Product Information

SIMATIC S7-300 Digital Output Module SM 322; DO 8 X 48-125 VDC/1.5A

Release

X 2 3 4

New Digital Output Module Available The S7--300 Digital Output Module SM 322; DO 8 X 48--125 VDC/1.5A has been added to the S7--300 family. The order number for this module is 6ES7 322-1CF00-0AA0. This product information includes details about the characteristics and technical specifications of the SM 322; DO 8 X 48--125 VDC/1.5A Module. Refer to the S7-300 Installation and Hardware Manual for more information about the S7-300 product family.

Additional Assistance For assistance in answering technical questions, for training on this product, or for ordering, contact your Siemens distributor or sales office.

Copyright 2003 by Siemens Energy & Automation, Inc. A5E00262196-01

Digital Output Module SM 322; DO 8 X 48-125 VDC/1.5A

Order Number 6ES7 322-1CF00--0AA0

Characteristics The SM 322; DO 8 48--125 VDC/1.5A features the following characteristics: ! 8 outputs, reverse polarity protection and isolated in groups of 4 ! 1.5 A output current ! Rated load voltage 48 to 125 VDC ! Suitable for solenoid valves, DC contactors and indicator lights ! Group error display Using the module with high-speed counters Please take note of the following information on the use of the module in connection with high-speed counters:

Note When connecting the power supply via a mechanical contact, the outputs of the SM 322; DO 8 48-125 VDC/1.5 A carry a 1 signal for approximately 50 !s for reasons associated with the circuitry.

Product Information S7-300 Digital Output Module SM 322 DO 8 x 48-125 VDC/1.5 A A5E00262196-01

Terminal Assignment and Block Diagram of the SM 322; DO 8 X 48-125 VDC/1.5A

+5V SF

1 L+

3 SF 5 7 9 Backplane bus interface +5V 10 1M 48 to 125 V

11 13

2 L+

15 17 19 20 Channel number Status display - green Fault indicator - red 2M 48 to 125 V

Figure 1

Module View and Block Diagram of the SM 322; D0 8 48--125 VDC/1.5 A

Product Information S7-300 Digital Output Module SM 322 DO 32 x 48-125 VDC/1.5 A A5E00262196-01

Technical specifications of the SM 322; DO 8 48-125 VDC/1.5 A


Dimensions and Weight Dimensions W H D (in millimeters) Weight 40 !125 !117 Approx. 250 g Data for Specific Module Supports clocked operation Number of outputs Length of cable No 8 Data for Selecting an Actuator Output voltage

! !

At 1 signal

min. L + (-1.2 V)

Output current At 1 signal Rated value Permitted range 1.5 A 10 mA to 1.5 A max. 3 A for 10 ms max. 0.5 mA

! !

Permitted surge current For 0 signal (leakage current)

! !

Unshielded Shielded

max. 600 m max. 1000 m

Output delay (for resistive load)

Voltages, Currents, Potentials Rated load voltage L+ 48 VDC to 125 VDC Yes, by means of fuse1)

! !

At 0 to 1 At 1 to 0

max. 2 ms max. 15 ms max. 15 W at 48 V max. 40 W at 125 V

Reverse polarity protection

Lamp load Parallel connection of 2 outputs

Total current of the outputs (per group)

!
max. 6 A max. 4 A max. 3 A

Horizontal configuration Up to 40 "C Up to 50 "C Up to 60 "C

For redundant actuation of a load To increase performance

Possible (only outputs of the same group) Not possible Possible

Triggering a digital input Switch rate

Vertical configuration Up to 40 "C max. 4 A

Isolation

! ! !

For resistive load For inductive load For lamp load

max. 25 Hz max. 0.5 Hz max. 10 Hz typ. M (-1V)

! !

Between channels and backplane bus Between the channels In groups of

Yes Yes 4

Limit (internal) of the in ductive circuit interruption voltage up Short-circuit protection of the output

Yes, electronic3) typ. 4.4 A Fuse 6.3 A/250 V, quick blow, 5 x 20 mm SP0001.1012 194-1630-0

Permitted potential difference

Between the different circuits

146 VDC / 132 VAC 1500 VAC

Threshold on

Replacement fuses

Insulation tested with Current consumption

! !

From the backplane bus From the load voltage L+ (no load)

max. 100 mA max. 2 mA typ. 7.2 W

! ! !
1)

Schurter Wickmann

Fuse carrier Wickman 653 0000 040

Power dissipation of the module

Status, Interrupts, Diagnostics Status display Interrupts Diagnostic functions Green LED per channel None Red LED (SF)2)
3) 2)

Group error display

The fuses on this module are merely supplementary fuses. External overcurrent protection (suitable for branch circuits conforming to the local regulations for electrical engineering) is required in the supply cables of the load circuit. Potential errors are: - No load voltage - Fuse defective - Output overloaded If an overload condition is detected, the output is inhibited for approximately 2.4 s.

Product Information S7-300 Digital Output Module SM 322 DO 8 x 48-125 VDC/1.5 A A5E00262196-01