16/12/2007
ED /R01/012 Issue 1
Document ED/R01/012
Approved by NC
ED/R01/012
16 December 2007
Approved by NC
Contents
1. General ........................................................................................................... 3
1.1 1.2 1.3 Citation and commencement............................................................................ 3 Scope, enforcement and disputes ................................................................... 3 Relevant documents.......................................................................................... 4
2.
Definitions...................................................................................................... 5
2.1 Interpretation...................................................................................................... 5
3.
4.
Approved by NC
1.
1.1
1.1.1
General
Citation and commencement
These Regulations shall be cited as the Electricity Supply Regulations 2007. These Regulations shall come into force on 1 January 2008. These Regulations are issued by the Regulation & Supervision Bureau through the powers vested in it under Article 62 of Law No (2) of 1998 (including amendments and re-enactments thereof).
1.1.2 1.1.3
1.2
1.2.1
1.2.2
1.2.3
1.2.4
The Electricity Supply Regulations 2007 Author TK Document ED/R01/012 Version 1(0) Page 3 of 13 Publication date 16 December 2007 Approved by NC
1.3
1.3.1
Relevant documents
The Electricity Wiring Regulations 2007: this document covers detailed requirements and guidelines for Electrical Installations within Premises, issued by the Bureau. The Electricity Distribution Code: covers requirements for the development, operation and maintenance of distribution networks owned and operated by Licensed Distribution Companies. Electricity Distribution Licences: define the responsibilities and scope of operation of Distribution Companies, including their obligations to Customers, issued by the Bureau. The Incident Reporting Regulations 2001: specify the obligations on Distribution Companies for the reporting of major incidents in the public supply system, issued by the Bureau. The Customer Metering Regulations 2005: specify the operating codes and requirements for meters connected to Customers receiving electricity supply from any Distribution Company, issued by the Bureau. Distribution Company Standards: give details of requirements, standards and operating procedures for activities of the Licensed Distribution Companies, including plant and equipment specifications. These are issued by the Distribution Companies and, where appropriate, are approved by the Bureau. International Standards: where appropriate these may be referenced or adopted by Licensed Distribution Companies or by the Bureau. These may include, but are not limited to, British Standards (BS), IEC Standards (International Electrotechnical Commission) or ISO Standards (International Standardisation Organisation). UAE Standards: issued by the Emirates Standardisation and Metrology Authority (ESMA). These standards may be referenced where appropriate. Distribution Company Safety Rules: these define safe procedures for work on Distribution Companies systems, including at the interface with Customers Installations.
1.3.2
1.3.3
1.3.4
1.3.5
1.3.6
1.3.7
1.3.8
1.3.9
The Electricity Supply Regulations 2007 Author TK Document ED/R01/012 Version 1(0) Page 4 of 13 Publication date 16 December 2007 Approved by NC
2.
2.1
Definitions
Interpretation
Words which are defined under this section are used in the Regulations beginning with capital letters e.g. all Electrical Installations within a Premises shall be .... Words and expressions other than those described in this section, which are defined in the Law shall have the meanings ascribed to them in the Law. Words using the singular or plural number also include the plural or singular number, respectively. 2.1.1 2.1.2 Appliance: an item of current using equipment Bureau: means the Regulation & Supervision Bureau for the Water, Wastewater and Electricity Sector in the Emirate of Abu Dhabi, as established under the Law. Customer: means any person, corporate body, or company who has an agreement with a Distribution Company for the supply of electricity. Customer Connection Point (CCP): the point which defines the boundary between the Customers Installation and that of the Distribution Company. This point will normally be at the incoming cable of the main distribution board and before the main circuit breaker. In special cases an alternative definition of the Connection Point may be agreed between the Customer and the Distribution Company. Danger: risk of injury to people or animals from fire, electric shock, burns, explosion or from mechanical movement of electrically controlled equipment, or the risk of damage to property. Distribution Company: a person authorised pursuant to the Law to carry on distribution of water or electricity.. Earth: the conductive mass of earth, whose electrical potential (voltage) at any point is conventionally taken as zero.
2.1.3
2.1.4
2.1.5
2.1.6
2.1.7
The Electricity Supply Regulations 2007 Author TK Document ED/R01/012 Version 1(0) Page 5 of 13 Publication date 16 December 2007 Approved by NC
2.1.8
Earthing or Earthed: a general term used to describe the connection of metallic parts of Electrical Apparatus or Appliances to Earth. Earth Electrode: a conductor or group of conductors in intimate contact with Earth, providing an electrical connection to Earth, and normally having a known and measurable value of Earth Resistance (may also be known outside these Regulations as earth rod, or grounding rod.) Earth Resistance: the resistance (in Ohms) from any point on an Installation to Earth, being measured using an approved testing device and approved procedure. Electrical Apparatus: a general term used in these Regulations which means any cable, line, circuit or sub-circuit, switchgear, transformer, etc within a distribution network or any part of an Electrical Installation within a Premises. Electrical Installation (abbrv: Installation): an Electrical Installation generally comprises any fixed or temporary cable, switchgear, transformer or other electrical equipment or apparatus within a Premises or other place where there is an electricity supply (including outdoor locations). Appliances are not considered to be part of the Electrical Installation. HV (high voltage): an a.c. voltage greater than Low Voltage and less than 36 kV between phases or 21 kV between any phase and Earth (internationally referred to as Medium Voltage). Law: means Law No (2) of 1998 Concerning the Regulation of the Water, Wastewater and Electricity Sector (as amended by Law No (19) of 2007). Licence: means a licence issued by the Bureau authorising the distribution, generation, supply or transmission of electricity as described in the Law (part 6). Licensed Contractor: a company which has been assessed by the Distribution Company as competent to work on Electrical Installations and issued a Competency Licence.
2.1.9
2.1.10
2.1.11
2.1.12
2.1.13
2.1.14
2.1.15
2.1.16
The Electricity Supply Regulations 2007 Author TK Document ED/R01/012 Version 1(0) Page 6 of 13 Publication date 16 December 2007 Approved by NC
2.1.17
LV (low voltage): an a.c. voltage below 1000 V between phases, or below 600 V between any phase and Earth, or a d.c. voltage below 1500 V between conductors, or below 900 V between any conductor and earth. Main Earth Terminal (MET): the main connection point at which the nominal value of Earth Resistance for an installation is taken, and to which Earth Electrodes or the Distribution Company Earth are connected. This will normally be at or close to the Customer Connection Point. The Main Earth Terminal may also be known as the main earth bar. Owner: the legal owner of a building or property in which an Electrical Installation is installed and connected to a supply of electricity. In some cases an Owner may also be a Customer. Premises: any occupied or unoccupied building or enclosure or other place where there is an electricity supply. Such locations would include, but are not limited to, domestic premises, commercial premises, industrial premises, public buildings, parks, farms, temporary supplies, construction sites, wedding tents, outbuildings, caravans, street lighting and traffic signs. Prospective Fault Current: the value of current that would flow due to a short-circuit fault of negligible impedance between live phase conductors, or between phase conductors and Earth, also known as fault level. The maximum Prospective Fault Current for an installation is normally taken at the Customer Connection Point. Supply Intake: a term used to describe the location or room housing the main cable and equipment provided by a Distribution Company to provision a supply of electricity to a Premises (includes the Customer Connection Point).
2.1.18
2.1.19
2.1.20
2.1.21
2.1.22
The Electricity Supply Regulations 2007 Author TK Document ED/R01/012 Version 1(0) Page 7 of 13 Publication date 16 December 2007 Approved by NC
3.
3.1
3.1.1
3.1.2
3.1.3
3.1.4
3.1.5
3.2
3.2.1
3.2.2
3.2.3
The Electricity Supply Regulations 2007 Author TK Document ED/R01/012 Version 1(0) Page 8 of 13 Publication date 16 December 2007 Approved by NC
3.3
3.3.1
3.3.2
3.4
3.4.1
Earthing system
Customers shall be provided with a supply operating under either of the following earthing systems:
(a)
Customer Earthed System (TT): the Customer provides a Main Earth Terminal for the Installation, which is connected to a sufficient number of local Earth Electrodes to provide a maximum Earth Resistance measured at the Customers Main Earth Terminal of no greater than 10 Ohms (referred to as a TT system); Distribution Company Earthed System (TN-S): the Distribution Company provides a connection to the Customers Main Earth Terminal, using the distribution network Earthing system, via the armouring or metallic sheath of the incoming supply cable (referred to as a TN-S system). The Distribution Company system is earthed at the distribution transformer (11 kV / 400 V) and separate earth and neutral conductors are used throughout the distribution network; or, Distribution Company Earthed System with additional Customer Earth (TN-S-TT): the Distribution Company provides an earth connection to the Customers Main Earth Terminal and a local Earth provided by the Customer is also connected to the same MET, having an Earth Resistance value of no greater than 10 Ohms.
(b)
(c)
The Electricity Supply Regulations 2007 Author TK Document ED/R01/012 Version 1(0) Page 9 of 13 Publication date 16 December 2007 Approved by NC
3.4.2
These types of earthing systems and their associated requirements are explained in the Electricity Wiring Regulations 2007. The preferred type of earthing system to be used in Abu Dhabi Emirate is TN-S-TT. However, either TN-S or TT systems may be used where agreed between the Distribution Company and the Customer. The type of earthing system must be clearly labelled at the Supply Intake.
3.4.3
3.5
3.5.1
Interruptions of supply
Distribution Companies are required to report to the Bureau interruptions of supply to customers, as well as other system incidents, in accordance with procedures defined by the Bureau. The Distribution Company shall operate its network so as to minimise interruptions of supply to Customers. Specific standards of performance for Distribution Companies shall be set by the Bureau, including the average frequency and duration of interruptions and the maximum times for restoration of supply. The Distribution Company shall have a right to interrupt the supply to Customers, without prior notice, in the event of an emergency (for example, in the case of fire, or other risk to life). Where the Distribution Company has a reasonable need for a preplanned interruption of supply to one or more Customers (e.g. for essential network maintenance) it shall give notice of at least two working days to the affected Customers. Such interruptions shall be arranged to take place at a reasonable time of day.
3.5.2
3.5.3
3.5.4
The Electricity Supply Regulations 2007 Author TK Document ED/R01/012 Version 1(0) Page 10 of 13 Publication date 16 December 2007 Approved by NC
4.
4.1
4.1.1
4.1.2
4.1.3
4.1.4
4.1.5
4.1.6
4.1.7
The Electricity Supply Regulations 2007 Author TK Document ED/R01/012 Version 1(0) Page 11 of 13 Publication date 16 December 2007 Approved by NC
may be exempt from this requirements (see the Electricity Wiring Regulations 2007 section 3.6).
4.2
4.2.1
4.2.2
4.2.3
4.2.4
4.2.5
4.2.6
4.2.7
4.2.8
The Electricity Supply Regulations 2007 Author TK Document ED/R01/012 Version 1(0) Page 12 of 13 Publication date 16 December 2007 Approved by NC
4.3
4.3.1
Customers Installations
The Distribution Company shall install suitable connection equipment in order to provide supply to any new Customer or Owner upon reasonable request, and make a reasonable charge. The basis of such charges shall be approved by the Bureau. The Customers Installation must meet the requirements of the Electricity Wiring Regulations 2007 before a supply is provided by the Distribution Company. The Customer Connection equipment shall be clearly marked and metering equipment shall be security sealed. Any work or testing on the Customers Installation may only be carried out by a Licensed Contractor or the Distribution Company. Detailed requirements for the design, construction and testing of Customers Installations are given in the Electricity Wiring Regulations 2007.
4.3.2
4.3.3
4.3.4
4.3.5
The Electricity Supply Regulations 2007 Author TK Document ED/R01/012 Version 1(0) Page 13 of 13 Publication date 16 December 2007 Approved by NC