Apparatus Maintenance and Power Management for Energy Delivery

Brief Introduction for Automated Relay Testing


Kamin Dave Application Engineer (Protective Relaying)

DOBLE ENGINEERING COMPANY

Protection Relay Testing:

Testing of Differential Protection Relay type KBCH120

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: KBCH120


Two Differential Protection relays Automatic calculation for TAP values based on CTR Settings for Transformer & CT vector group compensations 2nd Harmonic Blocking during inrush period due to point on wave switching
Inrush Gap Detection Criterion

5th Harmonic Blocking for Over excitation phenomena Inverse Time Over Excitation Trip Characteristic
Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: KBCH120


MAKE MODEL : AREVA : KBCH120

Relay Settings:
Differential Element: Rated MVA = 100 HV = 220KV LV = 66KV TR VECTOR GROUP = YY0. CT CONNECTION = YY ID> = 0.2PU Turn Point1 = 1.0PU ID>> = 5.0PU SLP1 = 20% SLP2 = 80% In = 1A
Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: KBCH120


MAKE MODEL : AREVA : KBCH120

Relay Settings:
Differential Element: HV CT Ratio = 300/1A LV CT Ratio = 1200/1A CF1 = 1.14 CF2 = 1.37 HV Vector Correction = YY0 LV Vector Correction = YY0
Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: KBCH120


FLC on TR Primary side: IFLC = (100*1000) / (1.7325*220) = 262.36 Ampere FLC on TR Secondary side: IFLC = (100*1000) / (1.7325*66) = 874.54 Ampere CF1 = (1*300) / (262.36*1) = 1.14 CF2 = (1*1200) / (874.54*1) = 1.37

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Characteristic: Dual Slope

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Characteristic: Dual Slope

Idiff@SLP1 = (IBIAS)*(0.2) + (IS) Idiff@SLP2 = (IS) + 0.2 + (Ibias - 1)*0.8

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Test Equipment Make : DOBLE Model : F6150 F6TesT Version 2.18-1028

Software

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Test Circuit:

Source Configurations: Six current sources Winding 1 currents Winding 2 currents

IA IB IC

I1
KBCH I2

I3

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Tests conducted:
Pickup test for Winding1 Pickup test for winding2 Slope Characteristic test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Winding Pickup Test Use RAMP Module

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Winding Pickup Test:


Pickup Test for Winding1 (WDG1):Ipickup = (IS)*(1/CF1) = (0.2)*0.8745

= 0.1749A
Pickup Test for Winding2 (WDG2):Ipickup = (IS)*(1/CF2) = (0.2)*0.7287

= 0.1457A

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Winding Pickup Test:

How to Create Test Plan???

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Location Level Add new Location or Double click on Existing Location

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Level

Add new Relay or Double click on Existing Relay

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on Mouse & Press Append & create New Testplan
Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Double click on New test Plan

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on Mouse & Press on Append & Create new Test Module
Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Select RAMP Module from list

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Press on OK & Create New Test Definition


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Select 6 Currents (Right bank)


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Press on Yes
Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Select Trigger

Enter Action details

WDG1 current sources

Enter Expected Value = 0.175A


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test: WDG1

Click on RUN

Actual Test value = 0.197A


Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Select Trigger

Enter Action details

WDG2 current sources

Enter Expected Value = 0.165A


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test: WDG2

WDG2 current sources

Actual Test value = 0.167A


Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Slope Characteristic Test Use DiffChar Module

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Slope Characteristic Test:


Star conn. Star conn.

IP

Is

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

How to Create Slope Characteristic???

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Click on Add & select Differential


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Bias current Formula

Ibias = (IP+IS) / 2

Select Bias current (Ibias) formula from list Knowledge Is Power


SM

Apparatus Maintenance and Power Management for Energy Delivery

Software Configuration
Star conn.

YY0

Star conn.

YY0

YY0

R
Amplitude Compensation

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Click on Pickup Column & then after Click on Modify


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Pickup setting Say; 0.2

Select IBias Vs Idiff

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

How to Adjust Slope?

SLP2=80% SLP1=20%

Enter Slope 20% & 80% based on relay setting


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Click on Close
Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

How to create New Test Module?

Right click on Mouse & click on Append

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

How to create New Test Module?

Select DiffChar Module from list

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Double Click on Test Module & create New Test Definition


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Select characteristic from list

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Select elements

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Max. Test current (i.e. 12A)


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Select Trigger (i.e. Open to Close)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Select test points on curve Knowledge Is Power


SM

Apparatus Maintenance and Power Management for Energy Delivery

click on Add Point to List Knowledge Is Power


SM

Apparatus Maintenance and Power Management for Energy Delivery

Test Points are added for Test Knowledge Is Power


SM

Apparatus Maintenance and Power Management for Energy Delivery

Right Click on check box Right click on check box


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Click on RUN

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Test results

Red color shows Expected Curve & White color shows actual Curve