Home Subscribe eNewsletters Subscription Customer Service Online Web Features Webinars Podcasts ES-TV Videos Blog Products White Papers Boiler Microsite Current Issue Cover Story Features Columns Case In Point Issues and Events Departments Letters to the Editor Green Intelligent Buildings Supplement ES Glossary Calendar of Events HVAC Challenge HVAC Designer Tips The Facility Files Product Info (Free) Resources Ad Index Archives Digital Edition Archives Career Center Back2Basics Mechanical Products Sourcebook Industry Links Market Research PennWell Books ES Info

Search in:

Editorial

Products

Companies

Engineered Systems

The Myth About Fan Static Pressure


by Dr. Alex London, P.E. March 26, 2006

ARTICLE TOOLS

Email

The message is possibly controversial, yet quite simple: Selection is all about fan total pressure. The article is a bit more complex, with discussion of what the author sees as confused logic, accompanied by multiple illustrations to back up his premise. Take a look for yourself when it comes to proper selection methodology, the pressure is on.

The selection of a proper fan for a vent system must pursue the proper basis. This is an essential element in the engineering design phase of a vent system. However, many controversial articles in engineering journals and other literature consider contradictive bases for selection1 through 6. Those articles notwithstanding, the natural laws of aerodynamics have strict requirements that do not allow contradictions.

This article presents graphical illustrations as the clearest demonstration of the fan selection procedure, with system and fan curves, air capacity and pressure, and energy consumption.

GRAPHICAL ILLUSTRATIONS OF AERODYNAMIC COMPONENTS IN A VENT SYSTEM

Fan and air ducts together with their associated parts comprise a vent system Enlarge this picture

illustrate the relationship of all existing pressures in the working system, whe Ft fan total pressure - system total resistance Fvpo fan outlet velocity pressure Fvpi fan inlet velocity pressure

FIGURE 1A. Illustration of pressure values in the working vent system.

Fs - fan static pressure SPs - system total static pressure TPi and TPo inlet and outlet system tota and SPo inlet and outlet system static pressure at a point VPi and VPo velocity pressure at a point

CONFUSION A great deal of confusion exists in engineering literature regarding the use of static pressure. The difference in terminology and nature of the SPs and Fs is clearly illustrated in Figures 1 and 1a. SPs = SPo-SPi7,9 Fs = Ft Fvpo9,10 Since neither SPs nor Fs represent the amount of energy which must be imparted to the system by the properly selected fan, these two values are absolutely irrelevant as a basis for the fan selection.

http://www.esmagazine.com/Articles/Feature_Article/87328157de43a010VgnVCM100000f93... 3/9/2010

The Myth About Fan Static Pressure - Feature Article - Engineered Systems

2 4

Today's Boiler Advertising The ASHRAE handbook states that Fan total pressure is a true indication of Enlarge this picture the energy imparted to the air stream by the fan An energy loss in a duct system can be defined only as a total pressure loss By using total pressure for both fan selection and air distribution system design, the design engineer is assured that he is using the correct fundamentals. These fundamentals will apply equally well to both high and low velocity systems.7

However, there is apparent contradiction even in the ASHRAE handbook, such as: where the fan total pressure is known, use: Ps = Pt - Pv,o.8 Now, the following questions must be solved:

to air flow is noted by total pressure To obtain the fan static pressure requirem
FIGURE 3. Vent system curves of the different fans.

Why is this the requirement to obtain fan static pressure? Why is it necessary to calculate the fan static pressure if the fan total pressure is already known? And especially when the total pressure is ... the correct fundamental[s].7

As described in the ASHRAE handbook, the following is a procedure for the fan selection8: Determine air capacity and fan total pressure as a result of the vent system calculation. Select a fan by means of the air capacity only. Calculate the selected fans outlet velocity Vo. Calculate Fvpo. Calculate Fs = Ft Fvpo. Make final fan selection on the basis of the cfm and the Fs.

This fan selection process evaluation can be better demonstrated through the use of an illustrative example, where two different sizes of fans are selected for the same 3,000 cfm at Fs = 1 in. wg (Tables 1 and 2). In the first case, a designer selects fan size of 20 PLR. In the second case, a contractor selects the least expensive fan size of 12 PLR (Table 2). In both instances, it appears that both fans have the same cfm and Fs, however, there is a noticeable difference in Ft pressure between the two options. Figure 2 is provided to illustrate the results: Fan 20 PLR, 3,000 cfm at Fs =1 in. wg; 1,000 rpm:

Parabola 0-1-3 is the characteristic of the designed or existing vent system with 3,000 cfm at Fs1 = line 1 Parabola 0-1c is the characteristic of the fan outlet velocity pressure Fvpo1 = line 1b-1c = 0.1 in. wg. Fan 12 PLR, 3,000 cfm at Fs=1 in. wg; 3,200 rpm: Parabola 0-2 is the characteristic of the imaginary vent system with 3,000 cfm at Fs2 = line 2 Parabola 0-2b-3c is the characteristic of Fvpo2 = line 2b-1b = 0.8 in. wg. Fan 12 PLR, 3,400 cfm at Fs=1 in. wg; 3,200 rpm: Parabola 0-1-3 is the characteristic of the designed vent system with 3,400 cfm at Fs3= line 3 Parabola 0-2b-3c is the characteristic of Fvpo3 = line 3c-3b = 1 in. Wg

http://www.esmagazine.com/Articles/Feature_Article/87328157de43a010VgnVCM100000f93... 3/9/2010

The Myth About Fan Static Pressure - Feature Article - Engineered Systems

3 4

Key Point 1. Table 1, Table 2, and Figure 2 expose an error, which occurs whe Enlarge this picture
TABLE 2. The NYB catalog data for fan 12 PLR. (Table courtesy of New York Blower Co., Bulletin 051.)

fans 20 PLR and 12 PLR with the same Fs (1 in. wg) have different Ft. The fan vent system comes to 3,400 cfm at Ft = 1.7 in. wg and Fs = 0.7 in. wg.

in. wg and Fan-12 PLR has Ft = 1.8 in. wg. As a result, the real capacity of th

Table 3 lists fans, which were selected from fan manufacturers data, for an at 1 in. wg Fs (Point a).

Figure 3 shows that each of the selected fans has a different curve for its particular individual system as com

vent system. The parabola 0-a, is the imaginary characteristic line of the designed vent system with 3,000 c

Key Point 2. The artificially determined value of Fs, while neglecting the Fvpo, cannot be produced by a fan a reality, the fan imparts in a vent system the Ft.

Therefore, in spite of having the equal Fs and air capacity, the different fans (Table 3, Figure 3) have differen that when a selection of fan is based on Fs, neither one of the fans satisfies the designed vent system.

CONCLUSION The articles intention is to graphically prove that Fs is an unacceptable basis for fan selection. It cannot be read directly from the calculation sheet and cannot be measured in the field. In a vent system, fans do not impart only Fs as a single value. As stated before, a fan impeller imparts static and kinetic energy to the air. This energy is represented in the increase in total pressure.7 The essential point is a designer must recognize that no matter what methods have been applied to calculate the vent system (equal friction, velocity reduction, static regain, or constant velocity, etc.), the result appears in value of the total pressure, not in static pressure. The attention-grabbing fact is that both the pressure loss calculations and fan performance results selection. curves, air capacity and total pressure, mechanical efficiency, energy consumption, and noise levels.

eventuate in a value of the total pressure. Thus, fan total pressure, evidently and logically, is the only proper

As the essential energy saving measure, the fan manufacturers must provide graphs, illustrating system /

Dr. Alex London, P.E. apcco@surfside.net London is with Air Pollution Control Co. Reach him at apcco@surfside.net.

References
1. Graham, J. Barrie, The Importance of Fan Total Pressure, HPAC Engineering, September 1994:78. 2. Williams, P.E., Gerald J. Williams, P.E., Air System Basics HPAC Engineering, June 1997:78. 4. Houlihan, P.E., Tom, Understanding Fan Static Pressure Engineered Systems, March 1997. 5. Halko, George, Jeff S. Forman, The Static Pressure Paradox, HPAC Engineering, March 2002:57. 6. Forman, Jeff S., Air Handlers: Sizing and Selection, HPAC Engineering, January 2003:70. 7. 1983 ASHRAE Handbook Systems and Equipment, Chapter 3, Fans. 8. 2001 ASHRAE Handbook Fundamentals, Chapter 34.6, Duct Design. 9. AMCA 210-99. 10. AMCA International, Fan Testing, supplement to ASHRAE Journal, November 2001:11.

3. London, P.E., Dr. Alex, Destroy the Beliefs. Understand Fan Total Pressure, Engineered Systems, Aug

http://www.esmagazine.com/Articles/Feature_Article/87328157de43a010VgnVCM100000f93... 3/9/2010

The Myth About Fan Static Pressure - Feature Article - Engineered Systems

4 4

Did you enjoy this article? Click here to subscribe to the magazine.

2010 BNP Media. All rights reserved. | Privacy Policy

http://www.esmagazine.com/Articles/Feature_Article/87328157de43a010VgnVCM100000f93... 3/9/2010

Das könnte Ihnen auch gefallen