FEEDER PROTECTION SySTEM Cost-effective protection and control for single/multiple distribution feeders
KEy BENEFITS
Cost effective and flexible protection and control device for distribution feeder applications Complete IEC 61850 Process Bus solution providing resource optimization and minimizing total P&C life cycle costs Improved system stability at reduced cost - Control schemes using hi-speed communications High-end fault and disturbance recording, including internal relay operating signals thus eliminating the need for redundant recording devices Robust network security enabling Critical Infrastructure Protection through user command logging, and dual permission access control Accurate built-in metering functions - Eliminates auxiliary metering devices and reduces cost Advanced automation capabilities for providing customized protection and control solutions Simplified system integration with communications supporting serial and Ethernet interfaces and multiple protocols Reduced relay to relay wiring and associated installation costs through high-speed inter-relay communications Embedded IEC61850 Protocol with no external communications hardware required Ambient temperature monitoring with alarming when outside temperature exceeds upper thresholds Busblocking/ interlocking schemes Throw over schemes (bus transfer scheme applications) Distributed Generation (DG) interconnect protection, including active and passive anti-islanding
Distribution Feeder Protection
APPLICATIONS
Primary protection and control for multiple distribution feeders Distribution load shedding schemes based on voltage and frequency elements
FEATURES
Protection and Control
Instantaneous and time phase overcurrent protection Instantaneous and time ground/neutral overcurrent protection Neutral and auxiliary overvoltage Phase and auxiliary undervoltage Under frequency Four-shot automatic reclosers for up to six breakers Built-in selector switch
Communications
Networking interfaces 100Mbit Fiber Optic Ethernet, RS485, RS232, RS422, G.703, IEEE C37.94 Multiple Protocols - IEC61850, DNP 3.0 Level 2, Modbus RTU, Modbus TCP/IP, IEC60870-5-104, Ethernet Global Data (EGD) Direct I/O secure, high-speed exchange of data between URs for Direct Transfer Trip applications Embedded Managed Ethernet Switch with 4 - 100 Mbit Fiber optic ports and 2 copper ports
EnerVista Software
Graphical Logic Designer and Logic Monitor to simplify designing and testing procedures Document and software archiving toolset to ensure reference material and device utilities are up-to-date EnerVista Integrator providing easy integration of data in the F35 into new or existing monitoring and control systems
309
The F35 is the single point for protection, control, metering, and monitoring in one integrated device that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint Monitoring as shown.
Pickup current level for trip, alarm, or control Choice of 17 curve shapes (including FlexCurves) and curve multipliers Instantaneous or linear reset time characteristic to coordinate with upstream transformer damage curves and downstream reclosers and fuses. Voltage restraint to increase sensitivity The majority of distribution systems are either solidly grounded or through a low impedance. Fast fault clearance is required due to the ground fault impact. Following functions are incorporated in F35 to provide ground protection:
Overcurrent Protection
The F35 has built-in standard IEEE, IEC, IAC and FlexCurves overcurrent characteristics (TOC), most commonly used for primary and back up protection in various protective zones. The F35 has phase IOC elements with level detectors for each phase. Each TOC element has the following programmable characteristics:
Monitoring
79
CLOSE TRIP
50P
2
51P
1
50N
2
51N
1
For Breaker 1
27X
27P
2
81U
6
59N
59X
FUNCTION Phase Undervoltage 27X Auxiliary Undervoltage 27P Phase Undervoltage 50G Ground Undervoltage 27X AuxiliaryInstantaneous Overcurrent 50N Neutral Instantaneous Overcurrent 50G (up to 12) Ground Instantaneous Overcurrent 50N (up to 12) NeutralInstantaneous Overcurrent 50P Phase Instantaneous Overcurrent 50P (up to 12) Phase Instantaneous Overcurrent 51G Ground Time Overcurrent 51G (up to 6) Ground Time Overcurrent 51N Neutral Time Overcurrent 51N (up to 6) Neutral Time Overcurrent 51P (up to 6) Phase Time Overcurrent 51P Phase Time Overcurrent 52 AC Circuit Breaker 52 AC Circuit Breaker 59N Neutral Overvoltage 59N Neutral Overvoltage 59X Auxiliary Overvoltage 59X Auxiliary Overvoltage 79 (up to 6) Autoreclose 79 Automatic Recloser 81 (up to 6) Underfrequency 81 Underfrequency
Device Number
Function
50G
2
51G
1
METERING
Transducer Inputs
FlexElement
TM
F35
310
www.GEDigitalEnergy.com
Communicates using open standard IEC 61850 messaging Drastically reduces P&C design, installation and testing labor by eliminating individual copper terminations Integrates with existing F35s by replacing traditional CT/VT inputs with IEC 61850 Process Bus module Does not introduce new Cyber Security concerns Visit the HardFiber System product page on the GE Multilin web site for more details.
Autorecloser
Up to 6 programmable breaker autoreclosers for a variety of reclosing practices are provided. These elements are intended for use with distribution lines in tripping schemes for single breaker applications. Up to four selectable reclosers shots are possible prior to locking out.
Advanced Automation
The F35 incorporates advanced automation features including powerful FlexLogic programmable logic, communication, and SCADA capabilities that far surpass what is found in the average line relay. The F35 integrates seamlessly with other UR relays for complete system protection, including the unit and auxiliary transformers, and Balance of Plant protection.
FlexLogic
FlexLogic is the powerful UR-platform programming logic engine that provides the ability of creating customized protection and control schemes thereby minimizing the need, and the associated costs, of auxiliary components and wiring. Using FlexLogic, the F35 can be programmed to provide required tripping logic along with custom scheme logic for line phase comparison (including interlocking with external synchronizers), transfer tripping schemes for remote breakers and dynamic setting group changes.
Source CB1
Fault 1 CB2
Scalable Hardware
The F35 is available with a multitude of I/O configurations to suit the most demanding application needs. The expandable modular design allows for easy configuration and future upgrades. Multiple CT/VT configurations allow for implementation of many differential schemes, including concurrent splitphase and differential protection Up to 80 digital inputs and up to 56
CB3
Fault 2
Reverse zone interlocking protection - By using the IEC61850 GOOSE or hi-speed Direct I/O capability blocking signals can be transferred upstream, allowing minimal coordination delays. Fast clearance can be provided for Fault 1 and still maintain coordination for Fault 2.
www.GEDigitalEnergy.com
311
FlexLogicTM Designer
FlexLogic allows for customizing the F35 to operate and control the breakers and other auxiliary devices needed to fit most protection schemes and applications.
Communications
The F35 provides advanced communications technologies for remote data and engineering access, making it the easiest and most flexible feeder protection relay to use and integrate into new and existing infrastructures. Direct support for fiber optic Ethernet provides high-bandwidth communications allowing for low-latency controls and high-speed file transfers of relay fault and event record information. The available redundant Ethernet option and the embedded managed Ethernet switch provide the means of creating fault tolerant communication architectures in an easy, cost-effective manner without the need for intermediary communication hardware. The F35 supports the most popular industry standard protocols enabling easy, direct integration into DCS and SCADA systems. IEC61850 DNP3.0 Ethernet Global Data (EGD) IEC6870-5-104 Modbus RTU, Modbus TCP/IP
digital outputs are available Types of digital outputs include triprated Form-A and Solid State Relay (SSR) mechanically latching, and Form-C outputs Form-A and SSR outputs available with optional circuit continuity monitoring and current detection to verify proper operation of the connected primary equipment Mechanically latching outputs can be used to develop secure interlocking applications and replace electromechanical lockout relays RTDs and DCmA inputs are available to monitor equipment parameters such as temperature & pressure
312
www.GEDigitalEnergy.com
Communication with up to 16 UR relays in single or redundant rings rather than simplistic point-to-point configurations Connect to standard DS0 channel banks through standard RS422, G.703 or IEEE C37.94 interfaces or via direct fiber optic connections Built-in continuous loop and channel monitoring provides real-time diagnostics of your communication channels no external or handheld tester required
EnerVista Launchpad
EnerVista Launchpad is a powerful software package that provides users with all of the setup and support tools needed for configuring and maintaining GE Multilin products. The setup software within
Multi-Language
The F35 supports English, French, Russian, and Chinese languages on the front panel,
Analyze feeder faults using both analog and digital power system quantities that are measured and recorded up to a rate of 64 samples per cycle.
Record the operation of the internal F35 elements and external connected devices with 1ms time-stamped accuracy to identify the Sequence of Operation of station devices during feeder faults and disturbances.
www.GEDigitalEnergy.com
313
multiplexer channel bank. Regardless of the connection method, Direct I/O provides continuous real-time channel monitoring that supplies diagnostics information on channel health. Direct I/O provides superior relay-to-relay communications that can be used in advanced interlocking, generation rejection and other special protection schemes.
EnerVista setup software, and product manual. Easily switch between English and an additional language on the local displays without uploading new firmware.
EnerVistaTM Software
The EnerVista Suite is an industry-leading set of software programs that simplifies every aspect of using the F35 relay. The EnerVista suite provides all the tools to monitor the status of feeders, maintain the relay, and integrate information measured by the F35 into DCS or SCADA monitoring systems. Convenient COMTRADE and Sequence of Events viewers are an integral part of the UR Setup software included with every UR relay, to carry out postmortem event analysis to ensure proper protection system operation.
Launchpad allows configuring devices in real-time by communicating using serial, Ethernet, or modem connections, or offline by creating setting files to be sent to devices at a later time. Included in Launchpad is a document archiving and management system that ensures critical documentation is up-to-date and available when needed. Documents made available include: Manuals Application Notes Guideform Specifications Brochures Wiring Diagrams FAQs Service Bulletins
complete HMI package with the following functionality: Plug-&-Play Device Monitoring System Single-Line Monitoring & Control Annunciator Alarm Screens Trending Reports Automatic Event Retrieval Automatic Waveform Retrieval
Viewpoint Maintenance
Viewpoint Maintenance provides tools that will create reports on the operating status of the relay, simplify the steps to download fault and event data, and reduce the work required for cyber-security compliance audits. Tools available in Viewpoint Maintenance include: Settings Security Audit Report Device Health Report Single Click Fault Data Retrieval
Viewpoint Engineer
Viewpoint Engineer is a set of powerful tools that will allow you to configure and test UR relays at a system level in an easy-to-use graphical drag-and-drop environment . Viewpoint Engineer provides the following configuration and commissioning utilities: Graphical Logic Designer Graphical System Designer Graphical Logic Monitor Graphical System Monitor
EnerVista Integrator
EnerVista Integrator is a toolkit that allows seamless integration of GE Multilin devices into new or existing automation systems. Included in EnerVista Integrator is: OPC/DDE Server GE Multilin Drivers Automatic Event Retrieval Automatic Waveform Retrieval
Viewpoint Monitoring
Viewpoint Monitoring is a simple-to-use and full-featured monitoring and data recording software package for small systems. Viewpoint Monitoring provides a
User Interface
The F35 front panel provides extensive local HMI capabilities. The local display is used for monitoring, status messaging, fault diagnosis, and device configuration. User configurable messages that combine text with live data, can be displayed when user-defined conditions are met. LED Indicators
314
www.GEDigitalEnergy.com
Typical Wiring
P1
I V I V I V I V V I V I V I V V I V I V I V
IA5 IA IA1 IB5 IB IB1 IC5 IC IC1 IG5 IG IG1 IA5 IA IA1 IB5 IB IB1 IC5
6G
F1a
P2
P3
P4
P8b
F35
H1
6G
H2
H3
H4
M2b
IB
SURGE
M4c IG1
6G
M6b
IB
W2
W3
W4
U2a IB5
SURGE
U2b
IB IB1
U2c
U3c
U4a U4b U4c
U8a U8c
832767A5.CDR
X
6
V
8
R
6
N
8
M
CT
J
6
G
8 CT
D
9 CPU
B
1 Power Supply
VA VA VB VB VC VC
Inputs/ outputs
Inputs/ outputs
www.GEDigitalEnergy.com
IC
H1a H1b H1c H2a H2b H2c H3a H3b H3c H4a H4b H4c H5a H5c H6a H6c H5b
UR TXD RXD
COMPUTER
SGND
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
CONNECTOR
CONNECTOR
W1a W1b W1c W2a W2b W2c W3a W3b W3c W4a W4b W4c W5a W5c W6a W6c W5b
B1b B1a B2b B3a B3b B5b B6b B6a B8a B8b
10BaseFL
DC
Tx1 Tx2
Rx1
Fibre * Optic
10BaseFL
Rx2
10BaseT
BNC BNC
Minimum
PROVIDED
F35-H00-HCH-F8H-H6G-M8H-P6G-U8F-W6G
315
P1a P1b P1c P2a P2b P2c P3a P3b P3c P4a P4b P4c P5a P5c P6a P6c P5b
TC 1
TC 2
Ordering
Base Unit CPU
00 03
User Interface
Transducer I/O
Inter-Relay Communications
K L M N Q T U V F H H L 8F 8F 8F 8G 8G 8G 8H 8H 8H 8J 8J 8J 8L 8L 8L 8M 8M 8M 8N 8N 8N 8R 8R 8R 81 XX XX XX XX 4A 4A 4A 4A 4C 4C 4C 4C 4D 4D 4D 4D 4L 4L 4L 4L 67 67 67 67 6C 6C 6C 6C 6D 6D 6D 6D 6E 6E 6E 6E 6F 6F 6F 6F 6K 6K 6K 6K 6L 6L 6L 6L 6M 6M 6M 6M 6N 6N 6N 6N 6P 6P 6P 6P 6R 6R 6R 6R 6S 6S 6S 6S 6T 6T 6T 6T 6U 6U 6U 6U 6V 6V 6V 6V 5A 5A 5A 5A 5C 5C 5C 5C 5D 5D 5D 5D 5E 5E 5E 5E 5F 5F 5F 5F
H A V B
RH
XX 4A 4C 4D 4L 67 6C 6D 6E 6F 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 5A 5C 5D 5E 5F 7A 7B 7C 7H 7I 7J 7S 7T 7W 76 77 2S 2T
Base Unit RS485 + RS485 (IEC61850 option not available) RS485 + Multi-mode ST 10BaseF RS485 + Mutli-mode ST Redundant 10BaseF RS485 + Multi-mode ST 100BaseFX RS485 + Multi-mode ST Redundant 100BaseFX RS485 + 10/100 BaseT RS485 + 6 port, 100 Mbps, Managed Ethernet Switch No Software Options IEC61850 Horizontal (19" rack) - Standard Horizontal (19" rack) - Harsh Chemical Environment Option Vertical (3/4 size) - Standard Vertical (3/4 size) - Harsh Chemical Environment Option Enhanced English Front Panel Enhanced English Front Panel with User-Programmable Pushbuttons Enhanced French Front Panel Enhanced French Front Panel with User-Programmable Pushbuttons Enhanced Russian Front Panel Enhanced Russian Front Panel with User-Programmable Pushbuttons Enhanced Chinese Front Panel Enhanced Chinese Front Panel with User-Programmable Pushbuttons Vertical Front Panel with English display 125 / 250 V AC/DC 125/250 V AC/DC with redundant 125/250 V AC/DC power supply 24 - 48 V (DC only) Standard 4CT/4VT Sensitive Ground 4CT/4VT Standard 8CT Sensitive Ground 8CT Standard 4CT/4VT w/ enhanced diagnostics Sensitive Ground 4CT/4VT w/ enhanced diagnostics Standard 8CT w/ enhanced diagnostics Sensitive Ground 8CT w/ enhanced diagnostics 8 Port IEC 61850 Process Bus Module No Module 4 Solid State (No Monitoring) MOSFET Outputs 4 Solid State (Current w/opt Voltage) MOSFET Outputs 16 Digital Inputs with Auto-Burnish 14 Form-A (No Monitoring) Latchable Outputs 8 Form-A (No Monitoring) Outputs 8 Form-C Outputs 16 Digital Inputs 4 Form-C Outputs, 8 Digital Inputs 8 Fast Form-C Outputs 4 Form-C & 4 Fast Form-C Outputs 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs 2 Form-A (Cur w/ opt Volt) 1 Form-C Output, 2 Latching Outputs, 8 Digital Inputs 4 dcmA Inputs, 4 dcmA Outputs 8 RTD Inputs 4 RTD Inputs, 4 dcmA Outputs 4 dcmA Inputs, 4 RTD Inputs 8 dcmA Inputs 820 nm, multi-mode, LED, 1 Channel 1300 nm, multi-mode, LED, 1 Channel 1300 nm, single-mode, ELED, 1 Channel 820 nm, multi-mode, LED, 2 Channels 1300 nm, multi-mode, LED, 2 Channels 1300 nm, single-mode, ELED, 2 Channels G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels IEEE C37.94, 820 nm, multimode, LED, 1 Channel IEEE C37.94, 820 nm, multimode, LED, 2 Channel 6 port, 100 Mbps, Managed Ethernet Switch, HI (125/250V AC/DC) 6 port, 100 Mbps, Managed Ethernet Switch, LO (24-48 Vdc)
Ordering Note: To view the latest options available for the F35, or to order the UR Classic Front Panel, please visit our online store for more details.
316
www.GEDigitalEnergy.com