Geist Manufacturing 1821 Yolande Ave., Lincoln, NE 68521 800.432.3219 | 402.474.3400 | F: 402.474.4369 | www.geistmfg.com
GM1021 1 Revision Date: 5/30/08
Contents
___________________________
Installation3 XP Series ZP Series Specifications4 Environmental Electrical Plug Ratings Receptacle Ratings PDU Monitoring Options..7 PM-1 (Power Meter, Current Meter) PM-3 (3 Phase Current Meter) EM (Local + Remote Current Meter) Ethernet Meter Instructions...8 Setting an IP Address Viewing/Resetting IP Local Display SNMP/XML Firmware Updates Technical Support..10
GM1021
800-432-3219
www.geistmfg.com
Installation
Permanently Connected PDU 1. Using appropriate hardware, mount PDU in rack or enclosure. 2. Apply proper strain relief to PDU. 3. Connect PDU into appropriately rated and protected branch circuit according to local codes, Note internal wiring of PDU is labeled. (A = Red Wire, B = Black Wire, C = Blue Wire, Ground = Green/Yellow Wire). 4. Connect devices into power outlets on PDU. 5. Turn on branch circuit energizing PDU. 6. Power on devices. Sequential power-up is recommended to avoid high inrush current. NOTE: Permanently connected equipment requires an accessible disconnect device in the building installation. Plug Connected PDU 1. Using appropriate hardware, mount PDU in rack or enclosure. 2. Connect PDU into appropriately rated and protected branch circuit. 3. Connect devices into power outlets on PDU. 4. Turn on branch circuit energizing PDU. 5. Power on devices. Sequential power-up is recommended to avoid high inrush current. NOTE: Install the equipment so the input plug may be disconnected for service Installation Guidelines When installed in a closed rack, the operating ambient temperature may be greater than room ambient. Consideration should be given to installing the equipment in an environment compatible with the maximum ambient temperature of 45C. Install the equipment such that the airflow required for safe operation is not compromised. Mount the equipment so that hazardous conditions due to uneven mechanical loading do not arise. Adhere strictly to nameplate ratings when connecting equipment to the branch circuit. Avoid overloading circuits as this may damage wiring at the installation site. The equipment relies on the building installation for protection from overcurrent. A listed or certified circuit breaker is required in the building installation. A reliable ground should be maintained for all rack-mounted equipment. Particular attention should be given to supply connections other than direct connections to the branch circuit. Disconnect power to the equipment before servicing. The equipment is intended for installation in Restricted Access Locations. Only service personnel should install and access the equipment. The equipment is designed for indoor use only. Do not mount to furniture such that spilled liquid could come into contact with equipment.
GM1021
800-432-3219
www.geistmfg.com
Specifications
Environmental Specifications Elevation Operating: 0 to 10,000 ft Storage: 0 to 50,000 ft Temperature Operating: 23 to 113F Storage: -13 to 149F Humidity Operating: Storage:
Electrical Ratings See unit Name Plate for device ratings. Products are
to 60950, E214832
EMI Verification Class A digital device. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference (2) This device must accept any interference received, including interference that may cause undesired operation. Warning: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the users authority to operate this equipment. FCC requirements: Devices with the EM meter require the ferrite core shipped with the unit to be placed around the Ethernet cable close to the PDU.
GM1021
800-432-3219
www.geistmfg.com
Plug Options NEMA Type 5-15P L5-15P 5-20P L5-20P L5-30P 6-20P L6-20P L6-30P L14-20P L14-30P L15-20P L15-30P L21-20P L21-30P Calif Style 3P, 4W IEC Type IEC C-14 IEC C-20 IEC PS 2P, 3W IEC PS 3P, 4W Rating 15A, 125V 15A, 125V 20A, 125V 20A, 125V 30A, 125V 20A, 250V 20A, 250V 30A, 250V 20A, 125/250V 30A, 125/250V 20A, 250V, 3~ 30A, 250V, 3~ 20A, 120/208V, 3~ 30A, 120/208V, 3~ 50A, 250V, 3~ Rating 15A, 125/250V 20A, 125/250V 60A, 250V 60A, 250V, 3~
GM1021
800-432-3219
www.geistmfg.com
Receptacle Options NEMA Type 5-15R L5-15R 5-20R L5-20R L5-30R 6-20R L6-20R L6-30R L21-20R L21-30R IEC Type IEC C-13 IEC C-19 Rating 15A, 125V 15A, 125V 20A, 125V 20A, 125V 30A, 125V 20A, 250V 20A, 250V 30A, 250V 20A, 120/208V, 3~ 30A, 120/208V, 3~ Rating 15A, 125/250V* 20A, 125/250V
GM1021
800-432-3219
www.geistmfg.com
Power Factor
Amps
Volts
Watts
PM-1 (Current Meter) The Geist Current Meter is factory programmed to only display the Amps. The meter consumes less than 2 Watts of power and has a range of 0-30.0 Amps with +/-2% accuracy*.
Current Meter
PM-3 (3 Phase Current Meter) The new PM-3 is a RMS 3 Circuit Ammeter that scrolls between 3 circuits and displays the Amps of each. Units are marked with circuit labels to identify the corresponding receptacles and breakers for each circuit. The meter consumes less than 2 Watts of power and has a range of 030.0 Amps with +/-2% accuracy*.
EM (Local + Remote Current Meter) The EM is a Web-enabled RMS Ammeter with the ability to display Amps locally and remotely over Ethernet. The meter consumes less than 5 Watts of power and has a range of 0-120.0 Amps with +/-2% accuracy*.
GM1021
800-432-3219
www.geistmfg.com
Typical Network Card Settings for PC or Laptop to connect to default IP address *In some configurations, leaving the gateway field blank may resolve connectivity issues.
GM1021
800-432-3219
www.geistmfg.com
LED Display
Each PDU has a built-in 4-digit LED display mounted midway down the chassis. The display scrolls through the most recent current measurement (in amps) for each circuit, one at a time. It displays a circuit name, pauses, and then displays the measurement. Momentarily press the Pause Scroll/IP Address Reset button on the front of the PDU to pause the display on the current measurement. While paused, the display will cycle back and forth between circuit name and current reading every three seconds. Momentarily pressing the Pause Scroll/IP Address Reset button again will skip ahead to the next circuit. The display will begin to scroll again thirty seconds after the last button push. NOTES: During the first cycle after the display has been paused, the display may take up to six seconds to display a measurement.
GM1021
800-432-3219
www.geistmfg.com
Due to the time required to measure current accurately, the same reading may be shown twice while the display is paused. For reference: Cr-1 = Circuit 1 Cr-2 = Circuit 2 Cr-3 = Circuit 3 Cr-4 = Circuit 4 Cr-5 = Circuit 5 Cr-6 = Circuit 6 Ph-A = Phase A Ph-b = Phase B Ph-C = Phase C nEUt = Neutral Fd-A = Feed A Fd-B = Feed B
Web Page
The main interface to the PDU is its web page, accessible by typing the units IP address into a web browser. On the web page is the most up to date measurement of each circuit. All measurements are in Amps.
SNMP/XML
In addition to HTML based web pages, the PDU presents its data via SNMP and an XML page. To use the PDU with SNMP Client software, download the MIB from the link on the units web page and import it into the SNMP software. Contact the client software manufacturer for instructions specific to their software. The PDUs SNMP community comes preset to public. To change this, go to the Configuration page, enter a new name in the SNMP Community box and hit Save Changes. In addition SNMP traps can be utilized to monitor a user set threshold for each circuit, alarm settings and SNMP server settings are located on the Configuration page. The XML page provides terse output that is easily parsed by both humans and computers and is useful for creating scripts to download and process information off the unit automatically. The XML page is available at http://<IP address of meter>/data.xml. Sample uses of XML and SNMP data are provided Sample Usage section of this document.
Firmware Updates/Instruction
The unit firmware is field upgradeable via ftp. Firmware Updates and Instructions are available at the following website.
GM1021
10
800-432-3219
Unix/Linux Command Line Example: wget http://192.168.123.123/data.xml This command will download data.xml into the current directory. At this point, the file is ready to be used by any local application or script. SNMP Example Getif is a simple, free SNMP viewer for Windows available from: http://www.wtcs.org/snmp4tpc/getif.htm 1. 2. Drop the EM meters MIB file into Getifs MIBs directory (Typically C:\Program Files\Getif 2.3.1\MIBs) and start Getif. Type in the units IP address into the box labeled Host Name and click the Start button.
3. 4.
Click the MBrowser tab and expand the .iso tree down to geistmfg. Select geistmfg and click the Start button. Getif should start requesting data from the unit via SNMP and display it in the large box at the bottom of the window.
GM1021
11
800-432-3219
Technical Support
http://www.geistmfg.com (800) 432-3214 Email: support@geistmfg.com