Sie sind auf Seite 1von 4

315

IMPACT OF DISTRIBUTED GENERATION ON THE PROTECTION OF DISTRIBUTION NETWORKS

K Kauhaniemi”’, L Knmpnlained
‘University of Vaasa, Finland, *VTT Technical Research Centre of Finland, Finland

INTRODUCTION
The appearance of these kinds of problems depends on
both the characteristics of the network and DG. Often
Traditionally distribution networks have been designed the existing protection arrangements of the network
to operate radially so that the power flows from upper must be changed as well. The DG interconnection
voltage levels down-to customers situated along the procedure can be complicated since the best solution
radial feeders. This has enabled also quite requires engineering studies covering the whole system
straightforward protection concept. Especially when including the network and the DG. An idealistic vision
applying overcurrent protection it bas been possible to for a plug and play solution seems to be still rather far
assume that the fault current can have only one away.
direction. This is not always true if there are distributed
generation (DG) units in the network. As the share of In short-circuit faults DG generates fault current that
distributed generation increases, distribution networks depends strongly both on the generator type and the
are becoming more like transmission networks where network configuration. Synchronous generators are able
generation and load nodes are mixed, and more complex to feed rather large sustained fault current while inverter
protection system design is unavoidable. based systems may be controlled so that their output is
limited to the rated current. From the point of view of
In order to analyze thoroughly the effects of distributed protection coordination the location of the fault in
generation on the requirements for the protection of relation to generator and protection devices dictates the
distribution networks, detailed simulation studies are outcome of the fault situation.
necessary. Dynamic modeling of various types of DG
technologies is required. Two serious problems, blinding of protection and false
tripping, are studied with more details in the following
This paper is based on simulation studies carried out by chapters. Loss-of-mains protection is an interesting
VTT Processes and University of Vaasa. In these issue that cannot be omitted when discussing about DG
studies PSCADEMTDC transient simulation software and protection. It is closely related to the automatic
has been applied. One of the key issues has been to reclosing and thus both of these topics will be briefly
verify that normal network protection schemes and covered also in this paper.
settings are not adequate when there are DG units
connected to the network. The protection coordination
between network protection and the protection of the PREVENTING OVERCURRENT RELAY
distributed generation units has also been studied. The OPERATION
results will be used to focus further research and
development of protection concepts on the essential
areas. When a large production unit or several small ones are
connected to medium voltage network, the fault current
seen by the feeder protection relay may be reduced,
POTENTIAL PROBLEMS TO PROTECTION which can lead to prevention of the operation of
overcurrent relays. This is also called protection under-
reach.
Previous studies have shown that distributed generation
causes several challenges to the protection of
distribution networks. The most commonly mentioned Basic Theory
problems are the following:
False tripping of feeders (sympathetic hipping)
Nuisance tripping of production units Theoretically the problem can be explained as follows.
Blinding of protection A situation, where a production unit is connected in a
Increased or decreased fault levels medium voltage (MV) feeder close to a primary
Unwanted islanding substation, is studied. When a fault occurs at the end of
Prohibition of automatic reclosing the feeder the fault current consists of contributions both
Unsynchronized reclosing from the grid (I,) and from the generator (I,) as shown

0 2004 T h e Institution of Electrical Engineers.


Printed a n d published by t h e IEE, Michael Faraday House, Six Hills Way, S t e v e n a g e , SGI 2AY
316

in Figure 1. The impedances involved in this situation


are:
2, = impedance of the grid and primary transformer
Z,= impedance of the generator
ZL = impedance of the feeder (line)

I1

ZL 2

Fault

Figure 1. Short-circuit fault in MV network and the 0 0


corresponding single phase Thtvenin equivalent circuit. Figure 2. The ratio of the currents seen by the relay
with and without generator.
Let’s assume that the feeder relay sees a current Ik when
there is no production unit. For the ratio between the
feeder relay current 1, in the situation shown in Figure I Simulation Results
and the current 1, the following formula can he derived

Figure 3 presents simulation results of the current seen


by the feeder overcurrent relay, when a diesel power
plant is connected to different locations (0 km, 12 km,
20 km and 34 km) on the feeder, and a three-phase fault
The short-circuit impedance of the generator can he
occurs at the end of the feeder. The relay pickup current
expressed using the short-circuit impedance of the
is 300 A, and the time delay is 0.5 s. The fault current
feeding network Z, = aZr Analogically the impedance
without the power plant would be ca. 420 A. The fault
of the line (to the fault location) can he expressed as
occurs at time 10.1 s. In three of the above mentioned
ZL = bZ,.
cases the power plant reduces the current seen by the
protection so much that the relay will not start until the
The ratio of the currents with and without generator can
power plant trips, which in theses cases takes several
then be simplified:
seconds.

xOkm 0 1 2 k m o 2 0 km * 24 km
0.5 I , I

Figure 2 presents the impact of the coefficients a and b


on the ratio l,llk.In all practical cases the impact is such
that the ratio is less than one, which means that the
contribution from the generator reduces the current seen Ik
by the feeder relay. We can also conclude that the Current
impact of the production unit increases with the size of (W
the unit (larger unit 3 lower coefficient a ) and with the
length of the line section between the production unit
and the fault (larger coefficient b).

If the production unit is not located at the beginning of


the feeder but along the feeder, Figure 1 can be changed
9 12 15 18 21
so that the impedance of the feeder, ZL, is divided into
, , ,Z
two parts, ja Zlend. When Z,, is combined with t /Time (s)
Z,: Z, = Z,+ Z ,
,
, we can write Z, = aZ, and ZL.,~
= bZ, and repeat the procedure above to find out the Figure 3. Current seen by feeder overcurrent relay
ratio of the feeder relay currents. when power plant distance from the substation is varied.
317

FALSE TRIPPINGS
False tripping of healthy feeders can probably be solved
by directional overcurrent relays, but with the following
The basic principle of false tripping is shown in Figure considerations:
4. The short-circuit fault occurs on feeder 2, but also Protection against the bus faults may have to be
feeder 1 is tripped because of overcunent fed by the DG changed. There should be a transfer trip from the
unit. False tripping (sympathetic tripping) is typically main infeed relays (overcurrent relays at secondary
caused by synchronous generators, which are capable of side of the primary transformer) and the arc
feeding sustained short-circuit current. protection rclays to the feeder relays for the feeders
having significant amount of DG connected.
Directional relays are slower than non-directional
relays. In most cases they also cause extra costs~and
lead to solutions that differ from practices favored
by the network companies.

DG may also cause false operation of series protection


devices. This may happen, e.g., in LV systems applying
fuses. In USA reclosers are applied together with fuses
at medium voltage. The coordination of this kind of
system when there is DG involved is discussed in

c Brahma and Girgis (1).

I LOSS-OF-MAINS PROTECTION

In the case of sudden loss of grid connection a part of


the network may keep on operating as an island. In most
cases this is not desirable for the following reasons:
e Reconnection of the islanded part becomes
complicated, especially when automatic reclosing is
4 used. This can lead to damage of equipment and
Figure 4. Principle of false tripping. decrease of reliability of the network
Network operator is unable to guarantee the power
False tripping of healthy feeder was verified by quality in the island. There could he abnormal
simulations with a diesel power plant model. Figure 5 voltage or frequency, and the fault level may be too
presents an example, where a 3-phase short-circuit fault low, so that the overcurrent protection will not
on adjacent feeder causes false tripping of feeder 1, work the way it is designed.
because the diesel power plant on feeder 1 feeds short- Safety problems to maintenance personnel arise
circuit current to the fault. when de-energized circuits are backfed.

x Feeder 1 0 Feeder 2 In order to achieve adequate safety and reliability level


4.2 I I of the distribution system, loss-of-main protection is
usually considered necessary. LOM protection is even
specifically required in many of the relating rules. The
rules and guidelines vary from country to country but
requirements similar to the following are often given:
HI, if2 DG should be disconnected from the network in the
Current case of abnormality in voltage or frequency
If one or more phases is disconnected from the grid
supply the DG should be rapidly disconnected from
the network
If autoreclosing is applied, the DG units must
disconnect clearly before the reclosing, so that there
will be enough time for the fault arc to extinguish.

The loss-of-mains protection is very hard to accomplish


t / Time (s) by traditional means. E.g., the hasic under-lovervoltage
and under-loverfrequency relays may fail to operate if
Figure 5. Example of false tripping caused by a short-
circuit fault on adjacent feeder.
318

the power mismatch in the island to be created in the Primary results of these studies have given a clear
loss-of-main situation is close to zero. indication of the potential protection problems that need
to be solved either by suitable recommendations relating
There are several methods developed for loss-of-mains to protection design or possibly some new protection
protection. One of the standard solutions seems to be the algorithms. Solutions are urgently needed since the
rate of change of frequency (ROCOF) protection share of distributed generation is expected to increase
method as pointed out by Guillot et al (2). Another quite rapidly.
common protection method applied is the vector shift
method presented, e.g., in Jenkins et al (3). One of the areas where further studies are needed is the
application of autoreclosing with DG. From the network
Redfern et al (4) have proposed monitoring of the reliability point of view this is a very important issue
fluctuation of the power output from the generator. This since today autoreclosings are able to handle a major
method is suitable only for synchronous generators. part of the faults.
Positive sequence undervoltage method has been found

r
effecti e in Denmark by DEFU (5). However, totally
satisfy ng LOM protection solutions are still missing.
This paper has focused on the medium voltage
networks. However similar problems may arise in the
low voltage networks where mainly fuses are applied
for the network protection. Another group of problems
AUTORECLOSING that has not been covered is the earth faults related
problems. Further studies are going on with the aim of
new protection concepts for distribution networks
In overhead medium voltage networks, automatic having distributed generation.
reclosing is a very effective mean to clear faults. E.g. in
Finland, ca. 80% of faults can be cleared with high-
speed autoreclosing and 15% with time-delayed REFERENCES
autoreclosing. The impact of autoreclosing is based on
extinction of arc during the dead time of the reclosing
sequence. In the Nordic countries, dead time is typically 1. Brahma, S.M., Girgis, A.A., 2002, IEEE PES Winter
only 0.3 s. Meetinr, Vol. I , “Microprocessor-Based Reclosing
to Coordinate Fuse and Recloser in a System with
Distributed generation seems to be rather incompatible High Penetration of Distributed Generation”, 453 -
with current reclosing practices as noted, e.g., in Dugan 458
and McDermott (6). In suitable conditions DG may
prevent the arc extinction and the momentary fault 2. Guillot, M., Collombet, C., Bertrand, P., Gotzig, B.,
becomes permanent. During the dead time of the 2001, CIRED, IEE Conf, Pub. No. 482, “Protection
reclosing sequence the generators in the network usually of Embedded Generation Connected to a
tend to drift away from the synchronism with respect to Distribution Network and Loss of Mains Detection”
the grid. Thus the reconnection made without any
synchronization, which is the usual way, may cause 3. Jenkins, N., Allan, R., Crossley, P., Kirschen, D.,
serious damages to the generators, as well as high Strbac, G., 2000, Embedded Generation, IEE
currents and voltages in the neighboring network.
4. Redfern, M.A., Usta, O., Bmett, J.I., Fielding, G.,
Simulation studies have confirmed the high risk of out- 1993, 5th Int. Conf. on Developments in Power
of-phase reclosing. As a conclusion to this it can be System Protection, “A new digital relay for loss of
stated that rapid and reliable loss-of-mains protection is grid to protect embedded generation”, 127 -130
needed. DG units must be disconnected very fast during
the dead time of autoreclosing sequence. 5. D E W , 1995, Relaebeskvttelse ved decentrale
produktionsanlaeg med synkrongeneratorer.
Teknisk rapport 293,2. udgave
CONCLUSIONS
6. Dugan, R.C., McDermott, T.E., 2002, IEEE Ind.
Appl. Mag., MadApr. 2002, 19 - 25
According to the simulation studies proper coordination
of the protection of network and DG units is important
in order to avoid false tripping. In certain cases also
directional protection is necessary to guarantee
selectivity. DG units that are capable of providing large
short-circuit current may prevent the operation of feeder
relays. On the other hand, overcurrent relays cannot be
applied with inverter based DG units that do not feed
any significant short-circuit current.

Das könnte Ihnen auch gefallen