Ahmedabad Municipal Corporation

Tender Documents for Electrification Work of Central Administration Building of AMC @ Sardar Patel Bhavan, Dana pith, Amdavad

TENDER NO : AMC/_______________________/2009 NOTICE NO. : _________________________________

Volume III :- Price Bid

(1)

Date of Price bid Meeting

: 27/03/2009 at 16:00Hrs. Hours.

(2)

Last date of Tender Submission

: 09/04/2009 Upto 14:00 Hours. By RPAD / Speed post / Hand delivery : 09/04/2009 at 16:00 Hours.

(3)

Date of Tender Opening (Only Technical Bid)

Municipal Commissioner
Ahmedabad Municipal Corporation Sardar Patel Bhavan Ahmedabad - 380 001. Gujarat India

PROJECT : AHMEDABAD MUNICIPAL COMPLEX BUILDING. ARCHITECT : HIREN GANDHI AND ASSOCIATES. SUMMARY OF PRICES FOR ELECTRICAL WORKS SECTION NO DESCRIPTION OF WORK PART-A SOR ITEM 1 ELECTRICAL WIRING 2 LIGHT FIXTURES AND FANS 3 DISTRIBUTION BOARDS 4 EARTHING 5 L.T. CABLES 6 FANS AND ACCESSORIES 7 EXTERNAL LIGHTING 8 SUBSTATION EQUIPMENTS TOTAL COST FOR ELECTRICAL WORKS- PART - A PART-B NON SOR ITEM 9 CABLE TRAY 10 INDUSTRIAL SOCKETS 11 TRANSFORMER AND HT VCB PANEL 12 EARTHING WIRES 13 LIGHT FIXTURES 14 LT PANEL 15 TELEPHONE / COMPUTER NETWORKING 16 LIGHTINING PROTECTION SYSTEM 17 FIRE ALARM SYSTEM 18 CCTV SYSTEM 19 ACCESS CONTROL SYSTEM 20 CONFERENCE SYSTEM TOTAL COST FOR ELECTRICAL WORKS- PART - B TOTAL COST FOR ELECTRICAL WORKS DT:13.03.09 AMOUNT (Rs.)

M/s. HIREN A GANDHI & ASSOCIATES.

PAGE : 1/18

M/s.TRANSENERGY ELECTRICAL CONSULTANTS

PART-A SOR RATE ITEM Sr. No SOR NO ITEM SECTION -1. ELECTRICAL WIRING CH-I Section - 1 -2 Point wiring in Copper (Modular) WIRING 1.1 1-2-1. Point wiring for Light / Bell with 2-1.0 sq. mm & earthwire of 1.0 sq. mm (green) both are of ISI marked of FR PVC insulated multistrand copper wires, in existing pipe duly erected complete with 6A Modular type switch / bell push & accessories and earth continuity of following type, erected on PVC / Metallic box covered with appropriate front plate modules erected concealed in Wall / ceiling. B) Single mounting base-frame & Textured / Metallic front plates. UNIT COST MATRIAL Rs.Ps. COST LABOUR Rs.Ps. TOTAL FOR 2008-2009 Rs.Ps. QTY. AMOUNT Rs.

Cat-I Cat-II Pt. 1,000.00

1.2

1-1-4.

Point wiring for secondary light point with 2-1.0 sq.mm & earthwire of 1.0 sq. mm (green) both are of ISI marked FR PVC insulated multistrand copper wires, in existing pipe duly erected complete with earth continuity and necessary connection with primary light with accessories erected on polished wooden block / Metal / PVC box covered with 3 mm thick laminated sheet for open / concealed wiring. Note:- Maximum up to 3 mtrs length, excess will be considered as Mains for Secondary Point. b) For Concealed wiring Pt. 1,200.00

1.3

1-2-2.

Point wiring for FAN with2-1.0 sq. mm & earthwire of 1.0 sq. mm (green) both are of ISI marked FR PVC insulated multistrand copper wires, in existing pipe duly erected complete with 6A Modular type switch and hum free EME 5/6 step type electronic fan regulator with separately mounted and accessories with earth continuity of following type erected on PVC / Metallic box covered with appropriate front plate modules erected concealed in wall / ceiling. B) Single mounting base-frame & Textured / Metallic front plates.

Cat-I Cat-II

Pt. Pt.

275.00

1.4

1-2-3.

Point wiring for Individual Plug with 2-1.0 sq. mm & earthwire of 1.0 sq. mm (green) both are of ISI marked FR PVC insulated multistrand copper wires, in existing pipe duly erected complete with 6 A Modular type switch & 6 A 5pin Plug erected on PVC/ Metallic box covered with appropriate front plate modules erected concealed in wall / ceiling with following type of accessories. B) Single mounting base-frame & Textured / Metallic front plates. Cat-I Cat-II Pt. 400.00

1.5

1-2-4.

Point wiring for Looped Plug with 6 A Modular type switch & 5 pin socket erected on PVC/ Metallic box covered with appropriate front plate modules erected concealed in wall / ceiling with following type accorries. B) Single mounting base-frame & Textured / Metallic front plates. Cat-I Cat-II Pt.
PAGE : 2/18

1,000.00

M/s. HIREN A GANDHI & ASSOCIATES.

M/s.TRANSENERGY ELECTRICAL CONSULTANTS.

Sr. No

SOR NO

ITEM

UNIT

COST MATRIAL Rs.Ps.

COST LABOUR Rs.Ps.

TOTAL FOR 2008-2009 Rs.Ps.

QTY.

AMOUNT Rs.

1.6

1-2-5.

Point wiring for Two Way Controlled Light Point with 2-1.0 sq. mm & eirthwire of 1.0 sq. mm (green) both are of ISI marked FR PVC insulated multistrand copper wires, in existing pipe duly erected complete with 6A Modular type switches and following type of accessories ereced on PVC / Metallic box covered with appropriate front plate modules erected concealed in wall / ceiling. B) Single mounting base-frame & Textured / Metallic front plates.

Cat-I Cat-II Pt. 125.00

1.7

1-2-6.

Providing following type of Modular Type Accessories mounted on PVC / Metallic box covered with appropriate front plate modules erected with necessary connection. (4) RJ-11 Telephone Socket with top Cat-II Ea. Ea. 420.00 10.00 (5) TV Co-axial Socket outlet Cat-II (6) Electronic hum free Five Steps EME Fan regulator. Cat-II Ea. Ea. Ea. Ea. 275.00 455.00 110.00 110.00 (9) Modem Jack fro Computer Open RJ-45 Cat-II (10) 16 Amp. Sp One way switch Cat-II (11) 6/16 Amp. Universal Socket Cat-II Section :- 1- 4 Conduits & Pipes Providing and erecting 1.5 mm thick FIA approved and ISI mark ( embossed) RIGID PVC PIPES of following size complete erected with necessary PVC fittings and Junction boxes fixed with adhesive solution and Clamps with following type of erection. (2) For erection concealed in wall / slab along with continuous fish wire to draw mains, laid in approved manner with Plastering by cement mortar & finishing the surface to match the wall / ceiling. b) 25 mm c) 32 mm d) 40 mm

1.7.1 1.7.2 1.7.3

1.7.4 1.7.5

1.8

1-4-2.

1.8.1 1.8.2 1.8.3

Mtr. Mtr. Mtr.

28,000.00 500.00 100.00

1.9

1.9.1 1.9.2 1.10

SEC 1-5 Mains & Wires 1-5-1. Mains with 1.1 KV grade FRPVC insulated ISI marked stranded Copper conductor wire in existing pipe erected with 1.5 sq. mm copper conductor FR PVC insulated stranded wire of green colour for earth. continuity of following size. b) 2 Wire 1.5 sq. mm c) 2 Wire 2.5 sq. mm 1-5-2. Mains with 1.1 KV grade FR PVC insulated ISI marked stranded Copper conductor wire in existing pipe erected with 2.5 sq. mm copper conductor FR PVC insulated stranded wire of green colour for earth continuity of following size. a) 2 wire 4 sq. mm. b) 2 wire 6 sq. mm. c) 2 wire 10 sq. mm. d) 3 wire 4 sq. mm. g) 4 wire 4 sq. mm. h) 4 wire 6 sq. mm. I) 4 wire 10 sq. mm. Providing & Erecting following sie of TV Co-axial flexible cable comprising inner conductor of solid bare copper insulated

Mtr. Mtr.

3,500.00 22,000.00

1.10.1 1.10.2 1.10.3 1.10.4 1.10.5 1.10.6 1.10.7 1.11 1-5-8.

mtr mtr mtr mtr mtr mtr mtr

2,500.00 250.00 100.00 100.00 100.00 100.00 100.00

PAGE : 3/18 M/s. HIREN A GANDHI & ASSOCIATES. M/s.TRANSENERGY ELECTRICAL CONSULTANTS.

Sr. No

SOR NO

ITEM with Foam PE & Secondary conductor made of poly- Aluminium film bonded Al. Braids @ coverage of 65% overall sheathed with black PVC insulation. a) RG -6 b) RG-11

UNIT

COST MATRIAL Rs.Ps.

COST LABOUR Rs.Ps.

TOTAL FOR 2008-2009 Rs.Ps.

QTY.

AMOUNT Rs.

1.11.1 1.11.2 1.12 1-5-9.

Mtr. Mtr.

500.00 100.00

Supplying & erecting Delton or approved make Telephone Cable electrolytic grade annealed copper conductor insulated with PE insulation twisted in to pairs with colour combination bunched together in concentric layers so as to minimies crosstak & wrapped with FR PVC tape & sheathed with FR PVC or HFFR outer Jacket suitable for indoor telephone wiring & confirming to C-DOT S/WS - 113 / IEC 60189-2, UL-1581 SECTION 1080 V W-1 erected in existing pipe of following size of conductors & nos.of pairs. With necessary connections. B. Conductor Size 0.5 mm (b) Armoured 13). Ten Pair 14). Twenty Pair 15). Fifty Pair 13). Hundred Pair

1.12.1 1.12.2 1.12.3 1.12.4

Mtr. Mtr. Mtr. Mtr.

100.00 100.00 400.00 200.00

1.13

1.13.1 1.13.2 1.13.3 1.13.4 1.14

SEC-1.6 Concealed Boxes & Laminated Sheets. 1-6-1. Supplying & erecting 16 Gauge painted with red oxide M. S. Box / PVC box erected flushed on wall or concealed in wall with necessary plastering & finishing as directed of following size. a). 100 mm x 100 mm x 75 mm (d) b) 175 mm x 100 mm x 75 mm (d) c) 200 mm x 250 mm x 75 mm (d) d) 250 mm x 300 mm x 75 mm (d) 1-6-3. Providing & erecting 3 mm thick laminated sheet with grooving as directed. TOTAL OF SECTION -1. SECTION -2 LIGHT FIXTURES AND FAN CH-II CHAPTER -II Lamps & Fittings. SEC-2.1 SECTION 2-1 FILAMENT LAMPS 2-1-2. Approved make G.F.LAMP 230/250V, 40 watt / 60 watt erected, if required. Cat-III SEC-2.2 SECTION 2-2 FLUORESCENT TUBES 2-2-2. Approved make Fluorescent tube 120 cms. 36/40 watt erected, if required. (2X36W AND 1X36W ) SEC-2.4 SECTION 2-4 SODIUM VAPOUR LAMPS 2-4-1. Approved make High pressure sodium vapour lamp, Tubular / Elliptical type 70W. 230/240/250V erected, if required. Cat-III SEC-2.6 COMPACT FLUORESENT LAMP 2-6-1. Approved make C.F.L. Lamp Retrofit 9/11 Watt.(BRACKET LIGHT) Cat-III

Ea. Ea. Ea. Ea.

1,500.00 200.00 200.00 100.00

Sq.Inch.

65,000.00 -

2.1

Ea.

15.00

2.2

Cat-III

Ea.

175.00

2.3

Ea.

25.00

2.4

Ea.

35.00

2.5

2-6-2.

Approved make C.F.L. Lamp Retrofit 13/15/18 Watt. (2X18W DL AND BRICK LIGHT) Cat-II Ea. 1,200.00

2.6

SEC-2.7 SECTION 2-7 METAL HALIDE LAMPS 2-7-2. Approved make Double Ended type Metal Halide Lamps. (II) 150 Watt.
PAGE : 4/18 M/s. HIREN A GANDHI & ASSOCIATES. M/s.TRANSENERGY ELECTRICAL CONSULTANTS.

Sr. No

SOR NO

ITEM Cat-III

UNIT Ea.

COST MATRIAL Rs.Ps.

COST LABOUR Rs.Ps.

TOTAL FOR 2008-2009 Rs.Ps.

QTY. 10.00

AMOUNT Rs.

2.7

ENERGY SAVING FLUORESENT SEC-2-9 TUBE FITTINGS ( With Electronic Ballast) 2-9-4. Decorative Box type with plasitc/polyester cover fluorescent fitting with HFHC Electronic Ballast, finished with anti-rust treated white stove enameled with black or white end plates and lockor rotor type, holders with erection on site with lead wire and connections. Suitable for 1 Tube 40 watt 120 cms. Cat-III Ea. 145.00

2.8

2-9-5.

Providing & erecting mirror optic surface or pendent mounting fl.fitting Suitable for 2 number 120 cms. 40 watt tubes complete with HFHC Electronic Ballast complete with holder with lead wire and connection . Cat-III Ea. 15.00

2.9

2.8.4

Bulk head fitting with glass wire guard rubber gasket & porcelain holder suitable for 40 Watt. To 100 Watt. Lamp with suitable conduit entry to be erected as directed. Cat-III Ea. 15.00

2.10

SEC-2-11 COMPACT FLOURCENT FITTING 2-11-3. Providing & erecting approved make CFL outdoors type Bollard comprising serrated diffuser mounted on aluminium cast control gear housing with two no. of 9 watt CFL Lamps holder & accessories mounted on 60 cms. High rotomoulded LLDPE pillar dully grouted on a concrete base by means of four nos of M8 X 75 mm studs with necessary base ring. Cat-III Ea. 20.00

2.11

2-11-4.

Providing & erecting approved make C.F.L. docorative wall mounted luminaire complete with 11 watt tube, ballast, holder, clear/ opal diffuser complete erected with lead wire. (a). For One lamp. Cat-III Ea. 15.00

2.12

2-11-6.

Providing & erecting approved make decorative surface mounting type mirror optic luminaire complete with tubes, ballast, holder clear/ opal duffuser complete erected with necessary lead wire. (b). With Two 18 E. CFL Cat-III Ea. 600.00

2.13

SEC 2.13 SODIUM VAPOUR LAMP FITTINGS 2-13-3. Supplying & erecting approved make HPSV public lighting luminair as per Keselec'Z' range or approved make comprising an injection moulded Aluminium body 2 side reflection or a single piece deep drawn reflector in high puirty polished & enodised Aluminium, with polystyrene acrylonitrite protective cover & a clear acrylic protector. The control gear monted in the body on to removable mounting plate. Suitable for vertical mounting directly on 76mm dia. Pole top with prismatic or reinforced glass protector. B). Suitable for 70 W Sodium Lamp. TOTAL OF SECTION -2. SECTION -3 DISTRIBUTION BOARDS. Ea. 25.00 -

PAGE : 5/18 M/s. HIREN A GANDHI & ASSOCIATES. M/s.TRANSENERGY ELECTRICAL CONSULTANTS.

Sr. No

SOR NO

ITEM

UNIT

COST MATRIAL Rs.Ps.

COST LABOUR Rs.Ps.

TOTAL FOR 2008-2009 Rs.Ps.

QTY.

AMOUNT Rs.

3.1

SEC-3.10 MINIATURE CIRCUIT BREAKERS. 3-10-1. Miniature circuit breaker Single Pole 6 A to 32 A suitable to operate on 240 V A. C. system and having overload and short circuit tripping elements and breaking capacity 10 KA to be erected in existing M. S. Box confirming to IS 8828/1996 with ISI mark. Cat-III Ea. 978.00 -

3.2

3-10-2.

3.2.1 3.2.2

Providing & erecting 240 V. MCB Double Pole Switch for motor & inductive load (C Curve) having 10 KA breaking capacity & confirms to IS: 8828 in existing box having following capacity. A) 6 to 32 Amp. Cat-III B) 40 Amp. Cat-III Ea. 79.00 Ea. 48.00 -

3.3

3-10-5.

3.3.1 3.3.2

Providing & erecting 415 V. MCB Four Pole switch for Motor & inductive Load ( C Curve) having 10 KA breaking capacity & confirms to IS: 8828 in existing box having following capacity B) 40 Amp. Cat-III C) 63 Amp. Cat-III Ea. 25.00 Ea. 16.00 -

3.4

3.4.1 3.4.2 3.5

SEC 3-11. MCB DISTRIBUTION BOARDS. 3-11-5. Providing and erecting Sheet Steel powder coated MCB distribution board - Flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, confirming to IS:13032 and BS-5486-1986 without MCB to house appropriate nos. of MCB's (The DBs should be used of same company of MCB to be used) N) Three Phase 8 way SS Double door for single phase outgoing horizontal box. F) Single Phase 8 way SS Double door. 3-11-8. Providing and erecting thermo plastic "SHOKARE" L & T - Hager or equivalent MCB / ELCB distributions board having modular Double Door with DIN rails, epoxy powder coated finish metal frame & door assembly with Acrylic / Plstic door, spring & hinged pains complete with required PVC sleeved 32 / 63 A copper Bus strips without MCB / ELCBs f) Two Row 36 Mod EARTH LEAKAGE CIRCUIT BREAKERS. SEC-3.12 3-12-1. Approved make ELCBs / RCCBs conforming to IS:12640 and having sensititvity of 30 m A and Short Circuit with stand capacity of 6KA and suitable for operation on single phase 240 V having charectorstic of quick action & tripping with all advance feature & do not incorporate any electronic component for following Max. rating. (I) 25 Amps. DP Cat-III

Ea. Ea.

4.00 4.00

Ea.

37.00

3.6

3.6.1 3.6.2

Ea. Ea.

48.00 79.00

(II) 40 Amps. DP Cat-III SEC-3.14 DANGER NOTICE BOARDS. 3-14-1. Providing and erecting metallic vetrified Danger Notice Boards for MEDIUM VOLTAGE installation to be erected as per I.S. 3-14-2. Providing and erecting metallic vetrified Danger Notice Boards for HIGH VOLATAGE installation to be erected as per I. S.

3.7

Ea.

47.00

3.8

Ea.
PAGE : 6/18

10.00

M/s. HIREN A GANDHI & ASSOCIATES.

M/s.TRANSENERGY ELECTRICAL CONSULTANTS.

Sr. No

SOR NO

ITEM

UNIT

COST MATRIAL Rs.Ps.

COST LABOUR Rs.Ps.

TOTAL FOR 2008-2009 Rs.Ps.

QTY.

AMOUNT Rs. -

TOTAL OF SECTION -3 SECTION - 4 EARTHING SEC-3-15 EARTHINGS 3-15-3. Providing and erecting required size Copper Strip for earthing of H.T.OCB / ACB / Transformer, LT panne board, Motors etc., using copper clamp. 3-15-4. Providing and erecting Annealed bare 8SWG CU wire

4.1

Kg.

1,000.00

4.2

Kg.

100.00

4.3

4.3.1 4.3.2 4.3.3

3-15-12. Supplying & erecting funnel type earthing having earth plate of following size burried in specifically prepared earth pit 3 mtr. below ground with 40 kg charcol and salt with alternate layers of charcol & salt, 20mm dia. G.I.Pipe with Funnel with a wire mesh for watering & bricks masonry block, C.I. Cover complete as per para 7.3 of IS 3043 with necessary length of double G.P/copper earth wire No.6 SWG bolted with lug to the nearest switch gear with end socket as per direction & duly tested by earth tester confirming to ISS (As per drawing) with following specification. B) With 30 x 30 x0.35 cms: Copper C) With 45 x45 x 0.315 cms: Copper D) With 60 x 60 x0.315 cms: Copper earth plate. TOTAL OF SECTION - 4 SECTION - 5 CABLES SEC 4.2 UNARMOURED COPER CABLES. 4-2-1. Supplying & erecting XLPE(IS:7098) (I)-88 ISI marked unarmoured copper cable 1.1 KV grade with necessary clamps on wall of following size. B) 3 Core 2.5 Sq.mm. CH-4 SEC-4.3 ARMOURED ALUMINIUM CABLES. 4-3-3. Providing & erecting XLPE(IS:7098) (I)-88 ISI marked armoured cable multistrand Aluminium conductor for 1.1 KV to be laid on wall with necessary clamps or in existing cable trench / pipe at road corssing or floor of following size of cables. A)3.1/2 Core 35 Sq.mm (16 Sq.mm1/2 Core) B)3.1/2 Core 50 Sq.mm (25 Sq.mm1/2 Core) C)3.1/2 Core 70 Sq.mm (35 Sq.mm 1/2 Core) D)3.1/2 Core 95 Sq.mm (50 Sq.mm 1/2 Core) E)3.1/2 Core 120 Sq.mm (70 Sq.mm 1/2 Core) F)3.1/2 Core 150 Sq.mm (70 Sq.mm 1/2 Core) G)3.1/2 Core 185 Sq.mm (95 Sq.mm 1/2 Core) H)3.1/2 Core 300 Sq.mm (185 Sq.mm 1/2 Core) J)3.1/2 Core 400 Sq.mm (185 Sq.mm 1/2 Core) 4-3-4. Providing & erecting XLPE(IS:7098) (I)-88 ISI marked armoured cable multistrand Aluminium conductor for 1.1 KV to be laid on wall with necessary clamps or in existing cable trench / pipe at road corssing or floor of following size of cables. d) 4 Core 16 Sq.mm. e) 4 Core 25 Sq.mm.

Ea. Ea. Ea.

2.00 12.00 12.00

5.1

Mtr.

300.00

5.2

5.2.1 5.2.2 5.2.3 5.2.4 5.2.5 5.2.6 5.2.7 5.2.8 5.2.9 5.3

Mtr. Mtr. 305 Mtr. Mtr. Mtr. Mtr. Mtr. Mtr.

100.00 100.00 50.00 150.00 50.00 300.00 50.00

5.3.1 5.3.2

Mtr. Mtr.

100.00 100.00

5.4

SEC-4.4 ARMOURED COPPER CABLES. 4-4-2. Providing and erecting XLPE(IS:7098)(I)-88 ISI marked armoured cable multistrand Copper Conductor for 1.1 KV to be laid on wall with necessary clamps or in existing cable trench / pipe at road crossing or floor of following size of cables.
PAGE : 7/18 M/s. HIREN A GANDHI & ASSOCIATES. M/s.TRANSENERGY ELECTRICAL CONSULTANTS.

Sr. No 5.4.1 5.4.2 5.5

SOR NO a) 3 Core 4 Sq.mm. b) 3 Core 6 Sq.mm. 4-4-4.

ITEM

UNIT Mtr. Mtr.

COST MATRIAL Rs.Ps.

COST LABOUR Rs.Ps.

TOTAL FOR 2008-2009 Rs.Ps.

QTY. 100.00 100.00

AMOUNT Rs. -

5.5.1 5.5.2 5.5.3 5.5.4 5.5.5 5.5.6

MR

Providing and erecting XLPE(IS:7098)(I)-88 ISI marked armoured cable multistrand Copper Conductor for 1.1 KV to be laid on wall with necessary clamps or in existing cable trench / pipe at road crossing or floor of following size of cables. A) 4 Core 4 Sq.mm. B) 4 Core 6 Sq.mm. C) 4 Core 10 Sq.mm. D) 4 Core 16 Sq.mm. E) 4 Core 25 Sq.mm. 12 Core 1.5 Sq.mm.

Mtr. Mtr. Mtr. Mtr. Mtr. Mtr.

200.00 200.00 800.00 2,800.00 200.00 100.00

5.6

SEC-4.5 MISCELLANEOUS. 4-5-1. Making trench in soft soil of suitable width of 90 cms deep for laying cable or locating the fault all over the run and back filling the same and making the surface proper. A) Upto 25Sq.mm cable. B) For 35 Sq.mm to 95 Sq.mm cable. C) For 120 Sq.mm to 300 Sq.mm cable. 4-5-6. supplying following size of Light duty "A" Class G.I. Pipe & erecting as directed by Engineer-in-charge. B) 50 mm dia. Providing & laying R.C.C. hume pipe for cable to be laid 90 cms below ground across the raod crossing or on floor with necessary meterial in an approved manner. A) 250 mm dia. B) 150 mm dia.

Mtr. Mtr. Mtr.

100.00 50.00 300.00

5.7

Mtr.

30.00

5.8

4-5-7.

5.8.1 5.8.2

Mtr. Mtr.

50.00 100.00

5.9

5.9.1 5.9.2 5.9.3 5.9.4 5.9.5 5.10

SEC-4.6 CABLE GLANDS. 4-6-1. Providing and fixing heavy duty flange type brass cable gland with rubber ring for PVC insulated armourd cable complete with out going tails, insulating tape etc. for following size of cables. b) 2 to 4 Core 4 Sq.mm c) 2 to 4 Core 6 Sq.mm d) 2 to 4 Core 10 Sq.mm e) 2 to 4 Core 16 Sq.mm f ) 2 to 4 Core 25 Sq.mm 4-6-3. Providing and fixing heavy duty flange type brass cable gland with rubber ring for PVC insulated armourd cable complete with out going tails, insulating tape etc. for following size of cables. A) 3.1/2 /4 Core 25 Sq.mm B) 3.1/2 Core 35 Sq.mm B) 3.1/2 Core 50 Sq.mm C) 3.1/2 Core 70 Sq.mm D) 3.1/2 Core 95 Sq.mm E) 3.1/2 Core 120 Sq.mm F) 3.1/2 Core 150 Sq.mm G) 3.1/2 Core 185 Sq.mm I) 3.1/2 Core 300 Sq.mm K) 3.1/2 Core 400 Sq.mm SEC4.7 4-7-1. CABLE LUGS. Solderiess crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with high pressure tool & connected to switchgear terminals with brass / cadmium plated nut bolts in as approved manner. A) 4 Sq.mm. A) 6 Sq.mm.

nos nos nos nos Mtr.

25.00 25.00 75.00 100.00 35.00

5.10.1 5.10.2 5.10.3 5.10.4 5.10.5 5.10.6 5.10.7 5.10.8 5.10.9 5.10.10

Mtr. Mtr. Mtr. Mtr. Mtr. Mtr. Mtr. Mtr. Mtr. Mtr.

34.00 32.00 2.00 16.00 6.00 2.00 2.00 2.00 4.00 24.00

5.11

5.11.1 5.11.2

Ea. Ea.
PAGE : 8/18

40.00 40.00

M/s. HIREN A GANDHI & ASSOCIATES.

M/s.TRANSENERGY ELECTRICAL CONSULTANTS.

Sr. No 5.11.3 5.11.4 5.11.5 5.11.6 5.11.7 5.11.8 5.11.9 5.11.10 5.11.10 5.11.11 5.11.10 5.11.12 5.12

SOR NO B) 10 Sq.mm. C) 16 Sq.mm. D) 25 Sq.mm. E) 35 Sq.mm. E) 50 Sq.mm. F) 70 Sq.mm. G) 95 Sq.mm. H) 120 Sq.mm. I) 150 Sq.mm. J) 185 Sq.mm. L) 300 Sq.mm. M) 400 Sq.mm. 4-7-2.

ITEM

UNIT Ea. Ea. Ea. Ea. Ea. Ea. Ea. Ea. Ea. Ea. Ea. Ea.

COST MATRIAL Rs.Ps.

COST LABOUR Rs.Ps.

TOTAL FOR 2008-2009 Rs.Ps.

QTY. 40.00 288.00 136.00 128.00 8.00 64.00 24.00 8.00 8.00 16.00 8.00 64.00

AMOUNT Rs. -

5.12.1 5.12.2 5.12.3 5.12.4

Solderiess crimping type Copper lugs conforming to IS suitable for cable of following size evenly crimped with high pressure tool & connected to switchgear terminals with brass / cadmium plated nut bolts in as approved manner. A) 4 Sq. mm. A) 6 Sq. mm. B) 10 Sq.mm. C) 16 Sq.mm. TOTAL OF SECTION - 5

Ea. Ea. Ea. Ea.

20.00 10.00 10.00 10.00

6.1

SECTION - 6 FANS AND ACCESSORIES CH-5 SEC-5.1 CEILING FANS AND ACCESSORIS. 5-1-1. Approved make Ceiling Fan with condenser A.C.230 V. 50 Cys. 1200 mm. Sweep Complete, canopy and 30 cms down rod erected on existing hook or clamp with 24/ 0.2 flat 3 Core flexible wire with earthing (Or R.C. Rate) ( Add Rs. 80/- Extra for Resistant type Fan Regulator) SEC 5.2 FAN ACCESSORIES. 5-2-3. Supplying & erecting fan hook box of 10mm M.S.round bar bounded to the RCC brass up to 50 mm length each side and pierced through a 16 Gauge M.S.Box / Heavy Duty PVC box having depth of 75 mm complete erected concealed in Ceiling with necessary finishing. SEC 5.2 TABLE FANS, EXHAUST FANS & ACCESSORIES. 5-3-3. Supplying and erecting approved make reversible fress air cum exhaust fan having size 305 mm, 1400 RPM. 5-3-9. Providing suitable M.S.louver shutter of the Exhaust Fan. TOTAL OF SECTION - 6 SECTION - 7 EXTERNAL LIGHTING SEC 6-1 STREET LIGHT POLES. 6-1-1. Galvanised iron pipe post " B " class 88.9 mm O D 4 Mtr. Long duly painted with two coats of alluminium paint complete with metalic base plate of 300 mm x 300 mm x 4 mm thick to be erected as compound light pole with approx weight 32 Kg. SEC 6-3 POLE FOUNDATION 6-3-1. Providing C.I./ M.S. flange type base plate of 300 mm x 300 mm x 6 mm. 6-3-3. Providing and erecting cable clamp of 25 mm x 3 mm M.S. flat suitable for fixing 2 Nos. of armoured cable with nuts and bolts. c) for 140 mm dia. Pole Providing cement concrete foundation

Ea.

275.00

6.2

Ea.

275.00

6.3

Ea.

125.00

6.4

Ea.

35.00

7.1

Ea.

25.00

7.2

Ea.

25.00

7.3

Ea.

50.00

7.4

6-3-4.

PAGE : 9/18 M/s. HIREN A GANDHI & ASSOCIATES. M/s.TRANSENERGY ELECTRICAL CONSULTANTS.

Sr. No

SOR NO

ITEM including excavation for the pole with 45 x45 x 100 cms deep in 1:3:6 cement concrete (20 to 25 mm stone metal) with 45 cms x 45 cms (or 45 cms dia) x 45 cms high cement concrete plinth with necessary curing and finishing in approved manner. (for 4 & 6 mtr pole)

UNIT

COST MATRIAL Rs.Ps.

COST LABOUR Rs.Ps.

TOTAL FOR 2008-2009 Rs.Ps.

QTY.

AMOUNT Rs.

Ea.

25.00

7.5

SEC-6.4 POLE BOXES. 6-4-3. Supplying & erecting Sintex or approved make SMC press moulded composite FRP (plastic) loop-in, loop-out box approx 207mm thick complete with bakelite connector strip 4 way & hingled doors having locking arrangements with mounting clamp with nuts, bolts & washers suitable for erection on pole with cable clamps & earth bolt of following size of box. b) 250 mm x 200 mm x 200 mm TOTAL OF SECTION - 7 SECTION - 8 SUBSTATION EQUIPMENTS SEC 10-2 SUBSTATION EQUIPMENTS. 10-2-1. Providing Printed instruction chart both in English and Gujarati and duly framed with front glasses, for treatment of person suffering from Electric shock. 10-2-2. Providing pair of rubber hand gloves suitable for working on 11 KV / 22 KV supply. Supplying 12.00mm thick rubber mat for L.T. of required length and breadth. Supplying standard first aid box with all the standard contents. Supplying FIRE bucket round botton of 9 litres capacity made out of 24 gauge G.I Sheet with extra handle at bottom duly painted white inside and Red out side with FIRE mark. Filled with dry-sand and kept on existing stand provided or hung on wall hook. Supplying and erecting floor mounting Stand for keeping four nos. of FIRE buckets comprising 1500 mm in length, 900 mm height frame made out of 30mm x 30 mm x 4 mm angle iron with cross suports legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of approved enamelled silver paint. Wall hook 22 to 25 cms. Projection for keeping fire buckets made out of 15 mm dia. M. S. rod grouted in wall to a depth of minimum 15 cms. Ea. 50.00

8.1

Ea.

2.00

8.2

Ea.

2.00

8.3

10-2-4.

Sq. Mtr.

36.00

8.4

10-2-5.

Ea.

2.00

8.5

10-2-6.

Ea.

10.00

8.6

10-2-7.

Ea.

2.00

8.7

10-2-8.

Ea.

2.00

8.8

10-2-15. Providing & erecting ISI marked 3 Core 120/185 Sq.mm XLPE inulated 11 KV armoured cable Aluminium conductor to be laid on wall with clamps or in provided cable trench/ pipe in approved manner as directed. 10-2-17. Providing and erecting Cable and Termination kit heat shrinkable push on type Densons/ Raychem / Elastimold make suitable for 11 KV XLPE cable 3 Core 120/185 Sq. mm. A) Outdoor Type B) Indoor Type TOTAL OF SECTION - 8

mtr

25.00

8.9

8.9.1 8.9.2

Ea. Ea.

1.00 3.00

PAGE : 10/18 M/s. HIREN A GANDHI & ASSOCIATES. M/s.TRANSENERGY ELECTRICAL CONSULTANTS.

Sr. No

SOR NO TOTAL OF PART-A

ITEM

UNIT

COST MATRIAL Rs.Ps.

COST LABOUR Rs.Ps.

TOTAL FOR 2008-2009 Rs.Ps.

QTY.

AMOUNT Rs.

PART-B NON SOR ITEM- MR ITEM SECTION - 9 CABLE TRAY Supply and Erecting of perforated type Hot dip G.I. cable tray of 14G of specific dimensions. The cable tray shall be hung from ceiling/ fixed to wall with necessary ceiling suspensors, tee, nots, nuts etc, together with tees, bends etc. The tray shall be earthed. 50 x 50 mm 100 x 50 mm 150 x 50 mm 300 x 50 mm 450 x 50 mm 600 x 50 mm 1000 x 75 mm - ladder type Supply, fabricating and installing of M.S. supports and other items. The fabricated items shall be coated with 2 coats of redoxide and then applied with 2 coats of enamel paint. Size of M.S. steel shall be as per detials given by EIC/ Consultant. Rates shall include necessary hardware required for fixing. TOTAL OF SECTION - 9 SECTION - 10 INDUSTRIAL SOCKETS SITC of 20 A 1 phase PVC type industrial plug sockets of IP 65 category with DP MCB complete. (wiring for the same shall be paid in rmt) SITC of 32 A 3 phase PVC type industrial plug sockets of IP 65 category with FP MCB complete. (wiring for the same shall be paid in rmt) SITC of 63 A 3 phase PVC type industrial plug sockets of IP 65 category with FP MCB complete. (wiring for the same shall be paid in rmt) TOTAL OF SECTION - 10 SECTION - 11 TRANSFORMER AND 11KV HT VCB Supply Installation testing and Commissioning of indoor type 3nos x 11KV HT VCB Panel for 1 Incoming and 2 Out going panel having with checking of foundation level, welding of stoppers on foundation channels, including all labour and materials.Inteconnection between accssories mounted on the transformer & marshalling box Supply, Installation testing and Commissioning of indoor type transformer having 11 KV/415V for 750KVA Dry type transformer with checking of foundation level, welding of stoppers on foundation channels, including all labour and materials.Inteconnection between accssories mounted onthe transformer & marshalling box TOTAL OF SECTION - 11 SECTION - 12 EARTHING WIRES 16 sq mm single core flexible copper wire of green colour with 25 mm dia PVC conduit 6 sq mm single core flexible copper wire of green colour with 25 mm dia PVC conduit 4 sq mm single core flexible copper wire of green colour with 25 mm dia PVC conduit Equipotential bar of 500 x 25 x 3 mm Cu strip TOTAL OF SECTION - 12 SECTION - 13 LIGHT FIXTURE mtr mtr mtr mtr mtr mtr mtr 100.00 100.00 100.00 150.00 100.00 150.00 50.00

9.1

MR

9.1.1 9.1.2 9.1.3 9.1.4 9.1.5 9.1.6 9.1.7

MR MR MR MR MR MR MR

9.2

MR

kg

2,000.00

10.1

MR

nos

5.00

10.2

MR

nos

5.00

10.3

MR

nos

5.00

11.1

MR

set

1.00

11.2

MR

nos.

1.00

12.1 12.2 12.3 12.4

MR MR MR MR

mtr mtr mtr mtr

50.00 50.00 100.00 10.00

PAGE : 11/18 M/s. HIREN A GANDHI & ASSOCIATES. M/s.TRANSENERGY ELECTRICAL CONSULTANTS.

Sr. No

SOR NO

ITEM

UNIT

COST MATRIAL Rs.Ps.

COST LABOUR Rs.Ps.

TOTAL FOR 2008-2009 Rs.Ps.

QTY.

AMOUNT Rs.

13.0

MR

Supply 'Installation, testing & commissioning of standard light fittings and lighting accessories including lamp.The scope shall include, providing of all hardware such as nuts,anchor fastners, bolts, screws, cleats, clamps, PVC insulated wires / cables from Junction box to lighting fixtures, ball and socket 'arrangement with J.B., suspension conduit pipe for drop for flourescent fitting The cost for supports (wire ropes etc) shall be included in the cost. Contractor shall use Aluminium blanking foils for fixtures where by spilage of lights shall be visible through AC duct. All fixtures shall be with APFC type electronic ballasts of less than 10% THD content of intellux / Atco / Vossloh make. All fixtures shall be with high lumen output lamps of Osram / Philiphs / GE. All fixtures shall be of either Philips / Wipro / Artlite make for cat nos depicted below of one make as per approval (cost shall be included ballast and lamp) Surface mounted bottom opeanable type 2 x 36 W CFL fixture CRFQ11236/P5 or approved equivalent Surface mounted 150W metal halide integral type fixture at 5 mtr height -FADR1215IH (CA) or approved equivalent. Surface mounted 1 x 18 W CFL Brick light fixture - LSTA 10 BLUE LED or approved equivalent Surface mounted 2 x 26 W CFL fixture DDLH226/B8 or approved equivalent Step Light - ARTLITE CAT. NO - RL 11370/T or approved equivalent Surface mounted bottom opeanable type 2 x 42 W CFL fixture ARTLITE CAT. NO - RL - 2400 or approved equivalent without Ballast Supply and fixing of 1 x 20 W FL T/L self contained emergency light with dry type maintenance free battery. TOTAL OF SECTION - 13 SECTION - 14 LT PANELS Design, manufacture, supply, storing, inspection, handling, assembling, installation in correct alignment, position, effecting proper connections,testing and commissioning of 14 SWG CRCA sheet steel fabricated cubical type Main L.T. class - IP 52, Painting by one coat of red oxide primer with two coats of approved synthetic enamel paint complete with top/bottom removable gland plates, as required, double compression type cable glands, earth bus, hinged and lockable doors to achieve dust and vermin proof complete with all inter connections small wiring by min. 2,5 sq.mm copper wires, ckt labels etc.- In case of any discrepancies in SLD and BOQ, SLD shall be considered final. The Copper Bus Bar shall be of suitable length, 500 volts, 3 phase 50 Hz TPN, electrolic aluminium as per IS 8623. The instrument chamber shall be separate and shall comprise of flush type ammeter, voltmeter, selector switches, CT's, PT's, etc. (Switchgears Make : Schneidder/ Siemens / ABB ) Main L.T. Panel Incoming- all reases microprosser based 2 nos 1200A Four Pole, EDO ACB with microprocessor based release, over voltage protections, 50 KA Breaking Capacity with all standard accessories i.e. auxillary switch with 4NO + 4NC contacts, cradle, handle, safety shutter in confirmity with IS:13947-2 with O/L, S/C, U/V and E/F releases. (Incomer from Transformer & DG set side only space) Both the incomers shall be mechanically and electrically interlocked. All Incoming ACB/MCCB shall have multi function meter (EM6400 of conzerv or equivalent) All Outgoing MCCB shall have multi function meter (EM6436 of conzerv or equivalent)
PAGE : 12/18

13.1 13.2 13.3 13.4 13.5 13.6

MR MR MR MR MR MR

Nos Nos Nos Nos Nos Nos

345.00 10.00 25.00 635.00 20.00 125.00

MR 13.7

nos

2.00

14.0

14.1.1

M/s. HIREN A GANDHI & ASSOCIATES.

M/s.TRANSENERGY ELECTRICAL CONSULTANTS.

Sr. No

SOR NO

ITEM C.T. shall be of 15VA class 1 type and shall be resin cast type 3 nos. phase LED type indicating lamps; each lamp shall have one toggle switch backed up with HRC fuse on incommer & outgoing. 3 nos. indicating LED lamp on each incomer & outgoing feeder for indicating the status of feeder.(ON /OFF/TRIP) Incomer panels shall be suitable for terminating suitable nos. 3.5 core armoured aluminium cable entry. 1200 AMP. 415 Volts, 3 phase 50 Hz FP Copper bus bars of suitable length - Current ratio shall be 1 sq mm = 1.2 A Outgoing 1 nos 630A FPMCCB, 35 KA with electronic releases. 2 nos 400A FP MCCB, 35 KA with electronic releases. 3 nos 300A FP MCCB, 25 KA with electronic releases. 2 nos 200A FPMCCB, 25 KA with electronic releases. 1 nos 150A FPMCCB, 25 KA with thermal magnetic adjustable releases. 3 nos 100A FPMCCB, 16 KA with thermal magnetic adjustable releases. 2 nos 63A FP MCCB, 16 KA with thermal magnetic adjustable releases. Sub total APFCR panel (300KVAR) Incoming-all reases microprosser based 1No 630A TP, 50KA, MCCB, with O/L, S/C, S/T, 630A TP CU Busbar. 50KA 1 set of phase Indicating lamps 1No. Ammeter with CTs & 1No. Voltmeter 1No. 10Stage APFC relay with Auto - Manual Switch. (APFC CT input from Main Panel at substation ). Feeders of 50+15 KVAR shall be fixed type capacitor feeders bypassed from APFCR. Outgoing-all reases microprosser based 125A TP MCCB with TP capacitor duty contactors and indicating lamps auto manual selector switch and 50 Kvar Capacitor banks - 2 nos 100A TP MCCB with TP capacitor duty contactors and indicating lamps auto manual selector switch and 25 Kvar Capacitor banks - 3 nos 63A TP MCB with TP capacitor duty contactors and indicating lamps auto manual selector switch and 15 Kvar Capacitor banks -2 nos 40A TP MCB with TP capacitor duty contactors and indicating lamps auto manual selector switch and 10 Kvar Capacitor banks - 2 nos Sub total Raw Power panel Incoming 1 nos. 400Amp FP MCCB, 35 KA with thermal magnetic releases. All Incoming MCCB shall have digital Ammeter / Voltmeter with inbuilt selector switch C.T. shall be of 15VA class 1 type and shall be resin cast type 3 nos. phase LED type indicating lamps; each lamp shall have one toggle switch backed up with HRC fuse on incommer & outgoing. 3 nos. indicating LED lamp on each incomer feeder for indicating the status of feeder. Incomer panels shall be suitable for terminating suitable nos. 3.5/4 core armoured aluminium cable entry as required. 400 AMP. 500 Volts, 3 phase 50 Hz FP Copper bus bars of suitable length - Current ratio shall be 1 sq mm = 1.2 A Outgoing-

UNIT

COST MATRIAL Rs.Ps.

COST LABOUR Rs.Ps.

TOTAL FOR 2008-2009 Rs.Ps.

QTY.

AMOUNT Rs.

MR 14.1.2

Each

1.00

MR 14.1.3

Each

1.00

PAGE : 13/18 M/s. HIREN A GANDHI & ASSOCIATES. M/s.TRANSENERGY ELECTRICAL CONSULTANTS.

Sr. No

SOR NO

ITEM 3 no. 125A FP MCB, C curve 16KA with thermal magnetic releases. 18 no. 63A FP MCB, C curve 10KA with thermal magnetic releases. Sub total Lighting Power panel Incoming-all reases microprosser based 1 nos. 300Amp FP MCCB, 25 KA with electronic releases. All Incoming MCCB shall have digital Ammeter / Voltmeter with inbuilt selector switch C.T. shall be of 15VA class 1 type and shall be resin cast type 3 nos. phase LED type indicating lamps; each lamp shall have one toggle switch backed up with HRC fuse on incommer & outgoing. 3 nos. indicating LED lamp on each incomer feeder for indicating the status of feeder. Incomer panels shall be suitable for terminating suitable nos. 3.5/4 core armoured aluminium cable entry as required. 300 AMP. 500 Volts, 3 phase 50 Hz FP Copper bus bars of suitable length - Current ratio shall be 1 sq mm = 1.2 A Outgoing 18 no. 40A FP MCB, C curve 10KA with thermal magnetic releases. Sub total UPS Power panel Incoming 1 nos. 300Amp FP MCCB, 35 KA with electronic releases. All Incoming MCCB shall have digital Ammeter / Voltmeter with inbuilt selector switch C.T. shall be of 15VA class 1 type and shall be resin cast type 3 nos. phase LED type indicating lamps; each lamp shall have one toggle switch backed up with HRC fuse on incommer & outgoing. 3 nos. indicating LED lamp on each incomer feeder for indicating the status of feeder. Incomer panels shall be suitable for terminating suitable nos. 3.5/4 core armoured aluminium cable entry as required. 300 AMP. 500 Volts, 3 phase 50 Hz FP Copper bus bars of suitable length - Current ratio shall be 1 sq mm = 1.2 A Outgoing 15 no. 63A FP MCB, C curve 10KA with thermal magnetic releases. Sub total Utility Power panel Incoming 1 nos. 100Amp FP MCCB, 16 KA with thermal magnetic releases. All Incoming MCCB shall have digital Ammeter / Voltmeter with inbuilt selector switch C.T. shall be of 15VA class 1 type and shall be resin cast type 3 nos. phase LED type indicating lamps; each lamp shall have one toggle switch backed up with HRC fuse on incommer & outgoing. 3 nos. indicating LED lamp on each incomer feeder for indicating the status of feeder. Incomer panels shall be suitable for terminating suitable nos. 3.5/4 core armoured aluminium cable entry as required. 100 AMP. 500 Volts, 3 phase 50 Hz FP copper bus bars of suitable length - Current ratio shall be 1 sq mm = 1.2 A Outgoing 2 no. 63A FP MCB, C curve 10KA with thermal magnetic releases.

UNIT

COST MATRIAL Rs.Ps.

COST LABOUR Rs.Ps.

TOTAL FOR 2008-2009 Rs.Ps.

QTY.

AMOUNT Rs.

MR 14.1.4

Each

1.00

MR 14.1.5

Each

1.00

MR 14.1.6

Each

1.00

PAGE : 14/18 M/s. HIREN A GANDHI & ASSOCIATES. M/s.TRANSENERGY ELECTRICAL CONSULTANTS.

Sr. No

SOR NO

ITEM 3 no.40A FP MCB, C curve 10KA with thermal magnetic releases. 2 no.25A FP MCB, C curve 10KA with thermal magnetic releases. 1 no. 20A FP MCB, C curve 10KA with thermal magnetic releases. Sub total Lift panel Incoming 1 nos. 100Amp FP MCCB, 16 KA with thermal magnetic releases. All Incoming MCCB shall have digital Ammeter / Voltmeter with inbuilt selector switch C.T. shall be of 15VA class 1 type and shall be resin cast type 3 nos. phase LED type indicating lamps; each lamp shall have one toggle switch backed up with HRC fuse on incommer & outgoing. 3 nos. indicating LED lamp on each incomer feeder for indicating the status of feeder. Incomer panels shall be suitable for terminating suitable nos. 3.5/4 core armoured aluminium cable entry as required. 100 AMP. 500 Volts, 3 phase 50 Hz FP Copper bus bars of suitable length - Current ratio shall be 1 sq mm = 1.2 A Outgoing 5nos. 63A FP MCB, C curve 10KA with thermal magnetic releases. 5 nos.25A DP MCB, C curve 10KA with thermal magnetic releases. Sub total External Lighting panel Incoming 1 nos. 63Amp FP MCCB, 16 KA with thermal magnetic releases. All Incoming MCCB shall have digital Ammeter / Voltmeter with inbuilt selector switch C.T. shall be of 15VA class 1 type and shall be resin cast type 3 nos. phase LED type indicating lamps; each lamp shall have one toggle switch backed up with HRC fuse on incommer & outgoing. 3 nos. indicating LED lamp on each incomer feeder for indicating the status of feeder. 63A FP Digital 7day 24Hrs Programable timer with suitable contactor. Incomer panels shall be suitable for terminating suitable nos. 3.5/4 core armoured aluminium cable entry as required. 63 AMP. 500 Volts, 3 phase 50 Hz FP copper bus bars of suitable length - Current ratio shall be 1 sq mm = 1.2 A Outgoing 4no. 25A FP MCB, C curve 10KA with thermal magnetic releases. 3 no.16A DP ELMCB,100mA, C curve 10KA Sub total TOTAL OF SECTION - 14

UNIT

COST MATRIAL Rs.Ps.

COST LABOUR Rs.Ps.

TOTAL FOR 2008-2009 Rs.Ps.

QTY.

AMOUNT Rs.

MR 14.1.7

Each

1.00

MR 14.1.8

Each

1.00

MR

Each

1.00

15.1 15.2 15.3 15.4 15.5 15.6

MR MR MR MR MR MR

SECTION - 15 TELEPHONE / COMPUTER NETWORKING Supply, Installation testing and commissioning of 500 nos pair telephone tag block for commercial. Supply, Installation testing and commissioning of 60 pair nos telephone tag block. Supply, Installation testing and commissioning of 50 pair nos telephone tag block. Supply, Installation testing and commissioning of 20 pair nos telephone tag block. Supply, Installation testing and commissioning of 10 pair nos telephone tag block. Supply, Laying of 300 pair 0.5 mm dia jelly filled mtr armoured telephone cable
PAGE : 15/18

1.00 3.00 7.00 1.00 5.00 100.00

M/s. HIREN A GANDHI & ASSOCIATES.

M/s.TRANSENERGY ELECTRICAL CONSULTANTS.

Sr. No 15.7

SOR NO MR

ITEM Supply, Laying of Cat 6 computer wire in prelaid conduit/ raceway for data and voice Supply, Installation testing and commissioning of GI / Al floor raceway of 100 x 38 mm of 1.6 mm thickness including cutting of civil works if required. - MK UMDX 100/1/6 or approved equivalent Supply, Installation testing and commissioning of GI / Al floor raceway vertical access junction box of 300 x 200 x 50 mm equivalent to MK make - Cat no EVB 300/2 Supply, Installation testing and commissioning of GI / Al floor raceway outlet junction box of 300 x 300 x 65-70 mm approved equivalent to MK make - Cat no ESB 300/3/ GIE Supply, Installation testing and commissioning of GI / Al floor raceway cross over junction box of 300 x 300 x 6075 mm approved equivalent to MK make - Cat no EJB 300/3 TOTAL OF SECTION - 15 SECTION - 16 LIGHTNING PROTECTION SYSTEM SITC of Lightening protection system with early Streamer Emmision (ESE), technology, having a coverage range up to 58 mtr.(Level 1) when mounted at a height of 5 mtrs with Down Conductor & mounting structure as per specifications. Nimbus CPT-2, make :CIRPROTECT, Spain or approved equivalent SITC of Lightening Discharging Counter to verify the lighting discharge occurrence. SITC of Chemical type of earthing for maintenance free, 3mtr long and 40 mm dia, operation for a period of 7 yrs maintenance free earthing system TOTAL OF SECTION - 16 SECTION -17 FIRE ALARM SYSTEM SITC of Intelligent Addrressable Photoelectric Smoke Detectors with built in Isolators. The Detectors should be micro-proccessor based with inbuilt algorithm to distinguish and differenciate between real fire, steam and dust to avoid any false alarm. All the detectors should have a common base in case of future arrangements of the following combination such as: (Smoke+Sounder), (Smoke+Sounder +Flasher), (Smoke+Sounder+Flasher+Evacutation Speaker). The detectors should have VDS approvals & certification.Note: The certification should be for the complete system and not for an individual product. SITC of Addressable Manul Pull Station with built in Isolators.It should have VDS approvals & certification.Note: The certification should be for the complete system and not for an individual product SITC of Intelligent Addrressable Photoelectric Smoke Detector with Sounder, Strobe, Speaker and built in Isolators . The Detectors should be microproccessor based with inbuilt algorithm to distinguish and differenciate between real fire, steam and dust to avoid any false alarm. All the detectors should have a common base in case of future arrangements of the following combination such as: (Smoke+Sounder), (Smoke+Sounder +Flasher), (Smoke+Sounder+Flasher+Evacutation Speaker). The detectors should have VDS approvals & certification.Note: The certification should be for the complete system and not for an individual product SITC of Response Indicator For Detectors SITC of Intelligent Adressable Control Modules as per specifications

UNIT mtr

COST MATRIAL Rs.Ps.

COST LABOUR Rs.Ps.

TOTAL FOR 2008-2009 Rs.Ps.

QTY. 20,000.00

AMOUNT Rs.

15.8

MR

nos

3,000.00

15.9

MR

nos

14.00

15.10

MR

nos

350.00

15.11

MR

nos

20.00

16.1

MR

nos.

1.00

16.2 16.3

MR MR

nos. nos.

1.00 2.00

17.1

MR

nos

283.00

17.2

MR

nos

8.00

17.3

MR

nos

34.00

17.4 17.5

MR MR

nos nos

170.00 2.00

PAGE : 16/18 M/s. HIREN A GANDHI & ASSOCIATES. M/s.TRANSENERGY ELECTRICAL CONSULTANTS.

Sr. No

SOR NO

ITEM SITC of 4 Loop Analogue Intelligent Addressable Fire Alarm control Panel with 127 devices per loop (Expandable to 7 loops). The Panel should recognise all the detectors and ancillary soft address and register the same inside the Non Volatile Memory. The Panel should be capable to drive a loop lenght of 3.5 Km without any conventional power supply to any of the devices fitted in the loop. The panel should deliver an automatic signal to the neccessary detectors to play the evacuation / caution message incase of emergency. The panel should have all the functions and display as per the NFPA guidelines and can be networked into a group of panels incase of future expansion. It should store atleast 100000 events in its memory. The panel should be able to scrutinise each detectors and display a report regarding thier health, maintenance and replacement. The panel should generate an automatic report incase if any detectors needs to be replaced or serviced. The Panel should have VDS approvals & certification.Note: The certification should be for the complete system and not for an individual product. SITC of Beam Detector,Combined transmitter and receiver unit,Unique servo-operated test filter,Range 5 100 metres,4 x fixed sensitivity/threshold levels,2 x automatic variable sensitivity modes,Operates in the Infra-Red light spectrum,Numerical indicators to aid beam alignment,Standby, fault and alarm LED indicators visible from the front and bottom,10 horizontal and vertical beam alignment,Automatic drift compensation,Complies to EN54 12:2002 (Amendment 1) SITC of 2 core 1.5 sqr mm. Copper Armoured cable with junctions & saddles complete as required TOTAL OF SECTION - 17 SECTION - 18 CCTV SYSTEM SITC of Fixed Dome Camera 1/3" CCD with 500 TV lines and Low Light Sensitivity of 0.5lux colour camera with dome type housing to mount them. SITC of Day and night varifocal high resolution camera 1/3" CCD camera with 500 TVL with auto iris veri focal lens 3.5mm-8mm SITC of 16CH Standalone Digital Video Recorder with MPEG4 compression format, superior real time performance with 480 IPS (NTSC) / 400 IPS (PAL), longer recording time via independent disk array, USB backup function, advance motion trigger recording, and pentaplex functions with 500GB hard Disk SITC of 12Vdc/500mA power supply units with overload & short-circuit protection for cameras. SITC of 17"Flat Colour Lcd monitor,TFT active matrix SXGA LCD,Resolution:1280 x 1024,Fh: 30-80kHz, Fv: 50-85Hz,8 ms,VGA (HD-15),280 cd/m2, Contrast ratio:600:1,Horizontal:170,Vertical:155 SITC of Co-axial RG-6 Cable with 2 core 1.5 sqr mm with 19/25 MM Conduits,junctions,saddles & accessries complete as required TOTAL OF SECTION - 18 SECTION - 19 ACCESS CONTROL SYSTEM Supply, installation, testing and commissioning of Proximity card readers Supply, installation, testing and commissioning of 4Door Controller,Support multiple proximity, keypad, biometric, smart card and RS485/WiegandReader, Embedded control unit to support working under off-line condition withcomputer,Capability of connecting external backup power supply for emergency,Auto detects reader on-line status.

UNIT

COST MATRIAL Rs.Ps.

COST LABOUR Rs.Ps.

TOTAL FOR 2008-2009 Rs.Ps.

QTY.

AMOUNT Rs.

17.6

MR

nos

1.00

17.7

MR

nos

2.00

17.8

MR

mtr

5,000.00 -

18.1

MR

nos

38.00

18.2

MR

nos

2.00

18.3

MR

nos

3.00

18.4

MR

nos

40.00

18.5

MR

nos

3.00

18.6

MR

mtr

4,000.00

19.1

MR

nos

16.00

19.2

MR

nos

2.00

19.3

MR

Supply, installation, testing and commissioning of Electro Magnetic Latches

nos
PAGE : 17/18

16.00

M/s. HIREN A GANDHI & ASSOCIATES.

M/s.TRANSENERGY ELECTRICAL CONSULTANTS.

Sr. No

SOR NO

ITEM Providing and installing ACCESS & ATTENDANCE Software for controller and The software shall also be common for all Controller. Supply, installation, testing and commissioning of Proximity cards with Frontside Four Color Printing & Back side monochrome printing with YOYO or Card holder & Printed Ribbons as required SITC of CAT-5E Cable & 2-Core 1.5 sq mm Cable with 19/25 MM Conduits,junctions,saddles & accessries complete as required TOTAL OF SECTION - 19 SECTION - 19 CONFERENCE SYSTEM SITC of Wall Mount Swivel Bracket Speakers with tweeter and built in line matching transformer. 100/70 V line input,15/30 watt output. SITC of Delegate Microphone Unit with Digital Control and Condenser Microphone with replaceable wind cover.Microphone head with red ring indicator with speech switch key & volume control power-off function SITC of Chairman Microphone Unit do-as-above with Priority Speech Function priority music chime,free from any restriction and Chairman only mode SITC of Digital Conference Control Unit can connect to 128 Microphones upto 4096 units can be connect in series and shall be capable of connecting upto 5 translation unit,Line in for BGM or Phone signal input & Line out for tape recording or audio amplification system with built in equalizer & frequency shifter with Automatic Camera Follow Function & Voting and Data management function SITC of 250 Watts Amplifier with 6-Channel outputs & Individual Volume Control for each channel,2Mic,3-Aux Inputs,Chime & Mute Function,Shortcircuit,Over-current & Over-load Protection SITC of Oxygen Free Flat Speaker Cable Size 70X76 Dia with 19/25 MM Conduits,junctions,saddles & accessries complete as required TOTAL OF SECTION - 19 TOTAL OF PART - B GRAND TOTAL (PART - A + PART - B)

UNIT

COST MATRIAL Rs.Ps.

COST LABOUR Rs.Ps.

TOTAL FOR 2008-2009 Rs.Ps.

QTY.

AMOUNT Rs.

19.4

MR

nos

1.00

19.5

MR

nos

100.00

19.6

MR

mtr

1,500.00

20.1

MR

nos

14.00

20.2

MR

nos

127.00

20.3

MR

nos

4.00

20.4

MR

nos

2.00

20.5

MR

nos

1.00

20.6

MR

mtr

1,500.00

PAGE : 18/18 M/s. HIREN A GANDHI & ASSOCIATES. M/s.TRANSENERGY ELECTRICAL CONSULTANTS.