RTU211 data sheet

7HFKQLFDO LQIRUPDWLRQ DERXW WKH UHPRWH WHUPLQDO XQLW 578

&RPPXQLFDWLRQV
Standard protocols IEC870-5-101 DNP3.0 (level2) Modbus (RTU & ASCII) RP570, ADLP180 4 RS232 serial ports for connection to central station, local display and control unit, local printer Modbus (RTU & ASCII) Fixed line V23 modem, max 1200 baud Hayes compatible dial-up modems: PSTN, ISDN and GSM (mobile phone) Fibre-optic connection; plastic, HCS or glass RS232 port for connection to other media types e.g. radio, PLC, satellite Redundant line with RP570 & IEC870-5-101 (unbalanced) Dual-master (also multiple protocol) with IEC870-5-101, Modbus & DNP3.0

Proprietary protocols Ports IED protocols Media

Additional features

([SDQGDELOLW\
The RTU211 begins with a base module and can be expanded to several hundred I/O points. Dedicated CPUs on each I/O board ensure that expansion does not affect performance. Remote I/O modules can be connected to a base module up to circa 2km away.

(QYLURQPHQWDO FRQGLWLRQV
Temperature Humidity Vibration -40 to +70 oC 5 to 95% non-condensing IEC870-2 Class VL3

(0& 3HUIRUPDQFH
According to EN 50081-2 Generic mission Standard and EN 50082-2 Generic Immunity Standard (Industrial Environment)

3RZHU VXSSOLHV
Input voltage 24Vdc 24 110Vdc 110Vac, 230 Vac +15/-20% Wide input: 19.2 to 126.5 Vdc +10/-15%, battery back-up option

$%% $XWRPDWLRQ

abb

,QSXW2XWSXW ERDUGV
23IO96 Combined I/O board which forms part of base unit. 16 digital inputs, 6 analogue inputs and 8 digital outputs (with 1 of n control) 16 binary inputs (dual pole) Available for 24-48Vdc, 60-110Vdc or 220Vdc 16 binary inputs (single pole) Available for 24-48Vdc or 60-110Vdc 8 binary outputs 1, 11/2 or 2 pole connections. Potential free make contacts Max ratings: 100Vdc 0.4A or 220Vac 0.5A 8 binary outputs 1, 11/2 or 2 pole connections. Solid state relays. Max rating: 50Vdc 0.2A 8 interposing relays for direct connection to 23BO61/23IO96 Two potential free change over contacts Max ratings: 110Vdc 2x0.4A, 220Vac 10A or 110Vdc 3A 6 analogue inputs Resolution: 11 bit plus sign. Accuracy: 0.25% Current ranges: 0-2.5/5/10/20, 4-20, +/-2.5/5/10/20mA Voltage ranges: 0-1/10, +/-1/10V 2 analogue outputs Resolution: 11 bit plus sign. Accuracy: 0.25% Current ranges: 4-10, +/-2.5/5/10/20mA Voltage ranges: 0-1.25/2.5/5/10V 3x line voltage (RMS), 3x phase voltage (RMS) 3x phase current (0-5 A RMS), unbalanced current (5 A RMS), zero sequence voltage (RMS) Calculated values: active power (W), reactive power (Var), apparent power (VA), power factor, frequency (Hz), accumulated power consumed (active & reactive), accumulated power delivered (active & reactive) 6 analogue inputs for PT100 elements Resolution: 11 bit plus sign Range: -200 to +200 oC

23BI60 23BI61 23BO60

23BO61 23RL60

23AI60

23AO60

23DP61

23PT60

2SWLRQV
Local display and control unit, LDCU Local Automation Functions, LAF Alphanumeric, 4 lines x 40 characters Logic programs running in RTU

abb
677Dqv6T

P.O. Box 6540 Rodelkka N-0510 OSLO Tel: +47 22 87 20 00 Fax: +47 22 87 36 00 www.abb.com/control