Beruflich Dokumente
Kultur Dokumente
To parallel an ac generator with another already on load, the following operations are necessary. See Figure
1and Figure 4.
(a) The terminal voltage of the incoming machine and the already running alternator on the bus bar must
be equal.
(c) The phase sequence of the two voltages must be the same.
(d) The emf of the incoming generator and the bus bars must be in phase.
The circuit breaker of the incoming generator must be closed when the voltages of the two generators are in
phase with each other i.e. waveform of both bus bar and incoming generator are synchronised.
This is done by adjusting the frequency/speed of the incoming generator and watching the synchroscope or
synchronising lamps for the moment when the two voltages are in phase.
If a synchroscope is used in paralleling, the two waveforms will be in phase when the synchroscope pointer
remains stationery at 12 0’clock. This is not easy to achieve so in practice, when the pointer is rotating not
faster than 1 revolution in 5 seconds in the fast direction, initiate closing of the circuit breaker when the pointer
is at about 11 0’clock (considering circuit breaker mechanism also takes some time to close).
In this way, with the incoming machine slightly fast, it will immediately assume load.
If switch on when running slow, it would take motoring load which might possibly operate the reverse power
relay. That is why reverse power relays are provided with time lag, to give sufficient time to correct the fault.
Bus Bars
R
Line Voltage
Y
Line Voltage
B
Circuit
Breaker
Alternator
Phase
Winding
Phase
Voltage
Figure 1
When the phase angle, Ø, between bus bar and in-coming machine voltages becomes zero, VR, VY, VB, all
become zero and the lamps becomes dark. The e.m.f. of the bus bar and the incoming generator are in phase.
This is the required condition for closing the switch.
1) The lamps need a fair bit of voltage before their light becomes visible so they are not very accurate.
2) When the speed is not quite correct there is not indication of whether the speed is too high or too slow.
Bus Bars
R
Y
B
L L L
Y1
B1
R1
Incoming
VR
Generator
R2 R1
VB
B2
B1
VY
Y2 Y1
VR V R1 V
V Y2 Y
V V Y1
R2
V VB2
B1
Figure 2 VB
The condition for synchronising is indicated when the red lamp is out and the yellow and blue lamps are of
equal brightness. This is much more accurate. Furthermore, the sequence of brightness reverses from too
slow to too fast.
Bus
R
L L L
VR V
R1 V Y2
V
Y1
V
R2
Incoming
Generator V
B1
VR
V
B2
R2 R1
VB
B2 B1
VY
Y2 Y1 Figure 3
B
Incoming Voltmeter
V S F V
Bus Bar
Incoming Synchroscope Voltmeter
Generator
Figure 4
Synchronising Power
If one alternator is ahead of another in phase when the synchronising switch is closed; i.e. the generator emfs
are not in phase, a resultant emf, Ec ia set up in the local circuit even though the alternator e.m.f.s or terminal
voltage are equal.
The synchronising current, Ic set up by this e.m.f. takes power from the machine that is running faster and
delivers it to the machine that is running slower. Thus the faster machine is pulled back or accelerated by motor
action, until their voltages come more nearly into phase.
(A time delay of say 5 seconds prevents reverse power tripping due to surges at synchronising).
This action reduces Ec and therefore reduces Ic so that again, the synchronising current limits itself. The
greater the phase displacement of the e.m.f.s when the synchronising switch is closed, the greater are
Ec and Ic and the more violent is the action pulling the machines into phase. This sets up dangerous high
values of torque on the shafts against the driving torque of the prime movers.
Assume machines are synchronised when E1 of alternator 1 is Φ° in advance of its proper phase relation to E2
of alternator 2 shown as E1’.
IC
E'1
-
Ec 0 φ
• Figure 5 E
E2 1
Resultant e.m.f. is Ec.
The current Ic again lags behind Ec by the angle θ determined by the ratio of reactance to resistance in the
circuit between the machines.
P1 = E1Ic cos α
P2 = E2Ic cos β
Note that P1 is positive, representing generator action and P2 is negative representing motor action, This results
in pulling E1 back (clockwise) and pushing E2 ahead (counter-clockwise) thus bringing them more nearly into
phase (180° to each other in the local circuit) as they should have been when synchronised.
The mechanical power which is exchanged between the machines while they are out of phase and which brings
them into phase is very important for the successful operation of alternators in parallel. It is called
synchronising power and the circulating or synchronising current is so called because it keeps the machine in
synchronism.°
Figure 6
I1
I2
XS
IS
Terminal volttage
R across a load
E1 E2
E1 E2
E2
External Local
Circuit Circuit
Suppose the alternator 1 gets extra input, its rotor will accelerate and emf E1
will get ahead of E2. As a consequence there is a resultant voltage Ec = E1 - E2 in the local series circuit which
will drive a current, Ic through the two armatures.
The current Ic lags behind Ec by 90° (because alternator impedance is predominantly reactive).
From Fig. 7 it is seen that Ic known as synchronising current is almost in phase with E1 and in phase opposition
to E2.
Alternator 1 is generating a power:
In other words, alternator 1experiences a generating action tending to retard it and alternator 2 receives the
power generated by Alternator 1 and thus experience motoring action tending to accelerate it. It is thus seen
that there is an automatic synchronizing
action, tending to retard the faster machine
E1 and accelerate the slower machine, thereby
maintaining the synchronism.
IC
Ec
2
Local Circuit
E2
Figure 7
Suppose the 2 alternators are now equally loaded such that I1 = I2 and internal pf cos θ1 = cos θ2. If fuel supply
to alternator 1 is increased by governor setting Ic is set up as before.
• For alternator 1
• For alternator 2
E1 E1
I ' I '
1 1
' '
1 1
I I
1
1
1
1 I C
IC
Ec
Ec
'
' I2
I2
' ' 2
2 2 2
I2
I2
E2
E2
Figure 9
Fig-8
Consider again 2 alternators running in parallel at no-load with E1 = E2. If the excitation of alternator 1is
increased a resultant voltage Ec = E1 - E2 is established in the local circuit. Since the impedances of the local
circuit is mainly reactive, Ic lag Ec by about 90°. It is found that Ic produced armature reaction, which is
demagnetising for alternator 1 and magnetising for alternator 2, tending to equalise the 2 alternator emf’s.
If two alternators are equally loaded and the currents are I1 and I2 at internal pf angles θ1 and θ2 respectively.
EC = E1 - E2
which circulates a load current Ic. This circulating current Ic must be added to I1 and I2 to get the new
currents. These are I1’ for alternator I and I2’ for alternator 2.
From Figure 10 which is a phasor diagram showing the effect of excitation, it is seen that though I1’ has
increased, its real power component is unchanged and similarly I2’ has decreased but its real
component remains the same.
It can thus be said that a change in the excitation modifies the distribution of reactive power but the
division of active or real power is unaltered.
a) a variation of prime-mover governor setting changes the distribution of active power shared by the 2
alternators.
b) a variation of the excitation determine the terminal voltage and distribution of reactive power of the two
alternators.
E1 E1
E2 E2
I '
' 1
1 I
1
Ec Ec
IC
IC
2
'
I2 2
'
I2
E2 E2
Figure 10
Alternators in parallel must be driven at the same electrical speed; that is at the same frequency. The terminal
voltages of all parallel connected generators must be the same, since their terminals are all respectively
connected together.
Hence a 4-pole alternator, driven at 1800 rpm may be operated in parallel with a 6-pole alternator driven at
1200 rpm. Each generates a 60 cycle e.m.f. and therefore is driven at the same electrical speed.