that will rust n All models are fully potted for water-proofing...maximum durability
MODEL
SD Spot Detector SD-R01 Spot Detector with Relay Output
DESCRIPTION
n n n
Operates on either 12-36VAC or 18-36VDC power Includes a 14ft (4.2m) leader cable
DESCRIPTION
5Year
Warranty
Works with any system that accepts dry contacts n Operates on 24VAC/VDC10% n Automatically resets when conductive fluid is no longer present (AC power only; if DC power is used, device must be reset by disconnecting power momentarily) n Includes a 14ft (4.2m) leader cable
n Designed for use with the all detection panels, with SC sensing cable to integrate both zone and spot detection into one panel n Powered by the LD300, LD1000, LD5100, LDRA6, or LD2000 n When used with a distance read panel (LD2000 or OD5100), the location of the leak will be identified (simulates 50 feet) n Includes one male and one female end connector, each on a 1ft (30cm) lead wire n
SD, SD-R01, SD-Z and MX1 Spot Detectors detect conductive fluids at a single point for the most economical way to detect fluids in small, confined areas. These devices are commonly used in small rooms and in air-conditioning drip pans. Veris offers four models of spot detectors which can integrate with various building management systems.
LEAK DETECTION
SPECIFICATIONS (MX1)
Input Power Max Current Draw, Voltage Units Only Output Output Rating Sensing Electrodes Operating Environment: Temperature Humidity 12-30VDC/24VAC; 10-year lithium battery model available 10mA N.C. solid-state, (opens on alarm) 30VAC/DC @ 0.1A max., polarity insensitive Gold plated -20 to 80C (-4 to 176F) 0 to 100% RH
800.354.8556
+1 503.598.4564
www.veris.com
07101
APPLICATION/WIRING DIAGRAMS
SD
Reset Push Button
(Normally Closed)
DIMENSIONAL DRAWINGS
SD thru SD-Z
2.9 (73 mm)
White/Red (+)
24 VDC
(not polarity sensitive)
Black (-)
Once triggered, device remains on until power is removed (if using VDC power).
SD-R01
Reset Push Button
(Normally Closed, VDC applications only)
24 VAC/DC
Red (+) Black (-) White (N.O.) Green (Comm) Blue (N.C.) Brown (Not Used)
0.3 (8 mm)
Once triggered, device remains on until power is removed (if using VDC power).
SD-Z The SD-Z works with all panels (LD300 and LD1000 shown here; LD5100, LDRA6, and LD2000 are also compatible).
or
LD1000
MX1 Series
Power/Alarm
LD300
NSC
MX1 Series
Red POWER SOURCE 12 to 30VDC/24VAC Black NOTE: Power supply not required for battery powered version
Green White
ORDERING INFORMATION
MODEL
U006-0006 U006-0007 U006-0008 MX1B MX1V
MANUF. PART #
SD SD-R01 SD-Z MX1B MX1V
DESCRIPTION
Spot Detector, 14 leader cable Spot Detector, 14 leader cable, relay out Spot Detector, 2x10 leader cable Spot Detector, battery Spot Detector, 12-30VDC/24VAC
CE
RoHS ETL
800.354.8556
+1 503.598.4564
www.veris.com
07101
LEAK DETECTION
SC