PERIODIC INSPECTION REPORT FOR AN ELECTRICAL INSTALLATION

REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - BS7671 [IEE WIRING REGULATIONS]


__________________________________________________________________________________________________________
|| DETAILS OF THE CLIENT
||
| Mr A A Jones, Mount Pleasant, Thrumbush Road, Aldershot, RG91 7BR
|
||__________________________________________________________________________________________________________ ||
|| Purpose for which this Report is required:
||
Insurance
|__________________________________________________________________________________________________________
|
|| DETAILS OF THE INSTALLATION
||
|| Occupier:
||
Mr A A Jones
|| Installation:
||
JonesAA
|| Address:
||
Mount Pleasant, Thrumbush Road, Aldershot, RG91 7BR
||
||
|| Description of Premises:
Domestic
||
|| Estimated age of the electrical installation:
30 years
||
|| Evidence of alterations or additions:
No
||
|| Date of last inspection:
Not known
Records are not available.
|
||__________________________________________________________________________________________________________ |||
|| EXTENT AND LIMITATIONS OF THE INSPECTION
||
| Extent of the electrical installation covered by this report
|
|| The full electrical installation
||
||
||
| Limitations
|
|| None
||
||
||
|| This inspection has been carried out in accordance with BS7671: 2001 (IEE Wiring Regulations), amended to Feb
||
|| 2002. Cables concealed within trunking and conduits, or cables and conduits concealed under floors, in roof
||
|| spaces and generally within the fabric of the building or underground have not been inspected.
|
||__________________________________________________________________________________________________________ |||
|| NEXT INSPECTION
||
|| I/We recommend that this installation is further inspected and tested after an interval of not more than 10
||
|| years, provided that any Observations marked as Requiring Urgent Attention are attended to without delay.
|
||__________________________________________________________________________________________________________ |||
|| DECLARATION
||
|| INSPECTED AND TESTED BY:
||
|| Name:
Tom Jackson
||
|| Position:
Test engineer
||
|| For and on behalf of:
Custom Maintenance Systems
||
| Address:
Unit 27
|
|
Lewes RoadIndustrial Estate
|
|
BRIGHTON
|
||
BN71 3XY
||
|| Phone:
01473 4141410
||
| NICEIC Enrolment No: 414141: NICEIC Branch Number: 301
|
|
|
|
|
|
|
|| Signature:
..................................................
Date: 8 Jan 2003
||
|__________________________________________________________________________________________________________ |
CERTIFICATE No: PER3140

Page 1 of 5

__________________________________________________________________________________________________________
|| SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS
|
||__________________________________________________________________________________________________________ |||
|| Earthing arrangements || Number and Type of Live ||
||
||
Nature of Supply Parameters
Supply
|
|
Conductors
|
| Protective Device |
|| TN-C
||
||
|| Characteristics ||
|| TN-S
*
|| ac
* dc
- || Nominal voltage U/Uo 230
V || Type
||
|| TN-C-S
|| 1-phase, 2-wire * 2-pole - || Nominal frequency
50
Hz || BS 1361 ||
|| TT
|| 2-phase, 3-wire 3-pole - || Prospective fault current
2.67
kA ||
||
|| IT
|| 3-phase, 3-wire other - || External loop impedance
0.09
ohm || Nominal current
||
||__________________________________________________________________________________________________________
Alternative source | 3-phase, 4-wire |
| rating 60 A
||
|
|
||__________________________________________________________________________________________________________
PARTICULARS OF INSTALLATION REFERRED TO IN THE CERTIFICATE
||
||
||
||
| Means of Earthing
Maximum Demand
|
|| Supplier's facility
|| Maximum demand (load) 60
||
*
Amps
||
|| _____
||
|| Installation earth
|
||
|
Details of Installation Earth Electrode
|
electrode
|
|
|
| Location
|
||__________________________________________________________________________________________________________
| Type
Electrode resistance to earth
ohm
||
||
||
||
Main Protective Conductors
||
| Earthing conductor
material: Copper
csa: 16
mm2
connection verified
|
|
|
| Main equipotential
material: Copper
csa: 10
mm2
connection verified
|
||
bonding conductor
||
||__________________________________________________________________________________________________________
Bonding to :
Water, Oil
||
||
||
||
Main Switch or Circuit Breaker
||
| BS and Type BS5419
No of Poles 2
Current rating 100
A
Voltage rating 500
V|
|
|
| Location
Hall cupboard
Fuse rating or setting
100
A
|
|
|
||__________________________________________________________________________________________________________
Rated residual operating current
100
mA, and operating time of 14
mS
||
||
||
| OBSERVATIONS AND RECOMMENDATIONS
|
||| Referring to the attached Schedule(s) of Inspection and Test Results, and subject to the limitations specified at the Extent
|||
|| and Limitations of the Inspection section.
||
||
||
|
No remedial work is required.
|
||
||
||
||
||
||
||
||
||
||
||
||
||
||
|| One of the following numbers, as appropriate, is to be allocated to each of the observations made above to indicate to the
||
|| person(s) responsible for the installation the action recommended
||
||
||
||
1 Requires urgent attention:
2 Requires improvement:
3 Requires further investigation
||
||
4 Does not comply with BS 7671: 2001 updated to Feb 2002. This does not imply that the electrical installation
||
||
inspected is unsafe.
|
||__________________________________________________________________________________________________________ |||
|| SUMMARY OF THE INSPECTION
||
|| Dates of the inspection:
||
8-9 January 2003
|| General condition of the installation:
||
|| Fair. Some insulation resistance readings are getting low
||
|| Overall assessment:
|
Satisfactory
|__________________________________________________________________________________________________________ ||
|| SCHEDULES
||
|| This Report consists of 5 pages and a sheet giving Guidance to Recipients. The Report is not valid if any page is
||
|| missing.
||
|
|
|__________________________________________________________________________________________________________ |
CERTIFICATE No: PER3140

Page 2 of 5

SCHEDULE OF INSPECTIONS
__________________________________________________________________________________________________________
||
||
Prevention of mutual detrimental influence
| Protection against electric shock
|
| (a) Protection against both direct and indirect
Yes (a) Proximity of non-electrical services and other influences |
||
contact
||
Yes (b) Segregation of band I and band II circuits or band II
|| Yes (i) SELV
insulation used.
||
| N/A (ii) Limitation of discharge of energy
Yes (c) Segregation of safety circuits
|
|| (b) Protection against direct contact
||
Identification
|| Yes (i) Insulation of live parts
||
Yes (a) Presence of diagrams, instructions, circuit charts and
|| Yes (ii) Barriers or enclosures
similar information
||
|| N/A (iii) Obstacles
Yes (b) Presence of danger notices and other warning notices
||
|| N/A (iv) Placing out of reach
Yes (c) Labelling of protective devices, switches and terminals
||
|| N/A (v) PELV
Yes (d) Identification of conductors
||
|| Yes (vi) Presence of RCD for supplementary
||
Cables and connectors
|
protection
Yes (a) Routing of cables in prescribed zones or within
|
|| (c) Protection against indirect contact
mechanical protection
||
||
Yes (b) Connection of conductors
||
(i) EEBAD including:
|| Yes
Yes
(c)
Erection
methods
||
Presence of earthing conductor
|| Yes
Yes (d) Selection of conductors for current-carrying capacity
||
Presence of circuit protective conductors
|
and voltage drop
|
|| Yes
Presence of main equipotential bonding
||
Yes (e) Presence of fire barriers, suitable seals and protection
||
conductors
||
against thermal effects
|| Yes
Presence of supplementary equipotential
||
General
|
bonding conductors
|
|| N/A
Yes (a) Presence and correct location of appropriate devices
||
Presence
of
earthing
arrangements
for
||
for
isolation
and
switching
||
combined protective and functional
||
purposes
Yes (b) Adequacy of access to switchgear and other equipment
||
| N/A
Presence of adequate arrangements for
Yes (c) Particular protective measures for special
|
||
alternative sources where applicable
installations and locations
||
| Yes
Presence of residual current device(s)
Yes (d) Connection of single-pole devices for protection
|
|| N/A (ii) Use of Class II equipment or
or switching in phase conductors only
||
||
equivalent insulation
Yes (e) Correct connection of accessories and equipment
||
| N/A (iii) Non-conducting location: Absence
N/A (f) Presence of undervoltage protective devices
|
||
of protective conductors
||
Yes (g) Choice and setting of protective and monitoring devices
| N/A (iv) Earth-free equipotential bonding:
for protection against indirect contact and/or overcurrent |
||
presence of earth-free equipotential
||
Yes (h) Selection of equipment and protective measures
||
bonding conductors
||
appropriate to external influences
|| N/A (v) Electrical separation
||
Yes (i) Selection of appropriate functional switching devices
|
|
|
|
| Inspector name Tom Jackson
Date 8 Jan 2003
|
| __________________________________________________________________________________________________________ |
Notes:
'Yes' indicates that an inspection has been carried out and the result is satisfactory
'No' indicates that an inspection has been carried out and the result is unsatisfactory
'N/A' indicates that the inspection is not applicable
CERTIFICATE No: PER3140

Page 3 of 5

SCHEDULE OF CIRCUIT DETAILS FOR DISTRIBUTION BOARD DB1

Page 4 of 5

_________________________________________________________________________________________________________________________________________________________________________________________
|
|
| LOCATION
Hall cupboard
PROTECTIVE DEVICE
RATING
A
PROTECTION AGAINST INDIRECT CONTACT
|
| SUPPLIED FROM
REC
RCD
RATING
mA
|
| NOMINAL VOLTAGE
230
V No. OF PHASES 1
RCD No. OF POLES
|
| _________________________________________________________________________________________________________________________________________________________________________________________ |
|| CIRCUIT
||
|| WIRING || REF || NO OF || CONDUCTOR || MAX || OVERCURRENT PROTECTIVE DEVICE
|| RCD || MAX ||
|
&
| DESCRIPTION
| TYPE | METH. | POINTS |
CSA (mm2) | DISC | BS(EN) and type, rating and S/C capacity
|
| PERM. |
|| PHASES
||
||
||
|| SERVED|| LIVE || CPC || TIME ||
(A)
(kA)
|| (mA) || Zs(ohm) ||
| _________________________________________________________________________________________________________________________________________________________________________________________
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1 | Lighting
|
A |
1
|
8
| 1.5
| 1.0
|
5.0 | BS3871 - 2
10
6
| 100 | 3.43
|
| 2 | Power 1
|
A |
1
|
3
| 2.5
| 1.5
|
0.4 | BS3871 - 2
15
6
| 100 | 2.29
|
| 3 | Power - ring
|
A |
1
|
14 | 2.5
| 1.5
|
0.4 | BS3871 - 2
30
6
| 100 | 1.14
|
| 4 | DB4
|
A |
1
|
1
| 4
| 2.5
|
5
| BS3871 - 2
20
6
| 100 | 1.71
|
| 5 | Power - radial
|
A |
1
|
9
| 2.5
| 1.5
|
0.4 | BS3871 - 2
15
6
| 100 | 2.29
|
| 6 | Water heater
|
A |
1
|
2
| 2.5
| 1.5
|
0.4 | BS3871 - 2
20
6
| 100 | 1.71
|
| 7 | DB2
|
A |
1
|
1
| 6
| 2.5
|
5.0 | BS3871 - 2
40
6
| 100 | 0.86
|
| 8 | Power - ring
|
A |
1
|
14 | 2.5
| 1.5
|
0.4 | BS3871 - 2
30
6
| 100 | 1.14
|
| 9 | DB5 - Garage
|
G |
1
|
1
| 6
| 6
|
5.0 | BS3871 - 2
30
6
| 100 | 1.14
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
||
||
||
||
||
||
||
||
||
||
||
| _________________________________________________________________________________________________________________________________________________________________________________________
|
|
|
|
|
|
|
|
|
|
|

CERTIFICATE No: PER3140

SCHEDULE OF TEST RESULTS FOR DISTRIBUTION BOARD DB1

Page 5 of 5

_________________________________________________________________________________________________________________________________________________________________________________________
|
|
| Distribution board test results
Zs
ohm
RCD operating time at rated current
mSecs
|
|
Ipf
kA
at 5 times rated current
mSecs
|
| _________________________________________________________________________________________________________________________________________________________________________________________ |
|| CIRCUIT
||
RING FINAL CIRCUIT
|| ALL CIRCUITS'
||
INSULATION RESISTANCES
||
|| EARTH ||
RCD TIMES
||
||
|
&
|
CONTINUITIES
| CONTINUITY
| Phase/
| Phase/
| Phase/ | Neutral/ | POLAR- | LOOP
| At rated | 5 times | COMMENT
|
| PHASES
| Phase | Neutral |
cpc
| R1 + R2 |
R2
| Phase
| Neutral | Earth
| Earth
|
ITY | IMPED. | current | current |
|
|| _________________________________________________________________________________________________________________________________________________________________________________________
|| r1(ohm) || rn(ohm) || r2(ohm) || (ohm) || (ohm) || (Mohm) || (Mohm) || (Mohm) || (Mohm) ||
|| (ohm) || (mSecs) || (mSecs) ||
||
|| 1 || || || || || 1.0
|| N/A
|| 10
|| 10
|| 20
|| Pass
|| 0.79
|| 14
|| 10
|| None
||
| 2 | | | | | 0.3
| N/A
| 3.5
| 3.5
| 12
| Pass
| 0.91
| 14
| 10
| None
|
| 3 | 0.5
| 0.5
| | | 0.6
| N/A
| 3
| 3
| 3
| Pass
| 0.37
| 14
| 10
| None
|
| 4 | | | | | 0.3
| N/A
| 15
| 12
| 12
| Pass
| 0.55
| 14
| 10
| None
|
| 5 | | | | | 0.7
| N/A
| 3
| 3
| 3
| Pass
| 0.37
| 14
| 10
| None
|
| 6 | | | | | 0.2
| N/A
| 200
| 200
| 200
| Pass
| 0.18
| 14
| 10
| None
|
| 7 | | | | | 0.1
| N/A
| 200
| 200
| 200
| Pass
| 0.12
| 14
| 10
| None
|
| 8 | 0.6
| 0.6
| | | | N/A
| 200
| 200
| 200
| Pass
| 0.33
| 14
| 10
| None
|
| 9 | | | | | 0.2
| N/A
| 200
| 200
| 200
| Pass
| 0.20
| 14
| 10
| Nune
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
||
||
||
||
||
||
||
||
||
||
||
||
||
||
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|| _________________________________________________________________________________________________________________________________________________________________________________________
||
| DEVIATIONS FROM THE REGULATIONS AND SPECIAL NOTES
|
|| None
||
|| _________________________________________________________________________________________________________________________________________________________________________________________ ||

CERTIFICATE No: PER3140

PERIODIC INSPECTION REPORT


GUIDANCE FOR RECIPIENTS
The Periodic Inspection Report is intended for reporting on the condition of an existing installation.
You should have received an original Report and the contractor should have retained a duplicate. If you were the person
ordering this Report, but not the owner of the installation, you should pass this Report, or a copy of it, immediately to
the owner.
The original Report is to be retained in a safe place and be shown to any person inspecting or undertaking work on the
electrical installation in the future. If you later vacate the property, this Report will provide the new owner with details
of the condition of the electrical installation at the time the Report was issued.
The Extent and Limitations box should fully identify the extent of the installation covered by the Report and any
limitations on the inspection and tests. The contractor should have agreed these aspects with you and with any other
interested parties (Licensing Authority, Insurance Company, Building Society etc) before the inspection was carried out.
The Report will usually contain a list of recommended actions necessary to bring the installation up to the current
standard. For items classified as Requires Urgent Attention, the safety of those using the installation may be at risk, and
it is recommended that a competent person undertakes the necessary remedial work without delay.

For safety reasons, the electrical installation will need to be re-inspected at appropriate intervals by a competent person.
The maximum time interval recommended before the next inspection is stated in the Report under Next Inspection.