Asbestos Management.....................................................Art Schweitzer AED..........................................................................George Berndt AWAIR........................................................................Art Schweitzer Bleacher Safety............................................................ Art Schweitzer Bloodborne Pathogens......................................................Judy Huisman Community Right-to-Know...............................................Art Schweitzer Compressed Gas Safety...................................................Art Schweitzer Confined Space Entry.....................................................Art Schweitzer Emergency Action Planning...............................................Art Schweitzer Employee Right-to-Know/Hazard Communication...................Art Schweitzer Facilities Safety Management............................................Art Schweitzer First Aid/CPR ................................................................Judy Huisman Hazardous Waste Management..........................................Art Schweitzer Hearing Conservation.....................................................Art Schweitzer Indoor Air Quality..........................................................Art Schweitzer Integrated Pest Management............................................Art Schweitzer Laboratory Standard/Chemical Hygiene Plan......................................Matt McDowell Lead Management.........................................................Art Schweitzer Lockout/Tagout ...........................................................Art Schweitzer Machine Guarding .........................................................Art Schweitzer Personal Protective Equipment.........................................Art Schweitzer Playground Safety.........................................................Art Schweitzer Radon Gas Safety..........................................................Art Schweitzer Respiratory Protection...................................................Art Schweitzer USTs/ASTs...................................................................Art Schweitzer Welding Cutting Brazing....................................................Darrel Mayer
. . .
Notification appeared in the following publication(s): Name of publication Fall News letter Date Fall, 2010 .
Three-year re-inspection Surveillance was conducted: 6/29/2010 6-month Periodic Surveillance was conducted: 6/29/2010
(first date)
02/15/2011
(second date)
All caution labels have been posted. Label locations: Boiler room Tunnels Hard lagging
Are supplies of repair materials adequate to meet the requirements of maintenance and repair of ACM? Yes No N/A
Status of the Asbestos repair and maintenance Work Order System: N/A Established, Pending Comments: Repairs to asbestos are limited to replacement of damaged floor tile. **For information regarding the medical review and questionnaire, see the Respiratory Protection Program.** Note: click here this link to review 6 month periodics. The tunnels were cleaned and maintained during the summer of 2009. This work was conducted as O&M activities. LC
Gym entrance
Have all software updates been installed? Yes No N/A Date of update installation: 12-2010 Expiration date of pads? 12-2012 Expiration date of batteries? 01-2016
(date)
Has staff been trained on operation of the device? Yes, all school staff. Most recent date of training:12-2010
(date
Location of operators manual: Are battery checks documented? Yes, a check list is available at each AED station Notes:
Who is the Contact Person for OSHA 300? Darcy Groen Is the OSHA 300A Log completed for the previous calendar year? Yes Have the Logs been maintained for five (5) years? Location: Activities Manual Is the Log posted from February 1 until April 30? Yes Yes
The location/s of the posted log: Main School Office. Is information on injuries recorded on the Log with five (5) working days? Yes No N/A
Location
Principals office Principals office Principals office Principles office
Time
3:00pm 3:00pm 3:00pm 3:00pm
District Safety Committee Members Member George Berndt Judy Huisman Art Schweitzer Mike Palm Darin DeBoer Molly Schilling Darrel Mayer Dianne Johnson Darcey Groen Position Principal Lead Secretary Custodian Staff Staff Staff Staff Food Service Secretary Building Ellsworth Public Ellsworth Public Ellsworth Public Ellsworth Public Ellsworth Public Ellsworth Public Ellsworth Public Ellsworth Public Ellsworth Public
I have been given a copy of and have read or have had explained to me the information about hepatitis B and hepatitis B vaccine. I have had a chance to ask questions which were answered to my satisfaction. I believe I understand the benefits and risks of the hepatitis B vaccine, and request that it be given to me or to the person named below for whom I am authorized to make this request.
Please Print: Name_________________________________________Date of Birth_________________ Social Security or Visa #__________________________Employee #__________________ Department and Lab room #__________________________________________________ Principal Investigator________________________________________________________
Signature______________________________________Date________________________ Note: I have previously participated in an HBV vaccination program. Employer at time of vaccination _____________________________ Date ___________ Record maintained where __________________________________
Date: 2-15-2011
Dimension Of Confined Space 4X4X8 4X4X8 4X4X>200 4X4X>200 Potential Hazards Permit/ NonPermit Permit Required Permit Required Permit Required Permit Required Labeled Photo ID #
Boiler Room Boiler #1 Boiler Room Boiler #2 Boiler Room Tunnel access Boiler Room Water Tank #2
Has training been provided? Yes No N/A Date: N/A Presenter: N/A
Inventory Form
Client: Ellsworth Public School
Contact Person: Art Schweitzer Hazardous Material Quantity Date: 10-8-07 Location Reported on Tier Two Installation Date(s)
#2 Fuel Oil
5,000 gal
yes
1975
Note: a 6,000 gal tank was removed from service during the summer of 2006. The tank was approximately installed in 1975. The tank remains in place but has been pumped and filled with water. The tank had never knowingly leaked product into the ground. The remaining tank has been reported on the Tier II form. Sent 2-14-2008 The Tier Two can be managed on line see web site: http://minnesota.idsimaps.com/submit/T2_Menu.asp Login: dgroen25 Password: igloo55
Are MSDS available and located with the chemical inventory? Yes No Do the MSDS concur with the chemical inventory? Yes No Has training been provided for the following staff?
Art Instructors Custodians Food Service
Date: 2-15-2011
Checklist of E/OHS Activities for Facilities Safety Management and Fire Safety in Schools
Program Contact Person: George Berndt Is the Facilities Safety Management program in place? Yes No Does this school use contracted services for the Management Assistant Program? Yes No N/A If no, who is the designated person or persons?
Recommendations
Has annual report and license application sent in? Yes No N/A Note: A Hazardous Waste License Application was sent in on Jan. 9, 2009. The school is declaring that it is a VSQG and will not be required to pay a license fee. The science lab was cleaned this summer and the U of M removed the unneeded chemicals. It was reported that about 20 kilograms was removed. 1-9-2009 LC
Note: The school has continued to meet the VSQG criteria during the 20092010 school year. They are not required to report their waste generating activities. LC 4-5-2010 Note: The school has continued to meet the VSQG criteria during the 20102011 school year. They are not required to report their waste generating activities. LC 10-26-2010
Reason for Testing: General Survey Affected Personnel: Band Custodial, Maintenance, Shop Location Equipment Results Recommendations
Chop Saw Jet Router Delta Band Saw Stationary Belt/Disk Sander Radial Arm Saw Joiner Sander Planner
99.5.dBA 84.9 dBA 82.7 dBA 83.3 dBA 84.4 dBA 86.3-87.7 dBA 80.7 dBA
Note: No over limit exposures could be determined. However due to the exceptionally loud readings for short periods it is recommended that hearing protection be provided to affected staff. LC
Training conducted Aug 29, 2007 Training has been scheduled for ____N/A___________.
(date)
Has the District determined the mechanical ventilation rate of each occupied space? Yes No. Supportive technical services were conducted on: 2/26/2010.
(date)
The results indicate air velocity to be: satisfactory, unsatisfactory, N/A. Chemical inventory: Date of most recent survey: 2009-2010 school year Location of inventory listing: Science Room Are Material Safety Data Sheets (MSDSs) located with inventory? Yes No N/A The MSDS are listed at the following website: http://www.flinnsci.com/search_MSDS.asp Are the MSDS readily accessible? Yes No N/A Has the Minnesota Dept of Ed Science Lab Checklist been completed? Yes No N/A Is training for affected personnel complete? Yes No N/A Date(s) of instruction: Roster signed? Yes No N/A Lesson plan outline available with roster? Yes No N/A Status of Emergency Eye Wash/Deluge Shower: Is flushing conducted weekly? Yes No N/A Is descriptive signage properly posted? Yes No N/A Is flushing activity documented? Yes No N/A
X X X
X X
UFC (97) Appendix 1-A 7.2 as amended UBC (97), 305.2.4 UFC (97) 1007.2.4.2 & 1007.2.4.1.1 as amended
9) All electrical outlets must be properly grounded and all fixed electrical equipment and appliances must be plugged in to grounded outlets as required by the electrical code. ITEM 10) Electrical receptacles, switches, and controls must be located so as not to be subject to liquid spills. 11) Extension cords must not be used as a substitute for permanent wiring. 12) The use of multi-plug adapters, octopus arrangements, cube adapters, strip plugs, or any other device that does not comply with the electrical code is prohibited. 13) A minimum of 30 of clearance must be maintained in front of electrical control panels for access. 14) Written procedures for laboratory emergencies, including emergency evacuation, must be developed for each lab. 15) Piping systems must comply with nationally recognized standards. 16) Enough eye protection devices (goggles) must be provided for every student in the room, visitors, and the teacher whenever potentially hazardous activities are taking place. 17) Refrigerators, freezers, and other cooling equipment used to store of cool flammable liquids must be of explosion-proof construction 18) Each refrigerator, freezer, or cooler must be prominently labeled to indicate whether it is or is not suitable for storing flammable liquids. 19) Flammable liquids stored in refrigerated equipment must be in closed containers.
UFC (97) 8504 99NEC 250-112 CITATION NFPA 45 (91) 3-6.1 UFC (97) 8506.1 UFC (97) 8507 UFC (97) 8509.2 NFPA 45 (91) 4-6.3.1 NFPA 45 (91) 8-1.1 MN Public Law, section 126.20 NFPA 45 (91) 9-2.2.2 NFPA 45 (97) 9-2.2.1 NFPA 45 (91) 9-1.6.6
X
CONDITION LACKING
EXISTS
N/A
X X X
ANSI Z-358.1-1981
X
UFC (97) 8001.11.1.1
X X
X
NFPA 45 (91) 6-13 UFC (97) 8004.1.12 UFC (97) 8001.4.4 & 8001.4.7.1 Recommendation
X X X
ITEM 14) It is recommended that due to the serious explosion hazard present, the following chemicals not be used in an instructional setting: Benzoyl Peroxide Percholoric Acid Carbon Disulfide Picric Acid Ethyl Ether Potassium Metal Magnesium Powdered Metal 15) Loose clothing (e.g., full cut blouses, neckties, etc.) and long hair should be properly restrained. Also, some laboratory activities could be dangerous to persons wearing contact lenses.
CITATION
EXISTS
CONDITION LACKING
N/A
X
Recommendation
X
Recommendation
X
UFC (97) 7902.5.8
X
UFC (97) table 7902.5-A
UFC (97) 7902.1-A UFC (97) 7902.5.4 UFC (97) 7401.7.1 UFC (97) 7401.6.4 UFC (97) 8001.6 UFC (97) 8001.4.2
X X X X X X
ITEM 12) All shelving must be of substantial construction and properly secured to prevent falling over. (Shelving above work areas should be kept free of chemicals; storage above eye level should be avoided.) 13) Shelving must be equipped with a lip or guard to avoid products rolling off. 14) Defective containers must be removed and disposed of in a proper manner. 15) Disposal of chemical wastes must be in accordance with applicable federal and state regulations and good safety practices. 16) All storage cabinets and storage rooms must be locked or otherwise secured against unauthorized entry. 17) All containers must be properly labeled to identify the contents. 18) Toxic and highly toxic compressed gas, Class IV liquid, solid oxidizers, unclassified detonable, Class I organic peroxides, Class III and IV unstable and reactive material shall not be allowed in the classroom. 19) When transferring flammable liquids between metal containers, the containers must be properly bonded together. The practice of purchasing large containers and dispensing into smaller ones is discouraged.
CITATION UFC (97) 8001.11.9 UFC (97) 8001.11.9 UFC (97) 8001.4.7.3 UFC (97) 8001.5.1 UFC (97) 8001.11.2 UFC (97) 8001.7 UFC (97) 8001.15.2.4
EXISTS
CONDITION LACKING
N/A
X X X X X X X X
UFC (97) 8001.11.5
TABLE 7902.5-A: EXEMPT AMOUNTS OF FLAMMABLE AND COMBUSTIBLE LIQUIDS MAXIMUM QUANTITIES STORED PER CONTROL AREA1,2,3
TYPE OF LIQUID EXEMPT AMOUNT (gallons) Flammable Class I-A 30 Class I-B 60 Class I-C 90 Combination I-A, I-B, I-C 1204 Combustible Class II 120 Class III-A 330 Class III-B 13,2005 1 Control areas shall be separated from each other by not less than a one-hour fire-resistive occupancy separation. The number of control areas within a building used for retail or wholesale sales shall not exceed two. The number of control areas in buildings with other uses shall not exceed four. See Sections 204 and 8001.10.2. 2 Quantities are allowed to be increased 100 percent when stored in approved storage cabinets. When Note 3 applies, the increase for each Note is allowed. 3 Quantities are allowed to be increased 100 percent in buildings equipped with an approved automatic sprinkler system. When Note 2 applies, the increase for each Note is allowed. 4 Combinations shall not contain more than the exempt amounts of any individual class. 5 Quantities permitted in a building equipped with an approved automatic sprinkler system are not limited.
SUSPECT CARCINOGENS Cadmium/Cadmium Compounds Carbon Tetrachloride Chloroform DDT 2,4D Methylene Chloride Formaldehyde (Gas) Lead Acetate Lead Phosphate Nickel/Nickel Compounds (Powder) Saccharin Urethane
OTHERS
List total time (in hours) employee is exposed to carcinogens (checked chemicals above) per academic year. N/A hours per academic year
Are checked chemicals required, or could acceptable substitutes be implemented? Will retain carcinogen in curriculum chemicals Will discontinue use of
3. Use of Personal Protective Equipment, like impermeable gloves, aprons, and face shields. 4. Protect surfaces where carcinogens are handled by using chemically resistant trays or pans that can be decontaminated. 5. On leaving a controlled area, laboratory workers should remove any protective apparel that has been used and thoroughly wash hands, forearms, face, and neck. If disposable apparel or absorbent paper liners have been used, these items should be placed in a closed and impervious container that should then be labeled in some manner such as the following: CAUTION CONTENTS CONTAMINATED WITH SUBSTANCES OF HIGH CHRONIC TOXICITY. Non-disposable protective apparel should be thoroughly washed, and containers of disposable apparel and paper liners should be incinerated. 6. Wastes and other contaminated materials from an experiment involving substances of high chronic toxicity should be collected together with the washings from flasks and such and either decontaminated chemically or placed in closed, suitable labeled containers for incineration away from the controlled area. If chemical decontamination is to be used, a method should be chosen that can reasonable by expected to convert essentially all of the toxic materials into nontoxic materials. For example, residues and wastes from experiments in which B-propiolactone, bis (chloromethyl) ether, or methyl chloromethyl ether have been used should be treated for 10 minutes with concentrated aqueous ammonia.
In the event that chemical decontamination is not feasible, wastes and residues should be placed in an impervious container that should be closed and labeled in some manner such as the following: CAUTION COMPOUNDS OF HIGH CHRONIC TOXICITY or CAUTIONCANCERSUSPECT AGENT. 7. Transfer of contaminated wastes from the controlled area to the incinerator should be done under the supervision of authorized personnel and in such a manner as to prevent spill or loss. In general, liquid wastes containing such compounds should be placed in glass or polyethylene (usually preferable) bottles half-filled with vermiculite, and these should be transported in plastic or metal pails of sufficient capacity to contain the material in case of accidental breakage of the primary container. 8. Normal laboratory work should not be resumed in a space that has been used as a controlled area until it has been adequately decontaminated. Work surfaces should be thoroughly washed and rinsed. If experiments have involved the use of finely divided solid materials, dry sweeping should not be done. In such cases, surfaces should be cleaned by wet mopping or by use of a vacuum cleaner equipped with a high efficiency particulate air (HEPA) filter. All equipment (e.g., glassware, vacuum traps, and containers) that is known or suspected to have been in contact with substances of high chronic toxicity should be washed and rinsed before they are removed from the controlled area. 8. In the event of continued experimentation with a substance of high chronic toxicity (i.e., if a worker regularly uses toxicologically significant quantities of such a substance three times a week), a qualified physician should be consulted to determine whether it is advisable to establish a regular schedule of medical surveillance or biological monitoring. Note: Chemical MSDS may be obtained at the following website: http://www.flinnsci.com/search_MSDS.asp
Is a map of all potable water taps available for review? Yes No N/A
Is the Machine Guarding Plan for each affected work area in place? Yes No Is the plan/plans current? Yes No Has the Plan been reviewed this school year? Yes No Has a survey of all district fixed equipment been conducted? Yes No When was the evaluation completed? _______________________ Who conducted the evaluation? _______________________ How are corrections documented? _______________________________ Is all fixed equipment safeguarded to meet OSHA criteria? Yes No Has the alternative MDE best practices criteria used to safeguard equipment? Yes No Has equipment determined not in compliance scheduled for repair or replacement? Yes No N/A If replaced, was best practices, bid specification criteria used for procurement? Yes No
Automotive Shop Wood Shop Custodial/Maintenanc e Welding Shop Ag Shop Bus Garage Art Scene shop Science Contracted technical services to review and recommend? __________________. Name of person or contractor conducting survey? ___________________.
(date)
Results of technical services located where? ________________________ Checklist for minimum requirements: Power outage protection provided for required equipment Emergency stops provided for required equipment Safe work practice placards at applicable fixed tool stations Proper guards provided and used Color coding as prescribed by OSHA standards Non-slip surfaces by each piece of equipment Fixed equipment secured to prevent walking or movement Has a log of employee accidents and near misses been established and used? Yes No Annual training for affected staff is provided? Yes No Training conducted ____________. Training has been scheduled for ____________. (date)
(date)
General Hazards: X X X X X X There are no sharp points, corners, or edges on the equipment There are no missing or damaged protective caps or plugs There are no hazardous protrusions and projections There are no potential clothing entanglement hazards, such as open Shooks or protruding bolts There are no pinch, crush, and shearing points or exposed moving parts There are no trip hazards, such as exposed footings on anchoring devices and rocks, roots, or any other environmental obstacles in the play area
Deterioration of the Equipment: X The equipment has no rust, rot, cracks, or splinters, especially where it comes in contact with the ground
There are no broken or missing components on the equipment (e.g., handrails, guardrails, protective barriers, steps, or rungs on ladders) and there are no damaged fences, benches, or signs on the playground All equipment is securely anchored
Security of Hardware: X X There are no loose fastening devices or worn connections, such as Shooks Moving components, such as swing hangers or merry-go-round bearings, are not worn
Drainage: X The entire play area has satisfactory drainage, especially in heavy use areas such as under swings and at slide exits
Leaded Paint: X X The leaded paint used on the playground equipment has not deteriorated as noted by peeling, cracking, chipping, or chalking There are no areas of visible leaded paint chips or accumulation of lead dust
General Upkeep of Playgrounds: X X The entire playground is free from miscellaneous debris or litter such as tree branches, soda cans, bottles, glass, etc. There are no missing or full trash receptacles
Click here to view playground equipment. Note: Recommend replacing trip hazard wood retainers with plastic retainers. LC 4-7-2010
Hazard (Heat, Noise, Radiation) Heat, chemical, body fluids, noise, asbestos Noise, chemical, hot water, Heat, chemical, body fluids, noise Noise, impact, compressed gas, dust
Affected Employees Name Art Schweitzer Margaret L. Dianne J. Molly Shilling Darrel Meyer Department Custodial/Maintenance Food Service Food Service Education (science) Tech Ed
________ Date_4-06-10_____________
Location: Chemistry Employee: Molly Gort Nitrile Latex Vinyl Leather Neoprene Impact Splash Shield Respirator Muffs Plugs Neo Apron Denim Steel Toes Metatarsal Hard Hat
X X X X X X X
X X X X X X X X X X X X X X
Hand
Face
X X X
Hazard(s)
Heat, chemical, body fluids, noise, open flame, impact Suggest additional hearing protection for students
Date 2/15/2011
Results of tests:
Room Name & No. Level Tested Recommendation
Has training is not requirement of this program. However if elevated levels are determine present training of affected persons is recommended. Date training complete: N/A Testing is / is not now in progress: Note: No records could be located that indicated testing for radon in the past. I recommend that areas below grade be tested.
N/A.
(date)
Type of testing protocol; Irritant Smoke (Stannic Chloride) or Bitrex (Denatonium Benzoate)
Condition and location of respirators: Condition: Good condition Location(s): In metal cabinet next to desk in boiler room.
Are the appropriate adequate accessories on hand? Yes No N/A Verified by Lee Carlson
Respirator Equipment Inventory Cartridges Respirator Type PAPR Power Flow PAPR Power Flow mask mask mask Full face Full face Wilson Boiler room yes yes yes Respirator Brand Location Valve Flaps? Straps? Organic Particulate Combination
AOS
Boiler room
yes
yes
yes
The respirators were cleaned and checked 1-4-10. LC Art is no longer fit checked and having physicals completed as a requirement of the local fire department. Future use will be on a voluntary basis.1-4-10
Tank No.
Location
Size
Contents
Registered
Install date
#1
5,000
#2 fuel oil
yes
Regulated Tanks:Motor fuel tanks larger than 110 gallons Non-regulated Tanks:Heating oil tanks Requirements for All USTs: Tank must be registered with MPCA Requirements for Regulated Tanks:Annual tightness testing and inventory control Tank must be updated, replaced, or removed by December 22, 1998 Upgrades: --Overfill protection --Corrosion protection STPI approved
--Leak detection Tightness Testing Results on File: Dates of past testing:_____N/A_______________ Records on file:_____N/A___________________
Is the Welding and Brazing Plan in place? Yes No Is the Plan current? Yes No Has the Plan been reviewed this school year? Yes No Method or methods used to control airborne particulate matter? negative air and internal filters Has training been conducted for affected personnel? Yes No Type of welding equipment available Electric arch. Yes No N/A Wire feed/TIG MIG. Yes No N/A Electric spot weld Yes No N/A External
Personal Protective Equipment: availability and condition Gloves Yes No N/A Goggles Yes No N/A Welding mask Yes No N/A Apron Yes No N/A Steel toed shoes Yes No N/A
Describe location of welding activities, example; out-of-doors, booth, floor, all of the above: Welding can conducted indoors or out. The air filter is adequate to handle a significant particle load.