Benefits and advantages.................................................................................................. 200
Application......................................................................................................................... 201
Approvals and marks........................................................................................................ 201

Ordering details
Analog standard signal converters
CC-E/STD, CC-E x/x.................................................................................................... 202
CC-E I/I......................................................................................................................... 203
CC-U/STD..................................................................................................................... 204
CC-U/STDR.................................................................................................................. 205
Temperature signal converters for RTD sensors
CC-E/RTD..................................................................................................................... 206
CC-U/RTD..................................................................................................................... 207
CC-U/RTDR.................................................................................................................. 208

5
Temperature signal converters for thermocouples
CC-E/TC....................................................................................................................... 209
CC-U/TC....................................................................................................................... 210
CC-U/TCR..................................................................................................................... 211
Measuring converters for currents (E/I) and (U/I) and voltages (U/V)
CC-E/I........................................................................................................................... 212
CC-E IAC / ILPO............................................................................................................. 213
CC-U/I........................................................................................................................... 214
CC-U/V.......................................................................................................................... 215
Accessories................................................................................................................... 216
Technical data
CC-E/STD, CC-E x/x, CC-E/RTD, CC-E/TC................................................................. 217
CC-E I/I......................................................................................................................... 218
CC-U/STD, CC-U/RTD, CC-U/TC................................................................................ 219
CC-U/STDR, CC-U/RTDR, CC-UTCR.......................................................................... 220
CC-E/I, CC-E IAC / ILPO................................................................................................ 221
CC-U/I, CC-U/V............................................................................................................ 222
Technical diagrams.............................................................................................................. 223
Dimensional drawings......................................................................................................... 223

ABB 199
2CDC110004C0205
Analog signal converters
CC range
Benefits and advantages

2CDC 285 001 F0b05


Product range for analog signal processing
5 CC-U range CC-E range
J 8 different standard signal outputs on one device J Universally configurable devices and single-function devices
J Input and output side universally configurable J Adjustment and operating elements on the front side
J Also available with 2 threshold relay outputs J Safe operation by electrical 3-way isolation
J Adjustment and operating elements on the front side J Unambiguous and clear connecting terminal markings
J Safe operation by electrical 3-way isolation
J Plug-in connecting terminals, unambiguously and clearly mar-
Conversion, measurement and separation of
ked
J standard signals (0-5 V, 0-10 V, 0-20 mA, 4-20 mA)
J temperature signals of RTD sensors (PT 100)
Conversion, measurement and separation of
J thermocouple signals (types J and K)
J standard signals J current measurement signals (0-5 A, 0-20 A AC/DC)
J signals of RTD sensors (PT10, PT100, PT1000)
J thermocouple signals
Characteristics of single-function devices
J RMS values of currents and voltages
J No adjustment or balancing necessary.

Characteristics
Characteristics of universal devices
J The required input and output ranges can be configured for all
devices by means of directly accessible DIP switches positioned J The required input and output ranges can be configured by means
on the side. of directly accessible DIP switches positioned on the side
J Due to the wide input range of the gain and offset stages all input J Gain adjustment of ± 5 % by means of an adjustment
signals between the minimum and the maximum input value can be potentiometer on the front-side
universally converted to all common output signals. J Offset adjustment of ±5 % by means of adjustment
J Devices for DC or AC (50/60 Hz) supply available. potentiometers on the front-side
2CDC 283 016 F0b03

200 ABB
2CDC110004C0205
Analog signal converters
CC range
Application, Approvals and marks

Applications for analog signal processing and


correct solution using CC-E and CC-U 0-10 V 0-10 V

converters
Nearly every process includes a control system that receives data by Controller
means of analog signals and then evaluates the data and sets the re- 1.
e.g. AC500
2.
spective parameters correspondingly. Analog signal converter
(e.g. CC-E or CC-U)
Analog signal converter
(e.g. CC-E or CC-U)

When transmitting analog signals numerous problems may arise which


can disturb or even block an ideal behavior of the process.
100 m 0-20 mA 100 m 4-20 mA

Below we have listed some processing problems together with the Actuator

respective solutions to solve these problems: Measuring sensor

Signal conversion

2CDC 282 013 F0206


Sometimes the available signals cannot be processed by the controller
or the actuator. In this case, signal converters are required to convert
the input signal (or different input signals) to the desired output signal.

Signal amplification Signal separation


If long lines or high burdens have to be operated, it may be necessary J Protection against overvoltage
to amplify the signal. CC analog signal converters require only low in- The increased use of micro-electronics make controls much more
put power and provide high output power. sensitive against overvoltages, resulting from lightning discharges
Thus, there are no restrictions for the converter's position on the line, or switching processes. Suppression diodes are incorporated in
the input of the CC analog signal converters which enable the
i.e. it can be used converters to arrest overvoltages with low energy level (resulting
J for signal refreshing  at the end of the line from switching processes) by themselves. The products further-
(low input power) more provide electrical isolation between input, output and sup-
J or for signal amplification  at the beginning of the line
(high output power).
ply circuit for protection of the controller connected to the output.
5
J Protection against ground loops
Signal filtering If components are used which refer to ground, the measuring
Particularly on long lines or in rough industrial environments the signals signals can be falsified by a so-called ground loop. In this case,
are exposed to high electromagnetic interferences. The frequency of certain parts of the signal are transmitted via earth and not via the
the coupled interference signals may be in the range of the common analog transmission line, thus causing incorrect evaluation of the
mains frequency (50 Hz) or even much higher (in case of frequency signal. The electrical isolation between the input and the output
converters). According to the specific requirements, analog signal disconnects these ground loops and thus enables correct signal
converters are available which provide reliable suppression of those transmission.
interferences by means of an input low-pass filter.

J existing
G existing for some devices
j pending
CC-E IAC/ILPO
CC-U/RTDR
CC-U/STDR

CC-U/TCR
CC-U/RTD
CC-U/STD

CC-E/RTD
CC-E/STD

CC-U/TC
CC-E/TC
CC-E I/I

CC-U/V
CC-U/I
CC-E/I

Approvals

A UL 508, CAN/CSA C22.2 No.14 J J J J J J J J J J J J J J


UL 1604 (Class I, Div 2, hazardous locations),
A G J G J G J G J J
CAN/CSA C22.2 No.213

K CB scheme J J J

E CCC J J J
Marks
a CE J J J J J J J J J J J J J J
b C-Tick J J J J J J J J J J J J J J

ABB 201
2CDC110004C0205
Analog standard signal converters
CC-E/STD, CC-E x/x
Ordering details

CC-E/STD analog signal converter with 3-way electrical isolation


J 2 universally configurable devices (type CC-E/STD)
2CDC 281 001 F0t03

J 2x10 single-function devices


J "Plug and Work", no adjustment of single-function devices required

� Wiring instruction DIP switch settings (universal devices)


� Input Output
Switch
1 2 3 4 5 6 7 8
0...5 V
� 0...10 V
0...5 V 0...20 mA
Burden
4...20 mA
� R � 1.0 k�
0...5 V
Burden 0...10 V

2CDC 282 006 F0206


R � 500 � 0...10 V 0...20 mA
4...20 mA
CC-E/STD 0...5 V

2CDC 282 002 F0204


2CDC 282 001 F0204
0...10 V
0...20 mA 0...20 mA
supply 4...20 mA
24 V DC or 110-240 V AC 0...5 V
0...10 V Legend
4...20 mA 0...20 mA ON
2CDC 281 014 F0t04

4...20 mA OFF

Type Input signal Output signal Order code Pack. unit Price
piece 1 piece

Supply voltage: 24 V DC
universal
0-5 V, 0-10 V 0-5 V, 0-10 V
CC-E/STD 1SVR 011 700 R00001) 1
0-20 mA, 4-20 mA 0-20 mA, 4-20 mA
CC-E V/V
5 single-function

1 U: green LED - CC-E V/V 0-10 V 1SVR 011 710 R2100 1


supply voltage CC-E V/I 0-10 V 0-20 mA 1SVR 011 711 R1600 1
CC-E V/I 4-20 mA 1SVR 011 712 R1700 1
2 Gain adjustment
3 Offset adjustment CC-E I/V 0-10 V 1SVR 011 713 R1000 1
 DIP switch for input and CC-E I/I 0-20 mA 0-20 mA 1SVR 011 714 R1100 1
output configuration CC-E I/I 4-20 mA 1SVR 011 715 R1200 1
(only available on
CC-E I/V 0-10 V 1SVR 011 716 R1300 1
universal devices)
CC-E I/I 4-20 mA 0-20 mA 1SVR 011 717 R1400 1
CC-E I/I 4-20 mA 1SVR 011 718 R2500 1

CC-E V/V -10...+10 V -10...+10 V 1SVR 011 719 R2600 1

Supply voltage: 110-240 V AC


universal
0-5 V, 0-10 V 0-5 V, 0-10 V
CC-E/STD 1SVR 011 705 R2100 1
0-20 mA, 4-20 mA 0-20 mA, 4-20 mA
single-function
CC-E V/V 0-10 V 1SVR 011 720 R2300 1
CC-E V/I 0-10 V 0-20 mA 1SVR 011 721 R1000 1
CC-E V/I 4-20 mA 1SVR 011 722 R1100 1

CC-E I/V 0-10 V 1SVR 011 723 R1200 1


CC-E I/I 0-20 mA 0-20 mA 1SVR 011 724 R1300 1
CC-E I/I 4-20 mA 1SVR 011 725 R1400 1

CC-E I/V 0-10 V 1SVR 011 726 R1500 1


CC-E I/I 4-20 mA 0-20 mA 1SVR 011 727 R1600 1
CC-E I/I 4-20 mA 1SVR 011 728 R2700 1

CC-E V/V -10...+10 V -10...+10 V 1SVR 011 729 R2000 1

1)
B 1604 Class I, Div.2
(universal device) • Technical data .......................................................................... 217 • Dimensional drawings ...............................................................223

202 ABB
2CDC110004C0205
Current/current isolator
CC-E I/I-1 and CC-E I/I-2
Ordering details

Loop-powered current/current isolator without external power supply for analog


current signals of 0-20 mA and 4-20 mA
2CDC 281 001 F0b06

J Electrical isolation between input and output


J Very low internal voltage drop  2.5 V
J Available with one or two independent channels
J Width only 18 mm (1 and 2 channels)

Wiring instructions

CC-E I/I-1

Channel 1 Channel 1
CC-E I/I-1 input output

2CDC 282 003 F0205


0-20 mA or IN OUT 0-20 mA or
4-20 mA C F 4-20 mA
UL

D E
IN OUT

100 � � RL � 500 �
2CDC 281 041 F0b03

CC-E I/I-2
Channel 1 Channel 1
input output
0-20 mA or IN OUT 0-20 mA or
4-20 mA C F 4-20 mA
UL

D E
IN OUT

100 � � RL � 500 �

CC-E I/I-2 Channel 2 Chanel 2

5
input output

2CDC 282 004 F0205


0-20 mA or IN OUT 0-20 mA or
4-20 mA A H 4-20 mA
UL

B G
IN OUT
100 � � RL � 500 �

Type Input signal Output signal Order code Pack. unit Price
piece 1 piece
1 channel
CC-E I/I-1 0-20 mA, 4-20 mA 0-20 mA, 4-20 mA 1SVR 010 200 R1600 1
2 channel
CC-E I/I-2 0-20 mA, 4-20 mA 0-20 mA, 4-20 mA 1SVR 010 201 R0300 1

• Technical data .......................................................................... 218 • Dimensional drawings ...............................................................223

ABB 203
2CDC110004C0205
Analog standard signal converter
CC-U/STD
Ordering details

CC-U/STD universal signal converter with 3-way electrical isolation


J More than 120 configurations possible
2CDC 281 002 F0t03

J Configurable output signal response on input voltage signal interruption (low fail safe / high fail safe)
� J Adjustment and operating elements on the front
� J Short-circuit proof signal outputs
J Plug-in connecting terminals for inputs, outputs and supply

J Very fast signal transmission enables use in control systems


Adjustment range
� Continuously variable adjustment range:
Example ➀:
Input configuration: 0...10 V
Output configuration: -5...5 V
CC-U/STD Wiring instruction OUT [%]

100
90 Gain
“gain-coarse”
80 und
 Plug-in terminals 70
“gain-fine”

60
 Gain: Coarse adjustment 50

+ 2.5 V 40
 Gain: Fine adjustment G Pot.
Burden 30

J R � 4.7 k� 20
 Offset adjustment 10

2CDC 282 015 F0206


Burden IN [%]
 U: green LED - H R � 600 �
10 20 30 40 50 60 70 80 90 100

supply voltage Offset remote poti

 Marker label SW1.6 = +22.5 %


supply
SW1.4 = +100 %

2CDC 282 018 F0203


SW1.5 = +50 %

5 DIP switch settings

Input Switch 1 Coarse Output Switch 2


Gain Type
1 2 3 4 5 6 7 8 1 2 3 4 5 6
Potentiometer A...D C 0...5 V
0...50 mV A...D C 0...10 V
0...100 mV 4...5 5 1...5 V
0...250 mV 0...1 1 2...10 V
0...500 mV 7...9 8 -10...+10 V
0...1 V 3...4 3 -5...+5 V
0...2.5 V 0 0 -10...0 V
0...5 V 5...7 6 -5...0 V
0...10 V 2 2 0...6.66 V
1...5 V 7...9 8 -10...+3.33 V
2... 10 V 2...4 3 -5...+1.66 V
-10...+10 V 0 0 0...8 V
0...125 mV 3...4 3 0...4 V
0...8 V 3...4 3 -10...-2 V
-22.5...+22.5 mV B...F D -5...-1 V
-11...+11 V 0 0 1.25...6.25 V
2.5...7.5 V 5...7 6 -7.5...+2.5 V
3.33...9.99 V 3...4 4 -3.75...+1.25 V
10...0 V 2 2 1.66...8.33 V
100...0 mV 4...5 5 -6.66...+6.66 V
0...1 mA A...D B -3.33...+3.33 V
0...20 mA 2...4 3 -8...0 V
4...20 mA 4...5 4 -4...0 V
10...50 mA 0...1 1 0...1 mA
2CDC 282 019 F0203

20...4 mA 4...5 4 0...20 mA


20...0 mA 4...2 3 4...20 mA
-0.45...+0.45 mA B...F D 0...10 mA
-55...+55 mA 4...6 5 0...0.5 mA
High fail safe *) - - 0...13.33 mA
Low faile safe *) - - 0...666 µA
No fail safe *) - - 0...16 mA
0...800 µA
0...8 mA
0...400 µA
2CDC 282 003 F0204
2CDC 282 020 F0203

2.5...12.5 mA
*) Detection of input voltage signal interruptions: 125...625 µA
3.33...16.66 mA
If the input signal circuit is interrupted, the output signal changes to the 166...833 µA Legend
adjusted minimum value (low fail safe) or maximum value (high fail safe). 0.2...1 mA ON
If "No fail safe" is configured, input signal interruptions are not detected. 2...10 mA OFF
100...500 µA no influence

Type Rated supply voltage Order code Pack. unit Price


pieces 1 piece

CC-U/STD 24-48 V DC 1SVR 040 000 R1700 1


110-240 V AC 1SVR 040 001 R0400 1

• Accessories . ............................................................................ 216 • Technical data ...........................................................................219


• Dimensional drawings .............................................................. 223

204 ABB
2CDC110004C0205
Analog standard signal converter
CC-U/STDR with relay output
Ordering details

CC-U/STDR universal signal converter for standard signals, with 2 threshold relay
outputs and with 3-way electrical isolation
2CDC 281 003 F0t03

J Standard signal converter with 7 setting ranges



J 2 threshold relay outputs with one c/o contact each (threshold and respective hysteresis can be ad-
� justed independently from each other)
� J Open-circuit or closed-circuit principle configurable by means of a DIP switch
� J 2 yellow LEDs for clear status indication of the output relays
� J Plug-in connecting terminals for inputs, outputs and supply

� Wiring instruction Function diagrams

� Value R1

Closed-circuit principle
R1 Threshold value

CC-U/STDR Threshold Hysteresis


R1 Hysteresis

Temperature

R2 Hysteresis

2CDC 282 044 F0203


R2 Threshold value

2CDC 282 016 F0206


 Plug-in connecting Value R2
terminals 11-14
R1 11-12
21-24
R2 21-22
 Threshold value for R1
supply
 Hysteresis for R1
 Threshold value for R2
 Hysteresis for R2 DIP switch settings
Open-circuit principle

 U: green LED - Input


Switch 1 R1 Threshold value
R1 Hysteresis
1 2 3 4 5 6
supply voltage 0...0 V Temperature
0...5 V
 R2: yellow LED - 0...1 V R2 Hysteresis

2CDC 282 046 F0203


R2 Threshold value
-10...+10 V
Relay 2 energized
2CDC 282 003 F0204
2CDC 282 005 F0204

1...5 V
0...20 mA
 R1: yellow LED - 4...20 mA
11-14
R1 11-12

5
Legend
Relay 1 energized Output
ON
21-24
R2 21-22

Closed-circuit principle OFF


 Marker label Open-circuit principle no influence

Switching points
Switching points of the output relay depending on the input range,
configuration open-circuit principle
IN [%]

100
ue l

90
va
al

Threshold value R1
tu
Ac

2-100 % 80
Hysteresis R1
of input range
5-50 % of
70 threshold
value R1
60

50

40
Threshold value R2
Hysteresis R2
2-100 % 30
of input range 5-50 % of
threshold
20 value R2

10

0
2CDC 282 021 F0203

OUT

R1 11-14
11-12

21-24
R2 21-22

Type Rated supply voltage Order code Pack. unit Price


pieces 1 piece

CC-U/STDR 24-48 V DC 1SVR 040 010 R0000 1


110-240 V AC 1SVR 040 011 R2500 1

• Accessories . ............................................................................ 216 • Technical data ...........................................................................220


• Technical diagrams .................................................................. 223 • Dimensional drawings ...............................................................223

ABB 205
2CDC110004C0205
Temperature signal converter for RTD sensors
CC-E/RTD
Ordering details

CC-E/RTD temperature signal converter for RTD sensors, linearized with 3-way
electrical isolation
2CDC 281 004 F0t03

J 2 universally configurable devices (type CC-E/RTD)


J 2x12 single-function devices
J "Plug and Work", no adjustment of single-function devices required
� J Temperature signal converter for PT100 sensors
J 2- or 3-wire connection
� DIP switch settings (universal devices)
� Switch 1
Wiring instruction Input Output 1 2 3 4 5 6
� 0...10 V
0...100 °C 0-20 mA
4-20 mA
0-10 V
0...300 °C 0-20 mA
G 4-20 mA
Burden 0-10 V
CC-E/RTD R � 1.0 k� 0...500 °C 0-20 mA
H 4-20 mA
Burden

2CDC 282 007 F0206


0-10 V
J R � 500 � -50...+50 °C 0-20 mA
4-20 mA
 Gain adjustment 0-10 V

2CDC 282 003 F0204


2CDC 282 006 F0204
-50...+250 °C 0-20 mA
 Offset adjustment supply
4-20 mA
0-10 V
24 V DC or 110-240 V AC
 U: green LED - -50...+450 °C 0-20 mA
4-20 mA
Legend
ON
supply voltage High fail safe OFF
Low fail safe no influence
 DIP switch for input
and output configuration Type Input signal Output signal Order code Pack. unit Price
(only available on universal piece 1 piece
devices)
Supply voltage: 24 V DC
universal
0-10 V, 0-20 mA,
CC-E/RTD refer to table 1SVR 011 701 R25001) 1
4-20 mA

5 single-function
CC-E RTD/V 0-10 V 1SVR 011 730 R2500 1
PT100
CC-E RTD/I 0-20 mA 1SVR 011 731 R1200 1
0...100 °C
CC-E RTD/I 4-20 mA 1SVR 011 732 R1300 1
CC-E RTD/V 0-10 V 1SVR 011 733 R1400 1
PT100
CC-E RTD/I 0-20 mA 1SVR 011 734 R1500 1
-50...+50 °C
CC-E RTD/I 4-20 mA 1SVR 011 735 R1600 1
CC-E RTD/V 0-10 V 1SVR 011 736 R1700 1
PT100
CC-E RTD/I 0-20 mA 1SVR 011 737 R1000 1
0...300 °C
CC-E RTD/I 4-20 mA 1SVR 011 738 R2100 1
CC-E RTD/V 0-10 V 1SVR 011 739 R2200 1
PT100
CC-E RTD/I 0-20 mA 1SVR 011 740 R0700 1
-50...+250 °C
CC-E RTD/I 4-20 mA 1SVR 011 741 R2400 1

Supply voltage: 110-240 V AC


universal
0-10 V, 0-20 mA,
CC-E/RTD refer to table 1SVR 011 706 R2200 1
4-20 mA
single-function
CC-E RTD/V 0-10 V 1SVR 011 788 R2400 1
PT100
CC-E RTD/I 0-20 mA 1SVR 011 789 R2500 1
0...100 °C
CC-E RTD/I 4-20 mA 1SVR 011 790 R2200 1
CC-E RTD/V 0-10 V 1SVR 011 791 R1700 1
PT100
CC-E RTD/I 0-20 mA 1SVR 011 792 R1000 1
-50...+50 °C
CC-E RTD/I 4-20 mA 1SVR 011 793 R1100 1
CC-E RTD/V 0-10 V 1SVR 011 794 R1200 1
PT100
CC-E RTD/I 0-20 mA 1SVR 011 795 R1300 1
0...300 °C
CC-E RTD/I 4-20 mA 1SVR 011 796 R1400 1
CC-E RTD/V 0-10 V 1SVR 011 797 R1500 1
PT100
CC-E RTD/I 0-20 mA 1SVR 011 798 R2600 1
-50...+250 °C
CC-E RTD/I 4-20 mA 1SVR 011 799 R2700 1
1)
B 1604 Class I, Div.2
(universal device) • Technical data .......................................................................... 217 • Dimensional drawings ...............................................................223

206 ABB
2CDC110004C0205
Temperature signal converter for RTD sensors
CC-U/RTD
Ordering details

CC-U/RTD universal signal converter for PT10, PT100, PT1000 temperature sensors
(acc. to IEC 751 and JIS C 16041), linearized with 3-way electrical isolation
2CDC 281 005 F0t03

� J Configurable output signal response on Wiring instruction


input signal interruption (low fail safe /
� high fail safe) G

� J Adjustment and operating elements on Burden


R � 4.7 k�
the front-side J
Burden

2CDC 282 017 F0206


� J Short-circuit proof signal outputs H R � 600 �

J Plug-in connecting terminals for inputs,


� outputs and supply
supply
1)
Japanese standard 24 V DC or 110-240 V AC

Characteristic curves
Resistance of PT10, PT100 and PT1000 sensors depending on the temperature
CC-U/RTD

PT1000
 Plug-in connecting
terminals
 Gain: Coarse adjustment
 Gain: Fine adjustment
Resistance [�]

PT100
 Offset adjustment
 U: green LED -
supply voltage
 Marker label

PT10

2CDC 282 022 F0203


5
Temperature [°C]

Output Switch 3
DIP switch settings 1 2 3 4 5 6
0...5 V
0...10 V
1...5 V
2...10 V
-10...+10 V
Input Switch 1 Switch 2 Gain -5...+5 V
Type Range 1 2 3 4 5 6 1 2 3 4 5 6 Coarse -10...0 V
0...500 °C F -5...0 V
0...550 °C E 0...6.66 V
0...600 °C D -10...+3.33 V
0...650 °C C -5...+1.66 V
PT10 0...8 V
0...700 °C B
0...750 °C A 0...4 V
0...800 °C 9 -10...-2 V
0...850 °C 8 -5...-1 V
0...50 °C F 1.25...6.25 V
0...60 °C E -7.5...+2.5 V
0...70 °C B -3.75...+1.25 V
0...80 °C A 1.66...8.33 V
0...90 °C 9 -6.66...+6.66 V
PT100 0...100 °C 8 -3.33...+3.33 V
0...200 °C 3 -8...0 V
-4...0 V
0...300 °C 2
0...1 mA
0...400 °C 1
0...20 mA
0...500 °C 0
4...20 mA
0...10 °C 8
2CDC 282 023 F0203

0...10 mA
0...20 °C 3
0...0.5 mA
0...30 °C 2
0...13.33 mA
PT1000 0...40 °C 1
0...50 °C 0 0...666 µA
0...16 mA
0...60 °C 0
Low fail safe *) - 0...800 µA
High fail safe *) - 0...8 mA
0...400 µA
2CDC 282 003 F0204
2CDC 282 024 F0203

2.5...12.5 mA
*) Detection of input signal interruptions: 125...625 µA
3.33...16.66 mA
If the input signal circuit is interrupted, the output signal changes 166...833 µA Legend
to the adjusted minimum value (low fail safe) or maximum value 0.2...1 mA ON
(high fail safe). 2...10 mA OFF
100...500 µA no influence

Type Rated supply voltage Order code Pack. unit Price


pieces 1 piece

CC-U/RTD 24-48 V DC 1SVR 040 002 R0500 1


110-240 V AC 1SVR 040 003 R0600 1

• Accessories . ............................................................................ 216 • Technical data ...........................................................................219


• Dimensional drawings .............................................................. 223

ABB 207
2CDC110004C0205
Temperature signal converter for RTD sensors
CC-U/RTDR with relay output
Ordering details

CC-U/RTDR universal signal converter for temperature and resistance signals,


with 2 threshold relay outputs and 3-way electrical isolation
2CDC 281 006 F0t03

J Temperature signal converter for PT100 signals (5 ranges up to 800 °C) and variable resistances from
� 0-380 q
� J 2 threshold relay outputs with one c/o contact each (threshold and respective hysteresis can be
� adjusted independently from each other)
� J Open-circuit or closed-circuit principle configurable by means of a DIP switch
� J 2 yellow LEDs for clear status indication of the output relays
� J Plug-in connecting terminals for inputs, outputs and supply


� Wiring instruction Function diagrams

Value R1
CC-U/RTDR E (12) Closed-circuit principle
G R1 F (11) R1 Threshold value
D (14)
υ
R1 Hysteresis

Threshold Hysteresis
J Temperature
 Plug-in connecting B (22) R2 Hysteresis
R2 C (21)
terminals

2CDC 282 044 F0203


R2 Threshold value
H A (24)

2CDC 282 045 F0203


 Threshold value for R1 Value R2 11-14
R1 11-12

 Hysteresis for R1 21-24


R2 21-22

K M
 Threshold value for R2 supply
24 V DC or 110-240 V AC
 Hysteresis for R2
 U: green LED -
supply voltage DIP switch settings Open-circuit principle
R1 Threshold value

 R2: yellow LED - Switch 1


R1 Hysteresis

Input PT100
Relay 2 energized 1 2 3 4 5 6 Temperature

0...100 °C R2 Hysteresis

 R1: yellow LED - 0...200 °C

2CDC 282 046 F0203


R2 Threshold value
2CDC 282 003 F0204
2CDC 282 007 F0204

5
0...400 °C
Relay 1 energized 0...600 °C
0...800 °C 11-14
R1 11-12
 Marker label Output
Legend 21-24
R2 21-22
ON
Closed-circuit principle OFF
Open-circuit principle no influence

Switching points
Switching points of the output relay depending on the input range,
configuration open-circuit principle
IN [%]

800 100
e
lu
va

90
al

700
tu
Ac

Threshold value R1
80
2-100 % Hysteresis R1
600
of input range 5-50 % of
70
Temperature υ [°C]

threshold
500 value R1
60

400 50

40
300 Threshold value R2
2-100 % Hysteresis R2
30
of input range 5-50 % of
200 threshold
20 value R2
100 10

0 OUT
2CDC 282 025 F0203

50 100 150 200 250 300 350 400


11-14
Resistance [�] R1
11-12

21-24
R2
21-22

Type Rated supply voltage Order code Pack. unit Price


pieces 1 piece

CC-U/RTDR 24-48 V DC 1SVR 040 012 R2600 1


110-240 V AC 1SVR 040 013 R2700 1

• Accessories . ............................................................................ 216 • Technical data ...........................................................................220


• Technical diagrams .................................................................. 223 • Dimensional drawings ...............................................................223

208 ABB
2CDC110004C0205
Temperature signal converter for thermocouples
CC-E/TC
Ordering details

CC-E/TC analog signal converter for thermocouple signals of the types J and K
with 3-way electrical isolation
2CDC 281 007 F0t03

J 2 universally configurable devices (type CC-E/TC)


J 2x6 single-function devices
J "Plug and Work", no adjustment of single-function devices required


Wiring instruction DIP switch settings (universal devices)


Burden
R � 1.0 k�
Switch 1
Input Output 1 2 3 4 5 6
Burden

2CDC 282 008 F0206


0...10 V

2CDC 282 003 F0204


2CDC 282 009 F0204
R � 500 � TC-J:
0...20 mA
CC-E/TC 0...600 °C
4...20 mA
0...10 V
TC-K:
0...20 mA Legend
0...1000 °C
4...20 mA ON
supply High fail safe OFF
 Gain adjustment 24 V DC or 110-240 V AC Low fail safe no influence

 Offset adjustment
 U: green LED -
supply voltage
 DIP switch for input Type Input signal Output signal Order code Pack. unit Price
and output configuration piece 1 piece
(only available on universal
devices) Supply voltage: 24 V DC
universal
thermocouple 0-10 V, 0-20 mA,
CC-E/TC 1SVR 011 702 R26001) 1
types J and K 4-20 mA
single-function
5
CC-E TC/V 0-10 V 1SVR 011 750 R0100 1
type J
CC-E TC/I 0-20 mA 1SVR 011 751 R2600 1
0...600 °C
CC-E TC/I 4-20 mA 1SVR 011 752 R2700 1

CC-E TC/V 0-10 V 1SVR 011 753 R2000 1


type K
CC-E TC/I 0-20 mA 1SVR 011 754 R2100 1
0...1000 °C
CC-E TC/I 4-20 mA 1SVR 011 755 R2200 1

Supply voltage: 110-240 V AC


universal
thermocouple 0-10 V, 0-20 mA,
CC-E/TC 1SVR 011 707 R2300 1
types J and K 4-20 mA
single-function
CC-E TC/V 0-10 V 1SVR 011 760 R0300 1
type J
CC-E TC/I 0-20 mA 1SVR 011 761 R2000 1
0...600 °C
CC-E TC/I 4-20 mA 1SVR 011 762 R2100 1

CC-E TC/V 0-10 V 1SVR 011 763 R2200 1


type K
CC-E TC/I 0-20 mA 1SVR 011 764 R2300 1
0...1000 °C
CC-E TC/I 4-20 mA 1SVR 011 765 R2400 1


B 1604 Class I, Div.2
1)

(universal device) • Technical data .......................................................................... 217 • Dimensional drawings ...............................................................223

ABB 209
2CDC110004C0205
Temperature signal converter for thermocouples
CC-U/TC
Ordering details

CC-U/TC universal signal converter for thermocouples with 3-way electrical isolation
2CDC 281 008 F0t03

J Temperature signal converter for thermo- Wiring instruction


couples of the types K, J, T, S, E, N, R, B

J Continuously adjustable voltage signal input
� 0-10 mV and 0-50 mV Burden
R � 4.7 k�
J Differential temperature meas. possible 1)

2CDC 282 018 F0206


Burden
J Configurable output signal response on input R � 600 �

� signal interruption (low fail safe / high fail safe)


J Adjustment and operating elements on the
� front-side supply

J Short-circuit proof signal outputs 1)



J Plug-in connecting terminals for inputs,
outputs and supply
CC-U/TC

2CDC 282 019 F0206


 Plug-in connecting
terminals without cold-junction compensation:

 Gain: Coarse adjustment DIP switch settings switch SW2.2 = OFF

 Gain: Fine adjustment Input Switch 1 Switch 2


Type Range 1 2 3 4 5 6 1 2 3 4 5 6
 Offset adjustment 0-100...900 °C
K 0-250...1350 °C
 U: green LED - Switch 2 J 0-100...750 °C
Output
supply voltage 0...5 V
1 2 3 4 5 6 0-100...400 °C
T -150-0...400 °C
*) Detection of input signal
S 0-250...1550 °C
 Marker label 0...10 V
1...5 V 0-100...700 °C
interruptions:
E 0-200...1000 °C
2...10 V If the input signal circuit is inter-
-10...+10 V 0-100...650 °C rupted, the output signal changes
N 0-200...1300 °C
-5...+5 V to the adjusted minimum value

2CDC 282 010 F0204


-10...0 V 0-250...1350 °C (low fail safe) or maximum value
R
-5...0 V 0-450...1700 °C (high fail safe).
0...6.66 V B 0-700...1750 °C

5
-10...+3.33 V 0-2...10 mV
mV 0-10...50 mV
-5...+1.66 V
0...8 V Low fail safe *)
0...4 V High fail safe *)
-10...-2 V
-5...-1 V
1.25...6.25 V Characteristic curves
-7.5...+2.5 V
-3.75...+1.25 V Thermocouple voltages depending on the temperature
1.66...8.33 V
-6.66...+6.66 V 80000
-3.33...+3.33 V Typ E
-8...0 V 75000
-4...0 V
0...1 mA 70000 Typ J
0...20 mA
4...20 mA 65000
0...10 mA
0...0.5 mA 60000
0...13.33 mA
0...666 µA 55000
Typ K
0...16 mA
0...800 µA 50000
0...8 mA Typ N
0...400 µA 45000
2CDC 282 020 F0203

2.5...12.5 mA
Thermoelement-Spannung [µV]

125...625 µA 40000
3.33...16.66 mA
166...833 µA 35000
0.2...1 mA
2...10 mA 30000
100...500 µA
25000
Typ R
20000 Typ T
15000 Typ S

10000
Typ B
2CDC 282 003 F0204

5000

0
Legend
ON -5000
OFF
2CDC 282 026 F0103

no influence -10000

-15000
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
1550
1600
1650
1700
1750
1800
-250
-200
-150
-100

100
150
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
-50

50
0

Temperatur [°C]

Type Rated supply voltage Order code Pack. unit Price


pieces 1 piece

CC-U/TC 24-48 V DC 1SVR 040 004 R0700 1


110-240 V AC 1SVR 040 005 R0000 1

• Accessories . ............................................................................ 216 • Technical data ...........................................................................219


• Dimensional drawings .............................................................. 223

210 ABB
2CDC110004C0205
Temperature signal converter for thermocouples
CC-U/TCR with relay output
Ordering details

CC-U/TCR universal signal converter for thermocouples, with 2 threshold relay


outputs and 3-way electrical isolation
2CDC 281 009 F0t03

J Temperature signal converter for thermocouples of the types K, J, T, S



J 2 threshold relay outputs with one change-over contact each (threshold and respective hysteresis can
� be adjusted independently from each other)
� J Open-circuit or closed-circuit principle configurable by means of a DIP switch
� J 2 yellow LEDs for clear status indication of the output relays
� J Plug-in connecting terminals for inputs, outputs and supply

� Wiring instruction Function diagrams

� Value R1
Closed-circuit principle
R1 Threshold value

CC-U/TCR R1 Hysteresis

Threshold Hysteresis Temperature

R2 Hysteresis

2CDC 282 044 F0203


R2 Threshold value

 Plug-in connecting

2CDC 282 020 F0206


Value R2
terminals 11-14
R1 11-12
21-24
R2 21-22
 Threshold value for R1
 Hysteresis for R1 supply

 Threshold value for R2


 Hysteresis for R2
DIP switch settings Open-circuit principle

 U: green LED - R1 Threshold value


R1 Hysteresis

supply voltage Input Switch 1


Temperature
Type Range 1 2 3 4 5 6
 R2: yellow LED - 0...240 °C R2 Hysteresis

2CDC 282 046 F0203


J 0...480 °C R2 Threshold value
Relay 2 energized 0...1200 °C
0...250 °C
 R1: yellow LED - K 0...500 °C 11-14
R1 11-12

5
0...1350 °C
Relay 1 energized -150...+120 °C
21-24
R2 21-22

T 0...220 °C
 Marker label 0...400 °C
0...210 °C
2CDC 282 003 F0204
2CDC 282 004 F0204

0...380 °C
S
0...860 °C
0...1550 °C
Legend
Output
ON
Closed-circuit principle OFF
Open-circuit principle no influence

Switching points
Switching points of the output relay depending on the input range,
configuration open-circuit principle
IN [%] Threshold value
R1 = 1000 °C
7000 100
6500 Typ J
6000

5500

5000
Thermocouple voltage [µV]

Typ K
4500 Release hysteresis
4000

3500
Threshold value
3000 R2 = 400 °C
2500
Typ T
2000 Release hysteresis
1500

1000
Typ S

500

0 0 OUT
-500
2CDC 282 027 F0203

-1000 11-14
R1 11-12
-1500
-275
-175
-75
25
125
225
325
425
525
625
725
825
925
1025
1125
1225
1325
1425
1525
1625
1725
1825

21-24
Temperature [°C] R2 21-22

Type Rated supply voltage Order code Pack. unit Price


pieces 1 piece

CC-U/TCR 24-48 V DC 1SVR 040 014 R2000 1


110-240 V AC 1SVR 040 015 R2100 1

• Accessories . ............................................................................ 216 • Technical data ...........................................................................220


• Technical diagrams .................................................................. 223 • Dimensional drawings ...............................................................223

ABB 211
2CDC110004C0205
Measuring converter for sinusoidal and DC
currents CC-E/I
Ordering details

CC-E/I current measuring converter for current signals 0-5 A, 0-20 A, AC/DC
with 3-way electrical isolation
2CDC 281 010 F0t03

J 2 universally configurable devices (type CC-E/I)


J 2x6 single-function devices
J "Plug and Work", no adjustment of single-function devices required

� Wiring instruction

� Burden
R � 1.0 k�

Burden

2CDC 282 009 F0206


R � 500 �

CC-E/I
supply
24 V DC or 110-240 V AC

 Gain adjustment
 Offset adjustment
Input range selection
 U: green LED -
supply voltage DIP switch settings (universal devices)
Select input range by terminals
 DIP switch for input
Input range 5 A
and output configuration Connected lines
(only available on Switch 1

2CDC 282 002 F0204


Used terminals

2CDC 282 008 F0204


Input Output 1 2 3 4 5 6
Terminal marking
2CDC 282 011 F0204

universal devices) I - DC
0...10 V
I - AC
Input range 20 A I - DC
0...20 mA Legend
Connected lines I - AC
Used terminals I - DC ON
4...20 mA OFF
Terminal marking I - AC

5
Type Input signal Output signal Order code Pack. unit Price
pieces 1 piece

Supply voltage: 24 V DC
universal
0-5 A, 0-10 V, 0-20 mA,
CC-E/I 1SVR 011 703 R27001) 1
0-20 A, AC/DC 4-20 mA
single-function
CC-E IAC/V 0-10 V 1SVR 011 770 R0500 1
CC-E IAC/I 0-5 A, 0-20 A, AC 0-20 mA 1SVR 011 771 R2200 1
CC-E IAC/I 4-20 mA 1SVR 011 772 R2300 1

CC-E IDC/V 0-10 V 1SVR 011 773 R2400 1


CC-E IDC/I 0-5 A, 0-20 A, DC 0-20 mA 1SVR 011 774 R2500 1
CC-E IDC/I 4-20 mA 1SVR 011 775 R2600 1

Supply voltage: 110-240 V AC


universal
0-5 A, 0-10 V, 0-20 mA,
CC-E/I 1SVR 011 708 R0400 1
0-20 A, AC/DC 4-20 mA
single-function
CC-E IAC/V 0-10 V 1SVR 011 780 R1100 1
CC-E IAC/I 0-5 A, 0-20 A, AC 0-20 mA 1SVR 011 781 R0600 1
CC-E IAC/I 4-20 mA 1SVR 011 782 R0700 1

CC-E IDC/V 0-10 V 1SVR 011 783 R0000 1


CC-E IDC/I 0-5 A, 0-20 A, DC 0-20 mA 1SVR 011 784 R0100 1
CC-E IDC/I 4-20 mA 1SVR 011 785 R1100 1

1)
B 1604 Class I, Div.2
(universal device) • Technical data .......................................................................... 221 • Dimensional drawings ...............................................................223

212 ABB
2CDC110004C0205
Measuring converter for sinusoidal currents
CC-E IAC/ILPO
Ordering details

CC-E IAC/ILPO current measuring without auxiliary power for sinusoidal currents
0-1 A, 0-5 A, output 4 - 20 mA
2CDC 281 018 F0t04

J Measuring converter for sinusoidal AC currents (0-1 A, 0-5 A)


J Measuring range selection by front-face sliding switch
J 4-20 mA output current in propotion to input current
� J no additional power supply required


Wiring instruction

CC-E IAC/ILPO

 Gain adjustment
 Offset adjustment

2CDC 282 010 F0b06


 Selection of measuring
range

5
Type Input signal Order code Pack. unit Price
pieces 1 piece

CC-E IAC/ILPO 0-1 A, 0-5 A, AC 1SVR 010 203 R0500 1

• Technical data .......................................................................... 221 • Dimensional drawings ...............................................................223

ABB 213
2CDC110004C0205
Measuring converter for current RMS values
CC-U/I
Ordering details

CC-U/I universal current measuring converter for RMS values of 0-1 A and 0-5 A,
with 3-way electrical isolation
2CDC 281 012 F0t03

J RMS converter for current signals up to 1 A and up to 5 A of any wave form (DC, DC with superimposed
AC components, pure sinusoidal, triangular, phase-angle controlled, etc. in a measuring range of
� 0-600 Hz)
J Adjustment and operating elements on the front

J Short-circuit proof signal outputs
� J Plug-in connecting terminals for inputs, outputs and supply


Wiring instruction DIP switch settings

Output Switch 1
1 2 3 4 5 6
0...5 V
Burden 0...10 V
CC-U/I R � 4.7 k� 1...5 V
2...10 V
Burden -10...+10 V

2CDC 282 021 F0206


R � 600 � -5...+5 V
-10...0 V
 Plug-in connecting -5...0 V
0...6.66 V
terminals -10...+3.33 V
supply -5...+1.66 V
 Gain adjustment 24 V DC or 110-240 V AC 0...8 V
0...4 V
 Offset adjustment -10...-2 V
-5...-1 V
 U: green LED - 1.25...6.25 V
-7.5...+2.5 V
supply voltage -3.75...+1.25 V
Input range selection 1.66...8.33 V
 Marker label -6.66...+6.66 V
-3.33...+3.33 V
-8...0 V
-4...0 V
0...1 mA
Select input range by terminals 0...20 mA
4...20 mA
Input range 1 A 0...10 mA
0...0.5 mA
Connected lines J H G
0...13.33 mA

5
Used terminals
Terminal marking 0...666 µA
2CDC 282 033 F0203

5A 1A C 0...16 mA
0...800 µA
Input range 5 A 0...8 mA
0...400 µA

2CDC 282 003 F0204


2CDC 282 029 F0203
Connected lines J H G
Used terminals 2.5...12.5 mA
Terminal marking 125...625 µA
5A 1A C 3.33...16.66 mA
166...833 µA Legend
0.2...1 mA ON
2...10 mA OFF
100...500 µA no influence

Example of application
RMS measurement and conversion of a current signal
IN [%] Gain �15 %

I(t) [A]

2 resulting
RMS value
1

0
t OUT [%]
-1 0 50 100

-2
Offset �20 %
2CDC 282 028 F0203

-3

-4

-5

Type Rated supply voltage Order code Pack. unit Price


pieces 1 piece

CC-U/I 24-48 V DC 1SVR 040 006 R0100 1


110-240 V AC 1SVR 040 007 R0200 1

• Accessories . ............................................................................ 216 • Technical data ...........................................................................222


• Dimensional drawings .............................................................. 223

214 ABB
2CDC110004C0205
Measuring converter for voltage RMS values
CC-U/V
Ordering details

CC-U/V universal voltage measuring converter for RMS values of 0-600 V,


with 3-way electrical isolation
2CDC 281 013 F0t03

J RMS converter for voltage signals up to 600 V of any wave form (DC, DC with superimposed AC
� components, pure sinusoidal, triangular, phase-angle controlled, etc. in a measuring range of
� 0-600 Hz)
J Adjustment and operating elements on the front
� J Short-circuit proof signal outputs
� J Plug-in connecting terminals for inputs, outputs and supply


Wiring instruction DIP switch settings

Output Switch 1
1 2 3 4 5 6
0...5 V
CC-U/V 0...10 V
1...5 V
Burden
2...10 V
R � 4.7 k�
-10...+10 V
-5...+5 V
Burden
 Plug-in connecting

2CDC 282 022 F0206


-10...0 V
R � 600 �
-5...0 V
terminals 0...6.66 V
-10...+3.33 V
 Input voltage range -5...+1.66 V
0...8 V
selection supply 0...4 V
24 V DC or 110-240 V AC -10...-2 V
 Gain adjustment -5...-1 V
1.25...6.25 V
 Offset adjustment -7.5...+2.5 V
-3.75...+1.25 V
 U: green LED - 1.66...8.33 V
-6.66...+6.66 V
supply voltage -3.33...+3.33 V
-8...0 V
 Marker label -4...0 V
0...1 mA
Input range selection 0...20 mA
4...20 mA
0...10 mA
0...0.5 mA

5
0...13.33 mA
Selecting input range by Switch 0...666 µA
front-face rotary switch position 0...16 mA
0...100 V 1 0...800 µA
2CDC 282 012 F0204

0...150 V 2 0...8 mA
0...250 V 3

2CDC 282 003 F0204


0...400 µA

2CDC 282 029 F0203


0...300 V 4 2.5...12.5 mA
0...400 V 5 125...625 µA
0...450 V 6 3.33...16.66 mA
0...550 V 7 166...833 µA Legend
0...600 V 8 0.2...1 mA ON
2...10 mA OFF
100...500 µA no influence

Example of application
RMS measurement and conversion of a phase-angle controlled voltage signal L1 = 230 V

INUeff [V]
U(t) [V]
resulting Gain �15 %
RMS value
300

0 OUT [%]
0 50 100
2CDC 282 030 F0203

Offset �20 %
-300

operating angle

Type Rated supply voltage Order code Pack. unit Price


pieces 1 piece

CC-U/V 24-48 V DC 1SVR 040 008 R1300 1


110-240 V AC 1SVR 040 009 R1400 1

• Accessories . ............................................................................ 216 • Technical data ...........................................................................222


• Dimensional drawings .............................................................. 223

ABB 215
2CDC110004C0205
Analog signal converters
Accessories for CC-U range
Ordering details

Accessories
Adapter for screw mounting

2CDC 252 187 F0005


.453”
11,5

Type for type Width Order code Pack. Price Weight


.177”

62,5 2.46”
4,5

in mm unit 1 piece 1 piece


pieces kg / lb
.394”

.886”
22,5
10

60 2.36”
ADP.01 CC-U 22.5 1SVR 430 029 R0100 1
ADP.01

Marker label
2CDC 252 186 F0005

3A11
.315”

Type for type Order code Pack. Price Weight


8

20
.787”
unit 1 piece 1 piece
pieces kg / lb
MAR.01
MAR.01 CC-U 1SVR 366 017 R0100 1

Sealable transparent cover


7 .275”
2CDC 252 185 F0005

22,5
3,5 .138”
.886”
Type for type Width Order code Pack. Price Weight
in mm unit 1 piece 1 piece
pieces kg / lb
68,5 2.70 ”

COV.01 CC-U 22.5 1SVR 430 005 R0100 1

front-to-back
size 107

5 Sealable cover
COV.01

216 ABB
2CDC110004C0205
Analog signal converters
CC-E/STD, CC-E x/x, CC-E/RTD, CC-E/TC
Technical data

Type CC-E/STD CC-E/RTD CC-E/TC


Input circuits - Analog inputs J-G-H Thermocouples
Current Voltage Temperature sensors
(IEC 584-1 and 2)
Input signal Standard signals PT100 TC.K, TC.J
Rated input range 0...5 V /
0...20 mA / TC.K: 0...1000 °C,
0...10 V / -50...+500 °C
4...20 mA TC.J: 0...600 °C
-10...+10 V
Limitation of input signals +55 mA ± 11 V
Influence of line resistance - < 0.01 %/ < 0.5 % / 100 
Gain adjustment range ± 5 % (universal devices)
Offset adjustment range ± 5 % (universal devices)
Input impedance 50  1 M - -
Suppression at 50 Hz - - > 35 dB
Common-mode rejection - 100 dB
Output circuits - Analog outputs D-F, A-C Current Voltage
Output signal 0-20 mA, 4-20 mA 0-5 V, 0-10 V
Output burden m 500   1.0 K
Accuracy 1) ± 0.5 % of full-scale
Residual ripple < 0.5 %
Response time 200 µs 10 ms
Transmission frequency 2 kHz 80 Hz 2 Hz (up to -3 dB)
Reaction to input circuit interruption Low fail safe: Output voltage > 15 % of measuring range 2)
Low fail safe: Output voltage < -0.6 V, output current = 0 mA
Supply circuits K-M DC versions AC versions
Supply voltage 24 V DC 110-240 V AC - 50/60 Hz
Supply voltage tolerance -15...+15 % -15...+10 %
Power consumption
Indication of operational states
1.5 W typ. 1.5 VA typ.
5
Rated control supply voltage US U: green LED
General data
Ambient temperature range operation 0...+60 °C
storage -20...+80 °C
Temperature coefficient ± 500 ppm/°C
Degree of protection (DIN 40050) IP20
Mounting position ventilation slots on top and bottom
Mounting DIN rail, snap-on mounting
Electrical connection
Wire size rigid 4 mm2 (10 AWG)
fine-strand 2.5 mm2 (14 AWG)
Electromagnetic compatibility
Interference immunity EN 61000-6-2
electrostatic discharge (ESD) IEC/EN 61000-4-2 Level 3 (±6 kV / ±8 kV)
electromagnetic field
10 V/m
(HF radiation resistance) IEC/EN 61000-4-3
fast transients (Burst) IEC/EN 61000-4-4 Level 3 (±2 kV / 5 kH)
powerful impulses (Surge) IEC/EN 61000-4-5 ±2 kV / ±1 kV
HF line emission IEC/EN 61000-4-6 10 V
Interference emission EN 61000-6-4 class B
Isolation data
Test voltage between all isolated circuits 2.5 kV AC
Rated insulation voltage - - -

1)
includes: non-linearity, factory setting, drift of temperature, supply voltage and output load
2)
Only -/RTD and -/TC: Single-function devices respond with Low fail safe to input signal interruptions

ABB 217
2CDC110004C0205
Analogsignal converter
CC-E I/I-1, CC-E I/I-2
Technical data

Type CC-E I/I


Input circuits - channel 1: A (+), B (-),
Analog inputs channel 1 or 2: C (+), D (-) Current
Input current IIN 0-20 mA, 4-20 mA
Min. input current < 100 µA
Max. input current 50 mA1) (VIN < 18 V)
Input voltage UIN < 2.5 V + (IIN x RL)
Input voltage drop Ui < 2.5 V (20 mA, RL = 0 )
Max. input voltage 18 V1) (IIN < 50 mA)
Output circuits channel 1: H (+), G (-),
channel 2: F (+), E (-)
Output current IOUT 0-20 mA, 4-20 mA
Output load RL 0-500 
Output voltage UOUT IOUT x RL
Residual ripple < 20 mVpp (500 , 20 mA)
Response time (0-100 %) < 15 ms (0-500 , 20 mA),
< 5 ms (500 , 20 mA, 25 °C)
Accuracy  0.1 % of full-scale (20 mA)
Load influence (0-500 )  0.05 % / 100 ,
 -0.1 % / 100  (25 °C)
General data
Width of the enclosure 18 mm
Weight 1 channel approx. 0.037 kg (0.082 lb)
2 channel approx. 0.044 kg (0.097 lb)
Mounting position any
Degree of protection enclosure / terminals IP20 / IP20

5 Ambient temperature range operation


storage
-25...+60 °C
-40...+85 °C
Temperature coefficient < 50 ppm / °C
Mounting DIN rail (EN 50022)
Electrical connection
Wire size max. 2.5 mm2 (14 AWG)
Standards
Product standard EN 50178
Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC
Electromagnetic compatibility
Interference immunity EN 61000-6-2
electrostatic discharge (ESD) EN 61000-4-2 Level 3 (±6 kV / ±8 kV)
electromagnetic field
10 V/m
(HF radiation resistance) EN 61000-4-3
fast transients (Burst) EN 61000-4-4 Level 3 (±2 kV / 5 kH)
powerful impulses (Surge) EN 61000-4-5 ±2 kV / ±1 kV
HF line emission EN 61000-4-6 10 V
magnetisches Feld EN 61000-4-8 30 A/m
Interference emission EN 61000-6-4
Radiated noise EN 55011 class B
Operational reliability (EN 68-2-6) 4g
Mechanical resistance (EN 68-2-6) 10 g
Environmental testing (IEC 68-2-30 Db) 24 h cycle, 55 °C, 93 % rel., 96 h
Isolation data
Insulation voltage input / output 500 Veff / 50 Hz
Insulation voltage between
channels (device with 2 channels) 5 kVeff / 50 Hz
Pollution category 2
Overvoltage category II

1)
The input parameters have to be limited to the indicated maximum values.

218 ABB
2CDC110004C0205
Analog signal converters
CC-U/STD, CC-U/RTD, CC-U/TC
Technical data

Type CC-U/STD CC-U/RTD CC-U/TC


Input circuits - Analog inputs J-G-H Potentio- Thermocouples
Current Voltage Temperature sensors
meter (IEC 584-1 and 2)
Input signal 0-20 mA 0-100 mV 470  - PT10, PT100, PT1000 TC.K TC.J
4-20 mA 0-1 V 1 M 2) (IEL 751 and JICC 1604) TC.T TC.S
10-50 mA 0-5 V TC.E TC.N
0-1 mA 1-5 V TC.R TC.B
0-10 V
2-10 V
± 10 V
Limitation of input signals ± 55 mA ± 11 V - -
Rated input range Max. temperature adjustable:
6-60 °C for PT1000 refer to temperature specs.
- - -
50-500 °C for PT100 of individual thermocouples
500-850 °C for PT10
Influence of line resistance - - - 0.015 °C/ < 0.01 % / 100 
Gain adjustment range 0.9- 45 mV -
- see DIP switch settings
(universal devices) 110 mA 22 V
Offset adjustment range (universal devices) -137.5...+62.5 % ±5% ± 10 %
Input impedance for different ranges - -
without detection of input signal interruption 51  6 M 3 G - -
with detection of input signal interruption 51  3.5 M 9.5 G - -
Suppression at 50 Hz - - - - > 40 dB
Common-mode rejection - - - 120 dB 105 dB
Output circuits - Analog outputs D-F, A-C Current Voltage
Output signal 0-20 mA, 4-20 mA 0-5 V, 1-5 V, 0-10 V, 2-10 V, ± 10 V
Output burden  600   4.7 K
Accuracy 1) ±0.1 % of full-scale ±0.2 % of full-scale ±0.1 % of full-scale
Residual ripple - < 0.15 % -
Response time 200 µs 10 ms 200 ms
Transmission frequency 1 kHz 80 Hz 2 Hz (to -3 dB)
Supply circuits
Rated supply voltage
K-M
24-48 V DC 110-240 V AC
5
Supply voltage range 24-48 V DC / 24 V AC 110-240 V AC / 100-300 V DC
Supply voltage tolerance DC: -15...+15 % AC: -15...+10 %
Rated frequency 0 Hz or 50/60 Hz
Power consumption 2 W at 24 V DC 4.5 VA at 230 V AC
Indication of operational states
Supply voltage U: green LED
General data
Ambient temperature range operation -20...+60 °C
storage -40...+80 °C
Temperature coefficient ±200 ppm/°C at min. offset
±150 ppm/°C ±250 ppm/°C
±400 ppm/°C at max. offset
Mounting position any
Mounting DIN rail, snap-on mounting / screw mounting with adapter
Electrical connection
Wire size rigid plug-connector with screw terminals 1.5 mm2 (16 AWG)
fine-strand plug-connector with screw terminals 2.5 mm2 (14 AWG)
Electromagnetic compatibility
Interference immunity EN 61000-6-2
electrostatic discharge (ESD) IEC/EN 61000-4-2 Level 3 (±6 kV / ±8 kV)
electromagnetic field
10 V/m
(HF radiation resistance) IEC/EN 61000-4-3
fast transients (Burst) IEC/EN 61000-4-4 Level 3 (±2 kV / 5 kH)
powerful impulses (Surge) IEC/EN 61000-4-5 2 kV / 1 kV
HF line emission IEC/EN 61000-4-6 10 V
Interference emission EN 61000-6-4 Class B

Isolation data
Isolation test (between all isolated circuits) 1.5 kV
Test voltage (between all isolated circuits) 1.5 kV / 50 Hz

1)
includes: non-linearity, factory setting, drift of temperature, supply voltage and output load
2)
Detection of an input signal break (fail safe) and resistance > 10 kq results in a linearity of w0,2 %.

ABB 219
2CDC110004C0205
Analog signal converters with relay output
CC-U/STDR, CC-U/RTDR, CC-U/TCR
Technical data

Type CC-U/STDR CC-U/RTDR CC-U/TCR


Input circuits - Analog inputs J-H Thermocouples
Current Voltage Temperature sensors
(IEC 584-1 and 2)
Measuring signal / input range 0-20 mA 0-1 V / 1-5 V PT100 TC.K, TC.J
4-20 mA 0-10 / ±10 V TC.T, TC.S
Input resistance approx. 50  approx. 1,5 M
Adjustable threshold 2-100 % of selected input range
Adjustable hysteresis 5-50 % of threshold
Repeat accuracy (constant parameters) ±0.5 % of full-scale
Output circuits - Relay outputs E-D-F, B-C-A Relay, 2 c/o contacts
Rated switching voltage 250 V AC
Rated switching current AC12 (resistive) 230 V 4A
AC15 (inductive) 230 V 3A
DC12 (resistive) 24 V 4A
DC13 (inductive) 24 V 2A
Minimum switching voltage 12 V
Minimum switching current / 10 mA / 0.6 VA (W)
Response time 10 ms
Mechanical lifetime 30 x 106 switching cycles
Electrical lifetime at AC12, 230 V, 4 A 0.1 Mio. switching cycles
Supply circuits K-M
Rated supply voltage 24-48 V DC 110-240 V AC
Supply voltage range 24-48 V DC / 24 V AC 110-240 V AC / 100-300 V DC
Supply voltage tolerance DC: -15...+15 % AC: -15...+10 %
Rated frequency 0 Hz or 50/60 Hz
Power consumption 2 W at 24 V DC 4.5 VA at 230 V AC
5 Indication of operational states
Supply voltage U: green LED
1st / 2nd output relay energized R1: yellow LED / R2: yellow LED
General data
Ambient temperature range operation -20...+60 °C
storage -40...+80 °C
Temperature coefficient ±300 ppm/°C
Mounting position any
Mounting DIN rail (EN 50 022), snap-on mounting / screw mounting with adapter
Electrical connection
Wire size rigid plug-connector with screw terminals 1.5 mm2 (16 AWG)
fine-strand plug-connector with screw terminals 2.5 mm2 (14 AWG)
Electromagnetic compatibility
Interference immunity EN 61000-6-2
electrostatic discharge (ESD) IEC/EN 61000-4-2 Level 3 (±6 kV / ±8 kV)
electromagnetic field
10 V/m
(HF radiation resistance) IEC/EN 61000-4-3
fast transients (Burst) IEC/EN 61000-4-4 Level 3 (±2 kV / 5 kH)
powerful impulses (Surge) IEC/EN 61000-4-5 2 kV / 1 kV
HF line emission IEC/EN 61000-4-6 10 V
Interference emission EN 61000-6-4 Class B
Isolation data
Insulation voltage (between all isolated circuits) 2.5 kV
Test voltage (between all isolated circuits) 2.5 kV

220 ABB
2CDC110004C0205
Analog signal converters
CC-E/I, CC-E IAC/ILPO
Technical data

Type CC-E/I CC-E IAC/ILPO


J-G-H C-D

Input circuits - Analog inputs AC current DC current 2 meas. ranges selectable


Rated input range 0-5 A / 0-20 A 0-5 A / 0-20 A 0-1 A / 0-5 A / sinusoidal
Measuring frequency 50/60 Hz
Overload capacity of inputs input range 1 10 x INom (50 A) for max. 1 s 10 x INom (50 A) for max. 2 s
input range 2 10 x INom (200 A) for max. 1 s 10 x INom (200 A) for max. 2 s
Gain adjustment range ±5 % (universal devices) -
Offset adjustment range ±5 % (universal devices) -
Input impedance / resistance 5A : 65 m 20 A : 2.5 m 5 m
Output circuits - Analog outputs D-F A-C F-E
Current Voltage passive current output in proportion
to input current
Output signal 0-20 mA / 4-20 mA 0-10 V 4-20 mA
Output burden / load 12 V DC: 150 ,
 500   1.0  24 V DC: 750 
30 V DC: 1050 
Accuracy 1) ± 2 % of full-scale
Offset adjustment range ±5 % (universal device) ±5%
Gain adjustment range ±5 % (universal device) ± 20 %
Residual ripple < 0.5 %
Response time 0.5 s 0.6 s
Transmission frequency DC or 50/60 Hz AC: 50/60 Hz
Reaction to input circuit interruption Low fail safe: output voltage < 200 mA,
-
output current < 400 µA
Supply circuits K-M DC versions AC versions
Supply voltage
Supply voltage tolerance
24 V DC
-15...+15 %
110-240 V AC 50/60 Hz
-15...+10 %
12-30 V DC
-
5
Power consumption typ 1.5 W typ 1.5 VA -
Indication of operational states
Supply voltage U: green LED -
General data
Ambient temperature range operation 0...+60 °C -20...+60 °C
storage -20...+80 °C -40...+80 °C
Temperature coefficient ± 500 ppm/°C 300 ppm/°C
Degree of protection (DIN 40050) IP20
Mounting position ventilation slots on top and bottom
Mounting DIN rail, snap-on mounting
Electrical connection
Wire size rigid 4 mm2 (12 AWG) 1x2.5 mm2 (1x14 AWG)
fine-strand 2.5 mm2 (14 AWG)
Electromagnetic compatibility
Interference immunity EN 61000-6-2
electrostatic discharge (ESD) IEC/EN 61000-4-2 Level 3 (±6 kV / ±8 kV)
electromagnetic field
10 V/m
(HF radiation resistance) IEC/EN 61000-4-3
fast transients (Burst) IEC/EN 61000-4-4 Level 3 (±2 kV / 5 kH)
powerful impulses (Surge) IEC/EN 61000-4-5 ±2 kV / ±1 kV
HF line emission IEC/EN 61000-4-6 10 V
Interference emission EN 61000-6-4 Class B
Isolation data
Test voltage (between all isolated circuits) 2.5 kV AC
Rated insulation voltage - 250 V AC

1)
includes: non-linearity, factory setting, drift of temperature, supply voltage and output load

ABB 221
2CDC110004C0205
Analog signal converters
CC-U/I, CC-U/V
Technical data

Type CC-U/I CC-U/V


Input circuits - Analog inputs J-G-H any current signals, any voltage signals,
RMS measurement RMS measurement
Rated input range 0-100 V, 0-200 V
0-1 A
0-300 V, 0-400 V
0-5 A
0-500 V, 0-600 V
Measuring frequency 0-600 Hz
Overload capacity of inputs input range 1 10 x INom (10 A) for max. 2 s -
input range 2 10 x INom (50 A) for max. 2 s -
Gain adjustment range ±15 %
Offset adjustment range ±20 %
Input impedance / resistance 1A: 60 m,
> 800 k
5 A: 12 m
Output circuits - Analog outputs D-F, A-C Current Voltage
Output signal 0-20 mA, 4-20 mA 0-5 V, 1-5 V, 0-10 V, 2-10 V, ± 10 V
Output load  600   4.7 K
Accuracy1) ±0.5 % of full-scale
Temperature coefficient ±250 ppm/°C max. ±300 ppm/°C max.
Residual ripple < 0.15 %
Response time 150 ms
Supply circuits K-M
Rated supply voltage 24-48 V DC 110-240 V AC
Supply voltage range 24-48 V DC, 24 V AC 110-240 V AC, 100-300 V DC
Supply voltage tolerance DC: -15...+15 % AC: -15...+10 %
Rated frequency 0 Hz or 50/60 Hz
Power consumption 2 W at 24 V DC 4.5 VA at 230 V AC
Indication of operational states

5 Supply voltage
General data
U: green LED

Ambient temperature range operation -20...+60 °C


storage -40...+80 °C
Mounting position any
Mounting DIN rail (EN 50022), snap-on mounting / screw mounting with adapter
Electrical connection
Wire size rigid plug-connector with screw terminals 1.5 mm2 (16 AWG)
fine-strand plug-connector with screw terminals 2.5 mm2 (14 AWG)
Standards
Product standard
Low Voltage Directive
EMC Directive
RoHS Directive
Electromagnetic compatibility
Interference immunity EN 61000-6-2
electrostatic discharge (ESD) IEC/EN 61000-4-2 Level 3 (±6 kV / ±8 kV)
electromagnetic field
10 V/m
(HF radiation resistance) IEC/EN 61000-4-3
fast transients (Burst) IEC/EN 61000-4-4 Level 3 (±2 kV / 5 kH)
powerful impulses (Surge) IEC/EN 61000-4-5 2 kV / 1 kV
HF line emission IEC/EN 61000-4-6 10 V
Interference emission EN 61000-6-4 Class B
Isolation data
Insulation voltage (between all isolated circuits) 1.5 kV
Test voltage (between all isolated circuits) 1.5 kV / 50 Hz

1)
includes: non-linearity, factory setting, drift of temperature, supply voltage and output load

222 ABB
2CDC110004C0205
Analog signal converters
CC-E, CC-U
Technical diagr., Connection diagr., Dimensional drawings

Technical diagrams Connection diagram CC-U/x


Width 22.5 mm (0.89 in)
Load limit curves CC-U/xxR
Resistive AC load Resistive DC load

M L K

J H G
2CDC 282 025 F0b06

2CDC 282 026 F0b06


Derating curve

2CDC 282 023 F0b06


1.0
D E F
0.9

A B C
0.8

F
0.7

0.6

0.5
2CDC 282 014 F0b06

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

cos

5
Dimensional drawnings Dimensions in mm

CC-E/x CC-E IAC/ILPO, CC-E I/I


2CDC 282 011 F0b06

2CDC 282 012 F0b06

22.5