Beruflich Dokumente
Kultur Dokumente
Condensing Air: The ambient condensing air enters the condenser at 95F and leaves at 115F. Compressor: Moves the refrigerant through the system.
Condenser Coil: Rejects heat absorbed from the air along with the heat added to the system during the compression process. Expansion Device: Causes expansion cooling by creating a pressure loss between the high and low side of the system.
Evaporator Tubes Condenser Tubes Liquid Line
Sight Glass / Moisture Indicator: Provides a view into the system. Indicator is green normally, yellow when high in moisture.
Evaporator Coil: The evaporator coil transfers heat from the warm air to the cool refrigerant.
Suction Line
Supply Air: Enters the evaporator coil warm and leaves cool. Design condition for outdoor air is 95F dry bulb 75F wet bulb. Typical leaving air design condition is 55F dry bulb, 54F wet bulb.
Filter-Dryer: Removes water, debris and other contaminants from the refrigerant.
Refrigerant State
LOAD CALCULATIONS
Condenser Evaporator Qout (Btu/hr) = 1.08 x SCFM x Temperature Qin (Btu/hr) = 4.5 x SCFM x Enthalpy
Low Pressure Saturated Low Pressure Superheated Vapor High Pressure Gas High Pressure Saturated High Pressure Liquid
Condenser Coil
Suction Line
Evaporator Coil
Reheat Coil Air Conditions after Evaporator Coil 55F DB / 54F WB 94% Relative Humidity
Models Airflow Range Min. CFM Max. CFM Cooling Performance Cooling
Evaporator Coil
Air Conditions after Reheat Coil 5 - 30 70F DB / 60F Capacity Range WB 56% Relative Humidity tons
Hot Gas Bypass Hot Gas Reheat Digital Scroll Compressors Additional Cooling Options Chilled Water Water Source Heat Pump Heating Options Indirect Gas Hot Water Electric Water Source Heat Pump
Reheat Coil
Air Conditions after Evaporator Coil 55F DB / 54F WB 94% Relative Humidity
Evaporator Coil