12
11
EC
Reserved Reserved
09 08 07 06 05 04 Real Time Sample Value Reserved EA AL EI Reserved Inpt Dta Fm Reserved Chl0 Process Alarm High Data Value Channel 0 Process Alarm Low Data Value Channel 0 Alarm Dead Band Value Channel 0 Pad EA AL EI Reserved Inpt Dta Fm Reserved Chl1 Process Alarm High Data Value Channel 1 Process Alarm Low Data Value Channel 1 Alarm Dead Band Value Channel 1 Pad EA AL EI Reserved Inpt Dta Fm Reserved Chl2 Process Alarm High Data Value Channel 2 Process Alarm Low Data Value Channel 2 Alarm Dead Band Value Channel 2 Pad EA AL EI Reserved Inpt Dta Fm Reserved Chl3 Process Alarm High Data Value Channel 3 Process Alarm Low Data Value Channel 3 Alarm Dead Band Value Channel 3 Pad EA AL EI Reserved Inpt Dta Fm Reserved Chl4 Process Alarm High Data Value Channel 4 Process Alarm Low Data Value Channel 4 Alarm Dead Band Value Channel 4 Pad
10
03
02
01
00
WHERE: EC = Enable Channel Inpt Dta Fm Chlx = Input Data Format Select: select the form the analog data is presented to the controller and used in the control program. Inpt Tp/Rnge Sel Chlx = Input Type/Range Select: configure the Input Type/Range. Reserved = Bits not used, allows for future expansion. Should be programmed to 0.
EC
Reserved Reserved
Reserved Reserved
The areas in red are the only bits that need to be changed to get the channels operational. 1. Set the enable bit to turn on the channel. Configuration Word 2, 8, 14, 20, 26, 32, 38, or 44: Bit 15: E Channel Enable. (0) Disabled. (1) Enabled. 2. Set the bits necessary for the output type and data type according to the lists below. Configuration Word 3, 9, 15, 21, 27, 33, 39, or 45: Bit 0-3: Input Type/ Range Bit 8-10: Input Data Format
INPUT DATA FORMAT SELECT Bit 08-10 Settings Bit 10 Bit 09 Bit 08 0 0 0 0 0 0 0 1 1 1 0 1
Input Type/ Normal Operating Range -10 to +10 Vdc 0-5 vdc 0-10 Vdc 4-20 mA 1-5 Vdc 0-20 mA
Bit 03
0 0 0 0 0 0
0 0 0 0 1 1
0 0 1 1 0 0
0 1 0 1 0 1
Data Format Raw/Proportional Data Engineering Units Scaled For PID Percent Range
3. Download the program to the processor to make the configuration take affect. Note: The actual addressing for the configuration word will appear as Local:e:C.Data[0] where e is the slot number of the analog card.
+/-10 Vdc
-105.00 to 105.00%* 0 to 105.00% 0 to 105.00% -5.00 to 106.25% -12.50 to 106.25% 0.00 to 105.00%
0-5 Vdc
0 to 16,383
0-10 Vdc
0.0V to 10.5V
0 to 16,383
-0 to 17202
0-100%
4-20 mA
0 to 16,383
0-100%
1-5 Vdc
0 to 16,383
0-100%
0 20 mA
0 to 16,383
0-100%