FM Global Property Loss Prevention Data Sheets

8-3
September 1998 Revised May 2001 Page 1 of 22

RUBBER TIRE STORAGE

Table of Contents
Page 1.0 SCOPE ................................................................................................................................................... 3 1.1 Changes .......................................................................................................................................... 3 2.0 LOSS PREVENTION RECOMMENDATIONS ....................................................................................... 3 2.1 Construction and Location ............................................................................................................... 3 2.1.1 Steel Protection ..................................................................................................................... 3 2.1.2 Emergency Smoke and Heat Venting ................................................................................... 3 2.2 Occupancy ....................................................................................................................................... 4 2.3 Protection ......................................................................................................................................... 4 2.3.1 General .................................................................................................................................. 4 2.3.2 Ceiling Sprinkler Design ........................................................................................................ 4 2.3.2.1 Warehouses ............................................................................................................... 4 2.3.2.2 Locations Other than Warehouses and Green Tires ............................................. 4 2.3.3 In-Rack Sprinkler Design ....................................................................................................... 5 2.3.3.1 Warehouses ............................................................................................................... 5 2.3.3.2 Locations Other Than Warehouses ........................................................................... 5 2.3.4 High-Expansion Foam Systems ............................................................................................ 9 2.3.5 Water Supplies ...................................................................................................................... 9 2.3.6 Recommended Safe Practices ............................................................................................ 10 2.3.7 Mounted Tires ...................................................................................................................... 10 2.3.8 Suppression Mode and Large-drop Sprinkler Protection .................................................... 10 3.0 SUPPORT FOR RECOMMENDATIONS ............................................................................................. 12 3.1 General .......................................................................................................................................... 12 3.2 Loss History ................................................................................................................................... 12 4.0 REFERENCES ..................................................................................................................................... 12 4.1 FM Global ...................................................................................................................................... 12 APPENDIX A GLOSSARY OF TERMS ..................................................................................................... 12 APPENDIX B DOCUMENT REVISION HISTORY ..................................................................................... 15 APPENDIX C FIRE FIGHTING .................................................................................................................. 15 C.1 Incipient Stage .............................................................................................................................. 16 C.2 Active Stage .................................................................................................................................. 16 C.3 Critical Stage ................................................................................................................................. 16 C.4 Overhaul ........................................................................................................................................ 17 C.5 Use of High-Expansion Foam ....................................................................................................... 17 APPENDIX D NFPA STANDARDS ............................................................................................................ 18

List of Figures
Fig. Fig. Fig. Fig. Fig. Fig. 1. 2. 3. 4. 5. 6. On On On On On On side, double-row racks, with barriers. ........................................................................................... 6 side, double-row racks, without barriers. ...................................................................................... 7 side, multiple-row racks. ............................................................................................................... 8 tread, double-row racks, with barriers. ......................................................................................... 9 tread, double-row racks, without barriers. .................................................................................. 10 tread, multiple-row racks. ............................................................................................................ 11

2002 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced, stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.

Valid Through May 2003

8-3
Page 2

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

Figs. 7, 8 and 9. ............................................................................................................................................ 13 Fig. 10. Typical green tire storage. Storage is two carts high or 16 ft (4.9 m). ....................................... 14 Fig. 11. Typical storage arrangements in locations other than warehouses. .............................................. 15 Fig. 12. On-floor storage. On tread unbundled (could be bundled). .......................................................... 16 Fig. 13. Pyramid tire storage, on side, on floor. .......................................................................................... 17 Fig. 14. Typical storage arrangement using pallet based portable rack. ................................................... 18 Fig. 15. Double-row rack storage with on-side palletized storage. ............................................................. 19 Fig. 16. Rack frequently used for on-tread storages. .................................................................................. 20 Fig. 17. Typical on-tread storage arrangement. Note horizontal channels. ................................................ 21 Fig. 18. Portable rack using wood pallet base and steel frame. ................................................................. 22

List of Tables
Table 1. On-side Storage in Permanent Racks and Partially Loaded Portable Racks, Without Solid Shelves .................................................................................................................................. 5 Table 2. On-tread Storage in Permanent Racks and Portable Racks, Without Solid Shelves ..................... 6 Table 3. On-floor and On-side Storage in Fully Loaded Portable Racks ...................................................... 7 Table 4. Locations Other Than Warehouses and Green Tires .................................................................. 8 Table 5. Hose Stream Demand and Duration of Supply ............................................................................... 9 Table 6. Suppression Mode Sprinkler Protection Requirements ................................................................. 11 Table 7. Large-drop Sprinkler Protection Requirements ............................................................................ 12

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

8-3
Page 3

1.0 SCOPE This FM Global Data Sheet provides fire protection guidelines for the storage of rubber tires. This includes passenger car, truck and tractor, motorcycle, bicycle, and green tires. Protection of rubber tires mounted on metal wheels also is covered in this data sheet. This data sheet provides guidelines for warehouse storage and for indoor locations other than warehouses. Outdoor storage of rubber tires is not included in this data sheet. 1.1 Changes May 2001. Added recommendations for the protection of specific storage arrangements of rubber tires using suppression mode and control mode specific application sprinklers (2.3.8) January 2000. This revision of the document has been reorganized to provide a consistent format. September 1998. The following changes were made during this revision: 1. Demand areas for 212F (100C) sprinklers has been included. (2.3.1.1.4) 2. A Recommended Safe Practice section has been added recommending a well trained Emergency Organization. (2.3.6) 3. Protection of mounted tires has been included. (2.3.7) 4. In-rack design for locations other than warehouses has been revised. Previously extra-hazard pipe schedule system and a rack water demand of 150 gpm (568 dm3/min) was recommended. (2.3.3.2) A hydraulic design is now recommended, mainly for ease of use because almost all systems are now being hydraulically designed. Also, it represents a reduction in cost of providing the protection without reducing the protection. Using the pipe schedule approach to size the in-rack piping can still be considered an acceptable design method, although the cost of installation may be higher. 2.0 LOSS PREVENTION RECOMMENDATIONS 2.1 Construction and Location 2.1.1 Steel Protection 2.1.1.1 Roof steel does not require additional protection when sprinkler or sprinkler plus high expansion foam protection is installed in accordance with this data sheet. 2.1.1.2 Column steel protection is recommended for on-floor storage or on-side storage in fully loaded portable racks when storage heights are 15 ft (4.6 m) and greater. However, column steel protection can be omitted provided one of the following: 1. High-expansion foam systems are used with ceiling sprinklers in accordance with this data sheet. 2. Ceiling sprinkler systems can provide both a 0.90 gpm/ft2 (37 mm/min) minimum density over the most remote 3000 ft2 (279 m2) demand area, and a 0.60 gpm/ft2 (24 mm/min) minimum density over the most remote 5000 ft2 (464 m2) demand area, using 286F (141C) rated sprinklers. When column protection is recommended, provide either a coating of at least one-hour fire resistance along the entire length of the column (see note 2 of Table 3), or one of the following: For solid H columns, provide a sidewall sprinkler directed toward the column at the 15 ft (4.6 m) level. For hollow tube and box columns, provide two sidewall sprinklers, one on each side of the column, directed at the column at the 15 ft (4.6 m) level. 2.1.2 Emergency Smoke and Heat Venting 2.1.2.1 Fire tests indicate that heat and smoke vents may increase the fuel consumed and sprinkler water demand. Hence, heat and smoke vents, if any, should not be arranged for automatic operation. Information in this data sheet applies to locations where roof vents and draft curtains are not provided.

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

8-3
Page 4

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

However, where local codes require that automatic vents be installed, it is preferred they be operated by a fusible link rated at 360F (141C). Smoke removal during mop-up operations frequently can be achieved through eaveline windows, doors, monitors, nonautomatic exhaust systems (gravity or mechanical), manually operated heat and smoke vents, or holes cut by fire department personnel. 2.2 Occupancy 2.2.1 When tires are stored on-tread, the dimension of the pile in the direction of the wheel hole should not be more than 25 ft (7.6 m) between aisles or vertical barriers (see Appendix A for definitions). Dimensions in the direction of wheel holes need not be considered when in-rack sprinklers or highexpansion foam systems are used. Aisles at least 8 ft (2.5 m) wide should be maintained between piles of tires and between tire storage and any other combustible storage. 2.2.2 The clearance from the top of storage to ceiling sprinkler deflectors should be at least 36 in. (0.91 m). 2.3 Protection 2.3.1 General 2.3.1.1 General installation details for ceiling and in-rack sprinklers should be in accordance with FM Global standards as outlined in Data Sheet 2-8N, Installation of Sprinkler Systems (NFPA), and Data Sheet 8-9, Storage of Class 1, 2, 3, 4 and Plastic Commodities, unless otherwise specified in this data sheet. In particular, the following general recommendations apply: 2.3.1.1.1 For racks with shelves (solid or slatted), sprinklers should be installed at the ceiling and at each level in all types of racks. In-rack sprinklers may be omitted if high-expansion foam systems are installed. 2.3.1.1.2 Single-row racks should be protected in the same manner as double-row racks. 2.3.1.1.3 Dry-pipe sprinkler systems should be used only in locations where wet-pipe systems are not practical. Water demands for dry-pipe systems are shown in Tables 1-3. 2.3.1.1.4 For new installations, large orifice (1732 in. [20 mm]), 286F (141C) rated sprinklers should be used. Demand areas shown for 165F (74C) rated sprinklers are given to evaluate existing sprinkler systems. To evaluate existing sprinkler systems with 212F (100C) rated sprinklers, the demand area should be interpolated between those shown for 165F (74C) and 286F (141C). 2.3.1.1.5 Two-point water demands are recommended in Table 1 and Table 2 for certain storage heights. When recommended, the ceiling sprinkler system should be capable of providing both water demands. Demands need not be available simultaneously. 2.3.2 Ceiling Sprinkler Design Tables 1, 2, 3 and 4 provide sprinkler water demands for various storage arrangements that may be found at tire storage locations. See Appendix A for descriptions and definitions of the various storage arrangements referenced below. 2.3.2.1 Warehouses 2.3.2.1.1 Use Table 1 when tire storage is on-side in permanent racks or partially loaded portable racks. 2.3.2.1.2 Use Table 2 when tire storage is on-tread in permanent or portable racks. 2.3.2.1.3 Use Table 3 when tire storage is on-floor or on-side in fully loaded portable racks. 2.3.2.2 Locations Other than Warehouses and Green Tires 2.3.2.2.1 Use Table 4 when tire storage is at locations other than warehouses such as retail stores, fleet garages and auto-service centers. Also use Table 4 for green tire storage in manufacturing areas.

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

8-3
Page 5

2.3.3 In-Rack Sprinkler Design 2.3.3.1 Warehouses 2.3.3.1.1 When recommended in Tables 1 and 2, in-rack sprinkler piping and water demand should be hydraulically designed, based on the simultaneous operation of the most hydraulically remote 20 sprinklers if two or more levels are installed (10 on each of the remote two levels) or 12 sprinklers if only one level is installed. A minimum of 30 gpm (114 dm3) should be available at the hydraulically most remote operating sprinkler. 2.3.3.1.2 Spacing of sprinklers on branch lines in racks should not exceed 10 ft (3 m) or an 80 ft2 (7.4 m2) area in a horizontal plane for multiple-row racks. 2.3.3.1.3 Sprinklers in longitudinal flues of racks should be located a minimum of 2 ft (0.6 m) from rack uprights. See Figures 1 through 6 for horizontal and vertical spacing. 2.3.3.1.4 When horizontal barriers are used in double-row racks with an overall shelf depth greater than 12 ft (3.7 m), install three lines of in-rack sprinklers beneath each barrier (see Note 4, Table 1 and Table 2). 2.3.3.2 Locations Other Than Warehouses 2.3.3.2.1 When in-rack sprinklers are recommended they should be installed in each double-row rack as shown in Figure 11 in Appendix A. In-rack sprinklers should be spaced a maximum of 8 ft (2.4 m) apart, with a maximum area coverage of 64 ft2 (6 m2). 2.3.3.2.2 In-rack piping can be hydraulically designed based on the operation of the 6 most remote in-rack sprinklers each flowing a minimum of 30 gpm (113 dm3/min).
Table 1. On-side Storage in Permanent Racks and Partially Loaded Portable Racks, Without Solid Shelves Height of Clearance storage ft ft (m) (m) (See Note 1) 510 10 (1.53.0) (3) 1015 10 (3.04.5) (3) 15-25 10 (4.5-7.5) (3) (See Note 3) 25-30 10 (7.5-9.0) (3) (See Note 3) Any height over 15 (4.5) 10 (3) Density gpm/ft2 (mm/min) 0.30.45 (1218) 0.450.60 (1824) 0.9 (37) and .60 (24) 0.30 (12) Area of demand (See Note 2) ft2 (m2) Wet system Dry system 286F 165F 286F 165F (141C) (74C) (141C) (74C) 3000 5000 3900 6500 (279) (464) (363) (604) 3000 5000 3900 6500 (279) (464) (363) (604) 3000 (279) 3900 (363) 5000 (464) 6500 (604)

Type of rack Portable, double row and multiple row

Alternate protection for double row

1.

2. Alternate protection for multiple row Any height over 15 (4.5) 10 (3) 1. 2.

3000 5000 3900 6500 (279) (464) (363) (604) Plus high-expansion foam (a) Horizontal barriers every 20 ft (6 m) vertically as in Fig. 1 with two lines of in-rack sprinklers under each barrier (see Note 4) OR (b) In-rack sprinklers every 15 ft (4.6 m) vertically as in Fig. 2. Provide ceiling sprinkler protection based on the height of storage above the top barrier/level of in-rack sprinklers (see Note 5). In-rack sprinklers every 15 ft (4.6 m) vertically as in Fig. 3. Provide ceiling sprinkler protection based on the height of storage above the top barrier/level of in-rack sprinklers (see Note 5).

1. For storage over 15 ft (4.6 m), when clearance between top of storage and ceiling sprinklers is greater than 10 ft (3 m), a horizontal barrier should be placed over the top of storage with sprinklers installed under the barrier. Ceiling density should be 0.20 gpm/ft2 (8 mm/min) over 2000 ft2 (186 m2) with 286F (141C) sprinklers. 2. When clearance between top of storage and ceiling sprinkler is about 3 ft (0.9 m), the area of demand may be reduced by 25%. 3. Do not interpolate for intermediate heights. 4. When double-row racks are deeper than 12 ft (3.6 m), at least three lines of sprinklers should be installed under each barrier. 5. When storage is less than 5 ft (1.5 m) high above the top barrier/level of in-rack sprinkler protection, the area of demand may be reduced by 15%. 6. See Appendix A for definition of Partial Loads.

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

8-3
Page 6

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

Fig. 1. On side, double-row racks, with barriers.

Table 2. On-tread Storage in Permanent Racks and Portable Racks, Without Solid Shelves Height of Clearance storage ft ft (m) (m) (See Note 1) 58 10 (1.52.4) (3) 812 10 (2.43.6) (3) 12-20 10 (3.6-6.0) (3) (See Note 3) 20-30 (6.0-9.0) (See Note 3) Alternate protection for double row Any height over 12 (3.6) 10 (3) 10 (3) Area of demand (see Note 2)ft2 (m2) Wet system Dry system Density gpm/ft2 286F 165F 286F 165F (mm/in) (141C) (74C) (141C) (74C) 0.300.40 3000 5000 3900 6500 (1216) (279) (464) (363) (604) 0.400.60 3000 5000 3900 6500 (1624) (279) (464) (363) (604) 0.9 (37) 3000 3900 and (279) (363) .60 (24) 5000 6500 (464) (604) 0.30 3000 5000 3900 6500 (12) (279) (464) (363) (604) Plus high-expansion foam 1. (a) Horizontal barriers every 15 ft (4.6 m) vertically as in Fig. 4 with two lines of in-rack sprinklers under each barrier (see Note 4) OR (b) In-rack sprinklers every 10 ft (3.0 m) vertically as in Fig. 5. 2. Provide ceiling sprinkler protection based on the height of storage above the top barrier/level of in-rack sprinklers (see Note 5). 1. In-rack sprinklers every 5 ft (1.5 m) vertically as in Fig. 6. 2. Provide ceiling sprinkler protection based on the height of storage above the top barrier/level of in-rack sprinklers (see Note 5)

Type of rack Portable, double row and multiple row

Alternate protection for multiple row

Any height over 12 (3.6)

10 (3)

1. For storage over 15 ft (4.6 m), when clearance between top of storage and ceiling sprinklers is greater than 10 ft (3 m), a horizontal barrier should be placed over the top of storage with sprinklers installed under the barrier. Ceiling density should be 0.20 gpm/ft2 (8 mm/min) over 2000 ft2 (186 m2) with 286F (141C) sprinklers. 2. When clearance between top of storage and ceiling sprinkler is about 3 ft (0.9 m), the area of demand may be reduced by 25%. 3. Do not interpolate for intermediate heights. 4. When double-row racks are deeper than 12 ft (3.6 m), at least three lines of sprinklers should be installed under each barrier. 5. When storage is less than 5 ft (1.5 m) high above the top barrier/level of in-rack sprinkler protection, the area of demand may be reduced by 15%.

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

8-3
Page 7

Fig. 2. On side, double-row racks, without barriers.

Table 3. On-floor and On-side Storage in Fully Loaded Portable Racks Height of storage ft (m) 510 (1.53) 1015 (34.5) 1520 (4.56) (See Note 2 below) 2030 (69.1) Density gpm/ft2 (mm/min) 0.250.35 (1014) 0.350.45 (1418) 0.450.60 (1824) Area of demand (See Note 1 below) ft2 (m2) Wet system Dry system 286F 165F 286F (141C) (74C) (141C) 2000 3300 2600 (186) (307) (242) 2000 3300 2600 (186) (307) (242) 3000 5000 3900 (279) (464) (363)

165F (74C) 4300 (400) 4300 (400) 6500 (604)

0.30 (12)

3000 (279)

5000 3900 (464) (363) Plus high-expansion foam

6500 (604)

1. When clearance between top of storage and ceiling sprinklers is about 3 ft (0.9 m), the area of demand may be reduced by 25%, but not less than 2000 ft2 (186 m2) for 286F (141C) sprinklers and 3000 ft2 (279 m2) for 165F (71C) sprinklers. 2. Provide steel column protection as recommended in Section 2.1.1, Steel Protection.

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

8-3
Page 8

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

Fig. 3. On side, multiple-row racks.

Table 4. Locations Other Than Warehouses and Green Tires Height of storage ft (m) 8 (2.4) 816 (2.44.0) Density gpm/ft2 (mm/min) 0.45 (18) 0.30 (12) Plus in-rack sprinklers (See Note 1 below) 0.20 (8) Area of demand ft2 (m2) 286F 165F (141C) (74C) 2000 2000 (186) (186) 2500 (229)

Arrangement Locations other than warehouses, On-tread, fixed, double-row racks

Green tires, in portable carts, 1-cart high Green tires, in portable carts, 2-carts high

8 (2.4) 816 (2.44.0)

3000 (279)

4000 (368)

0.30 (12)4000 (368) or 0.35 (14)3000 (279) or 0.40 (16)2000 (186)

1. A single row of in-rack sprinklers should be provided in each double-row rack as shown in Fig. 11. In-rack sprinklers should be spaced 8 ft (2.4 m) apart, with a maximum area coverage of 64 ft2 (6 m2). In-rack pipe sizing and water demand should be based on the operations of the six most remote in-rack sprinklers each flowing 30 gpm (113 dm3/min).

2.3.3.2.3 Alternatively, in-rack piping can be based on an extra hazard pipe schedule system. When in-rack piping is on an extra hazard pipe schedule, the in-rack water demand should be considered 150 gpm (568 dm3/min).

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

8-3
Page 9

Fig. 4. On tread, double-row racks, with barriers.

2.3.4 High-Expansion Foam Systems 2.3.4.1 When only ceiling sprinklers are provided, they may be supplemented by high-expansion foam systems, and the ceiling sprinkler density may be reduced to 0.25 gpm/ft2 (10 mm/min) over the area specified. 2.3.4.2 High-expansion foam systems when recommended should be installed in accordance with Data Sheet 4-3N, Medium and High Expansion Foam Systems. Inspection, testing and maintenance of high-expansion foam systems also are covered in Data Sheet 4-3N. System reliability is dependent on performing the recommended inspection, testing and maintenance at the recommended annual, semi-annual or weekly intervals. 2.3.5 Water Supplies 2.3.5.1 Water supplies should include provision for hose streams or high-expansion foam generators, whichever is greater, in addition to that required for sprinklers at ceiling and in racks. Hose stream allowance and the duration of supply should be in accordance with Table 5.
Table 5. Hose Stream Demand and Duration of Supply Storage arrangement Warehouse storage Green tires Location other than warehouse Hose stream allowance, gpm (dm3/min) 750 (2840) 500 (1893) 250 (947) Duration, hr. 3 2 2

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

8-3
Page 10

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

Fig. 5. On tread, double-row racks, without barriers.

2.3.6 Recommended Safe Practices 2.3.6.1 A well-trained Emergency Organization (EO) should be provided at rubber tire storage locations. Early detection and effective action by personnel during the early stages of a rubber tire fire can greatly help reduce ensuing damage. Controlling possible ignition sources, maintaining proper aisle spaces and practicing good housekeeping are other recommended safe practices. 2.3.6.2 When fighting a rubber tire fire, caution should be exercised because of the intense heat and large volume of smoke generated in this type of fire. It is not intended that fires beyond the incipient stage (see Appendix C) be fought by anyone other than trained fire fighters. 2.3.6.3 More specific details regarding manual fire fighting and fire behavior of a rubber tire fire can be found in the Appendix C, Fire Fighting. 2.3.7 Mounted Tires 2.3.7.1 Protect tires mounted on metal wheels as an unexpanded plastic commodity in accordance with Data Sheet 8-9, Storage of Class 1, 2, 3, 4 and Plastic Commodities. 2.3.8 Suppression Mode and Large-drop Sprinkler Protection 2.3.8.1 Based on the results of several large-scale fire tests with rubber tires the following guidelines are recommended. These guidelines should be applied at locations that store passenger car, truck and tractor, motorcycle, bicycle and green tires. The guidelines are for on-side and on-tread storage without solid shelves as defined in this data sheet. These guidelines are not intended for the storage of tires where the tires are stored in a laced arrangement. The laced arrangement is described as tires stored where the sides of the

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

8-3
Page 11

Fig. 6. On tread, multiple-row racks.

tires overlap, creating a woven or laced appearance. Large-scale fire tests have demonstrated that laced storage of tires cannot be adequately protected with the following suppression mode or large-drop recommendations. 2.3.8.2 These recommendations are specific to storage arrangements that are less than or equal to the storage heights and building heights specified in Tables 6 and 7. Without additional testing, protection recommendations for higher buildings or storage heights cannot be provided.
Table 6. Suppression Mode Sprinkler Protection Requirements Sprinklers: System type: Sprinkler system design: FM Approved Suppression Mode Sprinklers Wet-pipe (no dry-pipe or preaction) Design for 12 (K-factor 14) sprinklers at 50 psi (3.4 bar) or 12 K-factor 16.8 sprinklers at 35 psi (2.4 bar) or 12 K-factor 25.2 sprinklers at 20 psi (1.4 bar), flowing 4 sprinklers per branch line on 3 branch lines. Nominal 165F (74C) Follow all installation guidelines in Data Sheet 2-2, Installation Guidelines for Suppression Mode Automatic Sprinklers. 25 ft (7.6 m) 30 ft (9.1 m) 500 gal/min (1900 l/min). Two hours

Sprinkler Temperature Rating: Sprinkler Installation Guidelines: Maximum Storage Height: Maximum Building Height: Hose Stream (see note): Water Supply Duration (see note):

Note: The design of an suppression mode sprinkler system has traditionally included a hose stream and water supply duration of 250 gal/min (945 l/min) and one hour respectively. Fires with rubber tires produce dense black smoke, limiting access to the building. Because of the smoke, many authorities having jurisdiction require that the sprinkler system be allowed to operate for at least 60-90 min Also, the recommendations for using suppression mode sprinkler protection are based on the favorable results of two large scale rubber tire fire tests using Large-drop Sprinklers.

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

8-3
Page 12

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

Table 7. Large-drop Sprinkler Protection Requirements Sprinklers: System Type: Sprinkler System Design: Sprinkler Temperature Rating: Sprinkler Installation Guidelines: Maximum Storage Height: Maximum Building Height: Hose Stream: Water Supply Duration: FM Approved Large-drop Sprinklers Wet-pipe (no dry-pipe or preaction) 20 sprinklers at 75 psi (5.1 bar) Nominal 286F (141C) Follow all installation guidelines in Data Sheet 2-7, Installation Rules for Sprinkler Systems Using Large Drop Sprinklers. 25 ft (7.6 m) 30 ft (9.1 m) 500 gal/min (1900 l/min) Two hours

3.0 SUPPORT FOR RECOMMENDATIONS 3.1 General Tire storage presents a severe fire hazard. Tires burn rapidly, emitting intense heat and large quantities of dense smoke that hamper fire fighting. Tires are generally manufactured from synthetic compounds, carbon, oil, various additives and fabrics of steel, fiberglass, polyester, cotton, etc. The principal rubber materials used in tires are synthetic rubbers. Heat of combustion can vary from 14,000 to 20,000 Btu/lb (33 to 34 MJ/kg). Ignition temperature can vary from 700 to 800F (371 to 425C). The hollow toroidal shape of the tire provides a large shielded surface area and excellent flue spaces which, combined with the material, result in a severe fire hazard. Automatic sprinklers can control fires in most tire storages, but water demands are high. Manual fire fighting is valuable, but difficult because of the intense heat and smoke produced. 3.2 Loss History Fire experience in sprinklered buildings with rubber tires is very limited. FM Global records for the period January 1975August 1990 show only five fires involving rubber tire storage, but all of these involved storage without sprinklers or locations where sprinkler protection was out of service. 4.0 REFERENCES 4.1 FM Global Data Sheet 2-8N, Installation of Sprinkler Systems (NFPA). Data Sheet 4-3N, Medium and High Expansion Foam Systems. Data Sheet 8-9, Storage of Class 1, 2, 3, 4 and Plastic Commodities. APPENDIX A GLOSSARY OF TERMS Approved: references to Approved in this data sheet means the product and services have satisfied the criteria for FM Approval. Refer to the Approval Guide, a publication of FM Approvals for a complete listing of products and services that are FM Approved. Bundled tires: a storage method in which a number of tires are strapped together. Bundled tires may be compressed up to 50 percent of their original thickness. (See Fig. 7). Full loads: a portable rack is considered to be fully loaded when the open space between the top tire in one rack and the bottom of the next rack above is less than 12 in. (305 mm). When the space is 12 in. (305 mm) or more, the load should be considered partially loaded. (See Figs. 8 and 9.) Green tires: a green tire consists of a tire carcass, cylindrical in shape, approximately 17 in. (0.43 m) in diameter by 2 ft (0.61 m) long. The green tire at this point in the manufacturing process is ready for molding and curing into a finished tire. The preparatory process results in an advanced supply of green tires in storage in the manufacturing area awaiting molding and curing. (See Fig. 10.)

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

8-3
Page 13

Figs. 7, 8 and 9.

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

8-3
Page 14

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

Fig. 10. Typical green tire storage. Storage is two carts high or 16 ft (4.9 m).

Horizontal channel: an uninterrupted space in excess of 5 ft (1.5 m) in length between horizontal layers of storage. Such channels may be formed by pallets, shelving, racks, or other storage aids. (See Figs. 7, 14 and 17.) Locations other than warehouses: refers to tire storage in retail stores, fleet garages and auto-service centers. Tires are usually on tread in double-row racks. One arrangement has tires six high (about 16 ft [4.8 m]) with an open grid mezzanine at the three high (about 8 ft [2.4 m]) level. Another common arrangement has three high (about 8 ft [2.4 m]) storage. Generally aisles are 3 ft (0.9 m) wide. The storage areas are usually smallgenerally not more than 50 percent of the total room area. (See Fig. 11.) On-floor storages: tires 5 ft (1.5 m) or higher stored directly on the floor, on side or on tread; may be pyramided to provide pile stability. (See Figs. 12 and 13.) On-side storage: tires 5 ft (1.5 m) or higher stored horizontally or flat. (See Figs. 13, 14 and 15.) On-tread storage: tires 5 ft (1.5 m) or higher stored vertically or on their treads. (See Figs. 12, 16 and 17.) Palletized storage: a term used by the tire industry to designate tire storage on portable racks as shown in Figures 8, 14 and 16. Palletized storage as defined in Data Sheet 8-9 is not found in the tire industry. The conventional piling method is to store tires on-side when using portable pipe racks. However, using an alternative piling method, tires are piled both on-tread and on-side, enabling more tires to be stored per pallet. (See Fig. 8.) Racks are fully loaded and packed tight, such that there are no horizontal channels. Figure 9 shows a closer view of a single pallet load. Provide protection for this storage arrangement as outlined in Table 3.

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

8-3
Page 15

Fig. 11. Typical storage arrangements in locations other than warehouses.

Partial loads: a portable rack is considered to be partially loaded when the open space between the top tire in one rack and the bottom of the next rack above is 12 in. (25 mm) or more. When the space is less than 12 in. (25 mm), the loads should be considered fully loaded. Rack: any combination of vertical, horizontal and diagonal members which support tires. Racks may be fixed or portable. Some portable racks use a wood pallet as the base (see Fig. 18). Portable racks, as arranged in Figure 14, are called palletized storage in the tire industry. Vertical barriers: solid material such as sheet metal, plywood, gypsum board, etc., arranged to limit horizontal fire spread through the wheel holes. APPENDIX B DOCUMENT REVISION HISTORY This document does not have any revision history. APPENDIX C FIRE FIGHTING FM Global Research fire tests have indicated that while properly designed sprinkler systems can control a fire in tire storage, manual fire fighting may be necessary for complete extinguishment. An understanding of the behavior of tire storage fires is therefore essential if a fire under control is to be completely extinguished by the overhaul crew. Due to the hazardous conditions present in developed fires involving rubber tires, it is not intended that fires beyond the incipient stage be fought by anyone other than trained fire fighters.

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

8-3
Page 16

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

Fig. 12. On-floor storage. On tread unbundled (could be bundled). Distance along tire hole less than 25 ft (7.6 m).

C.1 Incipient Stage If discovered in the early stages, the fire can be effectively extinguished with manual protection. Drychemical extinguishers are effective because the powder can pass into the mass of tires and control the fire temporarily. However, it is necessary to back up extinguishers with small hose, and to remove burning tires from the pile. Removed tires should be taken outdoors away from other combustibles and thoroughly wetted down. The area in which the fire occurred should be constantly attended for several hours to watch for rekindling. Automatic sprinklers usually operate within two to five minutes of ignition. At this point, extinguishers are not generally effective. Because of smoke, the area becomes increasingly obscured and untenable. C.2 Active Stage At this point, because of poor visibility in the building, the ability to use hose streams effectively is questionable. Sprinklers should be allowed to operate until control of the fire is obtained. During this period, the building is best left unventilated. As control of the fire is gained, smoke will tend to change from black to gray and will diminish in intensity. Charged 1-12 in. (38 mm) hose lines should be laid out preparatory to entering the building for overhaul. Portable flood lights, self-contained breathing apparatus, personal protective gear, etc., should be assembled for the crew. C.3 Critical Stage After 60 to 90 minutes, when smoke intensity should have diminished, the building should be ventilated around the periphery of the suspected fire location. Close observation should be made of smoke conditions. If smoke generation increases, cease ventilating and close up the building if possible. Sprinklers should remain in operation during the critical stage.

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

8-3
Page 17

Fig. 13. Pyramid tire storage, on side, on floor.

C.4 Overhaul As soon as smoke clears enough to permit entry, the building should be entered, with small hose streams directed into burning tires. Sprinklers should remain in operation until the fire chief is certain that the fire is small enough to be extinguished by hose streams. Any sprinkler control valve that is shut off should be manned during the entire period of closure, to enable prompt reopening of the valve, if needed. Fork trucks and other means should be employed to remove tires from the fire area. It will be necessary to keep sprinklers or hose streams in operation during this procedure at least until evidence of flame is gone. The fire area should be patrolled for 24 hours following the fire. C.5 Use of High-Expansion Foam If a high-expansion foam system is used in conjunction with automatic sprinklers, sprinklers may be shut off one hour after ignition. An additional hour should be allowed for soaking of foam before the building is opened up for overhauling. After the initial fill, foam generators should be operated periodically during the soaking period to maintain the foam level. Any sprinkler control valve that is shut off should be monitored during the entire period of closure, to enable prompt reopening of the valve, if needed. Limited tests with highexpansion foam indicated that with adequate foam soaking, fire extinguishment is nearly complete. As a precautionary measure, charged hose streams should be available when foam is drained away.

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

8-3
Page 18

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

Fig. 14. Typical storage arrangement using pallet based portable rack. Note lack of horizontal channels when pallets are fully loaded.

APPENDIX D NFPA STANDARDS NFPA standards for the protection of rubber tire storage are covered in NFPA 231D. There are some significant differences in protection guidelines between this data sheet and NFPA 231D.

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

8-3
Page 19

Fig. 15. Double-row rack storage with on-side palletized storage.

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

8-3
Page 20

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

Fig. 16. Rack frequently used for on-tread storages.

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

8-3
Page 21

Fig. 17. Typical on-tread storage arrangement. Note horizontal channels.

2002 Factory Mutual Insurance Company. All rights reserved.

Valid Through May 2003

8-3
Page 22

Rubber Tire Storage


FM Global Property Loss Prevention Data Sheets

Fig. 18. Portable rack using wood pallet base and steel frame.

FM Engr. Comm. September 1991

2002 Factory Mutual Insurance Company. All rights reserved.