This article is about the electrical component. For other uses, see Relay (disambiguation).

Automotive-style miniature relay, dust cover removed A relay is an electrically operated switch. Electric current through the coil of the relay creates a magnetic field which attracts a lever and changes the switch contacts. The coil current can be on or off so relays have two switch positions and they are doublethrow (changeover) switches.

Contents
[hide]

1 Basic design and operation 2 Types of relay o 2.1 Latching relay o 2.2 Reed relay o 2.3 Mercury-wetted relay o 2.4 Polarized relay o 2.5 Machine tool relay o 2.6 Contactor relay o 2.7 Solid-state relay o 2.8 Solid state contactor relay o 2.9 Buchholz relay o 2.10 Forced-guided contacts relay o 2.11 Overload protection relay 3 Pole and throw 4 Applications 5 Relay application considerations 6 Protective relay o 6.1 Overcurrent relay o 6.2 Induction disc overcurrent relay 7 Distance relay 8 Motor protection relay 9 Railway signalling o 9.1 General

9.2 Double switching 9.3 Proving 10 See also 11 References


o o

12 External links

[edit] Basic design and operation

Simple electromechanical relay

Small relay as used in electronics A simple electromagnetic relay, such as the one taken from a car in the first picture, is an adaptation of an electromagnet. It consists of a coil of wire surrounding a soft iron core, an iron yoke, which provides a low reluctance path for magnetic flux, a movable iron armature, and a set, or sets, of contacts; two in the relay pictured. The armature is hinged to the yoke and mechanically linked to a moving contact or contacts. It is held in place by a spring so that when the relay is de-energised there is an air gap in the magnetic circuit. In this condition, one of the two sets of contacts in the relay pictured is closed, and the other set is open. Other relays may have more or fewer sets of contacts depending on their function. The relay in the picture also has a wire connecting the armature to the yoke. This ensures continuity of the circuit between the moving contacts on the armature, and the circuit track on the Printed Circuit Board (PCB) via the yoke, which is soldered to the PCB. When an electric current is passed through the coil, the resulting magnetic field attracts the armature, and the consequent movement of the movable contact or contacts either makes or breaks a connection with a fixed contact. If the set of contacts was closed when the relay was de-energised, then the movement opens the contacts and breaks the connection, and vice versa if the contacts were open. When the current to the coil is switched off, the armature is returned by a force, approximately half as strong as the magnetic force, to its relaxed position. Usually

this force is provided by a spring, but gravity is also used commonly in industrial motor starters. Most relays are manufactured to operate quickly. In a low voltage application, this is to reduce noise. In a high voltage or high current application, this is to reduce arcing. If the coil is energized with DC, a diode is frequently installed across the coil, to dissipate the energy from the collapsing magnetic field at deactivation, which would otherwise generate a voltage spike dangerous to circuit components. Some automotive relays already include that diode inside the relay case. Alternatively a contact protection network, consisting of a capacitor and resistor in series, may absorb the surge. If the coil is designed to be energized with AC, a small copper ring can be crimped to the end of the solenoid. This "shading ring" creates a small out-of-phase current, which increases the minimum pull on the armature during the AC cycle.[1] By analogy with the functions of the original electromagnetic device, a solid-state relay is made with a thyristor or other solid-state switching device. To achieve electrical isolation an optocoupler can be used which is a light-emitting diode (LED) coupled with a photo transistor.

[edit] Types of relay


[edit] Latching relay

Latching relay, dust cover removed, showing pawl and ratchet mechanism. The ratchet operates a cam, which raises and lowers the moving contact arm, seen edge-on just below it. The moving and fixed contacts are visible at the left side of the image. A latching relay has two relaxed states (bistable). These are also called "impulse", "keep", or "stay" relays. When the current is switched off, the relay remains in its last state. This is achieved with a solenoid operating a ratchet and cam mechanism, or by having two opposing coils with an over-center spring or permanent magnet to hold the armature and contacts in position while the coil is relaxed, or with a remanent core. In the ratchet and cam example, the first pulse to the coil turns the relay on and the second pulse turns it off. In the two coil example, a pulse to one coil turns the relay on and a pulse to the opposite coil turns the relay off. This type of relay has the advantage that it consumes power only for an instant, while it is being switched, and it retains its last setting across a power outage. A remanent core latching relay requires a current pulse of opposite polarity to make it change state.

[edit] Reed relay


A reed relay has a set of contacts inside a vacuum or inert gas filled glass tube, which protects the contacts against atmospheric corrosion. The contacts are closed by a magnetic field generated when current passes through a coil around the glass tube. Reed relays are capable of faster switching speeds than larger types of relays, but have low switch current and voltage ratings. See also reed switch.

[edit] Mercury-wetted relay


A mercury-wetted reed relay is a form of reed relay in which the contacts are wetted with mercury. Such relays are used to switch low-voltage signals (one volt or less) because of their low contact resistance, or for high-speed counting and timing applications where the mercury eliminates contact bounce. Mercury wetted relays are position-sensitive and must be mounted vertically to work properly. Because of the toxicity and expense of liquid mercury, these relays are rarely specified for new equipment. See also mercury switch.

[edit] Polarized relay


A Polarized Relay placed the armature between the poles of a permanent magnet to increase sensitivity. Polarized relays were used in middle 20th Century telephone exchanges to detect faint pulses and correct telegraphic distortion. The poles were on screws, so a technician could first adjust them for maximum sensitivity and then apply a bias spring to set the critical current that would operate the relay.

[edit] Machine tool relay


A machine tool relay is a type standardized for industrial control of machine tools, transfer machines, and other sequential control. They are characterized by a large number of contacts (sometimes extendable in the field) which are easily converted from normally-open to normally-closed status, easily replaceable coils, and a form factor that allows compactly installing many relays in a control panel. Although such relays once were the backbone of automation in such industries as automobile assembly, the programmable logic controller (PLC) mostly displaced the machine tool relay from sequential control applications.

[edit] Contactor relay


A contactor is a very heavy-duty relay used for switching electric motors and lighting loads. High-current contacts are made with alloys containing silver. The unavoidable arcing causes the contacts to oxidize and silver oxide is still a good conductor. Such devices are often used for motor starters. A motor starter is a contactor with overload protection devices attached. The overload sensing devices are a form of heat operated relay where a coil heats a bi-metal strip, or where a solder pot melts, releasing a spring to operate auxiliary contacts. These auxiliary contacts are in series with the coil. If the overload senses excess current in the load, the coil is de-energized. Contactor relays can be extremely loud to operate, making them unfit for use where noise is a chief concern.

[edit] Solid-state relay

Solid state relay, which has no moving parts

25 A or 40 A solid state contactors A solid state relay (SSR) is a solid state electronic component that provides a similar function to an electromechanical relay but does not have any moving components, increasing long-term reliability. With early SSR's, the tradeoff came from the fact that every transistor has a small voltage drop across it. This voltage drop limited the amount of current a given SSR could handle. As transistors improved, higher current SSR's, able to handle 100 to 1,200 Amperes, have become commercially available. Compared to electromagnetic relays, they may be falsely triggered by transients.

[edit] Solid state contactor relay


A solid state contactor is a very heavy-duty solid state relay, including the necessary heat sink, used for switching electric heaters, small electric motors and lighting loads; where frequent on/off cycles are required. There are no moving parts to wear out and there is no contact bounce due to vibration. They are activated by AC control signals or DC control signals from Programmable logic controller (PLCs), PCs, Transistortransistor logic (TTL) sources, or other microprocessor and microcontroller controls.

[edit] Buchholz relay


A Buchholz relay is a safety device sensing the accumulation of gas in large oil-filled transformers, which will alarm on slow accumulation of gas or shut down the transformer if gas is produced rapidly in the transformer oil.

[edit] Forced-guided contacts relay


A forced-guided contacts relay has relay contacts that are mechanically linked together, so that when the relay coil is energized or de-energized, all of the linked

contacts move together. If one set of contacts in the relay becomes immobilized, no other contact of the same relay will be able to move. The function of forced-guided contacts is to enable the safety circuit to check the status of the relay. Forced-guided contacts are also known as "positive-guided contacts", "captive contacts", "locked contacts", or "safety relays".

[edit] Overload protection relay


One type of electric motor overload protection relay is operated by a heating element in series with the electric motor . The heat generated by the motor current operates a bi-metal strip or melts solder, releasing a spring to operate contacts. Where the overload relay is exposed to the same environment as the motor, a useful though crude compensation for motor ambient temperature is provided.

[edit] Pole and throw

Circuit symbols of relays. "C" denotes the common terminal in SPDT and DPDT types.

The diagram on the package of a DPDT AC coil relay Since relays are switches, the terminology applied to switches is also applied to relays. A relay will switch one or more poles, each of whose contacts can be thrown by energizing the coil in one of three ways:

Normally-open (NO) contacts connect the circuit when the relay is activated; the circuit is disconnected when the relay is inactive. It is also called a Form A contact or "make" contact.

Normally-closed (NC) contacts disconnect the circuit when the relay is activated; the circuit is connected when the relay is inactive. It is also called a Form B contact or "break" contact. Change-over (CO), or double-throw (DT), contacts control two circuits: one normally-open contact and one normally-closed contact with a common terminal. It is also called a Form C contact or "transfer" contact ("break before make"). If this type of contact utilizes a "make before break" functionality, then it is called a Form D contact.

The following designations are commonly encountered:

SPST - Single Pole Single Throw. These have two terminals which can be connected or disconnected. Including two for the coil, such a relay has four terminals in total. It is ambiguous whether the pole is normally open or normally closed. The terminology "SPNO" and "SPNC" is sometimes used to resolve the ambiguity. SPDT - Single Pole Double Throw. A common terminal connects to either of two others. Including two for the coil, such a relay has five terminals in total. DPST - Double Pole Single Throw. These have two pairs of terminals. Equivalent to two SPST switches or relays actuated by a single coil. Including two for the coil, such a relay has six terminals in total. The poles may be Form A or Form B (or one of each). DPDT - Double Pole Double Throw. These have two rows of change-over terminals. Equivalent to two SPDT switches or relays actuated by a single coil. Such a relay has eight terminals, including the coil.

The "S" or "D" may be replaced with a number, indicating multiple switches connected to a single actuator. For example 4PDT indicates a four pole double throw relay (with 14 terminals).

[edit] Applications
Relays are used to and for:

Control a high-voltage circuit with a low-voltage signal, as in some types of modems or audio amplifiers, Control a high-current circuit with a low-current signal, as in the starter solenoid of an automobile, Detect and isolate faults on transmission and distribution lines by opening and closing circuit breakers (protection relays),

A DPDT AC coil relay with "ice cube" packaging

Isolate the controlling circuit from the controlled circuit when the two are at different potentials, for example when controlling a mains-powered device from a low-voltage switch. The latter is often applied to control office lighting as the low voltage wires are easily installed in partitions, which may be often moved as needs change. They may also be controlled by room occupancy detectors in an effort to conserve energy, Logic functions. For example, the boolean AND function is realised by connecting normally open relay contacts in series, the OR function by connecting normally open contacts in parallel. The change-over or Form C contacts perform the XOR (exclusive or) function. Similar functions for NAND and NOR are accomplished using normally closed contacts. The Ladder programming language is often used for designing relay logic networks. o Early computing. Before vacuum tubes and transistors, relays were used as logical elements in digital computers. See ARRA (computer), Harvard Mark II, Zuse Z2, and Zuse Z3. o Safety-critical logic. Because relays are much more resistant than semiconductors to nuclear radiation, they are widely used in safetycritical logic, such as the control panels of radioactive waste-handling machinery. Time delay functions. Relays can be modified to delay opening or delay closing a set of contacts. A very short (a fraction of a second) delay would use a copper disk between the armature and moving blade assembly. Current flowing in the disk maintains magnetic field for a short time, lengthening release time. For a slightly longer (up to a minute) delay, a dashpot is used. A dashpot is a piston filled with fluid that is allowed to escape slowly. The time period can be varied by increasing or decreasing the flow rate. For longer time periods, a mechanical clockwork timer is installed.

[edit] Relay application considerations

A large relay with two coils and many sets of contacts, used in an old telephone switching system.

Several 30-contact relays in "Connector" circuits in mid 20th century 1XB switch and 5XB switch telephone exchanges; cover removed on one Selection of an appropriate relay for a particular application requires evaluation of many different factors:

Number and type of contacts - normally open, normally closed, (doublethrow) Contact sequence - "Make before Break" or "Break before Make". For example, the old style telephone exchanges required Make-before-break so that the connection didn't get dropped while dialing the number. Rating of contacts - small relays switch a few amperes, large contactors are rated for up to 3000 amperes, alternating or direct current Voltage rating of contacts - typical control relays rated 300 VAC or 600 VAC, automotive types to 50 VDC, special high-voltage relays to about 15 000 V Coil voltage - machine-tool relays usually 24 VAC, 120 or 250 VAC, relays for switchgear may have 125 V or 250 VDC coils, "sensitive" relays operate on a few milliamperes Coil current - Usually in the range of 40 - 200 mA for 0 - 24 VDC coils.[2] Package/enclosure - open, touch-safe, double-voltage for isolation between circuits, explosion proof, outdoor, oil and splash resistant, washable for printed circuit board assembly Assembly - Some relays feature a sticker that keeps the enclosure sealed to allow PCB post soldering cleaning agents. Which is removed once assembly is complete. Mounting - sockets, plug board, rail mount, panel mount, through-panel mount, enclosure for mounting on walls or equipment Switching time - where high speed is required "Dry" contacts - when switching very low level signals, special contact materials may be needed such as gold-plated contacts

Contact protection - suppress arcing in very inductive circuits Coil protection - suppress the surge voltage produced when switching the coil current Isolation between coil circuit and contacts Aerospace or radiation-resistant testing, special quality assurance Expected mechanical loads due to acceleration - some relays used in aerospace applications are designed to function in shock loads of 50 g or more Accessories such as timers, auxiliary contacts, pilot lamps, test buttons Regulatory approvals Stray magnetic linkage between coils of adjacent relays on a printed circuit board.

[edit] Protective relay


A protective relay is a complex electromechanical apparatus, often with more than one coil, designed to calculate operating conditions on an electrical circuit and trip circuit breakers when a fault was found. Unlike switching type relays with fixed and usually ill-defined operating voltage thresholds and operating times, protective relays had well-established, selectable, time/current (or other operating parameter) curves. Such relays were very elaborate, using arrays of induction disks, shaded-pole magnets, operating and restraint coils, solenoid-type operators, telephone-relay style contacts, and phase-shifting networks to allow the relay to respond to such conditions as over-current, over-voltage, reverse power flow, over- and under- frequency, and even distance relays that would trip for faults up to a certain distance away from a substation but not beyond that point. An important transmission line or generator unit would have had cubicles dedicated to protection, with a score of individual electromechanical devices. The various protective functions available on a given relay are denoted by standard ANSI Device Numbers. For example, a relay including function 51 would be a timed overcurrent protective relay. These protective relays provide various types of electrical protection by detecting abnormal conditions and isolating them from the rest of the electrical system by circuit breaker operation. Such relays may be located at the service entrance or at major load centers. Design and theory of these protective devices is an important part of the education of an electrical engineer who specializes in power systems. Today these devices are nearly entirely replaced (in new designs) with microprocessor-based instruments (numerical relays) that emulate their electromechanical ancestors with great precision and convenience in application. By combining several functions in one case, numerical relays also save capital cost and maintenance cost over electromechanical relays. However, due to their very long life span, tens of thousands of these "silent sentinels" are still protecting transmission lines and electrical apparatus all over the world. See also Protective Device Coordination.

Top, middle: reed switches, bottom: reed relay

[edit] Overcurrent relay


An "Overcurrent Relay" is a type of protective relay which operates when the load current exceeds a preset value. The ANSI Device Designation Number is 50 for an Instantaneous OverCurrent (IOC), 51 for a Time OverCurrent (TOC). In a typical application the overcurrent relay is used for overcurrent protection, connected to a current transformer and calibrated to operate at or above a specific current level. When the relay operates, one or more contacts will operate and energize a trip coil in a Circuit Breaker and trip (open) the Circuit Breaker.

[edit] Induction disc overcurrent relay


These robust and reliable electromagnetic relays use the induction principle discovered by Ferraris in the late 19th century. The magnetic system in induction disc overcurrent relays is designed to detect overcurrents in a power system and operate with a pre determined time delay when certain overcurrent limits have been reached. In order to operate, the magnetic system in the relays produces rotational torque that acts on a metal disc to make contact, according to the following basic current/torque equation: T = K x 1 x 2 Sin Where K is a constant 1 and 2 are the two fluxes is the phase angle between the fluxes The relay's primary winding is supplied from the power systems current transformer via a plug bridge, which is also commonly known as the plug setting multiplier (psm). The variations in the current setting are usually seven equally spaced tappings or operating bands that determine the relays sensitivity. The primary winding is located on the upper electromagnet. The secondary winding has connections on the upper electromagnet that are energised from the primary winding and connected to the lower electromagnet. Once the upper and lower electromagnets are energised they produce eddy currents that are induced onto the metal disc and flow through the flux paths. This relationship of eddy currents and fluxes creates rotational torque proportional to the input current of the primary winding, due to the two flux paths been out of phase by 90.

Therefore in an overcurrent condition a value of current will be reached that overcomes the control spring pressure on the spindle and the breaking magnet causing the metal disc to rotate moving towards the fixed contact. This initial movement of the disc is also held off to a critical positive value of current by small slots that are often cut into the side of the disc. The time taken for rotation to make the contacts is not only dependent on current but also the spindle backstop position, known as the time multiplier (tm). The time multiplier is divided into 10 linear divisions of the full rotation time. Providing the relay is free from dirt, the metal disc and the spindle with its contact will reach the fixed contact, thus sending a signal to trip and isolate the circuit, within its designed time and current specifications. Drop off current of the relay is much lower than its operating value, and once reached the relay will be reset in a reverse motion by the pressure of the control spring governed by the braking magnet.

[edit] Distance relay


The most common form of protection on high voltage transmission systems is distance relay protection. Power lines have set impedance per kilometre and using this value and comparing voltage and current the distance to a fault can be determined. The ANSI standard device number for a distance relay is 21. The main types of distance relay protection schemes are:

Three step distance protection Switched distance protection Accelerated or permissive intertrip protection Blocked distance protection

In three step distance protection, the relays are separated into three separate zones of impedance measurement to accommodate for over reach and under reach conditions. Zone 1 is instantaneous in operation and has a purposely set under reach of 80% of the total line length to avoid operation for the next line. This is due to measurements of impedance of lines not being entirely accurate, errors in voltage and current transformers and relay tolerances. These errors can be up to 20% of the line impedance, hence the zones 80% reach. Zone 2 covers the last 20% of the feeder line length and provides backup to the next line by having a slight over reach. To prevent mal-operation the zone has a 0.5 second time delay. Zone 3 provides backup for the next line and has a time delay of 1 second to grade with zone 2 protection of the next line.

[edit] Motor protection relay


AC motors need overcurrent protection against short circuits from external faults in connecting cables and from internal faults in motor windings. In addition, transformers are thermally rated and limited, and protective relays must be applied to prevent overheating during operating conditions where no fault is present. [3]

[edit] Railway signalling

[edit] General
Railway signalling relays are very big and cumbersome compared to the mostly small voltages and currents that they switch. Contacts are widely spaced to prevent dangerous flashovers and short circuits over a lifetime that may exceed fifty years. The Q-series of plug-in relays are widely used on railways following English practice. These are 120mm high, 180mm deep and 56mm wide and weigh about 1400 g.

[edit] Double switching


In railway signalling, relays energise to give a green light, so that if the power fails or a wire breaks, the signal goes to red. This is called "fail-safe". To protect against false feeds relay circuits are often cut on both the positive and negative side, so that two false feeds are needed to cause a false green.

[edit] Proving
In railway signalling, many relays are proved down before a signal is allowed to show green. For example, before a points normal detector is allowed to pick up (and allow that signal to show green) the corresponding points reverse detector must be proved in the de-energized position. Not all relays can be proved, for example repeat relays in distant locations, so there needs to be is reliance on other features such as carbon to silver contacts to resist lightning induced contact welding and AC immunity.

[edit] See also


Digital protective relay Contactor Dry contact Wire spring relay Race condition

Digital protective relay


From Wikipedia, the free encyclopedia

Jump to: navigation, search A digital protective relay uses a microcontroller with software-based protection algorithms for the detection of electrical faults.

Contents
[hide]

1 Description and definition

2 Basic principles 3 Protective element types 4 See also 5 External links / manufacturers

[edit] Description and definition


The digital protective relay, also called a numeric relay by some manufacturers and resources, refers to a protective relay that uses an advanced microprocessor to analyze power system voltages and currents for the purpose of detection of faults in an electric power system. There are gray areas on what constitutes a digital/numeric relay, but most engineers will recognize the design as having the majority of these attributes:

The relay applies A/D (analog/digital) conversion processes to the incoming voltages and currents. The relay analyzes the A/D converter output to extract, as a minimum, magnitude of the incoming quantity, most commonly using Fourier transform concepts (RMS and some form of averaging are used in basic products). Further, the Fourier transform is commonly used to extract the signal's phase angle relative to some reference, except in the most basic applications. The relay is capable of applying advanced logic. It is capable of analyzing whether the relay should trip or restrain from tripping based on current and/or voltage magnitude (and angle in some applications), complex parameters set by the user, relay contact inputs, and in some applications, the timing and order of event sequences. The logic is user-configurable at a level well beyond simply changing front panel switches or moving of jumpers on a circuit board. The relay has some form of advanced event recording. The event recording would include some means for the user to see the timing of key logic decisions, relay I/O (input/output) changes, and see in an oscillographic fashion at least the fundamental frequency component of the incoming AC waveform. The relay has an extensive collection of settings, beyond what can be entered via front panel knobs and dials, and these settings are transferred to the relay via an interface with a PC (personal computer), and this same PC interface is used to collect event reports from the relay. The more modern versions of the digital relay will contain advanced metering and communication protocol ports, allowing the relay to become a focal point in a SCADA system.

As a point of comparison, an electromechanical relay converts the voltages and currents to magnetic and electric forces and torques that press against spring tensions in the relay. The tension of the spring and taps on the electromagnetic coils in the relay are the main processes by which a user sets such a relay. In a solid state relay, the incoming voltage and current waveforms are monitored by analog circuits, not recorded or digitized. The analog values are compared to settings made by the user via potentiometers in the relay, and in some case, taps on transformers.

In some solid state relays, a simple microprocessor does some of the relay logic, but the logic is fixed and simple. For instance, in some time overcurrent solid state relays, the incoming AC current is first converted into a small signal AC value, then the AC is fed into a rectifier and filter that converts the AC to a DC value proportionate to the AC waveform. An op-amp and comparator is used to create a DC that rises when a trip point is reached. Then a relatively simple microprocessor does a slow speed A/D conversion of the DC signal, integrates the results to create the time-overcurrent curve response, and trips when the integration rises above a setpoint. Though this relay has a microprocessor, it lacks the attributes of a digital/numeric relay, and hence the term "microprocessor relay" is not a clear term. The digital/numeric relay was introduced in the early 1980s, with AREVA and ABB's forerunners and SEL making some of the early market advances in the arena, but the arena has become crowded today with many manufacturers. In transmission line and generator protection, by the mid 1990's the digital relay had nearly replaced the solid state and electromechanical relay in new construction. In distribution applications, the replacement by the digital relay proceeded a bit more slowly. While the great majority of feeder relays in new applications today are digital, the solid state relay still sees some use where simplicity of the application allows for simpler relays, and which allows one to avoid the complexity of digital relays.

[edit] Basic principles


Low voltage and low current signals (i.e., at the secondary of a VT and CT) are brought into a low pass filter that removes frequency content above about 1/3 of the sampling frequency (a relay A/D converter needs to sample faster than 2x per cycle of the highest frequency that it is to monitor). The AC signal is then sampled by the relay's analog to digital converter at anywhere from about 4 to 64 (varies by relay) samples per power system cycle. In some relays, the entire sampled data is kept for oscillographic records, but in the relay, only the fundamental component is needed for most protection algorithms, unless a high speed algorithm is used that uses subcycle data to monitor for fast changing issues. The sampled data is then passed through a low pass filter that numerically removes the frequency content that is above the fundamental frequency of interest (i.e., nominal system frequency), and uses Fourier transform algorithms to extract the fundamental frequency magnitude and angle. Next the microprocessor passes the data into a set of protection algorithms, which are a set of logic equations in part designed by the protection engineer, and in part designed by the relay manufacturer, that monitor for abnormal conditions that indicate a fault. If a fault condition is detected, output contacts operate to trip the associated circuit breaker(s).

[edit] Protective element types


Protective Elements refer to the overall logic surrounding the electrical condition that is being monitored. For instance, a differential element refers to the logic required to monitor two (or more) currents, find their difference, and trip if the difference is beyond certain parameters. The term element and function are quite interchangeable in many instances.

For simplicity on one-lines, the element/function is usually identified by what is referred to as an ANSI device number, and hence there are three terms (element, function, device number) in use for approximately the same concept. In the era of electromechanical and solid state relays, any one relay could implement only one or two protective elements/functions, so a complete protection system may have many relays on its panel. In a digital/numeric relay, many functions/elements are implemented by the microprocessor programming. Any one digital/numeric relay may implement one or all of these device numbers/functions/elements. A listing of device numbers is found at the site ANSI Device Numbers. A summary of some common device numbers seen in digital relays is:

21 - Impedance (21G implies ground impedance) 27 - Under Voltage (27LL = line to line, 27LN = line to neutral/ground) 32 - Directional Power Element 46 - Negative sequence current 47 - Negative sequence voltage 50 - Instantaneous OverCurrent (subscript N or G implies Ground) 51 - Inverse Time Overcurrent (subscript N or G implies Ground) 59 - Over Voltage (59LL = line to line, 59LN = line to neutral/ground) 67 - Directional Over Current (typically controls a 50/51 element) 79 - Auto-reclosure 81 - Under/Over Frequency 87 - Current Differential (87L=transmission line diff; 87T=transformer diff; 87G=generator diff)