IEC 61850 for the PowerLogic ION7550/ION7650

Power and energy meter Daniel Brandao PLUG Conference Edmonton Nov 5, 2010

Introduction
A major part of Schneider Electric strategy to differentiate its products is based on providing the most comprehensive set of communication options: Multiple communication ports: RS-232; RS-485; InfraRed optical port, Modem, Ethernet (100BaseTX and 100BaseFX)

Multiple protocols: ION; Modbus RTU (slave / master); Modbus TCP; DNP 3.0, Ethergate, Modemgate and now IEC 61850

Schneider Electric

- Division - Name Date

Where does IEC 61850 come from? Substation situation

What are these challenges? Lack of interoperability between devices high integration costs; Limited vendor choice not always the best product for a particular need; Multiple technologies working together high maintenance costs;

Schneider Electric

- Division - Name Date

Why IEC 61850 is different


IEC 61850 protocol was created to take advantage of modern Ethernet switched technology and, in addition to the specification of the protocol elements (how bytes are transmitted on the wire), IEC 61850 provides a comprehensive model for how power system devices should organize data in a manner that is consistent across all types and brands of devices: Object model based on human understandable names: V Phase A is 26.3 kV instead of IED1, Obj 30, Var 4, #6 = Va; Standardized data grouping based on function, rather than on device type; Self describing devices vendor provides a file with the devices features; Standardized configuration language (SCL): precise definition of a devices role in a power system

Schneider Electric

- Division - Name Date

Why IEC61850 is different

Schneider Electric

- Division - Name Date

IEC 61850 Customer Benefits

Schneider Electric

- Division - Name Date

IEC 61850 Implementation on ION meters


Both ION 7550 and ION 7650 will support IEC 61850 protocol. The meters will provide via 61850:
Operational metering data (V, I, PF, Power, Energy totals) and some power quality parameters (harmonics, symmetrical components); Access to read and write meter digital & analog I/O; Custom mapping of ION values into 61850 in addition to standard models; Up to 4 client connections Reporting service for 61850 data: 1 buffered and 5 unbuffered reports per client, 50 members max;

Additional features: COMTRADE waveform recording and time synchronization via


SNTO

Schneider Electric

- Division - Name Date

IEC 61850 Implementation on ION meters


IEC 61850 Configuration flow:

Schneider Electric

- Division - Name Date

IEC 61850 Implementation on ION meters


The ICD files can be downloaded from www.powerlogic.com

Schneider Electric

- Division - Name Date

IEC 61850 Implementation on ION meters


ION modules:
Within the devices native ION architecture, specific ION modules map data to each of the IEC 61850 logical nodes:

Schneider Electric

- Division - Name Date

10

IEC 61850 Implementation on ION meters


Summary:
High accuracy (0.2S) and Power Quality metering data are now available through IEC 61850 protocol ION 7550 and ION 7650 PQ meters This new feature will be available in the next firmware release (V360) and installed meters can be upgraded on the field; COMTRADE waveform formats are now available directly from the meter; An FTP server is now available on the meter for transfer of IEC 61850 configuration files and COMTRADE records; IEC 61850 implementation on ION 7550 and 7650 meters are certified by Kema;

Schneider Electric

- Division - Name Date

11

Questions?
Daniel Brandao Neto Power Monitoring Offer Manager PQ Meters daniel.brandao@ca.schneider-electric.com