NOTICE

Midea water cooled packaged air conditioner is designed and manufactured strictly based on relevant standard to ensure good performance, high reliability and excellent adaptability. Instructions on correct installation, debugging, operation and maintenance are specified in this manual. Please read this manual carefully before operating the unit. The installation and debugging should be conducted by professionals. Our company will be not responsible for the damage to machine or personal hurt caused by incorrect installation, improper debugging and unnecessary maintenance which are not specified in this manual.

CONTENTS
Specification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Outline and Dimension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Air Pressure Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Installation of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Electric Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 Installation of Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Installation of Water System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 Working Condition and Description of Functions . . . . . . . . . . . . . . . . . . .16 Reparation and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22 Troubles and Shooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

The illustrations and information in this manual are just for reference, please refer to the actual product. Manufacturer has the right to make amendment to drawing or technical parameter due to improvement of product without notice.

Specification
Model Cooling capacity Rated power EER Rated current Power supply kW kW W/W A L60/S-C 60 15.2 3.95 30.9 L80/S-C 75 19.0 3.95 37.2 L100/S-C 97 23.8 4.07 45.0 380V 3N 50Hz L120/S-C 117 29.5 3.97 58.5 L135/S-C 133 34.1 3.9 62.5

Compressor

Type Starting method Output power Chilling oil kW Type L 1.84 82 1 kW Drive Air flow m /h
3

Hermetically sealed flexible scroll compressor Direct staring 3.094 4.04 3.096 Mineral oil 1.84 92 1 3.0 14000 147 16.5 9806 65(2-1/2") 65(2-1/2") 25(1") 25(1") 1839/2047 1420/1604 1055/1230 700/733 1.86 R22 83 2 5.3 Belt drive 11000 147 12.9 9806 65(2-1/2") 65(2-1/2") 25(1") 25(1") 1839/2047 1420/1604 1055/1230 690/723 18200 147 22.1 9806 65(2-1/2") 65(2-1/2") 25(1") 25(1") 1839/2047 1912/2152 1055/1230 820/870 20600 147 26.7 9806 65(2-1/2") 65(2-1/2") 25(1") 25(1") 1839/2047 1912/2152 1055/1230 830/880 20600 230 28.8 9806 65(2-1/2") 65(2-1/2") 25(1") 25(1") 1839/2047 1912/2152 1055/1230 840/890 Pa m3/h Pa mm/inch mm/inch mm/inch mm/inch mm mm mm kg 93 2 5.5 9.53 2 5.5 3.03 3.33 8.03 9.533

Refrigerant Fan motor Windmill Motor

Type kg

2.8

External static pressure Cooled Water flow water Water side pressure Pipe dia. Water inlet Pipe dia. Water outlet Water outlet, evaporator Water outlet, chassis Height (before/after packaging) Length (before/after packaging) Width (before/after packaging) Net weight/gross weight Protection device High-pressure protection Low-pressure protection Noise

Overcurrent protection, High/low pressure protection, Antifreeze protection, Internal temp. protection of compressor, phase protection 24 0.3 66 24 0.3 66 24 0.3 74 24 0.3 74 24 0.3 75

kgf/cm2 kgf/cm2 dB(A)

Note: 1. Input power in Table 3 excludes that of motor of cooling tower and water pump. 2. 38Working condition17 dry bulb temp. inlet water temp.33 relative humidity30%95%. 3. Max. pressure of water system 1Mpa. 4. Test condition of nominal capacity: indoor dry bulb temp. 27, wet bulb temp. 19, outlet water temp.35, inlet water temp.30.

Outline and Dimension


1. Dimension of L100120135/S-C

A ir o u tlet

A ir strainer T o uc h sc reen

C oo led w a ter ou tlet C oo led w ater inlet

P ressure g au ge In stallation h ole4- 15 E m erg en cy -relief ou tlet

C on d ensa te o utle t

Model L100/S-C L120/S-C L135/S-C

A 206 206 206

B 632 632 632

C 434 434 434

D 1055 1055 1055

E 482 482 482

H 1839 1839 1839

W 1912 1912 1912

2. Dimension of L6080/S-C

A i r o u tlet

A ir st rain e r T o u ch scr e en

C o o le d w ate r o u tl et C o o le d w ate r in le t

P r e ss u r e g a u g e In stall atio n o4- 1 5 h le

E m erg en c y - relief o u tl et

C o n d e n sa te o u tlet

Model L60/S-C L80S-C

A 235 235

B 558 558

C 1055 1055

E 478 478

H 1839 1839

W 1420 1420

Air

Pressure Curve

10 m / h

147

L120/ S- C( 810 ) turn

L135/ S- C( 910 ) turn

L100/ S- C( 740 rn) tu L80/ S- C( 800 ) turn

L60/ S- C( 710 ) turn

Pa

Air pressure curve* refers to the working state of static pressure

Installation of Unit
A. Primary inspection 1. Relevant document: about installation location. 2. Installation location: Install the unit at the place where it is convenient for installing water pipe and wiring. Keep the unit away from oil, smoke or other heat sources and make sure that the noise and outlet air do not influence the surroundings. 3. Installation space: Keep a certain space for reparation and maintenance (see Fig. 1). Make sure the air flow of heat exchanger on gas side is unblocked.

>1. 2m

U n it

>1. 2m >1. 2m >1. 2m

Chart 1 4. Installation basement: Ensure that the unit is installed on concrete basement or metal bracket with smooth surface which are solid and firm enough. 5. Delivery and inspection: Users should unpack and check the unit at the place of delivery. a) Check whether all the accessories are all complete. Item Quantity Installation, operation and maintenance manual Users service manual b) Check the model and specification of unit. d) Check whether there is refrigerant leakage. Remark Given to user Given to user

c) Make sure the unit and the components thereof are intact and complete.

If there is any problem, please contact us or our local dealer. Note: Do not unpack the package after inspection; otherwise the unit may be damaged. B. Carry the unit 1. Please handle with care while carrying the unit. 2. Carry the unit with crane or roller rather than by pushing. 3. Do not remove the wooden base until the installation of unit is completed. 4. Please lift the unit with hoisting equipment. 5. Cushion should be used lest the unit is damaged. C. Location and space The unit should be installed at horizontal steel or concrete basement which can support the weight of unit. Its forbidden to install the unit at damp, caustic or explosible place. If the unit is installed in the open air where the temperature is low, our company will not responsible for antifreeze protection. Keep a certain space for drainage, ventilation and maintenance, where it is convenient to remove the compressor and condenser. D. Noise control For normal operation, we take the following measures to control noise: 1. Interior shockproof of compressor. 2. Adopt low-noise fan and the motor equipped with rubber shockproof cushion. 3. If there is an air return duct, a flexible pipe is necessary on site. Partition the unit and pipe with wall or ceiling. For least influence by noise, please locate the unit at the places away from users such as the location near staircase, elevator or restroom. Its suggested to build a partition wall between the unit and the room, on such occasion, the door and window should be well-tight and the air return device is needed in equipment room. For the noise can be transmitted into the room, absorbing sponge should be put in the duct.

Electric installation WARNING

Make sure the electric components accord with the following specification and relevant regulations:
Table 5

Item Model

Power supply

L60/S-C L80/S-C L100/S-C L120/S-C L135/S-C

380V 3N 50Hz

Min diameter of power cordmm2 (Metal wiring with synthetic resin insulation) Groundin Power cord g wire 30m 25 10 35 16

Manual switch A Capacit y 150 Fuse 100

Leakage protector

100mA

Do not switch on power before completing installation, or danger may occur. The unit should be correctly grounded according to electric regulation to avoid leakage. A. Wiring of main power supply 1. Locate the switch control box of main power supply at proper place. 2. Fix an insulation washer through the power cord. 3. Connect the power, zero conductor and grounding wire with terminals in electric box. 4. Connect the wiring with terminals A, B, C and N. 5. The phase connection should be correct. 6. Keep the main power supply away from nonprofessionals to avoid misoperation. Note: Please refer to the wiring chart when doing wiring work. B. Control wiring connection 1. Control wiring connection of cooled water pump: Connect the terminals of AC contactors of cooled water pump with terminals A5 and A6 as follows:

Cooled water pump

A5

A6

380V 3 ~ 50Hz

Water pump

AC contactor, cooled water pump


Working voltage: 220V 50Hz ~

2. Control wiring connection of fan of cooling tower: Connect the terminals of AC contactor of cooling tower fan with terminals A7 and A8 as follows:

Fan, cooling tow er

A7

A8

380V 3 ~ 50Hz

Fan

A C contactor, cooling tow er fan W orking voltage: ~ 50Hz 220V

Wiring Chart

10

XT1

Ma i n p o we r cor d i nl et
380V 3 N~5 0 Hz
L12 C O MP 1 B

C N 2

B C N
C O MP 1 A L 11 K M1 B
Red C N2 2 C N2 3 Bl a c k

Wh i t e Bl ue Bl ack
RT 3

RT2

RT1
TO C UR RE NT C HE CK B OA RD 2 TO C UR RE NT C HE CK B OA RD 1

r o 3 H - p 3 r L o - p P Q 5P Q 6 B l u e B l u e o 2 H - p 2 r L o - p Pr Q 3P Q 4 Y e l l o w Y e l l o w 1 H - p 1r Lo - p rP o 1 Q R e d R e d

A
Re d

Cn2 4

CN21 B l ue ( wh i t e)

Ma g n e t i c

C N 4 C N 4 C7 N 4 C8 N 4 9 C N 3 6

D i s p l a y k e y b o a r d

2 c i r c l e

l oo p CN20

RT4

K M2 A
C N 3

T r a n s f o r me r 1

Ma i n c o n t r o l b o a r d
CN26

L13 K M2 B L14
Code I ndi c at i on of f ai l ur e
Op e n c i r c u i t o r s ho r t c i r c u i t o f T 1 P h a s e e rro r E0 E1 E 2&1 u ni t E 2 &2 u n i t E 2 &3 u n i t E 5&1 u ni t E 5&2 u ni t E 5&3 u ni t P 0&1 u ni t P 0&2 u ni t P 0&3 u ni t P 1&1 u ni t P 2&1 u ni t P 3&2 u ni t P 4&2 u ni t P 5&3 u ni t P 6&3 u ni t

C OMP 2 A

A
C N 2

N
C N2 5 C N4 3 CN 1 4 C N1 3 CN 1 2 C N8 CN 5 C N4 CN6 CN7 CN38 CN 9 C N34

CN 3 1 C N1 8

C OMP 2 B K M3 A

3B
K M3 B K M3 A

3A

2B

2A

1B

1A

A5

A6

A7

A8
Coo l e d F an w a t e r p u mp c o o l i n g t o w e r K M2 B K M2 A

Red

Bl ue

XT2
KM5 K M6

L21 K M3 B L22 K M4 L23 L24


D i s c r i p t i o n o f s y mb o l s
L 1 1, 12 , 1 3, 14 , 2 1, 2 2, 23 , 2 4 C O MP 1 A , 1 B , 2 A , 2 B , 3 A , 3 B F AN RT1 RT 2 RT3 RT 4 1H- p r o / 1 L - pr o 2 H- p r o / 2 L - p r o 3 H- p r o / 3 L - p r o

C O MP 3 A

K M1 A

T r a n s f o r me r KM4
C N 5

C N 4

C OMP 3 B

Cur r e nt c hec k bo a r d 1 l ef t L11 L12 L13 L14


K M5

CN 3 C N2

C N1

C N5

Cur r ent c heck bo ar d 2 r i ght

L 21
3 8 0V 3 5 0 Hz P

L 22

L23

L24

~
FAN

K M6

380V 3 5 0 Hz

~
C u r r e n t t r a n s f o r me r AC cont ac t or C o mp r e s s o r mo t o r I ndoor f an R e t u r n a i r t e mp . s e n s o r

Mo d e l

R e ma r k

E v a p o r a t o r p i p e t e mp . s e n s o r , N o . 1 , 2 a n d 3 u n i t P r e s s u r e s wi t c h , No . 1 u n i t ( h i g h / l o w pr e s s u r e ) P r e s s u r e s wi t c h , No . 2 u n i t ( h i g h / l o w pr e s s u r e ) P r e s s u r e s wi t c h , No . 3 u n i t ( h i g h / l o w pr e s s u r e ) C o mp r e s s o r d i s c h a r g e t e mp . p r o t e c t i o n s w i t c h XT1 2 4 - p h a s e t e r mi n a l M o t o r , c o o l e d w a t e r p u mp

P9&1 uni t P9&2 uni t P9&3 uni t

P F

F a n mo t o r , c o o l i n g t o w e r

C N 4

11

K M1 B

Pr ov i ded by us er

Installation of Fan RPM of fan depends on the air flow needed, accessories as well as resistance in air supply and return ducts. Pulley and the specification of belt are determined according to RPM and power. Adjust the resistance in air supply and return ducts after starting the motor to ensure even air flow in the room.

Fr e oc
R le u r

4k yp ins e o t

Make the belt in proper tensity by adjusting the position of motor pulley and fan pulley. (See following picture, press the belt and the distortion is about 20mm.) When stopping the pulleys, the time interval between these two pulleys should be more than 7s.

Chart 2: Adjust the tensity of belt Readjust the tensity of belt 1 week after the operation of unit. Check regularly every 1 to 2 months and make sure the distortion should be about 20mm. Replace the belt when necessary. Note: The belt which is too tight or too loose may generate noise and be harmful to the unit.

12

Installation of Water System


A. Water system with single unit

Pressure gauge Pipe joint

Thermometer

Maintenance valve Filling valve

Cooling tower Water strainer Maintenance valve

Pipe joint

Pressure Thermometer gauge Adjusting valve Drain valve

Water pump

Installation schematic diagram (water system with single unit)


B. Water system with multi-unit

13

Turnoff valve

Cooling tower Pipe joint Pressure gauge Thermometer Maintenance valve Filling valve Maintenance valve

Pressure gauge Thermometer Pipe Adjusting joint valve Drain vavle

Water pump

Water strainer

Installation schematic diagram (water system with multi-unit)

WARNING
Water pump and fan of cooling tower should be together controlled by the unit. High-pressure

protection will work in case water pump or cooling tower does not start. In case the water pump and fan of cooling tower are not controlled by the unit, please make sure

that they are turned on before starting the unit. unit. The minimum distance between every unit should be 1200mm. A maximum of 3 units can be paralleled connected in water system. C. Precautions C.1 Water pump 1. Water pump is installed in the inlet of condenser for the purpose of reducing resistance. The suction port of pump should be close to water pool or cooling tower and the suction pipe should not be too long. 2. Maintenance valve is fixed between suction pipe of pump and condenser. Please use throttle Be sure that the unit is turned on if the water pump and fan of cooling tower are connected with the

14

valve rather than maintenance valve to adjust water flow. 3. Flexible pipe fixed on suction pipe and discharge pipe of pump can effectively reduce vibration and noise caused. 4. Pressure gauge and thermometer should be installed at the place where it is convenient to get the reading. C.2 Cooling tower 1. Its suggested to install the cooling tower in shady, well-ventilated and unpolluted place. 2. Do not locate the cooling tower at air outlet or in the kitchen or the like places where the temperature is high. 3. Check the structure and dimension of cooling tower to determine whether it is applicable. Take into account the bearing capacity of floor and the noise level of cooling tower. 4. Either load or the ambient temperature should ensure constant water flow in condenser and normal working state of every pressure valve and every sensor. 5. The cooling tower needs water constantly because the water inside keeps evaporating. The amount of supplementary water is usually 1~3% of circulating water. The bottom of cooling tower should be equipped with filling pipe and overflow pipe which can drain the filth into sewer. 6. Clean the water with cleaning agent and softening agent regularly to keep the water in good quality. P-H value of water should be within 6~8 and the turbidity is less than 5mg./Litre. The content of iron and CaCO3 should be less than 0.3mg/Litre and 50ppm respectively. 7. One cooling tower can be connected with a maximum of 3 units. When one unit is running, the condensers and the switches of filling valve of other units should be turned off. Otherwise some circulating water will pass through the unworking units, which may cause insufficient water or over high water temperature in the working unit, reducing cooling capacity. Working Condition and Description of Functions A. Power supply Voltage: rated voltage 380V, acceptable range: 343~418V. Frequency: AC input frequency is 50Hz. Electric control: working temperature: -748; humidity: RH40%~RH90% B. Color LED display and operation instructions

15

B.1 Description of LED icons

FAN COOL
T1 T2 T3 T4 T5

SWING FAULT QUERY


Timer ON

sto p

STANDBY

Unit
MODE ADJUST

LOCK QUERY

h Timer OFF

ON/OFF

TIMER

B.2 Operation instructions 1. ON/OFF This button is used to turn on and turn off the air conditioner. 2. MODE 2.1 2.2 Two working modes can be selected: FAN and COOL The mode will be changed by pressing this button. The corresponding icon of selected mode will flash with the frequency of 2Hz. No operation within 3s, the unit will work on the selected mode. 2.3 Following the item 2.2 can shift to the other mode.

3. ADJUST 3.1 : For increasing temperature. The temperature will increase 1 once pressing this button. If keeps pressing more than 1s, the temperature will increase with the rate of 1/second. The highest temperature is 30 (no sound by buzzer now). 3.2 : For decreasing temperature. The temperature will decrease 1 once pressing this button. If keeps pressing more than 1s, the temperature will decrease with the rate of 1/second. The lowest temperature is 17 (no sound

16

by buzzer now). 4. TIMER 4.1 : For increasing the time.

The time will increase 1 hour once pressing this button. If keeps pressing more than 1s, the time will increase with the rate of 1hour/second until it reaches 24 hours (no sound by buzzer now). If no other operation within 6s, it will return to original state which can be shown from the display in icon 88. 4.2 : For reducing the time.

The time will decrease 1 hour once pressing this button. If keeps pressing more than 1s, the time will decrease with the rate of 1hour/second until it reaches 0 hour (no sound by buzzer now). If no other operation within 6s, it will return to original state which can be shown from the display in icon 8. 4.3 If the time of Timer ON and Timer OFF is 0, the timer setting has been canceled.

5. QUERY Following information will be displayed in sequence once pressing this button: 1) T1, icon QUERY is lightened; 2) T2 of No. 1 unit, icon QUERY is lightened; 3) T2 of No. 2 unit, icon QUERY is lightened; 4) T2 of No. 3 unit, icon QUERY is lightened; 5) The latest failure code or protection code, icon QUERY is lightened. 6. LOCK The icon will be lightened when pressing this button for the first time, which will be off for the second time. When setting this function, other buttons are unavailable. (Note: This button is on the low right side of the display which should be pressed with a needle.) C. Description of LED display 1. When turn on the unit, icon Midea is lightened. 2. ON/OFF will be lightened and off as the unit is on and off. 3. Display of running mode: 1) Press MODE button and the corresponding icon will flash, which will keep lightened after 3s. 2) Description of mode icons:

17

3) If failure occurs, the corresponding mode icon and icon FAULT are lightened, meanwhile the failure code is displayed. 4. State of fan As the fan is working, three-layer of light below logo Midea will flash with a certain frequency circularly like a wave. It will be off as the fan stops. 5. Locking state Icon 6. Swing Press and simultaneously, icon SWING will be lightened or off. As the fan is turned on, the swing direction can be controlled; if the fan is turned off, this function is unavailable. (Note: This function is reserved.) 7. Display of temperature 1) Instructions is lightened when the buttons are locked and it will be off when they are unlocked.

No temperature display when selecting FAN mode. 2) When displaying temperature, the value of temperature will be displayed at the latter two digits and the first digit will show whether this figure is positive or negative. ( for negative and blank for positive). reflects that this figure is the value of temperature. 3) Icon 88 displays the set time, h shows that this figure is the value of time and the range is 0~24 hours. 4) For the situation of displaying protection or failure code, the first digit displays P (protection)

18

or E (Failure), and the latter digit displays code 0~9. 8. Timer 1) Two functions: Timer ON and Timer OFF. 2) Pressing TIMER, the set time will be displayed on icon 88h. 3) The state of Timer ON and Timer OFF will be displayed in turn by alternating pressing the button. Adjust the time through buttons and. 4) The range of set time: 0~24 hours. 5) Set the time via buttons and. 6) On Timer ON mode, the icon will be lightened when the unit is turned off. When it is time for Timer ON, the unit will be turned on automatically. No pressing on and in 6 seconds, the display at 888 will return to the original state. 7) On Timer OFF mode, the icon will be lightened when the unit is working. When it is time for Timer OFF, the unit will be turned off automatically. No pressing and in 6 seconds, the display at 888 will return to the original state. D. Failure codes table The failure codes will be displayed on the screen in case there is failure. You can find the corresponding content of failure from following table.

Display E0, icon FAULT is lightened E1, icon FAULT is lightened E2 and No.1, icon FAULT lightened E2 and No.2, icon FAULT lightened E2 and No.3, icon FAULT lightened E5 and No.1, icon FAULT lightened E5 and No.2, icon FAULT lightened E5 and No.3, icon FAULT lightened P0 and lightened P0 and lightened P0 and lightened No.1, No.2, No.3, icon icon icon FAULT FAULT FAULT

is is is is is is

Content of failure or protection Open circuit or short circuit of T1 Phase error Open circuit and short circuit of T2, No.1 unit (T2A) Open circuit and short circuit of T2, No.2 unit (T2B) Open circuit and short circuit of T2, No.3 unit (T2C) System failure 3 times in 30 minutes, No.1 unit System failure 3 times in 30 minutes, No.2 unit System failure 3 times in 30 minutes, No.3 unit

is is is

T2 low-temperature protection, No.1 unit (T2A) T2 low-temperature protection, No.2 unit (T2B) T2 low-temperature protection, No.3 unit (T2C)

19

P1 and No.1, icon FAULT lightened P2 and No.1, icon FAULT lightened P3 and No.2, icon FAULT lightened P4 and No.2, icon FAULT lightened P5 and No.3, icon FAULT lightened P6 and No.3, icon FAULT lightened P7, icon FAULT is lightened P9 and No.1, icon FAULT lightened P9 and No.2, icon FAULT lightened P9 and No.3, icon FAULT lightened

is is is is is is is is is

Current protection, compressor 1 Current protection, compressor 2 Current protection, compressor 3 Current protection, compressor 4 Current protection, compressor 5 Current protection, compressor 6 Current protection, indoor fan Discharge temp. and high/low pressure protection, No.1 unit Discharge temp. and high/low pressure protection, No.2 unit Discharge temp. and high/low pressure protection, No.3 unit

Reparation and Maintenance


A. Ensure the water quality The water from well and river which contains lots of solid particles, organic substances or scalelike sediment should be filtrated or softened before they are used in condenser and evaporator. Otherwise, the sand or mud in chilled water may block the pipeline. Please analyze the PH-value, conductivity, the content of ammonia ion and sulfide ion and make sure they meet the following standard, if not, only industrial water can be adopted. Cooled water system Item Standard requirement pH (25) Conductivity(mS/m) (25) {s/cm}(25) (2) Ion chlorine(Clmg/ l ) Ion sulfate (SO42mg/ l ) Acid consumption (pH4.8) (CaCO3 mg/ l ) Aggregate hardness (CaCO3mg/ l ) Calcium hardness (CaCO3mg/ l ) Silicon L (SiO2mg/ l ) Referential standard Iron content (Femg/ l ) Copper content (Cumg/ l ) Sulfide ion (S2mg/ l ) Ammonia ion (NH4+ mg/ l ) Residual chlorine (Clmg/ l ) Circulating water 6.5 ~8.2 80 (800) 200 200 100 200 150 50 1.0 0.3 6.0 ~8.0 30 (300) 50 50 50 70 50 30 0.3 Supplying water Feature(1) Corrosion Scalelike sediment

0.1 No detecting 1.0 0.1 0.3 0.3

20

Dissociative cabonic acid (CO2mg/ l

4.0

4.0

) Stability standard 6.0 8.0 Note: in the table above reflects the possibility of causing corrosion and scalelike sediment. In case the water does not accord with the above standard, please consult the local dealer to soften or filtrate the water. B. Maintenance 1. Regular cleaning Please check and clean the surface of condenser regularly. 1) Daily maintenance Make sure the water in cooling tower is overflow. 2) Weekly maintenance Replace with fresh water and ensure the water quality. Make sure there is no water leakage. 3) Monthly maintenance Clean the surface on water side and supplying water system with a brush or detergent. 4) Quarterly maintenance Do testing on water quality and replace with fresh water if necessary. 5) Air filter should be cleaned regularly. Note: Remove the inside baffle first before cleaning the filter. 2. Turn off the unit in winter Please make the inside and outside of casing clean and dry and drain the water from condenser as well. 3. Starting in spring Please follow the requirement below before starting the unit. 1) Examine and clean the unit. 2) Clean or replace the air filter. 3) Clean the condensate drainpipe. 4) Do cleaning on condensate pipe and check whether there is leakage. 5) Clear the dust on evaporator. 6) Make sure the impeller is in balance. 7) Fix all the electric wiring and lock the cover board. C. Replace the components If you need to replace the components, please consult the local dealer.

21

Non operative

Troubles and Shooting Symptom Cause (1)No power 1No electricity (2)With power 1The fuse is melted 2Defective phase 3Incorrect phase 4Series circuit breaker works 5High-pressure switch is not reset 6Temp. sensor failure 7Incorrect wiring 8 Loop on electromagnetic contactor is burnt 9Voltage is too low 1Discharg 1Over high temp. on the surface of e temp. switch compressor and high degree of protection superheat of refrigerant 2Insufficient refrigerant 2Insufficie 3High air flow nt air flow, 1The belt is loose low-pressure 2Evaporator is too dirty protection 3Filter is too dirty 4Inappropriate duct design 5Air outlet is blocked 6Air return pipe is block 7Reversal running of fan motor 1 Insufficient capacity of cooled 3Highwater pump pressure 2 Radiating fan of cooling tower protection does not run 3Strainer of water pipe is blocked, insufficient water 4Cooled water is too dirty 5Condenser is too dirty 6 Reversal running of fan motor of cooled water pump 7 Reversal running of radiating motor of cooling tower 8Water pump and cooling tower are not started

Treatment Notify the power company Replace the fuse Examine the power supply Exchange the phase Do reparation Reset Replace the temp. sensor Do reparation Replace the contactor Contact power company Add refrigerant

The unit stops suddenly

Add refrigerant Adjust the air flow Adjust the belt Do cleaning Do cleaning Replace the duct Clear up the blockage Clear up the blockage Make adjustment Replace the water pump Do reparation or replacement Clear the blockage Replace with fresh water Clean the condenser Make adjustment Make adjustment Turn off and reset the unit

22

Insufficient cooling effect

(1) (2) (3) (4) (5) (6) (7) (8) (1) (2) (3) (4) (5) (6) (7) (1) (2) (3) (4) (5) (6)

Insufficient refrigerant Insufficient air flow Overload or insufficient capacity The system is blocked (insufficient flow) Improper setting of thermostat Over high temp. of return cooled water Incondensable gas in system The filter is too dirty Defective installation The belt is loose The fan is unbalanced The iron for fixing the compressor is not removed Defective shockproof rubber of compressor The rotating shaft of fan is bent The rotating shaft of fan motor is bent Bearing of fan is damaged The belt is loose The fan contacts the casing of unit Pulley is loose Voltage is too low Iron core of electromagnetic contactor gets rust

Add the refrigerant Examine and do reparation Increase the capacity Examine and do reparation Adjust the setting Examine and do reparation Retreatment of system Clean the filter Reinstall the unit Adjust the belt Make adjustment Remove the fixing iron Replace the rubber Replace the rotating shaft Replace the rotating shaft of motor Replace the bearing Adjust the belt Make adjustment Adjust and fix the pulley Contact power company Replace the contactor

Abnormal noise

The body of unit shakes

23