RESPONSE SHEET

CLIENT PROJEC T CLIENT S REF. PETROVIETNAM GAS SOUTH EAST GAS MANAGEMENT BOARD NAM CON SON 2 GAS PIPELINE PROJECT Job No Comment Sheet No. Received date PVGAS-SEG'S COMMENT No GENERAL COMMENTS - PVE to add the standard information as: Part of standard, year of edition into Item/Section of all documents below in Detail Comments section, except the Specification for electrical cable document. + For short circuit calculation - PVE to add Equivalent circuit diagram 132 CM-PVE 04, November, 2011 Rev . Statu s Response date Response sheet No. NCS2-PVE-FD (034040) 08 November 2011 PVE'S ANSWER NCS2-E -PVE-PVGAS-SEGPrepar e T.V.D Check V.V.H Remark Approve

- PVE will add the standard information as per agreement between PVE and PVGAS SEG in the meeting dated 01/11/2011. The overall single line diagram in section 4.1 can be used as equivalent circuit diagram. It gives all the necessary information of the circuit and the position of fault in order to calculate the short circuit current. - The selection of Ssc = 500 MVA is based on Quy nh u ni vo h thng in quc gia 37/2006/Q-BCN dated 16/10/2006. - The selection of Xcb = 0.00015; Rcb = 0 is based on IEC 60909-0 and the Electrical installation handbook. The selection of Ukr = 2.2 or 2.3 is based on c tnh k thut v vt t thit b in Tp 1 : My bin p phn phi, dy dn v cp in 1094/EVN-DDL dated 10/05/2005 and IEC 60076-5. The selection of Total loss of transformer P = 50 is based on c tnh k thut v vt t thit b in Tp 1 : My bin p phn phi, dy dn v cp in 1094/EVN-DDL dated 10/05/2005. Itr = S/U=15000/230: Transformer current.

- PVE to clarify the selection for Ssc = 500 MVA and Xcb = 0.00015; Rcb = 0

- PVE to clarify the selection for Ukr = 2.2 or 2.3.

- PVE to clarify the selection for Total loss of transformer P = 50, Itr = 15000.

- PVE to clarify the selection for parameters : R and X of LV cable. - PVE to clarify the selection for Cos = 0.8

The resistance and reactance parameters of LV cable are selected based on IEC 228 Amendment 1 1993. The selection for Cos = 0.8 is based on IEC 60034-2 The selection for Xd is based on the electrical installation handbook. Furthermore, this parameter can be decided by reviewing the actual value of a variety range of generator. The selected parameter is one kind of typical value for synchronous generator used for calculating purposes. 2 O Please see in General comments answers. 3 O Please see in General comments answers. 2 O Please see in General comments answers. 3 O Please see in General comments answers. 2 O Please see in General comments answers.

- PVE to clarify the selection for Xd = 0.2

SHORT CIRCUIT CALCULATION AT LONG HAI LFS NCS2-PVE-FD-1-00-05-CA-005 Please see in General comments section ELECTRICAL LOAD CALCULATION AT LONG HAI LFS NCS2-PVE-FD-1-00-05-CA-006 Please see in General comments section SHORT CIRCUIT CALCULATION AT GAS LBV NCS2-PVE-FD-2-01-05-CA-005 Please see in General comments section ELECTRICAL LOAD CALCULATION AT GAS LBV NCS2-PVE-FD-2-01-05-CA-006 Please see in General comments section SHORT CIRCUIT CALCULATION AT 1 LBV NCS2-PVE-FD-2-02-05-CA-005 Please see in General comments section ELECTRICAL LOAD CALCULATION AT 1 LBV NCS2-PVE-FD-2-02-05-CA-006 Please see in General comments section SHORT CIRCUIT CALCULATION AT 2 NCS2-PVE-FD-2-02-05-CA-011
nd st st

O Please see in General comments answers.

LBV

O Please see in General comments answers.

Please see in General comments section 8 ELECTRICAL LOAD CALCULATION AT 2 LBV NCS2-PVE-FD-2-02-05-CA-012 Please see in General comments section
nd

O Please see in General comments answers.

*) **)

O = Open; C = Closed; CI = Closed if implemented in relevant document / site work. NC =Non Conformance (Response required); N=Note (Response required); A=Advice (No Response required).