Beruflich Dokumente
Kultur Dokumente
Jl. Gatot Subroto Km 7,8 Kel Pasir Jaya, Kec. Jati Uwung, Tangerang 15135-Indonesia
Phone : (62-21) 5922404, 5928066 (Hunting) Fax. : (62-21) 59301979, 5922576, 5901469
c
Copyright Sumi Indo Kabel 2007
All rights reserved. This catalogue is the copyright work of PT. Sumi Indo Kabel Tbk. No part of this publication may be reproduced, stored in a retrieval system, or transmitted,
in any form or by means, electronic, mechanical, photocopying, recording or otherwise, without prior permission of PT. Sumi Indo Kabel.
All information contained in this catalogue is believed to be accurate at the time issue. PT. Sumi Indo Kabel reserve the right to change information or specification at any time
in the light of technical developments or revisions.
600/1000 Volts PVC Insulated and PVC Sheathed Cables (PVC/PVC, NYY) 18
600/1000 Volts PVC Insulated, Copper Tape Shielded and PVC Sheathed Cables (PVC/PVC-S, NYSY) 30
Armoured Cables
600/1000 Volts PVC Insulated, Steel Wire Armoured and PVC Sheathed Cables (PVC/SWA/PVC, NYRY) 35
600/1000 Volts PVC Insulated, Flat Steel Wire Armoured and PVC Sheathed Cables (PVC/FSWA/PVC, NYFGbY) 41
600/1000 Volts PVC Insulated, Double Steel Tape Armoured and PVC Sheathed Cables (PVC/DSTA/PVC, NYBY) 46
Armoured Cables
600/1000 Volts XLPE Insulated, Steel Wire Armoured and PVC Sheathed Cables (XLPE/SWA/PVC, N2XRY) 67
600/1000 Volts XLPE Insulated, Flat Steel Wire Armoured and PVC Sheathed Cables (XLPE/FSWA/PVC, N2XFGbY) 73
600/1000 Volts XLPE Insulated, Double Steel Tape Armoured and PVC Sheathed Cables (XLPE/DSTA/PVC, N2XBY) 78
Page - 1
Section 1 - Contents & Information
The Company was established on July 23, 1981 with its Head Office
and Factory located in Tangerang, Banten. The Company is engaged 1
in the manufacturing of Power Cable, Telecommunication Cable &
Fiber Optic, and Copper Wire.
The Company was listed in the Jakarta and Surabaya Stock Exchanges
in 1990. The Company became Foreign Capital Investment (PMA)
in 1994, with the participation of Sumitomo Electric Industries, Ltd.,
Japan, one of the biggest in cable and wire industries in the world. The
name of Company became PT Sumi Indo Kabel Tbk. since 1999.
Page - 2
Section 1 - Contents & Information
Cable Specification
1 Scope
These specification apply to material and constructions of cross-linked thermosetting polyethylene
(XLPE) or Polivinyl chloride (PVC) insulated wire and cables for rated voltages 0.3/0.5 kV up to
0.6/1(1.2) kV accordance to IEC 60502-1, Indonesia Electric Power Company (SPLN)
2 Conductor
The conductor shall be formed from plain annealed copper or aluminium complying with IEC
60228, ASTM B3 and B8.
The conductor shall be solid, circular stranded or compacted stranded.
3 Insulation
The insulation shall be cross-linked polyethylene (XLPE) or Polivinyl chloride (PVC) in accordance
to IEC 60502-1.
4 Identification of cores
The cores of all cables shall be identified by color or numbered printed on the surface of insulation
in accordance with the following sequence or other sequence.
Number of core Identification of cores
Single core Black (Natural for XLPE insulated)
Two cores Red, Black
Three cores Red, Yellow, Blue
Four cores Red, Yellow, Blue, Black
Five core or more Black insulation with white numbered code.
8 Metallic armour
The metallic armour shall consist of single layer of round galvanized steel wire or flat galvanized
steel wire and steel tape or double layer of galvanized steel tapes in accordance to IEC 60502-1.
The armour of single core cables shall consist of single layer of aluminium wire or double layers of
aluminium tape as non magnetic material.
9 Outer sheath
The outer sheath shall consist of a thermoplastic compound such as polyvinyl chloride (PVC),
polyethylene (PE), halogen free (LSOH), etc in accordance with IEC 60502-1.
Page - 3
Section 2 - PVC Insulated Cables
Unarmoured Cables
Colour of Insulation : Red, White, Black, Green, Brown, Blue, Yellow, Green-yellow
Colour of Insulation : Red, White, Black, Green, Brown, Blue, Yellow, Green-yellow
Page - 4
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 5
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 6
Section 2 - PVC Insulated Cables
Unarmoured Cables
Conductor
PVC Insulation PVC Sheath
Page - 7
Section 2 - PVC Insulated Cables
Unarmoured Cables
No. Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Core section of wire Conductor Insulation covering Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
- mm² No./mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.7 0.4 1.2 9.5 129 12.1
7 / 0.52 1.56 0.7 0.4 1.2 10.0 138 12.1
2.5 1 / 1.78 1.78 0.8 0.4 1.2 11.0 173 7.41
7 / 0.67 2.01 0.8 0.4 1.2 11.0 184 7.41
4 1 / 2.26 2.26 0.8 0.4 1.2 12.0 222 4.61
Page - 8
Section 2 - PVC Insulated Cables
Unarmoured Cables
No. Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Core section of wire Conductor Insulation covering Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
- mm² No./mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.7 0.4 1.2 11.0 177 12.1
7 / 0.52 1.56 0.7 0.4 1.2 11.5 189 12.1
2.5 1 / 1.78 1.78 0.8 0.4 1.2 12.5 247 7.41
7 / 0.67 2.01 0.8 0.4 1.2 13.0 262 7.41
4 1 / 2.26 2.26 0.8 0.4 1.4 14.0 340 4.61
Page - 9
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 10
Section 2 - PVC Insulated Cables
Unarmoured Cables
TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² mm mm mm mm mm kg/km Ω/km
Page - 11
Section 2 - PVC Insulated Cables
Unarmoured Cables
THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² mm mm mm mm mm kg/km Ω/km
Page - 12
Section 2 - PVC Insulated Cables
Unarmoured Cables
FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² mm mm mm mm mm kg/km Ω/km
Page - 13
Section 2 - PVC Insulated Cables
Unarmoured Cables
FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal Maximum Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² mm mm mm mm mm kg/km Ω/km
Page - 14
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 15
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 16
Section 2 - PVC Insulated Cables
Unarmoured Cables
1 1
2 2
3
4
5 5
Page - 17
Section 2 - PVC Insulated Cables
Unarmoured Cables
SINGLE CORE
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.4 6.5 55 12.1
1.5 7 / 0.52 1.56 0.8 1.4 6.5 58 12.1
2.5 1 / 1.78 1.78 0.8 1.4 7.0 68 7.41
2.5 7 / 0.67 2.01 0.8 1.4 7.0 71 7.41
4 1 / 2.26 2.26 1.0 1.4 7.5 94 4.61
4 7 / 0.85 2.55 1.0 1.4 8.0 98 4.61
6 7 / 1.04 3.12 1.0 1.4 8.5 123 3.08
10 7 / 1.35 4.05 1.0 1.4 9.5 172 1.83
16 7 / 1.70 5.10 1.0 1.4 10.5 239 1.15
25 7 / 2.13 6.39 1.2 1.4 12.0 349 0.727
35 7 / 2.52 7.56 1.2 1.4 13.5 457 0.524
50 19 / 1.83 9.15 1.4 1.4 15.5 623 0.387
70 19 / 2.17 10.85 1.4 1.4 17.0 832 0.268
95 19 / 2.52 12.60 1.6 1.5 19.5 1114 0.193
120 37 / 2.03 14.21 1.6 1.5 21.0 1359 0.153
150 37 / 2.27 15.89 1.8 1.6 23.5 1689 0.124
185 37 / 2.52 17.64 2.0 1.7 25.5 2068 0.0991
240 61 / 2.26 20.34 2.2 1.8 29.0 2698 0.0754
300 61 / 2.52 22.68 2.4 1.9 32.0 3327 0.0601
400 61 / 2.86 25.74 2.6 2.0 36.0 4249 0.0470
500 61 / 3.20 28.80 2.8 2.1 39.5 5266 0.0366
630 91 / 2.96 32.56 2.8 2.2 43.5 6580 0.0283
800 127 / 2.85 37.05 2.8 2.3 48.0 8345 0.0221
1000 127 / 3.20 41.60 3.0 2.5 53.5 10455 0.0176
Page - 18
Section 2 - PVC Insulated Cables
Unarmoured Cables
TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.8 10.5 128 12.1
1.5 7 / 0.52 1.56 0.8 1.8 11.0 136 12.1
2.5 1 / 1.78 1.78 0.8 1.8 11.5 159 7.41
2.5 7 / 0.67 2.01 0.8 1.8 12.0 168 7.41
4 1 / 2.26 2.26 1.0 1.8 13.0 220 4.61
4 7 / 0.85 2.55 1.0 1.8 14.0 231 4.61
6 7 / 1.04 3.12 1.0 1.8 15.0 287 3.08
10 7 / 1.35 4.05 1.0 1.8 17.0 398 1.83
16 7 / 1.70 5.10 1.0 1.8 19.0 545 1.15
25 7 / 2.13 6.39 1.2 1.8 22.0 794 0.727
35 7 / 2.52 7.56 1.2 1.8 24.5 1032 0.524
50 19 / 1.83 9.15 1.4 1.8 28.5 1411 0.387
70 19 / 2.17 10.85 1.4 1.9 32.0 1880 0.268
95 19 / 2.52 12.60 1.6 2.0 37.0 2507 0.193
120 37 / 2.03 14.21 1.6 2.1 40.5 3065 0.153
150 37 / 2.27 15.89 1.8 2.2 45.0 3796 0.124
185 37 / 2.52 17.64 2.0 2.4 49.5 4654 0.0991
240 61 / 2.26 20.34 2.2 2.6 56.0 6067 0.0754
300 61 / 2.52 22.68 2.4 2.7 62.0 7463 0.0601
Page - 19
Section 2 - PVC Insulated Cables
Unarmoured Cables
THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.8 11.0 155 12.1
1.5 7 / 0.52 1.56 0.8 1.8 11.5 163 12.1
2.5 1 / 1.78 1.78 0.8 1.8 12.0 195 7.41
2.5 7 / 0.67 2.01 0.8 1.8 12.5 207 7.41
4 1 / 2.26 2.26 1.0 1.8 14.0 277 4.61
4 7 / 0.85 2.55 1.0 1.8 14.5 290 4.61
6 7 / 1.04 3.12 1.0 1.8 15.5 367 3.08
10 7 / 1.35 4.05 1.0 1.8 18.0 521 1.83
16 7 / 1.70 5.10 1.0 1.8 20.0 728 1.15
25 7 / 2.13 6.39 1.2 1.8 23.5 1078 0.727
35 7 / 2.52 7.56 1.2 1.8 26.0 1410 0.524
50 6.8 1.4 1.8 25.0 1741 0.387
70 8.2 1.4 2.0 28.0 2415 0.268
95 Three- 9.7 1.6 2.1 33.0 3319 0.193
120 Segmental 10.9 1.6 2.2 35.5 3963 0.153
150 Stranded 11.9 1.8 2.3 38.5 4851 0.124
185 13.6 2.0 2.5 43.5 6056 0.0991
240 15.8 2.2 2.7 49.0 8072 0.0754
300 17.5 2.4 2.9 54.0 10034 0.0601
Page - 20
Section 2 - PVC Insulated Cables
Unarmoured Cables
FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.8 12.0 184 12.1
1.5 7 / 0.52 1.56 0.8 1.8 12.5 193 12.1
2.5 1 / 1.78 1.78 0.8 1.8 13.0 239 7.41
2.5 7 / 0.67 2.01 0.8 1.8 13.5 251 7.41
4 1 / 2.26 2.26 1.0 1.8 15.0 342 4.61
4 7 / 0.85 2.55 1.0 1.8 16.0 360 4.61
6 7 / 1.04 3.12 1.0 1.8 17.0 461 3.08
10 7 / 1.35 4.05 1.0 1.8 19.5 658 1.83
16 7 / 1.70 5.10 1.0 1.8 22.0 930 1.15
25 7 / 2.13 6.39 1.2 1.8 26.0 1378 0.727
35 7 / 2.52 7.56 1.2 1.8 29.0 1818 0.524
50 8.1 1.4 1.9 28.5 2264 0.387
70 9.7 1.4 2.1 32.0 3148 0.268
95 Four- 11.4 1.6 2.2 37.5 4326 0.193
120 Segmental 12.9 1.6 2.4 41.0 5198 0.153
150 Stranded 14.2 1.8 2.5 45.0 6373 0.124
185 16.0 2.0 2.7 50.0 7938 0.0991
240 18.2 2.2 2.9 56.0 10564 0.0754
300 20.6 2.4 3.1 62.5 13201 0.0601
Page - 21
Section 2 - PVC Insulated Cables
Unarmoured Cables
FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section area of wire Conductor Insulation Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.8 13.0 218 12.1
1.5 7 / 0.52 1.56 0.8 1.8 13.5 230 12.1
2.5 1 / 1.78 1.78 0.8 1.8 14.0 280 7.41
2.5 7 / 0.67 2.01 0.8 1.8 14.5 296 7.41
4 1 / 2.26 2.26 1.0 1.8 16.5 408 4.61
4 7 / 0.85 2.55 1.0 1.8 17.5 430 4.61
6 7 / 1.04 3.12 1.0 1.8 18.5 556 3.08
10 7 / 1.35 4.05 1.0 1.8 21.5 800 1.83
16 7 / 1.70 5.10 1.0 1.8 24.0 1135 1.15
25 7 / 2.13 6.39 1.2 1.8 28.5 1692 0.727
35 7 / 2.52 7.56 1.2 1.9 32.0 2257 0.524
50 19 / 1.83 9.15 1.4 2.1 38.0 3152 0.387
Page - 22
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 23
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 24
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 25
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 26
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 27
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 28
Section 2 - PVC Insulated Cables
Unarmoured Cables
Page - 29
Section 2 - PVC Insulated Cables
Unarmoured Cables
TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of of Resistance
section area of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm kg/km Ω/km
Page - 30
Section 2 - PVC Insulated Cables
Unarmoured Cables
THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of of Resistance
section area of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm kg/km Ω/km
Page - 31
Section 2 - PVC Insulated Cables
Unarmoured Cables
FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of of Resistance
section area of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm kg/km Ω/km
Page - 32
Section 2 - PVC Insulated Cables
Unarmoured Cables
FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of of Resistance
section area of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm kg/km Ω/km
Page - 33
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/AWA/PVC (acc. to IEC 60502-1)
1 Constructions :
2 1 Conductor (Annealed Copper)
3 2 Insulation (PVC Compound)
4 3 Inner Covering (PVC Compound)
5 4 Round Aluminium Wire armour
5 Binding tape (Manufacturer's option)
6 6 Outer sheath (PVC Compound)
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/SWA/PVC (acc. to IEC 60502-1)
Constructions :
1
1 Conductor (Annealed Copper)
2 2 Insulation (PVC Compound)
3 3 Filler (Polyprophylene yarn,or extruded filler
4 up to request)
5 4 Binding tape (Manufacturer's option)
6 5 Inner Covering (PVC Compound)
6 Galvanized Round Steel Wire armour
7
7 Binding tape (Manufacturer's option)
8 Outer sheath (PVC Compound)
8
Page - 34
Section 2 - PVC Insulated Cables
Armoured Cables
SINGLE CORE
Conductor Nominal Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter of Thickness diameter Weight Conductor
Cross- Diameter of of of inner Aluminium of of of Resistance
section of wire Conductor Insulation covering wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
120 37 / 2.03 14.21 1.6 1.0 1.6 1.8 27.0 1705 0.153
150 37 / 2.27 15.89 1.8 1.0 1.6 1.8 29.0 2054 0.124
185 37 / 2.52 17.64 2.0 1.0 1.6 1.8 31.0 2450 0.0991
240 61 / 2.26 20.34 2.2 1.0 1.6 1.9 34.0 3110 0.0754
300 61 / 2.52 22.68 2.4 1.0 2.0 2.0 38.0 3865 0.0601
400 61 / 2.86 25.74 2.6 1.2 2.0 2.1 42.0 4885 0.0470
500 61 / 3.20 28.80 2.8 1.2 2.0 2.2 46.0 5965 0.0366
630 91 / 2.96 32.56 2.8 1.2 2.0 2.4 50.0 7335 0.0283
800 127 / 2.85 37.05 2.8 1.4 2.5 2.5 56.0 9410 0.0221
1000 127 / 3.20 41.60 3.0 1.4 2.5 2.7 61.0 11635 0.0176
Page - 35
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/SWA/PVC (IEC 60502-1)
TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Diameter Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. of of of Resistance
section of wire Conductor Insulation covering Steel wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.8 1.8 14.0 332 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 1.8 14.5 347 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 1.8 15.0 380 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 1.8 15.5 395 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 1.8 16.5 473 4.61
4 7 / 0.85 2.55 1.0 1.0 0.8 1.8 17.5 494 4.61
6 7 / 1.04 3.12 1.0 1.0 1.25 1.8 19.0 667 3.08
10 7 / 1.35 4.05 1.0 1.0 1.25 1.8 21.0 837 1.83
16 7 / 1.70 5.10 1.0 1.0 1.25 1.8 23.0 1019 1.15
25 7 / 2.13 6.39 1.2 1.0 1.6 1.8 27.5 1507 0.727
35 7 / 2.52 7.56 1.2 1.0 1.6 1.8 30.0 1810 0.524
50 19 / 1.83 9.15 1.4 1.0 1.6 1.9 34.0 2318 0.387
70 19 / 2.17 10.85 1.4 1.0 2.0 2.0 38.0 3122 0.268
95 19 / 2.52 12.60 1.6 1.2 2.0 2.2 43.5 3987 0.193
120 37 / 2.03 14.21 1.6 1.2 2.0 2.3 47.0 4695 0.153
150 37 / 2.27 15.89 1.8 1.2 2.5 2.4 52.0 5994 0.124
185 37 / 2.52 17.64 2.0 1.4 2.5 2.6 57.0 7109 0.0991
240 61 / 2.26 20.34 2.2 1.4 2.5 2.8 63.5 8827 0.0754
300 61 / 2.52 22.68 2.4 1.6 2.5 2.9 70.0 10574 0.0601
Page - 36
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/SWA/PVC (IEC 60502-1)
THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Diameter Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. of of of Resistance
section of wire Conductor Insulation covering Steel wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.8 1.8 14.5 371 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 1.8 15.0 385 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 1.8 15.5 429 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 1.8 16.0 446 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 1.8 18.0 637 4.61
4 7 / 0.85 2.55 1.0 1.0 1.25 1.8 18.5 660 4.61
6 7 / 1.04 3.12 1.0 1.0 1.25 1.8 20.0 768 3.08
10 7 / 1.35 4.05 1.0 1.0 1.25 1.8 22.0 973 1.83
16 7 / 1.70 5.10 1.0 1.0 1.25 1.8 24.0 1229 1.15
25 7 / 2.13 6.39 1.2 1.0 1.6 1.8 29.0 1819 0.727
35 7 / 2.52 7.56 1.2 1.0 1.6 1.8 31.5 2230 0.524
50 6.8 1.4 1.0 1.6 2.0 30.5 2558 0.387
70 Sector Shape 8.2 1.4 1.2 2.0 2.1 34.5 3577 0.268
95 stranded 9.7 1.6 1.2 2.0 2.2 39.0 4653 0.193
120 10.9 1.6 1.2 2.0 2.3 42.0 5410 0.153
150 11.9 1.8 1.4 2.5 2.5 46.0 6830 0.124
185 13.6 2.0 1.4 2.5 2.7 51.0 8260 0.0991
240 15.8 2.2 1.6 2.5 2.9 57.0 10632 0.0754
300 17.5 2.4 1.6 2.5 3.1 62.0 12795 0.0601
Page - 37
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/SWA/PVC (IEC 60502-1)
FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Diameter Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. of of of Resistance
section of wire Conductor Insulation covering Steel wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.8 1.8 15.5 412 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 1.8 16.0 434 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 1.8 16.5 486 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 1.8 17.0 508 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 1.8 19.5 736 4.61
4 7 / 0.85 2.55 1.0 1.0 1.25 1.8 20.0 762 4.61
6 7 / 1.04 3.12 1.0 1.0 1.25 1.8 21.0 894 3.08
10 7 / 1.35 4.05 1.0 1.0 1.25 1.8 23.5 1142 1.83
16 7 / 1.70 5.10 1.0 1.0 1.6 1.8 27.0 1621 1.15
25 7 / 2.13 6.39 1.2 1.0 1.6 1.8 31.0 2183 0.727
35 7 / 2.52 7.56 1.2 1.0 1.6 1.9 34.0 2698 0.524
50 8.1 1.4 1.2 2.0 2.1 35.0 3467 0.387
70 Sector Shape 9.7 1.4 1.2 2.0 2.2 38.5 4455 0.268
95 stranded 11.4 1.6 1.2 2.5 2.4 44.5 6222 0.193
120 12.9 1.6 1.4 2.5 2.5 48.5 7248 0.153
150 14.2 1.8 1.4 2.5 2.7 52.5 8663 0.124
185 16.0 2.0 1.6 2.5 2.9 58.0 10503 0.0991
240 18.2 2.2 1.6 2.5 3.1 63.5 13414 0.0754
300 20.6 2.4 1.6 2.5 3.3 70.0 16298 0.0601
Page - 38
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/SWA/PVC (IEC 60502-1)
FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Diameter Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. of of of Resistance
section of wire Conductor Insulation covering Steel wire Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.8 1.8 16.5 465 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 1.8 17.0 488 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 1.8 17.5 551 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 1.8 18.0 572 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 1.8 20.5 835 4.61
4 7 / 0.85 2.55 1.0 1.0 1.25 1.8 21.5 865 4.61
6 7 / 1.04 3.12 1.0 1.0 1.25 1.8 22.5 1021 3.08
10 7 / 1.35 4.05 1.0 1.0 1.6 1.8 26.5 1479 1.83
16 7 / 1.70 5.10 1.0 1.0 1.60 1.8 29.0 1893 1.15
25 7 / 2.13 6.39 1.2 1.0 1.6 1.9 33.5 2577 0.727
35 7 / 2.52 7.56 1.2 1.0 2.0 2.0 38.0 3468 0.524
50 19 / 1.83 9.15 1.4 1.2 2.0 2.2 44.0 4503 0.387
Page - 39
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (acc. to IEC 60502-1)
3
4
C Constructions :
1 Conductor (Annealed Copper) Note : Special application upon request
2 Insulation (PVC Compound) * Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
3 Filler (Polyprophylene yarn,or extruded filler * Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
up to request) * Anti termite performance.
* Tin coated Copper conductor.
4 Inner Covering (PVC Compound)
* Polyethylene / Low smoke Halogen Free sheathed
5 Galvanized Flat Steel Wire armour
6 Galvanized Steel Tape binding
7 Outer sheath (PVC Compound)
Page - 40
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)
TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.8 0.3 1.8 14.0 406 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 0.3 1.8 14.5 417 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 0.3 1.8 15.0 442 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 0.3 1.8 15.5 480 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 0.3 1.8 17.0 569 4.61
4 7 / 0.85 2.55 1.0 1.0 0.8 0.3 1.8 17.5 584 4.61
6 7 / 1.04 3.12 1.0 1.0 0.8 0.3 1.8 18.5 674 3.08
10 7 / 1.35 4.05 1.0 1.0 0.8 0.3 1.8 20.5 826 1.83
16 7 / 1.70 5.10 1.0 1.0 0.8 0.3 1.8 22.5 1040 1.15
25 7 / 2.13 6.39 1.2 1.0 0.8 0.3 1.8 26.0 1365 0.727
35 7 / 2.52 7.56 1.2 1.0 0.8 0.3 1.8 28.0 1672 0.524
50 19 / 1.83 9.15 1.4 1.0 0.8 0.3 1.8 32.0 2134 0.387
70 19 / 2.17 10.85 1.4 1.0 0.8 0.3 1.9 35.5 2691 0.268
95 19 / 2.52 12.60 1.6 1.2 0.8 0.3 2.1 41.0 3484 0.193
120 37 / 2.03 14.21 1.6 1.2 0.8 0.3 2.2 44.5 4149 0.153
150 37 / 2.27 15.89 1.8 1.2 0.8 0.3 2.3 49.0 4995 0.124
185 37 / 2.52 17.64 2.0 1.4 0.8 0.3 2.4 53.5 5968 0.0991
240 61 / 2.26 20.34 2.2 1.4 0.8 0.3 2.6 60.0 7540 0.0754
300 61 / 2.52 22.68 2.4 1.6 0.8 0.3 2.8 66.5 9178 0.0601
Page - 41
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)
THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.8 0.3 1.8 14.5 437 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 0.3 1.8 15.0 447 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 0.3 1.8 15.5 509 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 0.3 1.8 16.0 524 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 0.3 1.8 17.5 631 4.61
4 7 / 0.85 2.55 1.0 1.0 0.8 0.3 1.8 18.0 649 4.61
6 7 / 1.04 3.12 1.0 1.0 0.8 0.3 1.8 19.0 760 3.08
10 7 / 1.35 4.05 1.0 1.0 0.8 0.3 1.8 21.5 982 1.83
16 7 / 1.70 5.10 1.0 1.0 0.8 0.3 1.8 23.5 1230 1.15
25 7 / 2.13 6.39 1.2 1.0 0.8 0.3 1.8 27.0 1685 0.727
35 7 / 2.52 7.56 1.2 1.0 0.8 0.3 1.8 30.0 2089 0.524
50 6.8 1.4 1.0 0.8 0.3 1.9 28.5 2385 0.387
70 Sector Shape 8.2 1.4 1.2 0.8 0.3 2.0 32.0 3149 0.268
95 stranded 9.7 1.6 1.2 0.8 0.3 2.2 37.0 4184 0.193
120 10.9 1.6 1.2 0.8 0.3 2.3 39.5 4902 0.153
150 11.9 1.8 1.4 0.8 0.3 2.4 43.0 5887 0.124
185 13.6 2.0 1.4 0.8 0.3 2.6 47.5 7212 0.0991
240 15.8 2.2 1.6 0.8 0.3 2.8 54.0 9457 0.0754
300 17.5 2.4 1.6 0.8 0.3 2.9 58.5 11517 0.0601
Page - 42
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)
FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.8 0.3 1.8 15.5 497 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 0.3 1.8 16.0 510 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 0.3 1.8 16.5 560 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 0.3 1.8 17.0 602 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 0.3 1.8 18.5 731 4.61
4 7 / 0.85 2.55 1.0 1.0 0.8 0.3 1.8 19.5 754 4.61
6 7 / 1.04 3.12 1.0 1.0 0.8 0.3 1.8 20.5 890 3.08
10 7 / 1.35 4.05 1.0 1.0 0.8 0.3 1.8 23.0 1157 1.83
16 7 / 1.70 5.10 1.0 1.0 0.8 0.3 1.8 25.5 1498 1.15
25 7 / 2.13 6.39 1.2 1.0 0.8 0.3 1.8 29.5 2055 0.727
35 7 / 2.52 7.56 1.2 1.0 0.8 0.3 1.9 32.5 2567 0.524
50 8.1 1.4 1.2 0.8 0.3 2.0 32.5 3041 0.387
70 Sector Shape 9.7 1.4 1.2 0.8 0.3 2.1 36.0 3991 0.268
95 stranded 11.4 1.6 1.2 0.8 0.3 2.3 41.5 5307 0.193
120 12.9 1.6 1.4 0.8 0.3 2.4 45.0 6286 0.153
150 14.2 1.8 1.4 0.8 0.3 2.6 49.0 7567 0.124
185 16.0 2.0 1.6 0.8 0.3 2.7 54.5 9306 0.0991
240 18.2 2.2 1.6 0.8 0.3 3.0 60.5 12117 0.0754
300 20.6 2.4 1.6 0.8 0.3 3.2 66.5 14861 0.0601
Page - 43
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)
FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.8 0.3 1.8 16.5 538 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.8 0.3 1.8 17.0 580 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.8 0.3 1.8 17.5 635 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.8 0.3 1.8 18.0 654 7.41
4 1 / 2.26 2.26 1.0 1.0 0.8 0.3 1.8 20.0 832 4.61
4 7 / 0.85 2.55 1.0 1.0 0.8 0.3 1.8 21.0 860 4.61
6 7 / 1.04 3.12 1.0 1.0 0.8 0.3 1.8 22.0 1022 3.08
10 7 / 1.35 4.05 1.0 1.0 0.8 0.3 1.8 25.0 1338 1.83
16 7 / 1.70 5.10 1.0 1.0 0.8 0.3 1.8 27.5 1745 1.15
25 7 / 2.13 6.39 1.2 1.0 0.8 0.3 1.8 32.0 2413 0.727
35 7 / 2.52 7.56 1.2 1.0 0.8 0.3 1.9 35.5 3066 0.524
50 19 / 1.83 9.15 1.4 1.2 0.8 0.3 2.1 41.5 4013 0.387
Page - 44
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DATA/PVC (acc. to IEC 60502-1)
1
Constructions :
2 1 Conductor (Annealed Copper)
2 Insulation (PVC Compound)
3
3 Inner Covering (PVC Compound)
4
4 Double Aluminium Tape armour
5 Outer sheath (PVC Compound)
5
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (acc. to IEC 60502-1)
Constructions :
1 1 Conductor (Annealed Copper)
2 Insulation (PVC Compound)
2
3 Filler (Polyprophylene yarn,or extruded filler
3
up to request)
4
4 Binding tape (Manufacturer's option)
5
5 Inner Covering (PVC Compound)
6
6 Double Galvanized Steel Tape armour
7 Outer sheath (PVC Compound)
Page - 45
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DATA/PVC (IEC 60502-1)
SINGLE CORE
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner thickness of of of of Resistance
section of wire Conductor Insulation covering Aluminium Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
50 19 / 1.83 9.15 1.4 1.0 0.5 1.8 19.5 817 0.387
70 19 / 2.17 10.85 1.4 1.0 0.5 1.8 21.0 1045 0.268
95 19 / 2.52 12.60 1.6 1.0 0.5 1.8 23.5 1344 0.193
120 37 / 2.03 14.21 1.6 1.0 0.5 1.8 25.0 1607 0.153
150 37 / 2.27 15.89 1.8 1.0 0.5 1.8 27.0 1949 0.124
185 37 / 2.52 17.64 2.0 1.0 0.5 1.8 29.5 2339 0.0991
240 61 / 2.26 20.34 2.2 1.0 0.5 1.9 32.5 2987 0.0754
300 61 / 2.52 22.68 2.4 1.0 0.5 1.9 35.0 3628 0.0601
400 61 / 2.86 25.74 2.6 1.2 0.5 2.1 39.5 4638 0.0470
500 61 / 3.20 28.80 2.8 1.2 0.5 2.2 43.5 5694 0.0366
Page - 46
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (IEC 60502-1)
TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. of of of Resistance
section of wire Conductor Insulation covering Steel tape Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.2 1.8 13.0 237 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.2 1.8 13.0 250 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.2 1.8 13.5 276 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.2 1.8 14.0 290 7.41
4 1 / 2.26 2.26 1.0 1.0 0.2 1.8 15.5 357 4.61
4 7 / 0.85 2.55 1.0 1.0 0.2 1.8 16.0 374 4.61
6 7 / 1.04 3.12 1.0 1.0 0.2 1.8 17.0 440 3.08
10 7 / 1.35 4.05 1.0 1.0 0.2 1.8 19.0 574 1.83
16 7 / 1.70 5.10 1.0 1.0 0.2 1.8 21.0 742 1.15
25 7 / 2.13 6.39 1.2 1.0 0.2 1.8 24.5 1026 0.727
35 7 / 2.52 7.56 1.2 1.0 0.2 1.8 27.0 1290 0.524
50 19 / 1.83 9.15 1.4 1.0 0.2 1.8 31.0 1712 0.387
70 19 / 2.17 10.85 1.4 1.0 0.2 1.9 34.0 2262 0.268
95 19 / 2.52 12.60 1.6 1.2 0.2 2.1 39.0 2896 0.193
120 37 / 2.03 14.21 1.6 1.2 0.5 2.2 43.5 3921 0.153
150 37 / 2.27 15.89 1.8 1.2 0.5 2.3 48.0 4722 0.124
185 37 / 2.52 17.64 2.0 1.4 0.5 2.4 52.5 5675 0.0991
240 61 / 2.26 20.34 2.2 1.4 0.5 2.6 58.5 7166 0.0754
300 61 / 2.52 22.68 2.4 1.6 0.5 2.8 64.5 8710 0.0601
Page - 47
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (IEC 60502-1)
THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. of of of Resistance
section of wire Conductor Insulation covering Steel tape Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.2 1.8 13.5 270 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.2 1.8 13.5 281 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.2 1.8 14.0 318 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.2 1.8 14.5 335 7.41
4 1 / 2.26 2.26 1.0 1.0 0.2 1.8 16.0 420 4.61
4 7 / 0.85 2.55 1.0 1.0 0.2 1.8 16.5 441 4.61
6 7 / 1.04 3.12 1.0 1.0 0.2 1.8 18.0 530 3.08
10 7 / 1.35 4.05 1.0 1.0 0.2 1.8 20.0 707 1.83
16 7 / 1.70 5.10 1.0 1.0 0.2 1.8 22.0 935 1.15
25 7 / 2.13 6.39 1.2 1.0 0.2 1.8 26.0 1328 0.727
35 7 / 2.52 7.56 1.2 1.0 0.2 1.8 28.5 1685 0.524
50 6.8 1.4 1.0 0.2 1.9 27.0 2002 0.387
70 8.2 1.4 1.2 0.2 2.0 30.5 2724 0.268
95 Three- 9.7 1.6 1.2 0.5 2.2 36.5 4062 0.193
120 Segmental 10.9 1.6 1.2 0.5 2.3 39.5 4765 0.153
150 Stranded 11.9 1.8 1.4 0.5 2.4 42.5 5745 0.124
185 13.6 2.0 1.4 0.5 2.6 47.5 7055 0.0991
240 15.8 2.2 1.6 0.5 2.8 53.5 9254 0.0754
300 17.5 2.4 1.6 0.5 2.9 58.0 11299 0.0601
Page - 48
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (IEC 60502-1)
FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. of of of Resistance
section of wire Conductor Insulation covering Steel tape Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.2 1.8 14.0 307 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.2 1.8 14.5 322 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.2 1.8 15.0 372 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.2 1.8 15.5 390 7.41
4 1 / 2.26 2.26 1.0 1.0 0.2 1.8 17.5 499 4.61
4 7 / 0.85 2.55 1.0 1.0 0.2 1.8 18.0 524 4.61
6 7 / 1.04 3.12 1.0 1.0 0.2 1.8 19.0 638 3.08
10 7 / 1.35 4.05 1.0 1.0 0.2 1.8 21.5 860 1.83
16 7 / 1.70 5.10 1.0 1.0 0.2 1.8 24.0 1158 1.15
25 7 / 2.13 6.39 1.2 1.0 0.2 1.8 28.0 1650 0.727
35 7 / 2.52 7.56 1.2 1.0 0.2 1.8 31.0 2120 0.524
50 8.1 1.4 1.2 0.2 2.0 31.0 2592 0.387
70 9.7 1.4 1.2 0.5 2.1 36.0 3862 0.268
95 Four- 11.4 1.6 1.2 0.5 2.3 41.0 5171 0.193
120 Segmental 12.9 1.6 1.4 0.5 2.4 44.5 6122 0.153
150 Stranded 14.2 1.8 1.4 0.5 2.6 49.0 7405 0.124
185 16.0 2.0 1.6 0.5 2.7 54.0 9113 0.0991
240 18.2 2.2 1.6 0.5 3.0 60.0 11899 0.0754
300 20.6 2.4 1.6 0.5 3.2 66.5 14624 0.0601
Page - 49
Section 2 - PVC Insulated Cables
Armoured Cables
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (IEC 60502-1)
FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. of of of Resistance
section of wire Conductor Insulation covering Steel tape Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.8 1.0 0.2 1.8 15.0 350 12.1
1.5 7 / 0.52 1.56 0.8 1.0 0.2 1.8 15.5 368 12.1
2.5 1 / 1.78 1.78 0.8 1.0 0.2 1.8 16.0 424 7.41
2.5 7 / 0.67 2.01 0.8 1.0 0.2 1.8 16.5 446 7.41
4 1 / 2.26 2.26 1.0 1.0 0.2 1.8 18.5 578 4.61
4 7 / 0.85 2.55 1.0 1.0 0.2 1.8 19.5 609 4.61
6 7 / 1.04 3.12 1.0 1.0 0.2 1.8 20.5 748 3.08
10 7 / 1.35 4.05 1.0 1.0 0.2 1.8 23.5 1022 1.83
16 7 / 1.70 5.10 1.0 1.0 0.2 1.8 26.0 1386 1.15
25 7 / 2.13 6.39 1.2 1.0 0.2 1.8 30.5 1991 0.727
35 7 / 2.52 7.56 1.2 1.0 0.2 1.9 34.0 2577 0.524
50 19 / 1.83 9.15 1.4 1.2 0.2 2.1 40.0 3400 0.387
Page - 50
Section 3 - XLPE Insulated Cables
Unarmoured Cables
Page - 51
Section 3 - XLPE Insulated Cables
Unarmoured Cables
SINGLE CORE
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
Page - 52
Section 3 - XLPE Insulated Cables
Unarmoured Cables
TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
Page - 53
Section 3 - XLPE Insulated Cables
Unarmoured Cables
THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
Page - 54
Section 3 - XLPE Insulated Cables
Unarmoured Cables
FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
Page - 55
Section 3 - XLPE Insulated Cables
Unarmoured Cables
FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
section of wire Conductor Insulation Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm kg/km Ω/km
Page - 56
Section 3 - XLPE Insulated Cables
Unarmoured Cables
Page - 57
Section 3 - XLPE Insulated Cables
Unarmoured Cables
Page - 58
Section 3 - XLPE Insulated Cables
Unarmoured Cables
Page - 59
Section 3 - XLPE Insulated Cables
Unarmoured Cables
Page - 60
Section 3 - XLPE Insulated Cables
Unarmoured Cables
1 Constructions :
1 Conductor (Annealed Copper)
2 2 Insulation (XLPE Compound)
3 Filler (Polyprophylene yarn,or extruded filler
up to request)
3
4 Binding tape (Manufacturer's option)
4
5 Copper Tape screen
5 6 Binding tape (Manufacturer's option)
7 Outer sheath (PVC Compound)
6
Page - 61
Section 3 - XLPE Insulated Cables
Unarmoured Cables
TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of of Resistance
section area of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm kg/km Ω/km
Page - 62
Section 3 - XLPE Insulated Cables
Unarmoured Cables
THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of of Resistance
section area of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm kg/km Ω/km
Page - 63
Section 3 - XLPE Insulated Cables
Unarmoured Cables
FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of of Resistance
section area of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm kg/km Ω/km
Page - 64
Section 3 - XLPE Insulated Cables
Unarmoured Cables
FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of of of of Resistance
section area of wire Conductor Insulation Copper tape Sheath cable cable at 20°C
(approx.) (approx.) (approx.) (approx.) (approx.)
mm² No./mm mm mm mm mm mm kg/km Ω/km
Page - 65
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/AWA/PVC (acc. to IEC 60502-1)
1
Constructions :
2
1 Conductor (Annealed Copper)
3 2 Insulation (XLPE Compound)
4 3 Inner Covering (PVC Compound)
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/SWA/PVC (acc. to IEC 60502-1)
Constructions :
1
1 Conductor (Annealed Copper)
2 2 Insulation (XLPE Compound)
3 3 Filler (Polyprophylene yarn,or extruded filler
4 up to request)
5 4 Binding tape (Manufacturer's option)
6 5 Inner Covering (PVC Compound)
6 Galvanized Round Steel Wire armour
7
7 Binding tape (Manufacturer's option)
8 Outer sheath (PVC Compound)
8
Page - 66
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, ALUMINIUM WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/AWA/PVC (IEC 60502-1)
SINGLE CORE
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner diameter of of of of Resistance
section of wire Conductor Insulation covering Aluminium Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) wire (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
150 Compact 14.3 1.4 1.0 1.6 1.8 26.5 1865 0.124
185 round 16.0 1.6 1.0 1.6 1.8 28.5 2270 0.0991
240 stranded 18.3 1.7 1.0 1.6 1.9 31.0 2860 0.0754
1000 Round stranded 41.6 2.8 1.4 2.5 2.5 60.5 11315 0.0176
Page - 67
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/SWA/PVC (IEC 60502-1)
TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner diameter of of of Resistance
section of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.7 1.0 0.8 1.8 13.5 314 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 1.8 14.0 325 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 1.8 14.5 355 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 1.8 15.0 372 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 1.8 15.5 422 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 1.8 16.0 437 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 1.8 16.5 485 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 1.8 17.0 511 3.08
10 7 / 1.35 4.05 0.7 1.0 1.25 1.8 20.0 757 1.83
16 4.7 0.7 1.0 1.25 1.8 21.0 907 1.15
25 5.9 0.9 1.0 1.6 1.8 25.0 1342 0.727
35 Compact 7.1 0.9 1.0 1.6 1.8 27.5 1630 0.524
50 round 8.1 1.0 1.0 1.6 1.8 30.0 1965 0.387
70 stranded 9.7 1.1 1.0 1.6 2.0 34.0 2549 0.268
95 11.6 1.1 1.2 2.0 2.1 39.0 3517 0.193
120 12.9 1.2 1.2 2.0 2.2 42.0 4159 0.153
150 14.3 1.4 1.2 2.0 2.3 46.0 4966 0.124
185 16.0 1.6 1.4 2.5 2.5 52.0 6435 0.0991
240 18.3 1.7 1.4 2.5 2.7 57.5 7894 0.0754
300 20.7 1.8 1.6 2.5 2.8 63.0 9543 0.0601
Page - 68
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/SWA/PVC (IEC 60502-1)
THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner diameter of of of Resistance
section of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.7 1.0 0.8 1.8 14.0 343 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 1.8 14.5 360 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 1.8 15.0 398 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 1.8 15.5 417 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 1.8 16.0 474 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 1.8 17.0 502 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 1.8 17.0 570 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 1.8 18.0 591 3.08
10 7 / 1.35 4.05 0.7 1.0 1.25 1.8 20.5 887 1.83
16 4.7 0.7 1.0 1.25 1.8 22.0 1087 1.15
25 5.9 0.9 1.0 1.6 1.8 26.5 1622 0.727
35 Compact 7.1 0.9 1.0 1.6 1.8 29.0 2015 0.524
50 round 8.1 1.0 1.0 1.6 1.9 31.5 2461 0.387
70 stranded 9.7 1.1 1.2 2.0 2.0 37.0 3522 0.268
95 11.6 1.1 1.2 2.0 2.2 41.5 4491 0.193
120 12.9 1.2 1.2 2.0 2.3 45.0 5381 0.153
150 14.3 1.4 1.4 2.5 2.5 50.0 6919 0.124
185 16.0 1.6 1.4 2.5 2.6 55.0 8285 0.0991
240 18.3 1.7 1.6 2.5 2.8 61.5 10398 0.0754
300 20.7 1.8 1.6 2.5 3.0 67.5 12550 0.0601
Page - 69
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/SWA/PVC (IEC 60502-1)
FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner diameter of of of Resistance
section of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.7 1.0 0.8 1.8 15.0 384 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 1.8 15.5 398 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 1.8 16.0 455 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 1.8 16.5 471 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 1.8 17.0 550 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 1.8 18.0 575 4.61
6 7 / 2.77 2.77 0.7 1.0 1.25 1.8 19.0 755 3.08
6 7 / 1.04 3.12 0.7 1.0 1.25 1.8 19.5 792 3.08
10 7 / 1.35 4.05 0.7 1.0 1.25 1.8 22.0 1039 1.83
16 4.7 0.7 1.0 1.25 1.8 23.5 1292 1.15
25 5.9 0.9 1.0 1.6 1.8 28.5 1955 0.727
35 Compact 7.1 0.9 1.0 1.6 1.9 31.5 2440 0.524
50 round 8.1 1.0 1.0 1.6 2.0 34.5 3039 0.387
70 stranded 9.7 1.1 1.2 2.0 2.2 40.5 4345 0.268
95 11.6 1.1 1.2 2.0 2.3 45.0 5577 0.193
120 12.9 1.2 1.4 2.5 2.5 50.0 7191 0.153
150 14.3 1.4 1.4 2.5 2.6 55.0 8600 0.124
185 16.0 1.6 1.4 2.5 2.8 60.5 10388 0.0991
240 18.3 1.7 1.6 2.5 3.0 67.5 13059 0.0754
300 20.7 1.8 1.6 2.5 3.2 74.0 15807 0.0601
Page - 70
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/SWA/PVC (IEC 60502-1)
FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner diameter of of of Resistance
section of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.7 1.0 0.8 1.8 16.0 427 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 1.8 16.5 447 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 1.8 17.0 510 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 1.8 17.5 531 7.41
4 1 / 2.26 2.26 0.7 1.0 1.25 1.8 19.0 727 4.61
4 7 / 0.85 2.55 0.7 1.0 1.25 1.8 19.5 763 4.61
6 1 / 2.77 2.77 0.7 1.0 1.25 1.8 20.5 905 3.08
6 7 / 1.04 3.12 0.7 1.0 1.25 1.8 21.0 908 3.08
10 7 / 1.35 4.05 0.7 1.0 1.25 1.8 24.0 1203 1.83
16 Compact 4.7 0.7 1.0 1.6 1.8 26.5 1666 1.15
25 round 5.9 0.9 1.0 1.6 1.8 30.5 2290 0.727
35 stranded 7.1 0.9 1.0 1.6 1.9 34.0 2878 0.524
50 8.1 1.0 1.2 2.0 2.1 39.0 3920 0.387
Page - 71
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (acc. to IEC 60502-1)
2
1 Conductor (Annealed Copper)
2 Insulation (XLPE Compound)
3
3 Filler (Polyprophylene yarn,or extruded filler
4 up to request)
4 Binding tape (Manufacturer's option)
5
5 Inner Covering (PVC Compound)
6 6 Galvanized Flat Steel Wire armour
7 Galvanized Steel Tape binding
7
8 Outer sheath (PVC Compound)
Page - 72
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)
TWO CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.7 1.0 0.8 0.3 1.8 14.0 365 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 0.3 1.8 14.0 398 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 0.3 1.8 14.5 426 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 0.3 1.8 15.0 434 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 0.3 1.8 15.5 502 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 0.3 1.8 16.0 514 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 0.3 1.8 16.5 575 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 0.3 1.8 17.0 598 3.08
10 7 / 1.35 4.05 0.7 1.0 0.8 0.3 1.8 19.0 744 1.83
16 4.7 0.7 1.0 0.8 0.3 1.8 20.5 896 1.15
25 5.9 0.9 1.0 0.8 0.3 1.8 23.5 1187 0.727
35 Compact 7.1 0.9 1.0 0.8 0.3 1.8 26.0 1472 0.524
50 round 8.1 1.0 1.0 0.8 0.3 1.8 28.5 1804 0.387
70 stranded 9.7 1.1 1.0 0.8 0.3 1.9 32.0 2328 0.268
95 11.6 1.1 1.2 0.8 0.3 2.0 36.5 3031 0.193
120 12.9 1.2 1.2 0.8 0.3 2.1 39.5 3635 0.153
150 14.3 1.4 1.2 0.8 0.3 2.2 43.5 4381 0.124
185 16.0 1.6 1.4 0.8 0.3 2.4 48.5 5342 0.0991
240 18.3 1.7 1.4 0.8 0.3 2.6 54.0 6724 0.0754
300 20.7 1.8 1.6 0.8 0.3 2.7 60.0 8222 0.0601
400 23.4 2.0 1.6 0.8 0.3 3.0 66.5 10210 0.0470
Page - 73
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)
THREE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.7 1.0 0.8 0.3 1.8 14.5 418 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 0.3 1.8 14.5 426 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 0.3 1.8 15.0 460 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 0.3 1.8 15.5 497 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 0.3 1.8 16.0 551 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 0.3 1.8 17.0 593 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 0.3 1.8 17.5 665 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 0.3 1.8 18.0 671 3.08
10 7 / 1.35 4.05 0.7 1.0 0.8 0.3 1.8 20.0 884 1.83
16 4.7 0.7 1.0 0.8 0.3 1.8 21.5 1087 1.15
25 5.9 0.9 1.0 0.8 0.3 1.8 25.0 1466 0.727
35 Compact 7.1 0.9 1.0 0.8 0.3 1.8 27.5 1841 0.524
50 round 8.1 1.0 1.0 0.8 0.3 1.8 30.0 2285 0.387
70 stranded 9.7 1.1 1.2 0.8 0.3 2.0 34.5 3070 0.268
95 11.6 1.1 1.2 0.8 0.3 2.1 39.0 3989 0.193
120 12.9 1.2 1.2 0.8 0.3 2.2 42.0 4816 0.153
150 14.3 1.4 1.4 0.8 0.3 2.3 46.5 5871 0.124
185 16.0 1.6 1.4 0.8 0.3 2.4 52.0 7162 0.0991
240 18.3 1.7 1.6 0.8 0.3 2.7 58.0 9123 0.0754
300 20.7 1.8 1.6 0.8 0.3 2.8 64.0 11130 0.0601
Page - 74
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)
FOUR CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.7 1.0 0.8 0.3 1.8 15.0 446 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 0.3 1.8 15.5 483 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 0.3 1.8 16.0 532 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 0.3 1.8 16.5 544 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 0.3 1.8 17.0 637 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 0.3 1.8 18.0 659 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 0.3 1.8 18.5 645 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 0.3 1.8 19.0 783 3.08
10 7 / 1.35 4.05 0.7 1.0 0.8 0.3 1.8 21.5 1039 1.83
16 4.7 0.7 1.0 0.8 0.3 1.8 23.0 1295 1.15
25 5.9 0.9 1.0 0.8 0.3 1.8 27.0 1795 0.727
35 Compact 7.1 0.9 1.0 0.8 0.3 1.8 30.0 2263 0.524
50 round 8.1 1.0 1.0 0.8 0.3 1.9 32.5 2830 0.387
70 stranded 9.7 1.1 1.2 0.8 0.3 2.1 38.0 3838 0.268
95 11.6 1.1 1.2 0.8 0.3 2.2 42.5 5013 0.193
120 12.9 1.2 1.4 0.8 0.3 2.3 47.0 6144 0.153
150 14.3 1.4 1.4 0.8 0.3 2.5 51.5 7450 0.124
185 16.0 1.6 1.4 0.8 0.3 2.7 57.5 9123 0.0991
240 18.3 1.7 1.6 0.8 0.3 2.9 64.0 11666 0.0754
300 20.7 1.8 1.6 0.8 0.3 3.1 70.5 14268 0.0601
Page - 75
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)
FIVE CORES
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness thickness Minimum Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of Galv. thickness of of of Resistance
section of wire Conductor Insulation covering Flat of Galv. Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel wire Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.7 1.0 0.8 0.3 1.8 16.0 508 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.8 0.3 1.8 16.5 520 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.8 0.3 1.8 17.0 601 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.8 0.3 1.8 17.5 615 7.41
4 1 / 2.26 2.26 0.7 1.0 0.8 0.3 1.8 18.5 730 4.61
4 7 / 0.85 2.55 0.7 1.0 0.8 0.3 1.8 19.0 750 4.61
6 1 / 2.77 2.77 0.7 1.0 0.8 0.3 1.8 20.0 875 3.08
6 7 / 1.04 3.12 0.7 1.0 0.8 0.3 1.8 20.5 897 3.08
10 7 / 1.35 4.05 0.7 1.0 0.8 0.3 1.8 23.0 1196 1.83
16 Compact 4.7 0.7 1.0 0.8 0.3 1.8 25.0 1512 1.15
25 round 5.9 0.9 1.0 0.8 0.3 1.8 29.0 2100 0.727
35 stranded 7.1 0.9 1.0 0.8 0.3 1.9 32.5 2700 0.524
50 8.1 1.0 1.2 0.8 0.3 2.0 36.0 3432 0.387
Page - 76
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DATA/PVC (acc. to IEC 60502-1)
1
Constructions :
2 1 Conductor (Annealed Copper)
2 Insulation (XLPE Compound)
3
3 Inner Covering (PVC Compound)
4
4 Double Aluminium Tape armour
5 Outer sheath (PVC Compound)
5
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (acc. to IEC 60502-1)
Constructions :
1 1 Conductor (Annealed Copper)
2 Insulation (XLPE Compound)
2
3 Filler (Polyprophylene yarn,or extruded filler
3
up to request)
4
4 Binding tape (Manufacturer's option)
5
5 Inner Covering (PVC Compound)
6
6 Double Galvanized Steel Tape armour
7 Outer sheath (PVC Compound)
7
Note : Special application upon request
* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed
Page - 77
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, ALUMINIUM TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DATA/PVC (IEC 60502-1)
SINGLE CORE
Conductor Nominal Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Thickness Thickness diameter Weight Conductor
Cross- Diameter of of of Inner of of of of Resistance
section of wire Conductor Insulation covering Aluminium Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
Page - 78
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)
TWO CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner thickness of of of Resistance
section of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.7 1.0 0.2 1.8 12.5 220 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.2 1.8 13.0 230 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.2 1.8 13.0 258 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.2 1.8 13.5 268 7.41
4 1 / 2.26 2.26 0.7 1.0 0.2 1.8 14.0 312 4.61
4 7 / 0.85 2.55 0.7 1.0 0.2 1.8 15.0 326 4.61
6 1 / 2.77 2.77 0.7 1.0 0.2 1.8 15.0 372 3.08
6 7 / 1.04 3.12 0.7 1.0 0.2 1.8 16.0 387 3.08
10 7 / 1.35 4.05 0.7 1.0 0.2 1.8 18.0 514 1.83
16 4.7 0.7 1.0 0.2 1.8 19.0 643 1.15
25 5.9 0.9 1.0 0.2 1.8 23.0 893 0.727
35 Compact 7.1 0.9 1.0 0.2 1.8 24.5 1134 0.524
50 round 8.1 1.0 1.0 0.2 1.8 27.0 1422 0.387
70 stranded 9.7 1.1 1.0 0.2 1.9 30.5 1905 0.268
95 11.6 1.1 1.2 0.2 2.0 35.0 2544 0.193
120 12.9 1.2 1.2 0.5 2.1 39.5 3505 0.153
150 14.3 1.4 1.4 0.5 2.3 43.5 4245 0.124
185 15.9 1.6 1.4 0.5 2.4 48.5 5180 0.0991
240 18.3 1.7 1.6 0.5 2.6 54.0 6530 0.0754
300 20.7 1.8 1.6 0.5 2.7 59.5 8004 0.0601
Page - 79
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)
THREE CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner thickness of of of Resistance
section of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.58 1.58 0.7 1.0 0.2 1.8 13.0 249 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.2 1.8 13.5 259 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.2 1.8 13.5 294 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.2 1.8 14.0 307 7.41
4 1 / 2.26 2.26 0.7 1.0 0.2 1.8 15.0 263 4.61
4 7 / 0.85 2.55 0.7 1.0 0.2 1.8 15.5 381 4.61
6 1 / 2.77 2.77 0.7 1.0 0.2 1.8 16.0 445 3.08
6 7 / 1.04 3.12 0.7 1.0 0.2 1.8 16.5 463 3.08
10 7 / 1.35 4.05 0.7 1.0 0.2 1.8 18.5 630 1.83
16 4.7 0.7 1.0 0.2 1.8 20.0 812 1.15
25 5.9 0.9 1.0 0.2 1.8 23.5 1150 0.727
35 Compact 7.1 0.9 1.0 0.2 1.8 26.0 1481 0.524
50 round 8.1 1.0 1.0 0.2 1.8 28.5 1882 0.387
70 stranded 9.7 1.1 1.2 0.2 1.9 33.0 2588 0.268
95 11.6 1.1 1.2 0.2 2.1 37.5 3456 0.193
120 12.9 1.2 1.2 0.5 2.2 42.0 4669 0.153
150 14.3 1.4 1.4 0.5 2.4 46.5 5708 0.124
185 15.9 1.6 1.4 0.5 2.5 51.5 6965 0.0991
240 18.3 1.7 1.6 0.5 2.7 58.0 8905 0.0754
300 20.7 1.8 1.6 0.5 2.9 64.0 10919 0.0601
Page - 80
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)
FOUR CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner thickness of of of Resistance
section of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.7 1.0 0.2 1.8 13.5 280 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.2 1.8 14.0 293 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.2 1.8 14.5 343 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.2 1.8 15.0 357 7.41
4 1 / 2.26 2.26 0.7 1.0 0.2 1.8 16.0 426 4.61
4 7 / 0.85 2.55 0.7 1.0 0.2 1.8 16.5 446 4.61
6 1 / 2.77 2.77 0.7 1.0 0.2 1.8 17.0 531 3.08
6 7 / 1.04 3.12 0.7 1.0 0.2 1.8 17.5 552 3.08
10 7 / 1.35 4.05 0.7 1.0 0.2 1.8 20.0 764 1.83
16 4.7 0.7 1.0 0.2 1.8 21.5 999 1.15
25 5.9 0.9 1.0 0.2 1.8 25.5 1434 0.727
35 Compact 7.1 0.9 1.0 0.2 1.8 28.5 1859 0.524
50 round 8.1 1.0 1.0 0.2 1.9 31.5 2383 0.387
70 stranded 9.7 1.1 1.2 0.2 2.0 36.0 3311 0.268
95 11.6 1.1 1.2 0.5 2.2 42.5 4872 0.193
120 12.9 1.2 1.4 0.5 2.4 46.5 5983 0.153
150 14.3 1.4 1.4 0.5 2.5 51.0 7274 0.124
185 15.9 1.6 1.4 0.5 2.7 57.0 8922 0.0991
240 18.3 1.7 1.6 0.5 2.9 64.0 11427 0.0754
300 20.7 1.8 1.6 0.5 3.1 70.5 14015 0.0601
Page - 81
Section 3 - XLPE Insulated Cables
Armoured Cables
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)
FIVE CORES
Conductor Nominal Nominal Overall Maximum
Nominal No./ Diameter Thickness Thickness Nominal Thickness diameter Weight Conductor
Cross- Diameter of of of Inner thickness of of of Resistance
section of wire Conductor Insulation covering of Sheath cable cable at 20°C
area (approx.) (approx.) (approx.) Steel tape (approx.) (approx.)
mm² No./mm mm mm mm mm mm mm kg/km Ω/km
1.5 1 / 1.38 1.38 0.7 1.0 0.2 1.8 14.5 319 12.1
1.5 7 / 0.52 1.56 0.7 1.0 0.2 1.8 15.0 333 12.1
2.5 1 / 1.78 1.78 0.7 1.0 0.2 1.8 15.5 390 7.41
2.5 7 / 0.67 2.01 0.7 1.0 0.2 1.8 16.0 405 7.41
4 1 / 2.26 2.26 0.7 1.0 0.2 1.8 17.0 496 4.61
4 7 / 0.85 2.55 0.7 1.0 0.2 1.8 17.5 520 4.61
6 1 / 2.77 2.77 0.7 1.0 0.2 1.8 18.5 620 3.08
6 7 / 1.04 3.12 0.7 1.0 0.2 1.8 19.0 645 3.08
10 7 / 1.35 4.05 0.7 1.0 0.2 1.8 22.0 900 1.83
16 Compact 4.7 0.7 1.0 0.2 1.8 23.5 1196 1.15
25 round 5.9 0.9 1.0 0.2 1.8 27.5 1720 0.727
35 stranded 7.1 0.9 1.0 0.2 1.9 31.0 2252 0.524
50 8.1 1.0 1.2 0.2 2.0 35.0 2946 0.387
Page - 82
CURRENT CARRYING CAPACITY FOR SINGLE CORE XLPE INSULATED CABLE
Current Carrying Capacity DC Alternating Minimum Conductor
1) Reactance2) (50 Hz) Inductance2) (50 Hz)
Conductor In Air ( 30°C ) In Ground Conductor Current Insulation Short
Nominal Flat Trefoil Trefoil Resistance resistance Nominal Resistance circuit
Area at 20°C at 90°C / Trefoil Flat Trefoil Flat Capacitance at 20°C current /
core to core core to core 1 sec
50 Hz
mm² A A A Ω / km Ω / km Ω / km Ω / km mH / km mH / km µF / km M Ω. km A
1.5 re/rm 22 21 22 12.1 15.43 0.1459 0.1603 0.4646 0.5108 0.0520 3000 212
2.5 re/rm 30 29 29 7.41 9.45 0.1339 0.1484 0.4264 0.4726 0.0571 2500 353
4 re/rm 42 40 37 4.61 5.88 0.1244 0.1391 0.3962 0.4424 0.0621 2000 564
6 re/rm 55 53 46 3.08 3.93 0.1160 0.1305 0.3693 0.4155 0.0665 2000 846
10 re/rm 77 74 61 1.83 2.34 0.1072 0.1217 0.3416 0.3878 0.0721 1500 1410
16 cm 105 101 79 1.15 1.47 0.1028 0.1172 0.3264 0.3726 0.0751 1500 2256
25 cm 141 135 101 0.727 0.927 0.0984 0.1130 0.3124 0.3586 0.0752 1500 3525
35 cm 176 169 122 0.524 0.669 0.0932 0.1077 0.2967 0.3429 0.0789 1000 4935
50 cm 216 207 144 0.387 0.494 0.0911 0.1056 0.2890 0.3353 0.0796 1000 7050
70 cm 279 268 178 0.268 0.343 0.0875 0.1023 0.2778 0.3240 0.0815 900 9870
95 cm 342 328 211 0.193 0.247 0.0845 0.0991 0.2674 0.3136 0.0848 800 13395
120 cm 400 383 240 0.153 0.196 0.0827 0.0974 0.2629 0.3091 0.0853 800 16920
150 cm 464 444 271 0.124 0.159 0.0829 0.0975 0.2626 0.3088 0.0846 800 21150
185 cm 533 510 304 0.0991 0.1272 0.0830 0.0976 0.2612 0.3074 0.0833 900 26085
240 cm 634 607 351 0.0754 0.0972 0.0814 0.0960 0.2565 0.3028 0.0848 800 33840
300 cm 736 703 396 0.0601 0.0779 0.0799 0.0944 0.2526 0.2988 0.0860 800 42300
400 cm 868 823 464 0.0470 0.0614 0.0728 0.0874 0.2500 0.2962 0.0865 700 56400
1)
Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W Note : Reference methode of installation to be used to obtain current carrying
rm : Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cm capacity for : in cable ducting, in cables conduit, cables direct in the -
cm : Circular stranded compacted conductor IEC 60228 class 2 Base temperature : 20°C ground with / without added protection against mechanical damage
2)
The Inductance calculated for non armour cable.
Section 4 - General Information
Page - 84
1.5 re/rm 26 23 26 22 12.1 15.43 0.0999 0.1125 0.3181 0.2498 0.0520 3000 212
2.5 re/rm 36 32 34 29 7.41 9.45 0.0961 0.1086 0.3057 0.2325 0.0571 2500 353
4 re/rm 49 42 44 37 4.61 5.88 0.0899 0.1025 0.2860 0.2128 0.0621 2000 564
6 re/rm 63 54 56 46 3.08 3.93 0.0853 0.0980 0.2714 0.1982 0.0665 2000 846
10 re/rm 86 75 73 61 1.83 2.34 0.0802 0.0930 0.2552 0.1819 0.0721 1500 1410
16 cm 115 100 95 79 1.15 1.47 0.0781 0.0910 0.2485 0.1752 0.0751 1500 2256
25 cm 149 127 121 101 0.727 0.927 0.0779 0.0908 0.2480 0.1748 0.0752 1500 3525
35 cm 185 158 146 122 0.524 0.669 0.0753 0.0883 0.2397 0.1664 0.0789 1000 4935
50 cm 225 192 173 144 0.387 0.494 0.0748 0.0877 0.2379 0.1646 0.0796 1000 7050
70 cm 289 246 213 178 0.268 0.343 0.0734 0.0864 0.2335 0.1602 0.0815 900 9870
95 cm 352 298 252 211 0.193 0.247 0.0711 0.0842 0.2262 0.1530 0.0848 800 13395
120 cm 410 346 287 240 0.153 0.197 0.0708 0.0839 0.2254 0.1521 0.0853 800 16920
150 cm 473 399 324 271 0.124 0.160 0.0712 0.0843 0.2267 0.1534 0.0846 800 21150
185 cm 542 456 363 304 0.0991 0.1281 0.0720 0.0851 0.2292 0.1559 0.0833 900 26085
240 cm 641 538 419 351 0.0754 0.0984 0.0711 0.0842 0.2264 0.1531 0.0848 800 33840
300 cm 741 621 474 396 0.0601 0.0799 0.0704 0.0835 0.2240 0.1507 0.0860 800 42300
400 cm 892 745 555 464 0.0470 0.0633 0.0701 0.0832 0.2231 0.1498 0.0865 700 56400
Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W 4* : 3 Phasa + Netral / Ground
rm : Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cm
cm : Circular stranded compacted conductor IEC 60228 class 2 Base temperature : 20°C
CURRENT CARRYING CAPACITY FOR SINGLE CORE PVC INSULATED CABLE
Current Carrying Capacity DC Alternating Minimum Conductor
1)
Reactance2) (50 Hz) Inductance 2) (50 Hz)
Conductor In Air ( 30°C ) In Ground Conductor Current Insulation Short
Nominal Flat Trefoil Trefoil Resistance resistance Nominal Resistance circuit
Area at 20°C at 70°C / Trefoil Flat Trefoil Flat Capacitance at 20°C current /
core to core core to core 1 sec
50 Hz
mm² A A A Ω / km Ω / km Ω / km Ω / km mH / km mH / km µF / km M Ω. km A
1.5 re/rm 18 17 18 12.1 14.4777 0.1476 0.1735 0.4697 0.5159 0.1391 50 174
2.5 re/rm 25 24 24 7.41 8.8661 0.1359 0.1621 0.4327 0.4789 0.1531 50 290
4 re/rm 34 33 31 4.61 5.5159 0.1291 0.1555 0.4110 0.4572 0.1553 50 464
6 re/rm 45 43 39 3.08 3.6853 0.1209 0.1475 0.3848 0.4310 0.1671 50 696
10 re/rm 63 60 52 1.83 2.1897 0.1112 0.1381 0.3538 0.4000 0.1827 50 1160
95 rm 275 264 179 0.193 0.2317 0.0864 0.1145 0.2749 0.3212 0.2205 30 11020
120 rm 321 308 203 0.153 0.1841 0.0838 0.1121 0.2669 0.3131 0.2270 30 13920
150 rm 372 356 230 0.124 0.1497 0.0833 0.1116 0.2651 0.3113 0.2274 20 17400
185 rm 427 409 258 0.0991 0.1202 0.0828 0.1111 0.2634 0.3096 0.2279 20 21460
240 rm 507 485 297 0.0754 0.0924 0.0814 0.1098 0.2592 0.3054 0.2308 20 27840
300 rm 587 561 336 0.0601 0.0746 0.0807 0.1091 0.2567 0.3029 0.2323 20 34800
400 rm 689 656 394 0.0470 0.0597 0.0799 0.1084 0.2543 0.3005 0.2387 20 46400
500 rm 789 749 445 0.0366 0.0482 0.0790 0.1075 0.2513 0.2975 0.2355 20 58000
1)
Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W Note : Reference methode of installation to be used to obtain current carrying
rm
Page - 85
: Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cm capacity for : in cable ducting, in cables conduit, cables direct in the -
Base temperature : 20°C ground with / without added protection against mechanical damage
2)
The Inductance calculated for non armour cable.
Section 4 - General Information
Page - 86
1.5 re/rm 22 18.5 22 18 12.1 14.4777 0.1075 0.1199 0.3421 0.2688 0.1391 50 174
2.5 re/rm 30 25 29 24 7.41 8.8661 0.0994 0.1120 0.3165 0.2433 0.1531 50 290
4 re/rm 40 34 38 31 4.61 5.5159 0.0983 0.1109 0.3130 0.2398 0.1553 50 464
6 re/rm 51 43 47 39 3.08 3.6853 0.0928 0.1054 0.2954 0.2221 0.1671 50 696
50 rm/sm 180 153 148 122 0.387 0.4635 0.0822 0.0950 0.2617 0.1884 0.2127 30 5800
70 rm/sm 232 196 183 151 0.268 0.3213 0.0789 0.0917 0.2510 0.1777 0.2223 30 8120
95 rm/sm 282 238 216 179 0.193 0.2318 0.0791 0.0920 0.2518 0.1785 0.2205 30 11020
120 rm/sm 328 276 246 203 0.153 0.1842 0.0772 0.0901 0.2457 0.1724 0.2270 30 13920
150 rm/sm 379 319 278 230 0.124 0.150 0.0775 0.0904 0.2466 0.1733 0.2274 20 17400
185 rm/sm 434 364 312 258 0.0991 0.1204 0.0769 0.0898 0.2447 0.1714 0.2279 20 21460
240 rm/sm 514 430 361 297 0.0754 0.0926 0.0759 0.0889 0.2417 0.1684 0.2308 20 27840
300 rm/sm 593 497 408 336 0.0601 0.0749 0.0756 0.0886 0.2407 0.1674 0.2323 20 34800
Note : re : Round solid conductor IEC 60228 class 1 Underground : Thermal resistivity of soil : 2.5 K.m / W 4* : 3 Phasa + Netral / Ground
rm : Circular stranded conductor IEC 60228 class 2 Depth of laying : 80 cm
sm : Sector shape stranded conductor IEC 60228 class 2 Base temperature : 20°C
Rating factor relating to open air temperature
Air temperature°C 10 15 20 25 30 35 40 45 50 55 60 65 70 80
PVC Insulation 1.22 1.17 1.12 1.06 1.00 0.94 0.87 0.79 0.71 0.61 0.50 - - -
XLPE Insulation 1.15 1.12 1.08 1.04 1.00 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.41
PVC Insulation 1.10 1.05 1.00 0.95 0.89 0.84 0.77 0.71 0.63 0.55 0.45 - - -
XLPE Insulation 1.07 1.04 1.00 0.96 0.93 0.89 0.85 0.80 0.76 0.71 0.65 0.60 0.53 0.38
5 0.70 0.75
7 0.60 0.65
10 0.50 0.55
14 0.45 0.50
19 0.40 0.45
40 0.30 0.35
61 0.25 0.30
Page - 87
Section 4 - General Information
Reduction factors for group of more than one multi-core cable (note 1)
to be applied to reference ratings for multi-core cables in free air
Number Number of cables
Method of installation
of trays 1 2 3 4 6 9
Touching
1 1.00 0.88 0.82 0.79 0.76 0.73
2 1.00 0.87 0.80 0.77 0.73 0.68
3 1.00 0.86 0.79 0.76 0.71 0.66
≥ 20 mm
Perforated trays
(note 2) Spaced
D
1 1.00 1.00 0.98 0.95 0.91 -
2 1.00 0.99 0.96 0.92 0.87 -
3 1.00 0.98 0.95 0.91 0.85 -
≥ 20 mm
trays
(note 3)
1 1.00 0.91 0.89 0.88 0.87 -
≥
225 mm
D
2 1.00 0.91 0.88 0.87 0.85 -
Spaced
Touching
1 1.00 0.87 0.82 0.80 0.79 0.78
2 1.00 0.86 0.80 0.78 0.76 0.73
Ladder 3 1.00 0.85 0.79 0.76 0.73 0.70
≥ 20 mm
supports,
cleats, etc. Spaced
D
(note 2) 1 1.00 1.00 1.00 1.00 1.00 -
2 1.00 0.99 0.98 0.97 0.96 -
3 1.00 0.98 0.97 0.96 0.93 -
≥ 20 mm
Factors apply to single layer groups of cables as shown above and do not apply when cables are installed in more than one layer touching each other.
Values for such installations may be significantly lower and shall be determined by an appropriate method.
NOTE 1 Values given are averages for the cable types and range of conductor sizes considered. The spread of values is generally less than ± 5 %.
NOTE 2 Values are given for vertical a spacing between trays of 300 mm and at least 20 mm between trays and wall. For closer spacing the factors
should be reduced.
NOTE 3 Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back. For closer spacing the factors should be
reduced.
Page - 88
Section 4 - General Information
Reduction factors for groups of more than one circuit of single-core cables (Note 1)
to be applied to reference rating for one circuit of single-core cables in free air
Number of Use as a multiplier to
Method of installation
trays 1 2 3 rating for
Touching
Perforated 1 0.98 0.91 0.87 Three cables in
trays 2 0.96 0.87 0.81 horizontal
(Note 3) 3 0.95 0.85 0.78 formation
≥ 20 mm
Touching
Vertically
≥
Perforated 225 mm 1 0.96 0.86 - Three cables
trays in vertcal
(note 4) 2 0.95 0.84 - formation
Touching
Ladder 1 1.00 0.97 0.96 Three cables in
supports,cleats etc. 2 0.98 0.93 0.89 horizontal
(Note 3) 3 0.97 0.90 0.86 formation
≥ 20 mm
D
≥ 2D 1 1.00 0.98 0.96
Perforated
trays 2 0.97 0.93 0.89
(Note 3) 3 0.96 0.92 0.86
≥ 20 mm
≥
225 mm
Vertical 1 1.00 0.91 0.89 Three cables in
≥ 2D
perforated trays trefoil
(Note 4) 2 1.00 0.90 0.86 formation
D
Spaced
D
≥ 2D 1 1.00 1.00 1.00
Ladder
supports,cleats etc. 2 0.97 0.95 0.93
(Note 3) 3 0.96 0.94 0.90
≥ 20 mm
NOTE 1 Value given are averages for the cable types and range of conductor sizes considered. The spread of values is generally less than ± 5 %.
NOTE 2 For circuits having more than one cable in parallel per phase, each three phase set of conductors should be considered as a circuit for the
purpose of this table
NOTE 3 Values are given for vertical spacings between trays of 300 mm.For closer spacing the factors should be reduced.
NOTE 4 Values are given for horizontal spacings between trays of 225 mm with trays mounted back to back and at least 20 mm between the tray
and any wall. For closer spacing the factors should be reduced.
Page - 89
Section 4 - General Information
PERMISSIBLE PULLING TENSION
Pulling equipment Permissible pulling tension (kg)
PULLING EYE 7 x (Number of core) x (Cross section area of conductor)
CABLE NET About 500 kg, but the maximum tension shall not be more than one of
conductor (same calculation as using PULLING EYE)
The cable pulling tension (T2) during installation can be calculated with below formula.
IEC 60332-3
Part 3 - Test on bunched wire or cables
This test was developed to obtain a method to determine the flame propagation characteristics of bunched cables.
It can not be assumed that because a single vertical cable complies with the requirements of IEC 60332 part 1 it will also behave in 1
a similar manner when bunched with others cables.
The propagation of a flame along a bunch of cables depends on a number of features, such as :
The volume of combustible material exposed to the fire
The geometrical configuration of the cables
The temperature at which it is possible to ignite any gases emitted from the cables
The quantity of combustible gas released from the cables
The volume of air passing through the cable installation
The test consists of a vertical chamber, 1 x 2 x 4 m. Openings air inlet and outlet are provided in the base and the top of the test
chamber for a controlled air flow rate during the test. The cable samples to be tested are 3.5 m long and fixed to a steel ladder mounted
150 mm from the rear wall vertically with the test chamber. The number of lengths of cables in the test depends on the test categoty
based on the volume of combustible material.
Test Category Volume of combustible material Time of flame application
A 7 litres / m 40 Minutes
B 3.5 litres / m 40 Minutes
C 1.5 litres / m 20 Minutes
A ribbon gas burner of a set size and heat flow rate, operating at 800°C is mounted horizontally in front of the cable samples at a set
distance and height. The test is passed if the charred or affected portion of the samples have not reached a height exceeding 2.5 m