Sie sind auf Seite 1von 48

University of Sydney

School of Electrical and Information Engineering

Dr Keith Mitchell

ELEC 5205 - High Voltage Engineering

ELEC 5205 - High Voltage Engineering


3. Switchgear

Types of Power System Switchgear


Only fuses and circuit breakers are designed to interrupt shortcircuit currents
Source: ref 2

CT and VT Connection
Source

To load

Circuit Breaker and Relay Wiring Schematic (1 of 3 phases)

Source: Ref 1

Power System Protection Relays

Power system protection relays accept signals representing the fault current and voltages (derived from measuring transducers known as current and voltage transformers) and then analyse these signals and send a trip signal to a circuit breaker if an abnormal condition is detected. The main types of relays are (for short-circuits): Over current Distance (impedance) Unit (differential)

Other relay types are Thermal, over and undervolts, Buchholz, negve sequence, etc

Protection Relays and Circuit Breakers

Upon detection of a fault, protection relays provide the trip signals for the circuit breakers. These are switching devices designed to be able to carry and interrupt safely the often very high currents, which flow during faults. Modern high capacity circuit breakers are capable of interrupting currents of up to 60 000 amps at a nominal voltage of 750kV within 40 milliseconds. The purpose of the circuit breakers is To disconnect the faulty element or circuit, leaving the rest of the power system intact To prevent other healthy equipment from being damaged by the fault currents they must carry. To reduce damage at the point of fault, important because the less damage caused by the fault the greater the probability of successful repair.

Circuit Breaker Ratings

Rated load current the normal load current it can carry indefinitely without thermal damage Rated voltage the rated voltage it can withstand indefinitely without insulation breakdown Breaking current the short circuit current it can safely interrupt without damage Making current the maximum short-circuity it can close onto (assuming an upstream device can interrupt the current) Eg 630A, 11000 volts, 21 kA Load current Rated voltage Breaking current

Steady-State or Asymmetric Current?

Transmission system protection is designed to clear faults very quickly (sub-second), so asymmetric current is relevant Distribution system protection is often much slower and transients have usually decayed away - so steady state may be more applicable.

Fully Offset Fault Current

Calculation of Fully Offset Fault Current

Source: ref 2

ShortCircuit Equiv Cct


Source: ref 4 The total source and line R and L will determine the DC transient time constant = Ltot/Rtot

CB Symmetrical Interrupting Capability

For CBs < 120 kV, a proportionally higher breaking capacity may be possible at reduced voltages (K factor)

Circuit Breaker Fault Clearance

Circuit Breaker Fault Clearance .. 2

Current Choppin g

Circuit Breaker Types


OIL AIR Air-Blast SF6

VACUUM

Oil is vaporised and gas extinguishes arc Old technology maintenance intensive Explosion and fire risk Arc shute designed to lengthen arc and extinguish Used for LV <1100V High pressure air extinguishes arc Used for HV AC and DC Low maintenance. Soft switching Gas disposal issue Maintenance free. Suitable for MV < 36kV Hard switching voltage transients Cant monitor vacuum condition

330 kV Switchgear - TransGrid Liverpool 330/132kV Substation


330kV busbars 330kV CTs 330kV Air-Blast CBs

132 kV Switchgear Energy Aust 132kV Substation


132 kV low oil volume CBs The author in front gives an idea of size at these sorts of voltages.

HV, MV and LV CBs


Voltage very much dictates size and type of circuit breaker Low Voltage >120 V and < 1.1 kV AC Encased, Air CBs are the main type Medium Voltage > 1.1 kV and < 52 kV Vacuum (<36 kV) and SF6 main types. Many designs are indoor High Voltage > 52 kV SF6 the main design. SF6 GIS switchgear up to 400 kV now available for indoor applications Oil, low volume oil, and air-blast older types for high voltage.

Typical CB Ratings

120 kV Load 800-2000 A; S/C 12.5-40 kA 300 kV Load 1250-3150 A; S/C 16-50 kA 800 kV Load 2000-4000 A; S/C 40 kA

Oil CBs

SF6 CB Operation
Source: ref 4 Arc quenching process in a puffer type SF6 CB

SF6 Dielectric Properties


Source: ref 4 SF6 is a heavy largely inert gas and has superior dielectric and arc quenching properties compared to air and oil. Most SF6 switchgear operates at a pressure of about 5-6 bars.

Air-Blast CBs

Source: Ref 4

LV Air CBs

Source: Ref 4

LV Magnetic Arc Extinction

Source: Ref 4

Vacuum CBs
Becoming very popular for voltages up to about 15 kV (eg motor contactors). Basically maintenancefree. Issues with hard arc extinction (current chopping) and

Indoor or Outdoor?

Originally, most switchgear, right down to 11 kV, was placed outdoors, designed for use with aerial busbars, for both technical and cost reasons, especially at high voltages. The advent of SF6 gas insulation has enabled the use of switchgear to 400 kV indoors. Inner city substations use indoor gear for aesthetic and space-saving reasons. Indoor subs may cause earthing design problems - why?

Outdoor CBs

Source: ref 4

HV GIS Switchgear
Source: ref 4. A 440 kV packaged substation. The CBs are in the front and busbars at the rear. An incoming circuit is on the top right.

Other CB Design Issues

Insulation level - set by system BIL Transient voltage withstand - 3 phase CBs do not open all 3 poles precisely at the same instant - over-voltages of ~1.5 times on other phases may occur.

CB Maintenance

Traditional CB maintenance has been based on duty cycles - so many switching operations, so many fault clearing operations, etc. Normally minor maintenance interwoven with major maintenance. The latter involving complete stripping down of gear, and replacement of contacts. Newer concepts based on condition monitoring.

Condition Monitoring

Refers to the actual amount of wear and tear a CB has experienced, and using this to determine the timing and nature of next CB maintenance. Uses sensors and microprocessors to log actual operational behaviour. Vibration analysis to monitor wear of CB contacts and operation mechanisms Oil analysis to determine amount of carbonisation caused by arcing, etc.

Switchgear Testing

Manufacturers tests - R & D testing, type testing Commissioning tests - voltage pressure tests, tripping/closing tests, dielectric tests, etc Routine maintenance tripping tests.

Substation Layouts Full Mesh


Source: ref 4. Used on HV transmission substations where deliberate redundancy in current paths ensures maximum reliability.

Substation Layouts Breaker and Half

Substation Layouts Simple Single Bus


NB: The Xs are CBs and the switches are isolators.

Source: ref 4. A design for a simple 132 kV sub with one incoming 132 kV feeder and 2 transformer CBs and isolators, and switchroom with the lower voltage side switchgear being indoor. Note the denser earth grid under the switchroom. The earth grid must keep voltage rise due to fault current inflow to acceptable levels.

HV Switchyard & Earth Grid Layout

Earth Grid Resistance

Earth Ground Rod Resistance

Source: ref 4 The earth grid resistance will be specified in the substation design (usually < 0.5 ohm). Actual grid resistance tests are done as part of the commissioning tests of a new substation, by direct current injection.

Step and Touch Potentials

Allowable Human Body Currents

Electrocution is caused by currents flowing through a body and interfering with the operation of key organs eg lungs, heart Body resistance varies with voltage and dryness Up to 900 mA acceptable for very short (<0.05 sec) periods; only 80 mA at 1 second and <50 mA continuous

Allowable Touch Potentials

Source: ref 4. For example, for a 1-second fault duration, touch potential should be 60 volts, or less.

Typical Computer Model of Step & Touch Potentials

Source: ref 4.

Switchyard Spacings

Source: ref 4.

IEC Phase Clearances

Source: ref 4.

IEC Safe Working Distances

Source: ref 4.

Das könnte Ihnen auch gefallen