Sie sind auf Seite 1von 5

2004 E E E International Conference on Electric Utility Deregulation, Restructuring and Power Technologies (DRPT2004) April 2004 Hong Kong

Some Novel Techniques for Improving Power Quality in Distribution Networks


Zeng Xiangjun, MEEE, Li K.K, Senior MEEE, Chan W.L., Senior MEEE, Yin Xianggen, Non-Member

Abstract--Power quality is influenced by neutral grounding (DA), which only isolates faulty section without interrupting
methods in distribution systems. Optimization for neutral grounding the power supply to the healthy sections, and which clears
methods is discussed in the paper. Petersen-coil in parallel with high impermanent fault without interrupting the power supply in
resistance earthed technique has a better performance in safety and ineffectivily neutral earthed conditions. The above are difficult
power quality than other neutral point grounding techniques. To
improve power quality, a novel method for measurement of zero to be implemented, and are influenced by neutral earthed
sequence impedance in distribution systems is presented, method.
Petersen-coil inductance is adjusted to compensate the total
capacitance, and the resistor which is in parallel with the A. Selection of Neutral Grounding Method
Petersen-coil is adjusted to control the over-voltage; some other In distribution system, fault detection and over-voltage
novel techniques for grounding fault feeder protection based on suppression are related to the method of neutral grounding. In
testing the fault resistance or the energy dissipated in the fault point solid or low resistance earthed system, the grounding fault
are also presented. The method of Petersen-coil tuning has been current magnitude is large for easy detection, but the arc
developed. Experimental results show that the optimization for grounding fault is difficult to be self-extinguished, and the
neutral grounding methods and the protections proposed can improve
the power quality by reducing the over-voltage, the residual current over-voltage is suppressed. In resonance or high resistance
and the grounding fault duration. earthed system, the arc grounding fault is easy to be
self-extinguished, but the grounding fault current is small for
Index Terms-Power quality, Petersen-coil tuning, Protective detection, and the over-voltage is high. Every type of neutral
relaying, Fault detection grounding technique has virtues as well as defects. It is difficult
to decide the method of neutral grounding.
I INTRODUCTION In China, most distribution networks are isolated systems or
In recent years, both industrial and commercial customers resonant earthed neutral systems, which have been operated
of electric utilities have reported rising incidences related to over 50 years with a good record. Most instantaneous
power quality. The power quality problem can be described as grounding fault can be self-extinguished, and the system can
voltage dips and fluctuations, momentary interruption, continue operation until the load of the faulted feeder is
harmonics, transient surges, and so on, resulting in redirected while permanent single-phase grounding fault
misoperation and failure of line or equipment. These occurs. At present feeders are extended at a fast rate and their
disturbances and interruption, though always existed on utility capacitance to ground increases dramatically. Consequently,
system, degrade the reliability and quality of the power supply, arc grounding fault cannot be self-extinguished in isolated
and nowadays causing more and more troubles. This is due to systems. In order to self-extinguish the arc grounding fault and
the increased refinement of today's automated equipment, such to suppress over-voltage, many utilities change isolated system
as variable-speed drives, automated production lines or to resonant earthed system. In the process of developing
machine tools, programmable logic controllers or power distribution automation, Petersen-coil need to be tuned
supplies in computers. They are far more vulnerable to automatically and grounding fault to be detected
disturbances on the utility systems than previous less
automated production and information systems ['I. B. Petersen-Coil Tuning
More peoples now pay attention to improve power quality Most Petersen-coils are unadjustable on-line. Only in the
in distribution systems. It needs to suppress the over-voltage, last several years, some automatic tuning systems of
to detect and isolate faulty section when fault occurs. Among Petersen-coil have been developed
all faults, more than 80 percent occurs in distribution systems. Traditional principle to determine the appropriate coil
In these faults, about 80 percent are grounding faults, and position of Petersen-coil is based on an analysis of the
among grounding faults, about 90 percents are instantaneous neutral-to-earth voltage (i.e., resonance curve). This principle
faults. Many utilities want to develop distribution automation has some limitations. For example, a variation in the coil
inductance is necessary for the present measurement of
This work was supported in part by Hong Kong Polytechnic University system's capacitive current, which generally includes frequent
Research Grant GYC52 and National Natural Science Foundation of China operation upon the coil ['Ir3], and it is difficult to carry out in
50207001.
large distribution networks, which contain several
Zeng Xiangjun is with the College of Electrical and Information
Engineering, Changsha University of Science and Technology, Changsha, Petersen-coils.
Hunan Province, 4 10077, China (e-mail: eexjzeng@maiI.csuep.edu.cn).
Li K.K. is with the Department of Electrical Engineering, Hong Kong C. Grounding Fault Detection
Polytechnic University (e-mail: Gilbert.KK.Li@polyu.edu.hk),
In isolated systems, the grounding fault feeder can be
Chan W.L. is with the Department of Electrical Engineering, Hong
Kong Polytechnic University (e-mail: eewlchan@polyu.edu.hk). detected by comparing the amplitude of hndamental zero
Yin Xianggen is with the College of Electrical & Electronic sequence current or their phases. Whereas, in resonant earthed
Engineering, Huazhong University of Science and Technology, Wuhan, systems, grounding fault current is very small and their
430074, P.R. China (e-mail: xgyin@mail.hust.edu.cn) direction is disturbed by the compensation current due to
0-7803-8237-4/04/$17.0002004IEEE

306
2004 IEEE International Conference o n Electric Utility Deregulation, Restructuring and Power Technologies (DRPT2004) April 2004 Hong Kong

Petersen-coil. It is thus impossible to detect it by comparing the transient neutral voltage and generator frequency has been
amplitude of findamental zero sequence current or their tested by TNA. The result is shown in Fig.1, where
phases. On the other hand, Petersen-coil has high impedance to Petersen-coil entirety compensates capacitance of generator
high order harmonics. The grounding fault feeder can be unit to ground in system frequency (60Hz).
detected by comparing the amplitude of all feeders or phases of U0 (p. U. 1
harmonic zero sequence current. Among high order harmonic
currents, the fifth order harmonic current is the best one to be
applied to detect the grounding fault feeder. Many utilities
have implemented this method 12’ [31. Whereas, the high order
harmonic current is very small and varies in different systems,
it often has poor sensitivity in
Another way to detect arc grounding fault feeder was
developed in France [41. It measures the transfer of zero
sequence energy during the first 20ms after grounding fault 50 55 60 65 70
happens. When high impedance grounding fault occurs, the fkquence (Hz)
zero sequence voltage is very low, and the transfer of zero Fig.]. Test result of maximum transient neutral voltage varying with
sequence energy is also limited and hence this method also has frequency in generator units. Curve 1 - Petersen-coil directly grounding
poor performance in detecting high impedance grounding system by GE company P.G.Br0-m; curve 2 - counting for leaking resistance
fault. by Tsinghua university (in China); curve 3 - Petersen-coil in parallel
connecting high resistance grounding system by M.V.Hadded (U.S.A); curve
In order to enhance power quality in distribution systems, 4 - high resistance grounding system.
the selection of neutral grounding method is discussed in this
paper. A novel technique for Petersen-coil tuning based on From Fig. 1, it is found that the over-voltage of generator unit
injecting different frequency currents is presented. The with Petersen-coil in parallel with high resistance earthed
appropriate coil position is calculated easily by measuring the system is lower than that in Petersen-coil directly earthed
system resonance frequency. Another novel technique for system. Two methods can usually satisfy requirement of safety
grounding fault detection based on testing the fault resistance if generator frequency is between 55Hz and 65Hz.
or the energy dissipated at the fault point is also presented. It is However, in resonance neutral earthed distribution system,
not influenced by the method of system neutral point grounding capacitance varies with the topologic changing, and
grounding and it can be applied in detecting arc grounding compensated inductance varies with Petersen-coil tap
fault. changing, but system frequency is quite constant. The
resonance deviation is defined as:
11. OPTIMIZATION ON NEUTRALGROUNDING
METHOD I -I,
v = ~ x 1 0 8 ! (1)
4
There are a wide variety of neutral grounding techniques Where: I,, grounding capacitance current; I,, inductive current
throughout the world: solidly earthed neutral system (UK), flowing in Petersen-coil.
systematic and multiple grounding (U.S and Canada), through The maximum transient voltage varies with resonance
impedance (France, Spain, etc) or resonant (Germany,
WP.4
Scandinavia, China, etc) earthed neutral systems.1n order to
estimate the impact of neutral grounding method on power 4.01 1
quality, four criteria must be examined:
0 fault voltage Vf,
ability of self-extinguishing arc grounding fault,
0 grounding fault detection,
0 safety.
The impact of grounding fault will depend on value of these
four criteria and on the fault duration.

A. Impact of Fault Voltage


In resistance neutral grounding system, lower the resistance -jO% -15% 0 15% 30% v
can help to reduce the fault point voltage in grounding fault Fig.2. the relation of maximum transient over-voltage and resonance
deviation in resonance neutral earthed distribution system. curve 1 -
condition. Experiences in China show when the resistance is Petersen-coil directly grounding system; curve 2 - Petersen-coil
lower than distribution’s capacitive impedance, the fault point parallel connecting high resistance grounding system.
voltage is usually lower than 2.6p.u., which usually satisfy the
deviation while grounding fault occurs. In a distribution
requirement of suppressing over-voltage.
network, the relation of maximum transient voltage and
In resonance neutral earthed generator unit, grounding
resonance deviation obtained from EMTP simulating is shown
capacitance is constant, but frequency sometimes varies. The
in Fig.2. The resistance parallel connected Petersen-coil can
maximum transient voltage varies with generator frequency
suppress over-voltage. If resonance deviation is controlled in
while grounding fault occurs. The relation of maximum
the range from -10% to lo%, over-voltage can usually satisfy

307
2004 IEEE International Conference on Electric Utility Deregulation, Restructuring and Power Technologies (DRPT2004)April 2004 Hong Kong

requirement of safety. grounding fault current is limited to a low value by


Petersen-coil automatic tuning, arc grounding fault can be
B. Self-extinguish Arc Fault self-extinguished, transient voltage can be suppressed and
Among all neutral earthed methods, the capacitance current grounding fault current will not be harmful to people and
is compensated in resonance neutral earthed method, so the equipment. On the other hand it is difficult to detect the faulted
grounding fault current is small. If the fault current is limited in feeder. With technology development, Petersen-coil tuning and
1OA(35kv) or 20A( 1Okv) by Petersen-coil automatic tuning, fault feeder detecting can be implemented. Resonance neutral
instantaneous fault can self-clear without interruption. earthed technique, especially Petersen-coil in parallel with high
Arcing-fault usually amounts to 80 percent in all faults. resistance earthed technique, will have better future in
Therefore, resonance neutral earthed system with Petersen-coil improving power quality.
automatically tuning can improve power quality effectively.
In. AUTOMATICALLY
PETERSEN-COIL TUNING
C. Grounding Fault Detection
Among all neutral earthed methods, resonant earthed The Petersen-coil automatic tuning system includes the
neutral system has the poorest sensitivity to protect against measurement of capacitive current and Petersen-coil
grounding In order to improve, many utilities tuning.With a signal injecting from neutral point to distribution
introduce earthing via Petersen-coil in parallel with high systems, the signal voltage U@ and the signal current I,,@ are
resistance. By selecting an optimization value of resistance, not measured, the zero sequence impedance Z @ can be calculated
only grounding faults can be detected, but also arc faults can be by:
self-extinguished. Moreover, it has a better performance of
suppressing over-voltage.

D. Safety Based on the zero sequence impedance, total grounding


Safety to people and equipment is related to fault current, capacitance and leakage conductance of equipment and
fault-voltage and fault duration when grounding faults occur[61. feeders are obtained. Petersen-coil inductance is adjusted to
In low resistance neutral earthed system, although the fault compensate the total capacitance. The resistor which is in
breakout is instant, fault current is large, step-voltage around parallel with the Petersen-coil is adjusted to control
the fault point is high, and hence it will threaten people’s safety over-voltage during system normal operation.
if they are near the fault point.
In some countries, the grounding point of MV neutral is not
isolated to the grounding point of LV neutral line. Moreover,
consumer’s neutral line is not connected with metal structure or
pipe of building. An example is showed in Fig.3. The lOkV
network’s neutral is grounded through a low resistance R. One
distribution transformer’s high-voltage coil is discharged to the
tank. This fault current makes the voltage of neutral point in
low-voltage system (380V) rising to rather high voltage Uf.
Their voltage at the tank is also rising to UJ, It will threaten
people’s safety.
Fig.4. the equivalent circuit for current injection
lOkV 380V
A. Measurement of Capacitive
A different frequency constant current is injected through
the secondary side of zero sequence voltage transformers,
which is contained in the Petersen-coil, into the zero sequence
circuit from a source of constant current as shown in Fig.4. The
+ -I- signal frequency is changed until the resonance frequency of
the compensated network is found.
Fig.3. Fault in low resistance earthed neutral system The total capacitance (3C=CI+ Cz+ C , ) to earth of
cause appliance electrified compensated networks can be calculated by:
Whereas, in resonance neutral earthed distribution system, 3c = - I (3)
grounding fault current is low, voltage at the fault point is also 06L
low. Grounding fault, thus, do not threaten people’s safety. Where: Q, is the resonance angular frequency, L is the
On all accounts, in low resistance neutral grounding system, inductance of Petersen-coil.
transient voltage is suppressed and grounding fault feeder is Therefore, the total capacitive current is:
easy to be detected, but arc grounding fault is difficult to be
self-extinguished and grounding fault usually threatens the
I , = 3mcu = =
(4)
0:L
safety. However, in resonance neutral grounding system, if Where: o is the system angular frequency, U is the phase

308
2004 IEEE International Conference on Electric Utility Deregulation, Restructuring and Power Technologies (DRPT2004) April 2004 Hong Kong

voltage of system. capacitive current of substation is 2.5A and that the capacitive
The resonance deviation of compensated networks can be current of every kilometer overhead line is 0.106A. From this
determined by: table, we can find that the largest error is 0.6A. The reasons for
WU U (5) error maybe:
A. The estimated value of capacitive current is not accurate.
B. The inductive current of Petersen-coil changes in testing
Where:h, resonance frequency; J; system frequency (50Hz in because of the nonlinearity of magnetic curve.
China). C. the test error of the prototype.
The inductive current of the compensated system can be
read through the switch tap of Petersen-coil. So, the capacitive N. GROUNDING
FAULTDETECTION
current of the network can be calculated easily:
A. Protection for High Impedance Grounding Fault
In resonant earthed systems, the ground fault current is very
Where: Z,,the sum of all Petersen-coils’ inductive current in the small. The direction and amplitude of fundamental zero
sequence current is disturbed by the current of compensation
compensated networks.
coil. Even in high impedance ground fault condition, it is
When a distribution system has several Petersen-coils, the
resonance deviation and capacitive current of the whole impossible to detect the faulted feeder by the fundamental zero
network can be calculated easily by selecting one Petersen-coil sequence current protection. Two methods for high impedance
to inject signal current and to observe the system resonant earth fault detection are presented below.
frequency.
(1) Relay on Grounding Fault Resistance
B. Petersen-coil Tuning After zero sequence voltage is started up (larger than its
One solution to Petersen-coil tuning is to use plunger core threshold), fault grounding resistance is calculated by fault
coils, which are effective for fine and continuous tuning but phase voltage and fault components of three phase currents.
expensive. Another useful, but much less expensive solution is R - . U, (7)
a switchable fixed coil system with a control switch which has - A I A -(AiB +Aic)12
many taps (from 7 to 20). Some switches are adjusted by Where, U, is the fault phase voltage, ZA, ZB and Zc are phase a, b
manpower. Others are driven by motor and controlled remotely and c’s current variation respectively.
by computer. The former is popular in China, but now the latter When the fault resistance is lower than a threshold,
is becoming popular in some distribution automation systems. ground fault is detected.
While the capacitive current and resonance deviation is
measured, Petersen-coil automatic tuning is implemented by (2) Relay on fault-point energy dissipation
adjustment at real time. Petersen-coil tuning assures resonance After zero sequence voltage is started up (larger than its
deviation in the range of -5% - -10% and residual current of threshold), the energy dissipated at the fault point is calculated
grounding fault point in the range of 0-1 5A. as :
Wf= X u a ( A i A-(AiB + A i c ) / 2 ) (8)
C. Practical Experience of Petersen-coil Timing When the energy dissipated is higher than a threshold,
The prototype for Petersen-coil tuning is developed, and ground fault is detected. The method can detect arc grounding
has already been tested in the network for several years. Some fault.
operation feedback has already been received. The capacitive
current of one 35kv distribution networks in Minlou (Hunan B. High Impedance Grounding Fault Protection Implemented
province, China) was measured on January 6,1997. Each in FTU
feeder was switched on or off, and the result for capacitive The Field Terminal Unit (FTU), a device for distribution
current was tested (TABLE. 1). system automation, is developed with DSP TMS320F206 and
TABLE.l 14 bit A/D transform as shown in Fig.5.
TESTRESULTFOR CAPACITIVE CURRENT ON NETWORK

2 1 13.6 I 45.250 I 16.6 I 17.01 I 136.9


2 1 13.6 I 41.863 I 19.4 I 19.95 I 164.6
In the above table, the estimation value of capacitive current
is the sum of all feeders and substation. It is estimated that the Fig.5. Prototype of FTU

309
2004 IEEE International Conference o n Electric Utility Deregulation, Restructuring and Power Technologies (DRPT2004) April 2004 H o n g Kong

C. Test with Dynamic Simulation developed and has been tested on power systems for several
years.
To improve power quality, some other novel techniques for
grounding fault feeder protection based on testing the fault
resistance or the energy dissipation in the fault point are also
presented. The proposed grounding fault protection methods
are implemented in FTU for distribution automation systems.
Experimental results show that the optimization for neutral
Fig.6. Model of dynamic simulation test grounding methods and the protections proposed can improve
TABLE. II
power quality by reducing over-voltage, residual current and
TESTRESULTSFOR HIGH lMPEDANCE GROUNDING
FAULT the grounding fault duration.

VI. REFERENCES
[ I ] L.Angrisani, P.Daponte, M.D’ Apuzzo, A.Testa. “A measurement
method based on the wavelet transform for power quality analysis” IEEE
Transaction on Power Delivery, Vol. 13, No.4, Oct. 1998, pp.990-998.
[2] Fushou Li. “Electrical Power system with neutral ineffective Grounding”
Beijing: Electric power publication (in Chinese). 1993. pp98-I 1 I
[3] “IEEE recommended practice for grounding of industrial and commercial
power systems,” IEEE Std 142, 1991. pp. 17-80,
[4] D.Griffel, Y Harmmand. “A new deal for safety and quality on MV
networks”. IEEE Transactions on Power Delivery, Vol. 12, No.4, 1997,
3313.1428-1433.
[5] Zeng Xiangjun, Yin Xianggen, and Chen Deshu. “A novel technique for
measuring grounding capacitance and ground fault resistance in
ineffectively grounded systems,” IEEE Power Engineering Review,
Note: Resistance Relay is the relay with Grounding Fault Resistance, Energy Relay is V01.20, NOS, 2000, pp.72-73
the relay with fault-point energy dissipated. [6] Zeng Xiangjun, Li K.K., Chan W.L., Yin Xianggen, ‘On Site Evaluation
for Ground Fault in Mining Power Systems’, 2001 IEEE Indusfry
Tests have been carried out on a dynamic power system Application Sociefy Annual Meeting, Chicago, U.S.A., Oct. 2001, Vol. 2,
model in the laboratory. The configuration for the test system pp. 1404- I4 I0
[7] Zhu Jun. David L. Lubkeman. “Automated fault location and diagnosis
is shown in Fig.6. In the dynamic simulation test model on electric power distribution feeders”. IEEE Transactions on Power
(Shown in Fig.S), L1 is a long line of 260 km,equivalent of Delivery, V01.12, No.2, 1997, pp.801-809.
many power lines; L2 and L3 are short lines, FTU is installed [8] Zeng Xiangjun, Yin Xianggen, Zhang Zhe, Chen Deshu, and Wen
onL3. By changing the neutral earthed method and fault point, Minghao, “Study on feeder grounding fault protection based on zero
sequence admittance” (in Chinese) Proceedings of the Chinese Society
the zero sequence voltage (Uo), the faulted phase voltage (uA),
,for Electrical Engineering (CSEE) V01.21, No.4, 2001, pp.20-26
and the fault component of three phase currents (Ai) have been [9] Zeng Xiangjun, Yin Xianggen, Chen Deshu, and Zhang zhe, “Ground
measured by the FTU prototype. The test results are listed in fault protection for generator stator windings with inductance
TABLE. 11. When the earth fault occurs on L l (K,) or L2 (K2), compensating based on injecting signal,” (in Chinese) Proceedings ofthe
Chinese Sociefyfor Electrical Engineering (CSEE), V01.20, No. 11,2000,
the prototype does not trip. When the high impedance
pp.51-55.
grounding fault occurs on L3 (K3),the prototype trips, isolate
the fault section L3, and reduce grounding fault duration. VII. BIOGRAPHY
Experimental results also show that the Petersen-coil in Zeng Xiangjun was bom in Hunan, China in 1972. He received his MSc.
parallel with high resistance earthed technique can improve degree from Wuhan University, and PhD degree from Huazhong University of
power quality by reducing over-voltage and residual current. Science & Technology. He is at present an Associate Professor in Changsha
University of Science and Technology, China. He currently works as a
Post-doctor in Huazhong University of Science & Technology and
V. CONCLUSION Xiangneng-Xuji Company. His research interest is real-time computer
Power quality is influenced by neutral grounding method in application in power systems control and protection.
distribution systems. Optimization for neutral grounding K. K. Li received the MSc. degree from the University of Manchester
Institute of Science and Technology, Manchester, U.K., and the PhD degree
methods is discussed in this paper. Petersen-coil in parallel from City University, London, U.K. He has worked as a Protection Engineer
with high resistance earthed technique has a better performance in Hong Kong. He is currently an Associate Professor in the Department of
in safety and power quality than other neutral point grounding Electrical Engineering, Hong Kong Polytechnic University. His research
techniques. In this compensated system with Petersen-coil interests are power system protection and applications of artificial intelligence
in power systems.
automatic tuning and novel grounding fault protectors, W. L. Chan obtain his BSc(Eng) and MPhil degree from University of Hong
grounding fault can be protected, arc fault can be Kong and PhD. degree from City University, London. He is now with the
self-extinguished, and over-voltage is suppressed. department of Electrical Engineering, Hong Kong Polytechnic University
To improve power quality, zero sequence impedance is while his major interests are in microprocessor applications in power systems
and applications of artificial intelligence.
tested with a resonance signal injection from neutral point to Yin Xianggen received his PhD. in electrical power engineering from
distribution systems. Petersen-coil inductance is adjusted to Huazhong University of Science and Technology in 1989. He is at present the
compensate the total capacitance. The resistor which is in professor at the same university. His research interests are power system
parallel with the Petersen-coil is adjusted to control control and protection relaying.
over-voltage. The method of Petersen-coil tuning has been

310

Das könnte Ihnen auch gefallen