Modbus Register Map: Single-Phase Symmetra

990-3250
Absolute Starting //Absolute Starting Register Register Number, Bit Number, (Hexadecimal) (Decimal) Position Data Point // Status Word 0 40000 0 158 Reserved 1 = UPS ready to provide power to the load upon return of normal line or upon user command 1 = UPS ready to provide power to the load upon user command 1 = UPS in bypass mode as a result of manual bypass control 1 = UPS returning from bypass 1 = UPS in bypass due to command Reserved 1 = UPS in bypass due to an internal fault (indicated through register 40002 or 40003) UPS turning on Reserved 1= UPS fault - internal temperature exceeded nominal limits Reserved 1 = Battery charger failure 1 = UPS in shutdown mode 1 = UPS in sleep mode Reserved 1 = UPS unable to transfer to on-battery operation due to overload 1 = UPS output not receiving power due to low battery shut down R 1

10/2007

R/W Length Units R 1 BIT

Valid Response

7 6 5 4 3 2 1 0 // Status Word 1 40001 1 158 7 6 5 4 3 2 1 0

BIT BIT BIT BIT BIT

1 = State == Enable Load Disconnect (Output is off - But not due to delayed wakeup command) 1 = State == Load Disconnect (Output is off) (Number of modules != 0) && (Bad Modules != Installed Modules) 1 = State == Manual Bypass (System bypass by front switch) 1 = State == Temporary Bypass (Bypass with intention of leaving bypass state) 1 = State == Command Bypass (UPS Commanded into Bypass) 1 = State == Temporary Bypass (Bypass with no intention of leaving) 1 = State == Wakeup (Output turning on - Waiting for modules to start, processing system overrides)

BIT BIT BIT BIT BIT BIT BIT BIT

Any battery is too hot (Cleared 2 minutes after battery cools off) Any module has reported a charger fault (Cleared when no module has a charger failure) State == Enable Load Disconnect (Output is off - Waiting for power to return) State == Enable Load Disconnect (Output is off - By sleep with delayed wakeup command) State == Load Disconnect (Output is off - No modules providing power to load, and bypass was not available) State == Enable Load Disconnect (Output is off - Due to low battery - Waiting for power to return)

BIT BIT

Single-Phase Symmetra Modbus Register Map 1

Absolute Starting //Absolute Starting Register Register Number, Bit Number, (Hexadecimal) (Decimal) Position Data Point // Status Word 2 40002 2 152 Reserved 1 = Fan failure 1 0 Reserved // Status Word 3 40003 3 158 Reserved 7 1 = Replace battery 1 = Low battery 6 5 1 = Overload

R/W Length Units R 1 BIT

Valid Response

UPS fault - Base fan(s) not spinning (When Vin > 160 Vac)

1 BIT BIT BIT Low Battery Runtime <= Low Battery Setting ("j" <= "q") 1 = On battery - Any Module On Battery || Battery Discharging || Sim Power Failure || UPS Doing Self Test || Runtime Calibration

4 3 2 1 0 // Status Word 4 40004 4

1 = On battery 1 = Online Reserved 1 = Reboot/Sleep Mode 1 = Performing battery calibration discharge 1

BIT BIT BIT BIT

Symmetra sets this bit when in Reboot or Sleep Mode

1511 Reserved R 10 1 = Site wiring fault 1 = Fault found in register 40033, 40034, 40035, or 40036 9 1 = Battery voltage high 8 7 1 = No batteries 1 = System not synchronized 6 5 1 = Output voltage out of range 4 1 = XR frame fault 3 1 = Runtime below alarm threshold 1 = Load shutdown from bypass Input frequency or voltage outside limits 2 1 1 = No good modules present 0 1 = Internal communication failure 15 14 13 12 11 10 1 = RIM is in control 1 = System level fan failed 1 = Input CB tripped open 1 = System is in maintenance bypass 1 = UPS in bypass due to overload 1 = UPS in bypass due to internal fault R

(Symmetra LX Only) (Symmetra LX Only) Fault found in abnormal condition register (second abnormal condition register) (Symmetra LX Only) (Symmetra LX Only) (Symmetra LX Only) (Symmetra LX Only) Extended Run (XR) frame fault

// Status Word 5 40005

BIT BIT BIT BIT BIT BIT

Single-Phase Symmetra Modbus Register Map 2

Absolute Starting //Absolute Starting Register Register Number, Bit Number, (Hexadecimal) (Decimal) Position Data Point 1 = Bypass contactor stuck in online position 9 8 7 6 5 4 3 2 1 0 // 40006 40007 40008 40009 6 7 8 9 Line Quality % Battery Capacity Runtime Remaining Battery Voltage 1 = Bypass contactor stuck in bypass position 1 = Bypass not in range (either frequency or voltage unacceptable) 1 = Redundancy below threshold 1 = Loss of redundancy 1 = Load is above alarm threshold 1 = An installed battery has failed 1 = RIM is installed and failed 1 = IM is installed and failed An installed Power Module has failed

R/W Length Units BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT

Valid Response

R R R R

1 1 1 1

WORD WORD WORD WORD

4000A 4000B 4000C 4000D 4000E 4000F 40010 40011 40012 40013 40014 40015 40016 40017 40018

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

UPS Internal Temperature Amps Drawn by Load Number of Battery Packs with Bad Batteries Number of Battery Packs % Power Drawn By Load Maximum Input Voltage Since Last Reading Minimum Input Voltage Since Last Reading Nominal Battery Voltage Actual Battery Voltage Utility Input Frequency Utility Input Voltage Phase A Utility Input Current Phase A Bypass Input Voltage Phase A Percent of Maximum Output VAs Phase A @ n+0 Percent of Maximum Output VAs Phase A @ n+x

R R R R R R R R R R R R R R R

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD

00FF = acceptable utility line quality 0000 = unacceptable utility line quality % Min V Present internal operating temperature (0209C) 00XX =Valid reading FFXX =Invalid reading (XX is sensor reading) A Variable (1-99) Variable (1-99) % V V V V Hz V A V

WORD % WORD %

Single-Phase Symmetra Modbus Register Map 3

Absolute Starting //Absolute Starting Register Register Number, Bit Number, (Hexadecimal) (Decimal) Position Data Point 40019 Output Phase A 25 4001A Output Voltage Phase A 26 4001B Output Current Phase A 27 4001C Peak Output Current Phase A 28 4001D Utility Input Voltage Phase B 29 4001E Utility Input Current Phase B 30 4001F Bypass Input Voltage Phase B 31 Percent of Maximum Output VAs Phase B @ 40020 n+0 32 Percent of Maximum Output VAs Phase B @ 40021 n+x 33 40022 Output Phase B 34 40023 Output Voltage Phase B 35 40024 Output Current Phase B 36 40025 Peak Output Current Phase B 37 40026 Reserved 38 40027 39 Reserved 40028 40 Reserved 40029 41 Reserved 4002A 42 Reserved 4002B 43 Reserved 4002C 44 Reserved 4002D 45 Reserved 4002E 46 Reserved 4002F 40030 40031 40032 40033 40034 40035 //Status Word 9 40036 47 48 49 50 51 52 53 54 154 3 2 1

R/W Length Units Valid Response R 1 WORD kVA R 1 WORD V R 1 WORD A R 1 WORD A R 1 WORD V R 1 WORD A R 1 WORD V R R R R R R 1 1 1 1 1 1 WORD % WORD WORD WORD WORD WORD % kVA V A A

Measure-UPS Temperature Reading (sensor 1) R Measure-UPS Humidity Reading (sensor 1) R Measure-UPS Temperature Reading (sensor 2) R Measure-UPS Humidity Reading (sensor 2) R Reserved Reserved Reserved Reserved 1 = System power supply card failure 1 = External DC disconnect switch tripped 1 = Isolation transformer over temperature R

1 1 1 1

WORD C WORD % WORD C WORD %

BIT BIT BIT BIT

Reserved Frame Identification Fault (Symmetra LX Only) Power Module Failed to Turn Off (Symmetra LX Only) Bypass Relay Fault (Symmetra LX Only)

Single-Phase Symmetra Modbus Register Map 4

Absolute Starting //Absolute Starting Register Register Number, Bit Number, (Hexadecimal) (Decimal) Position 0 // 40037 55 40038 56 40039 57 4003A 58 4003B 59 4003C 60 4003D 61 4003E 62 4003F 63 40040 64 40041 65 40042 66 40043 67 40044 68 40045 69 40046 70 40047 71 40048 72 40049-4004F 7379 40050-FFFF 8065535

Data Point 1 = Maintenance bypass failure Measure-UPS Contact Position Minimum Return Battery Capacity Lower Transfer Point Upper Transfer Point Nominal Output Voltage Shutdown Delay Low Battery Duration Turn On Delay Sensitivity UPS ID Character #1 UPS ID Character #2 UPS ID Character #3 UPS ID Character #4 UPS ID Character #5 UPS ID Character #6 UPS ID Character #7 UPS ID Character #8 Battery Current Reserved INVALID ADDRESS

R/W Length Units BIT R R R R R R R R R R R R R R R R R R 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD WORD

Valid Response System Failure (Symmetra LX Only)

% V V V Sec Min Sec Sensitivity

Single-Phase Symmetra Modbus Register Map 5