Sie sind auf Seite 1von 16

AUTHORS NAME: MICHAEL WILLIAMS BUSINESS UNIT: TELSTRA OPERATIONS SUB BUSINESS UNIT: NETWORKS AND ACCESS TECHNOLOGIES

ISSUE DATE: 9 MAY. 2011| ISSUE NUMBER: 1.0 DOCUMENT NO: 007338 E10-2

INNOTECH DDC APPROVED CONTROL STRATEGY


BUILDING SERVICES 007338 - Power & Engineering Services
DESIGN STANDARD SUB DOMAIN: BUILDING SERVICES

This Power & Engineering Services document is to be used by network designers and constructors to design and install infrastructure approved for Network under 007338 Part D and in accordance with the deployment criteria specified in 007338 Part C in order to meet Telstras Business Objectives.

SUMMARY: The Purpose of this document is to provide a framework for programmers of Innotech Direct Digital Controls (DDC) which details the minimum requirements for functions and concepts to be incorporated and how those functions are to be programmed in a standard manner.

VERSION LABEL: Final SECURITY CLASSIFICATION: Telstra Unrestricted

TELSTRA CORPORATION LIMITED (ABN 33 01 775 556) | ISSUED: 9 MAY. 2011 FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 |ISSUE NUMBER: 1.0

TABLE OF CONTENTS

1. PURPOSE ....................................................................................................................... 3 2. SCOPE........................................................................................................................... 3 3. KEY STAKEHOLDERS....................................................................................................... 3 4. PROGRAMMING FUNCTIONAL REQUIREMENTS .................................................................. 4 4.1. GENERAL ................................................................................................................ 4 4.2. HVAC ENABLE.......................................................................................................... 4 4.3. TEMPERATURE CONTROL .......................................................................................... 5 4.4. ECONOMY CYCLE ..................................................................................................... 6 4.4.1. 4.4.2. 4.4.3. ECONOMY CYCLE ENABLE ENTHALPY .......................................................... 6 ECONOMY CYCLE ENABLE SENSIBLE TEMPERATURE ..................................... 7 ECONOMY CYCLE CONTROL .......................................................................... 8

4.5. SENSOR ALARMS ..................................................................................................... 9 4.6. COMFORT CONTROLLED AREAS............................................................................... 10 4.7. HEATING CONTROL ................................................................................................ 10 4.8. FAULT HANDLING .................................................................................................. 10 4.9. WATCH PAGES ...................................................................................................... 10 4.10. DATA LOGGING ..................................................................................................... 11 4.11. LEAD / LAG AND DUTY / STANDBY CHANGEOVER ..................................................... 12 5. APPROVED SOFTWARE AVAILABILITY ............................................................................. 13 6. APPLICATION RULES..................................................................................................... 14 7. REFERENCES ............................................................................................................... 14 7.1. 007338 ................................................................................................................. 14 7.2. OTHER INTERNAL .................................................................................................. 14 7.3. EXTERNAL ............................................................................................................. 14 8. DEFINITIONS ............................................................................................................... 14 9. ATTACHMENTS ............................................................................................................. 15 10. DOCUMENT CONTROL SHEET ........................................................................................ 16

TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) | ISSUED: 9 MAY. 2011 FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0

PAGE 2 OF 16

1.

PURPOSE
The Purpose of this document is to provide a framework for programmers of Innotech Direct Digital Controls (DDC) which details the minimum requirements for functions and concepts to be incorporated and how those functions are to be programmed in a standard manner.

2.

SCOPE
This document applies to all new Innotech DDC control strategies. Individual site and HVAC plant specific requirements may necessitate the addition of some functions such as lead / lag changeovers etc., however, the programming methodology, minimum required functions and standard look and feel should not require significant change. Retro upgrading of existing DDC programs should be considered at such times when this can be undertaken cost effectively. Note that in some cases existing older controls and system resources may not allow for full retro implementation. The document uses hyperlinks and colour.

3.

KEY STAKEHOLDERS
The following stakeholders (listed alphabetically) have reviewed and agreed to the content of this document before issue: NAME George Bakogianis Chris Baran-Kamp George Bradilovic Greg Dendle Pat Fitzgerald Allan Gontar Mark Kelly Anthony Price David Roach Ron Roberts Aurecon Silcar (O&M) Silcar (D&C) TITLE Senior Capacity Planner, Network Planning Studies, Telstra 007338 Technical Editor - Network & Facilities Mgmt, Telstra General Manager Network and Facilities Management, Telstra Senior Technology Specialist, Building Network Design, Telstra Strategic Facilities Mgmt, Network Services, Telstra National Energy Manager Telstra Property Snr Capacity Planner Network Standards & Compliance, Telstra Strategic Planning Manager, Network Group, Telstra Property Technology Team Manager Power, Telstra National Contract & Service Mgr, Network & IT Ops, Telstra (Represented by Paul Brown) (Represented by G. McIntyre) (Represented by G. Mullen)
Table 1: Key Stakeholders

PAGE 3 OF 16

TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) |ISSUED: 9 MAY. 2011 FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0

4.
4.1.

PROGRAMMING FUNCTIONAL REQUIREMENTS


GENERAL
For conceptual illustration, the control system described is based on a networkable Direct Digital Controller (DDC) serving a 4 stage HVAC system with Economy Cycle Cooling (ECC). This control strategy concept can be applied to other DDC systems and plant configurations. Where Economy Cycle Cooling is not employed, the description of mechanical cooling control is still applicable and can be adapted to systems incorporating fewer or greater than four cooling stages as described here. Some functions included for illustration (such as Fire and VESDA status inputs and alarms) may be applicable to specific projects or required by regulatory code or Telstra Standards on an individual installation basis. Where these functions are not required by specification they should be deleted from the final control strategy. Ensure all control strategies are compliant with Fire & VESDA standards C9-2 & E10-1. Note that all program blocks are to be discretely named and a printed copy of the as installed control program, block details and wiring diagram must be included in O&M manuals. Text blocks should be used to label programming functions and provide detail regarding any variation to standard such as inclusion of time delays etc.

4.2.

HVAC ENABLE
Generally, the Air-conditioning Unit will run continuously. A Master On/Off switch accessed via the front panel of the Controller (Watch page 1) can be used to stop the unit from running. An airflow switch in the supply air ductwork confirms the supply air fan status. Once the fan is requested and the status is confirmed as running, the automatic control functions are enabled (Control Enable). If the fan status is lost, the control functions are disabled. If the supply air fan is called to run and no fan status has been received by the duct mounted air-flow switch after a 60 second delay period, a Supply Air Fan fault will be displayed on the LCD of the Controller. This fault will be displayed as SAF Fault.

TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) | ISSUED: 9 MAY. 2011 FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0

PAGE 4 OF 16

Figure 1: HVAC Enable Logic Diagram

4.3.

TEMPERATURE CONTROL
If the automatic control functions are enabled, the controller responds to its discrete temperature sensor (or the averaged value or high signal select input as appropriate where multiple sensors are specified and installed) to maintain a target long term average room temperature of 250C. As the space temperature rises above a nominal 24.50C set-point, the four compressors will be cycled through a single Cooling PID loop with a nominal proportional band of 2.50C. For all cases Integral and Derivative values will both be 0% Individual Hysteresis blocks and values as below are provided for each cooling stage. With nominal set-point and proportional band values as above, the four compressors will be cycled in the following manner to maintain conditions i. ii. Compressor 1 On 25.1C (25% output) Off - 24.6C (5% Output) Compressor 2 On - 25.7C (50% Output) Off - 25.1 C (25% Output)

iii. Compressor 3 On - 26.3C (75% Output) Off - 25.7C (50% Output) iv. Compressor 4 On - 26.8C (95% Output) Off - 26.3C (75% Output)
(C4 on) (C3 on) (C4 off) (C2 on) (C3 off) OUTPUT (C1 on) (C2 off) (C1 off)

24.5C

25C

25.5C TEMPERATURE

26C

26.5C

27C

Figure 2: Temperature Control Compressor Cycling

Time delay blocks are not incorporated into the temperature controlled cooling sequence unless these are a necessary replacement for absent electrical / mechanical start delay or short cycle timers within the HVAC plant. For systems incorporating fewer or greater than 4 stages, the above staging schedule and proportional band should be amended as required to maintain an average long term temperature of 250C while maintaining the main control point values e.g. 2 stage cooling Compressor 1 on at 50% output and Off at 5% output, Compressor 2 On at 95% output and Off at 50% output. Limits are placed on the User Temperature Set-point so this cannot be adjusted below 24C or above 28C. For maintenance purposes a Unit Test Mode soft switch (User Variable) is provided via Watch Page 1, which operates the plant at a reduced control set-point between 18C and 22C (User adjustable) for a set time of 20 minutes.
PAGE 5 OF 16 TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) |ISSUED: 9 MAY. 2011 FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0

Figure 3: Temperature Control Logic Diagram

Figure 4: Temperature Control Test Logic Diagram

4.4.

ECONOMY CYCLE
(Where specified for inclusion) The Economy Cycle is enabled by an Enthalpy Comparator mode. If the Ambient Enthalpy is 1 KJ/Kg below the Return Air Enthalpy the economy cycle will be enabled to operate. If the Ambient Enthalpy rises to equal the Return Air Enthalpy then the Economy Cycle will be disabled. Where specified, a VESDA or Fire Alert will inhibit operation of the economy cycle. Further interlocks for the economy cycle to be enabled are as follows: Ambient Humidity Low Limit > 20% High Limit < 80% Ambient Temperature Low Limit >5C High Limit <25C These operating parameters are established through the use of Hysteresis blocks.

4.4.1. ECONOMY CYCLE ENABLE ENTHALPY

TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) | ISSUED: 9 MAY. 2011 FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0

PAGE 6 OF 16

Figure 5: Economy Cycle Enable (Enthalpy Comparison) Logic Diagram

4.4.2. ECONOMY CYCLE ENABLE SENSIBLE TEMPERATURE


(Where specified for inclusion) The Economy Cycle is enabled by a Temperature comparison mode. When the ambient temperature is a minimum 1C below return air or conditioned space temperature the economy cycle will be enabled to operate. If the ambient temperature rises to equal the return air or conditioned space temperature then the Economy Cycle will be disabled. No Relative Humidity sensing or limits are included in a sensible temperature enabled Economy Cycle system. Further interlocks for the economy cycle to be enabled are as follows: Ambient Temperature Low Limit >5C High Limit <18C (to a maximum of 23 C in some nominated colder climates) These operating parameters are established through the use of Hysteresis blocks.

PAGE 7 OF 16

TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) |ISSUED: 9 MAY. 2011 FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0

Figure 6: Economy Cycle Enable (Sensible Temperature) Logic Diagram

4.4.3. ECONOMY CYCLE CONTROL


(Enthalpy or Sensible temperature models) When enabled by the above conditions, the economy cycle is ready to be controlled. If the Return Air Temperature rises above a nominal set-point (named ECC Low Limit), of 20C the economy cycle dampers will modulate through a proportional band of 3C. That is, at a room temperature of 20C the ECC fresh air make-up and spill air dampers would have modulated to the fully closed position with the return air damper fully open. At 23C the ECC fresh air make up and spill air dampers would have modulated to the fully open position and return air dampers would be fully closed. Limits are placed on this Set-point (ECC Low Limit) so this cannot be adjusted below 18C or above 20C. The control strategy shall also include a Test Mode Function of 5 minutes duration operated via a soft switch grouped with other ECC functions. This test mode will operate all ECC dampers to their fully on position. An automatic timer function (ECC Damper maintenance) will operate all ECC dampers to their fully functioning positions each Monday from 2:00 am to 2:05 am. This is to reduce the incidence of dampers seizing after long periods of inactivity.

TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) | ISSUED: 9 MAY. 2011 FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0

PAGE 8 OF 16

Figure 7: Economy Cycle Control Logic Diagram

4.5.

SENSOR ALARMS
If any outside air sensor output is below 1% or above 85% of normal full scale output and if this condition is sustained for a continuous period of greater than 168 hours, a latched alarm within the DDC is to output the warning Check OA Sensor to the display panel. This latched alarm should not lock out the economy cycle as under some conditions e.g. prolonged rain periods, a false alarm might be generated. The purpose of this flag alarm is to alert maintenance operators that the outside air sensors should be checked for operation / accuracy. A soft switch alarm reset must be provided within the DDC.

Figure 8: Ambient Conditions Logic Diagram

PAGE 9 OF 16

TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) |ISSUED: 9 MAY. 2011 FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0

Figure 9: Ambient Sensor Fault Alarm Logic Diagram

4.6.

COMFORT CONTROLLED AREAS


(Offices, Lunch rooms etc.) Where controlled supply air dampers or stand alone HVAC plant are provided to office or other areas conditioned for human comfort only, then for each independently conditioned space, an On/Off user variable soft switch will be provided and HVAC will be enabled via individual discrete time control functions activating operation during normal business hours only (nominally 7:30 am 5:00 pm MonFri). A physical push button will be provided which enables cooling for a 1 hour period outside normal business hours. A separate independent cooling set point and PID block will be provided with a limited user input range of 23C to 28C. The controlled dampers or mechanical cooling will modulate though a 1 deg proportional band.

4.7.

HEATING CONTROL
In limited cases where heating is provided for human comfort in office spaces etc. for each independent conditioned space, a Heating Enable on/off user variable soft switch will also be incorporated. Heating will be controlled via a discrete time control block activating the heating function during normal business hours only (nominally 7:30 am 5:00 pm Mon Fri). A separate independent heating PID block will be enabled after confirmation of Supply Air Fan Status (Control enable). The user input set-point range will be limited to 18C to 22C. Note that this provides a minimum 1C difference between the maximum heating and minimum cooling independent set-points to avoid heat/cool conflicts.

4.8.

FAULT HANDLING
System faults within the DDC should be logged and display if in alarm but should not latch (with the exception described under Economy Cycle). DDC configurations should inhibit the running of any component in fault condition but automatically reset when a fault clears without requiring a hard reset. This does not apply to hardware faults such as HP/LP and motor contactor overloads etc. Treatment of these faults should be specified elsewhere.

4.9.

WATCH PAGES
The following system data is displayed via the DDC watch pages. Any repetitive display is deliberate in order to maintain logical grouping of data. Flash page and Watch page 1 are mandatory but some additions or deletions to subsequent pages may be necessary dependant on the program configuration. The assignment of all data should follow a logical grouping. Where a watch page is left totally blank through deletions then all subsequent watch pages move up 1 designation. Typical Layout Flash Page Control Enable Status Supply Fan Status Return Air or Room Temp (Controlling temperature point)

TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) | ISSUED: 9 MAY. 2011 FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0

PAGE 10 OF 16

Cooling Demand % Economy Cycle Demand % (For ECC installed systems only) Page 1 Master (Unit) On / Off switch ( User variable) Test Mode Set-point ( User variable) Test Mode On/Off (Cooling Test mode User Variable) Return Air or Room Temp (Controlling temperature point) Cooling Set Point (User variable) Page 2 Cooling Demand % Compressor or Cooling Stage 1 enable Status Compressor or Cooling Stage 2 enable Status Compressor or Cooling Stage 3 enable Status Compressor or Cooling Stage 4 enable Status Page 3 Outside Air Temp (For all ECC installed systems only) Outside Air Humidity (For Enthalpy ECC installed systems only) Outside Air Sensor Alarm reset (For all ECC installed systems only) Return or Room Air Temp (Controlling temperature point) Return or Room Air Humidity (Controlling RH point) (For Enthalpy ECC installed systems only) Page 4 Economy Cycle Enabled Status (For all ECC installed systems only) Outside Air Enthalpy or Temperature (specific to the type of ECC installed) Return Air Enthalpy or Temperature (specific to the type of ECC installed) Economy Test On/Off (For all ECC installed systems only) Economy Cycle Low Limit (User Variable) (For all ECC installed systems only) Subsequent Watch Pages All other data points specific to the installation

4.10. DATA LOGGING


All available points should be logged and grouped together on a common program page. This necessitates that each logged point be assigned and individual label. If system resources are limited, the following points are to be logged as a minimum Supply Fan Fault.
PAGE 11 OF 16 TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) |ISSUED: 9 MAY. 2011 FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0

Return Air and or Room Air Temperature/s. (all sensor points and averaged or high select values as specific to the installation) Return Air and or Room Air Humidity (For Economy Cycle installations) Cooling Set-point. Unit Test Mode function Heating Set-point if heating is provided Return Air Enthalpy. (For Enthalpy Economy Cycle installations) Ambient Air Temperature. (For all Economy Cycle installations) Ambient Air Relative Humidity. (For Enthalpy Economy Cycle installations) Ambient Enthalpy. (For Enthalpy Economy Cycle installations) Economy Damper Actuators. (For all Economy Cycle installations) All Cooling Stages Economy Cycle Test Mode function (For all Economy Cycle installations) Other points specific to a particular configuration such as VESDA Alert, Fire Alarm shut down, Standby Generator status etc. where these are specified to form an integral part of a control strategy

Figure 10: Typical Data Logging Layout (for illustration only - not all required points included)

4.11. LEAD / LAG AND DUTY / STANDBY CHANGEOVER


Where lead/lag and duty/standby changeover is required, this should be achieved through a calendar block and counter function with an automatic reset and user manual advance.

TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) | ISSUED: 9 MAY. 2011 FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0

PAGE 12 OF 16

Figure 11: Lead / Lag and Duty / Standby Changeover Logic Diagram

5.

APPROVED SOFTWARE AVAILABILITY


Software and HVAC control strategy programming is available from Innotech Control Systems Global Headquarters and Manufacturing Innotech Control Systems - Brisbane Office Address: Brisbane Technology Park, 6 McKechnie Drive Eight Mile Plains, QLD, 4113, Australia Postal Address: PO Box 292 Sunnybank, QLD, 4109, Australia Phone: +61 7 3841 1388 Fax: +61 7 3841 1644 Office Hours: 7:30 AM - 5:00 PM (EST) Monday - Friday E-Mail: sales@innotech.com.au Web: www.innotech.com.au

PAGE 13 OF 16

TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) |ISSUED: 9 MAY. 2011 FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0

6.

APPLICATION RULES
The control strategy and functions described are applicable to Innotech Maxim and Genesis series direct digital controllers. Individual site and HVAC plant specific requirements may necessitate the addition of some functions such as Supply Air Fan damper control, Toilet Exhaust Fan control or load shedding of some mechanical cooling capacity during Emergency Power Plant operation etc. However, the programming methodology, minimum required functions and standard look and feel should not require significant change. This document applies to all Telstra sites where any HVAC plant is controlled by an Innotech DDC. This does not apply to small individual modular HVAC plant such as IVTRES or Emerson TEX plant which is delivered and installed with an integrated pre programmed Innotech DDC.

7.

REFERENCES
DOCUMENT NUMBER TITLE C3-1 C3-3 C3-4 C3-5 C9-2 E10-1 Network Building Environmental Standards Air Conditioning Services Environmental Controls Economy Cycle Provision of Fire Detection & Alarm Systems and Portable Fire Extinguishers Multi-Point Aspirated Smoke Detection Systems for Network Sites

7.1. 007338

7.2. OTHER INTERNAL


DOCUMENT NUMBER TITLE Nil

7.3. EXTERNAL
DOCUMENT NUMBER TITLE Nil

8.

DEFINITIONS
TERM DDC DEFINITION Direct Digital Controller

TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) | ISSUED: 9 MAY. 2011 FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0

PAGE 14 OF 16

TERM DUTY / STANDBY

DEFINITION Two or more HVAC plant controlled in such a manner that only the duty plant operates and the standby plant is called into operation if the duty plant fails. The plant designated as duty can be rotated on a time based schedule Economy Cycle Cooling. The introduction of up to 100% fresh air into the HVAC air distribution system when the outside air condition is suitable. Heating, Ventilation and Air Conditioning plant Two or more HVAC plant controlled in such a manner that if heat load cannot be satisfied by the primary Lead plant, then the cooling strategy will call the additional Lagging plant to operate in unison. The plant designated as leading can be rotated on a time schedule or fault condition basis. A group of data or controlled point status values viewed via an LCD front panel of the DDC

ECC

HVAC LEAD /LAG

WATCH PAGE

9.

ATTACHMENTS
DOCUMENT NUMBER TITLE Nil

PAGE 15 OF 16

TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) |ISSUED: 9 MAY. 2011 FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0

10. DOCUMENT CONTROL SHEET


Contact for Enquiries and Proposed Changes If you have any questions regarding this document contact: NAME: DESIGNATION: PHONE: EMAIL: MICHAEL WILLIAMS TECHNOLOGY SPECIALIST (03) 8647 5425 Michael.Williams.1@team.telstra.com

If you have a suggestion for improving this document, please contact the person listed above or complete the online Change Proposal Form at http://www.in.telstra.com.au/ism/007338/feedback.asp

ISSUE ISSUE DATE APPROVED NO. 1.0 May 9, 2011 Chris Baran-Kamp 007338 Technical Editor

NATURE OF AMENDMENT

TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) | ISSUED: 9 MAY. 2011 FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0

PAGE 16 OF 16

Das könnte Ihnen auch gefallen