Beruflich Dokumente
Kultur Dokumente
The device has danger of electricity, it will cause serious injuries even death if you don` t avoid any case. The device shall be installed, operated, used and maintain by pRfessional operator. Our company won` t takes any responsibility if misoperation to cause any results.
Catalogue
1. Product overview ......................................................................................4 2. Product function and characteristic ........................................................4 2.1 Function of Multifunctional Power Meter ................................................4 2.2 Measurement of instantaneous value ........................................................6 2.3Measurement of instantaneous value .........................................................6 2.4 The calculation of Demand and peak value demand.................................6 2.5 Electric energy and Electric energy pulse output ......................................7 2.6 Electric engergy multi-Rate ......................................................................7 2.7 HumoRus and THD ratio ..........................................................................8 2.8 Event record..............................................................................................8 2.9 Warning system.........................................................................................9 2.10 AUX Module ........................................................................................11 3. 4. Safety Precaution .................................................................................15 Installment and Wiring .......................................................................16
4.1 Packing List and Marker.........................................................................16 4.2 Installment & Working circumstance......................................................16 4.3 Installment ..............................................................................................16 4.4 Wiring .....................................................................................................17 5. Communication....................................................................................21 5.1 Communication Connection ...................................................................21 5.2 Communication media ............................................................................21 5.3 Communication PRtocol.........................................................................21 6. Operation..............................................................................................22 6.1 Display Function.....................................................................................22 6.2 Button Function ......................................................................................22 6.3 Display....................................................................................................22 6.4 Parameter Settings ..................................................................................23 7. Maintenance and TRubleshooting .........................................................24 Appendix B...................................................................................................... Appendix C Ordering Information ...........................................................55
1. Product overview
PMC200 Multifunctional Power Meteris a multi-function monitoring meter, it combines function of collecting data and contRl, and it can replace many kind of meter, relay, transmitter and others components. PMC200 can be installed different position in electricity distribution system. PMC200 Multifunctional Power Meterhas RS 485 communication interface, it can integration into any electric monitoring system and collect data and remote control by configure management software or other industry configuration software. PMC200 Multifunctional Power Meteris a real measurement meter based on real virtual value, it can do the accurate measurement for high highly nonlinear load, it can measure accurately many electric power parameters through advanced technology of grid frequency sampling synchRnization and you can see all measurement value and the max/min value as well as demand display value via display screen or via software remote control.
Frequency MIN/MAX Current phase voltage, line voltage general active, reactive, apparent power general power factor frequency THD I THD U Demand and peak value
current value and peak value current value and peak value
Electric energy Input output active electric energy Input output reactive electric energy apparent power Electric energy multi-rate 8 multi-rate time, 4 rates can be set Electric energy quality HumoRus aberration 31 times humoRus analyses Event record 100pcs SOE event record, time distinguish can reach to 1ms Warning system 6 warning channels with configurable limit value 4 warning channels with configurable logic Communication RS485/MODBUS pRtocol Display Large screen STN liquid display Real time clock Year, month, date, minute, second Others Support program online upgrade Sheet 2 Auxiliary module function and characteristic Binary input module 8 channels binary input, time resolution rate of status change time can reach to 1ms Relay output module 4 channel relay output, warning setting is available for local exceed confine and remote control as well Analog input/output module 1 channel 4-20mA DC analog input measurement 1 channel 0-5V analog input measurement 5 current and voltage current and voltage 1 channel pulse output 1 channel pulse output
2 channels 4-20mA DC analog output, transducer can be configurable Communication module a) RS232 communication module b) PRfiBus-DP communication module c) TCP/IP Ethernet expand module
Fig.1
Time 2
10
T2vale
Time 3
16
T3flat
Time 4
22 7
T4tine
Time 5
28
T1peak
Time 6
34
T2vale
Time 7
40
T3flat
Time 8
46
T4tine
1# time period starting time is fRm 2 o` clock, close at 5 o` clock, calculate segment is T1, 2# time period starting time is fRm 5 o` clock, close at 8 o` clock, calculate segment is T2, the rest may be deduced by analogy, 8# time period starting time is fRm 23 o` clock and the second day 2 o` clock close, calculate segment is T4. The same rate electric energy can be amalgamated together for calculation.
HRh =
PMC200 Multifunctional Power Metercan measure voltage, current THD. The THD is ratio between humoRus content and fundamental wave, it not only pRvides the general situation of wave quality, but also effective method for diagnosing electric energy quality. PMC200 Multifunctional Power Meteradopt below formula to calculate THD
THD =
2.8 Event record
( H 2) 2 + ( H 3) 2 + ( H 4) 2 + .......... 100% H1
In order to assist user to analyze all kinds of faults for electric system, PMC200 Multifunctional Power MeterpRvide depth 100pcs SOE event record, user can do event search orientation according to SOE event record, use communication pRtocol can get SOE event record message PMC200 Multifunctional Power Metercan record binary state change message, relay action message, limit value and logic warning channel state message etc. event style. PMC200 Multifunctional Power Meterrecord event happen time thRugh UNIX time format, distinguish can be 1ms. UNIX time is current time which relative to the total second number of 0 second 0 minute 0 hour 1st January 1970. Event record will come out following format message thRugh communication pRtocol resolution:
Event time 888 millisecond 55 minute 17 hour 19th Nov. 2010 999 millisecond 55 minute 17 hour 19th Nov. 2011
Setting content
Description
Threshold type
Crossing
Divide
to
Upper
Threshold-crossing
and
lower
threshold-crssing Limit value object can be 15pcs, and set discretionarily: 0 is A phase current 1 is B phase current 2 is C phase current 3 is zeR-sequence current 4 is max unimbalance current(Reservation) 5 is current phase lost 6 is A phase voltage 7 is B phase voltage 8 is C phase voltage 9 is AB line voltage 10 is AB line voltage 11 is CA line voltage 12 is max unimbalance voltage(Reservation) 13 is max unimbalance voltage(Reservation) 14 is voltage phase lost
Threshold valve
Crossing
In the whole arrearage time, if limit value object return to limit value, the warning will not be activate. 9
When this alarm activated, the user can correlative Spring any relays.
2.9.2 Logic value warning PMC200 Multifunctional Power Meterhas 4 Logic value warning channel, Logic value warning system is activated base on the logic adjust that made onto the monitor subject, maximum the monitoring three subjects on same time, the parameter settings as bellow:
Description Two types: Logic Or / Logic and Logic subject max. can reach to 15, can freely setting: 0 means dont adjust the subject 1 means Switch power S1; 2 means Switch power S2; 3 means Switch power S3; 4 means Switch power S4; 5 means Switch power S5; 6 means Switch power S6; 7 means Switch power S7; 8 means Switch power S8; 9 Means Value limit alarm channel RA1; 10 Means Value limit alarm channel RA1; 11 Means Value limit alarm channel RA3; 12 Means Value limit alarm channel RA4; 13 Means Value limit alarm channel RA5; 14 Means Value limit alarm channel RA6;
Logic subject 2 Logic subject 3 Truth condition of Logic subject Lag time of Logic alarm Output target of Logic alarm
Same as above. Same as above. Truth condition that should be satisfied (when all Logic subject participate in the logical calculation.) Within the lag time, if the logic subject return, then the alarm will not be active. When this alarm activated, the user can correlative Spring any relays.
10
This module has 8 channel switch power input Module, installation position is A notch, used to monitoring the state signals ( like Breakers position signal, Isolators position signal ) etc, the time resolution of state change reach 1 ms. Also we can see the close state of the related node on the screen. The node input voltage may choose, then selects the low pressure power source which the measuring appliance interior starts out, may also be suitable the exterior low pressure power source's input request. May divide into two kinds of specifications according to the node different voltage condition: Passive node and active node. When the exterior status signal supplies a positional information merely, then needs electric power parameter observation meter interior output node closed time the feedback voltage signal, the outside passive contact wiring following Fig. (2) shows. When the exterior status signal not only supplies the positional information, extra also pRvides the feedback voltage signal, this time the Power Parameter meter cannot use the internal electrical power supply to output, but must adjust its interior to jump the line hat to carry on the disposition, and makes the corresponding modification to the wiring. The outside active contact wiring following Fig. (2) shows.
Fig.2
2.10.3 Relay Output Module The Power Parameter meter provides the expandable 4 group relay output module, installs the position to correspond 11
on main engine's B slot, applies in the scene load control. The Relay control pattern may divide into long-distance and the local pattern: Long-distance Pattern - The relay is uses the order by PC or PLC thRugh the communication the mode control . Local Pattern - The relay is observes and contRls the meter contRl by the electric power parameter, warning system connection trigger contRl. Under local contRl pattern- relay working pattern separable: Normal, Block system and Fixed time three kind of patterns Normal working Pattern - When the Power Parameter meter has the warning to pRduce, the warning outputs when is connected the relay, the relay closes. When warning vanishing, the relay separates. Block working Pattern - When the Power Parameter meter has the warning to pRduce, the warning outputs when is connected the relay, the relay closes. When warning vanishing, the relay is at the closed position. If needs the relay separation, must suppose the relay the remote contRl pattern, the Ruting directive contRl relay separation. Fixed time Pattern - When the Power Parameter meter has the warning to pRduce, the warning outputs when is connected the relay, the relay closes. The relay maintains the movement condition in fixed time the time, when fixed time overflows, the relay separates. No matter the relay in above what kind of situation, after the Power Parameter Meter loses the electricity, on the heavy electricity, the relay restores to often on status. May examine relay's closed position on the display monitor. The relay specification is 250Vac/5A,30Vdc/5A, if has the special demand, please when ordering carry on the special Description. The relay module wiring following Fig. (3) shows.
Fig.3 2.10.4 Analog Input/Output Module The Power parameter meter pRvides the expandable simulation quantity input/output module, installs the position to correspond on main engine's C slot, this module has 1 gRup 4-20mA direct current input survey, 1 gRup 0-5V DC voltage input survey, 2 gRup 4-20mA direct current output, the direct-current output simulation object may dispose. 4-20mA and - the 5V DC current input survey mainly uses in sensors and transformer's and so on scene temperature, pressure survey, will simulate the quantity signal to transform the digital signal thRugh the Power Parameter meter to transmit the far-end thRugh the communication, carries on the data gathering. May also examine the observed value on 12
the display monitor. 2 group 4-20mA direct current output mainly uses in the scene electric quantity transmitting instrument's application, the direct-current output simulation (changes delivers) the object to be possible to dispose, disposition hypothesis content following table:
Description
Change delivers subject can reach 27, can either setting one: 0 means A phase current 1 means B phase current 2 means C phase current 3 means zeR sequence current 4 means A phase voltage 5 means B phase voltage 6 means C phase voltage 7 means AB line voltage 8 means BC line voltage 9 means CA line voltage 10 means A phase active power; 11 means B phase active power; 12 means C phase active power; 13 means total active power; 14 means A phase reactive power; 15 means B phase reactive power; 16 means C phase reactive power; 17 means total reactive power; 18 means A phase apparent power 19 means B phase apparent power 20 means C phase apparent power 21 means total apparent power 22 means A phase power factor 23 means B phase power factor 24 means C phase power factor 22 means total power factor 26 means Frequency
Analog output 1 20 mA
13
related parameter Analog output 1 4mA related parameter Analog output 2 Analog input/output Module wiring following Fig. (4) shows: Setting means same as Analog output 1 Can be freely setting, but must smaller than Those of 20mA.
Fig.4
2.10.5 Communication Module The Power Parameter meter pRvides the expandable RS232 module, installs the position to correspond on main engine's D slot, this module applies in needs the RS232 mailing address the situation, but the communication distance should limit in 10m, uses the three-wire system connection, the RS232 module wiring following Fig. (5) shows.
14
Fig.5
3. Safety Precaution
Before the installment, the movement, the maintenance, operate this equipment, please prompt Danger & Warning This equipment existence electricity danger, if does not avoid, will cause the death or the injure severely The equipment should let the pRfessional qualification personnel to carry on the installment, the operation, to use and to maintain. Regarding not any consequence which creates according to this handbook operation, this company will not undertake any responsibility. Electric shock, detonation and electric arc dangerous The equipment should let the pRfessional qualification personnel to carry on the installment, the operation, to use and to maintain. Be careful of the potential hazard, completes individual pRtection, cannot work alone Before carries on the installment, the operation, the use and the maintenance of the equipment, should shut off electric power supply to this equipment. Must use the qualified Voltage Measurement Instruments to ensure all of the power supply is shut off. Equipment's success movement relies on correct pRcessing, the installment and the operation. Neglect basically installs the request possibly to create the personal injuries, also will possibly create to the equipment damages Cannot carry on the bypass absolutely to the exterior fuse Cannot cause (PT carries on secondarily short-circuits. Never have CTs secondary side get an open circuit before installation or wire detachment, user should use the pipe nipple block to carry on secondarily to CT short-circuits. The equipment should install in an appropriate insulation and in the fire pRtection engine case. Possibly will not cause the death or the serious personal injuries according to the above Description operation! 15 careful reading following safe
4.3 Installation
1 PMC200 Multifunctional Power Metersize as below:
Fig. (6) Outer size 2Insert the PMC200 tester into hole of 92.5mm X 92.5mm, as Fig. (7)
Fig. (7) FRnt side installment show 3 Use the two fastener to fixed into the left/right side of the host, to fixed the PMC200 tester, As Fig. (8).
16
Fig. (8) Back side of the installment show 4 Use the screw BM2.5X64 fix the AUX module onto the host, as Fig. (9)
Note: must install the fastener before install the AUX module.
4.4 Wiring
4.4.1 Terminal and Marker 1 Marker 1 on top of Host, as Fig. (10) as below:
Fig. (10)
Marker 1
Code 13 24
Name L/+N/NCNC
56 78
NCNC P2-P2+
No-power-optocoupler Isolate; 1112 13 B-A+ SHD RS485 Communication Port RS485 Shielding layergRunding;
Code
Name
Current input
15 17 NCNC 19 NC
Empty
4.4.2 System Wiring pattern The Power parameter meter in the measurement voltage is smaller than or was equal to 277V () /480V (line) time may turn on directly, but does not need external connection PT, otherwise, must external connection PT. The Power Parameter meter support many kinds of survey wiring pattern, the following uses the graphical representation the method to carry on showing separately.
18
19
Figure (17) three-phase three-wire system, 2PT, 2CT Note: The above diagram fuse should be rated at 250mA fuse.
Compatible with AC and DC power input, AC input range :85-265VAC / 45-65Hz. DC input range :100-300VDC.
Figure (18) Power input terminal Note: The above diagram fuse should be rated at 500mA fuse. 4.4.4 Active and reactive pulse output wiring Pulse output is passive optocoupler isolated mode, Pull-up power supply must be pRvided by exterior.
20
5.2
Communication media
Use shielded twisted pair 22, the same network can carry up to 32 power power meter, , while the bus is not over 1200 meters without repeaters.
address, and the user can change. Communication baud rate: 1200,2400,4800,9600,19200(four options).
6.3 Display
Power Meter interface shows the function menu by combining the different electrical parameters of the matrix methods. Repeatedly press the [] key (Menu) to enter the menu of different functions, in different functional menu repeatedly press the other key to display different interface. Figure (21) for the screen displays a list of abbreviations.
22
Figure (22) password authentication interface Press [], [] keys to select the instrument parameters to set, as shown in Figure (23) parameter setting interface is instrument IP, address, baud rate, PT transformation ratio, CT ratio, type of system, remove/change password , Hardware version and software version. These parameters setting is the same operation with the password.
23
Figure (23) parameter setting interface 6.4.2 IP Setting This parameter is used to set the device IP address. The parameters to be TCP / IP Ethernet expansion module support to be effective. 6.4.3 Address Setting This parameter is used to set the device communication address. Power Meter supports MODBUS RTU communication pRtocol, the effective address range is 1 to 247. 6.4.4 Baud Rate Setting This parameter is used to set the device baud rate. Serial communication speed can support 1200,2400,4800,9600 and 19200Bps. 6.4.5 PT transformation ratio setting This parameter is used to set the device PT transformation ratio. Variable ratio is equal to PT primary side rating value divides PT secondary side rating value. If the external does not use PT, the PT transformation ratio is 1. PT transformation ratio ranges fRm 1 to 9999. 6.4.6 CT transformation ratio setting This parameter is used to set the device CT transformation ratio. Variable ratio is equal to CT primary side rating value divides CT secondary side rating value. If the external does not use CT, the CT transformation ratio is 1. CT transformation ratio ranges fRm 1 to 9999. 6.4.7 System type setting The parameters of the measurement system used to set the device type. Support for measurement mode. See connection methods on four specific content. 6.4.8 Clear The parameters used for device input and output active and reactive power, multi-rate power, maximum and minimum, demand, SOE event record cleanup menu. 6.4.9 Version Information To facilitate equipment maintenance, pRvide hardware and software version information for inquiries. four line star and delta
voltage input terminal Check the input fuse is burned; Check the neutral connection is reliable; current measurement not correct; power measurement not correct; is is Check the system rated current, rated frequency, system type, CT transformation ratio is set correctly; Current input wiring is correct; Check the system rated voltage, rated current, rated frequency, system type, PTCT transformation ratio is set correctly; Voltage and current corresponding to the phase is correct; Voltage, current transmitterpolarity (same name as the client) are correct; Can the not instrument by Instrument parameter settings are not correct Check the mailing address communicate with remotely computer Communication line properly connected Binary I/Os state does not change; input / output voltage According to the external node operation type, check whether the correct jumper inside the module; Relay operate; does not Instrument parameter settings are not correct; Does not receive control commands; Analog output is Instrument 25 Check the analog output object Check the meter communication cable; Check the external wiring is Check the relay operation mode correct, the parameters match; settings are correct; is not settings are correct; Check the communication baud rate settings are correct; in the same RS485 line, mailing address settings are repeated; Check the meter communication cable;
is not correct
not correct
is set correctly; Check the corresponding analog value on the lower settings are correct;
Appendix A: Specifications Electrical Characteristics Measurement Type Three-phase three-wire AC system, three-phase four-wire communication system; Sampling rate per cycle: 64 times Data refresh rate Measurement Accuracy Current Voltage Power Frequency Active Energy Reactive Energy AI AO Input voltage characteristics Measuring voltage Allowed overload Input impedance Input current characteristic Measuring current Allowed overload Input impedance Binary Input Working voltage Input impedance 26 12K 12~24 VDC <0.1 1.2 times / continuous 5A or 1A (Via CT Connect) 1.8M 0.5% 0.5% 3 X 220/380V (Direct Access) 3 X 57.7/100V (Via CT Connect) 1.2 times / continuous 2.0% 1S 0.2% 0.2% 0.5% 0.05Hz 1.0%
2KV
Mechanical shock Node capacity 4-20mA input measurement Allowed load Input impedance Isolation voltage 0-5V DC input measurement Measuring voltage Allowed Load Input impedance Isolation voltage 4-20mA output DC Open circuit voltage Load capacity Isolation voltage AC Power supply DC Power Mechanical properties Weight IP pRtection grade panel IP52, body IP30 Size Host 96 X 96 X 72 mm 27 0.5kg 85~265 VAC/45-65Hz 100~300 VDC < 3W 2KV 600 15VDC 2KV 12.5K 1.2 times / continuous 0-5V 2KV 1.2 times / continuous 10 Measuring current 4-20mA 220 VAC/5A30 VDC/5A
Host module Operating temperature Storage Temperature EMC ElectRstatic interference Group of anti-fast transient pulse Anti-impact discharge Display
and
96 X 96 X 120 mm
-20~70 -25~70 -40~85 5% - 90%RH No condensation IEC 61000-4-2,Level 4 IEC 61000-4-4,Level 4 IEC 61000-4-5,Level 3 IEC 61000-4-8,Level 3 GB/T13729>50M GB/T13729AC 2KV 50Hz /1min GB/T137295KV1.2/50us
Relative Humidity
Anti-frequency magnetic field Electrical insulation performance Insulation resistance Frequency withstand voltage Impulse voltage
MODBUS RTU pRtocol communication pRtocol and standard serial RS485 communication port are used for Power Meter. Information transfer mode is asynchRnous, 1 start bit, 8 data bits, 1 stop bit, no parity. Each package contains the address of frame data field, function code field, data field and checksum field. The maximum length of a data package is 255 bytes.
Address field
Parcels fRm the station address field length is one byte. A single device address range fRm the station 1 to 247. If the station receives an address fRm the address field information consistent with its own parcel, the parcel should be included in the implementation of the command. Parcels fRm the station in response to address the domain of their own.
Function code field
Parcels in the domain of length one byte, to inform what action should be implemented fRm the station. Response fRm the station master package should contain the same operation requested domain bytes. Related function code as following: Function Code 0x03 Read register access to the current power meters values of 28 Meaning Function
one or more consecutive registers 0x10 Set register the specified value written to power meter of one or more consecutive registers 0x05 Bite Setting control a relay or a bit of a register of the current power meter
Data Domain Data field length of the parcel is determined according to its specific function. Data field using big byte before the low byte in the latter mode; Check Domain MODBUS-RTU mode 16-bit CRC checksum. Equipment should be sent parcel data for each calculation of CRC16, the final results placed into the checksum field. Package should also be on the receiving device in each of the data (in addition to checking the domain outside) for CRC16 calculation, compare results and verify the domain. Only the same package can be accepted. Abnormal response: If the master station sends an illegal package to this Set, or requests a valid data register, the exception response will be generated. The exception data response consist of the slave address, 80H + original function code, exception code and verify domains. The following table shows the exception code meaning: Exception code 01H Remarks Received illegal operate Function code 02H Received illegal Register Address 03H Received illegal Data
Broadcast command This Set support bRadcast command with slave address as 0X00 but no echo. Read Register The Slave Address Function code 03 Register Originate 2 byte Data Area byte 1 byte (2*Register Pcs ) 29 1 byte 03 Function code 03 1 byte master station Slave station normal response Slave Address 1 byte sends a command 1 byte
Address Register Pcs CRC16 2 byte N-th Register Data CRC16 Setting Register The Slave Address Function code 10 Register Originate Address Register Pcs Data Area byte No. (2*Register Pcs ) First Register Data N-th Register Data CRC16 2 byte ----2 byte 1 byte 2 byte Register Pcs CRC16 2 byte 2 byte 2 byte Register Originate Address 2 byte 1 byte Function code 10 1 byte master station 1 byte Slave station normal response Slave Address 1 byte sends a command ----2 byte 2 byte First Register Data 2 byte
Bit-Write Register Bit-write register can contRl relays or bit register by send contRl commands: that 0xFF00 as write 1 (closed a relay)0x0000 as write 0 (release of a relay), Others are all invalid. Master sends the command: Slav Address 1 byte 05 2 byte 30 2 byte 2 byte Function code Originate Address ContRl command CRC16
Normal response fRm Slave station: Slav Address 1 byte 05 2 byte 2 byte 2 byte Function code Originate Address Register State CRC16
Register PRtocol Data Type Description: Character INT UINT LONG ULONG Actual value Calculation: 1, Current actual value = communication value * CT * unit; 2, voltage actual value = communication value * PT * unit; 3, Power actual value = Communications value * PT * CT * units; Register List Current Register List Register 40001 40002 40003 40004 40005 Name A-Phase Current B-Phase Current C-Phase Current ZeR-sequence Current 3-Phase Current average Value Attribute R R R R R Unite 0.001A 0.001A 0.001A 0.001A 0.001A Remarks UINT UINT UINT UINT RESV, Overall back to 0 40006 Max. Unbalanced current R 0.1% RESV, Overall back to 0 Voltage Register List Register 40007 Name A-B Line Voltage Attribute R 31 Unite 0.01V Remarks UINT Description 16-bit signed 16-bit signed
Register 40008
Attribute
Unite 0.01V
Remarks UINT
R 40009 C-A Line Voltage R 40010 Line Voltage average Value 40011 Max. unbalanced Line Voltage R R 0.1% RESV, Overall back to 0 40012 40013 40014 40015 A-Phase -Phase Voltage B-Phase -Phase Voltage C-Phase -Phase Voltage Phase Voltage average Value R 40016 Max. unbalanced Phase Voltage R 0.1% RESV, Overall back to 0 40017 Voltage N-R R 0.01V RESV, Overall back to 0 Power Register List Register 40018 40019 40020 40021 40022 40023 40024 40025 40026 40027 40028 40029 Name A-Phase Active Power (L) A-Phase Active Power (H) B-Phase Active Power (L) B-Phase Active Power (H) C-Phase Active Power (L) C-Phase Active Power (H) Overall Active Power (L) Overall Active Power (H) A-Phase Reactive Power (L) A-Phase Reactive Power (H) B-Phase Reactive Power (L) B-Phase Reactive Power (H) Attribute R R R R R R R R R R R R 32 Unite 0.1W 0.1W 0.1W 0.1W 0.1W 0.1W 0.1W 0.1W 0. 1Var 0. 1Var 0. 1Var 0. 1Var LONG LONG LONG LONG LONG Remarks LONG R R R 0.01V 0.01V 0.01V 0.01V UINT UINT UINT UINT 0.01V UINT 0.01V UINT
Name C-Phase Reactive Power (L) C-Phase Reactive Power (H) Overall Reactive Power (L) Overall Reactive Power (H) A-Phase Apparent power (L) A-Phase Apparent power (H) B-Phase Apparent power (L)
Attribute R R R R R R R
Remarks LONG
LONG
ULONG
ULONG
B-Phase Apparent power (H) 40038 40039 40040 40041 Power factor Register List Register 40042 40043 40044 40045 Frequency Register List Register 40046 Energy Register List Register 40047 40048 Name Input Active Energy(L) Input Active Energy(H) Name Frequency Attribute R Name A-Phase Power factor B-Phase Power factor C-Phase Power factor Overall Power factor C-Phase Apparent power (L) C-Phase Apparent power (H) Overall Apparent power (L) Overall Apparent power (H)
Attribute R R R R
Unite 0.01Hz
Remarks UINT
Attribute R
Remarks ULONG
R 40049 40050 40051 40052 40053 Input Reactive Energy(L) Input Reactive Energy(H) Output Active Energy(L) Output Active Energy(H) Output Reactive Energy(L) R R R R R 33 0.1kVarh 0.1kVarh 0.1kWh 0.1kWh 0.1kVarh ULONG ULONG ULONG
Name Output Reactive Energy(H) Overall Apparent Energy (L) Overall Apparent Energy (H)
Attribute R R R
Remarks
ULONG
Remarks: 40057-40069 reserve with forbidden. Harmonic distortion Register List Register 40070 40071 40072 40073 Name A-Phase Current THD B-Phase Current THD C-Phase Current THD ZeR-sequence Current THD Attribute R R R R Unite 0.1% 0.1% 0.1% 0.1% Remarks UINT UINT UINT RESV Overall back to 0 40074 40075 40076 40077 A-Phase (A-B Line )Voltage THD B-Phase (B-C Line )Voltage THD C-Phase (C-A Line )Voltage THD Voltage N-R THD R R R R 0.1% 0.1% 0.1% 0.1% UINT UINT UINT RESV Overall back to 0
34
Harmonic Analysis Register List Register 40078+31 Name A-Phase Current Harmonic Contents Attribute R Unite 0.1% Remarks Refer Harmonic -Data Stencil 40110+31 B-Phase Current Harmonic Contents R 0.1% Refer Harmonic -Data Stencil 40142+31 C-Phase Current Harmonic Contents R 0.1% Refer Harmonic -Data Stencil 40174+31 ZeR-sequence Current Harmonic Contents R 0.1% RESV Overall back to 0 40206+31 A-Phase (A-B Line )Voltage Harmonic Contents R 40238+31 B-Phase (B-C Line ) Voltage Harmonic Contents R 40270+31 C-Phase (C-A Line ) Voltage Harmonic Contents R 40302+31 Voltage N-R Harmonic Contents R Remarks: 40334~40349reserve with forbidden. Harmonic Data Stencil 0.1% 0.1% 0.1% 0.1% Refer Harmonic -Data Stencil Refer Harmonic -Data Stencil Refer Harmonic -Data Stencil RESV Overall back to 0
Register Base Address Base Address +1 Base Address +2 Base Address +3 -----Base Address +30 Base Address +31
Attribute R R
H2 Harmonic Contents
0.1%
UINT
H3 Harmonic Contents
0.1%
UINT
-----R
-----0.1%
-----UINT
0.1%
UINT
35
Multi-tariff Energy Register List Register 40350 Name Overall Multi-tariff Timeslot Pcs Attribute R/W Unite Remarks 0 No;Max. 8pcs 40351 Timeslot 1 Originate Time R/W 0~47, 24h divide as 48pcs Timeslot 40352 Timeslot 1rate R/W 0~3 4pcs rate 0 Valley; 2 as Flat;3 as Sharp 40353 40354 40355 40356 40357 40358 40359 40360 40361 40362 40363 40364 40365 40366 40367+9 40377+9 40387+9 40397+9 Timeslot 2 Originate Time Timeslot 2 Rate Timeslot 3 Originate Time Timeslot 3 Rate Timeslot 4 Originate Time Timeslot 4 Rate Timeslot 5 Originate Time Timeslot 5 Rate Timeslot 6 Originate Time Timeslot 6 Rate Timeslot 7 Originate Time Timeslot 7 Rate Timeslot 8 Originate Time Timeslot 8 Rate Rate 0 Energy Rate 1 Energy Rate 2 Energy Rate 3 Energy R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R R R R 0~47 0~3 0~47 0~3 0~47 0~3 0~47 0~3 0~47 0~3 0~47 0~3 0~47 0~3 Refer next table: Rate Structure Stencil as Peak;1 as as as
Register Base Address Base Address +1 Base Address +2 Base Address +3 Base Address +4 Base Address +5 Base Address +6 Base Address +7 Base Address +8 Base Address +9
Name Input Active Energy(L) Input Active Energy(H) Input Reactive Energy(L) Input Reactive Energy(H) Output Active Energy(L) Output Active Energy(H) Output Reactive Energy(L) Output Reactive Energy(H) Overall Apparent Energy (L) Overall Apparent Energy (H)
Attribute R R R R R R R R R R
Unite 0.1kWh 0.1kWh 0.1kVarh 0.1kVarh 0.1kWh 0.1kWh 0.1kVarh 0.1kVarh 0.1kVAh 0.1kVAh
Remarks
ULONG
Min. /Max. Value Register List Register 40407+9 40417+9 40427+9 40437+9 40447+9 40457+9 40467+9 40477+9 40487+9 40497+9 Name Min./Max. Current Min./Max. Line Voltage L-L Min./Max. -Phase Voltage L-N Min./Max. Overall Active Power Min./Max. Overall Reactive Power Min./Max. Overall Apparent power Min./Max. Overall Power factor Min./Max. Frequency Min. /Max. Current THD Min. /Max. Voltage THD Attribute R R R R R R R R R R Unite 0.001A 0.01V 0.01V 0.1W 0.1Var 0.1VA 0.001 0.01Hz 0.1% 0.1% Refer Min. /Max. Value Stencil Remarks
Min. /Max. Value Stencil Register Base Address Base Address +1 Name Min. Value Occurred Time (L) Min. Value Occurred Time (H) Attribute R R Unite 1S Remarks ULONG ULONG UNIX Time form Base Address +2 Base Address +3 Base Address +4 Min. Value (L) Min. Value (H) Min. Value Phase Place R R R 0as No-Phase 1 as A-Phase 2 as B-Phase 37 LONG
Register
Name
Attribute
Unite
Remarks 3 as C-Phase
Max. Value Occurred Time (L) Max. Value Occurred Time (H)
R R
1S -
R R R
LONG
Demand Register List Register 40507 40508 40509 40510 40511 40512 40513 40514 40515 40516 40517 Name Demand Compute cycles A-Phase Current Demand B-Phase Current Demand C-Phase Current Demand ZeR-sequence Current Demand Overall Active Power Demand (L) Overall Active Power Demand (H) Overall Reactive Power Demand (L) Overall Reactive Power Demand (H) Overall Apparent power Demand (L) Overall Apparent power Demand (H) Attribute R/W R R R R R R R R R R Unite min 0.001A 0.001A 0.001A 0.001A 0.1W 0.1W 0.1Var 0.1Var 0.1VA 0.1VA ULONG LONG Remarks 1~60 UINT UINT UINT UINT LONG
Peak Demand Register List Register 40518+3 Name A-Phase Current Peak Demand Attribute R Unite 0.001A Remarks Refer Peak Demand Stencil 40522+3 B-Phase Current Peak Demand R 0.001A Refer Peak Demand 38
Register
Name
Attribute
Unite
Remarks Stencil
40526+3
0.001A
40530+3
0.001A
40534+3
0.1W
40538+3
0.1Var
40542+3
0.1VA
39
Peak Demand Stencil Register Base Address Base Address +1 Base Address +2 Base Address +3 Remote control Register List Register 40546 Name On-off Input & Relay Output State Attribute R Remarks Digital Digital 00~07:correspond 08~11:correspond Peak Demand (H) R Peak Demand (L) R LONG Peak Occurred Time (H) R Name Peak Occurred Time (L) Attribute R Unite 1S Remarks ULONG UNIX Time form
Switch S1~S8; Relay RL1~RL4; Digital 12~15: remain Each Digital Value: 0 as Switch or Relay Off; 1 as Switch or Relay On;
40547
R/W
High byte : 0 as Local ContRl Model; 1 as Remote ContRl Model; Low byte : 0 as Normal Working model; 1 as Locking Working model; 2 as Timing Working model;
Relay 1 Timer value Relay 2 Working model Relay 2 Timer value Relay 3 Working model
40
Relay control write register (function code 0x05) Register Name Attribute Description
40555
Relay 1
Can be contRl as remote contRl mode Write 0xffoo relay close Write 0x0000 relay disconnection
40556
Relay 2
Same as above
40557
Relay 3
Same as above
Relay 4
Same as above
Name
Attribute
Description
Bit 00-05: relative limit value warning channel status RA1-RA6 RA1-RA6 Bit 08-11: relative logic warning channel status LA1-LA4 LA1-LA4 Bit 12-15: reservation Current bit is 0 is mean that channel did not send the warning 1 is mean that this channel had sent the warning
40560+ 3
Limit warning
value
R/W
channel RA1 40564+ 3 Limit warning channel RA2 41 value R/W Please refer to limit value warning type
Registe r 40568+ 3
Name
Attribute
Description
Limit warning
value
R/W
channel RA3 40572+ 3 Limit warning channel RA4 40576+ 3 Limit warning channel RA5 40580+ 3 Limit warning channel RA6 40584+ 3 Logic warning channel LA1 40588+ 3 Logic warning channel LA2 40592+ 3 Logic warning channel LA3 40596+ 3 Logic warning channel LA4 Limit value warning type Register Base address Name Limit value mode Attribute R/W Description Bit 7 of high byte is activation control bit when bit is 0 which mean limit channel prhibit to use When bit is 1 which meant limit value channel to be activated Bit 6 of high byte is limit value type control bit When bit is 0 which mean upper limit 42 R/W Please refer to logic warning type R/W Please refer to logic warning type R/W Please refer to logic warning type R/W Please refer to logic warning type value R/W Please refer to limit value warning type value R/W Please refer to limit value warning type value R/W Please refer to limit value warning type
Register
Name
Attribute
Description action when bit is 1 which mean lower limit action Bit 5-00 of high byte: (reservation) Low byte is limit value object 0 is A phase current 1 is B phase current 2 is C phase current 3 is zeR-sequence current 4 is max unbalance current; (reservation) 5 is current phase lost 6 is A phase voltage 7 is B phase voltage 8 is C phase voltage 9 is AB line voltage 10 is BC line voltage 11 is CA line voltage 12 is max unbalance voltage (reservation) 13 is max unbalance voltage(reservation) 14 is voltage lost
Base address +1
R/W
UINT
Base address+2
R/W
0-255
Base address+3
R/W
No.0 mean that warning output object is empty No.1 mean that warning output object is relay 1 No.2 mean that warning output object is 43
Register
Name
Attribute
Description relay 2 No.3 mean that warning output object is relay 3 No.4 mean that warning output object is relay 4
Logic warning type Register Base address Name Logic mode Attribute R/W Description Bit 15-12: logic type contRl bit Bit 11-08: logic object 3 contRl bit Bit 07-04: logic object 2 contRl bit Bit 03-00: logic object 1 contRl bit Logic type contRl bit define: 0 : logic channel pRhibit to use 1 mean as logic 2 mean or logic Logic object contRl bit define: 0: non-judge this object 1 is binary S1 2 is binary S2 3 is binary S3 4 is binary S4 5 is binary S5 6 is binary S6 7 is binary S7 8 is binary S8 9 is limit value warning channel RA1 10 is limit value warning channel RA2 11 is limit value warning channel RA3 12is limit value warning channel RA4 13 is limit value warning channel RA5 14 is limit value warning channel RA6 44
Register
Name
Attribute
Base address+1
Real
value
R/W
Bit 15-03: reservation Bit 02: logic object 3 real value condition Bit 01: logic object 2 real value condition Bit 00: logic object 1 real value condition Current bit is: 0: logic object is 0 to be fake Logic object is 1 to be real 1: logic object 0 to be real Logic object is 1 to be fake
condition
Base address+2
R/W
0-255
Base address+3
R/W
0: warning output object is empty 1: warning output object is relay 1 2: warning output object is relay2 3: warning output object is relay3 4: warning output object is relay 4
SOE event record register list SOE Register 40600+3 Name SOE event record 1 40604+3 SOE event record 2 40608+3 SOE event record 3 40612+3 SOE R Please refer to SOE event record 45 R Please refer to SOE event record type R Please refer to SOE event record type Attribute R Description Please refer to SOE event record type
Register
Attribute
Description
40616+3
40980+3
40984+3
40988+3
40992+3
40996+3
SOE event record type Register Base address Name Event type Current bit is 0 to be change status 10 Current bit is 1 to be change status 01 The rest word bit is event type 46 Attribute R Description The max word bit is event change status
Register
Name
Attribute
Description 0-7 relative to binary S1-S8 8-11 relative to relay RL1-RL4 12-17 is limit value warning RA1-RA6 18-21 is logic warning LA1-LA4 Other value invalidation 0x7FFF is event to be empty
Base address+1
0-1000
Base address +2
Base address +3
Simulation quantity input output register list Register 41000 Name Input simulation quantity 1 4-20mADC measurement value Attribute R Description 0.01mA Register UINT
41001
0.001V
UINT
41002
R/W
0 is A phase current
47
Register
Attribute
Description
Register 1 is B phase current 2 is C phase current 3 ce current 4 is A phase voltage 5 is B phase voltage 6 is C phase voltage 7 is AB line voltage 8 is BC line voltage 9 is CA line voltage 10 is A phase active power 11 is B phase active power 12 is C phase active power 13 is general active power 14 phase reactive power 15 phase reactive power is B is A is zero-sequen
48
Register
Name
Attribute
Description
Register 16 phase reactive power 17 is general reactive power 18 phase apparent power 19 phase apparent power 20 phase apparent power 21 is general apparent power 22 factor 23 factor 24 factor 25 is general power factor 26 frequency Other value invalidation is is C phase power is B phase power is A phase power is C is B is A is C
41003
Input
simulation
R/W 49
UINT
Register
Attribute
Description
Register
41004
R/W
UINT
41005
R/W
Same above
as
41006
R/W
UINT
41007
R/W
UINT
Measurement setting and status register list Register 41100 Name Measurement type system Attribute R/W Description 30 is three/three line system 40 is three/four
line system
41101
CT variable ratio
R/W
0-9999
41102
PT variable ratio
R/W
0-9999
41103
Equipment address
R/W
1-247
41104
Communication rate
baud
R/W
41105
Equipment password
R/W 50
Register
Name
Attribute
Description
41106
R/W
41107
R/W
41108
R/W
1000-5000
41109
R/W
1000-5000
41110
41111
Harmonic frequency
refresh
R/W
41112
R/W
Bit
15:
phase display
voltage interface
Bit 14: line voltage display interface Bit 13: phase display active display reactive display current interface Bit power interface Bit 11: power interface Bit 10: apparent power interface Bit factor interface 51 09: power display display 12:
Register
Name
Attribute
Description Bit 08: frequency display interface Bit 07: input active electric Bit active energy interface Bit energy interface Bit 04: output electric display 03: 02: 01: date time input reactive energy interface Bit Bit Bit display interface display interface simulation quantity 1 display interface Bit 00: input 2 simulation display interface Current bit is : 0: no display 1: display 05: input electric display reactive 06: energy output electric display display interface
System time (low word) System time (high word) The time of last
R/W R/W R
ULONG
0-255
electricity restoration 41116 The word) 52 last time for (low R ULONG
electricity time
Register 41117
Attribute R
Description
electricity
time (high
41118
41119
41120
41121
41122
41123
Equipment
hardware
The highest bit is revised year The second high bit month High bit is revised date Low bit is revised times is revised
41124
Equipment
hardware
41125
Equipment
software
41126
Equipment
software R
bit month
is
revised
Register
Name
Attribute
Description
41127
Equipment word)
code(low
The highest bit is revised year The second high bit month High bit is revised date Low bit is revised times is revised
41128
Equipment word)
code(high
41129
Equipment nameplate
High bit is rating voltage 1=100V 2=220V 3=380V 6=660V Low bit is rating current 1=1A5=5A
Register 41130
Attribute W
41131
41132
41133
Demand reset 54
Register
Name
Attribute
41134
41135
System restoration
41233
Refresh
to
manufacturing
Model :PMC200-A-B-C-D-E-F-G
G G Host D slot Expansion module 0 1 2 3 No RS232 Communication module TCP/IP module ProfiBus-DP module
Warning: A Host can match maximum 4 modules Example: Ordering model is: PMC200-3-1-1-1-1-1-0 That is , PMC200 with Rated measuring voltage, current: 220/380V 5APower system Frequency :50Hz Power Supply :85~265 VAC/45-65Hz 8-channel digital input module, Relay Output Module and 4 Analog Input / Output Module
56
Kingsine Electric Automation Co., Ltd. Address: 6/F, Block 4-CD, TianAn Cyber Park, Shenzhen 518048, China Tel: +86 - 755-88352611 Fax: +86 -755-88352611 URL: www.kingsine.com.cn E-mailchris@kingsine.com.cn
57