control wires (exchange side and line side) Ground Ground pulse indicator Speech jack

Tab. 4.33

Meaning of the jacks on the module faceplate

698

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.6.70

TEM:LE (-Q607-)
TEM:LE

Test Equipment Module for Level transmitting and measuring

B1 A1 B2 A2 DB

Test jack Test jack Test jack Test jack Test jack

Line side b-wire (2-wire) or I b-wire (4-wire) Line side a-wire (2-wire) or I a-wire (4-wire) Circuit side b-wire (2-wire) or II b-wire (4-wire Circuit side a-wire (2-wire) or II a-wire (4-wire) Digital side speech path b-wire (analog access by D/A conversion) Digital side path a-wire (analog access by D/A conversion)

DA

Test jack

4.6.71

TOGB (-Q738-)
TOGB

Tone Generator B

TOGEN

green LED

TOGEN on: tone generator is operational

4.6.72

TOGC (-Q1290-)
TOGC

Tone Generator C

TOGEN

green LED

TOGEN on: tone generator is operational

A30828-X1160-M-2-7620

699

Construction

Maintenance Node

4.6.73

TOGD (-Q1291-)
TOGD

Tone Generator D and Receiver Module for continuity Check (RM:CTC)

ERR

q q

red LED green LED

ERR on: fault on the module BSY on: CTC is busy

BSY

4.6.74

VPU (-Q190-)
VPU ERR BOST

Voice Processing Unit red LED green LED LED ERR off on off off on flashes flashes on LED BOST Alarm and status signaling Normal operation Error or Reset active Normal operatio, port seized Self-test running, no errors Error during self-test Self-test completed, no errors

q q

V24

off off on off

BDM connector

700

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.7

MB
4.7.1 4.7.2 4.7.3 4.7.4 MBDA (-Q54-) MBDC (-Q55-) MBDCG (-Q56-) MBDH (-Q57-)

4.7.1

MBDA (-Q54-)
MBDA
RESET

Interface module for ATM connection Key RUN LED ERR LED Reset module with initial program loading

RUN ERR

qq

see: Meaning of the LED

HW-TRACER

HW-TRACER Connection for HW / SW debugging

V24

V24

V24 Interface for connecting a service PC

IBUS

IBUS

Interface for connecting a serial ICE

green LED on on flashing off off

red LED off on on on off MBDA ready for service

Meaning

BOST has detected an error. MBDA capable of limited operation. MBDA is in the testing/initialization phase BOST has detected an error. MBDA not ready for service. Voltage failure, or LED control faulty

Tab. 4.34

Meaning of the LED

A30828-X1160-M-2-7620

701

Construction

Maintenance Node

4.7.2

MBDC (-Q55-)
MBDC
RESET

Central processor interface Key green LED red LED Reset module with initial program loading see: Meaning of the LED

RUN ERR

qq

HW-TRACER

HW-TRACER Connection for HW / SW debugging

V24

V24

V24 Interface for connecting a service PC

IBUS

IBUS

Interface for connecting a serial ICE

green LED on on flashing off off

red LED off on on on off MBDC ready for service

Meaning

BOST has detected an error. MBDC capable of limited operation. MBDC is in the testing/initialization phase BOST has detected an error. MBDC not ready for service. Voltage failure, or LED control faulty

Tab. 4.35

Meaning of the LED

702

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.7.3

MBDCG (-Q56-)
MBDCG
RESET

MBD Clock Generator

Key
RUN ERR

Reset module with initial program loading see: Meaning of the LED

qq

green LED red LED

DEBUG

DEBUG

Connection for HW / SW debugging

green LED on on flashing off off

red LED off on on on off MBDCG ready for service

Meaning

BOST has detected an error. MBDCG capable of limited operation. MBDCG is in the testing/initialization phase BOST has detected an error. MBDCG not ready for service. Voltage failure, or LED control faulty

Tab. 4.36

Meaning of the LED

A30828-X1160-M-2-7620

703

Construction

Maintenance Node

4.7.4

MBDH (-Q57-)
MBDH
RESET

Interface module for HDLC connection Key green LED red LED Reset module with initial program loading see: Meaning of the LED

RUN ERR

qq

HW-TRACER

HW-TRACER Connection for HW / SW debugging

V24

V24

V24 Interface for connecting a service PC

IBUS

IBUS

Interface for connection of a serial ICE

green LED on on flashing off off

red LED off on on on off MBDH ready for service

Meaning

BOST has detected an error. MBDH capable of limited operation. MBDH is in the testing/initialization phase BOST has detected an error. MBDH not ready for service. Voltage failure, or LED control faulty

Tab. 4.37

Meaning of the LED

704

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.8

RSU
4.8.1 4.8.2 4.8.3 4.8.4 4.8.5 4.8.6 4.8.7 AMUX (-Q104-) DIU240A (-Q106-) DIU240B (-Q107-) RSUC (-Q98-) MH (-Q97-) TSIMA (-Q105-) TSIMB (-Q105-X100)

4.8.1

AMUX (-Q104-)
AMUX

Access Multiplexer

q
ERR

red LED Function: see following table green LED red LED off on on on off on off green LED off off off on on flashing flashing Meaning Voltage failure Current converter is on BoST is finished - errors found AMUX in service BoST is running - errors found BoST is running - no errors found Voltage failure

q
RUN

A30828-X1160-M-2-7620

705

Construction

Maintenance Node

4.8.2

DIU240A (-Q106-)
DIU240A Digital Interface Unit 240A for PCM30

Switch
PON

PON Switch up: DC/DC converter on PON Switch down: DC/DC converter off

q
ERR

red LED green LED yellow LED

q
RUN

Function: see following table red LED off on flashing green LED off off off yellow LED off off off Meaning Voltage failure Hardware error or DIU out of service BoST is running or DIU diagnosis or DIU is loading DIU in service (no HW errors and PCM alarm) DIU in service (HW fault detected, no PCM alarm) DIU in service (PCM alarm detected) DIU in service (HW fault and PCM alarm detected)

q
PDC

off V24 Interface Test connector


V24

on on on on

off off on on

on off on

706

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.8.3

DIU240B (-Q107-)
DIU240B

Digital Interface Unit 240B for PCM24

Switch
PON

PON Switch up: DC/DC converter on PON Switch down: DC/DC converter off

q
ERR

red LED green LED yellow LED

q
RUN

Function: see following table red LED off on flashing green LED off off off yellow LED off off off Meaning Voltage failure Hardware error or DIU out of service BoST is running or DIU diagnosis or DIU is loading DIU in service (no HW errors and PCM alarm) DIU in service (HW fault detected, no PCM alarm) DIU in service (PCM alarm detected) DIU in service (HW fault and PCM alarm detected)

q
PDC

off V24 Interface Test connector


V24

on on on on

off off on on

on off on

A30828-X1160-M-2-7620

707

Construction

Maintenance Node

4.8.4

RSUC (-Q98-)
RSUC

RSU Control

Switch
PON

PON Switch up: DC/DC converter on PON Switch down: DC/DC converter off

q
ERR

red LED Function: see following table green LED Serial Interface Layer 2 Controller Parallel Interface Main Controller

q
RUN

red LED off on flashing on off on off

green LED off off off on on flashing flashing

Meaning Voltage failure Hardware error BoST is finished - errors found RSUC in service BoST is running - errors found BoST is running - no errors found Voltage failure

L2S

MCP

Serial Interface Main Controller

MCS

RSUC
1 0 LED1 red LED2 red LED3 green LED4 green LED5 green

DIP Switch 1 2 3 4

DIP Switch (only for test): during normal operation, all switches should be on Meaning of the LED see: LED on the RSUC component side

LED 1 red 2 red 3 green 4 green 5 green

LED = on No AMUX clock present No TSIM clock present

LED = ashing PLL not locked on AMUX clock TSIM clock faulty

LED = off PLL locked on AMUX clock TSIM clock ok

Tab. 4.38

LED on the RSUC component side

708

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.8.5

MH (-Q97-)
MH

Message Handler

Switch
PON

PON Switch up: DC/DC converter on PON Switch down: DC/DC converter off

q
ERR

red LED Function: see following table green LED Serial Interface Layer 2 Controller Parallel Interface Main Controller

q
RUN

red LED off on flashing on off on off

green LED off off off on on flashing flashing

Meaning Voltage failure

L2S

BoST is finished - errors found MH in service BoST is running - errors found BoST is running - no errors found

MCP

Serial Interface Main Controller

MCS

MH
1 0 LED1 red LED2 red LED3 green LED4 green LED5 green

DIP Switch 1 2 3 4

DIP Switch (only for test): during normal operation, all switches should be on Meaning of the LED see: LED on the MH component side

LED 1 red 2 red 3 green 4 green 5 green

LED = on No AMUX clock present No significance

LED = ashing PLL not locked on AMUX clock No significance

LED = off PLL locked on AMUX clock No significance

Tab. 4.39

LED on the MH component side

A30828-X1160-M-2-7620

709

Construction

Maintenance Node

4.8.6

TSIMA (-Q105-)
TSIMA

Time Slot Interchange Matrix A for PCM30

Switch
PON

PON Switch up: DC/DC converter on PON Switch down: DC/DC converter off

q
ERR

red LED Function: see following table green LED

q
RUN

red LED off on

green LED off off

Meaning Voltage failure TSIM startup until start OS fatal startup error total fault after start OS RCG has not reached his operating temperature after start OS partial fault after start OS TSIMA in service BoST is running - errors found BoST is running - no errors found

flashing on V24 Interface Test controller


V24

off on on flashing flashing

off on off

710

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.8.7

TSIMB (-Q105-X100)
TSIMB

Time Slot Interchange Matrix B for PCM24

Switch
PON

PON Switch up: DC/DC converter on PON Switch down: DC/DC converter off

q
ERR

red LED Function: see following table green LED

q
RUN

red LED off on

green LED off off

Meaning Voltage failure TSIM startup until start OS fatal startup error total fault after start OS RCG has not reached his operating temperature after start OS partial fault after start OS TSIMB in service BoST is running - errors found BoST is running - no errors found

flashing on V24 Interface Test controller


V24

off on on flashing flashing

off on off

A30828-X1160-M-2-7620

711

Construction

Maintenance Node

4.9

SDHI
4.9.1 4.9.2 OIM*W (-D3559-) OIM*P (-D3560-)

4.9.1

OIM*W (-D3559-)
OIM*W
INT LED (red) is lit: - if a hardware fault occurs - during the software start phase in conjunction with the ID LED ID LED (green) is lit: - if the module has been disabled (maintenance) - during the software start phase in conjunction with the INT LED

INT-LED (red) ID-LED (green) Test jacks


Ringer

RS-232 Test Reset

in in

out out

712

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.9.2

OIM*P (-D3560-)
OIM*P
INT LED (red) is lit: - if a hardware fault occurs -during the software start phase in conjunction with the ID LED ID LED (green) is lit: - if the module has been disabled (maintenance) - during the software start phase in conjunction with the INT LED

INT-LED (red) ID-LED (green) Test jacks

in in

out out

A30828-X1160-M-2-7620

713

Construction

Maintenance Node

4.10

SMSC
4.10.1 4.10.2 4.10.3 4.10.4 4.10.5 4.10.6 4.10.7 CCGB (-Q887-) CCGXXA (-Q888-) CDEX (-Q900-) CDEX (-Q900-X100-) PU:SYCR (-Q867-) T/RM:SYCR (-Q868-) T/RM:SYCR (-Q868-X200-)

4.10.1

CCGB (-Q887-)
see 4.1.3 "CCGB (-Q887-)"

4.10.2

CCGXXA (-Q888-)
see 4.1.4 "CCGXXA (-Q888-)"

4.10.3

CDEX (-Q900-)
see 4.1.5 "CDEX (-Q900-)"

4.10.4

CDEX (-Q900-X100-)
see 4.1.6 "CDEX (-Q900-X100-)"

4.10.5

PU:SYCR (-Q867-)
PU: SYCR

Processing unit for system panel control R

red LED

A timer must be reset every 13 ms in order to supervise the firmware programs and ensure that they are executed perfectly. If one of these reset commands is omitted, a reset pulse is generated to restart the firmware. If more than three reset pulses are generated within 11 minutes, the processor on module PU:SYCR is halted and all interfaces are inhibited. This status is indicated by the flashing red LED.

Switch

This inhibit function can only be released by depresseing this switch. If the processor is to be manually reset, this switch must be depressed.

4.10.6

T/RM:SYCR (-Q868-)
The module T/RM:SYCR is the interface to the connected SYPDs, the external fault signaling units and the external alarm devices.

714

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.10.6.1

Interface to the SYPDs


With the module T/RM:SYCR up to 2 SYPDs can be controlled, SYPD0 and SYPD1. It is possible to connect one SYPD in the 2-wire method (SYPD0), and one SYPD in the 4-wire method (SYPD1 via MDF).
T/RM:SYCR Transmitter/receiver module for system panel control R

Switch BR: This switch is used to connect the MB-line to ground in Position 2 for the SYPD which runs via 4-wire method on the transmit side. This is necessary, for example, if a connected carriere frequency device is no grounded.
BR 1 2

If module T/RM:SYCR with part number -Q868-X- is to be replaced by a new module with part number -Q868-X200-, and if a SYPD is connected on the other side, the corresponding module T/RM:SYPD in SYPD with part number -Q709-X- must also be replaced by a new module with part number -Q709-X100-. The programming of the user EPROM on module PU:SYCR also has to be changed if SYPD0 has been used up to now.

4.10.6.2

Interface to external fault signaling units


Via the T/RM:SYCR module it is possible to pass 8 alarms or indications, which are displayed on the SYPD, to external fault signaling units. This is done via relays. In the userEPROM on module PU:SYCR it is fixed which priority (critical alarm, major alarm or minor alarm) from which SYPD-LEDs are to be output to one ore more relays. The assignment of the individual relays to the alarm lines AL1A ... AL8B is fixed. The relays have the same identifiers as the individual alarm lines; the relay contacts are identified with al. Alarms can be transferred electrically in four different ways: a) contact against ground b) contact against exchange voltage c) loop passive d) loop active Depending on the method of alarm transfer used, the corresponding link or the corresponding resistance must be strapped on module TXA:SYPC (see diagram on the following page). The resistance R must have a value of 1 kiloohm and withstand power up to 2 watts. The link between point 7 and point 8 (RC spark protection) must always be strapped. If the RC combination causes difficulties for some loads (but only if this is the case), this link may be omitted.

A30828-X1160-M-2-7620

715

Construction

Maintenance Node

4.10.6.3

The four types of link connection on module T/RM:SYCR


a) 2 3 ground b) 2 3 ground c) 2 3 ground d) 2 3 ground R or wire link

5 R

4 R

4 R

- 48V/60V al 7 8

- 48V/60V al 7 8

1 - 48V/60V - 48V/60V al 7 8

al 7 8

ALxA

ALxB

ALxA

ALxB

ALxA

ALxB

ALxA

ALxB

R1

R1

R1

R2

R1

-48V/60V R1 2kOhm

ground R1 2kOhm

-48V/60V

ground R1 2kOhm

R1 + R2 2kOhm

716

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.10.6.4

Location of the links on module T/RM:SYCR


2 3
1 2 3 4 5 6 7 8

5 4 1 7 8

AL 1

AL 3

AL 5

AL 7

AL 2

AL 4

AL 6

AL 8

The lines to the external alarm devices are normally connected to the T/RM:SYCR module via the MDF. The direct connection plug for T/RM:SYCR is on backplane in MUT02 in MOLOC D141. The two following tables show the assignment of the individual ALs to the connector pins of module T/RM:SYCR on the wiring board (wiring side).
AL No AL1A AL1B AL2A AL2B AL3A AL3B AL4A AL4B Pin. No 203 204 205 206 207 208 209 210 Plug location SMSC0 MUT02 T/RM:SYCR MOLOC D141 AL-No AL5A AL5B AL6A AL6B AL7A AL7B AL8A AL8B Pin. No 211 212 213 214 215 216 217 218 Plug location SMSC0 MUT02 T/RM:SYCR MOLOC D141

Tab. 4.40

Alarm lines

4.10.6.5

Interface to external alarm devices


The T/RM:SYCR module has 8 external data lines for connection of 8 external alarm devices. On every SYPD there are 8 pairs of LEDs and 8 single LEDs which are used to indicate external alarms. On each of the 8 pairs of the LEDs critical alarms, major alarms

A30828-X1160-M-2-7620

717

Construction

Maintenance Node

and minor alarms can be indicated. On each of the single LEDs a major alarm or a minor alarm can be indicated. If for a particular LED pair or single LED more than one alarm is to be indicated at the same time, then the higher priority alarm is indicated (e.g., critical alarm before major alarm or major alarm before minor alarm). The T/RM:SYCR module has 8 external data lines EAI (also called EAP, EAD) which can be assigned to the individual LEDs or LED pairs on the SYPD. This assignment is done via a program. Up to 3 EAIs (EAPs, EADs) can be assigned to a LED pair and up to 2 EAIs can be assigned to an individual LED. The allocation of the individual EAIs to the LEDs on the SYPD is done via appropriate programming of the user-EPROM on the PU:SYCR module. The alarm priority assigned to the EAIs is also programmed onto the user-EPROM. The lines from the external alarm devices are normally connected to the module T/RM:SYCR over the MDF. The plug for direct connections on the T/RM:SYCR module is on the backplane in MUT02 in MOLOC D141.

4.10.6.6

Assignment of the individual EAIs (EAPs/EADs) to the pins on module T/RM:SYCR in the backplane
EAI- No. (EAP/EAD- No.) EAI1 (EAP1) EAI2 (EAP2) EAI3 (EAP3) EAI4 (EAP4) EAI5 (EAD1) EAI6 (EAD2) EAI7 (EAD3) EAI8 (EAD4) 243 244 245 246 347 248 249 250 Pin. No. Plug Location

SMSC0 MUT02 T/RM:SYCR MOLOC D141

Tab. 4.41

EAI lines

718

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.10.6.7

LED numbers for the external alarms on the SYPD

:
MONTH DAY TIME EXTERNAL ALARMS LINE/TRUNK GROUPS LTG SWITCHING NETWORK SN

15 16

31 32 33 34 35 36 37 38
HW-UNITS MBL SIGNALING LINK NO.7 BLOCKED ALARM DISPLAY SUPPRESSION

MAINTEN. ALARM

SERVICE ALARM

EXTERN. EQUIPM.

17 18

COORDINATION PROCESSOR CP

CENTRAL UNITS

MESSAGE BUFFER

19 20

ERL PROCESSOR LOAD

CLOCK

COM. CHAN. SIGNALING

21 22

SYSTEM PANEL SYP

TRUNK GROUP ALARM LINE LOCKOUT SIGNALING LINK NO.7 CALL IDENTIFICATION

TRUNK GROUP BLOCKED CAT 1 CAT 2 SYSTEM OPERATOR

EXT. DLU ALARM ADMIN. ALARM RECOVERY TIME INSECURE

UPDATE

TEST

ACCEPT.

4.10.7

T/RM:SYCR (-Q868-X200-)
The module T/RM:SYCR is the interface to the connected SYPDs, the external fault signaling units and the external alarm devices.

4.10.7.1

Interface to the SYPDs


With the module T/RM:SYCR up to 2 SYPDs can be controlled, SYPD0 and SYPD1. It is possible to connect one SYPD in the 2-wire method (SYPD0), and one SYPD in the 4-wire method (SYPD1 via MDF). If module T/RM:SYCR with part number -Q868-X- is to be replaced by a new module with part number -Q868-X200-, and if a SYPD is connected on the other side, the corresponding module T/RM:SYPD in SYPD with part number -Q709-X- must also be replaced by a new module with part number -Q709-X100-. The programming of the user EPROM on module PU:SYCR also has to be changed if SYPD0 has been used up to now. On the new modules the U-plugs X59 and X61 (on T/RM:SYCR) and X5 and X6 (on T/RM:SYPD) must be set according to the signals transmitted (inverted or non-inverted).

A30828-X1160-M-2-7620

719

Construction

Maintenance Node

In the previous SYP (T/RM:SYCR module with part number -Q868-X- and T/RM:SYPD module with part number -Q709-X-) there was one two-wire SYPD terminal on module T/RM:SYCR (for SYPD0) and one four-wire SYPD terminal (for SYPD1). The new SYP modules (T/RM:SYCR in V24 technology with part number -Q868-X200- and T/RM:SYPD in V24 technology with part number -Q709-X100-) require two wires in each direction for data transfer between SYCR and SYPD or CT, i.e. only four-wire connections (forward and backward direction) are possible. In the existing frames, only the terminals for SYPD1 is available as four-wire terminals, but not the terminal for SYPD0. Therefore the terminal for SYPD0 cannot be used if both modules (T/RM:SYCR and T/RM:SYPD) using the old technology have been replaced by new V24 modules. This means that in the transmission direction (from T/RM:SYCR to T/RM:SYPD or CT) only the signal MA and the corresponding ground terminal MB can be used; in the receive direction (from T/RM:SYPD or CT to T/RM:SYCR) only the signal EA and the corresponding ground terminal EB can be used. Signals T and R (corresponding to the old SYPD0 terminal) cannot be used.
T/RM:SYCR Transmitter/receiver module for system panel control R The V24 signals transmitted from SYCR to SYPD or CT (forward signals), can be provided in inverted and non-inverted form. The default setting of the U-plugs is such that a noninverted signal is transmitted. Setting of the U-plugs X59 and X6, according to the type of signal see:Tab. 4.42

3 1

4 4 3 2 2 1 X61 2 4 1 3 3 1 X59 4 2

non inverted signal Name of U-Plug Pin no. to be connected 1-2

inverted signal

Pin no. to be connected 3-4

Signal name and module pin no.

X59

MA on pin 257 for SYPD1 MB (ground) on pin 258 EA on pin 255 for SYPD1 EB (ground) on pin 256

X61

1-2

3-4

Tab. 4.42

Assignment of the U-Plugs on module T/RM:SYCR

4.10.7.2

Interface to external fault signaling units


Via the T/RM:SYCR module it is possible to pass 8 alarms or indications, which are displayed on the SYPD, to external fault signaling units. This is done via relays. In the userEPROM on module PU:SYCR it is fixed which priority (critical alarm, major alarm or minor alarm) from which SYPD-LEDs are to be output to one ore more relays. The assignment of the individual relays to the alarm lines AL1A ... AL8B is fixed. The relays have the same identifiers as the individual alarm lines; the relay contacts are identified with al.

720

A30828-X1160-M-2-7620

Maintenance Node

Construction

Alarms can be transferred electrically in four different ways: a) contact against ground b) contact against exchange voltage c) loop passive d) loop active Depending on the method of alarm transfer used, the corresponding link or the corresponding resistance must be strapped on module TXA:SYPC (see diagram on the following page). The resistance R must have a value of 1 kiloohm and withstand power up to 2 watts. The link between point 7 and point 8 (RC spark protection) must always be strapped. If the RC combination causes difficulties for some loads (but only if this is the case), this link may be omitted.

4.10.7.3

The four types of link connection on module T/RM:SYCR


a) 2 3 ground b) 2 3 ground c) 2 3 ground d) 2 3 ground R or wire link 5 5 5 R 4 4 R 1 - 48V/60V al 7 8 7 8 1 - 48V/60V al 7 8 1 - 48V/60V - 48V/60V al 7 8 al 4 4 R 1 5

ALxA

ALxB

ALxA

ALxB

ALxA

ALxB

ALxA

ALxB

R1

R1

R1

R2

R1

-48V/60V R1 2kOhm

ground R1 2kOhm

-48V/60V

ground R1 2kOhm

R1 + R2 2kOhm

A30828-X1160-M-2-7620

721

Construction

Maintenance Node

4.10.7.4

Location of the links on module T/RM:SYCR


(AL1 AL2 AL3 AL4 AL5 AL6 AL7 AL8)
(2)

X56 X49 X42 X35 X28 X21 X14 X7


(3)

X58 X51 X44 X37 X30 X23 X16 X9


(5)

X54 X47 X40 X33 X26 X19 X12 X5


(4)

X52 X45 X38 X31 X24 X17 X10 X3


(1)

X8 X15 X22 X29 X36 X43 X50 X57


3 1 4 3 2 1 X61 (8) 2 4 X59 1 3 3 1 4 2 4 2 (7)

X53 X46 X39 X32 X25 X18 X11 X4 X55 X48 X41 X34 X27 X20 X13 X6

K1

K3

K5

K7

K2

K4

K6

K8

The lines to the external alarm devices are normally connected to the T/RM:SYCR module via the MDF. The direct connection plug for T/RM:SYCR is on backplane in MUT02 in MOLOC D141. The two following tables show the assignment of the individual ALs to the connector pins of module T/RM:SYCR on the wiring board (wiring side).

722

A30828-X1160-M-2-7620

Maintenance Node

Construction

AL No AL1A AL1B AL2A AL2B AL3A AL3B AL4A AL4B

Pin No 203 204 205 206 207 208 209 210

Plug location SMSC0 MUT02 T/RM:SYCR MOLOC D141

AL No AL5A AL5B AL6A AL6B AL7A AL7B AL8A AL8B

Pin No 211 212 213 214 215 216 217 218

Plug location CMSC0 MUT02 T/RM:SYCR MOLOC D141

Tab. 4.43

Alarm lines

4.10.7.5

Interface to external alarm devices


The T/RM:SYCR module has 8 external data lines for connection of 8 external alarm devices. On every SYPD there are 8 pairs of LEDs and 8 single LEDs which are used to indicate external alarms. On each of the 8 pairs of the LEDs critical alarms, major alarms and minor alarms can be indicated. On each of the single LEDs a major alarm or a minor alarm can be indicated. If for a particular LED pair or single LED more than one alarm is to be indicated at the same time, then the higher priority alarm is indicated (e.g., critical alarm before major alarm or major alarm before minor alarm). The T/RM:SYCR module has 8 external data lines EAI (also called EAP, EAD) which can be assigned to the individual LEDs or LED pairs on the SYPD. This assignment is done via a program. Up to 3 EAIs (EAPs, EADs) can be assigned to a LED pair and up to 2 EAIs can be assigned to an individual LED. The allocation of the individual EAIs to the LEDs on the SYPD is done via appropriate programming of the user-EPROM on the PU:SYCR module. The alarm priority assigned to the EAIs is also programmed onto the user-EPROM. The lines from the external alarm devices are normally connected to the module T/RM:SYCR over the MDF. The plug for direct connections on the T/RM:SYCR module is on the backplane in MUT02 in MOLOC D141.

4.10.7.6

Assignment of the individual EAIs (EAPs/EADs) to the pins on module T/RM:SYCR in the backplane
EAI No (EAP/EAD- No.) EAI1 (EAP1) EAI2 (EAP2) EAI3 (EAP3) EAI4 (EAP4) EAI5 (EAD1) EAI6 (EAD2) EAI7 (EAD3) EAI8 (EAD4) 243 244 245 246 247 248 249 250 Pin No Plug Location

SMSC0 MUT02 T/RM:SYCR MOLOC D141

Tab. 4.44

EAI lines

A30828-X1160-M-2-7620

723

Construction

Maintenance Node

4.10.7.7

LED numbers for the external alarms on the SYPD


:
MONTH DAY TIME EXTERNAL ALARMS

LINE/TRUNK GROUPS LTG

SWITCHING NETWORK SN

15 16

31 32 33 34 35 36 37 38
HW-UNITS MBL SIGNALING LINK NO.7 BLOCKED ALARM DISPLAY SUPPRESSION

MAINTEN. ALARM

SERVICE ALARM

EXTERN. EQUIPM.

17 18

COORDINATION PROCESSOR CP

CENTRAL UNITS

MESSAGE BUFFER

19 20

ERL PROCESSOR LOAD

CLOCK

COM. CHAN. SIGNALING

21 22

SYSTEM PANEL SYP

TRUNK GROUP ALARM LINE LOCKOUT SIGNALING LINK NO.7 CALL IDENTIFICATION

TRUNK GROUP BLOCKED CAT 1 CAT 2 SYSTEM OPERATOR

EXT. DLU ALARM ADMIN. ALARM RECOVERY TIME INSECURE

UPDATE

TEST

ACCEPT.

724

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.11

SN
4.11.1 4.11.2 4.11.3 4.11.4 4.11.5 4.11.6 4.11.7 LILD (-Q70-) LILE (-Q263-) MATC (-Q73-) MATM (-Q72-) MUXC (-Q71-) OFC (-Q264-) SNOPT (-Q280-)

4.11.1

LILD (-Q70-)
LILD

Link Interface LTG LED Function: see following table LED red LED off on off green LED off off on Meaning Voltage failure Hardware error LILD in service

q q

A30828-X1160-M-2-7620

725

Construction

Maintenance Node

4.11.2

LILE (-Q263-)
LILE

Link Interface LTG LED Function: see following table LED red LED off on off green LED off off on Meaning Voltage failure Hardware error LILE in service

q q

726

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.11.3

MATC (-Q73-)
MATC

Matrix Control

q q
V24

red LED green LED V24 Interface

Function: see following table

red LED off on

green LED off off on on flashing flashing

Meaning Voltage failure Hardware error BoST is finished - error found MUXC in service BoST is running - errors found BoST is running - no errors found

TRIF

Tracer Interface

on off on off

4.11.4

MATM (-Q72-)
MATM

Matrix Module (

q q
V24

red LED green LED Function: see following table

V24 Interface

red LED off on on

green LED off off on on flashing flashing

Meaning Voltage failure Hardware error BoST is finished - error found MUXC in service BoST is running - errors found BoST is running - no errors found

TRIF

off Tracer Interface on off

A30828-X1160-M-2-7620

727

Construction

Maintenance Node

4.11.5

MUXC (-Q71-)
MUXC

Multiplexer Control

q q

red LED Function: see following table green LED

red LED off V24 Interface


V24

green LED off off on on flashing flashing

Meaning Voltage failure Hardware error BoST is finished - error found MUXC in service BoST is running - errors found BoST is running - no errors found

on on off

TRIF Tracer

on off

Interface

4.11.6

OFC (-Q264-)

1SU R25

728

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.11.7

SNOPT (-Q280-)
1SU

A:OMUX R25

DC/DC

1SU

A30828-X1160-M-2-7620

729

Construction

Maintenance Node

4.12

SSNC
4.12.1 4.12.2 4.12.3 4.12.4 4.12.5 4.12.6 4.12.7 4.12.8 4.12.9 4.12.10 4.12.11 4.12.12 4.12.13 4.12.14 4.12.15 ACCG (Q145) (Q1022) ALIB (Q1065) AMXE (Q1019) ASMG16/16 (Q1034) GMX:E (Q1032) LIC:2A (Q1014) LIC:1,5A (Q1013) MDD (U2594) MOD (Q1028) MPUC (SA,512MB)(Q82-X401) MPUC (AP,512MB)(Q80-X401) MPUC (equipment side) MPUD (Q83) MPUD (Q85-X801) PSAG (Q6124)

4.12.1

ACCG (Q145) (Q1022)


ACCG

ASN Clock Control Generator

ERR

q q

LED: ERR LED: RUN

RUN on off on

ERROR off on on off off

Meaning Normal state, unit active and in operation Unit faulty or blocked The unit has a partial failure, is being tested, or the IR bit is set Without voltage Unit is being loaded

RUN

REP

No function off flashes

V24

RS232C/V24 Interface

730

A30828-X1160-M-2-7620

Maintenance Node

Construction

ACCG

Switch position Q1022

Switch position Q145

1 2 3 4 1 0

1 2 3 4

S100

Switch 1 and 2 ON = Reference clock 0 Switch 3 and 4 ON = Reference clock 1 Switch 2 and 4 ON = for Connection 120 Ohm symmetrisch Switch 1 and 3 ON = for Connection 75 Ohm unsymmetrisch (koax.)

A30828-X1160-M-2-7620

731

Construction

Maintenance Node

4.12.2

ALIB (Q1065)
ALIB

Alarm Line Interface Type B LED LED ERROR off ERROR on ERROR on ERROR off ERROR off Meaning Normal state, unit is active and in operation Unit is faulty or blocked Unit has a partial failure or is being tested, or the IR bit is set Without voltage Unit is being loaded Critical alarm Fault in central unit without redundancy Major alarm Fault in central units with loss of redundancy Minor alarm Fault in central units with loss of redundancy

q RUN q
ERR

red LED green LED

RUN on RUN off RUN on RUN off RUN flashes CR on

CR

q MJ q MN q

red LED red LED red LED MN on MJ on

4.12.3

AMXE (Q1019)
AMXE

ATM Multiplexer Type E

ERR RUN

q q

RUN on off on off flashes

ERROR off on on off off

Meaning Normal state, unit active and in operation Unit faulty or blocked Unit has a partial failure, is being tested, or the IR bit is set Without voltage Unit is being loaded

V24

RS232C/V24 Interface

732

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.12.4

ASMG16/16 (Q1034)
ASMG

ATM Switching Core Module G16/16

ERR RUN

q q

RUN on off on off flashes

ERROR off on on off off

Meaning Normal state, unit active and in operation Unit faulty or blocked Unit has a partial failure, is being tested, or the IR bit is set Without voltage Unit is being loaded

4.12.5

GMX:E (Q1032)
GMXE

Giga Multiplexer Type E

RUN

ERROR off on on off off

Meaning Normal state, unit active and in operation Unit faulty or blocked Unit has a partial failure, is being tested, or the IR bit is set Without voltage Unit is being loaded

q RUN q
ERR

on off on off flashes

A30828-X1160-M-2-7620

733

Construction

Maintenance Node

4.12.6

LIC:2A (Q1014)
LIC:2A

Line Interface Card 2A

q RUN q
ERR

RUN on off on off flashes

ERROR off on on off off

Meaning Normal state, unit active and in operation Unit faulty or blocked Unit has a partial failure, is being tested, or the IR bit is set Without voltage Unit is being loaded

V24

RS232C/V24 Interface

LIC:2A

1 2 3 4 5 6 7 8 ON 1 OFF 0

Termination 120 Ohm, for twisted pair cables (balanced): Switch OFF Termination 75 Ohm, for coaxial cables (unbalanced): Switch ON Switch 1 = Port 7, Switch 2 = Port 6, Switch 3 = Port 5, Switch 4 = Port 4 Switch 5 = Port 3, Switch 6 = Port 2, Switch 7 = Port 1, Switch 8 = Port 0

734

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.12.7

LIC:1,5A (Q1013)
LIC:1,5A

Line Interface Card 5A

RUN
ERR RUN

ERROR off on on off off

Meaning Normal state, unit active and in operation Unit faulty or blocked Unit has a partial failure, is being tested, or the IR bit is set Without voltage Unit is being loaded

q q

on off on off flashes

RS232C/V24
V24

Interface

A30828-X1160-M-2-7620

735

Construction

Maintenance Node

4.12.8

MDD (U2594)
MDD

Magnetic Disk Device

q RUN q
ERR

RUN on off off

ERROR off on off

Meaning Normal state, unit active and in operation Unit faulty or blocked Without voltage

Consisting of: MDD drive (U938) PC board (Q217)

4.12.9

MOD (Q1028)
MOD

Magnetic Optical Disk Device

q q

red LED green LED

RUN on off off

ERROR off on off

Meaning Normal state, unit active and in operation Unit faulty or blocked Without voltage

736

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.12.10

MPUC (SA,512MB)(Q82-X401)
MPUC

Main Processor Unit Type C for Standalone Configuration 512MB

RES

q ERR q RUN q

Reset switch red LED green LED

RUN on off

ERROR off on on off off

Meaning Normal state, unit active and in operation Unit faulty or blocked Unit has a partial failure, is being tested, or the IR bit is set Without voltage Unit is being loaded

V24

on HWT for Hardware Tracer


HWT

................ ................ ................ ................ ................

off flashes

4.12.11

MPUC (AP,512MB)(Q80-X401)
MPUC

....... ....... ....... ....... .......

Main Processor Unit Type C for Application 512MB

RES

q q RUN q
ERR

Reset switch

RUN on off

ERROR off on on off off

Meaning Normal state, unit active and in operation Unit faulty or blocked Unit has a partial failure, is being tested, or the IR bit is set Without voltage Unit is being loaded

V24

on off
HWT

................ ................ ................ ................ ................

flashes HWT for Hardware Tracer

....... ....... ....... ....... .......

A30828-X1160-M-2-7620

737

Construction

Maintenance Node

4.12.12

MPUC (equipment side)


MPUC LED 1

LED 2

LED 3

LED 1 on

LED 3 off

LED 2

Meaning Master MPU and synchronized by the ACCG (clock from the ACCG) (this state can be indicated for both MPUs at the same time if the MP is split) Master MPU and free-running (no clock from the ACCG) (this state can be indicated for both MPUs at the same time if the MP is split) Slave MPU and synchronized by the Master MPU

on off

on off on

Both MPUs are operating in micro-synchronism.

4.12.13

MPUD (Q83)
MPUD

Main Processor Unit Type D for 512MB

RES

q q RUN q
ERR

Reset switch

RUN on off

ERROR off on on off off

Meaning Normal state, unit active and in operation Unit faulty or blocked Unit has a partial failure, is being tested, or the IR bit is set Without voltage Unit is being loaded

V24

on off
HWT

................ ................ ................ ................ ................

flashes HWT for Hardware Trace

....... ....... ....... ....... .......

738

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.12.14

MPUD (Q85-X801)
MPUD

Main Processor Unit Type D for Standalone Configuration 1GB

RES

q ERR q RUN q

Reset switch red LED green LED

RUN on off

ERROR off on on off off

Meaning Normal state, unit active and in operation Unit faulty or blocked Unit has a partial failure, is being tested, or the IR bit is set Without voltage Unit is being loaded

V24

on HWT for Hardware Tracer


HWT

................ ................ ................ ................ ................

off flashes

4.12.15

PSAG (Q6124)
PSAG

....... ....... ....... ....... .......

Power Supply for ASMG

q RUN q
ERR

RUN red LED green LED on off on off flashes

ERROR off on on off off

Meaning Normal state, unit active and in operation Unit faulty or blocked Unit has a partial failure, is being tested, or the IR bit is set Without voltage Unit is being loaded

PWR

PWR switch

A30828-X1160-M-2-7620

739

Construction

Maintenance Node

4.13

STMI
4.13.1 4.13.2 4.13.3 4.13.4 4.13.5 4.13.6 4.13.7 4.13.8 GPSF (-Q278-X000-) GPSG (-Q278-X100-) GPSH (-Q278-X200-) GPSI (-Q278-X300-) STMI:E(W) (-Q300-) STMI:E(P) (-Q301-) STMI:O(W) (-Q298-) STMI:O(P) (-Q299-)

4.13.1

GPSF (-Q278-X000-)
GPSF

Group processor module with 4 LTG functions, 128 Mbyte memory, 63 x E1 interface Switch up: Power on Switch in central position: Power off Switch downwards press.: Module hardware reset. LTG 0 = 1st LTG on the module.LTG 1 = 2nd LTG on the module. LTG 2 = 3rd LTG on the module.LTG 3 = 4th LTG on the module. LED red LED green all off Module status power failure or all LTG have loaded code and are not in service (PLA, MBL or UNA). LTG has loaded code and is not in service (PLA, MBL or UNA). normal service hardware fault; after manual reset/power one the red LED LTG1 light while BOST is running. initialization, configuration, loading or self-test, no faults module has loaded no code and is not in service (PLA, MBL or UNA).

PWR Switch LTG 0 LTG 1 LTG 2 LTG 3

all off

off off on

off on off

off V24 Interface flashes briefly


V24

flashes flashes

740

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.13.2

GPSG (-Q278-X100-)
GPSG

Group processor module with 4 LTG functions, 256 Mbyte memory, 63 x E1 interface Switch up: Power on Switch in central position: Power off Switch downwards press.: Module hardware reset. LTG 0 = 1st LTG on the module.LTG 1 = 2nd LTG on the module. LTG 2 = 3rd LTG on the module.LTG 3 = 4th LTG on the module. LED red LED green all off Module status power failure or all LTG have loaded code and are not in service (PLA, MBL or UNA). LTG has loaded code and is not in service (PLA, MBL or UNA). normal service hardware fault; after manual reset/power one the red LED LTG1 light while BOST is running. initialization, configuration, loading or self-test, no faults module has loaded no code and is not in service (PLA, MBL or UNA).

PWR Switch LTG 0 LTG 1 LTG 2 LTG 3

all off

off off on

off on off

off V24 Interface flashes briefly


V24

flashes flashes

A30828-X1160-M-2-7620

741

Construction

Maintenance Node

4.13.3

GPSH (-Q278-X200-)
GPSH

Group processor module with 4 LTG functions, 512 Mbyte memory, 63 x E1 interface Switch Switch up: Power on Switch in central position: Power off Switch downwards press.: Module hardware reset. LTG 0 = 1st LTG on the module.LTG 1 = 2nd LTG on the module. LTG 2 = 3rd LTG on the module.LTG 3 = 4th LTG on the module. LED red LED green all off Module status power failure or all LTG have loaded code and are not in service (PLA, MBL or UNA). LTG has loaded code and is not in service (PLA, MBL or UNA). normal service hardware fault; after manual reset/power one the red LED LTG1 light while BOST is running. initialization, configuration, loading or self-test, no faults module has loaded no code and is not in service (PLA, MBL or UNA).

PWR LTG 0 LTG 1 LTG 2 LTG 3

all off

off off on

off on off

off V24 Interface flashes briefly


V24

flashes flashes

742

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.13.4

GPSI (-Q278-X300-)
GPSI

Group processor module with 4 LTG functions, 1 Gbyte memory, 63 x E1 interface Switch up: Power on Switch in central position: Power off Switch downwards press.: Module hardware reset. LTG 0 = 1st LTG on the module.LTG 1 = 2nd LTG on the module. LTG 2 = 3rd LTG on the module.LTG 3 = 4th LTG on the module. LED red LED green all off Module status power failure or all LTG have loaded code and are not in service (PLA, MBL or UNA). LTG has loaded code and is not in service (PLA, MBL or UNA). normal service hardware fault; after manual reset/power one the red LED LTG1 light while BOST is running. initialization, configuration, loading or self-test, no faults module has loaded no code and is not in service (PLA, MBL or UNA).

PWR Switch LTG 0 LTG 1 LTG 2 LTG 3

all off

off off on

off on off

off V24 Interface flashes briefly


V24

flashes flashes

A30828-X1160-M-2-7620

743

Construction

Maintenance Node

4.13.5

STMI:E(W) (-Q300-)
STMI: E(W)

Synchronous Transport Module Interface with Electrical link, Working module

INT

q
ID

LED green LED red

LED green/INT flashes on off

LED red/ID on on off on on

Module status startup BOST, no valid application SW loaded operating SW active - no fault, module state enabled operating SW active - HW fault module state disable unavailable operating SW active - subrack equipping fault and HW fault module state disable unavailable operating SW active - subrack equipping fault and HW fault module state disable wrong module type or disable wrong SW version

2 Mbit/s 2Mbit/s monitoring


RESET

on on

Reset key

V.24 (F) Interface

on

off

744

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.13.6

STMI:E(P) (-Q301-)
STMI: E(P)

Synchronous Transport Module Interface with Electrical link, Protection module

INT

q
ID

green LED red LED

LED green/INT flashes on off

LED red/ID on on off on on

Module status startup BOST, no valid application SW loaded operating SW active - no fault, module state enabled operating SW active - HW fault module state disable unavailable operating SW active - subrack equipping fault and HW fault module state disable unavailable operating SW active - subrack equipping fault and HW fault module state disable wrong module type or disable wrong SW version

2 Mbit/s 2Mbit/s monitoring


RESET

on on

Reset key

V.24 (F) Interface

on

off

A30828-X1160-M-2-7620

745

Construction

Maintenance Node

4.13.7

STMI:O(W) (-Q298-)
STMI: O(W)

Synchronous Transport Module Interface with Optical link, Working module

INT

q
ID

green LED red LED

LED green/INT flashes on off

LED red/ID on on off on on

Module status startup BOST, no valid application SW loaded operating SW active - no fault, module state enabled operating SW active - HW fault module state disable unavailable operating SW active - subrack equipping fault and HW fault module state disable unavailable operating SW active - subrack equipping fault and HW fault module state disable wrong module type or disable wrong SW version

q
2Mbit/s RESET

2 Mbit/s monitoring Reset key

on on

V.24 (F) Interface

on

off

746

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.13.8

STMI:O(P) (-Q299-)
STMI: O(P)

Synchronous Transport Module Interface with Optical link, Protection module

INT

q
ID

green LED red LED

LED green/INT flashes on

LED red/ID on on off on on

Module status startup BOST, no valid application SW loaded operating SW active - no fault, module state enabled operating SW active - HW fault module state disable unavailable operating SW active - subrack equipping fault and HW fault module state disable unavailable operating SW active - subrack equipping fault and HW fault module state disable wrong module type or disable wrong SW version

q
2Mbit/s RESET

2 Mbit/s monitoring Reset key

off on on

V.24 (F) Interface on off

A30828-X1160-M-2-7620

747

Construction

Maintenance Node

4.14

SYP
4.14.1 4.14.2 4.14.3 4.14.4 4.14.5 4.14.6 4.14.7 4.14.8 4.14.9 4.14.10 4.14.11 4.14.12 4.14.13 COM:SYPC (-Q758-) RM:EA (-Q760-) T/RM:SYPC (-Q761-) T/RM:SYPC (-Q761-X100-) TXA:SYPC (-Q759-) ACC:SYPD (-Q776-) DYM:SYPD (-Q708-) EWA:SYPD (-Q5517-) T/RM:SYPD (-Q709-X-) T/RM:SYPD (-Q709-X100-) PBSL32J (-U2607-) PBSL8RO (-U2608-) PBSLV24 (-U2609-)

4.14.1

COM:SYPC (-Q758-)
COM: SYPC HOLD

Control module for system panel control In order to monitor execution of the firmware programs, a timer must be reset every 13 ms. If no reset command is input, a reset pulse is generated; this restarts the firmware. If more than threereset pulses are generated within 11 minutes, the processor is halted on module COM:SYPC and all interfaces are disabled. This state is indicated by the red LED HOLD, which flashes. Pressing switch H-OFF restarts the processor and enablesall interfaces.

q
H-OFF HS

red LED

Switch

RESET

Switch

To reset the processor manually, press first switch H-OFF and then switch RESET.

COM:SYPC EPROM 0 from address 0000 to 07FF EPROM 1 from address 0800 to 0FFF EPROM 2 from address 1000 to 17FF EPROM 3 from address 1800 to 1FFF User EPROM EPROM 4 from address 2000 to 27FF EPROM 5 from address 2800 to 2FFF EPROM 6 from address 3000 to 37FF EPROM 7 from address 3800 to 3FFF
7 6 5 4

EPROM 7 is the user EPROM


3 2 1 0

748

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.14.2

RM:EA (-Q760-)
Receiver module for external alarms On the SYPD there are 8 pairs of lamps and 8 single lamps for displaying external alarms. The 8 lamp pairs can display a critical alarm, a major alarm, a minor alarm or a major alarm and a minor alarm. The 8 single lamps can display a major alarm or a minor alarm. If there are alarm combinations for the same lamp pair or single lamp that cannot be displayed at the same time, the alarm with the higher priority is displayed (i.e. critical alarm before major alarm or minor alarm). Module RM:EA has 24 EDLs (external data lines. These EAIs can be assigned for each program to single lamps or lamp pairs on the SYPD. Up to three EAIs can be switched to a lamp pair and up to two EAIs to a single lamp. The assignment of the EALs to the lamps on the SYPD is carried out by appropriate programming in the user EPROM on module COM:SYPC. The user EPROM is also used to determine which priority (critical alarm, major alarm, minor alarm) is assigned to which EAL. The lines from the external alarm units are usually connected via MDF to module RM:EA. The connector for direct connection to module RM:EA is on the rear side of the SYPC(A).

4.14.2.1

Assignment of the individual EDI (EDLs, EALs) to the connector pins of module RM:EA on the wiring board of the frame F:SYPC(A)
F:SYPC(A): Mounting unit 04 or 05, Mounting location A022
EAI no. (EDL no. EAI no.) 1 2 3 4 5 6 7 8 9 10 11 12 3 4 5 6 7 8 9 10 11 12 13 14 Pin no. EAI no (EDL no. EAI no.) 13 14 15 16 17 18 19 20 21 22 23 24 43 44 45 46 47 48 49 50 51 52 53 54 Pin no.

Tab. 4.45

EAI list

A30828-X1160-M-2-7620

749

Construction

Maintenance Node

4.14.2.2

LED numbers for the external alarms on the SYPD

:
MONTH DAY TIME EXTERNAL ALARMS LINE/TRUNK GROUPS LTG SWITCHING NETWORK SN

15 16

31 32 33 34 35 36 37 38
HW-UNITS MBL SIGNALING LINK NO.7 BLOCKED ALARM DISPLAY SUPPRESSION

MAINTEN. ALARM

SERVICE ALARM

EXTERN. EQUIPM.

17 18

COORDINATION PROCESSOR CP

CENTRAL UNITS

MESSAGE BUFFER

19 20

ERL PROCESSOR LOAD

CLOCK

COM. CHAN. SIGNALING

21 22

SYSTEM PANEL SYP

TRUNK GROUP ALARM LINE LOCKOUT SIGNALING LINK NO.7 CALL IDENTIFICATION

TRUNK GROUP BLOCKED CAT 1 CAT 2 SYSTEM OPERATOR

EXT. DLU ALARM ADMIN. ALARM RECOVERY TIME INSECURE

UPDATE

TEST

ACCEPT.

4.14.3

T/RM:SYPC (-Q761-)
T/RM:SYPC Transmitter/receiver module for system panel control Switches 1 BR, 2 BR, 3 BR: In position 2 on the SYPD connectors, which use four-wire lines, these three switches strap the corresponding MB line to ground on the transmitter side.This is necessary, for example if there is no ground for a connected carrier frequency device: Switch 1 BR straps line MB 1 i. e. pin 41 to ground. Switch 2 BR straps line MB 2 i. e. pin 50 to ground. Switch 3 BR straps line MB 3 i. e. pin 42 to ground.
3 BR 1 2 1 2 BR 2 1 1 BR 2

750

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.14.4

T/RM:SYPC (-Q761-X100-)
Transmitter/receiver module for system panel control If a module T/RM:SYPC with part number -Q761-X- is to be replaced by a new module with part number -Q761-X100-, and if a SYPD is connected on the other side, the corresponding module T/RM:SYPD in SYPD with part number -Q709-X- must also be replaced by a new module with part number -Q709-X100-. The programming of the user EPROM on module COM:SYPC also has to be changed if SYPD0 has been used up to now. On the new modules the U-plugs (X5, X6, X7 and X9, X10, X11 on T/RM:SYPC and X5 and X6 on T/RM:SYPD) must be set according to the signals transmitted (inverted or non-inverted). In the previous SYP (SYPC and SYPD modules with part number -Qxxx-X-) there was one two-wire SYPD terminal on module T/RM:SYPC (for SYPD0) and three four-wire SYPD terminals (for SYPD1 to SYPD3). The new SYP modules (T/RM:SYPC and T/RM:SYPD in V24 technology with part number -Qxxx-X100-) require two wires in each direction for data transfer between SYPC and SYPD or CT, i.e. only four-wire connections (forward and backward direction) are possible. In the existing frames, only the terminals for SYPD 1 to SYPD3 are available as fourwire terminals, but not the terminal for SYPD0. Therefore the terminal for SYPD0 cannot be used if both modules (T/RM:SYPC and T/RM:SYPD) using the old technology have been replaced by new V24 modules. This means that in the transmission direction (from T/RM:SYPC to T/RM:SYPD or CT) only the signals TX2A, TX3A, TX4A and the corresponding ground terminals TX2B, TX3B and TX4B can be used; in the receive direction (from T/RM:SYPD or CT to T/RM:SYPC) only the signals RX2A, RX3A, RX4A and the corresponding ground terminals RX2B, RX3B and RX4B can be used. Signals TX1 and RX1 (corresponding to the old SYPD0 terminal) cannot be used.
T/RM:SYPC Transmitter/receiver module for system panel control

X12 3 1 3 X11 1 3 X10 1 X9 3 1

4 2 4 2 4 2 4 2

3 1 3 1 3 1 3 1

4 2 4 2 4 2 4 2

X5 X6 X7 X8

Location of the U-Plugs on module T/RM:SYPC The V24 signals transmitted from SYPC to SYPD or CT (forward signals), can be provided in inverted and non-inverted form. The default setting of the U-plugs is such that a non-inverted signal is transmitted. The table below shows how to insert the U-plugs, according to the type of signal. All signals designated Rxxx are forward signals (from T/RM:SYPC to T/RM:SYPD or CT) and all signals designated Txxx are backward signals (from T/RM:SYPD or CT to T/RM:SYPC):

A30828-X1160-M-2-7620

751

Construction

Maintenance Node

Name of U-plug

non-inverted signal Pin no. to be connected 1-2

inverted signal Pin no. to be connected 3-4

Signal name and module pin no.

X5

RX4A on pin 3 for SYPD3 RX4B (ground) on pin 6 RX3A on pin 30 for SYPD2 RX3B (ground) on pin 31 RX2A on pin 8 for SYPD1 RX2B (ground) on pin 9 RX1 on pin 46 (do not use, SYPD0)

X6

1-2

3-4

X7

1-2

3-4

X8

1-2

3-4

X9

1-2

3-4

TX4A on pin 45 for SYPD3 TX4B (ground) on pin 42 TX3A on pin 49 for SYPD2 TX3B (ground) on pin 50 TX2A on pin 23 for SYPD1 TX2B (ground) on pin 41 TX1 on pin 47 (do not use, SYPD0)

X10

1-2

3-4

X11

1-2

3-4

X12

1-2

3-4

Tab. 4.46

Assignment of U-plugs T/RM:SYPC

4.14.5

TXA:SYPC (-Q759-)
TXA: SYPC

Alarm transmitter for system panel control When module TXA:SYPC has been inserted or power has been switched on, all relays on this module are blocked, i.e. all relay contacts are opened. This state is indicated by LED DIS, which lights up. A reset pulse from the processor of module COM:SYPC turns LED DIS off. However, the outputs of the parallel interface component 8255A-5 remain high. The relays contacts therefore remain opened. They do not set themselves to the alarm status indicated on SYPD until the 8255A-5 has received the control word and the setting information.

DIS

q
HS

red LED

Module TXA:SYPC is used to transfer alarms which are displayed on the SYPD via relays to external fault signaling units. A maximum of 24 different SYPD can be transferred. The user EPROM determines which priority (critical alarm, major alarm, minor alarm) is output to one or more relay by which SYPD. The assignment of the individual relays to the alarm lines (AL) is preset and cannot be changed. The relays are given the same designation as the individual ALs; the relay contacts are referred to as al. Alarms can be transferred electrically in four different ways: a) contact against ground b) contact against exchange voltage c) loop passive d) loop active

752

A30828-X1160-M-2-7620

Maintenance Node

Construction

Depending on the method of alarm transfer used, the corresponding link or the corresponding resistance must be strapped on module TXA:SYPC (see 4.14.5.1) The resistance R must have a value of 1 kiloohm and withstand power up to 2 watts. The link between point 7 and point 8 (RC spark protection) must always be strapped. If the RC combination causes difficulties for some loads (but only if this is the case), this link may be omitted.

4.14.5.1

The four types of link connection on module TXA:SYPC


a) 2 3 ground b) 2 3 ground c) 2 3 ground d) 2 3 ground R or wire link 5 5 5 R 4 4 R 1 1 1 4 4 R 1 5

al 7 8

-48V/60V
7 8

al

-48V/60V
7 8

al

-48V/60V
7 8

al

-48V/60V

ALxA

ALxB

ALxA

ALxB

ALxA

ALxB

ALxA

ALxB

R1

R1

R1

R2

R1

-48V/60V R1 2kOhm

ground R1 2kOhm

-48V/60V ground R1 + R2 2kOhm R1 2kOhm

The values for load resistance must be maintained as minimal values by the external fault signaling unit (depending on the link connections):

A30828-X1160-M-2-7620

753

Construction

Maintenance Node

4.14.5.2

Location of the links on module TXA:SYPC

3 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 5

1 7 8

AL 24

AL 22

AL 20

AL 18

AL 16

AL 14

AL 12

AL 10

AL 8

AL 6

AL 4

AL 2

AL 23

AL 21

AL 19

AL 17

AL 15

AL 13

AL 11

AL 9

AL 7

AL 5

AL 3

AL 1

4.14.5.3

Alarm lines for external fault signaling units


The alarm lines (AL) to the external fault signaling units are normally connected to module TXA:SYPC via the MDF. The connectors for direct connection to module TXY:SYPC are on the wiring board in mounting unit 04 or 05 at mounting locations A046 and B046. The two following tables show the assignment of the individual ALs to the connector pins of module TXA:SYPC on the wiring board (wiring side).

754

A30828-X1160-M-2-7620

Maintenance Node

Construction

AL no.

Pin no.

Connector MOLOC in F:SYPC(A) A046

AL no.

Pin no.

Connector MOLOC in F:SYPC(A) A046

AL1A AL1B AL2A AL2B AL3A AL3B AL4A AL4B AL5A AL5B AL6A AL6B

45 05 46 06 47 07 48 08 49 09 50 10

AL7A AL7B AL8A AL8B AL9A AL9B AL10A AL10B AL11A AL11B AL12A AL12B

51 11 52 12 53 13 54 14 55 15 56 16

Tab. 4.47

Alarm lines

AL no.

Pin no.

Connector MOLOC in F:SYPC(A) B046

AL no.

Pin no.

Connector MOLOC in F:SYPC(A) B046

AL13A AL13B AL14A AL14B AL15A AL15B AL16A AL16B AL17A AL17B AL18A AL18B

245 205 246 206 247 207 248 208 249 209 250 210

AL19A AL19B AL20A AL18B AL21A AL21B AL22A AL22B AL23A AL23B AL24A AL24B

251 211 252 212 253 213 254 214 255 215 256 216

Tab. 4.48

Alarm lines

A30828-X1160-M-2-7620

755

Construction

Maintenance Node

4.14.6

ACC:SYPD (-Q776-)
AC/DC Converter (rectifier) for system panel display (module)

ACC:SYPD C2

C1 SH Transformer TR

SI +UE -UE

BR

Power cable

4.14.6.1

Fuse position
Safety hood SH: The safety hood SH must be removed if the ACC module is to be switched to a different ac line voltage (Primary voltage) or if the fuse SI is to be replaced. Fuse SI: The ac line fuse SI is underneath safety hood SH. For the terminal strip with 8 terminal points the fuse rating for an ac line voltage of 110V...120V is 0,63AT and for an ac line voltage of 220V...240V 0,315AT. For the terminal strip with 10 terminal points, the fuse rating for an ac line voltage of 110V...120V is 1AT and for an ac line voltage of 220V...240V 0,4AT. Output voltage pins + UE, - UE: Output voltage pins + UE and - UE the output voltage of the ACC module is 60 V.

4.14.6.2

Power Supply Adjustment


Terminal strip BR: Terminal strip BR, on which appropriate links must be strapped for the various ac line voltages, is beneath safety hood SH. For the terminal strip with 8 terminal points, the terminal points must be connected as shown in the following table:

756

A30828-X1160-M-2-7620

Maintenance Node

Construction

110 V BR 1 with BR 8 BR 2 with BR 7 BR 4 with BR 8 BR 5 with BR 7

120 V BR 1 with BR 8 BR 3 with BR 7 BR 4 with BR 8 BR 6 with BR 7

220 V BR 1 with BR 8 BR 2 with BR 4 BR 5 with BR 7

240 V BR 1 with BR 8 BR 3 with BR 4 BR 6 with BR 7

Tab. 4.49

Connections on terminal strip with 8 terminal points

For the terminal strip with 10 terminal points, the terminal points must be connected as shown in the following table:
110 V BR 1 with BR 6 BR 3 with BR 6 BR 3 with BR 4 BR 7 with BR 8 BR 8 with BR 10 120 V BR 1 with BR 5 BR 3 with BR 5 BR 3 with BR 4 BR 7 with BR 8 BR 8 with BR 9 220 V BR 1 with BR 2 BR 2 with BR 6 BR 4 with BR 7 BR 8 with BR 10 240 V BR 1 with BR 2 BR 2 with BR 5 BR 4 with BR 7 BR 8 with BR 9

Tab. 4.50

Connections on terminal strip with 10 terminal points

4.14.7

DYM:SYPD (-Q708-)
Display module for system panel display The SYPD modules cannot be accessed unless the SYPD faceplate is removed. To do this, unscrew the cross-head screws in the four corners and lift off the faceplate. Behind the faceplate is module DYM:SYPD. This module can be swivelled out to the left. Behind this module there is a protective shield which also acts as the module support for modules EWA:SYPD and T/RM:SYPD. This protective shield can be swivelled out to the left, once the two screws in the right-hand corners have been unscrewed. The two modules EWA:SYPD and T/RM:SYPD are at the back. In addition, an ACC:SYPD module can also be attached to the inside of the rear of the SYPD. When assembling the SYPD, make shure that the three keys at the bottom on the left on module DYM:SYPD pass through the faceplate before the faceplate is fastened.

A30828-X1160-M-2-7620

757

Construction

Maintenance Node

RESET

UPDATE

TEST

ACCEPT

4.14.7.1

Location of the Keys and LEDs on Module DYM:SYPD


RESET key: Press the RESET key to manually reset the processor on module DYM:SYPD. The UPDATE lights up. UPDATE key: This key updates the displays on all connected SYPDs, e.g. after a SYPD failure. An LED above the key lights up while updating is taking place. TEST key: If this key is pressed all LEDs and all 7 segment displays should light up and the buzzer should sound for 800 ms. The signal only sounds if it has not been switched off in the SYPD and if the SYPD displays are not being updated. The test key functions only for the SYPD where it is pressed. ACCEPT key: Every new alarm is signaled at the SYPD by switching on the buzzer and rapid flashing of the relevant LED. Now the accept key on the SYPD has to be pressed to switch off the buzzer. Pressing the accept key switches off the buzzer only. The alarm status which is the actual acceptation of the alarm, is set with the command SET ALSTAT within procedure SYP 100. If the alarm status is set, the flashing frequency of the relevant display is halved. This halving of the flashing frequency is only for system displays, but not for external alarms. One SYPD, usually the SYPD in the maintenance center, is a master panel (several master panels could be present). Pressing the accept key at the master panel switches

758

A30828-X1160-M-2-7620

Maintenance Node

Construction

off the buzzer at all connected SYPDs. It is usual that all SYPDs are programed as master panel. If an SYPD is not a master manuel, then the accept key only works for that SYPD where it is pressed. The other SYPDs remain unaffected. The displays CALL IDENTIFICATION and SYSTEM OPERATOR are an exception. Here, the buzzer is only switched off when the accept key has been pressed at a master panel. If the accept key for a new alarm is not pressed within 5 minutes the buzzer is increased to maximum volume. The duration of the buzzer can be limited with the command ENTR ALMODE.

4.14.8

EWA:SYPD (-Q5517-)
DC converter for SYPD

EWA

green LED

This LED lights up when the direct current converter generates 5 V and switches them through to its output. The LED goes out when no voltage is generated at all

+
Test jack 1 Test jack 1 (+), Test jack 2 (-):The output voltage of the direct current converter (5V) can be measured between these two jacks. Test jack 2

5V

Switch BR: In position 2 on the SYPD connectors, which use four-wire lines, this switch straps the corresponding MB line to ground on the transmitter side: Switch BR straps line MB i.e. pin 4 to ground. This is necessary, for example if there is no ground for a connected carrier frequency device. Switch HI: In position 1, switch HI switches off the internal audible alarm. Switch HE: In position 1, switch HE switches off the external audible alarm (if there is one). Potentiometer R61: Potentiometer R61 is used to set the volume of the audible alarm.

A30828-X1160-M-2-7620

759

Construction

Maintenance Node

4.14.9

T/RM:SYPD (-Q709-X-)
Transmitter/receiver module for system panel display

T/RM:SYPD 1 BR 2

1 HE R 61

1 HI

Location of the switches and the potentiometer on module T/RM:SYPD: Switch BR: In position 2 on the SYPD connectors, which use four-wire lines, this switch straps the corresponding MB line to ground on the transmitter side: Switch BR straps line MB i.e. pin 4 to ground. This is necessary, for example if there is no ground for a connected carrier frequency device. Switch HI: In position 1, switch HI switches off the internal audible alarm. Switch HE: In position 1, switch HE switches off the external audible alarm (if there is one). Potentiometer R61: Potentiometer R61 is used to set the volume of the audible alarm.

4.14.10

T/RM:SYPD (-Q709-X100-)
Transmitter/receiver module for system panel display If, in the SYPC, a module T/RM:SYPC with part number -Q761-X- is to be replaced by a new module with part number -Q761-X100- , and if a SYPD is connected on the other side, the corresponding module T/RM:SYPD in the SYPD with part number -Q709-Xmust also be replaced by a new module with part number -Q709-X100-. Only four-wire transmission with V24 can be used with the new modules (T/RM:SYPC with -Q761X100- and T/RM:SYPD with -Q709-X100-). The terminals provided in the frame for connecting SYPD0 are two-wire terminals and those for SYPD1 to 3 are four-wire terminals. However, since only four-wire transmission is possible with the new modules, a SYPD that was previously operated as SYPD0 on a two-wire basis will now have to be operated as SYPD1, SYPD2 or SYPD3 on a four-wire basis. The programming of the user EPROM on module COM:SYPC therefore also has to be changed.

760

A30828-X1160-M-2-7620

Maintenance Node

Construction

T/RM:SYPD

14 X5 23

43 X6 12

R19

S2 1 2 1

S1 2

Location of the switches, U-plugs and the potentiometer on module T/RM:SYPD: Switch S1: In position 1, switch S1 switches off the internal audible alarm. Switch S2: In position 1, switch S2 switches off the external audible alarm (if there is one). Potentiometer R19: Potentiometer R19 is used to set the volume of the audible alarm. In the previous SYP (SYPC and SYPD modules with part number -Qxxx-X-) there was one two-wire SYPD terminal on module T/RM:SYPC (for SYPD0) and three four-wire SYPD terminals (for SYPD1 to SYPD3). With the new SYP modules (T/RM:SYPC and T/RM:SYPD in V24 technology with part number -Qxxx-X100-) two wires are required in each direction for data transfer between SYPC and SYPD or CZ, i.e. only four-wire connections (forward and backward direction) are possible. In the existing frames, only the terminals for SYPD1 to SYPD3 are available as four-wire terminals, but not the terminal for SYPD0. Therefore the terminal for SYPD0 cannot be used if both modules (T/RM:SYPC and T/RM:SYPD) using the old technology have been replaced by new V24 modules. This means that in the transmission direction (from T/RM:SYPC to T/RM:SYPD) only signal RXA and the corresponding ground terminal RXB can be used; in the receive direction (from T/RM:SYPD to T/RM:SYPC) only signal TXA and the corresponding ground terminal TXB can be used. Signals T and R (corresponding to the old two-wire terminal) cannot be used. On the new modules the U-plugs (X5, X6, X7 and X9, X10 X11 on T/RM:SYPC and X5 and X6 on T/RM:SYPD) must be set according to the signals transmitted (inverted or non-inverted).

A30828-X1160-M-2-7620

761

Construction

Maintenance Node

Name of U-plug

non-inverted signal Pin no. to be connected 1-2

inverted signal Pin no. to be connected 3-4

Signal name and module pin no.

X5

RXA on pin 5 RXB (ground) on pin 6 T on pin 16 (identical to RXA) TXA on pin 3 TXB (ground) on pin 4 R on pin 15 (identical to TXA)

X6

1-2

3-4

Tab. 4.51

Assignment of U-plugs T/RM:SYPD

4.14.11

PBSL32J (-U2607-)
Profibus unit for alarm registration Profibus unit PBSL32J registers alarms from up to 32 external alarm generators. The alarm status of these external alarm generators is passed on via the profibus interface to the alarm IOP and to profibus unit PBSLV24. State: Operating state indicated with a green LED and a red LED

SI E M E NS
State X3 Alarms 1 X2 DP 20

X2 DP: Profibus interface via a 9-contact D-Sub jack

X3 Alarms: 32 alarm inputs via a 37-contact D-Sub jack

19

37

CC

762

A30828-X1160-M-2-7620

Maintenance Node

Construction

S1 DP1 2 4 8 16 32 64 addresses and settings 0 1 remove to change PE 0V X1

S1 DPAddress 1 2 4 8 16 32 64 0 1

110..230V AC -38..-75V DC 100mA F1,6A

4.14.11.1

S1 DP address
The address of profibus module PBSL32J (jack X2 DP) is set on these switches. S1 DPAddress

1 2 4 8 16 32 64 0

Switch number 1 2 4 8 16 32 64 --

Function 2 to the 0th 2 to the 1st 2 to the 2nd 2 to the 3rd 2 to the 4th 2 to the 5th 2 to the 6th reserved

Addend 1 2 4 8 16 32 64 0

The address of the profibus module is given by the sum of the set (activated) addends. An addend is activated when the relevant switch is in position 1.

A30828-X1160-M-2-7620

763

Construction

Maintenance Node

4.14.11.2

State
Operating state indication of profibus module PBSL32J The operating state of profibus module PBSL32J is indicated by these two LEDs. The following indications are possible: a) The green LED and the red LED are dark! The probus unit is off circuit. b) The green LED is dark and the red LED shines steadily! This is the way the LEDs appear when the supply voltage has been switched on. If a malfunction is detected when the probus is started, this indication remains. c) The green LED ashes and the red LED is dark: The probus unit is ready for operation but the operating parameters have not yet been set. d) The green LED shines steadily and the red LED is dark! The operating parameters have been set, the probus unit has been activated and data is continuously being exchanged with the IOP.

4.14.11.3

X1
The operating voltage is fed to profibus unit PBSL32J via this connector. The following supply voltages are possible: 1. Exchange voltage (dc voltage) of -38 V to -75 V, with protection against polarity inversion 2. Mains voltage (ac voltage) with 110 V or 230 V Pin assignment: Pin 1: 110 V or 230 V ac voltage or -38 V to -75 V dc voltage (L+, protected against polarity inversion) Pin 2: Protective ground (PE, for ac voltage), this pin is extra long Pin 3: Neutral conductor (N, for ac voltage) or 0 V (L- , for dc voltage)

X1

1 2 3

Plug connection X 1 must not be pulled or plugged when the voltage is switched on.

764

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.14.11.4

X2 DP
Interface of profibus module PBSL32J to the profibus The connection to the profibus is established via this 9-contact D-Sub jack. The pins are assigned as follows:

X2 DP 5

9 6

Pin 1: not assigned Pin 2: not assigned Pin 3: RS485-B Pin 4: RTS Pin 5: GND Pin 6: VCC Pin 7: not assigned Pin 8: RS485-A Pin 9: not assigned

4.14.11.5

X3 Alarms
Interface of profibus module PBSL32J to the external alarm generators Up to 32 external alarm generators can be connected via this 37-contact D-Sub jack. The pins are assigned as shown below:

X3 Alarms 1 20

19

37

Pin 1: Input 1 Pin 2: Input 2 Pin 3: Input 3 Pin 4: Input 4 Pin 5: Input 5 Pin 6: Input 6 Pin 7: Input 7 Pin 8: Input 8 Pin 9: Input 9 Pin 10: Input 10 Pin 11: Input 11 Pin 12: Input 12 Pin 13: Input 13 Pin 14: Input 14 Pin 15: Input 15 Pin 16: Input 16 Pin 17: Input 17 Pin 18: Input 18 Pin 19: Input 19

Pin 20: Input 20 Pin 21: Input 21 Pin 22: Input 22 Pin 23: Input 23 Pin 24: Input 24 Pin 25: Input 25 Pin 26: Input 26 Pin 27: Input 27 Pin 28: Input 28 Pin 29: Input 29 Pin 30: Input 30 Pin 31: Input 31 Pin 32: Input 32 Pin 33: Function ground* Pin 34: Function ground* Pin 35: Function ground* Pin 36: Function ground* Pin 37: Function ground*

* The reference potential has to be fed in on these pins. This is usually the function ground.

A30828-X1160-M-2-7620

765

Construction

Maintenance Node

Relay outputs of the external alarm generators must be connected to the inputs for the external alarm generators. Profibus unit PBSL32J applies a constant current (at least 9 mA) to each of pins 1 to 32. By measuring the voltage between the individual pins and the function ground it is possible to determine whether the connected relay contact is open or closed. If the measured voltage corresponds to a resistance of greater than 1.5 kilohms plus/minus 15 %, the connected relay contact is interpreted as being open. The voltage value at 1.5 kilohms (open-circuit voltage) is therefore 14.25 V.

4.14.12

PBSL8RO (-U2608-)
Profibus unit for alarm forwarding Profibus unit PBSL8RO forwards alarms that are present on the profibus to external fault signaling equipment via 8 relay outputs.

SI E M E NS

State: Operating state indicated with a green LED and a red LED

State

X3 Relay

1
X2 DP

X2 DP: Profibus interface via a 9-contact D-SUB jack

2 3 4 5 6 7 8
X3 Relay: 8 Alarm outputs via a 16-contact Mini-Combicon connector strip

CC

766

A30828-X1160-M-2-7620

Maintenance Node

Construction

S1 DP- S2 1 2 4 8 16 32 64 1 2 3 4 5 6 7 8 addresses and settings 0 1 Remove to change Closer

S1 DP- S2 Address Relay 1 2 4 8 16 32 64 0 1 Closer 1 2 3 4 5 6 7 8 Opener

110..230V AC -38..-75V DC 100mA F1,6A

Opener PE 0V X1

4.14.12.1

S1 DP address
The address of profibus module PBSL8RO (jack X2 DP) is set on these switches S1 DPAddress 1 2 4 8 16 32 64 0 1

Switch number 1 2 4 8 16 32 64 --

Function 2 to the 0th 2 to the 1st 2 to the 2nd 2 to the 3rd 2 to the 4th 2 to the 5th 2 to the 6th reserved

Addend 1 2 4 8 16 32 64 0

The address of the profibus module is given by the sum of the set (activated) addends. An addend is activated when the relevant switch is set to 1.

A30828-X1160-M-2-7620

767

Construction

Maintenance Node

4.14.12.2

S2 Relay
The type of contact of the alarm outputs on connector strip X3 Relay is set on these switches. S2 Relay 1 2 3 4 5 6 7 8 Closer Opener The 8 alarm outputs of connector strip X3 Relay are implemented as relay contacts. With the aid of the S2 Relay switches, each individual relay contact can be set as an opener (closed when idle) or as a closer (open when idle). The label Opener or Closer means that each setting is assigned an unambiguous function.

4.14.12.3

State
The operating state of profibus module PBSL8RO is indicated by these two LEDs. The following indications are possible: a) The green LED and the red LED are dark! The probus module is off circuit. b) The green LED is dark and the red LED shines steadily! This is the way the LEDs appear when the supply voltage has been switched on. If a malfunction is detected when the probus is started, this indication remains. c) The green LED ashes and the red LED is dark: The probus unit is ready for operation but the operating parameters have not yet been set. d) The green LED shines steadily and the red LED is dark! The operating parameters have been set, the probus unit has been activated and data is continuously being exchanged with the IOP.

4.14.12.4

X1
The operating voltage is fed to profibus unit PBSL8RO via this connector. The following supply voltages are possible: 1. Exchange voltage (dc voltage) of -38 V to -75 V, with protection against polarity inversion 2. Mains voltage (ac voltage) with 110 V or 230 V

768

A30828-X1160-M-2-7620

Maintenance Node

Construction

X1

1 2 3

Pin assignment: Pin 1: 110 Vor 230 V ac voltage or -38 V to -75 V dc voltage (L+, protected against polarity inversion) Pin 2: Protective ground (PE, for ac voltage), this pin is extra long Pin 3: Neutral conductor (N, for ac voltage) or 0 V (L-, for dc voltage)

Plug connection X 1 must not be pulled or plugged when the voltage is switched on.

4.14.12.5

X2 DP
Interface of profibus module PBSL8RO to the profibus The connection to the profibus is established via this 9-contact D-Sub jack. The pins are assigned as follows:

X2 DP 5

9 6

Pin 1: not assigned Pin 2: not assigned: Pin 3: RS485-B Pin 4: RTS Pin 5: GND Pin 6: VCC Pin 7: not assigned Pin 8: RS485-A Pin 9: not assigned

A30828-X1160-M-2-7620

769

Construction

Maintenance Node

4.14.12.6

X3 Relay
Interface to 8 external fault signaling equipment units Up to 8 external fault signaling equipment units can be connected via this 16-contact Mini-Combicon connector strip. The pins are assigned as shown below:

1 Relay 1, contact 1 2 3 4 5 6 7 8
Relay 1, contact 2 Relay 2, contact 1 Relay 2, contact 2 Relay 3, contact 1 Relay 3, contact 2 Relay 4, contact 1 Relay 4, contact 2 Relay 5, contact 1 Relay 5, contact 2 Relay 6, contact 1 Relay 6, contact 2 Relay 7, contact 1 Relay 7, contact 2 Relay 8, contact 1 Relay 8, contact 2

The type of contact that is available on the individual relays is described in the chapter on S2 Relay.

4.14.13

PBSLV24 (-U2609-)
Profibus unit for accessing SYSD Profibus module PBSLV24 converts the data supplied via the profibus and outputs them again via the V24 interface, e.g. for a SYSD display on the BCT. It also converts data arriving from the V24 interface and passes it on to the profibus.

770

A30828-X1160-M-2-7620

Maintenance Node

Construction

SI E M E NS

State: Operating state indicated with a green LED and a red LED

State X2 DP: Profibus interface via a 9-contact D-SUB jack X2 DP X3 V24 X3 V24: V24 interface e.g. for SYSD indication

CC
S1 DP1 2 4 8 16 32 64 addresses and settings 0 1 S2 Bd0 Bd1 Bd2 Odd Remove to change 0 1 S1 DP- S2 Address V24 1 2 4 8 16 32 64 0 1 0 1 Check - P. Stop bits Data bits Bd0 Bd1 Bd2 Odd

Check - P. Stop bits Data bits

A30828-X1160-M-2-7620

771

Construction

Maintenance Node

110..230V AC -38..-75V DC 100mA F1.6A

PE 0V X1

4.14.13.1

S1 DP address
The address of the profibus module PBSLV24 (jack X2 DP) is set on these switches. S1 DPAddress 1 2 4 8 16 32 64 0 1

Switch number 1 2 4 8 16 32 64 --

Function 2 to the 0th 2 to the 1st 2 to the 2nd 2 to the 3rd 2 to the 4th 2 to the 5th 2 to the 6th reserved

Addend 1 2 4 8 16 32 64 0

The address of the profibus module is given by the sum of the set (activated) addends. An addend is activated when the relevant switch is set to 1.

772

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.14.13.2

S2 V24
The data transmission rate for the D-Sub connector X3 V24 of profibus module PBSLV24 is set on these switches. S2 V24 Bd0 Bd1 Bd2 Odd Name of switch Bd0 Bd1 Bd2 Odd Check-P. Stop bits Data bits -Function Baud rate 0 Baud rate 1 Baud rate 2 odd parity check parity Stop bits Data bits reserved

0 1 Check-P. Stop bits Data bits

The data transmission rate via connector X3 V24 is set with switches S2 V24 as follows:
Switch setting Bd0 0 0 0 0 1 1 1 1 Switch setting Bd1 0 0 1 1 0 0 1 1 0 1 0 1 0 1 0 1 Switch setting Bd 2 Data transmission rate 50 Baud 300 Baud 600 Baud 1200 Baud 2400 Baud 4800 Baud 9600 Baud 19200 Baud

Tab. 4.52

Setting the data transmission rate with switches S2 V24

The setting of switch Odd of S2 V24 determines whether data transmission via connector X3 V24 is to be performed with even or odd parity. Switch setting 1 means odd parity and switch setting 0 means even parity. The setting of switch Check-P. of S2 V24 determines whether the parity check is active or inactive. Switch setting 1 means that the parity check is switched on, and switch setting 0 means that the parity check is switched off. The setting of switch Stop bits of S2 V24 determines whether one or two stop bits are to be used for data transmission. Switch setting 1 means that two stop bits are used and switch setting 0 means that one stop bit is used. The setting of switch data bits of S2 V24 determines whether data transmission is to be performed with 7 or 8 data bits. Switch setting 1 means that 8 data bits are used, and switch setting 0 means that 7 data bits are used.

A30828-X1160-M-2-7620

773

Construction

Maintenance Node

4.14.13.3

State
The operating state of profibus module PBSL32J is indicated by means of these two LEDs. The following indications are possible: a) The green LED and the red LED are dark! The probus unit is carrying no voltage. b) The green LED is dark and the red LED shines steadily! This is the way the LEDs appear when the supply voltage has been switched on. If a malfunction is detected when the probus is started, this indication remains. c) The green LED ashes and the red LED is dark: The probus unit is ready for operation but the operating parameters have not yet been set. d) The green LED shines steadily and the red LED is dark! The operating parameters have been set, the probus unit has been activated and data is continuously being exchanged with the IOP.

4.14.13.4

X1
The operating voltage is fed to the profibus unit PBSLV24 via this connector. The following supply voltages are possible: 1. Exchange voltage (dc voltage) of -38 V to -75 V, with protection against polarity inversion 2. Mains voltage (ac voltage) with 110 V or 230 V Pin assignment: Pin 1: 110 V or 230 V ac voltage or -38 V to -75 V dc voltage (L+, protected against polarity) Pin 2: Protective ground (PE, for ac voltage), this pin is extra long Pin 3: Neutral conductor (N, for ac voltage) or 0 V (L-, for dc voltage)

X1

1 2 3

Plug connection X 1 must not be pulled or plugged when the voltage is switched on.

774

A30828-X1160-M-2-7620

Maintenance Node

Construction

4.14.13.5

X2 DP
Interface of profibus module PBSLV24 to the profibus The connection to the profibus is established via this 9-contact D-Sub jack. The pins are assigned as follows:

X2 DP 5

9 6

Pin 1: not assigned Pin 2: not assigned: Pin 3: RS485-B Pin 4: RTS Pin 5: GND Pin 6: VCC Pin 7: not assigned Pin 8: RS485-A Pin 9: not assigned

4.14.13.6

X3 V24
V24 interface to a display unit, e.g. to the SYSD display The V24 interface is provided via this 9-contact D-Sub connector. The pins are assigned as shown below:

X3 V24 5

Pin 1: not assigned Pin 2: RxD Pin 3: TxD Pin 4: not assigned Pin 5: GND Pin 6: not assigned Pin 7: RTS Pin 8: CTS Pin 9: not assigned

A30828-X1160-M-2-7620

775