Medium Voltage Power Cables

Medium Voltage Power Cables


Medium Voltage Power Cables up to 30 kV with XLPE-insulation The XLPE-insulation possesses very good electrical, mechanical and thermal characteristics in medium voltage networks. This type of insulation is excellent chemical resistant and also resistant to cold. Due to various advantages, the XLPE-insulated type has vastly displaced the traditional classical paper insulated types in many sectors. The XLPE-insulated medium voltage cables are designed with longitudinally water-proof. In comparison to PVC and paper-insulated cables, the advantages of XLPE-insulated medium voltage power cables are possessing a low dielectric factor. The good properties of XLPE-insulated cables remain constant at a long temperature range. These cables can be laid in earth, in air or in tubes. Further information for laying, bending radius ambient temperatures, permissible tensile strength with pulling head test voltages should be taken in the following pages. To the nearness of our customers (stock in Hemmingen/Stuttgart, Neuenhagen/Berlin, Pleia/ Chemnitz and Windsbach/Nurnberg) we are also direct deliverer to the customers construction site for short term scheduled.

Contents and Index


Description N Power Cables Type Page

Code-designation for power cables with PVC or XLPE insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N 1

Power Cables, Underground Cables, Earth Conductors


PVC PVC PVC PVC cables cables cables cables 0,6/1 kV, 0,6/1 kV, 0,6/1 kV, 0,6/1 kV, VDE VDE VDE VDE approved. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . approved. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . approved. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . approved. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NYY-J, NYY-O. . . . . . . . . . . . . . . . . . . . . . . . . N 2 N 4 NAYY-J . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N 5 NYCY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N 6 N 7 NYCWY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N 8

Earth conductors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ESUY, ESY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N 22

Petrol station cables


Data transmission cable with BAM-certificate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-Y(ST)Yo/A-Y(STE)Yo/A-LiY(STE)Yo . . N 9 Power and data transmission cables with BAM-certificate. . . . . . . . . . . . . . . . . . . . . . . . . . (N)YYo-J . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N 10

Power Cables up to 30 kV, XLPE-insulated


Power and control cable with lead sheath, VDE-approved . . . . . . . . . . . . . . . . . . . . . . . . . NYKY-J 0,6/1 kV . . . . . . . . . . . . . . . . N 11 N 12 XLPE-insulated, copper conductor, PVC jacket, VDE-approved . . . . . . . . . . . . . . . . . . . . XLPE-insulated, aluminium-conductor, PVC jacket, VDE-approved . . . . . . . . . . . . . . XLPE-insulated, copper conductor, PE jacket, VDE-approved . . . . . . . . . . . . . . . . . . . . . . XLPE-insulated, aluminium conductor, PE jacket, VDE-approved . . . . . . . . . . . . . . . . XLPE-insulated, copper conductor, longitudinally water-tight, PE jacket, VDE-approved. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . XLPE-insulated, aluminium conductor, longitudinally water-tight, PE jacket, VDE-approved. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . XLPE-insulated, 3 cores copper conductor, PVC jacket, VDE-approved . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N2XSY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NA2XSY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N2XS2Y. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NA2XS2Y . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N 15 N 16 N 17 N 18

N2XS(F)2Y . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N 19 NA2XS(F)2Y . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N 20 N2XSEY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N 21

Code-designation for power cables with PVC or XLPE insulation

Design

Identification of design N

Explanations

Core

According to VDE standard (no abbreviation for copper conductor) Aluminium conductors Insulation of thermoplastic Polyvinylchloride (PVC) Insulation cross-linked Polyethylene (XLPE)

A Y 2X Concentric conductor, screen

Concentric conductors of copper wires and copper tape, helically wounded Concentric conductor of copper wires in waveconal formation and copper tape, helically wounded Concentric conductor of copper wires and copper tape over each individual core, helically wounded Screen of copper wires and copper tape, helically wounded Screen of copper wires and copper tape over each individual core, helically wounded Longitudinally water-proof screen Armour of steel tape

CW

CE

Screen

SE

(F) Armour B

F G Sheath Outer jacket K Y 2Y

Armour of galvanized flat steel wires Counter helix of galvanized steel tape Lead sheath PVC jacket PE jacket

Cable for U0/U 0,6/1 kV are additionally designated with J Cables with green-yellow (green-natural) core are marked with protective conductor Cable without green-yellow (green-natural) core are marked without protective conductor

N1

NYY-J and NYY-O

Power Cable 0,6/1 kV, VDE approved

Technical data
Power and control cable to DIN VDE 0276 part 603, HD 603 S1 and IEC 60502 Insulation and jacket-compound of thermoplastic PVC Temperature range flexing 58 C to +508 C fixed installation 308 C to +708 C Nominal voltage U0/U 0,6/1 kV Test voltage 4 kV Max. permissible tensile stress with cable grip for Cu-conductor = 50 N/mm2 Minimum bending radius for single core approx. 15 x cable 1 for multi core approx. 12 x cable 1 The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

Cable structure
Plain copper conductor, to DIN VDE 0295 cl. 1 or cl. 2 solid or stranded type, BS 6360 cl. 1 or cl. 2, IEC 60228 and HD 383 PVC core insulation, DIV4 to HD 603.1 Cores stranded concentrically Colour coded to DIN VDE 0293, 0276 part 603 or HD 186 PVC outer jacket black, DMV5 to HD 603.1, sheath colour black PVC self-extinguishing and flame retardant according to DIN VDE 0482 part 265-2-1/EN 50265-2-1/IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B) Power ratings table see page T 20 f Caloric load values see page T 67

Application
Power cables for energy supply are installed in open air, in underground, in water, indoors, in cable ducts, power stations, for industry and distribution boards as well as in subscriber networks, where mechanical damages are not to be expected. Attention should be paid to DIN VDE 0298 part 1 and 0276 part 603. Highest permissible voltage Direct current systems Alternating current systems, single-phase systems Both conductors insulated, single-phase systems One conductor earthed, three-phase systems With concentric conductor and a cross-section of 240 mm2 and above 1,8 kV 1,4 kV 0,7 kV 1,2 kV

3,6 kV

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.
No. cores x cross-sec. mm2 1x4 1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 1 x 500 1 x 630 2 x 1,5 2 x 2,5 2x4 2x6 2 x 10 2 x 16 2 x 25 3 x 1,5 3 x 2,5 3x4 3x6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185 3 x 240 re re re re rm rm rm rm rm rm rm rm rm rm rm rm rm re** re** re** re** re** re** rm** re re re re re re rm sm sm sm sm sm sm sm sm Outer 1 ca. mm Cop. weight kg / km 38 58 96 154 240 336 480 672 912 1152 1440 1776 2304 2880 3840 4800 6048 29 48 77 115 192 307 480 43 72 115 173 288 461 720 1008 1440 2016 2736 3456 4320 5328 6912 Weight ca. kg / km J-type Part no. Hohlpreis DM / 100 m Cu 0, Standardlange Hohlpreis DM / 100 m Cu 0, Schnittlange O-type Part no. Hohlpreis DM / 100 m Cu 0, Standardlange AWGno.*)

9,0 9,5 10,0 11,0 12,0 13,0 15,0 16,5 19,0 20,5 22,5 25,0 28,0 30,0 34,0 38,0 43,0 11,0 12,0 14,0 15,0 16,5 18,5 23,5 11,5 12,5 14,0 15,0 17,0 19,0 24,0 25,0 26,5 30,0 34,5 37,0 40,0 46,0 51,0

115 135 179 245 360 470 620 810 1110 1360 1670 2050 2630 3200 4150 5200 6650 175 215 295 370 495 670 960 195 250 340 430 590 820 1320 1450 1850 2450 3300 4100 4900 6500 8300

32001 32002 32003 32004 32005 32006 32007 32008 32009 32010 32011 32012 32013 32014 32015 32556 32557 32016 32017 32018 32019 32020 32021 32022 32023 32024 32025 32026 32027 32028 32029 32030 32031 32032 32033 32034 32293 32294 32295

32089 32090 32091 32092 32093 32094 32095 32096 32097 32098 32099 32100 32101 32102 32103 32558 32559 32104 32105 32106 32107 32108 32109 32110 32111 32112 32113 32114 32115 32116 32117 32118 32119 32120 32121 32122 32296 32297 32298 Also available in NYFGBY, NYBY versions etc. ** Adapted to DIN VDE.

300 350 500 600 750 1000

12 10 8 6 4 2 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil 16 14 12 10 8 6 4

16 14 12 10 8 6 4 2 1 2/0 3/0 4/0 300 kcmil 350 kcmil 500 kcmil Continuation "

PVC cables will be changed to lead free PVC successively. re = solid, round core. rm = stranded, round core. sm = stranded, sectional core.

N2

NYY-J and NYY-O

Power Cable 0,6/1 kV, VDE approved

Technical data
Power and control cable to DIN VDE 0276 part 603, HD 603 S1 and IEC 60502 Insulation and jacket-compound of thermoplastic PVC Temperature range flexing 58 C to +508 C fixed installation 308 C to +708 C Nominal voltage U0/U 0,6/1 kV Test voltage 4 kV Max. permissible tensile stress with cable grip for Cu-conductor = 50 N/mm2 Minimum bending radius for multi core approx. 12 x cable 1 The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

Cable structure
Plain copper conductor, to DIN VDE 0295 cl. 1 or cl. 2 solid or stranded type, BS 6360 cl. 1 or. cl 2, IEC 60228, HD 383 PVC core insulation, DIV4 to HD 603.1 Cores stranded concentrically Colour coded to DIN VDE 0293, 0276 part 603 or HD 186 1 Core colour for 3+ /2 conductor * J-type gnye (1/2), bk, bu, bn * O-type bk, bu (1/2), bn, bk PVC outer jacket black, DMV5 to HD 603.1 sheath colour black PVC self-extinguishing and flame retardant according to DIN VDE 0482 part 265-2-1/EN 50265-2-1/IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B) Power ratings table see page T 20 f Caloric load values see page T 67

Application
Power cables for energy supply are installed in open air, in underground, in water, indoors, in cable ducts, power stations, for industry and distribution boards as well as in subscriber networks, where mechanical damages are not to be expected. Attention should be paid to DIN VDE 0298 part 1 and 0276 part 603. Highest permissible voltage Direct current systems Alternating current systems, single-phase systems Both conductors insulated, single-phase systems One conductor earthed, three-phase systems With concentric conductor and a cross-section of 240 mm2 and above 1,8 kV 1,4 kV 0,7 kV 1,2 kV

3,6 kV

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.
No. cores x cross-sec. mm2 3+1/2 conductors* 3 x 25/16 rm/re 3 x 35/16 sm/re 3 x 50/25 sm/rm 3 x 70/35 sm/sm 3 x 95/50 sm 3 x 120/70 sm 3 x 150/70 sm 3 x 185/95 sm 3 x 240/120 sm 3 x 300/150 sm 4 x 1,5 4 x 2,5 4x4 4x6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95 4 x 120 4 x 150 4 x 185 4 x 240 5 x 1,5 5 x 2,5 5x4 5x6 5 x 10 5 x 16 5 x 25 5 x 35 5 x 50 re re re re re re rm sm sm sm sm sm sm sm sm re re re re re re rm rm rm Outer 1 ca. mm Cop. weight kg / km Weight ca. kg / km J-type Part no. Hohlpreis DM / 100 m Cu 0, Standardlange Hohlpreis DM / 100 m Cu 0, Schnittlange O-type Part no. Hohlpreis DM / 100 m Cu 0, Standardlange AWGno.*)

24,5 26,0 29,0 32,0 38,0 41,0 46,0 51,0 58,0 64,0 12,0 13,5 15,0 16,5 18,5 21,5 26,0 27,5 30,0 34,0 39,0 42,5 47,5 52,0 58,0 13,0 14,5 16,5 18,0 20,0 22,5 28,0 34,0 40,0

874 1162 1680 2352 3216 4128 4992 6240 8064 10080 58 96 154 230 384 614 960 1344 1920 2688 3648 4608 5760 7104 9216 72 120 192 288 480 768 1200 1680 2400

1530 1750 2350 2850 3850 4780 5800 7600 9800 11500 230 300 410 520 730 1045 1640 1760 2350 3100 4250 5300 6400 8500 11000 270 360 490 600 890 1255 1960 2400 3500

32035 32036 32037 32038 32039 32040 32041 32042 32043 32256 32044 32045 32046 32047 32048 32049 32050 32051 32052 32053 32054 32055 32056 32057 32058 32059 32060 32061 32062 32063 32064 32065 32300 32257

32123 32124 32125 32126 32127 32128 32129 32130 32131 32132 32133 32134 32135 32136 32137 32138 32139 32140 32141 32142 32143 32144 32145 32146 32147 32148 32149 32150 32151 32152

300 350 500 600

4 2 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil

16 14 12 10 8 6 4 2 1 2/0 3/0 4/0 300 kcmil 350 kcmil 500 kcmil 16 14 12 10 8 6 4 2 1 Continuation "

* Note In respect to 3+1/2 conductors Whereby only one cnductor is allowed to contain a smaller cross-section (as per DIN VDE 0276 part 603 table 5) and permitted to place as insulated core (gree-yellow and blue as 1/2-conductor), stranded in layer.

PVC cables will be changed to lead free PVC successively. re = solid, round core. rm = stranded, round core. sm = stranded, sectional core. Also available in NYFGBY, NYBY versions etc.

N3

NYY-J and NYY-O

Power Cable 0,6/1 kV, VDE approved

Technical data
Power and control cable to DIN VDE 0276 part 627, HD 627 S1 and IEC 60502 Insulation and jacket-compound of thermoplastic PVC Temperature range flexing 58 C to +508 C fixed installation 308 C to +708 C Nominal voltage U0/U 0,6/1 kV Test voltage 4 kV Max. permissible tensile stress with cable grip for Cu-conductor = 50 N/mm2 Minimum bending radius for multi core approx. 12 x cable 1 The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

Cable structure
Plain copper conductor, to DIN VDE 0295 cl. 1 or cl. 2, IEC 60228 cl. 1 or cl. 2 solid or stranded type, BS 6360 cl. 1 or cl. 2 PVC core insulation, DIV4 to HD 603.1 Cores stranded concentrically Colour coded to DIN VDE 0293, 0276 part 603 or HD 186 PVC outer jacket black, DMV5 to HD 603.1 sheath colour black PVC self-extinguishing and flame retardant according to DIN VDE 0482 part 265-2-1/EN 50265-2-1/IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B) Power ratings table see page T 20 f Caloric load values see page T 67

Application
Power cables for energy supply are installed in open air, in underground, in water, indoors, in cable ducts, power stations, for industry and distribution boards as well as in subscriber networks, where mechanical damages are not to be expected. Attention should be paid to DIN VDE 0298 part 1 and 0276 part 627. Highest permissible voltage Direct current systems Alternating current systems, single-phase systems Both conductors insulated, single-phase systems One conductor earthed, three-phase systems With concentric conductor and a cross-section of 240 mm2 and above 1,8 kV 1,4 kV 0,7 kV 1,2 kV

3,6 kV

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.
No. cores x cross-sec. mm2 7 x 1,5 10 x 1,5 12 x 1,5 14 x 1,5 16 x 1,5 19 x 1,5 21 x 1,5 24 x 1,5 30 x 1,5 40 x 1,5 61 x 1,5 7 x 2,5 10 x 2,5 12 x 2,5 14 x 2,5 16 x 2,5 19 x 2,5 21 x 2,5 24 x 2,5 30 x 2,5 40 x 2,5 52 x 2,5 re re re re re re re re re re re re re re re re re re re re re re Outer 1 ca. mm Cop. weight kg / km 101 144 173 202 230 274 302 346 432 576 878 168 240 288 336 384 456 504 576 720 960 1248 269 403 672 Weight ca. kg / km J-type Part no. Hohlpreis DM / 100 m Cu 0, Standardlange Hohlpreis DM / 100 m Cu 0, Schnittlange O-type Part no. Hohlpreis DM / 100 m Cu 0, Standardlange AWGno.*)

15,5 18,0 19,0 20,0 21,0 22,0 23,0 25,0 26,0 29,0 34,0 16,5 19,5 20,5 21,0 22,0 23,0 24,5 27,0 28,0 31,5 35,0 18,5 20,0 23,5

310 380 420 470 520 570 650 750 860 1070 1680 450 520 600 680 750 850 980 1100 1280 1700 2150 640 850 1200

32066 32067 32068 32069 32070 32071 32072 32073 32074 32075 32176 32076 32077 32078 32079 32080 32081 32082 32083 32084 32085 32169 32086 32087 32088

32153 32154 32155 32156 32157 32158 32159 32160 32161 32162 32174 32175

16 16 16 16 16 16 16 16 16 16 16 14 14 14 14 14 14 14 14 14 14 14 12 10 8

7 x 4 re 7 x 6 re 7 x 10 re

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 see page T 15. re = solid, round core. rm = stranded, round core. sm = stranded, sectional core. Also available in NYFGBY, NYBY versions etc.

PVC cables will be changed to lead free PVC successively.

N4

NAYY-J

Power Cable 0,6/1 kV, VDE approved

Technical data
Power and control cable to DIN VDE 0276 part 603, HD 603 S1 and IEC 60502 Insulation and jacket-compound of thermoplastic PVC Temperature range flexing 58 C to +508 C fixed installation 308 C to +708 C Permissible short circuit temperature +1608 C (short circuit duration 5 sec.) Nominal voltage U0/U 0,6/1 kV Test voltage 4 kV Max. permissible tensile stress with cable grip for Alu-conductor = 30 N/mm2 Current carrying capacity as per DIN VDE 0276 part 603, in normal operation table 14 and 15, under short circuit conditions table 17 Minimum bending radius for multi core approx. 12 x cable 1 The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

Cable structure
Solid aluminium conductor, as per VDE 0295 cl. 1 or cl. 2 (round and sector shaped), BS 6360 cl. 1 or cl. 2, IEC 60228 and HD 383 PVC core insulation, DIV4 to HD 603.1 Conductor colours: black, blue, brown and green-yellow Inner covering PVC outer jacket black, DMV5 to HD 603.1 sheath colour black PVC self-extinguishing and flame retardant according to DIN VDE 0482 part 265-2-1/EN 50265-2-1/IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B) Power ratings table see page T 29 Caloric load values see page T 67

Application
Power cables for energy supply are installed in open air, in underground, in water, indoors, in cable ducts, power stations, for industry and distribution boards as well as in subscriber networks, where mechanical damages are not be expected. Attention should be paid to DIN VDE 0298 part 1 and 0276 part 603. Highest permissible voltage Direct current systems Alternating current systems, single-phase systems Both conductors insulated, single-phase systems One conductor earthed, three-phase systems With concentric conductor and a cross-section of 240 mm2 and above 1,8 kV 1,4 kV 0,7 kV 1,2 kV

3,6 kV

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.
Part No. No. cores x cross-sec. mm2 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95 4 x 120 4 x 150 4 x 185 4 x 240 re re re se se se se se se se Outer 1 ca. mm Alu weight kg / km Weight ca. kg / km Preis DM / 100 m Alu 0, Standardlange AWGno.*)

32301 32302 32303 32304 32305 32306 32307 32308 32309 32310

23,0 26,0 28,5 30,0 35,0 39,5 44,0 46,0 51,0 56,0

186 290 406 580 812 1102 1392 1740 2146 2784

750 950 1120 1151 1549 2030 2400 3030 3650 4800

6 4 2 1 2/0 3/0 4/0 300 kcmil 350 kcmil 500 kcmil

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 see page T 15. PVC cables will be changed to lead free PVC successively.

re = round solid core

se = sectional core

N5

NYCY

Power Cable 0,6/1 kV, VDE approved with concentric copper conductor

Technical data
Power and control cable to DIN VDE 0276 part 603, HD 603 S1 and IEC 60502 Insulation and jacket-compound of thermoplastic PVC Temperature range flexing 58 C to +508 C fixed installation 308 C to +708 C Nominal voltage U0/U 0,6/1 kV Test voltage 4 kV Max. permissible tensile stress with cable grip for Cu-conductor = 50 N/mm2 Minimum bending radius for single core approx. 15 x cable 1 for multi core approx. 12 x cable 1 Highest permissible voltage 1,8 Direct current systems Alternating current systems, single-phase systems 1,4 Both conductors insulated, single-phase systems 0,7 One conductor earthed, three-phase systems 1,2 With concentric conductor and a cross-section of 240 mm2 and above 3,6

Cable structure
Plain copper solid conductor as per VDE 0295 cl. 1, BS 6360 cl. 1, IEC 60228 and HD 383 PVC core insulation, DIV4 to HD 603.1 Colour coded to VDE 0293 and HD 186 Cores stranded concentrically Filling compound Concentric conductor in inner layer of round copper wires, outer layer with copper tape PVC outer sheath, DMV5 to HD 603.1, sheath colour black PVC self-extinguishing and flame retardant according to DIN VDE 0482 part 265-2-1/EN 50265-2-1/IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B) kV Power ratings table see page T 20 f kV Caloric load values see page T 67 kV kV The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

Application
Power cables for energy supply are used for industry and distribution boards, power stations, house connecting boxes and street lighting as well as control cable for the transmission of control impulses and test datas. Overall, where increased electrical and also mechanical protection are required. Those cables are installed in open air, in underground, in water, indoors and in cable ducts. The concentric conductor (C) is allowed to use as neutral-, protective or earthed conductor. Simultaneously, this also is permitted to apply as a screen for example earth-connected protection against contact. Attention should be paid to DIN VDE 0298 part 1 and 0276 part 603.

kV

PVC cables will be changed to lead free PVC successively.

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.
Part No. No. cores x cross-sec. mm2 1 x 10 1 x 16 2 x 1,5 2 x 2,5 2x4 2x6 2 x 10 2 x 16 3 x 1,5 3 x 2,5 3x4 3x6 3 x 10 3 x 16 4 x 1,5 4 x 2,5 4x4 4x6 4 x 10 4 x 16 5 x 1,5 5 x 2,5 5x4 5x6 5 x 10 7 x 41) 7 x 61) re/10 re/16 re/1,5 re/2,5 re/4 re/6 re/10 re/16 re/1,5 re/2,5 re/4 re/6 re/10 re/16 re/1,5 re/2,5 re/4 re/6 re/10 re/16 re/1,5 re/2,5 re/4 re/6 re/10 re/4 re/6 Outer 1 ca. mm Cop. weight kg / km 216 336 52 80 123 182 312 489 66 104 161 240 408 643 81 128 200 297 504 796 95 152 238 355 600 315 470 Weight ca. kg / km Hohlpreis DM / 100 m Cu 0, Standardlange AWGno.*)

32200 32201 32202 32203 32204 32205 32206 32207 32208 32209 32210 32211 32212 32213 32214 32215 32216 32217 32218 32219 32220 32221 32222 32223 32224 32225 32255

11,0 12,0 13,0 13,5 15,5 17,0 19,5 20,5 13,5 14,5 16,5 17,5 20,0 23,0 14,5 15,5 17,0 18,5 21,0 23,0 15,0 16,0 19,0 21,0 23,0 21,0 24,0

280 440 205 270 360 435 590 820 225 290 400 510 850 1080 260 350 470 590 900 1250 330 400 560 710 1000 670 790

8 6 16 14 12 10 8 6 16 14 12 10 8 6 16 14 12 10 8 6 16 14 12 10 8 12 10 Continuation " Available with outer sheath in alternative colours on request.

* Construction according to DIN VDE 0276 part 627 see page N 7. Medium voltage cable of copper and aluminium conductor see pages N 15 N 21.

N6

NYCY

Power Cable 0,6/1 kV, VDE approved with concentric copper conductor

Technical data
Power and control cable to DIN VDE 0276 part 627, HD 627 S1 and IEC 60502 Insulation and jacket-compound of thermoplastic PVC Temperature range flexing 58 C to +508 C fixed installation 308 C to +708 C Nominal voltage U0/U 0,6/1 kV Test voltage 4 kV Max. permissible tensile stress with cable grip for Cu-conductor = 50 N/mm2 Minimum bending radius for single core approx. 15 x cable 1 for multi core approx. 12 x cable 1 The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

Cable structure
Plain copper solid conductor as per VDE 0295 cl. 1, BS 6360 cl. 1 or IEC 60228 PVC core insulation, DIV4 to HD 603.1 Colour coded to DIN VDE 0293 and HD 186 Cores stranded concentrically Filling compound Concentric conductor in inner layer of round copper wires, outer layer with copper tape PVC outer sheath, DMV5 to HD 603.1 sheath colour black PVC self-extinguishing and flame retardant according to DIN VDE 0482 part 265-2-1/EN 50265-2-1/IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B) Power ratings table see page T 20 f Caloric load values see page T 67

Application
Power cables for energy supply are used for industry and distribution boards, power stations, house connecting boxes and street lighting as well as control cable for the transmission of control impulses and test datas. Overall, where increased electrical and also mechanical protection are required. Those cables are installed in open air, in underground, in water, indoors and in cable ducts. The concentric conductor (C) is allowed to use as neutral-, protective or earthed conductor. Simultaneously, this also is permitted to apply as a screen for example earth-connected protection against contact. Attention should be paid to DIN VDE 0298 part 1 and 0276 part 603. Highest permissible voltage Direct current systems Alternating current systems, single-phase systems Both conductors insulated, single-phase systems One conductor earthed, three-phase systems With concentric conductor and a cross-section of 240 mm2 and above 1,8 kV 1,4 kV 0,7 kV 1,2 kV

PVC cables will be changed to lead free PVC successively.

3,6 kV

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.
Part No. No. cores x cross-sec. mm2 7 x 1,5 7 x 1,5 8 x 1,5 8 x 1,5 10 x 1,5 12 x 1,5 14 x 1,5 16 x 1,5 19 x 1,5 21 x 1,5 24 x 1,5 30 x 1,5 40 x 1,5 52 x 1,5 61 x 1,5 7 x 2,5 8 x 2,5 10 x 2,5 12 x 2,5 14 x 2,5 14 x 2,5 16 x 2,5 19 x 2,5 21 x 2,5 24 x 2,5 30 x 2,5 40 x 2,5 52 x 2,5 61 x 2,5 re/1,5 re/2,5 re/1,5 re/2,5 re/2,5 re/2,5 re/2,5 re/4 re/4 re/6 re/6 re/6 re/10 re/10 re/10 re/2,5 re/2,5 re/4 re/4 re/4 re/6 re/6 re/6 re/10 re/10 re/10 re/10 re/10 re/10 Outer 1 ca. mm Cop. weight kg / km 124 133 138 147 176 205 234 276 320 369 413 499 696 869 998 200 224 286 334 382 403 451 523 571 696 840 1080 1368 1584 Weight ca. kg / km Hohlpreis DM / 100 m Cu 0, Standardlange AWGno.*)

32226 32227 32228 32229 32230 32231 32232 32233 32234 32235 32236 32237 32238 32239 32240 32241 32242 32243 32244 32245 32246 32247 32248 32249 32250 32251 32252 32253 32254

15,0 16,0 17,0 17,0 19,0 20,0 20,5 22,0 23,0 24,0 26,0 27,0 30,0 32,0 33,0 17,5 18,0 20,5 21,0 22,0 22,5 23,0 23,5 26,0 28,0 30,0 35,0 38,0 40,0

320 350 380 400 440 500 540 600 690 810 860 1230 1590 1820 2000 450 510 600 660 760 800 910 950 1100 1300 1610 2100 2500 2850

16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 14 14 14 14 14 14 14 14 14 14 14 14 14 14 Available with outer sheath in alternative colours on request.

Medium voltage cable of copper and aluminium conductor see pages N 15 N 21.

N7

NYCWY

Power Cable 0,6/1 kV, VDE approved with concentric copper conductor

Technical data
Power and control cable to DIN VDE 0276 part 603, HD 603 S1 and IEC 60502 Insulation and jacket-compound of thermoplastic PVC Temperature range flexing 58 C to +508 C fixed installation 308 C to +708 C Nominal voltage U0/U 0,6/1 kV Test voltage 4 kV Max. permissible tensile stress with cable grip for Cu-conductor = 50 N/mm2 Minimum bending radius for single core approx. 15 x cable 1 for multi core approx. 12 x cable 1 Attention should be paid to DIN VDE 0298 part 1 and 0276 part 603. Highest permissible voltage see NYCY page N 7. Power ratings table see page T 29 f

Cable structure
Plain copper conductors, as per VDE 0295 cl. 1 od. cl. 2, IEC 60228, BS 6360 cl. 1 and HD 383, solid or stranded versions, conductor types 10 16 mm2 round, solid cores (re) alt. 10 25 mm2, stranded conductor (rm), 35 240 mm2, sector shaped conductor, stranded (sm) PVC core insulation, DIV4 to HD 603.1 Colour coded to DIN VDE 0293 and HD 186 Cores stranded concentrically Filling compound Concentric conductor (Ceander), inner layer of corrugated copper wires, outer layer with copper tape PVC outer sheath, DMV5 to HD 603.1, sheath colour black PVC self-extinguishing and flame retardant according to DIN VDE 0482 part 265-2-1/EN 50265-2-1/IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B) Caloric load values see page T 67

Application
Power cables for energy supply, preferably used for underground laying, especially in subscriber networks, power stations as well as control cables for the transmission of control impulses and test datas. Overall, where increased electrical and also mechanical protection are required. Those cables are installed in open air, in underground, in water, indoors and in cable ducts. The corrugated concentric conductor (CW) is allowed to use as neutral-, protective or earth conductor. Simultaneously, this also is permitted to apply as a screen for example earthed-connected protection against contact. Due to the typical construction of corrugated concentric conductors (Ceander), are possible to obtain many more cable joints, without cutting any conductor. In that way the operating reliability is guaranteed. The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.
Part No. No. cores x cross-sec. mm2 2 x 10 2 x 16 2 x 25 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185 3 x 240 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185 4 x 10 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95 4 x 120 4 x 150 4 x 185 4 x 240 re/10 re/16 rm/25** re/10 re/16 rm/16** sm/16 sm/25 sm/35 sm/50 sm/70 sm/70 sm/95 sm/120 rm/25** sm/35 sm/50 sm/70 sm/95 sm/120 sm/150 sm/185 re/10 re/16 rm/16** sm/16 sm/25 sm/35 sm/50 sm/70 sm/70 sm/95 sm/120 Outer 1 ca. mm Cop. weight kg / km 312 489 763 408 643 902 1190 1723 2410 3296 4236 5100 6383 8242 1003 1402 2000 2796 3791 4786 5970 7363 504 796 1142 1526 2203 3082 4208 5388 6540 8159 10546 Weight ca. kg / km Hohlpreis DM / 100 m Cu 0, Standardlange AWGno.*)

32260 32261 32262 32263 32264 32265 32266 32267 32268 32269 32270 32271 32272 32273 32274 32275 32276 32277 32278 32279 32280 32281 32282 32283 32284 32285 32286 32287 32288 32289 32290 32291 32292

19,0 21,0 24,0 19,5 22,0 26,0 27,0 29,0 33,0 38,0 41,0 45,0 50,0 57,0 26,0 27,5 29,5 34,0 38,5 42,0 46,0 51,0 20,5 23,5 28,0 29,0 33,0 37,0 43,5 47,0 51,0 56,0 62,5

650 850 1210 730 1000 1550 1750 2250 2950 4100 5050 6000 7550 9950 1600 1850 2450 3350 4550 5550 6900 8500 890 1250 1800 2050 2700 3750 5000 6350 7650 9350 11600

8 6 4 8 6 4 2 1 2/0 3/0 4/0 300 kcmil 350 kcmil 500 kcmil 4 2 1 2/0 3/0 4/0 300 kcmil 350 kcmil 8 6 4 2 1 2/0 3/0 4/0 300 kcmil 350 kcmil 500 kcmil PVC cables will be changed to lead free PVC successively. * Round cables are more compact thus smaller core 1 . Available with outer sheath in alternative colours on request.

*) Note AWG sizes are approximate equivalent values, The actual cross-section is in mm2 see page T 15. Medium voltage cable of copper and aluminium conductor see pages N 15 N 21.

N8

A-Y(ST)Yo

A-Y(STE)Yo

A-LiY(STE)Yo

Data transmission cables for petrol stations and refineries with BAM*-Test report

Cable structure
A-Y(ST)Yo Copper conductor, solid, tinned Core insulation of special PVC, according to DIN VDE 0207 Black cores with continuous white numbering Cores stranded in layers with optimal lay-length Foil taping, aluminium/polyester foil, drain wire tinned copper, 0,75 mm2 Special PVC-outer sheath, oil- and fuel resistant Sheath colour black for 2 x 1 sheath colour blue*

Cable structure
A-Y(STE)Yo Copper conductor, solid, tinned Core insulation of special PVC, according to DIN VDE 0207 Black cores with continuous white numbering Each single core screened with aluminium polyester foil, metal layer at outside Screened cores in layers with optimal lay-lenght screenings of each core make contact mutually 2 Drain wire, tinned copper 0,75 mm Overall core-filler Special PVC-outer sheath, oil- and fuel resistant, sheath colour black

Cable structure
A-LiY(STE)Yo Tinned copper conductor, 7 strands Core insulation of special PVC according to DIN VDE 0207 Black cores with continuous white numbering Each single core screened with aluminium polyester foil, metal layer at outside Screened cores in layers with optimal lay-lenght screenings of each core make contact mutually 2 Drain wire, tinned copper 0,75 mm 7 strands Overall core-filler Special PVC-outer sheath, oil- and fuel resistant, sheath colour black

Technical data
Oil- and fuel-resistant data transmission cables Temperature range flexing 58 C to +708 C fixed installation 308 C to +708 C Nominal voltage 200 V Test voltage 0,75 mm2 = 1000 V 1 mm2 = 1500 V Insulation resistance min. 100 MOhm x km Minimum bending radius approx. 12 x cable 1 Radiation resistance up to 80 x 106 cJ/kg (up to 80 Mrad) A-Y(ST)YO (Overall screening), solid conductor
Part no. 32438 32598 32439 32631 32632 No. cores x cross-sec. mm2 4 x 0,75 7 x 0,75 8 x 0,75 12 x 0,75 2 x 1* Outer 1 ca. mm 8,8 9,9 10,5 12,1 8,4 Cop. weight kg / km 38 60 68 99 28

Application
These data transmission cables, oil- and fuel-resistant, are used for internal and external wiring applications at petrol pumps, for data transmission from the pumps to the cash desk and in the installation of video surveillance systems. These cables are also installed directly in the ground and are resistant to UV radiation. Special screens over individual cores guarantee good overall screening and ensure an interference-free transmission of control pulses.

Tests
Compound characteristic according to DIN VDE 0207 Oil- and fuel resistance of sheath: according to BAM-Specification Oil-resistance of sheath: DIN ISO 6722 part 1, 4.11, DIN VDE 0472 part 803 test method B Fuel-resistance of sheath: DIN ISO 6722 part 1, 4.12 PVC self-extinguishing and flame retardant according to DIN VDE 0482 part 265-2-1/EN 50265-2-1/IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B)

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.

A-LiY(STE)YO (Each core individually screened)


Weight ca. kg / km 102 141 159 213 83 AWGno.*) 18 18 18 18 17 Part no. 32597 32633 32599 32634 No. cores x cross-sec. mm2 4 x 0,75 7 x 0,75 8 x 0,75 12 x 0,75 Outer 1 ca. mm 9,0 10,3 11,0 12,9 Cop. weight kg / km 38 60 68 99 Weight ca. kg / km 105 150 169 223 AWGno.*) 18 18 18 18

A-Y(STE)YO (Each core individually screened), solid conductor


Part no. 32635 32636 32637 32638 No. cores x cross-sec. mm2 4 x 0,75 7 x 0,75 8 x 0,75 12 x 0,75 Outer 1 ca. mm 8,7 9,9 10,6 12,3 Cop. weight kg / km 38 60 68 99 Weight ca. kg / km 101 142 165 216 AWGno.*) 18 18 18 18 *) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 see page T 15. * BAM = Bundesanstalt fur Materialprufung

N9

Petrol station cable

(N)YYo-J 0,6/1 kV, with BAM*-Test report

Technical data
Power and data transmission cable based on DIN VDE 0271 with VDE registration number and BAM1)-test report on manufacturing Temperature range flexing 58 C to +508 C fixed installation 308 C to +708 C Limiting temperature at the conductor +708 C Nominal voltage U0/U 0,6/1 kV Test voltage 4 kV Max. permissible tensile stress by cable grip for Cu-conductor = 50 N/mm2 Minimum bending radius approx. 12 x cable 1

Cable structure
Plain copper conductor, solid according to DIN VDE 0295 cl. 1, BS 6360 cl. 1 and IEC 60228 cl. 1 Core insulation of PVC, compound YI3 according to DIN VDE 0207 part 4 Concentric lay-up of cores Core identification according to DIN VDE 0293 1) PVC outer jacket black according to DIN VDE 0207 part 5 Oil and fuel-resistant according to DIN ISO 6722 PVC self-extinguishing and flame retardant according to DIN VDE 0482 part 265-2-1/EN 50265-2-1/IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B)

Application
Power and data transmission cables are used for outdoor and underground applications, in water and in concrete provided mechanical damage can be ruled out. These cables are installed for applications such as petrol stations and oil refineries where resistance to oils and fuels is required. VDE 0298 part 1 shall be observed.

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.
Part No. 32592 32593 32594 32595 32596 No. of cores x cross-section mm2 2 x 1,5 3G1,5 4G1,5 5G1,5 7G1,5 Outer 1 ca. mm 12,2 13,2 14,2 15,2 16,2 Cop. weight kg / km 29 43 58 72 101 Weight ca. kg / km 180 225 260 280 370 AWGno.*) 16 16 16 16 16

Design: 7 x 1,5

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 see page T 15.
1)

* BAM = Bundesanstalt fur Materialprufung. Version with blue outer jacket available upon request.

N 10

NYKY-J 0,6/1 kV

with lead sheath, VDE approved

Technical data
Power and control cable, PVC insulation and lead inner-sheath to DIN VDE 0265 Temperature range 58 C to +708 C Temperature at conductor +708 C Short circuit temperature +1608 C (short circuit duration 5 sec.) Nominal voltage U0/U 0,6/1 kV nominal voltage U * for three-phase system 1,0 kV * for one-phase system 1,2 kV (outer conductor insulated) * for one phase system 0,6 kV (one outer conductor earthed) * nominal voltage U0 = between conductor and lead sheath U = voltage between the outer conductors, e. g. U0/U for cables: 1 For three-phase system U0 U p 3 For one-phase 1 d. c. system, U0 U 2 (both outer conductor insulated) For one-phase and d. c. system U0 U (one outer conductor earthed) * operating voltage the voltage between the conductors of a current-circuit (or between conductor and earth) in a given time during undisturbed operation under specified condition Test voltage (5 min.) 6,0 kV Min. permissible bending radius approx. 12 x cable 1

Cable structure
Bare copper conductor to DIN VDE 0295, BS 6360, IEC 60228 and HD 383 Core insulation of PVC, compound type DIV4 to VDE 0276 part 603 Core identification to DIN VDE 0293 * up to 5 cores coloured * 7 cores black with numbering Green-yellow earth core Cores stranded concentrically Overall jacket of soft plastics material, if exists, permits also as extrusion or taping or a combination of both Lead inner-sheath, jointless and enclosed PVC outer jacket black, DMV5 to DIN VDE 0276 part 603, sheath colour black Advantage Good coupling resistance due to enclosed lead sheath is suitable for special EMC-requirements (Electromagnetic Compatibility). Power ratings table see page T 30

Application
These cables of PVC insulation and lead inner-sheath are installed everywhere, where the danger of chemical reaction of solvents, energy fuels, oils, gasolines or of that kind in filling stations particularly in petrol pump areas for carburetor propellants, in refining plants and in chemical industries are to be caused. Suitable for installation under ground, in water, indoor areas and cable conduits. Resistant to Turpentine substitute Fuels Oils Toluene Xylol Trichlor Petroleum Hydrocarbon

Note * The lead sheath is not permitted to use as neutral-conductor (N). * If drain-wire exists, only for use as earthing of lead sheath in a grounding system e. g. in hazardous areas to DIN VDE 0165. This drain-wire is not allowed to install as protective, neutral or earth conductor.

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.
Part No. No. cores x cross-sec. mm2 3 x 1,5 re 3 x 2,5 re 3 x 4 re 3 x 6 re 3 x 25/16 3 x 35/16 rm sm Outer 1 ca. mm Cop. weight kg / km 43 72 115 173 874 1162 1680 2352 3216 4128 4992 6240 8064 58 96 154 230 Lead weight kg / km 427 487 555 610 1290 1340 1670 2020 2440 2770 3530 4230 5230 464 530 605 665 Weight ca. kg / km Hohlpreis DM / 100 m Cu 0, Standardlange AWGno.*)

32640 32641 32642 32643 32644 32645 32646 32647 32648 32649 32650 32651 32652 32653 32654 32655 32656

13,5 14,8 16,2 17,3 27,8 29,2 32,7 35,8 40,3 43,2 48,8 53,4 59,8 14,5 15,5 17,5 18,5

598 690 840 990 2550 3080 3850 5360 6950 8235 9620 11940 15380 650 760 960 1100

16 14 12 10 4 2 1 2/0 3/0 4/0 300 kcmil 350 kcmil 500 kcmil 16 14 12 10 Continuation "

3 x 50/25 sm 3 x 70/35 sm 3 x 95/50 sm 3 x 120/70 sm 3 x 150/70 sm 3 x 185/95 sm 3 x 240/120 sm 4 x 1,5 re 4 x 2,5 re 4 x 4 re 4 x 6 re

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 see page T 15.

N 11

NYKY-J 0,6/1 kV
Part No. No. cores x cross-sec. mm2 4 x 10 re 4 x 16 re 4 x 25 rm 4 x 35 rm 4 x 50 sm 4 x 70 sm 4 x 95 sm 5 x 1,5 re 5 x 2,5 re 5 x 4 re 5 x 6 re 5 x 10 re 5 x 16 re 7 x 1,5 re 10 x 1,5 re 12 x 1,5 re 14 x 1,5 re 19 x 1,5 re 24 x 1,5 re 30 x 1,5 re 40 x 1,5 re 7 x 2,5 re 10 x 2,5 re 12 x 2,5 re 14 x 2,5 re 19 x 2,5 re 24 x 2,5 re 30 x 2,5 re 40 x 2,5 re 3 x 1,5 re+1,5 4 x 1,5 re+1,5 5 x 1,5 re+1,5 7 x 1,5 re+1,5 Outer 1 ca. mm

with lead sheath, VDE approved

= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.
Cop. weight kg / km 384 614 960 1344 1920 2688 3648 72 120 192 288 480 768 101 144 173 202 274 346 432 576 168 240 288 336 456 576 720 960 57 72 86 115 Lead weight kg / km 750 975 1290 1340 1680 2020 2440 505 580 665 730 930 1070 545 680 710 735 900 1170 1240 1390 625 865 940 980 1170 1370 1550 1770 427 464 505 545 Weight ca. kg / km Hohlpreis DM / 100 m Cu 0, Standardlange AWGno.*)

32657 32658 32659 32660 32661 32662 32663 32664 32665 32666 32667 32668 32669 32670 32671 32672 32673 32674 32675 32676 32677 32678 32679 32680 32681 32682 32683 32684 32685 32686 32687 32688 32689

21,3 24,2 28,5 30,5 33,3 37,5 42,3 15,3 17,2 19,4 20,2 22,8 26,4 17,2 21,3 21,3 21,3 23,0 27,3 28,2 31,4 18,0 22,4 23,2 24,5 26,0 31,0 32,3 36,4 14,5 15,3 16,4 17,2

1400 1910 2750 3630 4580 5340 7120 710 910 1090 1270 1700 2231 810 918 988 1100 1440 1610 1830 2300 1070 1330 1440 1530 1680 2160 2530 3310 610 650 780 970

8 6 4 2 1 2/0 3/0 16 14 12 10 8 6 16 16 16 16 16 16 16 16 14 14 14 14 14 14 14 14 16 16 16 16

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 see page T 15.

N 12

Medium Voltage Power Cables


6/10 kV, 12/20 kV, 18/30 kV
Since about 1970 the cross-linked polyethylene (XLPE)-insulated power cables has been used in Germany. The XLPE-insulation possesses very good electrical, mechanical and thermal characteristics in medium voltage networks. This type of insulation is excellent chemical resistant and also resistant to cold. Due to various advantages, the XLPE-insulated type has vastly displaced the traditional classical paper-insulated types in many sectors. In order to prevent the penetration of moisture and also to extend the duration of life, the XLPE-insulated medium voltage cables are designed with longitudinally water-proof screen including an additional swell tape and a PE outer sheath. The manufacture of this sheath is based on high density polyethylene (HDPE), in which an additive organic peroxide is mixed. Due to the heating and pressure the molecule chains are joined each other, assuring the transion from thermoplastic to elastic condition. In comparison to PVC and paper-insulated cables, the advantages of XLPE-insulated medium voltage power cables are possessing a low dielectric factor, such as it is 100 times smaller than of PVC-insulated cables. Moreover, a better dielectric constant value has an effect on the low mutual capacitance, the shortcircuit to ground and the charging current of XLPEinsulated cables. The good properties of XLPE-insulated cables remain constant at a long temperature range. Characteristics of XLPE * permissible operating temperature For permanent (normal) operation + 908 C In short circuit +2508 C In overload operation and damage by sea up to +1308 C
* * * * * * *

XLPE-insulated

Conductor Copper or aluminium, round, multiwire stranded and compact, according to VDE 0295 and HD 383. Inner semi-conducting layer Semi-conducting compound, cross-linked, minimum wall-thickness 0,3 mm. Insulation Cross-linked polyethylene (XLPE), compound type 2XI1 according to DIN VDE 0207 part 22 and HD 620.1. Insulation nominal wall-thickness for 6/10 kV = 3,4 mm 12/20 kV = 5,5 mm 18/30 kV = 8,0 mm Outer semi-conducting layer Outer semi-conducting layer is extruded together with the inner semi-conducting layer and the insulation in one working process and are spliced with each other. Semi-conducting compound, cross-linked, wallthickness 0,3 to 0,6 mm. Concentricity of conductor The difference between the maximum and minimum value of 0,5 mm should not be exceeded. Semi-conducting type Over the outer semi-conducting layer, a semi-conducting tape must be used. Screen Screening of copper wires must have a minimum diameter of 0,5 mm and over that a copper tape applied helically with a minimum thickness of 0,1 mm. Copper cross-section according to DIN VDE 0273 and 0276 to the corresponded table 2. Separator Over the screen as well as under outer jacket, a separating layer must be used (e. g. taping). Outer jacket PE compound DMP2 according to HD 620.1 and 2YM3 to DIN VDE 0276 part 3, black or PVC compound DMV6 according to HD 620.1 and YM5 to DIN VDE 0207 part 5, red Wall-thickness = 2,5 mm, for 1 x 500 mm2/30 kV = 2,6 mm

Specific heat resistance Dielectric constant Specific resistance (208 C) Loss factor (tan d) (208 C) Density Breaking strength Tensile strength

3,5 K ? m/W 2,4 min. 1016 Ohm ? cm max. 0,5 ? 103 0,92 g/cm3 min. 200% min. 12,5 N/mm2

Continuation "

N 13

Medium Voltage Power Cables


6/10 kV, 12/20 kV, 18/30 kV

XLPE-insulated

Laying of Cable In order to avoid any damage, the XLPE-insulated medium voltage cables should carefully laid and installed. It must be ensured that the cables should not be pulled over the hard or sharp edges. The cable ends must be water-tight-sealed. After cutting the length both ends must be sealed immediately. A laying depth of 60 to 80 cm is recommended. Single conductor cables are normally arranged in a trefoil touching or tringular shape. For laying in conduits, specially the influence of thermal insulation of air space between the cable and the inner wall of conduit should be considered. The inner diameter of the conduit should be at least 1,5 times that of the diameter of the cable. Bending radius During the laying of XLPE cables, the bending radius should not be below of the following values: * Cable without metal sheath = 15 x cable 1 * Cable with Alu-laminated sheath = 30 x cable 1 Temperature range During the installation, the temperature should not be below the following values: * for XLPE-insulation + PVC jacket = 58 C * for XLPE-insulation + PE jacket = 208 C Max. permissible tensile strength By pulling the conductors with a pulling head (not for armoured cables) P = No. of cores x conductor cross-section x d d = permissible pulling tension N/mm2 2 For Cu-conductor: 50 N/mm 2 For Alu-conductor: 30 N/mm Current carrying capacity according to VDE 0276 part 620, 5C or HD 620 S1 Laying in earth (ground) Laying depth * Earth temperature in the laying depth * Specific heat resistance * Load factor
*

Laying in conduits Cables for conduit systems laying in earth, a reduction of the current carrying capacity with a factor of 0,85 is recommended. Test voltages
Kind of voltage test Voltage test in kV U0/U = 18/30 kV 45 144 54 76 up to 108 U0/U = 18/30 kV 36 U0/U = 12/20 kV 30 96 36 24 U0/U = 12/20 kV 67 up to 96

Voltage test a. c. in kV

15

Voltage test d. c. in kV

48

Voltage test a. c. (voltage test = 1000 h)

18

Voltage test to cable system During the operation or after laying the medium voltage power cables, the dielectric can be tested with alternating or direct current. The test duration continues 30 minutes.
U0/U = 6/10 kV 24 34 up to 48

Kind of voltage test

0,7 0,8 m 208 C 1,0 K ? m/W 0,7 (EVU-Load) 308 C 1,0

Voltage test a. c. in kV

Laying in air Air temperature * Load factor (permanent load)


*

Voltage test d. c. in kV

N 14

U0/U = 6/10 kV

N2XSY 6/10 kV, 12/20 kV, 18/30 kV


Cu-conductor, single core, screened, PVC-jacket

XLPE-insulated

Technical data
XLPE-insulated power cables to DIN VDE 0276 part 620, HD 620 S1 and IEC 60502 Temperature range during installation up to 58 C Operating temperature max. 908 C Short circuit temperature 2508 C (short circuit duration up to 5 sec.) Nominal voltages U0/U 6/10 kV, 12/20 kV, 18/30 kV Operating voltages for 6/10 kV = max. 12 kV 12/20 kV = max. 24 kV 18/30 kV = max. 36 kV Test voltages for 6/10 kV = 15 kV 12/20 kV = 30 kV 18/30 kV = 45 kV Minimum bending radius max. 15 x cable 1 Power ratings table see page T 35 f

Cable structure
Circular bare Cu-conductor of stranded wires to HD 383 Inner semi-conducting coating Core insulation of cross-linked Polyethylene (XLPE), PE-compound DIX8 to HD 620.1 Outer extrusion of semi-conducting coating spliced with the insulation Tape of conductive material Screen of copper wires and one or two copper tape(s) applied helically Inner covering or tape lapping PVC outer jacket, compound DMV6 to HD 620.1, jacket colour red Installation notes To guarantee an optimum on operating reliability the extruded semi-conductive layer is spliced with the insulation for long duration. For this reason we recommend a peeling tool for installation.

Application
Suitable for installation mostly for power supply stations, in indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switch-boards and power stations. Due to the good laying characteristic, this can also be laid easily in difficult line guideways. See DIN VDE 0298 part 1. To avoid the influence of the outer interferences, an adherent semi-conductive layer is extruded between the conductor and the VPE insulation and also a concentric copper conductor which guarantees the field-limitation and the resistance to the partial discharges # 2 pC by a measuring volt of 2 U0. The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

Part No.

No. cores x cross-sec. n x mm2

Insulation thickness mm

PVCjacket thickness mm 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5

Outer 1 min. mm 23 24 26 27 29 30 30 32 32 34 34 36 40 43 27 28 30 31 33 34 34 36 36 39 39 41 44 47 33 35 36 38 39 41 43 46 49 52 max. mm 28 29 31 32 34 35 35 37 37 39 39 41 45 48 32 33 35 36 38 39 39 41 41 44 44 46 49 52 38 40 41 43 44 46 48 51 54 57

Cop. weight kg / km

Weight ca. kg / km

Hohlpreis DM / 100 m Cu 0, Standardlange

AWGno.*)

N2XSY 6/10 kV 32400 1 x 35 32401 1 x 50 32402 1 x 70 32403 1 x 95 32404 1 x 120 32405 1 x 150 32406 1 x 150 32407 1 x 185 32408 1 x 185 32409 1 x 240 32410 1 x 240 32411 1 x 300 32412 1 x 400 32413 1 x 500 N2XSY 12/20 kV 32414 1 x 35 32415 1 x 50 32416 1 x 70 32417 1 x 95 32418 1 x 120 32419 1 x 150 32420 1 x 150 32421 1 x 185 32422 1 x 185 32423 1 x 240 32424 1 x 240 32425 1 x 300 32426 1 x 400 32427 1 x 500 N2XSY 18/30 kV 32428 1 x 50 32429 1 x 70 32430 1 x 95 32431 1 x 120 32432 1 x 150 32433 1 x 185 32434 1 x 240 32435 1 x 300 32436 1 x 400 32437 1 x 500

rm/16 rm/16 rm/16 rm/16 rm/16 rm/16* rm/25 rm/16* rm/25 rm/16* rm/25 rm/25 rm/35 rm/35 rm/16 rm/16 rm/16 rm/16 rm/16 rm/16* rm/25 rm/16* rm/25 rm/16* rm/25 rm/25 rm/35 rm/35 rm/16 rm/16 rm/16 rm/16 rm/25 rm/25 rm/25 rm/25 rm/35 rm/35

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0

518 662 860 1094 1334 1723 1725 1958 2059 2486 2587 3163 4234 5194 518 662 854 1094 1334 1622 1723 1958 2059 2486 2587 3163 4234 5194 662 854 1094 1334 1723 2059 2587 3163 4234 5194

905 1080 1310 1580 1860 2040 2210 2450 2580 3000 3130 3780 4670 5750 1110 1250 1510 1780 2070 2310 2420 2650 2810 3260 3360 4020 4930 6050 1480 1730 2060 2330 2720 3100 3730 4000 5330 6480

300 300 350 350 500 500 600 750 1000

2 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil 2 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil

300 300 350 350 500 500 600 750 1000

300 350 500 600 750 1000

* For cables laying in earth a screen-cross section of 16 mm2 is permitted. Further types and dimensions on request.

N 15

NA2XSY 6/10 kV, 12/20 kV, 18/30 kV XLPE-insulated


Alu-conductor, single core, screened, PVC-jacket

Technical data
XLPE-insulated power cables to DIN VDE 0276 part 620, HD 620 S1 and IEC 60502 Temperature range during installation up to 58 C Operating temperature max. 908 C Short circuit temperature 2508 C (short circuit duration up to 5 sec.) Nominal voltages U0/U 6/10 kV, 12/20 kV, 18/30 kV Operating voltages for 6/10 kV = max. 12 kV 12/20 kV = max. 24 kV 18/30 kV = max. 36 kV Test voltages for 6/10 kV = 15 kV 12/20 kV = 30 kV 18/30 kV = 45 kV Minimum bending radius max. 15 x cable 1

Cable structure
Circular bare alu-conductor of stranded wires to HD 383 Inner semi-conducting coating Core insulation of cross-linked Polyethylene (XLPE), PE-compound DIX8 to HD 620.1 Outer extrusion of semi-conducting coating spliced with the insulation Tape of conductive material Screen of copper wires and one or two copper tape(s) applied helically Inner covering or tape lapping PVC outer jacket, compound DMV6 to HD 620.1, jacket colour red Installation notes see page N15 Power ratings table see page T 35 f

Application
Suitable for installation mostly for power supply stations, in indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switch-boards and power stations. Due to the good laying characteristic, this can also be laid easily in difficult line guideways. See DIN VDE 0298 part 1. To avoid the influence of the outer interferences, an adherent semi-conductive layer is extruded between the conductor and the VPE insulation and also a concentric copper conductor which guarantees the field-limitation and the resistance to the partial discharges # 2 pC by a measuring volt of 2 U0. The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers
Hohlpreis DM / 100 m Alu 0, Standardlange AWGno.*)

Part No.

No. cores x cross-sec. n x mm2

Insulation thickness mm 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0

PVCjacket thickness mm 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,6

Outer 1 min. mm 24 26 27 29 30 30 32 32 34 34 36 40 43 28 30 31 33 34 34 36 36 39 39 41 44 47 33 35 36 38 39 39 41 41 43 43 46 49 52 max. mm 29 31 32 34 35 35 37 37 39 39 41 45 48 33 35 36 38 39 39 41 41 44 44 46 49 52 38 40 41 43 44 44 46 46 48 48 51 54 57

Cop. weight kg / km

Alu weight kg / km

Weight ca. kg / km

NA2XSY 6/10 kV 32440 1 x 50 rm/16 32441 1 x 70 rm/16 32442 1 x 95 rm/16 32443 1 x 120 rm/16 32444 1 x 150 rm/16* 32445 1 x 150 rm/25 32446 1 x 185 rm/16* 32447 1 x 185 rm/25 32448 1 x 240 rm/16* 32449 1 x 240 rm/25 32450 1 x 300 rm/25 32451 1 x 400 rm/35 32452 1 x 500 rm/35 NA2XSY 12/20 kV 32453 1 x 50 rm/16 32454 1 x 70 rm/16 32455 1 x 95 rm/16 32456 1 x 120 rm/16 32457 1 x 150 rm/16* 32458 1 x 150 rm/25 32459 1 x 185 rm/16* 32460 1 x 185 rm/25 32461 1 x 240 rm/16* 32462 1 x 240 rm/25 32463 1 x 300 rm/25 32464 1 x 400 rm/35 32465 1 x 500 rm/35 NA2XSY 18/30 kV 32466 1 x 50 rm/16 32467 1 x 70 rm/16 32468 1 x 95 rm/16 32469 1 x 120 rm/16 32470 1 x 150 rm/16* 32471 1 x 150 rm/25 32472 1 x 185 rm/16* 32473 1 x 185 rm/25 32474 1 x 240 rm/16* 32475 1 x 240 rm/25 32476 1 x 300 rm/25 32477 1 x 400 rm/35 32478 1 x 500 rm/35

182 182 182 182 182 283 182 283 182 283 283 394 394 182 182 182 182 182 283 182 283 182 283 283 394 394 182 182 182 182 182 283 182 283 182 283 283 394 394

145 203 276 348 435 435 537 537 696 696 870 1160 1450 145 203 276 348 435 435 537 537 696 696 870 1160 1450 145 203 276 348 435 435 537 537 696 696 870 1160 1450

780 875 990 1110 1240 1310 1405 1460 1615 1660 1910 2315 2750 950 1110 1220 1310 1460 1520 1660 1720 1860 1910 2220 2620 3030 1260 1360 1510 1610 1760 1810 1960 2020 2210 2260 2560 2960 3460

300 300 350 350 500 500 600 750 1000

1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil

300 300 350 350 500 500 600 750 1000

300 300 350 350 500 500 600 750 1000

* For cables laying in earth a screen-cross section of 16 mm2 is permitted. Further types and dimensions on request.

N 16

N2XS2Y 6/10 kV, 12/20 kV, 18/30 kV XLPE-insulated


Cu-conductor, single core, screened, PE-jacket

Technical data
XLPE-insulated power cables to IEC 60502, DIN VDE 0276 part 620, HD 620 S1 Temperature range during installation up to 208 C Operating temperature max. 908 C Short circuit temperature 2508 C (short circuit duration up to 5 sec.) Nominal voltages U0/U 6/10 kV, 12/20 kV, 18/30 kV Operating voltages for 6/10 kV = max. 12 kV 12/20 kV = max. 24 kV 18/30 kV = max. 36 kV Test voltages for 6/10 kV = 15 kV 12/20 kV = 30 kV 18/30 kV = 45 kV Minimum bending radius max. 15 x cable 1 Power ratings table see page T 35 f

Cable structure
Circular bare cu-conductor of stranded wires to HD 383 Inner semi-conducting coating Core insulation of cross-linked Polyethylene (XLPE), PE-compound DIX8 to HD 620.1 Outer extrusion of semi-conducting coating spliced with the insulation Tape of conductive material Screen of copper wires and one or two copper tape(s) applied helically Inner covering or tape lapping PE-outer jacket black, compound DMP2 to HD 620.1, jacket colour black Installation notes To guarantee an optimum on operating reliability the extruded semi-conductive layer is spliced with the insulation for long duration. For this reason we recommend a peeling tool for installation.

Application
Suitable for indoor installation and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switch-boards and power stations. The PE-outer jacket is resistant to high mechanical stress for laying the cables. This PE-jacket is not flame-resistant (does not conform the test method B, as per VDE 0472 part 804). To avoid the influence of the outer interferences, an adherent semi-conductive layer is extruded between the conductor and the VPE insulation and also a concentric copper conductor which guarantees the field-limitation and the resistance to the partial discharges # 2 pC by a measuring volt of 2 U0. See DIN VDE 0298 part 1. The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers
Hohlpreis DM / 100 m Cu 0, Standardlange AWGno.*)

Part No.

No. cores x cross-sec. n x mm2

Insulation thickness mm

PEjacket thickness mm 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5

Outer 1 min. mm 23 24 26 27 29 30 30 32 32 34 34 36 40 43 27 28 30 31 33 34 34 36 36 39 39 41 44 47 33 35 36 38 39 41 43 46 49 52 max. mm 28 29 31 32 34 35 35 37 37 39 39 41 45 48 32 33 35 36 38 39 39 41 41 44 44 46 49 52 38 40 41 43 44 46 48 51 54 57

Cop. weight kg / km

Weight ca. kg / km

N2XS2Y 6/10 kV 32480 1 x 35 rm/16 32481 1 x 50 rm/16 32482 1 x 70 rm/16 32483 1 x 95 rm/16 32484 1 x 120 rm/16 32485 1 x 150 rm/16* 32486 1 x 150 rm/25 32487 1 x 185 rm/16* 32488 1 x 185 rm/25 32489 1 x 240 rm/16* 32490 1 x 240 rm/25 32491 1 x 300 rm/25 32492 1 x 400 rm/35 32493 1 x 500 rm/35 N2XS2Y 12/20 kV 32494 1 x 35 rm/16 32495 1 x 50 rm/16 32496 1 x 70 rm/16 32497 1 x 95 rm/16 32498 1 x 120 rm/16 32499 1 x 150 rm/16* 32500 1 x 150 rm/25 32501 1 x 185 rm/16* 32502 1 x 185 rm/25 32503 1 x 240 rm/16* 32504 1 x 240 rm/25 32505 1 x 300 rm/25 32506 1 x 400 rm/35 32507 1 x 500 rm/35 N2XS2Y 18/30 kV 32508 1 x 50 rm/16 32509 1 x 70 rm/16 32510 1 x 95 rm/16 32511 1 x 120 rm/16 32512 1 x 150 rm/25 32513 1 x 185 rm/25 32514 1 x 240 rm/25 32515 1 x 300 rm/25 32516 1 x 400 rm/35 32517 1 x 500 rm/35

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0

518 662 854 1094 1334 1622 1723 1958 2059 2486 2587 3163 4234 5194 518 662 854 1094 1334 1622 1723 1958 2059 2486 2587 3163 4234 5194 662 854 1094 1334 1723 2059 2587 3163 4234 5194

910 990 1205 1520 1760 2020 2130 2360 2470 2960 3020 3630 4560 5580 960 1160 1410 1670 1960 2220 2310 2620 2670 3160 3270 3880 4820 5860 1410 1660 1970 2220 2650 2980 3570 4220 5170 6260

300 300 350 350 500 500 600 750 1000

2 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil 2 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil

300 300 350 350 500 500 600 750 1000

300 350 500 600 750 1000

* For cables laying in earth a screen-cross section of 16 mm2 is permitted. Further types and dimensions on request.

N 17

NA2XS2Y 6/10 kV, 12/20 kV, 18/30 kV


Alu-conductor, single core, screened, PE-jacket

XLPE-insulated

Technical data
XLPE-insulated power cables to DIN VDE 0276 part 620, HD 620 S1 and IEC 60502 Temperature range during installation up to 208 C Operating temperature max. 908 C Short circuit temperature 2508 C (short circuit duration up to 5 sec.) Nominal voltages U0/U 6/10 kV, 12/20 kV, 18/30 kV Operating voltages for 6/10 kV = max. 12 kV 12/20 kV = max. 24 kV 18/30 kV = max. 36 kV Test voltages for 6/10 kV = 15 kV 12/20 kV = 30 kV 18/30 kV = 45 kV Minimum bending radius max. 15 x cable 1 Power ratings table see page T 35 f

Cable structure
Circular bare alu-conductor of stranded wires to HD 383 Inner semi-conducting coating Core insulation of cross-linked Polyethylene (XLPE), PE-compound DIX8 to HD 620.1 Outer extrusion of semi-conducting coating spliced with the insulation Tape of conductive material Screen of copper wires and one or two copper tape(s) applied helically Inner covering or tape lapping PE-outer jacket black, compound DMP2 to HD 620.1, jacket colour black Installation notes To guarantee an optimum on operating reliability the extruded semi-conductive layer is spliced with the insulation for long duration. For this reason we recommend a peeling tool for installation.

Application
Suitable for indoor installation and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switch-boards and power stations. The PE-outer jacket is resistant to high mechanical stress for laying the cables. This PE-jacket is not flame-resistant (does not conform the test method B, as per VDE 0472 part 804). To avoid the influence of the outer interferences, an adherent semi-conductive layer is extruded between the conductor and the VPE insulation and also a concentric copper conductor which guarantees the field-limitation and the resistance to the partial discharges # 2 pC by a measuring volt of 2 U0. See DIN VDE 0298 part 1. The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers
Hohlpreis DM / 100 m Alu 0, Standardlange AWGno.*)

Part No.

No. cores x cross-sec. n x mm2

Insulation thickness mm 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0

PEjacket thickness mm 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5

Outer 1 min. mm 24 26 27 29 30 30 32 32 34 34 36 40 43 28 30 31 33 34 34 36 36 39 39 41 44 47 33 35 36 38 39 41 43 46 49 52 max. mm 29 31 32 34 35 35 37 37 39 39 41 45 48 33 35 36 38 39 39 41 41 44 44 46 49 52 38 40 41 43 44 46 48 51 54 57

Cop. weight kg / km

Alu weight kg / km

Weight ca. kg / km

NA2XS2Y 6/10 kV 32520 1 x 50 rm/16 32521 1 x 70 rm/16 32522 1 x 95 rm/16 32523 1 x 120 rm/16 32524 1 x 150 rm/16* 32525 1 x 150 rm/25 32526 1 x 185 rm/16* 32527 1 x 185 rm/25 32528 1 x 240 rm/16* 32529 1 x 240 rm/25 32530 1 x 300 rm/25 32531 1 x 400 rm/35 32532 1 x 500 rm/35 NA2XS2Y 12/20 kV 32533 1 x 50 rm/16 32534 1 x 70 rm/16 32535 1 x 95 rm/16 32536 1 x 120 rm/16 32537 1 x 150 rm/16* 32538 1 x 150 rm/25 32539 1 x 185 rm/16* 32540 1 x 185 rm/25 32541 1 x 240 rm/16* 32542 1 x 240 rm/25 32543 1 x 300 rm/25 32544 1 x 400 rm/35 32545 1 x 500 rm/35 NA2XS2Y 18/30 kV 32546 1 x 50 rm/16 32547 1 x 70 rm/16 32548 1 x 95 rm/16 32549 1 x 120 rm/16 32550 1 x 150 rm/25 32551 1 x 185 rm/25 32552 1 x 240 rm/25 32553 1 x 300 rm/25 32554 1 x 400 rm/35 32555 1 x 500 rm/35

182 182 182 182 182 283 182 283 182 283 283 394 394 182 182 182 182 182 283 182 283 182 283 283 394 394 182 182 182 182 283 283 283 283 394 394

145 203 276 348 435 435 537 537 696 696 870 1160 1450 145 203 276 348 435 435 537 537 696 696 870 1160 1450 145 203 276 348 435 537 696 870 1160 1450

710 790 920 990 1110 1220 1260 1370 1480 1530 1820 2220 2570 890 970 1120 1210 1370 1420 1530 1570 1720 1830 2070 2460 2890 1120 1270 1380 1530 1720 1860 2110 2370 2820 3280

300 300 350 350 500 500 600 750 1000

1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil kcmil 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil

300 300 350 350 500 500 600 750 1000

300 350 500 600 750 1000

* For cables laying in earth a screen-cross section of 16 mm2 is permitted. Further types and dimensions on request.

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 see page T 15.

N 18

XLPE-insulated Cu-conductor, single core, screened, longitudinally water-tight, PE-jacket

N2XS(F)2Y 6/10 kV, 12/20 kV, 18/30 kV

Technical data
XLPE-insulated power cables to DIN VDE 0276 part 620, HD 620 S1 and IEC 60502 Temperature range during installation up to 208 C Operating temperature max. 908 C Short circuit temperature 2508 C (short circuit duration up to 5 sec.) Nominal voltages U0/U 6/10 kV, 12/20 kV, 18/30 kV Operating voltages for 6/10 kV = max. 12 kV 12/20 kV = max. 24 kV 18/30 kV = max. 36 kV Test voltages for 6/10 kV = 15 kV 12/20 kV = 30 kV 18/30 kV = 45 kV Minimum bending radius max. 15 x cable 1 Power ratings table see page T 35 f

Cable structure
Circular bare Cu-conductor of stranded wires to HD 383 Inner semi-conducting coating Core insulation of cross-linked Polyethylene (XLPE), PE-compound DIX8 to HD 620.1 Outer extrusion of semi-conducting coating spliced with the insulation Tape of conductive material Tape of longitudinally water-tight material Screen of copper wires and one or two copper tape(s) applied helically Inner covering or tape lapping PE-outer jacket black, compound DMP2 to HD 620.1, jacket colour black Installation notes To guarantee an optimum on operating reliability the extruded semi-conductive layer is spliced with the insulation for long duration. For this reason we recommend a peeling tool for installation.

Application
Suitable for indoor installation and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switch-boards and power stations. The PE-outer jacket is resistant to high mechanical stress for laying the cables. This PE-jacket is not flame-resistant (does not conform the test method B, as per VDE 0472 part 804). To avoid the influence of the outer interferences, an adherent semi-conductive layer is extruded between the conductor and the VPE insulation and also a concentric copper conductor which guarantees the field-limitation and the resistance to the partial discharges # 2 pC by a measuring volt of 2 U0. See DIN VDE 0298 part 1. The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

Part No.

No. cores x cross-sec. n x mm2

Insulation thickness mm 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0

Screen crosssec. mm2 16 16 16 16 16 25 25 25 25 35 35 16 16 16 16 16 25 25 25 25 35 35 16 16 16 16 25 25 25 25 35 35

PEjacket thickness mm 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5

Outer 1 ca. mm

Cop. weight kg / km

Weight ca. kg / km

Hohlpreis DM / 100 m Cu 0, Standardlange

AWGno.*)

N2XS(F)2Y 6/10 kV 32560 1 x 35 32561 1 x 50 32562 1 x 70 32563 1 x 95 32564 1 x 120 32565 1 x 150 32566 1 x 185 32567 1 x 240 32568 1 x 300 32569 1 x 400 32570 1 x 500 N2XS(F)2Y 12/20 kV 32571 1 x 35 32572 1 x 50 32573 1 x 70 32574 1 x 95 32575 1 x 120 32576 1 x 150 32577 1 x 185 32578 1 x 240 32579 1 x 300 32580 1 x 400 32581 1 x 500 N2XS(F)2Y 18/30 kV 32582 1 x 50 32583 1 x 70 32584 1 x 95 32585 1 x 120 32586 1 x 150 32587 1 x 185 32588 1 x 240 32589 1 x 300 32590 1 x 400 32591 1 x 500

rm/16 rm/16 rm/16 rm/16 rm/16 rm/25 rm/25 rm/25 rm/25 rm/35 rm/35 rm/16 rm/16 rm/16 rm/16 rm/16 rm/25 rm/25 rm/25 rm/25 rm/35 rm/35 rm/16 rm/16 rm/16 rm/16 rm/25 rm/25 rm/25 rm/25 rm/35 rm/35

26 28 30 31 32 34 36 38 40 44 47 31 33 34 36 37 39 41 43 45 48 52 37 38 40 42 43 45 47 50 53 56

518 662 854 1094 1334 1723 2059 2587 3163 4234 5194 518 662 854 1094 1334 1723 2059 2587 3163 4234 5194 662 854 1094 1334 1723 2059 2587 3163 4234 5194

1050 1150 1460 1700 2030 2350 2700 3300 3900 4850 6000 1210 1400 1550 1800 2150 2400 2850 3250 3850 4900 6100 1700 1950 2300 2600 3000 3350 4100 4800 5750 6700

300 350 500 600 750 1000

2 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil 2 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil

300 350 500 600 750 1000

300 350 500 600 750 1000

Note For longitudinally and crosswise water-tight cable type N2XS(FL)2Y with PE-copolymere coated aluminium. Further types and dimensions on request.

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 see page T 15.

N 19

XLPE-insulated Alu-conductor, single core, screened, longitudinally water-tight, PE-jacket

NA2XS(F)2Y 6/10 kV, 12/20 kV, 18/30 kV

Technical data
XLPE-insulated power cables to DIN VDE 0276 part 620, HD 620 S1 and IEC 60502 Temperature range during installation up to 208 C Operating temperature max. 908 C Short circuit temperature 2508 C (short circuit duration up to 5 sec.) Nominal voltages U0/U 6/10 kV, 12/20 kV, 18/30 kV Operating voltages for 6/10 kV = max. 12 kV 12/20 kV = max. 24 kV 18/30 kV = max. 36 kV Test voltages for 6/10 kV = 15 kV 12/20 kV = 30 kV 18/30 kV = 45 kV Minimum bending radius max. 15 x cable 1 Power ratings table see page T 35 f

Cable structure
Circular bare alu-conductor of stranded wires to HD 383 Inner semi-conducting coating Core insulation of cross-linked Polyethylene (XLPE), PE-compound DIX8 to HD 620.1 Outer extrusion of semi-conducting coating spliced with the insulation Tape of conductive material Tape of longitudinally water-tight material Screen of copper wires and one or two copper tape(s) applied helically Inner covering or tape lapping PE-outer jacket black, compound DMP2 to HD 620.1, jacket colour black Installation notes To guarantee an optimum on operating reliability the extruded semi-conductive layer is spliced with the insulation for long duration. For this reason we recommend a peeling tool for installation.

Application
Suitable for indoor installation and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switch-boards and power stations. The PE-outer jacket is resistant to high mechanical stress for laying the cables. This PE-jacket is not flame-resistant (does not conform the test method B, as per VDE 0472 part 804). To avoid the influence of the outer interferences, an adherent semi-conductive layer is extruded between the conductor and the VPE insulation and also a concentric copper conductor which guarantees the field-limitation and the resistance to the partial discharges # 2 pC by a measuring volt of 2 U0. See DIN VDE 0298 part 1. The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

Part No.

No. cores x cross-sec. n x mm2

Insulation thickness mm 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0 8,0

Screen crosssec. mm2 16 16 16 16 16 25 25 25 25 35 35 16 16 16 16 25 25 25 25 35 35 16 16 16 16 25 25 25 25 35 35

PEjacket thickness mm 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5

Outer 1 ca. mm

Cop. weight kg / km

Alu weight kg / km

Weigth ca. kg / km

Hohlpreis DM / 100 m Alu 0, Standardlange

AWGno.*)

NA2XS(F)2Y 6/10 kV 32600 1 x 35 32601 1 x 50 32602 1 x 70 32603 1 x 95 32604 1 x 120 32605 1 x 150 32606 1 x 185 32607 1 x 240 32608 1 x 300 32609 1 x 400 32610 1 x 500 NA2XS(F)2Y 12/20 kV 32611 1 x 50 32612 1 x 70 32613 1 x 95 32614 1 x 120 32615 1 x 150 32616 1 x 185 32617 1 x 240 32618 1 x 300 32619 1 x 400 32620 1 x 500 NA2XS(F)2Y 18/30 kV 32621 1 x 50 32622 1 x 70 32623 1 x 95 32624 1 x 120 32625 1 x 150 32626 1 x 185 32627 1 x 240 32628 1 x 300 32629 1 x 400 32630 1 x 500

rm/16 rm/16 rm/16 rm/16 rm/16 rm/25 rm/25 rm/25 rm/25 rm/35 rm/35 rm/16 rm/16 rm/16 rm/16 rm/25 rm/25 rm/25 rm/25 rm/35 rm/35 rm/16 rm/16 rm/16 rm/16 rm/25 rm/25 rm/25 rm/25 rm/35 rm/35

26 28 30 31 32 34 36 38 40 44 47 33 34 36 37 39 41 43 45 48 52 37 38 40 42 43 45 47 50 53 56

182 182 182 182 182 283 283 283 283 394 394 182 182 182 182 283 283 283 283 394 394 182 182 182 182 283 283 283 283 394 394

102 145 203 276 348 435 537 696 870 1160 1450 145 203 276 348 435 537 696 870 1160 1450 145 203 276 348 435 537 696 870 1160 1450

780 850 980 1080 1150 1280 1420 1630 1950 2350 2780 920 1030 1140 1250 1320 1570 1780 2100 2480 2900 1250 1500 1700 1800 2050 2150 2400 2700 3200 3550

300 350 500 600 750 1000

2 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil kcmil kcmil

300 350 500 600 750 1000

300 350 500 600 750 1000

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 see page T 15. Further types and dimensions on request.

Note For longitudinally and crosswise water-tight cable type N2XS(FL)2Y with PE-copolymere coated aluminium.

N 20

N2XSEY 3 x . . . 6/10 kV,

XLPE-insulated Cu-conductor, PVC-jacket

Technical data
Three core XLPE-insulated power cables to VDE 0273 and IEC 60502 Temperature range during installation up to 58 C Operating temperature max. 908 C Short circuit temperature core 2508 C screen 3508 C (duration) (short circuit duration up to 5 sec.) Nominal voltages U0/U 6/10 kV Operating voltages max. 12 kV Test voltages 15 kV Test voltages d. c. 48 kV Power rating to DIN VDE 0298 part 2 Minimum bending radius 15 x cable 1 Tests according to DIN VDE 0273 und IEC 60502 The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

Cable structure
Circular bare Cu-conductor of stranded wires to DIN VDE 0295 cl. 2 and IEC 60228 cl. 2 Inner semi-conducting coating Core insulation of cross-linked Polyethylene (XLPE), PE-compound 2XI1 to DIN VDE 0207 part 22 Outer extrusion of semi-conducting coating spliced with the insulation Tape of conductive material Screen of copper wires and one or two copper tape(s) applied helically 3 cores stranded in layer Extruded sheath over three cores PVC outer jacket red, compound YM5 to DIN VDE 0207 part 5, jacket colour red

Application
Because of its very low dielectric loss factor that remains constant over the entire operating range, a high-grade insulation material on the basis of highmolecular pure polyethylene of crosslinked structure proves very suitable for medium-voltage cables. High operational reliability is assured by the combination of both conducting layers in combination with the insulation. Suitable for installation in indoors and in cable ducts, outdoors as well as for laying on racks for industrial and switching systems and power plants. Limited use when buried in the earth if the PVC outer jacket could be damaged by high mechanical stress. Installation note The inner semi-conducting layer, core insulation and outer semi-conducting layer are co-extruded in one process, and thus the both semi-conducting layers are spliced very tightly. We therefore recommend the use of a stripping tool for installation work.

Part No.

No. cores x cross-sec. mm2 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185 3 x 240 3 x 300 rm/16 rm/16 rm/16 rm/16 rm/16 rm/16 rm/25 rm/25 rm/25 rm/25

Insulation thickness mm 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4

PVCjacket thickness mm 2,5 2,5 2,5 2,6 2,8 2,9 3,0 3,1 3,3 3,3

Screen cross-sec. mm2 16 16 16 16 16 16 25 25 25 25

Outer 1 ca. mm

Cop. weight kg / km 1046 1210 1670 2250 2995 3715 4635 5645 7274 9160

Weight ca. kg / km

AWGno.*)

34339 34340 34341 34342 34343 34344 34345 34346 34347 34348

43 48 50 54 58 61 65 68 74 79

2850 3300 3750 4650 5700 6700 7900 9200 11450 14450

300 350 500 600

4 2 1 2/0 3/0 4/0 kcmil kcmil kcmil kcmil

Power ratings and electrical characteristics


Cross-sec. mm2 laying in earth1) 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185 3 x 240 3 x 300 rm/16 rm/16 rm/16 rm/16 rm/16 rm/16 rm/25 rm/25 rm/25 rm/25 149 179 211 258 309 351 394 445 517 583 Power ratings laying in air2) 144 175 209 260 315 362 411 469 552 630 Conductor resistance 208 C Ohm / km 0,727 0,524 0,387 0,268 0,193 0,153 0,124 0,0991 0,0754 0,0601 Operating capacity mF / km 0,203 0,225 0,249 0,283 0,315 0,345 0,374 0,406 0,456 0,495 Effective resistance 908 C Ohm / km 0,928 0,669 0,494 0,343 0,247 0,197 0,160 0,129 0,0991 0,0803 Inductance per core mH / km 0,399 0,378 0,359 0,338 0,323 0,311 0,302 0,293 0,282 0,274

Conversion factors for laying in earth especially for laying in bundle form and other requirements are noted in DIN VDE 0298 part 2 and 0276 part 1000. Conversion factors for laying in air Air temperature 8 C 15 20 25 30 35 40 45 50 Conversion factor 1,12 1,08 1,04 1,00 0,96 0,91 0,87 0,82

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 see page T 15.
1)

2)

For ground thermal resistivity of 1 K ? m/W, laying depth 0,7 m, Ground temperature 208 C. EVU load grade 0,7. For laying in air. Air temperature 308 C. EVU load grade 1,0.

N 21

ESUY (H00V-D) and ESY Earth conductors


ESUY

ESY

Technical data ESUY (H00V-D)


Earthing cable of braid wires over core strands in adapted to DIN VDE 0283 part 3, and EN 61138, DIN 46438, DIN 46440 Conductor resistance at 208 C according DIN VDE 0283 part 100 Temperature range 58 C to +708 C Nominal voltage as per VDE 0105 part 1/5.75 Test voltage 2000 V Spark test (during winding) 16 mm2 to 35 mm2 5000 V 50 mm2 to 70 mm2 6000 V 95 mm2 to 240 mm2 8000 V Insulation resistance min. 20 MOhm x km Minimal bending radius approx. 12 x cable 1

Cable structure ESUY (H00V-D)


Bare copper, extra fine wire conductors, high flexible Braiding of bare copper wires over the stranded copper conductor PVC-jacket, transparent (glass clear), compound type TM2 according DIN VDE 0281 part 1

Application ESUY (H00V-D) ESY


These high flexible earth conductors are used for earthing of portable equipment and short-circuiting. These cables specially perform a protective function in repair live working of high voltage power supply company as EVU, in railway systems, failing current equipment, alternating current systems and in networks of transmission and distribution. Because of that these are designated as safety cables. These earthing cables offer special characteristics with low weights, high flexibility to a wide temperature range and the behavior in high temperature. The protective sheath over conductor assures the essential function for protection against the mechanical and chemical stresses. Features For these cable types no nominal voltages are mentioned, as these are: only used for earthing performances. Note For further requirements see European Norm EN 61230 and DIN VDE 0683 part 100: Live working Portable equipment for earthing and earthing

ESY
Bare copper, fine wire conductors Copper conductors of stranded wires PVC-jacket, transparent (glass clear), compound type TM2 according DIN VDE 0281 part 1

ESY
Earthing cable in adapted to DIN VDE 0283 part 3 and EN 61138, DIN 46438, DIN 46440 for further technical datas from conductor resistance see above ESUY (H00V-D)

Type ESUY (H00V-D), high flexible


Part No. 28930 28931 28932 28933 28934 28935 28936 28937 28938 28939 Conductor sizes mm2 16 25 35 50 70 95 120 150 185 240 Stranding x diameter 4200 x 0,07 3192 x 0,10 4480 x 0,10 6383 x 0,10 8918 x 0,10 12100 x 0,10 15300 x 0,10 19152 x 0,10 23580 x 0,10 30600 x 0,10 Outer 1 ca. mm 9,1 10,5 12,5 14,2 16,8 19,8 21,5 24,0 27,6 31,0 Cop. weight kg / km 194 280 415 585 820 1090 1360 1650 2150 2750 Weigth ca. kg / km 230 335 475 670 905 1220 1505 1940 2390 3090 AWGno.*) 6 4 2 1 2/0 3/0 4/0 300 kcmil 350 kcmil 500 kcmil

Type ESY, flexible


Part No. 28940 28941 28942 28943 28944 28945 28946 28947 Conductor sizes mm2 16 25 35 50 70 95 120 150 Stranding x diameter 525 x 0,20 798 x 0,20 1120 x 0,20 1617 x 0,20 2254 x 0,20 3087 x 0,20 3822 x 0,20 4802 x 0,20 Outer 1 ca. mm 8,5 10,0 12,5 14,0 17,2 19,5 22,8 25,4 Cop. weight kg / km 155 240 336 480 672 912 1152 1440 Weigth ca. kg / km 185 270 390 575 810 1080 1320 1680 AWGno.*) 6 4 2 1 2/0 3/0 4/0 300 kcmil

*) Note AWG sizes are approximate equivalent values. The actual cross-section is in mm2 see page T 15.

N 22

Photo: HELUKABEL

HELUKABEL presents at Baltic

It is important to know that for all exporters of machines and machinery plants as well as for measuring and control technique, HELUKABEL is certified according to the GOST-R terms of references for the usual electrical cables and wires in respect of Eastern European and Russian market.

N 23