Thisdocumentisthecoursetext.Youmayreviewthismaterialat yourleisurebeforeorafteryoupurchasethecourse.Ifyouhavenot alreadypurchasedthecourse,youmaydosonowbyreturningtothe courseoverviewpagelocatedat: http://www.pdhengineer.com/pages/M2033.htm (Pleasebesuretocapitalizeandusedashasshownabove.) Oncethecoursehasbeenpurchased,youcaneasilyreturntothe courseoverview,coursedocumentandquizfromPDHengineersMy Accountmenu. Ifyouhaveanyquestionsorconcerns,rememberyoucancontactus byusingtheLiveSupportChatlinklocatedonanyofourwebpages, byemailatadministrator@PDHengineer.comorbytelephonetoll freeat1877PDHengineer. ThankyouforchoosingPDHengineer.com.

PDHengineer.com,aservicemarkofDecaturProfessionalDevelopment,LLC.M2033C1

B63

Engineering Guidelines Fan Coils

Fan Coils
Types of Fan Coils
Vertical Stack The Vertical Stack unit consists of a blower and motor capable of supplying up to 1200 cfm to the space, a cooling/ heating water coil, a drain pan for coil condensation and large amount of accessories to reduce installation times and cost. The purpose of the Vertical Stack Fan Coil is to provide cooling and heating to single or dual room spaces in response to a control signal from a single room thermostat. The unit is typically mounted in the room walls forming part of the conditioned area. There are four types of Vertical Stack units to meet various water distribution designs. Model VSR (Vertical Stack Stand Alone)vertical mounted unit with wall mounted return air/access panel and discharge grilles normally have the water distribution risers as an integral part of the unit to facilitate the unit installation and reduce cost and time on the eld. Model VSRM (Vertical Stack Remote Master) as per the model VSR, however the risers are manufactured with various alternatives of connections for led connection to a remote Slave (VSRS) unit. Model VSRS (Vertical Stack Remote Slave) as per the VSR unit, however the unit does not have risers and pipe connections are manufactured ready for connection to a remote Master (VSRM) unit. Model VSM/S (Vertical Stack Master/Slave) twin pack unit, pre-piped at the factory, sharing a single set of risers and typically used when conditioning similar space areas such as hotel rooms. Horizontal Basic The Horizontal Basic unit consists of a blower and motor capable of supplying up to 1200 cfm to the space, a cooling/ heating water coil and a drain pan for coil condensation. The purpose of the Horizontal Basic Fan Coil unit is to provide cooling and heating to a single room space in response to a control signal from the room thermostat. The unit is typically mounted above the space ceiling in a ceiling drop or sot to maximize the usable oor space in the conditioned area. There are four types of Horizontal Basic units to meet various structural requirements. Model HBC (Horizontal Basic Cabinet) mounts in the ceiling plenum and is ducted to a high sidewall air outlet. The HBC is an economical source of supplying warm or cool air to a room in response to the room thermostat. Model HBP (Horizontal Basic Plenum) is the same unit as the HBC with the fan and blower housed inside an insulated plenum. The plenum provides sound absorption for the fan noise and a housing to mount an optional plenum air lter. VSR VSRM

Fan Coils

Figure 110. Typical Vertical Stack Application

VSRS

VSM/VSS

Figure 111. Typical Horizontal Basic Application

HBC

HBP

B64

Engineering Guidelines Fan Coils


B
Types of Fan Coils (continued) Horizontal Basic (continued) Model HBR (Horizontal Basic Recessed) is mounted with the face exposed to the room on the ceiling. The face of the unit houses the return air inlet for inducing room air directly back to the unit for re-circulation. The face is painted.

Fan Coils

Model HBE (Horizontal Basic Exposed) is mounted below the ceiling line with the entire unit under the ceiling line. This unit is commonly used in high bay open areas. Vertical Basic The Vertical Basic unit consists of a blower and motor capable of supplying up to 1200 cfm to the space, a cooling/ heating water coil and a drain pan for coil condensation. The purpose of the Vertical Basic Fan Coil unit is to provide cooling and heating to a single room space in response to a control signal from the thermostat. The thermostat could be located on the unit or on the wall. The unit is typically mounted beneath the window to be located in the area of the maximum load in the conditioned area. There are four types of Vertical Basic units to meet various structural requirements. Model VBC (Vertical Basic Cabinet) mounts in an enclosed area on the perimeter beneath or adjacent to the window. The unit is enclosed with material similar to the room walls. A supply grille mounted atop the unit discharges conditioned air vertically into the space. Model VBF (Vertical Basic Flat Top) typically mounts on the oor beneath the window but can be located on a wall adjacent to the window. The unit is encased in a painted sheet metal enclosure. An integral supply air grille is located atop the unit for conditioned air to be discharged vertically into the space. Model VBA (Vertical Basic Angle Top) typically mounts on the oor beneath the window but can be located on a wall adjacent to the window. The unit is encased in a painted sheet metal enclosure. An integral supply air grille is located on an angled surface atop the unit for conditioned air to be discharged vertically into the space. The angled surface discourages placing items on top of the unit, which blocks the air supply into the space. Model VBL (Vertical Basic Low Prole) typically mounts on the oor beneath the window. The unit is encased in a painted sheet metal enclosure. An integral supply air grille is located atop the unit for conditioned air to be discharged vertically into the space. The VBL is mounted in a lower prole cabinet for use with a window, which is mounted closer to the oor. The smaller cabinet limits the maximum airow to 600 cfm for this model. Model VBLC (Vertical Basic Low Prole Concealed Floor) mounts in an enclosed area on the perimeter beneath or adjacent to the window. The unit is enclosed with material similar to the room walls. A supply grille mounted atop the unit discharges conditioned air vertically into the space. The VBLC is mounted in a lower prole cabinet for use with a window, which is mounted closer to the oor. The smaller cabinet limits the maximum airow to 600 cfm for this model.

HBR

HBE

Figure 112. Typical Vertical Basic Application

VBC

VBF

VBA

VBL

VBLC

B65

Engineering Guidelines Fan Coils


Types of Fan Coils (continued) High Output Series The High Output Series units consist of a blower and motor capable of supplying up to 2000 cfm to the space, a cooling/ heating water coil and a drain pan for coil condensation. The purpose of the High Output Series Fan Coil units is to provide cooling and heating to a multi-room space in response to a control signal from the area thermostat. The unit is typically mounted outside the conditioned area to minimize the noise generated by a larger blower. There are three Horizontal High Output models and one Vertical High Output model. Model HHC (Horizontal High Output Cabinet) is typically mounted in a ceiling plenum space above a hallway or noncritical room. Care must be taken to provide access to the unit for service. Ductwork attached to the unit discharge will deliver the conditioned air to the air outlets mounted in the ceiling or high sidewall of the rooms being served. Return air inlets from the room to the ceiling plenum are required for units mounted above a ceiling. Model HHP (Horizontal High Output Plenum) is the same unit as the HHC with the fan and blower housed inside an insulated plenum. The plenum provides sound absorption for the fan noise, and a housing to mount an optional plenum air lter. The return air inlets can be ducted directly to the unit plenum. Model HHE (Horizontal High Output Exposed) is designed for larger spaces where noise is not critical. The galvanized steel cabinet is typically not painted. The unit is mounted above the conditioned space and can be ducted to multiple air outlets or discharged directly above the space. Model VHC (Vertical High Output Cabinet) is designed for larger spaces where ease of maintenance is desired. The unit is typically located in a closet where a door from the occupied space opens for easy access. Figure 114. Typical Vertical High Output Application

Fan Coils

Figure 113. Typical Horizontal High Output Application

HHC

HHP

HHE

VHC

B66

Engineering Guidelines Fan Coils


B

Heat Transfer

ASHRAE denes heat transfer as the ow of heat energy induced by a temperature dierence. Thermal energy can be transferred or be aected by:

Fan Coils

Conduction Convection

Radiation Humidity

Thermal conduction is the mechanism of heat transfer by the transfer of kinetic energy between particles or groups of particles at the atomic level. With solid bodies, such as with an air jet near a window, thermal conduction dominates only very close to the solid surface. Thermal convection is the transfer by eddy mixing and diusion in addition to conduction. The transfer of uid currents produced by external sources, such as by a blower, is called forced convection. When the uid air movement is caused by the dierence in density and the action of gravity, it is called natural convection. Natural convection is very active near windows and near heat sources in the occupied spaces. The colder air falls and the warmer air rises. Radiant heat transfer takes place through matter. It is a change in energy form, from internal energy at the source to electromagnetic energy for transmission, then back to internal energy at the receiver. Examples of radiation are sunshine through the air and window to the inside oor or ceiling light to occupants and to the oor. All of these methods of heat transfer eect a persons comfort reaction. In addition, humidity has some eect caused by a change in evaporation rate from the body. Heat transfer is also aected by the following factors: A greater temperature dierence will result in a greater amount of heat transfer. The amount of surface area is directly proportional to the amount of heat transfer. The amount of time is also directly proportional to the amount of heat transfer. The thermal resistance of the material use aects the rate of heat transfer.

Heat loss is measured in Btu which is the amount of heat required to raise 1 lb. of water 1F. Coecients used to estimate the value of the heat loss include: K Factor, which is the amount of heat transferred in 1 hour through 1 sq. ft. of material, 1 thick at 1F of temperature dierence. C Factor, which is the amount of heat transferred in 1 hour through 1 sq. ft. of material through the specied thickness of the material used. R Value, is the resistance to heat transfer, measured as the reciprocal of conductance (1/K or 1/C). U Value, designates the overall transmission of heat in 1 hour per sq. ft. of area for the dierence of 1F across specied material. Conductance of individual materials is not directly applicable to the heat loss calculation. First, it must be converted to the R value, which is (1/K or 1/C). Equation 1: For a structure with multiple skin materials, the total heat transmission can be calculated as: U = 1/(R1 + R2 + ..Rn)

Hydronic (Fan Coil) Systems

For hydronic heating and cooling fan coil systems heat is removed from the occupied space (cooling) or added to the occupied space (heating) via a closed looop water system. Return air from the space passes across a n tube coil. The re-conditioned air is returned to the space through the supply air outlets. During the cooling season, heat from the return air is transferred to the water passing through the coil. The warmer water is piped to the chiller where the heat is removed and the cooler water is re-circulated. After the return air passes through the coil and the heat is removed, it is directed back to the space through the supply air outlets as directed by the room thermostat. During the heating season, the cool return air passes through the n tube coil. Return air is heated by the warm water being piped through the coil, and is directed back to the room through the supply air outlets as directed by the room thermostat. Manufacturers performance data will quantify the coil heat transfer rate (Btu/H), given the airow rate (cfm), entering air temperature dry and wet bulb (eat), water-ow rate (gpm) and entering supply water temperature (ewt) or entering and leaving water temperature (ewt/lwt) instead of water ow rate.

B67

Engineering Guidelines Fan Coils

Room Load Calculations

Equation 2: Heat transfer through a window or wall: Q = U * A (t1 t2) Where : Q is the Btu/h U is the overall coecient Btu/HA A is the area in Ft2 t1 and t2 are the temperatures in F Equation 3: Equation for exterior surfaces cooling: Q = U * A * t. Where: Q is the heat ow in Btu/H U is the value for the component under consideration t is the temperature dierence across the component under consideration Equation 4: Equation for heating and non-exterior cooling: Q = U * A * TD. Where: Q is the heat ow in Btu/H U is the value for the component under consideration TD is the temperature dierence in degrees F between indoors and outdoors across the component under consideration, taking into account the combined eect of radiation, time lag, storage and temperature Equation 5: Equation for sensible heating and cooling load: Q = 1.08 * cfm * t Where : Q = is the load in Btu/H 1.08 is a constant for density at sea level. cfm is the volume of conditioned air t is the temperature dierence between the supply air and the room control temperature Equation 6: Equation for latent cooling load: Q = .68 * cfm * GR Where: Q = Load in Btu/H .68 is the latent load constant GR = dierence between absolute humidity between indoor humidity/area and outdoor humidity/area

For fan coil products the typical application characteristics are similar to multi-family residential building. For these structures heating and cooling load calculations will dier from commercial applications. Some of the unique features dierentiating fan coil applications from other commercial applications include: Heat gains are primarily imposed on the building through walls, windows, ceilings, doors and inltration. Loads imposed by people and lighting is less signicant. Load characteristics for fan coil zones can be more narrowly dened than zones for commercial spaces. The factors for a specic zone orientation, outdoor exposure and climate zone need to be considered. Exterior or interior shading and the time of the day aect the solar load. Another load on the space may be imposed by inltration of outdoor air through windows and doors. Additional implements may be used for occupant comfort during extreme design situations. Ceiling fans can provide occupant comfort during warm conditions. Heat from sources such as a replace may provide extra comfort for cold conditions. For sleeping rooms, bed linens may be added or removed to enhance comfort. Most fan coil systems are used for relatively small capacity systems. Because loads are commonly determined by outdoor conditions, and very few days during a heating or cooling season are at design conditions, partial load conditions are prevalent. Therefore, over sizing the unit can decrease comfort in the space, especially during humid conditions. During high humidity operations with lower dry bulb temperatures, the thermostat will direct an oversized unit to short cycle, leaving uncomfortable levels of humidity in the space. For climate zones with higher humidity levels, selecting a smaller capacity unit will allow for maximum dehumidication and comfort for the majority of the cooling season with slight discomfort on the few days when design conditions occur. Additional information and a detailed discussion of calculating the cooling and heating loads in a space can be found in the Air Conditioning Contractors Association (ACCA) Manual N for Commercial Load Calculation, ASHRAE SDL Curriculum on Heating and Cooling Loads, or ASHRAE TC-4.0 Technical Committee for Load Calculations. The following are some equations commonly used for heating and cooling load calculations in a space.

Fan Coils

B68

Engineering Guidelines Fan Coils


B

Psychrometrics

Fan Coils

One of the four major elements of thermal energy and comfort is humidity. Psychrometrics uses thermodynamics properties to analyze conditions and processes involving moist air. A detailed study of psychrometrics can be found in Chapter 6 of ASHRAE 2005 Fundamentals Handbook. This section is a summary of how knowledge of psychrometrics can be used to maximize space comfort and system performance. Atmospheric Air (the air that you breathe), contains many gaseous components including water vapor and containments. Dry Air is atmospheric air with all moisture removed and is used only as a point of reference. Moist Air is a combination of dry air and water vapor and can be considered equal to atmospheric air for this discussion. A psychrometric chart (Figure 115) is a graphical representation of the thermodynamic properties of moist air. There are several charts available to cover all common conditions. The one shown here is taken from ASHRAE Fundamentals Handbook, Chapter 6 and illustrates conditions of 32 to 100F at sea level. The Dry-bulb Temperature (DBT), is the temperature measured using a standard thermometer. Dry-bulb is also known as the sensible temperature.

The Wet-bulb Temperature (WBT), is the temperature measured using a wetted thermometer. Wet-bulb is used to determine the moisture content of air. The Absolute Humidity (AH), is the vapor content of air. It is described in terms of moisture per lb of dry air or grains of moisture per lb of dry air. AH is also referred to as moisture content or humidity ratio. There are 7000 grains in a lb of water. The Relative Humidity (RH), is the vapor content of air. It is described as the percentage of saturation humidity at the same temperature (%). The goal for optimum space comfort is 30-35% for heating conditions, and 45-60% for cooling conditions. Saturation humidity is the maximum vapor content (lb/lb) per lb dry air that air can hold at a xed temperature. The Dew Point Temperature (DPT), is the temperature at which vapor begins to fall out of air to form condensation. DPT is the temperature at which a state of saturation humidity occurs, or 100% RH. It is also known as the saturation temperature.

55

60

90
50

.028
85

Sensible Heat Ratio


:
5000
1.0

60

1.0
2.0 4.0 8.0 : -48.0 -2 .0 .0

:
-2000 -1000

15.0

0.8
0.6 0.5
0.4
0. 3
.5 -0 .4 -0 3 -0.

.026

Sensible Heat Total Heat

Qs Qt
-1

0.2

0.1

ir

ry

of

nd

ou

pe r

at

ur

e,

rP

pe

Te

tu

-B

lp y

th a

Sa

25

tu r

at

io

En

Humidity Ratio - Pounds Moisture per Pound Dry Air

15

40 35
35
40

Dry Bulb Temperature, F

105

110

100

10

15

20

Enthalpy - Btu per Pound of Dry Air

Figure 115. Psychrometric Chart

115

35

50

65

80

95

40

45

55

60

70

75

85

90

120

00 20
20

3000
12.5

45

.0

85 We tB ulb

.024
Te mp era tur e, F
55

50

80
40

.022

-0.2

-0.1

15 00
45

80
35

1000

.020
50

Enthalpy Humidity Ratio

Dh DW

75

.018

14.5

75
30

70

.016

70
65

.014

45

60

% 90
% 80

65

.012
14.0 elum Vo

55

60

.010

40

cu.

% 70
50

er lb ft. p

55
50

.008

% 60
50 %

.D

13.5

ry A ir

.006
35

45

40%
30%

.004

13.0

20%
10% Relative Humidity

.002
30

B69

Engineering Guidelines Fan Coils


Psychrometrics (continued) The Specic Volume (Spv), is the reciprocal of air density which is described in terms of cubic feet per lb of dry air (cu ft/lb). An increase in air temperature will result in a decrease in density and an increase in volume. A decrease in atmospheric pressure also decreased air density while increasing volume. At 5000 feet above sea level, density is decreased by 17%. Higher altitudes require larger motors and blowers to move the same eective mass, due to the increase in specic volume. The Enthalpy (H) is the heat content of air. Enthalpy is also known as the total heat of air. Enthalpy is dependant on the wet-bulb temperature of air. It is described in terms of Btus per lb dry air (Btu/lb). A Status Point is a location on the psychometric chart dened by any two psychometric properties. A hydrometer or psychrometer is commonly used to dene a status point. Using a psychrometer. A sling psychrometer incorporates a standard thermometer and a wetted thermometer. The wetted thermometer should be dipped in room temperature distilled water. The psychrometer is spun (slung) until the wet-bulb temperature has stabilized. It should be noted that standing near furniture while slinging can result in retesting after the broken thermometer has been repaired. When the wet-bulb temperature has stabilized, record both the dry-bulb and wet-bulb temperatures on your log sheet. Because of evaporation, the wet-bulb temperature will be equal to or less than the dry-bulb temperature. At 100% RH the wet-bulb will equal the dry-bulb temperature. (Locate an umbrella before continuing the test). As the temperature dierence between temperatures increases, the RH will decrease. To locate your status-point, nd the dry-bulb temperature on the bottom of the psychometric chart. Follow this line upward until it intersects with the wet-bulb temperature from the left side of the chart. From the status point you can locate: Absolute Humidity (AH) Relative Humidity (RH) Dew Point Temperature (DPT) Specic Volume (Spv) When will condensation occur? To determine if a supply air duct or air outlet device will form condensation on the surface: First, using the R-value of any thermal barrier, determine the minimum surface temperature. Next, determine the DPT of the atmospheric air in contact with the surface. If the surface temperature is equal or lower than the DPT, the surface will form condensation. If yes, an additional thermal barrier may be required to solve the problem. Sensible heating (Qsen), is the heat that raises the dry-bulb temperature of air without increasing the moisture content. Because we can easily sense this change in temperature, it is called sensible. Sensible cooling is the removal of heat without removing moisture content of the air. Latent Heat (Qlat), is the heat content of air due to the presence of water vapor. Latent heat is the heat required to evaporate this same amount of water (970 Btu/lb), also known as the latent heat of vaporization. As latent heat increases, moisture content increases. Water can be heated to 212F. If more heat is added, the water will vaporize but the temperature will not change. Latent Cooling (Qlat), is the removal of latent eat from air without lowering the dry-bulb temperature. To retrieve 1 lb of condensate, 970 Btus would need to be removed. As latent heat decreased, moisture content decreases. Latent Heat of Fusion is the heat required to change a liquid into a solid (144 Btu/lb. Water can be cooled to 32F. If more heat is removed, it wall cause ice to form. To retrieve 1 lb of water from ice, 144 Btus will need to be added. Sensible processes can be shown as horizontal paths on a psychrometric chart. Latent processes can be shown as vertical paths on a psychrometric chart. Most processes include both, resulting in an angled or diagonal path. Sensible heat factor is the measure of sensible heat to latent heat. Sensible heating only is 1.0. Equal proportions result in 0.5. SHF is generally higher than 0.5 because of the cooling processes that remove more sensible heat than latent heat. For residential applications the typical Sensible heat factor is 0.8.

Fan Coils

B70

Engineering Guidelines Fan Coils


B

Properties of Coils and Coil Design

Fan coil units are typically selected and sized to heat and cool a small zone with specic load requirements. Each unit denes a small zone, which typically serves a few rooms with a centrally located thermostat. Basic and vertical stack units are usually selected for single room applications.

Air Stream

Fan Coils

The hot and cold water supply usually serves all or part of a single building. Water can be supplied to each unit through a two-pipe or four-pipe water supply system. Two-pipe systems will have a lower installed cost. With a two-pipe system, both hot and cold water are supplied using the same pair of pipes. The lower cost usually translates to a lower level of occupant comfort. This limitation can cause problems when heating is desired in one unit at the same time cooling is desired in another due to solar or internal load requirements. For moderate climate regions, two-pipe systems can operate in the cooling mode with supplemental resistance heat available in zones requiring heat. Four-pipe systems maintain higher levels of occupant comfort for all seasons. Both hot and cold water are left operational during the spring and fall seasons. This additional comfort may result in higher operational cost for utilities to operate both the chiller and the boiler during the spring and fall months. Water side applications for fan coil designs use a chiller to lower the water temperature for heat removal and a boiler to raise the water temperature to overcome heat losses. The water supply used is typically supplied by the local utilities. Other chemicals may need to be added to the water. Sometimes, local climate conditions require that additives such as Ethylene glycol, Propylene glycol, Methanol, Calcium chloride or Sodium chloride be added to the water supply. Care should be taken to account for changes in heat transfer caused by these additives.

T = 80F

T = 60F

Ts = 45F T = 55F

Ts = 45F T = 45F

Figure 116. Coil Design

In

Out

Air

Return Bend End


Figure 117. Parallel Flow

Out

Out

Air

In Return Bend End


Figure 118. Cross Flow

In

B71

Engineering Guidelines Fan Coils

Vertical Stack Risers

For high-rise buildings where a common oor to oor footprint is present, it may be economical to design the system using vertical stack fan coil units. Vertical stack models can minimize installation cost because the units are orientated one on top of the other and use common supply and return water pipes. For tall structures with more than three oors, it is recommended to adjust the pipe size for optimum performance. The term riser describes the pipe used to transport supply or return water (chilled or hot) to or from the vertical stack unit water coil as well as condensate water from the drain pan. Risers are typically insulated with elastomeric, closed cell, thermal insulation to minimize heat loss or gain from the water to the ambient space. If the unit is not equipped with a riser pipe of adequate length to reach from oor to oor, a riser extension can be installed to connect the vertical stack unit to a unit located on an adjacent oor. The riser extension can also act as the transition where the pipe size changes from one oor to the next. The diameter of the pipe will increase or decrease as piping extends throughout the building in order to equalize pressure and velocity of the water ow.
R R

VSR VSM

VSR VSM

VSR VSM

Fan Coils

VSR VSM

VSR VSM

VSR VSM

VSR VSM

VSR VSM

VSR VSM

VSR VSM

VSR VSM

VSR VSM

S S S R

CHILLER

BOILER

Figure 119. Piping Layout for a Horizontal 2-Pipe System with Standard Return Piping

Riser Sizing

A detailed discussion on water pipe sizing can be found in the ASHRAE Fundamentals Handbook. In general, operating pressure between the supply and return riser is in the range of 10 to 15 psi. Design velocities are typically between 1 and 4 fps. Typical riser pressure loss is designed for about 3 feet of head pressure loss per 100 feet of piping. As a rule of thumb, 10 feet of head pressure equates to about 5 psi. Water delivery can be made through a two-pipe system using three risers (one each supply, return and condensate) or a four-pipe system using ve pipes (chilled water supply, chilled water return, hot water supply, hot water return and condensate pipe) as specied. Reminder: Two-pipe systems may require supplemental electric heat for moderate times when some zones require cooling while other zones require heat. Two dierent congurations are available for return piping, standard return and reverse return. In the standard conguration, Figures 119 and 120, water ows from the rst fan coil in the loop through the last, and returns from the last unit back through the rst. In a reverse return system, Figures 121 and 122, both the supply and return ow run from the rst unit in the system through the last and returns to the chiller through a separate riser.

CHILLER

BOILER

VSR VSM

VSR VSM

VSR VSM
R S

Figure 120. Piping Layout for a Vertical Stack 2-Pipe System with Standard Return Piping

B72

Engineering Guidelines Fan Coils


B
Vertical Stack Risers (continued)

VSR VSM

VSR VSM

VSR VSM

Fan Coils

VSR VSM

VSR VSM

CHILLER
R S

BOILER

VSR VSM

VSR VSM

VSR VSM
VSR VSM
VSR VSM

VSR VSM

VSR VSM

VSR VSM

VSR VSM

R R
CHILLER

S S S R
BOILER

VSR VSM
S

Figure 121. Piping Layout for a Horizontal 2-Pipe System with Reverse Return Piping

Figure 122. Piping Layout for a Vertical 2-Pipe System with Reverse Return Piping

S
CHILLER

R
BOILER

CHILLER

BOILER

R
VSR VSM

VSR VSM

VSR VSM

VSR VSM

VSR VSM

VSR VSM
S S

S S
Figure 124. Vertical Stack 4-Pipe System with Reverse Return Piping

Figure 123. Vertical Stack 4-Pipe System with Standard Return Piping

Expansion Loops

Copper pipe will expand and contract with changes in pipe temperature created by changes of water temperature. Each TITUS vertical stack unit is equipped with an internal expansion loop.

For two-pipe systems where the same pipe carries both chilled and hot water and high rise buildings with more than ve oors, additional expansion loops may be required.

B73

Engineering Guidelines Fan Coils

Controls and Valve Packages

Comfort control for occupants in the space is regulated by a room thermostat and control valve package mounted on the unit water coil. The room thermostat performs the function monitoring the room temperature conditions and signaling the unit fan and valve controls to operate within in preset limits to maintain occupant comfort. Figure 125 shows a basic two-pipe system package. Supply water is piped to the bottom of the coil to ensure that any air bubbles forming in the supply water will be transmitted to the upper level where they can be discharged from the system through the optional air vent on the return pipe immediately outside the coil. Shut o valves are located on both supply and return waterlines to enable the coil to be isolated during installation and maintenance. Drain valves allow the coil to be drained during maintenance or removal. A two-way water valve is used to adjust and balance the water ow into the coil to provide the specied amount of heat to the zone. A valve motor operates on a signal from the room thermostat to adjust the water ow in response to space heating conditions. The air vent allows air bubbles to escape the system for maximum heat transfer system performance. Optional control components, Figure 126, are available to enhance the operations of the system or improve the process of installation and maintenance. Automatic air vent ports keep the water supply system free of air build up on a continuous basis.
Flow Control Valve Adjustable - Option 1 & 2 Fixed - Option 3 & 4 Air Vent Port Automatic - Option A

B
Air Vent Port Shut Off Valve

Motorized 2-Way Valve Coil

Return Supply Drain


Shut Off Valve

Fan Coils

Figure 125. 2-Pipe with 2-Way Valve and 2 Shut off Valves Unions can be provided for the connection of the water coil to the supply and return water lines. Unions allow the water coil to be removed from the unit without cutting into the water lines and soldering them together during installation and maintenance. Petes Plugs provide the installer or maintenance technician a tool for connecting a pressure gage for reading the water pressure at the coil. Flow Control Valves are available as xed or adjustable options. A xed valve will be sized in accordance to the CV specied by the design engineer to provide the water ow required to meet the maximum load conditions required in the zone. This feature may save time during the initial start up. An adjustable valve must be commissioned at the jobsite during start up to limit the specied water ow to the coil. The adjustable feature does provide for future changes to match changes in load requirements.

Pete's Plug option B & C (2-pipe) Pete's Plug option D (4-pipe) Union option B (2-pipe) Union option D (4-pipe) Shut Off Valve With Memory Stop

Return
Coil

Supply
Shut Off Valve Union option B (2-pipe) Union option D (4-pipe) Pete's Plug option A & C (2-pipe) Pete's Plug option D (4-pipe)

Motorized 2-Way Valve Y Strainer option A (2-pipe) Y Strainer option B (4-pipe)

Figure 126. 2-Way Valve Component Options

B74

Engineering Guidelines Fan Coils


B
Controls and Valve Packages (continued) A Motorized Water Valve can be provided. The motor will be operated in response to a signal from the zone thermostat to automatically reset the water ow to meet changing zone load requirements. A two-way valve controls water ow by opening or closing the ow control valve to the coil with a spring return. A three-way valve controls ow to the coil by bypassing excess water directly to the return pipe. The Y-Strainer option is installed in the supply water line ahead of the coil. It will remove sediment from the water supply before it can enter the coil and restrict water ow and lower system performance. Manual Shut O Valves are available with or without memory stops. The basic valve allows maintenance personal to shut o the ow of water to the coil at the unit. The optional memory stop lets the operator re-open the valve to it previous position without re-balancing. An Aquastat Switch can be installed in the water supply line and connected to the thermostat. Aquastats are most commonly used where there is a two-pipe system or supplemental electric heat. The Aquastat senses when the supply water is for heating or cooling. For a two-pipe system, if a zone thermostat is calling for heat and the supply water is cold, the thermostat will be locked out. For supplemental heat, the heat will be locked out when warm water is available in the supply lines.

Fan Coils

Thermostat

The zone thermostat may be mounted on the fan coil unit, on the wall near the unit, or mounted on the wall or in the return duct away from the unit. Thermostats may be powered by a 24-volt power supply (with transformer) or by the same line voltage as the unit. Economically, if the thermostat is physically located more than 8 feet from the unit, line voltage is preferred. Each fan coil controls the room space temperature in response to a signal from the thermostat. The thermostat is programmed with cooling and heating set-point values as directed by the occupant or building manager. Typically, the zone thermostat provides a read out to tell the occupant what the set-point temperature is for the unit and what the temperature is the temperature in the space at present. Space temperature control is + or -1F from the set point temperature. (Thermostats with an auto-changeover feature have a 4F dead-band for switching.) Other thermostat features include a three-speed switch for the occupant to adjust the fan output volume, a manual changeover switch to change operation from cooling to heating conditions and an on/o switch to override the thermostat and shut the unit o as desired by the occupant.

Fan Coils

Fan Coils

V2

Fan Coils Table of Contents


Fan Coils Series Overview ............................................................................................................... V3 Vertical Stack Series ......................................................................................................................... V4
VSR Recessed Hi-Rise ............................................................................................................................. V4 VSRM Recessed Hi-Rise Remote Master ............................................................................................... V8
Dimensions ............................................................................................................................................................... V5 Performance Data ..................................................................................................................................................... V6 Dimensions ............................................................................................................................................................... V9 Performance Data ................................................................................................................................................... V10 Dimensions ............................................................................................................................................................. V13 Performance Data ................................................................................................................................................... V14 Dimensions ............................................................................................................................................................. V17 Performance Data ................................................................................................................................................... V18

VSRS Recessed Hi-Rise Remote Slave ................................................................................................ V12

VSM/VSS Recessed Master/Slave ......................................................................................................... V16 VS Sound Power ....................................................................................................................................... V20 Suggested Specications ........................................................................................................................ V21 HBC Concealed Ceiling .......................................................................................................................... V24 HBP Concealed Ceiling with Plenum .................................................................................................... V28

Horizontal Basic Series .................................................................................................................. V24


Dimensions ............................................................................................................................................................. V25 Performance Data ................................................................................................................................................... V26 Dimensions ............................................................................................................................................................. V29 Performance Data ................................................................................................................................................... V30 Dimensions ............................................................................................................................................................. V33 Performance Data ................................................................................................................................................... V34 Dimensions ............................................................................................................................................................. V37 Performance Data ................................................................................................................................................... V38

HBE Exposed Cabinet ............................................................................................................................ V32 HBR Recessed Cabinet .......................................................................................................................... V36 Suggested Specications ........................................................................................................................ V40 VBC Concealed Floor ............................................................................................................................. V42 VBF Flat Top Cabinet .............................................................................................................................. V46 VBA Angled Top Cabinet ........................................................................................................................ V50

Vertical Basic Series ...................................................................................................................... V42

Dimensions ............................................................................................................................................................. V43 Performance Data ................................................................................................................................................... V44 Dimensions ............................................................................................................................................................. V47 Performance Data ................................................................................................................................................... V48 Dimensions ............................................................................................................................................................. V51 Performance Data ................................................................................................................................................... V52 Dimensions ............................................................................................................................................................. V55 Performance Data ................................................................................................................................................... V56 Dimensions ............................................................................................................................................................. V58 Performance Data ................................................................................................................................................... V59

VBL Low Prole Cabinet ........................................................................................................................ V54 V VBLC Low Prole Concealed Floor ...................................................................................................... V57

Horizontal High Output Series ...................................................................................................... V63


Fan Coils

Suggested Specications ........................................................................................................................ V60 HHC Concealed Ceiling .......................................................................................................................... V63 HHP Concealed Ceiling with Plenum .................................................................................................... V67

Dimensions ............................................................................................................................................................. V64 Performance Data ................................................................................................................................................... V65 Dimensions ............................................................................................................................................................. V68 Performance Data ................................................................................................................................................... V69 Dimensions ............................................................................................................................................................. V72 Performance Data ................................................................................................................................................... V73

HHE Exposed Cabinet ............................................................................................................................ V71 Suggested Specications ........................................................................................................................ V75 VHC Concealed Closet ........................................................................................................................... V77

Vertical High Output Series ............................................................................................................ V77


Dimensions ............................................................................................................................................................. V78 Performance Data ................................................................................................................................................... V79

Accessories ........................................................................................................................V83

Suggested Specications ........................................................................................................................ V81

V3

Fan Coils Overview

Fan Coils Series Overview


Vertical Stack
VSR, VSRM, VSRS, VSM/VSS 300 to 1200 cfm nominal airows. 0 to 0.3 inches horizontal exterior static pressue.

Horizontal Basic
HBC, HBP, HBE, HBR 200 to 1200 cfm nominal airows. 0 to 0.3 inches horizontal exterior static pressue.

VSM/VSS

Vertical Basic
VBC, VBF, VBA 200 to 1200 cfm nominal airows. 0 to 0.3 inches horizontal exterior static pressue. VBL, VBLC 200 to 600 cfm nominal airows. 0 to 0.3 inches horizontal exterior static pressue. HBC

Horizontal High Output


HHC, HHP, HHE 600 to 2000 cfm nominal airows. 0 to 0.5 inches horizontal exterior static pressue.

Vertical High Output


VHC 600 to 2000 cfm nominal airows. 0 to 0.5 inches horizontal exterior static pressue. VBC

Fan Coils

HHP

VHC

V4

Fan Coils Vertical Stack VSR Description

Vertical Stack Series


VSR Recessed Hi-Rise
Factory assembled, vertical high-rise building VSR fan coils are designed for free-blow or ducted, concealed installations, suitable for hotel, motel and apartment building applications. Standard Features Include: Performance ARI Certied to Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. All casing sheet metal components fabricated of 18GA G90 galvanized steel. High-eciency 2-row coil suitable for a 2-pipe system. Coil manual air vent. 1-inch thick disposable lter. Cabinet liner in -inch dual-density berglass. Multi-speed motor of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blowers of the whisper quite type. Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally protected on the outside (Consult TITUS for availability). Translucent exible condensate water P-trap. Plenum discharge air anges for duct and dry wall applications. Optional Features Include: 3-, 4- and 5-row coils for 2-pipe systems. Single block 2, 3 and 4 rows CW with 1-row re-heat coils for 4-pipe system applications (5 rows max). Single block 2 and 3 rows CW with 2 rows re-heat for 4-pipe system applications (5 rows max). Automatic coil air vents. Filter option include: - 1-inch high-eciency pleated lters. - 1-inch washable lters. Cabinet liner in 1-inch dualdensity berglass. Motor voltage suitable for 208V, 230V or 277V/1Ph/ 60Hz power supplies. Motor in-line quick disconnect. Thermostat and Accessories (refer to Accessories on page V83 for details). Single power supply disconnect switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. Standby electric heater auto changeover switch. Fresh air opening. Fresh air manual and auto dampers. Fresh air freeze protection. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel (Consult TITUS for availability). - Double wall construction consisting of outer and inner skins.

A Participating Corporation in the ARI 440 Certication Program

Condensate pan mastic coating applicable to the inside of the condensate pans for a prolonged life. Condensate pan overow safety switch. Discharge air grilles: - Aluminum double defection. - Deluxe aluminum double deection grilles (Contact TITUS for availability). - Linear bar aluminum grilles. Discharge air grille options: - Dual discharge. - Air damper controls for units with dual discharge grilles. Special discharge air grille colors (Contact TITUS for color range availability and price). Discharge air grille location. Return air/access panels painted white: - Stamped galvanealed steel. - Remote stamped galvanealed steel. - ADA stamped galvanealed steel. - ADA remote stamped panel. - Invislot blank front panel. - Deluxe aluminum panel with a removable core. - Linear bar aluminum panel with a removable core. Special return air/access panel color (Contact TITUS for color range availability and price). Return air/access panel fasteners: - Philips head fasteners. - Tamper proof fasteners. - Quarter turn fasteners. Fan section noise reduction kit. 1-hour re rating. Riser Installation options: - Unit mounted riser. - Risers supplied loose. Riser pipe type M, L and K. (Consult TITUS for availability of type K risers). Riser thermal Insulation in - or -inch wall thickness. Riser connections to unit options: - Welded to the unit piping. - Union connections using rigid copper pipe. - Union connections with exible braided stainless steel hoses. Riser extensions. Riser extension end connection reducers.

VSR

V5

Fan Coils Vertical Stack VSR Dimensions Dimensions


VSR Recessed Hi-Rise
TOP VIEW 3 H 3 3

L D

OPTIONAL TOP SUPPLY E FRONT VIEW F 2 D E 1 SIDE VIEW OPTIONAL TOP SUPPLY 3 6

1
D OPTIONAL SIDE SUPPLY 11 3 5 4 6 62 G 7 8

13 9 6 J 12

6 K C 10 1

Note: For units with standard return and supply grilles. 1. 2. 3. 4. 5. Supply Air Grille (optional) Unit-Mounted Thermostat (optional) Motor/Blower Assemby Riser Expansion Loops Electrical Control Box

6. Valve Package (optional) 7. Filter 8. Coil 9. Condensate Tray 10. See through P-Trap Drain
Dimensions (inches) F G H J 2 56 8 3 2 56 8 3 56 8 3 2 56 8 3 2 56 10 3 4 56 10 3 1 56 10 3 4 59 10 3 2 59 12 2 4 59 12 2 1 59 12 2 4 59 12 2

11. Riser Assembly 12. Fresh Air Damper Opening (optional) 13. Stamped Return Air/Access Panel (optional)
Approx. Weight (pounds) 230 230 240 240 270 270 280 280 310 310 320 320

Dimensions

Model VSR03 VSR03 Dual Supply VSR04 VSR04 Dual Supply VSR06 VSR06 Dual Supply VSR08 VSR08 Dual Supply VSR10 VSR10 Dual Supply VSR12 VSR12 Dual Supply

A 88 88 88 88 88 88 88 88 88 88 88 88

B 17 17 17 17 20 20 20 20 24 24 24 24

C 17 17 17 17 20 20 20 20 24 24 24 24

D 10 8 10 8 12 10 12 10 14 12 16 12

E 12 12 16 12 16 12 18 12 20 16 22 16

K 7 7 7 7 8 8 8 8 10 10 10 10

L 3 4 3 4 4 5 4 5 5 6 4 6

Filter 13x23x1 13x23x1 13x23x1 13x23x1 16x27x1 16x27x1 16x27x1 16x27x1 20x31x1 20x31x1 20x31x1 20x31x1

All dimensions are in inches.

V6

Fan Coils Vertical Stack VSR Performance Data Performance Data


VSR Recessed Hi-Rise
2-PIPE SYSTEM 2 Rows Cooling (1) 2 Rows Heating (1) Total Sensible Flow PD Sensible Flow PD MBH MBH gpm ft wg MBH gpm ft wg 9.7 6.9 1.9 4.54 25.3 1.7 2.84 10.9 7.9 2.2 5.63 29.2 2.0 3.70 14.9 11.1 3.0 2.39 41.7 2.8 1.86 18.0 13.8 3.6 3.44 52.1 3.6 2.84 23.8 18.0 4.7 3.14 68.0 4.6 2.70 26.2 20.2 5.2 3.80 76.4 5.2 3.37 2-PIPE SYSTEM 3 Rows Cooling 3 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.5 2.5 11.31 31.9 2.2 6.58 9.2 2.6 2.00 36.1 2.5 1.54 13.8 4.0 5.82 52.9 3.6 3.99 16.8 4.6 3.18 66.1 4.5 2.72 22.7 6.5 7.38 87.1 5.9 5.52 25.0 6.9 4.98 97.5 6.7 4.34 2-PIPE SYSTEM 4 Rows Cooling 4 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.8 2.6 2.67 33.7 2.3 1.70 10.2 3.0 3.43 39.4 2.7 2.29 14.7 4.4 3.45 56.7 3.9 2.44 19.0 5.5 5.39 73.5 5.0 3.99 24.6 7.2 6.39 94.6 6.5 4.77 28.1 8.2 8.09 108.3 7.4 6.17 2-PIPE SYSTEM 5 Rows Cooling 5 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 9.1 2.8 3.63 34.0 2.3 2.08 10.6 3.2 4.76 40.0 2.7 2.84 15.2 4.7 4.72 57.6 3.9 2.92 19.3 5.7 3.95 75.1 5.1 2.96 25.5 7.8 8.43 96.7 6.6 5.65 29.4 8.9 10.83 111.5 7.6 7.42 4-PIPE SYSTEM 2 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 6.6 1.9 4.19 16.1 1.1 4.43 7.5 2.1 5.21 18.2 1.2 5.52 10.5 2.8 2.19 26.2 1.8 2.08 13.2 3.5 3.19 32.2 2.2 3.04 17.2 4.6 2.89 42.5 2.9 6.76 19.3 5.0 3.51 47.2 3.2 8.22 4-PIPE SYSTEM 3 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.1 2.4 10.26 15.4 1.1 4.09 8.7 2.5 1.83 17.3 1.2 5.09 13.1 3.8 5.28 25.1 1.7 2.02 16.0 4.4 2.92 30.8 2.1 2.93 21.5 6.2 6.71 40.6 2.8 6.51 23.7 6.6 4.56 45.1 3.1 7.89 4-PIPE SYSTEM 4 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.3 2.5 2.38 14.6 1.0 3.73 9.3 2.9 3.09 16.5 1.1 4.68 13.8 4.1 3.10 23.8 1.6 1.90 17.8 5.2 4.86 29.3 2.0 2.83 23.1 6.9 5.75 38.6 2.6 6.13 26.5 7.8 7.29 43.0 2.9 7.53

Model VSR03 VSR04 VSR06 VSR08 VSR10 VSR12

Model VSR03 VSR04 VSR06 VSR08 VSR10 VSR12

Total MBH 9.3 10.4 14.2 17.3 22.8 25.2

Model VSR03 VSR04 VSR06 VSR08 VSR10 VSR12

Total MBH 12.7 12.9 20.0 23.0 32.5 34.4

Model VSR03 VSR04 VSR06 VSR08 VSR10 VSR12

Total MBH 12.1 12.3 19.0 22.0 31.0 32.9

Model VSR03 VSR04 VSR06 VSR08 VSR10 VSR12

Total MBH 13.3 15.1 21.8 27.5 36.3 41.0

Model VSR03 VSR04 VSR06 VSR08 VSR10 VSR12

Total MBH 12.5 14.3 20.6 26.1 34.4 38.8

Model

Performance Data

VSR03 VSR04 VSR06 VSR08 VSR10 VSR12

Total MBH 14.1 16.3 23.4 28.8 39.1 44.6

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high fan speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V7

Fan Coils Vertical Stack VSR Performance Data


Performance Data (continued)

Nominal Air Volumes cfm (1) Model High Med Low VSR03 375 300 225 VSR04 449 353 268 VSR06 642 503 375 VSR08 888 760 556 VSR10 1102 920 717 VSR12 1305 1124 931

Air Volume (cfm) Vs External Static Pressure in wg (2) Model 0.05 0.10 0.15 0.20 0.25 0.30 VSR03 355 340 326 308 283 249 VSR04 440 423 402 376 349 319 VSR06 630 601 565 526 483 434 VSR08 844 809 778 743 705 664 VSR10 1060 1028 998 968 935 903 VSR12 1261 1238 1221 1201 1176 1149

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

2. Air volumes at alternative external static pressures are based at high fan speed.

Model VSR03 VSR04 VSR06 VSR08 VSR10 VSR12

Motor Total HP AMPS 1/15 1.80 1/10 2.10 1/15 1.80 1/10 2.10 1/8 2.60 1/5 3.20

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/60Hz.

Performance Data

V8

Fan Coils Vertical Stack VSRM Description


Vertical Stack Series (continued) Discharge air grilles: - Aluminum double defection. - Deluxe aluminum double deection grilles (Contact TITUS for availability). - Linear bar aluminum grilles. Discharge air grille options: - Dual discharge. - Air damper controls for units with dual discharge grilles. Special discharge air grille colors (Contact TITUS for color range availability and price). Discharge air grille location. Return air/access panels painted white: - Stamped galvanealed steel. - Remote stamped galvanealed steel. - ADA stamped galvanealed steel. - ADA remote stamped panel. - Invislot blank front panel. - Deluxe aluminum panel with a removable core. - Linear bar aluminum panel with a removable core. Special return air/access panel color (Contact TITUS for color range availability and price) Return air/access panel fasteners: - Philips head fasteners. - Tamper proof fasteners. - Quarter turn fasteners. Fan section noise reduction kit. 1-hour re rating. Riser Installation options: - Unit mounted riser. - Risers supplied loose. Riser pipe type M, L and K. Consult TITUS for availability of type K risers. Riser thermal Insulation in - or -inch wall thickness. Riser connections to master unit options: - Welded to the unit piping. - Union connections using rigid copper pipe. - Union connections with exible braided stainless steel hoses. Riser connections to salve unit (supplied separate) options: - Union connections using rigid copper pipe. - Union connections with exible braided stainless steel hoses. Riser extensions. Riser extension end connection reducers.

VSRM Recessed Hi-Rise Remote Master


Factory assembled, vertical high-rise building VSRM master fan coils stand alone with riser water connections ready for a remote slave unit VSRS, are designed for free-blow or ducted, concealed installations, suitable for hotel, motel and apartment building applications. Standard Features Include: Performance ARI Certied to Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. All casing sheet metal components fabricated of 18GA G90 galvanized steel. High-eciency 2-row coil suitable for a 2-pipe system. Coil manual air vent. 1-inch thick disposable lter. Cabinet liner in -inch dual-density berglass. Multi-speed motor of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blowers of the whisper quite type. Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally protected on the outside. (Consult TITUS for availability). Translucent exible condensate water P-trap. Plenum discharge air anges for duct and dry wall applications.

A Participating Corporation in the ARI 440 Certication Program

Optional Features Include: 3-, 4- and 5-row coils for 2-pipe systems. Single block 2, 3 and 4 rows CW with 1-row re-heat coils for 4-pipe system applications (5 rows max). Single block 2 and 3 rows CW with 2 rows re-heat for 4-pipe system applications (5 rows max). Automatic coil air vents. Filter option include: - 1-inch high-eciency pleated lters. - 1-inch washable lters. Cabinet liner in 1-inch dualdensity berglass. Motor Voltage suitable for 208V, 230V or 277V/1Ph/ 60Hz power supplies. Motor in-line quick disconnect. Thermostat and Accessories (refer to Accessories on page V83 for details). Single power supply disconnects switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. Standby electric heater auto changeover switch. Fresh air opening. Fresh air manual and auto dampers. Fresh air freeze protection. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel. - Double wall construction consisting of outer and inner skins. - Condensate pan mastic coating applicable to the inside of the condensate pans for a prolonged life.

VSRM

V9

Fan Coils Vertical Stack VSRM Dimensions Dimensions


VSRM Recessed Hi-Rise Remote Master
TOP VIEW H

L D

OPTIONAL TOP SUPPLY E

SIDE VIEW OPTIONAL TOP SUPPLY 1 3

FRONT VIEW E 1

6 D OPTIONAL SIDE SUPPLY 11

D 2

E 5 14 4 6 8 G 7 9 3

62

13 41

6 J B C 1 10

361/64 1 12

Note: For units with standard return and supply grilles. 1. Supply Air Opening 2. Unit-Mounted Thermostat (optional) 3. Motor/Blower(s) Assemby 4. Riser Expansion Loops (optional) 5. Electrical Control Box

6. Valve Package (optional) 7. Filter 8. Coil 9. Condensate Tray 10. See through P-Trap Drain 11. Riser Assembly (optional)
Dimensions (inches) F G 2 56 2 56 56 2 56 2 56 4 56 1 56 4 59 2 59 4 59 1 59 4 59

12. Fresh Air Damper Opening (optional) 13. 1-hour Firewall (optional) 14. Return Air/Access Panel (optional)

Dimensions

Model VSRM03 VSRM03 Dual Supply VSRM04 VSRM04 Dual Supply VSRM06 VSRM06 Dual Supply VSRM08 VSRM08 Dual Supply VSRM10 VSRM10 Dual Supply VSRM12 VSRM12 Dual Supply A 88 88 88 88 88 88 88 88 88 88 88 88 B 17 17 17 17 20 20 20 20 24 24 24 24 C 17 17 17 17 20 20 20 20 24 24 24 24 D 10 8 10 8 12 10 12 10 14 12 16 12 E 12 12 16 12 16 12 18 12 20 16 22 16

Approx. Weight H 8 8 8 8 10 10 10 10 12 12 12 12 J 3 3 3 3 3 3 3 3 2 2 2 2 K 7 7 7 7 8 8 8 8 10 10 10 10 L 3 4 3 4 4 5 4 5 5 6 4 6 Filter 13x23x1 13x23x1 13x23x1 13x23x1 16x27x1 16x27x1 16x27x1 16x27x1 20x31x1 20x31x1 20x31x1 20x31x1 (pounds) 230 230 240 240 270 270 280 280 310 310 320 320

All dimensions are in inches.

V10

Fan Coils Vertical Stack VSRM Performance Data Performance Data


VSRM Recessed Hi-Rise Remote Master
2-PIPE SYSTEM 2 Rows Cooling (1) 2 Rows Heating (1) Total Sensible Flow PD Sensible Flow PD MBH MBH gpm ft wg MBH gpm ft wg 9.7 6.9 1.9 4.54 25.3 1.7 2.84 10.9 7.9 2.2 5.63 29.2 2.0 3.70 14.9 11.1 3.0 2.39 41.7 2.8 1.86 18.0 13.8 3.6 3.44 52.1 3.6 2.84 23.8 18.0 4.7 3.14 68.0 4.6 2.70 26.2 20.2 5.2 3.80 76.4 5.2 3.37 2-PIPE SYSTEM 3 Rows Cooling 3 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.5 2.5 11.31 31.9 2.2 6.58 9.2 2.6 2.00 36.1 2.5 1.54 13.8 4.0 5.82 52.9 3.6 3.99 16.8 4.6 3.18 66.1 4.5 2.72 22.7 6.5 7.38 87.1 5.9 5.52 25.0 6.9 4.98 97.5 6.7 4.34 2-PIPE SYSTEM 4 Rows Cooling 4 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.8 2.6 2.67 33.7 2.3 1.70 10.2 3.0 3.43 39.4 2.7 2.29 14.7 4.4 3.45 56.7 3.9 2.44 19.0 5.5 5.39 73.5 5.0 3.99 24.6 7.2 6.39 94.6 6.5 4.77 28.1 8.2 8.09 108.3 7.4 6.17 2-PIPE SYSTEM 5 Rows Cooling 5 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 9.1 2.8 3.63 34.0 2.3 2.08 10.6 3.2 4.76 40.0 2.7 2.84 15.2 4.7 4.72 57.6 3.9 2.92 19.3 5.7 3.95 75.1 5.1 2.96 25.5 7.8 8.43 96.7 6.6 5.65 29.4 8.9 10.83 111.5 7.6 7.42 4-PIPE SYSTEM 2 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 6.6 1.9 4.19 16.1 1.1 4.43 7.5 2.1 5.21 18.2 1.2 5.52 10.5 2.8 2.19 26.2 1.8 2.08 13.2 3.5 3.19 32.2 2.2 3.04 17.2 4.6 2.89 42.5 2.9 6.76 19.3 5.0 3.51 47.2 3.2 8.22 4-PIPE SYSTEM 3 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.1 2.4 10.26 15.4 1.1 4.09 8.7 2.5 1.83 17.3 1.2 5.09 13.1 3.8 5.28 25.1 1.7 2.02 16.0 4.4 2.92 30.8 2.1 2.93 21.5 6.2 6.71 40.6 2.8 6.51 23.7 6.6 4.56 45.1 3.1 7.89 4-PIPE SYSTEM 4 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.3 2.5 2.38 14.6 1.0 3.73 9.3 2.9 3.09 16.5 1.1 4.68 13.8 4.1 3.10 23.8 1.6 1.90 17.8 5.2 4.86 29.3 2.0 2.83 23.1 6.9 5.75 38.6 2.6 6.13 26.5 7.8 7.29 43.0 2.9 7.53

Model VSRM03 VSRM04 VSRM06 VSRM08 VSRM10 VSRM12

Model VSRM03 VSRM04 VSRM06 VSRM08 VSRM10 VSRM12

Total MBH 9.3 10.4 14.2 17.3 22.8 25.2

Model VSRM03 VSRM04 VSRM06 VSRM08 VSRM10 VSRM12

Total MBH 12.7 12.9 20.0 23.0 32.5 34.4

Model VSRM03 VSRM04 VSRM06 VSRM08 VSRM10 VSRM12

Total MBH 12.1 12.3 19.0 22.0 31.0 32.9

Model VSRM03 VSRM04 VSRM06 VSRM08 VSRM10 VSRM12

Total MBH 13.3 15.1 21.8 27.5 36.3 41.0

Model VSRM03 VSRM04 VSRM06 VSRM08 VSRM10 VSRM12

Total MBH 12.5 14.3 20.6 26.1 34.4 38.8

Model

Performance Data

VSRM03 VSRM04 VSRM06 VSRM08 VSRM10 VSRM12

Total MBH 14.1 16.3 23.4 28.8 39.1 44.6

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high fan speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V11

Fan Coils Vertical Stack VSRM Performance Data


Performance Data (continued)

Nominal Air Volumes cfm (1) Model High Med Low VSRM03 375 300 225 VSRM04 449 353 268 VSRM06 642 503 375 VSRM08 888 760 556 VSRM10 1102 920 717 VSRM12 1305 1124 931

Air Volume (cfm) Vs External Static Pressure in wg (2) Model 0.05 0.10 0.15 0.20 0.25 0.30 VSRM03 355 340 326 308 283 249 VSRM04 440 423 402 376 349 319 VSRM06 630 601 565 526 483 434 VSRM08 844 809 778 743 705 664 VSRM10 1060 1028 998 968 935 903 VSRM12 1261 1238 1221 1201 1176 1149

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

2. Air volumes at alternative external static pressures are based at high fan speed.

Model VSRM03 VSRM04 VSRM06 VSRM08 VSRM10 VSRM12

Motor Total HP AMPS 1/15 1.80 1/10 2.10 1/15 1.80 1/10 2.10 1/8 2.60 1/5 3.20

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/60Hz.

Performance Data

V12

Fan Coils Vertical Stack VSRS Description


Vertical Stack Series (continued) Condensate pan mastic coating applicable to the inside of the condensate pans for a prolonged life. Condensate pan overow safety switch. Discharge air grilles: - Aluminum double defection. - Deluxe aluminum double deection grilles (Contact TITUS for availability). - Linear bar aluminum grilles. Discharge air grille options: - Dual discharge. - Air damper controls for units with dual discharge grilles. Special discharge air grille colors (Contact TITUS for color range availability and price). Discharge air grille location. Return air/access panels painted white: - Stamped galvanealed steel. - Remote stamped galvanealed steel. - ADA stamped galvanealed steel. - ADA remote stamped panel. - Invislot blank front panel. - Deluxe aluminum panel with a removable core. - Linear bar aluminum panel with a removable core. Special return air/access panel color (Contact TITUS for color range availability and price). Return air/access panel fasteners: - Philips head fasteners. - Tamper proof fasteners. - Quarter turn fasteners. Fan section noise reduction kit. 1-hour re rating. Connections to master unit risers options (supplied separate): - Union connections using rigid copper pipe. - Union connections with exible braided stainless steel hoses.

VSRS Recessed Hi-Rise Remote Slave


Factory assembled, vertical high-rise building VSRS slave fan coils stand alone ready, to connect to a remote master unit VSRM, are designed for free-blow or ducted, concealed installations suitable for hotel, motel and apartment building applications. Standard Features Include: Performance ARI Certied to Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. All casing sheet metal components fabricated of 18GA G90 galvanized steel. High-eciency 2-row coil suitable for a 2-pipe system. Coil manual air vent. 1-inch thick disposable lter. Cabinet liner in -inch dual-density berglass. Multi-speed motor of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blowers of the whisper quite type. Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally protected on the outside (Consult TITUS for availability). Translucent exible condensate water P-trap. Plenum discharge air anges for duct and dry wall applications. Optional Features Include: 3-, 4- and 5-row coils for 2-pipe systems. Single block 2, 3 and 4 rows CW with 1-row re-heat coils for 4-pipe system applications (5 rows max). Single block 2 and 3 rows CW with 2 rows re-heat for 4-pipe system applications (5 rows max). Automatic coil air vents. Filter option include: - 1-inch high-eciency pleated lters. - 1-inch washable lters. Cabinet liner in 1-inch dualdensity berglass. Motor voltage suitable for 208V, 230V or 277V/1ph/ 60hz power supplies. Motor in-line quick disconnect. Thermostat and Accessories (refer to Accessories on page v83 for details). Single power supply disconnects switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. Standby electric heater auto changeover switch. Fresh air opening. Fresh air manual and auto dampers. Fresh air freeze protection. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel (Consult TITUS for availability). - Double wall construction consisting of outer and inner skins.

Dimensions

A Participating Corporation in the ARI 440 Certication Program

V13

Fan Coils Vertical Stack VSRS Dimensions Dimensions


VSRS Recessed Hi-Rise Remote Slave
TOP VIEW L D

OPTIONAL TOP SUPPLY E FRONT VIEW

E 1 D D 2

SIDE VIEW OPTIONAL TOP SUPPLY

OPTIONAL SIDE SUPPLY E

5 A 13 6 4 62 G 7 9 8

3 12

11 6 J B C 1 10 K 1

Note: For units with standard return and supply grilles. 1. Supply Air Opening 2. Unit-Mounted Thermostat (optional) 3. Blower / Motor Assembly 4. Riser Expansion Loops (optional) 5. Electrical Control Box
Model VSRS 03 VSRS 03 Dual Supply VSRS 04 VSRS 04 Dual Supply VSRS 06 VSRS 06 Dual Supply VSRS 08 VSRS 08 Dual Supply VSRS 10 VSRS 10 Dual Supply VSRS 12 VSRS 12 Dual Supply

6. Valve Package (optional) 7. Filter 8. Coil Assembly 9. Condensate pan 10. See through P-Trap Drain
Dimensions (inches) F G 2 56 2 56 56 2 56 2 56 4 56 1 56 4 59 2 59 4 59 1 59 4 59

11. Fresh Air Damper Opening (optional) 12. 1-hour Firewall (optional) 13. Return Air/Access Panel (optional)

A 88 88 88 88 88 88 88 88 88 88 88 88

B 17 17 17 17 20 20 20 20 24 24 24 24

C 17 17 17 17 20 20 20 20 24 24 24 24

D 10 8 10 8 12 10 12 10 14 12 16 12

E 12 12 16 12 16 12 18 12 20 16 22 16

J 3 3 3 3 3 3 3 3 2 2 2 2

K 7 7 7 7 8 8 8 8 10 10 10 10

L 3 4 3 4 4 5 4 5 5 6 4 6

Filter 13x23x1 13x23x1 13x23x1 13x23x1 16x27x1 16x27x1 16x27x1 16x27x1 20x31x1 20x31x1 20x31x1 20x31x1

Approx. Weight (pounds) 210 210 220 220 250 250 260 260 290 290 300 300

Dimensions

All dimensions are in inches.

V14

Fan Coils Vertical Stack VSRS Performance Data Performance Data


VSRS Recessed Hi-Rise Remote Slave
2-PIPE SYSTEM 2 Rows Cooling (1) 2 Rows Heating (1) Total Sensible Flow PD Sensible Flow PD MBH MBH gpm ft wg MBH gpm ft wg 9.7 6.9 1.9 4.54 25.3 1.7 2.84 10.9 7.9 2.2 5.63 29.2 2.0 3.70 14.9 11.1 3.0 2.39 41.7 2.8 1.86 18.0 13.8 3.6 3.44 52.1 3.6 2.84 23.8 18.0 4.7 3.14 68.0 4.6 2.70 26.2 20.2 5.2 3.80 76.4 5.2 3.37 2-PIPE SYSTEM 3 Rows Cooling 3 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.5 2.5 11.31 31.9 2.2 6.58 9.2 2.6 2.00 36.1 2.5 1.54 13.8 4.0 5.82 52.9 3.6 3.99 16.8 4.6 3.18 66.1 4.5 2.72 22.7 6.5 7.38 87.1 5.9 5.52 25.0 6.9 4.98 97.5 6.7 4.34 2-PIPE SYSTEM 4 Rows Cooling 4 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.8 2.6 2.67 33.7 2.3 1.70 10.2 3.0 3.43 39.4 2.7 2.29 14.7 4.4 3.45 56.7 3.9 2.44 19.0 5.5 5.39 73.5 5.0 3.99 24.6 7.2 6.39 94.6 6.5 4.77 28.1 8.2 8.09 108.3 7.4 6.17 2-PIPE SYSTEM 5 Rows Cooling 5 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 9.1 2.8 3.63 34.0 2.3 2.08 10.6 3.2 4.76 40.0 2.7 2.84 15.2 4.7 4.72 57.6 3.9 2.92 19.3 5.7 3.95 75.1 5.1 2.96 25.5 7.8 8.43 96.7 6.6 5.65 29.4 8.9 10.83 111.5 7.6 7.42 4-PIPE SYSTEM 2 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 6.6 1.9 4.19 16.1 1.1 4.43 7.5 2.1 5.21 18.2 1.2 5.52 10.5 2.8 2.19 26.2 1.8 2.08 13.2 3.5 3.19 32.2 2.2 3.04 17.2 4.6 2.89 42.5 2.9 6.76 19.3 5.0 3.51 47.2 3.2 8.22 4-PIPE SYSTEM 3 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.1 2.4 10.26 15.4 1.1 4.09 8.7 2.5 1.83 17.3 1.2 5.09 13.1 3.8 5.28 25.1 1.7 2.02 16.0 4.4 2.92 30.8 2.1 2.93 21.5 6.2 6.71 40.6 2.8 6.51 23.7 6.6 4.56 45.1 3.1 7.89 4-PIPE SYSTEM 4 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.3 2.5 2.38 14.6 1.0 3.73 9.3 2.9 3.09 16.5 1.1 4.68 13.8 4.1 3.10 23.8 1.6 1.90 17.8 5.2 4.86 29.3 2.0 2.83 23.1 6.9 5.75 38.6 2.6 6.13 26.5 7.8 7.29 43.0 2.9 7.53

Model VSRS03 VSRS04 VSRS06 VSRS08 VSRS10 VSRS12

Model VSRS03 VSRS04 VSRS06 VSRS08 VSRS10 VSRS12

Total MBH 9.3 10.4 14.2 17.3 22.8 25.2

Model VSRS03 VSRS04 VSRS06 VSRS08 VSRS10 VSRS12

Total MBH 12.7 12.9 20.0 23.0 32.5 34.4

Model VSRS03 VSRS04 VSRS06 VSRS08 VSRS10 VSRS12

Total MBH 12.1 12.3 19.0 22.0 31.0 32.9

Model VSRS03 VSRS04 VSRS06 VSRS08 VSRS10 VSRS12

Total MBH 13.3 15.1 21.8 27.5 36.3 41.0

Model VSRS03 VSRS04 VSRS06 VSRS08 VSRS10 VSRS12

Total MBH 12.5 14.3 20.6 26.1 34.4 38.8

Model

Performance Data

VSRS03 VSRS04 VSRS06 VSRS08 VSRS10 VSRS12

Total MBH 14.1 16.3 23.4 28.8 39.1 44.6

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high fan speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V15

Fan Coils Performance Data


Performance Data (continued)

Nominal Air Volumes cfm (1) Model High Med Low VSRS03 375 300 225 VSRS04 449 353 268 VSRS06 642 503 375 VSRS08 888 760 556 VSRS10 1102 920 717 VSRS12 1305 1124 931

Air Volume (cfm) Vs External Static Pressure in wg (2) Model 0.05 0.10 0.15 0.20 0.25 0.30 VSRS03 355 340 326 308 283 249 VSRS04 440 423 402 376 349 319 VSRS06 630 601 565 526 483 434 VSRS08 844 809 778 743 705 664 VSRS10 1060 1028 998 968 935 903 VSRS12 1261 1238 1221 1201 1176 1149

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

2. Air volumes at alternative external static pressures are based at high fan speed.

Model VSRS03 VSRS04 VSRS06 VSRS08 VSRS10 VSRS12

Motor Total HP AMPS 1/15 1.80 1/10 2.10 1/15 1.80 1/10 2.10 1/8 2.60 1/5 3.20

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/60Hz.

Performance Data

V16

Fan Coils Vertical Stack VSM/VSS Description


Vertical Stack Series (continued) Condensate pan mastic coating applicable to the inside of the condensate pans for a prolonged life. Condensate pan overow safety switch. Discharge air grilles: - Aluminum double defection. - Deluxe aluminum double deection grilles (Contact TITUS for availability). - Linear bar aluminum grilles. Discharge air grille options: - Dual discharge. - Air damper controls for units with dual discharge grilles. Special discharge air grille colors (Contact TITUS for color range availability and price). Discharge air grille location. Return air/access panels painted white: - Stamped galvanealed steel. - Remote stamped galvanealed steel. - ADA stamped galvanealed steel. - ADA remote stamped panel. - Invislot blank front panel. - Deluxe aluminum panel with a removable core. - Linear bar aluminum panel with a removable core. Special return air/access panel color (Contact TITUS for color range availability and price). Return air/access panel fasteners: - Philips head fasteners. - Tamper proof fasteners. - Quarter turn fasteners. Fan section noise reduction kit. 1-hour re rating. Unit mounted risers. Welded connections to risers Riser pipe type M, L and K. Consult TITUS for availability of type K risers. Riser thermal insulation in or -inch wall thickness. Riser extensions. Riser extension end connection reducers.

VSM/VSS Recessed Master/Slave


Factory assembled, vertical high-rise building VSM/VSS master/slave twin pack fan coils are designed for freeblow or ducted, concealed installations, sharing a single set of risers suitable for hotel, motel and apartment building applications. Standard Features Include: Performance ARI Certied to Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. All casing sheet metal components fabricated of 18GA G90 galvanized steel. High-eciency 2-row coil suitable for a 2-pipe system. Coil manual air vent. 1-Inch thick disposable lter. Cabinet liner in -inch dual-density berglass. Multi-speed motor of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blowers of the whisper quite type. Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally protected on the outside. (Consult TITUS for availability). Translucent exible condensate water P-trap. Plenum discharge air anges for duct and dry wall applications. Optional Features Include: 3-, 4- And 5-row coils for 2-pipe systems. Single block 2, 3 and 4 rows CW with 1-row re-heat coils for 4-pipe system applications (5 rows max). Single block 2 and 3 rows CW with 2 rows re-heat for 4-pipe system applications (5 rows max). Automatic coil air vents. Filter option include: - 1-Inch high-eciency pleated lters. - 1-Inch washable lters. Cabinet liner in 1-inch dualdensity berglass. Motor voltage suitable for 208V, 230V or 277V/1ph/ 60hz power supplies. Motor in-line quick disconnect. Thermostat and Accessories (refer to Accessories on page V83 for details). Single power supply disconnect switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. Standby electric heater auto changeover switch. Fresh air opening. Fresh air manual and auto dampers. Fresh air freeze protection. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel (Consult TITUS for availability). - Double wall construction consisting of outer and inner skins.

VSM/VSS

A Participating Corporation in the ARI 440 Certication Program

V17

Fan Coils Vertical Stack VSM/VSS Dimensions Dimensions


VSM/VSS Recessed Master/Slave
TOP VIEW

3 3 L D H OPTIONAL TOP SUPPLY 1 D 2 D E 13 A 62 G 3 5 6 4 8 7 9 6 SIDE VIEW 11 3

OPTIONAL TOP SUPPLY E

F 2

FRONT VIEW E

OPTIONAL SIDE SUPPLY

Note: For units with standard return and supply grilles. 1. Supply Air Opening 2. Unit Mounted Thermostat (optional) 3. Motor/Blower(s) Assembly 4. Expansion Loop 5. Electrical Control Box
Model VSM/VSS03 VSM/VSS03 Dual Supply VSM/VSS04 VSM/VSS04 Dual Supply VSM/VSS06 VSM/VSS06 Dual Supply VSM/VSS08 VSM/VSS08 Dual Supply VSM/VSS10 VSM/VSS10 Dual Supply VSM/VSS12 VSM/VSS12 Dual Supply

5 6

12

10

6. Valve Package (optional) 7. Filter 8. Coil 9. Condensation Tray 10. See through P-Trap Drain 11. Riser (optional)
Dimensions (inches) G H 56 8 56 8 56 8 56 8 56 10 56 10 56 10 59 10 59 12 59 12 59 12 59 12

12. Fresh air damper opening (optional) 13. Return Air/Access Panel (optional)

A 88 88 88 88 88 88 88 88 88 88 88 88

B 17 17 17 17 20 20 20 20 24 24 24 24

C 17 17 17 17 20 20 20 20 24 24 24 24

D 10 8 10 8 12 10 12 10 14 12 16 12

E 12 12 16 12 16 12 18 12 20 16 22 16

F 2 2 2 2 4 1 4 2 4 1 4

J 3 3 3 3 3 3 3 3 2 2 2 2

K 7 7 7 7 8 8 8 8 10 10 10 10

L 3 4 3 4 4 5 4 5 5 6 4 6

Filter 13x23x1 13x23x1 13x23x1 13x23x1 16x27x1 16x27x1 16x27x1 16x27x1 20x31x1 20x31x1 20x31x1 20x31x1

Approx. Weight (pounds) 460 460 480 480 540 540 560 560 620 620 640 640

Dimensions

All dimensions are in inches.

V18

Fan Coils Vertical Stack VSM/VSS Performance Data Performance Data


VSM/VSS Recessed Master/Slave
4-PIPE SYSTEM Model VSM/S03 VSM/S04 VSM/S06 VSM/S08 VSM/S10 VSM/S12 2 Rows Cooling (1) 2 Rows Heating (1) PD Total Sensible Flow PD Sensible Flow MBH MBH gpm ft wg MBH gpm ft wg 9.7 6.9 1.9 4.54 25.3 1.7 2.84 10.9 7.9 2.2 5.63 29.2 2.0 3.70 14.9 11.1 3.0 2.39 41.7 2.8 1.86 18.0 13.8 3.6 3.44 52.1 3.6 2.84 23.8 18.0 4.7 3.14 68.0 4.6 2.70 26.2 20.2 5.2 3.80 76.4 5.2 3.37 2-PIPE SYSTEM 3 Rows Cooling 3 Rows Heating Total Sensible Flow PD Sensible Flow PD MBH MBH gpm ft wg MBH gpm ft wg 12.7 8.5 2.5 11.31 31.9 2.2 6.58 12.9 9.2 2.6 2.00 36.1 2.5 1.54 20.0 13.8 4.0 5.82 52.9 3.6 3.99 23.0 16.8 4.6 3.18 66.1 4.5 2.72 32.5 22.7 6.5 7.38 87.1 5.9 5.52 34.4 25.0 6.9 4.98 97.5 6.7 4.34 2-PIPE SYSTEM 4 Rows Cooling 4 Rows Heating Total Sensible Flow PD Sensible Flow PD MBH MBH gpm ft wg MBH gpm ft wg 13.3 8.8 2.6 2.67 33.7 2.3 1.70 15.1 10.2 3.0 3.43 39.4 2.7 2.29 21.8 14.7 4.4 3.45 56.7 3.9 2.44 27.5 19.0 5.5 5.39 73.5 5.0 3.99 36.3 24.6 7.2 6.39 94.6 6.5 4.77 41.0 28.1 8.2 8.09 108.3 7.4 6.17 2-PIPE SYSTEM 5 Rows Cooling 5 Rows Heating Total Sensible Flow PD Sensible Flow PD MBH MBH gpm ft wg MBH gpm ft wg 14.1 9.1 2.8 3.63 34.0 2.3 2.08 16.3 10.6 3.2 4.76 40.0 2.7 2.84 23.4 15.2 4.7 4.72 57.6 3.9 2.92 28.8 19.3 5.7 3.95 75.1 5.1 2.96 39.1 25.5 7.8 8.43 96.7 6.6 5.65 Model VSM/S03 VSM/S04 VSM/S06 VSM/S08 VSM/S10 VSM/S12 Total MBH 9.3 10.4 14.2 17.3 22.8 25.2 2 Rows Cooling Sensible Flow MBH gpm 6.6 1.9 7.5 2.1 10.5 2.8 13.2 3.5 17.2 4.6 19.3 5.0 1 Row Heating PD Sensible Flow PD ft wg MBH gpm ft wg 4.19 16.1 1.1 4.43 5.21 18.2 1.2 5.52 2.19 26.2 1.8 2.08 3.19 32.2 2.2 3.04 2.89 42.5 2.9 6.76 3.51 47.2 3.2 8.22

Model VSM/S03 VSM/S04 VSM/S06 VSM/S08 VSM/S10 VSM/S12

Model VSM/S03 VSM/S04 VSM/S06 VSM/S08 VSM/S10 VSM/S12

Total MBH 12.1 12.3 19.0 22.0 31.0 32.9

4-PIPE SYSTEM 3 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.1 2.4 10.26 15.4 1.1 4.09 8.7 2.5 1.83 17.3 1.2 5.09 13.1 3.8 5.28 25.1 1.7 2.02 16.0 4.4 2.92 30.8 2.1 2.93 21.5 6.2 6.71 40.6 2.8 6.51 23.7 6.6 4.56 45.1 3.1 7.89 4-PIPE SYSTEM 4 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.3 2.5 2.38 14.6 1.0 3.73 9.3 2.9 3.09 16.5 1.1 4.68 13.8 4.1 3.10 23.8 1.6 1.90 17.8 5.2 4.86 29.3 2.0 2.83 23.1 6.9 5.75 38.6 2.6 6.13 26.5 7.8 7.29 43.0 2.9 7.53

Model VSM/S03 VSM/S04 VSM/S06 VSM/S08 VSM/S10 VSM/S12

Model VSM/S03 VSM/S04 VSM/S06 VSM/S08 VSM/S10 VSM/S12

Total MBH 12.5 14.3 20.6 26.1 34.4 38.8

Model

Performance Data

VSM/S03 VSM/S04 VSM/S06 VSM/S08 VSM/S10

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high fan speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V19

Fan Coils Vertical Stack VSM/VSS Performance Data


Performance Data (continued)

Nominal Air Volumes cfm (1) Model High Med Low VSM/S03 375 300 225 VSM/S04 449 353 268 VSM/S06 642 503 375 VSM/S08 888 760 556 VSM/S10 1102 920 717 VSM/S12 1305 1124 931

Air Volume (cfm) Vs External Static Pressure in wg (2) Model 0.05 0.10 0.15 0.20 0.25 0.30 VSM/S03 355 340 326 308 283 249 VSM/S04 440 423 402 376 349 319 VSM/S06 630 601 565 526 483 434 VSM/S08 844 809 778 743 705 664 VSM/S10 1060 1028 998 968 935 903 VSM/S12 1261 1238 1221 1201 1176 1149

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

2. Air volumes at alternative external static pressures are based at high fan speed.

Model VSM/S03 VSM/S04 VSM/S06 VSM/S08 VSM/S10 VSM/S12

Motor Total HP AMPS 1/15 1.80 1/10 2.10 1/15 1.80 1/10 2.10 1/8 2.60 1/5 3.20

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/60Hz.

Performance Data

V20

Fan Coils Vertical Stack Sound Power VS Sound Power


Fan Speed VS 03 High Medium Low Fan Speed VS 04 High Medium Low Fan Speed VS 06 High Medium Low Fan Speed VS 08 High Medium Low Fan Speed VS 10 High Medium Low Fan Speed VS 12 High Medium Low 2 125 76 71 49 2 125 76 72 51 2 125 72 65 58 2 125 79 74 64 2 125 77 74 64 2 125 75 71 67 3 250 60 55 45 3 250 62 57 49 3 250 60 52 47 3 250 66 61 55 3 250 65 59 55 3 250 63 58 56 4 5 6 CENTER FREQUENCY (CPS) 500 1000 2000 57 52 49 52 46 43 38 34 29 4 5 6 CENTER FREQUENCY (CPS) 500 1000 2000 59 53 50 55 48 45 42 37 32 4 5 6 CENTER FREQUENCY (CPS) 500 1000 2000 57 52 53 50 44 44 42 37 35 4 5 6 CENTER FREQUENCY (CPS) 500 1000 2000 63 59 58 59 53 52 50 45 44 4 5 6 CENTER FREQUENCY (CPS) 500 1000 2000 62 57 57 57 51 51 49 45 43 4 5 6 CENTER FREQUENCY (CPS) 500 1000 2000 60 56 55 56 54 53 51 46 44 7 4000 45 39 23 7 4000 47 42 27 7 4000 49 40 29 7 4000 56 49 38 7 4000 54 47 37 7 4000 52 46 38 8 8000 39 31 23 8 8000 42 35 27 8 8000 46 35 28 8 8000 53 44 36 8 8000 51 42 36 8 8000 51 41 37

Performance Data

Notes: 1. Tested to ARI Standard 350 Section 4.2. 2. Sound levels expressed in decibels, dB RE:1 x 10-12 watts (1 pico watt).

3. 115 volt, 60 cycle, single-phase, three-speed motor. 4. One-inch throwaway lter. 5. External static pressure 0.0 inch. 6. Total sound.

7. Stamped return air/access panel.

V21

Fan Coils Vertical Stack Specications Suggested Specications


Fan Coils
Vertical Stack Units Standard Congurations 1. Furnish and install TITUS Models VSR, VSRM, VSRS and VSM/ VSSS vertical stack high rise fan coils of sizes and capacities shown on the plans to meet prevailing cooling and heating requirements. 2. Fan coils shall be performance certied to ARI Standard 440. Units shall be wired in compliance with ANSI/UL 1995 Standard and listed with ETL. 3. Fan coils shall be sound tested in accordance with ARI Standard 260 for ducted units and ARI Standard 350 for non-ducted units. Manufacturer shall provide these dB ratings on request for each model specied. 4. Casing components shall be fabricated of 18-gauge G90 galvanized steel. 5. High-eciency, 2-row coil shall be suitable for a 2-pipe system. Coils shall be manufactured with aluminum ns mechanically bonded to seamless copper tubes. The copper tubes shall be -inch OD with a wall thickness of 0.017inch which comply with ASTM B-75. The ns shall be waved with ripple hedges for superior eciency with a thickness of 0.0045-inch and spaced at 10 fpi. All coils shall be at 100 psi leak tested with 100% helium to ensure a leak free coil. All coils shall be shipped with a safety air pressure of 100 - 125 psi to guarantee a leak free arrival at the nal destination. 6. Coils shall be installed with manual Schrader type air vents with a sealing cap and be located at the highest point of the coil. The cap shall have a dual purpose, to seal any potential water leakage in the eventuality of Schrader valve failure and as a service tool for the extraction/insertion of the internal Schrader valve. 7. Unit pipe entry/riser location shall be in accordance with the project schedule. 8. Standard lters shall be 1-inch thick of the disposable type with a one-piece, moisture resistant chipboard frame to eliminate corner separations. The spun glass ltering media shall be bonded with a resinous agent providing rigidity and resistance to media compression and meets UL class 2. 9. Filters shall be installed near the coil with two spring clips for easy removal. 10. Cabinet steel panels shall be lined with -inch dual-density berglass with a density of 1.5lbs/ft3 and 4.0lbs/ft3 for the face meeting NFPA 90A and 90B (appliances), NFPA 255, UL 181, UL723 and ASTM E84. 11. Motors shall be multi-speed of the permanent split capacitor type (PSC) and be directly coupled to the centrifugal fan blower. Motor shall be suitable for a power supply of 115V/1Ph/60Hz and shall be internally protected with an automatic thermal overload. Motor shaft shall be supported by sleeve bearings of the permanently lubricated type for the full life expectancy of the motor. All motors shall be directly mounted to the fan blower casing side and be isolated from the unit casing by three resilient anti-vibration mounts. 12. Direct-driven fan shall be of the whisper quite type, double width double inlet (DWDI) forward curved statically and dynamically balanced at the factory. The fan wheel and casing shall be constructed of galvanized steel. 13. Electric components shall be wired to a single control panel for single point power supply. 14. Condensate pan shall be singlewall 18-gauge G90 galvanized steel welded at the corners, thermally protected on the outside with re and smoke rated -inch high-density insulation to prevent condensation. The factory installed -inch OD sweat copper condensate connection shall be located at the lowest point of the condensate pan to ensure all water drains from the condensate pan (Consult TITUS for availability). 15. A translucent exible P-trap shall be installed and secured to the condensate tray connection via a spring clip for easy inspection and maintenance. 16. Discharge air plenum shall have discharge openings with a inch discharge air collar(s) for location of the dry wall and/or eld connection. Top discharge supply air ange shall be 1-inch. 17. Return air/access panel shall be of the stamped type made of 18gauge galvanealed steel, painted white with polyester powder coated paint and oven baked.

Specications

V22

Fan Coils Vertical Stack Specications


Suggested Specications (continued) Thermostat and Accessories Refer to Accessories on page V83. Disconnect Switches and Fuses Units shall be wired for single power with supply with a disconnect switch and fuse(s) to match the unit full maximum circuit ampacity (MCA) in line with UL 1995. 2-Pipe Heat/Cool Auto Changeover Switch A mechanical or electronic changeover switch shall be supplied on 2-pipe systems for automatic changeover of the operation of the thermostat for summer and winter modes. Electric Heater and Accessories 1. Electric heaters shall be of the wound type mounted in a metal frame and supported by ceramic rings and terminals. Electric heaters shall installed on the blower discharge side for better heat dissipation and shall include an automatic reset, high limit cutout and contactor. 2. 2-pipe standby electric heating - heaters shall be installed and pre-wired as standby heating in the eventuality of a failure of the primary hot water (HW) system. A changeover sensor shall be installed in each unit and the changeover between the failed hot water system and the standby electric heater shall be automatic. Chilled and Hot Water Valve Controls Refer to Accessories on page V83. Fresh Air and Accessories 1. A fresh air opening shall be provided with an external 1-inch ange for eld connection, or 2. A fresh air opening shall be provided with an external 1inch ange for eld connection complete with an internal manual adjustable damper control, or 3. A fresh air opening shall be provided with an external 1inch ange for eld connection complete with an automatic ON/OFF damper control which shall close if the unit is in the OFF mode. A freeze protection thermostat shall be installed at the fresh air intake and close the fresh air damper to prevent damage to the coil if temperature drops below 40F. Condensate Pan and Accessories 1. Condensate pan shall be single wall manufactured in 20-gauge 304 stainless steel and shall be thermally protected on the outside with re and smoke rated -inch high-density insulation to prevent condensation. The factory installed -inch OD sweat copper condensate connection shall be located at the lowest point of the condensate pan to ensure that all water is drained from the condensate pan (Consult TITUS for availability), or 2. Condensate pan shall be double wall construction consisting of an outer and inner skin. The outer skin shall be manufactured of 18-gauge G90 galvanized sheet metal wrapped around the inner skin with 1-inch thermal insulation between both skins to prevent condensation. The inner skin of the double wall condensate pan shall be of 18-gague G90 galvanized sheet metal, or 3. Condensate pan shall be double wall construction consisting of an outer and inner skin. The outer skin shall be manufactured of 18-gauge G90 galvanized sheet metal wrapped around the inner skin with 1-inch thermal insulation between both skins to prevent the formation of condensation. The inner skin of the double wall condensate pan shall be of 20-gauge 304 stainless steel galvanized sheet metal. 4. An automatic safety overow switch shall be installed in the condensate pan and shall prevent the operation of the unit electric system if an overow status is detected. 5. A mastic coating shall be applied to the inside of the condensate pan for a prolonged life. Noise Reduction Kit A noise reduction kit, fan section blank o acoustic panel shall be installed in the fan section to reduce the noise propagation thru the return air/access panel. UL 1479 Fire Rating Units shall be installed with -inch gypsum board X rated to meet a 1-hour re rating in accordance with UL1479 standards.

Fan Coils
Vertical Stack Units Optional Congurations Cooling and Heating Coils 1. High-eciency 3-, 4- and 5-row coils suitable for 2-pipe systems or, 2. High-eciency single block with 2, 3 and 4 rows chilled water (CW) with 1-row re-heat coil suitable for 4-pipe system applications, or 3. High-eciency single block with 2, 3 rows chilled water (CW) with 2row re-heat coil suitable for 4-pipe system applications. 4. Coils shall be installed with an automatic air vent capable of operation in chilled or hot water systems to a maximum pressure 125 psi. Filter 1. Filter shall be 1-inch pleated lter with an average atmospheric dust spot eciency range of 20 - 30% per ASHRAE Standard 52.1 test method, or 2. Filter shall be 1-inch washable lter consisting of synthetic bers coated with a special resin, then baked together at a high temperature resulting in a tough and springy, thoroughly bonded, nearly rigid air ltration media. Washable lters shall have a longer service life, better structural integrity as well as being completely odor free. 3. A spare set of lters shall be available for replacement after the commissioning of the unit and prior to the handover of the project. Cabinet Insulation Cabinet liners shall be 1-inch dualdensity berglass with a density of 1.5lbs/ft3 and 4.0lbs/ft3 for the face meeting NFPA 90A and 90B (appliances) and NFPA 255 with less than 25 ame and less than 50 smoke spread, UL 181, UL723 and ASTM E84. Motor 1. Motor shall be suitable for 115V/1Ph/60Hz or 208V/1Ph/60Hz or 230V/1Ph/60Hz or 277V/1Ph/ 60Hz power supplies (delete as applicable). 2. A motor in-line quick disconnect shall be installed to facilitate the removal/replacement of motor.

Specications

V23

Fan CoilsFan Coils Vertical Stack Specications


Suggested Specications (continued) 3. Remote ADA return air/access panel shall be installed away from the unit, stamped, galvanealed steel, painted white with polyester powder coated paint, oven baked and designed for applications to meet the Americans with Disability Act. The thermostat shall be installed in the return air/access panel located at a max height of 48 from the oor. An in-line quick connector shall be provided between the thermostat and the unit electric control box to facilitate the removal of the return air/ access panel, or 4. Invislot return air/access panel shall be a blank front panel, galvanealed steel, painted white with polyester powder coated paint, oven baked. The panel shall be oset from the wall as per the manufacturers recommendations to allow the return air entry into the units, or 5. Deluxe return air/access panel shall be manufactured of aluminum, painted white with a removable core for easy access to the unit, or 6. Linear bar return air/access panel shall be manufactured of aluminum painted white with a removable core for easy access to the unit. 7. Special Return air/access panel color shall be___________. Contact TITUS for color range availability and price. 8. Return air/access panel security fasteners shall be tamperproof, which require a special tool to access the units, or 9. Return air/access panel security fasteners shall be of the quarter turn type, to facilitate the removal of the access panel. Riser Assembly 1. Risers shall be installed at the factory and supplied in two pieces (riser and riser extension) to reduce eld installation time or, supplied loose in a single piece for eld installation. 2. Riser pipe diameters shall vary between -inch and 2 inches OD and be in accordance with the riser schedule. 3. Riser pipes shall be copper type M, L or K (Contact TITUS for availability of K copper risers). 4. Riser insulation shall be of the closed cell, exible elastomeric thermal insulation type available in - or -inch wall thickness. 5. Riser connections shall be welded directly to the unit piping or, connected to the units via O-ring unions (risers supplied loose or separate Master/Slave units) or connected to the unit via Oring unions and exible braided connectors (risers supplied loose or separate Master/Slave units). Riser Extensions 1. Riser extension material and insulation type shall be the same as the main risers attached to the unit. Riser extensions shall be supplied loose and clearly marked to bridge the space between the xed risers of two units. All riser extension insulation shall be supplied loose uncut for eld installation. 2. Riser extension length shall be in accordance with the riser schedule. Riser Extension Connections Riser extension end connections shall be swaged or installed with an expanding or reducing coupling in accordance with the riser schedule.

Fan Coils
Vertical Stack Units Optional Congurations (continued) Discharge Air Grilles and Accessories 1. Discharge air grilles shall be double-deection made of aluminum and painted white, or 2. Discharge air grilles shall be double-deection of the Deluxe type, made of aluminum and painted white, or 3. Discharge air grilles shall be non adjustable of the linear type, made of aluminum and painted white. 4. Units shall have dual discharge grilles with manual adjustable dampers to control the air discharge thru each air outlet. 5. Special discharge air grilles colors shall be______________. (Contact TITUS for color range availability and price). 6. Discharge air grille location shall be in accordance with the project specication and drawings. Return Air/Access Panel and Accessories 1. Remote Return air/access panel shall be installed away from the unit, stamped, galvanealed steel painted white with polyester powder coated paint, oven baked suitable for application where the unit is remote from the wall. Discharge air must be ducted to avoid air recirculation between the supply and the return air, or 2. ADA return air/access panel shall be stamped, galvanealed steel, painted white with polyester powder coated paint, oven baked and designed for applications to meet the Americans with Disability Act. The thermostat shall be installed in the return air/access panel located at a max height of 48 inches from the oor. An in-line quick connector shall be provided between the thermostat and the unit electric control box to facilitate the removal of the return air/access panel, or

Specications

V24

Fan Coils Horizontal Basic HBC Description

Horizontal Basic Series


HBC Concealed Ceiling
Factory assembled, horizontal blowthru ducted fan coils designed for concealed installations above ceilings with ducted air discharge and suitable for projects such as hotels, motels, condominiums and general commercial application. Standard Features Include: Performance ARI Certied to Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. All casing sheet metal components are fabricated of 18GA G90 galvanized steel. High-eciency 2-row coil suitable for a 2-pipe system. Coil manual air vent. Multi-speed motor of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blowers of the whisper quite type. Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally protected on the outside (Consult TITUS for availability). 1-inch discharge air ange. Anti-Vibration Mounts for eld installation.

Optional Features Include: 3-, 4- And 5-row coils for 2-pipe systems. Single block 2, 3 and 4 rows CW with 1 row re-heat coils for 4-pipe system applications (5 rows max). Single block 2 and 3 rows CW with 2 rows re-heat for 4-Pipe system applications (5 rows max). Automatic coil air vents. LH or RH entry pipe connections. Motor voltage suitable for 208V, 230V or 277V/1Ph/ 60Hz power supplies. Thermostat and Accessories (refer to Accessories on page V83 for details). Single power supply disconnect switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. HW standby electric heater auto changeover switch. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel. - Double wall construction consisting of outer and inner skins. Condensate pan mastic coating applicable to the inside of the condensate pans for a prolonged life. Condensate pan overow safety switch. Condensate pan safety overow connection.

HBC

A Participating Corporation in the ARI 440 Certication Program

V25

Fan Coils Horizontal Basic HBC Dimensions Dimensions


HBC Concealed Ceiling
1

TOP VIEW

4 5

5 6 2 1

1-inch typ .

C A

RIGHT HAND UNIT SHOWN


18 9

FRONT VIEW

10

8 2

4 2

1. Motor 2. Motor under protection plate 3. Motor/Blower(s) Assemby

4. Condensate Tray (Double Wall optional) 5. Condensate Copper Connection O.D.


Dimensions (inches) B C 14. 18 17 21 23 27 32 36 40 44 50 54 60 64

6. 7. 8. 9.

Coil Connections (2-Pipe Shown) Installation Hanging Points Coil Supply Air Flange

Model HBC02 HBC03 HBC04 HBC06 HBC08 HBC10 HBC12 A 25 28 34 43 51 61 71

Approx. Weight D (pounds) 43 52 65 76 85 115 118

Dimensions

All dimensions are in inches.

V26

Fan Coils Horizontal Basic HBC Performance Data Performance Data


HBC Concealed Ceiling
2-PIPE SYSTEM 2 Rows Cooling (1) 2 Rows Heating (1) Total Sensible Flow PD Sensible Flow PD MBH MBH GPM ft WG MBH GPM ft WG 4.3 3.6 0.9 0.39 14.2 1.0 0.37 6.3 5.1 1.2 0.85 19.8 1.4 0.77 9.2 7.5 1.8 2.02 28.5 1.9 1.74 12.4 10.5 2.5 1.03 40.6 2.8 1.12 15.8 12.8 3.2 1.86 48.0 3.3 1.78 22.0 17.4 4.4 3.94 65.7 4.5 3.52 25.1 20.4 5.0 2.72 78.0 5.3 2.78 2-PIPE SYSTEM 3 Rows Cooling 3 Rows Heating Sensible Flow PD Sensible Flow PD MBH GPM ft WG MBH GPM ft WG 4.6 1.2 1.16 18.4 1.3 0.92 6.6 1.8 2.50 25.8 1.8 1.92 9.8 2.6 6.01 37.5 2.6 4.41 13.6 3.6 2.78 53.5 3.6 2.46 16.5 4.5 4.81 64.0 4.4 3.90 21.6 5.7 3.97 84.5 5.8 3.67 26.4 7.1 6.60 102.3 7.0 5.75 2-PIPE SYSTEM 4 Rows Cooling 4 Rows Heating Sensible Flow PD Sensible Flow PD MBH GPM ft WG MBH GPM ft WG 5.2 1.5 2.19 20.5 1.4 1.50 7.4 2.1 4.75 28.8 2.0 3.18 10.3 2.8 1.71 41.2 2.8 1.49 15.5 4.4 5.01 60.3 4.1 3.80 17.9 5.0 3.29 70.7 4.8 2.77 24.6 7.0 6.81 95.4 6.5 5.44 29.3 8.2 6.45 110.4 7.8 5.54 2-PIPE SYSTEM 5 Rows Cooling 5 Rows Heating Sensible Flow PD Sensible Flow PD MBH GPM ft WG MBH GPM ft WG 5.4 1.6 3.26 21.1 1.4 1.98 7.3 2.1 1.05 29.3 2.0 0.83 11.0 3.1 2.52 43.4 3.0 1.93 16.4 4.9 7.27 63.0 4.3 4.88 19.0 5.6 4.60 73.7 5.0 3.41 25.4 7.4 5.39 98.9 6.7 4.35 30.9 9.1 8.71 119.3 8.1 6.71 4-PIPE SYSTEM 2 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH GPM ft WG MBH GPM ft WG 3.4 0.8 0.35 8.0 0.5 0.46 4.8 1.2 1.89 11.0 0.8 0.93 7.2 1.8 1.89 15.7 1.1 2.07 10.0 2.4 0.96 23.4 1.6 5.89 12.2 3.0 1.72 27.3 1.9 1.36 16.6 4.2 3.65 36.4 2.5 2.80 19.5 4.8 2.52 44.1 3.0 4.58 4-PIPE SYSTEM 3 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH GPM ft WG MBH GPM ft WG 4.4 1.2 1.07 7.7 0.5 0.44 6.3 1.7 2.33 10.6 0.7 0.89 9.2 2.5 5.47 15.1 1.0 1.98 12.9 3.4 2.55 22.5 1.5 5.57 15.6 4.3 4.42 26.2 1.8 1.42 20.5 5.5 3.63 35.0 2.4 2.81 25.0 6.8 6.02 42.4 2.9 4.65 4-PIPE SYSTEM 4 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH GPM ft WG MBH GPM ft WG 4.9 1.4 1.98 7.4 0.5 0.42 7.0 2.0 4.31 10.1 0.7 0.85 9.7 2.6 1.53 14.4 1.0 1.85 14.6 4.2 4.54 21.6 1.5 5.23 16.8 4.8 2.96 25.1 1.7 1.40 23.2 6.6 6.18 33.5 2.3 2.85 27.5 7.8 5.79 40.6 2.8 4.57

Model HBC02 HBC03 HBC04 HBC06 HBC08 HBC10 HBC12

Model HBC02 HBC03 HBC04 HBC06 HBC08 HBC10 HBC12

Total MBH 4.1 6.0 8.9 11.9 15.3 21.2 24.2

Model HBC02 HBC03 HBC04 HBC06 HBC08 HBC10 HBC12

Total MBH 6.2 8.7 13.2 18.0 22.5 28.6 35.7

Model HBC02 HBC03 HBC04 HBC06 HBC08 HBC10 HBC12

Total MBH 6.0 8.5 12.5 17.2 21.5 27.3 34.0

Model HBC02 HBC03 HBC04 HBC06 HBC08 HBC10 HBC12

Total MBH 7.5 10.7 13.9 21.9 25.1 34.8 41.2

Model HBC02 HBC03 HBC04 HBC06 HBC08 HBC10 HBC12

Total MBH 7.1 10.1 13.1 20.8 23.8 33.1 38.9

Model HBC02 HBC03 HBC04 HBC06 HBC08 HBC10 HBC12

Performance Data

Total MBH 8.2 10.4 15.7 24.3 28.0 36.9 45.6

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high fan speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V27

Fan Coils Horizontal Basic HBC Performance Data


Performance Data (continued)

Nominal Air Volumes cfm (1) Model High Med Low HBC02 246 214 198 HBC03 358 316 439 631 696 883 979 278 364 471 562 674 797 HBC04 551 HBC06 776 HBC08 899 HBC10 1231 HBC12 1477

Air Volume (cfm) Vs External Static Pressure in wg (2) Model 0.05 0.10 0.15 0.20 0.25 0.30 HBC02 230 203 171 HBC03 321 299 235 177 HBC04 HBC06 HBC08 HBC10 HBC12 509 727 864 1178 1405 458 664 758 1095 1360 419 599 715 988 1293 379 525 734 869 1192 288 417 688 751 1090 537 652 1058

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

2. Air volumes at alternative external static pressures are based at high fan speed.

Model HBC02 HBC03 HBC04

Motor Total AMPS 1/20 0.78 1/20 0.78 HP 1/20 0.78

HBC06 1/12 1.37 HBC08 1/12 1.37 HBC10 2 x 1/12 2 x 1.37 HBC12 2 x 1/12 2 x 1.37

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/60Hz.

Performance Data

V28

Fan Coils Horizontal Basic HBP Description


Horizontal Basic Series (continued) Optional Features Include: 3-, 4- And 5-row coils for 2-pipe systems. Single block 2, 3 and 4 rows CW with 1 row re-heat coils for 4-pipe system applications (5 rows max). Single block 2 and 3 rows CW with 2 rows re-heat for 4-pipe system applications (5 rows max). Automatic coil air vents. LH or RH entry pipe connections. Filter option include: - 1-inch high-eciency pleated lters. - 1-inch washable lters. Bottom or rear return air and lter location. Filter supports with slides or clips. Filter removal from LH/ RH, bottom and rear. Motor voltage suitable for 208V, 230V or 277V/1Ph/ 60Hz power supplies. Motor in-line quick disconnect (Not available on bottom return lter). Thermostat and Accessories (refer to Accessories on page V83 for details). Single power supply disconnect switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. HW standby electric heater auto changeover switch. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel. - Double wall construction consisting of outer and inner skins. Condensate pan mastic coating applicable to the inside of the condensate pans for a prolonged life. Condensate pan overow safety switch. Condensate pan safety overow connection.

HBP Concealed Ceiling with Plenum


Factory assembled, horizontal blow-thru ducted HBP fan coils are designed for concealed installations above ceilings with ducted return and discharge air and are suitable for projects such as hotels, motels, condominiums and general commercial applications.

Standard Features Include: Performance ARI Certied to Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. All casing sheet metal components fabricated of 18GA G90 galvanized steel. Return air plenum thermally and acoustically insulated covering the motor(s)/blower(s) assembly to reduce noise dissipation from the unit. High-eciency 2-row coil suitable for a 2-pipe system. Coil manual air vent. 1-Inch thick disposable lter. Multi-speed motor of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blowers of the whisper quite type. Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally protected on the outside. (Consult TITUS for availability). 1-Inch discharge air ange. 1-Inch return air ange Anti-vibration mounts for eld installation.

HBP

A Participating Corporation in the ARI 440 Certication Program

V29

Fan Coils Horizontal Basic HBP Dimensions Dimensions


HBP Concealed Ceiling with Plenum
C 3 7 TOP VIEW 1 2 10

9 14 5

4 5

6 1 1-inch typ. E A 3 B FRONT VIEW

1 RIGHT HAND REAR RETURN UNIT SHOWN SIDE VIEW 23 20 1 1

12 3

10

4 8

1-inch BOTTOM FILTER SLIDE (OPTIONAL)

1. 2. 3. 4.

Return Air Flange Filter Rear Return Motor/Blower(s) Assemby Condensate Tray (Double Wall optional)
Model HBP02 HBP03 HBP04 HBP06 HBP08 HBP10 HBP12 A 25 28 34 43 51 61 71

5. Condensate Copper Connection O.D. 6. Coil Connections (2-Pipe Shown) 7. Hanging Points 8. Coil
Dimensions (inches) C D 18 21 27 36 44 54 64

9. Supply Air Flange 10. Electric Control Panel

Approx. Weight E 18 21 27 36 44 54 64 Filter 20x12x1 23x12x1 29x12x1 38x12x1 46x12x1 56x12x1 66x12x1 (pounds) 63 70 80 99 106 136 150

B 14 17 23 32 40 50 60

Dimensions

All dimensions are in inches.

V30

Fan Coils Horizontal Basic HBP Performance Data Performance Data


HBP Concealed Ceiling with Plenum
2-PIPE SYSTEM 2 Rows Cooling (1) 2 Rows Heating (1) Total Sensible Flow PD Sensible Flow PD MBH MBH gpm ft wg MBH gpm ft wg 4.1 3.3 0.8 0.34 13.2 0.9 0.32 5.9 4.8 1.2 0.77 18.6 1.3 0.69 8.7 7.0 1.7 1.84 26.9 1.8 1.56 11.6 9.7 2.3 0.92 37.6 2.6 0.97 15.0 11.9 3.0 1.66 45.9 3.1 1.58 21.2 16.7 4.2 3.66 62.9 4.3 3.24 24.1 19.4 4.8 2.50 74.3 5.1 2.54 2-PIPE SYSTEM 3 Rows Cooling 3 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.2 1.2 1.00 17.0 1.2 0.78 6.1 1.7 2.25 24.2 1.6 1.70 9.1 2.5 5.39 35.2 2.4 3.92 12.6 3.4 2.44 49.5 3.4 2.12 15.3 4.2 4.26 59.7 4.1 3.41 20.6 5.5 3.67 80.7 5.5 3.36 25.0 6.8 6.02 97.1 6.6 5.20 2-PIPE SYSTEM 4 Rows Cooling 4 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.8 1.4 1.88 18.7 1.3 1.26 6.9 2.0 4.21 26.9 1.8 2.78 9.6 2.6 1.52 38.5 2.6 1.31 14.3 4.1 4.36 55.5 3.8 3.25 16.6 4.7 2.88 65.5 4.5 2.40 23.4 6.6 6.24 90.7 6.2 4.94 27.6 7.8 5.82 100.8 7.4 4.96 2-PIPE SYSTEM 5 Rows Cooling 5 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 5.0 1.5 2.77 19.2 1.3 1.65 6.8 2.0 0.93 27.1 1.9 0.72 10.2 2.9 2.23 40.4 2.8 1.68 15.0 4.5 6.20 57.7 3.9 4.13 17.5 5.2 4.00 68.0 4.6 2.93 24.0 7.0 4.91 93.7 6.4 3.93 29.2 8.6 7.86 112.4 7.7 5.99 4-PIPE SYSTEM 2 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 3.2 0.8 0.31 7.5 0.5 0.40 4.6 1.1 0.72 10.4 0.7 0.84 6.7 1.7 1.72 14.9 1.0 1.89 9.3 2.2 0.85 22.0 1.5 5.24 11.3 2.9 1.52 25.8 1.8 1.22 15.9 4.1 3.39 35.0 2.4 2.60 18.4 4.6 2.28 42.3 2.9 4.22 4-PIPE SYSTEM 3 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.0 1.1 0.93 7.2 0.5 0.38 5.8 1.6 2.07 10.0 0.7 0.80 8.7 2.4 4.92 14.4 1.0 1.80 11.9 3.2 2.22 21.1 1.4 4.94 14.5 4.0 3.91 24.8 1.7 1.27 19.5 5.2 3.34 33.7 2.3 2.60 23.8 6.5 5.53 40.6 2.8 4.28 4-PIPE SYSTEM 4 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.5 1.3 1.70 6.9 0.5 0.36 6.5 1.9 3.81 9.6 0.7 0.76 9.0 2.5 1.35 13.7 0.9 1.68 13.4 3.8 3.91 20.2 1.4 4.63 15.6 4.4 2.58 23.7 1.6 1.25 22.0 6.3 5.64 32.2 2.2 2.63 26.0 7.4 5.23 38.9 2.7 4.19

Model HBP02 HBP03 HBP04 HBP06 HBP08 HBP10 HBP12

Model HBP02 HBP03 HBP04 HBP06 HBP08 HBP10 HBP12

Total MBH 3.9 5.7 8.4 11.2 14.3 20.4 23.0

Model HBP02 HBP03 HBP04 HBP06 HBP08 HBP10 HBP12

Total MBH 5.8 8.4 12.5 16.8 21.1 27.5 34.0

Model HBP02 HBP03 HBP04 HBP06 HBP08 HBP10 HBP12

Total MBH 5.5 8.0 11.9 16.0 20.2 26.2 32.6

Model HBP02 HBP03 HBP04 HBP06 HBP08 HBP10 HBP12

Total MBH 6.9 10.0 13.1 20.4 23.5 33.3 39.0

Model HBP02 HBP03 HBP04 HBP06 HBP08 HBP10 HBP12

Total MBH 6.6 9.5 12.3 19.2 22.2 31.6 37.0

Model HBP02 HBP03 HBP04 HBP06 HBP08 HBP10 HBP12

Performance Data

Total MBH 7.6 9.8 14.7 22.4 26.0 35.2 43.2

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high fan speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V31

Fan Coils Horizontal Basic HBP Performance Data


Performance Data (continued)

Nominal Air Volumes cfm (1) Model High Med Low HBP02 219 187 171 HBP03 326 289 230 HBP04 503 391 310 HBP06 696 567 439 HBP08 813 647 535 HBP10 1150 867 696 HBP12 1370 931 781

Air Volume (cfm) Vs External Static Pressure in wg (2) Model 0.05 0.10 0.15 0.20 0.25 0.30 HBP02 198 182 166 HBP03 289 262 219 150 HBP04 478 441 399 341 245 HBP06 651 613 569 504 401 HBP08 777 722 681 658 628 536 HBP10 1075 1012 939 848 737 616 HBP12 1297 1236 1171 1095 1015 947

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

2. Air volumes at alternative external static pressures are based at high fan speed.

Model HBP02 HBP03 HBP04 HBP06 HBP08 HBP10 HBP12

Motor Total HP AMPS 1/20 0.78 1/20 0.78 1/20 0.78 1/12 1.37 1/12 1.37 2 x 1/12 2 x 1.37 2 x 1/12 2 x 1.37

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/60Hz.

Performance Data

V32

Fan Coils Horizontal Basic HBE Description


Horizontal Basic Series (continued) Optional Features Include: 3-, 4- And 5-row coils for 2-pipe systems. Single block 2, 3 and 4 rows CW with 1 row re-heat coils for 4-pipe system applications (5 rows max). Single block 2 and 3 rows CW with 2 rows re-heat for 4-pipe system applications (5 rows max). LH or RH entry pipe connections. Filter option include: - 1-inch high-eciency pleated lters. - 1-inch washable lters. Motor voltage suitable for 208V, 230V or 277V/1Ph/ 60Hz power supplies. Motor in-line quick disconnect. Thermostat and Accessories (refer to Accessories on page V83 for details). Single power supply disconnect switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. HW standby electric heater auto changeover switch. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel. - Double wall construction consisting of outer and inner skins. Condensate pan mastic coating applicable to the inside of the condensate pans for a prolonged life. Condensate pan overow safety switch. Condensate pan safety overow connection. Aluminum double defection discharge air grilles. Cabinet painted in a powder polyester baked coating in either white or beige colors (Contact TITUS for special colors availability and prices). Return air/access panel fasteners: - Philips head screws. - Tamper proof fasteners. - Quarter turn fasteners.

HBE Exposed Cabinet


Factory assembled, horizontal blowthru HBE fan coils are designed for exposed ceiling installations free blowing into the space suitable for projects such as hotels, motels, condominiums and general commercial applications.

Standard Features Include: Performance ARI Certied to Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. All internal metal components are fabricated of 18GA G90 galvanized steel and the exposed metal casing panels are fabricated of 18GA galvanealed for superior adhesion of the powder paint. Cabinet components are painted with a powder polyester baked coating in white of beige and are acoustically insulated to reduce noise dissipation from the unit. Cabinet liner in -inch dual-density berglass. High-eciency 2-row coil suitable for a 2-pipe system. Coil manual air vent. 1-Inch thick disposable lter. Multi-speed motor of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blowers of the whisper quite type. Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally protected on the outside. (Consult TITUS for availability). Stamped discharge grille. Stamped return air/ access panel grille. Anti-vibration mounts for eld installation.

HBE

A Participating Corporation in the ARI 440 Certication Program

V33

Fan Coils Horizontal Basic HBE Dimensions Dimensions


HBE Exposed Cabinet
TOP VIEW A 1 1 B 1

-inch typ.

3 3 21 19 5 4 6

10

8 FRONT VIEW (W/ STANDARD STAMPED GRILLE)

RIGHT HAND UNIT SHOWN N SIDE VIEW

5 1 4

D 9

13" 4

10

1. Access Panel w/ Return Air Stamped Grille 2. Filter 3. Motor/Blower(s) Assemby

4. Condensate Tray (Double Wall optional) 5. Condensate Connection O.D. 6. Coil Connections (2-Pipe Shown)
Dimensions (inches) C D 14 1511/16 211/16 3113/16 39 49 60

7. Hanging Points 8. Coil 9. Discharge Air Stamped Grille 10. Electric Control Panel
Approx. Weight

Model HBE02 HBE03 HBE04 HBE06 HBE08 HBE10 HBE12 A 29 32 38 47 55 65 75 B 26 29 35 44 52. 62 72

(pounds) Filter 16x12x1 98 24x12x1 112 29x12x1 126 38x12x1 144 46x12x1 165 (2) 28x14x1 196 (2) 31x14x1 221

Dimensions

All dimensions are in inches.

V34

Fan Coils Horizontal Basic HBE Performance Data Performance Data


HBE Exposed Cabinet
2-PIPE SYSTEM 2 Rows Cooling (1) 2 Rows Heating (1) Total Sensible Flow PD Sensible Flow PD MBH MBH gpm ft wg MBH gpm ft wg 3.9 3.2 0.8 0.31 12.5 0.9 0.29 5.8 4.7 1.2 0.74 18.2 1.2 0.66 8.3 6.6 1.7 1.68 25.4 1.7 1.40 11.2 9.3 2.3 0.86 36.5 2.5 0.91 14.9 11.8 3.0 1.64 45.5 3.1 1.55 20.5 16.0 4.1 3.41 60.4 4.1 2.99 23.2 18.6 4.6 2.32 71.3 4.9 2.34 2-PIPE SYSTEM 3 Rows Cooling 3 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.0 1.1 0.92 16.0 1.1 0.71 6.0 1.6 2.16 23.6 1.6 1.62 8.6 2.3 4.85 33.1 2.3 3.49 12.1 3.2 2.29 47.6 3.3 1.97 15.2 4.2 4.19 59.1 4.0 3.35 19.7 5.3 3.40 77.3 5.3 3.09 23.9 6.5 5.57 92.8 6.3 4.77 2-PIPE SYSTEM 4 Rows Cooling 4 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.5 1.3 1.70 17.6 1.2 1.13 6.7 2.0 4.04 26.2 1.8 2.64 9.0 2.5 1.35 36.0 2.5 1.15 13.7 3.9 4.06 53.2 3.6 3.00 16.4 4.7 2.83 64.9 4.4 2.35 22.3 6.4 5.73 86.5 5.9 4.51 26.3 7.5 5.34 100.3 7.0 4.52 2-PIPE SYSTEM 5 Rows Cooling 5 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.7 1.4 2.49 18.0 1.2 1.47 6.6 1.9 0.88 26.4 1.8 0.68 9.5 2.8 1.98 37.6 2.6 1.47 14.4 4.3 5.79 55.1 3.8 3.79 17.3 5.2 3.92 67.2 4.6 2.87 22.9 6.7 4.52 89.1 6.1 3.57 27.7 8.2 7.16 110.6 7.3 5.41 4-PIPE SYSTEM 2 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 3.0 0.7 0.29 8.0 0.5 0.46 4.5 1.1 0.69 11.4 0.8 0.98 6.3 1.6 1.56 15.5 1.1 2.02 8.9 2.2 0.80 22.7 1.6 5.55 11.3 2.8 1.50 28.0 1.9 1.40 15.2 3.9 3.14 36.6 2.5 2.77 17.7 4.4 2.12 43.6 3.0 4.43 4-PIPE SYSTEM 3 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 3.8 1.1 0.84 7.6 0.5 0.43 5.7 1.6 1.98 10.9 0.7 0.92 8.1 2.2 4.43 14.8 1.0 1.90 11.4 3.1 2.08 21.7 1.5 5.19 14.4 4.0 3.85 26.8 1.8 1.43 18.6 5.0 3.12 35.0 2.4 2.74 22.7 6.2 5.11 41.8 2.9 4.42 4-PIPE SYSTEM 4 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.2 1.2 1.54 7.3 0.5 0.40 6.3 1.9 3.65 10.3 0.7 0.86 8.5 2.3 1.22 14.1 1.0 1.75 12.9 3.7 3.65 20.7 1.4 4.83 15.4 4.4 2.53 25.5 1.7 1.38 20.9 6.0 5.18 33.4 2.3 2.72 24.7 7.1 4.79 39.8 2.7 4.27

Model HBE02 HBE03 HBE04 HBE06 HBE08 HBE10 HBE12

Model HBE02 HBE03 HBE04 HBE06 HBE08 HBE10 HBE12

Total MBH 3.7 5.6 8.0 10.8 14.2 19.6 22.1

Model HBE02 HBE03 HBE04 HBE06 HBE08 HBE10 HBE12

Total MBH 5.5 8.2 11.8 16.2 20.9 26.4 32.7

Model HBE02 HBE03 HBE04 HBE06 HBE08 HBE10 HBE12

Total MBH 5.3 7.8 11.2 15.5 20.0 25.3 31.2

Model HBE02 HBE03 HBE04 HBE06 HBE08 HBE10 HBE12

Total MBH 6.6 9.8 12.3 19.6 23.3 31.9 37.3

Model HBE02 HBE03 HBE04 HBE06 HBE08 HBE10 HBE12

Total MBH 6.2 9.3 11.7 18.6 22.0 30.2 35.3

Model HBE02 HBE03 HBE04 HBE06 HBE08 HBE10 HBE12

Performance Data

Total MBH 7.1 9.5 13.8 21.5 25.7 33.7 41.2

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high fan speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V35

Fan Coils Horizontal Basic HBE Performance Data


Performance Data (continued)

Nominal Air Volumes cfm (1) Model High Med Low HBE02 203 171 155 HBE03 316 278 219 HBE04 460 342 262 HBE06 658 535 396 HBE08 803 621 487 HBE10 1081 803 621 HBE12 1284 893 717

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

Model HBE02 HBE03 HBE04 HBE06 HBE08 HBE10 HBE12

Motor Total HP AMPS 1/20 0.78 1/20 0.78 1/20 0.78 1/12 1.37 1/12 1.37 2 x 1/12 2 x 1.37 2 x 1/12 2 x 1.37

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/60Hz.

Performance Data

V36

Fan Coils Horizontal Basic HBR Description


Horizontal Basic Series (continued) Optional Features Include: 3-, 4- And 5-row coils for 2-pipe systems. Single block 2, 3 and 4 rows CW with 1 row re-heat coils for 4-pipe system applications (5 rows max). Single block 2 and 3 rows CW with 2 rows re-heat for 4-pipe system applications (5 rows max). LH or RH entry pipe connections. Filter option include: - 1-inch high-eciency pleated lters. - 1-inch washable lters. Bottom or rear return air and lter location. Motor voltage suitable for 208V, 230V or 277V/1Ph/ 60Hz power supplies. Motor in-line quick disconnect (Available with rear return air). Thermostat and Accessories (refer to Accessories on page V83 for details). Single power supply disconnect switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. HW standby electric heater auto changeover switch. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel. - Double wall construction consisting of outer and inner skins. Condensate pan mastic coating applicable to the inside of the condensate pans for a prolonged life. Condensate pan overow safety switch. Condensate pan safety overow connection. Bottom or rear return air. Fascia panel painted in a powder polyester baked coating in either white or beige colors (Contact TITUS for special colors availability and prices). Return air/access panel fasteners: - Philips head screws. - Tamper proof fasteners. - Quarter turn fasteners.

HBR Recessed Cabinet


Factory assembled, horizontal blowthru ducted HBR fan coils are designed for over ceiling installations with ducted discharge air suitable for projects such as hotels, motels, condominiums and general commercial applications.

Standard Features Include: Performance certied to ARI Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. All casing sheet metal components fabricated of 18GA G90 galvanized steel. Fascia panels are fabricated of 18GA galvannealed for superior adhesion of the powder paint. Telescopic ceiling fascia panel with adjustment up to 3 inches. Cabinet liner in -inch dual-density berglass. High-eciency 2-row coil suitable for a 2-pipe system. Coil manual air vent. 1-Inch thick disposable lter. Multi-speed motor of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blowers of the whisper quite type. Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally protected on the outside (Consult TITUS for availability). -inch discharge air ange. Stamped return air/ access panel grille. Anti-vibration mounts for eld installation.

HBR

A Participating Corporation in the ARI 440 Certication Program

V37

Fan Coils Horizontal Basic HBR Dimensions Dimensions


HBR Recessed Cabinet
TOP VIEW 1 B 3 -inch typ. 1 5 19 4 4 6

7 1 4 FRONT VIEW C

RIGHT HAND UNIT SHOWN SIDE VIEW 1-inch typ. 21 1

6 -inch Flange 11 1

12 13 10 Adjust 0 to 3 inches A 24 2

1. Access Panel w/ Return Air Stamped Grille 2. Filter 3. Motor/Blower(s) Assemby

4. Condensate Tray (Double Wall optional) 5. Condensate Connection O.D. 6. Coil Connections (2-Pipe Shown) 7. Hanging Points
Dimensions (inches) C D 14 17 23 32 40 50 60

8. Coil 9. Supply Air Flange 10. Electric Control Panel 11. Telescopic Return Air / Access Panel
Approx. Weight

Model HBR02 HBR03 HBR04 HBR06 HBR08 HBR10 HBR12 A 32 35 41 50 58 68 78 B 31 34 40 49 57 67 77

(pounds) Filter 24x12x1 100 28x12x1 115 28x12x1 130 42x12x1 145 50x12x1 170 (2) 30x12x1 200 (2) 34x12x1 225

Dimensions

All dimensions are in inches.

V38

Fan Coils Horizontal Basic HBR Performance Data Performance Data


HBR Recessed Cabinet
2-PIPE SYSTEM 2 Rows Cooling (1) 2 Rows Heating (1) Total Sensible Flow PD Sensible Flow PD MBH MBH gpm ft wg MBH gpm ft wg 4.2 3.5 0.8 0.37 13.8 0.9 0.35 5.8 4.7 1.2 0.74 18.2 1.2 0.66 8.0 6.4 1.6 1.57 24.4 1.7 1.30 11.2 9.3 2.2 0.86 36.3 2.5 0.90 14.6 11.6 2.9 1.59 44.7 3.1 1.50 19.3 14.9 3.9 3.05 56.6 3.9 2.64 22.0 17.5 4.4 2.10 67.3 4.6 2.09 2-PIPE SYSTEM 3 Rows Cooling 3 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.5 1.2 1.09 17.9 1.2 0.86 6.0 1.6 2.16 23.6 1.6 1.62 8.2 2.3 4.50 31.7 2.2 3.22 12.0 3.2 2.26 47.4 3.2 1.95 14.9 4.1 4.06 58.0 4.0 3.23 18.3 5.0 3.01 72.0 4.9 2.70 22.4 6.2 5.01 87.3 6.0 4.24 2-PIPE SYSTEM 4 Rows Cooling 4 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 5.0 1.5 2.06 19.8 1.4 1.40 6.7 2.0 4.03 26.2 1.8 2.64 8.6 2.4 1.25 34.4 2.4 1.06 13.6 3.9 4.02 53.0 3.6 2.96 16.1 4.6 2.73 63.5 4.3 2.26 20.6 5.9 5.00 80.2 5.5 3.90 24.6 7.0 4.76 96.0 6.6 3.98 2-PIPE SYSTEM 5 Rows Cooling 5 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 5.3 1.6 3.07 20.3 1.4 1.85 6.6 1.9 0.89 26.4 1.8 0.68 9.1 2.7 1.83 35.8 2.4 1.34 14.3 4.3 5.69 54.8 3.7 3.74 16.9 5.0 3.76 65.7 4.5 2.75 22.9 6.7 4.52 89.1 6.1 3.57 25.8 7.7 6.34 99.3 6.8 4.73 4-PIPE SYSTEM 2 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 3.3 0.8 0.34 7.8 0.5 0.43 4.5 1.1 0.69 10.2 0.7 0.81 6.1 1.5 1.46 13.7 0.9 1.61 8.8 2.1 0.79 21.2 1.4 5.55 11.1 2.8 1.46 25.1 1.7 1.16 14.2 3.7 2.81 31.9 2.2 2.18 16.7 4.2 1.93 38.7 2.6 3.58 4-PIPE SYSTEM 3 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.3 1.2 1.02 7.5 0.5 0.41 5.7 1.6 1.98 9.8 0.7 0.77 7.8 2.2 4.15 13.2 0.9 1.53 11.4 3.1 2.08 20.4 1.4 4.60 14.1 3.9 3.72 24.1 1.6 1.21 17.4 4.7 2.76 30.7 2.1 2.17 21.3 5.9 4.59 37.2 2.5 3.61 4-PIPE SYSTEM 4 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.7 1.4 187.00 7.2 0.5 0.39 6.3 1.9 3.65 9.4 0.6 0.73 8.1 2.2 1.13 12.6 0.9 1.42 12.8 3.7 3.62 19.4 1.3 4.31 15.1 4.3 2.45 23.1 1.6 1.18 19.4 5.6 4.54 29.3 2.0 2.18 23.0 6.6 4.26 35.5 2.4 3.51

Model HBR02 HBR03 HBR04 HBR06 HBR08 HBR10 HBR12

Model HBR02 HBR03 HBR04 HBR06 HBR08 HBR10 HBR12

Total MBH 4.1 5.6 7.7 10.8 14.0 18.5 21.1

Model HBR02 HBR03 HBR04 HBR06 HBR08 HBR10 HBR12

Total MBH 6.0 8.2 11.3 16.2 20.6 24.8 30.9

Model HBR02 HBR03 HBR04 HBR06 HBR08 HBR10 HBR12

Total MBH 5.8 7.8 10.8 15.4 19.7 23.7 29.6

Model HBR02 HBR03 HBR04 HBR06 HBR08 HBR10 HBR12

Total MBH 7.3 9.8 11.8 19.5 22.9 29.7 35.2

Model HBR02 HBR03 HBR04 HBR06 HBR08 HBR10 HBR12

Total MBH 6.9 9.3 11.2 18.5 21.6 28.2 33.3

Model HBR02 HBR03 HBR04 HBR06 HBR08 HBR10 HBR12

Performance Data

Total MBH 8.0 9.6 13.3 21.4 25.2 33.7 38.7

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high fan speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V39

Fan Coils Horizontal Basic HBR Performance Data


Performance Data (continued)

Nominal Air Volumes cfm (1) Model High Med Low HBR02 220 195 170 HBR03 295 245 190 HBR04 405 290 210 HBR06 610 440 300 HBR08 730 575 420 HBR10 915 805 530 HBR12 1100 870 600

Air Volume (cfm) Vs External Static Pressure in wg (2) Model 0.05 0.10 0.15 0.20 0.25 0.30 HBR02 198 150 102 HBR03 278 241 193 166 HBR04 401 363 337 310 235 HBR06 602 546 508 473 380 HBR08 690 624 578 542 497 419 HBR10 911 840 769 693 602 475 HBR12 1106 1044 986 927 859 775

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

2. Air volumes at alternative external static pressures are based at high fan speed.

Model HBE02 HBE03 HBE04 HBE06 HBE08 HBE10 HBE12

Motor Total HP AMPS 1/20 0.78 1/20 0.78 1/20 0.78 1/12 1.37 1/12 1.37 2 x 1/12 2 x 1.37 2 x 1/12 2 x 1.37

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/60Hz.

Performance Data

V40

Fan Coils Horizontal Basic Specications Suggested Specications


Fan Coils
Horizontal Basic Units Standard Congurations 1. Furnish and install TITUS models HBC, HBP, HBE and HBR horizontal basic fan coils of sizes and capacities shown on the plans to meet prevailing cooling and heating requirements. 2. Fan coils shall be performance certied to ARI Standard 440. Units shall be wired in compliance with ANSI/UL 1995 Standard and listed with ETL. 3. Fan coils shall be sound tested in accordance with ARI Standard 260 for ducted units and ARI Standard 350 for non-ducted units. Manufacturer shall provide these dB ratings on request for each model specied. 4. Unit casing shall be 18-gauge, zinc coated, phosphate treated, galvanized steel. Painted sheet metal components (HBE and R units only) components shall be 18-gauge galvanealed sheet metal. 5. Painted panels (HBE and HBR units only) shall be painted with a polyester powder coating, electrostatically applied, oven baked to 400F for 10 minutes in beige or white tones. 6. High-eciency, 2-row coil shall be suitable for a 2-pipe system. Coils shall be manufactured with aluminum ns mechanically bonded to seamless copper tubes. The copper tubes shall be -inch OD with a wall thickness of 0.014inch which comply with ASTM B-75. The ns shall be waved with ripple hedges for superior eciency with a thickness of 0.0045-inch and spaced at 10 fpi. All coils shall be leak tested with 100% helium to ensure a leak free coil. All coils shall be shipped with a safety air pressure of 100 - 125 psi to guarantee a leak free arrival at the nal destination. 7. Unit pipe entry location shall be in accordance with the project schedule. 8. Coils shall be installed with manual Schrader type air vents with a sealing cap and be located at the highest point of the coil. The cap shall have a dual purpose, to seal any potential water leakage in the eventuality of Schrader valve failure and as a service tool for the extraction/insertion of the internal Schrader valve. 9. Standard lters (HBP, HBR and HBE only) shall be 1-inch nominal thickness of the disposable type with a one-piece moisture resistant chipboard frame to eliminate corner separations. The spun glass ltering media shall be bonded with a resinous agent providing rigidity and resistance to media compression and meets UL class 2. 10. Cabinets (HBP, HBR and HBE only) shall be lined with -inch dual-density berglass with a density of 1.5lbs/ft3 and 4.0lbs/ft3 for the face meeting NFPA 90A and 90B (appliances), NFPA 255, UL 181, UL723 and ASTM E84. 11. Motors shall be multi-speed of the permanent split capacitor type (PSC) and be directly coupled to the centrifugal fan blower. Motor shall be suitable for a power supply of 115V/1Ph/60Hz and shall be internally protected with an automatic thermal overload. Motor shaft shall be supported by sleeve bearings of the permanently lubricated type for the full life expectancy of the motor. All motors shall be directly mounted to the fan deck and be isolated from the unit casing by two resilient antivibration mounts. 12. Direct-driven fan(s) shall be of the whisper quite type, double width, double inlet (DWDI) forward curved statically and dynamically balanced at the factory. The fan wheel and casing shall be constructed of galvanized steel. 13. Electric components shall be wired to a single control panel for single point power supply. Wiring exposed to the outside of the units shall be installed in conduits to meet UL 1995 safety requirements. 14. Condensate pans shall be singlewall 18-gauge G90 galvanized steel welded at the corners, thermally protected on the outside with re and smoke rated inch high-density insulation to prevent condensation. The factory installed -inch OD sweat copper condensate connection shall be located at the lowest point of the condensate pan to ensure all water drains from the condensate pan (Consult TITUS for availability). 15. Discharge air ange (HBC and HBP units only) shall be 1-inch or -inch (HBR unit only) to facilitate the connection of eld ducts. 16. Return air anges (HBP and HBR units only) shall be 1-inch to facilitate the connection of eld ducts. 17. Return air grilles/access panels (HBR and HBE only) shall be of the stamped louvered type and be removable for better access on the eld. 18. Four (4) anti-vibration rubber mountings shall be provided for eld installation in order to isolate any cabinet vibrations from the building structure.

Specications

V41

Fan Coils Horizontal Basic Specications


Suggested Specications (continued) 2. A motor in-line quick disconnect shall be installed to facilitate the removal/replacement of motor (HBP and HBR). Thermostat and Accessories Refer to Accessories on page V83. Disconnect switch and Fuses Units shall be wired for single power with supply with a disconnect switch and fuse(s) to match the unit full minimum circuit ampacity (MCA) in line with UL 1995. 2-Pipe Heat/Cool Auto Changeover Switch A mechanical changeover switch shall be supplied on 2-pipe systems for automatically change over of the operation of the thermostat for summer and winter modes. Electric Heater and Accessories 1. Electric heaters shall be of the wound type mounted in a metal frame and supported by ceramic rings and terminals. Electric heaters shall installed on the blower and coil discharge side for better heat dissipation and shall include an automatic reset high limit cut-out and contactor. 2. 2-pipe standby electric heating - heaters shall be installed and pre-wired as standby heating in the eventuality of a failure of the primary hot water (HW) system. A changeover sensor shall be installed in each unit and the changeover between the failed hot water system and the standby electric heater shall be automatic. Chilled and Hot Water Valve Controls Refer to Accessories on page V83. Condensate Pan and Accessories 1. Condensate pan shall be single wall manufactured in 20-gauge 304 stainless steel and shall be thermally protected on the outside with re and smoke rated -inch high-density insulation to prevent condensation. The factory installed -inch OD sweat copper condensate connection shall be located at the lowest point of the condensate pan to ensure that all water is drained from the condensate pan (Consult TITUS for availability), or 2. Condensate pan shall be double wall construction consisting of an outer and inner skin. The outer skin shall be manufactured of 18-gauge G90 galvanized sheet metal wrapped around the inner skin with 1-inch thermal insulation between both skins to prevent condensation. The inner skin of the double wall condensate pan shall be of 18-gague G90 galvanized sheet metal, or 3. Condensate pan shall be double wall construction consisting of an outer and inner skin. The outer skin shall be manufactured of 18-gauge G90 galvanized sheet metal wrapped around the inner skin with 1.00 thermal insulation between both skins to prevent the formation of condensation. The inner skin of the double wall condensate pan shall be of 20-gauge 304 stainless steel galvanized sheet metal. 4. An automatic safety overow switch shall be installed in the condensate pan and shall prevent the operation of the unit electric system if an overow status is detected. 5. A mastic coating shall be applied to the inside of the condensate pan for a prolonged life. Discharge Air Grilles and Accessories (HBE only) 1. Discharge air grilles shall be double-deection made of aluminum and painted white fro white painted cabinet units or aluminum for beige painted cabinets. 2. Special discharge air grilles colors shall be______________. (Contact TITUS for color range availability and price). Return Air/Access Panel and Accessories (HBR and HBE only) 1. Return air/access panel security fasteners shall be tamperproof, which require a specialist tool to access the units, or 2. Return air/access panel security fasteners shall be of the quarter turn type, to facilitate the removal of the access panel.

Fan Coil Accessories


Horizontal Basic Units Optional Conguration Cooling and Heating Coil 1. Shall be high-eciency 3-, 4- and 5-row coils suitable for 2-pipe systems, or 2. High-eciency single block with 2, 3 and 4 rows chilled water (CW) with 1-row re-heat coil suitable for 4-pipe system applications, or 3. High-eciency single block with 2, 3-rows chilled water (CW) with 2row re-heat coil suitable for 4-pipe system applications. 4. Coils shall be installed with an automatic air vent capable of operation in chilled or hot water systems to a maximum of 125 psi (HBC or HBP units only). Filter 1. Filter shall be 1-inch pleated lter with an average atmospheric dust spot eciency range of 20 - 30% per ASHRAE Standard 52.1 test method, or 2. Filter shall be 1-inch washable lter consisting of synthetic bers coated with a special resin, then baked together at a high temperature resulting in a tough and springy, thoroughly bonded, nearly rigid air ltration media. Washable lters shall have a longer service life; better structural integrity as well as being completely odor free. 3. A spare set of lters shall be available for replacement after the commissioning of the unit and prior to the handover of the project. Cabinet Insulation Cabinet liners shall be 1-inch dualdensity berglass with a density of 1.5lbs/ft3 and 4.0lbs/ft3 for the face meeting NFPA 90A and 90B (appliances) and NFPA 255 with less than 25 ame and less than 50 smoke spread, UL 181, UL723 and ASTM E84. Motor and Motor Accessories 1. Motors shall be suitable for 115V/1Ph/60Hz or 208V/1Ph/60Hz or 230V/1Ph/60Hz or 277V/1Ph/ 60Hz power supplies (delete as applicable).

Specications

V42

Fan Coils Vertical Basic VBC Description

Vertical Basic Series


VBC Concealed Floor
Factory assembled, vertical blow-thru, ducted VBC fan coils are designed for concealed installations inside a closet or furred-in under a window and ducted, for projects such as public buildings, hotels, schools, hospitals and general commercial applications.

Standard Features Include: Performance ARI Certied to Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. All sheet metal components fabricated of 18GA G90 galvanized steel. Cabinet liner in -inch dual-density berglass. High-eciency 2-row coil suitable for a 2-pipe system. Coil manual air vent. Easily removal 1-inch thick disposable lter. Multi-speed motor of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blowers of the whisper quite type. Three speed Motor switch. Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally insulated on the outside. (Consult TITUS for availability). Single wall auxiliary condensate pan thermally insulates on the outside. Top discharge air ange. Optional Features Include: 3-, 4- And 5-row coils for 2-pipe systems. Single block 2, 3 and 4 rows CW with 1 row re-heat coils for 4-pipe system applications (5 rows max). Single block 2 and 3 rows CW with 2 rows re-heat for 4-pipe system applications (5 rows max). Automatic coil air vents LH or RH pipe entry connections. Filter option include: - 1-inch high-eciency pleated lters. - 1-inch washable lters.

Motor voltage suitable for 208V, 230V or 277V/1Ph/ 60Hz power supplies. Motor in-line quick disconnect. Thermostat and Accessories (refer to Accessories on page V83 for details). Single power supplies disconnect switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. HW standby electric heater auto changeover switch. Fresh air opening. Fresh air with manual or auto dampers. Fresh air freeze protection. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel. - Double wall construction consisting of outer and inner skins. Condensate pan Mastic coating applied to the inside of the condensate pans for a prolonged life. Single wall auxiliary condensate pan manufactured in 20GA 304 Stainless Steel. Auxiliary condensate pan mastic coating applied to the inside of the condensate pans for a prolonged life. Auxiliary condensate pan overow safety switch. Remote discharge air grilles: - Stamped with access doors - Aluminum double defection - Deluxe aluminum double deection grilles (Contact TITUS for availability). - Linear bar aluminum grilles (Contact TITUS for availability). Special discharge air grille colors (Contact TITUS for color range availability and price). Remote stamped return air/access panel with lter access door.

VBC

A Participating Corporation in the ARI 440 Certication Program

V43

Fan Coils Vertical Basic VBC Dimensions Dimensions


VBC Concealed Floor
TOP VIEW A 6 43/16 C 4 57/16

1 FRONT VIEW 1 2 3

RIGHT HAND UNIT SHOWN SIDE VIEW 5 2

25 8

4 5

2 F E B 9

7 55/16

8 10

63/16

Note: Right hand unit shown. 1. 2. 3. 4. Supply Air Flange = C Coil Coil Connections (2-Pipe Shown) Motor/Blower(s) Assemby 5. 6. 7. 8. Auxiliary Condensate Tray Condensate Connection O.D. Filter Control box
Dimensions (inches) D E 12 12 12 24 24 36 36

9. Fresh air damper opening (optional) = 2 x E

Model VBC02 VBC03 VBC04 VBC06 VBC08 VBC10 VBC12 A 31 34 38 49 57 67 77 B 19 22 26 37 45 55 65 C 11 14 18 29 37 47 57

Approx. Weight F 3 5 7 6 10 9 14 (pounds) Filter 17x10x1 63 20x10x1 70 24x10x1 80 35x10x1 99 43x10x1 106 2(26)x10x1 136 2(31)x10x1 150

Dimensions

All dimensions are in inches.

V44

Fan Coils Vertical Basic VBC Performance Data Performance Data


VBC Concealed Floor
2-PIPE SYSTEM 2 Rows Cooling (1) 2 Rows Heating (1) Total Sensible Flow PD Sensible Flow PD MBH MBH gpm ft wg MBH gpm ft wg 4.1 3.5 0.8 0.33 13.8 0.9 0.34 5.6 4.6 1.1 0.66 18.0 1.2 0.62 7.9 6.3 1.6 1.47 24.4 1.7 1.26 11.1 9.3 2.2 0.83 36.5 2.5 0.90 14.4 11.5 2.9 1.52 44.3 3.0 1.45 19.1 14.8 3.8 2.95 56.5 3.9 2.60 21.9 17.5 4.4 2.06 67.8 4.6 2.10 2-PIPE SYSTEM 3 Rows Cooling 3 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.5 1.2 1.01 18.1 1.2 0.84 5.9 1.6 1.99 23.4 1.6 1.55 8.2 2.2 4.26 31.8 2.2 3.14 12.1 3.2 2.21 47.8 3.3 1.95 14.8 4.0 3.89 57.6 3.9 3.14 18.2 4.9 2.93 71.9 4.9 2.67 22.6 6.2 4.97 88.0 6.0 4.27 2-PIPE SYSTEM 4 Rows Cooling 4 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 5.1 1.4 1.97 20.1 1.4 1.39 6.7 1.9 3.78 26.0 1.8 2.55 8.6 2.3 1.19 34.7 2.4 1.05 13.7 3.9 3.95 53.5 3.7 2.97 16.6 4.8 6.77 64.0 4.4 4.75 20.6 5.9 4.94 80.2 5.5 3.87 25.4 7.4 8.31 97.9 6.7 6.19 2-PIPE SYSTEM 5 Rows Cooling 5 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 5.4 1.6 2.97 20.8 1.4 1.86 7.1 2.1 5.64 27.0 1.8 3.40 9.1 2.6 1.77 36.2 2.5 1.34 14.4 4.3 5.66 55.6 3.8 3.78 17.4 5.3 9.56 66.1 4.5 6.00 21.7 6.5 6.78 82.9 5.7 4.72 26.7 8.1 11.30 101.2 6.9 7.58 4-PIPE SYSTEM 2 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 3.3 0.8 0.31 7.7 0.5 0.41 4.4 1.1 0.63 10.0 0.7 0.76 6.1 1.5 1.36 13.6 0.9 1.53 8.9 2.1 0.76 21.2 1.4 4.76 10.9 2.7 1.39 25.8 1.8 8.21 14.2 3.7 2.76 32.8 2.2 15.46 16.7 4.2 1.91 40.0 2.7 26.00 4-PIPE SYSTEM 3 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.3 1.1 0.94 7.4 0.5 0.39 5.6 1.5 1.81 9.7 0.7 0.72 7.8 2.1 3.90 13.0 0.9 1.46 11.5 3.1 2.03 20.4 1.4 4.50 14.0 3.9 3.57 24.8 1.7 7.73 17.3 4.7 2.69 31.4 2.1 14.44 21.4 5.9 4.56 38.3 2.6 24.40 4-PIPE SYSTEM 4 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.8 1.4 1.78 7.1 0.5 0.37 6.3 1.8 3.39 9.2 0.6 0.68 8.1 2.2 1.07 12.4 0.9 1.36 12.9 3.7 3.57 19.4 1.3 4.22 15.6 4.6 6.11 23.6 1.6 7.21 19.4 5.6 4.43 30.0 2.0 13.43 23.9 7.0 7.42 36.6 2.5 22.65

Model VBC02 VBC03 VBC04 VBC06 VBC08 VBC10 VBC12

Model VBC02 VBC03 VBC04 VBC06 VBC08 VBC10 VBC12

Total MBH 3.9 5.4 7.6 10.7 13.7 18.4 21.0

Model VBC02 VBC03 VBC04 VBC06 VBC08 VBC10 VBC12

Total MBH 5.9 8.0 11.2 16.1 20.3 24.6 31.0

Model VBC02 VBC03 VBC04 VBC06 VBC08 VBC10 VBC12

Total MBH 5.7 7.6 10.7 15.4 19.4 23.5 29.6

Model VBC02 VBC03 VBC04 VBC06 VBC08 VBC10 VBC12

Total MBH 7.2 9.6 11.7 19.5 24.2 29.7 37.0

Model VBC02 VBC03 VBC04 VBC06 VBC08 VBC10 VBC12

Total MBH 6.9 9.1 11.1 18.5 22.9 28.0 34.9

Model VBC02 VBC03 VBC04 VBC06 VBC08 VBC10 VBC12

Performance Data

Total MBH 8.0 10.6 13.2 21.5 26.4 32.5 40.4

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high fan speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V45

Fan Coils Vertical Basic VBC Performance Data


Performance Data (continued)

Nominal Air Volumes cfm (1) Model High Med Low VBC02 246 214 187 VBC03 321 268 209 VBC04 444 326 241 VBC06 669 482 332 VBC08 781 626 471 VBC10 984 872 583 VBC12 1198 952 669

Air Volume (cfm) Vs External Static Pressure in wg (2) Model 0.05 0.10 0.15 0.20 0.25 0.30 VBC02 198 150 102 VBC03 278 241 193 166 VBC04 402 363 338 310 235 VBC06 602 545 509 473 380 VBC08 690 624 578 542 497 419 VBC10 912 839 769 693 601 476 VBC12 1107 1043 987 928 858 775

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

2. Air volumes at alternative external static pressures are based at high fan speed.

Model VBC02 VBC03 VBC04 VBC06 VBC08 VBC10 VBC12

Motor Total HP AMPS 1/30 0.50 1/30 0.50 1/20 0.78 1/20 0.78 1/20 0.78 2 x 1/20 2 x 0.78 2 x 1/20 2 x 0.78

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/60Hz.

Performance Data

V46

Fan Coils Vertical Basic VBF Description


Vertical Basic Series (continued) Condensate pan mastic coating applicable to the inside of the condensate pans for a prolonged life. Single wall auxiliary condensate pan manufactured in 20GA 304 Stainless Steel. Auxiliary condensate pan mastic coating applicable to the inside of the condensate pans for a prolonged life. Auxiliary condensate pan overow safety switch. Discharge air grilles: - Aluminum double defection - Deluxe aluminum double deection grilles (Contact TITUS for availability). - Linear bar aluminum grilles (Contact TITUS for availability). Special discharge air grille colors (Contact TITUS for color selection and price). Special cabinet paints. (Contact TITUS for special colors availability and prices). Heavy duty access panel in 16GA painted steel Return air/access panel fasteners: - Philips head screws. - Tamper proof fasteners. - Quarter turn fasteners. Access doors keyed locks.

VBF Flat Top Cabinet


Factory assembled, vertical blow-thru, slim and attractively styled VBF fan coils are designed for exposed oor standing applications such as public buildings, hotels, schools, hospitals and general commercial applications. Standard Features Include: Performance ARI Certied to Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. All internal sheet metal components are fabricated of 18GA G90 galvanized steel and exposed metal casing panels fabricated of 18GA galvanealed for superior adhesion of the powder paint. Cabinet components are painted with a powder polyester baked coating in white of beige and are acoustically insulated to reduce noise dissipation from the unit. Cabinet liner in -inch dual-density berglass. High-eciency 2-row coil suitable for a 2-pipe system. Coil manual air vent. Easily removal 1-inch thick disposable lter. Multi-speed motor of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blowers of the whisper quite type. Three speed motor switch Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally insulated on the outside (Consult TITUS for availability).

Single wall auxiliary condensate pan thermally insulated on the outside. Flat stamped discharge top grille. Electric controls and valve package access doors. Optional Features Include: 3-, 4- And 5-row coils for 2-pipe systems. Single block 2, 3 and 4 rows CW with 1 row re-heat coils for 4-pipe system applications (5 rows max). Single block 2 and 3 rows CW with 2 rows re-heat for 4-pipe system applications (5 rows max). Automatic coil air vents. LH or RH pipe connections entry. Filter option include: - 1-inch high-eciency pleated lters. - 1-inch washable lters. Motor voltage suitable for 208V, 230V or 277V/1Ph/ 60Hz power supplies. Motor in-line quick disconnect. Thermostat and Accessories (refer to Accessories on page V83 for details). Single power supply disconnect switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. HW standby electric heater auto changeover switch. Fresh air opening. Fresh air with manual or auto dampers. Fresh air freeze protection. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel. - Double wall construction consisting of outer and inner skins.

VBF

A Participating Corporation in the ARI 440 Certication Program

V47

Fan Coils Vertical Basic VBF Dimensions Dimensions


VBF Flat Top Cabinet
TOP VIEW

2 SIDE VIEW 1 FRONT VIEW 4 5 10

6 8 7 2511/16

2 D C B A 9 2

3 2

Note: Right hand unit shown. 1. 2. 3. 4. Control Box Stamped Supply Air Grille Control Access Door Coil 5. 6. 7. 8. Coil Connections (2-Pipe Shown) Motor/Blower(s) Assemby Condensate Connection O.D. Filter 9. Fresh air damper opening (optional) = 2 x C

Model VBF02 VBF03 VBF04 VBF06 VBF08 VBF10 VBF12 A 34 37 41 52 60 70 80 B 18 21 25 36 44 54 64

Dimensions (inches) C D 12 11 12 12 12 14 24 14 24 18 36 17 36 22

Approx. Weight (pounds) Filter 17x10x1 95 20x10x1 104 24x10x1 106 35x10x1 128 43x10x1 146 (2)26x10x1 178 (2)31x10x1 186

Dimensions

All dimensions are in inches.

V48

Fan Coils Vertical Basic VBF Performance Data Performance Data


VBF Flat Top Cabinet
2-PIPE SYSTEM 2 Rows Cooling (1) 2 Rows Heating (1) Total Sensible Flow PD Sensible Flow PD MBH MBH gpm ft wg MBH gpm ft wg 4.0 3.4 0.8 0.31 13.4 0.9 0.32 5.5 4.5 1.1 0.65 17.8 1.2 0.61 7.8 6.2 1.6 1.43 23.9 1.6 1.22 11.0 9.1 2.2 0.80 35.9 2.4 0.87 14.4 11.5 2.9 1.52 44.3 3.0 1.45 19.0 14.8 3.8 2.94 56.2 3.8 2.58 21.8 17.3 4.3 2.04 66.9 4.6 2.05 2-PIPE SYSTEM 3 Rows Cooling 3 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.3 1.2 0.96 17.5 1.2 0.79 5.8 1.6 1.95 23.1 1.6 1.51 8.0 2.2 4.14 31.2 2.1 3.03 11.9 3.2 2.15 46.9 3.2 1.88 14.8 4.1 3.89 57.5 3.9 3.14 18.2 4.9 2.92 71.6 4.9 2.64 22.2 6.1 4.88 86.8 5.9 4.16 2-PIPE SYSTEM 4 Rows Cooling 4 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.9 1.4 1.86 19.4 1.3 1.30 6.6 1.9 3.70 25.8 1.8 2.48 8.4 2.3 1.16 34.0 2.3 1.01 13.4 3.8 3.84 52.4 3.6 2.87 16.6 4.8 6.79 64.0 4.4 4.75 20.5 5.9 4.91 79.8 5.4 3.83 25.1 7.3 8.13 96.5 6.6 6.03 2-PIPE SYSTEM 5 Rows Cooling 5 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 5.1 1.5 2.79 20.0 1.4 1.73 7.0 2.1 5.51 26.7 1.8 3.31 9.0 2.6 1.71 35.4 2.4 1.29 14.2 4.2 5.47 54.4 3.7 3.63 17.4 5.3 9.56 66.1 4.5 6.00 21.5 6.5 6.73 82.5 5.6 4.67 26.3 7.9 11.00 99.7 6.8 7.36 4-PIPE SYSTEM 2 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 3.2 0.8 0.29 8.5 0.6 0.49 4.3 1.1 0.61 11.0 0.8 0.90 6.0 1.5 1.33 14.7 1.0 1.76 8.7 2.1 0.74 22.3 1.5 5.24 10.9 2.7 1.39 27.3 1.9 9.08 14.0 3.6 2.71 34.2 2.3 16.70 16.5 4.2 1.87 41.1 2.8 27.50 4-PIPE SYSTEM 3 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.1 1.1 0.89 8.2 0.6 0.46 5.6 1.5 1.78 10.6 0.7 0.85 7.6 2.1 3.79 14.0 1.0 1.66 11.3 3.0 1.97 21.4 1.5 4.90 14.0 3.9 3.57 26.1 1.8 8.49 17.2 4.7 2.67 32.7 2.2 15.54 21.1 5.9 4.47 39.4 2.7 25.63 4-PIPE SYSTEM 4 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.6 1.3 1.68 7.8 0.5 0.43 6.2 1.8 3.34 10.1 0.7 0.80 7.9 2.2 1.04 13.4 0.9 1.53 12.7 3.6 3.46 20.4 1.4 4.57 15.6 4.6 6.12 24.9 1.7 7.88 19.3 5.6 4.41 31.2 2.1 14.38 23.6 6.9 7.30 37.5 2.6 23.69

Model VBF02 VBF03 VBF04 VBF06 VBF08 VBF10 VBF12

Model VBF02 VBF03 VBF04 VBF06 VBF08 VBF10 VBF12

Total MBH 3.8 5.3 7.5 10.5 13.7 18.3 20.8

Model VBF02 VBF03 VBF04 VBF06 VBF08 VBF10 VBF12

Total MBH 5.8 7.9 11.0 15.8 20.3 24.5 30.6

Model VBF02 VBF03 VBF04 VBF06 VBF08 VBF10 VBF12

Total MBH 5.5 7.5 10.4 15.2 19.4 23.4 29.3

Model VBF02 VBF03 VBF04 VBF06 VBF08 VBF10 VBF12

Total MBH 7.0 9.5 11.5 19.2 24.2 29.5 36.6

Model VBF02 VBF03 VBF04 VBF06 VBF08 VBF10 VBF12

Total MBH 6.7 9.0 10.9 18.2 22.9 27.9 34.6

Model VBF02 VBF03 VBF04 VBF06 VBF08 VBF10 VBF12

Performance Data

Total MBH 7.7 10.4 13.0 21.1 26.4 32.4 39.8

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high fan speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V49

Fan Coils Vertical Basic VBF Performance Data


Performance Data (continued)

Nominal Air Volumes cfm (1) Model High Med Low VBF02 220 195 170 VBF03 295 245 190 VBF04 405 290 210 VBF06 610 440 300 VBF08 730 575 420 VBF10 915 805 530 VBF12 1100 870 600

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

Model VBF02 VBF03 VBF04 VBF06 VBF08 VBF10 VBF12

Motor Total HP AMPS 1/30 0.50 1/30 0.50 1/20 0.78 1/20 0.78 1/20 0.78 2 x 1/20 2 x 0.78 2 x 1/20 2 x 0.78

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/60Hz.

Performance Data

V50

Fan Coils Vertical Basic VBA Description


Vertical Basic Series (continued) Condensate pan mastic coating applicable to the inside of the condensate pans for a prolonged life. Single wall auxiliary condensate pan manufactured in 20GA 304 Stainless Steel. Auxiliary condensate pan mastic coating applicable to the inside of the condensate pans for a prolonged life. Auxiliary condensate pan overow safety switch. Discharge air grilles: - Aluminum double defection - Deluxe aluminum double deection grilles (Contact TITUS for availability). - Linear bar aluminum grilles (Contact TITUS for availability). Special discharge air grille colors (Contact TITUS for color selection and price). Special cabinet paints (Contact TITUS for special colors availability and prices). Heavy duty access panel in 16GA painted steel. Return air/access panel fasteners: - Philips head screws. - Tamper proof fasteners. - Quarter turn fasteners. Access doors keyed locks.

VBA Angled Top Cabinet


Factory assembled, vertical blow-thru, slim and attractively styled VBA fan coils are designed for exposed oor standing applications such as public buildings, hotels, schools, hospitals and general commercial applications. Standard Features Include: Performance ARI Certied to Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. All internal sheet metal components are fabricated of 18GA G90 galvanized steel and exposed metal casing panels fabricated of 18GA galvanealed for superior adhesion of the powder paint. Cabinet components are painted with a powder polyester baked coating in white of beige and are acoustically insulated to reduce noise dissipation from the unit. Cabinet liner in -inch dual-density berglass. High-eciency 2-row coil suitable for a 2-pipe system. Coil manual air vent. Easily removal 1-inch thick disposable lter. Multi-speed motor of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blowers of the whisper quite type. Three speed Motor switch Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally insulated on the outside (Consult TITUS for availability).

Single wall auxiliary condensate pan thermally insulated on the outside. Angle stamped discharge top/grille. Electric controls and valve package access doors. Optional Features Include: 3-, 4- And 5-row coils for 2-pipe systems. Single block 2, 3 and 4 rows CW with 1 row re-heat coils for 4-pipe system applications (5 rows max). Single block 2 and 3 rows CW with 2 rows re-heat for 4-pipe system applications (5 rows max). Automatic coil air vents. LH or RH pipe connections entry Filter option include: - 1-inch high-eciency pleated lters. - 1-inch washable lters. Motor voltage suitable for 208V, 230V or 277V/1Ph/ 60Hz power supplies. Motor in-line quick disconnect. Thermostat and Accessories (refer to Accessories on page V83 for details). Single power supply disconnect switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. HW standby electric heater auto changeover switch. Fresh air opening. Fresh air with manual or auto dampers. Fresh air freeze protection. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel. - Double wall construction consisting of outer and inner skins.

VBA

A Participating Corporation in the ARI 440 Certication Program

V51

Fan Coils Vertical Basic VBA Dimensions Dimensions


VBA Angled Top Cabinet
TOP VIEW

FRONT VIEW

SIDE VIEW 10

6 8 7 2415/16

2613/16

2 D
Note: Right hand unit shown. 1. 2. 3. 4. Control Box Stamped Supply Air Grille Control Access Door Coil 5. 6. 7. 8. Coil Connections (2-Pipe Shown) Motor/Blower(s) Assemby Condensate Connection O.D. Filter
Dimensions (inches) C D 12 11 12 12 12 14 24 14 24 18 36 17 36 22

3 C B A 9 2 2

9. Fresh air damper opening (optional) = 2 x C

Model VBA02 VBA03 VBA04 VBA06 VBA08 VBA10 VBA12 A 34 37 41 52 60 70 80 B 18 21 25 36 44 54 64

Approx. Weight (pounds) Filter 17x10x1 95 20x10x1 104 24x10x1 106 35x10x1 128 43x10x1 146 (2)26x10x1 178 (2)31x10x1 186

Dimensions

All dimensions are in inches.

V52

Fan Coils Vertical Basic VBA Performance Data Performance Data


VBA Angled Top Cabinet
2-PIPE SYSTEM 2 Rows Cooling (1) 2 Rows Heating (1) Total Sensible Flow PD Sensible Flow PD MBH MBH gpm ft wg MBH gpm ft wg 4.0 3.4 0.8 0.31 13.4 0.9 0.32 5.5 4.5 1.1 0.65 17.8 1.2 0.61 7.8 6.2 1.6 1.43 23.9 1.6 1.22 11.0 9.1 2.2 0.80 35.9 2.4 0.87 14.4 11.5 2.9 1.52 44.3 3.0 1.45 19.1 14.8 3.8 2.94 56.2 3.8 2.58 21.8 17.3 4.3 2.04 66.9 4.6 2.05 2-PIPE SYSTEM 3 Rows Cooling 3 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.3 1.2 0.96 17.5 1.2 0.79 5.9 1.6 1.95 23.1 1.6 1.51 8.0 2.2 4.14 31.2 2.1 3.03 11.9 3.2 2.15 46.9 3.2 1.88 14.8 4.1 3.89 57.5 3.9 3.14 18.2 4.9 2.92 71.6 4.9 2.64 22.3 6.1 4.88 86.8 5.9 4.16 2-PIPE SYSTEM 4 Rows Cooling 4 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.9 1.4 1.86 19.5 1.3 1.30 6.6 1.9 3.70 25.8 1.8 2.48 8.4 2.3 1.16 34.0 2.3 1.01 13.4 3.8 3.84 52.5 3.6 2.87 16.6 4.8 6.79 64.0 4.4 4.75 20.5 5.9 4.91 79.8 5.4 3.83 25.1 7.3 8.13 96.5 6.6 6.03 2-PIPE SYSTEM 5 Rows Cooling 5 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 5.2 1.5 2.79 20.0 1.4 1.73 7.0 2.1 5.51 26.7 1.8 3.31 9.0 2.6 1.71 35.0 2.4 1.29 14.1 4.2 5.47 54.4 3.7 3.63 17.4 5.3 9.56 66.1 4.5 6.00 21.5 6.5 6.73 82.5 5.6 4.67 26.3 7.9 11.02 99.7 6.8 7.36 4-PIPE SYSTEM 2 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 3.2 0.8 0.29 8.6 0.6 0.49 4.3 1.1 0.61 11.1 0.8 0.90 5.9 1.5 1.33 14.7 1.0 1.76 8.7 2.1 0.74 22.4 1.5 5.24 11.0 2.7 1.39 27.3 1.9 9.08 14.1 3.6 2.71 34.2 2.3 16.70 16.5 4.2 1.87 41.1 2.8 27.52 4-PIPE SYSTEM 3 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.1 1.1 0.89 8.2 0.6 0.46 5.6 1.5 1.78 10.6 0.7 0.85 7.6 2.1 3.79 14.0 1.0 1.66 11.2 3.0 1.97 21.3 1.5 4.91 14.0 3.9 3.57 26.1 1.8 8.49 17.2 4.7 2.67 32.7 2.2 15.54 21.1 5.9 4.47 39.4 2.7 25.60 4-PIPE SYSTEM 4 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 4.6 1.3 1.68 7.8 0.5 0.43 6.2 1.8 3.34 10.1 0.7 0.80 7.9 2.2 1.04 13.4 0.9 1.53 12.6 3.6 3.46 20.4 1.4 4.57 15.6 4.6 6.12 24.9 1.7 7.88 19.3 5.6 4.41 31.2 2.1 14.38 23.6 6.9 7.30 37.6 2.6 23.69

Model VBA02 VBA03 VBA04 VBA06 VBA08 VBA10 VBA12

Model VBA02 VBA03 VBA04 VBA06 VBA08 VBA10 VBA12

Total MBH 3.8 5.3 7.5 10.5 13.7 18.3 20.8

Model VBA02 VBA03 VBA04 VBA06 VBA08 VBA10 VBA12

Total MBH 5.8 7.9 11.0 15.8 20.3 24.5 30.7

Model VBA02 VBA03 VBA04 VBA06 VBA08 VBA10 VBA12

Total MBH 5.5 7.5 10.5 15.1 19.4 23.4 29.3

Model VBA02 VBA03 VBA04 VBA06 VBA08 VBA10 VBA12

Total MBH 7.0 9.5 11.5 19.2 24.2 29.6 36.6

Model VBA02 VBA03 VBA04 VBA06 VBA08 VBA10 VBA12

Total MBH 6.7 9.0 10.9 18.2 22.9 27.9 34.6

Model VBA02 VBA03 VBA04 VBA06 VBA08 VBA10 VBA12

Performance Data

Total MBH 7.7 10.4 13.0 21.1 26.4 32.4 39.8

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high fan speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V53

Fan Coils Vertical Basic VBA Performance Data


Performance Data (continued)

Nominal Air Volumes cfm (1) Model High Med Low VBA02 235 209 182 VBA03 316 262 203 VBA04 433 310 225 VBA06 653 471 321 VBA08 781 615 449 VBA10 979 861 567 VBA12 1177 931 642

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

Model VBA02 VBA03 VBA04 VBA06 VBA08 VBA10 VBA12

Motor Total HP AMPS 1/20 0.78 1/20 0.78 1/20 0.78 1/12 1.37 1/12 1.37 2 x 1/12 2 x 1.37 2 x 1/12 2 x 1.37

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/60Hz.

Performance Data

V54

Fan Coils Vertical Basic VBL Description


Vertical Basic Series (continued) Single block 2 and 3 rows CW with 2 rows re-heat for 4-pipe system applications (5 rows max). Automatic coil air vents. LH or RH pipe connections entry. Filter option include: - 1-inch high-eciency pleated lters. - 1-inch washable lters. Motor voltage suitable for 208V, 230V or 277V/1Ph/ 60Hz power supplies. Motor in-line quick disconnect. Thermostat and Accessories (refer to Accessories on page V83 for details). Single power supplies disconnect switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. HW standby electric heater auto changeover switch. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel. - Double wall construction consisting of outer and inner skins. Condensate pan Mastic coating applicable to the inside of the condensate pans for a prolonged life. Single wall auxiliary condensate pan manufactured in 20GA 304 Stainless Steel. Auxiliary condensate pan mastic coating applicable to the inside of the condensate pans for a prolonged life. Auxiliary condensate pan overow safety switch. Special Cabinet paints (Contact TITUS for special colors availability and prices). Heavy duty access panel in 16GA painted steel. Return air/access panel fasteners: - Philips head screws. - Tamper proof fasteners. - Quarter turn fasteners. Access doors keyed locks.

VBL Low Prole Cabinet


The low silhouette styling of this cabinet unit makes it ideal for applications in public buildings, hotels, schools, hospitals and general commercial applications where the unit height is restricted.

Standard Features Include: Performance ARI Certied to Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. All internal sheet metal components are fabricated of 18GA G90 galvanized steel and exposed metal casing panels fabricated of 18GA galvanealed for superior adhesion of the powder paint. Cabinet components are painted with a powder polyester baked coating in white or beige and are acoustically insulated to reduce noise dissipation from the unit. Cabinet liner in -inch dual-density berglass. High-eciency 2-row coil suitable for a 2-pipe system. Coil manual air vent. 1-Inch thick disposable lter. Multi-speed motor of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blowers of the whisper quite type. Three speed Motor switch. Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally insulated on the outside (Consult TITUS for availability). Single wall auxiliary condensate pan thermally insulated on the outside. Flat stamped discharge top/grille. Electric controls and valve package access door. Optional Features Include: 3-, 4- And 5-row coils for 2-pipe systems. Single block 2, 3 and 4 rows CW with 1 row re-heat coils for 4-pipe system applications (5 rows max).

VBL

A Participating Corporation in the ARI 440 Certication Program

V55

Fan Coils Vertical Basic VBL Dimensions Dimensions


VBL Low Prole Cabinet
TOP VIEW

3 SIDE VIEW 12

FRONT VIEW

5 7 15 8

8
Note: Right hand unit shown.

B A

1. 2. 3. 4.

Control Access Door Control Box Stamped Supply Air Grille Coil

5. 6. 7. 8.

Coil Connections (2-Pipe Shown) Motor/Blower(s) Assemby Condensate Connection O.D. Filter
Dimensions (inches) B C 21 25 36 44

9. Stamped Return Air Grille

V
Approx. Weight

Model VBL02 VBL03 VBL04 VBL06 A 37 41 52 60

Filter 21x10x1 25x10x1 36x10x1 44x10x1

(pounds) 90 95 100 120

Dimensions

All dimensions are in inches.

V56

Fan Coils Vertical Basic VBL Performance Data Performance Data


VBL Low Prole Cabinet
2-PIPE SYSTEM 2 Rows Cooling (1) Model VBL02 VBL03 VBL04 VBL06 Total Sensible Flow MBH 4.8 7.0 11.5 14.1 MBH 4.1 5.9 9.0 12.0 gpm 0.9 1.4 2.3 2.8 PD ft wg 0.43 1.03 3.54 1.34 2 Rows Heating (1) Sensible Flow MBH 16.5 23.4 34.6 47.4 gpm 1.1 1.6 2.4 3.2 PD ft wg 0.46 1.02 2.87 1.51 VBL02 VBL03 VBL04 VBL06 Model MBH 4.6 6.8 11.1 13.6 4-PIPE SYSTEM 2 Rows Cooling Total Sensible Flow MBH 3.9 5.6 8.5 11.4 gpm 0.9 1.4 2.2 2.7 PD ft wg 0.40 0.96 3.27 1.25 1 Row Heating Sensible Flow MBH 11.1 15.4 22.3 31.0 gpm 0.8 1.0 1.5 2.1 PD ft wg 0.79 1.67 4.57 10.00

2-PIPE SYSTEM 3 Rows Cooling Model VBL02 VBL03 VBL04 VBL06 Total Sensible Flow MBH 6.7 9.8 15.3 19.7 MBH 5.0 7.3 10.9 14.8 gpm 1.3 2.0 3.1 3.9 PD ft wg 1.24 2.91 9.05 3.35 3 Rows Heating Sensible Flow MBH 20.8 29.7 43.3 60.4 gpm 1.4 2.0 3.0 4.1 PD ft wg 1.08 2.42 6.61 3.12 VBL02 VBL03 VBL04 VBL06 Model MBH 6.4 9.3 14.5 18.8

4-PIPE SYSTEM 3 Rows Cooling Total Sensible Flow MBH 4.7 6.9 10.3 14.0 gpm 1.3 1.9 2.9 3.8 PD ft wg 1.13 2.64 8.23 3.05 1 Row Heating Sensible Flow MBH 10.6 14.7 21.3 29.7 gpm 0.7 1.0 1.5 2.0 PD ft wg 0.74 1.56 4.25 9.38

2-PIPE SYSTEM 4 Rows Cooling Model VBL02 VBL03 VBL04 VBL06 Total Sensible Flow MBH 7.8 11.4 15.7 23.1 MBH 5.4 8.0 11.0 16.2 gpm 1.6 2.3 3.1 4.6 PD ft wg 2.23 5.20 2.35 5.61 4 Rows Heating Sensible Flow MBH 22.4 32.2 45.4 65.6 gpm 1.5 2.2 3.1 4.5 PD ft wg 1.66 3.76 1.96 4.48

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high fan speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V
Nominal Air Volumes cfm (1) Model High Med Low VBL02 241 171 123 VBL03 353 235 182 VBL04 492 364 268 VBL06 728 567 396

Performance Data

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

Model VBL02 VBL03 VBL04 VBL06

Motor Total HP AMPS 1/30 0.50 1/30 0.50 1/20 0.78 1/20 0.78

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/ 60Hz.

V57

Fan Coils Vertical Basic VBLC Description


Vertical Basic Series (continued) Motor voltage suitable for 208V, 230V or 277V/1Ph/ 60Hz power supplies. Motor in-line quick disconnect. Thermostat and Accessories (refer to Accessories on page V83 for details). Single power supplies disconnect switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. HW standby electric heater auto changeover switch. Fresh air opening. Fresh air with manual or auto dampers. Fresh air freeze protection. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel. - Double wall construction consisting of outer and inner skins. Condensate pan mastic coating applied to the inside of the condensate pans for a prolonged life. Single wall auxiliary condensate pan manufactured in 20GA 304 Stainless Steel. Auxiliary condensate pan mastic coating applied to the inside of the condensate pans for a prolonged life. Auxiliary condensate pan overow safety switch. Remote discharge air grilles: - Stamped with access doors - Aluminum double defection - Deluxe aluminum double deection grilles (Contact TITUS for availability). - Linear bar aluminum grille (Contact TITUS for availability). Special discharge air grille colors (Contact TITUS for color range availability and price). Remote stamped return air/access panel with lter access door.

VBLC Low Prole Concealed Floor


The low silhouette, vertical discharge, oor mounted unit is designed for concealed applications inside a closet or furred-in under window installations for applications in public buildings, hotels, schools, hospitals and general commercial applications where the unit height is restricted.

Standard Features Include: Performance ARI Certied to Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. All sheet metal components are fabricated of 18GA G90 galvanized steel. Cabinet liner in -inch dual-density berglass. High-eciency 2-row coil suitable for a 2-pipe system. Coil manual air vent. Easily removal 1-inch thick disposable lter. Multi-speed motor of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blowers of the whisper quite type. Three speed Motor switch. Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally insulated on the outside (Consult TITUS for availability). Single wall auxiliary condensate pan thermally insulated on the outside. -Inch top discharge air ange. Optional Features Include: 3- And 4-row coils for 2-pipe systems. Single block 2 and 3 rows CW with 1 row re-heat coils for 4-pipe system applications (5 rows max). Single block 2 rows CW with 2 rows re-heat for 4-pipe system applications (5 rows max). Automatic coil air vents. LH or RH pipe connections entry Filter option include: - 1-inch high-eciency pleated lters. - 1-inch washable lters.

VBLC

A Participating Corporation in the ARI 440 Certication Program

V58

Fan Coils Vertical Basic VBLC Dimensions Dimensions


VBLC Low Prole Concealed Floor
TOP VIEW 1 6 A C 2 6 1 5 4

1 SIDE VIEW 12 1 3 10 12 5 2 15 REF.

8 1

FRONT VIEW B

10 6 10 10 6

7 9 12 5

Note: Right hand unit shown. 1. 2. 3. 4. Supply Duct Collar Coil Coil Connections (2-Pipe Shown) Motor/Blower(s) Assemby 5. 6. 7. 8. Auxillary Condensate Tray Condensate Connection O.D. Filter Control Box
Dimensions (inches) C Filter 18 21x10x1 22 25x10x1 33 36x10x1 44 44x10x1

9. Sub-base (optional) 10. Filter Clips

Model VBLC02 VBLC03 VBLC04 VBLC06 A 34 38 49 57 B 231/9 271/9 381/9 461/9

Approx. Weight (pounds) Opt. Cover 37 x 155/7 x 90 41 x 155/7 x 95 52 x 155/7 x 100 60 x 155/7 x 120

Dimensions

All dimensions are in inches.

V59

Fan Coils Vertical Basic VBLC Performance Data Performance Data


VBLC Low Prole Concealed Floor
2-PIPE SYSTEM 2 Rows Cooling (1) Model VBLC02 VBLC03 Total Sensible Flow MBH 4.8 7.0 MBH 4.1 5.9 9.0 12.0 gpm 0.9 1.4 2.3 2.8 PD ft wg 0.43 1.03 3.54 1.34 2 Rows Heating (1) Sensible Flow MBH 16.5 23.4 34.6 47.4 gpm 1.1 1.6 2.4 3.2 PD ft wg 0.46 1.02 2.87 1.51 VBLC02 VBLC03 Model MBH 4.6 6.8 4-PIPE SYSTEM 2 Rows Cooling Total Sensible Flow MBH 3.9 5.6 8.5 11.4 gpm 0.9 1.4 2.2 2.7 PD ft wg 0.40 0.96 3.27 1.25 1 Row Heating Sensible Flow MBH 11.1 15.4 22.3 31.0 gpm 0.8 1.0 1.5 2.1 PD ft wg 0.79 1.67 4.57 10.00

VBLC04 11.5 VBLC06 14.1

VBLC04 11.1 VBLC06 13.6

2-PIPE SYSTEM 3 Rows Cooling Model VBLC02 VBLC03 Total Sensible Flow MBH 6.7 9.8 MBH 5.0 7.3 10.9 14.8 gpm 1.3 2.0 3.1 3.9 PD ft wg 1.24 2.91 9.05 3.35 3 Rows Heating Sensible Flow MBH 20.8 29.7 43.3 60.4 gpm 1.4 2.0 3.0 4.1 PD ft wg 1.08 2.42 6.61 3.12 VBLC02 VBLC03 Model MBH 6.4 9.3

4-PIPE SYSTEM 3 Rows Cooling Total Sensible Flow MBH 4.7 6.9 10.3 14.0 gpm 1.3 1.9 2.9 3.8 PD ft wg 1.13 2.64 8.23 3.05 1 Row Heating Sensible Flow MBH 10.6 14.7 21.3 29.7 gpm 0.7 1.0 1.5 2.0 PD ft wg 0.74 1.56 4.25 9.38

VBLC04 15.3 VBLC06 19.7

VBLC04 14.5 VBLC06 18.8

2-PIPE SYSTEM 4 Rows Cooling Model VBLC02 Total Sensible Flow MBH 7.8 VBLC03 11.4 VBLC04 15.7 VBLC06 23.1 MBH 5.4 8.0 11.0 16.2 gpm 1.6 2.3 3.1 4.6 PD ft wg 2.23 5.20 2.35 5.61 4 Rows Heating Sensible Flow MBH 22.4 32.2 45.4 65.6 gpm 1.5 2.2 3.1 4.5 PD ft wg 1.66 3.76 1.96 4.48

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high fan speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V
Nominal Air Volumes cfm (1) Model High Med Low VBLC02 241 171 123 VBLC03 353 235 182 VBLC04 492 364 268 VBLC06 728 567 396

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

Performance Data

Model VBLC02 VBLC03 VBLC04 VBLC06

Motor Total HP AMPS 1/30 0.50 1/30 0.50 1/20 0.78 1/20 0.78

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/ 60Hz.

V60

Fan Coils Vertical Basic Specications Suggested Specications


Fan Coils
Vertical Basic Units Standard Congurations 1. Furnish and install TITUS models VBC, VBA, VBF and low prole VBL, VBLC vertical basic fan coils of sizes and capacities shown on the plans to meet prevailing cooling and heating requirements. 2. Fan coils shall be performance certied to ARI Standard 440. Units shall be wired in compliance with ANSI/UL 1995 Standard and listed with ETL. 3. Fan coils shall be sound tested in accordance with ARI Standard 260 for ducted units and ARI Standard 350 for non-ducted units. Manufacturer shall provide these dB ratings on request for each model specied. 4. Unit casing shall be 18-gauge, zinc coated, phosphate treated, galvanized steel. Painted sheet metal components (VBA, VBF and VBLC units only) components shall be 18-gauge galvanealed sheet metal. 5. Painted panels (VBA, VBF and VBLC units only) shall be painted with a polyester powder coating, electrostatically applied, oven baked to 400F for 10 minutes in beige or white tones. 6. High-eciency, 2-row coil shall be suitable for a 2-pipe system. Coils shall be manufactured with aluminum ns mechanically bonded to seamless copper tubes. The copper tubes shall be -inch OD with a wall thickness of 0.017inch which comply with ASTM B-75. The ns shall be waved with ripple hedges for superior eciency with a thickness of 0.0045-inch and spaced at 10 fpi. All coils shall be leak tested with 100% helium to ensure a leak free coil. All coils shall be shipped with a safety air pressure of 100 - 125 psi to guarantee a leak free arrival at the nal destination. 7. Unit pipe entry location shall be in accordance with the project schedule. 8. Coils shall be installed with manual Schrader type air vents with a sealing cap and be located at the highest point of the coil. The cap shall have a dual purpose, to seal any potential water leakage in the eventuality of Schrader valve failure and as a service tool for the extraction/insertion of the internal Schrader valve. 9. Standard lters shall be 1inch nominal thickness of the disposable type with a one-piece moisture resistant chipboard frame to eliminate corner separations. The spun glass ltering media shall be bonded with a resinous agent providing rigidity and resistance to media compression and meets UL class 2. 10. Cabinets shall be lined with -inch dual-density berglass with a density of 1.5lbs/ft3 and 4.0lbs/ft3 for the face meeting NFPA 90A and 90B (appliances), NFPA 255, UL 181, UL723 and ASTM E84. 11. Motors shall be multi-speed of the permanent split capacitor type (PSC) and be directly coupled to the centrifugal fan blower. Motor shall be suitable for a power supply of 115V/1Ph/60Hz and shall be internally protected with an automatic thermal overload. Motor shaft shall be supported by sleeve bearings of the permanently lubricated type for the full life expectancy of the motor. All motors shall be directly mounted to the fan deck and be isolated from the unit casing by two resilient anti-vibration mounts. 12. Direct-driven fan shall be of the whisper quite type, double width double inlet (DWDI) forward curved statically and dynamically balanced at the factory. The fan wheel and casing shall be constructed of galvanized steel. 13. Electric components shall be wired to a single control panel for single point power supply. Wiring exposed to the outside of the units shall be installed in conduits to meet UL 1995 safety requirements. 14. Condensate pans shall be single wall 18-gauge G90 galvanized steel-welded at the corners, thermally protected on the outside with re and smoke rated -inch high-density insulation to prevent condensation. The factory installed -inch OD sweat copper condensate connection shall be located at the lowest point of the condensate pan to ensure all water drains from the condensate pan (Consult TITUS for availability). 15. Auxiliary condensate pan shall be removable, single wall, 18gauge G90 galvanized steel, thermally protected on the outside with re and smoke rated inch high-density insulation to prevent condensation. The factory installed -inch OD sweat copper condensate eld connection shall be located at the lowest point of the auxiliary condensate pan to ensure that all water is drained from the condensate pan. 16. Discharge air ange (VBC and VBLC units only) shall be -inch to facilitate the eld connection of ducts. 17. Discharge air grille (VBA, VBF and VBL) shall be of the stamped louvered type and be an integral part of the cabinet assembly. 18. Access doors shall be provided for access to the electric controls and valve package.

Specications

V61

Fan Coils Vertical Basic Specications


Suggested Specications (continued) 2-Pipe Heat/Cool Auto Changeover Switch A mechanical changeover switch shall be supplied on 2-pipe systems to automatically change over the thermostat operation for summer and winter modes. Electric Heater and Accessories 1. Electric heaters shall be of the wound type mounted in a metal frame and supported by ceramic rings and terminals. Electric heaters shall be installed on the blower discharge side for better heat dissipation and shall include an automatic reset, high limit cutout and contactor. 2. 2-pipe standby electric heating heaters shall be installed and pre-wired as standby heating for the eventuality of a failure of the primary hot water (HW) system. A changeover sensor shall be installed in each unit and the changeover between the failed hot water system and the standby electric heater shall be automatic. Chilled and Hot Water Valve Controls Refer to Accessories on page V83. Condensate Pan and Accessories 1. Condensate pan shall be single wall manufactured in 20-gauge 304 stainless steel and shall be thermally protected on the outside with re and smoke rated -inch high-density insulation to prevent condensation. The factory installed -inch OD sweat copper condensate connection shall be located at the lowest point of the condensate pan to ensure that all water is drained from the condensate pan (Consult TITUS for availability), or 2. Condensate pan shall be double wall construction consisting of an outer and inner skin. The outer skin shall be manufactured of 18-gauge G90 galvanized sheet metal wrapped around the inner skin with 1-inch thermal insulation between both skins to prevent condensation. The inner skin of the double wall condensate pan shall be of 18-gague G90 galvanized sheet metal, or 3. Condensate pan shall be double wall construction consisting of an outer and inner skin. The outer skin shall be manufactured of 18-gauge G90 galvanized sheet metal wrapped around the inner skin with 1-inch thermal insulation between both skins to prevent the formation of condensation. The inner skin of the double wall condensate pan shall be of 20-gauge 304 stainless steel galvanized sheet metal. 4. A mastic coating shall be applied to the inside of the condensate pan for a prolonged life. Auxiliary Condensate Pan and Accessories 1. Auxiliary condensate pan shall be removable, single wall 20-gauge 304 stainless steel, thermally protected on the outside with re and smoke rated -inch highdensity insulation to prevent condensation. The factory installed -inch OD sweat copper condensate eld connection shall be located at the lowest point of the auxiliary condensate pan to ensure that all water is drained from the condensate pan. 2. An automatic safety overow switch shall be located in the auxiliary condensate pan and be interconnected to the unit electric system preventing the unit operation if an overow status is detected. 3. A mastic coating shall be applied to the inside of the condensate pans for a prolonged life.

Fan Coils
Vertical Basic Units Optional Congurations Cooling and Heating Coil 1. High-eciency 3-, 4- and 5-row coils suitable for 2-pipe systems (VBC, VBA and VBF 5-row maximum). 2. High-eciency single block with 2, 3 and 4-rows chilled water (CW) with 1-row re-heat coil suitable for 4-pipe system applications, or 3. High-eciency single block with 2, 3 rows chilled water (CW) with 2row re-heat coil suitable for 4-pipe system applications. 4. Coils shall be installed with an automatic air vent capable of operation in chilled or hot water systems to a maximum of 125 psi. Filter 1. Filter shall be 1-inch pleated lter with an average atmospheric dust spot eciency range of 20 - 30% per ASHRAE Standard 52.1 test method, or 2. Filter shall be 1-inch washable lter consisting of synthetic bers coated with a special resin, then baked together at a high temperature resulting in a tough and springy, thoroughly bonded, nearly rigid air ltration media. Washable lters shall have a longer service life, better structural integrity as well as being completely odor free. 3. A spare set of lters shall be available for replacement after the commissioning of the unit and prior to the handover of the project. Motor and Motor Accessories 1. Motors shall be suitable for 115V/1Ph/60Hz or 208V/1Ph/60Hz or 230V/1Ph/60Hz or 277V/1Ph/ 60Hz power supplies (delete as applicable). 2. A motor in-line quick disconnect shall be installed to facilitate the removal/replacement of motor. Thermostat and Accessories Refer to Accessories on page V83. Disconnect Switch and Fuses Units shall be wired for single power with supply with a disconnect switch and fuse(s) to match the unit full maximum circuit ampacity (MCA) in line with UL 1995.

Specications

V62

Fan Coils Vertical Basic Specications


Suggested Specications (continued) 5. Access panel security fasteners (VBA, VBF and VBC units) shall be of the quarter turn type, to facilitate the removal of the access panel. 6. Four adjustable leveling feet shall be installed to ensure that the unit is correctly level and prevent condensate water leaks. 7. Access doors shall be tted with keyed locks.

Fan Coils
Vertical Basic Units Optional Congurations (continued) Discharge Air Grilles and Accessories Unit mounted (VBA and VBF units only) discharge air grille shall be double-deection, made of aluminum and painted white for white painted cabinet units or aluminum for beige painted cabinets, or Unit mounted (VBA and VBF units only) deluxe discharge air grille shall be doubledeection, made of aluminum and painted white for white painted cabinet units or aluminum for beige painted cabinets, or Unit mounted (VBA and VBF units only) xed linear discharge air grille shall be made of aluminum and painted white for white painted cabinet units or aluminum for beige painted cabinets, or Remote mounted (VBC and VBLC) stamped grille with access doors painted white or beige, or Remote mounted (VBC and VBLC) grille assembly with access doors painted white or beige and a deluxe aluminum grille core, or Remote mounted (VBC and VBLC) grille assembly with access doors painted white or beige and a linear aluminum grille core, or Special discharge air grilles colors shall be______________. (Contact TITUS for color range availability and price). Cabinet and Accessories 1. Special cabinet color shall be___ ___________. Contact TITUS for color range availability and price. 2. Access panel (VBA, VBF and VBC units) shall be manufactured in heavy duty 16GA steel. 3. Remote access/return grille panel (VBC and VBLC) shall be stamped with a hinged door for easy access to the lters and painted white or beige. 4. Access panel security fasteners (VBA, VBF and VBC units) shall be tamperproof, requiring a specialist tool to access the units, or

Specications

V63

Fan Coils Horizontal High Output HHC Description

Horizontal High Output Series


HHC Concealed Ceiling
Factory assembled, horizontal blowthru, high-output, ducted fan coils are designed for concealed installations above ceilings with ducted air discharge and suitable for projects such as hotels, motels, condominiums and general commercial applications. Standard Features Include: Performance ARI Certied to Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. All casing sheet metal components fabricated of 18GA G90 galvanized steel. High-eciency 3-row coil suitable for a 2-pipe system. Coil manual air vent. Multi-speed motor(s) of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blower(s) of the whisper quite type. Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally protected on the outside (Contact TITUS for availability). 1-inch discharge air ange.

Optional Features Include: 4-, 5- And 6-row coils for 2-pipe systems. Single block 2, 3, 4 and 5 rows CW with 1 row reheat coils for 4-pipe system applications (6 rows max). Single block 2, 3, and 4 rows CW with 2 rows re-heat for 4-pipe system applications (5 rows max). Automatic coil air vents. LH or RH pipe connections entry. Motor voltage suitable for 208V, 230V or 277V1Ph/ 60Hz power supplies. Thermostat and Accessories (refer to Accessories on page V83 for details). Single power supplies disconnect switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. HW Standby electric heater auto changeover switch. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel. - Double wall construction consisting of outer and inner shins. Condensate pan mastic coating applicable to the inside of the condensate pans for a prolonged life. Condensate pan overow safety switch. Condensate pan safety overow connection.

HHE

A Participating Corporation in the ARI 440 Certication Program

V64

Fan Coils Horizontal High Output HHC Dimensions Dimensions


HHC Concealed Ceiling
TOP VIEW 1

2 3

11

9 4 5 5

37/16 1

C B B+2 A

1 FRONT VIEW

SIDE VIEW 28

15

11

16

Note: Right hand unit shown.

1. Motor/Blower(s) Assemblies 2. Condensate Tray (Double Wall) 3. Condensate Connection O.D.

4. Coil Connections (2-Pipe Shown) 5. Installation Hanging Points 6. Coil

7. Supply Air Flange

V
Model HHC06 HHC08 HHC10 HHC12 HHC14 HHC16 HHC18 HHC20 A 25 30 33 38 42 46 51 55 Dimensions (inches) B C 18 13 23 18 26 21 31 26 35 30 39 34 44 39 48 43 Approx. Weight D (pounds) 60 69 75 99 108 115 125 175

Dimensions

All dimensions are in inches.

V65

Fan Coils Horizontal High Output HHC Performance Data Performance Data
HHC Concealed Ceiling
2-PIPE SYSTEM 3 Rows Cooling 3 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 12.3 2.9 2.62 48.3 3.3 2.50 16.4 4.2 5.77 63.8 4.4 4.83 20.4 5.2 9.25 78.5 5.4 26.70 21.8 5.3 2.03 86.9 5.9 2.02 26.8 6.6 3.23 105.4 7.2 3.08 31.5 7.9 4.75 123.0 8.4 4.36 36.2 9.2 6.84 140.0 9.6 5.98 38.2 9.4 3.17 150.6 10.3 3.22 2-PIPE SYSTEM 4 Rows Cooling 4 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 14.2 3.7 5.34 56.0 3.8 4.35 17.5 4.4 1.52 71.0 4.8 1.48 21.9 5.6 2.51 87.8 6.0 2.33 25.1 6.7 3.88 99.7 6.8 3.27 30.8 8.3 6.12 121.2 8.3 5.02 34.7 9.0 3.18 139.1 9.5 3.01 40.0 10.5 4.53 158.3 10.8 4.08 43.9 11.7 5.81 173.2 11.8 5.07 2-PIPE SYSTEM 5 Rows Cooling 5 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 15.3 4.2 1.11 58.0 4.0 1.07 18.8 5.1 2.41 75.8 5.2 2.01 23.6 6.5 3.96 94.1 6.4 3.19 26.9 7.6 5.96 105.7 7.2 4.40 31.7 8.7 3.30 126.9 8.7 2.81 37.4 10.4 4.82 148.5 10.1 3.97 42.9 12.0 6.80 168.5 11.5 5.38 45.8 12.7 4.57 182.3 12.4 3.96 2-PIPE SYSTEM 6 Rows Cooling 6 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 14.8 4.1 1.62 60.2 4.1 1.35 19.6 5.6 3.34 78.0 5.3 2.47 24.6 7.1 5.44 97.0 6.6 3.94 26.7 7.7 2.80 106.7 7.3 2.18 32.9 9.5 4.44 130.3 8.9 3.37 38.9 11.3 6.45 152.6 10.4 4.78 43.3 12.5 4.72 171.4 11.7 3.80 47.6 13.8 5.98 187.2 12.8 4.67 4-PIPE SYSTEM 2 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.9 1.9 0.79 19.1 1.3 1.08 12.1 2.7 1.84 26.2 1.8 2.24 15.0 3.5 3.02 32.0 2.2 3.48 17.3 4.2 4.81 37.4 2.6 5.25 19.7 4.3 1.08 45.1 3.1 7.96 23.1 5.2 1.60 50.0 3.4 1.60 26.6 6.1 2.33 57.4 3.9 2.26 29.3 6.8 3.03 63.3 4.3 2.89 4-PIPE SYSTEM 3 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 11.7 2.8 2.47 18.6 1.3 1.05 15.7 4.0 5.41 25.4 1.7 2.16 19.6 5.0 8.79 31.0 2.1 3.36 20.8 5.1 1.90 36.2 2.5 5.00 25.6 6.4 3.02 43.7 3.0 7.63 30.1 7.6 4.44 48.4 3.3 1.65 34.6 8.9 6.38 55.7 3.8 2.32 36.5 9.0 2.95 61.4 4.2 2.89 4-PIPE SYSTEM 4 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 13.4 3.5 4.91 18.0 1.2 1.02 16.6 4.2 1.41 24.6 1.7 2.05 20.8 5.3 2.33 30.0 2.0 3.19 23.7 6.4 3.58 35.0 2.4 4.78 29.2 7.9 5.66 42.2 2.9 7.29 33.0 8.6 2.94 46.9 3.2 1.64 37.9 10.1 4.18 53.9 3.7 2.30 41.7 11.2 5.36 59.4 4.1 2.93 4-PIPE SYSTEM 5 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 14.1 3.9 1.04 19.5 1.5 0.97 17.9 4.9 2.23 23.8 1.6 1.97 22.5 6.2 3.66 29.1 2.0 3.07 25.5 7.3 5.47 33.9 2.3 4.58 30.2 8.4 3.06 40.8 2.8 6.93 35.5 9.9 4.44 45.4 3.1 1.67 40.7 11.5 6.25 52.2 3.6 2.33 43.6 12.2 4.23 57.5 3.9 2.89

Model HHC06 HHC08 HHC10 HHC12 HHC14 HHC16 HHC18 HHC20

Total MBH 14.6 20.8 25.9 26.7 33.1 39.5 46.2 46.9

Model HHC06 HHC08 HHC10 HHC12 HHC14 HHC16 HHC18 HHC20

Total MBH 9.3 13.7 17.3 20.9 21.7 25.0 30.6 34.2

Model HHC06 HHC08 HHC10 HHC12 HHC14 HHC16 HHC18 HHC20

Total MBH 18.6 22.0 27.9 33.5 41.3 45.0 52.7 58.7

Model HHC06 HHC08 HHC10 HHC12 HHC14 HHC16 HHC18 HHC20

Total MBH 14.1 20.1 25.2 25.7 31.9 38.0 44.4 45.2

Model HHC06 HHC08 HHC10 HHC12 HHC14 HHC16 HHC18 HHC20

Total MBH 19.2 25.6 32.4 38.2 43.6 51.9 60.3 63.4

Model HHC06 HHC08 HHC10 HHC12 HHC14 HHC16 HHC18 HHC20

Total MBH 17.7 21.1 26.8 32.0 39.5 43.1 50.4 56.2

Model HHC06 HHC08 HHC10 HHC12 HHC14 HHC16 HHC18 HHC20

Total MBH 20.3 28.1 35.4 38.5 47.7 56.5 62.3 69.2

Model HHC06 HHC08 HHC10 HHC12 HHC14 HHC16 HHC18 HHC20

Total MBH 18.2 24.5 30.1 36.4 41.9 49.6 57.5 60.9

Performance Data

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high fan speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V66

Fan Coils Horizontal High Output HHC Performance Data


Performance Data (continued)

Nominal Air Volumes cfm (1) Model High Med Low HHC06 738 599 524 HHC08 920 749 567 HHC10 1156 936 754 HHC12 1241 1038 808 HHC14 1530 1166 872 HHC16 1798 1279 888 HHC18 2022 1691 1354 HHC20 2194 1835 1477

Model HHC06 HHC08 HHC10 HHC12 HHC14 HHC16 HHC18 HHC20

Air Volume (cfm) Vs External Static Pressure in wg (2) 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 716 696 674 649 619 584 545 503 459 899 873 844 809 770 726 677 625 571 114 1059 1020 983 945 902 855 801 741 1193 1145 1097 1048 997 943 886 826 764 1486 1453 1423 1384 1330 1258 1168 1066 960 1727 1662 1599 1536 1469 1396 1313 1219 1111 1947 1870 1793 1714 1633 1550 1463 1370 1266 2127 2058 1989 1917 1841 1759 1668 1566 1449

0.50 417 518 673 700 864 986 1150 1315

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

2. Air volumes at alternative external static pressures are based at high fan speed.

Model HHC06 HHC08 HHC10 HHC12 HHC14 HHC16 HHC18 HHC20

Motor Total HP AMPS 1/5 3.20 1/5 3.20 1/5 3.20 1/5 3.20 2 x 1/5 2 x 3.2 2 x 1/5 2 x 3.2 2 x 1/5 2 x 3.2 2 x 1/5 2 x 3.2

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/60Hz.

Performance Data

V67

Fan Coils Horizontal High Output HHP Description


Horizontal High Output Series (continued) Optional Features Include: 4-, 5- And 6-row coils for 2-pipe systems. Single block 2, 3, 4 and 5 rows CW with 1 row reheat coils for 4-pipe system applications (5 rows max). Single block 2, 3 and 4 rows CW with 2 rows re-heat for 4-pipe system applications (5 rows max). Automatic coil air vents. LH or RH entry pipe connections. Filter option include: - 1-inch high-eciency pleated lters. - 1-inch washable lters. Bottom or rear return air and lter location. Filter supports with slides or clips. Vertical removal of lter on return air installations. Motor(s) voltage suitable for 208V, 230V or 277V/1Ph/ 60Hz power supplies. Motor in-line quick disconnect(s) (Rear return air option only). Thermostat and Accessories (refer to Accessories on page V83 for details). Single power supplies disconnect switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. HW standby electric heater auto changeover switch. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel. - Double wall construction consisting of outer and inner skins. Condensate pan mastic coating applicable to the inside of the condensate pans for a prolonged life. Condensate pan overow safety switch. Secondary overow condensate water connection.

HHP Concealed Ceiling with Plenum


Factory assembled, horizontal blowthru, ducted high-output HHP fan coils designed for concealed installations above ceilings with ducted return and discharge air and suitable for projects such as hotels, motels, condominiums and general commercial applications.

Standard Features Include: Performance ARI Certied to Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. Casing sheet metal components fabricated of 18GA G90 galvanized steel. Return air plenum thermally and acoustically insulated covering the motor(s)/blower(s) assembly to reduce noise dissipation from the unit. High-eciency 3-row coil suitable for a 2-pipe system. Coil manual air vent. 1-Inch thick disposable lter. Filter removal from LH or RH sides. Multi-speed motor(s) of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blower(s) of the whisper quite type. Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally protected on the outside (Consult TITUS for availability). 1-inch discharge air ange. 1-Inch return air return air ange. Anti-vibration mounts for eld installation.

HHP

A Participating Corporation in the ARI 440 Certication Program

V68

Fan Coils Horizontal High Output HHP Dimensions Dimensions


HHP Concealed Ceiling with Plenum
1 3 TOP VIEW B

2 10

14 4 5 9 6 8 5 11

1 37/16 1

C B B+2 A

7 SIDE VIEW 1 /16


7

FRONT VIEW

28

15

11

15

17

Note: Right hand rear return unit shown. 1. Return Air Flange 2. Filter Bottom Return (Optional) 3. Motor/Blower(s) Assemby 4. Condensate Tray (Double Wall optional) 5. Condensate Connection O.D. 6. Coil Connections (2-Pipe Shown)

7. Hanging Points 8. Coil 9. Supply Air Flange 10. Electric Control Panel

V
Model HHP06 HHP08 HHP10 HHP12 HHP14 HHP16 HHP18 HHP20 A 25 30 33 38 42 46 51 55 B 18 23 26 31 35 39 44 48 Dimensions (inches) C 13 18 21 26 30 34 39 43 Approx. Weight D Filter (pounds) 20x17x1 81 25x17x1 94 28x17x1 106 33x17x1 117 37x17x1 154 41x17x1 175 46x17x1 195 50x17x1 212

Fan Coils

All dimensions are in inches.

V69

Fan Coils Horizontal High Output HHP Performance Data Performance Data
HHP Concealed Ceiling with Plenum
2-PIPE SYSTEM 3 Rows Cooling 3 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 12.0 2.9 2.55 47.4 3.2 2.42 15.9 4.1 5.52 62.0 4.2 4.58 19.9 5.1 8.94 76.7 5.2 7.28 21.5 5.3 1.98 85.4 5.8 1.95 26.1 6.5 3.12 103.0 7.0 2.96 30.7 7.7 4.56 119.7 8.2 4.15 35.3 9.0 6.59 136.9 9.3 5.74 37.0 9.1 3.03 146.4 10.0 3.06 2-PIPE SYSTEM 4 Rows Cooling 4 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 13.9 3.6 5.17 54.9 3.7 4.21 16.9 4.3 1.45 68.7 4.7 1.39 21.3 5.5 2.41 85.6 5.8 2.23 24.6 6.6 3.77 97.9 6.7 3.17 30.0 8.1 5.90 118.2 8.1 4.80 33.7 8.8 3.04 135.0 9.2 2.85 38.8 10.3 4.35 154.2 10.5 3.90 42.6 11.4 5.54 168.0 11.5 4.79 2-PIPE SYSTEM 5 Rows Cooling 5 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 14.5 4.2 1.09 56.8 3.9 1.04 18.2 5.0 2.29 73.2 5.0 1.89 23.0 6.3 3.78 91.5 6.2 3.03 26.4 7.5 5.80 103.6 7.1 4.24 30.8 8.5 3.17 123.5 8.4 2.67 36.3 10.1 4.59 144.0 9.8 3.75 41.7 11.7 6.51 164.0 11.2 5.11 44.3 12.3 4.33 176.4 12.0 3.73 2-PIPE SYSTEM 6 Rows Cooling 6 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 14.4 4.0 1.55 58.9 4.0 1.29 18.9 5.4 3.16 75.1 5.1 2.31 23.9 6.9 5.20 94.1 6.4 3.73 26.2 7.5 2.71 104.4 7.1 2.10 32.0 9.3 4.25 126.7 8.6 3.20 37.6 10.9 6.10 147.5 10.1 4.49 42.0 12.1 4.50 166.4 11.4 3.59 46.0 13.4 5.65 180.7 12.3 4.38 4-PIPE SYSTEM 2 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.8 1.8 0.77 18.8 1.3 1.06 11.7 2.7 1.74 25.5 1.7 2.15 14.6 3.4 2.92 31.4 2.1 3.37 17.0 4.1 4.70 36.9 2.5 5.13 19.2 4.3 1.05 44.3 3.0 7.72 22.5 5.1 1.54 48.9 3.3 1.54 26.0 6.0 2.26 56.4 3.8 2.19 28.5 6.7 2.92 61.9 4.2 2.78 4-PIPE SYSTEM 3 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 11.5 2.8 2.40 18.3 1.2 1.03 15.2 3.9 5.17 24.8 1.7 2.07 19.0 4.9 8.39 30.4 2.1 3.25 20.5 5.1 1.85 35.8 2.4 4.89 25.0 6.2 2.91 42.9 2.9 7.39 29.3 7.4 4.26 47.4 3.2 1.59 33.7 8.7 6.14 54.7 3.7 2.25 35.4 8.8 2.82 60.0 4.1 2.78 4-PIPE SYSTEM 4 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 13.2 3.5 4.80 17.7 1.2 0.99 16.0 4.1 1.34 23.9 1.6 1.96 20.2 5.2 2.24 29.5 2.0 3.09 23.3 6.3 3.48 34.6 2.4 4.67 28.5 7.7 5.45 41.4 2.8 7.06 32.0 8.4 2.80 45.9 3.1 1.58 36.8 9.8 4.01 52.9 3.6 2.22 40.3 10.9 5.10 58.0 4.0 2.81 4-PIPE SYSTEM 5 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 13.1 3.4 1.01 17.2 1.2 0.94 17.2 4.7 2.11 23.2 1.6 1.88 21.8 6.0 3.50 28.5 1.9 2.97 25.0 7.1 5.30 33.5 2.3 4.47 29.3 8.2 2.95 40.1 2.7 6.71 34.4 9.6 4.21 44.5 3.0 1.60 39.7 11.3 6.03 51.2 3.5 2.25 42.2 11.8 4.02 56.2 3.8 2.77

Model HHP06 HHP08 HHP10 HHP12 HHP14 HHP16 HHP18 HHP20

Total MBH 14.4 20.3 25.4 26.3 32.5 38.6 45.2 45.8

Model HHP06 HHP08 HHP10 HHP12 HHP14 HHP16 HHP18 HHP20

Total MBH 9.2 13.3 17.1 20.7 21.3 25.4 30.0 33.5

Model HHP06 HHP08 HHP10 HHP12 HHP14 HHP16 HHP18 HHP20

Total MBH 18.2 21.4 27.3 33.0 40.5 43.9 51.5 57.2

Model HHP06 HHP08 HHP10 HHP12 HHP14 HHP16 HHP18 HHP20

Total MBH 13.9 19.6 24.5 25.4 31.3 37.1 43.5 44.1

Model HHP06 HHP08 HHP10 HHP12 HHP14 HHP16 HHP18 HHP20

Total MBH 19.4 24.8 31.6 37.7 42.6 50.5 58.8 61.7

Model HHP06 HHP08 HHP10 HHP12 HHP14 HHP16 HHP18 HHP20

Total MBH 17.5 20.5 26.2 31.5 38.7 42.0 49.3 54.7

Model HHP06 HHP08 HHP10 HHP12 HHP14 HHP16 HHP18 HHP20

Total MBH 19.8 27.2 34.5 37.8 46.5 54.8 60.8 67.1

Model HHP06 HHP08 HHP10 HHP12 HHP14 HHP16 HHP18 HHP20

Total MBH 17.0 23.7 30.3 35.8 41.0 48.2 56.4 59.3

Performance Data

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high fan speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V70

Fan Coils Horizontal High Output HHP Performance Data


Performance Data (continued)

Nominal Air Volumes cfm (1) Model High Med Low HHP06 717 562 482 HHP08 877 701 514 HHP10 1113 877 696 HHP12 1209 1006 770 HHP14 1477 1107 803 HHP16 1723 1177 824 HHP18 1947 1616 1273 HHP20 2097 1744 1359

Model HHP06 HHP08 HHP10 HHP12 HHP14 HHP16 HHP18 HHP20

Air Volume (cfm) Vs External Static Pressure in wg (2) 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 693 667 638 607 573 537 499 459 417 845 812 453 745 709 672 631 585 532 1061 1016 977 938 899 856 809 757 701 1165 1115 1061 1005 948 892 835 779 723 1423 1385 1353 1315 1262 1191 1103 1003 901 1648 1585 1526 1464 1396 1320 1232 1135 1027 1863 1783 1705 1629 1553 1475 1392 1301 1198 2024 1956 1889 1820 1747 1666 1576 1474 1359

0.50 375 470 641 664 810 911 1081 1230

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

2. Air volumes at alternative external static pressures are based at high fan speed.

Model HHP06 HHP08 HHP10 HHP12 HHP14 HHP16 HHP18 HHP20

Motor HP Total AMPS 1/5 3.20 1/5 3.20 1/5 3.20 1/5 3.20 2 x 1/5 2 x 3.2 2 x 1/5 2 x 3.2 2 x 1/5 2 x 3.2 2 x 1/5 2 x 3.2

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/60Hz.

Performance Data

V71

Fan Coils Horizontal High Output HHE Dimensions


Horizontal High Output Series (continued) Motor voltage suitable for 208V, 230V or 277V/1Ph/ 60Hz power supplies. Motor in-line quick disconnect. Remote thermostat options include: - Basic electromechanical model - Electronic I model with LED indication. - Deluxe electronic II model with LCD display. - Modulated control model. Thermostat and Accessories (refer to Accessories on page V83 for details). Single power supplies disconnect switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. HW standby electric heater auto changeover switch. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel. - Double wall construction consisting of outer and inner skins. Condensate pan mastic coating applicable to the inside of the condensate pans for a prolonged life. Condensate pan overow safety switch. Secondary overow condensate water connection. Bottom or rear return air Access panel fasteners: - Philips head screws. - Tamper proof fasteners. - Quarter turn fasteners.

HHE Exposed Cabinet


Factory assembled, horizontal blowthru, high-output HHE fan coils are designed for exposed ceiling installations free blowing into the space suitable for industrial and commercial applications.

Standard Features Include: Performance ARI Certied to Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. Cabinet components fabricated of 18GA G90 galvanized Unpainted cabinet. Cabinet liner in -inch dual-density berglass. High-eciency 3-row coil suitable for a 2-pipe system. Coil manual air vent. 1-Inch thick disposable lter. Multi-speed motor(s) of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blower(s) of the whisper quite type. Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally protected on the outside (Consult TITUS for availability). 1-Inch discharge grille air anges. 1-Inch return air anges. Anti-vibration mounts for eld installation. Optional Features Include: 4-, 5- And 6-row coils for 2-pipe systems. Single block coil with 2, 3, 4 and 5 rows CW with 1 row re-heat coils for 4-pipe system applications (6 rows max). Single block coil with 2, 3 and 4 rows CW with 2 rows re-heat for 4-pipe system applications (6 rows max). Automatic coil air vents. LH or RH pipe connections entry. Filter option include: - 1-inch high-eciency pleated lters. - 1-inch washable lters. Bottom or rear return air and lter location.

HHE

A Participating Corporation in the ARI 440 Certication Program

V72

Fan Coils Horizontal High Output HHE Dimensions Dimensions


HHE Exposed Cabinet
TOP VIEW 2 C 1 2

2 27 5

6 7 1 5 1 8 9 10 1 FRONT VIEW - STANDARD GRILLE 1 SIDE VIEW 3 1 1

B A - 2 A

19

11

14

3 35/16 30

Note: Right hand unit with duct ange shown.

1. 2. 3. 4.

Return Air Flange Filter Access panel Motor/Blower(s) Assemby

5. Condensate Connection O.D. 6. Condensate Tray (Double Wall optional) 7. Coil Connections (2-Pipe Shown) 8. Hanging Points
Dimensions (inches) C 20 25 28 33 37 41 46 50

9. Coil 10. Supply Air Flange

Model HHE06 HHE08 HHE10 HHE12 HHE14 HHE16 HHE18 HHE20 A 29 34 37 42 46 50 55 59 B 13 18 21 26 30 34 39 43

Approx. Weight D Filter (pounds) 22x16x1 120 27x16x1 132 30x16x1 135 35x16x1 156 39x16x1 200 43x16x1 230 48x16x1 248 52x16x1 262

Dimensions

All dimensions are in inches.

V73

Fan Coils Horizontal High Output HHE Performance Data Performance Data
HHE Exposed Cabinet
2-PIPE SYSTEM 3 Rows Cooling 3 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 12.0 2.9 2.55 47.4 3.2 2.42 15.9 4.1 5.52 62.0 4.2 4.58 19.9 5.1 8.94 76.7 5.2 7.28 21.4 5.3 1.98 85.4 5.8 1.95 26.1 6.5 3.12 103.0 7.0 2.96 30.7 7.7 4.56 119.6 8.2 4.15 35.3 9.0 6.59 136.9 9.3 5.74 37.0 9.1 3.03 146.4 10.0 3.06 2-PIPE SYSTEM 4 Rows Cooling 4 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 13.9 3.6 5.17 54.9 3.7 4.21 16.8 4.3 1.45 68.7 4.7 1.39 21.3 5.5 2.41 85.6 5.8 2.23 24.6 6.6 3.77 98.9 6.7 3.17 30.0 8.1 5.90 118.2 8.1 4.80 33.7 8.8 3.04 135.0 9.2 2.85 38.8 10.3 4.35 154.2 10.5 3.90 42.5 11.4 5.54 168.0 11.5 4.79 2-PIPE SYSTEM 5 Rows Cooling 5 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 13.8 3.5 1.09 56.8 3.9 1.04 18.2 5.0 2.29 72.2 5.0 1.89 23.0 6.3 3.78 91.4 6.2 3.03 26.4 7.5 5.80 103.6 7.1 4.24 30.8 8.5 3.17 123.5 8.4 2.67 36.2 10.1 4.59 143.7 9.8 3.75 41.7 11.7 6.51 163.9 11.2 5.11 44.3 12.3 4.33 176.4 12.0 3.73 2-PIPE SYSTEM 6 Rows Cooling 6 Rows Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 14.4 4.0 1.55 58.9 4.0 1.29 18.9 5.4 3.16 75.1 5.1 2.31 23.9 6.9 5.20 94.1 6.4 3.73 26.2 7.5 2.71 104.4 7.1 2.10 32.0 9.3 4.25 126.7 8.6 3.20 37.6 10.9 6.10 147.5 10.1 4.49 42.0 12.1 4.50 166.4 11.4 3.59 45.9 13.4 5.65 180.7 12.3 4.38 4-PIPE SYSTEM 2 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 8.8 1.8 0.77 18.8 1.3 1.06 11.7 2.7 1.74 25.5 1.7 2.15 14.7 3.4 2.92 31.4 2.1 3.37 17.1 4.1 4.70 36.9 2.5 5.13 19.2 4.3 1.05 44.3 3.0 7.72 22.5 5.1 1.54 48.9 3.3 1.54 26.0 6.0 2.26 56.4 3.8 2.19 28.5 6.7 2.92 61.9 4.2 2.78 4-PIPE SYSTEM 3 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 11.5 2.8 2.40 18.3 1.2 1.03 15.2 3.9 5.17 24.8 1.7 2.07 19.0 4.9 8.39 30.5 2.1 3.25 20.5 5.1 1.85 35.8 2.4 4.89 25.0 6.2 2.91 42.9 2.9 7.39 29.3 7.4 4.26 47.4 3.2 1.59 33.7 8.7 6.14 54.7 3.7 2.25 35.4 8.8 2.82 60.0 4.1 2.78 4-PIPE SYSTEM 4 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 13.2 3.5 4.80 17.7 1.2 0.99 16.0 4.1 1.34 23.9 1.6 1.96 20.2 5.2 2.24 29.5 2.0 3.09 23.3 6.3 3.48 34.6 2.4 4.67 28.5 7.7 5.45 41.4 2.8 7.06 32.0 8.4 2.80 45.9 3.1 1.58 36.8 9.8 4.01 52.8 3.6 2.22 40.3 10.9 5.10 58.0 4.0 2.81 4-PIPE SYSTEM 5 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH gpm ft wg MBH gpm ft wg 13.1 3.4 1.01 17.2 1.2 0.94 17.2 4.7 2.11 23.2 1.6 1.88 21.8 6.0 3.50 28.6 1.9 2.97 25.0 7.1 5.30 33.5 2.3 4.47 29.4 8.2 2.95 40.1 2.7 6.71 34.4 9.6 4.21 44.5 3.0 1.60 39.7 11.3 6.03 51.2 3.5 2.25 42.1 11.8 4.02 56.2 3.8 2.77

Model HHE06 HHE08 HHE10 HHE12 HHE14 HHE16 HHE18 HHE20

Total MBH 14.4 20.3 25.4 26.3 32.5 38.6 45.2 45.8

Model HHE06 HHE08 HHE10 HHE12 HHE14 HHE16 HHE18 HHE20

Total MBH 9.2 13.3 17.0 20.7 21.3 25.4 30.0 33.5

Model HHE06 HHE08 HHE10 HHE12 HHE14 HHE16 HHE18 HHE20

Total MBH 18.2 21.4 27.4 33.0 40.5 43.9 51.5 57.1

Model HHE06 HHE08 HHE10 HHE12 HHE14 HHE16 HHE18 HHE20

Total MBH 13.9 19.6 24.5 25.4 31.3 37.1 43.5 44.1

Model HHE06 HHE08 HHE10 HHE12 HHE14 HHE16 HHE18 HHE20

Total MBH 17.8 24.9 31.6 37.6 46.6 50.5 58.8 61.7

Model HHE06 HHE08 HHE10 HHE12 HHE14 HHE16 HHE18 HHE20

Total MBH 17.5 20.5 26.2 31.5 38.7 42.0 49.3 54.6

Model HHE06 HHE08 HHE10 HHE12 HHE14 HHE16 HHE18 HHE20

Total MBH 19.9 27.2 34.5 37.8 46.5 54.8 60.8 67.1

Model HHE06 HHE08 HHE10 HHE12 HHE14 HHE16 HHE18 HHE20

Total MBH 17.0 23.7 30.3 35.8 41.0 48.2 56.4 59.3

Performance Data

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high an speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V74

Fan Coils Horizontal High Output HHE Performance Data


Performance Data (continued)

Nominal Air Volumes cfm (1) Model High Med Low HHE06 717 562 482 HHE08 877 701 514 HHE10 1113 877 696 HHE12 1209 1006 770 HHE14 1477 1107 803 HHE16 1723 1177 824 HHE18 1947 1616 1273 HHE20 2097 1744 1359

Model HHE06 HHE08 HHE10 HHE12 HHE14 HHE16 HHE18 HHE20

Air Volume (cfm) Vs External Static Pressure in wg (2) 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 693 667 638 607 573 537 499 459 417 845 812 453 745 709 672 631 585 532 1061 1016 977 938 899 856 809 757 701 1165 1115 1061 1005 948 892 835 779 723 1423 1385 1353 1315 1262 1191 1103 1003 901 1648 1585 1526 1464 1396 1320 1232 1135 1027 1863 1783 1705 1629 1553 1475 1392 1301 1198 2024 1956 1889 1820 1747 1666 1576 1474 1359

0.50 375 470 641 664 810 911 1081 1230

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

2. Air volumes at alternative external static pressures are based at high fan speed.

Model HHE06 HHE08 HHE10 HHE12 HHE14 HHE16 HHE18 HHE20

Motor Total HP AMPS 1/5 3.20 1/5 3.20 1/5 3.20 1/5 3.20 2 x 1/5 2 x 3.2 2 x 1/5 2 x 3.2 2 x 1/5 2 x 3.2 2 x 1/5 2 x 3.2

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/60Hz.

Performance Data

V75

Fan Coils Horizontal High Output Specications Suggested Specications


Fan Coils
Horizontal High Output Standard Congurations 1. Furnish and install TITUS models HHC, HHP and HHR horizontal high output fan coils of sizes and capacities shown on the plans to meet prevailing cooling and heating requirements. 2. Fan coils shall be performance certied to ARI Standard 440. 3. Units shall be wired in compliance with ANSI/UL 1995 Standard and listed with ETL. 4. Fan coils shall be sound tested in accordance with ARI Standard 260 for ducted units and ARI Standard 350 for non-ducted units. Manufacturer shall provide these dB ratings on request for each model specied. 5. Unit casing shall be 18-gauge, zinc coated, phosphate treated, G90 galvanized steel. 6. High-eciency, 3-row coil shall be suitable for a 2-pipe system. Coils shall be manufactured with aluminum ns mechanically bonded to seamless copper tubes. The copper tubes shall be -inch OD with a wall thickness of 0.017inch which comply with ASTM B-75. The ns shall be waved with ripple edges for superior eciency with a thickness of 0.045-inch and spaced at 10 fpi. All coils shall be leak tested with 100% helium to ensure a leak free coil. All coils shall be shipped with a safety air pressure of 100 - 125 psi to guarantee a leak free arrival at the nal destination. 7. Unit pipe entry location shall be in accordance with the project schedule. 8. Coils shall be installed with manual Schrader type air vents with a sealing cap and be located at the highest point of the coil. The cap shall have a dual purpose, to seal any potential water leakage in the eventuality of Schrader valve failure and as a service tool for the extraction/insertion of the internal Schrader valve. 9. Standard lters (HHP and HBE only) shall be 1-inch nominal thickness of the disposable type with a one-piece moisture resistant chipboard frame to eliminate corner separations. The spun glass ltering media shall be bonded with a resinous agent providing rigidity and resistance to media compression and meets UL class 2. 10. Cabinets/plenum (HBP and HBE only) shall be lined with -inch dual-density berglass with a density of 1.5lbs/ft3 and 4.0lbs/ft3 for the face meeting NFPA 90A and 90B (appliances), NFPA 255, UL 181, UL723 and ASTM E84. 11. Motors shall be multi-speed of the permanent split capacitor type (PSC) and be directly coupled to the centrifugal fan blower. Motor shall be suitable for a power supply of 115V/1Ph/60Hz and shall be internally protected with an automatic thermal overload. Motor shaft shall be supported by sleeve bearings of the permanently lubricated type for the full life expectancy of the motor. All motors shall be directly mounted to the fan blower and be isolated from the unit casing by three resilient anti-vibration mounts. 12. Direct-driven fan shall be of the whisper quite type, double width double inlet (DWDI) forward curved statically and dynamically balanced at the factory. The fan wheel and casing shall be constructed of galvanized steel. 13. Electric components shall be wired to a single control panel for single point power supply. Wiring exposed to the outside of the units shall be installed in conduits to meet UL 1995 safety requirements. 14. Condensate pans shall be singlewall 18-gauge G90 galvanized steel welded at the corners, thermally protected on the outside with re and smoke rated -inch high-density insulation to prevent condensation. The factory installed -inch OD sweat copper condensate connection shall be located at the lowest point of the condensate pan to ensure all water drains from the condensate pan (Consult TITUS for availability). 15. Discharge air ange shall be 1inch to facilitate the connection of eld ducts. 16. Return air anges (HHP and HHE only units) shall be 1-inch to facilitate the connection of eld ducts. 17. Four (4) anti-vibration rubber mountings shall be provided for eld installation in order to isolate any cabinet vibrations from the building structure.

Specications

V76

Fan Coils Horizontal High Output Specications


Suggested Specications (continued) Thermostat and Accessories Refer to Accessories on page V83. Disconnect switch and Fuses Units shall be wired for single power supply with a disconnect switch and fuse(s) to match the unit full maximum circuit ampacity (MCA) in line with UL 1995. 2-Pipe Heat/Cool Auto Changeover Switch A mechanical changeover switch shall be supplied on 2-pipe systems to automatically change over the operation of the thermostat for summer and winter modes. Electric Heater and Accessories 1. Electric heaters shall be of the wound type mounted in a metal frame and supported by ceramic rings and terminals. Electric heaters shall be installed on the blower discharge side for better heat dissipation and shall include an automatic reset high limit cutout and contactor. 2. 2-pipe standby electric heating - heaters shall be installed and pre-wired as standby heating for the eventuality of a failure of the primary hot water (HW) system. A changeover sensor shall be installed in each unit and the changeover between the failed hot water system and the standby electric heater shall be automatic. Chilled and Hot Water Valve Controls Refer to Accessories on page V83. Condensate Pan and Accessories 1. Condensate pan shall be single wall manufactured in 20-gauge 304 stainless steel and shall be thermally protected on the outside with re and smoke rated -inch high-density insulation to prevent condensation. The factory installed -inch OD sweat copper condensate connection shall be located at the lowest point of the condensate pan to ensure that all water is drained from the condensate pan (Consult TITUS for availability), or 2. Condensate pan shall be double wall construction consisting of an outer and inner skin. The outer skin shall be manufactured of 18-gauge G90 galvanized sheet metal wrapped around the inner skin with 1-inch thermal insulation between both skins to prevent condensation. The inner skin of the double wall condensate pan shall be of 18-gague G90 galvanized sheet metal, or 3. Condensate pan shall be double wall construction consisting of an outer and inner skin. The outer skin shall be manufactured of 18-gauge G90 galvanized sheet metal wrapped around the inner skin with 1-inch thermal insulation between both skins to prevent the formation of condensation. The inner skin of the double wall condensate pan shall be of 20-gauge 304 stainless steel galvanized sheet metal. 4. An automatic safety overow switch shall be installed in the condensate pan and shall prevent the operation of the unit electric system if an overow status is detected. 5. A condensate water safety overow connection shall be provided. 6. A mastic coating shall be applied to the inside of the condensate pan for a prolonged life. Access Panel and Accessories (HHE only) 1. Access panel security fasteners shall be tamperproof, which requires a special tool to access the units, or 2. Return air/access panel security fasteners shall be of the quarter turn type, to facilitate the removal of the access panel.

Fan Coils
Horizontal High Output Optional Congurations Cooling and Heating Coil 1. Shall be high-eciency 4-, 5- and 6-row coils suitable for 2-pipe systems, or 2. High-eciency single block with 2, 3,4 and 5 rows chilled water (CW) with 1-row re-heat coil suitable for 4-pipe system applications, or 3. High-eciency single block with 2, 3 and 4 rows chilled water (CW) with 2-row re-heat coil suitable for 4-pipe system applications. 4. Coils shall be installed with an automatic air vent capable of operation in chilled or hot water systems to a maximum of 125 psi. Filter 1. Filter shall be 1-inch pleated lter with an average atmospheric dust spot eciency range of 20 - 30% per ASHRAE Standard 52.1 test method, or 2. Filter shall be 1-inch washable lter consisting of synthetic bers coated with a special resin, then baked together at a high temperature resulting in a tough and springy, thoroughly bonded, nearly rigid air ltration media. Washable lters shall have a longer service life, better structural integrity as well as being completely odor free. 3. A spare set of lters shall be available for replacement after the commissioning of the unit and prior to the handover of the project. Cabinet Insulation Cabinet liners shall be 1-inch dualdensity berglass with a density of 1.5lbs/ft3 and 4.0lbs/ft3 for the face meeting NFPA 90A and 90B (appliances) and NFPA 255 with less than 25 ame and less than 50 smoke spread, UL 181, UL723 and ASTM E84. Motor and Motor Accessories 1. Motors shall be suitable for 115V/1Ph/60Hz or 208V/1Ph/60Hz or 230V/1Ph/60Hz or 277V/1Ph/ 60Hz power supplies (delete as applicable). 2. A motor in-line quick disconnect shall be installed to facilitate the removal/replacement of motor (HHP and HHE units only).

Specications

V77

Fan Coils Vertical High Output VHC Description

Vertical High Output Series


VHC Concealed Closet
Factory assembled vertical drawthru, high-output VHC fan coils are designed for ducted closet installations suitable for industrial and commercial applications. Standard Features Include: Performance ARI Certied to Standard 440. ETL-Listed. Constructed in compliance with ANSI/ UL 1995 Standard. All casing sheet metal components fabricated of 18GA G90 galvanized steel. High-eciency 3-row coil suitable for a 2-pipe system. Coil manual air vent. 1-Inch thick disposable lter. Cabinet liner in -inch dual-density berglass. Multi-speed motor of the permanent split capacitor (PSC) type. Double width double Inlet (DWDI) direct driven blowers of the whisper quite type. Controls installed in a single control box suitable for single power supply. Single wall condensate pan in galvanized steel, thermally protected on the outside. 1-inch discharge air ange for duct applications.

Optional Features Include: 4-, 5- And 6-row coils for 2-pipe systems, or Single block coil with 2, 3, 4 and 5 rows CW with 1 row re-heat coils for 4-pipe system applications (6 rows max). Single block coil with 2, 3 and 4 rows CW with 2 rows re-heat for 4-pipe system applications (6 rows max). LH or RH pipe connections entry. Automatic coil air vents. Filter option include: - 1-inch high-eciency pleated lters. - 1-inch washable lters. Cabinet liner in 1-inch dualdensity berglass. Motor voltage suitable for 208V, 230V or 277V/1Ph/ 60Hz power supplies. Motor in-line quick disconnect. Thermostat and Accessories (refer to Accessories on page V83 for details). Single power supplies disconnect switch and fuses. Automatic 2-pipe changeover switch for heating and cooling applications. Electric heaters. HW standby electric heater auto changeover switch. Valve Packages (refer to Accessories on page V83 for details). Condensate pan options: - Single wall condensate pan manufactured in 20GA 304 Stainless Steel. Condensate pan mastic coating applicable to the inside of the condensate pan for a prolonged life. Condensate pan safety overow switch.

VHC

A Participating Corporation in the ARI 440 Certication Program

V78

Fan Coils Vertical High Output VHC Dimensions Dimensions


VHC Concealed Closet
TOP VIEW B 11 2 11 2 E 1

2 2 4 7

FRONT VIEW 5

Left Side 3 Right Side 5 10 12 6

SIDE VIEW

9 41 7 7 6

6 A

8 D

Note: Right hand unit shown.

1. Cold Water Coil Connections - 2/4 pipe supply and return O.D. = C 2. Hot Water Coil Connections - 4 pipe supply and return O.D. =

3. 4. 5. 6.

Supply Duct Collar Electrical Control Box Motor/Blower(s) Assemby Coil

7. Filter 8. Condensate Connection O.D. 9. Electrical Knockout Entires

Model VHC06 VHC08 VHC10 VHC12 VHC14 VHC16 VHC18 VHC20 A 23 28 32 37 42 47 52 56 B N/A N/A N/A N/A 27 31 35 39

Dimensions (inches) C D 11 14 16 18 21 23 26 28

Dimensions

Approx. Weight E 5 8 10 12 7 8 8 8 Filter (pounds) 15x17x1 150 15x20x1 170 15x23x1 195 15x28x1 200 15x32x1 240 15x36x1 260 15x41x1 268 15x45x1 280

All dimensions are in inches.

V79

Fan Coils Vertical High Output VHC Performance Data Performance Data
VHC Concealed Closet
2-PIPE SYSTEM 3 Rows Cooling 3 Rows Heating Sensible Flow PD Sensible Flow PD MBH GPM ft WG MBH GPM ft WG 12.3 3.0 3.32 48.4 3.3 3.07 16.8 4.4 7.88 65.2 4.4 6.23 21.7 5.8 14.52 83.3 5.7 10.88 23.7 6.2 3.28 93.4 6.4 2.84 29.4 7.8 5.54 114.7 7.8 4.55 34.8 9.4 8.45 134.9 9.2 6.67 40.0 10.9 12.03 154.0 10.5 9.19 42.3 11.3 5.49 165.1 11.3 4.71 2-PIPE SYSTEM 4 Rows Cooling 4 Rows Heating Sensible Flow PD Sensible Flow PD MBH GPM ft WG MBH GPM ft WG 14.2 3.8 6.71 55.9 3.8 5.29 17.8 4.7 2.04 71.8 4.9 1.80 23.2 6.3 3.83 92.0 6.3 3.13 25.6 6.9 2.08 103.4 7.1 1.85 32.0 8.8 3.55 127.0 8.7 2.94 38.0 10.6 5.35 149.2 10.2 4.26 43.6 12.3 7.57 170.2 11.6 5.82 46.4 13.0 5.01 183.2 12.5 4.21 2-PIPE SYSTEM 5 Rows Cooling 5 Rows Heating Sensible Flow PD Sensible Flow PD MBH GPM ft WG MBH GPM ft WG 14.0 3.6 1.36 57.7 3.9 1.25 19.0 5.3 3.15 75.9 5.2 2.41 24.7 7.1 5.77 97.0 6.6 4.18 27.3 7.8 3.08 108.3 7.4 2.37 33.9 9.8 5.11 132.8 9.1 3.76 39.0 11.3 4.00 154.3 10.5 3.17 44.9 13.1 5.61 175.9 12.0 4.30 49.0 14.4 6.99 190.9 13.0 5.23 2-PIPE SYSTEM 6 Rows Cooling 6 Rows Heating Sensible Flow PD Sensible Flow PD MBH GPM ft WG MBH GPM ft WG 14.7 4.1 1.95 59.6 4.1 1.56 19.6 5.8 4.25 77.3 5.3 2.93 24.4 7.1 2.67 97.3 6.6 2.01 28.0 8.4 4.02 109.4 7.5 2.78 33.8 10.1 3.40 133.0 9.1 2.54 40.1 12.1 5.10 156.0 10.6 3.65 46.0 13.9 7.09 177.4 12.1 4.93 50.1 15.3 8.81 192.2 13.1 5.99 4-PIPE SYSTEM 2 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH GPM ft WG MBH GPM ft WG 9.0 1.9 1.02 19.4 1.3 1.36 12.5 3.0 2.63 27.4 1.9 3.02 16.2 4.0 5.00 35.2 2.4 5.34 19.1 4.9 8.25 39.6 2.7 1.18 22.0 5.3 1.97 48.9 3.3 1.89 26.2 6.5 3.07 57.8 3.9 2.83 30.2 7.6 4.44 66.5 4.5 4.00 33.1 8.4 5.71 72.9 5.0 5.06 4-PIPE SYSTEM 3 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH GPM ft WG MBH GPM ft WG 11.7 2.9 3.13 18.8 1.3 1.32 16.0 4.2 7.38 26.5 1.8 2.90 20.7 5.6 13.60 34.0 2.3 5.11 22.6 5.9 3.07 38.3 2.6 1.17 28.0 7.5 5.17 47.3 3.2 1.91 33.3 9.0 7.89 55.9 3.8 2.85 38.2 10.5 11.22 64.3 4.4 4.01 40.3 10.8 5.12 70.5 4.8 4.98 4-PIPE SYSTEM 4 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH GPM ft WG MBH GPM ft WG 13.4 3.6 6.16 18.2 1.2 1.26 16.8 4.5 1.88 25.6 1.7 2.74 21.9 6.0 3.53 32.9 2.2 4.83 24.3 6.6 1.93 37.0 2.5 1.14 30.3 8.4 3.24 45.7 3.1 1.87 36.1 10.2 4.96 54.0 3.7 2.79 41.3 11.8 6.97 62.0 4.2 3.91 43.9 12.3 4.56 68.0 4.6 4.84 4-PIPE SYSTEM 5 Rows Cooling 1 Row Heating Sensible Flow PD Sensible Flow PD MBH GPM ft WG MBH GPM ft WG 13.3 3.5 1.27 17.7 1.2 1.20 18.1 5.1 2.91 24.8 1.7 2.62 23.5 6.8 5.37 31.8 2.2 4.62 25.9 7.5 2.84 35.8 2.4 1.14 32.2 9.4 4.72 44.2 3.0 1.86 37.1 10.8 3.69 52.2 3.6 2.71 42.7 12.5 5.17 60.0 4.1 3.79 46.5 13.8 6.45 65.7 4.5 4.76

Model VHC06 VHC08 VHC10 VHC12 VHC14 VHC16 VHC18 VHC20

Total MBH 14.9 22.0 29.0 30.9 39.1 47.0 54.6 56.4

Model VHC06 VHC08 VHC10 VHC12 VHC14 VHC16 VHC18 VHC20

Total MBH 9.7 14.9 19.9 24.5 26.5 32.3 38.0 42.2

Model VHC06 VHC08 VHC10 VHC12 VHC14 VHC16 VHC18 VHC20

Total MBH 18.9 23.4 31.3 34.6 44.2 53.0 61.7 64.9

Model VHC06 VHC08 VHC10 VHC12 VHC14 VHC16 VHC18 VHC20

Total MBH 14.4 21.2 27.9 29.8 37.6 45.2 52.5 54.3

Model VHC06 VHC08 VHC10 VHC12 VHC14 VHC16 VHC18 VHC20

Total MBH 18.3 26.8 35.3 39.3 49.3 56.4 65.5 72.0

Model VHC06 VHC08 VHC10 VHC12 VHC14 VHC16 VHC18 VHC20

Total MBH 18.0 22.4 29.9 33.2 42.1 50.9 58.9 61.7

Model VHC06 VHC08 VHC10 VHC12 VHC14 VHC16 VHC18 VHC20

Total MBH 20.4 28.9 35.6 42.1 50.4 60.4 69.8 76.4

Model VHC06 VHC08 VHC10 VHC12 VHC14 VHC16 VHC18 VHC20

Total MBH 17.6 25.6 33.9 37.5 47.2 54.0 62.7 68.9

Performance Data

1. Standard basic unit. 2. All ratings are based at sea level altitude, nominal air volumes at 0 external static pressure and with water as the cooling uid.

3. Cooling capacities are based on 80F DB/67F WB entering air, 45F entering water, 10F water temperature rise and high fan speed.

4. Heating capacities are based on 70F DB entering air temperature, 180F entering hot water, 30F water temperature drop and high fan speed.

V80

Fan Coils Vertical High Output VHC Performance Data


Performance Data (continued)

Nominal Air Volumes cfm (1) Model High Med Low VHC06 717 562 482 VHC08 877 701 514 VHC10 1113 877 696 VHC12 1209 1006 770 VHC14 1477 1107 803 VHC16 1723 1177 824 VHC18 1947 1616 1273 VHC20 2097 1744 1359

Air Volume (cfm) Vs External Static Pressure in WG (2) Model 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 VHC06 693 667 638 607 573 537 499 459 417 VHC08 845 812 779 745 709 672 631 585 532 VHC10 1061 1016 977 938 899 856 809 757 701 VHC12 1165 1115 1061 1005 948 892 835 779 723 VHC14 1423 1385 1353 1315 1262 1191 1103 1003 901 VHC16 1648 1585 1526 1464 1396 1320 1232 1135 1027 VHC18 1863 1783 1705 1629 1553 1475 1392 1301 1198 VHC20 2024 1956 1889 1820 1747 1666 1576 1474 1359

0.50 375 470 641 664 810 911 1081 1230

1. Nominal air volume ratings are based on a 2-row coil at sea level altitude.

2. Air volumes at alternative external static pressures are based at high fan speed.

Model VHC06 VHC08 VHC10 VHC12 VHC14 VHC16 VHC18 VHC20

Motor Total HP AMPS 1/5 3.20 1/5 3.20 1/5 3.20 1/5 3.20 2 x 1/5 2 x 3.2 2 x 1/5 2 x 3.2 2 x 1/5 2 x 3.2 2 x 1/5 2 x 3.2

1. Electric ratings are based on units suitable for a power supply of 115V/1Ph/60Hz.

Performance Data

V81

Fan Coils Vertical High Output Specications Suggested Specications


Fan Coils
Vertical High Output Standard Congurations 1. Furnish and install TITUS model VHC vertical high-output fan coils of sizes and capacities shown on the plans to meet prevailing cooling and heating requirements. 2. Fan coils shall be performance certied to ARI Standard 440. 3. Units shall be wired in compliance with ANSI/UL 1995 Standard and listed with ETL. 4. Fan coils shall be sound tested in accordance with ARI Standard 260 for ducted units and ARI Standard 350 for non-ducted units. Manufacturer shall provide these dB ratings on request for each model specied. 5. Unit casing shall be 18-gauge, zinc coated, phosphate treated, G90 galvanized steel. 6. High-eciency, 3-row coil shall be suitable for a 2-pipe system. Coils shall be manufactured with aluminum ns mechanically bonded to seamless copper tubes. The copper tubes shall be -inch OD with a wall thickness of 0.014inch which comply with ASTM B-75. The ns shall be waved with ripple edges for superior eciency with a thickness of 0.0060-inch and spaced at 10 fpi. All coils shall be leak tested with 100% helium to ensure a leak free coil. All coils shall be shipped with a safety air pressure of 100 - 125 psi to guarantee a leak free arrival at the nal destination. 7. Unit pipe entry location shall be in accordance with the project schedule. 8. Coil shall be installed with manual Schrader type air vents with a sealing cap and be located at the highest point of the coil. The cap shall have a dual purpose, to seal any potential water leakage in the eventuality of Schrader valve failure and as a service tool for the extraction/insertion of the internal Schrader valve. 9. Filter shall be 1-inch nominal thickness of the disposable type with a one-piece moisture resistant chipboard frame to eliminate corner separations. The spun glass ltering media shall be bonded with a resinous agent providing rigidity and resistance to media compression and meets UL class 2. 10. Cabinet shall be lined with -inch dual-density berglass with a density of 1.5lbs/ft3 and 4.0lbs/ft3 for the face meeting NFPA 90A and 90B (appliances), NFPA 255, UL 181, UL723 and ASTM E84. 11. Motor(s) shall be multi-speed of the permanent split capacitor type (PSC) and be directly coupled to the centrifugal fan blower. Motor shall be suitable for a power supply of 115V/1Ph/60Hz and shall be internally protected with an automatic thermal overload. Motor shaft shall be supported by sleeve bearings of the permanently lubricated type for the full life expectancy of the motor. All motors shall be directly mounted to the fan blower and be isolated from the unit casing by three resilient anti-vibration mounts. 12. Direct-driven fan(s) shall be of the whisper quite type, double width double inlet (DWDI) forward curved statically and dynamically balanced at the factory. The fan wheel and casing shall be constructed of galvanized steel. 13. Electric components shall be wired to a single control panel for single point power supply. Wiring exposed to the outside of the units shall be installed in conduits to meet UL 1995 safety requirements. 14. Condensate pans shall be singlewall 18-gauge G90 galvanized steel welded at the corners, thermally insulated on the outside with -inch dual-density berglass with a density of 1.5lbs/ft3 and 4.0lbs/ft3 for the face meeting NFPA 90A and 90B (appliances), NFPA 255, UL 181, UL723 and ASTM E84 (Consult TITUS for availability). 15. The factory installed -inch OD sweat copper condensate connection shall be located at the lowest point of the condensate pan to ensure all water drains from the condensate pan. 16. Discharge air ange(s) shall be 1-inch to facilitate the connection of eld ducts.

Specications

V82

Fan Coils Vertical High Output Specications


Suggested Specications (continued) Thermostat and Accessories Refer to Accessories on page V83. Disconnect Switch and Fuses Units shall be wired for single power supply with a disconnect switch and fuse(s) to match the unit full maximum circuit ampacity (MCA) in line with UL 1995. 2-Pipe Heat/Cool Auto Changeover Switch A mechanical changeover switch shall be supplied on 2-pipe systems to automatically change over the operation of the thermostat for summer and winter modes. Electric Heater and Accessories 1. Electric heaters shall be of the wound type mounted in a metal frame and supported by ceramic rings and terminals. Electric heaters shall installed on the blower and coil discharge side for better heat dissipation and shall include an automatic reset high limit cut-out and contactor. 2. 2-pipe standby electric heating - heaters shall be installed and pre-wired as standby heating for the eventuality of a failure of the primary hot water (HW) system. A changeover sensor shall be installed in each unit and the changeover between the failed hot water system and the standby electric heater shall be automatic. Chilled and Hot Water Valve Controls Refer to Accessories on page V83. Condensate Pan and Accessories 1. Condensate pan shall be single wall manufactured in 20-gauge 304 stainless steel and shall be thermally protected on the outside with -inch dual-density berglass with a density of 1.5lbs/ft3 and 4.0lbs/ft3 for the face meeting NFPA 90A and 90B (appliances), NFPA 255, UL 181, UL723 and ASTM E84. 2. An automatic safety overow switch shall be installed in the condensate pan and shall prevent the operation of the unit electric system if an overow status is detected. 3. A mastic coating shall be applied to the inside of the condensate pan for a prolonged life.

Fan Coils
Vertical High Ouput Optional Congurations Cooling and Heating Coil 1. High-eciency 4-, 5- and 6-row coils suitable for 2-pipe systems, or 2. High-eciency single block with 2, 3, 4 and 5-rows chilled water (CW) with 1-row re-heat coil suitable for 4-pipe system applications, or 3. High-eciency single block with 2, 3 and 4 rows chilled water (CW) with 2-row re-heat coil suitable for 4-pipe system applications. 4. Coils shall be installed with an automatic air vent capable of operation in chilled or hot water systems to a maximum of 125psi. Filter 1. Filter shall be 1-inch pleated lter with an average atmospheric dust spot eciency range of 20 - 30% per ASHRAE Standard 52.1 test method or, 2. Filter shall be 1-inch washable lter consisting of synthetic bers coated with a special resin, then baked together at a high temperature resulting in a tough and springy, thoroughly bonded, nearly rigid air ltration media. Washable lters shall have a longer service life, better structural integrity as well as being completely odor free. 3. A spare set of lters shall be available for replacement after the commissioning of the unit and prior to the handover of the project. Cabinet Insulation Cabinet liners shall be 1-inch dualdensity berglass with a density of 1.5lbs/ft3 and 4.0lbs/ft3 for the face meeting NFPA 90A and 90B (appliances) and NFPA 255 with less than 25 ame and less than 50 smoke spread, UL 181, UL723 and ASTM E84. Motor and Motor Accessories 1. Motors shall be suitable for 115V/1Ph/60Hz or 208V/1Ph/60Hz or 230V/1Ph/60Hz or 277V/1Ph/ 60Hz power supplies (delete as applicable). 2. A motor in-line quick disconnect shall be installed to facilitate the removal/replacement of motor.

Specications

V83

Fan Coils Accessories Accessories


Thermostats Fan Speed Switch (RAB90) Simple fan speed switch shall have three speed levels and a switched output ON/OFF (to be used on all Vertical Basic Series Fan Coils when a thermostat is not required). Electronic I model (RCC) shall be electronic remote wall or unit mounted thermostat with LED indicators and shall include the following features: Temperature set-point control with dual set-point temperature scale (F/C) and adjustable min/max temperature mechanical limit stops; operational modes: o, normal, energy saving and frost protection; system o and 3-speed fan switch; fan continuous or temperature dependent operation; manual heat/cool temperature changeover control; heat/cool and fan on LED indication; on/o control valve(s) output; 24V control voltage, 50 or 60Hz; optional remote wall or duct sensor connection; and UL and cUL listed. Thermostat Accessories Thermostat shall be supplied with a remote duct mounted sensor (RCC, RDF and RLA models only). Thermostat shall be supplied with a remote wall mounted sensor (RCC, RDF and RLA models only).

Basic model (RAB) shall be electromechanical, remote wall thermostat, gas diaphragm based and shall include the following features: Temperature set-point control with dual set-point temperature scale (F/C) and adjustable min/max temperature mechanical limit stops; system o and 3-speed fan switch; heat/cool manual temperature switch; on/o control valve(s) output; fan auto or continuous selection; 24V thru 277V control voltage, 50 or 60Hz; and UL and cUL listed.

Thermostat shall be supplied with a wall mount plate (4.75 SQR) for covering unpainted wall areas or nonwallpaper areas.

Electronic II model (RDF) shall be electronic remote wall or unit mounted thermostat with LCD indication and shall include the following features: Operational modes: o, normal, energy saving and standby; system o and 3-speed fan switch; fan continuous or temperature dependent operation; automatic heat/cool temperature changeover control; min/max setpoint temperature limitation; setpoints or room temperature display; on/o control valve(s) output; 24V control voltage, 50 or 60Hz; optional remote duct or wall sensor connection; selectable installation and control parameters; and UL and cUL listed.

Thermostats shall be supplied with lockable covers to prevent unauthorized changes to the temperature set-points. Thermostat shall be suitable for 24V control voltage (all RCC, RDF and RLA thermostats must be 24V).

Accessories

Modulated model (RLA) Shall be an electronic remote wall mounted thermostat with modulated outputs, UL and cUL listed.

V84

Fan Coils Accessories


Accessories (continued) Motorized Control Valves Motorized control valves shall be 2- or 3-Way valve(s) with sweat or threaded connections and shall have the following features: Body and body trim made of brass; stem made of stainless steel ASTM A582 type 303 with Ethylene propylene sealing O-rings, suitable for water/glycol concentrations up to 50%; and operation between 34 to 230F. Maximum inlet pressure of 125 psig; metal-to-metal seat with a stroke of 1/10-inch and rated to ANSI Class 125, close-o ratings in accordance with ANSI/FCI 70-2, class rate ANSI Class III and mounting location shall be NEMA1 (interior only). Modulated actuators shall be suitable for 24V control voltage and a signal voltage of 0-10V; UL listed for plenums to UL 873; cUL certied to Canadian Standards C22.2 No 24-93; direct coupled installation without tools; manual override; visual position indication; 40 sec max running time; 1 /10-inch nominal stroke; 24lb nominal force; Operation temperature between 41 and 122F. Pressure and temperature test plugs shall have -inch MNPT thread, suitable for operation up to 325F and 1000 psi pressure. Test plugs shall be located in the return and supply CW and/or HW pipes to measure unit total pressure drop and/or unit water in/out temperatures.

All valve actuators shall be compatible with 2 or 3-Way valves. Valve Package Accessories Ball valves shall be manufactured of brass OT58-UNI-5705-65 with a chrome plated brass ball with Teon seals. The shaft shall be sealed via dual VITON O-rings and capable of operating at 325F and 600 psi pressure WOG. All ball valves shall be supplied with a memory stop actuator and be located in the inlet pipes to the fan coil unit.

Strainers shall be of forged brass ASTM B283, suitable for operation up to 325F and 600 psi pressure WOG. Mesh shall be #20 made of stainless steel and the mesh access cap shall be sealed with a VITON O-ring and the cap shall have a -inch NPT access port. Strainers shall be installed to the supply CW and/or HW pipes to avoid blockages on the unit water system components. Coil blow down drain valves shall be of the chromed plated ball type with Teon seals; dual VITON O-rings seal suitable for operation up to 325F and 600 psi pressure WOG. Valve connections shall be -inch MNPT and inch hose bib and cap. Blow down valves shall be installed at the lowest point of the coils to enable the evacuation of all water for system repairs and/or coil replacements.

Motorized Valve Actuators Valve actuators shall be ON/OFF or modulated, normally closed to the coil with spring return action for CW and HW applications or normally open to the coil for HW applications only and shall have the following features: ON/OFF actuators shall be suitable for 24, 120, 208 or 277V control voltage; UL listed for plenums to UL 873; cUL certied to Canadian Standards C22.2 No 24-93; direct coupled installation without tools; manual override; visual position indication; 40 sec max running time; 1/10-inch nominal stroke; 24lb nominal force; operation temperature between 41 and 122F and 0% to 90% relative humidity (non corrosive); NEMA 1 mounting location.

Accessories

Unions shall be of forged brass ASTM B283 with VITON O-rings installed in the return and supply CW and/or HW pipes to facilitate the connection or removal of the unit.

V85

Fan Coils Accessories


Accessories (continued) Valve Package Accessories (continued) Automatic water ow control valve shall be manufactured of forged brass ASTM B283, suitable for operation up to 325F and 600 psi pressure WOG. The automatic ow cartridge shall be removable and be accessible via forged brass cap sealed with VITON and EPDM O-rings. Auto ow control valves shall be installed with two pressure test plugs and be located in the return CW and/or HW pipes. The Auto Flow Control Valve(s) shall control the water ow in accordance with the project Fancoil coil schedule. Manual adjustable ow control valve shall br manufactured of forged brass ASTM B283 and be of the calibrated manual balancing valve type, modied venture ball valve with a union end and capable of operation at 325F, 600 psi pressure WOG with the following featues: Ball valve with chrome plated brass ball and Teon seals; Shaft sealed via dual VITON O-rings; Handle shall have a calibrated scale indicator and a stainless steel memory stop. Manual ow control valve shall be installed with two pressure test plugs and be located in the return CW and/or HW pipes. The Auto Flow Control Valve shall control the water ow in accordance with the project Fancoil coil schedule. Flexible Connectors Pipe exible connectors shall be re rated in compliance with ASTM E 8400 (NFPA 225, ANSI/UL 723 and UBC 8-1) with the following features: Operating pressure 400 psi @ 265F, ttings made of brass with NPSM swivel w/seal and MNPT; fabric reinforced EPDM core; stainless steel braid reinforcement; brass OT58 ttings; stainless steel ferrule; ber EPDM gasket. COMBO Accessories Valve package components shall be provided in single body COMBO package as follows: Ball valve + Strainer + Union and be installed in the supply side of the CW and/or HW coil, or Valve Package Connections Size Valve package connections shall be suitable for -inch in diameter copper piping for units up to and including sizes 08 (800 cfm nominal airows) with CW connections and units up to size 20 (2000 cfm nominal airow) for HW connections. All units sizes 10 (1000 cfm nominal airow) and above the CW connections shall be suitable for copper piping in -inch diameter. All drain water connections shall be suitable for copper piping -inch diameter.

Ball valve + Auto ow control valve + Union and installed in the return side of the CW and/or HW coil, or

Ball valve + Manual adjustable ow control valve + Union and be installed in the return side of the CW and/or HW coil.

Accessories