SUMMARY
1.Design Parameter
Design maximum Current Fault Current, Symmetrical Minimum size recommended Isc = = =
British
2.Section Property
Outer diameter Inner diameter Thickness of wall Area of Cross-section Moment of Inertia Section Modulus = = = = = = 102.00 mm 90.52 mm 5.74 mm 1735.95 mm2 201.78 cm4 39.56 cm3 4.000 in 3.564 in 0.226 in 2.59 sq.in
3.Electrical Design
Current Capacity = 2344 A
4.Deflection Check
Self Weight of Bus Bar Wind pressure Lateral Load due to wind on Bus Lateral Load due to wind on Insulator Unsupported span of Bus Bar Assumed Deflection = = = = = = 5.215 kg/m 75.00 kg/m2 7.65 kg/m 15.00 kg/m 1040 cm 3.75 cm 51.11 N/m 735 N/m2 74.97 N/m2 147 N/m2
BUS SIZES PROPOSED FOR DAMAK SUBSTATION Description 1 132kV Main Bus 2 33kV Main Bus 3 Interconnecting Branch Bus Aluminum Bus size OD ID Thickness 102 90.52 5.74 4 3.56 0.226 102 90.52 5.74 4 3.56 0.226 76 69.03 2 2.88 2.72 0.079
Refer Calculation
Refer Calculation
1.Design Parameter
Design maximum Current Fault Current, Symmetrical Isc = =
Metric 2000 A 25 kA
British
2.Section Property
Outer diameter Inner diameter Thickness of wall Area of Cross-section Moment of Inertia Section Modulus = = = = = = 102.00 mm 90.52 mm 5.74 mm 1735.95 mm2 201.78 cm4 39.56 cm3 4.000 in 3.564 in 0.226 in 2.59 sq.in
3.Electrical Design
Current Capacity = 2344 A
4.Deflection Check
Self Weight of Bus Bar Wind pressure Lateral Load due to wind on Bus Lateral Load due to wind on Insulator Unsupported span of Bus Bar Assumed Deflection = = = = = = 5.215 kg/m 75.00 kg/m2 7.65 kg/m 15.00 kg/m 1040 cm 2.50 cm 51.11 N/m 735 N/m2 74.97 N/m2 147 N/m2
73.03 59 7.01
57.03
Refer Calculation
Refer Calculation
1.Design Parameter
Design maximum Current Fault Current, Symmetrical Isc = =
Metric 2000 A 25 kA
British
2.Section Property
Outer diameter Inner diameter Thickness of wall Area of Cross-section Moment of Inertia Section Modulus = = = = = = 76.00 mm 62.00 mm 7.00 mm 1517.39 mm2 91.23 cm4 24.01 cm3 2.992 in 2.441 in 0.276 in 2.35 sq.in
3.Electrical Design
Current Capacity = 2052 A
4.Deflection Check
Self Weight of Bus Bar Wind pressure Lateral Load due to wind on Bus Lateral Load due to wind on Insulator Unsupported span of Bus Bar Assumed Deflection = = = = = = 3.943 kg/m 75.00 kg/m2 5.70 kg/m 11.25 kg/m 500 cm 2.50 cm 38.64 N/m 735.00 N/m2 55.86 N/m2 110.25 N/m2
73.03 59 7.01
57.03
Refer Calculation
Refer Calculation
1.Design Parameter
Design maximum Current Fault Current Isc = = 800 A 25 kA
2.Section Property
Outer diameter Inner diameter Thickness of wall Area of Cross-section Moment of Inertia Section Modulus = = = = = = 73.03 mm 69.03 mm 2.00 mm 446.26 mm2 28.16 cm4 7.71 cm3 2.875 in 2.718 in 0.079 in 0.69 sq.in
3.Electrical Design
Current Capacity = 1097 A
5.16
Refer Calculation
Refer Calculation
2.Section Property
WP/T6 (Range 2) Section Designation Outer diameter Inner diameter Thickness of wall Area of Cross-section Moment of Inertia Section Modulus Minimum Tensile Strength = = = = = = = 8000 50.00 42.00 4.00 578.05 154051.14 6162.05 20.40
3.Electrical Design
Conductivity = Current Capacity = Current Capacity > Design Current, Hence section is 1.63 941
= r= Spacing of bus = Hence F = Moment due to self weight Mw = Moment due to Short Circuit Msc = Fibre Stress due to selfweight Sw = Fibre Stress due to Short Circuit Ssc = Resultant Fiber Stress Sr = Resultant Fiber Stress < Tensile Strength, Hence section is
A kA
A/mm2 A OK
kg/m cm
2.Section Property
WP/T6 (Range 2) Section Designation Outer diameter Inner diameter Thickness of wall Area of Cross-section Moment of Inertia Section Modulus Minimum Tensile Strength = = = = = = = 8204 76.20 63.50 6.35 1393.45 856854.94 22489.63 20.40
3.Electrical Design
Conductivity = Current Capacity = Current Capacity > Design Current, Hence section is 1.44 2007
4.Deflection Check
Self Weight of Bus Bar = Wind pressure = Lateral Load due to wind = Unsupported span of Bus Bar L = Refer Annex-B for Deflection Calculation Calculated Deflection = Calculated Deflection < Outer Diameter, Hence section is 3.762 75.00 5.72 500 5.00
A kA
A/mm2 A OK