Beruflich Dokumente
Kultur Dokumente
Data
38AH024-134
Commercial Air-Cooled
Condensing Units
50/60 Hz
20 to 130 Nominal Tons
(63 to 390 Nominal kW)
a38-4143ef
Features/Benefits
The 38AH condensing unit
offers the utmost in system
configuration and control
adaptability. Its premiumquality standard components
ensure durable, efficient, and
reliable operation.
The 38AH units offer high unit EERs
(Energy Efficiency Ratios). These units
provide greater efficiency than similar
units in the marketplace, which translates into year-round operating savings.
Latest safety standards for 38AH units
are assured through UL and UL, Canada, approvals.
38AH024-034
Form 38AH-11PD
Features/Benefits (cont)
Versatility
The 38AH Series condensing units
feature up to 4 compressors and 2 refrigerant circuits, and can be matched
with a wide variety of air-handling
units. All condensing unit circuits can
supply a single air handler or 2 separate air handlers.
Standard units have constant volume
control. A variable air volume (VAV)
option is available. The VAV units have
electric unloaders on the compressors
to closely match building loads. The
VAV option requires only a simple connection to a discharge air controller,
thereby saving installation time and
cost.
Durable construction
All 38AH units have weatherized
cabinets constructed of heavy-duty
galvanized steel prepainted with
corrosion-resistant baked enamel. Inside and outside surfaces are protected
to ensure long life and good looks. The
Reliability
The 38AH condensing units feature
time-proven, highly reliable 06D and
06E semi-hermetic compressors. Unloading capability is a standard feature
on each circuits lead compressor.
Each compressor has vibration isolators to provide quiet operation and
reduced component stress.
Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1,2
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Capacity Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-16
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17-19
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20-27
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28,29
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30-92
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93-97
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98-102
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .103-106
Typical Control Wiring Schematics. . . . . . . . . . . . . . . . . . . . . . . . . . .107-115
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .116-128
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129-131
*
a38-7054
Al
Cu
NFD
VAV
LEGEND
Aluminum
Copper
Non-Fused Disconnect
Variable Air Volume
Quality Assurance
Certified to ISO 9001:2000
Capacity ratings
38AH024-034 CAPACITY RATINGS 60 Hz
38AH CONDENSING
UNIT
024
028
034
AHRI
EER
IPLV
SST
SYSTEM
Net Capacity
EER
(Btuh)
222,000
9.8
240,000
9.6
250,000
10.2
268,000
9.4
282,000
9.6
290,000
9.4
324,000
9.4
332,000
9.5
LEGEND
Air Conditioning, Heating, and Refrigeration Institute
Energy Efficiency Ratio
Integrated Part Load Value
Saturated Suction Temperature
IPLV
9.4
9.7
10.3
9.5
9.5
9.3
9.2
8.9
IPLV
251,000
11.7
13.7
290,000
11.2
12.9
344,000
11.1
12.9
024
028
034
AHRI
EER
IPLV
wb
SST
016
024
028
024
028
034
028
034
AIR-HANDLING
UNIT AIRFLOW
L/s
2800
3800
4700
3800
4700
5650
4700
5650
Cfm
6,000
8,000
10,000
8,000
10,000
12,000
10,000
12,000
SYSTEM GROSS
SYSTEM GROSS CAPACITY
CONDENSING UNIT ONLY
CAPACITY
(High-Capacity 4-Row Coil)
GROSS CAPACITY
(Standard 3-Row Coil)
kW*
Btuh
kW*
Btuh
kW** Btuh EER IPLV
57.3
195,000
60.2
205,300
62.5
214,000
64.7
220,600
63.0 216,000 11.8 13.1
66.3
227,000
68.6
234,000
68.9
236,000
72.1
246,100
73.5
251,000
76.7
261,600
73.0 250,000 11.6 12.4
77.6
265,000
80.5
274,500
82.6
283,000
86.0
293,600
87.0 297,000 11.6 13.4
87.7
300,000
90.9
310,000
LEGEND
Air Conditioning, Heating, and Refrigeration Institute
Energy Efficiency Ratio
Integrated Part Load Value
Wet Bulb
Saturated Suction Temperature
CAPACITY
NOMINAL TONS
(60 Hz)
40
50
60
70
80
90
100
120
130
CAPACITY
NOMINAL TONS
(50 Hz)
35
41
50
61
69
78
87
100
111
10.7
10.5
10.5
10.1
10.1
10.2
10.4
10.5
10.2
10.8
10.7
10.8
10.3
10.6
10.6
10.9
10.8
10.6
13.0
13.0
13.3
12.6
12.5
13.4
13.8
13.6
12.5
13.4
13.2
13.9
12.8
12.6
14.0
14.3
14.0
12.9
LEGEND
AHRI Air Conditioning, Heating, and Refrigeration Institute
EER Energy Efficiency Ratio
IPLV Integrated Part Load Value
NOTES:
1. Ratings are based on 45 F (7.2 C) suction temperature and 95 F
(35 C) outside-air temperature, and include suction line losses.
2. Units are rated in accordance with AHRI standard 365.
910
Physical data
38AH024-134 UNITS, 60 Hz ENGLISH
UNIT 38AH
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)
Cu-Al Coil (standard)
Cu-Cu Coil (optional)
REFRIGERANT, TYPE*
Operating Charge, Typical (lb)
COMPRESSOR
(Qty) Model
No. Cylinders (per circuit)
Speed (rpm)
Oil Charge Per Circuit (pt)
Capacity Control Steps (%)
Unloader Setting (psig)
Load
Unload
CONDENSER FANS
(Qty) Dia (in.)
Nominal Hp
Airflow (cfm)
Speed (rpm)
Total Power (kW)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
Storage Cap. (lb)***
CONTROLS
Pressurestat (psig)
High Pressure
Open
Close
Low Pressure
Open
Close
Oil Pressure
Open
Close
FAN CYCLING CONTROLS
No. 2 Fan:
Temp Close (F)
Temp Open (F)
PRESSURE RELIEF
Location
Temperature (F)
CONNECTIONS (in. ODM)
Suction in. OD
Liquid in. OD
Hot Gas Bypass in. OD
Cu-Al
Cu-Cu
ODF
ODM
VAV
024
Ckt 1
20
028
Ckt 2
Ckt 1
034
Ckt 2
Ckt 1
Ckt 2
20
25
30
1760
1923
1820
1982
R-22
1880
2097
20
20
20
25
25
Reciprocating Semi-Hermetic
(1) 06DH824
(1) 06DA824
(1) 06DH328
(1) 06DA328
(1) 06DH328
(1) 06DA537
6
6
6
6
6
6
1750
1750
1750
1750
1750
1750
10
67**,33
67**,33
67**,33
Factory Installed
76
76
76
58
58
58
LEGEND
Copper Tubes with Aluminum Fins
Copper Tubes with Copper Fins (Optional)
Outside Diameter, Female
Outside Diameter, Male
Variable Air Volume
426 7
320 20
27 3
44 5
Manual Reset
6.0
8.8
70 3
60 3
Liquid Line, Suction Line, Compressor
210
1 3 /8
5/
8
5/
8
NOTES:
1. Certified dimensional drawings available on request.
2. Refer to Unloading Sequences tables, pages 119-121 for additional capacity step data.
*Typical operating charge with 25 ft of interconnecting piping. Operating charge is approximate for maximum system capacity. Unit is factory supplied with nitrogen holding charge.
Circuit A compressor is lead.
**Standard unit single suction pressure-actuated unloader on compressor no. 1.
VAV factory-installed option two electrically actuated unloaders on
compressor no. 1.
***Condenser 80% full of liquid R-22 at 120 F.
044
40
054
50
064
60
074
70
084
80
3259
3547
3309
3597
3565
3998
3812
4229
4057
4730
3250
3538
3290
3578
3780
4197
4000
4678
62
72
3530
3963
R-22
88
104
130
(4) A
250
17
(4) B
250
17
100
75
50
25
(4) A1 (4) A2
250
250
17
17
100
75
50
25
2...17
80.5
35
35
LEGEND
Copper Tubes with Aluminum Fins
Copper Tubes with Copper Fins (Optional)
Outside Diameter, Female
Outside Diameter, Male
Variable Air Volume
(4) A
250
17
Reciprocating Semi-Hermetic...1750
(6) B
(6) A
(6) B
(6) A
(6) B
265
265
275
275
299
21
21
21
21
19
100
100
100
79
84
86
58**
69**
71**
42
48
43
21
32
29
16**
14**
Reciprocating Semi-Hermetic...1750
(6) A1 (4) A2 (6) A1 (6) A2 (6) A1 (6) A2
265
250
275
265
299
275
21
17
21
21
19
21
100
100
100
80
82
81
61**
64**
62**
56
55
57
37
36
38
18**
19**
(6) A
299
19
(6) B
299
19
100
83
67**
50
33
17**
(6) A1 (6) A2
299
299
19
19
100
83
67**
50
33
17**
(4) 30
(6) 30
1.0
1.0
35,000
52,000
51,000
1140
1140
6.2
9.3
Enhanced Copper Tubes, Lanced Aluminum Fins
2...17
3...17
2...19
3...17
80.5
80.5
116.7
116.7
35
35
55
55
55
55
80
80
255 10
160 10
21 / 8
7/
8
5/
8
***On all 044-134 units, fans no. 3 and 4; also on 38AH074, 084 (dualcircuit units only) and 38AH094, 104, fans no. 5 and 6.
For optional single-circuit units, suction ODF is 25/8 in. and liquid
ODF is 11/8 inches. Single circuit units have a single suction line
and single liquid line. No field modification is required.
NOTES:
1. Certified dimensional drawings available on request.
2. Refer to Unloading Sequences tables, pages 119-121, for additional system capacity step data.
094
104
124
134
134B
NOMINAL CAPACITY (tons)
90
100
70
OPERATING WEIGHT WITH
REFRIGERANT (lb) (approx)
Cu-Al Coil (standard)
5088
5435
3630*
3630*
3630*
3877*
Cu-Cu Coil (optional)
5813
6160
4063*
4063*
4063*
4294*
SHIPPING WEIGHT WITH
COIL PROTECTION AND
SKID (lb) (approx)
Cu-Al Coil (standard)
5630
5990
3907*
3907*
3907*
4080*
Cu-Cu Coil (optional)
6355
6715
4340*
4340*
4340*
4497*
REFRIGERANT, TYPE
R-22
Operating Charge,
148
135
88
88
88
104
Typical (lb)
Qty of Circuits
2
2
1
1
1
1
COMPRESSOR Type...Rpm
(Quantity Cylinder)
Reciprocating Semi-Hermetic...1750
Compressor**
(6)A1 (4)A2 (6)B1 (6)A1 (4)A2 (6)B1 (6)B2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2
Model No. 06E
275 250 299 265 250 265 265 275 265 275 265 275 265 299 275
Oil Charge (pt)
21
17
19
21
17
21
21
21
21
21
21
21
21
19
21
Circuit Capacity %
55
45
47
53
50
50
45
55
(approx)
Capacity Control Steps
6
8
4
4
4
4
CONDENSER FANS
(6 Blade)
(Quantity) Dia (in.)
(6) 30
(6) 30
(4) 30
(4) 30
(4) 30
(6) 30
Nominal Hp
1.0
1.0
1.0
1.0
1.0
1.0
Airflow (cfm)
52,000
52,000
35,000
35,000
35,000
52,000
Speed (rpm)
1140
1140
1140
1140
1140
1140
Total Power (kW)
9.4
9.5
6.4
6.4
6.4
9.2
CONDENSER COIL
Enhanced Copper Tubes, Lanced Aluminum Fins
Rows...Fins per in.
3...17
3...17
3...17
3...17
3...17
2...19
Face Area (sq ft)
128.3
128.3
80.5
80.5
80.5
116.7
Storage Capacity
89
89
110
110
110
110
(lb per ckt) at 120 F
FAN CYCLING CONTROLS***
Close (psig)
255 10
Open (psig)
160 10
CONNECTIONS
Suction, ODF (in.)
21 / 8
21/8
25/8
25/8
25/8
25/8
7/
7/
Liquid, ODF (in.)
11/8
11/8
11/8
11/8
8
8
Hot Gas Bypass,
5/
5/
5/
5/
5/
5/
8
8
8
8
8
8
ODF (in.)
Cu-Al
Cu-Cu
ODF
ODM
VAV
LEGEND
Copper Tubes with Aluminum Fins
Copper Tubes with Copper Fins (Optional)
Outside Diameter, Female
Outside Diameter, Male
Variable Air Volume
124A
60
124B
60
134A
60
NOTES:
1. Unit 38AH124 consists of one 124A module and one 124B module. Unit 38AH134 consists of one 134A module and one 134B
module.
2. Certified dimensional drawings available on request.
3. Lead and lag circuits and compressors are as follows:
UNIT 38AH
LEAD CIRCUIT
Compressor, Lead
Compressor, Lag
LAG CIRCUIT
Compressor, Lead
Compressor, Lag
094
A
A1
A2
B
B1
104
124
134
A Module 124A Module 134A
A1
A1
A1
A2
A2
A2
B Module 124B Module 134B
B1
A1
A1
B2
A2
A2
024
Ckt 1
Ckt 2
Ckt 1
Ckt 2
70
88
106
798
872
826
899
R-22
18
853
951
23
Reciprocating Semi-Hermetic
(6) A
H824
(6) B
A824
2...748
3.6
17
(6) A
H328
(6) B
A328
(6) A
H328
4.7
100
67**
33
Propeller Type Direct Driven
(2) 762
.746
7882
19
1.55
Enhanced Copper Tubes, Lanced Aluminum Fins
2...748
3.6
17
LEGEND
Copper Tubes with Aluminum Fins
Copper Tubes with Copper Fins (Optional)
Outside Diameter, Female
Outside Diameter, Male
Variable Air Volume
*Typical operating charge with 7.6 m of interconnecting piping. Operating charge is approximate for maximum system capacity. Unit is
factory supplied with nitrogen holding charge.
Circuit A compressor is lead.
**Standard unit - single suction pressure actuated unloader on compressor no. 1.
VAV factory-installed option - two electronically actuated unloaders
on compressor no. 1.
***Condenser 80% full of liquid R-22 at 49 C.
034
Ckt 1
18
CONDENSER FANS
(Qty) Dia (mm)
Nominal kW
Airflow (L/s)
Speed (r/s)
Total Power (kW)
CONDENSER COIL
Rows...Fins per m
Face Area (sq m)
Storage Cap. (kg)***
FAN CYCLING CONTROLS
Close (C)
Open (C)
CONNECTIONS
Suction in. ODF
Liquid in. ODF
Hot Gas Bypass ODF (in.)
Cu-Al
Cu-Cu
ODF
ODM
VAV
028
Ckt 2
(6) B
A537
3...669
3.6
26
21 2
16 2
21 / 8
7/
8
5/
8
NOTES:
1. Certified dimensional drawings available on request.
2. Refer to Unloading Sequences tables, pages 119-121, for additional system capacity step data.
3. Equivalent connection values in mm are as follows:
in.
5/
8
7/
8
1 1 /8
2 1 /8
2 5 /8
mm
15.9
22.2
28.6
54.0
66.7
044
140
054
175
064
210
074
245
084
280
1480
1609
1501
1632
1617
1813
1729
1918
1840
2145
1474
1605
1492
1623
1714
1903
1814
2122
28
33
1600
1797
R-22
40
47
59
(4) A
250
8
(4) B
250
8
(4) A
250
8
100
75
50
25
(4) A1
250
8
(4) A2
250
8
100
75
50
25
Reciprocating Semi-Hermetic...29.2
(6) A1
(4) A2
(6) A1
(6) A2
(6) A1
(6) A2
265
250
275
265
299
275
8
10
10
10
10
9
100
100
100
80
82
81
61**
64**
62**
56
55
57
37
36
38
18**
19**
2...669
7.5
16
Reciprocating Semi-Hermetic...29.2
(6) B
(6) A
(6) B
(6) A
(6) B
265
265
275
275
299
10
10
10
10
9
100
100
100
79
84
86
58**
69**
71**
42
48
43
21
32
29
16**
14**
16
LEGEND
Copper Tubes with Aluminum Fins
Copper Tubes with Copper Fins (Optional)
Outside Diameter, Female
Outside Diameter, Male
Variable Air Volume
(6) A
299
9
(6) B
299
9
100
83
67**
50
33
17**
(6) A1
(6) A2
299
299
9
9
100
83
67**
50
33
17**
(4) 762
(6) 762
.746
.746
16520
24544
20472
19
19
6.2
9.3
Enhanced Copper Tubes, Lanced Aluminum Fins
2...669
3...669
2...782
3...669
7.5
7.5
10.8
10.8
16
16
25
25
25
25
36
36
1768 + 69
1103 69
21/8
7/
8
5/
8
For optional single-circuit units, suction ODF is 25/8 in. and liquid
ODF is 11/8 inches. Single circuit units have a single suction line and
single liquid line. No field modification is required.
NOTES:
1. Certified dimensional drawings available on request.
2. Refer to Unloading Sequences tables, pages 119-121, for additional system capacity step data.
3. Equivalent connection values in mm are as follows:
in.
5/
8
7/
8
1 1 /8
2 1 /8
2 5 /8
mm
15.9
22.2
28.6
54.0
66.7
094
104
316
Cu-Al
Cu-Cu
ODF
ODM
VAV
134
350
124B
210
134A
210
134B
245
2308
2637
2465
2794
1647*
1843*
1647*
1843*
1647*
1843*
1759*
1843*
2554
2883
1717
3046
1860*
1928*
1860*
1968*
1860*
1968*
1860*
2040*
67
61
40
40
40
47
R-22
(6)A1
275
10
(4)A2
250
8
55
(6)B1
299
9
45
(6)A1
265
10
(4)A2
250
8
(6) 762
.746
24,544
19
9.4
3...669
1139
Reciprocating Semi-Hermetic...29.2
(6)B1 (6)B2 (6)A1 (6)A2 (6)A1
265 265 275 265 275
10
10
10
10
10
47
53
(6)A2
265
10
40
(6)A2
265
9
(6)A1
299
10
50
45
55
(4) 762
.746
16,254
19
6.4
(6) 762
.746
24.544
19
9.2
3...669
7.5
2...78219
10.8
50
50
50
2 5 /8
1 1 /8
5/
8
25/8
11/8
5/
8
25/8
11/8
5/
8
(6) 762
(4) 762
(4) 762
.746
.746
.746
24,544
46,250
16,250
19
19
19
9.5
6.4
6.4
Enhanced Copper Tubes, Lanced Aluminum Fins
3...669
3...669
3...669
139
7.5
7.5
40
(6)A1
275
10
50
50
1958 69
1103 69
21 / 8
7/
8
5/
8
LEGEND
Copper Tubes with Aluminum Fins
Copper Tubes with Copper Fins (Optional)
Outside Diameter, Female
Outside Diameter, Male
Variable Air Volume
10
124
124A
210
21/8
7/
8
5/
8
25/8
11/8
5/
8
mm
15.9
22.2
28.6
54.0
66.7
024
028
Circuit 1
Circuit 2
Circuit 1
Circuit 1
Circuit 2
18
21
25
1760
1923
1820
1982
R-22
1880
2097
20
20
1...06DH824
6
1450
1...06DA824
6
1450
100
67*
33
100
LEGEND
Copper Tubes with Aluminum Fins
Copper Tubes with Copper Fins (Optional)
Factory-Installed Option
Outside Diameter, Female
Outside Diameter, Male
Variable Air Volume
034
Circuit 2
76
58
30
1.0
16,700
2...19
39.20
37.7
20
20
Reciprocating Semi-Hermetic
1...06DH328
1...06DA328
6
6
1450
1450
10
25
25
1...06DH328
6
1450
1...06DA537
6
1450
100
100
100
67
67*
33**
33
Factory Installed
76
76
58
58
Propeller Type Direct Driven
2...950
30
1.0
16,700
3100
Enhanced Copper Tubes, Aluminum Lanced Fin
2...19
39.20
37.7
100
30
1.0
15,700
3...17
39.20
56.6
426 7
320 20
27 3
44 5
Manual Reset
6.0
8.8
70 3
60 3
Fusible Plug
Liquid Line, Suction Line, Compressor
210
1 3 /8
5/
8
*Typical operating charge with 25 ft of interconnecting piping. Operating charge is approximate for maximum system capacity. Unit is factory supplied with nitrogen holding charge.
Standard unit single pressure-actuated suction unloader on compressor no. 1.
**VAV FIOP double electrically actuated unloaders on compressor
no. 1.
Storage capacity of condenser coil with coil 80% full of liquid R-22 at
120 F.
11
044
35
3259
3547
3250
3538
62
(4) A
250
17
074
61
3812
4229
3780
4197
084
69
4057
4730
4000
4678
130
(6) A
299
19
4...30
6...30
52,000
35,000
950
950
6.2
9.3
Enhanced Copper Tubes, Lanced Aluminum Fins
2...17
3...17
2...19
80.5
80.5
116.7
35
55
55
2...17
80.5
35
(6) B
299
19
51,000
3...17
116.7
80
255 10
160 10
2 1 /8
5/
LEGEND
Copper Tubes with Aluminum Fins
Copper Tubes with Copper Fins (Optional)
Outside Diameter, Female
Outside Diameter, Male
Variable Air Volume
12
064
50
3565
3998
3530
3963
72
88
104
Reciprocating Semi-Hermetic...1460
(4) A
(6) B
(6) A
(6) B
(6) A
(6) B
250
265
265
275
275
299
17
21
21
21
21
19
4
(4) B
250
17
054
41
3309
3597
3290
3578
5/
Ckt A
5/
7/
2 1 /8
8
Ckt B
7/
5/
***On all 044-134 units, fan no. 3 and 4; also on 38AH074,084 (dualcircuit units only) and 38AH094,104, fans no. 5 and 6.
For single-circuit units, suction ODF is 25/8 in. and liquid ODF is
11/8 inches. Single circuit units have a single suction line and single
liquid line. No field modification is required.
NOTE: Certified dimensional drawings available on request.
094
104
78
Cu-Al
Cu-Cu
ODF
ODM
VAV
124
134
87
124A
50
124B
50
134A
50
134B
61
5088
5813
5435
6160
3630*
4063*
3630*
4063*
3630*
4063*
3877*
4294*
5630
6355
5990
6715
3907*
4340*
3907*
4340*
3907*
4340*
4080*
4497*
R-22
148
2
135
88
88
88
104
2
1
1
1
1
Reciprocating Semi-Hermetic...1460
(6)A1 (4)A2 (6)B1 (6)A1 (4)A2 (6)B1 (6)B2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2
275 250 299 265 250 265 265 275 265 275 265 275 265 299 275
21
17
19
21
17
21
21
21
21
21
21
21
21
19
21
55
45
47
53
50
50
45
55
6
8
4
4
4
4
6...30
52,000
950
9.4
3...17
128.3
6...30
4...30
4...30
52,000
35,000
35,000
950
950
950
9.5
6.4
6.4
Enhanced Copper Tubes, Lanced Aluminum Fins
3...17
3...17
3...17
128.3
80.5
80.5
178
178
110
4...30
35,000
950
6.4
6...30
52,000
950
9.2
3...17
80.5
2...19
116.7
110
110
110
2 5 /8
1 1 /8
5/
8
2 5 /8
1 1 /8
5/
8
2 5 /8
1 1 /8
5/
8
255 10
160 10
21 / 8
7/
8
5/
8
LEGEND
Copper Tubes with Aluminum Fins
Copper Tubes with Copper Fins (Optional)
Outside Diameter, Female
Outside Diameter, Male
Variable Air Volume
2 1 /8
7/
8
5/
8
2 5 /8
1 1 /8
5/
8
NOTES:
1. Unit 38AH124 consists of one 124A module and one 124B module. Unit 38AH134 consists of one 134A module and one 134B
module.
2. Certified dimensional drawings available on request.
3. Lead and lag circuits and compressors are as follows:
UNIT 38AH
094 104
124
134
LEAD CIRCUIT
A
A Module 124A Module 134A
Compressor, Lead A1 A1
A1
A1
Compressor, Lag
A2 A2
A2
A2
LAG CIRCUIT
B
B Module 124B Module 134B
Compressor, Lead B1 B1
A1
A1
Compressor, Lag B2
A2
A2
Circuit only has one compressor.
13
14
LEGEND
Copper Tubes with Aluminum Fins
Copper Tubes with Copper Fins (Optional)
Factory-Installed Option
Outside Diameter, Female
Outside Diameter, Male
Variable Air Volume
024
028
Circuit 1
Circuit 2
Circuit 1
034
Circuit 2
Circuit 1
Circuit 2
63
73
87
798
872
826
899
R-22
853
951
9.10
9.10
1...06DH824
6
24.3
1...06DA824
6
24.3
100
67*
33
100
524
400
762
1.0
7870
2...748
3.64
17.4
9.10
9.10
Reciprocating Semi-Hermetic
1...06DH328
1...06DA328
6
6
24.3
24.3
4.73
11.40
11.40
1...06DH328
6
24.3
1...06DA537
6
24.3
100
100
100
67
67*
33**
33
Factory Installed
524
524
400
400
Propeller Type Direct Driven
2...16
762
762
1.0
1.0
7870
7400
3100
Enhanced Copper Tubes, Aluminum Lanced Fin
2...748
3...670
3.64
3.64
17.4
26.0
100
2940 50
2200 140
185 20
300 35
Manual Reset
42
62
21.1 1.6
15.6 1.6
Fusible Plug
Liquid Line, Suction Line, Compressor
100
1 3 /8
5/
8
*Typical operating charge with 7.6 m of interconnecting piping. Operating charge is approximate for maximum system capacity. Unit is factory supplied with nitrogen holding charge.
Standard unit single pressure-actuated suction unloader on compressor no. 1.
**VAV FIOP double electrically actuated unloaders on compressor
no. 1.
Storage capacity of condenser coil with coil 80% full of liquid R-22 at
48.8 C.
044
123
1480
1609
1474
1605
28.1
(4) A
250
8.0
064
175
1617
1813
1601
1798
074
214
1729
1918
1715
1904
32.7
39.9
47.2
Reciprocating Semi-Hermetic...24.3
(4) A
(6) B
(6) A
(6) B
(6) A
(6) B
250
265
265
275
275
299
8.0
9.9
9.9
9.9
9.9
9.0
4
(4) B
250
8.0
084
242
1840
2145
1814
2122
58.9
(6) A
299
9.0
(6) B
299
9.0
4...762
6...762
24 500
24 100
16 500
15.8
15.8
6.2
9.3
Enhanced Copper Tubes, Lanced Aluminum Fins
2...669
3...669
2...782
3...669
7.48
7.48
10.84
10.84
16
25
25
36
2...669
7.48
16
1758 69
1103 69
2 1 /8
5/
054
144
1501
1632
1492
1623
LEGEND
Copper Tubes with Aluminum Fins
Copper Tubes with Copper Fins (Optional)
Outside Diameter, Female
Outside Diameter, Male
Variable Air Volume
5/
7/
Ckt A
5/
2 1 /8
8
Ckt B
7/
5/
***On all 044-134 units, fan no. 3 and 4; also on 38AH074,084 (dualcircuit units only) and 38AH094,104, fans no. 5 and 6.
For single-circuit units, suction ODF is 25/8 in. and liquid ODF is
11/8 inches. Single circiut units have a single suction line and single
liquid line. No field modification is required.
NOTES:
1. Certified dimensional drawings available on request.
2. Equivalent connection values in mm are as follows:
in.
5/
8
7/
8
1
1 /8
1
2 /8
2 5 /8
mm
15.9
22.2
28.6
54.0
66.7
15
094
104
274
Cu-Al
Cu-Cu
ODF
ODM
VAV
134
305
124B
175.5
134A
175.5
134B
214.5
2308
2637
2465
2794
1647*
1843*
1647*
1843*
1647*
1843*
1759*
1843*
2554
2883
2717
3046
1860*
1968*
1860*
1968*
1860*
1968*
1851*
2040*
R-22
67.1
2
61.2
40
40
40
47.2
2
1
1
1
1
Reciprocating Semi-Hermetic...24.3
(6)A1 (4)A2 (6)B1 (6)A1 (4)A2 (6)B1 (6)B2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2
275 250 299 265 250 265 265 275 265 275 265 275 265 299 275
10
8
9
10
8
10
10
10
10
10
10
10
10
9
10
55
45
47
53
50
50
45
55
6
8
4
4
4
4
6...762
24 544
15.8
9.4
3...669.3
11.9
6...762
4...762
4...762
24 544
16 520
16 520
15.8
15.8
15.8
9.5
6.4
6.4
Enhanced Copper Tubes, Lanced Aluminum Fins
3...669.3
3...669.3
3...669.3
11.9
7.5
7.5
81
81
50
4...762
16 520
15.8
6.4
6...762
24 544
15.8
9.2
3...669.3
7.5
2...781.6
10.8
50
50
50
2 5 /8
1 1 /8
5/
8
2 5 /8
1 1 /8
5/
8
2 5 /8
1 1 /8
5/
8
1758 69
1103 69
21 / 8
7/
8
5/
8
LEGEND
Copper Tubes with Aluminum Fins
Copper Tubes with Copper Fins (Optional)
Outside Diameter, Female
Outside Diameter, Male
Variable Air Volume
16
124
124A
175.5
2 1 /8
7/
8
5/
8
2 5 /8
1 1 /8
5/
8
mm
15.9
22.2
28.6
54.0
66.7
FACTORY-INSTALLED OPTION
X
X
X
X
X
X
X
X
X
X
X
FIELD-INSTALLED ACCESSORY
X
X
X
X
X
X
X
X
X
X
X
X
X
LEGEND
NFD Non-Fused Disconnect
VAV Variable Air Volume
*See the Unloader, Accumulator, and NFD Factory-Installed Option Availability
table for more detailed information.
Factory-installed options
Enviro-Shield condenser options are available to
match coil protection to site conditions for optimum
durability. See the Condenser Coil Options table on
page 19 and refer to the Application Data for selection
guidance. Consult your Carrier representative for further
information.
VAV (variable air volume) control box modification makes the condensing unit compatible with VAV controller. This option includes factory-installed accumulators
and electric unloaders on the compressors as follows:
1 38AH044
2 38AH024-034,054-084,104
3 38AH094
4 38AH124,134 (2 per module)
Standard dual circuit with NFD (sizes 044-104
only) includes factory-installed non-fused disconnect
switch.
Standard dual circuit with NFD and VAV (sizes
044-104 only) includes factory-installed accumulators,
wiring, electric unloaders, and non-fused disconnect
switch.
Single-circuit (sizes 044-084 only) includes factoryinstalled accumulators and all piping and wiring required
to make the unit single circuit.
Single-circuit with VAV (sizes 044-084 only)
includes piping, wiring, and electric unloaders on the
compressors (one on size 044 and 2 on sizes 054-084) to
make the unit single circuit, VAV-ready. This option also
includes factory-installed accumulators.
Field-installed accessories
Motormaster V 20 F low-ambient controls controls outdoor-fan motor operation to maintain the correct
head pressure at low outdoor ambient temperatures. Only
one low ambient temperature kit is required per unit.
Gage panel package provides a panel-mounted suction
and a discharge pressure gage for the refrigerant circuit.
Transformer relay package (sizes 044-134 only) for
a remote-control (24-v) thermostat. One 2-stage thermostat is required for use with the relay package.
17
Unloader conversion kit allows you to convert factoryinstalled pressure unloaders to electric unloading.
Compressor grille package (sizes 044-134 only)
protects the compressor area after the unit is installed.
Condenser coil grille package (sizes 044-134 only)
protects the condenser area after the unit is installed.
Accumulator (sizes 024-084 only) should be used on
any VAV application or any CV unit separated by 75 ft or
more from indoor coil to minimize risk of liquid slug
entering compressor. One accumulator needed per refrigerant circuit.
Hot gas bypass kit allows additional capacity reduction
for unit and prevention of indoor coil freezing. Careful
attention should be placed on system oil management.
PU
1
1
1
AA
EU
ACC
PU
FA
ACC
2
2
2
2
2
4
4
EU
1
2
2
2
2
4
4
NFD
NFD
PU
AC*
EU
ACC
2
PU
1
1
1
1
1
2
2
KA
EU
ACC
NFD
NFD
1
1
1
1
1
2
2
LEGEND
Standard Unit, Dual Circuit (Sizes 024-034)
JA
Standard Unit, VAV (Sizes 024-034)
KA
Accumulator
Standard Unit, VAV (Sizes 044-104)
LA
Single Circuit (Sizes 044-084);
Dual Module Unit (Sizes 124-134)
NFD
Electric Unloader
PU
Single ckt and VAV (Sizes 044-084);
VAV
Dual Module Unit, VAV (Sizes 124-134)
- Standard Unit, NFD (Sizes 044-104)
NFD
PU
EU
1
2
2
2
2
3
2
BA
ACC
2
2
2
2
2
2
2
NFD
PU
1
1
1
1
1
2
2
EU
DA
ACC
2
2
2
2
2
4
4
NFD
PU
OPTION CODE
LA
EU
ACC
1
2
2
2
2
2
2
2
2
2
4
4
4
4
NFD
1
1
1
1
1
2
2
PU
1
1
1
1
1
2
2
EU
HA
ACC
2
2
NFD
1
1
1
1
1
1
1
PU
EU
1
2
2
2
2
3
2
JA
ACC
2
2
2
2
2
2
2
NFD
1
1
1
1
1
1
1
18
PU
1
1
1
1
1
2
2
OPTION CODE
-EU
ACC
Cu
E-Coated
Enviro-Shield
Pre-Coated
Standard
Mild
Coastal
ENVIRONMENT
Moderate
Severe
Coastal
Coastal
Industrial
Combined
Industrial/Coastal
X
X
X
X
LEGEND
Aluminum
Copper
Epoxy Coating Applied to Entire Coil Assembly
Family of Coil Protection Options
Epoxy Coating Applied to Fin Stock Material
19
20
578
[262]
610
[277]
602
[273]
634
[288]
610
[277]
657
[298]
632
[287]
667
[302]
659
[299]
693
[314]
667
[303]
718
[326]
263
[119]
309
[140]
267
[121]
313
[142]
288
[131]
345
[156]
3
288
[131]
338
[153]
292
[132]
342
[155]
315
[143]
377
[171]
A Dim.
in.
[mm]
40.00
[1016]
43.00
[1092]
39.25
[997]
42.25
[1073]
41.00
[1041]
44.00
[1117]
32.75
[832]
B Dim.
in.
[mm]
CENTER OF
GRAVITY
1760
[798]
1923
[872]
1820
[824]
1982
[899]
1880
[853]
2097
[951]
TOTAL
UNIT WT
lb [kg]
NOTES:
1. There must be 4 ft [1220 mm] for service and for unrestricted airflow
on all sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air space above unit.
3. C in the package number indicates copper coils.
4. Dimensions in [ ] are in millimeters.
5. The approximate operating weight of the unit is shown above.
6. Certified dimensional drawing is available on request.
034C
034
028C
028
024C
024
38AH
UNIT
38AH024-034 UNITS
Dimensions
a38-7055.eps
LEGEND
Mounting
Society of Automotive Engineers
SINGLE CIRCUIT,
ft-in. [mm]
0-25/8 [67]
0-11/8 [29]
1-105/16 [567]
1-105/16 [567]
2-5/8 [626]
2-111/8 [892]
NOTES:
1. The approximate operating weight of the unit is:
38AH044
3259 lb (1480 kg)
38AH044C
3547 lb (1609 kg)
38AH054
3309 lb (1501 kg)
38AH054C
3597 lb (1632 kg)
38AH064
3565 lb (1617 kg)
38AH064C
3998 lb (1813 kg)
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
MTG
SAE
DESCRIPTION
DUAL CIRCUIT,
ft-in. [mm]
Suction Connection(s)
0-21/8 [54]
Liquid Connection(s)
0-7/8 [22]
Suction C
2-11/16 [627]
Liquid D
1-101/16 [561]
Suction (Ckt A)
1-713/16 [503]
Suction (Ckt B)
2-5/8 [626]
Liquid (Ckt A)
2-53/4 [756]
Liquid (Ckt B)
2-105/8 [879]
4-3/16 [1224]
3-21/2 [978]
3-3 [991]
3-21/2 [978]
3-33/16 [995]
054
054C
064
064C
4-5/8 [1235]
4-1/2 [1232]
4-3/8 [1229]
4-9/16 [1234]
3-31/8 [994]
044C
4-1/2 [1232]
UNIT 38AH
DIMENSIONS
064
054
044
V-Ph-Hz
230-3-50
208/230-3-60
380/460/575-3-60
346/380-415/3/50
208/230-3-60
380/460/575-3-60
346-380/415-3-50
208/230-3-60
380/460/575-3-60
346-380/415-3-50
a38-7056
21
QTY
1
1
1
1
1
1
1
2
1
1
22
SINGLE CIRCUIT,
ft-in. [mm]
0-25/8 [67]
0-11/8 [29]
1-105/16 [567]
1-105/16 [567]
2-5/8
[626]
2-111/8 [892]
NOTES:
1. The approximate operating weight of the unit is:
38AH074
3812 lb [1729 kg]
38AH074C
4229 lb [1918 kg]
38AH084
4057 lb [1840 kg]
38AH084C
4730 lb [2145 kg]
LEGEND
MTG Mounting
SAE Society of Automotive Engineers
DUAL CIRCUIT,
DESCRIPTION
ft-in. [mm]
Suction Connection(s) 0-21/8 [54]
Liquid Connection(s)
0-7/8
[22]
Suction C
2-11/16 [627]
Liquid D
1-101/16 [561]
Suction (Ckt A)
1-713/16 [503]
Suction (Ckt B)
2-5/8
[626]
Liquid (Ckt A)
2-53/4 [756]
Liquid (Ckt B)
2-105/8 [879]
4.
3.
2.
38AH
UNIT
074
074C
084
084C
DIMENSION Y
ft-in. [mm]
3-31/8 [994 mm]
3-35/8 [1006 mm]
3-3
[991 mm]
3-311/16 [1008 mm]
084
074
38AH UNIT
SIZE
230-3-60
460-3-60
575-3-60
380-3-60
346-380/415-3-50
208/230-3-60
460-3-60
575-3-60
380-3-60
346-380/415-3-50
V-Ph-Hz
DIAMETER,
in. [mm]
21/2 [63.5]
21/2 [63.5]
21/2 [63.5]
35/8 [92.0]
35/8 [92.0]
35/8 [92.0]
35/8 [92.0]
21/2 [63.5]
35/8 [92.0]
35/8 [92.0]
2
1
1
1
1
2
1
1
1
1
QTY
DIMENSION X
ft-in. [mm]
4-813/16 [1443 mm]
-81/8 [1425 mm]
4-9
[1448 mm]
4-8
[1422 mm]
DIMENSIONS
Dimensions (cont)
a38-7080
TOTAL WEIGHT
lb [kg]
044
044C
054
054C
064
064C
074
074C
084
084C
3259 [1480]
3547 [1609]
3309 [1501]
3597 [1632]
3565 [1617]
3998 [1813]
3812 [1729]
4229 [1918]
4057 [1840]
4730 [2145]
A
939 [426]
1013 [460]
964 [437]
1034 [469]
1018 [462]
1125 [510]
1146 [520]
1272 [577]
1220 [553]
1425 [646]
D
732 [332]
802 [364]
742 [337]
814 [369]
771 [350]
879 [399]
903 [410]
1035 [470]
961 [436]
1159 [526]
23
24
A
1114 [505]
1273 [577]
OPERATIONAL CORNER
WEIGHTS lb [kg]
B
C
2192 [994]
1182 [536]
2504 [1136]
1350 [612]
D
601 [273]
686 [311]
35/8 [92]
460-575-380-3-60
LEGEND
Mounting
Society of Automotive Engineers
DIMENSIONS
ft-in. [mm]
X
Y
5-6 [1676]
2-7 [787]
5-6 [1676]
2-7 [787]
DIMENSIONS
1
2
346-380/415-3-50
208/230-3-60
QUANTITY
DIAMETER
in. [mm]
35/8 [92]
35/8 [92]
V-Ph-Hz
NOTES:
1. The approximate operating weight of the unit is:
38AH094 5088 lb [2308 kg]
38AH094C 5813 lb [2637 kg]
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
MTG
SAE
094
094C
38AH
UNIT
094
38AH
UNIT
094
094C
38AH
UNIT
CORNER WEIGHTS
38AH094 UNIT
Dimensions (cont)
a38-7081
2-91/2 [851]
208/230-3-60
380-460-575-3-60
346-380/415-3-50
104
DIAMETER,
in. [mm]
35/8 [92.0]
35/8 [92.0]
35/8 [92.0]
2
1
1
QTY
NOTES:
1. The approximate operating weight of the unit is:
38AH-104--5435 lb [2465 kg]
38AH-104--C
6160 lb [2794 kg]
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft [1524 mm]
Sides 6 ft [1829 mm]
LEGEND
MTG Mounting
SAE Society of Automotive Engineers
V-Ph-Hz
38AH UNIT
SIZE
5-3 [1600]
104C
104
38AH
UNIT
DIMENSIONS
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting
unit to spring isolators. If spring isolators are used, a
perimeter support channel between the unit and the
isolators is recommended.
4. Two 35/8 in. [92-mm] diameter holes are recommended for parallel conductors on 208/230-v units.
5. C in the package number indicates copper coils.
38AH104 UNIT
2423 [1099]
1476 [670]
856 [388]
1405 [637]
104C
104
CORNER WEIGHTS
a38-7082
25
26
1030 [467]
1137 [516]
1037 [470]
1144 [519]
889 [403]
779 [353]
894 [406]
785 [356]
124B
124A
38AH UNIT
SIZE
a38-7083
LEGEND
Mounting
Society of Automotive Engineers
DIAMETER,
in. [mm]
21/2 [63.5]
21/2 [63.5]
35/8 [92.0]
21/2 [63.5]
21/2 [63.5]
35/8 [92.0]
2
1
1
2
1
1
QTY
NOTES:
1. The approximate operating weight of the unit is:
38AH124 7260 lb [3293 kg]
38AH124C 8126 lb [3686 kg]
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft [1524 mm]
Sides 6 ft [1829 mm]
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting
unit to spring isolators. If spring isolators are used, a
MTG
SAE
208/230-3-60
380-460-575-3-60
346-380/415-3-50
208/230-3-60
380-460-575-3-60
346-380/415-3-50
V-Ph-Hz
124A
124B
124A-C
124B-C
38AH UNIT
MODULE
CORNER WEIGHTS
8.
7.
6.
5.
4.
38AH124 UNIT
124A
124B
124A-C
124B-C
38AH UNIT
MODULE
X
4-15/8 [1260]
4-15/8 [1260]
DIMENSIONS
ft-in. [mm]
Y
K
3-21/8 [968]
4-15/8 [1260]
3-27/8 [986]
4-15/8 [1260]
DIMENSIONS
3-21/8 [968]
3-27/8 [986]
Dimensions (cont)
134B
134A
DIAMETER,
in. [mm]
21/2 [63.5]
21/2 [63.5]
35/8 [92.0]
21/2 [63.5]
21/2 [63.5]
35/8 [92.0]
35/8 [92.0]
2
1
1
2
1
1
1
QTY
NOTES:
1. The approximate operating weight of the unit is:
38AH134 7507 lb [3405 kg]
38AH134C 8357 lb [3791 kg]
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft [1524 mm]
Sides 6 ft [1829 mm]
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting
unit to spring isolators. If spring isolators are used, a
MTG
SAE
208/230-3-60
380-460-575-3-60
346-380/415-3-50
208/230-3-60
460-575-3-60
380-3-60
346-380/415-3-50
V-Ph-Hz
LEGEND
Mounting
Society of Automotive Engineers
38AH UNIT
MODULE
a38-7084
27
8.
7.
6.
5.
4.
38AH134 UNIT
3-27/8 [986]
4-15/8 [1260]
134B
134B-C
X
4-15/8 [1260]
4-81/8 [1425]
4-87/8 [1443]
DIMENSIONS
ft-in. [mm]
Y
K
3-21/8 [968]
134A-C
134A
38AH UNIT
MODULE
DIMENSIONS
3-33/4 [1006]
3-31/8 [993]
Selection procedure
To select 38AH024-034 units English:
NOTE: See the Performance Data section for combination
ratings for 38AH024-034 units and matching 40RM air
handlers. If the 38AH units are matched with 39 series air
handlers, use the Carrier Electronic Catalog AHUBuilder
software package for combination ratings. If the 10RT DX
(direct expansion) water coolers are used, determine the performance by cross-plotting the condensing unit performance
found in the Performance Data section this book against the
10RT DX performance in the 10RT DX product data book.
If the 38AH condensing units are matched with 2 independent 40RM units, cross-plot for performance ratings or contact Carrier Application Engineering for assistance.
I. Determine cooling load, evaporator-air temperature and quantity.
Given:
Total Cooling Capacity
Required (TC) . . . . . . . . . . . . . . .235,000 Btuh
Sensible Heat Capacity
Required (SHC) . . . . . . . . . . . . . .185,000 Btuh
Temperature Air Entering
Condenser (Edb) . . . . . . . . . . . . . . . . . . . .95 F
Temperature Air Entering
Evaporator (db/wb) . . . . . . . . 80 F db, 67 F wb
Evaporator Air Quantity. . . . . . . . . . . . . 8000 cfm
External Static Pressure . . . . . . . . . . . .0.80 in. wg
Length of Interconnecting
Refrigerant Piping . . . . . . . . . . . . .30 ft (Linear)
II Select
condensing
unit
air-handler
combination.
For this example, select a 38AH024 matched
with a 40RM024. (See Combination Ratings table
on page 39.) This 38AH024/40RM024 condensing unit-air handler combination provides 237,200
Btuh of total cooling capacity and 188,600 Btuh of
sensible capacity at the given conditions. If other
temperatures or airflow values are required, interpolate the values from the combination ratings.
III Determine sizes of liquid and suction lines.
Enter the Refrigerant Piping Requirements table on
page 122. The sizes shown are based on a linear
length of pipe. For this example, note in the linear
length column that the proper pipe size is 5/8 in. for
the liquid lines and 13/8 in. for the suction lines.
28
29
Performance data
CONDENSING UNIT RATINGS, 60 Hz ENGLISH
38AH024
38AH034
SST
(F)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
20
25
30
35
40
45
50
38AH028
SST
(F)
20
25
30
35
40
45
50
30
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
SST
(F)
20
25
30
35
40
45
50
kW
SDT
SST
TC
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
LEGEND
Compressor Power
Saturated Discharge Temperature at Compressor (F)
Saturated Suction Temperature (F)
Gross Cooling Capacity (1000 Btuh)
38AH044
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
305.0
30.2
107.0
348.0
31.8
108.0
392.0
33.5
109.0
439.0
35.0
110.0
488.0
36.5
112.0
540.0
37.9
114.0
596.0
39.3
116.0
85
357.0
36.4
111.0
407.0
38.4
111.0
458.0
40.4
113.0
512.0
42.4
115.0
568.0
44.5
116.0
627.0
46.5
119.0
688.0
48.6
121.0
115
212.0
32.6
136.0
250.0
35.3
137.0
291.0
38.1
138.0
332.0
40.6
139.0
376.0
43.1
140.0
422.0
45.6
142.0
469.0
48.0
143.0
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
115
261.0
39.5
141.0
303.0
42.7
141.0
347.0
45.8
142.0
395.0
48.9
143.0
444.0
51.9
144.0
496.0
55.0
146.0
38AH064
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
567.1
57.2
108.0
634.2
60.3
110.0
705.5
63.7
111.0
778.8
66.9
113.0
856.3
70.3
115.0
939.9
73.8
118.0
1026.7
77.3
120.0
115
444.3
62.8
137.0
505.2
67.3
138.0
566.1
71.7
139.0
631.2
76.3
141.0
699.3
81.1
143.0
769.5
85.9
145.0
843.9
90.8
147.0
115
513.3
74.7
142.0
581.8
79.6
142.0
653.5
84.8
143.0
730.4
90.0
144.0
810.4
95.4
145.0
893.5
101.0
147.0
980.8
106.7
149.0
38AH084
38AH054
SST (F)
SST (F)
85
439.0
44.3
109.0
496.0
46.7
111.0
555.0
49.1
112.0
616.0
51.6
114.0
682.0
54.1
116.0
749.0
56.6
118.0
822.0
59.2
120.0
115
331.0
48.7
139.0
380.0
52.2
139.0
431.0
55.9
141.0
485.0
59.5
142.0
541.0
63.1
144.0
600.0
66.9
146.0
662.0
70.6
148.0
SST (F)
20
25
30
35
40
45
50
kW
SDT
SST
TC
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
646.3
67.9
112.0
725.2
71.6
113.0
810.4
75.4
114.0
898.7
79.1
115.0
991.2
83.1
117.0
1087.8
87.2
119.0
1188.6
91.6
122.0
LEGEND
Compressor Power
Saturated Discharge Temperature (F)
Saturated Temperature Entering Compressor (F)
Gross Cooling Capacity (1000 Btuh)
31
38AH104
SST (F)
20
25
30
35
40
45
50
kW
SCT
SCT(A)
SCT(B)
SDT
SDT(A)
SDT(B)
SST
TC
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
85
700
71.1
110
108
108
106
785
75.1
112
109
109
106
873
79.4
114
110
111
107
965
83.7
116
112
112
109
1062
88.1
119
114
114
110
1163
92.6
122
117
116
112
1269
97.3
125
119
118
114
LEGEND
Compressor Power
Saturated Condensing Temperature (F)
Saturated Condensing Temperature for Circuit A
Saturated Condensing Temperature for Circuit B
Saturated Discharge Temperature (F)
Saturated Discharge Temperature for Circuit A
Saturated Discharge Temperature for Circuit B
Saturated Suction Temperature Entering Condensing Unit (F)
Gross Cooling Capacity (1000 Btuh)
32
115
535
77.3
139
137
138
136
612
83.1
140
138
139
137
691
88.9
141
139
140
137
772
94.9
143
140
141
138
857
100.9
145
142
143
140
946
107.1
148
144
145
141
1038
113.5
150
146
147
143
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
85
782
77.4
108
110
106
107
877
82.1
110
112
107
109
977
86.9
112
114
109
111
1082
91.7
114
117
110
112
1192
96.8
117
120
112
114
1308
101.9
119
123
114
117
1429
107.3
122
126
116
119
115
592
85.6
137
138
136
137
676
92.1
137
139
136
138
762
96.5
139
141
137
140
853
105.1
141
143
139
141
948
111.9
143
146
141
143
1047
118.9
145
148
143
145
1151
125.9
148
151
145
148
38AH134
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT (A) or (B)
SCT (A) or (B)
TC
kW
SDT (A) or (B)
SCT (A) or (B)
TC
kW
SDT (A) or (B)
SCT (A) or (B)
TC
kW
SDT (A) or (B)
SCT (A) or (B)
TC
kW
SDT (A) or (B)
SCT (A) or (B)
TC
kW
SDT (A) or (B)
SCT (A) or (B)
TC
kW
SDT (A) or (B)
SCT (A) or (B)
LEGEND
kW
Compressor Power
SCT
Saturated Condensing Temperature (F)
SCT(A) Saturated Condensing Temperature for Module 38AH124A or
134A (F)
SCT(B) Saturated Condensing Temperature for Module 38AH124B or
134B (F)
SDT
Saturated Discharge Temperature (F)
SDT(A) Saturated Discharge Temperature for Module 38AH124A or
134A (F)
SDT(B) Saturated Discharge Temperature for Module 38AH124B or
134B (F)
SST
Saturated Suction Temperature Entering Condensing Unit (F)
TC
Gross Cooling Capacity (1000 Btuh)
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
85
992
99.8
109
108
108
104
1113
105.3
110
109
109
106
1240
110.9
112
111
110
107
1373
116.6
114
113
112
109
1514
122.5
116
115
114
110
1662
128.4
118
117
116
113
1817
134.4
121
120
118
115
115
765
109.7
138
137
138
134
872
117.5
139
138
139
134
983
125.5
140
139
139
136
1099
133.7
142
141
141
137
1220
141.8
142
142
142
139
1348
150.3
145
145
144
141
1481
158.9
148
147
146
142
NOTE: Unit 38AH124 consists of Modules 124A and 124B. Unit 38AH134 consists of Modules 134A and 134B. Each module is one refrigeration circuit.
33
kW
SDT
SST
TC
LEGEND
Compressor Power
Saturated Discharge Temperature at Compressor (F)
Saturated Suction Temperature (F)
Gross Cooling Capacity (1000 Btuh)
34
38AH044 CIRCUIT A
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
153.0
15.0
105.0
174.0
15.8
107.0
195.0
16.7
108.0
218.0
17.5
110.0
241.0
18.3
112.0
266.0
19.1
114.0
293.0
19.9
117.0
115
107.0
16.3
134.0
126.0
17.6
135.0
146.0
19.0
136.0
166.0
20.2
138.0
187.0
21.5
139.0
209.0
22.8
141.0
232.0
24.0
143.0
38AH054 CIRCUIT A
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
152.0
15.4
110.0
175.0
16.2
110.0
199.0
16.9
111.0
223.0
17.6
112.0
249.0
18.4
113.0
275.0
19.1
115.0
303.0
19.8
117.0
20
25
30
35
40
45
50
kW
SDT
SST
TC
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
207.0
20.8
109.0
234.0
21.9
111.0
262.0
23.1
112.0
291.0
24.3
114.0
323.0
25.6
116.0
355.0
26.8
119.0
390.0
28.1
121.0
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
STD
TC
kW
SDT
TC
kW
SDT
85
152.0
15.2
108.0
174.0
16.0
109.0
197.0
16.8
109.0
221.0
17.5
110.0
247.0
18.2
112.0
274.0
18.8
113.0
303.0
19.4
115.0
115
105.0
16.3
138.0
124.0
17.7
138.0
145.0
19.1
139.0
166.0
20.4
139.0
189.0
21.6
140.0
213.0
22.8
142.0
237.0
24.0
143.0
115
156.0
23.3
141.0
178.0
25.0
142.0
201.0
26.7
143.0
226.0
28.5
145.0
252.0
30.2
147.0
279.0
32.1
149.0
115
174.0
25.5
138.0
201.0
27.4
139.0
228.0
29.4
140.0
257.0
31.3
141.0
287.0
33.2
143.0
318.0
35.2
145.0
351.0
37.1
147.0
38AH054 CIRCUIT B
115
105.0
16.2
140.0
125.0
17.7
140.0
146.0
19.1
140.0
169.0
20.4
141.0
192.0
21.7
141.0
217.0
22.9
142.0
115
157.0
23.2
139.0
179.0
24.8
139.0
203.0
26.5
141.0
228.0
28.2
142.0
254.0
29.9
144.0
282.0
31.7
146.0
311.0
33.5
148.0
38AH064 CIRCUIT A
SST (F)
SST (F)
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
STD
TC
kW
SDT
TC
kW
STD
TC
kW
STD
TC
kW
SDT
TC
kW
SDT
85
205.0
21.0
112.0
232.0
22.2
113.0
259.0
23.5
115.0
289.0
24.8
117.0
319.0
26.1
119.0
352.0
27.4
122.0
385.0
28.8
124.0
38AH064 CIRCUIT B
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
STD
TC
kW
STD
TC
kW
STD
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
232.0
23.5
109.0
262.0
24.8
110.0
293.0
26.0
111.0
325.0
27.3
113.0
359.0
28.5
115.0
394.0
29.8
117.0
432.0
31.1
119.0
LEGEND
Compressor Power
Saturated Temperature Leaving Compressor (F)
Saturated Temperature Entering Compressor (F)
Gross Cooling Capacity (1000 Btuh)
35
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
241.9
23.8
108.0
271.6
25.0
109.0
303.4
26.4
110.0
336.2
27.6
112.0
370.0
28.9
114.0
406.9
30.2
117.0
444.9
31.6
119.0
38AH074 CIRCUIT B
Condenser Entering-Air Temperature (F)
90
95
100
105
110
232.7
222.4
213.2
203.0
192.7
24.3
24.7
25.1
25.4
25.8
113.0
118.0
122.0
127.0
132.0
262.4
252.2
241.9
231.7
221.4
25.7
26.3
26.8
27.2
27.6
114.0
118.0
123.0
128.0
133.0
293.2
281.9
271.6
261.4
250.1
27.1
27.7
28.3
28.9
29.3
115.0
120.0
124.0
129.0
134.0
324.9
313.7
302.4
291.1
279.8
28.5
29.2
29.9
30.6
31.1
117.0
121.0
126.0
131.0
135.0
358.8
346.5
335.2
322.9
310.6
29.8
30.7
31.6
32.3
33.0
119.0
123.0
128.0
132.0
137.0
394.6
381.3
369.0
356.7
343.4
31.2
32.3
33.2
34.1
34.8
121.0
126.0
130.0
135.0
139.0
431.5
418.2
404.9
391.6
377.2
32.7
33.8
34.8
35.8
36.7
123.0
128.0
132.0
137.0
141.0
115
182.5
26.0
137.0
211.2
27.9
138.0
238.8
29.7
138.0
268.6
31.7
140.0
299.3
33.7
142.0
331.1
35.6
144.0
363.9
37.6
146.0
38AH084 CIRCUIT A
SST (F)
20
25
30
35
40
45
50
kW
SDT
SST
TC
36
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
322.1
34.1
108.0
361.6
36.0
109.0
404.2
37.8
110.0
448.8
39.7
112.0
495.6
41.7
114.0
544.4
43.8
117.0
595.3
45.9
119.0
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
325.2
33.4
108.0
362.6
35.3
110.0
402.1
37.3
112.0
442.6
39.3
114.0
486.3
41.4
116.0
533.0
43.5
118.0
581.8
45.7
121.0
115
261.8
36.8
137.0
294.0
39.4
138.0
327.3
42.0
140.0
362.6
44.7
141.0
400.0
47.4
143.0
438.5
50.3
146.0
480.0
53.2
148.0
115
257.7
37.2
137.0
292.0
39.7
138.0
327.3
42.3
140.0
365.7
44.9
141.0
405.2
47.6
143.0
446.8
50.4
146.0
490.4
53.2
148.0
38AH084 CIRCUIT B
Condenser Entering-Air Temperature (F)
90
95
100
105
110
310.7
299.2
287.8
277.4
266.0
34.7
35.4
36.0
36.5
37.0
113.0
118.0
122.0
127.0
132.0
349.1
337.7
325.2
312.7
301.3
36.7
37.4
38.2
38.8
39.4
114.0
118.0
123.0
128.0
133.0
390.7
378.2
364.7
352.2
338.7
38.7
39.6
40.4
41.2
41.9
115.0
120.0
124.0
129.0
134.0
434.3
420.8
406.2
392.7
378.2
40.8
41.8
42.7
43.5
44.4
117.0
121.0
126.0
131.0
135.0
480.0
465.5
449.9
435.3
419.8
42.8
44.0
45.0
46.0
47.0
119.0
123.0
128.0
132.0
137.0
527.8
511.2
495.6
479.0
463.4
45.1
46.2
47.5
48.5
49.6
121.0
126.0
130.0
135.0
139.0
577.7
560.0
542.4
525.7
508.1
47.4
48.7
50.0
51.2
52.4
123.0
128.0
132.0
137.0
141.0
LEGEND
Compressor Power
Saturated Temperature Leaving Compressor (F)
Saturated Temperature Entering Compressor (F)
Gross Cooling Capacity (1000 Btuh)
115
255.6
37.4
137.0
289.9
39.9
138.0
326.2
42.5
138.0
364.7
45.1
140.0
405.2
47.8
142.0
446.8
50.6
144.0
490.4
53.5
146.0
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
324.2
33.8
108.0
363.7
35.7
110.0
406.2
37.5
112.0
449.9
39.4
114.0
495.6
41.4
116.0
543.4
43.4
118.0
593.3
45.6
121.0
20
25
30
35
40
45
50
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
85
385
39.0
110
108
433
41.3
112
109
482
43.7
114
111
533
46.1
116
112
587
48.6
119
114
643
51.1
122
116
702
53.7
125
118
38AH094 CIRCUIT B
Condenser Entering-Air Temperature (F)
90
95
100
105
110
368
352
335
318
300
39.8
40.4
40.9
41.4
41.6
115
119
124
129
134
113
118
123
128
133
416
398
381
363
346
42.2
43.1
43.8
44.4
44.9
116
121
126
130
135
114
119
124
129
134
464
446
428
410
392
44.8
45.7
46.6
47.4
48.1
118
123
127
132
136
115
120
125
130
135
515
496
477
458
439
47.3
48.5
49.5
50.5
51.3
121
125
130
134
138
117
122
127
132
136
568
548
528
508
487
50.0
51.3
52.5
53.6
54.6
123
128
132
136
141
119
124
129
133
138
623
602
581
559
538
52.6
54.1
55.5
56.8
58.0
126
130
135
139
143
121
126
131
136
140
680
658
636
613
591
55.4
57.0
58.6
60.0
61.4
129
133
138
142
146
123
128
133
138
142
115
283
41.7
139
138
328
45.2
140
139
373
48.6
141
140
419
52.0
143
141
467
55.5
145
143
517
59.0
148
145
568
62.6
150
147
38AH104 CIRCUIT A
SST (F)
20
25
30
35
40
45
50
kW
SCT
SDT
SST
TC
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
85
365
35.8
108
106
411
37.9
110
107
458
40.1
112
109
508
42.2
114
110
561
44.5
117
112
616
46.7
119
114
673
49.1
122
116
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
85
315
32.1
108
106
352
33.8
109
106
391
35.7
110
107
432
37.6
112
109
475
39.5
114
110
520
41.5
117
112
567
43.6
119
114
115
252
35.6
137
136
284
37.9
138
137
318
40.3
139
137
353
42.9
140
138
390
45.4
142
140
429
48.1
144
141
470
50.9
146
143
115
321
46.3
138
137
364
49.7
139
138
408
53.1
141
140
455
56.6
143
141
504
60.3
146
143
556
64.1
148
145
610
67.9
151
148
38AH104 CIRCUIT B
Condenser Entering-Air Temperature (F)
90
95
100
105
110
349
334
318
302
287
36.6
37.4
38.0
38.6
39.0
113
117
122
127
132
111
116
121
126
131
394
378
361
345
329
38.9
39.8
40.5
41.2
41.9
114
119
123
128
133
112
117
122
127
131
441
423
406
389
372
41.1
42.2
43.1
44.0
44.7
116
121
125
130
134
113
118
123
128
133
490
471
453
435
416
43.5
44.6
45.7
46.7
47.6
118
123
127
132
136
115
120
125
129
134
541
521
502
482
463
45.8
47.2
48.4
49.5
50.6
121
125
130
134
138
117
122
127
131
136
595
574
553
532
512
48.3
49.7
51.1
52.4
53.6
124
128
132
136
141
119
124
128
133
138
651
629
607
585
563
50.8
52.4
53.9
55.3
56.7
126
131
135
139
143
121
126
131
135
140
115
271
39.3
137
136
312
42.4
137
136
354
45.4
139
137
398
48.5
141
139
444
51.6
143
141
491
54.8
145
143
541
58.0
148
145
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
85
417
41.6
110
107
466
44.2
112
109
519
46.8
114
111
574
49.5
117
112
631
52.3
120
114
692
55.2
123
117
756
58.2
126
119
LEGEND
Compressor Power
Saturated Condenser Temperature (F)
Saturated Temperature Leaving Compressor (F)
Saturated Temperature Entering Compressor (F)
Gross Cooling Capacity (1000 Btuh)
37
kW
SCT
SDT
SST
TC
LEGEND
Compressor Power
Saturated Condensing Temperature (F)
Saturated Discharge Temperature (F)
Saturated Suction Temperature Entering Condensing Unit (F)
Gross Cooling Capacity (1000 Btuh)
NOTE: Unit 38AH124 consists of Modules 124A and 124B. Unit 38AH134 consists of Modules 134A and 134B. Each module is one circuit.
38
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
85
550
55.5
108
104
615
58.6
109
106
683
61.8
111
107
755
65.0
113
109
831
68.3
115
111
911
71.6
117
113
995
75.0
120
115
115
431
61.0
137
134
489
65.3
138
134
549
69.7
139
136
612
74.2
141
137
677
78.7
142
139
746
83.4
145
141
818
88.2
147
142
BF
Edb
Ewb
kW
SHC
TC
LEGEND
Bypass Factor
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHC is based on 80 F dry-bulb temperature of air entering evaporator coil.
Below 80 F dry-bulb, subtract (correction factor x cfm) from SHC.
Above 80 F dry bulb, add (correction factor x cfm) to SHC.
BYPASS
FACTOR
79
81
0.10
0.20
0.30
0.99
0.88
0.77
7500
67
251.1
176.7
16.52
239.4
172.1
17.99
233.5
169.6
18.72
227.5
167.2
19.42
215.4
162.5
20.82
62
230.1
211.9
16.00
219.4
206.1
17.38
213.9
203.2
18.05
208.4
200.3
18.71
197.3
193.4
20.02
10,000
67
274.5
214.1
17.11
261.1
208.9
18.67
254.4
206.5
19.43
247.5
203.8
20.18
233.7
198.5
21.63
62
254.5
254.5
16.64
244.3
244.3
18.19
239.0
239.0
18.95
233.8
233.8
18.70
222.7
222.7
21.16
3. Gross capacities shown do not include a deduction for evaporator fan motor
heat.
4. Formulas:
sensible heat capacity (Btuh)
tldb = tedb
1.1 x cfm
tlwb =
Interpolation is permissible.
Correction Factor = 1.1 x (1 BF) x (db 80).
39
BF
Edb
Ewb
kW
SHC
TC
LEGEND
Bypass Factor
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHC is based on 80 F dry-bulb temperature of air entering evaporator coil.
Below 80 F dry-bulb, subtract (correction factor x cfm) from SHC.
Above 80 F dry bulb, add (correction factor x cfm) to SHC.
BYPASS
FACTOR
79
81
0.10
0.20
0.30
0.99
0.88
0.77
Interpolation is permissible.
Correction Factor = 1.1 x (1 BF) x (db 80).
40
12,500
67
287.3
241.5
17.40
273.2
235.9
19.03
266.3
233.2
19.82
259.1
230.6
20.60
244.1
224.5
22.08
62
272.9
272.9
17.08
261.4
261.4
18.71
255.6
255.6
19.48
249.7
249.7
20.26
237.9
237.9
21.84
10,000
67
303.6
225.5
20.68
290.1
219.9
22.44
283.3
217.5
23.31
276.4
214.9
24.15
262.0
209.5
25.87
62
279.9
272.3
20.02
267.4
267.4
21.68
261.9
261.9
22.51
255.9
255.9
23.32
244.9
244.9
25.05
3. Gross capacities shown do not include a deduction for evaporator fan motor
heat.
4. Formulas:
sensible heat capacity (Btuh)
tldb = tedb
1.1 x cfm
tlwb =
BF
Edb
Ewb
kW
SHC
TC
LEGEND
Bypass Factor
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHC is based on 80 F dry-bulb temperature of air entering evaporator coil.
Below 80 F dry-bulb, subtract (correction factor x cfm) from SHC.
Above 80 F dry bulb, add (correction factor x cfm) to SHC.
BYPASS
FACTOR
79
81
0.10
0.20
0.30
0.99
0.88
0.77
10,000
67
319.6
253.4
21.16
304.8
247.5
22.98
297.4
245.0
23.86
289.8
242.1
24.74
274.8
236.3
26.52
62
297.8
297.8
20.55
286.4
286.4
22.36
280.7
280.7
23.26
274.9
274.9
24.15
262.8
262.8
25.96
15,000
67
323.2
280.6
20.07
320.4
279.6
23.54
312.6
276.8
24.46
304.9
273.8
25.38
288.2
267.0
27.21
62
320.5
320.5
21.22
307.8
307.8
23.11
301.4
301.4
24.05
294.9
294.9
24.98
282.0
282.0
26.91
3. Gross capacities shown do not include a deduction for evaporator fan motor
heat.
4. Formulas:
sensible heat capacity (Btuh)
tldb = tedb
1.1 x cfm
tlwb =
Interpolation is permissible.
Correction Factor = 1.1 x (1 BF) x (db 80).
41
BF
Edb
Ewb
kW
SHC
TC
LEGEND
Bypass Factor
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHC is based on 80 F dry-bulb temperature of air entering evaporator coil.
Below 80 F dry-bulb, subtract (correction factor x cfm) from SHC.
Above 80 F dry bulb, add (correction factor x cfm) to SHC.
BYPASS
FACTOR
79
81
0.10
0.20
0.30
0.99
0.88
0.77
Interpolation is permissible.
Correction Factor = 1.1 x (1 BF) x (db 80).
42
12,500
67
373.6
300.8
26.55
357.1
294.4
28.60
348.8
291.3
29.60
340.3
288.0
30.63
323.0
281.1
32.63
62
350.1
350.1
25.72
336.8
336.8
27.75
330.1
330.1
28.76
326.4
326.3
29.50
312.6
312.6
31.78
15,000
67
381.8
307.4
26.89
365.3
301.2
28.97
356.9
298.0
30.00
348.2
294.7
31.03
332.7
288.7
33.05
62
358.4
358.4
26.05
344.7
344.7
28.09
337.8
337.8
29.13
331.1
331.1
30.18
317.4
317.4
32.30
3. Gross capacities shown do not include a deduction for evaporator fan motor
heat.
4. Formulas:
sensible heat capacity (Btuh)
tldb = tedb
1.1 x cfm
tlwb =
2
0
2
4
6
8
10
21
124.6
31.8
33.8
136.0
32.4
34.7
147.5
33.1
35.5
158.9
33.8
36.3
170.4
34.4
37.2
181.8
35.1
38.0
193.2
35.7
38.8
27
113.8
33.1
39.6
124.8
34.0
40.4
135.8
35.0
41.2
146.7
35.9
41.9
157.7
36.8
42.7
168.7
37.8
43.5
179.6
38.7
44.3
30
108.4
33.7
42.5
119.2
34.8
43.3
129.9
35.9
44.0
140.6
36.9
44.7
151.4
38.0
45.5
162.1
39.1
46.2
172.8
40.2
47.0
32
104.8
34.2
44.4
115.4
35.3
45.2
126.0
36.5
45.9
136.6
37.7
46.6
147.1
38.8
47.3
157.7
40.0
48.1
168.3
41.1
48.8
43
85.1
36.6
55.0
94.8
38.2
55.7
104.5
39.9
56.3
114.2
41.5
56.9
123.9
43.2
57.5
133.6
44.9
58.2
143.3
46.5
58.8
46
79.7
37.2
57.9
89.2
39.0
58.5
98.6
40.8
59.1
108.1
42.6
59.7
117.6
44.4
60.3
127.1
46.2
60.9
136.5
48.0
61.5
49
74.3
37.9
60.8
83.6
39.8
61.4
92.8
41.7
62.0
102.0
43.7
62.5
111.3
45.6
63.1
120.5
47.5
63.7
129.7
49.5
64.2
52
68.9
38.5
63.7
77.9
40.6
64.3
86.9
42.6
64.8
95.9
44.7
65.3
104.9
46.8
65.9
113.9
48.9
66.4
21
144.5
38.4
35.5
157.4
39.4
36.4
170.2
40.3
37.4
183.1
41.3
38.4
195.9
42.3
39.3
208.8
43.3
40.3
221.6
44.3
41.2
27
132.9
39.9
41.5
145.2
41.2
42.4
157.5
42.5
43.2
169.8
43.7
44.1
182.1
45.0
44.9
194.5
46.3
45.7
206.8
47.5
46.6
30
127.1
40.7
44.5
139.1
42.1
45.3
151.2
43.5
46.1
163.2
44.9
46.9
175.3
46.3
47.7
187.3
47.8
48.5
199.4
49.2
49.3
32
123.2
41.2
46.5
135.0
42.7
47.3
146.9
44.2
48.0
158.8
45.7
48.8
170.7
47.2
49.6
182.5
48.8
50.3
194.4
50.3
51.1
43
101.8
44.0
57.6
112.7
46.0
58.1
123.6
48.1
58.7
134.5
50.1
59.3
145.4
52.2
59.8
156.3
54.2
60.4
167.2
56.3
60.9
46
96.0
44.8
60.6
106.6
47.0
61.1
117.3
49.1
61.6
127.9
51.3
62.1
138.5
53.5
62.6
149.2
55.7
63.1
159.8
57.9
63.6
49
90.2
45.5
63.6
100.5
47.9
64.1
110.9
50.2
64.5
121.3
52.5
65.0
131.6
54.9
65.4
142.0
57.2
65.8
52
84.4
46.3
66.6
94.5
48.8
67.0
104.6
51.3
67.4
114.6
53.7
67.8
124.7
56.2
68.2
21
174.0
46.4
35.1
188.9
47.7
36.2
203.7
49.0
37.2
218.5
50.3
38.2
233.3
51.5
39.3
248.1
52.8
40.3
262.9
54.1
41.3
27
161.0
48.4
40.9
175.1
50.0
41.9
189.3
51.6
42.9
203.5
53.2
43.8
217.6
54.8
44.8
231.8
56.4
45.8
245.9
58.0
46.8
30
154.5
49.3
43.8
168.3
51.1
44.8
182.1
52.9
45.7
196.0
54.7
46.7
209.8
56.4
47.6
223.6
58.2
48.5
237.5
60.0
49.5
32
150.1
50.0
45.7
163.7
51.9
46.7
177.3
53.7
47.6
191.0
55.6
48.5
204.6
57.5
49.4
218.2
59.4
50.4
231.8
61.3
51.3
43
126.1
53.5
56.3
138.6
56.0
57.2
151.0
58.5
58.0
163.4
61.0
58.8
175.9
63.5
59.6
188.3
66.0
60.5
200.7
68.5
61.3
46
119.6
54.5
59.2
131.7
57.1
60.0
143.8
59.8
60.8
155.9
62.5
61.6
168.0
65.1
62.4
180.1
67.8
63.2
192.2
70.4
64.0
49
113.1
55.5
62.1
124.9
58.3
62.9
136.6
61.1
63.7
148.4
63.9
64.4
160.2
66.7
65.2
172.0
69.6
66.0
183.8
72.4
66.7
52
106.5
56.4
65.0
118.0
59.4
65.7
129.5
62.4
66.5
140.9
65.4
67.2
152.4
68.4
68.0
163.8
71.4
68.7
175.3
74.3
69.5
38AH054
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
2
0
2
4
6
8
10
38AH064
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
2
0
2
4
6
8
10
kW
SDT
SST
TC
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
43
2
0
2
4
6
8
10
21
217.7
59.9
35.4
235.8
61.9
36.4
253.9
63.8
37.3
272.0
65.8
38.2
290.1
67.7
39.1
308.3
69.6
40.0
326.4
71.6
40.9
27
203.3
62.3
41.0
220.6
64.6
41.9
237.8
66.9
42.8
255.1
69.2
43.7
272.4
71.5
44.6
289.6
73.8
45.5
306.9
76.1
46.4
30
196.1
63.5
43.7
213.0
66.0
44.6
229.8
68.5
45.5
246.6
70.9
46.4
263.5
73.4
47.3
280.3
75.9
48.2
297.2
78.4
49.1
32
191.3
64.3
45.6
207.9
66.9
46.5
224.5
69.5
47.4
241.0
72.1
48.3
257.6
74.7
49.2
274.1
77.3
50.1
290.7
79.9
51.0
43
165.0
68.7
55.7
180.0
71.9
56.6
195.0
75.2
57.5
210.0
78.4
58.4
225.0
81.7
59.3
240.0
85.0
60.2
255.0
88.2
61.1
46
157.8
69.9
58.5
172.4
73.3
59.4
187.0
76.7
60.3
201.5
80.2
61.2
216.1
83.6
62.1
230.7
87.0
63.0
245.2
90.5
63.9
49
150.7
71.1
61.3
164.8
74.7
62.1
178.9
78.3
63.0
193.1
81.9
63.9
207.2
85.5
64.8
221.3
89.1
65.7
52
143.5
72.2
64.0
157.2
76.0
64.9
170.9
79.8
65.8
184.6
83.6
66.7
198.3
87.4
67.6
212.0
91.2
68.5
21
250.5
70.6
35.4
271.8
73.0
36.4
293.0
75.4
37.3
314.3
77.7
38.2
335.5
80.1
39.1
356.8
82.4
40.0
378.0
84.8
40.9
27
234.1
73.5
41.0
254.4
76.2
41.9
274.6
79.0
42.8
294.9
81.7
43.7
315.2
84.5
44.6
335.4
87.2
45.5
355.7
89.9
46.4
30
225.9
74.9
43.7
245.7
77.9
44.6
265.4
80.8
45.5
285.2
83.7
46.4
305.0
86.6
47.3
324.8
89.6
48.2
344.6
92.5
49.1
32
220.4
75.9
45.6
239.9
78.9
46.5
259.3
82.0
47.4
278.8
85.1
48.3
298.2
88.1
49.2
317.7
91.2
50.1
337.1
94.2
51.0
43
190.3
81.1
55.7
208.0
84.9
56.6
225.6
88.6
57.5
243.3
92.4
58.4
260.9
96.1
59.3
278.6
99.9
60.2
296.2
103.7
61.1
46
182.1
82.5
58.5
199.2
86.5
59.4
216.4
90.4
60.3
233.6
94.4
61.2
250.8
98.3
62.1
267.9
102.3
63.0
285.1
106.2
63.9
49
173.9
84.0
61.3
190.5
88.1
62.1
207.2
92.3
63.0
223.9
96.4
63.9
240.6
100.5
64.8
257.3
104.7
65.7
52
165.7
85.4
64.0
181.8
89.7
64.9
198.0
94.1
65.8
214.2
98.4
66.7
230.4
102.7
67.6
246.6
107.1
68.5
21
272.1
74.7
35.6
294.3
77.3
36.7
316.6
79.9
37.8
338.8
82.5
39.0
361.1
85.2
40.1
383.3
87.8
41.2
405.6
90.4
42.4
27
252.9
77.6
41.2
274.2
80.6
42.3
295.5
83.7
43.4
316.8
86.7
44.4
338.1
89.7
45.5
359.4
92.7
46.6
380.7
95.8
47.7
30
243.3
79.0
44.0
264.1
82.3
45.1
285.0
85.5
46.1
305.8
88.8
47.2
326.6
92.0
48.2
347.5
95.2
49.3
368.3
98.5
50.3
32
236.9
80.0
45.9
257.4
83.4
46.9
277.9
86.7
48.0
298.5
90.1
49.0
319.0
93.5
50.0
339.5
96.9
51.0
360.0
100.3
52.1
43
201.7
85.2
56.2
220.5
89.4
57.2
239.3
93.5
58.1
258.1
97.7
59.0
276.9
101.9
59.9
295.7
106.1
60.9
314.5
110.2
61.8
46
192.1
86.6
59.0
210.5
91.0
59.9
228.8
95.4
60.8
247.1
99.8
61.7
265.4
104.2
62.6
283.7
108.5
63.5
302.0
112.9
64.4
49
182.5
88.1
61.9
200.4
92.7
62.7
218.2
97.3
63.6
236.1
101.9
64.5
253.9
106.4
65.3
271.8
111.0
66.2
289.6
115.6
67.1
52
173.0
89.5
64.7
190.3
94.3
65.5
207.7
99.1
66.4
225.1
103.9
67.2
242.4
108.7
68.0
259.8
113.5
68.9
38AH084
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
2
0
2
4
6
8
10
38AH094
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
2
0
2
4
6
8
10
kW
SDT
SST
TC
44
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
2
0
2
4
6
8
10
21
304.0
81.0
37.1
329.8
84.0
38.3
355.6
87.1
39.4
381.5
90.1
40.5
407.3
93.1
41.7
433.1
96.1
42.8
458.9
99.1
43.9
27
281.9
84.6
42.5
306.5
88.0
43.5
331.0
91.5
44.6
355.5
95.0
45.7
380.0
98.5
46.8
404.5
102.0
47.8
429.0
105.5
48.9
30
270.9
86.3
45.1
294.8
90.0
46.2
318.6
93.8
47.2
342.5
97.5
48.3
366.4
101.2
49.3
390.2
104.9
50.4
414.1
108.6
51.4
32
263.5
87.5
46.9
287.0
91.4
47.9
310.4
95.3
48.9
333.8
99.1
50.0
357.3
103.0
51.0
380.7
106.9
52.0
404.1
110.7
53.1
43
223.0
94.0
56.7
244.1
98.7
57.6
265.1
103.4
58.5
286.2
108.2
59.4
307.3
112.9
60.4
328.3
117.6
61.3
349.4
122.3
62.2
46
212.0
95.8
59.3
232.4
100.7
60.2
252.8
105.7
61.1
273.2
110.6
62.0
293.6
115.6
62.9
314.1
120.5
63.8
49
200.9
97.5
62.0
220.7
102.7
62.9
240.5
107.9
63.7
260.2
113.1
64.6
280.0
118.3
65.5
299.8
123.5
66.3
52
189.9
99.3
64.6
209.0
104.7
65.5
228.1
110.1
66.3
247.2
115.6
67.2
266.4
121.0
68.0
21
347.1
92.5
35.4
377.2
95.3
36.4
407.3
98.0
37.5
437.4
100.7
38.5
467.4
103.5
39.6
497.5
106.2
40.7
527.6
108.9
41.7
27
321.5
96.5
41.3
350.1
99.8
42.2
378.8
103.2
43.1
407.5
106.5
44.1
436.2
109.9
45.0
464.9
113.2
46.0
493.6
116.6
46.9
30
308.7
98.5
44.2
336.6
102.1
45.1
364.6
105.8
46.0
392.6
109.4
46.9
420.6
113.1
47.8
448.5
116.8
48.6
476.5
120.4
49.5
32
300.1
99.8
46.1
327.6
103.6
47.0
355.1
107.5
47.9
382.6
111.4
48.7
410.2
115.2
49.6
437.7
119.1
50.4
465.2
123.0
51.3
43
253.2
107.0
56.9
278.1
112.0
57.6
303.0
117.0
58.2
327.9
122.0
58.9
352.9
127.0
59.5
377.8
132.0
60.2
402.7
137.0
60.8
46
240.4
109.0
59.9
264.6
114.3
60.5
288.8
119.6
61.1
313.0
124.9
61.7
337.2
130.2
62.3
361.4
135.5
62.9
385.6
140.9
63.5
49
227.6
110.9
62.8
251.1
116.6
63.3
274.6
122.2
63.9
298.1
127.8
64.4
321.6
133.4
65.0
345.1
139.1
65.5
368.6
144.7
66.1
52
214.8
112.9
65.7
237.6
118.8
66.2
260.4
124.8
66.7
283.2
130.7
67.2
306.0
136.7
67.7
328.8
142.6
68.2
21
384.1
104.2
35.3
417.0
107.5
36.3
449.8
110.8
37.2
482.6
114.1
38.1
515.4
117.4
39.0
548.3
120.7
40.0
581.1
124.0
40.9
27
357.5
108.6
41.1
388.8
112.5
42.0
420.0
116.5
42.9
451.2
120.4
43.7
482.5
124.3
44.6
513.7
128.3
45.5
545.0
132.2
46.3
30
344.2
110.8
44.0
374.7
115.0
44.8
405.1
119.3
45.7
435.6
123.5
46.5
466.0
127.8
47.4
496.4
132.0
48.2
526.9
136.3
49.1
32
335.4
112.2
45.9
365.3
116.7
46.7
395.2
121.2
47.6
425.1
125.6
48.4
455.0
130.1
49.2
484.9
134.6
50.1
514.8
139.0
50.9
43
286.6
120.3
56.5
313.6
125.9
57.2
340.6
131.5
58.0
367.6
137.2
58.7
394.6
142.8
59.4
421.6
148.5
60.1
448.6
154.1
60.9
46
273.3
122.4
59.4
299.5
128.4
60.1
325.7
134.4
60.8
351.9
140.3
61.5
378.1
146.3
62.2
404.3
152.3
62.9
430.5
158.2
63.6
49
260.0
124.6
62.3
285.4
130.9
63.0
310.8
137.2
63.6
336.2
143.5
64.3
361.6
149.8
65.0
387.0
156.0
65.6
412.5
162.3
66.3
52
246.7
126.8
65.2
271.3
133.4
65.8
295.9
140.0
66.5
320.5
146.6
67.1
345.1
153.2
67.8
369.8
159.8
68.4
38AH124
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
2
0
2
4
6
8
10
38AH134
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
2
0
2
4
6
8
10
kW
SDT
SST
TC
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
45
2
0
2
4
6
8
10
21
62.0
16.0
33.1
67.5
16.3
34.2
73.0
16.7
35.3
78.5
17.1
36.3
84.1
17.4
37.4
89.6
17.8
38.4
95.1
18.2
39.5
27
56.8
16.6
39.0
62.1
17.1
40.0
67.3
17.6
40.9
72.6
18.1
41.9
77.9
18.6
42.8
83.2
19.1
43.8
88.4
19.6
44.7
30
54.2
16.8
42.0
59.3
17.4
42.9
64.5
18.0
43.7
69.6
18.6
44.6
74.8
19.1
45.5
80.0
19.7
46.4
85.1
20.3
47.3
32
52.4
17.0
43.9
57.5
17.7
44.8
62.6
18.3
45.6
67.7
18.9
46.5
72.7
19.5
47.3
77.8
20.1
48.2
82.9
20.7
49.1
43
42.9
18.1
54.7
47.5
19.0
55.4
52.1
19.9
56.0
56.8
20.7
56.7
61.4
21.6
57.3
66.1
22.5
58.0
70.7
23.3
58.6
46
40.2
18.4
57.6
44.8
19.4
58.2
49.3
20.3
58.8
53.8
21.2
59.4
58.3
22.2
60.0
62.9
23.1
60.6
67.4
24.0
61.2
49
37.6
18.7
60.6
42.0
19.7
61.1
46.4
20.7
61.7
50.8
21.7
62.2
55.3
22.7
62.8
59.7
23.7
63.3
64.1
24.7
63.9
52
35.0
19.0
63.5
39.3
20.1
64.0
43.6
21.2
64.5
47.9
22.2
65.0
52.2
23.3
65.5
56.5
24.4
66.0
21
62.6
15.8
34.5
68.5
16.1
35.1
74.4
16.4
35.7
80.4
16.7
36.3
86.3
17.0
36.9
92.2
17.3
37.5
98.2
17.6
38.1
27
57.0
16.5
40.2
62.7
17.0
40.8
68.4
17.4
41.4
74.1
17.8
42.0
79.8
18.3
42.6
85.5
18.7
43.2
91.2
19.1
43.8
30
54.3
16.9
43.1
59.8
17.4
43.7
65.4
17.9
44.3
71.0
18.4
44.9
76.6
18.9
45.5
82.1
19.4
46.1
87.7
19.9
46.7
32
52.4
17.1
44.9
57.9
17.7
45.5
63.4
18.2
46.1
68.9
18.8
46.7
74.4
19.3
47.4
79.9
19.8
48.0
85.4
20.4
48.6
43
42.2
18.4
55.4
47.3
19.2
56.0
52.4
20.0
56.6
57.4
20.8
57.2
62.5
21.6
57.8
67.6
22.4
58.4
72.6
23.2
59.0
46
39.5
18.8
58.2
44.4
19.6
58.8
49.4
20.5
59.4
54.3
21.4
60.0
59.3
22.2
60.6
64.2
23.1
61.2
69.1
23.9
61.8
49
36.7
19.1
61.0
41.5
20.1
61.6
46.3
21.0
62.2
51.2
21.9
62.8
56.0
22.8
63.4
60.8
23.8
64.0
65.7
24.7
64.6
52
33.9
19.5
63.9
38.6
20.5
64.5
43.3
21.5
65.1
48.1
22.5
65.7
52.8
23.5
66.3
57.5
24.5
66.9
38AH044 CIRCUIT B
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
2
0
2
4
6
8
10
kW
SDT
SST
TC
46
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity, Gross (kW)
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
2
0
2
4
6
8
10
21
64.1
16.4
33.5
69.7
16.6
34.6
75.3
16.9
35.7
80.8
17.1
36.8
86.4
17.4
37.9
91.9
17.6
39.0
97.5
17.9
40.1
27
58.4
16.9
39.8
63.8
17.3
40.7
69.3
17.7
41.6
74.7
18.1
42.5
80.1
18.5
43.4
85.6
19.0
44.3
91.0
19.4
45.2
30
55.5
17.2
43.0
60.9
17.7
43.8
66.3
18.2
44.6
71.6
18.7
45.4
77.0
19.1
46.2
82.4
19.6
46.9
87.8
20.1
47.7
32
53.6
17.4
45.2
58.9
17.9
45.9
64.3
18.5
46.6
69.6
19.0
47.3
74.9
19.5
48.0
80.3
20.1
48.7
85.6
20.6
49.4
43
43.0
18.4
56.9
48.1
19.2
57.2
53.3
20.1
57.5
58.4
20.9
57.8
63.5
21.7
58.1
68.6
22.5
58.4
73.7
23.3
58.7
46
40.1
18.7
60.0
45.2
19.6
60.2
50.3
20.5
60.4
55.3
21.4
60.6
60.4
22.3
60.8
65.4
23.2
61.0
70.5
24.1
61.2
49
37.3
19.0
63.2
42.3
20.0
63.3
47.3
20.9
63.4
52.2
21.9
63.5
57.2
22.9
63.6
62.2
23.9
63.7
67.2
24.8
63.8
52
34.4
19.3
66.4
39.3
20.3
66.4
44.3
21.4
66.4
49.2
22.4
66.4
54.1
23.5
66.3
59.0
24.5
66.3
21
80.4
22.0
37.5
87.7
22.8
38.3
95.0
23.5
39.1
102.3
24.2
39.9
109.5
24.9
40.7
116.8
25.7
41.5
124.1
26.4
42.3
27
74.5
23.0
43.2
81.4
23.9
44.0
88.3
24.7
44.8
95.1
25.6
45.6
102.0
26.4
46.4
108.9
27.3
47.2
115.8
28.2
48.0
30
71.6
23.5
46.0
78.2
24.4
46.8
84.9
25.3
47.6
91.6
26.3
48.4
98.2
27.2
49.2
104.9
28.1
50.0
111.6
29.1
50.8
32
69.6
23.8
47.9
76.1
24.8
48.7
82.7
25.8
49.5
89.2
26.7
50.3
95.7
27.7
51.1
102.3
28.7
51.9
108.8
29.7
52.7
43
58.8
25.6
58.3
64.6
26.8
59.1
70.4
28.0
59.9
76.1
29.3
60.7
81.9
30.5
61.5
87.7
31.7
62.3
93.5
32.9
63.1
46
55.8
26.1
61.2
61.4
27.4
62.0
67.0
28.6
62.8
72.6
29.9
63.6
78.2
31.2
64.4
83.7
32.5
65.2
89.3
33.8
66.0
49
52.9
26.5
64.0
58.3
27.9
64.8
63.7
29.3
65.6
69.0
30.6
66.4
74.4
32.0
67.2
79.8
33.3
68.0
52
50.0
27.0
66.8
55.1
28.5
67.6
60.3
29.9
68.4
65.5
31.3
69.2
70.6
32.7
70.0
38AH054 CIRCUIT B
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
2
0
2
4
6
8
10
kW
SDT
SST
TC
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
47
2
0
2
4
6
8
10
21
81.9
21.6
35.0
89.0
22.3
36.3
96.2
22.9
37.5
103.4
23.6
38.8
110.5
24.3
40.0
117.7
25.0
41.3
124.8
25.7
42.5
27
75.7
22.6
40.9
82.5
23.4
42.0
89.3
24.2
43.2
96.1
25.1
44.3
102.9
25.9
45.5
109.7
26.7
46.6
116.5
27.5
47.8
30
72.7
23.1
43.8
79.3
24.0
44.9
85.9
24.9
46.0
92.5
25.8
47.1
99.2
26.7
48.2
105.8
27.6
49.3
112.4
28.5
50.4
32
70.6
23.4
45.8
77.1
24.4
46.8
83.6
25.3
47.9
90.1
26.3
48.9
96.6
27.2
50.0
103.1
28.1
51.1
109.6
29.1
52.1
43
59.3
25.3
56.6
65.2
26.5
57.4
71.0
27.7
58.3
76.9
28.9
59.1
82.8
30.1
60.0
88.6
31.3
60.8
94.5
32.5
61.7
46
56.2
25.8
59.5
61.9
27.1
60.3
67.6
28.3
61.1
73.3
29.6
61.9
79.0
30.9
62.7
84.7
32.1
63.5
90.3
33.4
64.3
49
53.2
26.3
62.4
58.7
27.7
63.2
64.2
29.0
63.9
69.7
30.3
64.7
75.2
31.6
65.4
80.7
33.0
66.2
86.2
34.3
66.9
52
50.1
26.9
65.4
55.4
28.2
66.1
60.7
29.6
66.8
66.1
31.0
67.4
71.4
32.4
68.1
76.7
33.8
68.8
82.1
35.2
69.5
21
92.2
24.9
35.3
99.8
25.4
36.1
107.5
26.0
36.9
115.1
26.6
37.7
122.8
27.2
38.5
130.4
27.8
39.3
138.1
28.4
40.1
27
85.3
25.8
41.0
92.6
26.6
41.8
100.0
27.3
42.6
107.3
28.1
43.4
114.7
28.9
44.2
122.0
29.7
45.0
129.4
30.5
45.8
30
81.8
26.2
43.8
89.0
27.1
44.6
96.2
28.0
45.4
103.4
28.9
46.2
110.6
29.8
47.0
117.8
30.6
47.8
125.1
31.5
48.6
32
79.5
26.5
45.7
86.6
27.5
46.5
93.7
28.4
47.3
100.8
29.4
48.1
107.9
30.3
48.9
115.1
31.3
49.7
122.2
32.2
50.5
43
66.8
28.2
56.1
73.4
29.5
56.9
80.0
30.8
57.7
86.5
32.1
58.5
93.1
33.4
59.3
99.7
34.7
60.1
106.2
36.0
60.9
46
63.4
28.7
58.9
69.8
30.1
59.7
76.2
31.5
60.5
82.6
32.9
61.3
89.1
34.3
62.1
95.5
35.7
62.9
101.9
37.1
63.7
49
59.9
29.1
61.8
66.2
30.6
62.6
72.5
32.1
63.4
78.7
33.6
64.2
85.0
35.1
65.0
91.3
36.6
65.8
97.5
38.1
66.6
52
56.5
29.6
64.6
62.6
31.2
65.4
68.7
32.8
66.2
74.8
34.4
67.0
81.0
35.9
67.8
87.1
37.5
68.6
93.2
39.1
69.4
38AH064 CIRCUIT B
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
2
0
2
4
6
8
10
kW
SDT
SST
TC
48
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
2
0
2
4
6
8
10
21
94.6
24.9
33.9
102.5
25.6
35.1
110.3
26.3
36.4
118.1
27.0
37.7
126.0
27.7
38.9
133.8
28.4
40.2
141.7
29.1
41.4
27
87.8
25.9
39.8
95.4
26.8
40.9
102.9
27.6
42.1
110.5
28.5
43.2
118.0
29.4
44.4
125.6
30.2
45.5
133.1
31.1
46.7
30
84.5
26.4
42.7
91.9
27.3
43.8
99.3
28.3
44.9
106.6
29.2
46.0
114.0
30.2
47.1
121.4
31.1
48.2
128.8
32.1
49.3
32
82.2
26.7
44.7
89.5
27.7
45.7
96.8
28.7
46.8
104.1
29.7
47.8
111.4
30.8
48.9
118.7
31.8
49.9
126.0
32.8
51.0
43
69.8
28.5
55.5
76.6
29.8
56.3
83.3
31.2
57.2
90.0
32.5
58.0
96.8
33.8
58.9
103.5
35.2
59.7
110.2
36.5
60.6
46
66.5
29.0
58.4
73.0
30.4
59.2
79.6
31.8
60.0
86.2
33.2
60.8
92.8
34.7
61.6
99.4
36.1
62.4
105.9
37.5
63.2
49
63.1
29.4
61.3
69.5
31.0
62.1
75.9
32.5
62.8
82.4
34.0
63.6
88.8
35.5
64.3
95.2
37.0
65.0
101.6
38.5
65.8
52
59.7
29.9
64.3
66.0
31.5
65.0
72.3
33.1
65.6
78.5
34.7
66.3
84.8
36.3
67.0
91.1
37.9
67.7
21
123.1
35.0
37.0
133.3
36.2
37.6
143.6
37.5
38.1
153.9
38.8
38.7
164.1
40.0
39.2
174.4
41.3
39.8
184.7
42.5
40.3
27
115.5
36.4
42.2
125.2
37.8
42.8
134.9
39.3
43.5
144.6
40.7
44.2
154.3
42.2
44.8
164.1
43.6
45.5
173.8
45.0
46.1
30
111.7
37.1
44.8
121.1
38.6
45.5
130.6
40.2
46.2
140.0
41.7
46.9
149.4
43.2
47.6
158.9
44.8
48.3
168.3
46.3
49.0
32
109.1
37.6
46.5
118.4
39.2
47.2
127.7
40.8
48.0
136.9
42.4
48.7
146.2
43.9
49.5
155.4
45.5
50.2
164.7
47.1
51.0
43
95.2
40.2
56.0
103.4
42.1
56.9
111.7
44.0
57.9
120.0
45.9
58.8
128.2
47.9
59.8
136.5
49.8
60.7
144.7
51.7
61.7
46
91.4
40.9
58.6
99.4
42.9
59.6
107.3
44.9
60.6
115.3
46.9
61.6
123.3
48.9
62.6
131.3
51.0
63.6
139.3
53.0
64.6
49
87.6
41.6
61.2
95.3
43.7
62.2
103.0
45.8
63.3
110.7
47.9
64.3
118.4
50.0
65.4
126.1
52.1
66.4
52
83.8
42.3
63.8
91.2
44.5
64.9
98.6
46.7
66.0
106.1
48.9
67.1
113.5
51.1
68.2
121.0
53.3
69.3
38AH074 CIRCUIT B
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
2
0
2
4
6
8
10
kW
SDT
SST
TC
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
49
2
0
2
4
6
8
10
21
125.0
35.6
33.9
135.7
36.8
35.1
146.4
37.9
36.4
157.0
39.0
37.7
167.7
40.2
38.9
178.4
41.3
40.2
189.1
42.4
41.4
27
116.8
37.0
39.8
127.0
38.3
40.9
137.2
39.7
42.1
147.4
41.0
43.2
157.6
42.4
44.4
167.7
43.7
45.5
177.9
45.0
46.7
30
112.7
37.7
42.7
122.6
39.1
43.8
132.6
40.6
44.9
142.5
42.0
46.0
152.5
43.4
47.1
162.4
44.9
48.2
172.4
46.3
49.3
32
109.9
38.2
44.7
119.7
39.7
45.7
129.5
41.2
46.8
139.3
42.7
47.8
149.1
44.2
48.9
158.9
45.7
49.9
168.6
47.2
51.0
43
94.9
40.7
55.5
103.8
42.6
56.3
112.7
44.4
57.2
121.5
46.3
58.0
130.4
48.2
58.9
139.3
50.1
59.7
148.2
51.9
60.6
46
90.8
41.4
58.4
99.4
43.4
59.2
108.1
45.3
60.0
116.7
47.3
60.8
125.3
49.3
61.6
134.0
51.2
62.4
142.6
53.2
63.2
49
86.7
42.1
61.3
95.1
44.1
62.1
103.5
46.2
62.8
111.9
48.3
63.6
120.3
50.4
64.3
128.7
52.4
65.0
52
82.6
42.8
64.3
90.7
44.9
65.0
98.9
47.1
65.6
107.0
49.3
66.3
115.2
51.5
67.0
123.3
53.6
67.7
21
125.5
35.0
37.0
136.1
36.2
37.6
146.7
37.5
38.1
157.2
38.7
38.7
167.8
39.9
39.2
178.4
41.1
39.8
188.9
42.3
40.3
27
117.3
36.5
42.2
127.4
37.9
42.8
137.5
39.3
43.5
147.5
40.7
44.2
157.6
42.1
44.8
167.7
43.5
45.5
177.8
44.9
46.1
30
113.2
37.2
44.8
123.0
38.7
45.5
132.9
40.2
46.2
142.7
41.7
46.9
152.5
43.2
47.6
162.4
44.7
48.3
172.2
46.2
49.0
32
110.5
37.7
46.5
120.1
39.3
47.2
129.8
40.8
48.0
139.5
42.4
48.7
149.1
43.9
49.5
158.8
45.5
50.2
168.5
47.0
51.0
43
95.4
40.4
56.0
104.2
42.3
56.9
112.9
44.2
57.9
121.7
46.1
58.8
130.5
48.0
59.8
139.3
49.8
60.7
148.0
51.7
61.7
46
91.3
41.2
58.6
99.8
43.1
59.6
108.4
45.1
60.6
116.9
47.1
61.6
125.4
49.1
62.6
133.9
51.0
63.6
142.5
53.0
64.6
49
87.2
41.9
61.2
95.5
44.0
62.2
103.8
46.0
63.3
112.0
48.1
64.3
120.3
50.2
65.4
128.6
52.2
66.4
52
83.1
42.6
63.8
91.1
44.8
64.9
99.2
47.0
66.0
107.2
49.1
67.1
115.2
51.3
68.2
123.3
53.4
69.3
38AH084 CIRCUIT B
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
2
0
2
4
6
8
10
kW
SDT
SST
TC
50
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
2
0
2
4
6
8
10
21
151.9
41.7
37.3
164.2
43.1
38.3
176.5
44.4
39.3
188.8
45.8
40.3
201.1
47.2
41.3
213.4
48.6
42.3
225.7
50.0
43.3
27
140.3
43.0
42.7
152.2
44.7
43.7
164.0
46.3
44.7
175.8
48.0
45.7
187.6
49.6
46.7
199.4
51.3
47.7
211.2
52.9
48.7
30
134.5
43.7
45.4
146.1
45.5
46.4
157.7
47.3
47.4
169.3
49.1
48.4
180.8
50.8
49.4
192.4
52.6
50.4
204.0
54.4
51.4
32
130.7
44.1
47.1
142.1
46.0
48.1
153.5
47.9
49.1
164.9
49.8
50.1
176.4
51.7
51.1
187.8
53.5
52.1
199.2
55.4
53.1
43
109.4
46.6
57.0
119.9
49.0
58.0
130.5
51.4
59.0
141.1
53.7
60.0
151.6
56.1
61.0
162.2
58.5
62.0
172.7
60.9
63.0
46
103.6
47.3
59.7
113.9
49.8
60.7
124.2
52.3
61.7
134.5
54.8
62.7
144.9
57.3
63.7
155.2
59.8
64.7
165.5
62.3
65.7
49
97.8
47.9
62.4
107.9
50.6
63.4
118.0
53.2
64.4
128.0
55.9
65.4
138.1
58.5
66.4
148.2
61.2
67.4
158.3
63.8
68.4
52
92.0
48.6
65.1
101.8
51.4
66.1
111.7
54.2
67.1
121.5
57.0
68.1
131.4
59.8
69.1
141.2
62.5
70.0
21
120.1
33.1
33.9
130.1
34.3
35.1
140.1
35.5
36.4
150.0
36.7
37.7
160.0
38.0
38.9
170.0
39.2
40.2
179.9
40.4
41.4
27
112.6
34.6
39.8
122.1
36.0
40.9
131.5
37.3
42.1
141.0
38.7
43.2
150.5
40.1
44.4
160.0
41.5
45.5
169.5
42.8
46.7
30
108.8
35.3
42.7
118.0
36.8
43.8
127.3
38.2
44.9
136.5
39.7
46.0
145.8
41.2
47.1
155.0
42.6
48.2
164.3
44.1
49.3
32
106.2
35.8
44.7
115.3
37.3
45.7
124.4
38.9
46.8
133.5
40.4
47.8
142.6
41.9
48.9
151.7
43.4
49.9
160.8
44.9
51.0
43
92.3
38.6
55.5
100.6
40.4
56.3
108.8
42.2
57.2
117.0
44.0
58.0
125.3
45.8
58.9
133.5
v47.6
59.7
141.7
49.4
60.6
46
88.5
39.4
58.4
96.5
41.2
59.2
104.5
43.1
60.0
112.5
45.0
60.8
120.5
46.8
61.6
128.5
48.7
62.4
136.5
50.6
63.2
49
84.8
40.1
61.3
92.5
42.1
62.1
100.3
44.0
62.8
108.0
46.0
63.6
115.8
47.9
64.3
123.6
49.9
65.0
131.3
51.8
65.8
52
81.0
40.9
64.3
88.5
42.9
65.0
96.0
44.9
65.6
103.5
47.0
66.3
111.1
49.0
67.0
118.6
51.0
67.7
126.1
53.0
68.4
38AH094 CIRCUIT B
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
2
0
2
4
6
8
10
kW
SDT
SST
TC
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
51
2
0
2
4
6
8
10
21
143.2
37.4
35.7
155.4
38.7
37.0
167.7
40.0
38.2
179.9
41.3
39.5
192.2
42.6
40.7
204.4
43.9
42.0
216.6
45.2
43.3
27
132.4
39.1
41.3
144.1
40.6
42.4
155.7
42.1
43.6
167.4
43.6
44.7
179.1
45.2
45.9
190.7
46.7
47.0
202.4
48.2
48.2
30
127.1
39.9
44.1
138.4
41.5
45.2
149.8
43.2
46.3
161.1
44.8
47.4
172.5
46.4
48.4
183.9
48.1
49.5
195.2
49.7
50.6
32
123.5
40.4
45.9
134.7
42.1
47.0
145.8
43.9
48.0
157.0
45.6
49.1
168.1
47.3
50.2
179.3
49.0
51.2
190.5
50.7
52.3
43
103.8
43.4
56.2
113.9
45.6
57.0
124.0
47.7
57.9
134.0
49.9
58.7
144.1
52.0
59.6
154.2
54.1
60.4
164.3
56.3
61.3
46
98.4
44.2
58.9
108.2
46.5
59.7
118.0
48.8
60.5
127.8
51.0
61.3
137.6
53.3
62.1
147.4
55.5
62.9
157.2
57.8
63.7
49
93.0
45.1
61.7
102.5
47.4
62.5
112.0
49.8
63.2
121.5
52.2
64.0
131.0
54.6
64.7
140.5
56.9
65.4
52
87.7
45.9
64.5
96.9
48.4
65.2
106.1
50.9
65.9
115.3
53.4
66.6
124.5
55.9
67.3
133.7
58.3
68.0
21
160.8
43.6
38.6
174.4
45.3
39.6
188.0
47.1
40.6
201.5
48.8
41.6
215.1
50.5
42.6
228.7
52.2
43.6
242.2
54.0
44.6
27
149.5
45.5
43.6
162.4
47.5
44.6
175.2
49.4
45.6
188.1
51.4
46.6
200.9
53.3
47.6
213.8
55.3
48.6
226.7
57.3
49.6
30
143.8
46.5
46.2
156.3
48.5
47.2
168.8
50.6
48.2
181.3
52.7
49.2
193.9
54.8
50.2
206.4
56.8
51.2
218.9
58.9
52.2
32
140.0
47.1
47.9
152.3
49.2
48.9
164.6
51.4
49.9
176.9
53.5
50.9
189.1
55.7
51.9
201.4
57.9
52.9
213.7
60.0
53.9
43
119.2
50.6
57.2
130.2
53.2
58.2
141.2
55.7
59.1
152.2
58.3
60.1
163.2
60.9
61.1
174.1
63.5
62.1
185.1
66.0
63.1
46
113.5
51.5
59.7
124.2
54.2
60.7
134.8
56.9
61.7
145.4
59.6
62.7
156.1
62.3
63.7
166.7
65.0
64.7
49
107.9
52.5
62.2
118.1
55.3
63.2
128.4
58.1
64.2
138.7
60.9
65.2
149.0
63.7
66.2
159.3
66.5
67.2
52
102.2
53.4
64.8
112.1
56.4
65.8
122.0
59.3
66.8
132.0
62.2
67.8
141.9
65.1
68.7
38AH104 CIRCUIT B
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
2
0
2
4
6
8
10
kW
SDT
SST
TC
52
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
2
0
2
4
6
8
10
21
173.5
46.3
35.4
188.6
47.6
36.4
203.6
49.0
37.5
218.7
50.4
38.5
233.7
51.7
39.6
248.8
53.1
40.7
263.8
54.5
41.7
27
160.7
48.2
41.3
175.1
49.9
42.2
189.4
51.6
43.1
203.8
53.3
44.1
218.1
54.9
45.0
232.4
56.6
46.0
246.8
58.3
46.9
30
154.3
49.2
44.2
168.3
51.1
45.1
182.3
52.9
46.0
196.3
54.7
46.9
210.3
56.5
47.8
224.3
58.4
48.6
238.3
60.2
49.5
32
150.1
49.9
46.1
163.8
51.8
47.0
177.6
53.8
47.9
191.3
55.7
48.7
205.1
57.6
49.6
218.8
59.6
50.4
232.6
61.5
51.3
43
126.6
53.5
56.9
139.1
56.0
57.6
151.5
58.5
58.2
164.0
61.0
58.9
176.4
63.5
59.5
188.9
66.0
60.2
201.3
68.5
60.8
46
120.2
54.5
59.9
132.3
57.1
60.5
144.4
59.8
61.1
156.5
62.5
61.7
168.6
65.1
62.3
180.7
67.8
62.9
192.8
70.4
63.5
49
113.8
55.5
62.8
125.5
58.3
63.3
137.3
61.1
63.9
149.0
63.9
64.4
160.8
66.7
65.0
172.6
69.5
65.5
184.3
72.3
66.1
52
107.4
56.5
65.7
118.8
59.4
66.2
130.2
62.4
66.7
141.6
65.4
67.2
153.0
68.3
67.7
164.4
71.3
68.2
21
210.6
57.9
35.3
228.4
59.9
36.1
246.2
61.8
36.9
263.9
63.7
37.7
281.7
65.7
38.5
299.5
67.6
39.3
317.3
69.5
40.1
27
196.8
60.3
41.0
213.7
62.6
41.8
230.6
64.9
42.6
247.5
67.1
43.4
264.4
69.4
44.2
281.3
71.6
45.0
298.2
73.9
45.8
30
189.9
61.5
43.8
206.3
64.0
44.6
222.8
66.4
45.4
239.3
68.8
46.2
255.7
71.2
47.0
272.2
73.7
47.8
288.6
76.1
48.6
32
185.3
62.3
45.7
201.5
64.9
46.5
217.6
67.4
47.3
233.8
70.0
48.1
249.9
72.5
48.9
266.1
75.0
49.7
282.3
77.6
50.5
43
160.0
66.8
56.1
174.5
69.9
56.9
189.1
73.0
57.7
203.6
76.2
58.5
218.2
79.3
59.3
232.7
82.5
60.1
247.3
85.6
60.9
46
153.1
68.0
58.9
167.2
71.3
59.7
181.3
74.6
60.5
195.4
77.9
61.3
209.5
81.2
62.1
223.6
84.5
62.9
237.7
87.8
63.7
49
146.2
69.2
61.8
159.8
72.6
62.6
173.5
76.1
63.4
187.2
79.6
64.2
200.8
83.0
65.0
214.5
86.5
65.8
228.2
90.0
66.6
52
139.3
70.4
64.6
152.5
74.0
65.4
165.7
77.6
66.2
178.9
81.3
67.0
192.2
84.9
67.8
205.4
88.5
68.6
218.6
92.2
69.4
38AH134 CIRCUIT B
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
2
0
2
4
6
8
10
kW
SDT
SST
TC
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
53
38AH024
SST
(F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
38AH028
SST
(F)
20
25
30
35
40
45
50
54
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
75
168.4
13.5
95.0
189.0
13.9
97.0
210.2
14.3
98.0
231.6
14.8
99.0
256.8
15.1
102.0
284.0
15.7
104.0
306.0
16.0
106.0
SST
(F)
20
25
30
35
40
45
50
kW
SDT
SST
TC
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
75
198.0
16.6
97.0
223.5
17.1
97.0
249.4
17.6
97.0
276.2
18.0
99.0
304.5
18.7
101.0
335.0
19.3
103.0
367.0
19.7
106.0
LEGEND
Compressor Power
Saturated Discharge Temperature at Compressor (F)
Saturated Suction Temperature
Gross Cooling Capacity (1000 Btuh)
NOTES:
1. Ratings are based on 15 F superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
70
293.0
22.9
91.0
332.0
23.7
91.6
373.0
24.4
92.4
416.0
25.1
93.6
462.0
25.8
94.9
509.0
26.4
96.4
560.0
27.0
98.0
80
268.0
24.4
102.0
305.0
25.5
101.5
345.0
26.5
102.0
387.0
27.5
103.5
431.0
28.4
104.5
477.0
29.3
106.0
525.0
30.2
107.5
85
255.0
25.1
106.0
292.0
26.3
106.5
331.0
27.5
107.0
372.0
28.6
108.0
415.0
29.7
109.5
460.0
30.6
111.0
508.0
31.7
112.5
90
242.0
25.8
111.0
279.0
27.1
111.5
317.0
28.4
112.0
357.0
29.6
113.0
400.0
30.9
113.5
444.0
32.0
115.0
491.0
33.1
117.0
110
189.3
27.0
131.0
224.0
29.1
131.0
259.0
31.1
131.5
297.0
33.0
132.5
336.0
34.8
133.0
376.0
36.5
134.5
419.0
38.2
135.5
115
175.9
27.1
135.5
210.0
29.4
136.0
244.0
31.6
136.5
281.0
33.6
136.5
320.0
35.6
138.0
359.0
37.5
139.0
401.0
39.3
140.5
120
162.6
27.0
140.5
195.1
29.6
141.0
230.0
31.9
141.0
265.0
34.1
141.5
303.0
36.3
142.5
343.0
38.4
144.0
384.0
40.4
145.5
125
149.1
26.7
145.5
180.8
29.5
146.0
214.0
32.1
146.0
250.0
34.5
146.5
287.0
36.9
147.5
325.0
39.2
148.5
366.0
41.3
149.5
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
70
341.0
27.8
95.5
387.0
28.9
96.0
435.0
29.9
96.7
485.0
30.9
97.7
538.0
31.9
99.2
593.0
32.9
100.9
652.0
34.0
102.7
80
313.0
29.5
105.5
357.0
30.9
105.5
403.0
32.3
106.5
451.0
33.5
107.0
503.0
34.8
108.5
555.0
36.1
110.0
611.0
37.4
112.0
85
299.0
30.2
110.5
342.0
31.8
110.5
386.0
33.3
111.0
434.0
34.8
112.0
485.0
36.1
113.0
537.0
37.6
114.5
592.0
39.1
116.5
90
286.0
30.9
115.5
327.0
32.6
115.5
371.0
34.3
116.0
417.0
35.9
117.0
467.0
37.5
118.0
518.0
39.1
119.5
571.0
40.6
121.0
110
231.2
32.6
135.5
268.0
35.1
135.5
308.0
37.4
136.0
350.0
39.7
136.5
395.0
41.9
137.0
442.0
44.1
138.5
491.0
46.3
139.5
115
217.6
32.9
140.5
253.0
35.6
140.5
292.0
38.0
141.0
333.0
40.5
141.0
377.0
42.9
142.0
423.0
45.2
143.0
471.0
47.5
144.5
120
204.9
33.0
145.5
239.2
35.9
145.5
277.0
38.5
145.5
316.0
41.1
146.0
359.0
43.7
146.5
403.0
46.3
148.0
450.0*
48.8*
149.0*
125
191.2*
33.0*
150.5*
225.1*
36.0*
150.5*
261.0*
38.9*
150.5*
300.0*
41.7*
151.0*
341.0*
44.5*
151.5*
385.0*
47.1*
153.0*
431.0*
49.8*
153.5*
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kWP
SDT
TC
kW
SDT
70
415.0
33.6
93.4
468.0
34.9
94.0
523.0
36.2
95.0
582.0
37.4
96.3
644.0
38.7
98.0
708.0
40.0
100.0
776.0
41.2
102.0
80
383.0
35.7
103.0
434.0
37.4
104.0
487.0
39.0
104.5
544.0
40.6
105.5
603.0
42.2
107.5
664.0
43.9
109.0
729.0
45.5
111.0
85
368.0
36.7
108.0
417.0
38.6
109.0
469.0
40.3
109.5
525.0
42.1
110.5
582.0
43.9
112.5
642.0
45.7
114.0
706.0
47.5
116.0
90
352.0
37.5
113.0
401.0
39.6
113.5
451.0
41.5
114.5
505.0
43.5
115.5
562.0
45.5
116.5
620.0
47.4
118.5
682.0
49.4
120.5
110
290.0
40.1
133.0
335.0
42.8
133.5
380.0
45.5
134.0
429.0
48.2
134.5
481.0
50.8
136.0
535.0
53.5
137.5
591.0
56.2
139.5
115
275.0
40.5
138.0
318.0
43.4
138.0
363.0
46.3
139.0
410.0
49.2
139.5
461.0
52.0
140.5
514.0
54.9
142.5
569.0
57.7
143.5
120
261.0
40.8
143.0
302.0
43.9
143.0
346.0
47.0
144.0
393.0
50.0
144.5
442.0
53.0
145.5
493.0
56.1
146.6
546.0
59.1
148.5
125
246.0
41.0
148.0
285.0
44.3
148.0
328.0
47.5
149.0
374.0
50.7
149.5
421.0*
54.0*
150.5*
471.0*
57.1*
151.5*
523.0*
60.3*
153.5*
SST
(F)
20
25
30
35
40
45
50
38AH054
SST
(F)
20
25
30
35
40
45
50
38AH064
SST
(F)
20
25
30
35
40
45
50
kW
SDT
SST
TC
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (1000 Btuh)
55
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
70
513.0
42.4
92.1
574.0
44.1
92.7
638.0
45.8
93.9
706.0
47.7
95.5
776.0
49.5
97.3
850.0
51.2
99.3
930.0
53.0
101.5
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
70
574.0
50.7
97.1
644.0
52.9
97.2
721.0
54.9
97.4
802.0
56.9
98.1
887.0
58.9
99.2
976.0
61.1
100.5
1067.0
63.3
102.5
80
478.0
44.9
102.0
538.0
47.0
102.5
600.0
49.1
103.5
664.0
51.3
104.5
731.0
53.6
106.5
803.0
55.8
108.5
879.0
57.9
110.5
85
461.0
46.0
107.0
520.0
48.3
107.0
580.0
50.6
108.0
643.0
53.0
109.5
710.0
55.4
111.5
780.0
57.8
113.0
853.0
60.3
115.0
90
444.0
47.1
112.0
501.0
49.6
112.0
561.0
52.1
113.0
623.0
54.6
114.5
688.0
57.2
116.0
756.0
59.8
118.0
828.0
62.5
120.0
110
376.0
50.2
131.5
428.0
53.5
132.0
483.0
56.8
132.5
540.0
60.1
133.5
600.0
63.4
134.5
662.0
66.8
136.5
727.0
70.3
138.0
115
360.0
50.8
136.5
410.0
54.3
137.0
463.0
57.8
137.0
520.0
61.3
138.0
578.0
64.8
139.5
640.0
68.4
141.0
703.0
72.1
143.0
120
342.0
51.2
142.0
392.0
54.9
142.0
444.0
58.6
142.0
499.0
62.3
143.0
557.0
66.0
144.0
616.0
69.8
145.5
678.0
73.7
147.0
125
326.0
51.6
147.0
373.0
55.4
147.0
425.0
59.3
147.0
479.0
63.2
148.0
534.0
67.1
148.5
593.0*
71.1*
150.0*
653.0*
75.1*
152.0*
120
395.0
60.6
147.0
448.0
64.8
147.0
506.0
69.0
147.0
568.0
73.2
147.0
634.0
77.5
148.0
705.0
81.8
149.0
779.0
86.2
150.0
125
378.0*
61.1*
152.0*
430.0*
65.5*
152.0*
486.0*
69.9*
152.0*
546.0*
74.4*
152.0*
610.0*
78.8*
153.0*
679.0*
83.3*
154.0*
750.0*
87.9*
154.5*
38AH084
SST
(F)
20
25
30
35
40
45
50
kW
SDT
SST
TC
56
80
536.0
53.3
107.0
604.0
55.9
107.0
676.0
58.5
107.0
754.0
60.9
108.0
835.0
63.5
109.0
920.0
66.1
110.5
1009.0
68.7
112.0
85
518.0
54.5
112.0
584.0
57.3
112.0
654.0
60.1
112.0
730.0
62.9
113.0
809.0
65.5
113.5
893.0
68.3
115.0
980.0
71.3
116.5
90
500.0
55.6
117.0
564.0
58.7
117.0
632.0
61.7
117.0
706.0
64.7
118.0
785.0
67.5
118.5
866.0
70.6
119.5
950.0
73.7
121.5
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (1000 Btuh)
110
429.0
59.2
137.0
486.0
63.0
137.0
548.0
66.8
137.0
614.0
70.7
138.0
684.0
74.5
138.0
758.0
78.5
139.0
836.0
82.4
140.5
115
412.0
59.9
142.0
467.0
64.0
142.0
526.0
68.0
142.0
590.0
72.0
143.0
659.0
76.1
143.0
731.0
80.2
144.0
807.0
84.4
145.0
20
25
30
35
40
45
50
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
70
657.0
54.3
93.9
92.1
91.7
90.4
738.0
56.5
95.0
92.4
92.1
90.2
821.0
58.8
96.7
93.3
93.0
90.5
907.0
61.3
98.7
94.7
94.3
91.2
999.0
63.8
101.0
96.5
95.7
92.3
1093.0
66.3
104.0
98.6
97.4
93.6
1193.0
68.9
106.0
101.0
99.1
95.1
80
611.0
57.4
104.0
102.0
102.0
101.0
689.0
60.2
105.0
102.0
102.0
100.0
769.0
62.9
106.0
103.0
103.0
101.0
853.0
65.8
108.0
104.0
104.0
101.0
940.0
68.8
110.0
106.0
106.0
102.0
1031.0
71.8
112.0
108.0
108.0
104.0
1127.0
74.8
115.0
110.0
109.0
105.0
85
588.0
59.0
109.0
107.0
107.0
106.0
663.0
62.0
109.0
107.0
108.0
106.0
743.0
65.0
111.0
108.0
108.0
106.0
825.0
68.1
112.0
109.0
109.0
107.0
911.0
71.3
115.0
111.0
111.0
108.0
1001.0
74.6
117.0
112.0
113.0
109.0
1095.0
77.8
119.0
114.0
114.0
110.0
LEGEND
kW
Compressor Power
SCT(A) Saturated Condensing Temperature (F) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SCT(B) Saturated Condensing Temperature (F) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SDT(A) Saturated Discharge Temperature (F) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SDT(B) Saturated Discharge Temperature (F) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SST
Saturated Suction Temperature Entering Condensing Unit
TC
Gross Cooling Capacity (1000 Btuh)
110
470.0
63.9
134.0
132.0
133.0
131.0
538.0
68.3
134.0
132.0
133.0
131.0
611.0
72.7
134.0
132.0
133.0
131.0
686.0
77.0
136.0
133.0
134.0
132.0
764.0
81.4
137.0
134.0
135.0
132.0
845.0
86.0
139.0
136.0
137.0
134.0
929.0
90.5
142.0
137.0
139.0
135.0
115
446.0
64.4
139.0
137.0
138.0
136.0
514.0
69.1
139.0
137.0
138.0
136.0
585.0
73.8
139.0
137.0
138.0
136.0
658.0
78.4
140.0
138.0
139.0
137.0
734.0
83.1
142.0
139.0
140.0
137.0
814.0
87.9
144.0
140.0
142.0
138.0
896.0
92.7
146.0
142.0
143.0
140.0
120
423.0
64.7
144.0
142.0
143.0
142.0
488.0
69.8
144.0
142.0
143.0
141.0
557.0
74.7
144.0
142.0
143.0
141.0
630.0
79.6
145.0
143.0
144.0
142.0
704.0
84.5
146.0
144.0
145.0
142.0
782.0
89.6
148.0
145.0
146.0
143.0
862.0
94.7
150.0
147.0
148.0
145.0
125
400.0
64.8
149.0
147.0
148.0
147.0
463.0
70.2
149.0
147.0
148.0
146.0
531.0
75.5
149.0
147.0
148.0
146.0
602.0
80.7
150.0
148.0
149.0
147.0
675.0
85.9
151.0
149.0
150.0
147.0
751.0
91.2
153.0
150.0
151.0
148.0
829.0
96.6
155.0*
151.0
153.0
149.0
57
20
25
30
35
40
45
50
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
70
747.0
58.4
91.9
93.5
89.8
90.9
837.0
61.0
93.0
95.1
90.2
91.7
932.0
63.8
94.7
97.1
91.2
92.9
1032.0
66.7
96.7
99.4
92.5
94.4
1137.0
69.5
98.9
102.0
94.0
96.0
1247.0
72.4
101.0
105.0
95.6
97.8
1363.0
75.5
104.0
108.0
97.3
99.6
80
689.0
62.2
102.0
103.0
100.0
101.0
777.0
65.2
102.0
104.0
100.0
102.0
869.0
68.5
104.0
106.0
101.0
103.0
964.0
71.8
106.0
108.0
103.0
104.0
1065.0
75.2
108.0
111.0
104.0
106.0
1170.0
78.7
110.0
113.0
106.0
108.0
1281.0
82.2
113.0
116.0
107.0
110.0
85
661.0
63.9
107.0
108.0
105.0
106.0
747.0
67.3
107.0
109.0
105.0
107.0
837.0
70.8
109.0
111.0
106.0
108.0
930.0
74.4
110.0
113.0
108.0
109.0
1029.0
78.1
112.0
115.0
109.0
111.0
1132.0
81.8
115.0
118.0
111.0
113.0
1240.0
85.6
117.0
120.0
112.0
115.0
90
633.0
65.6
112.0
113.0
110.0
111.0
718.0
69.2
112.0
114.0
111.0
112.0
805.0
72.9
113.0
115.0
111.0
113.0
896.0
76.8
115.0
117.0
112.0
114.0
993.0
80.7
117.0
120.0
114.0
116.0
1094.0
84.7
119.0
122.0
116.0
118.0
1199.0
88.8
122.0
125.0
117.0
120.0
LEGEND
kW
Compressor Power
SCT(A) Saturated Condensing Temperature (F) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SCT(B) Saturated Condensing Temperature (F) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SDT(A) Saturated Discharge Temperature (F) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SDT(B) Saturated Discharge Temperature (F) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SST
Saturated Suction Temperature Entering Condensing Unit
TC
Gross Cooling Capacity (1000 Btuh)
58
110
523.0
70.5
131.0
133.0
131.0
132.0
599.0
75.2
132.0
133.0
131.0
132.0
680.0
80.0
132.0
134.0
131.0
133.0
763.0
84.9
133.0
136.0
132.0
134.0
851.0
89.9
135.0
137.0
133.0
135.0
942.0
94.9
137.0
140.0
135.0
137.0
1037.0
100.1
139.0
142.0
137.0
139.0
115
495.0
71.3
136.0
138.0
136.0
137.0
571.0
76.4
137.0
138.0
136.0
137.0
649.0
81.4
137.0
139.0
136.0
138.0
731.0
86.6
138.0
140.0
137.0
139.0
816.0
91.8
140.0
142.0
138.0
140.0
905.0
97.1
141.0
144.0
140.0
142.0
998.0
102.6
144.0
146.0
141.0
144.0
120
469.0
71.9
141.0
142.0
141.0
142.0
541.0
77.4
141.0
143.0
141.0
142.0
619.0
82.7
142.0
144.0
141.0
143.0
698.0
88.1
143.0
145.0
142.0
144.0
781.0
93.6
144.0
147.0
143.0
145.0
868.0
99.2
146.0
149.0
144.0
147.0
958.0
104.9
148.0
151.0
146.0
148.0
125
443.0
72.4
146.0
147.0
146.0
147.0
513.0
78.1
146.0
148.0
146.0
147.0
588.0
83.8
147.0
148.0
146.0
148.0
665.0
89.5
148.0
150.0
147.0
148.0
747.0
95.3
149.0
151.0
148.0
150.0
831.0
101.2
150.0
153.0
149.0
151.0
919.0
107.1
152.0
155.0*
151.0
153.0
25
30
35
40
45
50
TC
kW
SDT(A) OR (B)
SCT(A) OR (B)
TC
kW
SDT(A) OR (B)
SCT(A) OR (B)
TC
kW
SDT(A) OR (B)
SCT(A) OR (B)
TC
kW
SDT(A) OR (B)
SCT(A) OR (B)
TC
kW
SDT(A) OR (B)
SCT(A) OR (B)
TC
kW
SDT(A) OR (B)
SCT(A) OR (B)
TC
kW
SDT(A) OR (B)
SCT(A) OR (B)
70
834.0
67.2
93.3
92.4
940.0
69.8
94.0
92.8
1050.0
72.4
95.0
93.5
1168.0
75.0
96.4
94.6
1290.0
77.6
98.1
95.9
1418.0
80.0
100.0
97.5
1552.0
82.6
102.0
99.3
80
772.0
71.4
103.0
103.0
872.0
74.6
104.0
103.0
980.0
78.0
105.0
103.0
1092.0
81.2
106.0
104.0
1208.0
84.4
108.0
106.0
1332.0
87.8
109.0
107.0
1460.0
91.0
112.0
109.0
85
740.0
73.4
108.0
108.0
840.0
77.0
109.0
108.0
944.0
80.6
110.0
108.0
1052.0
84.2
111.0
109.0
1168.0
87.8
112.0
111.0
1288.0
91.6
114.0
112.0
1414.0
95.2
116.0
114.0
LEGEND
kW
Compressor Power
SCT(A) Saturated Condensing Temperature (F) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SCT(B) Saturated Condensing Temperature (F) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SDT(A) Saturated Discharge Temperature (F) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SDT(B) Saturated Discharge Temperature (F) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SST
Saturated Suction Temperature Entering Condensing Unit
TC
Gross Cooling Capacity (1000 Btuh)
115
558.0
81.0
138.0
138.0
642.0
86.8
138.0
138.0
732.0
92.6
139.0
138.0
828.0
98.4
140.0
139.0
926.0
104.0
141.0
140.0
1032.0
109.8
142.0
141.0
1140.0
115.6
144.0
143.0
120
528.0
81.6
143.0
143.0
610.0
87.8
143.0
143.0
698.0
94.0
144.0
143.0
790.0
100.0
144.0
144.0
888.0
106.0
146.0
145.0
988.0
112.2
147.0
146.0
1096.0
118.2
149.0
147.0
125
498.0
82.0
148.0
148.0
578.0
88.6
148.0
148.0
662.0
95.0
149.0
148.0
752.0
101.4
149.0
149.0
848.0
108.0
150.0
150.0
946.0
114.4
152.0
151.0
1050.0
120.8
153.0
152.0
NOTES:
1. Ratings are based on 15 F superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
59
20
25
30
35
40
45
50
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
70
930.0
76.0
93.3
92.0
92.4
87.6
1045.0
79.0
94.0
92.7
92.8
88.6
1164.0
82.0
95.0
93.8
93.5
90.0
1290.0
85.1
96.4
95.4
94.6
91.5
1422.0
88.2
98.1
97.2
95.9
93.0
1561.0
91.2
100.0
99.2
97.5
94.6
1707.0
94.2
102.0
101.0
99.3
96.3
80
864.0
80.6
103.0
102.0
103.0
97.7
974.0
84.3
104.0
102.0
103.0
98.5
1090.0
88.1
105.0
103.0
103.0
99.7
1211.0
91.9
106.0
105.0
104.0
101.0
1337.0
95.7
108.0
107.0
106.0
103.0
1470.0
99.6
109.0
109.0
107.0
104.0
1610.0
103.4
112.0
111.0
109.0
106.0
85
831.0
82.8
108.0
107.0
108.0
103.0
940.0
86.8
109.0
107.0
108.0
103.0
1052.0
90.9
110.0
108.0
108.0
105.0
1170.0
95.1
111.0
110.0
109.0
106.0
1294.0
99.3
112.0
111.0
111.0
107.0
1425.0
103.6
114.0
113.0
112.0
109.0
1562.0
107.8
116.0
115.0
114.0
111.0
90
799.0
84.7
113.0
112.0
113.0
108.0
905.0
89.1
114.0
112.0
113.0
108.0
1015.0
93.6
114.0
113.0
113.0
109.0
1130.0
98.1
116.0
114.0
114.0
111.0
1252.0
102.7
117.0
116.0
116.0
112.0
1379.0
107.3
119.0
118.0
117.0
114.0
1513.0
111.9
121.0
120.0
119.0
116.0
LEGEND
kW
Compressor Power
SCT(A) Saturated Condensing Temperature (F) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SCT(B) Saturated Condensing Temperature (F) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SDT(A) Saturated Discharge Temperature (F) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SDT(B) Saturated Discharge Temperature (F) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SST
Saturated Suction Temperature Entering Condensing Unit
TC
Gross Cooling Capacity (1000 Btuh)
60
115
638.0
91.3
138.0
137.0
138.0
133.0
731.0
97.7
138.0
137.0
138.0
133.0
830.0
104.0
139.0
137.0
138.0
134.0
934.0
110.4
140.0
138.0
139.0
135.0
1042.0
116.7
141.0
139.0
140.0
136.0
1156.0
123.2
142.0
141.0
141.0
137.0
1274.0
129.8
144.0
143.0
143.0
139.0
120
606.0
92.1
143.0
142.0
143.0
138.0
697.0
98.8
143.0
142.0
143.0
138.0
794.0
105.6
144.0
142.0
143.0
139.0
895.0
112.2
144.0
143.0
144.0
139.0
1001.0
119.0
146.0
144.0
145.0
141.0
1111.0
125.8
147.0
145.0
145.0
142.0
1227.0
132.7
149.0
147.0
147.0
144.0
NOTES:
1. Ratings are based on 15 F superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
125
575.0
92.6
148.0
147.0
148.0
143.0
663.0
99.8
148.0
147.0
148.0
143.0
756.0
106.8
149.0
147.0
148.0
144.0
855.0
113.9
149.0
148.0
149.0
144.0
959.0
121.1
150.0
149.0
150.0
145.0
1066.0
128.3
152.0
150.0
150.0
147.0
1179.0
135.5
153.0
152.0
152.0
148.0
LEGEND
Compressor Power
Saturated Discharge Temperature at Compressor (F)
Saturated Suction Temperature
Gross Cooling Capacity (1000 Btuh)
NOTES:
1. Ratings are based on 15 F superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
kW
SDT
SST
TC
61
20
25
30
35
40
45
50
70
147.0
11.3
89.4
166.0
11.7
90.3
186.0
12.1
91.6
207.0
12.5
93.2
229.0
12.9
95.0
252.0
13.3
96.9
276.0
13.7
99.0
80
135.0
12.1
99.1
153.0
12.6
99.9
172.0
13.1
101.0
193.0
13.7
103.0
214.0
14.2
104.0
236.0
14.7
106.0
259.0
15.2
108.0
85
128.0
12.4
104.0
147.0
13.0
105.0
166.1
13.6
106.0
185.0
14.2
107.0
206.0
14.8
109.0
228.0
15.3
111.0
251.0
15.9
113.0
90
122.0
12.8
109.0
140.0
13.4
110.0
159.0
14.1
111.0
178.0
14.7
112.0
199.0
15.4
113.0
220.0
16.0
115.0
243.0
16.6
117.0
110
95.6
13.5
129.0
113.0
14.5
129.0
130.0
15.5
130.0
149.0
16.4
131.0
168.0
17.3
132.0
187.0
18.2
134.0
208.0
19.1
135.0
115
88.9
13.6
134.0
106.0
14.7
134.0
123.0
15.7
135.0
141.0
16.7
135.0
160.0
17.7
137.0
179.0
18.7
138.0
199.0
19.6
140.0
120
82.2
13.5
139.0
98.6
14.8
139.0
116.0
15.9
139.0
133.0
17.0
140.0
152.0
18.1
141.0
171.0
19.1
143.0
191.0
20.1
145.0
125
75.5
13.4
144.0
91.5
14.8
144.0
108.0
16.0
144.0
126.0
17.2
145.0
144.0
18.4
146.0
162.0
19.5
147.0
182.0
20.6
149.0
120
80.9
13.4
145.0
97.2
14.8
145.0
115.0
16.0
145.0
133.0
17.2
145.0
153.0
18.3
145.0
174.0
19.4
146.0
196.0*
20.4*
146.0*
125
74.2*
13.2*
150.0*
90.1*
14.7*
150.0*
107.0*
16.1*
150.0*
125.0*
17.4*
150.0*
145.0*
18.6*
150.0*
166.0*
19.7*
151.0*
187.0*
20.8*
151.0*
120
124.0
19.5
143.0
143.0
20.9
143.0
163.0
22.3
144.0
185.0
23.7
145.0
208.0
25.1
146.0
232.0
26.6
147.0
257.0
28.0
149.0
125
117.0
19.7
148.0
135.0
21.2
148.0
155.0
22.6
149.0
176.0
24.1
150.0
198.0*
25.6*
151.0*
221.0*
27.1*
152.0*
246.0*
28.6*
154.0*
38AH054 CIRCUIT A
SST
(F)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
20
25
30
35
40
45
50
70
146.0
11.8
95.1
166.0
12.2
95.1
188.0
12.5
95.3
210.0
12.8
95.7
234.0
13.1
96.4
258.0
13.4
97.7
284.0
13.7
99.3
80
133.0
12.5
105.0
153.0
13.1
105.0
174.0
13.6
105.0
195.0
14.0
105.0
219.0
14.4
106.0
242.0
14.8
107.0
267.0
15.2
109.0
85
127.0
12.8
110.0
146.0
13.5
110.0
166.0
14.0
110.0
188.0
14.6
110.0
211.0
15.0
111.0
234.0
15.5
112.0
259.0
16.0
113.0
90
121.0
13.1
115.0
139.0
13.8
115.0
159.0
14.5
115.0
180.0
15.1
115.0
203.0
15.6
116.0
226.0
16.2
117.0
250.0
16.7
118.0
70
197.0
15.7
93.5
222.0
16.3
94.2
249.0
17.0
95.4
278.0
17.6
96.9
308.0
18.3
98.8
339.0
19.0
101.0
372.0
19.6
103.0
80
181.0
16.7
103.0
205.0
17.5
104.0
231.0
18.3
105.0
258.0
19.1
106.0
287.0
19.9
108.0
316.0
20.8
110.0
348.0
21.6
112.0
85
174.0
17.2
108.0
197.0
18.1
109.0
222.0
18.9
110.0
249.0
19.8
111.0
276.0
20.7
113.0
305.0
21.6
115.0
336.0
22.5
117.0
90
166.0
17.6
113.0
189.0
18.6
114.0
213.0
19.5
115.0
239.0
20.5
116.0
266.0
21.5
117.0
294.0
22.4
119.0
324.0
23.4
121.0
115
87.6
13.5
140.0
104.0
14.8
140.0
122.0
15.9
140.0
141.0
17.0
140.0
162.0
18.0
140.0
183.0
18.9
141.0
206.0
19.8
142.0
38AH064 CIRCUIT A
SST
(F)
20
25
30
35
40
45
50
kW
SDT
SST
TC
62
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
110
137.0
19.0
133.0
158.0
20.3
134.0
179.0
21.6
134.0
202.0
22.8
135.0
227.0
24.0
136.0
252.0
25.3
138.0
279.0
26.6
140.0
115
130.0
19.3
138.0
150.0
20.6
138.0
171.0
21.9
139.0
193.0
23.3
140.0
217.0
24.6
141.0
242.0
26.0
143.0
268.0
27.3
144.0
20
25
30
35
40
45
50
70
146.0
11.6
92.6
166.0
12.0
92.9
187.0
12.3
93.2
209.0
12.6
93.9
233.0
12.9
94.7
257.0
13.1
95.8
284.0
13.3
97.0
80
133.0
12.3
103.0
152.0
12.9
103.0
173.0
13.4
103.0
194.0
13.8
104.0
217.0
14.2
105.0
241.0
14.6
106.0
266.0
15.0
107.0
85
127.0
12.7
108.0
145.0
13.3
108.0
165.0
13.9
108.0
187.0
14.4
109.0
209.0
14.9
110.0
232.0
15.3
111.0
257.0
15.8
112.0
90
120.0
13.0
113.0
139.0
13.7
113.0
158.0
14.3
113.0
179.0
14.9
114.0
201.0
15.5
114.0
224.0
16.0
115.0
248.0
16.5
117.0
110
93.7
13.5
132.0
111.0
14.6
133.0
129.0
15.6
133.0
148.0
16.6
133.0
168.0
17.4
134.0
189.0
18.3
135.0
211.0
19.1
136.0
115
87.0
13.5
137.0
104.0
14.7
138.0
121.0
15.9
138.0
140.0
16.9
138.0
160.0
17.9
139.0
180.0
18.8
140.0
202.0
19.7
141.0
120
80.4
13.5
142.0
96.5
14.8
143.0
114.0
16.0
143.0
132.0
17.1
143.0
151.0
18.2
144.0
172.0
19.3
145.0
193.0
20.3
146.0
125
73.6
13.3
147.0
89.3
14.7
148.0
106.0
16.1
148.0
124.0
17.3
148.0
143.0
18.5
149.0
163.0
19.7
150.0
184.0
20.7
150.0
70
195.0
16.0
96.0
221.0
16.7
96.8
247.0
17.4
98.1
275.0
18.1
99.7
304.0
18.8
102.0
335.0
19.5
104.0
368.0
20.3
106.0
80
180.0
17.0
106.0
204.0
17.8
106.0
229.0
18.7
108.0
256.0
19.5
109.0
284.0
20.4
111.0
313.0
21.3
113.0
344.0
22.2
115.0
85
172.0
17.4
111.0
196.0
18.3
111.0
220.0
19.3
112.0
246.0
20.2
114.0
274.0
21.1
115.0
303.0
22.1
117.0
333.0
23.1
120.0
90
165.0
17.8
116.0
188.0
18.8
116.0
212.0
19.8
117.0
237.0
20.8
119.0
264.0
21.9
120.0
292.0
22.9
122.0
321.0
23.9
124.0
110
137.0
19.1
136.0
157.0
20.4
136.0
178.0
21.7
137.0
201.0
23.0
138.0
225.0
24.3
139.0
250.0
25.7
141.0
276.0
27.0
142.0
115
130.0
19.4
141.0
149.0
20.8
141.0
170.0
22.1
142.0
192.0
23.5
142.0
215.0
24.9
144.0
240.0
26.3
145.0
265.0
27.7
147.0
120
124.0
19.6
146.0
142.0
21.1
146.0
162.0
22.5
146.0
183.0
23.9
147.0
206.0
25.4
148.0
229.0
26.9
150.0
254.0*
28.4*
152.0*
125
117.0*
19.8*
151.0*
135.0*
21.3*
151.0*
154.0*
22.8*
151.0*
175.0*
24.3*
152.0*
196.0*
25.9*
153.0*
219.0*
27.4*
155.0*
244.0*
29.0*
156.0*
70
218.0
17.9
93.2
246.0
18.6
93.7
274.0
19.2
94.5
304.0
19.8
95.7
336.0
20.4
97.1
369.0
21.0
98.9
404.0
21.6
101.0
80
202.0
19.0
103.0
229.0
19.9
104.0
256.0
20.7
104.0
286.0
21.5
105.0
316.0
22.3
107.0
348.0
23.1
108.0
381.0
23.9
110.0
85
194.0
19.5
108.0
220.0
20.5
109.0
247.0
21.4
109.0
276.0
22.3
110.0
306.0
23.2
112.0
337.0
24.1
113.0
370.0
25.0
115.0
90
186.0
19.9
113.0
212.0
21.0
113.0
238.0
22.0
114.0
266.0
23.0
115.0
296.0
24.0
116.0
326.0
25.0
118.0
358.0
26.0
120.0
110
153.0
21.1
133.0
177.0
22.5
133.0
201.0
24.0
134.0
227.0
25.4
134.0
254.0
26.8
136.0
283.0
28.2
137.0
312.0
29.6
139.0
115
145.0
21.2
138.0
168.0
22.8
138.0
192.0
24.4
139.0
217.0
25.9
139.0
244.0
27.4
140.0
272.0
28.9
142.0
301.0
30.4
143.0
120
137.0
21.3
143.0
159.0
23.0
143.0
183.0
24.7
144.0
208.0
26.3
144.0
234.0
27.9
145.0
261.0
29.5
146.0
289.0
31.1
148.0
125
129.0
21.3
148.0
150.0
23.1
148.0
173.0
24.9
149.0
198.0
26.6
149.0
223.0*
28.4*
150.0*
250.0*
30.0*
151.0*
277.0*
31.7*
153.0*
38AH054 CIRCUIT B
SST
(F)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
20
25
30
35
40
45
50
38AH064 CIRCUIT B
SST
(F)
20
25
30
35
40
45
50
kW
SDT
SST
TC
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
63
20
25
30
35
40
45
50
70
221.0
17.8
92.4
249.0
18.4
92.7
277.0
19.0
93.6
307.0
19.7
95.0
338.0
20.3
96.7
370.0
20.9
98.6
405.0
21.5
101.0
80
205.0
18.9
102.0
232.0
19.7
103.0
260.0
20.5
103.0
288.0
21.3
104.0
318.0
22.2
106.0
350.0
23.0
108.0
383.0
23.7
110.0
85
197.0
19.4
107.0
224.0
20.3
107.0
251.0
21.2
108.0
279.0
22.1
109.0
309.0
23.0
111.0
340.0
23.9
112.0
372.0
24.8
114.0
90
189.0
19.9
112.0
215.0
20.9
112.0
242.0
21.9
113.0
270.0
22.8
114.0
299.0
23.8
115.0
329.0
24.8
117.0
361.0
25.8
119.0
70
286.0
25.5
98.1
321.0
26.6
98.1
360.0
27.6
98.3
400.0
28.6
98.9
443.0
29.6
99.9
488.0
30.7
101.0
534.0
31.8
103.0
80
267.0
26.8
108.0
301.0
28.1
108.0
337.0
29.4
108.0
376.0
30.6
109.0
417.0
31.9
110.0
460.0
33.2
111.0
505.0
34.5
113.0
85
258.0
27.4
113.0
291.0
28.8
113.0
326.0
30.2
113.0
364.0
31.6
114.0
404.0
32.9
114.0
446.0
34.3
116.0
490.0
35.8
117.0
90
249.0
27.9
118.0
281.0
29.5
118.0
315.0
31.0
118.0
352.0
32.5
119.0
392.0
33.9
119.0
433.0
35.5
120.0
475.0
37.0
122.0
110
157.0
21.0
132.0
180.0
22.5
132.0
206.0
23.9
133.0
232.0
25.3
133.0
259.0
26.6
134.0
287.0
28.0
136.0
316.0
29.4
137.0
115
149.0
21.2
137.0
172.0
22.8
137.0
196.0
24.3
137.0
222.0
25.8
138.0
249.0
27.2
139.0
277.0
28.7
140.0
305.0
30.2
142.0
120
140.0
21.3
142.0
163.0
23.0
142.0
187.0
24.6
142.0
212.0
26.2
143.0
239.0
27.7
143.0
266.0
29.3
145.0
294.0
30.9
146.0
125
132.0
21.3
147.0
154.0
23.1
147.0
178.0
24.8
147.0
203.0
26.5
148.0
228.0
28.2
148.0
255.0*
29.9*
149.0*
282.0*
31.5*
151.0*
120
197.0
30.4
148.0
223.0
32.5
148.0
252.0
34.6
148.0
283.0
36.7
148.0
316.0
38.9
149.0
352.0
41.0
150.0
389.0*
43.2*
151.0*
125
188.0*
30.6*
153.0*
214.0*
32.8*
153.0*
242.0*
35.0*
153.0*
272.0*
37.3*
153.0*
304.0*
39.5*
154.0*
339.0*
41.8*
155.0*
375.0*
44.1*
155.0*
38AH084 CIRCUIT A
SST
(F)
20
25
30
35
40
45
50
kW
SDT
SST
TC
64
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
115
205.0
30.0
143.0
233.0
32.1
143.0
262.0
34.1
143.0
294.0
36.1
144.0
329.0
38.2
144.0
365.0
40.2
145.0
403.0
42.3
146.0
20
25
30
35
40
45
50
70
292.0
24.6
91.7
325.0
25.7
92.7
361.0
26.8
94.2
399.0
28.0
96.0
438.0
29.2
97.9
480.0
30.3
100.0
525.0
31.5
102.0
80
273.0
26.0
102.0
306.0
27.3
102.0
340.0
28.6
104.0
376.0
30.0
105.0
413.0
31.4
107.0
453.0
32.8
109.0
496.0
34.2
111.0
85
264.0
26.6
107.0
296.0
28.0
107.0
329.0
29.4
108.0
364.0
30.9
110.0
401.0
32.4
112.0
440.0
33.9
114.0
481.0
35.5
116.0
90
255.0
27.2
112.0
286.0
28.7
112.0
319.0
30.2
113.0
353.0
31.8
115.0
389.0
33.4
117.0
427.0
35.0
119.0
467.0
36.7
121.0
110
219.0
29.2
131.0
248.0
31.0
132.0
277.0
32.9
132.0
308.0
34.8
134.0
341.0
36.8
135.0
375.0
38.8
137.0
411.0
40.9
139.0
115
211.0
29.6
136.0
238.0
31.5
137.0
267.0
33.5
137.0
298.0
35.5
138.0
329.0
37.6
140.0
363.0
39.7
142.0
398.0
41.9
144.0
120
202.0
29.9
142.0
229.0
31.9
142.0
257.0
34.0
142.0
287.0
36.1
143.0
318.0
38.3
145.0
350.0
40.5
146.0
384.0
42.8
148.0
70
288.0
25.2
96.1
323.0
26.3
96.2
361.0
27.3
96.5
402.0
28.3
97.3
444.0
29.3
98.5
488.0
30.4
100.0
533.0
31.5
102.0
80
269.0
26.5
106.0
303.0
27.8
106.0
339.0
29.1
106.0
378.0
30.3
107.0
418.0
31.6
108.0
460.0
32.9
110.0
504.0
34.2
111.0
85
260.0
27.1
111.0
293.0
28.5
111.0
328.0
29.9
111.0
366.0
31.3
112.0
405.0
32.6
113.0
447.0
34.0
114.0
490.0
35.5
116.0
90
251.0
27.7
116.0
283.0
29.2
116.0
317.0
30.7
116.0
354.0
32.2
117.0
393.0
33.6
118.0
433.0
35.1
119.0
475.0
36.7
121.0
110
215.0
29.5
136.0
244.0
31.4
136.0
275.0
33.3
136.0
308.0
35.2
137.0
343.0
37.1
137.0
379.0
39.1
138.0
418.0
41.1
140.0
115
207.0
29.9
141.0
234.0
31.9
141.0
264.0
33.9
141.0
296.0
35.9
142.0
330.0
37.9
142.0
366.0
40.0
143.0
404.0
42.1
144.0
120
198.0
30.2
146.0
225.0
32.3
146.0
254.0
34.4
146.0
285.0
36.5
146.0
318.0
38.6
147.0
353.0
40.8
148.0
390.0
43.0
149.0
125
194.0
30.3
147.0
219.0
32.3
147.0
247.0
34.5
147.0
276.0
36.7
148.0
306.0
38.9
149.0
338.0*
41.2*
151.0*
371.0*
43.6*
153.0*
38AH084 CIRCUIT B
SST
(F)
20
25
30
35
40
45
50
kW
SDT
SST
TC
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
125
190.0*
30.5*
151.0*
216.0*
32.7*
151.0*
244.0*
34.9*
151.0*
274.0*
37.1*
151.0*
306.0*
39.3*
152.0*
340.0*
41.5*
153.0*
375.0*
43.8*
154.0*
65
20
25
30
35
40
45
50
70
366.0
29.7
93.9
91.7
411.0
30.9
95.0
92.1
457.0
32.2
96.7
93.0
505.0
33.6
98.7
94.3
556.0
35.0
101.0
95.7
608.0
36.4
104.0
97.4
663.0
37.8
106.0
99.1
80
338.0
31.4
104.0
102.0
382.0
33.0
105.0
102.0
427.0
34.5
106.0
103.0
474.0
36.1
108.0
104.0
522.0
37.8
110.0
106.0
573.0
39.4
112.0
108.0
626.0
41.1
115.0
109.0
85
324.0
32.3
109.0
107.0
367.0
34.0
109.0
108.0
412.0
35.7
111.0
108.0
458.0
37.4
112.0
109.0
506.0
39.2
115.0
111.0
556.0
41.0
117.0
113.0
608.0
42.8
119.0
114.0
70
349.0
27.0
91.9
89.8
392.0
28.1
93.0
90.2
437.0
29.3
94.7
91.2
484.0
30.6
96.7
92.5
534.0
38.1
98.9
94.0
586.0
33.0
101.0
95.6
640.0
34.3
104.0
97.3
80
321.0
28.8
102.0
100.0
363.0
30.1
102.0
100.0
407.0
31.6
104.0
101.0
452.0
33.0
106.0
103.0
500.0
34.5
108.0
104.0
550.0
36.0
110.0
106.0
602.0
37.5
113.0
107.0
85
308.0
29.6
107.0
105.0
349.0
31.1
107.0
105.0
392.0
32.7
109.0
106.0
436.0
34.3
110.0
108.0
483.0
35.9
112.0
109.0
532.0
37.5
115.0
111.0
583.0
39.2
117.0
112.0
90
310.0
33.0
114.0
113.0
352.0
34.8
114.0
113.0
396.0
36.7
115.0
113.0
442.0
38.6
117.0
114.0
489.0
40.5
119.0
116.0
538.0
42.4
121.0
118.0
589.0
44.4
124.0
119.0
110
251.0
34.7
134.0
133.0
291.0
37.3
134.0
133.0
333.0
39.8
134.0
133.0
376.0
42.3
136.0
134.0
420.0
44.8
137.0
135.0
465.0
47.4
139.0
137.0
512.0
49.9
142.0
139.0
115
236.0
34.8
139.0
138.0
276.0
37.6
139.0
138.0
317.0
40.3
139.0
138.0
359.0
43.0
140.0
139.0
402.0
45.7
142.0
140.0
447.0
48.4
144.0
142.0
493.0
51.1
146.0
143.0
120
221.0
34.7
144.0
143.0
260.0
37.8
144.0
143.0
300.0
40.7
144.0
143.0
342.0
43.6
145.0
144.0
384.0
46.4
146.0
145.0
428.0
49.3
148.0
146.0
473.0
52.2
150.0
148.0
125
207.0
34.5
149.0
148.0
244.0
37.8
149.0
148.0
284.0
41.0
149.0
148.0
325.0
44.1
150.0
149.0
367.0
47.1
151.0
150.0
410.0
50.1
153.0
151.0
454.0
53.2
155.0*
153.0
38AH104 CIRCUIT A
SST
(F)
20
25
30
35
40
45
50
kW
SCT
SDT
SST
TC
66
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
90
294.0
30.4
112.0
110.0
335.0
32.0
112.0
111.0
377.0
33.7
113.0
111.0
420.0
35.4
115.0
112.0
466.0
37.1
117.0
114.0
514.0
38.9
119.0
116.0
564.0
40.7
122.0
117.0
LEGEND
Compressor Power
Saturated Condensing Temperature (F)
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
110
240.0
32.5
131.0
131.0
277.0
34.7
132.0
131.0
316.0
37.0
132.0
131.0
356.0
39.2
133.0
132.0
398.0
41.5
135.0
133.0
442.0
43.8
137.0
135.0
487.0
46.1
139.0
137.0
115
226.0
32.8
136.0
136.0
263.0
35.2
137.0
136.0
301.0
37.6
137.0
136.0
340.0
40.0
138.0
137.0
381.0
42.4
140.0
138.0
424.0
44.8
141.0
140.0
468.0
47.3
144.0
141.0
120
213.0
32.9
141.0
141.0
248.0
35.6
141.0
141.0
286.0
38.1
142.0
141.0
324.0
40.7
143.0
142.0
364.0
43.2
144.0
143.0
406.0
45.8
146.0
144.0
449.0
48.4
148.0
146.0
125
200.0
33.0
146.0
146.0
234.0
35.8
146.0
146.0
271.0
38.6
147.0
146.0
308.0
41.3
148.0
147.0
348.0
44.0
149.0
148.0
388.0
46.7
150.0
149.0
431.0
49.4
152.0
151.0
20
25
30
35
40
45
50
70
291.0
24.6
92.1
90.4
327.0
25.6
92.4
90.2
364.0
26.6
93.3
90.5
402.0
27.7
94.7
91.2
443.0
28.8
96.5
92.3
485.0
29.9
98.6
93.6
530.0
31.1
101.0
95.1
80
273.0
26.0
102.0
101.0
307.0
27.2
102.0
100.0
342.0
28.4
103.0
101.0
379.0
29.7
104.0
101.0
418.0
31.0
106.0
102.0
458.0
32.4
108.0
104.0
501.0
33.7
110.0
105.0
85
264.0
26.7
107.0
106.0
296.0
28.0
107.0
106.0
331.0
29.3
108.0
106.0
367.0
30.7
109.0
107.0
405.0
32.1
111.0
108.0
445.0
33.6
112.0
109.0
487.0
35.0
114.0
110.0
90
254.0
27.2
112.0
111.0
286.0
28.7
112.0
111.0
320.0
30.1
113.0
111.0
356.0
31.6
114.0
112.0
393.0
33.1
115.0
113.0
432.0
34.7
117.0
114.0
473.0
36.3
119.0
115.0
110
219.0
29.2
132.0
131.0
247.0
31.0
132.0
131.0
278.0
32.9
132.0
131.0
310.0
34.7
133.0
132.0
344.0
36.6
134.0
132.0
380.0
38.6
136.0
134.0
417.0
40.6
137.0
135.0
115
210.0
29.6
137.0
136.0
238.0
31.5
137.0
136.0
268.0
33.5
137.0
136.0
299.0
35.4
138.0
137.0
332.0
37.4
139.0
137.0
367.0
39.5
140.0
138.0
403.0
41.6
142.0
140.0
120
202.0
30.0
142.0
142.0
228.0
32.0
142.0
141.0
257.0
34.0
142.0
141.0
288.0
36.0
143.0
142.0
320.0
38.1
144.0
142.0
354.0
40.3
145.0
143.0
389.0
42.5
147.0
145.0
125
193.0
30.3
147.0
147.0
219.0
32.4
147.0
146.0
247.0
34.5
147.0
146.0
277.0
36.6
148.0
147.0
308.0
38.8
149.0
147.0
341.0
41.1
150.0
148.0
375.0
43.4
151.0
149.0
70
398.0
31.4
93.5
90.9
445.0
32.9
95.1
91.7
495.0
34.5
97.1
92.9
548.0
36.1
99.4
94.4
603.0
37.7
102.0
96.0
661.0
39.4
105.0
97.8
723.0
41.2
108.0
99.6
80
368.0
33.4
103.0
101.0
414.0
35.1
104.0
102.0
462.0
36.9
106.0
103.0
512.0
38.8
108.0
104.0
565.0
40.7
111.0
106.0
620.0
42.7
113.0
108.0
679.0
44.7
116.0
110.0
85
353.0
34.3
108.0
106.0
398.0
36.2
109.0
107.0
445.0
38.1
111.0
108.0
494.0
40.1
113.0
109.0
546.0
42.2
115.0
111.0
600.0
44.3
118.0
113.0
657.0
46.4
120.0
115.0
90
339.0
35.2
113.0
111.0
383.0
37.2
114.0
112.0
428.0
39.2
115.0
113.0
476.0
41.4
117.0
114.0
527.0
43.6
120.0
116.0
580.0
45.8
122.0
118.0
635.0
48.1
125.0
120.0
110
283.0
38.0
133.0
132.0
322.0
40.5
133.0
132.0
364.0
43.0
134.0
133.0
407.0
45.7
136.0
134.0
453.0
48.4
137.0
135.0
500.0
51.1
140.0
137.0
550.0
54.0
142.0
139.0
115
269.0
38.5
138.0
137.0
308.0
41.2
138.0
137.0
348.0
43.8
139.0
138.0
391.0
46.6
140.0
139.0
435.0
49.4
142.0
140.0
481.0
52.3
144.0
142.0
530.0
55.3
146.0
144.0
120
256.0
39.0
142.0
142.0
293.0
41.8
143.0
142.0
333.0
44.6
144.0
143.0
374.0
47.4
145.0
144.0
417.0
50.4
147.0
145.0
462.0
53.4
149.0
147.0
509.0
56.5
151.0
148.0
125
243.0
39.4
147.0
147.0
279.0
42.3
148.0
147.0
317.0
45.2
148.0
148.0
357.0
48.2
150.0
148.0
399.0
51.3
151.0
150.0
443.0
54.5
153.0
151.0
488.0
57.7
155.0*
153.0
38AH104 CIRCUIT B
SST
(F)
20
25
30
35
40
45
50
kW
SCT
SDT
SST
TC
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
LEGEND
Compressor Power
Saturated Condensing Temperature (F)
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
67
20
25
30
35
40
45
50
70
417.0
33.6
93.3
92.4
470.0
34.9
94.0
92.8
525.0
36.2
95.0
93.5
584.0
37.5
96.4
94.6
645.0
38.8
98.1
95.9
709.0
40.0
100.0
97.5
776.0
41.3
102.0
99.3
80
386.0
35.7
103.0
103.0
436.0
37.3
104.0
103.0
490.0
39.0
105.0
103.0
546.0
40.6
106.0
104.0
604.0
42.2
108.0
106.0
666.0
43.9
109.0
107.0
730.0
45.5
112.0
109.0
85
370.0
36.7
108.0
108.0
420.0
38.5
109.0
108.0
472.0
40.3
110.0
108.0
526.0
42.1
111.0
109.0
584.0
43.9
112.0
111.0
644.0
45.8
114.0
112.0
707.0
47.6
116.0
114.0
90
355.0
37.6
113.0
113.0
403.0
39.6
114.0
113.0
454.0
41.6
114.0
113.0
507.0
43.5
116.0
114.0
563.0
45.5
117.0
116.0
622.0
47.5
119.0
117.0
684.0
49.5
121.0
119.0
110
294.0
40.1
133.0
133.0
337.0
42.8
133.0
133.0
384.0
45.5
134.0
133.0
432.0
48.2
135.0
134.0
483.0
50.8
136.0
135.0
537.0
53.5
138.0
136.0
593.0
56.2
139.0
138.0
115
279.0
40.5
138.0
138.0
321.0
43.4
138.0
138.0
366.0
46.3
139.0
138.0
414.0
49.2
140.0
139.0
463.0
52.0
141.0
140.0
516.0
54.9
142.0
141.0
570.0
57.8
144.0
143.0
120
264.0
40.8
143.0
143.0
305.0
43.9
143.0
143.0
349.0
47.0
144.0
143.0
395.0
50.0
144.0
144.0
444.0
53.0
146.0
145.0
494.0
56.1
147.0
146.0
548.0
59.1
149.0
147.0
125
249.0
41.0
148.0
148.0
289.0
44.3
148.0
148.0
331.0
47.5
149.0
148.0
376.0
50.7
149.0
149.0
424.0
54.0
150.0
150.0
473.0
57.2
152.0
151.0
525.0
60.4
153.0
152.0
70
513.0
42.4
92.0
87.6
575.0
44.1
92.7
88.6
639.0
45.8
93.8
90.0
706.0
47.6
95.4
91.5
777.0
49.4
97.2
93.0
852.0
51.2
99.2
94.6
931.0
52.9
101.0
96.3
80
478.0
44.9
102.0
97.7
538.0
47.0
102.0
98.5
600.0
49.1
103.0
99.7
665.0
51.3
105.0
101.0
733.0
53.5
107.0
103.0
804.0
55.7
109.0
104.0
880.0
57.9
111.0
106.0
85
461.0
46.1
107.0
103.0
520.0
48.3
107.0
103.0
580.0
50.6
108.0
105.0
644.0
53.0
110.0
106.0
710.0
55.4
111.0
107.0
781.0
57.8
113.0
109.0
855.0
60.2
115.0
111.0
90
444.0
47.1
112.0
108.0
502.0
49.5
112.0
108.0
561.0
52.0
113.0
109.0
623.0
54.6
114.0
111.0
689.0
57.2
116.0
112.0
757.0
59.8
118.0
114.0
829.0
62.4
120.0
116.0
110
376.0
50.2
132.0
128.0
428.0
53.5
132.0
128.0
484.0
56.7
132.0
129.0
541.0
60.0
133.0
130.0
601.0
63.4
135.0
131.0
663.0
66.8
136.0
133.0
729.0
70.3
138.0
134.0
115
359.0
50.8
137.0
133.0
410.0
54.3
137.0
133.0
464.0
57.7
137.0
134.0
520.0
61.2
138.0
135.0
579.0
64.7
139.0
136.0
640.0
68.3
141.0
137.0
704.0
72.0
143.0
139.0
120
342.0
51.3
142.0
138.0
392.0
54.9
142.0
138.0
445.0
58.6
142.0
139.0
500.0
62.2
143.0
139.0
557.0
66.0
144.0
141.0
617.0
69.7
145.0
142.0
679.0
73.6
147.0
144.0
125
326.0
51.6
147.0
143.0
374.0
55.5
147.0
143.0
425.0
59.3
147.0
144.0
479.0
63.2
148.0
144.0
535.0
67.1
149.0
145.0
593.0
71.1
150.0
147.0
654.0
75.1
152.0
148.0
25
30
35
40
45
50
kW
SCT
SDT
SST
TC
68
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
LEGEND
Compressor Power
Saturated Condensing Temperature (F)
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
62
195.4
195.4
13.19
188.3
188.3
14.37
184.4
184.4
14.93
180.3
180.3
15.62
171.8
171.8
16.78
162.9
162.9
18.11
62
220.2
220.2
13.60
211.5
211.5
14.90
206.8
206.8
15.57
202.0
202.0
16.26
192.3
192.3
17.63
182.0
182.0
19.07
7500
67
211.4
169.2
13.46
202.5
164.7
14.69
197.8
162.4
15.31
192.9
160.0
15.99
183.0
155.0
17.24
172.5
149.8
18.60
10,000
67
232.7
206.1
13.81
221.8
201.1
15.13
216.2
198.6
15.83
210.4
195.9
16.51
199.1
190.8
17.91
187.1
185.3
19.32
LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (1000 Btuh)
TC Total Capacity (1000 Btuh)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator
coil.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.
12,500
67
248.1
240.6
14.07
235.7
235.2
15.45
229.4
229.4
16.21
223.0
223.0
16.88
210.6
210.6
18.38
197.4
197.4
19.83
62
241.2
241.2
13.95
230.9
230.9
15.34
225.6
225.6
16.10
220.1
220.1
16.79
209.5
209.5
18.33
197.9
197.9
19.86
10,000
67
255.0
216.3
16.63
244.5
211.5
18.16
239.3
209.1
18.92
232.6
206.1
19.72
221.6
201.0
21.22
193.9
188.4
23.00
62
239.4
239.4
16.24
230.4
230.4
17.81
225.9
225.9
18.53
220.8
220.8
19.29
211.6
211.6
20.83
187.8
187.8
22.74
5. Formulas
sensible heat capacity (Btuh)
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb
hldb = hedb
69
62
261.4
261.4
16.78
251.9
251.9
18.35
247.2
247.2
19.15
240.8
240.8
20.02
230.4
230.4
21.55
204.6
204.6
23.44
62
280.5
280.5
17.26
270.3
270.3
18.81
265.2
265.2
19.68
257.4
257.4
20.62
245.8
245.8
22.14
217.6
217.6
23.98
kW
29.06 27.79 27.14 29.48 28.28 27.95
12,500
67
271.7
250.9
17.04
260.6
246.1
18.56
255.0
243.6
19.38
247.1
240.2
20.25
234.9
234.8
21.73
205.1
221.8
23.46
15,000
67
286.3
283.4
17.41
274.5
274.5
18.91
268.7
268.7
19.78
259.5
259.5
20.70
246.2
246.2
22.16
214.4
214.4
23.85
LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (1000 Btuh)
TC Total Capacity (1000 Btuh)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator
coil.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.
70
12,500
67
305.2
265.5
20.44
292.9
260.2
22.47
286.3
257.3
23.28
280.3
254.6
24.28
267.2
248.9
26.15
253.7
243.1
28.08
62
288.2
288.2
20.03
278.2
278.2
22.00
272.9
272.9
22.83
267.8
267.8
23.82
257.2
257.2
25.72
246.0
246.0
27.70
15,000
67
324.0
300.0
20.89
310.4
294.0
23.03
303.0
290.8
23.83
296.6
287.9
24.89
282.1
281.6
26.80
267.4
267.4
28.76
62
311.8
311.8
20.60
300.5
300.5
22.71
294.4
294.0
23.55
288.9
288.9
24.60
276.7
276.7
26.56
264.1
264.1
28.59
5. Formulas
sensible heat capacity (Btuh)
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb
hldb = hedb
62
205.5
198.2
13.57
195.6
191.8
14.80
190.7
190.7
15.40
186.2
186.2
16.00
177.3
177.3
17.21
62
227.7
227.6
14.22
215.5
215.5
15.38
210.8
210.8
16.04
205.8
205.8
16.69
195.9
195.9
17.97
7500
67
223.6
165.2
13.96
213.0
161.5
15.28
207.3
159.4
15.92
201.7
157.0
16.54
190.3
152.7
17.74
10,000
67
238.5
195.6
14.29
225.5
190.4
15.58
220.9
188.8
16.35
213.9
186.1
16.91
202.0
181.8
18.18
LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (1000 Btuh)
TC Total Capacity (1000 Btuh)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator
coil.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.
12,500
67
252.2
227.4
14.58
238.9
222.3
15.95
232.6
219.3
16.67
226.5
216.8
17.36
213.6
210.1
18.68
62
244.3
244.3
14.41
234.2
234.2
15.88
228.8
228.8
16.58
223.3
223.3
17.28
212.3
212.3
18.63
10,000
67
265.9
205.9
17.38
253.4
201.2
18.91
247.2
198.9
19.66
240.9
196.4
20.39
228.4
191.6
21.89
62
245.9
245.9
16.85
236.3
236.3
18.36
231.5
231.5
19.12
226.7
226.7
19.86
216.9
216.9
21.39
5. Formulas
sensible heat capacity (Btuh)
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb
hldb = hedb
71
62
268.6
268.6
17.45
257.8
257.8
19.06
252.4
252.4
19.86
246.9
246.9
20.64
236.1
236.1
22.26
62
287.0
287.0
17.91
275.5
275.5
19.63
269.5
269.5
20.46
263.5
263.5
21.28
251.2
251.2
22.95
12,500
67
281.7
238.7
17.77
268.5
233.6
19.40
262.0
231.2
20.20
255.4
228.8
20.97
241.4
222.7
22.50
15,000
67
294.6
269.2
18.12
280.0
263.6
19.76
273.4
260.6
20.57
266.5
257.1
21.39
252.5
249.8
23.01
LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (1000 Btuh)
TC Total Capacity (1000 Btuh)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator
coil.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.
72
12,500
67
316.4
252.2
22.04
302.4
246.8
23.82
295.4
244.2
24.69
288.2
241.6
25.58
273.4
235.7
27.28
62
297.8
296.2
21.51
284.3
284.3
23.10
278.7
278.6
23.96
273.0
273.0
24.86
261.4
261.4
26.63
15,000
67
333.0
284.4
22.60
317.7
278.3
24.41
310.2
275.3
25.30
302.6
272.1
26.21
287.3
265.3
27.99
62
317.7
317.7
22.06
306.9
306.9
24.03
299.6
299.6
24.84
293.3
293.3
25.77
280.5
280.5
27.60
5. Formulas
sensible heat capacity (Btuh)
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb
hldb = hedb
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
38AH034
24
42.9
11.3
35.2
47.0
11.5
35.2
51.4
11.7
35.2
55.5
11.9
35.6
59.9
12.1
36.2
64.3
12.3
36.9
69.2
12.5
37.7
74.1
12.8
38.5
78.9
13.0
39.2
52
25.7
14.2
63.2
28.8
14.9
63.2
31.8
15.6
63.2
35.5
16.3
63.2
39.3
16.9
63.2
42.9
17.5
63.1
46.8
18.1
63.6
50.7
18.8
64.1
54.7
19.4
64.7
38AH028
SST
(C)
6
4
2
0
2
4
6
8
10
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
24
51.1
13.4
35.4
55.2
13.8
36.0
59.7
14.1
36.5
64.5
14.4
37.1
69.3
14.7
37.8
74.0
15.0
38.8
79.4
15.3
39.6
85.0
15.7
40.5
90.6
16.0
41.5
52
33.3
17.7
63.1
37.0
18.4
63.0
40.5
19.1
63.1
43.9
19.8
63.4
47.9
20.6
64.0
51.6
21.3
64.4
55.6
22.2
65.1
59.8
22.9
65.7
64.0
23.6
66.4
SST
(C)
6
4
2
0
2
4
6
8
10
kW
SDT
SST
TC
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
52
39.5
21.8
63.8
43.5
22.7
63.8
47.7
23.5
63.9
52.2
24.5
63.8
57.0
25.3
64.0
61.7
26.2
64.2
66.7
27.1
64.8
71.7
28.0
65.4
76.8
29.0
66.0
LEGEND
Compressor Power
Saturated Discharge Temperature at Compressor (C)
Saturated Suction Temperature
Gross Cooling Capacity (kW)
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
73
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
21
105.5
24.2
33.3
114.2
24.7
33.7
123.6
25.1
34.2
133.1
25.6
34.7
143.1
26.1
35.3
153.5
26.6
35.9
164.1
27.0
36.6
27
96.9
26.3
39.2
105.4
27.0
39.5
114.3
27.7
39.9
123.6
28.4
40.5
133.1
29.0
41.0
143.1
29.7
41.6
153.3
30.4
42.3
30
92.6
27.3
42.1
100.8
28.2
42.4
109.6
28.9
42.8
118.7
29.7
43.3
128.0
30.5
43.9
137.9
31.2
44.5
147.9
31.9
45.1
32
89.6
27.9
44.0
97.8
28.8
44.3
106.5
29.7
44.8
115.4
30.5
45.2
124.7
31.4
45.7
134.3
32.2
46.4
144.2
32.9
47.0
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
21
123.0
29.5
35.7
133.3
30.2
36.0
144.2
30.9
36.5
155.4
31.6
36.5
167.0
32.5
37.6
178.9
33.2
38.4
191.2
33.9
39.2
27
113.2
32.0
41.6
123.0
32.9
41.8
133.4
33.8
42.2
144.2
34.7
42.7
155.3
35.7
43.3
166.8
36.6
44.0
179.0
37.6
44.7
30
108.1
33.0
44.5
117.8
34.2
44.8
128.0
35.1
45.2
138.5
36.2
45.5
149.4
37.2
46.1
160.7
38.3
46.7
172.2
39.3
47.4
32
104.9
33.7
46.5
114.3
34.9
46.7
124.4
36.0
47.1
134.7
37.1
47.5
145.5
38.3
48.0
156.6
39.4
48.6
168.0
40.5
49.3
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
21
148.5
35.7
34.7
160.3
36.6
35.1
172.9
37.5
35.7
185.8
38.4
36.4
199.4
39.3
37.2
213.0
40.2
38.0
227.0
41.1
38.9
27
137.2
38.6
40.5
148.6
39.8
40.9
160.7
41.0
41.5
173.1
42.2
42.1
185.9
43.4
42.8
198.9
44.5
43.6
213.0
45.7
44.4
30
131.7
40.0
43.5
142.8
41.3
43.8
154.6
42.6
44.3
166.6
43.9
44.9
179.2
45.3
45.6
192.4
46.5
46.4
205.8
47.9
47.2
32
127.9
40.8
45.5
138.9
42.3
45.7
150.5
43.6
46.3
162.4
45.0
46.8
174.7
46.4
47.5
187.5
47.8
48.2
200.3
49.3
49.1
SST
(C)
2
0
10
46
68.4
30.9
57.7
75.9
32.4
57.9
83.9
33.8
58.3
92.0
35.3
58.6
100.4
36.7
59.0
109.1
38.0
59.6
117.9
39.3
60.1
49
63.8
31.2
60.7
71.1
32.9
60.9
78.9
34.4
61.1
86.8
36.0
61.5
95.1
37.5
61.9
103.5
39.0
62.4
112.2
40.5
62.9
52
59.2
31.3
63.6
66.4
33.1
63.7
73.9
34.9
64.0
81.7
36.6
64.4
89.7
38.3
64.8
98.0*
39.9*
65.3*
106.5*
41.5*
65.8*
49
77.4
37.6
63.3
85.4
39.6
63.5
94.1
41.5
63.6
103.0
43.4
63.9
112.3
45.1
64.2
122.0
47.0
64.7
132.0*
48.8*
65.2*
52
72.6*
38.0*
66.3*
80.4*
40.1*
66.4*
88.8*
42.2*
66.6*
97.4*
44.1*
66.9*
106.5*
46.1*
67.2*
116.0*
48.0*
67.5*
125.5*
50.0*
68.0*
49
97.0
46.0
62.1
106.4
48.2
62.3
116.4
50.4
62.7
126.7
52.6
63.1
137.3
54.7
63.6
148.4
57.0
64.2
159.6
59.1
64.8
52
91.6
46.5
65.1
100.7
48.9
65.2
110.5
51.2
65.6
120.5
53.5
66.0
130.8*
55.9*
66.4*
141.6*
58.2*
67.0*
152.5*
60.5*
67.6*
38AH054
SST
(C)
2
0
10
46
82.2
37.3
60.3
90.4
39.1
60.5
99.4
40.7
60.7
108.5
42.4
61.0
118.1
44.2
61.3
128.2
45.9
61.8
138.3
47.5
62.3
38AH064
SST
(C)
2
0
10
kW
SDT
SST
TC
74
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (kW)
43
107.8
44.6
56.2
117.8
46.4
56.4
128.4
48.3
56.9
139.2
50.2
57.3
150.5
52.2
57.9
162.2
54.1
58.5
174.0
56.0
59.3
46
102.3
45.4
59.2
112.1
47.4
59.3
122.4
49.5
59.8
133.0
51.5
60.2
143.8
53.5
60.7
155.2
55.6
61.4
166.8
57.6
62.0
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
21
181.6
45.2
34.1
194.7
46.5
34.6
209.1
47.8
35.3
224.6
49.1
36.0
239.0
50.4
36.8
257.0
51.6
37.6
273.0
52.8
38.5
27
169.2
48.7
39.8
182.1
50.2
40.3
196.3
51.8
41.0
210.5
53.4
41.6
225.1
55.0
42.4
241.0
56.6
43.2
257.0
58.3
44.0
30
163.2
50.2
42.8
176.1
51.9
43.2
189.3
53.7
43.8
203.5
55.4
44.4
217.9
57.2
45.2
234.0
59.0
45.9
248.0
60.7
46.8
32
159.1
51.1
44.7
171.9
53.0
45.0
185.3
54.8
45.7
199.4
56.7
46.3
212.8
58.5
47.0
228.4
60.4
47.8
243.0
62.3
48.6
43
137.0
55.6
55.4
148.8
57.9
55.6
161.2
60.4
56.1
173.8
62.7
56.6
186.9
65.1
57.3
200.0
67.6
57.9
214.1
70.1
58.7
46
131.0
56.6
58.4
142.5
59.1
58.5
154.6
61.6
58.9
166.9
64.2
59.4
179.6
66.7
60.0
192.5
69.4
60.7
206.6
71.9
61.5
49
125.0
57.4
61.3
136.2
60.1
61.4
148.1
62.8
61.8
160.1
65.4
62.2
172.5
68.1
62.8
185.1
71.0
63.5
198.0
73.7
64.2
52
118.9
58.1
64.3
129.8
61.0
64.4
141.4
63.8
64.7
153.2
66.6
65.1
165.3
69.5
65.6
177.6*
72.4*
66.2*
190.4*
75.3*
66.9*
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
21
204.0
54.1
36.2
221.0
55.6
36.3
238.0
57.0
36.7
256.0
58.5
37.1
274.0
60.0
37.7
294.0
61.6
38.4
314.0
63.2
39.2
27
190.6
57.9
42.2
206.0
59.7
42.3
223.0
61.5
42.6
240.0
63.3
42.9
258.0
65.1
43.4
276.0
67.1
44.1
294.0
69.1
44.8
30
183.9
59.5
45.2
198.9
61.5
45.3
215.0
63.5
45.5
232.0
65.5
45.8
250.0
67.5
46.3
268.0
69.7
46.9
286.0
71.7
47.6
32
179.3
60.6
47.2
194.2
62.7
47.3
210.0
64.9
47.5
226.0
66.9
47.8
244.0
69.1
48.2
262.0
71.3
48.8
280.0
73.5
49.5
43
155.3
65.5
58.2
168.6
68.2
58.2
183.1
70.9
58.4
197.9
73.7
58.6
214.0
76.5
58.9
230.0
79.3
59.4
246.0
82.1
59.9
46
148.9
66.6
61.2
161.7
69.6
61.2
175.7
72.4
61.4
190.1
75.3
61.5
205.0
78.3
61.9
221.0
81.3
62.3
236.0
84.3
62.7
49
142.5
67.7
64.2
154.9
70.8
64.2
168.5
73.8
64.3
182.5
76.9
63.5
197.0
79.9
64.8
212.0
83.1
65.2
228.0
86.3
65.6
52
136.2*
68.6*
67.2*
148.2*
71.8*
67.2*
161.3*
75.0*
67.3*
174.9*
78.2*
67.4*
189.0*
81.5*
67.7*
204.0*
84.8*
68.1*
219.0*
88.1*
68.5*
SST
(C)
2
0
10
38AH084
SST
(C)
2
0
10
kW
SDT
SST
TC
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (kW)
75
10
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
21
233.0
58.1
35.5
33.8
33.6
32.3
251.0
59.7
36.2
34.2
34.0
32.4
269.0
61.5
37.1
34.9
34.6
32.8
289.0
63.3
38.0
35.6
35.2
33.3
309.0
65.1
39.0
36.4
35.8
33.8
329.0
66.9
40.1
37.3
36.5
34.3
350.0
68.7
41.1
38.2
37.2
34.9
27
216.5
62.3
41.2
39.6
39.7
38.5
234.0
64.3
41.8
39.9
40.1
38.6
252.0
66.5
42.6
40.5
40.6
39.0
270.0
68.6
43.5
41.2
41.2
39.4
290.0
70.8
44.4
41.9
41.9
39.9
309.0
73.0
45.4
42.7
42.6
40.4
329.0
75.2
46.4
43.6
43.3
41.0
30
209.1
64.3
44.0
42.5
42.8
41.5
226.0
66.6
44.5
42.8
43.1
41.7
243.0
68.9
45.3
43.4
43.7
42.0
261.0
71.3
46.2
44.0
44.3
42.4
279.0
73.6
47.1
44.7
44.9
42.9
299.0
76.0
48.0
45.5
45.6
43.5
319.0
78.4
49.1
46.3
46.4
44.1
32
202.9
65.6
45.9
44.5
44.8
43.6
220.2
67.9
46.4
44.8
45.1
43.7
237.0
70.4
47.2
45.3
45.7
44.0
255.0
72.9
48.0
45.9
46.3
44.4
274.0
75.4
48.9
46.5
46.9
44.9
292.0
77.9
49.8
47.3
47.6
45.5
312.0
80.5
50.8
48.2
48.4
46.1
LEGEND
kW
Compressor Power
SCT(A) Saturated Condensing Temperature (C) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SCT(B) Saturated Condensing Temperature (C) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SDT(A) Saturated Discharge Temperature (C) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SDT(B) Saturated Discharge Temperature (C) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SST
Saturated Suction Temperature Entering Condensing Unit
TC
Gross Cooling Capacity (kW)
76
46
164.8
72.2
59.4
58.3
58.9
57.9
180.0
75.6
59.6
58.4
59.0
57.9
196.0
78.9
60.2
58.8
59.4
58.1
211.9
82.3
60.8
59.2
59.9
58.4
228.0
85.6
61.5
59.7
60.5
58.8
246.0
89.1
62.3
60.3
61.1
59.3
263.0
92.5
63.2
61.0
61.8
59.8
49
156.5
73.2
62.3
61.3
61.9
60.9
171.4
76.7
62.5
61.4
62.0
60.9
186.4
80.2
63.0
61.7
62.3
61.1
202.2
83.8
63.5
62.1
62.7
61.3
219.2
87.5
64.2
62.5
63.3
61.7
235.0
91.0
65.0
63.1
64.0
62.2
253.0
94.7
65.9
63.8
64.7
62.7
52
148.2
73.9
65.3
64.3
64.9
63.9
162.7
77.7
65.4
64.4
64.9
63.9
177.9
81.5
65.8
64.6
65.3
64.1
193.4
85.2
66.3
65.0
65.6
64.3
209.3
89.1
66.9
65.4
66.2
64.7
225.0
92.9
67.7*
66.0
66.8
65.1
242.0
96.8
68.5*
66.6
67.5*
65.6
10
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
21
265.0
62.8
34.4
35.7
32.6
33.5
285.0
64.9
35.1
36.5
33.1
34.0
307.0
66.9
36.0
37.5
33.6
34.7
328.0
68.9
36.9
38.5
34.2
35.3
351.0
71.0
37.9
39.6
34.8
36.0
375.0
73.1
38.9
40.7
35.5
36.7
400.0
75.4
39.9
41.9
36.2
37.5
27
245.0
67.7
40.0
41.2
38.6
39.5
264.0
70.1
40.6
41.9
39.1
40.0
285.0
72.6
41.4
42.9
39.6
40.7
306.0
75.0
42.3
43.8
40.2
41.4
328.0
77.5
43.2
44.8
40.8
42.1
351.0
80.0
44.1
45.9
41.5
42.8
374.0
82.6
45.2
47.0
42.2
43.6
30
235.0
70.1
42.8
43.9
41.7
42.6
254.0
72.6
43.4
44.7
42.1
43.1
273.0
75.3
44.1
45.5
42.6
43.7
294.0
78.0
44.9
46.4
43.2
44.4
316.0
80.7
45.8
47.4
43.8
45.1
338.0
83.5
46.8
48.5
44.5
45.8
361.0
86.3
47.8
49.5
45.2
46.6
32
229.0
71.6
44.7
45.8
43.7
44.5
247.0
74.3
45.2
46.5
44.0
45.0
267.0
77.0
46.0
47.3
44.6
45.7
287.0
79.8
46.7
48.2
45.1
46.3
308.0
82.7
47.6
49.2
45.8
47.1
330.0
85.6
48.6
50.2
46.5
47.8
353.0
88.5
49.5
51.3
47.2
48.6
LEGEND
kW
Compressor Power
SCT(A) Saturated Condensing Temperature (C) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SCT(B) Saturated Condensing Temperature (C) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SDT(A) Saturated Discharge Temperature (C) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SDT(B) Saturated Discharge Temperature (C) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SST
Saturated Suction Temperature Entering Condensing Unit
TC
Gross Cooling Capacity (kW)
46
183.1
79.7
58.1
59.1
57.7
58.5
199.8
83.4
58.4
59.5
57.8
58.8
217.0
87.1
58.9
60.1
58.2
59.3
235.0
90.9
59.5
60.8
58.7
59.8
254.0
94.7
60.2
61.7
59.2
60.5
273.0
98.6
61.0
62.6
59.9
61.2
292.0
102.4
61.9
63.5
60.6
62.0
49
173.6
81.0
61.1
61.9
60.7
61.4
190.0
84.9
61.3
62.3
60.8
61.7
207.3
88.8
61.7
62.9
61.1
62.2
225.0
92.8
62.3
63.6
61.5
62.7
242.0
96.8
63.0
64.4
62.1
63.4
261.0
100.8
63.7
65.2
62.7
64.1
281.0
105.0
64.5
66.1
63.4
64.8
52
164.2
82.1
64.0
64.9
63.7
64.4
180.1
86.2
64.1
65.2
63.7
64.6
197.2
90.4
64.6
65.7
64.0
65.1
213.4
94.5
65.1
66.3
64.4
65.6
231.0
98.8
65.7
67.1*
64.9
66.2
250.0
103.0
66.4
67.9*
65.5
66.9
268.0
107.4
67.2
68.7*
66.2
67.6*
77
10
TC
kW
SDT(A) OR (B)
SCT(A) OR (B)
TC
kW
SDT(A) OR (B)
SCT(A) OR (B)
TC
kW
SDT(A) OR (B)
SCT(A) OR (B)
TC
kW
SDT(A) OR (B)
SCT(A) OR (B)
TC
kW
SDT(A) OR (B)
SCT(A) OR (B)
TC
kW
SDT(A) OR (B)
SCT(A) OR (B)
TC
kW
SDT(A) OR (B)
SCT(A) OR (B)
21
298.0
71.4
34.7
33.9
322.0
73.4
35.2
34.3
346.0
75.2
35.8
34.7
372.0
77.0
36.5
35.3
400.0
78.8
37.2
35.9
428.0
80.6
38.1
36.6
456.0
82.6
39.0
37.3
27
276.0
77.2
40.5
39.9
298.0
79.6
40.9
40.2
322.0
82.0
41.5
40.7
348.0
84.2
42.1
41.2
372.0
86.6
42.9
41.8
400.0
89.2
43.7
42.4
426.0
91.6
44.5
43.1
30
264.0
80.0
43.4
42.9
286.0
82.6
43.8
43.2
310.0
85.2
44.4
43.6
334.0
88.0
45.0
44.1
360.0
90.6
45.7
44.7
386.0
93.2
46.5
45.3
412.0
96.0
47.3
46.0
LEGEND
kW
Compressor Power
SCT(A) Saturated Condensing Temperature (C) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SCT(B) Saturated Condensing Temperature (C) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SDT(A) Saturated Discharge Temperature (C) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SDT(B) Saturated Discharge Temperature (C) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SST
Saturated Suction Temperature Entering Condensing Unit
TC
Gross Cooling Capacity (kW)
78
46
206.0
90.8
59.1
58.9
226.0
94.8
59.4
59.0
246.0
99.0
59.7
59.3
268.0
103.0
60.2
59.7
290.0
107.2
60.7
60.2
312.0
111.2
61.4
60.7
334.0
115.4
62.1
61.3
49
195.6
92.0
62.1
61.9
214.0
96.4
62.3
62.0
234.0
100.8
62.7
62.3
254.0
105.2
63.1
62.6
276.0
109.6
63.6
63.1
298.0
114.0
64.2
63.6
320.0
118.4
64.8
64.2
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
52
185.0
93.2
65.1
64.8
204.0
97.8
65.2
65.0
222.0
102.4
65.6
65.2
242.0
107.2
65.9
65.5
264.0
111.8
66.4
66.0
284.0
116.4
67.0
66.5
306.0
121.2
67.6
67.0
10
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
21
330.0
80.9
34.7
34.0
33.9
31.9
356.0
83.2
35.2
34.5
34.3
32.4
383.0
85.4
35.8
35.2
34.7
33.0
410.0
87.5
36.5
36.0
35.3
33.6
440.0
89.7
37.2
36.7
35.9
34.3
470.0
91.8
38.1
37.6
36.6
34.9
501.0
94.1
39.0
38.4
37.3
35.6
27
307.0
87.2
40.5
39.8
39.9
37.7
331.0
90.0
40.9
40.2
40.2
38.2
357.0
92.8
41.5
40.9
40.7
38.8
385.0
95.5
42.1
41.6
41.2
39.5
412.0
98.3
42.9
42.3
41.8
40.1
441.0
101.2
43.7
43.1
42.4
40.7
470.0
104.0
44.5
44.0
43.1
41.4
30
295.0
90.1
43.4
42.7
42.9
40.7
319.0
93.1
43.8
43.1
43.2
41.2
345.0
96.2
44.4
43.7
43.6
41.7
371.0
99.4
45.0
44.4
44.1
42.3
398.0
102.4
45.7
45.1
44.7
43.0
426.0
105.5
46.5
45.9
45.3
43.6
455.0
108.7
47.3
46.7
46.0
44.3
32
288.0
91.9
45.4
44.6
44.9
42.6
312.0
95.1
45.8
45.0
45.2
43.1
336.0
98.5
46.3
45.6
45.6
43.7
362.0
101.7
46.9
46.3
46.1
44.3
388.0
105.0
47.6
47.0
46.6
44.9
416.0
108.3
48.3
47.8
47.3
45.5
445.0
111.6
49.1
48.6
48.0
46.2
LEGEND
kW
Compressor Power
SCT(A) Saturated Condensing Temperature (C) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SCT(B) Saturated Condensing Temperature (C) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SDT(A) Saturated Discharge Temperature (C) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SDT(B) Saturated Discharge Temperature (C) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SST
Saturated Suction Temperature Entering Condensing Unit
TC
Gross Cooling Capacity (kW)
43
246.0
100.1
56.2
55.4
55.9
53.4
268.0
104.3
56.4
55.5
56.0
53.6
290.0
108.7
56.8
56.0
56.4
54.2
314.0
113.0
57.3
56.5
56.8
54.7
338.0
117.3
57.9
57.2
57.3
55.3
364.0
121.7
58.6
57.9
57.9
55.9
390.0
126.1
59.3
58.7
58.5
56.5
46
234.0
102.0
59.1
58.3
58.9
56.3
256.0
106.5
59.4
58.4
59.0
56.5
278.0
111.1
59.7
58.9
59.3
57.0
301.0
115.6
60.2
59.3
59.7
57.5
325.0
120.3
60.7
60.0
60.2
58.1
349.0
124.9
61.4
60.7
60.7
58.7
374.0
129.6
62.1
61.4
61.3
59.3
49
222.8
103.4
62.1
61.3
61.9
59.3
243.0
108.3
62.3
61.4
62.0
59.4
265.0
113.1
62.7
61.8
62.3
59.9
287.0
118.0
63.1
62.2
62.6
60.3
311.0
122.9
63.6
62.8
63.1
60.9
335.0
127.9
64.2
63.4
63.6
61.5
359.0
132.9
64.8
64.2
64.2
62.1
52
211.5
104.8
65.1
64.3
64.8
62.2
232.0
109.9
65.2
64.3
65.0
62.4
253.0
114.9
65.6
64.6
65.2
62.7
274.0
120.1
65.9
65.0
65.5
63.1
297.0
125.3
66.4
65.5
66.0
63.7
320.0
130.6
67.0
66.2
66.5
64.2
344.0
135.9
67.6*
66.9
67.0
64.8
79
80
LEGEND
Compressor Power
Saturated Discharge Temperature at Compressor (C)
Saturated Suction Temperature
Gross Cooling Capacity (kW)
52
12.8
7.1
63.2
14.4
7.5
63.2
15.9
7.8
63.2
17.7
8.2
63.2
19.7
8.5
63.2
21.4
8.8
63.1
23.4
9.1
63.6
25.4
9.4
64.1
27.3
9.7
64.7
52
15.6
8.9
63.2
17.4
9.2
63.2
19.1
9.6
63.4
21.2
9.9
63.2
23.4
10.2
63.0
25.5
10.5
62.9
27.7
10.9
63.4
29.9
11.2
63.8
32.3
11.5
64.3
52
16.7
8.9
63.1
18.5
9.2
63.0
20.3
9.5
63.1
22.0
9.9
63.4
23.9
10.3
64.0
25.8
10.7
64.4
27.8
11.1
65.1
29.9
11.4
65.7
32.0
11.8
66.4
52
23.9
13.0
64.4
26.1
13.4
64.5
28.6
13.9
64.3
31.0
14.5
64.4
33.6
15.1
65.0
36.1
15.7
65.4
38.9
16.2
66.2
41.7
16.8
66.9
44.5
17.4
67.7
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
10
21
52.7
12.0
32.8
56.9
12.3
33.4
61.4
12.5
34.0
66.0
12.8
34.7
70.8
13.1
35.5
75.8
13.4
36.3
80.9
13.7
37.1
27
48.5
13.0
38.5
52.6
13.4
39.0
56.9
13.8
39.6
61.4
14.2
40.3
66.0
14.5
41.0
70.8
14.9
41.8
75.7
15.3
42.6
30
46.4
13.5
41.3
50.4
14.0
41.8
54.6
14.4
42.4
59.0
14.8
43.0
63.5
15.2
43.8
68.3
15.6
44.5
73.1
16.0
45.3
21
53.0
12.4
35.0
57.6
12.6
35.1
62.5
12.8
35.3
67.5
13.0
35.6
72.6
13.3
36.0
77.9
13.5
36.6
83.2
13.7
37.3
27
48.7
13.5
41.0
53.1
13.8
41.0
57.8
14.1
41.2
62.7
14.4
41.4
67.7
14.7
41.8
72.8
15.0
42.3
78.0
15.3
42.8
30
46.4
13.9
44.0
50.8
14.4
44.1
55.4
14.7
44.2
60.2
15.1
44.3
65.1
15.4
44.7
70.2
15.8
45.1
75.3
16.1
45.6
32
44.9
13.8
43.2
48.9
14.3
43.7
53.1
14.8
44.3
57.4
15.2
44.9
61.9
15.7
45.6
66.5
16.1
46.4
71.3
16.5
47.1
43
36.8
15.1
53.8
40.5
15.8
54.2
44.5
16.5
54.6
48.5
17.1
55.1
52.6
17.8
55.8
56.9
18.4
56.4
61.3
19.0
57.1
46
34.5
15.4
56.7
38.2
16.1
57.0
42.1
16.8
57.5
46.0
17.6
57.9
50.1
18.3
58.5
54.3
18.9
59.2
58.5
19.6
59.9
49
32.2
15.6
59.7
35.8
16.4
59.9
39.6
17.1
60.3
43.5
17.9
60.8
47.5
18.7
61.3
51.6
19.4
61.9
55.8
20.2
62.6
52
29.9
15.6
62.6
33.5
16.5
62.7
37.2
17.4
63.1
41.0
18.2
63.6
44.9
19.1
64.1
48.9*
19.9*
64.7*
53.0*
20.7*
65.3*
49
31.9
15.6
63.0
35.6
16.5
63.0
39.7
17.4
63.0
43.9
18.2
63.1
48.3
18.9
63.2
52.8
19.7
63.4
57.5*
20.4*
63.7*
52
29.5*
15.6*
66.0*
33.2*
16.6*
66.0*
37.2*
17.6*
66.0*
41.2*
18.4*
66.1*
45.5*
19.3*
66.2*
50.0*
20.1*
66.3*
54.5*
20.9*
66.5*
38AH054 CIRCUIT A
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
10
32
44.9
14.2
46.0
49.2
14.7
46.0
53.8
15.1
46.1
58.5
15.5
46.3
63.4
15.9
46.6
68.4
16.3
47.0
73.5
16.6
47.5
46
34.2
15.6
60.0
38.0
16.4
60.0
42.2
17.1
60.0
46.5
17.8
60.1
51.0
18.5
60.2
55.7
19.2
60.5
60.4
19.8
60.8
38AH064 CIRCUIT A
SST
(C)
2
10
kW
SDT
SST
TC
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
21
70.7
16.7
34.9
76.4
17.2
35.4
82.5
17.7
36.1
88.8
18.1
36.8
95.4
18.6
37.7
102.0
19.1
38.6
109.0
19.6
39.5
27
65.0
18.1
40.7
70.5
18.7
41.1
76.3
19.3
41.7
82.3
19.9
42.4
88.5
20.5
43.2
94.9
21.1
44.1
102.0
21.7
44.9
30
62.3
18.8
43.6
67.5
19.4
44.0
73.2
20.1
44.6
79.0
20.7
45.2
85.1
21.4
46.0
91.4
22.0
46.8
97.8
22.7
47.7
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
43
50.8
21.1
56.3
55.5
21.9
56.5
60.5
22.8
57.0
65.6
23.7
57.5
70.9
24.7
58.1
76.5
25.6
58.8
82.1
26.5
59.6
46
48.2
21.5
59.2
52.8
22.4
59.4
57.6
23.4
59.9
62.6
24.4
60.3
67.7
25.3
60.9
73.1
26.3
61.6
78.6
27.3
62.3
49
45.8
21.9
62.2
50.1
22.9
62.5
54.8
23.9
62.8
59.6
24.9
63.2
64.6
25.9
63.8
69.8
27.0
64.4
75.1
28.0
65.1
52
43.3
22.2
65.1
47.5
23.3
65.3
52.1
24.3
65.7
56.7
25.4
66.1
61.5*
26.5*
66.6*
66.6*
27.6*
67.2*
71.7*
28.7*
67.9*
81
10
21
52.8
12.2
33.8
57.3
12.4
34.0
62.2
12.6
34.3
67.1
12.8
34.7
72.3
13.0
35.1
77.7
13.2
35.5
83.2
13.3
36.0
27
48.4
13.3
39.8
52.8
13.6
40.0
57.4
13.9
40.2
62.2
14.2
40.6
67.1
14.5
41.0
72.3
14.8
41.4
77.6
15.1
41.9
30
46.2
13.8
42.8
50.4
14.2
42.9
55.0
14.5
43.2
59.7
14.9
43.5
64.5
15.3
43.9
69.6
15.6
44.4
74.8
15.9
44.8
32
44.7
14.1
44.8
48.9
14.5
44.9
53.4
14.9
45.2
58.0
15.3
45.5
62.8
15.7
45.8
67.8
16.1
46.3
72.9
16.4
46.8
43
36.3
15.3
55.7
40.2
16.0
55.8
44.3
16.6
56.0
48.6
17.3
56.3
53.0
17.9
56.6
57.6
18.5
57.0
62.3
19.1
57.4
46
33.9
15.5
58.7
37.7
16.3
58.8
41.8
17.0
59.0
46.0
17.7
59.2
50.3
18.4
59.5
54.8
19.1
59.9
59.4
19.7
60.3
49
31.6
15.6
61.6
35.3
16.5
61.8
39.3
17.3
61.9
43.3
18.1
62.2
47.6
18.8
62.5
51.9
19.6
62.8
56.4
20.3
63.2
52
29.3
15.7
64.6
32.9
16.6
64.7
36.7
17.5
64.9
40.7
18.4
65.1
44.8
19.2
65.4
49.1*
20.0*
65.8*
53.5*
20.8*
66.1*
43
50.5
21.3
57.7
55.1
22.2
58.0
60.0
23.1
58.5
65.0
24.1
59.0
70.3
25.0
59.6
75.8
26.0
60.3
81.4
26.9
61.0
46
48.0
21.7
60.6
52.4
22.7
60.9
57.2
23.6
61.3
62.0
24.6
61.8
67.1
25.7
62.4
72.5
26.7
63.1
77.9
27.7
63.8
49
45.5
22.0
63.6
49.8
23.1
63.9
54.4
24.1
64.2
59.1
25.2
64.7
64.0
26.2
65.2
69.2
27.3
65.9
74.5*
28.4*
66.6*
52
43.1*
22.4*
66.5*
47.2*
23.5*
66.8*
51.6*
24.6*
67.2*
56.2
25.7*
67.6*
61.0*
26.8*
68.1
66.0*
27.9*
68.7*
71.0*
29.1*
69.4*
38AH054 CIRCUIT B
SST
(C)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
10
21
70.0
17.1
36.4
75.7
17.6
36.9
81.7
18.1
37.6
87.9
18.6
38.4
94.4
19.2
39.2
101.0
19.7
40.2
108.0
20.2
41.1
27
64.5
18.5
42.1
69.9
19.1
42.6
75.6
19.7
43.2
81.5
20.3
43.9
87.6
21.0
44.7
94.0
21.6
45.6
101.0
22.3
46.5
30
61.7
19.1
45.0
67.0
19.8
45.5
72.6
20.4
46.1
78.3
21.1
46.7
84.3
21.8
47.5
90.5
22.5
48.3
96.9
23.2
49.2
32
60.0
19.5
47.0
65.1
20.2
47.4
70.6
20.9
48.0
76.2
21.6
48.6
82.1
22.4
49.3
88.2
23.1
50.1
94.5
23.9
51.0
38AH064 CIRCUIT B
SST
(C)
2
10
kW
SDT
SST
TC
82
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
21
77.8
19.0
34.5
83.9
19.4
34.8
90.4
19.8
35.3
97.0
20.3
35.9
104.0
20.7
36.6
111.0
21.1
37.4
118.0
21.5
38.2
27
72.2
20.5
40.3
78.1
21.1
40.7
84.4
21.7
41.2
90.8
22.3
41.7
97.4
22.9
42.4
104.0
23.4
43.1
111.0
24.0
43.9
30
69.4
21.2
43.3
75.2
21.9
43.6
81.4
22.5
44.0
87.6
23.2
44.6
94.1
23.9
45.2
101.0
24.5
45.9
108.0
25.2
46.7
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
43
57.0
23.5
56.1
62.3
24.5
56.3
67.9
25.5
56.7
73.6
26.5
57.1
79.6
27.5
57.6
85.7
28.5
58.2
91.9
29.5
58.9
46
54.1
23.9
59.1
59.3
25.0
59.2
64.8
26.1
59.6
70.4
27.1
60.0
76.1
28.2
60.4
82.1
29.3
61.1
88.2
30.3
61.7
49
51.2
24.1
62.0
56.3
25.3
62.2
61.6
26.5
62.5
67.1
27.7
62.9
72.7
28.8
63.3
78.6
30.0
63.9
84.5
31.1
64.5
52
48.3
24.3
65.0
53.2
25.6
65.1
58.4
26.9
65.4
63.8
28.1
65.8
69.3*
29.4*
66.2*
75.0*
30.6*
66.7*
80.8*
31.8*
67.3*
10
21
78.6
18.8
33.9
84.7
19.3
34.4
91.1
19.7
35.0
97.6
20.2
35.7
104.0
20.6
36.4
112.0
21.0
37.2
119.0
21.4
38.0
27
73.2
20.4
39.7
79.1
20.9
40.1
85.3
21.5
40.7
91.5
22.1
41.3
98.1
22.7
42.0
105.0
23.3
42.7
112.0
23.9
43.5
30
70.5
21.1
42.7
76.3
21.7
43.0
82.3
22.4
43.5
88.5
23.0
44.1
94.9
23.7
44.8
102.0
24.4
45.5
108.0
25.0
46.3
43
58.2
23.4
55.5
63.6
24.4
55.5
69.3
25.4
55.9
75.0
26.3
56.3
80.9
27.3
56.9
87.0
28.3
57.5
93.1
29.3
58.2
46
55.3
23.8
58.5
60.6
24.9
58.5
66.2
25.9
58.7
71.8
27.0
59.1
77.6
28.0
59.6
83.5
29.1
60.3
89.6
30.1
61.0
49
52.4
24.1
61.4
57.6
25.3
61.4
63.1
26.4
61.6
68.6
27.5
61.9
74.3
28.6
62.4
80.1
29.8
63.0
86.0
30.9
63.7
21
102.0
27.2
36.7
110.0
28.0
36.8
119.0
28.7
37.1
128.0
29.4
37.5
137.0
30.2
38.0
147.0
31.0
38.7
157.0
31.8
39.5
27
95.0
29.1
42.7
103.0
30.0
42.8
111.0
30.9
43.0
120.0
31.8
43.3
129.0
32.7
43.8
138.0
33.7
44.4
147.0
34.7
45.1
30
91.7
29.9
45.7
99.2
30.9
45.8
107.0
31.9
46.0
116.0
32.9
46.2
125.0
33.9
46.7
134.0
35.0
47.3
143.0
36.0
47.9
43
77.4
32.9
58.7
84.0
34.2
58.7
91.3
35.6
58.9
98.7
37.0
59.1
107.0
38.4
59.4
115.0
39.8
59.8
123.0
41.2
60.3
46
74.2
33.4
61.7
80.6
34.9
61.7
87.6
36.3
61.9
94.8
37.8
62.0
102.0
39.3
62.3
110.0
40.8
62.7
118.0
42.3
63.1
49
71.0
33.9
64.7
77.2
35.5
64.7
84.0
37.0
64.8
91.0
38.6
65.0
98.3
40.1
65.2
106.0
41.7
65.6
114.0*
43.3*
66.0*
52
49.5
24.3
64.4
54.5
25.6
64.4
59.9
26.8
64.6
65.4
28.0
64.8
70.9
29.2
65.3
76.6*
30.4*
65.8*
82.4*
31.6*
66.4*
38AH084 CIRCUIT A
SST
(C)
2
10
kW
SDT
SST
TC
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
52
67.8*
34.4*
67.7*
73.8*
36.0*
67.7*
80.4*
37.6*
67.8*
87.2*
39.2*
67.9*
94.3*
40.9*
68.2*
102.0*
42.5*
68.5*
109.0*
44.2*
68.9*
83
10
21
103.0
26.4
34.2
110.0
27.2
34.8
118.0
28.1
35.6
127.0
28.9
36.3
135.0
29.8
37.1
145.0
30.6
38.0
154.0
31.4
38.9
27
96.0
28.3
39.9
103.0
29.3
40.5
111.0
30.3
41.2
119.0
31.3
41.9
127.0
32.3
42.7
136.0
33.3
43.6
145.0
34.4
44.4
30
92.7
29.1
42.8
99.8
30.2
43.3
107.0
31.3
44.0
115.0
32.4
44.7
123.0
33.5
45.5
132.0
34.6
46.3
140.0
35.7
47.2
32
90.5
29.6
44.7
97.5
30.8
45.2
105.0
31.9
45.9
113.0
33.1
46.6
120.0
34.2
47.4
129.0
35.4
48.2
137.0
36.6
49.0
46
75.7
32.8
58.2
81.9
34.2
58.5
88.4
35.7
59.1
95.1
37.2
59.7
102.0
38.7
60.4
109.0
40.3
61.1
117.0
41.8
61.9
49
72.6
33.3
61.2
78.6
34.8
61.4
85.0
36.4
61.9
91.5
37.9
62.5
98.2
39.5
63.1
105.0
41.2
63.9
112.0
42.8
64.6
52
69.4
33.8
64.1
75.3
35.4
64.3
81.5
37.0
64.8
87.8
38.6
65.3
94.4
40.3
65.9
101.0*
42.0*
66.6*
108.0*
43.7*
67.4*
21
102.0
26.9
35.7
111.0
27.6
35.8
119.0
28.3
36.2
128.0
29.1
36.7
137.0
29.8
37.3
147.0
30.6
38.1
157.0
31.4
38.9
27
95.6
28.8
41.6
103.0
29.7
41.8
112.0
30.6
42.1
120.0
31.5
42.5
129.0
32.4
43.0
138.0
33.4
43.7
147.0
34.4
44.5
30
92.2
29.6
44.6
99.7
30.6
44.7
108.0
31.6
45.0
116.0
32.6
45.4
125.0
33.6
45.9
134.0
34.7
46.5
143.0
35.7
47.3
32
89.9
30.2
46.6
97.4
31.2
46.7
105.0
32.3
47.0
113.0
33.3
47.3
122.0
34.4
47.8
131.0
35.5
48.4
140.0
36.6
49.1
46
74.7
33.2
60.6
81.1
34.7
60.6
88.1
36.1
60.8
95.3
37.5
61.0
103.0
39.0
61.4
111.0
40.5
61.8
118.0
42.0
62.3
49
71.5
33.8
63.6
77.7
35.3
63.6
84.5
36.8
63.7
91.5
38.3
63.9
98.7
39.8
64.3
106.0
41.4
64.7
114.0
43.0
65.2
52
68.4*
34.2*
66.6*
74.4*
35.8*
66.6*
80.8*
37.4*
66.7*
87.7*
39.0*
66.9*
94.7*
40.6*
67.2*
102.0*
42.3*
67.6*
110.0*
43.9*
68.1*
38AH084 CIRCUIT B
SST
(C)
2
10
kW
SDT
SST
TC
84
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
LEGEND
Compressor Power
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
10
21
130.0
31.8
35.5
33.6
140.0
32.7
36.2
34.0
150.0
33.7
37.1
34.6
161.0
34.7
38.0
35.2
172.0
35.7
39.0
35.8
183.0
36.7
40.1
36.5
195.0
37.7
41.1
37.2
27
120.0
34.2
41.2
39.7
130.0
35.3
41.8
40.1
140.0
36.5
42.6
40.6
150.0
37.7
43.5
41.2
161.0
38.9
44.4
41.9
172.0
40.1
45.4
42.6
183.0
41.3
46.4
43.3
30
116.0
35.3
44.0
42.8
125.0
36.6
44.5
43.1
135.0
37.9
45.3
43.7
145.0
39.2
46.2
44.3
155.0
40.5
47.1
44.9
166.0
41.8
48.0
45.6
177.0
43.1
49.1
46.4
32
112.0
36.0
45.9
44.8
122.0
37.3
46.4
45.1
131.0
38.7
47.2
45.7
141.0
40.1
48.0
46.3
152.0
41.5
48.9
46.9
162.0
42.9
49.8
47.6
173.0
44.3
50.8
48.4
43
94.2
38.9
56.5
55.9
103.0
40.7
56.8
56.0
112.0
42.5
57.4
56.5
122.0
44.3
58.0
57.0
131.0
46.1
58.8
57.6
141.0
47.9
59.6
58.3
151.0
49.8
60.5
59.0
46
89.1
39.4
59.4
58.9
97.9
41.4
59.6
59.0
107.0
43.3
60.2
59.4
116.0
45.2
60.8
59.9
125.0
47.1
61.5
60.5
135.0
49.1
62.3
61.1
145.0
51.0
63.2
61.8
49
84.0
39.8
62.3
61.9
92.6
41.9
62.5
62.0
101.0
43.9
63.0
62.3
110.0
46.0
63.5
62.7
120.0
48.1
64.2
63.3
129.0
50.1
65.0
64.0
139.0
52.2
65.9
64.7
52
78.8
40.0
65.3
64.9
87.3
42.3
65.4
64.9
96.0
44.5
65.8
65.3
105.0
46.7
66.3
65.6
114.0
48.9
66.9
66.2
123.0
51.1
67.7
66.8
132.0
53.3
68.5*
67.5
21
124.0
28.9
34.4
32.6
134.0
29.8
35.1
33.1
144.0
30.7
36.0
33.6
154.0
31.5
36.9
34.2
165.0
32.4
37.9
34.8
176.0
33.3
38.9
35.5
188.0
34.3
39.9
36.2
27
115.0
31.2
40.0
38.6
124.0
32.3
40.6
39.1
134.0
33.4
41.4
39.6
144.0
34.4
42.3
40.2
154.0
35.5
43.2
40.8
165.0
36.6
44.1
41.5
176.0
37.7
45.2
42.2
30
110.0
32.4
42.8
41.7
119.0
33.5
43.4
42.1
128.0
34.7
44.1
42.6
138.0
35.9
44.9
43.2
148.0
37.1
45.8
43.8
159.0
38.3
46.8
44.5
170.0
39.5
47.8
45.2
32
107.0
33.1
44.7
43.7
116.0
34.3
45.2
44.0
125.0
35.5
46.0
44.6
135.0
36.7
46.7
45.1
145.0
38.0
47.6
45.8
155.0
39.3
48.6
46.5
166.0
40.6
49.5
47.2
43
89.4
36.2
55.2
54.6
97.8
37.8
55.5
54.9
106.0
39.4
56.1
55.3
115.0
41.0
56.7
55.8
124.0
42.6
57.5
56.4
134.0
44.3
58.4
57.1
143.0
45.9
59.2
57.8
46
84.7
36.8
58.1
57.7
92.8
38.5
58.4
57.8
101.0
40.2
58.9
58.2
110.0
42.0
59.5
58.7
119.0
43.7
60.2
59.2
128.0
45.5
61.0
59.9
137.0
47.2
61.9
60.6
49
80.0
37.3
61.1
60.7
88.0
39.2
61.3
60.8
96.3
41.0
61.7
61.1
105.0
42.8
62.3
61.5
113.0
44.7
63.0
62.1
122.0
46.5
63.7
62.7
132.0
48.4
64.5
63.4
52
75.3
37.7
64.0
63.7
83.1
39.7
64.1
63.7
91.2
41.7
64.6
64.0
99.4
43.6
65.1
64.4
108.0
45.6
65.7
64.9
117.0
47.5
66.4
65.5
126.0
49.5
67.2
66.2
38AH104 CIRCUIT A
SST
(C)
2
10
kW
SCT
SDT
SST
TC
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
LEGEND
Compressor Power
Saturated Condensing Temperature (C)
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
85
10
21
103.0
26.3
33.8
32.3
111.0
27.0
34.2
32.4
119.0
27.8
34.9
32.8
128.0
28.6
35.6
33.3
137.0
29.4
36.4
33.8
146.0
30.2
37.3
34.3
155.0
31.0
38.2
34.9
27
96.5
28.1
39.6
38.5
104.0
29.0
39.9
38.6
112.0
30.0
40.5
39.0
120.0
30.9
41.2
39.4
129.0
31.9
41.9
39.9
137.0
32.9
42.7
40.4
146.0
33.9
43.6
41.0
30
93.1
29.0
42.5
41.5
101.0
30.0
42.8
41.7
108.0
31.0
43.4
42.0
116.0
32.1
44.0
42.4
124.0
33.1
44.7
42.9
133.0
34.2
45.5
43.5
142.0
35.3
46.3
44.1
32
90.9
29.6
44.5
43.6
98.2
30.6
44.8
43.7
106.0
31.7
45.3
44.0
114.0
32.8
45.9
44.4
122.0
33.9
46.5
44.9
130.0
35.0
47.3
45.5
139.0
36.2
48.2
46.1
43
78.9
32.2
55.4
54.8
85.5
33.5
55.5
54.8
92.6
34.9
55.9
55.1
99.7
36.2
56.3
55.4
107.0
37.6
56.9
55.8
115.0
39.1
57.5
56.3
123.0
40.5
58.3
56.9
46
75.7
32.8
58.3
57.9
82.1
34.2
58.4
57.9
89.0
35.6
58.8
58.1
95.9
37.1
59.2
58.4
103.0
38.5
59.7
58.8
111.0
40.0
60.3
59.3
118.0
41.5
61.0
59.8
49
72.5
33.4
61.3
60.9
78.8
34.8
61.4
60.9
85.4
36.3
61.7
61.1
92.2
37.8
62.1
61.3
99.2
39.4
62.5
61.7
106.0
40.9
63.1
62.2
114.0
42.5
63.8
62.7
52
69.4
33.9
64.3
63.9
75.4
35.4
64.4
63.9
81.9
37.0
64.6
64.1
88.4
38.5
65.0
64.3
95.3
40.2
65.4
64.7
102.0
41.8
66.0
65.1
110.0
43.5
66.6
65.6
21
141.0
33.9
35.7
33.5
151.0
35.1
36.5
34.0
163.0
36.2
37.5
34.7
174.0
37.4
38.5
35.3
186.0
38.6
39.6
36.0
199.0
39.8
40.7
36.7
212.0
41.1
41.9
37.5
27
130.0
36.5
41.2
39.5
140.0
37.8
41.9
40.0
151.0
39.2
42.9
40.7
162.0
40.6
43.8
41.4
174.0
42.0
44.8
42.1
186.0
43.4
45.9
42.8
198.0
44.9
47.0
43.6
30
125.0
37.7
43.9
42.6
135.0
39.1
44.7
43.1
145.0
40.6
45.5
43.7
156.0
42.1
46.4
44.4
168.0
43.6
47.4
45.1
179.0
45.2
48.5
45.8
191.0
46.8
49.5
46.6
32
122.0
38.5
45.8
44.5
131.0
40.0
46.5
45.0
142.0
41.5
47.3
45.7
152.0
43.1
48.2
46.3
163.0
44.7
49.2
47.1
175.0
46.3
50.2
47.8
187.0
47.9
51.3
48.6
43
103.0
42.1
56.2
55.5
112.0
44.0
56.7
55.8
122.0
45.9
57.4
56.4
131.0
47.8
58.1
57.0
141.0
49.8
59.0
57.7
151.0
51.8
59.9
58.4
162.0
53.8
60.8
59.2
46
98.4
42.9
59.1
58.5
107.0
44.9
59.5
58.8
116.0
46.9
60.1
59.3
125.0
48.9
60.8
59.8
135.0
51.0
61.7
60.5
145.0
53.1
62.6
61.2
155.0
55.2
63.5
62.0
49
93.6
43.7
61.9
61.4
102.0
45.7
62.3
61.7
111.0
47.8
62.9
62.2
120.0
50.0
63.6
62.7
129.0
52.1
64.4
63.4
139.0
54.3
65.2
64.1
149.0
56.6
66.1
64.8
52
88.9
44.4
64.9
64.4
97.0
46.5
65.2
64.6
106.0
48.7
65.7
65.1
114.0
50.9
66.3
65.6
123.0
53.2
67.1
66.2
133.0
55.5
67.9
66.9
142.0
57.9
68.7*
67.6
38AH104 CIRCUIT B
SST
(C)
2
10
kW
SCT
SDT
SST
TC
86
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
LEGEND
Compressor Power
Saturated Condensing Temperature (C)
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
10
21
149.0
35.7
34.7
33.9
161.0
36.7
35.2
34.3
173.0
37.6
35.8
34.7
186.0
38.5
36.5
35.3
200.0
39.4
37.2
35.9
214.0
40.3
38.1
36.6
228.0
41.3
39.0
37.3
27
138.0
38.6
40.5
39.9
149.0
39.8
40.9
40.2
161.0
41.0
41.5
40.7
174.0
42.1
42.1
41.2
186.0
43.3
42.9
41.8
200.0
44.6
43.7
42.4
213.0
45.8
44.5
43.1
30
132.0
40.0
43.4
42.9
143.0
41.3
43.8
43.2
155.0
42.6
44.4
43.6
167.0
44.0
45.0
44.1
180.0
45.3
45.7
44.7
193.0
46.6
46.5
45.3
206.0
48.0
47.3
46.0
32
129.0
40.8
45.4
44.9
140.0
42.2
45.8
45.2
151.0
43.7
46.3
45.6
163.0
45.1
46.9
46.1
175.0
46.5
47.6
46.6
188.0
47.9
48.3
47.3
201.0
49.4
49.1
48.0
43
109.0
44.5
56.2
55.9
119.0
46.4
56.4
56.0
129.0
48.4
56.8
56.4
140.0
50.3
57.3
56.8
151.0
52.2
57.9
57.3
163.0
54.1
58.6
57.9
175.0
56.1
59.3
58.5
46
103.0
45.4
59.1
58.9
113.0
47.4
59.4
59.0
123.0
49.5
59.7
59.3
134.0
51.5
60.2
59.7
145.0
53.6
60.7
60.2
156.0
55.6
61.4
60.7
167.0
57.7
62.1
61.3
49
97.8
46.0
62.1
61.9
107.0
48.2
62.3
62.0
117.0
50.4
62.7
62.3
127.0
52.6
63.1
62.6
138.0
54.8
63.6
63.1
149.0
57.0
64.2
63.6
160.0
59.2
64.8
64.2
52
92.5
46.6
65.1
64.8
102.0
48.9
65.2
65.0
111.0
51.2
65.6
65.2
121.0
53.5
65.9
65.5
132.0
55.9
66.4
66.0
142.0
58.2
67.0
66.5
153.0
60.6
67.6*
67.0
21
181.0
45.2
34.0
31.9
195.0
46.5
34.5
32.4
210.0
47.8
35.2
33.0
224.0
49.0
36.0
33.6
240.0
50.3
36.7
34.3
256.0
51.5
37.6
34.9
273.0
52.8
38.4
35.6
27
169.0
48.6
39.8
37.7
182.0
50.2
40.2
38.2
196.0
51.8
40.9
38.8
211.0
53.4
41.6
39.5
226.0
55.0
42.3
40.1
241.0
56.6
43.1
40.7
257.0
58.2
44.0
41.4
30
163.0
50.1
42.7
40.7
176.0
51.8
43.1
41.2
190.0
53.6
43.7
41.7
204.0
55.4
44.4
42.3
218.0
57.1
45.1
43.0
233.0
58.9
45.9
43.6
249.0
60.7
46.7
44.3
32
159.0
51.1
44.6
42.6
172.0
52.9
45.0
43.1
185.0
54.8
45.6
43.7
199.0
56.6
46.3
44.3
213.0
58.5
47.0
44.9
228.0
60.4
47.8
45.5
244.0
62.2
48.6
46.2
43
137.0
55.6
55.4
53.4
149.0
57.9
55.5
53.6
161.0
60.3
56.0
54.2
174.0
62.7
56.5
54.7
187.0
65.1
57.2
55.3
201.0
67.6
57.9
55.9
215.0
70.0
58.7
56.5
46
131.0
56.6
58.3
56.3
143.0
59.1
58.4
56.5
155.0
61.6
58.9
57.0
167.0
64.1
59.3
57.5
180.0
66.7
60.0
58.1
193.0
69.3
60.7
58.7
207.0
71.9
61.4
59.3
49
125.0
57.4
61.3
59.3
136.0
60.1
61.4
59.4
148.0
62.7
61.8
59.9
160.0
65.4
62.2
60.3
173.0
68.1
62.8
60.9
186.0
70.9
63.4
61.5
199.0
73.7
64.2
62.1
52
119.0
58.2
64.3
62.2
130.0
61.0
64.3
62.4
142.0
63.7
64.6
62.7
153.0
66.6
65.0
63.1
165.0
69.4
65.5
63.7
178.0
72.4
66.2
64.2
191.0
75.3
66.9
64.8
10
kW
SCT
SDT
SST
TC
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
LEGEND
Compressor Power
Saturated Condensing Temperature (C)
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Gross Cooling Capacity (kW)
87
16
59.2
59.2
11.89
57.6
57.6
12.77
56.0
56.0
13.51
54.4
54.4
14.52
52.5
52.5
15.36
50.8
50.8
16.16
49.0
49.0
17.15
47.1
47.1
18.14
16
66.3
66.3
12.32
64.5
64.5
13.20
62.6
62.6
14.08
60.7
60.7
15.10
58.7
58.7
16.06
56.7
56.7
17.00
54.6
54.6
17.99
52.5
52.5
18.97
3500
20
64.9
48.3
12.24
63.0
47.3
13.11
61.1
46.3
13.95
59.1
45.3
14.96
57.1
44.3
15.88
55.0
43.2
16.76
52.9
42.1
17.73
50.7
41.0
18.70
4700
20
71.3
58.3
12.63
69.2
57.3
13.50
66.9
56.2
14.46
64.6
55.2
15.46
62.4
54.2
16.49
60.0
53.1
17.47
57.5
21.9
18.43
55.1
50.8
19.38
LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (kW)
TC Total Capacity (kW)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.
88
5900
20
76.1
67.6
12.92
73.7
66.6
13.78
71.2
65.5
14.83
68.7
64.3
15.83
66.4
63.3
16.94
63.7
62.1
18.00
61.0
60.9
18.95
58.4
58.1
19.89
16
72.2
72.2
12.68
70.2
70.2
13.56
68.1
68.1
14.56
66.0
66.0
15.58
64.0
64.0
16.66
61.7
61.7
17.72
59.4
59.4
18.71
57.1
57.1
19.69
4700
20
77.9
61.3
15.20
75.9
60.4
16.28
73.6
59.3
17.38
71.4
58.3
18.52
69.0
57.2
19.60
66.7
56.1
20.76
64.3
21.9
21.70
61.5
53.7
23.52
16
71.6
71.6
14.75
70.0
70.0
15.96
68.2
68.2
16.95
66.3
66.3
18.01
64.3
64.3
19.02
62.4
62.4
20.19
60.4
60.4
21.17
58.1
58.1
22.76
5. Formulas (cooling)
sensible heat capacity (kW)
1.23 x 10-3 x (L/s)
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb
hldb = hedb
16
78.2
78.2
15.22
76.4
76.4
16.31
74.3
74.3
17.43
72.2
72.2
18.60
70.1
70.1
19.74
67.9
67.9
20.92
65.7
65.7
21.89
63.0
63.0
23.87
16
84.3
84.3
15.63
82.2
82.2
16.63
79.7
79.7
17.86
77.5
77.5
19.13
75.1
75.1
20.36
72.6
72.6
21.53
70.1
70.1
22.49
67.0
67.0
24.76
5900
20
83.5
70.9
15.60
81.3
69.9
16.58
78.6
68.7
17.77
76.2
67.7
19.00
73.6
66.5
20.18
71.0
65.3
21.32
68.4
64.2
22.25
65.1
62.8
24.34
7050
20
88.5
79.8
15.95
86.0
78.7
16.84
82.9
77.4
18.11
80.3
76.2
19.41
77.5
74.9
20.66
74.6
73.6
21.79
71.8
72.4
22.72
68.1
68.1
25.02
LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (kW)
TC Total Capacity (kW)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.
5900
20
93.5
75.3
18.83
90.9
74.2
20.04
88.3
73.1
21.38
85.6
71.9
22.83
82.9
70.7
24.15
80.2
69.5
25.53
77.2
68.1
26.97
74.5
66.9
28.50
16
86.2
86.2
18.26
84.1
84.1
19.50
82.1
82.1
20.76
79.9
79.9
22.24
77.7
77.7
23.50
75.5
75.5
24.83
73.1
73.1
26.24
70.7
70.7
27.83
7050
20
99.5
84.8
19.30
96.7
83.5
20.50
93.8
82.2
21.93
90.8
80.9
23.37
87.8
79.5
24.77
84.8
78.2
26.21
81.5
76.7
27.72
78.5
75.4
29.22
16
93.4
93.4
18.82
91.1
91.1
20.06
88.8
88.8
21.43
86.2
86.2
22.90
83.8
83.8
24.26
81.2
81.2
25.68
78.5
78.5
27.19
75.9
75.9
28.75
5. Formulas (cooling)
sensible heat capacity (kW)
1.23 x 10-3 x (L/s)
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb
hldb = hedb
89
17
60.2
58.0
13.57
57.3
56.2
14.80
55.8
55.8
15.40
54.5
54.5
16.00
51.9
51.9
17.21
17
66.7
66.6
14.22
63.1
63.1
15.38
61.7
61.7
16.04
60.3
60.3
16.69
57.4
57.4
17.97
3500
19
65.5
48.4
13.96
62.4
47.3
15.28
60.7
46.7
15.92
59.1
46.0
16.54
55.7
44.7
17.74
4720
19
69.8
57.3
14.29
66.0
55.8
15.58
64.7
55.3
16.35
62.6
54.5
16.91
59.1
53.2
18.18
LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (kW)
TC Total Capacity (kW)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.
90
5900
19
73.8
66.6
14.58
69.9
65.1
15.95
68.1
64.2
16.67
66.3
63.5
17.36
62.6
61.5
18.68
17
71.5
71.5
14.41
68.6
68.6
15.88
67.0
67.0
16.58
65.4
65.4
17.28
62.2
62.2
18.63
4720
19
77.8
60.3
17.38
74.2
58.9
18.91
72.4
58.2
19.66
70.5
57.5
20.39
66.9
56.1
21.89
17
72.0
72.0
16.85
69.2
69.2
18.36
67.8
67.8
19.12
66.4
66.4
19.86
63.5
63.5
21.39
5. Formulas (cooling)
sensible heat capacity (kW)
1.23 x 10-3 x (L/s)
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb
hldb = hedb
17
78.6
78.6
17.45
75.5
75.5
19.06
73.9
73.9
19.86
72.3
72.3
20.64
69.1
69.1
22.26
17
84.0
84.0
17.91
80.7
80.7
19.63
78.9
78.9
20.46
77.1
77.1
21.28
73.6
73.6
22.95
5900
19
82.5
69.9
17.77
78.6
68.4
19.40
76.7
67.7
20.20
74.8
67.0
20.97
70.7
65.2
22.50
7080
19
86.3
78.8
18.12
82.0
77.2
19.76
80.0
76.3
20.57
78.0
75.3
21.39
73.9
73.1
23.01
LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (kW)
TC Total Capacity (kW)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit.
4. Gross capacities shown do not include a deduction for evaporator-fan motor
heat.
5900
19
92.6
73.9
22.04
88.5
72.3
23.82
86.5
71.5
24.69
84.4
70.7
25.58
80.1
69.0
27.28
17
87.2
86.7
21.51
83.3
83.3
23.10
81.6
81.6
23.96
79.9
79.9
24.86
76.6
76.6
26.63
7080
19
97.5
83.3
22.60
93.0
81.5
24.41
90.8
80.6
25.30
88.6
79.7
26.21
84.1
77.7
27.99
17
93.0
93.0
22.06
89.9
89.9
24.03
87.7
87.7
24.84
85.9
85.9
25.77
82.1
82.1
27.60
5. Formulas (cooling)
sensible heat capacity (kW)
1.23 x 10-3 x (L/s)
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
tldb = tedb
hldb = hedb
91
63
95
95
96
102
102
102
103
103
104
104
125
95
95
96
96
96
96
95
96
95
95
250
93
93
94
95
95
96
97
98
97
97
102
96
96
95
93
102
95
96
95
102
95
96
95
NOTES:
1. Estimated sound power levels are -dB re 1 Picowatt.
2. The estimated sound power levels are assumed to originate at the
acoustic center of the unit. The acoustic center of the unit is
located at the projection of the condensing units geometric center
on its base.
4000
82
82
83
85
85
85
86
87
89
89
8000
81
81
83
80
80
81
81
82
87
88
dBA
93.5
93.5
94.6
97
97
98
98
99
99
99
89
85
81
98
93
89
85
81
98
93
89
85
81
98
ESTIMATED SOUND POWER LEVEL (dB), 60 Hz UNITS WITH SOUND REDUCTION KIT
UNIT
38AH044
38AH054
38AH064
38AH074
38AH084
38AH094
38AH104
38AH124
Module A&B
38AH134
Module A
38AH134
Module B
63
98
98
98
99
100
99
99
125
95
95
95
96
96
92
93
250
95
95
96
95
96
93
94
99
95
96
93
91
87
99
95
96
93
91
99
96
95
93
91
NOTES:
1. Estimated sound power levels are -dB re 1 Picowatt.
2. The estimated sound power levels are assumed to originate at the
acoustic center of the unit. The acoustic center of the unit is
located at the projection of the condensing units geometric center
on its base.
8000
80
80
80
79
80
87
97
dBA
95
95
96
95
96
97
96
82
80
87
82
80
86
82
79
63
97.7
97.7
98.5
125
93.6
93.6
94.2
NOTES:
1. Estimated sound power levels, dB re 1 Picowatt
This data is based upon a limited amount of actual testing with the
estimated sound power data being generated from this data in
accordance with AHRI (Air Conditioning, Heating, and Refrigeration Institute, U.S.A. Standard) standard 370 for large outdoor
refrigerating and air conditioning equipment.
92
4000
78.8
78.5
76.0
8000
74.4
74.5
74.9
dB(A)
92.5
92.6
93.2
2. Since this data is estimated, the sound power levels should not be
guaranteed or certified as being the actual sound power levels.
The acoustic center of the unit is located at the geometric center of
the unit.
a38-6600tf
LEGEND
LLSV Liquid Line Solenoid Valve
NEC National Electrical Code
TXV Thermostatic Expansion Valve
Piping
Double Riser Piping (if required)
*Field supplied.
If double suction riser is required for piping
system, size pipe diameter of 3 ft (maximum)
riser according to application data on pages
123-129.
**See Refrigerant Specialties Part Numbers
table on page 97.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System
Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not
intended for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.
93
b38-926tf
TXV
LEGEND
Thermostatic Expansion Valve
Piping
*Field supplied.
94
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System
Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not
intended for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.
a38-3604tf
LEGEND
NEC National Electrical Code
TXV Thermostatic Expansion Valve
Line Voltage
Piping
Double Riser Piping
(If Required)
a38-4395tf
95
a38-4396tf
LEGEND
NEC National Electrical Code
TXV Thermostatic Expansion Valve
Line Voltage
Piping
a38-3607tf
96
38AH028
38AH034
38AH044
38AH054
38AH064
38AH074-084
38AH094-104
38AH124
38AH134 Module A
38AH134 Module B
LIQUID LINE
SIZE* (in.)
1/
2
5/
8
7/
8
1/
2
5/
8
7/
8
1/
2
5/
8
7/
8
5/
8
7/
8
5/
8
7/
8
7/
8
11/8
7/
8
11/8
13/8
7/
8
11/8
13/8
7/
8
11/8
7/
8
11/8
7/
8
11/8
LIQUID LINE
SOLENOID VALVE (LLS)
200RB6T4M Qty 2
200RB6T5M Qty 2
200RB7T7M Qty 2
200RB6T4M Qty 2
200RB6T5M Qty 2
200RB7T7M Qty 2
200RB6T4M Qty 2
200RB6T5M Qty 2
200RB7T7M Qty 2
240RA9T5M Qty 2
240RA9T7M Qty 2
240RA9T7M Qty 2
240RA9T7M Qty 2
240RA9T7M Qty 2
240RA9T9M Qty 2
240RA16T9M Qty 2
240RA16T9M Qty 2
240RA16T11M Qty 2
240RA16T9M Qty 2
240RA16T9M Qty 2
240RA16T11M Qty 2
240RA9T7M Qty 4
240RA9T9M Qty 4
240RA9T7M Qty 2
240RA9T9M Qty 2
240RA16T9M Qty 2
240RA16T9M Qty 2
LLS COIL
50 Hz UNITS
AMG/208-240V Qty 2
AMG/208-240V Qty 2
AMG/208-240V Qty 2
AMG/208-240V Qty 2
AMG/208-240V Qty 2
AMG/208-240V Qty 2
AMG/208-240V Qty 2
AMG/208-240V Qty 2
AMG/208-240V Qty 2
AMG/208-240V Qty 2
AMG/208-240V Qty 2
AMG/208-240V Qty 2
AMG/208-240V Qty 4
AMG/208-240V Qty 4
AMG/208-240V Qty 2
AMG/208-240V Qty 2
AMG/208-240V Qty 2
AMG/208-240V Qty 2
LLS COIL
60 Hz UNITS
AMG/24V Qty 2
AMG/24V Qty 2
AMG/24V Qty 2
AMG/24V Qty 2
AMG/24V Qty 2
AMG/24V Qty 2
AMG/24V Qty 2
AMG/24V Qty 2
AMG/24V Qty 2
AMG/120V Qty 2
AMG/120V Qty 2
AMG/120V Qty 2
AMG/120V Qty 2
AMG/120V Qty 2
AMG/120V Qty 2
AMG/120V Qty 2
AMG/120V Qty 2
AMG/120V Qty 2
AMG/120V Qty 2
AMG/120V Qty 2
AMG/120V Qty 2
AMG/120V Qty 4
AMG/120V Qty 4
AMG/120V Qty 2
AMG/120V Qty 2
AMG/120V Qty 2
AMG/120V Qty 2
SIGHT
GLASS
AMI-1TT4 Qty 2
AMI-1TT5 Qty 2
AMI-1TT7 Qty 2
AMI-1TT4 Qty 2
AMI-1TT5 Qty 2
AMI-1TT7 Qty 2
AMI-1TT4 Qty 2
AMI-1TT5 Qty 2
AMI-1TT7 Qty 2
AMI-1TT5 Qty 2
AMI-1TT7 Qty 2
AMI-1TT5 Qty 2
AMI-1TT7 Qty 2
AMI-1TT7 Qty 2
AMI-1TT9 Qty 2
AMI-1TT7 Qty 2
AMI-1TT9 Qty 2
AMI-1TT9 Qty 2
AMI-1TT7 Qty 2
AMI-1TT9 Qty 2
AMI-1TT9 Qty 2
AMI-1TT7 Qty 2
AMI-1TT9 Qty 2
AMI-1TT7 Qty 1
AMI-1TT9 Qty 1
AMI-1TT7 Qty 1
AMI-1TT9 Qty 1
FILTER
DRIER
P502-8304S Qty 2
P502-8305S Qty 2
P502-8307S Qty 2
P502-8305S Qty 2
P502-8305S Qty 2
P502-8307S Qty 2
P502-8307S Qty 2
P502-8307S Qty 2
P502-8307S Qty 2
P502-8757S Qty 2
P502-8757S Qty 2
C-967 Qty 2
C-967 Qty 2
C-969 Qty 2
C-969 Qty 2
C-1449 Qty 2
C-1449 Qty 2
C-14411 Qty 2
C-14411 Qty 2
C-14411 Qty 2
C-14411 Qty 2
C-19211 Qty 2
C-19211 Qty 2
C-19211 Qty 1
C-19211 Qty 1
C-19211 Qty 1
C-19211 Qty 1
LEGEND
LLS Liquid LIne Solenoid
*Choose liquid line size using the tables on pages 123-129 before choosing refrigerant specialty parts.
required.
Bushings
NOTE: 38AH044-084 Single Circuit units, refrigerant specialties are installed in the branch sections of the liquid line at the indoor unit.
97
Electrical data
38AH024-034 UNITS, 60 Hz
UNIT
38AH
024
028
034
FLA
HACR
ICF
LRA
MCA
MOCP
RLA
UL
NOMINAL
VOLTAGE
3 Ph, 60 Hz
208/230
380
460
575
208/230
380
460
575
208/230
380
460
575
VOLTAGE
RANGE*
Min
187
342
414
518
187
342
414
518
187
342
414
518
Max
254
418
508
632
254
418
508
632
254
418
508
632
COMPRESSOR
RLA
LRA
Ckt 1
Ckt 2
Ckt 1
Ckt 2
39.3
39.3
198
198
24.0
24.0
93
93
19.6
19.6
99
99
15.7
15.7
79
79
43.6
43.6
228
228
26.4
26.4
104
104
22.1
22.1
114
114
19.7
19.7
91
91
43.6
63.6
228
266
26.4
34.3
104
145
22.1
30.0
114
120
17.9
22.9
91
96
LEGEND
Full Load Amps
Heating, Air Conditioning and Refrigeration
Maximum Instantaneous Current Flow
Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
Rated Load Amps
Underwriters Laboratories
*Units are suitable for use on electrical systems where voltage supplied
to unit terminals is not below or above listed minimum and maximum
limits.
All fans are protected by a single circuit breaker.
POWER SUPPLY
Nominal
Hp
Nominal
kW
0.75
0.75
0.75
MCA
MOCP**
ICF
100.5
61.8
50.2
42.1
110.2
67.2
55.8
47.1
135.2
77.0
65.7
53.3
125
80
60
50
150
90
70
60
175
110
90
70
249.7
124.8
124.8
101.5
284.0
138.2
142.3
117.5
322.0
179.2
148.3
120.7
044
054
064
074
084
VOLTAGE
DESIGNATION
5
2
6
1
5
2
6
1
5
2
6
1
5
2
6
1
5
2
6
1
98
COMPRESSOR
MODEL (A/B)
06E-250/250
06E-250/265
06E-265/275
06E-275/299
06E-299/299
NAMEPLATE
V-Ph-Hz
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
SUPPLY
VOLTAGE*
POWER SUPPLY
Min
Max
MCA
MOCP
ICF
187
342
414
518
187
342
414
518
187
342
414
518
187
342
414
518
187
342
414
518
254
418
508
632
254
418
508
632
254
418
508
632
254
418
508
632
254
418
508
632
177.0
93.5
90.1
78.4
204.3
107.1
101.3
88.0
246.4
126.9
114.3
100.6
327.2
174.5
147.4
132.2
368.2
200.7
166.0
148.9
225
125
110
100
250
150
125
110
350
175
150
125
450
250
200
175
500
250
225
200
434.7
241.2
218.6
162.4
535.7
297.2
268.6
206.4
617.5
341.1
307.6
226.1
829.0
458.0
408.2
336.8
870.0
484.2
426.8
353.5
COMPRESSOR
A
RLA
67.9
34.6
34.6
28.8
67.9
34.6
34.5
28.8
89.7
45.5
43.6
36.5
106.4
52.6
46.8
40.4
147.4
78.8
65.4
57.1
B
LRA
345
191
173
120
345
191
173
120
446
247
223
164
506
280
253
176
690
382
345
276
RLA
67.9
34.6
34.6
28.8
89.7
45.5
43.6
36.5
106.4
52.6
46.8
40.4
147.4
78.8
65.4
57.1
147.4
78.8
65.4
57.1
LRA
345
191
173
120
446
247
223
164
506
280
253
176
690
382
345
276
690
382
345
276
UNIT
VOLTAGE
38AH DESIGNATION
5
2
6
1
5
2
6
1
094
104
06E-275/
250/299/06E-265/250/
265/265
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
187
342
414
518
187
342
414
518
254
418
508
632
254
418
508
632
396.0
209.1
182.0
160.9
396.8
205.9
195.1
168.0
500
250
225
200
450
250
225
200
COMPRESSOR
754.2
416.8
369.4
282.3
725.9
396.0
361.2
286.2
A1
RLA LRA
106.4 506
52.6 280
46.8 253
40.4 176
89.7 446
45.5 247
43.6 223
36.5 164
A2
B1
RLA LRA RLA LRA
67.9 345 147.4 690
34.6 191
78.8 382
34.6 173
65.4 345
28.8 120
57.1 276
67.9 345
89.7 446
34.6 191
45.5 247
34.6 173
43.6 223
28.8 120
36.5 164
B2
RLA LRA
89.7 446
45.5 247
43.6 223
36.5 164
VOLTAGE
DESIGNATION
5
2
6
1
5
2
6
1
COMPRESSOR
A1/A2
MODEL NO.
06E-275/
265
06E-299/
275
NAMEPLATE
V-Ph-Hz
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
SUPPLY
VOLTAGE*
POWER SUPPLY**
Min
Max
MCA
MOCP
ICF
187
342
414
518
187
342
414
518
254
418
508
632
254
418
508
632
246.9
126.9
114.3
100.6
327.2
174.5
147.4
132.2
350
175
150
125
450
250
200
175
573.8
315.2
280.8
218.0
685.6
382.2
334.8
253.5
COMPRESSOR
A1
RLA
106.4
52.6
46.8
40.4
147.4
78.8
65.4
57.1
A2
LRA
506
280
253
176
690
382
345
276
RLA
89.7
45.5
43.6
36.5
106.4
52.6
46.8
40.4
LRA
446
247
223
164
506
280
253
176
044
054
064
074
084
VOLTAGE
DESIGNATION
5
2
6
1
5
2
6
1
5
2
6
1
5
2
6
1
5
2
6
1
COMPRESSOR
MODEL
(A1/A2)
06E-250/250
06E-265/250
06E-275/265
06E-299/275
06E-299/299
NAMEPLATE
V-Ph-Hz
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
SUPPLY
VOLTAGE*
POWER SUPPLY
Min
Max
MCA
MOCP
ICF
187
342
414
518
187
342
414
518
187
342
414
518
187
342
414
518
187
342
414
518
254
418
508
632
254
418
508
632
254
418
508
632
254
418
508
632
254
418
508
632
177.0
93.5
90.1
78.4
204.3
107.1
101.3
88.0
246.4
126.9
114.3
100.6
327.2
174.5
147.4
132.2
368.2
200.7
166.0
148.9
225
125
110
100
250
150
125
110
350
175
150
125
450
250
200
175
500
250
225
200
434.7
241.2
218.6
162.4
456.5
252.1
227.6
170.1
573.8
315.2
280.8
218.0
685.6
382.2
334.8
253.5
870.0
484.2
426.8
353.5
COMPRESSOR
A1
RLA
67.9
34.6
34.6
28.8
89.7
45.5
43.6
36.5
106.4
52.6
46.8
40.4
147.4
78.8
65.4
57.1
147.4
78.8
65.4
57.1
A2
LRA
345
191
173
120
446
247
223
164
506
280
253
176
690
382
345
276
690
382
345
276
RLA
67.9
34.6
34.6
28.8
67.9
34.6
34.6
28.8
89.7
45.5
43.6
36.5
106.4
52.6
46.8
40.4
147.4
78.8
65.4
57.1
LRA
345
191
173
120
345
191
173
120
446
247
223
164
506
280
253
176
690
382
345
276
99
044
054
064
074
084
094
104
Modules
124A, 124B,
134A
Module
134B
Nameplate
V-Ph-Hz
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
380-3-60
460-3-60
575-3-60
CONTROL CIRCUIT
UNIT POWER
V-Ph-Hz
208/230-3-60
380-3-60
460-3-60
575-3-60
38AH
044-134
5
2
6
1
CONTROL POWER
V-Ph-Hz
Min
Max
115-1-60
103
127
230-1-60
207
253
115-1-60
103
127
115-1-60
103
127
AMPS
4.1
2.0
4.1
4.1
LEGEND
American Wire Gage
Full Load Amps
Maximum Instantaneous Current Flow During Starting
Indoor-Fan Contactor
Thousand Circular Mils
Liquid Line Solenoid
Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
Rated Load Amps
Underwriters Laboratories
*Units are suitable for use on electrical systems where voltage supplied to unit
terminals is within listed minimum to maximum limits.
All compressors are across-the-line start only.
**38AH124 and 134 units require a separate power supply for each unit module.
NOTES:
1. Maximum allowable phase imbalance:
Voltage 2%
Amps 10%
2. Maximum incoming wire size for terminal block is 500 kcmil.
3. Wiring for field power supply must be rated 75 C minimum. Use copper,
copper-clad aluminum, or aluminum conductors. Maximum incoming wire
size for each terminal block is 500 kcmil.
4. Terminal blocks TB3 and TB4 are for external field control connections. Control connections are to be class 1 wiring.
5. The maximum ICF during starting is defined as the point in the starting
sequence where the sum of the LRA for the starting compressor, plus the
total RLA for all running compressors, plus the total FLA for all running fan
motors is maximum.
6. Minimum circuit amps is used for sizing; complies with National Electrical
Code [NEC] section 430-24.
7. Maximum overcurrent protection is used for sizing disconnect; complies with
NEC Article 440-22.
100
VA
(Each Stage)
044-084
300
094
275
104
325
124
134
300
300
AMPS
VAC
2.5
1.3
2.29
1.15
2.70
1.35
2.50
2.50
120
240
120
240
120
240
120
120
38AH024-034 UNITS, 50 Hz
UNIT
38AH
024
028
034
VOLTAGE
RANGE*
NOMINAL
VOLTAGE
(V-Ph-Hz)
Min
Max
230-3-50
380/415-3-50
230-3-50
380/415-3-50
230-3-50
380/415-3-50
198
342
198
342
198
342
254
440
254
440
254
440
COMPRESSOR
RLA
Ckt 1
Ckt 2
39.3
39.3
18.0
18.0
43.6
43.6
22.1
22.1
43.6
63.6
22.1
30.0
LRA
Ckt 1
Ckt 2
128
128
99
99
143
143
114
114
143
200
114
120
LEGEND
FLA Full Load Amps
ICF
Maximum Instantaneous Current Flow During Starting
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
RLA Rated Load Amps
*Units are suitable for use on electrical systems where voltage supplied
to unit terminals is not below or above listed minimum and maximum.
All fans are protected by a single circuit breaker.
POWER SUPPLY
FLA
(ea)
Nominal
Hp
Nominal
kW
6.3
3.0
6.3
3.0
6.3
3.0
0.75
0.75
0.75
MCA
MOCP
ICF
101.0
46.5
110.7
55.7
135.7
65.6
125
60
150
70
175
90
268.8
204.0
298.8
234.0
355.8
240.0
NOTES:
1. MCA and MOCP values are calculated in accordance with NEC
(National Electrical Code) (U.S.A. standard), Article 440.
2. Motor FLA values are established in accordance with UL (Underwriters Laboratories) Standard 1995 (U.S.A. standard).
3. The maximum ICF during starting is defined as the point in the
starting sequence where the sum of the LRA for the starting compressor, plus the total RLA for all running compressors, plus the
total FLA for all running fan motors is maximum.
4. Minimum circuit amps complies with National Electrical Code
[NEC] Section 430-24) (U.S.A. Standard).
38AH044-084, 50 Hz
UNIT
38AH
VOLTAGE
DESIGNATION
COMPRESSOR
MODEL
(A/B DUAL-CIRCUIT)
(A1/A2 SINGLE-CIRCUIT)
NAMEPLATE
VOLTS-PH-Hz
8
9
9
9
9
9
06E-250/250
06E-250/250
06E-250/265
06E-265/275
06E-275/299
06E-299/299
230-3-50
380/415-3-50
380/415-3-50
380/415-3-50
380/415-3-50
380/415-3-50
044
054
064
074
084
SUPPLY
VOLTAGE*
POWER SUPPLY
COMPRESSOR
A
Min
Max
MCA
MOCP
ICF
198
348
342
342
342
342
254
440
440
440
440
440
179.0
90.7
101.9
114.9
148.2
166.8
225
100
125
150
200
225
296.7
219.6
269.6
335.6
403.8
428.4
RLA
67.9
34.6
34.6
43.6
46.8
65.4
B
LRA
207
173
173
223
280
345
RLA
67.9
34.6
43.6
46.8
65.4
65.4
LRA
207
173
223
280
345
345
38AH094,104, 50 Hz
SUPPLY
COMPRESSOR NAMEPLATE VOLTAGE*
UNIT
VOLTAGE
A1/A2/B1/B2
VOLTS-PH-Hz
38AH DESIGNATION
MODEL NO.
Min Max
094
104
06E-275/250/
299/
06E-265/250/
265/265
POWER SUPPLY
MCA
MOCP ICF
COMPRESSOR
A1
A2
B1
B2
RLA LRA RLA LRA RLA LRA RLA LRA
380/415-3-50
342
440
182.8
225
444 46.8
280
34.6
173
65.4
345
380/415-3-50
342
440
195.9
225
363 43.6
223
34.6
173
43.6
223
43.6
223
101
COMPRESSOR
A1/A2
MODEL NO.
NAMEPLATE
VOLTS-PH-Hz
06E-275/265
06E-299/275
VOLTAGE
DESIGNATION
124A
124B
134A
134B
SUPPLY
VOLTAGE*
POWER SUPPLY**
Min
Max
MCA
MOCP
ICF
380/415-3-50
342
440
114.9
150
380/415-3-50
342
440
148.2
200
FANS
UNIT/MODULE
38AH
044
054
064
074
084
094
104
124A
124B
134A
134B
COMPRESSOR
A1
A2
RLA
LRA
RLA
LRA
336
46.8
280
43.6
223
404
65.4
345
46.8
280
CONTROL CIRCUIT
6.4
380/415-3-50
9.2
38AH
044-134
8
9
UNIT POWER
V-Ph-Hz
230-3-50
380/415-3-50
CONTROL POWER
V-Ph-Hz
Min Max
230-1-50
207
253
230-1-50
207
253
AMPS
2.0
2.0
IFC
kcmil
LLS
LRA
MCA
MOCP
PW
RLA
*Units are suitable for use on electrical systems where voltage supplied
to unit terminals is within listed minimum to maximum limits.
Compressors are across-the-line start unless voltage designation
shows (PW).
**38AH124 and 134 units require a separate power supply for each unit
module.
NOTES:
1. Maximum allowable phase imbalance:
Voltage 2%
Amps 10%
2. Maximum incoming wire size for terminal block is 500 kcmil.
3. Wiring for field power supply must be rated 75 C minimum. Use
copper, copper-clad aluminum, or aluminum conductors. Maximum incoming wire size for each terminal block is 500 kcmil.
4. Terminal blocks TB3 and TB4 are for external field control connections. Control connections are to be class 1 wiring.
5. The maximum ICF during starting is defined as the point in the
starting sequence where the sum of the LRA for the starting compressor, plus the total RLA for all running compressors, plus the
total FLA for all running fan motors is maximum.
6. Minimum circuit amps used for sizing; complies with National Electrical Code [NEC] section 430-24, U.S.A.
102
7. Maximum Overcurrent Protection used for sizing disconnect; complies with NEC Article 440-22, U.S.A.
8. Field-supplied components (IFC, LLS-A, and LLS-B) must have a
maximum sealed coil rating of 30 va each or less (0.13 amp at
230 vac). Thermostats must have a minimum pilot duty rating as
follows:
38AH
VA
(Each Stage)
AMPS
CONTROL
CIRCUIT
VOLTAGE
044-084
094
104
124
134
300
275
325
300
300
1.30
1.15
1.35
1.30
1.30
240
11. Unit 38AH124 consists of Modules 124A and 124B. Unit 38AH134
consists of Modules 134A and 134B. Each module has a control
box.
12. All fans are protected by a single circuit breaker.
Controls
38AH024-034 operating sequences
38AH024-034 standard constant volume unit with
2-stage cooling thermostat Seven seconds after a
thermostat call for the first stage of cooling, compressor
no. 1 and the outdoor fans start. The no. 2 fan only starts
if the outdoor ambient temperature is above 70 F (21.1 C).
The oil-pressure switch and the low-pressure switch are
bypassed for the 1 and 21/2 minutes, respectively. If either
the low-pressure switch or oil pressure switch remain open
after the delay, the unit shuts down and goes into alarm
mode. The indoor-fan motor starts immediately whenever
there is a call for cooling. If a liquid line solenoid valve has
been installed (for refrigerant control during the off cycle),
then the solenoid valve for compressor no. 1 opens immediately upon a call for cooling.
On standard units, compressor no. 1 operates either fully loaded or at one step of unloading, depending on the
suction pressure, which is dependent on the evaporator
load conditions.
As the cooling demand increases, the thermostat calls
for the second stage of cooling. Within 7 seconds from a
call for the second stage of cooling, compressor no. 2
starts. The oil switch and low-pressure switch for circuit
no. 2 are bypassed during start-up.
As the cooling load is satisfied, the thermostat stops the
call for the second stage of cooling, which in turn deenergizes compressor no. 2, closes the no. 2 liquid line solenoid (if installed) and energizes the compressor no. 2
crankcase heater.
If the space temperature continues to decrease, then the
thermostat stops the call for the first stage of cooling,
which then deenergizes compressor no. 1 and the outdoor
fans, closes the no. 1 liquid line solenoid valve (if installed),
and energizes the compressor no. 1 crankcase heater.
The unit controls prevent both compressors from reenergizing within 3 minutes from a previous call for operation.
If the unit safeties trip during operation, refer to the
Start-Up, Installation and Service instructions.
NOTE: If the thermostat fan switch is in the auto position,
the indoor fan cycles on and off as the thermostat calls for
cooling (or heating). If the switch is in the continuous position, the fan runs when the outdoor unit is powered.
38AH024-034 optional variable air volume unit
with ModuPanel control The ModuPanel control
regulates up to 10 stages of cooling to maintain a leavingair temperature for variable air volume (VAV) applications.
When connected to one 38AH condensing unit, only
6 stages are used. See the tables on next page for unit
loading and compressor operating sequence.
When the timeclock connected to the panel closes, the
indoor-fan contactor is energized through a field-supplied
relay. (The relay must be a pilot-duty SPST relay with
115-v coil and 30 va maximum coil draw.) After the time
delays programmed into the ModuPanel control have
elapsed, and with the leaving air above the set point, the
stages of mechanical cooling are sequenced as follows:
1. Stage 1 starts compressor no. 1 with 2 banks of cylinders unloaded (1/3 loaded). Both unloader solenoids
are energized.
103
Controls (cont)
38AH UNIT LOADING SEQUENCE WITH MODUPANEL CONTROL
STAGE
NO. CYLINDERS
1
2
3
4
5
6
2
4
6
8
10
12
LOADED CYLINDERS
Compressor No. 1
Compressor No. 2
2
2
6
4
6
6
6
NO. CYLINDERS
1
2
3
4
5
6
7
8
9
10
2
4
6
8
10
12
14
18
20
24
6
2
6
4
6
6
6
6
6
6
6
6
6
6
6
Restart Manual reset of the 24-v control circuit is required if unit is shut down by any of the safety devices. Applicable devices include the high-pressure switch (HPS),
low-pressure switch (LPS), oil-pressure switch (OPS), and
compressor overtemperature protection (COTP) switch.
To restart the unit after the unit has been shut down, raise
the thermostat set point above the space temperature
(thereby removing the call for cooling) and then lower the
set point back to the desired setting.
If unit circuit breakers trip during unit shutdown, they
must be reset manually.
104
6
2
6
6
6
and the Time Guard control is initiated. Time Guard control prevents the compressor from restarting for 5 minutes
after the demand for cooling is satisfied.
Units 38AH094 and 104 If circuit A operation is insufficient for the cooling requirements, the thermostat second stage TC2 closes to bring circuit B on-line for cooling.
This circuit follows the same sequence of operation as the
lead circuit, except a 60-second time-delay relay (TDR) delays compressor start-up for 60 seconds after the call for
cooling.
Modules 124A, 124B, 134A, and 134B If compressor A1 is insufficient for the cooling requirements, the
thermostat second stage closes, which opens the liquid line
solenoid valve LLS-A2. Compressor A2 starts only after
D-D2 contacts in the timer close and the suction pressure
is sufficient to close the capacity control switches.
All units When the fan switch is set for automatic (AUTO) operation, the indoor-fan contactor (IFC) is cycled with
the lead compressor. If the fan switch is set for continuous
operation (CONT), the IFC is energized as long as the unit
power is on.
Restart after stoppage by safety control The highpressure switch and the oil pressure switch must be reset
manually by breaking the control power supply at any of
the following points: Control circuit fuse, fan motor circuit
breaker, or thermostat. Restart follows the Time Guard
control 5-minute delay. Stoppage by the low-pressure
switch results in a Time Guard control 5-minute delay, then
the unit attempts to restart.
The compressor motor overcurrent protectors are
manual-reset circuit breakers. A control circuit reset may
also be necessary.
105
Controls (cont)
CARRIER CONTROLS
DEBONAIR COMMERCIAL
PROGRAMMABLE THERMOSTAT
Carrier
Pm
a33-9191
COOL
AUTO
HEAT
a33-638tf
106
a38-7050.eps
CB
EQUIP
GND
IFC
LLSV
NEC
TB
LEGEND
Circuit Breaker
Equipment
Ground
Indoor Fan Contactor
Liquid Line Solenoid Valve
National Electrical Code
Terminal Block
Field Control Wiring
Factory Wiring
Field Power Wiring
(115 v)
509
208/230-3-60
460-3-60
575-3-60
380-3-60
UNIT (V-Ph-Hz)
230-1-60
115-1-60
(24 v)
NOTES:
1. CB4 protects TB2 circuit; CB3 protects TB3 circuits.
2. LLSV1 and LLSV2 are field supplied.
3. TB2 is 24 v and TB3 is 115 v.
107
IFC
1
FAN
COOL
1
CKT 1
TSTAT
COOL
2
CCS
1
CB3*
CB4
IFC
2
FAN
COOL
1
CKT 2
TSTAT
COOL
2
CCS
2
**
TB2
10 10
9
9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1
1
(24 v)
CB
CCS
IFC
LEGEND
Circuit Breaker
Capacity Control Solenoid
Indoor-Fan Contactor
Field Control Wiring
a38-7051
UNIT (V-Ph-Hz)
208/230-3-60
460-3-60
575-3-60
380-3-60
108
509
TB4
TB3
TSTAT
24 vac
ACCESSORY
RELAY
PACKAGE
CR1
VIO
CR2
BRN
IFR
RED
Y1
Y2
W1
IFC
LLS (SEE
-A1 NOTE)
LLS (SEE
-B1 NOTE)
YEL
W2
G
C
24V
IFR
CR
1
CR
2
4
X
CR
HD
IFC
IFR
LLS
R
TB
L1
L2
R
HD
LEGEND
Control Relay
Heating Device
Indoor-Fan Contactor
Indoor-Fan Relay
Liquid Line Solenoid
Heating Relay (field-supplied 24-v sealed
coil, 10 va maximum rating)
Terminal Block
Factory Wiring
Field Wiring
*To control heating device and provide automatic indoor-fan operation on heating.
NOTES:
1. Field-supplied liquid line solenoid valves installed at the evaporator are required on all units.
2. Internal single zone relay contacts are rated for 1 amp/24 vac.
3. TB3 and TB4 control voltages are as follows:
115 v for 208/230, 460, and 575 v units
230 v for 380/415 and 380 v units
200 v for 346 v units
509
109
a38-7074
110
ATS
C
CB
CH
CM
COMP
COTP
CR
EQUIP
FC
FM
FR
FU
GND
HPS
LLSV
LPS
NEC
LEGEND
OPS
Air Temperature Switch
PL
Contactor, Compressor
TB
Circuit Breaker
TRAN
Crankcase Heater
U
Control Module
VAV
Compressor
Compressor Overtemperature
Protection
Control Relay
Equipment
Fan Contactor
Fan Motor
Fan Relay
Fuseblock
Ground
High-Pressure Switch
Liquid Line SolenoidValve
Low-Pressure Switch
National Electronic Code
a38-7075
ATS
C
CB
CH
CM
COMP
COTP
CR
EQUIP
FC
FM
FR
FU
GND
HPS
LLSV
LPS
NEC
LEGEND
Air Temperature Switch
Contactor, Compressor
Circuit Breaker
Crankcase Heater
Control Module
Compressor
Compressor Overtemperature
Protection
Control Relay
Equipment
Fan Contactor
Fan Motor
Fan Relay
Fuseblock
Ground
High-Pressure Switch
Liquid Line SolenoidValve
Low-Pressure Switch
National Electrical Code (U.S.A. Standard)
OPS
TB
TRAN
U
VAV
111
a38-7076
LEGEND
AHMS
C
CB
CH
COMP
CR
DU
EQUIP
FC
FCB
FCPS
FIOP
FM
GND
HPS
IFC
kcmil
LLS
LPR
LPS
MMSN
NEC
OPR
OPS
PL
PR
PRI
112
PW
SDR
SEC
TB
TDR
TM
TR
TRAN
U
VAV
XL
NOTES:
1. 208/230V units are factory wired for 230-v power supply. For 208-v power
Part-Wind Start
supply, connect yellow wire to terminal marked H2. For 460-v power supply,
Solenoid Drop Relay
connect yellow wire to terminal marked H4. For 575-v power supply, connect
Secondary
yellow wire to terminal marked H2.
Terminal Block
2. For units with 115-v controls, connect black wire to the white lead of TRAN2.
Time-Delay Relay
For units with 230-v controls, connect black wire to the red lead of TRAN2. For
Timer Motor
units with 200-v controls, connect black wire to the blue lead of TRAN2.
Timer Relay
3. Terminal blocks TB3, TBX1, and TBX2 are for external field control connecTransformer
tions. Control connections are to be class 1 wiring.
Unloader
4. Field-supplied components (IFC, LLS-A1 and LLS-A2) must have a maximum
Variable Air Volume
sealed coil rating of 30 va each (0.25 amp at 120 vac, 0.13 amp at 230 vac).
Across-the-Line Start
Thermostats must have a minimum pilot duty rating of 120 va (1 amp at
120 vac). The fan switch must have a minimum pilot duty rating of 30 va
Terminal Block Connection
(0.25 amp at 120 vac, 0.13 amp at 230 vac). On VAV units, the AHMS
IFC_AUX and control staging contacts must have a minimum pilot duty rating
Marked Terminal
of 120 VA (1 amp at 120 vac).
5. Wiring for field power supply must be rated 75 C minimum. Use copper, copper-clad aluminum, or aluminum conductors. Maximum incoming wire size for
Unmarked Terminal
each terminal block is 500 kcmil.
6. Replacement of factory wires must be with type 105 C wire or its equivalent.
Unmarked Splice
7. Factory wiring is in accordance with National Electrical Code (NEC). Field
modifications or additions must be in compliance with all applicable codes.
Marked Wire
8. Compressors and fan motors are thermally protected. Three phase motors
are protected against primary single phasing conditions.
Factory Wiring
9. Line numbers on the left side of the label diagrams indicate the contact number. The numbers on the right side of the label diagrams match the contacts
Field Wiring
with their corresponding coils. A plain number indicates normally open conIndicates Common Potential;
tacts. An underlined number indicates normally closed contacts.
Does Not Represent Wiring 10. Control circuit power available for field-installed accessories.
a38-3845ef
LEGEND
AHMS
ATS
C
CB
CCPR
CCPS
CH
COMP
CR
DU
EQUIP
FC
FCB
FCPS
FIOP
FM
GND
HPS
IFC
kcmil
LLS
LPR
LPS
MMSN
NEC
OPR
OPS
PL
PW
PR
PRI
SDR
SEC
TB
TDR
TM
TR
TRAN
U
VAV
XL
Part-Wind Start
Power Relay
Primary
Solenoid Drop Relay
Secondary
Terminal Block
Time-Delay Relay
Timer Motor
Timer Relay
Transformer
Unloader
Variable Air Volume
Across-the-Line Start
Terminal Block Connection
Marked Terminal
Unmarked Terminal
Unmarked Splice
Marked Wire
Factory Wiring
Field Wiring
Indicates Common Potential;
Does Not Represent Wiring
NOTES:
1. 208/230V units are factory wired for 230-v power supply. For 208-v power
supply, connect yellow wire to terminal marked H2. For 460-v power supply,
connect yellow wire to terminal marked H4. For 575-v power supply, connect
yellow wire to terminal marked H2.
2. For units with 115-v controls, connect black wire to the white lead of TRAN2.
For units with 230-v controls, connect black wire to the red lead of TRAN2. For
units with 200-v controls, connect black wire to the blue lead of TRAN2.
3. Terminal blocks TB3, TBX1, and TBX2 are for external field control connections. Control connections are to be class 1 wiring.
4. Field-supplied components (IFC, LLS-A1 and LLS-A2) must have a maximum
sealed coil rating of 30 va each (0.25 amp at 120 vac, 0.13 amp at 230 vac).
Thermostats must have a minimum pilot duty rating of 120 va (1 amp at
120 vac). The fan switch must have a minimum pilot duty rating of 30 va
(0.25 amp at 120 vac, 0.13 amp at 230 vac). On VAV units, the AHMS
IFC_AUX and control staging contacts must have a minimum pilot duty rating
of 120 VA (1 amp at 120 vac).
5. Wiring for field power supply must be rated 75 C minimum. Use copper,
copper-clad aluminum, or aluminum conductors. Maximum incoming wire size
for each terminal block is 500 kcmil.
6. Replacement of factory wires must be with type 105 C wire or its equivalent.
7. Factory wiring is in accordance with National Electrical Code (NEC). Field
modifications or additions must be in compliance with all applicable codes.
8. Compressors and fan motors are thermally protected. Three phase motors
are protected against primary single phasing conditions.
9. Line numbers on the left side of the label diagrams indicate the contact number. The numbers on the right side of the label diagrams match the contacts
with their corresponding coils. A plain number indicates normally open contacts. An underlined number indicates normally closed contacts.
10. Control circuit power available for field-installed accessories.
113
OPR
OPS
PL
PR
PRI
114
CONTROL
VOLTAGE
TRAN1
CONNECTION
TRAN2
CONNECTION
115
115
115
115
230
YEL to H2
YEL to H3
YEL to H4
YEL to H2
N/A
230
200
230
N/A
N/A
N/A
LEGEND
PW
SDR
SEC
TB
TDR
TM
TR
TRAN
U
VAV
XL
Part-Wind Start
Solenoid Drop Relay
Secondary
Terminal Block
Time-Delay Relay
Timer Motor
Timer Relay
Transformer
Unloader
Variable Air Volume
Across-the-Line Start
Terminal Block Connection
Marked Terminal
Unmarked Terminal
Unmarked Splice
Marked Wire
Factory Wiring
Field Wiring
Indicates Common Potential;
Does Not Represent Wiring
a38-7077
NOTES:
1. For units with 115-v controls, connect black wire to the white lead of TRAN2. For
units with 230-v controls, connect black wire to the red lead of TRAN2. For units with
200-v controls, connect black wire to the blue lead of TRAN2.
2. Terminal blocks TB3, TB4, TBX1, and TBX2 are for external field control connections. Control connections are to be class 1 wiring.
3. Field-supplied components (IFC, LLS-A1 and LLS-A2) must have a maximum sealed
coil rating of 30 va each (0.25 amp at 120 vac, 0.13 amp at 230 vac). Thermostats
must have a minimum pilot duty rating of 120 va (1 amp at 120 vac). The fan switch
must have a minimum pilot duty rating of 30 va (0.25 amp at 120 vac, 0.13 amp at
230 vac). On VAV units, the AHMS IFC_AUX and control staging contacts must have
a minimum pilot duty rating of 120 VA (1 amp at 120 vac).
4. Wiring for field power supply must be rated 75 C minimum. Use copper, copper-clad
aluminum, or aluminum conductors. Maximum incoming wire size for each terminal
block is 500 kcmil.
5. Replacement of factory wires must be with type 105 C wire or its equivalent.
6. Factory wiring is in accordance with NEC (U.S.A. Standard). Field modifications or
additions must be in compliance with all applicable codes.
7. Compressors and fan motors are thermally protected. The 3-phase motors are protected against primary single-phasing conditions.
8. Line numbers on the left side of the label diagrams indicate the contact number. The
numbers on the right side of the label diagrams match the contacts with their corresponding coils. A plain number indicates normally open contacts. An underlined
number indicates normally closed contacts.
9. Control circuit power available for field-installed accessories:
Standard Unit
094 165 VA
104 60 VA
124 120 VA
134 120 VA
VAV Unit
094 75 VA
104 0 VA
124 120 VA
134 120 VA
a38-6706tf.tif
CONTROL
VOLTAGE
TRAN1
CONNECTION
TRAN2
CONNECTION
115
115
115
115
230
YEL to H2
YEL to H3
YEL to H4
YEL to H2
N/A
230
200
230
N/A
N/A
N/A
LEGEND
AHMS
ATS
C
CB
CCPR
CCPS
CH
COMP
CR
DU
EQUIP
FC
FCB
FCPS
FIOP
FM
GND
HPS
IFC
kcmil
LLS
LPR
LPS
MMSN
NEC
OPR
OPS
PL
PW
PR
PRI
SDR
SEC
TB
TDR
TM
TR
TRAN
U
VAV
XL
Power Relay
Primary
Solenoid Drop Relay
Secondary
Terminal Block
Time-Delay Relay
Timer Motor
Timer Relay
Transformer
Unloader
Variable Air Volume
Across-the-Line Start
Terminal Block Connection
Marked Terminal
Unmarked Terminal
Unmarked Splice
Marked Wire
Factory Wiring
Field Wiring
Indicates Common Potential;
Does Not Represent Wiring
NOTES:
1. For units with 115-v controls, connect black wire to the white lead of TRAN2. For
units with 230-v controls, connect black wire to the red lead of TRAN2. For units with
200-v controls, connect black wire to the blue lead of TRAN2.
2. Terminal blocks TB3, TB4, TBX1, and TBX2 are for external field control connections. Control connections are to be class 1 wiring.
3. Field-supplied components (IFC, LLS-A1 and LLS-A2) must have a maximum sealed
coil rating of 30 va each (0.25 amp at 120 vac, 0.13 amp at 230 vac). Thermostats
must have a minimum pilot duty rating of 120 va (1 amp at 120 vac). The fan switch
must have a minimum pilot duty rating of 30 va (0.25 amp at 120 vac, 0.13 amp at
230 vac). On VAV units, the AHMS IFC_AUX and control staging contacts must have
a minimum pilot duty rating of 120 VA (1 amp at 120 vac).
4. Wiring for field power supply must be rated 75 C minimum. Use copper, copper-clad
aluminum, or aluminum conductors. Maximum incoming wire size for each terminal
block is 500 kcmil.
5. Replacement of factory wires must be with type 105 C wire or its equivalent.
6. Factory wiring is in accordance with NEC (U.S.A. Standard). Field modifications or
additions must be in compliance with all applicable codes.
7. Compressors and fan motors are thermally protected. The 3-phase motors are protected against primary single-phasing conditions.
8. Line numbers on the left side of the label diagrams indicate the contact number. The
numbers on the right side of the label diagrams match the contacts with their corresponding coils. A plain number indicates normally open contacts. An underlined
number indicates normally closed contacts.
9. Control circuit power available for field-installed accessories:
Standard Unit
094 165 VA
104 60 VA
124 120 VA
134 120 VA
VAV Unit
094 75 VA
104 0 VA
124 120 VA
134 120 VA
115
Application data
Installation
Select equipment to match or to be slightly less than peak
load. This provides better humidity control, less unit
cycling, and less part-load operation.
When selecting vapor line sizes, oil return must be evaluated, particularly at part-load conditions.
The indoor fan must always be operating when outdoor
unit is operating.
IMPORTANT: When application is in a VAV (variable air
volume) system, total building load is not the sum of the
individual peak loads. If individual peak loads are
summed, the equipment tends to be oversized for the
load.
To minimize return-air temperature extremes, use the
equipment room as a return-air plenum when applying
VVT (variable volume and temperature) systems with
supply-to-return air recycle as used with VVT control
systems.
Ductwork should be sized according to unit size, not
building load.
To minimize the possibility of air recirculation, avoid the
use of concentric supply/return grilles.
Indoor equipment should be selected at no less than
300 cfm/ton (40 L/s per kW).
Do NOT bury refrigerant piping underground.
IMPORTANT: Condensing units applied in VVT or VAV
systems must have field-supplied and installed accumulators. Order part number KH--73LZ-001 from Service
Parts.
OPERATING LIMITS
Maximum Outdoor Ambient
Minimum Outdoor Ambient
115 F (46 C)
See Minimum Outdoor-Air
Operating Temperature table,
pages 119-121.
55 F (12.8 C)
95 F (35 C)
20 to 50 F (-6.6 to 10.0 C)
275 F (135 C)
60 F (15.6 C)
Operating limits
Maximum outdoor ambient . . . . . . . 60 Hz, 115 F (46 C)
. . . . . . . . . . . . . . . . . . . . . . . . .50 Hz, 125 F (57.7 C)
Minimum outdoor ambient . . . . . . . . . . . . . . . . . . . . . .
Refer to Minimum Outdoor-Air Operating Temperature
table, pages 119-121.
Minimum return-air temperature . . . . . . . . 55 F (12.8 C)
Maximum return-air temperature . . . . . . . . . .95 F (35 C)
Range of acceptable saturation
suction temperature. . . . . . . 20 to 50 F (6.7 to 10 C)
116
E-coated coils
E-coated aluminum-fin coils have a flexible and durable
epoxy coating uniformly applied to all coil surfaces. Unlike
brittle phenolic dip and bake coatings, E-coat provides
superior protection with unmatched flexibility, edge coverage, metal adhesion, thermal performance, and most
importantly, corrosion resistance.
E-coated coils provide this protection since all coil surfaces are completely encapsulated from environmental
contamination. This coating is especially suitable in industrial environments.
E-coated copper-fin coils have the same flexible and
durable epoxy coating as E-coated aluminum-fin coils.
However, this option combines the natural salt and
environmental resistance of all-copper construction with
high levels of corrosion protection. This coating is recommended for harsh combinations of coastal and industrial
environments.
LIQUID LINE DATA (60 Hz), 38AH044-134 UNITS
UNIT
38AH
044
054
064
074
084
094
104
124
134
MAXIMUM
ALLOWABLE
LIQUID LIFT
(ft)
69
75
75
45
75
55
50
75
45
(m)
21
23
23
14
23
17
15
23
14
LIQUID LINE
Max Allowable
Max Allowable
Pressure Drop
Temp Loss
(psi)
(kPa)
(F)
(C)
48.3
1.1
MAXIMUM
ALLOWABLE
LIQUID LIFT
m
17.5
23.0
19.8
11.4
23.0
14.0
12.8
19.8
11.4
044
054
064
074
084
094
104
124
134
ft
57.5
75.0
65.0
37.5
75.0
46.0
42.0
65.0
37.5
LIQUID LINE
Max Allowable
Max Allowable
Pressure Drop
Temp Loss
kPa
Psi
C
F
48.3
1.1
NOTE: Values shown are for units operating at 7.2 C (45 F) saturated
suction at condensing unit and 35 C (95 F) entering outdoor air.
CAPACITY/STAGE (%)
Optional
Single-Circuit Units
100, 83, 50, 33
Standard Units
CAPACITY/STAGE (%)
Standard
Optional
Dual-Circuit Units
Single-Circuit Units
100, 83, 67, 50, 33, 17
NOTES:
1. Capacities are based on 45 F (7.2 C) saturated suction temperature
and 95 F (35 C) outdoor-air temperature.
2. Single-circuit option available for sizes 044-084 only.
117
024
028
034
044
054
064
074
084
QUANTITY OF LOADED
COMPRESSOR CYLINDERS
Ckt A
6
4
2
6
4
2
6
4
2
6
4
2
6
4
2
6
4
2
4
2
4
2
4
2
2
4
2
6
4
2
6
4
2
6
4
2
6
4
2
6
4
2
6
4
2
Ckt B
6
6
6
0
0
0
6
6
6
0
0
0
6
6
6
0
0
0
4
4
0
0
6
6
4
0
0
6
6
6
0
0
0
6
6
6
0
0
0
6
6
6
0
0
0
Total
12
10
8
6
4
2
12
10
8
6
4
2
12
10
8
6
4
2
8
6
4
2
10
8
6*
4
2
12
10
8*
6
4
2*
12
10
8*
6
4
2*
12
10
8*
6
4
2*
SYSTEM
CAPACITY
(%)
100
83
67*
50
33
17*
100
83
67*
50
33
17*
100
85
71*
43
28
14*
100
75
50
25
100
79
58*
42
21
100
84
69*
48
32
16*
100
86
71*
43
29
14*
100
83
67*
50
33
17*
118
11.7
53
28.9
-20
10
53
28.9
-20
9.4
53
28.9
-20
10.0
50
28.9
20
8.9
48
28.9
20
3.9
39
28.9
20
-0.6
31
28.9
20
-6.7
20
28.9
20
044
054
064
074
084
QUANTITY OF LOADED
CYLINDERS
8
6
4
2
10
8
6*
6
4
12
10
8*
6
4
2*
12
10
8*
6
4
2*
12
10
8*
6
4
2*
SYSTEM
CAPACITY
(%)
100
75
50
25
100
80
61*
56
37
100
82
64*
55
36
18*
100
81
62*
57
38
19*
100
83
67*
50
33
17*
47
28.9
20
5.0
41
28.9
20
3.3
38
28.9
20
5.6
22
28.9
20
6.7
20
28.9
20
119
094
104
124
134
Ckt A
10
10
10
10
8
6
4
10
10
10
10
10
10
10
8
6
4
2
12
12
12
12
12
12
12
10
8*
6
4
2*
12
12
12
12
12
12
12
10
8
6
4
2*
Ckt B
6
4
2*
0
0
0
0
12
10
8
6
4
2
0
0
0
0
0
12
10
8
6
4
2
0
0
0
0
0
0
12
10
8
6
4
2
0
0
0
0
0
0
Total
16
14
12
10
8
6
4
22
20
18
16
14
12
10
8
6
4
2
24
22
20
18
16
14
12
10
8
6
4
2
24
22
20
18
16
14
12
10
8
6
4
2
100
85
70*
55
44
33
22
100
91
82
74
65
56
47
38
26
17
9
100
91
82*
77
68
59
50
41
32*
27
18
9*
100
90
79*
76
66
56
45
37
28*
25
16
8*
120
with Motormaster V
Control
C
13.9
3.9
25
28.9
20
10.0
14
15.0
28.9
20
3.3
38
3.3
38
28.9
20
3.3
38
5.6
22
28.9
20
NOTES:
1. Temperatures calculated with the minimum number of fans operating per circuit.
2. For 38AH124 and 134 units, circuit A is Module 38AH124A or
134A. Circuit B is Module 38AH124B or 134B.
3. Minimum outdoor-air operating temperature is based on 32 C
(90 F) saturated condensing temperature and 100% capacity.
E-coated coils
E-coated aluminum-fin coils have a flexible and durable epoxy coating uniformly applied to all coil surfaces.
Unlike brittle phenolic dip and bake coatings, E-coating
provides superior protection with unmatched flexibility,
edge coverage, metal adhesion, thermal performance, and
most importantly, corrosion resistance.
E-coated coils provide this protection since all coil surfaces are completely encapsulated from environmental
contamination. This coating is especially suitable in industrial environments.
E-coated copper-fin coils have the same flexible and
durable epoxy coating as E-coated aluminum-fin coils.
However, this option combines the natural salt and
environmental resistance of all-copper construction with
high levels of corrosion protection. This coating is recommended in harsh combinations of coastal and industrial
environments.
a38-4149tf
LEGEND
Suction Riser
without Trap
Suction Riser
with Trap
Suction Line to
Condensing Unit
Pipe Diameter to be
Same Size as Riser A
(0.8 m)
(0.8 m)
(1.8 m)
028-034
044-134
DIMENSIONS, Ft (m)
A
B
4 (1.2)
4 (1.2)
6 (2.0)
5 (1.5)
a38-7066
121
UNIT 38AH
L
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
024
028
034
044
054
064
074
084
L
S
VAV
1/
2
1/
2
1/
2
1/
2
1/
2
1/
2
5/
8
5/
8
5/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
25-50
(7.6-15.2)
S
11/8
11/8
11/8
11/8
11/8
13/8
15/8
15/8
15/8
15/8
15/8
21/8
21/8
21/8
21/8
21/8
L
5/
8
5/
8
5/
8
5/
8
5/
8
5/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
11/8
11/8
11/8
LEGEND
Liquid Line
Suction Line
Variable Air Volume
*Double suction riser required on units with field installed unloader on circuit B compressor if condensing unit is elevated above evaporator.
Double suction riser required on units with field installed unloader on circuit A compressor if condensing unit is elevated above evaporator.
**Double suction riser required if evaporator is below condensing unit and compressor
has one or more unloader(s).
NOTES:
1. Addition of 2 unloaders to circuit B compressor is not recommended.
2. Piping sizes are based on unit operation above 40 F (4.4 C) saturated suction
temperature (SST). When operating below 40 F (4.4 C), refer to Carrier System
Design Manual, E20-II piping design program, or ASHRAE Handbook to select
proper line sizes.
3. Pipe sizes are based on the total linear length shown for each column, plus a 50%
allowance for fittings.
4. Suction and liquid line sizing is based on pressure drop equivalent to 2 F (1.1 C)
at nominal rating conditions. Higher pressure drop design criteria may allow
150-200
(45.7-61.0)
L
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
11/8
11/8
11/8
11/8
13/8
13/8
13/8
S
15/8*
15/8
21/8**
21/8**
21/8**
21/8
21/8
21/8
21/8
25/8*
25/8
25/8
25/8
25/8
25/8
25/8
selection of smaller pipe sizes, but at a penalty of decreased system capacity and
efficiency.
5. Double suction risers may be required if condensing unit is elevated above the
evaporator. See footnotes and double suction riser table below.
6. Refer to Carrier System Design Manual or to E20-II design programs for further
information on selecting pipe sizes for split systems.
7. All pipe sizes are OD inches. Equivalent sizes in millimeters follow:
in.
5/
8
7/
8
11/8
13/8
15/8
21/8
25/8
31/8
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
UNIT 38AH
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
024
028
034
054
064
074
084
Pipe A
Pipe B
Pipe C
11/8
50-75
(15.2-22.9)
B
13/8
15/8
13/8
15/8
21/8
15/8
21/8
25/8
15/8
21/8
25/8
15/8
21/8
25/8
LEGEND
Not Required
Suction Riser Without Trap
Suction Riser With Trap
Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need for
double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a
50% allowance for fittings.
3. Suction and liquid line sizing is based on pressure drop equivalent to 2 F (1.1 C)
at nominal rating conditions. Higher design pressure drop criteria may allow selection of smaller pipe sizes but at a penalty of decreased system capacity and
efficiency.
4. Refer to Carrier System Design Manual or to E20-II design programs for further
information on selecting pipe sizes for split systems.
122
A
11/8
13/8
13/8
13/8
13/8
13/8
15/8
15/8
15/8
15/8
150-200
(45.7-61.0)
B
13/8
13/8
15/8
15/8
15/8
15/8
21/8
21/8
21/8
21/8
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
C
15/8
15/8
21/8
21/8
21/8
21/8
25/8
25/8
25/8
25/8
044
7/
S
2 1 /8
054
7/
15-25
(4.6-7.6)
UNIT 38AH
L
150-200
(45.7-61.0)
L
S
1 3 /8
31/8***
2 1 /8
1 1 /8
25/8***
1 1 /8
25/8***
1 1 /8
25/8***
1 3 /8
31/8***
1 3 /8
31/8***
064;
Modules 124A,
124B,134A
1 1 /8
2 1 /8
1 1 /8
25/8***
1 1 /8
25/8***
1 3 /8
31/8***
1 3 /8
31/8***
1 3 /8
31/8***
074;
Module 134B
1 1 /8
2 1 /8
1 1 /8
25/8***
1 3 /8
31/8***
1 3 /8
31/8***
1 3 /8
31/8***
1 5 /8
35/8***
084
1 1 /8
25/8**
1 1 /8
25/8**
1 3 /8
31/8**
1 3 /8
31/8**
1 5 /8
35/8**
1 5 /8
35/8***
CV
L
S
VAV
LEGEND
Constant Volume
Liquid Line
Suction Line
Variable Air Volume
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
92.1
5/
8
7/
8
1
1 /8
3
1 /8
1 5 /8
2 1 /8
2 5 /8
3 1 /8
3 5 /8
150-200
(45.7-61.0)
A
B
C
1 5 /8
2 5 /8
3 1 /8
044
15-50
(4.6-15.2)
B
054
1 5 /8
2 1 /8
25/ 8
15/ 8
21/ 8
2 5 /8
1 5 /8
2 1 /8
2 5 /8
1 5 /8
2 5 /8
3 1 /8
1 5 /8
2 5 /8
3 1 /8
064
Modules 124A,
124B,134A
1 5 /8
2 1 /8
25/ 8
15/ 8
21/ 8
2 5 /8
1 5 /8
2 5 /8
3 1 /8
1 5 /8
2 5 /8
3 1 /8
1 5 /8
2 5 /8
3 1 /8
074;
Module 134B
1 5 /8
2 1 /8
25/ 8
15/ 8
25/ 8
3 1 /8
1 5 /8
2 5 /8
3 1 /8
1 5 /8
2 5 /8
3 1 /8
2 1 /8
3 1 /8
3 5 /8
084
1 5 /8
2 1 /8
25/ 8
15/ 8
25/ 8
3 1 /8
1 5 /8
2 5 /8
3 1 /8
2 1 /8
3 1 /8
3 5 /8
2 1 /8
3 1 /8
3 5 /8
UNIT 38AH
Pipe A
Pipe B
Pipe C
LEGEND
Not Required
Suction Riser Without Trap
Suction Riser With Trap
Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction line sizing is based on 2 F (1.1 C) pressure drop at nominal
rating conditions. Liquid line sizing is based on 2 F (1.1 C) pressure
drop. Higher design pressure drop criteria may allow selection of
smaller pipe sizes but at a penalty of decreased system capacity and
efficiency.
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
92.1
123
UNIT
38AH
094
Ckt A
094
Ckt B
104
Ckt A
104
Ckt B
CV
L
S
VAV
15-25
(4.6-7.6)
L
S
150-200
(45.7-61.0)
L
S
7/
2 1 /8
1 1 /8
2 1 /8
1 1 /8
25/8**
1 1 /8
25/8**
1 3 /8
25/8**
1 3 /8
31/8***
7/
2 1 /8
7/
2 1 /8
1 1 /8
21/8**
1 1 /8
25/8**
1 1 /8
25/8**
1 3 /8
25/8**
7/
2 1 /8
7/
2 1 /8
1 1 /8
2 5 /8
1 1 /8
2 5 /8
1 1 /8
2 5 /8
1 3 /8
31/8***
7/
2 1 /8
1 1 /8
2 1 /8
1 1 /8
25/8**
1 1 /8
25/8**
1 3 /8
31/8***
13/8
31/8***
LEGEND
Constant Volume
Liquid Line
Suction Line
Variable Air Volume
*Standard CV unit with 1 unloader on circuit A and 1 unloader on circuit B; double suction riser required.
Units with factory-installed VAV option or field-installed accessory
unloader 2 unloaders on circuit A, and 1 unloader on circuit B;
double suction riser required.
**Units with 2 field-installed unloaders on circuit A and 2 on circuit B;
double suction riser required.
NOTES:
1. It is possible to install 2 unloaders on circuit B, but not
recommended.
2. Double risers may be required if condensing unit is elevated above
evaporator. See footnotes and double suction riser table below.
3. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
in.
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
5/
8
7/
8
1
1 /8
3
1 /8
1 5 /8
2 1 /8
2 5 /8
3 1 /8
UNIT
38AH
50-75
(15.2-22.9)
75-100
(22.9-30.5)
100-150
(30.5-45.7)
150-200
(45.7-61.0)
094
Ckt A
1 5 /8
2 1 /8
2 5 /8
1 5 /8
2 1 /8
25/ 8
1 5 /8
2 1 /8
2 5 /8
1 5 /8
2 5 /8
3 1 /8
094
Ckt B
1 3 /8
1 5 /8
2 1 /8
1 5 /8
2 1 /8
25/ 8
1 5 /8
2 1 /8
2 5 /8
1 5 /8
2 1 /8
2 5 /8
104
Ckt A
1 3 /8
2 1 /8
2 5 /8
1 3 /8
2 1 /8
25/ 8
1 3 /8
2 1 /8
2 5 /8
1 5 /8
2 5 /8
3 1 /8
104
Ckt B
1 3 /8
2 1 /8
2 5 /8
1 3 /8
2 1 /8
25/ 8
1 3 /8
2 5 /8
3 1 /8
1 5 /8
2 5 /8
3 1 /8
Pipe A
Pipe B
Pipe C
LEGEND
Not Required
Suction Riser Without Trap
Suction Riser With Trap
Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction line sizing is based on 2 F (1.1 C) pressure drop at nominal
rating conditions. Liquid line sizing is based on 2 F (1.1 C) pressure
drop. Higher design pressure drop criteria may allow selection of
smaller pipe sizes but at a penalty of decreased system capacity and
efficiency.
124
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
0-25
(0-7.6)
L
024
028
034
044
054
064
074
084
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
1/
2
1/
2
1/
2
1/
2
1/
2
1/
2
5/
8
5/
8
5/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
S
11/8
11/8
11/8
11/8
11/8
13/8
13/8
13/8
13/8
15/8
15/8
15/8
15/8
21/8
21/8
21/8
5/
8
5/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
15/8
15/8
15/8
15/8
15/8
21/8
21/8
21/8
21/8
21/8
5/
8
5/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
11/8
11/8
11/8
LEGEND
L Liquid Line
S Suction Line
*Double suction riser required on units with field-installed unloader on circuit B
compressor if condensing unit is elevated above evaporator.
Double suction riser required on units with field-installed unloader on circuit A
compressor if condensing unit is elevated above evaporator.
**Double suction riser required on all unit configurations if condensing unit is elevated above evaporator.
NOTES:
1. Addition of 2 unloaders to circuit B compressor is not recommended.
2. Piping sizes are based on unit operation above 40 F (4.4 C) saturated suction temperature (SST). When operating below 40 F (4.4 C), refer to Carrier
System Design Manual, E20-II piping design program, or ASHRAE Handbook to select proper line sizes.
3. Pipe sizes are based on the total linear length shown for each column, plus
a 50% allowance for fittings.
13/8
15/8
15/8
15/8
15/8
21/8
21/8
21/8
21/8
21/8
21/8
21/8
5/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
11/8
11/8
11/8
13/8
15/8
21/8
21/8
21/8
21/8
21/8
21/8
21/8
25/8
25/8
25/8
7/
8
7/
8
7/
8
7/
8
7/
8
11/8
11/8
11/8
11/8
11/8
11/8
11/8
L
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
11/8
11/8
11/8
11/8
11/8
11/8
11/8
15/8*
21/8*
21/8
21/8
21/8
21/8
21/8
25/8*
25/8
25/8
25/8
25/8
150-200
(45.7-61.0)
S
15/8*
15/8*
15/8*
15/8*
15/8*
21/8*
21/8
21/8
21/8
25/8*
25/8**
25/8*
25/8
25/8
25/8
25/8
mm
12.7
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
UNIT
38AH
024
028
034
054
064
074
084
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
13/8
50-75
(15.2-22.9)
B
15/8
21/8
11/8
13/8
13/8
15/8
11/8
13/8
15/8
11/8
13/8
15/8
13/8
15/8
11/8
13/8
15/8
21/8
13/8
15/8
21/8
15/8
15/8
21/8
15/8
21/8
25/8
15/8
21/8
25/8
15/8
21/8
25/8
15/8
21/8
25/8
LEGEND
Not Required
Pipe A Suction Riser Without Trap
Pipe B Suction Riser With Trap
Pipe C Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need
for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus
a 50% allowance for fittings.
3. Suction and liquid line sizing is based on pressure drop equivalent to 2 F
(1.1 C) at nominal rating conditions. Higher design pressure drop criteria
may allow selection of smaller pipe sizes but at a penalty of decreased system capacity and efficiency.
A
11/8
13/8
11/8
11/8
11/8
13/8
15/8
15/8
15/8
15/8
15/8
150-200
(45.7-61.0)
B
13/8
13/8
13/8
13/8
13/8
15/8
21/8
21/8
21/8
21/8
21/8
C
15/8
15/8
15/8
15/8
15/8
21/8
25/8
25/8
25/8
25/8
25/8
4. Refer to Carrier System Design Manual or to E20-II design programs for further information on selecting pipe sizes for split systems.
5. All pipe sizes are OD inches. Equivalent sizes in millimeters follows:
in.
5/
8
7/
8
11/8
13/8
15/8
21/8
25/8
31/8
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
125
15-20
(4.6-6.1)
L
S
7/
2 1 /8
8
7/
2 1 /8
8
150-200
(45.7-61.0)
L
S
1 3 /8
2 5 /8 *
1 3 /8
3 1 /8 *
7/
2 1 /8
1 1 /8
2 5 /8
1 1 /8
2 5 /8
11/ 8
2 5 /8
1 3 /8
3 1 /8 *
1 3 /8
3 1 /8 *
7/
2 1 /8
1 1 /8
2 5 /8
1 1 /8
2 5 /8
11/ 8
3 1 /8 *
1 3 /8
3 1 /8 *
1 3 /8
3 1 /8 *
2 1 /8
1 1 /8
2 5 /8
1 3 /8
3 1 /8 *
11/ 8
3 1 /8 *
1 3 /8
3 1 /8 *
1 5 /8
3 5 /8 *
1 1 /8
LEGEND
CV Constant Volume
L
Liquid Line
S
Suction Line
VAV Variable Air Volume
*Double suction riser required on all units configurations if condensing
unit is elevated above evaporator.
Double suction riser required on units with factory installed VAV
option or CV units with additional field installed unloader on circuit A1
(lead) compressor if condensing unit is elevated above evaporator.
4. Suction line sizing is based on using the same diameter tube from
the evaporator riser outlet to the condensing unit.
5. Suction line riser selections are based on using maximum possible
unloaders.
6. Refer to Carrier System Design Manual or to E20-II design
programs for further information on selecting pipe sizes for split
systems.
7. All pipe sizes are OD inches; equivalent sizes in millimeters follow:
in.
5/
8
7/
8
1
1 /8
3
1 /8
1 5 /8
2 1 /8
2 5 /8
3 1 /8
3 5 /8
NOTES:
1. Double risers are required if condensing unit is elevated above
evaporator. See footnotes and double suction riser table below.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction line sizing is based on 1.1 C (2 F) pressure drop at nominal rating conditions. Liquid line sizing is based on 1.1 C (2 F)
pressure drop. Higher design pressure drop criteria may allow
selection of smaller pipe sizes but at a penalty of decreased system capacity and efficiency.
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
92.1
UNIT
38AH
044
054
064;
Modules 124A,
124B, 134A
074;
Module 134B
084
Pipe A
Pipe B
Pipe C
15-20
(4.6-6.1)
A
B
C
15/8
15 /8
2 1 /8
2 5 /8
1 5 /8
2 1 /8
2 5 /8
1 5 /8
2 1 /8
2 5 /8
1 5 /8
2 1 /8
2 5 /8
1 5 /8
2 1 /8
2 5 /8
1 5 /8
2 1 /8
2 5 /8
1 5 /8
2 5 /8
3 1 /8
1 5 /8
2 5 /8
3 1 /8
1 5 /8
2 1 /8
2 5 /8
1 5 /8
2 1 /8
2 5 /8
1 5 /8
2 5 /8
3 1 /8
1 5 /8
2 5 /8
3 1 /8
1 5 /8
3 1 /8
3 5 /8
1 5 /8
2 1 /8
2 5 /8
1 5 /8
2 5 /8
3 1 /8
1 5 /8
2 5 /8
3 1 /8
1 5 /8
2 5 /8
3 1 /8
1 5 /8
3 1 /8
3 5 /8
LEGEND
Not Required
Suction Riser Without Trap
Suction Riser With Trap
Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction line sizing is based on 1.1 C (2 F) pressure drop at nominal rating conditions. Liquid line sizing is based on 1.1 C (2 F)
pressure drop. Higher design pressure drop criteria may allow
selection of smaller pipe sizes but at a penalty of decreased system capacity and efficiency.
4. Suction line sizing is based on using the same diameter tube from
the evaporator riser outlet to the condensing unit.
126
150-200
(45.7-61.0)
A
B
C
1 5 /8
2 5 /8
3 1 /8
1 5 /8
2 5 /8
3 1 /8
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
92.1
15-25
(4.6-7.6)
UNIT
38AH
L
094
104
Ckt A
Ckt B
Ckt A
Ckt B
7/
8
7/
8
7/
8
7/
8
S
2 1 /8
2 1 /8
2 1 /8
2 1 /8
LEGEND
L Liquid Line
S Suction Line
*Double suction riser required on all unit configurations if condensing
unit is elevated above evaporator.
Double suction riser required on units with field-installed unloader on
circuit A compressor if condensing unit is elevated above evaporator.
NOTES:
1. Double risers are required if condensing unit is elevated above
evaporator. See footnotes and double suction riser table below.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction line sizing is based on 1.1 C (2 F) pressure drop at nominal rating conditions. Liquid line sizing is based on 1.1 C (2 F)
pressure drop. Higher design pressure drop criteria may allow
selection of smaller pipe sizes but at a penalty of decreased system capacity and efficiency.
150-200
(45.7-61.0)
L
S
1 3 /8
3 1 /8 *
1 1 /8
2 5 /8
1 3 /8
3 1 /8 *
1 3 /8
3 1 /8 *
4. Suction line sizing is based on using the same diameter tube from
the evaporator riser outlet to the condensing unit.
5. Suction line riser selections are based on using maximum possible
unloaders.
6. Refer to Carrier System Design Manual or to E20-II design
programs for further information on selecting pipe sizes for split
systems.
7. All pipe sizes are OD inches; equivalent sizes in millimeters follow:
in.
5/
8
7/
8
1
1 /8
3
1 /8
1 5 /8
2 1 /8
2 5 /8
3 1 /8
3 5 /8
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
92.1
UNIT
38AH
094
104
Ckt A
Ckt B
Ckt A
Ckt B
A
1 3 /8
50-75
(15.2-22.9)
B
2 1 /8
1 3 /8
2 1 /8
2 5 /8
1 5 /8
2 1 /8
25/ 8
1 5 /8
3
1
5
5
1
5
1 /8
2 /8
2 /8
1 /8
2 /8
2 /8
1 5 /8
1 5 /8
LEGEND
Pipe A Suction Riser Without Trap
Pipe B Suction Riser With Trap
Pipe C Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction line sizing is based on 1.1 C (2 F) pressure drop at nominal rating conditions. Liquid line sizing is based on 1.1 C (2 F)
pressure drop. Higher design pressure drop criteria may allow
selection of smaller pipe sizes but at a penalty of decreased system capacity and efficiency.
4. Suction line sizing is based on using the same diameter tube from
the evaporator riser outlet to the condensing unit.
150-200
(45.7-61.0)
B
2 5 /8
2 1 /8
2 5 /8
2 5 /8
C
3 1 /8
2 5 /8
3 1 /8
3 1 /8
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
92.1
127
A
B
C
D
RED.
STR
LEGEND
Pipe A, Suction Riser, Lower Trap
Pipe B, Suction Riser with Trap
Suction Line to Condensing Unit
Pipe D, Suction Riser Short Lift
Reducer
Street
NOTE: Short riser, pipe D, is used when routing suction line to condensing unit connection. See table below:
044
PIPE D DIAMETER*
Dual Circuit
Single Circuit
A
B
5
5
1 /8
1 /8
2 1 /8
054
1 5 /8
15/ 8
2 1 /8
064
15 /
21/
2 1 /8
074
21 /
21/
2 1 /8
084
21 /
21/
2 5 /8
094
21 /
21/
104
2 1 /8
21/ 8
124A,B
2 1 /8
21/ 8
134A,B
2 1 /8
21/ 8
UNIT 38AH
128
Guide specifications
Commercial Air-Cooled Condensing Units
HVAC Guide Specifications
C.
D.
E.
F.
G.
910
129
130
A polymer strip shall prevent the coil assembly from contacting the sheet metal coil pan
to minimize the potential for
galvanic corrosion between the coil and the pan. All
copper construction shall provide protection in moderate coastal environments.
c. E-Coated Aluminum-Fin Coils:
Shall be constructed of aluminum fins mechanically bonded to copper tubes. Coating process
shall have a flexible epoxy polymer coating
uniformly applied to all coil surfaces without
material bridging between the fins. The coating process shall ensure complete coil encapsulation. Color shall be high-gloss black with
gloss at 60 F of 65% to 90% per ASTM
D523-89. Uniform dry film thickness shall be
0.8 mil to 1.2 mil on all surfaces, including the
fin edges. Superior hardness characteristics
shall meet those requirements of 2H, per
ASTM D3363-92A. Cross-hatch adhesion
shall meet the requirements of 4B-5B, per
ASTM D3359-93. Impact resistance shall be
up to 160 in./lb, per ASTM D2794-93.
Humidity resistance shall be up to a minimum
of 1000 hours per ASTM D2247-92. Water
immersion resistance shall be up to a minimum of 250 hours per ASTM D870-92.
Durability shall be confirmed through testing to
no less than 1000 hours of salt spray per
ASTM B117-90.
d. E-Coated Copper Fin Coils:
Shall be copper fins mechanically bonded to
copper tubes with copper tube sheets. Coating process shall have a flexible epoxy polymer coating uniformly applied to all coil
surfaces without material bridging between
the fins. The coating process shall ensure
complete coil encapsulation. Shall be highgloss black with gloss at 60 F of 65% to 90%
per ASTM D523-89. Uniform dry film
thickness shall be 0.8 mil to 1.2 mil on all surfaces, including the fin edges. Superior hardness characteristics shall meet those
requirements of 2H, per ASTM D3363-92A.
Cross-hatch adhesion shall meet the requirements of 4B-5B, per ASTM D3359-93.
Impact resistance shall be up to
150 in./
lb, per ASTM D2794-93. Humidity resistance shall be up to a minimum of 1000
hours per ASTM D2247-92. Water immersion resistance shall be up to a minimum of
250 hours per ASTM D980-92. Durability
shall be confirmed through testing to no less
than 1000 hours of salt spray per ASTM
B117-90.
9. Hail Guard:
Unit shall be equipped with louvered condenser coil hail guard protection and installation
hardware.
10. Security Grilles:
A set of PVC-coated metal grilles complete with
support retainers and fasteners shall be provided for the protection of the condensing coils,
compressors, or both.
11. Sound Reduction Package Kit:
This field-installed accessory kit shall consist of a
specially designed fan system containing fans and
orifices for reducing system noise without compromising unit performance. No fan motor
change shall be required for accessory
installation.
12. VAV Control Box:
Modification shall include electric unloaders on
compressors (1 for 38AH044; 2 for
38AH024-034, 054-084 and 104; 3 for
38AH094; and 4 for 38AH124,134) to make
condensing unit compatible with VAV controller. Unit shall include factory-installed accumulator (except for 38AH024-034 units where
accumulator is field installed).
13. Single-Circuit Modification (sizes 044-084
only):
Modification shall include all piping and wiring
to make unit single circuit. Unit shall include
factory-installed accumulator.
14. Single-Circuit Modification with VAV:
Modification shall include piping, wiring, and
electric unloaders on compressors (one on
38AH044 and 2 on 38AH054-084) to make
unit single circuit, VAV ready.
15. Hot Gas Bypass Kit:
A hot gas bypass kit is available for additional
capacity reduction for unit and prevention of
indoor coil freezing. Careful attention should be
placed on system oil management.
16. Non-Fused Disconnect:
A non-fused disconnect is available on single
circuit, dual circuit, and dual module units.
131
910
3-09
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Section 7
Pg 132
Catalog No. 04-52380006-01
Printed in U.S.A.
Form 38AH-11PD
Replaces: 38AH-10PD
Tab
7a