Beruflich Dokumente
Kultur Dokumente
WHO Me ?
The following tests should only be carried out by qualified and/or experienced engineers who have received SAFETY TRAINING ON LIVE EQUIPMENT. All test instruments and their leads/connectors/ probes must be checked to ensure that they are suitable for the voltage levels being tested, and are in good working order. Never attempt to test a LIVE generator without another competent person present to shut down the engine or switchgear as necessary. Ensure that the work area is SAFE, other personnel in the area are advised of what you are doing, warning notices and tapes are displayed to advise others of the hazards.
Maintenance - Requirements
Maintenance requirements for A.C Brushless Generators are :-
1. Bearing inspection ( Single or 2 Bearing). 2. Winding Insulation/ Contamination checks. 3. Visual Inspection for Corrosion and Contamination 4. Operational Checks
o Frames HC4,5 are manufacturer sealed bearings packed with Kluber Asonic grease type GHY72. They are assembled directly into the Generator end-brackets. o Frame HC6 have cartridge assemblies, with manufacturers sealed for life bearings. o Frames HC7 and Frame 8, have regreaseable cartridge assemblies, packed with Kluber Asonic grease type GHY72. o Regreasable bearings are optional on Frames HC 5 and 6. o Application and Environmental conditions can effect bearing life, excessive moisture, vibration, or airborne dust, can reduced bearing life.
Vibration
Increased vibration in the Generator, suddenly, or slowly over a period of time. Vibration equipment is expensive, a check by hand near the bearing will give an indication. ( Note: this could also be an engine related problem).
Noise
Bearing making abnormal noises, audible, with or without Stethoscope. ( A Stethoscope is required for elimination of other possible causes of noise ) Experience gained from touch and sound, will establish normal conditions. Periodic Health monitoring is recommended throughout the life of the Generator to establish normal conditions.
1. The Generator has been STATIONARY for a long period without AntiCondensation heaters SWITCHED ON. 2. The Generator has been subjected to intake of high volumes of water 3. The Generator windings are contaminated with Airborne DUST and DIRT, and have become DAMP ( through high humidity). The Generator windings have become contaminated with airborne corrosive elements ( Salt or corrosive chemicals in the atmosphere).
2. The Exciter Stator Winding This winding is subject to all contamination from the air intakes. Severe contamination may cause temporary or permanent low IR, which could effect the AVR performance. 3. The Exciter Rotor, & Main Rotor These are rotating low voltage windings, and are unlikely to be affected by low IR. Minimum value of insulation should be 1 M to EARTH. 4. Permanent Magnet Stator This windings is totally enclosed and unlikely to be affected by low IR.
N
W5 W2
W6 U6V6
Neutral
00 10
100
10
M
0.1
.01
6 7 8
W V U
FRAME
V5 V2
U5
U2
EARTH
MEGGER
1. Disconnect the AVR completely before carrying out this test. 2. Disconnect any connections from Neutral to Earth. 3. The Stator insulation should be checked with an Insulation tester.The test instrument should be 500 or 1000 volts for low voltage Generators (up to 690V). 4. For low voltage machines (up to 690V), the MINIMUM insulation value is 1.0 MegOhm to Earth (Ground).
Recommended methods of drying out DAMP, WET, or CONTAMINATED Stator Windings are :- .
1. DRYING WHILE STATIONARY Hot air is blown into the Generator AIR INTAKE. 2. DRYING WHILE RUNNING ON SHORT CIRCUIT The Main Stator is Short Circuited while separately exciting the Generator with a BATTERY, or the MANUAL VOLTAGE REGULATOR.
Both Methods can be carried out ON SITE, without dismantling the Generator. (NOTE: Example 1 requires a standard 13 Amp Mains supply socket).
Domestic Supply
Remove Air Intake Access Covers Direct a Domestic FAN HEATER ( 2 - 2.5 kW) into the AIR INTAKE. Leave Overnight (or 8 Hours min.) to blow out all Moisture. RE-CHECK INSULATION RESISTANCE AFTER DRYING ( Minimum value 1 M )
+
Main Stator
X+
Bearing
Main Rotor
Main Rotor
Shaft
Rectifier Fan 1. Stop the Generator Set and disable the Engine. 2. Disconnect the AVR wiring. 3. Replace the AVR with a 12V or 24V battery 4. Connect the battery to the Exciter Stator,(polarity must be correct).
N
6 7 8
W5 W2
W6 U6V6
W V U
FRAME
V5 V2
U5
Clampmeter
V1
RM S
U2
Attach SHORT CIRCUIT link to all 3 phases (NOTE: Shorting Links must carry full load current).. Attach Clampmeter to Link, capable of measuring FULL LOAD AMPERES, (or use the Generator set panel meters). CHECK ALL WIRING IS SECURE BEFORE RUNNING GENSET
TR UE
U1
!
WARNING!
XXX+
RUN ENGINE
12-24v BATTERY
The Current MUST NOT BE HIGHER THAN FULL LOAD AMPERES For effective drying, at least 70% of FULL LOAD CURRENT is required. Add more Batteries to increase the short circuit current if necessary (24VDC) Run until the windings are HOT and DRY, (at least 1 HOUR). If the IR is still less than 1 M , the windings require cleaning /refurbish.
X XX P2 P3 P4 X XX P2 P3 P4
RUN ENGINE
The M.V.R must be switched to MANUAL control, MINIMUM setting, before running the engine. Slowly increase the Current until FULL LOAD AMPERES are indicated. For effective drying, run for at least 1 hour at FULL LOAD CURRENT. . If the IR is still less than 1 M , the windings require cleaning /refurbish.
Maintenance requirements - Cleaning the Windings When is it necessary to clean the windings?
1. When (after drying), the windings are still reading less than 1 M to earth. 2. When the windings are heavily contaminated with dust,dirt, and/or diesel exhaust deposits. 3. When the windings are contaminated with corrosive chemicals ( salt deposits or other deposits), which immediately give a temporary low IR reading when damp.
For removal of embedded dirt, grease, salts, hydrocarbons, and other chemicals from the winding surfaces, HOT WATER CLEANING at maximum 25 psi pressure is recommended. For very heavy contamination, a non- corrosive detergent additive, (i.e : Karcher RM81 or equivalent), can also be used. NOTE: Detergents containing CAUSTIC chemicals must never be used on copper windings.
. The windings should then be thoroughly WASHED with clean water to remove all traces of detergents. . The windings must be dried in an oven at approximately 100 to 110C for at least 12 hours until the IR is higher than 1 M. A final coating of Anti-track paint can be added for further protection, I.e :Sterling VA63 or VA39, or Ultimeg 2000, 372, air drying varnish ranges.
Periodic checks should be made to :1. AVR and accessory terminal connections, for corrosion or loose joints. 2. Main Rectifier diodes, should be cleaned or changed if badly corroded. 3. Main output terminal, look for loose or high resistance joints, (Joints can be scanned with a laser thermometer for hot-spots while running on load).
DATE ########
VOLTS 415
LOAD 0
This figure should NOT CHANGE throughout the life of the generator. If the D.C reading becomes HIGHER, it is an indication of :1. Possible SHORTS in the EXCITATION WINDINGS, OR, 2. Possible faults with the MAIN RECTIFIER DIODES. THE NO-LOAD D.C VOLTAGE GIVES AN INDICATION OF GENERATOR HEALTH FAULTS WITHIN THE GENERATOR WILL CAUSE AN INCREASE IN THE D.C. VOLTS.